CIB – Module of IR Interface, light sensor C-RI

CIB – Module of IR Interface, light sensor C-RI
CIB – Module of IR Interface, light sensor
Type
DI
C-RI-0401S
DO
See AI
Basic features
• Module is combined module with primary function of receiver and transmitter of IR commands.
• Module can learn IR commands of remote controllers of different devices – air-conditioning unit, audio/video devices
etc. and store them in module memory. Subsequently, these
commands can be reproduced by module transmitter on the
base of signal from system.
• This is the way how to replace manual control by Foxtrot
system.
• Module contains input for the light sensor.
• Module contains 2 universal AI/DI inputs for temperature
sensors or potential-free contacts.
• These inputs can operate also as double balanced inputs for
connection of security sensors.
• Status is indicated by LED on module.
AI
2 AI/DI, 1 × light
sensor
AO
Comm
CIB, IR
Connection
• Module is connected to two-wire CIB bus that provides both
communication and power supply of module.
• Module is designed mostly for assembly into standard
installation boxes in the wall or under device cover.
• Inputs, outputs and CIB bus are connected by stranded wires
with sleeves.
• Module can be individually customized and built-in into the
covers of wall switch design under the code C-RI-0401R-Design. Standard design is Time by ABB.
C-RI-0401S
Use
• Integration of infra red remote controlled devices. For
example:
• Interior air-condition units
• audio, video
• consumer electronics with IR control
• Measurement of light in interiors.
• Light intensity control in interiors.
• Specific sequence of actions can be defined in the system to
expand the basic features of the original IR remote controller.
Connection example
Variant:
C-RI-0401R-Design
IR receiver
Analog/digital inputs
Number of receivers
Galvanic isolation
Power supply
of receiver-demodulator
Pilot frequency of demodulator
1
No
No. of inputs
Galvanic isolation
Resolution
3.3 V
2
No
12 bit
36 kHz
IR transmitter
Measurement ranges
Number of transmitters
Galvanic isolation
IR transmitter type
1
No
IR LED (IFmax =100 mA) + resistor
according IF
Power supply of transmitter 3.3 V
Short-circuit protection
No
Input for light sensor
Number of inputs
Galvanic isolation
Sensor type/range/input error
1
No
photodiode,
0 – 50 000lx/<5%
Operating conditions
Operating temperature
Storage temperature
Electric strength
IP Degree of protection(IEC 529)
Overvoltage category
Degree of pollution
IEC EN60664-1:2008
Working position
Installation
Connection of CIB, AI/DI
Sensor type
Potential-free contact
Balanced input
(security system)
Pt1000
Ni1000
NTC 12k
KTY 81-121
Resistance
Analog input error
Range
on/off
broken link/0/1/
tamper
–90 .. 320 °C
–60 .. 200 °C
–40 .. 125 °C
–55 .. 125 °C
0 – 160 kΩ
<2%
Dimensions and weight
–20 .. +55 °C
–25 .. +70 °C
according EN 60730
IP 10B
II
1
any
into installation box, under cover
Wires 0.5 mm2. grouped on 2
connenctors inserted into module
Dimensionsy
Weight
55 × 32 × 13 mm
8 g
Power supply
Power supply and communication
Typical load
Maximal input power
Internal protection
24 V (27 V) from CIB bus
25 mA
0.5 W
No
Order number
TXN 133 47
62
C-RI-0401S; CIB input module for sensors 1 × IR, 1 × lighting, 2 × temperature, 1× output for IR transmitter
www.tecomat.cz | Teco a.s., Havlíčkova 260, 280 02, Kolín 4, Czech Republic | teco@tecomat.cz | www.tecomat.com