Measurement of the simplified earth resistance

Measurement of the simplified earth resistance
MODEL
4102A
4102A/4102A-H
Measurement
ranges
Accuracy
Earth resistance : 0 - 12Ω /0 - 120Ω /0 - 1200Ω
Earth voltage[50,60Hz] : 0 - 30V AC
Earth resistance: ±3% of full scale
Earth voltage: ±3% of full scale
Overload protection Earth resistance : 276V AC for 10 seconds
across 2 of the 3 terminals
Earth voltage : 276V AC for 1 minute
Applicable standards IEC 61010-1 CAT Ⅲ 300V Pollution degree 2 IEC 61557-1,5
IEC 60529(IP54)
Power source
R6(AA)(1.5V) × 6
Dimensions
105(L) × 158(W) × 70(D)mm
Weight
600g approx.
Accessories
7095A(Earth resistance test leads) × 1set(red-20m, yellow-10m,
green-5m) 8032(Auxiliary earth spikes[2 spikes/set]) × 1set
7127A(Simplified measurement probe) × 1set
R6(AA) × 6, 9121(Shoulder strap), Instruction manual
Carrying case
: 9084(Carrying case[Soft])
: 9164(Carrying case[Hard])
Optional
7100A(Precision measurement cord set)
MODEL
MODEL
4102A
4102A-H
Soft case model
Hard case model
Measurement of the earth electrode resistance
(3-Pole method)
[MODEL 4102A/KEW 4105A]
The international standard IEC 60364-6 provides information regarding the measurement of the resistance of an
earth electrode for TT, TN and IT systems.
This measurement shall be made by the Volt-Amperometric
method using two auxiliary earth electrodes.
The instrument that covers this requirement is the Earth
Tester.
Precise Measurement (with Test lead M-7095A)
Measurement of the simplified earth resistance
(2-Pole method)
[KEW 4300/MODEL 4102A/KEW 4105A]
Indicated
Value
Be sure to check
earthed side of a
commercial power supply.
Measuring the earth resistance of load
Measuring the earth
resistance of wall socket
Simplified Measurement
(with Test lead M-7127A)
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project