Fenwal Smoke Detectors
Fenwal
Smoke
Detectors
Tough and Reliable
with Great Looks
at a Low Cost
The latest line of Fenwal Smoke Detectors offers exactly what today’s demanding customer is seeking: more
reliability for less money, great aesthetics and significant cost savings in maintenance. Designed and tested
under extreme conditions of heat, cold and humidity, Fenwal Smoke Detectors are UL/ULC Listed and FM,
CSFM & MEA approved. Available in ionization, photoelectric or thermistor heat/photoelectric models, these
Detectors are ideally suited to all types of commercial, institutional and industrial applications.
ADVANTAGES/BENEFITS
INPLACE SENSITIVITY TESTING
All three Fenwal Smoke Detectors offer inplace sensitivity measurement in % per foot obscuration that
satisfies NFPA 72 and is UL Listed
• Faster and more economical way to test detector readiness
LOW PROFILE STYLING
Fenwal Smoke Detectors reflect the latest in surface mount design technology, combining functional performance with sleek styling
• Aesthetically pleasing and unobtrusive smoke detection
REMOTE TEST CAPABILITY
An optional Remote Test Switch enables fast, easy testing of detectors located in hard-to-reach spots (ducts,
high ceilings, etc.)
• Reduced maintenance costs
BACKWARD COMPATIBILITY
The latest Fenwal Smoke Detectors are mechanically and electrically backward compatible with previous
series Fenwal bases without rewiring and can even be mixed and matched on the same initiating loop
• Easy retrofitting or system expansion
WIDE RANGE OF OPERATING VOLTAGES
Fenwal Smoke Detectors have the ability to accept a wide range of voltage–from 10.2 to 36.8 Vdc, when
using the 2WB base
• More versatile application
CHOICE OF DETECTION METHODS
Select the precise detection method–ionization, photoelectric or photoelectric/thermistor combination–that’s
right for each application
• Superior smoke detection matched to the application
COST EFFECTIVE DETECTION
Fenwal Smoke Detectors incorporate customer-pleasing features and economical maintenance at very affordable cost, in the present and future.
• Easy to specify today, easy to own tomorrow
PROVEN FENWAL QUALITY
There’s only one brand of smoke detector that has a better than 20-year record for continuous product improvement, on-the-job reliability and superior customer service
• Assure the most value... specify Fenwal Smoke Detectors
B
A
C
D
ION IZAT ION
MOD E L C P D -7051
P H OT OE L E C T R IC
MOD E L P S D -7155
P H OT O W/H E AT
MOD E L P S D -7156
1.38" (35 mm)
1.38" (35 mm)
1.89" (48 mm)
A - Detector Height
B - Base Height
0.43" (11 mm)
0.43" (11 mm)
0.43" (11 mm)
C - Detector Diameter
3.90" (99 mm)
3.90" (99mm)
3.90" (99 mm)
D - Base Diameter
5.90" (150 mm)
5.90" (150 mm)
5.90" (150 mm)
SPECIFICATIONS
ION IZAT ION
MOD E L C P D -7051
P H OT OE L E C T R IC
MOD E L P S D -7155
P H OT O w /H E AT
MOD E L P S D -7156
Standby Voltage (using 2WB)
10.2 to 36.8 Vdc
10.2 to 36.8 Vdc
10.2 to 36.8 Vdc
Standby Voltage (using 4WRB)
16.8 to 36.8 Vdc
16.8 to 36.8 Vdc
16.8 to 36.8 Vdc
Maximum Ripple
50% of DC input
50% of DC input
50% of DC input
Standby Current
45µA (typical)
100µA peak at 24 Vdc
55µA (typical)
100µA peak at 24 Vdc
55µA (typical)
100µA peak at 24 Vdc
Startup Current
0.1mA max.
0.1mA max.
0.1mA max.
Alarm Current
100mA max.
100mA max.
100mA max.
Alarm Indicator
LED
LED
LED
32oF (0oC) to 100oF (37.8oC)
32oF (0oC) to 100oF (37.8oC)
32oF (0oC) to 100oF (37.8oC)
0 to 93% (non-condensing)
0 to 93% (non-condensing)
0 to 93% (non-condensing)
Reset Voltage
3V (typical) min.
3V (typical) min.
3V (typical) min.
Reset Time
1.0 second max.
1.0 second max.
1.0 second max.
Startup Time
20 seconds max.
20 seconds max.
20 seconds max.
5.5V (typical)
5.5V (typical)
5.5V (typical)
High impact plastic, off white
High impact plastic, off white
High impact plastic, off white
UL (268, 268A),
FM, ULC, CSFM, MEA
UL (268, 268A),
FM, ULC, CSFM, MEA
UL (268, 268A),
FM, ULC, CSFM, MEA
0.75 - 1.75%/ft.
1.47 - 3.75%/ft.
1.47 - 3.75%/ft.
I51FE1
P55FE1
P56FE1
Operating Temperature Range
Relative Humidity Range
Alarm Voltage
Finish
Approvals
UL Sensitivity
Compatibility ID
ACCESSORY ITEMS
•
Model ST-001 Smoke Detector Sensitivity Tester for performing “inplace” sensitivity testing and measurement.
•
Model DH-60 and DH-60(2W) Duct Detectors for use in air
handling duct applications to sample air and detect smoke
particles. DH-60 provides 2 auxiliary contacts for shutdowns.
Operates on 24 Vdc, 24 Vac, 120 Vac, and 240 Vac. The DH60(2W) works only in conjunction with a 24 Vdc fire alarm
control panel.
•
Test Magnet
•
RA-911 Remote Alarm Indicator
ST-001 Sensitivity Tester & DH-60 Duct Detector
R
Protection Systems
LICO Electronics GmbH,
400 A-2320 Kledering
TEL: +43 1 706 43 000 FAX: +43 1 706 41 31
http://www.mess-regeltechnik.at
office@lico.at , h.miksch@lico.at
This literature is provided for informational purposes only. KIDE-FENWAL,INC. assumes no responsibility for the product's suitability for a particular application. The product must be properly
applied to work correctly.
If you need more information on this product, or if you have a particular problem or question, contact
81-20(5)lephon: Te 0172. MAshland, INC.KDE-FWAL
KF0020
8/02
©2002 Kide-Fenwal, Inc.
U.S A in Pr ted
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising