Installation Guide Smart-UPS On-Line SRT001

Installation Guide Smart-UPS On-Line SRT001
Installation Guide Smart-UPS™On-Line
SRT001/SRT004/SRT005/SRT008
Important Safety Information
Read the instructions carefully to become familiar with the equipment before trying to install, operate,
service or maintain it. The following special messages may appear throughout this manual or on the
equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard
exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all
safety messages that follow this symbol to avoid possible injury or death.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or
moderate injury.
CAUTION
CAUTION addresses practices not related to physical injury including certain environmental
hazards, potential damage or loss of data.
Safety and General Information
Inspect the package contents upon receipt. Notify the carrier and dealer if there is
any damage.
Adhere to all local and national electrical codes.
Recycle the packaging.
Deenergizing safety
The UPS contains internal batteries and may present a shock hazard even when disconnected from the
branch circuit (mains). Before installing or servicing the equipment, check that the internal batteries are
removed, that external extended run batteries are disconnected and the branch circuit (mains) is
disconnected.
Hardwire safety
• Verify that all branch circuit (mains) and low voltage (control) circuits are deenergized, and locked out
before installing cables or making connections, whether in the junction box or to the UPS.
• Wiring by a qualified electrician is required.
• Adhere to all national and local codes.
• Select wire size and connectors according to national and local codes.
• Strain relief is required for all hardwiring.
• All openings allowing access to UPS hardwiring terminals must be covered. Failure to do so may
result in personal injury or equipment damage.
Package Contents
The UPS and PDU models may vary in appearance from those depicted in the diagrams. The PDU
installation procedure is similar for SRT001/SRT004/SRT005 models.
SRT001
SRT004
SRT005
1 Output Hardwire Kit
• 4 screws
• 1 PDU
• 4 screws
• 1 PDU
• 4 screws
74a
su08
75a
su08
76a
su08
SRT008
• 1 PDU
• 2 screws
s uo
2
085
7a
Smart-UPS On-Line SRT001/SRT004/SRT005/SRT008
Remove Standard PDU
UPS models SRT5K/SRT6K
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• Adhere to all local and national electrical codes.
• Wiring must be performed by a qualified electrician.
Failure to follow these instructions can result in equipment damage and minor or moderate injury.
Disconnect equipment connected to the UPS.
1. Press the POWER ON /OFF button located on the front of the UPS. Select Turn Off Immediately to turn
the UPS output off.
2. Disconnect all the battery modules.
3. Disconnect all the external battery packs (XLBPs), if installed.
4. Disconnect the UPS from the utility power. Disconnect methods will vary depending on the model.
– Unplug the UPS from the wall receptacle.
– Switch the utility circuit breaker off.
PDU with 4 pin connector in SRT5K/SRT6K models
Remove the ground screw and the standard PDU. Remove the connector clip and disconnect the 4 pin
connector.
s u 08
71d
x1
Ground
screw
x4
Smart-UPS On-Line SRT001/SRT004/SRT005/SRT008
3
PDU with 2 pin connector in SRT5KRMXLW-HW model
Remove the ground screw and the standard PDU. Remove the connector clip and disconnect the 2 pin
connector.
s u 08
72d
x1
Ground
screw
x4
Install PDU
PDU models SRT004/SRT005
SRT004
PDU
SRT004
UPS Models
SRT5KXLT
SRT5KRMXLT
SRT5KXLT-IEC
SRT5KRMXLT-IEC
SRT5KRMXLW-HW
Note: Secure the 2 pin connector from the PDU to the appropriate connector on the UPS. Ignore any
additional connectors on the UPS. Connect the ground cable to the ground screw.
Connect the 2 pin connector and install the connector clip. Install the SRT004 PDU and secure the ground
screw.
s u 08
71b
x1
Ground
screw
x4
4
Smart-UPS On-Line SRT001/SRT004/SRT005/SRT008
SRT005
PDU
SRT005
UPS Models
SRT6KXLT
SRT6KRMXLT
SRT6KXLT-IEC
SRT6KRMXLT-IEC
Note: Secure the 4 pin connector on the PDU to the appropriate connector on the UPS. Ignore any additional
connectors on the UPS. Connect the ground cable to the ground screw.
Connect the 4 pin connector and install the connector clip. Install the SRT005 PDU and secure the ground
screw.
s u0 8
71c
x1
Ground
screw
x4
Smart-UPS On-Line SRT001/SRT004/SRT005/SRT008
5
Install Output Hardwire Kit
Model SRT001
PDU
SRT001
UPS Models
SRT5KXLI
SRT5KRMXLI
SRT5KXLT
SRT5KRMXLT
SRT5KXLT-IEC
SRT5KRMXLT-IEC
Note: Secure the 2 pin connector on the PDU to the appropriate connector on the UPS. Ignore any additional
connectors on the UPS. Connect the ground cable to the ground screw.
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• Verify that all branch circuit (mains) and low voltage (control) circuits are deenergized, and locked out
before installing cables or making connections, whether in the junction box or to the UPS.
• Wiring by a qualified electrician is required.
• Check national and local codes before wiring.
• Strain reliefs are not supplied with the unit. Snap-In type strain reliefs are recommended.
• All openings that allow access to UPS hardwire terminals must be covered.
• Select wire size and connectors according to national and local codes.
• Recommended output terminal screw torque: 1.58 - 1.81 Nm (14-16 lbf-in).
Failure to follow these instructions can result in equipment damage and minor or moderate injury.

