SmartPro 120V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, 2U
SmartPro 120V 1.5kVA 1.35kW Line-Interactive Sine
Wave UPS, 2U Rack/Tower, Extended Run,
Pre-installed SNMPWEBCARD, LCD Display, USB,
DB9 Serial
Highlights
1.5kVA / 1500VA / 1350 watt line
interactive 2U rack / tower UPS,
0.9 power factor
120V nominal output during
brownouts to 83V and
MODEL NUMBER: SMART1500RMXLN
overvoltages to 145V
Interactive LCD provides UPS
status information and advanced
configuration options
USB, RS232, EPO and
Pre-installed SNMPWEBCARD
interface
Expandable runtime, Hot-swap
batteries, 95% efficiency, Sine
wave output
2 independently switchable
output load banks
NEMA 5-15P input, 8 NEMA
5-15R outlets
Description
Applications
Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade power protection for
Distributed Server Rooms
critical server, network and telecommunications equipment. Line Interactive Uninterruptible Power Supply (UPS)
Network Closets
with built-in Auto-Voltage Regulation (AVR) actively corrects brownouts and overvoltages back to usable levels
Small Business Networks
while maintaining a full battery charge in case of power failure. Tripp Lite's unique configuration excels in
Voice over IP (VoIP) Phone
exceptionally poor-power environments with two separate levels of voltage boost to correct both slight
Systems
undervoltages and severe brownout conditions. Interactive LCD interface reports UPS operating mode, detailed
UPS and site-power data, plus enables a variety of UPS setup and configuration options. Super-fast switchover
Package Includes
from line to battery power occurs within milliseconds to maintain operation of connected equipment without
SMART1500RMXLN UPS
interruption or reboot. 95% line-mode efficiency offers reduced heat emissions and operating costs. Network
system with Pre-installed
management interfaces support communications via USB, RS-232 and Pre-installed SNMPWEBCARD network
SNMPWEBCARD
interface. HID-compliant USB port enables integration with built-in power management and auto shutdown
PowerAlert software with USB,
features of Windows and Mac OS X. Network communications ports enable detailed monitoring of equipment
Serial & EPO cabling
load levels, self-test data and utility power conditions. Includes PowerAlert monitoring software and complete
4 post installation kit
cabling. Switched output load banks enable scheduled and real-time remote reboot and load shedding of select
Owner's manual
outlets. Emergency Power Off (EPO) interface. LCD display panel easily rotates for viewing in rackmount or
tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode configuration options. Programmable self-test.
Field-replaceable, hot-swappable battery modules.
Features
Tripp Lite SMART1500RMXLN line interactive 2U rack/tower UPS with 1500VA / 1.5kVA / 1350W capacity and extended runtime options
Line interactive UPS with Automatic Voltage Regulation (AVR) corrects brownouts and overvoltages from 83 to 145V
NEMA 5-15P input plug; 8 NEMA 5-15R output receptacles, Two independently switched output load banks
Maintains uninterrupted operation of connected networking equipment during blackouts, surges, brownouts and overvoltages
1/5
High 95% efficiency rating in line-power mode offers reduced power consumption and BTU emisssions
Internal batteries offer 14 minutes at 50% load (675W) and 4.9 minutes at 100% load (1350W)
Extended runtime is available with optional BP36V15-2U (limit 1); BP36V42-3U (multi-pack compatible) and BP36V27-2US (multi-pack compatible),
Output is reduced to 1200 watts maximum with external battery packs
External battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Hot-swappable, user-replaceable internal batteries and external battery packs can be replaced with no disruption to connected equipment
Front panel LCD monitoring screen with MODE and ENTER buttons reports operating mode with 5-bar battery charge graphic, plus 7 selectable screens
of detailed UPS and site power information
LCD interface also supports a number of advanced user setup and operating preferences
Ships with 4 post rackmount installation hardware; Optional 2POSTRMKITWM enables 2 post rackmount/wallmount installation; Optional 2-9USTAND
enables tower placement
Built-in USB, RS-232 and Pre-installed SNMPWEBCARD accessory monitoring options
HID-compliant USB port enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software; Built-in Emergency Power Off (EPO) interface with cable
Specifications
OUTPUT
Output Capacity Details
Output derates to 1200 watts in all external battery configurations
Output Volt Amp Capacity (VA)
1500
Output kVA Capacity (kVA)
1.5
Output Watt Capacity (Watts)
1350
Output kW Capacity (kW)
1.35
Power Factor
0.9
Nominal Output Voltage(s)
Supported
120V
Frequency Compatibility
60 Hz
Output Voltage Regulation (Line
Mode)
-14%, +6%
Output Voltage Regulation (Battery
Mode)
+/- 5%
Output Receptacles
(8) 5-15R
Load Management Receptacles
Two switchable two-outlet 5-15R load banks
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery Mode)
Pure Sine wave
INPUT
Rated input current (Maximum Load)
12A
Nominal Input Voltage(s) Supported
120V AC
UPS Input Connection Type
5-15P
2/5
Input Circuit Breakers
15A
UPS Input Cord Length (ft.)
10
UPS Input Cord Length (m)
3
Recommended Electrical Service
15A 120V
Input Phase
Single-Phase
BATTERY
Full Load Runtime (min.)
4.9 min. (1350w)
Half Load Runtime (min.)
14 min. (675w)
Expandable Battery Runtime
Extended runtime supported via optional external battery packs
External Battery Pack Compatibility
BP36V15-2U (limit 1); BP36V42-3U (multi-pack compatible); BP36V27-2US (multi-pack compatible)
DC System Voltage (VDC)
36
Battery Recharge Rate (Included
Batteries)
Less than 4.5 hours from 10% to 90% (typical, full load discharge)
Internal UPS Replacement Battery
Cartridge
RBC93-2U
Battery Access
Front panel battery access door
Battery Replacement Description
Hot-swappable, user replaceable batteries
Expandable Runtime
Yes
VOLTAGE REGULATION
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage Correction
Input voltages between 127 and 145 are reduced by 12%
Undervoltage Correction
Input voltages between 95 and 108 are boosted by 12%
Severe Undervoltage Correction
Input voltages between 83 and 94 are boosted by 24%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating
data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual
for detailed LCD configuration and monitoring options)
Switches
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Alarm Cancel Operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Audible Alarm
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
570
UPS AC Suppression Response
Time
Instantaneous
3/5
EMI / RFI AC Noise Suppression
Yes
PHYSICAL
Included Mounting Accessory
Description
4 post rackmount installation accessories included
Installation Form Factors Supported
with Optional Accessories
2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND); 2-4 post front rail
rackmount (UPSHDEARKIT)
Primary Form Factor
Rackmount
UPS Power Module Dimensions
(hwd, in.)
3.45 x 17.3 x 13.45
UPS Power Module Dimensions
(hwd, cm)
8.8 x 43.9 x 34.2
Rack Height (U Spaces)
2
UPS Power Module Weight (lbs.)
46.5
UPS Power Module Weight (kg)
21.1
UPS Shipping Dimensions (hwd / in.)
8.5 x 23.4 x 19.9
UPS Shipping Dimensions (hwd /
cm)
21.6 x 59.4 x 50.5
Shipping Weight (lbs.)
51.3
Shipping Weight (kg)
23.3
Cooling Method
Fan
UPS Housing Material
Steel
ENVIRONMENTAL
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
237
AC Mode Efficiency Rating (100%
Load)
95%
COMMUNICATIONS
Communications Interface
DB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface; USB
Network Monitoring Port Description
Includes Pre-installed SNMPWEBCARD network interface. Supports detailed monitoring of UPS and site power
conditions
PowerAlert Software
Included
Communications Cable
USB and DB9 cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network UPS Tools Compatibility
NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at
http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite
4/5
LINE / BATTERY TRANSFER
Transfer Time
4 milliseconds (AC to battery mode), 1 millisecond (Battery to AC mode)
Low Voltage Transfer to Battery
Power (Setpoint)
83
High Voltage Transfer to Battery
Power (Setpoint)
145
SPECIAL FEATURES
Grounding Lug
Back panel grounding lug
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Hot swappable batteries
Green Energy-Saving Features
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category B
(EMI); ROHS (Restriction of Hazardous Substances)
WARRANTY
Product Warranty Period (Worldwide)
2-year warranty, 3 year with registration. Note: Registration is required for 3-year warranty.
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$250,000 Ultimate Lifetime Insurance
© 2015 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies:
http://www.tripplite.com/products/product-certification-agencies
5/5