SPECIFICATION DATA Protect•IR Multispectrum IR Flame Detector

SPECIFICATION DATA Protect•IR Multispectrum IR Flame Detector
SPECIFICATION DATA
Protect•IR
Multispectrum IR Flame Detector
X3302
DESCRIPTION
Y
E
A
5
R
The X3302 brings state-of-the-art IR flame detection
to the difficult task of detecting invisible hydrogen
flames.
Focusing on the water-band IR emissions of
hydrogen flame, the X3302 overcomes the limited
detection range and false alarm tendencies of other
flame detectors by employing field proven multispectrum infrared
(MIR) technology. The result is unsurpassed flame sensitivity with
discrimination of non-flame sources in situations where traditional
flame detectors are unsuitable.
WARRANTY
Utilizing the X3301’s multi-patented* signal processing algorithms,
the X3302 provides a breakthrough in flame detection/surveillance
of hazardous materials that produce mostly water vapor, and little or
no CO2 in the combustion process. The detection capability of the
X3302 is double that of traditional UV and UVIR detectors. At the
same time, it attains complete solar resistance and insensitivity to
artificial lights, lightning, and “blackbody” radiation, which still plague
other detection technologies.
The X3302 provides superior performance in applications that are at the
extremes, and where background IR radiation is a normal condition:
— Hangars with hydrogen or hypergolic fueled vehicles
— Refineries hydrogen storage areas
— Chemical loading racks
— Hydrogen compressor areas
— Hydrogen cooled generators
— Fertilizer plants
— Silane storage
— Gas plants
— Refrigerator buildings
1.3
© Detector Electronics Corporation 2006
F E AT U R E S A N D B E N E F I T S
Protect•IR TECHNOLOGY FEATURES
• ATEX Compliant.
• Certified performance
• Extended detection range.
• New standard set for cone of vision.
• Maximum false alarm rejection.
• Microprocessor controlled heated optics.
• Calibrated manual/magnetic optical check for each sensor
eliminates need for testing with external test lamp.
• RFI and EMC Directive Compliant.
• Event logging with time and date stamp.
• International certifications.
• Integral wiring compartment for ease of installation.
• Total solar resistance.
BENEFITS
• Lowest cost of coverage.
• Ability to detect smaller fires earlier.
• Better detection zoning capability.
• Best combination of flame detection and false alarm rejection.
• Low maintenance costs.
• Reliable fault diagnostics.
• Suitable for heavy industrial applications.
• Explosion/flame proof or increased safety installations
(EEx de) in hazardous locations.
• Easily retrofitted to controller based systems.
* Multispectrum technology advancements are covered under the
following U.S. Patents: 5,995,008, 5,804,825 and 5,850,182.
8/06
90-1185
S P E C I F I C AT I O N S
Operating Voltage
24 vdc. Operating range is 18 to 32 vdc.
Enclosure Material
Copper-free aluminum or 316 stainless steel.
Power Consumption
4 watts minimum (without heater), 17 watts at 32 vdc
with EOL resistor installed and heater on maximum.
Conduit Entry Size
3/4 inch NPT or 25 mm.
Warranty
5 years, sensor and electronics.
Relays
Contacts rated 5 amperes at 30 vdc.
Shipping Weight
(Approximate)
Aluminum:
Stainless Steel:
Fire Alarm:
Fault:
Auxiliary:
— Form C (NO and NC contacts)
— normally de-energized
— latching/non-latching.
— Form A (NO contacts)
— normally energized
— latching/non-latching.
— Form C (NO and NC contacts)
— normally energized
— latching/non-latching.
Current Output
(Optional)
4–20 mA, with a maximum loop resistance of 500
ohms from 18–19.9 vdc, 600 ohms from 20–32 vdc.
Temperature Range
Operating:
Storage:
6 pounds (2.7 kg).
10 pounds (4.5 kg).
Response
Very High Sensitivity
Fuel
Size/
Flow Rate
Distance
feet (m)
Average Response Time
(seconds)
Hydrogen
24 in. plume/
100 SLPM*
100 (30.5)
2
Methanol
1 x 1 foot
70 (21.3)
2
*Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).
–40°F to +167°F (–40°C to +75°C).
–67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from -55°C to +125°C
available on extended temperature model.
Field of View
Very High Sensitivity
Fuel
Humidity Range
Certification
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
Class I, Div. 1, Groups B, C & D;
Class II, Div. 1, Groups E, F, & G;
Class I, Div. 2, Groups A, B, C & D (T3C);
Class II, Div. 2, Groups F & G (T3C);
Class III.
NEMA/Type 4X.
FM
APPROVED
®
Increased Safety Model
0539
II 2 GD
EEx de IIC T5–T6,
DEMKO 01 ATEX 130204
T6 (Tamb = –55°C to +60°C).
T5 (Tamb = –55°C to +75°C).
IP66.
Size/
Flow Rate
Distance Horiz. Avg. Horiz. Vert. Avg. Vert.
feet
Response
Response
(m)
Time
Time
(seconds)
(seconds)
Hydrogen 24 in. plume/
100 SLPM
100
(30.5)
+45°
–45°
4
3
+45°
–30°
3
3
Methanol
70
(21.3)
+45°
–45°
2
3
+45°
–30°
2
2
1 x 1 ft.
SUPERIOR PERFORMANCE OF X3302
45°
100 ft
X3302 MULTISPECTRUM IR
30°
90 ft
UV TECHNOLOGY
15°
80 ft
0°
70 ft
60 ft
Flameproof Model
0539
II 2 GD
EEx d IIC T4–T6,
DEMKO 01 ATEX 130204
T6 (Tamb = –55°C to +60°C).
T5 (Tamb = –55°C to +75°C).
T4 (Tamb = –55°C to +125°C).
IP66.
RE
RM
FI
T E ED
R
N
26
S
I
E RE D F
A2
REG
I
R EG
ST
IR M
ISO 9001
.
30 ft
30°
20 ft
10 ft
45°
20 ft
40 ft
60 ft
80 ft
100 ft
HORIZONTAL FIELD OF VIEW TO HYDROGEN FIRE
(24 INCH PLUME, WITH 100 SLPM FLOW RATE)
DETECTOR
ON AXIS DISTANCE
IN FEET
OFF AXIS DISTANCE
IN FEET
X3302
100
100
UV TECHNOLOGY
50
25
Detector Electronics Corporation
I
BS
D BY UL AN
ERE
D
IST
G
O
40 ft
14 AWG (2.08 mm2) or 16 AWG (1.31 mm2)
shielded cable is recommended.
Wiring
15°
50 ft
5
305 • N O. 2
8
6901 West 110th Street • Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491 • Fax (952) 829-8750
http://www.det-tronics.com • E-mail: detronics@detronics.com
Specifications subject to change without notice.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising