Pressure Sensors/ Pressure Sensor Controllers

Pressure Sensors/ Pressure Sensor Controllers
Remote Type
New
Pressure Sensors/
Pressure Sensor Controllers
Compact Pneumatic
Pressure Sensor
PSE530
sP.
Low Differential
Pressure Sensor
Pressure Sensor
for General Fluids
PSE560
sP.
Compact Pneumatic
Pressure Sensor
3
PSE550
12
sP.
PSE540
sP.
6
9
Pressure Sensor
for General Fluids
PSE570
sP.
15
New
Multi-Channel Digital
Pressure Sensor Controller
PSE200
sP.
18
2-Color Display Digital
Pressure Sensor Controller
PSE300
sP.
24
Connector type
Series PSE
DIN rail/Terminal block type
CAT.ES100-56C
Remote Type Pressure
Series
Sensors/Pressure Sensor Controllers
PSE
Series
PSE Variations
Pressure Sensors
PSE530
PSE540
PSE550
PSE560
P.3
P.6
P.9
P.12
Controllers
New
PSE570
PSE200
PSE300
P.18
P.24
Model
Basic Specifications
Fluid
Air
P.15
General fluids
Rated pressure range
(Minimum display)
Repeatability
±1
% (F.S.)
±0.2
% (F.S.)
±0.3
% (F.S.)
Voltage
±0.2
% (F.S.)
±0.1
% (F.S.)
12 to 24 VDC
No. of outputs for switch
5 outputs
Analog output
1 to 5 V
4 to 20 mA
1 to 5 V
Operating temp.
0 to 50°C
1 to 5 V
4 to 20 mA
−10 to 60°C
0 to 50°C
Wiring
IP40
Connector
IP65
Grommet
2-color
Front face IP65
Others IP40
IP40
Connector
Keylock, Peak/Bottom
values holding, Auto-preset,
Auto-shift, Display calibration,
Anti-chattering
Connection
threads
M
reducer
Int’l standards
CE
Wiring
1-color
Connector
Major setting
function
M
R, NPT
reducer
Resin piping
CE, UL, CSA
R, NPT, Rc
URJ, TSJ*
R
CE
CE
CE, UL, CSA
e-con
Flexible
cable
Direct
Mounting
Others
Functions
Digital display
Enclosure
2 outputs
With
bracket
Panel
mount
DIN rail
* URJ (VCR® fitting compliant), TSJ (Swagelok® fitting compliant)
1
Remote Type Pressure
Sensors/Pressure Sensor Controllers
Series
PSE
Pressure Sensors/Series PSE5 
PSE53m PSE54m PSE55m PSE56m
New
PSE57m
Rated pressure range
−100 kPa 0 100 kPa
•
•
•
Vacuum −101
kPa
Compound
pressure
1 MPa
•
PSE531
PSE541
—
PSE561
—
100 kPa
PSE533
PSE543
—
PSE563
PSE573
100 kPa
PSE532
—
—
—
—
—
—
—
PSE564
PSE574
PSE530
PSE540
—
PSE560
PSE570
—
—
PSE550
—
—
0
−100
kPa
0
Positive
pressure
500 kPa
•
0
500 kPa
0
Low differential
pressure
1 MPa
0 2 kPa
Pressure Sensor Controllers/Series PSE200/300
PSE200
PSE300
• NPN 2 outputs + 1–5 V outputs
• NPN 2 outputs + 4–20 mA output
• NPN 2 outputs +
auto-shift input
• PNP 2 outputs + 1–5 V outputs
• PNP 2 outputs + 4–20 mA output
• PNP 2 outputs +
auto-shift input
Input/Output
specifications
• NPN 5 outputs +
auto-shift input
• PNP 5 outputs +
auto-shift input
Applicable pressure sensor model
Set/Display resolution
PSE531 PSE541
—
PSE561
PSE533 PSE543
—
PSE563 PSE573
PSE532
—
—
—
—
—
—
PSE530 PSE540
—
—
PSE550
Input/Output
specifications
0.1 kPa
0.1 kPa
0.1 kPa
0.2 kPa
0.1 kPa
0.1 kPa
PSE564 PSE574
—
1 kPa
PSE560 PSE570
0.001 MPa
0.001 MPa
—
0.01 kPa
—
—
—
—
—
Main Functions (For details, refer to pages 31 to 33.)
Locks the keys from functioning.
Keylock
Peak/Bottom values holding Displays the maximum and minimum values being set and can keep those values on the display.
Auto-preset
Auto-shift
Display calibration
Anti-chattering
Able to set the pressure automatically. In the case of suction verification, it memorizes the pressure when
adsorbed and released. By repeating several times, the optimum values are calculated automatically.
Stable switch output is available even though the supply pressure may fluctuate. Automatically corrects the set value in accordance with the fluctuations in the supply pressure.
Able to adjust the displayed value (±5%) and justify distribution of the values displayed on respective pressure switch.
Prevents malfunction due to sharp pressure fluctuations. The detection of momentary pressure
fluctuation as abnormal pressure can be prevented by changing the setting of the response time.
2
Compact Pneumatic
Pressure Sensor
Series
PSE530
RoHS
Series
Rated pressure range
−100 kPa
PSE530
PSE531
100 kPa
500 kPa
0
–101 kPa
PSE532
PSE533
0
Connector type
1 MPa
0
0
–101 kPa
1 MPa
101 kPa
101 kPa
Application example
Leak test of radiator
Series PSE532
Locked
+ PSE300
Sensor body
Connector cover
Unlocked
Low pressure sensor (PSE532-) is used to detect minute differentiations.
Auto-shift function reduces influence of fluctuations in the supply pressure.
3
Pressure Sensor
Series PSE530
PSE530
RoHS
How to Order
Sensor range
Option
Positive pressure [0 to 1 MPa]
Vacuum [0 to –101 kPa]
Low pressure [0 to 101 kPa]
Compound pressure [–101 to 101 kPa]
Nil
Port size
M5 M5 x 0.8
R06 ø6 reducer
R07 1/4 inch reducer
None
Sensor cable (3 m)
L
Connector for pressure sensor controller (1 pc.) +
Sensor cable (3 m)
When only optional parts are required, order using the part numbers listed below.
Description
Part no.
Note
Connector for pressure sensor controller
ZS-28-C
1 pc. per set
Sensor cable
ZS-26-F
Cable length: 3 m
Connector for pressure sensor controller
+ Sensor cable
ZS-26-J
The connector is not attached
to the cable at the time of
shipment.
Proof pressure
PSE530 (Positive pressure)
PSE531 (Vacuum)
PSE532 (Low pressure)
PSE533 (Compound pressure)
0 to 1 MPa
0 to –101 kPa
0 to 101 kPa
–101 to 101 kPa
–0.1 to 0 MPa
10.1 to 0 kPa
–10.1 to 0 kPa
—
1.5 MPa
500 kPa
Applicable fluid
Power supply voltage
Air/Non-corrosive gas/Non-flammable gas
12 to 24 VDC ±10%, Ripple (p-p) 10% or less (with reverse connection protection)
Current consumption
15 mA or less (with no load)
Output specifications
Analog output 1 to 5 V (within rated pressure range), 0.6 to 1 V (within extension analog output range), Output impedance: Approx. 1 kW
Accuracy (Ambient temperature at 25°C)
±2% F.S. (within rated pressure range), ±5% F.S. (within extension analog output range)
±1% F.S.
Linearity
Enclosure
±1% F.S. based on the analog output at 18 V ranging from 12 to 24 VDC
IP40
Temperature range
Operating: 0 to 50°C; Stored: –10 to 70°C (No freezing or condensation)
Environment
Power supply voltage effect
Withstand voltage
Insulation resistance
1000 VAC (in 50/60 Hz) for 1 minute between terminals and housing
5 MW or more (500 VDC measured via megohmmeter) between terminals and housing
±2% F.S. (25°C reference)
Temperature characteristics
Sensor cable/Option
Controller
±1% F.S.
Repeatability
Halogen-free heavy-duty cable, 3 cores, ø2.7, 3 m, Conductor area: 0.15 mm2, Insulator O.D.: 0.8 mm
Standards
CE, RoHS
Piping Specifications
Model
Port size
Materials of parts in contact
with fluid
Weight
PSE560
For Pressure Switch Precautions and Specific Product Precautions, refer to “Handling
Precautions for SMC Products” and the Operation Manual on SMC website.
PSE570
Extension analog output range
Note) The connector is not attached to the cable, but is
included with the shipment.
M5
R06
R07
M5 x 0.8 male thread
ø6 reducer type
1/4 inch reducer type
Pressure sensor: Silicon, O-ring: NBR
Body: Stainless steel 304
Body: PBT
With sensor cable (3 m)
41 g
38 g
Without sensor cable
7g
3.8 g
4
PSE200
Model
C2L
Cable length: 3 m
Specifications
Rated pressure range
PSE550
Option/Part No.
PSE300
0
1
2
3
PSE540
PSE53 0 M5
Series
PSE530
Internal Circuit and Wiring Example
Analog Output
PSE53
1 to 5 VDC
Black OUT
(Analog output)
Blue DC (−)
+
−
12
to
24 VDC
5
Analog output [V]
1 kΩ
Load
Voltage output type
1 to 5 V
Output impedance
Approx. 1 kΩ
Main circuit
Brown DC (+)
1
0.6
CA
B
Range
For vacuum
Pressure
Rated pressure range
0 to −101 kPa
101 kPa
—
0
101 kPa
−10.1 kPa
For positive pressure
0 to 1 MPa
0
1 MPa
−0.1 MPa
5.4
ø2.
ø12
ø7.2
Pressure port
5
M5 x 0.8
3
12
4
5
5.5
PSE53- R06
R07
45.5
43.3
With sensor cable
ø10.4
ø2.7
9.8
5
Pressure port
øD
ø12
ø7.2
5.4
[mm]
Applicable fitting size (D)
6
PSE53-R06
1/4"
PSE53-R07
10.1 kPa
0 to 101 kPa
29.4
27.2
Model
C
−101 kPa
For low pressure
PSE53-M5
3.4
B
0
For compound pressure −101 kPa to 101 kPa −101 kPa
Dimensions
3.4
A
3
ø1
Compact Pneumatic
Pressure Sensor
Series PSE540
RoHS
Series
Rated pressure range
–100 kPa
0
PSE540
100 kPa
500 kPa
0
–101 kPa
PSE543
–100 kPa
1 MPa
0
100 kPa
PSE550
PSE541
1 MPa
PSE540
PSE530
®
· Weight: 2.9 g
· Head size: 9.6 x 20.8 x 18 mm
18
PSE560
20.8
9.6
For PSE54m-M3
6
PSE200
PSE300
Manifolding is possible.
Controller
Pads can be directly mounted.
PSE570
Application examples
Compact Pneumatic
Pressure Sensor
®
Series PSE540
RoHS
How to Order
Accuracy
Sensor range
0
1
3
±2% F.S.
±1% F.S.
Nil
A
Positive pressure [0 to 1 MPa]
Negative pressure [0 to –101 kPa]
Compound pressure [–100 to 100 kPa]
PSE54 1
Option (Connector)
Nil
M3
None
Connector for pressure
sensor controller (1 pc.)
C2
Port size
M3
M3 x 0.5
M5
M5 x 0.8
01
R1/8 (with M5 female thread)
N01
NPT1/8 (with M5 female thread)
R04
ø4 reducer
R06
ø6 reducer
IM5
IM5H
M5 female thread,
through type
Note) The connector is not attached to the cable, but is
included with the shipment.
M5 female thread,
through type
(with mounting hole)
Option/Part No.
Description
Part no.
Note
Connector for pressure sensor controller
ZS-28-C
1 pc.
For Pressure Switch Precautions and Specific Product Precautions, refer to “Handling
Precautions for SMC Products” and the Operation Manual on SMC website.
Specifications
Model
Rated pressure range
Extension analog output range
Proof pressure
PSE540
PSE541
PSE543
0 to 1 MPa
0 to –101 kPa
–100 to 100 kPa
–0.1 to 0 MPa
10.1 to 0 kPa
—
1.5 MPa
500 kPa
Applicable fluid
Air/Non-corrosive gas/Non-flammable gas
12 to 24 VDC ±10%, Ripple (p-p) 10% or less (with reverse connection protection)
Power supply voltage
Current consumption
15 mA or less
Output specifications
Analog output 1 to 5 V (within rated pressure range), 0.6 to 1 V (within extension analog output range), Output impedance: Approx. 1 kW
PSE54l: ±2% F.S. (within rated pressure range), ±5% F.S. (within extension analog output range)
PSE54lA: ±1% F.S. (within rated pressure range), ±3% F.S. (within extension analog output range)
Accuracy (Ambient temperature
at 25°C)
±0.7% F.S. or less
Linearity
±0.4% F.S.
±0.2% F.S.
Power supply voltage effect
±0.8% F.S.
IP40
Environment
Repeatability
Enclosure
Operating temperature range
Operating: 0 to 50°C, Stored: –20 to 70°C (No freezing or condensation)
Operating humidity range
Operating/Stored: 35 to 85% RH (No condensation)
Withstand voltage
1000 VAC (in 50/60 Hz) for 1 minute between terminals and housing
Insulation resistance
Temperature characteristics
Sensor cable
50 MW or more (500 VDC measured via megohmmeter) between terminals and housing
±2% F.S. (25°C reference)
Oilproof heavy-duty vinyl cable (ellipse), 3 cores, 2.7 x 3.2, 3 m, Conductor area: 0.15 mm2, Insulator O.D.: 0.9 mm
Standards
CE, UL/CSA (E216656), RoHS
Piping Specifications
Model
Port size
Material
M3
M3 x 0.5
Case
M5
M5 x 0.8
Resin case: PBT
Fitting: Stainless steel 303
Pressure sensing section
Weight
7
With sensor cable
Without sensor cable
01
N01
R1/8
NPT1/8
M5 x 0.8
M5 x 0.8
R04
ø4 reducer
Resin case: PBT
Fitting: C3604BD
R06
IM5
IM5H
ø6 reducer
M5 female
thread,
through type
M5 female
thread,
through type
(with mounting hole)
Resin case: PBT
Fitting: A6063S-T5
PBT
Pressure sensor: Silicon, O-ring: NBR
42.4 g
2.9 g
42.7 g
3.2 g
49.3 g
9.8 g
41.4 g
1.9 g
41.6 g
2.1 g
43.3 g
3.8 g
44.1 g
4.6 g
Compact Pneumatic Pressure Sensor
Internal Circuit and Wiring Example
Analog Output
PSE54m
1 to 5 VDC
12
to
24 VDC
5
1
PSE530
Blue DC (–)
+
–
0.6
CA
B
Range
For vacuum
Pressure
Rated pressure range
0 to –101 kPa
A
B
C
0
–101 kPa
10.1 kPa
For compound pressure –100 kPa to 100 kPa –100 kPa
For positive pressure
0 to 1 MPa
0
100 kPa
—
1 MPa
–0.1 MPa
PSE540
Black OUT
(Analog output)
Analog output [V]
1 kΩ
Load
Voltage output type
1 to 5 V
Output impedance
Approx. 1 kW
Main circuit
Brown DC (+)
Series PSE540
Dimensions
PSE560
PSE550
PSE54m- R04
R06
B
A
B
10
10
PSE54m- M3
M5
M3: M3 x 0.5
M5: M5 x 0.8
With across
flats 7
A
PSE54m-M3
PSE54m-M5
A
10.8
11.5
B
3
3.5
Common Dimensions
PSE54m-R06
A
ø4
ø6
B
18
20
9
4
8.7
Controller
9.6
3000
M5 x 0.8
PSE54m- 01
N01
8.7
01: R1/8
N01: NPT1/8
M5 x 0.8
.4
ø3
With across
flats 12
8
13
3
14.4
10
PSE54m-IM5H
7
M5 x 0.8
8
PSE200
PSE54m-IM5
PSE300
18
13
[mm]
PSE54m-R04
PSE570
[mm]
Low Differential
Pressure Sensor
Series PSE550
®
Series
RoHS
Rated pressure range
0
PSE550
1 kPa
2 kPa
0
Power LED status indicator
2 kPa
2 mounting types
Accuracy
1
LED display
± % F.S.
Proof pressure
Mounting directly
Mounting with
bracket
65 kPa
Application examples
9
Flow control
Filter clogging monitoring
Liquid level detection
Series PSE550
Series PSE550
Series PSE550
Can control air flow by monitoring the
flow rate inside the duct.
Can control filtration and replacement
periods by monitoring the clogging of
the filter.
Can detect the liquid level through
changes in the purge pressure.
Low Differential
Pressure Sensor
®
Series PSE550
PSE530
RoHS
How to Order
PSE550
C2
Voltage output type 1 to 5 V
Current output type 4 to 20 mA
Note 1) Current output type cannot be connected to the PSE 200 series.
Note 2) The connector is not attached to the cable, but is included
with the shipment.
Option 1 (Bracket)
Option/Part No.
Part no.
Note
Bracket
ZS-30-A
With M3 x 5L (2 pcs.)
Connector for pressure
sensor controller
ZS-28-C
1 pc.
None
Bracket
A
Note) The bracket is not attached to the product, but is included with the shipment.
Output specifications
PSE570
PSE550
PSE550-28
0 to 2 kPa
–50 to 50 kPa Note)
—
65 kPa
Air/Non-corrosive gas/Non-flammable gas
12 to 24 VDC ±10%, Ripple (p-p) 10% or less (with reverse connection protection)
—
15 mA or less
–0.2 to 0 kPa
Analog output:1 to 5 VDC (within rated differential pressure range) Analog output: 4 to 20 mA DC (within rated differential pressure range)
0.6 to 1 VDC (within extension analog output range) Maximum load impedance:500 W or less (at 24 VDC)
Output impedance: Approx. 1 kW
100 W or less (at 12 VDC)
±1% F.S. (within rated differential pressure range), ±3% F.S. (within extension analog output range)
±0.5% F.S.
±0.3% F.S.
Orange light is turned on. (When energized)
IP40
Operating: 0 to 50°C, Stored: –20 to 70°C (No freezing or condensation)
Operating/Stored: 35 to 85% RH (No condensation)
1000 VAC (in 50/60 Hz) for 1 minute between terminals and housing
50 MW or more (500 VDC measured via megohmmeter) between terminals and housing
±3% F.S. (25°C reference)
ø4.8 (ø4.4 in the end) resin piping
Port size
(Applicable to I.D. ø4 air tubing)
Materials of parts in contact with fluid
Resin pipe: Nylon, Piston area of sensor: Silicon
Oilproof heavy-duty vinyl cable (ellipse), 3 cores, 2.7 x 3.2, 3 m Oilproof heavy-duty vinyl cable (ellipse), 2 cores, 2.7 x 3.2, 3 m
Sensor cable
Conductor area: 0.15 mm2, Insulator O.D.: 0.9 mm
Conductor area: 0.15 mm2, Insulator O.D.: 0.9 mm
With sensor cable
75 g
Weight
Without sensor cable
35 g
Standards
CE, UL/CSA (E216656), RoHS
Note) Can detect differential pressure from 0 to 2 kPa within the range of –50 to 50 kPa.
Environment
Accuracy (Operating temperature at 25°C)
Linearity
Repeatability
Indicator light
Enclosure
Operating temperature range
Operating humidity range
Withstand voltage
Insulation resistance
Temperature characteristics
10
PSE200
Model
Rated differential pressure range
Operating pressure range
Extension analog output range
Proof pressure
Applicable fluid
Power supply voltage
Current consumption
For Pressure Switch Precautions and Specific Product Precautions, refer to “Handling
Precautions for SMC Products” and the Operation Manual on SMC website.
PSE300
Specifications
Controller
Description
Nil
PSE550
Output specifications
Nil
28
None
Connector for pressure
sensor controller (1 pc.)
PSE560
Nil
PSE540
Option 2 (Connector)
Series PSE550
Internal Circuit and Wiring Example
PSE550-28
Main circuit
Voltage output type
1 to 5 V
Output impedance
Approx. 1 kW
1 kΩ
Black OUT
(Analog output)
Blue DC (–)
Load
Brown DC (+)
+
–
12
to
24 VDC
Brown LINE (+) Load
Current output type
4 to 20 mA
Allowable load impedance
500 W or less (at 24 VDC)
100 W or less (at 12 VDC)
Main circuit
PSE550
+
–
Blue LINE (–) Load
12
to
24 VDC
∗ Install the load either on the LINE (+) or
LINE (–) side.
Analog Output
4 to 20 mA DC
5
Analog output [mA]
Analog output [V]
1 to 5 VDC
1
0.6
−0.2
20
4
2 Differential
pressure [kPa]
0
2 Differential
pressure [kPa]
0
Dimensions
2 x ø3.5 through
24.3
37
9
25
7.3
10.7
Indicator light
37
ø4.8
ø4.4
27
ø15
11.7
10.4
3000
2 x M3 x 0.5 depth 4
With bracket
A
37
1.6
38.5
Bracket
11
7
20
A View
40.9
4.2
11.6
69.5
68
25
27
Pressure Sensor
For General Fluids
RoHS
Series
Rated pressure range
−100 kPa
500 kPa
1 MPa
–101 kPa
PSE563
–100 kPa
PSE564
1 MPa
0
100 kPa
0
Applicable fluids example
Material of parts
in contact with fluid
• Hydraulic oil
• Lubricant
• Silicone oil
• Fluorocarbon
• Water
• Air
• Carbon dioxide
Port type
Port size
Variations
500 kPa
Leakage
Analog output
Stainless steel 316L
IP65
Copper-free
Fluorine-free
(Single
(Single diaphragm
diaphragm construction)
construction)
Thread type
Oil-free
Special fitting type for semiconductors
URJ1/4, TSJ1/4*
R1/8, R1/4, Rc1/8, NPT1/8, NPT1/4
–5
PSE550
PSE561
• Argon
• Air-containing drainage
• Refrigerant
• Nitrogen
100 kPa
0
PSE560
PSE560
0
3
PSE570
PSE540
®
PSE530
Series PSE560
1 x 10–10Pa·m3/s
1 x 10 Pa·m /s
1 to 5 V voltage output
4 to 20 mA current output
Check for working
pressure for hydraulic cylinders
Suction verification of
workpieces containing moisture
Controller
Cleaning lines
Note: When vacuum is released, take precautions to avoid water collision with
inertia force. (An adapter with restrictor (ZS-31-X175) is available to
prevent water collision with rush inertia.) (Refer to “NOTE” on the
Operation Manual at SMC website for details.)
12
PSE300
Application examples
PSE200
∗ For URJ1/4, TSJ1/4, refer to “Glossary of Terms/Technical Information” on SMC website or in the Best Pneumatics No. 6.
Pressure Sensor
For General Fluids
®
Series PSE560
RoHS
How to Order
Sensor range
0
1
3
4
Option (Connector)
Nil
Positive pressure [0 to 1 MPa]
Vacuum [0 to –101 kPa]
Compound pressure [–100 to 100 kPa]
Positive pressure [0 to 500 kPa]
C2
PSE56 0
01
Output specifications
Nil
28
Voltage output type 1 to 5 V
Current output type 4 to 20 mA
Extension analog output range
Part no.
Note
ZS-28-C
1 pc.
Adapter with restrictor Rc1/4
ZS-31-X175
1 pc.
Adapter with restrictor NPT1/4
ZS-31-X186
1 pc.
Adapter with restrictor Rc1/8
ZS-31-X188
1 pc.
Adapter with restrictor NPT1/8
ZS-31-X189
1 pc.
PSE560 (Positive pressure)
PSE561 (Vacuum)
0 to 1 MPa
0 to –101 kPa
–100 to 100 kPa
0 to 500 kPa
–0.1 to 0 MPa
10.1 to 0 kPa
—
–50 to 0 kPa
1.5 MPa
500 kPa
500 kPa
750 kPa
Proof pressure
PSE563 (Compound pressure) PSE564 (Positive pressure)
PSE56l-l
Model
Applicable fluid
PSE56l-l-28
Liquid or gas that will not corrode or attack stainless steel 316L
12 to 24 VDC ±10%, Ripple (p-p) 10% or less (with reverse connection protection)
Power supply voltage
Current consumption
Output specifications
Description
Connector for pressure sensor controller
For Pressure Switch Precautions and Specific Product Precautions, refer to “Handling
Precautions for SMC Products” and the Operation Manual on SMC website.
Specifications
Model
10 mA or less
—
Analog output:1 to 5 V (within rated pressure range)
Analog output: 4 to 20 mA DC (within rated pressure range)
0.6 to 1 V (within extension analog output range) Maximum load impedance:500 W or less (at 24 VDC)
Output impedance: Approx. 1 kW
100 W or less (at 12 VDC)
±1% F.S. (within rated pressure range), ±3% F.S. (within extension analog output range)
Accuracy (Ambient temperature at 25°C)
Linearity
±0.5% F.S.
Repeatability
±0.2% F.S.
Power supply voltage effect
±0.3% F.S.
IP65
Environment
Note 1) Current output type
cannot be connected
to the PSE200 series.
Note 2) The connector is not
attached to the cable,
but is included with
the shipment.
Option/Part No.
Port size
01
R1/8 (with M5 female thread)
02
R1/4 (with M5 female thread)
C01
Rc1/8
N01 NPT1/8 (with M5 female thread)
N02 NPT1/4 (with M5 female thread)
A2
URJ1/4
B2
TSJ1/4
Rated pressure range
None
Connector for pressure
sensor controller (1 pc.)
Enclosure
Operating temperature range
Operating: –10 to 60°C, Stored: –20 to 70°C (No freezing or condensation)
Operating humidity range
Operating/Stored: 35 to 85% RH (No condensation)
Withstand voltage
250 VAC for 1 minute between terminals and housing
Insulation resistance
50 MW or more (50 VDC measured via megohmmeter) between terminals and housing
±2% F.S. (0 to 50°C: 25°C reference), ±3% F.S. (–10 to 60°C: 25°C reference)
Temperature characteristics
PSE56l-l: Oilproof heavy-duty vinyl cable with air tubing, 3 cores, ø5.1, 3 m, Conductor area: 0.2 mm2, Insulator O.D.: 1.12 mm
PSE56l-l-28: Oilproof heavy-duty vinyl cable with air tubing, 2 cores, ø5.1, 3 m, Conductor area: 0.2 mm2, Insulator O.D.: 1.12 mm
Sensor cable
Standards
CE, UL/CSA (E216656), RoHS
Piping Specifications
Model
Port size
01
02
N01
N02
R1/8
R1/4
NPT1/8
NPT1/4
M5 x 0.8
M5 x 0.8
M5 x 0.8
M5 x 0.8
Material
Weight
13
With sensor cable
193 g
Without sensor cable
101 g
C01
A2
B2
Rc1/8
URJ1/4
TSJ1/4
Case: C3604 + Nickel plating, Piping port/Pressure sensor: Stainless steel 316L
200 g
194 g
201 g
187 g
203 g
108 g
102 g
109 g
95 g
111 g
193 g
101 g
Pressure Sensor for General Fluids
Series PSE560
Internal Circuit and Wiring Example
PSE56m-m-28
Black OUT
(Analog output)
Blue DC (–)
+
–
Current output type
4 to 20 mA
Allowable load impedance
500 W or less (at 24 VDC)
100 W or less (at 12 VDC)
12
to
24 VDC
4 to 20 mA DC
5
0.6
CA
B Pressure
Range
For vacuum
20
Rated pressure range
0 to –101 kPa
A
B
C
0
–101 kPa
10.1 kPa
For compound pressure –100 kPa to 100 kPa –100 kPa
For positive
pressure
100 kPa
—
0 to 1 MPa
0
1 MPa
–0.1 MPa
0 to 500 kPa
0
500 kPa
–50 kPa
4
A
PSE550
Analog output [mA]
1 to 5 VDC
Analog output [V]
Blue LINE (–) Load
12
to
24 VDC
∗ Install the load either on the LINE (+) or
LINE (–) side.
Analog Output
1
+
–
PSE530
1 kΩ
Load
Main circuit
Voltage output type
1 to 5 V
Output impedance
Approx. 1 kW
Brown LINE (+) Load
PSE540
Brown DC (+)
Main circuit
PSE56m-m
B Pressure
Dimensions
N01
PSE56m- 01
02 , PSE56m- N02
20
Be sure to release the air in the
air tubing of the cable to the
atmosphere. If the air tubing is
restricted, or left in environments
where it is exposed to water or
oil, it cannot be detected normally.
Air tubing
(Atmospheric release)
∗ The dimensions of part C are common to all PSE56m models.
PSE56m-C01
PSE56m-A2
24
24
B
24
B
A
PSE56m-01
PSE56m-02
PSE56m-N01
PSE56m-N02
PSE56m-C01
PSE56m-A2
PSE56m-B2
B
8.2
R1/8
12
R1/4
9.2
NPT1/8
12.2
NPT1/4
—
Rc1/8
15.5
URJ1/4
9.5
TSJ1/4
[mm]
D
H
E
ø1
ZS-31-Xmmm
G
I
F
A
Model
Adapter with restrictor
M5 x 0.8
A
B
[mm]
PSE56m-B2
PSE570
Part-C
5
Part no.
D
E
ZS-31-X188
ZS-31-X189
ZS-31-X175
ZS-31-X186
20
9
20
9
29
13
29
13
F
G
H
I
R1/8
Rc1/8
14
1.5
NPT1/8
NPT1/8
14
1.5
R1/4
Rc1/4
17
1.6
NPT1/4
NPT1/4
17
1.6
Note) If it is predicted that the pressure, such as the water hammer or surge
pressure fluctuates rapidly, refer to the Precautions stated in the
Operation Manual at SMC website (http://www.smcworld.com).
14
PSE200
M5 x 0.8
30
PSE300
B
PSE560
3025
ø14
5.5
Controller
11.5
ø5.1
37.5
A
ø24
24
Pressure Sensor
For General Fluids
Series PSE570
RoHS
Series
Rated pressure range
−100 kPa
0
PSE570
PSE573
100 kPa
500 kPa
1 MPa
0
1 MPa
−100 kPa
100 kPa
PSE574
0
Adopted M12 connector.
M Materials of parts in contact with fluid
Piping port*
C3604 + Nickel plating
Pressure sensor*
Al2O3 (Alumina 96%)
O-ring
FKM + Grease
500 kPa
Proof pressure
3.0 MPa
<Twice as compared with
the PSE560>
∗ For PSE570
Withstand voltage 500 VAC
<Twice as compared with
the PSE560>
* Stainless steel 316L is used for the PSE560.
IP65
For details, refer to page 12.
Application examples
Liquid coolant pressure
control
Discharge pressure control for
compressor
Suction verification of
workpieces containing moisture
Note: When vacuum is released, take precautions to avoid water collision with
inertia force. (An adapter with restrictor (ZS-31-X175) is available to
prevent water collision with rush inertia.) (Refer to “NOTE” on the
Operation Manual at SMC website for details.)
15
*
Pressure Sensor
For General Fluids
Series PSE570
How to Order
PSE57 0
01
Sensor range
Lead wire
Nil
N
Positive pressure [0 to 1 MPa]
Compound pressure [–100 to 100 kPa]
Positive pressure [0 to 500 kPa]
Output specifications
Nil
28
Part no.
ZS-37-A
Note
1 pc.
Connector for pressure sensor controller
ZS-28-CA-4
1 pc.
Adapter with restrictor Rc1/4
ZS-31-X175
1 pc.
Adapter with restrictor Rc1/8
ZS-31-X188
1 pc.
PSE570
PSE573
PSE574
0 to 1 MPa
−100 to 100 kPa
0 to 500 kPa
3.0 MPa
600 kPa
1.5 MPa
Proof pressure
±2% F.S. (0 to 50°C)
±3% F.S. (–10 to 60°C)
PSE57m-m
Model
Applicable fluid
12 to 24 VDC ±10% with 10% voltage ripple or less
Power supply voltage
Current consumption
10 mA or less
Protection
Output
Reverse connection protection
Analog output: 1 to 5 V
Output impedance: Approx. 1 kW
Analog output accuracy
(Ambient temperature at 25°C)
±1.0% F.S.
±0.5% F.S.
Linearity
±0.2% F.S. (Ambient temperature at 25°C)
IP65
Repeatability
Enclosure
Environment
Withstand voltage
500 VAC for 1 minute between terminals and housing
Insulation resistance
100 MW or more (500 VDC measured via megohmmeter) between terminals and housing
Operating temperature range
Operating: –10 to 60°C, Stored: –20 to 70°C (No freezing or condensation)
Operating humidity range
Operating/Stored: 35 to 85% RH (No condensation)
Standards
CE, RoHS
Piping Specifications
Model
Port size
Materials of parts in contact
with fluid
Weight
Analog output: 4 to 20 mA
Maximum load impedance: 500 W or less (at 24 VDC)
100 W or less (at 12 VDC)
Cable Specifications
01
02
R1/8
M5 x 0.8
R1/4
M5 x 0.8
Piping port: C3604 + Nickel plating
Pressure sensor: Al2O3 (Alumina 96%)
O-ring: FKM + Grease
Conductor
Nominal cross section
Outside diameter
Insulator
Outside diameter
Material
Color
Sheath
Material
AWG23
0.72 mm
Cross-linked vinyl
1.14 mm
Brown, Blue, Black, White
Oil resistant vinyl
Without lead wire and M12 connector
88 g
95 g
Finished outside diameter
ø4
With lead wire and M12 connector
175 g
182 g
Length
3m
16 B
PSE200
Analog output
PSE57m-m-28
Gas or liquid that will not attack or corrode materials of parts in contact with fluid
PSE300
Electrical
specifications
±3% F.S. (0 to 50°C)
±4% F.S. (–10 to 60°C)
PSE570
Model
Rated pressure range
Fluid
Port size
01 R1/8 (with M5 female thread)
02 R1/4 (with M5 female thread)
For Pressure Switch Precautions and Specific Product Precautions, refer to “Handling
Precautions for SMC Products” and the Operation Manual on SMC website.
Specifications
Temperature characteristics
(25°C reference)
PSE550
Description
Lead wire and M12 connector (3 m), Straight
Voltage output type 1 to 5 V
Current output type 4 to 20 mA
PSE560
Option/Part No.
Pressure
specifications
Lead wire and M12 connector (3 m), Straight
None
Controller
0
3
4
PSE540
PSE530
RoHS
Series PSE570
Internal Circuit and Wiring Example
PSE57m-m-28
Main circuit
N.C.
1 kΩ
Black OUT
(Voltage output)
Blue DC (–)
Load
Voltage output type
1 to 5 V
Output impedance
Approx. 1 kW
+
–
Current output type
4 to 20 mA
Allowable load impedance
500 W or less (at 24 VDC)
100 W or less (at 12 VDC)
12
to
24 VDC
Brown DC (+)
N.C.
Black OUT
(Current output)
Blue DC (–)
+
–
Load
Brown DC (+)
Main circuit
PSE57m-m
12
to
24 VDC
Analog Output
1 to 5 VDC
4 to 20 mA DC
Analog output [mA]
Analog output [V]
5
1
A
B
Pressure
20
Range
A
Rated pressure range
B
For compound
–100 kPa to 100 kPa –100 kPa
pressure
For positive
pressure
100 kPa
0 to 1 MPa
0
1 MPa
0 to 500 kPa
0
500 kPa
4
A
B
Pressure
Dimensions
A
24
36.5
10.5
M12
23.8
B
M5 x 0.8 depth 4
[mm]
Lead wire and M12 connector
Model
A
B
PSE57m-01
PSE57m-02
8
R1/8
12
R1/4
ZS-37-A
(38.6)
3000
45
30
2: White
ø15
1: Brown
4: Black
3: Blue
M12
Part no.
Description
Straight type 3 m
ZS-37-A
Adapter with restrictor
ZS-31-Xmmm
D
E
H
I
ø1
[mm]
G
M5 x 0.8
F
17
Part no.
D
E
F
G
H
I
ZS-31-X188
ZS-31-X175
20
9
R1/8
Rc1/8
14
1.5
29
13
R1/4
Rc1/4
17
1.6
INFORMATION
Pressure Sensor for General Fluids
RoHS
Rated pressure range
0 to 2 MPa /0 to 5 MPa /0 to 10 MPa added
Withstand voltage
500 VAC
<Twice that of the PSE560>
M12 connector
M12 connector
Enclosure: IP65
 Materials of Parts in Contact with Fluid
Piping port*1
C3604 + Nickel plating
Pressure sensor*1
Al2O3 (Alumina 96%)
Square ring
FKM
*1: Stainless steel 316L is used for the PSE560.
For details, refer to the WEB catalog.
Port size (with M5 female thread): R1/4
 Application Examples
Liquid coolant pressure control
PET bottle molding machines
Liquid pressure control of gun drills
 Series Variations
Series
Rated pressure range
−100 kPa
0
100 kPa
500 kPa
PSE570
PSE573
PSE574
New PSE575
New PSE576
New PSE577
1 MPa
Proof pressure
2 MPa
5 MPa
10 MPa
3.0 MPa
1 MPa
600 kPa
±100 kPa
1.5 MPa
500 kPa
5.0 MPa
2 MPa
12.5 MPa
5 MPa
10 MPa
30 MPa
For details, refer to the WEB catalog.
PSE57  Series
15-E652
How to Order
PSE57 7
02
Sensor range
5
6
7
Lead wire/Options
Output specifications
Positive pressure (0 to 2 MPa)
Positive pressure (0 to 5 MPa)
Port size
Positive pressure (0 to 10 MPa)
02
Nil
28
R1/4 (with M5 female thread)
L
Lead wire and M12 connector
(3 m), Straight
Lead wire and M12 connector
(3 m), Right angle
N
None
Nil
Voltage output (1 to 5 V)
Current output (4 to 20 mA)
Dimensions [mm]
12
39.7
10.5
M12
R1/4
Lead wire and M12 connector
ZS-37-A
4: Black
45
30
3: Blue
ZS-37-B
Adapter with restrictor
ZS-31-X175
M5 x 0.8
3000
M12
M5 x 0.8 thread depth 4
3000
(31)
23.5
45
30
29
17
13
ø1
1.6
*: If it is expected that the pressure, such as the water hammer or surge pressure will
fluctuate rapidly, refer to the
Precautions in the Operation
Manual on the SMC website
(http://www.smcworld.com).
(38.6)
2: White
ø15
23.8
1: Brown
24.55
(30.8)
24
Part no.
Description
ZS-37-A Straight type 3 m
ZS-37-B Right angle type 3 m
Rc1/4
R1/4
ø15
3: Blue
4: Black
2: White
1: Brown
M12
Specifications
Model
Fluid
PSE575
PSE576
PSE577
0 to 2 MPa
5 MPa
0 to 5 MPa
12.5 MPa
±5% F.S. (25°C reference)
0 to 10 MPa
30 MPa
PSE57-02
PSE57-02-28
Applicable fluid Gas or liquid that will not corrode materials of parts in contact with fluid
Power supply voltage
12 to 24 VDC ±10% with 10% voltage ripple or less
Electrical
Current consumption
10 mA or less
specifications
Protection
Reverse connection protection
Analog output Output
Analog output: 1 to 5 V
Output impedance: Approx. 1 kW
Analog output: 4 to 20 mA
Maximum load impedance:
500 W or less (at 24 VDC)
100 W or less (at 12 VDC)
Analog output accuracy (Ambient temperature at 25°C)
±2.5% F.S.
Linearity
±0.5% F.S.
Repeatability
±0.5% F.S. (Ambient temperature at 25°C)
Enclosure
IP65
Withstand voltage
500 VAC for 1 minute between terminals and housing
Environment Insulation resistance 100 MΩ or more (500 VDC measured via megohmmeter) between terminals and housing
Operating temperature range Operating: −10 to 60°C, Stored: −20 to 70°C (No freezing or condensation)
Operating humidity range
Operating/Stored: 35 to 85% RH (No condensation)
Standards
CE, RoHS
Piping Specifications
02
Model
R1/4
M5 x 0.8
Port size
Materials of parts
in contact with
fluid
Weight
Model
Rated pressure range
Pressure
specifications Proof pressure
Temperature characteristics
Without lead wire
and M12 connector
With lead wire
and M12 connector
Piping port:
C3604 + Nickel plating
Pressure sensor:
Al2O3 (Alumina 96%)
Square ring: FKM
103 g
Straight type Right angle type
191 g
Cable Specifications
Nominal cross section
AWG23
Outside diameter
0.72 mm
Cross-linked vinyl chloride
Material
1.14 mm
Insulator Outside diameter
Brown, Blue, Black, White
Color
Sheath
Material
Oil resistant vinyl chloride
Finished O.D.
ø4
Length
3m
Conductor
Safety Instructions Be sure to read the “Handling Precautions for SMC Products” (M-E03-3) and “Operation Manual” before use.
Multi-Channel Digital
Pressure Sensor Controller
RoHS
—
PSE561
PSE533 PSE543
—
PSE563 PSE573
PSE530 PSE540
—
PSE560 PSE570
PSE532
—
−101 kPa
—
−101 kPa
0.1 kPa
1 MPa
0
(Compared with the panel mounted ZSE40/ISE40)
MPa
0.1 kPa
101 kPa
V Functions
• Auto-shift function
• Auto-preset function
• Auto-identification function
• Copy function
• Channel scan function
• Zero-clear function
0.001 MPa
• Keylock function
• Peak/Bottom values holding/
display function
• Display unit switching function
• Display calibration function
• Anti-chattering function
Connector type
kPa
OUT1
3
0.1 kPa
0
40 mm
2
1 MPa
101 kPa
V A single controller monitors up to 4 pressure sensors.
• Sensor input: 4 inputs
• Switch output: 5 outputs (2 outputs for 1ch, 1 output for 2 to 4ch)
1
100 kPa
0
—
OUT2
0
CH
4
PRESSURE
SET
connector
OUT2
OUT1
kPa
OUT2
OUT1
SET
kPa
OUT2
OUT1
SET
kPa
SET
Power supply/Output
connection cable
OUT2
OUT1
PSE570
40 mm
165 mm
kPa
PSE540
PSE531 PSE541
−100 kPa
SET
PSE550
PSE53m PSE54m PSE55m PSE56m PSE57m 76% reduction in installation space
Set/Display
resolution
Rated pressure range
PSE560
Applicable sensors
PSE530
Series PSE200
Check for
working pressure for
hydraulic cylinders
Controller
Check for supply
pressure for ejectors
Suction
verification
MPa
kPa
Check for
supply pressure for
cleaning lines
OUT1
OUT2
1
2
3
4
CH
PRESSURE
SET
Leak test
Placement
verification
Suction verification
of workpieces
containing moisture
18
PSE300
A single controller monitors various applications.
PSE200
Panel mounted
Multi-Channel Controller
Series PSE200
RoHS
How to Order
PSE20 0
M
Option 2
Input/Output specifications
0
1
Nil
NPN 5 outputs + Auto-shift input
PNP 5 outputs + Auto-shift input
Unit specifications
None
Sensor connector (4 pcs.)
4C
Nil
M
With display unit switching function Note 1)
Fixed SI unit Note 2)
Note 1) Under the New Measurement Law, sales
of switches with the unit switching
function are not allowed for use in Japan.
Note 2) Fixed unit
Connector
Option 1
Nil
For vacuum, low pressure and
compound pressure: kPa
For positive pressure: MPa
Accessory: Power supply/Output connection cable (2 m)
None
Panel mount adapter
Mounting screw
(M3 x 8L)
(Accessory)
A
Included with the controller.
Waterproof seal
(Accessory)
Panel mount adapter
Panel
Power supply/Output connection cable
ZS-26-A
Front protective cover + Panel mount adapter
B
Mounting screw
(M3 x 8L)
(Accessory)
Front protective cover
Waterproof seal
(Accessory)
Option/Part No.
When only optional parts are required, order with the part numbers listed below.
Description
Part no.
Note
Panel mount adapter
ZS-26-B
Waterproof seal,
mounting screws M3 x 8L (2 pcs.) included
Front protective cover +
Panel mount adapter
ZS-26-C
Waterproof seal,
mounting screws M3 x 8L (2 pcs.) included
ZS-26-D
48 conversion adapter
m48 conversion adapter
* This adapter is used to
mount the PSE200
series on the panel
fitting of the PSE100
series.
Order panel mount adapter separately.
Front protective cover
ZS-26-01
Sensor connector
ZS-28-C (1 pc. per set)
19
Panel mount adapter
Panel
Multi-Channel Controller
Series PSE200
For Pressure Switch Precautions and Specific Product Precautions, refer to “Handling
Precautions for SMC Products” and the Operation Manual on SMC website.
PSE200
Model
PSE201
Power supply voltage
12 to 24 VDC ±10%, Ripple (p-p) 10% or less (with reverse connection protection)
Current consumption
55 mA or less (Current consumption for sensor is not included.)
Power supply voltage for sensor
[Power supply voltage] –1.5 V
Power supply current for sensor Note 1)
Maximum 40 mA (100 mA maximum for the total power supply current when 4 sensors are input.)
Sensor input
1 to 5 VDC (Input impedance: Approx. 800 kW)
Number of inputs
4 inputs
Input protection
NPN open collector output: 5 outputs
(Sensor input CH1: 2 outputs, CH2 to 4: 1 output)
Maximum load current
80 mA
Maximum load voltage
—
30 V
Residual voltage
1 V or less (with load current of 80 mA)
Response time
5 ms or less (Response time selections with anti-chattering function: 20 ms, 160 ms, 640 ms)
Short circuit protection
±0.1% F.S. ±1 digit
Adjustable (can be set from 0)
Hysteresis mode
Window comparator mode
Fixed (3 digits)
For measured value display: 4-digit, 7-segment indicator, Display color: Orange (Sampling frequency: 4 times/sec)
Display
For channel display: 1-digit, 7-segment indicator, Display color: Red
±0.5% F.S. ±1 digit
Red (Lights up when output is turned ON.)
Display accuracy (Operating temperature at 25°C)
Indicator light
Auto-shift input
PSE550
With short circuit protection
Repeatability
Non-voltage input (Reed or Solid state), Input 10 ms or more, Independently controllable auto-shift function ON/OFF
Auto-identification function
PSE560
With auto-identification function Note 2)
Enclosure
Front face: IP65 (when panel-mounted), Others: IP40 Note 3)
Ambient temperature range
Operating: 0 to 50°C, Stored: –10 to 60°C (No freezing or condensation)
Ambient humidity range
Operating/Stored: 35 to 85% RH (No condensation)
±0.5% F.S. (25°C reference)
Power supply/Output connection: 8P connector, Sensor connection: e-con connector
Temperature characteristics
Connection
Material
Heat resistant heavy-duty cable, 8 cores, ø4.8, 2 m, Conductor area: 0.15 mm2, Insulator O.D.: 0.9 mm
Standards
CE, RoHS
Note 1) If the Vcc and 0 V side of the sensor input connector are short circuited, the inside of the controller will be damaged.
Note 2) Auto-identification function comes with “the PSE53m series” pressure sensor only. Other SMC series (PSE540, 560, 570) are not equipped with this function.
Note 3) IP40 when using the m48 conversion adapter.
Applicable sensor
Rated pressure range
PSE53 PSE54 PSE55 PSE56 PSE57
−100 kPa
−
PSE561
PSE533 PSE543
−
PSE563 PSE573 −101 kPa
PSE530 PSE540
−
PSE560 PSE570
PSE532
−
−
100 kPa
0
−101 kPa
PSE531 PSE541
−
0
Set/Display
resolution
0.1 kPa
101 kPa
0
0
1 MPa
0.1 kPa
1 MPa 0.001 MPa
101 kPa
0.1 kPa
20
Controller
Applicable Pressure Sensor
PSE200
Approx. 60 g (Excluding power supply/output cable)
Power supply/Output connection cable
PSE570
Housing: PBT; Display: Transparent nylon; Back rubber cover: CR
Weight
PSE300
Environment
PNP open collector output: 5 outputs
(Sensor input CH1: 2 outputs, CH2 to 4: 1 output)
PSE540
With excess voltage protection (Up to 26.4 V)
Switch output
Hysteresis
PSE530
Specifications
Series PSE200
Internal Circuit and Wiring Example
PSE200-(M)m
Load
White CH1_OUT2
+
Load
Gray CH2_OUT1
12 to 24 VDC
–
Load
Red CH3_OUT1
Load
4
3
NC 2
1
Black CH1_OUT1
Load
Sensor
4
3
NC 2
1
Yellow Auto-shift input
Main circuit
Sensor
Sensor
4
3
NC 2
1
Brown DC (+)
U
4
3
NC 2
1
Sensor
· NPN open collector 5 outputs + Auto-shift 1 input
Green CH4_OUT1
Blue DC (–)
PSE201-(M)m
21
Load
Black CH1_OUT1
Load
White CH1_OUT2
Load
Gray CH2_OUT1
Load
Red CH3_OUT1
Green CH4_OUT1
Blue DC (–)
Load
4
3
NC 2
1
Yellow Auto-shift input
Main circuit
Sensor
Sensor
4
3
NC 2
1
Sensor
4
3
NC 2
1
Brown DC (+)
U
4
3
NC 2
1
Sensor
· PNP open collector 5 outputs + Auto-shift 1 input
+
12 to 24 VDC
–
Multi-Channel Controller
Series PSE200
Dimensions
PSE200/201
40
Sensor connector
(Option)
PSE530
(7.5)
40.1
2.5
6
MPa
kPa
2
3
CH
4
PRESSURE
MADE IN JAPAN
ZZ
PSE540
1
36.8
PSE200
OUT1
OUT2
SET
2
3
4
Sensor connector (4P x 4)
r
PIN no.
e
w
Terminal
DC (+)
N.C.
DC (–)
IN (1 to 5 V)
PSE560
q
Connector (Option)
PSE550
CH 1
PSE570
Power supply/Output connector (8P)
Power supply/Output connection cable (Accessory)
q w e r t y u i
DC (+)
7 Green : CH4_OUT1
DC (–)
6 Red
: CH3_OUT1
CH1_OUT1
5 Gray : CH2_OUT1
CH1_OUT2
4 White : CH1_OUT2
CH2_OUT1
3 Black : CH1_OUT1
CH3_OUT1
2 Blue : DC (–)
CH4_OUT1
1 Brown : DC (+)
2000
Auto-shift input
22
PSE200
Pin no.
8 Yellow : Auto-shift input
PSE300
Terminal
Controller
PIN no.
Series PSE200
Dimensions
Front protective cover + Panel mount adapter
53
47
9.4
42.4
(2)
OUT1
OUT2
46.4
MPa
kPa
CH
1
2
3
4
PRESSURE
SET
Panel mount adapter
Front protective cover
Waterproof seal
m48 conversion adapter + Panel mount adapter
6
48
Panel
(2)
1.5
MPa
kPa
OUT1
OUT2
CH
1
2
3
4
PRESSURE
SET
Panel mount adapter
Waterproof seal
Panel
55 or more
48 conversion adapter
+0.1
55 or more
37.5 –0.2
4
x
R
1
or
le
ss
Panel fitting dimensions
Applicable panel thickness: 0.5 to 8 mm
23
2-Color Display Digital
Pressure Sensor Controller
Series PSE300
RoHS
PSE531 PSE541
—
PSE561
PSE533 PSE543
—
PSE563 PSE573
PSE530 PSE540
—
PSE560 PSE570
PSE532
—
—
—
—
—
—
—
PSE550
0
–101 kPa
—
0
0
1 kPa
500 kPa
0.01 kPa
0 2 kPa
Can be mounted in close proximity with each other either horizontally or vertically.
Response time
1 ms
Possible to reduce panel fitting labor.
PRESSURE
OUT1
PRESSURE
MPa
OUT2
SET
OUT1
OUT2
SET
PRESSURE
MPa
0.001 MPa
0.1 kPa
100 kPa
0
OUT1
MPa
OUT2
SET
connector
Sensor connector
• Auto-shift function
• Auto-preset function
• Display calibration function
• Peak/Bottom values holding/display function
• Keylock function
• Zero-clear function
• Error indication function
• Display unit switching function
• Anti-chattering function
Current input type
Electrical current input (4 to 20 mA DC) is added to
the sensor input.
PSE31
(Current input type)
Applicable
sensor type
PSE550-28
(Current
output type)
Applicable
sensor type
PSE56--28
(Current
output type)
Applicable
sensor type
PSE57--28
(Current
output type)
24
PSE200
Power supply/Output connector
Functions
PSE300
V
PSE570
30 mm
Connector type
DIN rail/Terminal block type
1 MPa
Controller
ON
OFF
Red Green
Green Red
Red
Red
Green Green
0.2 kPa
100 kPa
—
Possible to set 4 patterns of display color.
1 MPa
0.1 kPa
–100 kPa
PSE564 PSE574
2-color display (Red/Green)
500 kPa
0
—
—
100 kPa
PSE560
—
−100 kPa
PSE540
PSE53m PSE54m PSE55m PSE56m PSE57m Pattern
q
w
e
r
Set/Display
resolution
Rated pressure range
PSE550
Applicable sensors
PSE530
®
Pressure Sensor Controller
®
Series PSE300
RoHS
How to Order
Option
Nil
None
Front protective cover
Front protective
cover
E
DIN rail/Terminal
block type
PSE3 0 0 T M
Connector type
PSE3 0 0
M
Input specifications
0
1
Option 3
Voltage input
Current input
Nil
None
Sensor connector
Input/Output specifications
0
1
2
3
4
5
NPN 2 outputs + 1-5 V output
NPN 2 outputs + 4-20 mA output
NPN 2 outputs + Auto-shift input
PNP 2 outputs + 1-5 V output
PNP 2 outputs + 4-20 mA output
PNP 2 outputs + Auto-shift input
Unit specifications
Note) The connector is not attached to the cable, but is
included with the shipment.
Nil
With display unit switching function Note 1)
M Fixed SI unit Note 2)
Note 1) Under the New Measurement Law, sales of switches with
the unit switching function are not allowed for use in Japan.
Note 2) Fixed unit
For vacuum, low pressure, low differential pressure and
compound pressure: kPa
For positive pressure:MPa (For 1 MPa)
kPa (For 500 kPa)
Option 1
Nil
Option 2
Nil
None
Bracket
M3 x 5L
A
None
Power supply/Output connection cable
L
Sensor connector
(e-con connector)
C
Bracket
M3 x 5L
Panel mount adapter
Power supply/
Output connection cable
ZS-28-A
Panel
B
Note) The cable is not attached to the product, but is
included with the shipment.
Mounting screw
(M3 x 8L)
Order DIN rail separately. Refer to page 30.
Panel mount adapter
Panel mount adapter + Front protective cover
Option/Part No.
Panel
Front protective cover
Description
Part no.
Power supply/Output connection cable (2 m)
ZS-28-A
Note
Bracket
ZS-28-B With M3 x 5L (2 pcs.)
Sensor connector
ZS-28-C
Panel mount adapter
ZS-27-C With M3 x 8L (2 pcs.)
Mounting screw
(M3 x 8L)
1 pc.
Panel mount adapter + Front protective cover
ZS-27-D With M3 x 8L (2 pcs.)
Front protective cover
ZS-27-01
25
D
1 pc.
Panel mount adapter
Note) These options are not attached to products, but are
included with the shipment.
Pressure Sensor Controller
Series PSE300
For Pressure Switch Precautions and Specific Product Precautions, refer to “Handling
Precautions for SMC Products” and the Operation Manual on SMC website.
Specifications
PSE3mm
PSE530
PSE533
PSE531
PSE564
PSE540
PSE543
PSE550
Applicable pressure sensor
PSE541
PSE532
PSE563
PSE574
PSE560
PSE561
PSE573
PSE570
Display/Set pressure (differential pressure) range –101 to 101 kPa
10 to –101 kPa
–10 to 100 kPa
–0.1 to 1 MPa
–50 to 500 kPa
–0.2 to 2 kPa
Display/Set resolution
0.2 kPa
0.1 kPa
0.1 kPa
0.001 MPa
1 kPa
0.01 kPa
For compound pressure
For vacuum
For low pressure
For positive pressure
For low differential pressure
Pressure range Note 1)
Rated pressure (differential pressure) range –100 to 100 kPa
0 to –101 kPa
0 to 100 kPa
0 to 1 MPa
0 to 500 kPa
0 to 2 kPa
—
10.1 to 0 kPa
–10 to 0 kPa
–0.1 to 0 MPa
–50 to 0 kPa
–0.2 to 0 kPa
Extension analog output range Note 2)
Power supply voltage
12 to 24 VDC ±10%, Ripple (p-p) 10% or less (with reverse connection protection)
Current consumption
50 mA or less (Current consumption for sensor is not included.)
PSE30l: Voltage input 1 to 5 VDC (Input impedance: 1 MW)
Sensor input
PSE31l: Current input 4 to 20 mA DC (Input impedance: 100 W)
Number of inputs
1 input
Input protection
With excess voltage protection (Up to 26.4 V)
Hysteresis
Hysteresis mode: Variable, Window comparator mode: Variable
Switch output
NPN or PNP open collector output: 2 outputs
Maximum load current
80 mA
Maximum load voltage
30 VDC (at NPN output)
Residual voltage
1 V or less (with load current of 80 mA)
Output protection
With short circuit protection
Response time
1 ms or less
Anti-chattering function
Response time settings for anti-chattering function: 20 ms, 160 ms, 640 ms, 1280 ms
Repeatability
±0.1% F.S.
Output voltage: 1 to 5 V (within rated pressure (differential pressure) range), 0.6 to 1 V (within extension analog output range)
Note
2)
Voltage output
Output impedance: Approx. 1 kW, Linearity: ±0.2% F.S. (Not including sensor accuracy), Response speed: 150 ms or less
Accuracy (To display value) (25°C)
±0.6% F.S.
±1.0% F.S.
±1.5% F.S.
Analog
Output current: 4 to 20 mA (within rated pressure (differential pressure) range), 2.4 to 4 mA (within extension analog output range)
output
Maximum load impedance: 300 W (at 12 VDC), 600 W (at 24 VDC), Minimum load impedance: 50 W
Current output Note 2)
Linearity: ±0.2% F.S. (Not including sensor accuracy), Response time: 150 ms or less
Accuracy (To display value) (25°C)
±1.0% F.S.
±1.5% F.S.
±2.0% F.S.
Display accuracy
±0.5% F.S.
±0.5% F.S. ±1 digit
(Ambient temperature at 25°C)
±2 digits
Display
3 + 1/2 digit, 7 segment indicator, 2-color display (Red/Green), Sampling frequency: 5 times/sec
Indicator light
OUT1: Lights up when turned ON (Green), OUT2: Lights up when turned ON (Red)
Auto-shift input Note 2)
Non-voltage input (Reed or Solid state), Low level input: 5 ms or more, Low level: 0.4 V or less
Enclosure
IP40
Operating temperature range
Operating: 0 to 50°C, Stored: –10 to 60°C (No freezing or condensation)
Operating humidity range
Operating/Stored: 35 to 85% RH (No condensation)
Withstand voltage
1000 VAC for 1 minute between terminals and housing
Insulation resistance
50 MW or more (500 VDC measured via megohmmeter) between terminals and housing
Temperature characteristics
±0.5% F.S. (25°C reference)
PSE3ll: Power supply/Output connection: 5P connector, Sensor connection: 4P connector
Connection
PSE3llT: Terminal block
Material
Front case: PBT, Rear case: PBT (PSE3ll), Modified PPE (PSE3llT)
With power supply/Output connection cable
PSE3ll: 85 g
Weight
Without power supply/Output connection cable
PSE3ll: 30 g, PSE3llT: 50 g
Power supply/Output connection cable
Oilproof heavy-duty vinyl cable, 5 cores, ø4.1, 2 m, Conductor area: 0.2 mm2 Insulator O.D.: 1.12 mm
Standards
CE, UL/CSA (E216656), RoHS
Note 1)Pressure range can be selected during initial setting.
Note 3) The following units can be selected with display unit switching function:
Note 2)Auto-shift function is not available when analog output option is selected.
For vacuum & compound pressure: kPa·kgf/cm2·bar·psi·mmHg·inHg
Also, analog output option is not available when auto-shift function is selected.
For positive pressure & low pressure: MPa·kPa·kgf/cm2·bar·psi
Extension analog output is not available for the PSE570 series.
For low differential pressure:
kPa·mmH2O
4 to 20 mA DC
Analog output [mA]
Analog output [V]
1 to 5 VDC
5
1
0.6
EA
FC
B Pressure
D Differential pressure
20
4
2.4
EA
FC
Range
Rated pressure range
A
For vacuum
0 to –101 kPa
0
For compound pressure –100 kPa to 100 kPa –100 kPa
For low pressure
0 to 100 kPa
0
0 to 1 MPa
0
For positive
pressure
0 to 500 kPa
0
Range
Rated pressure range
For low differential pressure
0 to 2 kPa
B
E
–101 kPa
100 kPa
100 kPa
1 MPa
500 kPa
10.1 kPa
—
–10 kPa
–0.1 MPa
–50 kPa
C
D
F
0
2 kPa
–0.2 kPa
B Pressure
D Differential pressure
26 a
PSE530
PSE540
PSE550
PSE560
PSE570
PSE200
PSE300
Analog Output
Controller
Environment
Model
Series PSE300
Internal Circuit and Wiring Example
PSE3
(T)
Input/Output specification
Input specification
PSE3m0(T)
PSE3m1(T)
NPN (2 outputs) + Analog voltage output
NPN (2 outputs) + Analog current output
Load
Load
PSE3m2(T)
PSE3m3(T)
NPN (2 outputs) + Auto-shift 1 input
PNP (2 outputs) + Analog voltage output
Brown DC (+)
Blue DC (–)
PSE3m4(T)
PSE3m5(T)
PNP (2 outputs) + Analog current output
PNP (2 outputs) + Auto-shift 1 input
Brown DC (+)
U
U
Connector for Sensor Connection
Terminal
PSE31 (Current input)
Pressure sensor 2-wire type Pressure sensor 3-wire type
1
DC (+) (Brown)
DC (+) (Brown)
2
N.C.
N.C.
N.C.
3
DC (–) (Blue)
N.C.
DC (–) (Blue)
4
DC (+) (Brown)
IN (1 to 5 V) (Black) IN (4 to 20 mA) (Blue) IN (4 to 20 mA) (Black)
Note: The colors in ( ) indicate the wire color of the PSE5mm series.
27
Load
Main circuit
White OUT2
Blue DC (–)
12
to
– 24 VDC
+
Black OUT1
Load
Blue DC (–)
Load
White OUT2
12
+
to
– 24 VDC
U
Load
Load
Gray Auto-shift input
U
Main circuit
Black OUT1
(Voltage input)
Load
Brown DC (+)
Gray Analog output
PSE30
Load
White OUT2
Blue DC (–)
12
to
– 24 VDC
+
Load
Load
White OUT2
Black OUT1
U
12
to
– 24 VDC
+
Black OUT1
Main circuit
Gray Analog output
U
Main circuit
U
U
Gray Auto-shift input
Load
Brown DC (+)
PIN
no.
Load
White OUT2
Blue DC (–)
12
to
– 24 VDC
+
Black OUT1
Load
Load
U
White OUT2
Blue DC (–)
12
to
– 24 VDC
+
Black OUT1
Main circuit
Gray Analog output
U
Main circuit
U
U
Gray Analog output
Load
Brown DC (+)
Brown DC (+)
Pressure Sensor Controller
Series PSE300
Dimensions
30
31
3
20 ±0.1
2 x M3 x 0.5
depth 4
10
1.5
Power supply/Output connector
PSE540
Sensor connector
3.2
1.5
8.2
20
2020
Terminal
PIN
no. PSE30l
PSE31l
1 DC(+)(Brown) DC(+)(Brown)
2
N.C.
N.C.
N.C.
3 DC(–)(Blue)
4 IN (1 to 5 V) (Black) IN (4 to 20 mA) (Blue)
PSE550
DC (+) Brown 5
OUT1 Black 4
OUT2 White 3
Analog output or auto-shift input Gray 2
DC (–) Blue 1
Sensor connector
4 3 2 1
Power supply/Output connection cable (ZS-28-A)
PSE530
PSE3ll
Note: The colors in ( ) indicate the wire color of
the PSE5ll series.
PSE560
With bracket
A
30
15
PSE570
26.5
31.5
1.6
40
10
4.2
46
20
7
A View
With panel mount adapter + Front protective cover
With panel mount adapter
42.4
34.5
7
24
Panel thickness 0.5 to 6
8.5
34.5
11
24
Panel mount adapter + Front protective cover
Panel mount adapter
28
Controller
Bracket
PSE300
35
41
PSE200
22
Series PSE300
Dimensions
Panel fitting dimensions
Horizontal stacking mount of multiple units (n pcs.)
Mount of single unit
0
31 –0.4
0
31 –0.4
0
31 –0.4
31 x n pcs. + 3.5 x (n pcs. – 1)
4
4
x
ss
le
ss
le
or
or
2
R
2
R
24 or more
x
Vertical stacking mount of multiple units (n pcs.)
0
24 or more
31 x n pcs. + 3.5 x (n pcs. – 1)
31 –0.4
4
x
2
R
s
es
l
or
29
Series PSE300
Pressure Sensor Controller
Dimensions
38
8 x M3
3 x 7.2 (= 21.6)
Front protective cover (Option)
2 x ø3.4 mounting hole
PSE530
PSE3llT
(Rotate 90° to mount.)
6.4
2 x ø6.4
3
2
1
28
4
OUT2
35.5
42.4
PSE540
OUT1
33.5
10
30
56
44
PRESSURE
SET
6
7
8
PSE550
5
4.5 (Max. 8)
16
11
29
21.4
1.5
34.8
38.6
(38.9)
12 to
24 VDC
OUT1
DC (+)
OUT2
IN
Brown
GND
Black
12 to
24 VDC
OUT1
FUNC
(Analog output
or auto-shift
input)
DC (–)
Blue
DC (+)
Brown
IN
OUT2
DC (–)
Blue
GND
FUNC
(Analog output
or auto-shift
input)
Pressure sensor
Controller
Pressure sensor
–
PSE570
+
–
DIN Rail
ISA-5-l
L
8
4.5
7.5
35
5.5
35
1.3
Part no.
L
ISA-5-1
ISA-5-2
ISA-5-3
ISA-5-4
ISA-5-5
ISA-5-6
ISA-5-7
73.0
135.5
173.0
210.5
248.0
285.5
323.0
30 A
PSE200
+
PSE31lT
(Current input: Pressure sensor 2-wire type)
PSE300
PSE3llT
(Voltage input, Current input: Pressure sensor 3-wire type)
PSE560
Connections
Series PSE200/300
Function Details
A Auto-shift function
Auto-shift circuit
When there are large fluctuations in the supply pressure, the switch
may fail to operate correctly. The auto-shift function compensates
such supply pressure fluctuations. It measures the (differential)
pressure at the time of auto-shift signal input and uses it as the
reference (differential) pressure to correct the set value on the switch.
PSE3l2
NPN open collector output: 2 outputs
Brown DC (+)
Gray
Supply pressure Supply pressure Supply pressure
normal
drop
increase
Rectified value∗
P-1
(P-3)
H-1
(H-2)
Switch ON
output OFF
1·(2)
Hi
B
Switch output
response time
when autoshift is input.
OUT1
OUT2
Blue
DC (−)
+ 12
Load − to 24 VDC
PNP open collector output: 2 outputs
Brown DC (+)
Gray
Lo
PSE200
PSE300
10 ms or more
15 ms or less
5 ms or more
10 ms or less
* Rectified value
When the auto-shift is selected, “ooo” will be displayed for approximately 1 second, and the pressure value at that point will be saved
as a rectified value “C_5” (for CH1 of PSE200 and PSE300) or “C_3”
(for CH2 to 4 for PSE200). Based on the saved rectified values
(Note), the set value “P_1” to “P_4” (for PSE200) or “P_1”, “H_1”,
“P_3”, “H_2” (for PSE300) will likewise be rectified.
Note) When an output is reversed, “n_1” to “n_4” (for PSE200) or
“n_1”, “H_1”, “n_3”, “H_2” (for PSE300) will be rectified.
Settable range
Compound pressure
–101.0 to 101.0 kPa
–101.0 to 101.0 kPa
Vacuum
10.0 to –101.0 kPa
101.0 to –101.0 kPa
Low pressure
–10.0 to 101.0 kPa
–100.0 to 101.0 kPa
–0.1 to 1.000 MPa
–1.000 to 1.000 MPa
—
—
Low differential pressure
—
—
PSE300
Set pressure
(differential pressure) range
Settable range
Compound pressure
–101.0 to 101.0 kPa
–101.0 to 101.0 kPa
Vacuum
10.0 to –101.0 kPa
101.0 to –101.0 kPa
Low pressure
–10 to 100.0 kPa
–100.0 to 100.0 kPa
–0.1 to 1.000 MPa
–1.000 to 1.000 MPa
Positive pressure
Positive pressure
Low differential pressure
White
OUT2
Blue
DC (−)
Load − to 24 VDC
Note) The colors in the circuit diagram indicate the color of the lead wire when it
is connected to the power supply/output connection cable (ZS-28-A).
B Auto-preset function
Auto-preset function, when selected in the initial setting, calculates
and stores the set-value from the measured (differential) pressure.
The optimum set-value is determined automatically by repeating
vacuum and break with the target workpiece several times.
Suction Verification
High
Vacuum
PSE200
+ 12
OUT1
Load
Settable Range for Auto-Shift Input
Set pressure
(differential pressure) range
Auto-shift input
Black
Pressure sensor
controller
A Auto-shift input B Switch output response time
time
at time of auto-shift input
Work 1
Max. A
P-1
Adsorption
Work 2
Work n
H-1
P-2
Min. B
Atmosphere
Nonadsorption
Work 1
Work 2
Work n
Formula for Obtaining the Set Value
–50 to 500 kPa
–500 to 500 kPa
–0.2 to 2.00 kPa
–2.00 to 2.00 kPa
Auto-shift zero (PSE300 series only)
The basic function of auto-shift zero is the same as the function for
auto-shift. Also, it corrects values on the display, based on a pressure value of 0, when the auto-shift is selected.
31
Black
White
PSE3l5
A
Auto-shift
input
Auto-shift input
Load
Pressure sensor
controller
Rectified
value∗
(Differential)
Pressure
Set value correction by auto-shift function
P_1 or P_3
PSE200
PSE300
P_1(P_3)=A-(A-B)/4
P_2(H_1) or P_4(H_2)
P_2(P_4)=B+(A-B)/4
H_1(H_2)=(A-B)/2
Pressure Sensor Controller
Series PSE200/300
H Copy function (PSE200 series only)
Information that can be copied includes the following: q Pressure
set values, w Range settings, e Display units, r Output modes, t
Response times.
• When CH1 is copied to CH2, CH3, and CH4, information of OUT1
in CH1 will be copied.
• When CH2, CH3, or CH4 is copied to CH1, information of OUT1 in
CH2, CH3, or CH4 will be copied only to OUT1 in CH1.
±5%R.D.
Note) When the copy function is used, the regulating pressure value
of the copied channel may change ±1 digit.
+
Applied pressure
E Keylock function
Prevents operation errors such as accidentally changing setting values.
F Zero-clear function
This function clears and resets the zero value on the display of measured (differential) pressure within ±7% F.S. of the factory adjusted value.
G Error indication function
Auto-shift
error
Applied pressure
error
Residual
pressure error
Overcurrent
error
Error code
Error
name PSE200 PSE300
Description
Load current of 80 mA or more is applied to
the switch output (OUT1).
Load current of 80 mA or more is applied to
the switch output (OUT2).
Pressure applied during the zero reset
operation exceeds ±7% F.S.
* After displaying the error code for 3
seconds, the switch automatically returns
to the measuring mode. Due to individual
product differences, the setting range
varies ±4 digits.
Supply pressure exceeds the maximum set
(differential) pressure or upper limit of the
display pressure.
A sensor may be disconnected or
mis-wired. Or, supply pressure is below the
minimum set (differential) pressure or lower
limit of the display pressure.
The value measured at the time of
auto-shift input is outside the set
(differential) pressure range.
* After displaying the error code for one
second, the switch returns to the
measuring mode.
System error
Internal data error
Internal data error
Internal data error
Internal data error
PSE550
This function constantly detects and updates the maximum and
minimum values and allows to hold the display value.
For PSE300, when the cd are simultaneously pressed for 1 second or longer, while “holding”, the hold value will be reset.
J Anti-chattering function
A large bore cylinder or ejector consumes a large volume of air in
operation and may experience a temporary drop in the supply pressure. This function prevents detection of such temporary drops in the
supply pressure as an error.
PSE560
D Peak/Bottom values holding/display function
Available response time settings
PSE200 20 ms, 160 ms, 640 ms
PSE300 20 ms, 160 ms, 640 ms, 1280 ms
<Principle>
This function averages pressure values measured during the response time set by the user and then compares the average pressure value with the pressure set point value to output the result on
the switch.
PSE570
Note) When the display calibration function is used, the set pressure
value may change ±1 digit.
I Auto-identification function (PSE200 series only)
This function automatically identifies the pressure range of the pressure sensor that is connected to the multi-channel pressure sensor
controller, thus eliminating the need of having to reset the range
again after replacing the sensor. This function will be activated either
when “Aon” is set in the auto-identification mode or when the power
is turned back on in that condition. However, this function only works
in conjunction with specific pressure sensors (SMC PSE53m series).
When other pressure sensors are used, this function will not work.
When using other types of pressure sensors, first set the autoidentification mode to “AoF”, and then proceed to setting the range.
Turning the power back on while in the “Aon” setting can cause a
malfunction.
Pressure ≠
Momentary change
Set-value
P-1
H-1
t (ms)
t (ms)
<Averaging>
<Averaging>
Switch output
operation in ON
normal
OFF
conditions
Switch output
operation when ON
anti-chattering OFF
function is on
Time →
Time →
Time →
K Channel selection function (PSE200 series only)
Pressure value for the selected channel is displayed.
L Channel scan function (PSE200 series only)
Pressure values for each channel are displayed by turns at 2-second
intervals.
32
PSE200
Adjustable range of display calibration function
PSE540
Indicated value at the time of shipment
PSE300
0
Controller
Indicated value of pressure
C Display calibration function
Fine adjustment of the indicated value of the pressure sensor can be
made within the range of ±5% of the read value.
(The scattering of the indicated value can be eliminated.)
PSE530
Function Details
Series PSE200/300
Function Details
M Display unit switching function
Display units can be switched with this function.
Units that can be displayed vary depending on the range of the
pressure sensors connected to the controller.
PSE200
Pressure
range
For
For
For
For low
compound
positive
pressure vacuum pressure pressure
PSE533
Applicable
pressure
sensor
PSE530
PSE531
PSE543
PSE541 PSE532
PSE563
PSE561
PSE573
PSE540
PSE560
PSE570
Set pressure –101 to 101 10 to –101 –10 to 101 –0.1 to 1
(differential
kPa
kPa
MPa
kPa
pressure) range
kPa
0.1
0.1
0.1
—
MPa
—
—
—
0.001
kgf/cm2
0.001
0.001
0.001
0.01
bar
0.001
0.001
0.001
0.01
psi
0.02
0.01
0.01
0.1
inHg
0.1
0.1
—
—
mmHg
1
1
—
—
PSE300
Pressure
range
Applicable
pressure
sensor
For
For low
For
compound
pressure vacuum pressure
PSE533
PSE543
PSE563
PSE573
For positive
pressure
For low
differential
pressure
PSE530
PSE531
PSE541 PSE532
PSE561
PSE540 PSE564
PSE560 PSE574
PSE550
PSE570
Set pressure –101 to 101 10 to –101 –10 to 100 –0.1 to 1 –50 to 500 –0.2 to 2.00
(differential
kPa
kPa
MPa
kPa
kPa
kPa
pressure) range
kPa
0.2
0.1
0.1
—
1
0.01
MPa
—
—
—
0.001
—
—
kgf/cm2 0.002
0.001
0.001
0.01
0.01
—
bar
0.002
0.001
0.001
0.01
0.01
—
psi
0.05
0.02
0.02
0.2
0.1
—
inHg
0.1
0.1
—
—
—
—
1
—
—
—
1 mmH2O
mmHg 2
33
Remote Type
Pressure Sensor/
3-Screen Display Sensor Monitor
RoHS
IP65
Pressure Sensor for General Fluids PSE57 Series
Rated pressure range
0 to 1 MPa
−100 to 100 kPa
0 to 500 kPa
0 to 2 MPa
0 to 5 MPa
0 to 10 MPa
Withstand voltage
500 VAC
<Twice that of the PSE560>
Materials of Parts in Contact with Fluid
Piping port
C3604 + Nickel plating
Pressure sensor
Al2O3 (Alumina 96%)
Square ring
FKM
New 3-Screen Display
Sensor Monitor PSE300AC Series
Change the settings
while checking
the measured value.
Visualization of Settings
Set value (Threshold value)
Main screen
Measured value (Current pressure value)
Sub screen
Label (Display item),
Set value (Threshold value)
Hysteresis value
Delay time
Peak value
Bottom value
PSE57 /PSE300AC Series
CAT.ES100-119A
Pressure Sensor for General Fluids PSE57 Series
PSE570/573/574
 PSE575/576/577
Materials of parts in
contact with fluid
(1 MPa/100 kPa/500 kPa)
(2 MPa/5 MPa/10 MPa)
Pressure sensor
O-ring
FKM + Grease
Materials of parts in
contact with fluid
Pressure sensor
Al2O3
(Alumina 96%)
Al2O3 (Alumina 96%)
Port size
R1/4 (with M5 female thread)
Square ring
FKM
Port size
R1/8, 1/4
(with M5 female thread)
Fitting
C3604 +
Nickel plating
Fitting
C3604 +
Nickel plating
Series Variations
Model
Series Variations
Proof
pressure
Rated pressure range
−100 kPa
0
100 kPa
500 kPa
1 MPa
2 MPa
5 MPa
1 MPa
PSE570
±100 kPa
PSE573
500 kPa
PSE574
Model
10 MPa
3.0
MPa
PSE575
600
kPa
PSE576
1.5
MPa
PSE577
0
100 kPa
500 kPa
1 MPa
5 MPa
10 MPa
5.0
MPa
5 MPa
10 MPa
<Integrated type>
Steel tube piping
2 MPa
2 MPa
Reduced Man Hours & Installation Space for Piping
<Remote type>
Proof
pressure
Rated pressure range
−100 kPa
12.5
MPa
30
MPa
ISE75 (with bracket)
360 mm
Steel tube piping
PSE57
Hydraulic
manifold
Hydraulic
manifold
180 mm
Hydraulic cylinder
Liquid coolant pressure control
PSE300AC
Hydraulic cylinder
Discharge pressure control for compressor
PET bottle molding machines
Liquid pressure control of gun drills
Suction verification of workpieces containing moisture
* W
hen vacuum is released, take
precautions to avoid water collision
with inertia force. (An adapter with
restrictor (ZS-31-X175) is available
to prevent water collision with rush
inertia.) (Refer to “NOTE” on the
Operation Manual at SMC website
for details.)
Variations For details, refer to the Web Catalog.
For General Fluids
PSE56 Series
¡Parts in contact with fluid: Stainless steel 316L
¡IP65
¡Oil-free
(Single diaphragm construction)
1
Applicable Pressure Sensors
 Compact Pneumatic Pressure Sensor
PSE53
PSE54
 Low Differential Pressure Sensor  Pressure Sensor for General Fluids
PSE55
PSE56
3-Screen Display Sensor Monitor PSE300AC Series
Visualization of Settings
Sub screen (label) shows
the item to be set.
Mode Examples
Hysteresis mode
New PSE300AC
Current model
Set value
Normal output (Threshold
value)
Set value
Reverse output (Threshold
value)
Hysteresis Set hysteresis
value
Displays
in turn.
Always
displayed
in one
screen.
Window comparator mode
Normal output/
Lo side
Set value
(Threshold value)
Normal output/
Hi side
Set value
(Threshold value)
Reverse
output/Lo side
Set value
(Threshold value)
Reverse
output/Hi side
Set value
(Threshold value)
Easy Screen Switching
Setting is possible while checking the measured value.
The sub screen can be switched by pressing up/down buttons.
Main screen
Measured value (Current pressure value)
Set value (Threshold value)
Sub screen/Left side
Hysteresis value
Bottom value
Peak value
Label (Display item)
Sub screen/Right side
* One arbitrary display mode can be added by setting the function.
Set value (Threshold value)
 Input Range Selection (for Pressure/ Flow rate)
NPN/PNP Switch Function
Reduced number of stock items.
Sensor input range can be set to required value and displayed.
(Voltage input: 1 to 5 V/Current input: 4 to 20 mA)
Pressure switch/Flow switch can be displayed.
B
A is displayed for 1 V (or 4 mA).
B is displayed for 5 V (or 20 mA).
The range can be set as required.
Display
A
5V
Input voltage 1 V
Input current 4 mA 20 mA
 For Digital Flow Switch for Water/PF3W511
Select NPN
or PNP
NPN
100
Display
PNP
0
Input voltage 1 V
Simple 3 Step Setting
A
0
0
0
0
PF3W504
PF3W520
PF3W540
PF3W511
5V
B
4
16
40
100
Set A and B to the values shown in the table above.
When S button is pressed, and the set value (P_1) is being displayed, the set value (threshold value) can be set.
When S button is pressed, and the hysteresis (H_1) is being displayed, the hysteresis can be set.
1
2
3
With a snapshot function for set value reading
Pressing the
and
buttons for a minimum of 1 second will make
the set value (threshold value) the same as the current pressure value.
Push
Adjust to the set
value by the
or
button.
Push
Push
Completion of setting
Start of setting
Release the button after “---” is
displayed on the right side sub screen.
Snap shot
function
Push
Completion of setting
2
Pressure Sensor for General Fluids
PSE57  Series
RoHS
How to Order
PSE57 0
01
Option (Lead wire)
Sensor range
0
3
4
5
6
7
Positive pressure [0 to 1 MPa]
Compound pressure [−100 to 100 kPa]
Positive pressure [0 to 500 kPa]
Positive pressure [0 to 2 MPa]
Positive pressure [0 to 5 MPa]
Positive pressure [0 to 10 MPa]
Nil
Lead wire and M12 connector
(3 m), Straight
L
Lead wire and M12 connector
(3 m), Right angle
N
None
* See page 9 for connection to the PSE300AC.
Output specification
Options/Part Nos.
Nil
28
Description
Lead wire and M12 connector (3 m), Straight
Lead wire and M12 connector (3 m), Right angle
Adapter with restrictor Rc1/4
Adapter with restrictor Rc1/8
Assembly type connector
Part no.
ZS-37-A
ZS-37-B
ZS-31-X175
ZS-31-X188
PCA-1557743
Note
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
Voltage output type 1 to 5 V
Current output type 4 to 20 mA
Port size
Symbol
Port size
01 R1/8 (with M5 female thread)
02 R1/4 (with M5 female thread)
Model
PSE570 PSE573 PSE574 PSE575 PSE576 PSE577






—

—

—

For pressure switch precautions and specific product precautions,
refer to the “Operation Manual” on the SMC website.
Specifications
Model
PSE570
PSE573
PSE574
PSE575
PSE576
PSE577
Applicable fluid
Gas or liquid that will not corrode materials of parts in contact with fluid
Rated pressure range
0 to 1 MPa
−100 to 100 kPa
0 to 500 kPa
0 to 2 MPa
0 to 5 MPa
0 to 10 MPa
Pressure
Proof pressure
3.0 MPa
600 kPa
1.5 MPa
5.0 MPa
12.5 MPa
30 MPa
Power supply voltage
12 to 24 VDC ±10% with 10% voltage ripple or less
10 mA or less
Electrical Current consumption
Protection
Reverse connection protection
Analog output accuracy (Ambient temperature at 25°C)
±1.0% F.S.
±2.5% F.S.
Linearity
±0.5% F.S.
Accuracy Repeatability (Ambient temperature at 25°C)
±0.2% F.S.
±0.5% F.S.
Temperature characteristics ±2%F.S. (0 to 50°C)
±3% F.S. (0 to 50°C)
±5% F.S. (−10 to 60°C)
(25°C reference)
±4% F.S. (−10 to 60°C)
±3%F.S. (−10 to 60°C)
Enclosure
IP65
Withstand voltage
500 VAC for 1 minute between terminals and housing
100 MΩ or more (500 VDC measured via megohmmeter) between terminals and housing
Environment Insulation resistance
Operating temperature range
Operating: −10 to 60°C, Stored: −20 to 70°C (No freezing or condensation)
Operating humidity range
Operating/Stored: 35 to 85% RH (No condensation)
Standards
CE, RoHS
Materials of parts
Piping port: C3604 + Nickel plating,
Piping port: C3604 + Nickel plating,
Pressure sensor: Al2O3 (Alumina 96%), O-ring: FKM + Grease Pressure sensor: Al2O3 (Alumina 96%), Square ring: FKM
in contact with fluid
Fluid
Model
Output
Analog
output
Impedance
PSE57-
PSE57--28
Voltage output: 1 to 5 V
Current output: 4 to 20 mA
Maximum load impedance: 500 Ω or less (at 24 VDC)
100 Ω or less (at 12 VDC)
Output impedance: Approx. 1 kΩ
Piping Specifications
Part no.
Port size
Materials of parts
in contact with fluid
Weight
3
Without lead wire
and M12 connector
With lead wire
and M12 connector
Cable Specifications
PSE570/573/574-01 PSE570/573/574-02
PSE575/576/577-02
R1/8
R1/4
M5 x 0.8
M5 x 0.8
Piping port: C3604 + Nickel plating
Pressure sensor: Al2O3 (Alumina 96%)
O-ring: FKM + Grease
R1/4
M5 x 0.8
Piping port: C3604 + Nickel plating
Pressure sensor: Al2O3 (Alumina 96%)
Square ring: FKM
88 g
95 g
103 g
175 g
182 g
191 g
Nominal cross section
AWG23
Outside diameter
0.72 mm
Material
Cross-linked vinyl chloride
Insulator Outside diameter
1.14 mm
Color
Brown, Blue, Black, White
Sheath Material
Oil resistant vinyl chloride
Finished O.D.
ø4
Length
3m
Conductor
Pressure Sensor for General Fluids
PSE57 Series
Internal Circuits and Wiring Examples
PSE57--28
N.C.∗1
1 kΩ
Black OUT
(Voltage output)
Blue DC (–)
+
–
Load
Main circuit
Voltage output type
1 to 5 V
Output impedance
Approx. 1 kΩ
Brown DC (+)
Current output type
4 to 20 mA
Allowable load impedance
500 Ω or less (at 24 VDC)
100 Ω or less (at 12 VDC)
12
to
24 VDC
N.C.∗1
12
to
24 VDC
+
Black OUT (Current output) –
Load
Brown DC (+)
Main circuit
PSE57-
Blue DC (−)
*1 The unconnected terminals are used in SMC, so please do not connect them.
Analog Output
1 to 5 VDC
4 to 20 mA DC
Analog output [mA]
Analog output [V]
5
1
A
20
Model
PSE570
PSE573
PSE574
PSE575
PSE576
PSE577
4
A
B Pressure
Rated pressure range
0 to 1 MPa
−100 to 100 kPa
0 to 500 kPa
0 to 2 MPa
0 to 5 MPa
0 to 10 MPa
A
B
0 MPa
−100 kPa
0 kPa
0 MPa
0 MPa
0 MPa
1 MPa
100 kPa
500 kPa
2 MPa
5 MPa
10 MPa
B Pressure
Dimensions
A
24
C
10.5
M12
B
23.8
[mm]
Part no.
PSE570/573/574-01
PSE570/573/574-02
PSE575/576/577-02
M5 x 0.8 thread depth 4
A
B
C
8
12
12
R1/8
R1/4
R1/4
36.5
36.5
39.7
Lead wire and M12 connector
ZS-37-A
3000
(38.6)
45
Brown
1: Brown
30
ø15
White
Blue
4: Black
Black
2: White
3: Blue
M12
ZS-37-B
Pin no.
1
2
3
4
(31)
3000
23.5
45
ø15
(30.8)
24.55
30
3: Blue
2: White
Lead wire color Description
Brown
DC (+)
White
N.C.*1
Blue
DC (−)
Black
OUT1
*1 T he unconnected terminals
are used in SMC, so please
do not connect them.
4: Black
Part no.
1: Brown
ZS-37-A
ZS-37-B
M12
Description
Straight type 3 m
Right angle type 3 m
Adapter with restrictor
ZS-31-X
[mm]
D
H
ø1
I
E
Part no.
G
M5 x 0.8
F
ZS-31-X188
ZS-31-X175
D
E
F
G
H
I
20
29
9
13
R1/8
R1/4
Rc1/8
Rc1/4
14
17
1.5
1.6
* If it is expected that the pressure, such as the water hammer or
surge pressure will fluctuate rapidly, refer to the Precautions in the
Operation Manual on the SMC website (http://www.smcworld.com).
4
Sensor Monitor
3-Screen Display
PSE300AC Series
RoHS
How to Order
PSE3 0 0AC AB M
Input specification
0
1
Voltage input
Current input
Output specification
Option (Power supply/output lead wire)
AB 2 output type (NPN or PNP switching type)
Nil
L
N
Options/Part Nos.
Description
Power
supply/
output
lead wire
Assembly type
connector
Part no.
Note
ZS-31-B
Straight (5 m) 1 pc.
ZS-31-C
Right angle (5 m) 1 pc.
PCA-1557743
1 pc.
Specifications
Straight lead wire
Right angle lead wire
None
Unit specification
Nil
M
P
With unit selection function*1
SI unit only*2
With unit selection function (Initial value psi)*1
*1 U
nder the new Measurement Act, sales of switches with the
unit selection function have not been allowed for use in Japan.
*2 Fixed unit: Pa, kPa, MPa
For pressure switch precautions and specific product precautions,
refer to the “Operation Manual” on the SMC website.
M12 Connector Type
Series
PSE300AC
PSE564
PSE531/PSE541 PSE533/PSE543
PSE530/PSE540
Applicable SMC pressure sensor
PSE550
PSE532
PSE575
PSE576
PSE577
PSE574
PSE561
PSE563/PSE573
PSE560/PSE570
Rated pressure range
0 to 2 kPa 0 to −101 kPa −100 to 100 kPa 0 to 100 kPa 0 to 500 kPa 0 to 1 MPa 0 to 2 MPa 0 to 5 MPa 0 to 10 MPa
Display/Set pressure range −0.2 to 2.1 kPa 10 to −105 kPa −105 to 105 kPa −10 to 105 kPa −50 to 525 kPa −0.105 to 1.05 MPa −0.105 to 2.1 MPa −0.1 to 5.25 MPa −0.1 to 10.5 MPa
Display/Smallest settable increment 0.001 kPa
0.1 kPa
0.1 kPa
0.1 kPa
1 kPa
0.001 MPa 0.001 MPa
0.01 MPa
0.01 MPa
Power supply voltage
12 to 24 VDC (±10%) with 10% voltage ripple or less
Electrical Current consumption
25 mA or less
Protection
Reverse connection protection
Display accuracy
±0.5% F.S. ±Min. display unit (Ambient temperature at 25°C)
Accuracy Repeatability
±0.1% F.S. ±Min. display unit (Ambient temperature at 25°C)
Temperature characteristics
±0.5% F.S. (Ambient temperature of 0 to 50°C, 25°C reference)
Output type
Select from NPN or PNP open collector output.
Output mode
Select from hysteresis mode, window comparator mode, error output or switch output OFF.
Switch operation
Select from normal output or reverse output.
Max. load current
20 mA
Switch
Max. applied voltage (NPN only)
30 VDC
output
Internal voltage drop (Residual voltage)
1 V or less (with load current of 20 mA)
Delay time *1
1 ms or less (with anti-chattering function: 20, 100, 500, 1000, 2000, 5000 ms)
Hysteresis
Variable from 0*2
Protection
Over current protection
Input type
Voltage input: 1 to 5 VDC (Input impedance: 1 MΩ), Current input: 4 to 20 mA DC (Input impedance: 51 Ω)
Number of inputs
1 input
Sensor
input
Connection method
M12-4 pin connector
Protection
Over voltage protection (up to a voltage of 26.4 VDC)
Unit *3
MPa, kPa, Pa, kgf/cm2, bar, mbar, psi, inHg, mmHg, mmH2O
Display type
LCD
Number of screens
3-screen display (Main screen, Sub screen x 2)
Display
Display color
1) Main screen: Red/Green, 2) Sub screen: Orange
Number of display digits
1) Main screen: 4-digit (7-segment), 2) Sub screen: 4-digit (Upper 1-digit 11-segment, 7-segment for other)
Indicator light
Lights up when switch output is turned ON. OUT1/OUT2: Orange
Digital filter *4
0, 10, 50, 100, 500, 1000, 5000 ms
Enclosure
IP65
Withstand voltage
1000 VAC for 1 minute between terminals and housing
Environment Insulation resistance
50 MΩ or more (500 VDC measured via megohmmeter) between terminals and housing
Operating temperature range
Operating: 0 to 50°C, Stored: −10 to 60°C (No freezing or condensation)
Operating humidity range
Operating/Stored: 35 to 85% RH (No condensation)
Standards
CE, RoHS
Weight
55.4 g (without power supply or output lead wires)
*1 Value without digital filter (at 0 ms)
*2 If the applied pressure fluctuates around the set value, the hysteresis must be
set to a value more than the amount of fluctuation, or chattering will occur.
5
*3 T
his setting is only available for models with the unit selection function.
Only MPa, kPa or Pa is available for models without this function.
*4 T
he response time indicates when the set value is 90% in relation to the step input.
3-Screen Display
Sensor Monitor
PSE300AC Series
Internal Circuits and Wiring Examples
qDC (+)
qLINE (+)
Load
12
to
24 VDC
12
to
24 VDC
Brown DC (+) q
rLINE (–)
Black OUT1 r
White OUT2 w
Blue DC (–) e
Blue DC (–) e
Load
+
–
Sensor
Load
Load
Main circuit
Sensor
White OUT2 w
Blue DC (–) e
+
–
Setting of PNP open collector 2 outputs: Pressure sensor 2-wire type
Brown DC (+) q
Black OUT1 r
White OUT2 w
Load
Setting of NPN open collector 2 outputs: Pressure sensor 2-wire type
rLINE (–)
Black OUT1 r
eDC (–)
Blue DC (–) e
qLINE (+)
rAnalog
input
Main circuit
eDC (–)
12
to
24 VDC
Brown DC (+) q
Main circuit
White OUT2 w
+
–
Sensor
Load
Black OUT1 r
Load
rAnalog
input
Setting of PNP open collector 2 outputs: Pressure sensor 3-wire type
Brown DC (+) q
Main circuit
Sensor
qDC (+)
Load
Setting of NPN open collector 2 outputs: Pressure sensor 3-wire type
+
–
12
to
24 VDC
* The output type can be changed in the function selection mode.
* Numbers in the figures show the connector pin layout.
Dimensions
Power supply/output connector pin no.
3
30
18
10
1.5
2
4
9
ø4.5
For power supply/output lead wire
Mounting hole
2 locations
30
5
ø8
1
Description
DC (+)
N.C.
DC (–)
Sensor input
(1 to 5 V, 4 to 20 mA)
N.C.
80
5
3
Pin no.
1
2
3
21.5
28
Sensor connector pin no.
4
29
34
29
21.5
6.6
6
2
(41)
(33)
Description
DC (+)
OUT2
DC (–)
OUT1
ø4.5
1
Pin no.
1
2
3
4
ø8
4
Power supply/output lead wire
Brown
White
5000
(38.6)
45
1: Brown
30
ø15
ZS-31-B
Blue
4: Black
Black
2: White
3: Blue
M12
ZS-31-C
5000
Brown
White
45
Pin no.
1
2
3
4
(31)
23.5
30
Part no.
ZS-31-B
ZS-31-C
Description
Straight type 5 m
Right angle type 5 m
24.55
Black
ø15
(30.8)
Blue
3: Blue
2: White
Lead wire color Description
Brown
DC (+)
White
OUT2
Blue
DC (–)
Black
OUT1
4: Black
1: Brown
M12
6
PSE300AC Series
Function Details
A Auto-preset function (F4)
Auto-preset function, when selected in the initial setting, calculates and stores the set value from the measured pressure. For example, if this function is
used for suction verification, the optimum set value is determined automatically by repeating vacuum and break with the target workpiece several times.
Suction Verification
High
Vacuum
Suction
Workpiece 1
Max. A
P_1
Workpiece 2
Workpiece n
H_1
n _1
Formula for Obtaining the Set Value
Min. B
P_1 or P_2
P_1 (P_2) = A – (A-B)/4
n_1 (n_2) = B + (A-B)/4
Released
Atmosphere
Workpiece 1
Workpiece 2
Workpiece n
H_1 or H_2
H_1 (H_2) = (A-B)/2
Indicated value of pressure
B Display value fine adjustment function (F6)
Fine adjustment of the indicated value of the
pressure sensor can be made within the range of
±5% of the read value. (The scattering of the
indicated value can be eliminated.)
±5% R.D.
0
+
Applied pressure
Indicated value at the time of
shipment
Adjustable range of display
value fine adjustment function
Note) When the display value fine
adjustment function is used,
the set pressure value may
change ±1 digit.
C Peak/Bottom value indication function
This function constantly detects and updates the maximum
(minimum) pressure when the power is supplied, and allows to hold
the maximum (minimum) pressure value.
The held value is maintained even if the power supply is cut.
buttons are simultaneously pressed for 1 second
When the
or longer, while “holding”, the held value will be reset.
D Keylock function
Prevents operation errors such as accidentally changing setting values.
E Zero-clear function
This function clears and resets the zero value on the display of measured pressure.
The indicated value can be adjusted within ±7% F.S. of the pressure when ex-factory. (±3.5% F.S. for compound pressure)
F Error indication function
This function is to display error location and content when a problem or error has occurred.
Error name
Error code
Description
Action
Over current
error
Load current of 20 mA or more is applied to the switch output.
Turn the power off and remove the
cause of the over current. Then
supply the power again.
Residual
pressure error
During zero-clear operation, pressure over ±7% F.S. (±3.5% F.S. for compound pressure) is
present. Note that the mode is returned to measurement mode automatically 1 second later.
The zero clear range varies by ±1% F.S. due to variation between individual products.
Perform zero-clear operation again
after restoring the applied pressure to
an atmospheric pressure condition.
Applied
pressure error
System error
Supply pressure exceeds the maximum set pressure.
Supply pressure is below the minimum set pressure.
Internal data error
Reset applied pressure to a level
within the set pressure range.
Turn off the power supply and then
turn on it again. If the failure cannot
be solved, please contact SMC for
investigation.
If the error cannot be reset after the above measures are taken, or errors other than above are displayed, please contact SMC.
7
3-Screen Display
Sensor Monitor
PSE300AC Series
Function Details
G Anti-chattering function (Simple setting mode or F1)
A large bore cylinder or ejector consumes a large volume of air in operation and may experience a temporary drop in the supply pressure.
This function prevents detection of such temporary drops in the supply pressure as an error by changing the delay time setting.
Available delay time settings
1 ms or less, 20 ms, 100 ms, 500 ms, 1000 ms, 2000 ms, 5000 ms
<Principle>
This function averages pressure values measured during the response time set by the user and then
compares the average pressure value with the pressure set point value to output the result on the switch.
Momentary change
Pressure ↑
Set value P_1
H_1
Switch output ON
operation in OFF
normal conditions
Switch output
operation when ON
anti-chattering OFF
function is on.
Time →
t (ms)
t (ms)
<Delay time>
<Delay time>
Time →
Time →
H Unit selection function (F0)
Display units can be switched with this function.
Applicable SMC pressure sensor
Display unit
Smallest settable increment
PSE550
PSE531
PSE541
PSE561
Rated pressure
range
0 to 2 kPa
MPa*1
kPa
0.001
0 to −101 kPa
0.001
−100 to 100 kPa
kgf/cm2
bar
0.1
0.001
0.001
0.1
0 to 100 kPa
0.001
0 to 500 kPa
PSE530
PSE540
PSE560
PSE570
PSE575
PSE576
PSE577
PSE533
PSE543
PSE563
PSE573
PSE532
PSE564
PSE574
Pa
1
mbar
0.01
psi
0.001
inHg
mmHg
0.001
0.01
0.1
1
0.001
0.001
0.02
0.1
1
0.1
0.001
0.001
0.01
0.001
1
0.01
0.01
0.1
0 to 1 MPa
0.001
1
0.01
0.01
0.1
0 to 2 MPa
0 to 5 MPa
0 to 10 MPa
0.001
0.01
0.01
1
0.01
0.1
0.1
0.01
0.1
0.1
0.2
1
1
mmH2O
0.1
*1 The PSE51 (vacuum pressure), PSE52 (low pressure), and PSE53 (compound pressure) will have different setting and display resolution when the unit is set to MPa.
I Power saving mode (F80)
Power saving mode can be selected.
It shifts to the power saving mode without button operation for 30 seconds.
It is set to the normal mode (Power saving mode is OFF.) when ex-factory.
(During power saving mode, [ECo] will flash in the sub screen and the operation light is ON (only when the switch is ON).)
J Setting of secret code (F81)
Users can select whether a secret code must be entered to release key lock.
At the time of shipment from the factory, it is set such that the secret code is not required.
8
Options / Connection Examples
Power supply/output lead wire
ZS-31-C (Right angle 5 m)
PLC
PSE300AC series
ZS-31-B (Straight 5 m)
To POWER
Lead wire and M12 connector (ZS-37-A/ZS-37-B)
+ PCA-1557743
To SENSOR
Assembly type connector
PCA-1557743
ZS-37-A (Lead wire and M12 connector, Straight 3 m)
+
ZS-37-B
(Lead wire and M12 connector, Right angle 3 m)
PSE57 series
9
Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or
equipment damage. These instructions indicate the level of potential hazard with
the labels of “Caution,” “Warning” or “Danger.” They are all important notes for
safety and must be followed in addition to International Standards (ISO/IEC)∗1),
and other safety regulations.
Caution indicates a hazard with a low level of risk which,
Caution:
if not avoided, could result in minor or moderate injury.
Warning:
Warning indicates a hazard with a medium level of risk which,
if not avoided, could result in death or serious injury.
Danger :
Danger indicates a hazard with a high level of risk which,
∗1) ISO 4414: Pneumatic fluid power – General rules relating to systems.
ISO 4413: Hydraulic fluid power – General rules relating to systems.
IEC 60204-1: Safety of machinery – Electrical equipment of machines.
(Part 1: General requirements)
ISO 10218-1: Manipulating industrial robots – Safety.
etc.
if not avoided, will result in death or serious injury.
Warning
1. The compatibility of the product is the responsibility of the
person who designs the equipment or decides its
specifications.
Since the product specified here is used under various operating conditions,
its compatibility with specific equipment must be decided by the person who
designs the equipment or decides its specifications based on necessary
analysis and test results. The expected performance and safety assurance
of the equipment will be the responsibility of the person who has determined
its compatibility with the product. This person should also continuously
review all specifications of the product referring to its latest catalog
information, with a view to giving due consideration to any possibility of
equipment failure when configuring the equipment.
2. Only personnel with appropriate training should operate
machinery and equipment.
The product specified here may become unsafe if handled incorrectly. The
assembly, operation and maintenance of machines or equipment including
our products must be performed by an operator who is appropriately trained
and experienced.
3. Do not service or attempt to remove product and machinery/
equipment until safety is confirmed.
1. The inspection and maintenance of machinery/equipment should only be
performed after measures to prevent falling or runaway of the driven
objects have been confirmed.
2. When the product is to be removed, confirm that the safety measures as
mentioned above are implemented and the power from any appropriate
source is cut, and read and understand the specific product precautions
of all relevant products carefully.
3. Before machinery/equipment is restarted, take measures to prevent
unexpected operation and malfunction.
4. Contact SMC beforehand and take special consideration of
safety measures if the product is to be used in any of the
following conditions.
1. Conditions and environments outside of the given specifications, or use
outdoors or in a place exposed to direct sunlight.
2. Installation on equipment in conjunction with atomic energy, railways, air
navigation, space, shipping, vehicles, military, medical treatment,
combustion and recreation, or equipment in contact with food and
beverages, emergency stop circuits, clutch and brake circuits in press
applications, safety equipment or other applications unsuitable for the
standard specifications described in the product catalog.
3. An application which could have negative effects on people, property, or
animals requiring special safety analysis.
4. Use in an interlock circuit, which requires the provision of double interlock
for possible failure by using a mechanical protective function, and
periodical checks to confirm proper operation.
Caution
1. The product is provided for use in manufacturing industries.
The product herein described is basically provided for peaceful use in
manufacturing industries.
If considering using the product in other industries, consult SMC beforehand
and exchange specifications or a contract if necessary.
If anything is unclear, contact your nearest sales branch.
Limited warranty and Disclaimer/
Compliance Requirements
The product used is subject to the following “Limited warranty and Disclaimer” and
“Compliance Requirements”.
Read and accept them before using the product.
Limited warranty and Disclaimer
1. The warranty period of the product is 1 year in service or 1.5 years after
the product is delivered, whichever is first.∗2)
Also, the product may have specified durability, running distance or
replacement parts. Please consult your nearest sales branch.
2. For any failure or damage reported within the warranty period which is clearly our
responsibility, a replacement product or necessary parts will be provided.
This limited warranty applies only to our product independently, and not to any
other damage incurred due to the failure of the product.
3. Prior to using SMC products, please read and understand the warranty terms
and disclaimers noted in the specified catalog for the particular products.
∗2) Vacuum pads are excluded from this 1 year warranty.
A vacuum pad is a consumable part, so it is warranted for a year after it is delivered.
Also, even within the warranty period, the wear of a product due to the use of the vacuum pad
or failure due to the deterioration of rubber material are not covered by the limited warranty.
Compliance Requirements
1. The use of SMC products with production equipment for the manufacture of
weapons of mass destruction (WMD) or any other weapon is strictly prohibited.
2. The exports of SMC products or technology from one country to another are
governed by the relevant security laws and regulations of the countries involved
in the transaction. Prior to the shipment of a SMC product to another country,
assure that all local rules governing that export are known and followed.
Caution
SMC products are not intended for use as instruments for legal
metrology.
Measurement instruments that SMC manufactures or sells have not been
qualified by type approval tests relevant to the metrology (measurement) laws
of each country. Therefore, SMC products cannot be used for business or
certification ordained by the metrology (measurement) laws of each country.
Revision history
Edition B ∗ Added DIN rail/Terminal block type and Current input type to the
PSE300 series.
LT
Edition C ∗ Added the pressure sensor for general fluids PSE570 series.