Connect the 2 pin connector and install the connector clip. Secure the ground screw.
su08
72c
x1
Ground
screw
6
Smart-UPS On-Line SRT001/SRT004/SRT005/SRT008


Secure the output hardwire kit to the UPS.
s u08
Remove the output hardwire box.
63 a
su 08
7 3a
x2
x4

Connect the output wires.
su08
6 4a

Secure the output panel to the UPS.
s u08
65a
L1
L2/N
x2
Smart-UPS On-Line SRT001/SRT004/SRT005/SRT008
7
Replace Standard PDU
UPS models SRT8K/SRT10K
PDU
UPS Models
SRT008
SRT8KXLT
SRT8KRMXLT
SRT8KXLT-IEC
SRT8KRMXLT-IEC
SRT10KXLT
SRT10KRMXLT
SRT10KXLT-IEC
SRT10KRMXLT-IEC
 Remove the rear access cover. Remove AC wiring box.
 Disconnect the ribbon cable. Disconnect the output
power cable.
x2
86 1a
suo 0
6 2a
suo 08
x5
 Remove the screws that secure the PDU to the UPS.
 Remove the PDU from the UPS.
x2
suo08
8
6 3a
Smart-UPS On-Line SRT001/SRT004/SRT005/SRT008
4a
suo086
 Install SRT008 PDU.
 Connect the output power cable. Connect the ribbon
cable.
x2
suo 08
6 3b
suo 08
6 2b
 Install the rear access cover. Install the AC wiring box.
x2
suo08
61b
x5
Smart-UPS On-Line SRT001/SRT004/SRT005/SRT008
9
Configure UPS for PDU Panel
Reconfigure the UPS, using the display interface, to work with the new PDU.
1. Reconnect internal RBC.
2. Reconnect the XLBP if installed.
3. Reconnect the UPS to utility power. Do not turn on the UPS output.
4. Configure the PDU once the display interface message is visible.
5. Navigate to the User Mode. Change the UPS User Mode to Advance User Mode.
Main Menu > Configuration > Display > User Mode
6. Navigate to the PDU Model to configure the PDU.
Main Menu > Configuration > UPS > PDU Model
7. Select the appropriate PDU from the given options and press OK button.
Note: The Standard PDU option is the factory default.
PDU options in SRT5K UPS
PDU option in SRT6K UPS
PDU Model
PDU Model
SRT001
SRT004
Output Off
PDU option in SRT8K/SRT10K UPS
PDU Model
SRT005
1
2
Output Off
SRT008
1
2
3
Output Off
1
2
3
8. Wait for 10 seconds for the display interface to reboot.
9. Verify that PDU model is updated.
Display Navigation: Main Menu > Configuration > UPS > PDU Model
10. Turn on the UPS output.
Customer support and warranty information is available at the APC Web site, www.apc.com.
© 2014 APC by Schneider Electric. APC, the APC logo and Smart-UPS are owned by Schneider
Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their
respective owners.
EN 990-4610B
8/2014
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising