Catalog KT10.1 2016 - SITOP Power Supply

Catalog KT10.1 2016 - SITOP Power Supply
© Siemens AG 2016
SITOP
Power Supply
SITOP
Catalog
KT 10.1
Edition
2016
siemens.com/sitop
© Siemens AG 2016
Related catalogs
Industrial Controls
SIRIUS
IC 10
PDF (E86060-K1010-A101-A6-7600)
SIMATIC
Products for
Totally Integrated Automation
E86060-K4921-A101-A3-7600
ST 70
SITRAIN
Training for Industry
ITC
Only available in German
E86060-K6850-A101-C5
E86060-K4670-A101-B5-7600
SIMATIC
SIMATIC PCS 7
Process Control System
System components
Motion Control
PM 21
SIMOTION, SINAMICS S120 & SIMOTICS
Equipment for Production Machines
ST PCS 7
Products for Automation and Drives
Interactive Catalog, DVD
E86060-K4678-A111-C3-7600
E86060-D4001-A510-D6-7600
SIMATIC HMI /
ST 80/ST PC
PC-based Automation
Human Machine Interface Systems
PC-based Automation
Industry Mall
Information and Ordering Platform
in the Internet:
E86060-K4680-A101-C3-7600
www.siemens.com/industrymall
CA 01
© Siemens AG 2016
SITOP power supply
SITOP
Introduction
1
SITOP compact
2
LOGO!Power
3
SITOP lite
4
SITOP smart
5
SITOP modular
6
SITOP modular,
PSU8600 power supply system
7
The products contained in this catalog can also be found
in the Interactive Catalog CA 01.
Article No.: E86060-D4001-A510-D6-7600
SITOP in the SIMATIC Design
8
Please contact your local Siemens branch.
Special designs, special uses
9
Catalog KT 10.1 · 2016
Supersedes:
Catalog KT 10.1 · 2015
Refer to the Industry Mall for current updates of
this catalog:
www.siemens.com/industrymall
© Siemens AG 2016
Printed on paper from
sustainably managed forests and
controlled sources.
Add-on modules
10
SITOP DC UPS uninterruptible power supplies
11
Accessories
12
SIPLUS power supplies
13
Power supplies for AS interface
14
Technical information and configuration
15
Appendix
16
www.pefc.org
The products and systems described in
this catalog are manufactured/distributed
under application of a certified quality
management system in accordance with
DIN EN ISO 9001 (Certified Registration
No. 000656 QM08). The certificate is
recognized by all IQNet countries.
© Siemens AG 2016
2
Siemens KT 10.1 · 2016
© Siemens AG 2016
Answers for industry.
Integrated technologies, vertical market expertise and services
for greater productivity, energy efficiency, and flexibility.
Siemens is the world's leading supplier
of innovative and environmentally
friendly products and solutions for
industrial companies. End-to-end
automation technology and industrial
software, solid market expertise, and
technology-based services are the
levers we use to increase our customers’
productivity, efficiency and flexibility.
We consistently rely on integrated technologies and, thanks to our bundled
portfolio, we can respond more quickly
and flexibly to our customers' wishes.
With our globally unmatched range of
automation technology, industrial
control and drive technology as well
as industrial software, we equip companies with exactly what they need over
their entire value chain – from product
design and development to production,
sales and service. Our industrial customers benefit from our comprehensive
portfolio, which is tailored to their
market and their needs.
Market launch times can be reduced
by up to 50% due to the combination
of powerful automation technology
and industrial software. At the same
time, the costs for energy or waste
water for a manufacturing company
can be reduced significantly. In this
way, we increase our customers’
competitive strength and make an
important contribution to environmental protection with our energy-efficient
products and solutions.
Siemens KT 10.1 · 2016
3
© Siemens AG 2016
(53 ²(QWHUSULVH5HVRXUFH3ODQQLQJ
3/0 ²3URGXFW/LIHF\FOH0DQDJHPHQW
0DQDJHPHQW
/HYHO
‡3URGXFW'HVLJQ
‡3URGXFWLRQ3ODQQLQJDQG6LPXODWLRQ
‡'DWD0DQDJHPHQW
0(6²0DQXIDFWXULQJ([HFXWLRQ6\VWHPV
3ODQW(QJLQHHULQJ
6,0$7,&,7
&2026
(WKHUQHW
2SHUDWLRQV
/HYHO
6,0$7,&3&6
2SHUDWRU6\VWHP
0DLQWHQDQFH
$VVHW0DQDJHPHQW
(QHUJ\
0DQDJHPHQW
(QJLQHHULQJ
6WDWLRQ
6,0$7,&:LQ&&
6&$'$6\VWHP
,QGXVWULDO(WKHUQHW
7,$3RUWDO
&RQWURO/HYHO
6,0$7,&3&6
$XWRPDWLRQ
6\VWHP
6,180(5,.
&RPSXWHU1XPHULF&RQWURO
6,027,21
0RWLRQ&RQWURO
6,0$7,&1(7
,QGXVWULDO
&RPPXQLFDWLRQ
6,0$7,&&RQWUROOHU
0RGXODU3&%DVHG
6,0$7,&+0,
+XPDQ0DFKLQH,QWHUIDFH
6,0$7,&'LVWULEXWHG,2
6,1$0,&6'ULYH6\VWHPV
6,5,86,QGXVWULDO&RQWUROV
)LHOG/HYHO
352),%863$
3URFHVV,QVWUXPHQWDWLRQ
7RWDOO\
,QWHJUDWHG
$XWRPDWLRQ
6,0$7,&,GHQW
,QGXVWULDO,GHQWLILFDWLRQ
+$57
/RZ9ROWDJH'LVWULEXWLRQ
,2/LQN
6,027,&60RWRUV
Efficient automation starts with
efficient engineering.
Totally Integrated Automation: Efficiency driving productivity.
Efficient engineering is the first step toward better production that is faster,
more flexible, and more intelligent. With all components interacting efficiently,
Totally Integrated Automation (TIA) delivers enormous time savings right from
the engineering phase. The result is lower costs, faster time-to-market, and
greater flexibility.
4
Siemens KT 10.1 · 2016
6,7233RZHU6XSSO\
© Siemens AG 2016
A unique complete approach for all industries
Totally Integrated Automation
Efficient interoperability of all automation components
As one of the world's leading automation suppliers,
Siemens provides an integrated, comprehensive portfolio
for all requirements in process and manufacturing industries.
All components are mutually compatible and system-tested.
This ensures that they reliably perform their tasks in industrial
use and interact efficiently, and that each automation solution can be implemented with little time and effort based
on standard products. The integration of many separate individual engineering tasks into a single engineering environment, for example, provides enormous time and cost savings.
With its comprehensive technology and industry-specific
expertise, Siemens is continuously driving progress in manufacturing industries – and Totally Integrated Automation plays
a key role.
Totally Integrated Automation creates real value added in
all automation tasks, especially for:
352),1(7
,QGXVWULDO(WKHUQHW
352),%86
$6,QWHUIDFH
.1;*$00$LQVWDEXV
7RWDOO\
,QWHJUDWHG
3RZHU
• Integrated engineering
Consistent, comprehensive engineering throughout the
entire product development and production process
• Industrial data management
Access to all important data occurring in productive
operation – along the entire value chain and across
all levels
• Industrial communication
Integrated communication based on international
cross-vendor standards that are mutually compatible
• Industrial security
Systematic minimization of the risk of an internal or
external attack on plants and networks
• Safety Integrated
Reliable protection of personnel, machinery, and the
environment thanks to seamless integration of safety
technologies into the standard automation
Making things right with Totally Integrated Automation
Totally Integrated Automation, industrial automation from
Siemens, stands for the efficient interoperability of all automation components. The open system architecture covers
the entire production process and is based on end-to-end
shared characteristics: consistent data management, global
standards, and uniform hardware and software interfaces.
Totally Integrated Automation lays the foundation for
comprehensive optimization of the production process:
• Time and cost savings due to efficient engineering
• Minimized downtime due to integrated diagnostic
functions
• Simplified implementation of automation solutions due
to global standards
• Better performance due to interoperability of systemtested components
Siemens KT 10.1 · 2016
5
© Siemens AG 2016
Totally Integrated Power
We bring power to the point –
safely and reliably.
Efficient, reliable, safe: These are the demands placed on electrification and especially
power distribution. And our answer – for all application areas of the energy system –
is Totally Integrated Power (TIP). It’s based on our comprehensive range of products,
systems, and solutions for low and medium voltage, rounded out by our support
throughout the entire lifecycle – from planning with our own software tools to installation,
operation, and services.
Comprehensive answers for
power distribution in complex
energy systems – from Siemens
Smart interfaces allow linking to industrial or building automation, making it possible to fully
exploit all the optimization potential of an integrated solution. This is how we provide our
customers around the world with answers to their challenges. With highly efficient, reliable,
and safe power distribution, we lay the foundation for sustainable infrastructure and cities,
buildings, and industrial plants. We bring power to the point – wherever and whenever it is
needed.
More information: www.siemens.com/tip
6
Siemens KT 10.1 · 2016
© Siemens AG 2016
Totally Integrated Power offers more:
• Consistency:
For simplified plant engineering and commissioning as well as smooth integration into automation solutions
for building or production processes
• One-stop-shop:
A reliable partner with a complete portfolio for the entire process and lifecycle – from the initial idea
to after-sales service
• Safety:
A comprehensive range of protection components for personnel safety and line and fire protection,
safety by means of type testing
• Reliability:
A reliable partner who works with customers to develop long-lasting solutions that meet the highest
quality standards
• Efficiency:
Bringing power to the point means greater plant availability and maximum energy efficiency in
power distribution
• Flexibility:
End-to-end consistency and modular design of Totally Integrated Power for any desired expansions and
adaptation to future requirements
• Advanced technology:
Reliable power distribution especially for applications in which supply is critical, continuous refinement of
the technology
Challenges are our speciality
Automation
Operation
&
Monitoring
Process/
Industrial
automation
Load
management
PROFINET
Load
curves
Forecast
Maintenance
PROFIBUS
Status
reporting/
failure management
...
Protocols
Power
Quality
Cost
center
Building
automation
Industrial Ethernet
Modbus
Electrification
Renewables
Storage
Medium-voltage switchgear
technologies and protection technology
Transformer
Low-voltage switchboard
with protection and measuring
technology
Low-voltage
distribution
≤ 110 kV
Products, systems and solutions
Consulting,
planning
Engineering
Order,
delivery
Installation,
commissioning
Operation
Service,
modernization
Siemens KT 10.1 · 2016
7
© Siemens AG 2016
Notes
8
Siemens KT 10.1 · 2016
1
© Siemens AG 2016
Introduction
1/2
1/2
1/3
1/4
1/6
1/8
SITOP power supplies
Introduction
The product range at a glance
SITOP Selection Tool
Selection tables for power supplies
Customized SITOP products
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP power supplies
1
Introduction
■ Overview
The benchmark in reliability, efficiency and integration
TOP reliability
Efficient operation of a machine or plant requires a
reliable, constant power supply.
You should only have to think once about a good power
supply when you are purchasing it – and then never again.
The quality and reliability of the SITOP stabilized power
supplies ensure high levels of safety in DC power supply 
in industrial engineering and building management
systems.
SITOP has proved its reliability more than 10 million times
over in almost every supply system in the world. With their
wide-range input, excellent load behavior and extensive
certification, SITOP power supplies alone ensure the
reliability of the power supply.
Our perfectly coordinated selection of SITOP power
supplies is enhanced by a unique range of add-on modules
that extensively protect the 24 V power supplies against
interference on the primary and secondary side, right up
to complete all-round protection.
Depending on requirements, SITOP power supplies can be
individually adapted with expansion modules and uninterruptible power supplies (DC UPS). This ensures reliability 
of the 24 V supply for machines or plants, even in the event
of an overload in the output circuit or a power failure on the
input side.
TOP efficiency
Production costs are determined more and more by energy
costs. Savings in this area generate valuable competitive
advantages. SITOP power supplies make an important
contribution here. Due to the high degree of efficiency, the
primary switched-mode power supplies operate extremely
effectively. The power loss across the entire performance
range is low – even during no-load operation. Because
power supplies are rarely operated at full load, there is
outstanding potential for savings here.
SITOP also supports the entire process chain of the customer efficiently. It offers easy product selection using the
SITOP Selection Tool, for example, and extensive additional
information such as 3D data, circuit diagram macros, certification and individually-configurable product documentation.
Every SITOP solution can therefore be planned and ordered,
designed, configured and operated in an extremely efficient
manner.
TOP integration
The better power supplies are integrated in their industrial
environment, the higher their productivity. SITOP is optimally
tailored to automation systems such as SIMATIC,
SINUMERIK and SIMOTION.
In addition, the PSU8600 power supply system and the
UPS1600 uninterruptible power supply are completely
integrated in TIA. Convenient engineering in the TIA Portal
supports, for example, easy network integration in
PROFINET or comprehensive diagnostics.
SIMATIC S7 function blocks support easy integration in 
STEP 7 user programs, and ready-to-use WinCC faceplates
are available for operator control and monitoring.
1/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP power supplies
The product range at a glance
SITOP compact
The slim power supply unit for control boxes
LOGO!Power
The flat power supply unit for distribution boards
SITOP lite
The low-cost basic power supply
SITOP smart
The powerful standard power supply
SITOP modular
The technology power supply for demanding solutions
Power supply system SITOP PSU8600 with Ethernet/PROFINET
and complete integration in TIA
SITOP power supplies in SIMATlC design
The optimum supply for SIMATIC S7 and more
SITOP in special desgns, made for special tasks
Well prepared for special tasks and conditions
Expansion modules
Redundancy modules
Protection against failure of a power supply by means of redundant
configuration of the power supply unit
Selectivity modules
Protection against overload and short circuit by means of electronic
protection of 24 V feeds
Buffer module
Protection against power failure for a few seconds
SITOP DC UPS
SITOP UPS500 with capacitors
Protection against power failure on the input side through buffering 
for a few minutes
SITOP UPS1600 with battery modules
Protection against power failure on the input side through buffering 
for a few hours.
DC UPS with Ethernet/PROFINET – open and integrated in TIA
Siemens KT 10.1 · 2016
1/3
1
© Siemens AG 2016
SITOP power supplies
1
SITOP Selection Tool
■ Overview
SITOP Selection Tool - get to the right power supply
simply and quickly
TIA Selection Tool - makes it easy to choose the right
power supply for 24 V loads
With the SITOP Selection Tool, you can select not only your
DC power supply, but now also the appropriate uninterruptible power supply (DC UPS) with capacitor or battery technology. Entering just a few technical specifications will automatically select the relevant parameters and show the
matching products. Selection parameters can be changed 
at any time.
The "24 V DC power consumer view" of the TIA Selection Tool
shows all automation products with 24 V infeed which have
already been selected. Using drag-and-drop, the loads can
be connected to one or more SITOP power supplies. The
total of the required rated and peak currents is automatically
calculated and taken into account when selecting power
supplies. Others loads such as sensors or actuators which
were not selected with the Tool can also be assigned. Only
those power supplies are offered which supply the total
power demand of the load to be supplied. It is also possible
to define additional power reserves for other loads, rated
diversity factors or redundant designs. Finally, the required
power supplies are transferred into the order list in the Industry Mall and any additional product data can be requested
from the CAX Download Manager.
You can individually configure the PSU8600 power supply
system using drag-and-drop to select additional modules for
extra outputs or add-on modules for bridging power failures,
for example. With the help of mandatory fields such as load
current, buffer time and buffer voltage, an appropriate DC
UPS is selected and then displayed with its performance
characteristics.
The Selection Tool checks the reliability of each production
selection or configuration automatically. The user can then
save the selected products in the product list and export the
list, including performance data, into several file formats, 
or directly to the Industry Mall shopping cart. More detailed
information about the selected products can be found in the
form of product data sheets, 3D data and operating instructions. The product data can also be requested directly by
means of the CAx Download Manager.
The tool is available on the Internet and in the Industry Mall:
www.siemens.com/sitop-selection-tool
www.siemens.com/industrymall
24 V DC power consumer view of the TIA Selection Tool
For more information about the "24 V DC power consumer
view" of the TIA Selection Tool, visit:
www.siemens.com/sitop-tst
Selection assistant for the SITOP PSU8600 power supply system
1/4
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP power supplies
SITOP Selection Tool
■ Overview
Everything you need for project planning
Additional information such as 3D data, circuit diagram macros, certificates and operating instructions are available at
the click of the mouse. The engineering data can be downloaded in DXF, STEP and EPLAN format and can be used
directly for your planning. They are also available via the CAx
Download Manager and can be individually selected there
as required and called up as a download. You not only save
valuable time on planning, but also benefit from traceable
documentation.
CAD and CAE data in the industry image database for easy configuration
All the product information is available to download using the 
CAx Download Managerh
Siemens KT 10.1 · 2016
1/5
1
© Siemens AG 2016
SITOP power supplies
1
Selection tables for power supplies
Input 
voltage
Output
current
Output voltage 24 V DC
SITOP
compact
LOGO!Power
SITOP
lite
SITOP
smart
SITOP
modular
PSU8600
SIMATIC
power supply design
system
Special design special uses
You will find all the technical specifications for these products on the pages specified below
1-phase AC
120 V, 230 V 0.6 A
2/6
1.3 A
2/6
3/13
8/3
2A
9/7
2.1 A
2.5 A
2/6
3/13
4/2
8/9
5/8
8/11
3A
9/7
3.1 A
3.5 A
3.7 A
2/9
4A
2/9
3/13
9/7
4.1 A
5A
4/2
5/8
8/6
6/3, 6/8
9/11, 9/33
6A
9/7
6.2 A
8A
10 A
4/2
5/8
6/3, 6/8
5/8
6/3
8/11
9/11, 9/14
8/6
9/33
12 A
9/7
12.5 A
20 A
40 A
6/3
1-phase DC
48 ... 220 V
0.375 A
48 ... 110 V
2A
24 ... 110 V
2A
9/25
9/27
8/3
110 ... 300 V 0.6 A
2/6
1.3 A
2/6
3/13
2.5 A
2/6
3/13
3.7 A
2/9
4A
2/9
3/13
120 ... 375 V 2.1 A
3.1 A
4.1 A
6.2 A
12 A
9/31
300 ... 900 V 20 A
3-phase AC
400 ... 500 V 5 A
9/36
5/13
9/14
8A
10 A
5/13
9/18
17 A
20 A
5/13
6/13
7/5
5/13
6/13
7/5
9/18
30 A
40 A
4x5A
7/5
4 x 10 A
7/5
400 ... 480 V
8A
1/6
Siemens KT 10.1 · 2016
8/14
9/14
© Siemens AG 2016
SITOP power supplies
Selection tables for power supplies
Input 
voltage
Output
current
Output voltage 
5, 12, 15, 36, 48 V DC
SITOP
compact
LOGO!Power SITOP
lite
SITOP
smart
SITOP
modular
PSU8600
SIMATIC
power supply design
system
Special design special uses
You will find all the technical specifications for these products on the pages specified below
1-phase AC
120 V, 230 V 3 - 52 V/2 - 10 A
9/23
5 V/3 A
3/3
5 V/6.3 A
3/3
12 V/1.9 A
12 V/2 A
3/6
2/3
12 V/3 A
9/4
12 V/4.5 A
12 V/6.5 A
3/6
2/3
12 V/7 A
5/3
12 V/8.3 A
9/4
12 V/14 A
5/3
15 V/1.9 A
3/9
15 V/4 A
3/9
2 x 15 V/3.5 A
9/21
1-phase DC
24 V
12 V/2.5 A
9/29
110 ... 300 V 5 V/3 A
3/3
5 V/6.3 A
3/3
12 V/1.9 A
12 V/2 A
3/6
2/3
12 V/2.5 A
9/29
12 V/4.5 A
12 V/6.5 A
3/6
2/3
15 V/1.9 A
3/9
15 V/4 A
3/9
3-phase AC
400 ... 500 V 12 V/20 A
9/16
36 V/13 A
6/17
48 V/10 A
6/19
48 V/20 A
6/19
Siemens KT 10.1 · 2016
1/7
1
© Siemens AG 2016
SITOP power supplies
1
Customized SITOP products
■ Overview
Our well-proven standard power supplies cannot, of course,
satisfy the requirements of every application. We make it
possible for you to optimize your system to suit applicationspecific requirements.
Our customer-specific solutions are used today in many sectors of mechanical engineering, in automation technology,
vehicle electronics, equipment manufacturing and in 
industrial instrumentation technology.
You benefit from the expertise of large-scale production and
gain maximum development security and quality.
Our offer is in principle open to every application case. If we
have awakened your interest or if you would like to receive
further details, please contact your local Siemens representative.
1/8
Siemens KT 10.1 · 2016
2
© Siemens AG 2016
SITOP compact
2/2
2/3
2/6
Introduction
1-phase, 12 V DC
1-phase, 24 V DC
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP compact
Introduction
■ Overview
■ More information
Select the appropriate power supply quickly and easily with the
SITOP Selection Tool:
2
http://www.siemens.com/sitop-selection-tool
The slim power supply unit for control boxes
The single-phase SITOP compact are power supplies for the
lower performance range. Thanks to the extremely space-saving
slim design, they are especially suited to distributed applications in control boxes or in small control cabinets. The series is
characterized by low power losses throughout the entire load
range. The losses are extremely low even during idling, which
means they are perfectly suited for applications that are frequently in stand-by mode. The SITOP PSU100C power supplies
have a wide-range input for AC and DC networks; plug-in terminals facilitate the electrical connection.
To further increase the 24 V availability, the SITOP compact
power supplies can be combined with DC UPS, redundancy
and selectivity modules.
Main product highlights
• 24 V DC/ 0.6 A, 1.3 A, 2.5 A, and 4 A as well as 12 V DC/
2 A and 6.5 A
• 24 V DC/3.7 A for the supply of NEC class 2 circuits with
limited output power (100 VA)
• 1-phase wide-range input from 85 V to 264 V AC or 110 V
to 300 V DC
• Small mounting surface thanks to its slim design
• High efficiency across the entire load range: up to 28 %
energy savings in comparison with similar devices
• Low energy consumption during no-load operation or
stand-by: Energy savings of up to 53 % are possible
• Adjustable output voltage for compensating voltage drops
• Green LED for "Output voltage OK"
• Plug-in connecting terminals for pre-fabricated wiring and
fast electrical connection
• Wide temperature range from –20 to +70 °C
• Comprehensive certifications, such as UL, ATEX or GL
2/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP compact
1-phase, 12 V DC
■ Overview
The single-phase SITOP compact are power supplies for the
lower performance range. Thanks to the extremely space-saving
slim design, they are especially suited to distributed applications in control boxes or in small control cabinets. The series is
characterized by low power losses throughout the entire load
range. The losses are extremely low even during idling, which
means they are perfectly suited for applications that are frequently in stand-by mode. The SITOP PSU100C power supplies
have a wide-range input for AC and DC networks; plug-in terminals facilitate the electrical connection.
Main product highlights
• 12 V DC, 2 A and 6.5 A
• 1-phase wide-range input from 85 V to 264 V AC or 110 V to
300 V DC
• Small mounting surface thanks to its slim design
• High efficiency across the entire load range.
• Low energy consumption during no-load operation or
stand-by
• Adjustable output voltage for compensating voltage drops
• Green LED for "12 V OK"
• Plug-in connecting terminals for pre-fabricated wiring and fast
electrical connection
• Wide temperature range from –20 to +70 °C
• Comprehensive certifications, such as UL, ATEX or GL
■ Technical specifications
Article number
6EP1321-5BA00
6EP1322-5BA10
Product
SITOP PSU100C
SITOP PSU100C
Power supply, type
12 V/2 A
12 V/6.5 A
Input
1-phase AC or DC
1-phase AC or DC
Rated voltage value Vin rated
100 ... 230 V
100 ... 230 V
Voltage range AC
85 ... 264 V
85 ... 264 V
• at DC
110 ... 300 V
110 ... 300 V
Wide-range input
Yes
Yes
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
20 ms; at Vin = 230 V
20 ms; at Vin = 230 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 100 V
0.63 A
1.6 A
• at rated input voltage 230 V
0.31 A
0.8 A
Switch-on current limiting (+25 °C), max.
33 A
31 A
I²t, max.
1.2 A²·s
3 A²·s
Built-in incoming fuse
internal
internal
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker:
from 16 A characteristic B or
from 10 A characteristic C
Recommended miniature circuit breaker:
from 16 A characteristic B or
from 10 A characteristic C
Input
Input voltage
Input current
Siemens KT 10.1 · 2016
2/3
2
© Siemens AG 2016
SITOP compact
1-phase, 12 V DC
■ Technical specifications (continued)
2
Article number
6EP1321-5BA00
6EP1322-5BA10
Product
SITOP PSU100C
SITOP PSU100C
Power supply, type
12 V/2 A
12 V/6.5 A
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
12 V
12 V
Total tolerance, static ±
3%
3%
Static mains compensation, approx.
0.5 %
0.5 %
Static load balancing, approx.
1%
1%
Residual ripple peak-peak, max.
200 mV
200 mV
Residual ripple peak-peak, typ.
40 mV
80 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
300 mV
300 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)
50 mV
80 mV
Adjustment range
10.5 ... 12.9 V
10.5 ... 12.9 V
Product function Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
Status display
Green LED for output voltage OK
Green LED for output voltage OK
On/off behavior
Overshoot of Vout approx. 5 %
Overshoot of Vout approx. 1 %
Startup delay, max.
0.6 s
1s
Voltage rise, typ.
10 ms
500 ms
Rated current value Iout rated
2A
6.5 A
Current range
0 ... 2 A
0 ... 6.5 A
• Note
+55 ... +70 °C: Derating 3%/K
+50 ... +70 °C: Derating 3.5%/K
Supplied active power typical
24 W
78 W
Parallel switching for enhanced performance
Yes; Start-up with single nominal load only
Yes; Start-up with single nominal load only
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency at Vout rated, Iout rated, approx.
82 %
86 %
Power loss at Vout rated, Iout rated, approx.
5.8 W
12.5 W
Power loss [W] during no-load operation
maximum
0.75 W
0.75 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
0.1 %
Dynamic load smoothing (Vout: 10/90/10 %),
Uout ± typ.
3%
3%
Load step setting time 10 to 90%, typ.
4 ms
3 ms
Load step setting time 90 to 10%, typ.
3 ms
3 ms
Output overvoltage protection
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Current limitation, typ.
2.4 A
7.2 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
Overload/short-circuit indicator
-
-
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
• maximum
3.5 mA
3.5 mA
• typical
0.4 mA
0.4 mA
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cCSAus (CSA C22.2 No. 60950-1,
UL 60950-1)
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cCSAus (CSA C22.2 No. 60950-1,
UL 60950-1)
Explosion protection
ATEX (EX) II 3G Ex nA IIC T4; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
ATEX (EX) II 3G Ex nA IIC T4; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
FM approval
-
-
CB approval
Yes
Yes
Marine approval
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
Output
Efficiency
Closed-loop control
Protection and monitoring
Safety
Leakage current
2/4
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP compact
1-phase, 12 V DC
■ Technical specifications (continued)
Article number
6EP1321-5BA00
6EP1322-5BA10
Product
SITOP PSU100C
SITOP PSU100C
Power supply, type
12 V/2 A
12 V/6.5 A
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
not applicable
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
-20 ... +70 °C
-20 ... +70 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
screw-type terminals
screw-type terminals
• Supply input
L, N, PE: Removable screw terminal,
each for 1 x 0.5 ... 2.5 mm²
L, N, PE: Removable screw terminal,
each for 1 x 0.5 ... 2.5 mm²
• Output
+: 1 screw terminal for 0.5 ... 2.5 mm²;
-: 2 screw terminals for 0.5 ... 2.5 mm²
+: 1 screw terminal for 0.5 ... 2.5 mm²;
-: 2 screw terminals for 0.5 ... 2.5 mm²
• Auxiliary
-
-
Width of the enclosure
30 mm
52.5 mm
Height of the enclosure
80 mm
80 mm
Depth of the enclosure
100 mm
100 mm
Weight, approx.
0.12 kg
0.32 kg
Product feature of the enclosure housing for
side-by-side mounting
Yes
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
Snaps onto DIN rail EN 60715 35x7.5/15
Electrical accessories
Removable spring-type terminal 6EP1971-5BA00
Removable spring-type terminal 6EP1971-5BA00
MTBF at 40 °C
3 737 060 h
2 853 800 h
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
2
EMC
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
■ Ordering data
SITOP PSU100C 1-phase,
12 V DC/2 A
Article No.
6EP1321-5BA00
Stabilized power supply
Input:
100 … 230 V AC (110 … 300 V DC)
Output: 12 V DC/2 A
SITOP PSU100C 1-phase,
12 V DC/6.5 A
■ Accessories
SITOP Power PSU100C
accessories
Article No.
6EP1971-5BA00
Removable spring-loaded terminal,
100 units, for SITOP PSU100C
6EP1322-5BA10
Stabilized power supply
Input:
100 … 230 V AC (110 … 300 V DC)
Output: 12 V DC/6.5 A
Siemens KT 10.1 · 2016
2/5
© Siemens AG 2016
SITOP compact
1-phase, 24 V DC
■ Overview
The single-phase SITOP compact are power supplies for the
lower performance range. Thanks to the extremely space-saving
slim design, they are especially suited to distributed applications in control boxes or in small control cabinets. The series is
characterized by low power losses throughout the entire load
range. The losses are extremely low even during idling, which
means they are perfectly suited for applications that are frequently in stand-by mode. The SITOP PSU100C power supplies
have a wide-range input for AC and DC networks; plug-in terminals facilitate the electrical connection.
2
To further increase the 24 V availability, the SITOP compact
power supplies can be combined with DC UPS, redundancy
and selectivity modules.
Main product highlights
• 24 V DC/ 0.6 A, 1.3 A, 2.5 A and 4 A
• 24 V DC/3.7 A for the supply of NEC class 2 circuits with
limited output power (100 VA)
• 1-phase wide-range input from 85 V to 264 V AC or 110 V to
300 V DC
• Small mounting surface thanks to its slim design
• High efficiency across the entire load range.
• Low energy consumption during no-load operation or
stand-by
• Adjustable output voltage for compensating voltage drops
(starting at 1.3 A)
• Green LED for "24 V OK"
• Plug-in connecting terminals for pre-fabricated wiring and fast
electrical connection
• Wide temperature range from –20 to +70 °C
• Comprehensive certifications, such as UL, ATEX or GL
■ Technical specifications
Article number
6EP1331-5BA00
6EP1331-5BA10
6EP1332-5BA00
Product
SITOP PSU100C
SITOP PSU100C
SITOP PSU100C
Power supply, type
24 V/0.6 A
24 V/1.3 A
24 V/2.5 A
Input
Input
1-phase AC or DC
1-phase AC or DC
1-phase AC or DC
Rated voltage value Vin rated
100 ... 230 V
100 ... 230 V
100 ... 230 V
Voltage range AC
85 ... 264 V
85 ... 264 V
85 ... 264 V
Input voltage
• at DC
110 ... 300 V
110 ... 300 V
110 ... 300 V
Wide-range input
Yes
Yes
Yes
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
20 ms; at Vin = 230 V
20 ms; at Vin = 230 V
20 ms; at Vin = 230 V
Rated line frequency 1
50 Hz
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
Input current
• at rated input voltage 100 V
0.28 A
0.63 A
1.21 A
• at rated input voltage 230 V
0.18 A
0.31 A
0.67 A
Switch-on current limiting (+25 °C),
max.
28 A
34 A
31 A
I²t, max.
0.7 A²·s
1.2 A²·s
2.4 A²·s
Built-in incoming fuse
internal
internal
internal
Protection in the mains power input
(IEC 898)
Recommended miniature circuit
breaker:
from 16 A characteristic B or
from 10 A characteristic C
Recommended miniature circuit
breaker:
from 16 A characteristic B or
from 10 A characteristic C
Recommended miniature circuit
breaker:
from 16 A characteristic B or
from 10 A characteristic C
2/6
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP compact
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1331-5BA00
6EP1331-5BA10
6EP1332-5BA00
Product
SITOP PSU100C
SITOP PSU100C
SITOP PSU100C
Power supply, type
24 V/0.6 A
24 V/1.3 A
24 V/2.5 A
2
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
24 V
24 V
Total tolerance, static ±
3%
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
0.1 %
Static load balancing, approx.
0.2 %
0.2 %
0.2 %
Residual ripple peak-peak, max.
200 mV
200 mV
200 mV
Residual ripple peak-peak, typ.
40 mV
25 mV
55 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
300 mV
300 mV
300 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
20 mV
20 mV
50 mV
Adjustment range
-
22.2 ... 26.4 V
22.2 ... 26.4 V
Product function Output voltage
adjustable
No
Yes
Yes
Output voltage setting
-
via potentiometer
via potentiometer
Status display
Green LED for output voltage OK
Green LED for output voltage OK
Green LED for output voltage OK
On/off behavior
Overshoot of Vout approx. 5 %
Overshoot of Vout approx. 5 %
Overshoot of Vout approx. 1 %
Startup delay, max.
1s
0.6 s
0.7 s
Voltage rise, typ.
25 ms
90 ms
100 ms
Rated current value Iout rated
0.6 A
1.3 A
2.5 A
Current range
0 ... 0.6 A
0 ... 1.3 A
0 ... 2.5 A
• Note
+55 ... +70 °C: Derating 3%/K
+55 ... +70 °C: Derating 3%/K
+55 ... +70 °C: Derating 3,5%/K
Supplied active power typical
14 W
30 W
60 W
• at short-circuit during operation
typical
1A
3.1 A
-
Parallel switching for enhanced
performance
No
Yes; Start-up with single nominal load
only
Yes; Start-up with single nominal load
only
Numbers of parallel switchable units
for enhanced performance
-
2
2
Efficiency at Vout rated, Iout rated,
approx.
82 %
86 %
87 %
Power loss at Vout rated, Iout rated,
approx.
2.6 W
4.5 W
9W
Power loss [W] during no-load
operation maximum
0.75 W
0.75 W
0.75 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
0.1 %
0.1 %
Dynamic load smoothing
(Iout: 10/90/10 %), Uout ± typ.
3%
3%
3%
Load step setting time 10 to 90%, typ. 3 ms
5 ms
4 ms
Load step setting time 90 to 10%, typ. 3 ms
5 ms
4 ms
Short-term overload current
Efficiency
Closed-loop control
Protection and monitoring
Output overvoltage protection
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Current limitation, typ.
0.7 A
1.4 A
3A
Property of the output Short-circuit
proof
Yes
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart Electronic shutdown, automatic restart Electronic shutdown, automatic restart
Overload/short-circuit indicator
-
-
-
Siemens KT 10.1 · 2016
2/7
© Siemens AG 2016
SITOP compact
1-phase, 24 V DC
■ Technical specifications (continued)
2
Article number
6EP1331-5BA00
6EP1331-5BA10
6EP1332-5BA00
Product
SITOP PSU100C
SITOP PSU100C
SITOP PSU100C
Power supply, type
24 V/0.6 A
24 V/1.3 A
24 V/2.5 A
Safety
Primary/secondary isolation
Yes
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Protection class
Class I
Class I
Class I
Leakage current
• maximum
3.5 mA
3.5 mA
3.5 mA
• typical
0.4 mA
0.4 mA
0.4 mA
CE mark
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259;
cURus-Recognized (UL 60950,
CSA C22.2 No. 60950),
File E151273, NEC class 2
(acc. to UL 1310)
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259;
cURus-Recognized (UL 60950,
CSA C22.2 No. 60950),
File E151273, NEC class 2
(acc. to UL 1310)
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259;
cURus-Recognized (UL 60950,
CSA C22.2 No. 60950),
File E151273, NEC class 2
(acc. to UL 1310)
Explosion protection
ATEX (EX) II 3G Ex nA IIC T4;
cCSAus (CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
ATEX (EX) II 3G Ex nA IIC T4;
cCSAus (CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
ATEX (EX) II 3G Ex nA IIC T4;
cCSAus (CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
FM approval
-
-
-
CB approval
Yes
Yes
Yes
Marine approval
GL, ABS
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
IP20
EMC
Emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
not applicable
not applicable
not applicable
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
-20 ... +70 °C
-20 ... +70 °C
-20 ... +70 °C
with natural convection
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
Climate class 3K3, no condensation
screw-type terminals
screw-type terminals
screw-type terminals
• Supply input
L, N, PE: Removable screw terminal,
each for 1 x 0.5 ... 2.5 mm²
L, N, PE: Removable screw terminal,
each for 1 x 0.5 ... 2.5 mm²
L, N, PE: Removable screw terminal,
each for 1 x 0.5 ... 2.5 mm²
• Output
+: 1 screw terminal for 0.5 ... 2.5 mm²; +: 1 screw terminal for 0.5 ... 2.5 mm²; +: 1 screw terminal for 0.5 ... 2.5 mm²;
-: 2 screw terminals for 0.5 ... 2.5 mm² -: 2 screw terminals for 0.5 ... 2.5 mm² -: 2 screw terminals for 0.5 ... 2.5 mm²
• Auxiliary
-
-
-
Width of the enclosure
22.5 mm
30 mm
45 mm
Height of the enclosure
80 mm
80 mm
80 mm
Depth of the enclosure
100 mm
100 mm
100 mm
Weight, approx.
0.12 kg
0.17 kg
0.22 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Yes
Installation
Snaps onto DIN rail EN 60715
35x7.5/15
Snaps onto DIN rail EN 60715
35x7.5/15
Snaps onto DIN rail EN 60715
35x7.5/15
Electrical accessories
Removable spring-type terminal
6EP1971-5BA00
Removable spring-type terminal
6EP1971-5BA00
Removable spring-type terminal
6EP1971-5BA00
MTBF at 40 °C
3 910 833 h
3 838 624 h
2 881 014 h
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
2/8
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP compact
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1332-5BA20
6EP1332-5BA10
Product
SITOP PSU100C
SITOP PSU100C
Power supply, type
24 V/3.7 A
24 V/4 A
2
Input
Input
1-phase AC or DC
1-phase AC or DC
Rated voltage value Vin rated
100 ... 230 V
100 ... 230 V
Voltage range AC
85 ... 264 V
85 ... 264 V
Input voltage
• at DC
110 ... 300 V
110 ... 300 V
Wide-range input
Yes
Yes
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
20 ms; at Vin = 230 V
20 ms; at Vin = 230 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
Input current
• at rated input voltage 100 V
1.88 A
2.25 A
• at rated input voltage 230 V
0.95 A
1.15 A
Switch-on current limiting (+25 °C),
max.
30 A
34 A
I²t, max.
3 A²·s
3 A²·s
Built-in incoming fuse
internal
internal
Protection in the mains power input
(IEC 898)
Recommended miniature circuit breaker:
from 16 A characteristic B or
from 10 A characteristic C
Recommended miniature circuit breaker:
from 16 A characteristic B or
from 10 A characteristic C
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
24 V
Total tolerance, static ±
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
0.2 %
0.2 %
Residual ripple peak-peak, max.
200 mV
200 mV
Residual ripple peak-peak, typ.
90 mV
80 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
300 mV
300 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
60 mV
80 mV
Adjustment range
22.2 ... 26.4 V
Product function Output voltage
adjustable
No
Yes
Output voltage setting
-
via potentiometer
Status display
Green LED for output voltage OK
Green LED for output voltage OK
On/off behavior
Overshoot of Vout approx. 1 %
Overshoot of Vout approx. 1 %
Startup delay, max.
1.5 s
1.5 s
Voltage rise, typ.
500 ms
400 ms
Rated current value Iout rated
3.7 A
4A
Current range
0 ... 3.7 A
0 ... 4 A
• Note
+55 ... +70 °C: Derating 3,5%/K
+55 ... +70 °C: Derating 3,5%/K
Supplied active power typical
89 W
96 W
• at short-circuit during operation
typical
-
-
Parallel switching for enhanced
performance
No
Yes; Start-up with single nominal load only
Numbers of parallel switchable units
for enhanced performance
-
2
Short-term overload current
Siemens KT 10.1 · 2016
2/9
© Siemens AG 2016
SITOP compact
1-phase, 24 V DC
■ Technical specifications (continued)
2
Article number
6EP1332-5BA20
6EP1332-5BA10
Product
SITOP PSU100C
SITOP PSU100C
Power supply, type
24 V/3.7 A
24 V/4 A
Efficiency at Vout rated, Iout rated,
approx.
87 %
88 %
Power loss at Vout rated, Iout rated,
approx.
14 W
13 W
Power loss [W] during no-load
operation maximum
0.75 W
0.75 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
0.1 %
Dynamic load smoothing
(Iout: 10/90/10 %), Uout ± typ.
3%
3%
Efficiency
Closed-loop control
Load step setting time 10 to 90%, typ. 4 ms
4 ms
Load step setting time 90 to 10%, typ. 4 ms
4 ms
Protection and monitoring
Output overvoltage protection
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Current limitation, typ.
4A
4.8 A
Property of the output Short-circuit
proof
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
Overload/short-circuit indicator
-
-
Safety
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1
and EN 50178
Safety extra-low output voltage Uout acc. to EN 60950-1
and EN 50178
Protection class
Class I
Class I
Leakage current
• maximum
3.5 mA
3.5 mA
• typical
0.4 mA
0.4 mA
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cURus-Recognized (UL 60950,
CSA C22.2 No. 60950), File E151273, NEC class 2
(acc. to UL 1310)
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cCSAus (CSA C22.2 No. 60950-1,
UL 60950-1)
Explosion protection
ATEX (EX) II 3G Ex nA IIC T4; cCSAus
(CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007)
Class I, Div. 2, Group ABCD, T4
ATEX (EX) II 3G Ex nA IIC T4; cCSAus
(CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007)
Class I, Div. 2, Group ABCD, T4
FM approval
-
-
CB approval
Yes
Yes
Marine approval
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
2/10
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP compact
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1332-5BA20
6EP1332-5BA10
Product
SITOP PSU100C
SITOP PSU100C
Power supply, type
24 V/3.7 A
24 V/4 A
2
EMC
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
-20 ... +70 °C
-20 ... +70 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
screw-type terminals
screw-type terminals
• Supply input
L, N, PE: Removable screw terminal, each for
1 x 0.5 ... 2.5 mm²
L, N, PE: Removable screw terminal, each for
1 x 0.5 ... 2.5 mm²
• Output
+: 1 screw terminal for 0.5 ... 2.5 mm²;
-: 2 screw terminals for 0.5 ... 2.5 mm²
+: 1 screw terminal for 0.5 ... 2.5 mm²;
-: 2 screw terminals for 0.5 ... 2.5 mm²
• Auxiliary
-
-
Width of the enclosure
52.5 mm
52.5 mm
Height of the enclosure
80 mm
80 mm
Depth of the enclosure
100 mm
100 mm
Weight, approx.
0.32 kg
0.32 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
Snaps onto DIN rail EN 60715 35x7.5/15
Electrical accessories
Removable spring-type terminal 6EP1971-5BA00
Removable spring-type terminal 6EP1971-5BA00
MTBF at 40 °C
2 776 544 h
2 726 727 h
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
Siemens KT 10.1 · 2016
2/11
© Siemens AG 2016
SITOP compact
1-phase, 24 V DC
■ Ordering data
2
SITOP PSU100C 1-phase,
24 V DC/0.6 A
Article No.
6EP1331-5BA00
6EP1331-5BA10
Stabilized power supply
Input:
100 … 230 V AC (110 … 300 V DC)
Output: 24 V DC/1.3 A
SITOP PSU100C 1-phase,
24 V DC/2.5 A
6EP1332-5BA00
6EP1332-5BA20
Stabilized power supply
Input:
100 … 230 V AC (110 … 300 V DC)
Output: 24 V DC/3.7 A
limited output power NEC Class 2
SITOP PSU100C 1-phase,
24 V DC/4 A
SITOP PSE202U
redundancy module
6EP1964-2BA00
Input/output: 24 V DC/10 A
suitable for decoupling two SITOP
power supplies
with a maximum of 5 A output
current
4-channel selectivity module
Input: 24 V DC
Output: 24 V DC/3A per each
channel
output current adjustable 0.5 … 3 A
• With common alarm signal
• With single-channel signaling
SITOP Power PSU100C
accessories
6EP1332-5BA10
Stabilized power supply
Input:
100 … 230 V AC (110 … 300 V DC)
Output: 24 V DC/4 A
2/12
6EP1962-2BA00
SITOP PSE200U 3 A
selectivity module
Stabilized power supply
Input:
100 … 230 V AC (110 … 300 V DC)
Output: 24 V DC/2.5 A
SITOP PSU100C 1-phase,
24 V DC/3.7 A
SITOP PSE202U
redundancy module
Article No.
Input/output: 24 V DC/NEC Class 2
suitable for decoupling two SITOP
power supplies output power
limited < 100 VA
Stabilized power supply
Input:
100 … 230 V AC (110 … 300 V DC)
Output: 24 V DC/0.6 A
SITOP PSU100C 1-phase,
24 V DC/1.3 A
■ Accessories
Siemens KT 10.1 · 2016
Removable spring-loaded terminal,
100 units, for SITOP PSU100C
6EP1961-2BA11
6EP1961-2BA31
6EP1971-5BA00
3
© Siemens AG 2016
LOGO!Power
3/2
3/3
3/6
3/9
3/12
Introduction
1-phase, 5 V DC
1-phase, 12 V DC
1-phase, 15 V DC
1-phase, 24 V DC
Siemens KT 10.1 · 2016
© Siemens AG 2016
LOGO!Power
Introduction
■ Overview
■ More information
Select the appropriate power supply quickly and easily with the
SITOP Selection Tool:
http://www.siemens.com/sitop-selection-tool
3
The flat power supply unit for distribution boards
Our miniature power supply units in the same design as the logic
modules offer great performance in the smallest space:
The excellent efficiency across the entire load range, and the low
power losses in no-load operation ensure efficient operation.
The wide-range input for 1-phase networks as well as operation
with direct voltage, the wide operating temperature range, comprehensive certifications as well as the switch-on behavior optimized for capacitive loads makes them suitable for universal
use. These reliable power supplies with their flat, stepped profile
can be used extremely flexibly in numerous applications such as
in distribution boards, for example.
To further increase the 24 V availability, the LOGO!Power power
supplies can be combined with DC UPS, redundancy and
selectivity modules.
Main product highlights
• 5 V DC/ 3 A and 6.3 A, 12 V DC/ 1.9 A and 4.5 A, 15 V DC/
1.9 A and 4 A as well as 24 V DC/ 1.3 A, 2.5 A and 4 A
• 1-phase, wide-range input for 85 V to 264 V AC or 110 V to
300 V DC
• Flat LOGO! design with an installation depth of only 55 mm
• High efficiency across the entire load range, low no-load
losses
• Power reserve on starting up through 1.5 times the rated
current for capacitive loads
• Wide temperature range from -20 to +70 °C
• Comprehensive certifications, such as cULus, CB, FM, ATEX,
cCSAus Class I Div. 2, GL and ABS
3/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
LOGO!Power
1-phase, 5 V DC
■ Overview
Our miniature power supply units in the same design as the logic
modules offer great performance in the smallest space: The
excellent efficiency across the entire load range, and the low
power losses in no-load operation ensure efficient operation.
The wide-range input for 1-phase networks as well as operation
with direct voltage, the wide operating temperature range, comprehensive certifications as well as the switch-on behavior optimized for capacitive loads makes them suitable for universal
use. These reliable power supplies with their flat, stepped profile
can be used extremely flexibly in numerous applications such as
in distribution boards, for example.
Main product highlights
• 5 V DC/ 3 A and 6.3 A
• 1-phase, wide-range input for 85 V to 264 V AC or 110 V to
300 V DC
• Flat LOGO! design with an installation depth of only 55 mm
• High efficiency across the entire load range, low no-load
losses
• Power reserve on starting up through 1.5 times the rated
current for capacitive loads
• Wide temperature range from -20 to +70 °C
• Comprehensive certifications, such as cULus, CB, FM, ATEX,
cCSAus Class I Div. 2, GL and ABS
■ Technical specifications
Article number
6EP1311-1SH03
6EP1311-1SH13
Product
LOGO!Power
LOGO!Power
Power supply, type
5 V/3 A
5 V/6.3 A
Input
1-phase AC or DC
1-phase AC or DC
Rated voltage value Vin rated
100 ... 240 V
100 ... 240 V
Voltage range AC
85 ... 264 V
85 ... 264 V
• at DC
110 ... 300 V
110 ... 300 V
Wide-range input
Yes
Yes
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
40 ms; at Vin = 187 V
40 ms; at Vin = 187 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 120 V
0.36 A
0.71 A
• at rated input voltage 230 V
0.22 A
0.37 A
Switch-on current limiting (+25 °C), max.
26 A
50 A
I²t, max.
0.8 A²·s
3 A²·s
Built-in incoming fuse
internal
internal
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker: from 16 A
characteristic B or from 10 A characteristic C
Recommended miniature circuit breaker: from 16 A
characteristic B or from 10 A characteristic C
Input
Input voltage
Input current
Siemens KT 10.1 · 2016
3/3
3
© Siemens AG 2016
LOGO!Power
1-phase, 5 V DC
■ Technical specifications (continued)
Article number
6EP1311-1SH03
6EP1311-1SH13
Product
LOGO!Power
LOGO!Power
Power supply, type
5 V/3 A
5 V/6.3 A
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
5V
5V
Total tolerance, static ±
3%
3%
Static mains compensation, approx.
0.2 %
0.1 %
Static load balancing, approx.
1.5 %
2%
Residual ripple peak-peak, max.
100 mV
100 mV
Residual ripple peak-peak, typ.
10 mV
15 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
100 mV
100 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)
20 mV
70 mV
Adjustment range
4.6 ... 5.4 V
4.6 ... 5.4 V
Product function Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
Status display
Green LED for output voltage OK
Green LED for output voltage OK
On/off behavior
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
Startup delay, max.
0.5 s
0.5 s
Voltage rise, typ.
20 ms
10 ms
Rated current value Iout rated
3A
6.3 A
Current range
0 ... 3 A
0 ... 6.3 A
• Note
+55 ... +70 °C: Derating 2%/K
+55 ... +70 °C: Derating 2%/K
Supplied active power typical
15 W
30 W
Parallel switching for enhanced performance
Yes
Yes
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency at Vout rated, Iout rated, approx.
77 %
83 %
Power loss at Vout rated, Iout rated, approx.
4W
6W
Power loss [W] during no-load operation
maximum
1.5 W
1.5 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.2 %
0.2 %
Dynamic load smoothing (Iout: 10/90/10 %),
Uout ± typ.
3%
3%
Load step setting time 10 to 90%, typ.
2 ms
2 ms
Load step setting time 90 to 10%, typ.
2 ms
2 ms
Output overvoltage protection
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Current limitation, typ.
3.8 A
8.2 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Constant current characteristic
Constant current characteristic
• maximum
5A
10 A
Overload/short-circuit indicator
-
-
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Output
3
Efficiency
Closed-loop control
Protection and monitoring
Enduring short circuit current RMS value
Safety
Protection class
Class II (without protective conductor)
Class II (without protective conductor)
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cURus-Recognized (UL 60950,
CSA C22.2 No. 60950), File E151273, NEC class 2
(acc. to UL 1310)
cULus-listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cURus-recognized (UL 60950,
CSA C22.2 No. 60950), File E151273
Explosion protection
ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
FM approval
Class I, Div. 2, Group ABCD, T4
Class I, Div. 2, Group ABCD, T4
CB approval
Yes
Yes
Marine approval
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
3/4
Siemens KT 10.1 · 2016
© Siemens AG 2016
LOGO!Power
1-phase, 5 V DC
■ Technical specifications (continued)
Article number
6EP1311-1SH03
6EP1311-1SH13
Product
LOGO!Power
LOGO!Power
Power supply, type
5 V/3 A
5 V/6.3 A
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
not applicable
not applicable
Noise immunity
EN 61000-6-2
EN 61000-6-2
-20 ... +70 °C
-20 ... +70 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
screw-type terminals
screw-type terminals
• Supply input
L, N: 1 screw terminal each for 0.5 ... 2.5 mm²
single-core/finely stranded
L, N: 1 screw terminal each for 0.5 ... 2.5 mm²
single-core/finely stranded
• Output
+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
• Auxiliary
-
-
Width of the enclosure
54 mm
72 mm
Height of the enclosure
90 mm
90 mm
Depth of the enclosure
52.6 mm
52.6 mm
Weight, approx.
0.17 kg
0.25 kg
Product feature of the enclosure housing for
side-by-side mounting
Yes
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
Snaps onto DIN rail EN 60715 35x7.5/15
MTBF at 40 °C
3 543 963 h
3 741 955 h
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
EMC
3
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
■ Ordering data
Article No.
LOGO!Power 1-phase,
5 V DC/3 A
Stabilized power supply
Input:
100 … 240 V AC (110 … 300 V DC)
Output: 5 V DC/3 A
6EP1311-1SH03
LOGO!Power 1-phase,
5 V DC/6.3 A
Stabilized power supply
Input:
100 … 240 V AC (110 … 300 V DC)
Output: 5 V DC/6.3 A
6EP1311-1SH13
Siemens KT 10.1 · 2016
3/5
© Siemens AG 2016
LOGO!Power
1-phase, 12 V DC
■ Overview
Our miniature power supply units in the same design as the logic
modules offer great performance in the smallest space: The
excellent efficiency across the entire load range, and the low
power losses in no-load operation ensure efficient operation.
The wide-range input for 1-phase networks as well as operation
with direct voltage, the wide operating temperature range, comprehensive certifications as well as the switch-on behavior optimized for capacitive loads makes them suitable for universal
use. These reliable power supplies with their flat, stepped profile
can be used extremely flexibly in numerous applications such as
in distribution boards, for example.
3
Main product highlights
• 12 V DC, 1.9 A and 4.5 A
• 1-phase, wide-range input for 85 V to 264 V AC or 110 V to
300 V DC
• Flat LOGO! design with an installation depth of only 55 mm
• High efficiency across the entire load range, low no-load
losses
• Power reserve on starting up through 1.5 times the rated
current for capacitive loads
• Wide temperature range from -20 to +70 °C
• Comprehensive certifications, such as cULus, CB, FM, ATEX,
cCSAus Class I Div. 2, GL and ABS
■ Technical specifications
Article number
6EP1321-1SH03
6EP1322-1SH03
Product
LOGO!Power
LOGO!Power
Power supply, type
12 V/1.9 A
12 V/4.5 A
Input
1-phase AC or DC
1-phase AC or DC
Rated voltage value Vin rated
100 ... 240 V
100 ... 240 V
Voltage range AC
85 ... 264 V
85 ... 264 V
• at DC
110 ... 300 V
110 ... 300 V
Wide-range input
Yes
Yes
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
40 ms; at Vin = 187 V
40 ms; at Vin = 187 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 120 V
0.53 A
1.13 A
• at rated input voltage 230 V
0.3 A
0.61 A
Switch-on current limiting (+25 °C), max.
25 A
55 A
I²t, max.
0.8 A²·s
3 A²·s
Built-in incoming fuse
internal
internal
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker: from 16 A
characteristic B or from 10 A characteristic C
Recommended miniature circuit breaker: from 16 A
characteristic B or from 10 A characteristic C
Input
Input voltage
Input current
3/6
Siemens KT 10.1 · 2016
© Siemens AG 2016
LOGO!Power
1-phase, 12 V DC
■ Technical specifications (continued)
Article number
6EP1321-1SH03
6EP1322-1SH03
Product
LOGO!Power
LOGO!Power
Power supply, type
12 V/1.9 A
12 V/4.5 A
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
12 V
12 V
Total tolerance, static ±
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
1.5 %
1.5 %
Residual ripple peak-peak, max.
200 mV
200 mV
Residual ripple peak-peak, typ.
10 mV
10 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
300 mV
300 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)
20 mV
70 mV
Adjustment range
10.5 ... 16.1 V
10.5 ... 16.1 V
Product function Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
Status display
Green LED for output voltage OK
Green LED for output voltage OK
On/off behavior
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
Startup delay, max.
0.5 s
0.5 s
Voltage rise, typ.
10 ms
10 ms
Rated current value Iout rated
1.9 A
4.5 A
Current range
0 ... 1.9 A
0 ... 4.5 A
• Note
+55 ... +70 °C: Derating 2%/K
+55 ... +70 °C: Derating 2%/K
Supplied active power typical
23 W
50 W
Parallel switching for enhanced performance
Yes
Yes
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency at Vout rated, Iout rated, approx.
80 %
85 %
Power loss at Vout rated, Iout rated, approx.
5W
10 W
Power loss [W] during no-load operation
maximum
1.8 W
1.9 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.2 %
0.2 %
Dynamic load smoothing (Iout: 10/90/10 %),
Uout ± typ.
3%
4%
Load step setting time 10 to 90%, typ.
1 ms
1 ms
Load step setting time 90 to 10%, typ.
1 ms
1 ms
Output overvoltage protection
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Current limitation, typ.
2.8 A
5.8 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Constant current characteristic
Constant current characteristic
• maximum
3.6 A
7A
Overload/short-circuit indicator
-
-
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Output
3
Efficiency
Closed-loop control
Protection and monitoring
Enduring short circuit current RMS value
Safety
Protection class
Class II (without protective conductor)
Class II (without protective conductor)
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cURus-Recognized (UL 60950,
CSA C22.2 No. 60950), File E151273, NEC class 2
(acc. to UL 1310)
cULus-listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cURus-recognized (UL 60950,
CSA C22.2 No. 60950), File E151273
Explosion protection
ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
FM approval
Class I, Div. 2, Group ABCD, T4
Class I, Div. 2, Group ABCD, T4
CB approval
Yes
Yes
Marine approval
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
Siemens KT 10.1 · 2016
3/7
© Siemens AG 2016
LOGO!Power
1-phase, 12 V DC
■ Technical specifications (continued)
Article number
6EP1321-1SH03
6EP1322-1SH03
Product
LOGO!Power
LOGO!Power
Power supply, type
12 V/1.9 A
12 V/4.5 A
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
not applicable
not applicable
Noise immunity
EN 61000-6-2
EN 61000-6-2
-20 ... +70 °C
-20 ... +70 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
screw-type terminals
screw-type terminals
• Supply input
L, N: 1 screw terminal each for 0.5 ... 2.5 mm²
single-core/finely stranded
L, N: 1 screw terminal each for 0.5 ... 2.5 mm²
single-core/finely stranded
• Output
+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
• Auxiliary
-
-
Width of the enclosure
54 mm
72 mm
Height of the enclosure
90 mm
90 mm
Depth of the enclosure
52.6 mm
52.6 mm
Weight, approx.
0.17 kg
0.25 kg
Product feature of the enclosure housing for
side-by-side mounting
Yes
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
Snaps onto DIN rail EN 60715 35x7.5/15
MTBF at 40 °C
3 593 503 h
3 800 981 h
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
EMC
3
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
■ Ordering data
Article No.
LOGO!Power 1-phase,
12 V DC/1.9 A
Stabilized power supply
Input:
100 … 240 V AC (110 … 300 V DC)
Output: 12 V DC/1.9 A
6EP1321-1SH03
LOGO!Power 1-phase,
12 V DC/4.5 A
Stabilized power supply
Input:
100 … 240 V AC (110 … 300 V DC)
Output: 12 V DC/4.5 A
3/8
6EP1322-1SH03
Siemens KT 10.1 · 2016
© Siemens AG 2016
LOGO!Power
1-phase, 15 V DC
■ Overview
Our miniature power supply units in the same design as the logic
modules offer great performance in the smallest space: The
excellent efficiency across the entire load range, and the low
power losses in no-load operation ensure efficient operation.
The wide-range input for 1-phase networks as well as operation
with direct voltage, the wide operating temperature range, comprehensive certifications as well as the switch-on behavior optimized for capacitive loads makes them suitable for universal
use. These reliable power supplies with their flat, stepped profile
can be used extremely flexibly in numerous applications such as
in distribution boards, for example.
Main product highlights
• 15 V DC/ 1.9 A and 4 A
• 1-phase, wide-range input for 85 V to 264 V AC or 110 V to
300 V DC
• Flat LOGO! design with an installation depth of only 55 mm
• High efficiency across the entire load range, low no-load
losses
• Power reserve on starting up through 1.5 times the rated
current for capacitive loads
• Wide temperature range from -20 to +70 °C
• Comprehensive certifications, such as cULus, CB, FM, ATEX,
cCSAus Class I Div. 2, GL and ABS
■ Technical specifications
Article number
6EP1351-1SH03
6EP1352-1SH03
Product
LOGO!Power
LOGO!Power
Power supply, type
15 V/1.9 A
15 V/4 A
Input
1-phase AC or DC
1-phase AC or DC
Rated voltage value Vin rated
100 ... 240 V
100 ... 240 V
Voltage range AC
85 ... 264 V
85 ... 264 V
• at DC
110 ... 300 V
110 ... 300 V
Wide-range input
Yes
Yes
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
40 ms; at Vin = 187 V
40 ms; at Vin = 187 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 120 V
0.63 A
1.24 A
• at rated input voltage 230 V
0.33 A
0.68 A
Switch-on current limiting (+25 °C), max.
25 A
55 A
I²t, max.
0.8 A²·s
3 A²·s
Built-in incoming fuse
internal
internal
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker: from 16 A
characteristic B or from 10 A characteristic C
Recommended miniature circuit breaker: from 16 A
characteristic B or from 10 A characteristic C
Input
Input voltage
Input current
Siemens KT 10.1 · 2016
3/9
3
© Siemens AG 2016
LOGO!Power
1-phase, 15 V DC
■ Technical specifications (continued)
Article number
6EP1351-1SH03
6EP1352-1SH03
Product
LOGO!Power
LOGO!Power
Power supply, type
15 V/1.9 A
15 V/4 A
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
15 V
15 V
Total tolerance, static ±
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
1.5 %
1.5 %
Residual ripple peak-peak, max.
200 mV
200 mV
Residual ripple peak-peak, typ.
10 mV
10 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
300 mV
300 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)
30 mV
70 mV
Adjustment range
10.5 ... 16.1 V
10.5 ... 16.1 V
Product function Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
Status display
Green LED for output voltage OK
Green LED for output voltage OK
On/off behavior
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
Startup delay, max.
0.5 s
0.5 s
Voltage rise, typ.
15 ms
15 ms
Rated current value Iout rated
1.9 A
4A
Current range
0 ... 1.9 A
0 ... 4 A
• Note
+55 ... +70 °C: Derating 2%/K
+55 ... +70 °C: Derating 2%/K
Supplied active power typical
23 W
50 W
Parallel switching for enhanced performance
Yes
Yes
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency at Vout rated, Iout rated, approx.
81 %
85 %
Power loss at Vout rated, Iout rated, approx.
7W
11 W
Power loss [W] during no-load operation
maximum
2W
2.3 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.2 %
0.2 %
Dynamic load smoothing (Iout: 10/90/10 %),
Uout ± typ.
2.8 %
3%
Load step setting time 10 to 90%, typ.
1 ms
1 ms
Load step setting time 90 to 10%, typ.
1 ms
1 ms
Output overvoltage protection
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Current limitation, typ.
2.7 A
5.7 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Constant current characteristic
Constant current characteristic
• maximum
3.6 A
7A
Overload/short-circuit indicator
-
-
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Output
3
Efficiency
Closed-loop control
Protection and monitoring
Enduring short circuit current RMS value
Safety
Protection class
Class II (without protective conductor)
Class II (without protective conductor)
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cURus-Recognized (UL 60950,
CSA C22.2 No. 60950), File E151273, NEC class 2
(acc. to UL 1310)
cULus-Listed (UL 508, CSA C22.2 No. 107.1), F
ile E197259; cURus-Recognized (UL 60950,
CSA C22.2 No. 60950), File E151273, NEC class 2
(acc. to UL 1310)
Explosion protection
ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
FM approval
Class I, Div. 2, Group ABCD, T4
Class I, Div. 2, Group ABCD, T4
CB approval
Yes
Yes
Marine approval
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
3/10
Siemens KT 10.1 · 2016
© Siemens AG 2016
LOGO!Power
1-phase, 15 V DC
■ Technical specifications (continued)
Article number
6EP1351-1SH03
6EP1352-1SH03
Product
LOGO!Power
LOGO!Power
Power supply, type
15 V/1.9 A
15 V/4 A
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
not applicable
not applicable
Noise immunity
EN 61000-6-2
EN 61000-6-2
-20 ... +70 °C
-20 ... +70 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
screw-type terminals
screw-type terminals
• Supply input
L, N: 1 screw terminal each for 0.5 ... 2.5 mm²
single-core/finely stranded
L, N: 1 screw terminal each for 0.5 ... 2.5 mm²
single-core/finely stranded
• Output
+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
• Auxiliary
-
-
Width of the enclosure
54 mm
72 mm
Height of the enclosure
90 mm
90 mm
Depth of the enclosure
52.6 mm
52.6 mm
Weight, approx.
0.17 kg
0.25 kg
Product feature of the enclosure housing for
side-by-side mounting
Yes
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
Snaps onto DIN rail EN 60715 35x7.5/15
MTBF at 40 °C
3 593 503 h
3 800 981 h
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
EMC
3
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
■ Ordering data
Article No.
LOGO!Power 1-phase,
15 V DC/1.9 A
Stabilized power supply
Input:
100 … 240 V AC (110 … 300 V DC)
Output: 15 V DC/1.9 A
6EP1351-1SH03
LOGO!Power 1-phase,
15 V DC/4 A
Stabilized power supply
Input:
100 … 240 V AC (110 … 300 V DC)
Output: 15 V DC/4 A
6EP1352-1SH03
Siemens KT 10.1 · 2016
3/11
© Siemens AG 2016
LOGO!Power
1-phase, 24 V DC
■ Overview
Our miniature power supply units in the same design as the logic
modules offer great performance in the smallest space:
The excellent efficiency across the entire load range,
and the low power losses in no-load operation ensure efficient
operation. The wide-range input for 1-phase networks as well as
operation with direct voltage, the wide operating temperature
range, comprehensive certifications as well as the switch-on
behavior optimized for capacitive loads makes them suitable for
universal use. These reliable power supplies with their flat,
stepped profile can be used extremely flexibly in numerous
applications such as in distribution boards, for example.
3
To further increase the 24 V availability, the LOGO!Power power
supplies can be combined with DC UPS, redundancy and
selectivity modules.
Main product highlights
• 24 V DC/ 1.3 A, 2.5 A, and 4 A
• 1-phase, wide-range input for 85 V to 264 V AC or 110 V to
300 V DC
• Flat LOGO! design with an installation depth of only 55 mm
• High efficiency across the entire load range, low no-load
losses
• Power reserve on starting up through 1.5 times the rated
current for capacitive loads
• Wide temperature range from -20 to +70 °C
• Comprehensive certifications, such as cULus, CB, FM, SEMI
F47, ATEX, cCSAus Class I Div. 2, GL, ABS, DNV, BV and LRS
3/12
Siemens KT 10.1 · 2016
© Siemens AG 2016
LOGO!Power
1-phase, 24 V DC
■ Technical specifications
Article number
6EP1331-1SH03
6EP1332-1SH43
6EP1332-1SH52
Product
LOGO!Power
LOGO!Power
LOGO!Power
Power supply, type
24 V/1.3 A
24 V/2.5 A
24 V/4 A
Input
Input
1-phase AC or DC
1-phase AC or DC
1-phase AC or DC
Rated voltage value Vin rated
100 ... 240 V
100 ... 240 V
100 ... 240 V
Voltage range AC
85 ... 264 V
85 ... 264 V
85 ... 264 V
3
Input voltage
• at DC
110 ... 300 V
110 ... 300 V
110 ... 300 V
Wide-range input
Yes
Yes
Yes
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
40 ms; at Vin = 187 V
40 ms; at Vin = 187 V
40 ms; at Vin = 187 V
Rated line frequency 1
50 Hz
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
Input current
• at rated input voltage 120 V
0.7 A
1.22 A
1.95 A
• at rated input voltage 230 V
0.35 A
0.66 A
0.97 A
Switch-on current limiting (+25 °C),
max.
25 A
46 A
30 A
I²t, max.
0.8 A²·s
3 A²·s
2.5 A²·s
Built-in incoming fuse
internal
internal
internal
Protection in the mains power input
(IEC 898)
Recommended miniature circuit
breaker: from 16 A characteristic B
or from 10 A characteristic C
Recommended miniature circuit
breaker: from 16 A characteristic B
or from 10 A characteristic C
Recommended miniature circuit
breaker: from 16 A characteristic B
or from 10 A characteristic C
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
24 V
24 V
Total tolerance, static ±
3%
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
0.1 %
Static load balancing, approx.
1.5 %
1.5 %
1.5 %
Residual ripple peak-peak, max.
200 mV
200 mV
200 mV
Residual ripple peak-peak, typ.
10 mV
10 mV
30 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
300 mV
300 mV
300 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
20 mV
50 mV
60 mV
Adjustment range
22.2 ... 26.4 V
22.2 ... 26.4 V
22.2 ... 26.4 V
Product function Output voltage
adjustable
Yes
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
via potentiometer
Status display
Green LED for output voltage OK
Green LED for output voltage OK
Green LED for output voltage OK
On/off behavior
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
Startup delay, max.
0.5 s
0.5 s
0.5 s
Voltage rise, typ.
15 ms
10 ms
15 ms
Rated current value Iout rated
1.3 A
2.5 A
4A
Current range
0 ... 1.3 A
0 ... 2.5 A
0 ... 4 A
• Note
+55 ... +70 °C: Derating 2%/K
+55 ... +70 °C: Derating 2%/K
+55 ... +70 °C: Derating 2%/K
Supplied active power typical
30 W
60 W
96 W
Parallel switching for enhanced
performance
Yes
Yes
Yes
Numbers of parallel switchable units
for enhanced performance
2
2
2
Siemens KT 10.1 · 2016
3/13
© Siemens AG 2016
LOGO!Power
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1331-1SH03
6EP1332-1SH43
6EP1332-1SH52
Product
LOGO!Power
LOGO!Power
LOGO!Power
Power supply, type
24 V/1.3 A
24 V/2.5 A
24 V/4 A
Efficiency at Vout rated, Iout rated,
approx.
85 %
88 %
89 %
Power loss at Vout rated, Iout rated,
approx.
6W
8W
12 W
Power loss [W] during no-load
operation maximum
2W
1.8 W
2W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.2 %
0.2 %
0.2 %
Dynamic load smoothing
(Iout: 10/90/10 %), Uout ± typ.
1%
2%
1.5 %
Load step setting time 10 to 90%, typ. 1 ms
1 ms
1 ms
Load step setting time 90 to 10%, typ. 1 ms
1 ms
1 ms
Efficiency
3
Closed-loop control
Protection and monitoring
Output overvoltage protection
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Current limitation, typ.
1.7 A
3.3 A
5.2 A
Property of the output Short-circuit
proof
Yes
Yes
Yes
Short-circuit protection
Constant current characteristic
Constant current characteristic
Constant current characteristic
• maximum
2.4 A
4.8 A
7.9 A
Overload/short-circuit indicator
-
-
-
Enduring short circuit current RMS
value
Safety
Primary/secondary isolation
Yes
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Protection class
Class II (without protective conductor) Class II (without protective conductor) Class II (without protective conductor)
CE mark
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259; cURusRecognized (UL 60950, CSA C22.2
No. 60950), File E151273, NEC class 2
(acc. to UL 1310)
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259; cURusRecognized (UL 60950, CSA C22.2
No. 60950), File E151273, NEC class 2
(acc. to UL 1310)
cULus-listed (UL 508, CSA C22.2
No. 107.1), File E197259; cURusrecognized (UL 60950, CSA C22.2
No. 60950), File E151273
Explosion protection
ATEX (EX) II 3G Ex nA IIC T3; cCSAus
(CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
ATEX (EX) II 3G Ex nA IIC T3; cCSAus
(CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
ATEX (EX) II 3G Ex nA IIC T3; cCSAus
(CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
FM approval
Class I, Div. 2, Group ABCD, T4
Class I, Div. 2, Group ABCD, T4
Class I, Div. 2, Group ABCD, T4
CB approval
Yes
Yes
Yes
Marine approval
GL, ABS, BV, DNV, LRS
GL, ABS, BV, DNV, LRS
GL, ABS, BV, DNV, LRS
Degree of protection (EN 60529)
IP20
IP20
IP20
3/14
Siemens KT 10.1 · 2016
© Siemens AG 2016
LOGO!Power
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1331-1SH03
6EP1332-1SH43
6EP1332-1SH52
Product
LOGO!Power
LOGO!Power
LOGO!Power
Power supply, type
24 V/1.3 A
24 V/2.5 A
24 V/4 A
EMC
Emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
not applicable
not applicable
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
-20 ... +70 °C
-20 ... +70 °C
-20 ... +70 °C
with natural convection
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
Climate class 3K3, no condensation
screw-type terminals
screw-type terminals
screw-type terminals
• Supply input
L, N: 1 screw terminal each for
0.5 ... 2.5 mm² single-core/finely
stranded
L, N: 1 screw terminal each for
0.5 ... 2.5 mm² single-core/finely
stranded
L, N: 1 screw terminal each for
0.5 ... 2.5 mm² single-core/finely
stranded
• Output
+, -: 2 screw terminals each for
0.5 ... 2.5 mm²
+, -: 2 screw terminals each for
0.5 ... 2.5 mm²
+, -: 2 screw terminals each for
0.5 ... 2.5 mm²
• Auxiliary
-
-
-
Width of the enclosure
54 mm
72 mm
90 mm
Height of the enclosure
90 mm
90 mm
90 mm
Depth of the enclosure
52.6 mm
52.6 mm
52.6 mm
Weight, approx.
0.17 kg
0.25 kg
0.34 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Yes
Installation
Snaps onto DIN rail EN 60715
35x7.5/15
Snaps onto DIN rail EN 60715
35x7.5/15
Snaps onto DIN rail EN 60715
35x7.5/15
MTBF at 40 °C
3 586 929 h
3 723 563 h
3 608 805 h
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
3
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
Siemens KT 10.1 · 2016
3/15
© Siemens AG 2016
LOGO!Power
1-phase, 24 V DC
■ Ordering data
Article No.
LOGO!Power 1-phase,
24 V DC/1.3 A
Stabilized power supply
Input:
100 … 240 V AC (110 … 300 V DC)
Output: 24 V DC/1.3 A
3
SITOP PSE202U redundancy
module
6EP1331-1SH03
LOGO!Power 1-phase,
24 V DC/2.5 A
Stabilized power supply
Input:
100 … 240 V AC (110 … 300 V DC)
Output: 24 V DC/2.5 A
6EP1332-1SH43
3/16
Article No.
6EP1962-2BA00
Input/output:
24 V DC/NEC Class 2
suitable for decoupling two SITOP
power supplies output power
limited < 100 VA
SITOP PSE202U redundancy
module
6EP1964-2BA00
Input/output:
24 V DC/10 A
suitable for decoupling two SITOP
power supplies with a maximum of
5 A output current
LOGO!Power 1-phase,
24 V DC/4 A
Stabilized power supply
Input:
100 … 240 V AC (110 … 300 V DC)
Output: 24 V DC/4 A
■ Accessories
6EP1332-1SH52
Siemens KT 10.1 · 2016
SITOP PSE200U 3 A selectivity
module
4-channel selectivity module
Input: 24 V DC
Output: 24 V DC/3A per each
channel output current adjustable
0.5 … 3 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA11
6EP1961-2BA31
4
© Siemens AG 2016
SITOP lite
4/2
1-phase, DC 24 V
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP lite
1-phase, 24 V
■ Overview
The single-phase SITOP lite power supplies are designed for
basic requirements in industrial environments and offer all the
key functions at an attractive price. Thanks to the slim design,
the power supplies require little space on the standard mounting
rail, and their excellent efficiency ensures low thermal losses in
the control cabinet.
To further increase 24 V availability, the SITOP lite power
supplies can be combined with DC UPS, redundancy and
selectivity modules.
Main product highlights
• 24 V DC/ 2.5 A, 5 A and 10 A
• 1-phase wide-range input with manual switchover
• Slim design - no lateral installation clearances required
• High degree of efficiency
• Green LED for "24 V OK"
• Adjustable output voltage for compensating voltage drops
• Parallel connection possible
• Ambient temperature range of 0 °C to 60 °C
(above 45 °C with derating)
• Short-circuit and overload protection
• Certification to CE, cULus and CD
4
■ Technical specifications
Article number
6EP1332-1LB00
6EP1333-1LB00
6EP1334-1LB00
Product
SITOP PSU100L
SITOP PSU100L
SITOP PSU100L
Power supply, type
24 V/2.5 A
24 V/5 A
24 V/10 A
1-phase AC
1-phase AC
1-phase AC
Input
Input
Supply voltage
• 1 at AC Rated value
120 V
120 V
120 V
• 2 at AC Rated value
230 V
230 V
230 V
• Note
Set by means of selector switch
on the device
Set by means of selector switch
on the device
Set by means of selector switch
on the device
Input voltage
• 1 at AC
93 ... 132 V
93 ... 132 V
93 ... 132 V
• 2 at AC
187 ... 264 V
187 ... 264 V
187 ... 264 V
Wide-range input
No
No
No
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
20 ms; at Vin = 93/187 V
20 ms; at Vin = 93/187 V
20 ms; at Vin = 93/187 V
Rated line frequency 1
50 Hz
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 120 V
1.1 A
2.1 A
4.1 A
• at rated input voltage 230 V
0.65 A
1.15 A
2A
Input current
4/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP lite
1-phase, 24 V
■ Technical specifications (continued)
Article number
6EP1332-1LB00
6EP1333-1LB00
6EP1334-1LB00
Product
SITOP PSU100L
SITOP PSU100L
SITOP PSU100L
Power supply, type
24 V/2.5 A
24 V/5 A
24 V/10 A
Switch-on current limiting (+25 °C),
max.
27 A
32 A
65 A
Duration of inrush current limiting at
25 °C
• typical
3 ms
3 ms
3 ms
I²t, max.
0.3 A²·s
0.8 A²·s
3.3 A²·s
Built-in incoming fuse
T 2 A/250 V (not accessible)
T 3,15 A/250 V (not accessible)
T 6.3 A/250 V (not accessible)
Protection in the mains power input
(IEC 898)
Recommended miniature circuit
breaker: from 3 A characteristic C
Recommended miniature circuit
breaker: from 6 A characteristic C
Recommended miniature circuit
breaker: from 10 A characteristic C
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
24 V
24 V
Total tolerance, static ±
3%
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
0.1 %
Static load balancing, approx.
0.5 %
0.5 %
0.5 %
Residual ripple peak-peak, max.
150 mV
150 mV
150 mV
Residual ripple peak-peak, typ.
10 mV
50 mV
50 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
240 mV
240 mV
240 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
50 mV
150 mV
150 mV
Adjustment range
22.8 ... 26.4 V
22.8 ... 26.4 V
22.8 ... 26.4 V
Product function Output voltage
adjustable
Yes
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
via potentiometer
Status display
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
On/off behavior
Overshoot of Vout approx. 4 %
Overshoot of Vout approx. 4 %
Overshoot of Vout approx. 4 %
Startup delay, max.
1.5 s
1.5 s
1.5 s
Voltage rise, typ.
150 ms
130 ms
170 ms
Rated current value Iout rated
2.5 A
5A
10 A
Current range
0 ... 2.5 A
0 ... 5 A
0 ... 10 A
• Note
+45 ... +60 °C: Derating 2%/K
+45 ... +60 °C: Derating 2%/K
+45 ... +60 °C: Derating 2%/K
Supplied active power typical
60 W
120 W
240 W
Parallel switching for enhanced
performance
Yes
Yes
Yes
Numbers of parallel switchable units
for enhanced performance
2
2
2
Efficiency at Vout rated, Iout rated,
approx.
85 %
86 %
89 %
Power loss at Vout rated, Iout rated,
approx.
9W
17 W
34 W
Efficiency
Siemens KT 10.1 · 2016
4/3
4
© Siemens AG 2016
SITOP lite
1-phase, 24 V
■ Technical specifications (continued)
Article number
6EP1332-1LB00
6EP1333-1LB00
6EP1334-1LB00
Product
SITOP PSU100L
SITOP PSU100L
SITOP PSU100L
Power supply, type
24 V/2.5 A
24 V/5 A
24 V/10 A
Dynamic mains compensation
(Vin rated ±15 %), max.
0.3 %
0.3 %
0.3 %
Dynamic load smoothing
(Iout: 10/90/10 %), Uout ± typ.
2%
2%
2%
Load step setting time 10 to 90%, typ. 0.5 ms
0.4 ms
0.5 ms
Load step setting time 90 to 10%, typ. 0.7 ms
0.4 ms
0.7 ms
Closed-loop control
4
Protection and monitoring
Output overvoltage protection
< 33 V
< 33 V
< 33 V
Current limitation, typ.
2.6 A
5.25 A
10.5 A
Property of the output
Short-circuit proof
Yes
Yes
Yes
Short-circuit protection
Constant current characteristic
Constant current characteristic
Constant current characteristic
• typical
4A
8A
16 A
Overload/short-circuit indicator
-
-
-
Enduring short circuit current
RMS value
Safety
Primary/secondary isolation
Yes
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Protection class
Class I
Class I
Class I
Leakage current
• maximum
3.5 mA
3.5 mA
3.5 mA
• typical
0.4 mA
0.4 mA
0.8 mA
CE mark
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259
Explosion protection
-
-
-
FM approval
-
-
-
CB approval
Yes
Yes
Yes
Marine approval
-
-
-
Degree of protection (EN 60529)
IP20
IP20
IP20
4/4
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP lite
1-phase, 24 V
■ Technical specifications (continued)
Article number
6EP1332-1LB00
6EP1333-1LB00
6EP1334-1LB00
Product
SITOP PSU100L
SITOP PSU100L
SITOP PSU100L
Power supply, type
24 V/2.5 A
24 V/5 A
24 V/10 A
EMC
Emitted interference
EN 55022 Class A
EN 55022 Class A
EN 55022 Class A
Supply harmonics limitation
not applicable
-
-
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
0 ... 60 °C
0 ... 60 °C
0 ... 60 °C
with natural convection
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
Climate class 3K3, no condensation
screw-type terminals
screw-type terminals
screw-type terminals
• Supply input
L, N, PE: 1 screw terminal
each for 0.5 ... 2.5 mm²
single-core/finely stranded
L, N, PE: 1 screw terminal
each for 0.5 ... 2.5 mm²
single-core/finely stranded
L, N, PE: 1 screw terminal
each for 0.5 ... 2.5 mm²
single-core/finely stranded
• Output
+, -: 2 screw terminals
each for 0.5 ... 2.5 mm²
+, -: 2 screw terminals
each for 0.5 ... 2.5 mm²
+, -: 2 screw terminals
each for 0.5 ... 2.5 mm²
• Auxiliary
-
-
-
Width of the enclosure
32.5 mm
50 mm
70 mm
Height of the enclosure
125 mm
125 mm
125 mm
Depth of the enclosure
120 mm
120 mm
120 mm
0.5 kg
0.75 kg
Operating data
Ambient temperature
• during operation
- Note
4
Mechanics
Connection technology
Connections
Weight, approx.
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Yes
Installation
Snaps onto DIN rail EN 60715
35x7.5/15
Snaps onto DIN rail EN 60715
35x7.5/15
Snaps onto DIN rail EN 60715
35x7.5/15
MTBF at 40 °C
3 153 082 h
3 076 166 h
2 333 396 h
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Siemens KT 10.1 · 2016
4/5
© Siemens AG 2016
SITOP lite
1-phase, 24 V
■ Ordering data
SITOP PSU100L 1-phase,
24 V DC/2.5 A
Article No.
6EP1332-1LB00
Stabilized power supply
Input: 120/230 V AC
Output: 24 V DC/2.5 A
SITOP PSU100L 1-phase,
24 V DC/5 A
6EP1333-1LB00
SITOP PSU100L 1-phase,
24 V DC/10 A
SITOP PSE202U redundancy
module
6EP1334-1LB00
Stabilized power supply
Input: 120/230 V AC
Output: 24 V DC/10 A
Article No.
6EP1962-2BA00
Input/output: 24 V DC/NEC Class 2
suitable for decoupling two
SITOP power supplies output
power limited < 100 VA
SITOP PSE202U redundancy
module
Stabilized power supply
Input: 120/230 V AC
Output: 24 V DC/5 A
4
■ Accessories
6EP1964-2BA00
Input/output: 24 V DC/10 A
suitable for decoupling two
SITOP power supplies with a
maximum of 5 A output current
SITOP PSE200U 3 A selectivity
module
4-channel selectivity module
Input: 24 V DC
Output: 24 V DC/3A
per each channel
output current adjustable 0.5 … 3 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA11
6EP1961-2BA31
SITOP PSE200U 10 A selectivity
module
4-channel selectivity module
Input: 24 V DC
Output: 24 V DC/10 A per channel
output current adjustable 3 ... 10 A
• With common alarm signal
• With single-channel signaling
4/6
Siemens KT 10.1 · 2016
6EP1961-2BA21
6EP1961-2BA41
5
© Siemens AG 2016
SITOP smart
5/2
5/3
5/7
5/13
Introduction
1-phase, 12 V DC
1-phase, 24 V DC
3-phase, 24 V DC
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP smart
Introduction
■ Overview
■ More information
Select the appropriate power supply quickly and easily with the
SITOP Selection Tool:
http://www.siemens.com/sitop-selection-tool
5
The powerful standard power supply
The one-phase and three-phase SITOP smart are the universal
and powerful standard power supplies for machinery and plant
engineering. Despite their compact design, they offer an excellent overload response: Thanks to an extra power of 150 %,
loads with high power consumption can be connected without
any problems and the permanent overload capability of 120%
offers power reserves in case of expansions. The high degree of
efficiency results in low energy consumption and minimal heat
generation inside the control cabinet.
To further increase the 24 V availability, the SITOP smart power
supplies can be combined with buffer, DC UPS, redundancy
and selectivity modules.
Main product highlights
• 1-phase, 24 V DC/2.5 A, 5 A, 10 A and 20 A as well as 
12 V/7 A and 14 A
• 3-phase, 24 V DC/5 A, 10 A, 20 A and 40 A
• Compact design - no lateral clearances required
• Extra power with 1.5 times the rated current (5 s/min) for brief
functional overload
• Permanent overload capability with 1.2 times the rated current
up to 45 °C ambient temperature (24 V versions)
• High degree of efficiency up to 91.5 %
• Adjustable output voltage for compensating voltage drops
• Signaling contact for easy integration in the plant monitoring
system
• Wide temperature range from -25 or -10 to +70 °C
• Comprehensive certifications, such as cULus, cCSAus, ATEX,
IECEx and GL
5/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP smart
1-phase, 12 V DC
■ Overview
The one-phase SITOP smart are the universal and powerful
standard power supplies for machinery and plant engineering.
Despite their compact design, they offer an excellent overload
response: Thanks to an extra power of 150 %, loads with high
power consumption can be connected without any problems.
The high degree of efficiency results in low energy consumption
and minimal heat generation inside the control cabinet.
Main product highlights
• 1-phase, 12 V DC/7 A and 14 A
• Input voltage 120 V and 230 V AC with automatic range
switching
• Compact design - no lateral clearances required
• Extra power with 1.5 times the rated current (5 s/min) for brief
functional overload
• Adjustable output voltage for compensating voltage drops
• Signaling contact for easy integration in the plant monitoring
system
• Wide temperature range from -25 to +70 °C
• Comprehensive certifications, such as cULus, cCSAus, ATEX,
IECEx and GL
■ Technical specifications
Article number
6EP1322-2BA00
6EP1323-2BA00
Product
SITOP PSU100S
SITOP PSU100S
Power supply, type
12 V/7 A
12 V/14 A
1-phase AC
1-phase AC
• 1 at AC Rated value
120 V
120 V
• 2 at AC Rated value
230 V
230 V
• Note
Automatic range selection
Automatic range selection
• 1 at AC
85 ... 132 V
85 ... 132 V
• 2 at AC
170 ... 264 V
170 ... 264 V
Wide-range input
No
No
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
20 ms; at Vin = 93/187 V
20 ms; at Vin = 93/187 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 120 V
1.73 A
3.24 A
• at rated input voltage 230 V
0.99 A
1.41 A
Switch-on current limiting (+25 °C), max.
45 A
60 A
Built-in incoming fuse
T 3,15 A/250 V (not accessible)
T 6.3 A/250 V (not accessible)
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker: 
from 6 A characteristic C
Recommended miniature circuit breaker:
from 10 A characteristic C
Input
Input
Supply voltage
Input voltage
Input current
Siemens KT 10.1 · 2016
5/3
5
© Siemens AG 2016
SITOP smart
1-phase, 12 V DC
■ Technical specifications (continued)
Article number
6EP1322-2BA00
6EP1323-2BA00
Product
SITOP PSU100S
SITOP PSU100S
Power supply, type
12 V/7 A
12 V/14 A
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
12 V
12 V
Total tolerance, static ±
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
1%
1%
Residual ripple peak-peak, max.
150 mV
150 mV
Residual ripple peak-peak, typ.
20 mV
20 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
240 mV
240 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)
100 mV
100 mV
Adjustment range
11.5 ... 15.5 V
11.5 ... 15.5 V
Product function Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
Status display
Green LED for 12 V OK
Green LED for 12 V OK
Signaling
Relay contact 
(NO contact, rating 60 V DC/ 0.3 A) for 12 V OK
Relay contact 
(NO contact, rating 60 V DC/ 0.3 A) for 12 V OK
On/off behavior
Overshoot of Vout < 3 %
Overshoot of Vout < 3 %
Startup delay, max.
0.3 s
0.3 s
Voltage rise, typ.
10 ms
10 ms
Rated current value Iout rated
7A
14 A
Current range
0 ... 7 A
0 ... 14 A
• Note
+50 ... +70 °C: Derating 0.75%/K
+50 ... +70 °C: Derating 3.5%/K
Supplied active power typical
84 W
168 W
• on short-circuiting during the start-up typical
25 A
40 A
• at short-circuit during operation typical
25 A
40 A
• on short-circuiting during the start-up
800 ms
800 ms
• at short-circuit during operation
800 ms
800 ms
Parallel switching for enhanced performance
Yes
Yes
Numbers of parallel switchable units for enhanced
performance
2
2
Efficiency at Vout rated, Iout rated, approx.
84 %
87 %
Power loss at Vout rated, Iout rated, approx.
15 W
24 W
Dynamic load smoothing (Iout: 10/90/10 %), 
Uout ± typ.
5%
5%
Load step setting time 10 to 90%, typ.
1 ms
1 ms
Load step setting time 90 to 10%, typ.
1 ms
1 ms
Output
5
Short-term overload current
Duration of overloading capability for excess current
Efficiency
Closed-loop control
5/4
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP smart
1-phase, 12 V DC
■ Technical specifications (continued)
Article number
6EP1322-2BA00
6EP1323-2BA00
Product
SITOP PSU100S
SITOP PSU100S
Power supply, type
12 V/7 A
12 V/14 A
Output overvoltage protection
< 20 V
< 20 V
Current limitation
7 ... 8.8 A
14 ... 16.4 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Constant current characteristic
Constant current characteristic
8.8 A
16.4 A
Protection and monitoring
Enduring short circuit current RMS value
• typical
Overcurrent overload capability in normal operation overload capability 150 % Iout rated up to 5 s/min
overload capability 150 % Iout rated up to 5 s/min
-
-
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
• maximum
3.5 mA
3.5 mA
• typical
0.4 mA
0.8 mA
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1), 
File E197259, cCSAus (CSA C22.2 No. 60950-1, 
UL 60950-1, UL 1604)
cULus-Listed (UL 508, CSA C22.2 No. 107.1), 
File E197259, cCSAus (CSA C22.2 No. 60950-1, 
UL 60950-1, UL 1604)
Explosion protection
IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA
nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group
ABCD, T4
IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA
nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group
ABCD, T4
FM approval
-
-
CB approval
Yes
Yes
Marine approval
GL
GL
Degree of protection (EN 60529)
IP20
IP20
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
-25 ... +70 °C
-25 ... +70 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
Overload/short-circuit indicator
Safety
5
Leakage current
EMC
Operating data
Ambient temperature
• during operation
- Note
Siemens KT 10.1 · 2016
5/5
© Siemens AG 2016
SITOP smart
1-phase, 12 V DC
■ Technical specifications (continued)
Article number
6EP1322-2BA00
6EP1323-2BA00
Product
SITOP PSU100S
SITOP PSU100S
Power supply, type
12 V/7 A
12 V/14 A
screw-type terminals
screw-type terminals
• Supply input
L, N, PE: 1 screw terminal each for 
0.5 ... 2.5 mm² single-core/finely stranded
L, N, PE: 1 screw terminal each for 
0.5 ... 2.5 mm² single-core/finely stranded
• Output
+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
• Auxiliary
Alarm signals: 2 screw terminals for 0.5 ... 2.5 mm²
Alarm signals: 2 screw terminals for 0.5 ... 2.5 mm²
Connections signaling contact
2 screw terminals for 0.5 ... 2.5 mm²
2 screw terminals for 0.5 ... 2.5 mm²
Width of the enclosure
50 mm
70 mm
Height of the enclosure
125 mm
125 mm
Depth of the enclosure
120 mm
120 mm
Weight, approx.
0.5 kg
0.7 kg
Product feature of the enclosure housing for 
side-by-side mounting
Yes
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
Snaps onto DIN rail EN 60715 35x7.5/15
MTBF at 40 °C
1 998 441 h
1 614 510 h
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Mechanics
Connection technology
Connections
5
■ Ordering data
Article No.
Select the appropriate power supply quickly and easily with the
SITOP Selection Tool:
SITOP PSU100S 1-phase,
12 V DC/7 A
Stabilized power supply
Input: 120/230 V AC
Output: 12 V DC/7 A
6EP1322-2BA00
SITOP PSU100S 1-phase,
12 V DC/14 A
Stabilized power supply
Input: 120/230 V AC 
Output: 12 V DC/14 A
5/6
■ More information
6EP1323-2BA00
Siemens KT 10.1 · 2016
http://www.siemens.com/sitop-selection-tool
© Siemens AG 2016
SITOP smart
1-phase, 24 V DC
■ Overview
The one-phase SITOP smart are the universal and powerful
standard power supplies for machinery and plant engineering.
Despite their compact design, they offer an excellent overload
response: Thanks to an extra power of 150 %, loads with high
power consumption can be connected without any problems
and the permanent overload capability of 120% offers power
reserves in case of expansions. The high degree of efficiency
results in low energy consumption and minimal heat generation
inside the control cabinet.
To further increase 24 V availability, the SITOP smart power
supplies can be combined with buffer, DC UPS, redundancy
and selectivity modules.
Main product highlights
• 1-phase, 24 V DC/2.5 A, 5 A, 10 A and 20 A
• Input voltage 120 V and 230 V AC with automatic range
switching
• Compact design - no lateral clearances required
• Extra power with 1.5 times the rated current (5 s/min) for brief
functional overload
• Permanent overload capability with 1.2 times the rated current
up to 45 °C ambient temperature
• Adjustable output voltage for compensating voltage drops
• Signaling contact for easy integration in the plant monitoring
system
• Wide temperature range from -25 or 0 to +70 °C
• Comprehensive certifications, such as cULus, cCSAus, ATEX,
IECEx and GL
Siemens KT 10.1 · 2016
5/7
5
© Siemens AG 2016
SITOP smart
1-phase, 24 V DC
■ Technical specifications
Article number
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Product
SITOP PSU100S
SITOP PSU100S
SITOP PSU100S
SITOP PSU100S
Power supply, type
24 V/2.5 A
24 V/5 A
24 V/10 A
24 V/20 A
1-phase AC
1-phase AC
1-phase AC
1-phase AC
• 1 at AC Rated value
120 V
120 V
120 V
120 V
• 2 at AC Rated value
230 V
230 V
230 V
230 V
• Note
Automatic range selection
Automatic range selection
Automatic range selection
Automatic range selection
• 1 at AC
85 ... 132 V
85 ... 132 V
85 ... 132 V
85 ... 132 V
• 2 at AC
170 ... 264 V
170 ... 264 V
170 ... 264 V
176 ... 264 V
Wide-range input
No
No
No
No
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
20 ms; at Vin = 93/187 V
20 ms; at Vin = 93/187 V
20 ms; at Vin = 93/187 V
20 ms; at Vin = 120/230 V
Rated line frequency 1
50 Hz
50 Hz
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 120 V
1.25 A
2.34 A
4.49 A
7.5 A
• at rated input voltage 230 V
0.74 A
1.36 A
1.91 A
3.5 A
Switch-on current limiting (+25 °C),
max.
33 A
40 A
60 A
11 A
I²t, max.
0.4 A²·s
1 A²·s
5.6 A²·s
10 A²·s
Built-in incoming fuse
T 3,15 A/250 V 
(not accessible)
T 3,15 A/250 V 
(not accessible)
T 6.3 A/250 V 
(not accessible)
T 10 A 
(not accessible)
Protection in the mains power input
(IEC 898)
Recommended miniature
circuit breaker: 
from 3 A characteristic C
Recommended miniature
circuit breaker: 
from 6 A characteristic C
Recommended miniature
circuit breaker: 
from 10 A characteristic C
Recommended miniature
circuit breaker: from 10 A
characteristic C or 
circuit-breaker 
3RV2411-1JA10 (120 V) or
3RV2411-1FA10 (230 V)
Input
Input
Supply voltage
Input voltage
5
Input current
5/8
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP smart
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Product
SITOP PSU100S
SITOP PSU100S
SITOP PSU100S
SITOP PSU100S
Power supply, type
24 V/2.5 A
24 V/5 A
24 V/10 A
24 V/20 A
Output
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Rated voltage Vout DC
24 V
24 V
24 V
24 V
Total tolerance, static ±
3%
3%
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
0.1 %
0.5 %
Static load balancing, approx.
1%
1%
1%
1%
Residual ripple peak-peak, max.
150 mV
150 mV
150 mV
150 mV
Residual ripple peak-peak, typ.
30 mV
30 mV
20 mV
Spikes peak-peak, max. 
(bandwidth: 20 MHz)
240 mV
240 mV
240 mV
Spikes peak-peak, typ. 
(bandwidth: 20 MHz)
70 mV
140 mV
160 mV
Adjustment range
22.8 ... 28 V
22.8 ... 28 V
22.8 ... 28 V
24 ... 28 V
Product function Output voltage
adjustable
Yes
Yes
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
via potentiometer
via potentiometer; 
max. 480 W
Status display
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
Signaling
Relay contact 
Relay contact 
Relay contact 
Relay contact 
(NO contact, rating 
(NO contact, rating 
(NO contact, rating 
(NO contact, rating 
60 V DC/ 0.3 A) for "24 V OK" 60 V DC/ 0.3 A) for "24 V OK" 60 V DC/ 0.3 A) for "24 V OK" 50 V DC/ 0.3 A) for "24 V OK"
On/off behavior
Overshoot of Vout < 3 %
Overshoot of Vout < 3 %
Overshoot of Vout < 3 %
No overshoot of Vout 
(soft start)
Startup delay, max.
0.3 s
0.3 s
0.3 s
1.5 s
Voltage rise, typ.
15 ms
15 ms
20 ms
50 ms
Output
240 mV
5
500 ms
Voltage increase time of the output
voltage maximum
Rated current value Iout rated
2.5 A
5A
10 A
20 A
Current range
0 ... 3 A
0 ... 6 A
0 ... 12 A
0 ... 20 A
• Note
3 A up to +45°C; 
+60 ... +70 °C: 
Derating 3%/K
6 A up to +45°C; 
+60 ... +70 °C: 
Derating 1.6%/K
12 A up to +45°C;
+60 ... +70 °C: 
Derating 3%/K
24 A up to +45°C; 
+60 ... +70 °C: 
Derating 5%/K
Supplied active power typical
60 W
144 W
288 W
480 W
• on short-circuiting during the 
start-up typical
9A
18 A
32 A
35 A
• at short-circuit during operation
typical
9A
18 A
32 A
35 A
• on short-circuiting during the 
start-up
100 ms
800 ms
1 000 ms
100 ms
• at short-circuit during operation
800 ms
800 ms
1 000 ms
100 ms
Parallel switching for enhanced
performance
Yes
Yes
Yes
Yes
Numbers of parallel switchable units
for enhanced performance
2
2
2
2
Short-term overload current
Duration of overloading capability 
or excess current
Siemens KT 10.1 · 2016
5/9
© Siemens AG 2016
SITOP smart
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Product
SITOP PSU100S
SITOP PSU100S
SITOP PSU100S
SITOP PSU100S
Power supply, type
24 V/2.5 A
24 V/5 A
24 V/10 A
24 V/20 A
Efficiency at Vout rated, Iout rated,
approx.
85 %
88 %
90 %
90 %
Power loss at Vout rated, Iout rated,
approx.
10 W
16 W
25 W
53 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.3 %
0.3 %
0.3 %
1%
Dynamic load smoothing 
(Iout: 50/100/50 %), Uout ± typ.
-
-
-
3%
Dynamic load smoothing 
(Iout: 10/90/10 %), Uout ± typ.
5%
3%
3%
-
Load step setting time 10 to 90%, typ. 1 ms
1 ms
1 ms
-
Load step setting time 90 to 10%, typ. 1 ms
1 ms
1 ms
-
-
-
-
10 ms
Output overvoltage protection
protection against
overvoltage in case of
internal fault Vout < 33 V
protection against
overvoltage in case of
internal fault Vout < 33 V
protection against
overvoltage in case of
internal fault Vout < 33 V
Yes, according to 
EN 60950-1
Efficiency
Closed-loop control
5
Setting time maximum
Protection and monitoring
Current limitation
3 ... 3.4 A
6 ... 7.1 A
12 ... 14.6 A
Current limitation, typ.
-
-
-
21 A
Property of the output 
Short-circuit proof
Yes
Yes
Yes
Yes
Short-circuit protection
Constant current 
characteristic
Constant current 
characteristic
Constant current 
characteristic
Electronic shutdown,
automatic restart
• maximum
-
-
-
7A
• typical
3.4 A
7.1 A
14.6 A
-
Overcurrent overload capability in
normal operation
overload capability 150 %
Iout rated up to 5 s/min
overload capability 150 %
Iout rated up to 5 s/min
overload capability 150 %
Iout rated up to 5 s/min
overload capability 150 %
Iout rated up to 5 s/min
Overload/short-circuit indicator
-
-
-
-
Primary/secondary isolation
Yes
Yes
Yes
Yes
Galvanic isolation
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
Class I
Class I
• maximum
3.5 mA
3.5 mA
3.5 mA
3.5 mA
• typical
0.4 mA
0.4 mA
0.8 mA
1 mA
CE mark
Yes
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259, cCSAus 
(CSA C22.2 No. 60950-1, 
UL 60950-1, UL 1604)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259, cCSAus
(CSA C22.2 No. 60950-1, 
UL 60950-1, UL 1604)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259, cCSAus 
(CSA C22.2 No. 60950-1, 
UL 60950-1, UL 1604)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259; cCSAus
(CSA C22.2 No. 60950-1,
UL 60950-1)
Explosion protection
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA12.12.01-2007) Class I, 
Div. 2, Group ABCD, T4
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA12.12.01-2007) Class I, 
Div. 2, Group ABCD, T4
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA12.12.01-2007) Class I, 
Div. 2, Group ABCD, T4
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T4
FM approval
-
-
-
-
CB approval
Yes
Yes
Yes
Yes
Marine approval
GL, BV
GL, BV
GL, BV
GL
Degree of protection (EN 60529)
IP20
IP20
IP20
IP20
Enduring short circuit current 
RMS value
Safety
Leakage current
5/10
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP smart
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Product
SITOP PSU100S
SITOP PSU100S
SITOP PSU100S
SITOP PSU100S
Power supply, type
24 V/2.5 A
24 V/5 A
24 V/10 A
24 V/20 A
Emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
not applicable
EN 61000-3-2
EN 61000-3-2
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
-25 ... +70 °C
-25 ... +70 °C
-25 ... +70 °C
0 ... 70 °C
with natural convection
with natural convection
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
screw-type terminals
screw-type terminals
screw-type terminals
screw-type terminals
• Supply input
L, N, PE: 1 screw terminal
each for 0.5 ... 2.5 mm²
single-core/finely stranded
L, N, PE: 1 screw terminal
each for 0.5 ... 2.5 mm²
single-core/finely stranded
L, N, PE: 1 screw terminal
each for 0.5 ... 2.5 mm²
single-core/finely stranded
L1, N, PE: 1 screw terminal
each for 0.2 ... 4 mm² 
single-core/finely stranded
• Output
+, -: 2 screw terminals 
each for 0.5 ... 2.5 mm²
+, -: 2 screw terminals 
each for 0.5 ... 2.5 mm²
+, -: 2 screw terminals 
each for 0.5 ... 2.5 mm²
+, -: 2 screw terminals 
each for 0.2 ... 4 mm²
• Auxiliary
Alarm signals: 
2 screw terminals for
0.5 ... 2.5 mm²
Alarm signals: 
2 screw terminals for
0.5 ... 2.5 mm²
Alarm signals: 
2 screw terminals for
0.5 ... 2.5 mm²
13, 14 (alarm signal): 
1 screw terminal each for
0.14 ... 1.5 mm²
Connections signaling contact
2 screw terminals for 
0.5 ... 2.5 mm²
2 screw terminals for 
0.5 ... 2.5 mm²
2 screw terminals for
0.5 ... 2.5 mm²
Width of the enclosure
32.5 mm
50 mm
70 mm
115 mm
Height of the enclosure
125 mm
125 mm
125 mm
145 mm
Depth of the enclosure
120 mm
120 mm
120 mm
150 mm
Weight, approx.
0.32 kg
0.5 kg
0.8 kg
2.4 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Yes
Yes
Installation
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Electrical accessories
Buffer module
Buffer module
Buffer module
Buffer module
Mechanical accessories
-
-
-
Device identification label
20 mm × 7 mm, pale
turquoise 3RT1900-1SB20
MTBF at 40 °C
1 804 044 h
1 998 441 h
1 614 510 h
1 778 916 h
Other information
Specifications at rated input
voltage and ambient
temperature +25 °C 
(unless otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C
(unless otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C 
(unless otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C 
(unless otherwise specified)
EMC
Operating data
Ambient temperature
• during operation
- Note
5
Mechanics
Connection technology
Connections
Siemens KT 10.1 · 2016
5/11
© Siemens AG 2016
SITOP smart
1-phase, 24 V DC
■ Ordering data
SITOP PSU100S 1-phase,
24 V DC/2.5 A
Article No.
6EP1332-2BA20
Stabilized power supply
Input: 120/230 V AC 
Output: 24 V DC/2.5 A
SITOP PSU100S 1-phase,
24 V DC/5 A
6EP1333-2BA20
6EP1334-2BA20
6EP1961-3BA21
6EP1962-2BA00
Input/output: 24 V DC/NEC Class 2 
suitable for decoupling two SITOP
power supplies output power
limited < 100 VA
6EP1964-2BA00
Input/output: 24 V DC/10 A 
suitable for decoupling two SITOP
power supplies with a maximum of
5 A output current
SITOP PSU100S 1-phase,
24 V DC/20 A
Stabilized power supply
Input: 120/230 V AC 
Output: 24 V DC/20 A
Article No.
Input/output: 24 V DC/40 A 
suitable for decoupling two SITOP
power supplies with a maximum of
20 A output current
SITOP PSE202U 
redundancy module
Stabilized power supply
Input: 120/230 V AC 
Output: 24 V DC / 10 A
5
SITOP PSE202U 
redundancy module
SITOP PSE202U
redundancy module
Stabilized power supply
Input: 120/230 V AC 
Output: 24 V DC/5 A
SITOP PSU100S 1-phase,
24 V DC/10 A
■ Accessories
6EP1336-2BA10
SITOP PSE200U 3 A 
selectivity module
4-channel selectivity module 
Input: 24 V DC 
Output: 24 V DC/3A per each
channel 
output current adjustable 0.5 … 3 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA11
6EP1961-2BA31
SITOP PSE200U 10 A
selectivity module
4-channel selectivity module 
Input: 24 V DC 
Output: 24 V DC/10 A per channel 
output current adjustable 3 ... 10 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA21
6EP1961-2BA41
SITOP PSE201U buffer module
6EP1961-3BA01
For SITOP smart and SITOP
modular
buffer time 100 ms to 10 s 
dependent on load current
■ More information
Select the appropriate power supply quickly and easily with the
SITOP Selection Tool:
http://www.siemens.com/sitop-selection-tool
5/12
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP smart
3-phase, 24 V DC
■ Overview
The high degree of efficiency results in low energy consumption
and minimal heat generation inside the control cabinet.
To further increase 24 V availability, the SITOP smart power
supplies can be combined with buffer, DC UPS, redundancy
and selectivity modules.
The three-phase SITOP smart are the universal and powerful
standard power supplies for machinery and plant engineering.
Despite their compact design, they offer an excellent overload
response: Thanks to an extra power of 150 %, loads with high
power consumption can be connected without any problems
and the permanent overload capability of 120% offers power
reserves in case of expansions.
Main product highlights
• 3-phase, 24 V DC/5 A, 10 A, 20 A and 40 A
• Wide-range input from 340 to 550 V AC for global use
• Compact design - no lateral clearances required
• Extra power with 1.5 times the rated current (5 s/min) for 
brief functional overload
• Permanent overload capability with 1.2 times the rated current
up to 45 °C ambient temperature
• Adjustable output voltage for compensating voltage drops
• Signaling contact for easy integration in the plant 
monitoring system
• Wide temperature range from -25 or 0 to +70 °C
• Comprehensive certifications, such as cULus, cCSAus, ATEX,
IECEx and GL
■ Technical specifications
Article number
6EP1433-2BA20
6EP1434-2BA20
6EP1436-2BA10
6EP1437-2BA20
Product
SITOP PSU300S
SITOP PSU300S
SITOP PSU300S
SITOP PSU300S
Power supply, type
24 V/5 A
24 V/10 A
24 V/20 A
24 V/40 A
Input
3-phase AC
3-phase AC
3-phase AC
3-phase AC
Rated voltage value Vin rated
400 ... 500 V
400 ... 500 V
400 ... 500 V
400 ... 500 V
Voltage range AC
340 ... 550 V
340 ... 550 V
340 ... 550 V
340 ... 550 V
Wide-range input
Yes
Yes
Yes
Yes
Mains buffering at Iout rated, min.
6 ms; at Vin = 400 V
6 ms; at Vin = 400 V
6 ms; at Vin = 400 V
6 ms; at Vin = 400 V
Rated line frequency 1
50 Hz
50 Hz
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 400 V
0.45 A
0.7 A
1.2 A
2A
• at rated input voltage 500 V
0.4 A
0.6 A
1A
1.7 A
Switch-on current limiting (+25 °C),
max.
20 A
20 A
36 A
60 A
I²t, max.
0.5 A²·s
0.5 A²·s
0.9 A²·s
3.4 A²·s
Built-in incoming fuse
none
none
none
none
Protection in the mains power input
(IEC 898)
Required: 
3-pole connected miniature
circuit breaker 3 ... 16 A
characteristic C or circuit
breaker 3RV2011-1DA10 
(setting 3 A) or 
3RV2711-1DD10 (UL 489)
Required: 
3-pole connected miniature
circuit breaker 3 ... 16 A
characteristic C or circuit
breaker 3RV2011-1DA10 
(setting 3 A) or 
3RV2711-1DD10 (UL 489)
Required:
3-pole connected miniature
circuit breaker 6 ... 16 A
characteristic C or circuit
breaker 3RV2011-1DA10 
(setting 3 A) or 
3RV2711-1DD10 (UL 489)
Required: 
3-pole connected miniature
circuit breaker 10 ... 16 A
characteristic C or circuit
breaker 3RV2011-1DA10 
(setting 3 A) or 
3RV2711-1DD10 (UL 489)
Input
Input current
Siemens KT 10.1 · 2016
5/13
5
© Siemens AG 2016
SITOP smart
3-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1433-2BA20
6EP1434-2BA20
6EP1436-2BA10
6EP1437-2BA20
Product
SITOP PSU300S
SITOP PSU300S
SITOP PSU300S
SITOP PSU300S
Power supply, type
24 V/5 A
24 V/10 A
24 V/20 A
24 V/40 A
Output
Controlled, isolated 
DC voltage
Controlled, isolated 
DC voltage
Controlled, isolated
DC voltage
Controlled, isolated 
DC voltage
Rated voltage Vout DC
24 V
24 V
24 V
24 V
Total tolerance, static ±
3%
3%
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
0.5 %
1%
Static load balancing, approx.
0.1 %
0.15 %
1%
2%
Residual ripple peak-peak, max.
200 mV
200 mV
150 mV
150 mV
Spikes peak-peak, max. 
(bandwidth: 20 MHz)
240 mV
240 mV
240 mV
240 mV
Adjustment range
24 ... 28 V
24 ... 28 V
24 ... 28 V
24 ... 28 V
Product function Output voltage
adjustable
Yes
Yes
Yes
Yes
Output voltage setting
via potentiometer; 
max. 120 W
via potentiometer; 
max. 240 W
via potentiometer; 
max. 480 W
via potentiometer; 
max. 960 W
Status display
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
Signaling
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
On/off behavior
Overshoot of Vout < 5 %
Overshoot of Vout < 5 %
No overshoot of Vout 
(soft start)
No overshoot of Vout 
(soft start)
Output
5
Startup delay, max.
1.5 s
1.5 s
1.5 s
1.5 s
Voltage rise, typ.
60 ms
50 ms
30 ms
15 ms
Voltage increase time of the output
voltage maximum
500 ms
500 ms
500 ms
500 ms
Rated current value Iout rated
5A
10 A
20 A
40 A
Current range
0 ... 5 A
0 ... 10 A
0 ... 20 A
0 ... 40 A
• Note
6 A up to +45 °C
12 A up to +45 °C
24 A up to +45°C; 
+60 ... +70 °C: 
Derating 5%/K
48 A up to +45°C;
+60 ... +70 °C: 
Derating 2.5%/K
Supplied active power typical
120 W
240 W
480 W
960 W
• on short-circuiting during the 
start-up typical
-
-
35 A
65 A
• at short-circuit during operation
typical
-
-
35 A
65 A
• on short-circuiting during the 
start-up
-
-
100 ms
120 ms
• at short-circuit during operation
-
-
100 ms
120 ms
Parallel switching for enhanced
performance
Yes
Yes
Yes
Yes
Numbers of parallel switchable units
for enhanced performance
2
2
2
2
Efficiency at Vout rated, Iout rated,
approx.
89 %
91 %
91 %
91.5 %
Power loss at Vout rated, Iout rated,
approx.
14 W
23 W
47 W
89 W
Dynamic mains compensation
(Vin rated ±15 %), max.
1%
1%
3%
3%
Dynamic load smoothing 
(Iout: 50/100/50 %), Uout ± typ.
1%
1%
3%
1.5 %
Load step setting time 
50 to 100%, typ.
3 ms
3 ms
2 ms
1 ms
Load step setting time 
100 to 50%, typ.
3 ms
3 ms
2 ms
1 ms
Dynamic load smoothing 
(Iout: 10/90/10 %), Uout ± typ.
3%
3%
3%
3%
Load step setting time 10 to 90%, typ. 4 ms
4 ms
2 ms
1 ms
Load step setting time 90 to 10%, typ. 4 ms
4 ms
2 ms
1 ms
10 ms
10 ms
10 ms
Short-term overload current
Duration of overloading capability 
for excess current
Efficiency
Closed-loop control
Setting time maximum
5/14
10 ms
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP smart
3-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1433-2BA20
6EP1434-2BA20
6EP1436-2BA10
6EP1437-2BA20
Product
SITOP PSU300S
SITOP PSU300S
SITOP PSU300S
SITOP PSU300S
Power supply, type
24 V/5 A
24 V/10 A
24 V/20 A
24 V/40 A
Output overvoltage protection
protection against
overvoltage in case of
internal fault Vout < 35 V
protection against
overvoltage in case of
internal fault Vout < 35 V
protection against
overvoltage in case of
internal fault Vout < 35 V
protection against
overvoltage in case of
internal fault Vout < 35 V
Current limitation, typ.
6.6 A
13 A
25 A
50 A
Property of the output Short-circuit
proof
Yes
Yes
Yes
Yes
Short-circuit protection
Constant current 
characteristic
Constant current 
characteristic
Electronic shutdown,
automatic restart
Electronic shutdown,
automatic restart
• maximum
8A
16 A
7A
14 A
Overcurrent overload capability in
normal operation
overload capability 
overload capability 
overload capability 
overload capability 
150 % Iout rated up to 5 s/min 150 % Iout rated up to 5 s/min 150 % Iout rated up to 5 s/min 150 % Iout rated up to 5 s/min
Protection and monitoring
Enduring short circuit current 
RMS value
Safety
Primary/secondary isolation
Yes
Yes
Yes
Yes
Galvanic isolation
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
Class I
Class I
• maximum
-
-
3.5 mA
-
• typical
-
-
1 mA
-
CE mark
Yes
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259; cCSAus 
(CSA C22.2 No. 60950-1, 
UL 60950-1)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259; cCSAus 
(CSA C22.2 No. 60950-1, 
UL 60950-1)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1),
File E197259; cCSAus
(CSA C22.2 No. 60950-1, 
UL 60950-1)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259; cCSAus 
(CSA C22.2 No. 60950-1, 
UL 60950-1)
Explosion protection
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T4
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T4
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nAC IIC
T4 Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T4
IECEx Ex nA nC IIC T3 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T3 Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T3
FM approval
-
-
-
-
CB approval
Yes
Yes
Yes
Yes
Marine approval
GL and ABS in process
GL and ABS in process
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
IP20
IP20
Emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
EN 61000-3-2
EN 61000-3-2
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
-25 ... +70 °C
-25 ... +70 °C
0 ... 70 °C
0 ... 70 °C
with natural convection
with natural convection
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
screw-type terminals
screw-type terminals
screw-type terminals
screw-type terminals
• Supply input
L1, L2, L3, PE:
1 screw terminal each for 
0.2 ... 4 mm² single-core/
finely stranded
L1, L2, L3, PE: 
1 screw terminal each for
0.2 ... 4 mm² single-core/
finely stranded
L1, L2, L3, PE: 
1 screw terminal each for
0.2 ... 4 mm² single-core/
finely stranded
L1, L2, L3, PE: 
1 screw terminal each for 
0.2 ... 4 mm² single-core/
finely stranded
• Output
+, -: 2 screw terminals each +, -: 2 screw terminals each +, -: 2 screw terminals each +, -: 2 screw terminals each
for 0.2 ... 4 mm²
for 0.2 ... 4 mm²
for 0.2 ... 4 mm²
for 0.5 ... 10 mm²
• Auxiliary
13, 14 (alarm signal): 
1 screw terminal each for
0.14 ... 1.5 mm²
Leakage current
EMC
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
13, 14 (alarm signal): 
1 screw terminal each for
0.14 ... 1.5 mm²
13, 14 (alarm signal): 
1 screw terminal each for
0.14 ... 1.5 mm²
13, 14 (alarm signal): 
1 screw terminal each for
0.14 ... 1.5 mm²
Siemens KT 10.1 · 2016
5/15
5
© Siemens AG 2016
SITOP smart
3-phase, 24 V DC
■ Technical specifications (continued)
5
Article number
6EP1433-2BA20
6EP1434-2BA20
6EP1436-2BA10
6EP1437-2BA20
Product
SITOP PSU300S
SITOP PSU300S
SITOP PSU300S
SITOP PSU300S
Power supply, type
24 V/5 A
24 V/10 A
24 V/20 A
24 V/40 A
Width of the enclosure
50 mm
70 mm
90 mm
150 mm
Height of the enclosure
125 mm
125 mm
145 mm
145 mm
Depth of the enclosure
120 mm
120 mm
150 mm
150 mm
Weight, approx.
0.5 kg
0.7 kg
1.6 kg
3.7 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Yes
Yes
Installation
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x15
Electrical accessories
Buffer module
Buffer module
Buffer module
Buffer module
Mechanical accessories
Device identification label
20 mm × 7 mm, pale
turquoise 3RT1900-1SB20
Device identification label
20 mm × 7 mm, pale
turquoise 3RT1900-1SB20
Device identification label
20 mm × 7 mm, pale
turquoise 3RT1900-1SB20
Device identification label
20 mm × 7 mm, pale
turquoise 3RT1900-1SB20
MTBF at 40 °C
1 506 720 h
1 458 540 h
571 429 h
718 292 h
Other information
Specifications at rated input
voltage and ambient
temperature +25 °C 
(unless otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C 
(unless otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C 
(unless otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C 
(unless otherwise specified)
■ Ordering data
SITOP PSU300S 3-phase,
24 V DC/5 A
Article No.
6EP1433-2BA20
Stabilized power supply 
Input: 400 … 500 V 3 AC
Output: 24 V DC/5 A
SITOP PSU300S 3-phase,
24 V DC/10 A
6EP1434-2BA20
Stabilized power supply
Input: 3 AC 400 … 500 V
Output: 24 V DC/10 A
SITOP PSU300S 3-phase,
24 V DC/20 A
6EP1436-2BA10
3RT1900-1SB20
SITOP PSE202U 
redundancy module
6EP1961-3BA21
Input/output: 24 V DC/40 A 
suitable for decoupling two 
SITOP power supplies with a
maximum of 20 A output current
Stabilized power supply
Input: 3 AC 400 … 500 V
Output: 24 V DC/40 A
■ More information
Select the appropriate power supply quickly and easily with the
SITOP Selection Tool:
http://www.siemens.com/sitop-selection-tool
6EP1962-2BA00
Input/output: 24 V DC/NEC Class 2 
suitable for decoupling two 
SITOP power supplies output power
limited < 100 VA
SITOP PSE202U
redundancy module
6EP1437-2BA20
Article No.
Device labeling plates
SITOP PSE202U
redundancy module
Stabilized power supply
Input: 3 AC 400 … 500 V
Output: 24 V DC/20 A
SITOP PSU300S 3-phase,
24 V DC/40 A
■ Accessories
6EP1964-2BA00
Input/output: 24 V DC/10 A 
suitable for decoupling two 
SITOP power supplies with a
maximum of 5 A output current
SITOP PSE200U 3 A 
selectivity module
4-channel selectivity module 
Input: 24 V DC 
Output: 24 V DC/3A per each
channel 
output current adjustable 0.5 … 3 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA11
6EP1961-2BA31
SITOP PSE200U 10 A 
selectivity module
4-channel selectivity module 
Input: 24 V DC 
Output: 24 V DC/10 A per channel 
output current adjustable 3 ... 10 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA21
6EP1961-2BA41
SITOP PSE201U buffer module
6EP1961-3BA01
For SITOP smart and 
SITOP modular
buffer time 100 ms to 10 s 
dependent on load current
5/16
Siemens KT 10.1 · 2016
6
© Siemens AG 2016
SITOP modular
6/2
6/3
6/8
6/13
6/17
6/19
Introduction
1-phase, 24 V DC
1- and 2-phase, 24 V DC
3-phase, 24 V DC
3-phase, 36 V DC
3-phase, 48 V DC
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP modular
Introduction
■ Overview
■ More information
Select the appropriate power supply quickly and easily with the
SITOP Selection Tool:
http://www.siemens.com/sitop-selection-tool
The technology power supply for demanding solutions
6
The one, two and three-phase SITOP modular units are the
technology power supplies for demanding solutions. They offer
maximum functionality for use in complex plants and machines.
The wide-range input allows a connection to almost any electrical power system worldwide and ensures a high degree of
safety even if there are large voltage fluctuations. They offer
outstanding overload characteristics: Power boost delivers up to
three-times the rated current for short periods of time, and with
extra power of 150%, loads with high power consumption can be
connected without any problems. And in the event of an overload, you can choose between constant current or latching shutdown. The extremely high efficiency keeps energy consumption
and heat buildup in the control cabinet low, and the compact
metal enclosure also saves space.
To further increase the 24 V availability, the SITOP smart power
supplies can be combined with buffer, DC UPS, redundancy
and selectivity modules.
Main product highlights
• 1-phase, 24 V DC / 5 A, 10 A, 20 A, 40 A
• 1-phase and 2-phase, 24 V DC / 5A, 10 A
• 3-phase, 24 V DC/ 20 A, 40 A, 36 V/ 13 A and 48 V/ 10 A, 20 A
• Extremely slim design – no lateral installation clearances
required
• Power boost with 3 times rated current (for 25 ms) for tripping
protective devices
• Extra power with 1.5 times rated current (5 s/min) for brief
functional overload
• Selectable short-circuit response between constant current
and latching shutdown
• Symmetrical load distribution can be selected for parallel
operation
• Operating state on 3 LEDs
• Extremely high efficiency up to 94 %
• Large temperature range from -25 to +70 °C
• Comprehensive certifications, such as cULus, ATEX, IECex
and GL
6/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP modular
1-phase, 24 V DC
■ Overview
The high degree of efficiency keeps energy consumption and
heating in the control cabinet low, and the compact metal 
housing also saves space.
To further increase the 24 V availability, the SITOP modular
power supplies can be combined with buffer, DC UPS,
redundancy and selectivity modules.
The 1-phase SITOP modular are technology power supplies for
sophisticated solutions and offer maximum functionality for use
in complex plants and machines. The wide-range input allows a
connection to almost any electrical power system worldwide and
ensures a high degree of safety even if there are large voltage
fluctuations. The power boost provides up to three times the
rated current for brief periods. In case of overload, you can
choose between constant current with automatic restart or
latching shutdown.
Main product highlights
• 24 V DC/ 5 A, 10 A, 20 A and 40 A
• 1-phase wide-range input for connection to any supply system
and for safety in case of voltage supply deviations
• Extremely slim design – no lateral installation clearances
required
• Power Boost with 3 times the rated current (for 25 ms) for
tripping protective devices
• Extra power with 1.5 times the rated current (5 s/min) for brief
functional overload
• Selectable short-circuit response between constant current
and latching shutdown
• Optional symmetrical load distribution for parallel operation
• Operating status on 3 LEDs
• Extremely high efficiency to 94 %
• Wide temperature range from -25 to +70 °C
• Comprehensive certifications, such as cULus, ATEX and GL
■ Technical specifications
Article number
6EP3333-8SB00-0AY0
6EP3334-8SB00-0AY0
6EP1336-3BA10
6EP1337-3BA00
Product
SITOP PSU8200
SITOP PSU8200
SITOP PSU8200
SITOP PSU100M
Power supply, type
24 V/5 A
24 V/10 A
24 V/20 A
24 V/40 A
1-phase AC
1-phase AC
1-phase AC or DC
1-phase AC
• 1 at AC Rated value
120 V
120 V
-
120 V
• 2 at AC Rated value
230 V
230 V
-
230 V
• at DC
-
-
110 ... 220 V
-
Rated voltage value Vin rated
-
-
120 ... 230 V
-
Voltage range AC
-
-
85 ... 275 V
-
• Note
Automatic range selection
Automatic range selection
Derating of temperature
necessary down to 50 °C 
at Vin < 100 V AC or DC
Set by means of wire jumper
on the device; starting from
Vin > 95/190 V
• 1 at AC
85 ... 132 V
85 ... 132 V
-
85 ... 132 V
• 2 at AC
170 ... 264 V
170 ... 264 V
-
176 ... 264 V
• at DC
-
-
88 ... 350 V
-
Wide-range input
No
No
Yes
No
Overvoltage resistance
-
-
-
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
35 ms; at Vin = 120/230 V
35 ms; at Vin = 120/230 V
20 ms; at Vin = 230 V
20 ms; at Vin = 230 V
Rated line frequency 1
50 Hz
50 Hz
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
45 ... 65 Hz
47 ... 63 Hz
Input
Input
Supply voltage
Input voltage
Siemens KT 10.1 · 2016
6/3
6
© Siemens AG 2016
SITOP modular
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP3333-8SB00-0AY0
6EP3334-8SB00-0AY0
6EP1336-3BA10
6EP1337-3BA00
Product
SITOP PSU8200
SITOP PSU8200
SITOP PSU8200
SITOP PSU100M
Power supply, type
24 V/5 A
24 V/10 A
24 V/20 A
24 V/40 A
• at rated input voltage 120 V
2.1 A
4A
4.6 A
15 A
• at rated input voltage 230 V
1.2 A
1.9 A
2.5 A
8A
Switch-on current limiting (+25 °C),
max.
10 A
10 A
20 A
125 A
I²t, max.
0.2 A²·s
0.3 A²·s
5 A²·s
26 A²·s
Built-in incoming fuse
T 3.15 A (not accessible)
T 6.3 A (not accessible)
Yes
Yes
Protection in the mains power input
(IEC 898)
Recommended miniature
circuit breaker at 1-phase
operation: from 6 A (10 A)
characteristic C (B); required
at 2-phase operation: 
circuit breaker 2-pole
connected or circuit breaker
3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10
(UL 489) at 230 V; 
3RV2011-1DA10 (setting 3 A)
or 3RV2711-1DD10 (UL 489)
at 400/500 V
Recommended miniature
circuit breaker at 1-phase
operation: from 6 A (10 A)
characteristic C (B); required
at 2-phase operation: 
circuit breaker 2-pole
connected or circuit breaker
3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10
(UL 489) at 230 V; 
3RV2011-1DA10 (setting 3 A)
or 3RV2711-1DD10 (UL 489)
at 400/500 V
Recommended miniature
circuit breaker at 1-phase
operation: 10 A characteristic
C; required at 2-phase
operation: circuit breaker 
2-pole connected or circuit
breaker 3RV2711-1HD10
(UL 489) at 120 V or 
3RV2711-1ED10 (UL 489) 
at 230 V
Recommended miniature
circuit breaker at 1-phase
operation: 20 A characteristic
C; required at 2-phase
operation: circuit breaker 
2-pole connected or circuit
breaker 3RV2421-4BA10
(120 V) or 3RV2411-1JA10
(230 V)
Output
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Rated voltage Vout DC
24 V
24 V
24 V
24 V
Total tolerance, static ±
3%
3%
3%
3%
Static mains compensation, approx. 0.1 %
0.1 %
0.1 %
0.1 %
Static load balancing, approx.
0.2 %
0.3 %
0.3 %
0.1 %
Residual ripple peak-peak, max.
50 mV
50 mV
100 mV
100 mV
Residual ripple peak-peak, typ.
-
-
80 mV
60 mV
Spikes peak-peak, max. 
(bandwidth: 20 MHz)
200 mV
200 mV
200 mV
200 mV
Spikes peak-peak, typ. 
(bandwidth: 20 MHz)
-
-
100 mV
120 mV
Adjustment range
24 ... 28.8 V
24 ... 28.8 V
24 ... 28.8 V
24 ... 28.8 V
Product function 
Output voltage adjustable
Yes
Yes
Yes
Yes
Output voltage setting
via potentiometer; 
max. 120 W
via potentiometer; 
max. 240 W
via potentiometer
via potentiometer
Status display
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
Signaling
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
via signaling module
(6EP1961-3BA10)
On/off behavior
Overshoot of Vout approx.
3%
Overshoot of Vout approx.
3%
No overshoot of Vout 
(soft start)
Overshoot of Vout approx.
3%
Startup delay, max.
1s
1s
0.25 s
0.1 s
Voltage rise, typ.
30 ms
70 ms
50 ms
50 ms
Rated current value Iout rated
5A
10 A
20 A
40 A
Current range
0 ... 5 A
0 ... 10 A
0 ... 20 A
0 ... 40 A
• Note
As of Ua>24 V: 4% [Ia]/V [Ua]; +60 ... +70 °C: Derating 
at Ue<100 V/<200 V: 
2%/K; as of Ua>24 V: 
80% Ia rated
4% [Ia]/V [Ua]; 
at Ue<100 V/<200 V: 
80% Ia rated
+60 ... +70 °C: Derating 
3%/K
+60 ... +70 °C: Derating
2.5%/K
Supplied active power typical
120 W
240 W
480 W
960 W
15 A
30 A
60 A
120 A
25 ms
25 ms
25 ms
25 ms
• on short-circuiting during the 
start-up typical
6A
12 A
30 A
46 A
Parallel switching for enhanced
performance
Yes; switchable 
characteristic
Yes; switchable 
characteristic
Yes; switchable 
characteristic
Yes; switchable 
characteristic
2
2
2
Input current
6
Output
Short-term overload current
• at short-circuit during operation
typical
Duration of overloading capability
for excess current
• at short-circuit during operation
Constant overload current
Numbers of parallel switchable units 2
for enhanced performance
6/4
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP modular
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP3333-8SB00-0AY0
6EP3334-8SB00-0AY0
6EP1336-3BA10
6EP1337-3BA00
Product
SITOP PSU8200
SITOP PSU8200
SITOP PSU8200
SITOP PSU100M
Power supply, type
24 V/5 A
24 V/10 A
24 V/20 A
24 V/40 A
Efficiency at Vout rated, Iout rated,
approx.
93 %
94 %
93 %
88 %
Power loss at Vout rated, Iout rated,
approx.
9W
18 W
42 W
131 W
Power loss [W] during no-load
operation maximum
1.5 W
1.5 W
-
-
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
0.1 %
0.5 %
1%
Dynamic load smoothing 
(Iout: 50/100/50 %), Uout ± typ.
2%
4%
1%
2%
Load step setting time 
50 to 100 %, typ.
0.25 ms
0.25 ms
1 ms
2 ms
Load step setting time 
100 to 50 %, typ.
0.5 ms
0.5 ms
1 ms
2 ms
Dynamic load smoothing 
(Iout: 10/90/10 %), Uout ± typ.
2%
4%
-
-
Load step setting time 
10 to 90%, typ.
0.25 ms
0.25 ms
-
-
Load step setting time 
90 to 10%, typ.
0.5 ms
0.5 ms
-
-
Setting time maximum
1 ms
1 ms
5 ms
5 ms
Output overvoltage protection
< 33 V
< 33 V
< 33 V
< 35 V
Current limitation, typ.
6A
12 A
21.5 A
46 A
Property of the output 
Short-circuit proof
Yes
Yes
Yes
Yes
Short-circuit protection
Alternatively, constant current Alternatively, constant current Alternatively, constant current Alternatively, constant current
characteristic approx. 6 A or characteristic approx. 12 A characteristic approx. 23 A characteristic approx. 46 A
latching shutdown
or latching shutdown
or latching shutdown
or latching shutdown
Efficiency
Closed-loop control
6
Protection and monitoring
Enduring short circuit current
RMS value
• typical
6A
Overcurrent overload capability in
normal operation
overload capability 
overload capability 
150 % Iout rated up to 5 s/min 150 % Iout rated up to 5 s/min
LED yellow for "overload",
LED yellow for "overload",
LED red for "latching
LED red for "latching
shutdown"
shutdown"
overload capability 
150 % Iout rated up to 5 s/min
LED yellow for "overload",
LED red for "latching
shutdown"
LED yellow for "overload",
LED red for "latching
shutdown"
Primary/secondary isolation
Yes
Yes
Yes
Yes
Galvanic isolation
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
Class I
Class I
• maximum
3.5 mA
3.5 mA
3.5 mA
3.5 mA
• typical
1 mA
1 mA
1 mA
0.4 mA
CE mark
Yes
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259, cCSAus 
(CSA C22.2 No. 60950-1,
UL 60950-1, UL 1604)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259, cCSAus 
(CSA C22.2 No. 60950-1,
UL 60950-1, UL 1604)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259
Explosion protection
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T3
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T3
IECEx Ex nA nC IIC T3 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T3 Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T3
IECEx Ex nA IIC T3 Gc; 
ATEX (EX) II 3G Ex nA IIC T3
Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T3
FM approval
-
-
-
-
CB approval
Yes
Yes
No
No
Marine approval
GL, ABS
GL, ABS
GL, ABS
-
Degree of protection (EN 60529)
IP20
IP20
IP20
IP20
Overload/short-circuit indicator
12 A
23 A
46 A
Safety
Leakage current
Siemens KT 10.1 · 2016
6/5
© Siemens AG 2016
SITOP modular
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP3333-8SB00-0AY0
6EP3334-8SB00-0AY0
6EP1336-3BA10
6EP1337-3BA00
Product
SITOP PSU8200
SITOP PSU8200
SITOP PSU8200
SITOP PSU100M
Power supply, type
24 V/5 A
24 V/10 A
24 V/20 A
24 V/40 A
Emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
EN 61000-3-2
EN 61000-3-2
-
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
-25 ... +70 °C
-25 ... +70 °C
-25 ... +70 °C
0 ... 70 °C
with natural convection;
Startup tested from -40 °C
Rated voltage
with natural convection;
Startup tested from -40 °C
Rated voltage
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
screw-type terminals
screw-type terminals
screw-type terminals
screw-type terminals
• Supply input
L, N, PE: 1 screw terminal
each for 0.2 ... 2.5 mm²
single-core/finely stranded
L, N, PE: 1 screw terminal
each for 0.2 ... 2.5 mm²
single-core/finely stranded
L, N, PE: 1 screw terminal
each for 0.2 ... 4 mm² 
single-core/finely stranded
L, N, PE: 1 screw terminal
each for 0.2 ... 4 mm² 
single-core/finely stranded
• Output
+, -: 2 screw terminals each
for 0.2 ... 2.5 mm²
+, -: 2 screw terminals each
for 0.2 ... 2.5 mm²
+, -: 2 screw terminals each
for 0.2 ... 4 mm²
+, -: 2 screw terminals each
for 0.5 ... 10 mm²
• Auxiliary
13, 14 (alarm signal):
1 screw terminal each for
0.14 ... 1.5 mm²; 15, 16
(Remote): 1 screw terminal
each for 0.14 ... 1.5 mm²
13, 14 (alarm signal): 
1 screw terminal each for
0.14 ... 1.5 mm²; 15, 16
(Remote): 1 screw terminal
each for 0.14 ... 1.5 mm²
13, 14 (alarm signal): 
1 screw terminal each for
0.14 ... 1.5 mm²
-
Width of the enclosure
45 mm
55 mm
90 mm
240 mm
Height of the enclosure
125 mm
125 mm
125 mm
125 mm
Depth of the enclosure
125 mm
125 mm
125 mm
125 mm
Weight, approx.
0.8 kg
1 kg
1.2 kg
2.9 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Yes
Yes
Installation
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x15
Electrical accessories
Buffer module
Buffer module
Buffer module
Buffer module, 
signaling module
Mechanical accessories
-
-
Device identification 
label 20 mm × 7 mm, 
pale turquoise 
3RT1900-1SB20
-
MTBF at 40 °C
1 421 519 h
1 292 102 h
667 048 h
540 249 h
Other information
Specifications at rated input
voltage and ambient
temperature +25 °C (unless
otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C (unless
otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C (unless
otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C (unless
otherwise specified)
EMC
Operating data
Ambient temperature
• during operation
- Note
Mechanics
6
Connection technology
Connections
6/6
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP modular
1-phase, 24 V DC
■ Ordering data
SITOP PSU8200 1-phase,
24 V DC/5 A
Article No.
6EP3333-8SB00-0AY0
6EP3334-8SB00-0AY0
Stabilized power supply
Input: 120/230 V AC
Output: 24 V DC/10 A
SITOP PSU8200, 1-phase,
24 V DC/20 A
6EP1336-3BA10
Stabilized power supply
Input: 120 … 230 V AC/
110-220 V DC
Output: 24 V DC/20 A
SITOP PSU100M 1-phase,
24 V DC/40 A
Stabilized power supply
Input: 120/230 V AC
Output: 24 V DC/40 A
SITOP PSE201U buffer module
Article No.
6EP1961-3BA01
For SITOP smart and
SITOP modular
buffer time 100 ms to 10 s 
dependent on load current
Stabilized power supply
Input: 120/230 V AC
Output: 24 V DC/5 A
SITOP PSU8200 1-phase,
24 V DC/10 A
■ Accessories
6EP1337-3BA00
SITOP modular signaling module
6EP1961-3BA10
For 6EP1XXX-3BA00 
signaling contacts: 
Output voltage OK, 
readiness for operation OK, 
remote ON/OFF
SITOP PSE202U 
redundancy module
6EP1961-3BA21
Input/output: 24 V DC/40 A 
suitable for decoupling two 
SITOP power supplies with a 
maximum of 20 A output current
SITOP PSE202U 
redundancy module
6EP1962-2BA00
Input/output: 24 V DC/NEC Class 2 
suitable for decoupling two 
SITOP power supplies; 
output power limited < 100 VA
SITOP PSE202U 
redundancy module
6
6EP1964-2BA00
Input/output: 24 V DC/10 A 
suitable for decoupling two 
SITOP power supplies with a 
maximum of 5 A output current
SITOP PSE200U 
selectivity module 3 A
4-channel 
Input: 24 V DC
Output: 24 V DC/3 A per channel 
Adjustable output current 0.5 … 3 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA11
6EP1961-2BA31
SITOP PSE200U 
selectivity module 10 A
4-channel 
Input: 24 V DC
Output: 24 V DC/10 A per channel 
Adjustable output current 3 ... 10 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA21
6EP1961-2BA41
Device labeling plates
3RT1900-1SB20
Siemens KT 10.1 · 2016
6/7
© Siemens AG 2016
SITOP modular
1- and 2-phase, 24 V DC
■ Overview
current with automatic restart or latching shutdown. The high
degree of efficiency keeps energy consumption and heating in
the control cabinet low, and the compact metal housing also
saves space.
To further increase 24 V availability, the SITOP modular power
supplies can be combined with buffer, DC UPS, redundancy
and selectivity modules.
6
The 1-phase and 2-phase SITOP modular are technology power
supplies for sophisticated solutions and offer maximum functionality for use in complex plants and machines. The ultra-wide
input range allows connections to almost any 1-phase power
supply system or directly between the line conductors of 
three-phase networks (2-phase) and ensures a high degree of
safety even if there are large voltage fluctuations. The power
boost provides up to three times the rated current for brief
periods. In case of overload, you can choose between constant
Main product highlights
• 24 V/5 A and 10 A, also available as version with PCB with
protective coating.
• 1-phase and 2-phase ultra-wide input range
• Extremely slim design – no lateral installation clearances
required
• Power Boost with 3 times the rated current (for 25 ms) for
tripping protective devices
• Extra power with 1.5 times the rated current (5 s/min) for brief
functional overload
• Selectable short-circuit response between constant current
and latching shutdown
• Optional symmetrical load distribution for parallel operation
• Operating status on 3 LEDs
• High degree of efficiency up to 91 %
• Wide temperature range from -25 to +70 °C
• Comprehensive certifications, such as cULus, ATEX and GL
■ Technical specifications
Article number
6EP1333-3BA10
6EP1333-3BA10-8AC0
6EP1334-3BA10
6EP1334-3BA10-8AB0
Product
SITOP PSU200M
SITOP PSU200M 
with protective coating
SITOP PSU200M
SITOP PSU200M 
with protective coating
Power supply, type
24 V/5 A
24 V/5 A
24 V/10 A
24 V/10 A
1-phase and 2-phase AC
1-phase and 2-phase AC
1-phase and 2-phase AC
1-phase and 2-phase AC
• 1 at AC
120 ... 230 V
120 ... 230 V
120 ... 230 V
120 ... 230 V
• 2 at AC
230 ... 500 V
230 ... 500 V
230 ... 500 V
230 ... 500 V
• Note
Set by means of selector
switch on the device;
starting from Vin > 90/180 V
Set by means of selector
switch on the device;
starting from Vin > 90/180 V
Set by means of selector
switch on the device
Set by means of selector
switch on the device
• 1 at AC
85 ... 264 V
85 ... 264 V
85 ... 264 V
85 ... 264 V
• 2 at AC
176 ... 550 V
176 ... 550 V
176 ... 550 V
176 ... 550 V
Wide-range input
Yes
Yes
Yes
Yes
Overvoltage resistance
1300 Vpeak, 1.3 ms
1300 Vpeak, 1.3 ms
1300 Vpeak, 1.3 ms
1300 Vpeak, 1.3 ms
Mains buffering at Iout rated, min.
25 ms; at Vin = 120/230 V,
typ. 150 ms at Vin = 400 V
25 ms; at Vin = 120/230 V,
typ. 150 ms at Vin = 400 V
25 ms; at Vin = 120/230 V,
typ. 150 ms at Vin = 400 V
25 ms; at Vin = 120/230 V,
typ. 150 ms at Vin = 400 V
Rated line frequency 1
50 Hz
50 Hz
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
Input
Input
Supply voltage
Input voltage
6/8
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP modular
1- and 2-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1333-3BA10
6EP1333-3BA10-8AC0
6EP1334-3BA10
6EP1334-3BA10-8AB0
Product
SITOP PSU200M
SITOP PSU200M 
with protective coating
SITOP PSU200M
SITOP PSU200M 
with protective coating
Power supply, type
24 V/5 A
24 V/5 A
24 V/10 A
24 V/10 A
• at rated input voltage 120 V
2.2 A
2.2 A
4.4 A
4.4 A
• at rated input voltage 230 V
1.2 A
1.2 A
2.4 A
2.4 A
• at rated input voltage 500 V
0.61 A
0.61 A
1.1 A
1.1 A
Switch-on current limiting (+25 °C),
max.
35 A
35 A
35 A
35 A
I²t, max.
1.7 A²·s
1.7 A²·s
4 A²·s
4 A²·s
Built-in incoming fuse
T 3.15 A (not accessible)
T 3.15 A (not accessible)
T 6.3 A (not accessible)
T 6.3 A (not accessible)
Protection in the mains power input
(IEC 898)
Recommended miniature
circuit breaker at 1-phase
operation: from 6 A (10 A)
characteristic C (B); required
at 2-phase operation: 
circuit breaker 2-pole
connected or circuit breaker
3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10
(UL 489) at 230 V; 
3RV2011-1DA10 (setting
3 A) or 3RV2711-1DD10
(UL 489) at 400/500 V
Recommended miniature
circuit breaker at 1-phase
operation: from 6 A (10 A)
characteristic C (B); required
at 2-phase operation: 
circuit breaker 2-pole
connected or circuit breaker
3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10
(UL 489) at 230 V; 
3RV2011-1DA10 (setting
3 A) or 3RV2711-1DD10
(UL 489) at 400/500 V
Recommended miniature
circuit breaker at 1-phase
operation: from 6 A (10 A)
characteristic C (B); required
at 2-phase operation: circuit
breaker 2-pole connected 
or circuit breaker 
3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10
(UL 489) at 230 V; 
3RV2011-1DA10 (setting
3 A) or 3RV2711-1DD10
(UL 489) at 400/500 V
Recommended miniature
circuit breaker at 1-phase
operation: from 6 A (10 A)
characteristic C (B); required
at 2-phase operation: circuit
breaker 2-pole connected 
or circuit breaker 
3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10
(UL 489) at 230 V; 
3RV2011-1DA10 (setting
3 A) or 3RV2711-1DD10
(UL 489) at 400/500 V
Output
Controlled, isolated DC
voltage
Controlled, isolated DC
voltage
Controlled, isolated DC
voltage
Controlled, isolated DC
voltage
Rated voltage Vout DC
24 V
24 V
24 V
24 V
Total tolerance, static ±
3%
3%
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
0.1 %
0.1 %
Static load balancing, approx.
0.1 %
0.1 %
0.1 %
0.1 %
Residual ripple peak-peak, max.
50 mV
50 mV
50 mV
50 mV
Spikes peak-peak, max. 
(bandwidth: 20 MHz)
200 mV
200 mV
200 mV
200 mV
Adjustment range
24 ... 28.8 V
24 ... 28.8 V
24 ... 28.8 V
24 ... 28.8 V
Product function Output voltage
adjustable
Yes
Yes
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
via potentiometer
via potentiometer
Status display
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
Signaling
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
On/off behavior
Overshoot of Vout approx.
3%
Overshoot of Vout approx.
3%
Overshoot of Vout approx.
3%
Overshoot of Vout approx.
3%
Input current
Output
Startup delay, max.
1s
1s
1s
1s
Voltage rise, typ.
50 ms
50 ms
50 ms
50 ms
Rated current value Iout rated
5A
5A
10 A
10 A
Current range
0 ... 5 A
0 ... 5 A
0 ... 10 A
0 ... 10 A
• Note
-
-
+60 ... +70 °C: Derating 
2%/K (at 120 V, 230 V) or
3.5%/K (at 400 V)
+60 ... +70 °C: Derating 
2%/K (at 120 V, 230 V) or
3.5%/K (at 400 V)
Supplied active power typical
120 W
120 W
240 W
240 W
15 A
15 A
30 A
30 A
25 ms
25 ms
25 ms
25 ms
• on short-circuiting during the 
start-up typical
6A
6A
12 A
12 A
Parallel switching for enhanced
performance
Yes; switchable 
characteristic
Yes; switchable 
characteristic
Yes; switchable 
characteristic
Yes; switchable 
characteristic
Numbers of parallel switchable units
for enhanced performance
2
2
2
2
Short-term overload current
• at short-circuit during operation
typical
Duration of overloading capability for
excess current
• at short-circuit during operation
Constant overload current
Siemens KT 10.1 · 2016
6/9
6
© Siemens AG 2016
SITOP modular
1- and 2-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1333-3BA10
6EP1333-3BA10-8AC0
6EP1334-3BA10
6EP1334-3BA10-8AB0
Product
SITOP PSU200M
SITOP PSU200M 
with protective coating
SITOP PSU200M
SITOP PSU200M 
with protective coating
Power supply, type
24 V/5 A
24 V/5 A
24 V/10 A
24 V/10 A
Efficiency at Vout rated, Iout rated,
approx.
88 %
88 %
91 %
91 %
Power loss at Vout rated, Iout rated,
approx.
17 W
17 W
24 W
24 W
Power loss [W] during no-load
operation maximum
4W
4W
6W
6W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
0.1 %
0.1 %
0.1 %
Dynamic load smoothing 
(Iout: 50/100/50 %), Uout ± typ.
3%
3%
3%
3%
Load step setting time 
50 to 100 %, typ.
2 ms
2 ms
2 ms
2 ms
Load step setting time 
100 to 50 %, typ.
2 ms
2 ms
2 ms
2 ms
Setting time maximum
5 ms
5 ms
5 ms
5 ms
Output overvoltage protection
< 35 V
< 35 V
< 35 V
< 35 V
Current limitation, typ.
6A
6A
12 A
12 A
Property of the output 
Short-circuit proof
Yes
Yes
Yes
Yes
Short-circuit protection
Alternatively, constant
current characteristic
approx. 5.5 A or latching
shutdown
Alternatively, constant
current characteristic
approx. 5.5 A or latching
shutdown
Alternatively, constant
current characteristic
approx. 12 A or latching
shutdown
Alternatively, constant
current characteristic
approx. 12 A or latching
shutdown
• typical
6A
6A
12 A
12 A
Overload/short-circuit indicator
LED yellow for "overload",
LED red for "latching
shutdown"
LED yellow for "overload",
LED red for "latching
shutdown"
LED yellow for "overload",
LED red for "latching
shutdown"
LED yellow for "overload",
LED red for "latching
shutdown"
Primary/secondary isolation
Yes
Yes
Yes
Yes
Galvanic isolation
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
Class I
Class I
• maximum
3.5 mA
3.5 mA
3.5 mA
3.5 mA
• typical
0.25 mA
0.25 mA
0.32 mA
0.32 mA
CE mark
Yes
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259
Explosion protection
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc (for AC 120-230/
230-400 V); cCSAus 
(CSA C22.2 No. 213, 
ANSI/ISA-12.12.01) Class I,
Div. 2, Group ABCD, T3
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc (for AC 120-230/
230-400 V); cCSAus 
(CSA C22.2 No. 213, 
ANSI/ISA-12.12.01) Class I,
Div. 2, Group ABCD, T3
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc (for AC 120-230/
230-400 V); cCSAus 
(CSA C22.2 No. 213, 
ANSI/ISA-12.12.01) Class I,
Div. 2, Group ABCD, T3
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc (for AC 120-230/
230-400 V); cCSAus 
(CSA C22.2 No. 213, 
ANSI/ISA-12.12.01) Class I,
Div. 2, Group ABCD, T3
CB approval
Yes
Yes
Yes
Yes
Marine approval
GL, ABS
GL
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
IP20
IP20
Efficiency
Closed-loop control
6
Protection and monitoring
Enduring short circuit current
RMS value
Safety
Leakage current
6/10
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP modular
1- and 2-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1333-3BA10
6EP1333-3BA10-8AC0
6EP1334-3BA10
6EP1334-3BA10-8AB0
Product
SITOP PSU200M
SITOP PSU200M 
with protective coating
SITOP PSU200M
SITOP PSU200M 
with protective coating
Power supply, type
24 V/5 A
24 V/5 A
24 V/10 A
24 V/10 A
Emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
EN 61000-3-2
EN 61000-3-2
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
-25 ... +70 °C
-25 ... +70 °C
-25 ... +70 °C
-25 ... +70 °C
with natural convection
with natural convection
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
screw-type terminals
screw-type terminals
screw-type terminals
screw-type terminals
• Supply input
L, N, PE: 1 screw terminal
each for 0.2 ... 2.5 mm²
single-core/finely stranded
L, N, PE: 1 screw terminal
each for 0.2 ... 2.5 mm²
single-core/finely stranded
L, N, PE: 1 screw terminal
each for 0.2 ... 2.5 mm²
single-core/finely stranded
L, N, PE: 1 screw terminal
each for 0.2 ... 2.5 mm²
single-core/finely stranded
• Output
+, -: 2 screw terminals each +, -: 2 screw terminals each +, -: 2 screw terminals each +, -: 2 screw terminals each
for 0.2 ... 2.5 mm²
for 0.2 ... 2.5 mm²
for 0.2 ... 2.5 mm²
for 0.2 ... 2.5 mm²
• Auxiliary
13, 14 (alarm signal): 
1 screw terminal each for
0.14 ... 1.5 mm²
13, 14 (alarm signal): 
1 screw terminal each for
0.14 ... 1.5 mm²
13, 14 (alarm signal): 
1 screw terminal each for
0.14 ... 1.5 mm²
13, 14 (alarm signal): 
1 screw terminal each for
0.14 ... 1.5 mm²
Width of the enclosure
70 mm
70 mm
70 mm
70 mm
Height of the enclosure
125 mm
125 mm
125 mm
125 mm
Depth of the enclosure
121 mm
121 mm
121 mm
121 mm
Weight, approx.
0.6 kg
0.6 kg
0.8 kg
0.8 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Yes
Yes
Installation
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Electrical accessories
Buffer module
Buffer module
Buffer module
Buffer module
MTBF at 40 °C
1 123 973 h
1 123 973 h
1 055 408 h
1 055 408 h
Other information
Specifications at rated input
voltage and ambient
temperature +25 °C 
(unless otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C 
(unless otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C 
(unless otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C 
(unless otherwise specified)
EMC
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
Siemens KT 10.1 · 2016
6/11
6
© Siemens AG 2016
SITOP modular
1- and 2-phase, 24 V DC
■ Ordering data
SITOP PSU200M 1-phase and 
2-phase, 24 V DC/5 A
Article No.
6EP1333-3BA10
6EP1333-3BA10-8AC0
Stabilized power supply 
Input: 120 … 230/230 … 500 V AC 
Output: 24 V DC/5 A
Version with protective coating
SITOP PSU200M 1-phase and 
2-phase, 24 V DC/10 A
6
6EP1961-3BA01
SITOP PSE202U 
redundancy module
6EP1961-3BA21
Input/output: 24 V DC/40 A 
suitable for decoupling two 
SITOP power supplies with a 
maximum of 20 A output current
6EP1334-3BA10
SITOP PSE202U 
redundancy module
6EP1962-2BA00
Input/output: 24 V DC/NEC Class 2 
suitable for decoupling two 
SITOP power supplies; 
output power limited < 100 VA
Stabilized power supply
Input: 120 ... 230 V/
230 … 500 V AC 
Output: 24 V DC/10 A
SITOP modular 1-phase and 
2-phase, 24 V DC /10 A
SITOP PSE201U buffer module
Article No.
For SITOP smart and
SITOP modular
buffer time 100 ms to 10 s 
dependent on load current
Stabilized power supply 
Input: 120 ... 230/230 … 500 V AC 
Output: 24 V DC/5 A
SITOP modular 1-phase and 
2-phase, 24 V DC /5 A
■ Accessories
6EP1334-3BA10-8AB0
Stabilized power supply
Input: 120 … 230/230 … 500 V AC 
Output: 24 V DC/10 A 
version with protective coating
SITOP PSE202U 
redundancy module
6EP1964-2BA00
Input/output: 24 V DC/10 A 
suitable for decoupling two 
SITOP power supplies with a 
maximum of 5 A output current
SITOP PSE200U 
selectivity module 3 A
4-channel 
Input: 24 V DC
Output: 24 V DC/3 A per channel 
output current adjustable 0.5 … 3 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA11
6EP1961-2BA31
SITOP PSE200U 
selectivity module 10 A
6/12
Siemens KT 10.1 · 2016
4-channel 
Input: 24 V DC
Output: 24 V DC/10 A per channel 
output current adjustable 3 ... 10 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA21
6EP1961-2BA41
Device labeling plates
3RT1900-1SB20
© Siemens AG 2016
SITOP modular
3-phase, 24 V DC
■ Overview
latching shutdown. The high degree of efficiency keeps energy
consumption and heating in the control cabinet low, and the
compact metal housing also saves space.
To further increase 24 V availability, the SITOP modular power
supplies can be combined with buffer, DC UPS, redundancy
and selectivity modules.
The 3-phase SITOP modular are technology power supplies for
sophisticated solutions and offer maximum functionality for use
in complex plants and machines. The wide-range input allows a
connection to almost any electrical power system worldwide and
ensures a high degree of safety even if there are large voltage
fluctuations. The power boost provides up to three times the
rated current for brief periods. In case of overload, you can
choose between constant current with automatic restart or
Main product highlights
• 24 V DC/ 20 A and 40 A
• 3-phase wide-range input from 320 to 575 V AC for global use
• Extremely slim design – no lateral installation clearances
required
• Power Boost with 3 times the rated current (for 25 ms) for
tripping protective devices
• Extra power with 1.5 times the rated current (5 s/min) for brief
functional overload
• Selectable short-circuit response between constant current
and latching shutdown
• Optional symmetrical load distribution for parallel operation
• Operating status on 3 LEDs
• Extremely high efficiency up to 94%
• Wide temperature range from -25 to +70 °C
• Comprehensive certifications, such as cULus, ATEX, IECex
and GL
■ Technical specifications
Article number
6EP3436-8SB00-0AY0
6EP1437-3BA10
Product
SITOP PSU8200
SITOP PSU8200
Power supply, type
24 V/20 A
24 V/40 A
Input
3-phase AC
3-phase AC
Rated voltage value Vin rated
400 ... 500 V
400 ... 500 V
Voltage range AC
320 ... 575 V
320 ... 575 V
Wide-range input
Yes
Yes
Mains buffering at Iout rated, min.
15 ms; at Vin = 400 V
15 ms; at Vin = 400 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 400 V
1.2 A
2.6 A
• at rated input voltage 500 V
1A
2.1 A
Switch-on current limiting (+25 °C), max.
16 A
56 A
I²t, max.
0.8 A²·s
2.24 A²·s
Built-in incoming fuse
none
none
Protection in the mains power input (IEC 898)
Required: 3-pole connected miniature circuit breaker
6 ... 16 A characteristic C or circuit breaker 
3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10
(UL 489)
Required: 3-pole connected miniature circuit breaker
10 ... 16 A characteristic C or circuit breaker 
3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10
(UL 489)
Input
Input current
Siemens KT 10.1 · 2016
6/13
6
© Siemens AG 2016
SITOP modular
3-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP3436-8SB00-0AY0
6EP1437-3BA10
Product
SITOP PSU8200
SITOP PSU8200
Power supply, type
24 V/20 A
24 V/40 A
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
24 V
Total tolerance, static ±
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
0.2 %
0.2 %
Residual ripple peak-peak, max.
100 mV
100 mV
Spikes peak-peak, max. 
(bandwidth: 20 MHz)
200 mV
200 mV
Adjustment range
24 ... 28 V
24 ... 28.8 V
Product function Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer; max. 480 W
via potentiometer; max. 960 W
Status display
Green LED for 24 V OK
Green LED for 24 V OK
Signaling
Relay contact (NO contact, rating 60 V DC/ 0.3 A) 
for "24 V OK"
Relay contact (NO contact, rating 60 V DC/ 0.3 A) 
for "24 V OK"
On/off behavior
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
Startup delay, max.
2.5 s
2.5 s
Voltage increase time of the output voltage
maximum
500 ms
500 ms
Rated current value Iout rated
20 A
40 A
Current range
0 ... 20 A
0 ... 40 A
• Note
+60 ... +70 °C: Derating 2%/K
+60 ... +70 °C: Derating 3.75%/K
Supplied active power typical
480 W
960 W
60 A
120 A
25 ms
25 ms
• on short-circuiting during the 
start-up typical
22 A
44 A
Parallel switching for enhanced performance
Yes; switchable characteristic
Yes; switchable characteristic
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency at Vout rated, Iout rated, approx.
94 %
92 %
Power loss at Vout rated, Iout rated, approx.
31 W
83 W
Dynamic mains compensation 
(Vin rated ±15 %), max.
0.1 %
1%
Dynamic load smoothing 
(Iout: 50/100/50 %), Uout ± typ.
1%
3%
Load step setting time 50 to 100 %, typ.
0.2 ms
-
Load step setting time 100 to 50 %, typ.
0.2 ms
-
Dynamic load smoothing 
(Iout: 10/90/10 %), Uout ± typ.
2%
-
Load step setting time 10 to 90%, typ.
0.2 ms
-
Load step setting time 90 to 10%, typ.
0.2 ms
-
Setting time maximum
10 ms
10 ms
Output overvoltage protection
< 32 V
< 35 V
Current limitation, typ.
22 A
44 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Alternatively, constant current characteristic 
approx. 22 A or latching shutdown
Alternatively, constant current characteristic 
approx. 44 A or latching shutdown
• typical
22 A
44 A
Overcurrent overload capability in normal
operation
overload capability 150 % Iout rated up to 5 s/min
overload capability 150 % Iout rated up to 5 s/min
Overload/short-circuit indicator
LED yellow for "overload", 
LED red for "latching shutdown"
LED yellow for "overload", 
LED red for "latching shutdown"
Output
6
Short-term overload current
• at short-circuit during operation typical
Duration of overloading capability for excess
current
• at short-circuit during operation
Constant overload current
Efficiency
Closed-loop control
Protection and monitoring
Enduring short circuit current RMS value
6/14
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP modular
3-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP3436-8SB00-0AY0
6EP1437-3BA10
Product
SITOP PSU8200
SITOP PSU8200
Power supply, type
24 V/20 A
24 V/40 A
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra low output voltage Vout 
according to EN 60950-1
Safety extra-low output voltage Uout acc. to 
EN 60950-1 and EN 50178
Protection class
Class I
Class I
• maximum
3.5 mA
3.5 mA
• typical
0.9 mA
-
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1), 
File E197259
cULus-Listed (UL 508, CSA C22.2 No. 107.1), 
File E197259
Explosion protection
IECEx Ex nA nC IIC T4 Gc; 
ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus
(CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, 
Div. 2, Group ABCD, T4
IECEx Ex nA nC IIC T4 Gc; 
ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus 
(CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, 
Div. 2, Group ABCD, T4
FM approval
-
-
CB approval
Yes
Yes
Marine approval
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
-25 ... +70 °C
-25 ... +70 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
screw-type terminals
screw-type terminals
• Supply input
L1, L2, L3, PE: 1 screw terminal each for 
0.2 ... 4 mm² single-core/finely stranded
L1, L2, L3, PE: 1 screw terminal each for 
0.2 ... 4 mm² single-core/finely stranded
• Output
+, -: 2 screw terminals each for 0.2 ... 4 mm²
+, -: 2 screw terminals each for 0.33 ... 10 mm²
• Auxiliary
13, 14 (alarm signal): 1 screw terminal each for
0.14 ... 1.5 mm²; 15, 16 (Remote): 
1 screw terminal each for 0.14 ... 1.5 mm²
13, 14 (alarm signal): 1 screw terminal each for
0.14 ... 1.5 mm²
Width of the enclosure
70 mm
150 mm
Height of the enclosure
125 mm
125 mm
Depth of the enclosure
125 mm
150 mm
• top
50 mm
-
• bottom
50 mm
-
• left
0 mm
-
• right
0 mm
-
Weight, approx.
1.2 kg
3.4 kg
Product feature of the enclosure housing for
side-by-side mounting
Yes
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
Snaps onto DIN rail EN 60715 35x15
Electrical accessories
Buffer module
Buffer module
Mechanical accessories
Device identification label 20 mm × 7 mm,
pale turquoise 3RT1900-1SB20
Device identification label 20 mm × 7 mm,
pale turquoise 3RT1900-1SB20
MTBF at 40 °C
590 573 h
885 739 h
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Safety
Leakage current
6
EMC
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
Required spacing
Siemens KT 10.1 · 2016
6/15
© Siemens AG 2016
SITOP modular
3-phase, 24 V DC
■ Ordering data
SITOP PSU8200, 3-phase,
24 V DC/20 A
Article No.
6EP3436-8SB00-0AY0
SITOP PSE201U buffer module
Article No.
6EP1961-3BA01
For SITOP smart and
SITOP modular
buffer time 100 ms to 10 s 
dependent on load current
Stabilized power supply
Input: 400 … 500 V 3 AC
Output: 24 V DC/20 A
SITOP PSU8200 3-phase,
24 V DC/40 A
■ Accessories
6EP1437-3BA10
Stabilized power supply
Input: 400 … 500 V 3 AC
Output: 24 V DC/20 A
SITOP PSE202U
redundancy module
6EP1961-3BA21
Input/output: 24 V DC/40 A 
suitable for decoupling two 
SITOP power supplies with a
maximum of 20 A output current
SITOP PSE202U 
redundancy module
6EP1962-2BA00
Input/output: 24 V DC/NEC Class 2 
suitable for decoupling two 
SITOP power supplies; 
output power limited < 100 VA
SITOP PSE202U 
redundancy module
6EP1964-2BA00
Input/output: 24 V DC/10 A 
suitable for decoupling two 
SITOP power supplies with a
maximum of 5 A output current
6
SITOP PSE200U 
selectivity module 3 A
4-channel 
Input: 24 V DC
Output: 24 V DC/3 A per channel 
output current adjustable 0.5 … 3 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA11
6EP1961-2BA31
SITOP PSE200U 
selectivity module 10 A
6/16
Siemens KT 10.1 · 2016
4-channel 
Input: 24 V DC
Output: 24 V DC/10 A per channel 
output current adjustable 3 ... 10 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA21
6EP1961-2BA41
Device labeling plates
3RT1900-1SB20
© Siemens AG 2016
SITOP modular
3-phase, 36 V DC
■ Overview
■ Technical specifications
Article number
6EP3446-8SB10-0AY0
Product
SITOP PSU8200
Power supply, type
36 V/13 A
Input
Input
3-phase AC
Rated voltage value Vin rated
400 ... 500 V
Voltage range AC
320 ... 575 V
Wide-range input
Yes
Mains buffering at Iout rated, min.
15 ms; at Vin = 400 V
Rated line frequency 1
50 Hz
Rated line frequency 2
60 Hz
Rated line range
47 ... 63 Hz
Input current
The 3-phase SITOP modular are technology power supplies for
sophisticated solutions and offer maximum functionality for use
in complex plants and machines. The wide-range input allows
connection to almost any electrical power system worldwide and
ensures a high degree of safety, even if there are large voltage
fluctuations. The power boost provides up to three times the
rated current for brief periods. In case of overload, you can
choose between constant current with automatic restart or
latching shutdown. The high degree of efficiency keeps energy
consumption and heating in the control cabinet low, and the
compact metal housing also saves space.
Main product highlights
• 36 V DC/13 A
• 3-phase AC input 400 to 500 volts
• Extremely slim design – no lateral installation clearances
required
• Power Boost with 3 times the rated current (for 25 ms) for
tripping protective devices
• Extra power with 1.5 times the rated current (5 s/min) for brief
functional overload
• Choice of constant current or latching shutdown short-circuit
response
• Optional symmetrical load distribution for parallel operation
• Operating state on 3 LEDs
• Extremely high efficiency up to 94%
• Wide temperature range from -25 to +70 °C
• Comprehensive certifications, such as cULus, ATEX
• at rated input voltage 400 V
1.2 A
• at rated input voltage 500 V
1A
Switch-on current limiting (+25 °C),
max.
16 A
I²t, max.
0.8 A²·s
Built-in incoming fuse
none
Protection in the mains power input
(IEC 898)
Required: 3-pole connected
miniature circuit breaker 6 ... 16 A
characteristic C or circuit breaker
3RV2011-1DA10 (setting 3 A) or
3RV2711-1DD10 (UL 489)
Output
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
36 V
Total tolerance, static ±
3%
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
0.2 %
Residual ripple peak-peak, max.
100 mV
Spikes peak-peak, max. 
(bandwidth: 20 MHz)
200 mV
Adjustment range
36 ... 42 V
Product function 
Output voltage adjustable
Yes
Output voltage setting
via potentiometer; max. 480 W
Status display
Green LED for 36 V OK
Signaling
Relay contact (NO contact, 
rating 60 V DC/ 0.3 A) for 36 V OK
On/off behavior
No overshoot of Vout (soft start)
Startup delay, max.
2.5 s
Voltage increase time of the output
voltage maximum
500 ms
Rated current value Iout rated
13 A
Current range
0 ... 13 A
• Note
+60 ... +70 °C: Derating 2%/K
Supplied active power typical
468 W
Short-term overload current
39 A
• at short-circuit during operation
typical
Duration of overloading capability for
excess current
• at short-circuit during operation
25 ms
Constant overload current
• on short-circuiting during the 
start-up typical
14 A
Parallel switching for enhanced
performance
Yes; switchable characteristic
Numbers of parallel switchable units
for enhanced performance
2
Siemens KT 10.1 · 2016
6/17
6
© Siemens AG 2016
SITOP modular
3-phase, 36 V DC
■ Technical specifications (continued)
Article number
6EP3446-8SB10-0AY0
Article number
6EP3446-8SB10-0AY0
Product
SITOP PSU8200
Product
SITOP PSU8200
Power supply, type
36 V/13 A
Power supply, type
36 V/13 A
Efficiency
Mechanics
Efficiency at Vout rated, Iout rated,
approx.
94 %
Connection technology
Power loss at Vout rated, Iout rated,
approx.
30 W
• Supply input
L1, L2, L3, PE: 1 screw terminal each
for 0.2 ... 4 mm² single-core/finely
stranded
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
• Output
+, -: 2 screw terminals each for
0.2 ... 4 mm²
Dynamic load smoothing 
(Iout: 50/100/50 %), Uout ± typ.
1%
• Auxiliary
Load step setting time 
50 to 100%, typ.
0.2 ms
Load step setting time 
100 to 50%, typ.
0.2 ms
13, 14 (alarm signal): 
1 screw terminal each for
0.14 ... 1.5 mm²; 15, 16 (Remote): 
1 screw terminal each for
0.14 ... 1.5 mm²
Width of the enclosure
70 mm
Height of the enclosure
125 mm
Depth of the enclosure
125 mm
Closed-loop control
Dynamic load smoothing 
(Iout: 10/90/10 %), Uout ± typ.
6
screw-type terminals
Connections
2%
Load step setting time 10 to 90%, typ. 0.2 ms
Required spacing
Load step setting time 90 to 10%, typ. 0.2 ms
• top
50 mm
• bottom
50 mm
• left
0 mm
Setting time maximum
10 ms
Protection and monitoring
Output overvoltage protection
< 48 V
• right
0 mm
Current limitation, typ.
14 A
Weight, approx.
1.2 kg
Property of the output 
Short-circuit proof
Yes
Product feature of the enclosure
housing for side-by-side mounting
Yes
Short-circuit protection
Alternatively, constant current
characteristic approx. 14 A or
latching shutdown
Installation
Snaps onto DIN rail EN 60715
35x7.5/15
Electrical accessories
Buffer module
Mechanical accessories
Device identification label
20 mm × 7 mm, pale turquoise
3RT1900-1SB20
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Enduring short circuit current
RMS value
• typical
14 A
Overcurrent overload capability in
normal operation
overload capability 150 % Iout rated
up to 5 s/min
Overload/short-circuit indicator
LED yellow for "overload", 
LED red for "latching shutdown"
Safety
■ Ordering data
Primary/secondary isolation
Yes
Galvanic isolation
Safety extra low output voltage Vout
according to EN 60950-1
SITOP PSU8200 3-phase,
36 V DC/13 A
Protection class
Class I
Stabilized power supply
Input: 400 … 500 V 3 AC
Output: 36 V DC/13 A
Leakage current
• maximum
3.5 mA
• typical
0.9 mA
CE mark
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259
Explosion protection
No
FM approval
-
CB approval
Yes
Marine approval
GL, ABS
Degree of protection (EN 60529)
IP20
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature
• during operation
-25 ... +70 °C
with natural convection
- Note
• during transport
-40 ... +85 °C
• during storage
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
6/18
Siemens KT 10.1 · 2016
■ Accessories
Device labeling plates
Article No.
6EP3446-8SB10-0AY0
Article No.
3RT1900-1SB20
© Siemens AG 2016
SITOP modular
3-phase, 48 V DC
■ Overview
rated current for brief periods. In case of overload, you can
choose between constant current with automatic restart or
latching shutdown. The high degree of efficiency keeps energy
consumption and heating in the control cabinet low, and the
compact metal housing also saves space.
The 3-phase SITOP modular are technology power supplies for
sophisticated solutions and offer maximum functionality for use
in complex plants and machines. The wide-range input allows a
connection to almost any electrical power system worldwide and
ensures a high degree of safety even if there are large voltage
fluctuations. The power boost provides up to three times the
Main product highlights
• 48 V DC / 10 A and 20 A
• 3-phase wide-range input
• Extremely slim design – no lateral installation clearances
required
• Power Boost with 3 times the rated current (for 25 ms) for
tripping protective devices
• Extra power with 1.5 times the rated current (5 s/min) for brief
functional overload
• Selectable short-circuit response between constant current
and latching shutdown
• Optional symmetrical load distribution for parallel operation
• Operating status on 3 LEDs
• Extremely high efficiency to 94 %
• Wide temperature range from -25 to +70 °C
• Comprehensive certifications, such as cULus, ATEX and GL
■ Technical specifications
Article number
6EP1456-3BA00
6EP1457-3BA00
Product
SITOP PSU300M
SITOP PSU300M
Power supply, type
48 V/10 A
48 V/20 A
Input
3-phase AC
3-phase AC
Rated voltage value Vin rated
400 ... 500 V
400 ... 500 V
Voltage range AC
320 ... 575 V
320 ... 550 V
• Note
-
Starting from Vin > 340 V
Wide-range input
Yes
Yes
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
15 ms; at Vin = 400 V
6 ms; at Vin = 400 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 400 V
1.2 A
2.2 A
• at rated input voltage 500 V
1A
Input
Input current
Switch-on current limiting (+25 °C), max.
18 A
70 A
I²t, max.
0.8 A²·s
2.8 A²·s
Built-in incoming fuse
none
none
Protection in the mains power input (IEC 898)
Required: 3-pole connected miniature 
circuit breaker 6 ... 16 A characteristic C or 
circuit breaker 3RV2011-1DA10 (setting 3 A) 
or 3RV2711-1DD10 (UL 489)
Required: 3-pole connected miniature 
circuit breaker 10 ... 16 A characteristic C or 
circuit breaker 3RV2011-1DA10 (setting 3 A) 
or 3RV2711-1DD10 (UL 489)
Siemens KT 10.1 · 2016
6/19
6
© Siemens AG 2016
SITOP modular
3-phase, 48 V DC
■ Technical specifications (continued)
Article number
6EP1456-3BA00
6EP1457-3BA00
Product
SITOP PSU300M
SITOP PSU300M
Power supply, type
48 V/10 A
48 V/20 A
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
48 V
48 V
Total tolerance, static ±
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
0.2 %
0.2 %
Residual ripple peak-peak, max.
100 mV
100 mV
Residual ripple peak-peak, typ.
-
10 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
200 mV
200 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)
-
80 mV
Adjustment range
42 ... 56 V
42 ... 56 V
Product function 
Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer; max. 480 W
via potentiometer; max. 960 W
Status display
Green LED for 48 V OK
Green LED for 48 V OK
Signaling
Relay contact (NO contact, 
rating 60 V DC/ 0.3 A) for 48 V OK
via signaling module (6EP1961-3BA10)
On/off behavior
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
Startup delay, max.
2.5 s
2.5 s
Voltage rise, typ.
150 ms
20 ms
Voltage increase time of the output voltage 
maximum
500 ms
-
Rated current value Iout rated
10 A
20 A
Current range
0 ... 10 A
0 ... 20 A
• Note
+60 ... +70 °C: Derating 3%/K
-
Supplied active power typical
480 W
960 W
23 A
60 A
25 ms
25 ms
• on short-circuiting during the start-up typical
11 A
23 A
Parallel switching for enhanced performance
Yes; switchable characteristic
Yes; switchable characteristic
Numbers of parallel switchable units for enhanced
performance
2
2
Efficiency at Vout rated, Iout rated, approx.
93 %
90 %
Power loss at Vout rated, Iout rated, approx.
36 W
106 W
Dynamic mains compensation (Vin rated ±15 %),
max.
1%
-
Dynamic load smoothing (Iout: 50/100/50 %), 
Uout ± typ.
2%
-
Load step setting time 50 to 100%, typ.
2 ms
-
Load step setting time 100 to 50%, typ.
2 ms
-
Setting time maximum
10 ms
-
Output overvoltage protection
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Current limitation, typ.
11 A
23 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Alternatively, constant current characteristic
approx. 11 A or latching shutdown
Alternatively, constant current characteristic
approx. 23 A or latching shutdown
11 A
23 A
Output
6
Short-term overload current
• at short-circuit during operation typical
Duration of overloading capability for excess current
• at short-circuit during operation
Constant overload current
Efficiency
Closed-loop control
Protection and monitoring
Enduring short circuit current RMS value
• typical
Overcurrent overload capability in normal operation overload capability 150 % Iout rated up to 5 s/min
Overload/short-circuit indicator
6/20
Siemens KT 10.1 · 2016
LED yellow for "overload", 
LED red for "latching shutdown"
LED yellow for "overload", 
LED red for "latching shutdown"
© Siemens AG 2016
SITOP modular
3-phase, 48 V DC
■ Technical specifications (continued)
Article number
6EP1456-3BA00
6EP1457-3BA00
Product
SITOP PSU300M
SITOP PSU300M
Power supply, type
48 V/10 A
48 V/20 A
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout according to
EN 60950-1 and EN 50178
Safety extra low output voltage Vout according to 
EN 60950-1
Protection class
Class I
Class I
• maximum
3.5 mA
3.5 mA
• typical
-
0.68 mA
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1), 
File E197259
cULus-Listed (UL 508, CSA C22.2 No. 107.1), 
File E197259; cCSAus (CSA C22.2 No. 60950,
UL 60950)
Explosion protection
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus 
(CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I,
Div. 2, Group ABCD, T4
-
FM approval
-
-
CB approval
Yes
No
Marine approval
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
-10 ... +70 °C
0 ... 60 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
screw-type terminals
screw-type terminals
• Supply input
L1, L2, L3, PE: 1 screw terminal each for 
0.5 ... 2.5 mm² single-core/finely stranded
L1, L2, L3, PE: 1 screw terminal each for
0.2 ... 4 mm² single-core/finely stranded
• Output
+, -: 2 screw terminals each for 0.2 ... 4 mm²
+, -: 2 screw terminals each for 0.33 ... 10 mm²
• Auxiliary
13, 14 (alarm signal): 1 screw terminal each for 
0.14 ... 1.5 mm²
-
Width of the enclosure
70 mm
240 mm
Height of the enclosure
125 mm
125 mm
Depth of the enclosure
125 mm
125 mm
Weight, approx.
1.2 kg
3.2 kg
Product feature of the enclosure housing 
for side-by-side mounting
Yes
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
Snaps onto DIN rail EN 60715 35x15
Safety
Leakage current
6
EMC
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
Signaling module
Electrical accessories
Mechanical accessories
Device identification label 20 mm × 7 mm, 
pale turquoise 3RT1900-1SB20
-
MTBF at 40 °C
664 995 h
-
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Siemens KT 10.1 · 2016
6/21
© Siemens AG 2016
SITOP modular
3-phase, 48 V DC
■ Ordering data
SITOP PSU300M 3-phase,
48 V DC/10 A
Article No.
6EP1456-3BA00
Stabilized power supply
Input: 3 AC 400 … 500 V
Output: 48 V DC / 10 A
SITOP PSU300M 3-phase,
48 V DC / 20 A
6EP1457-3BA00
Stabilized power supply
Input: 3 AC 400 … 500 V
Output: 48 V DC/20 A
6
6/22
Siemens KT 10.1 · 2016
■ Accessories
Device labeling plates
Article No.
3RT1900-1SB20
7
© Siemens AG 2016
SITOP modular,
PSU8600 power supply system
7/2
7/5
7/10
7/13
Introduction
3-phase, basic units 24 V DC (PSU8600)
Modular system, 
expansions of outputs (CNX8600)
Modular system, buffering (BUF8600)
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
Introduction
■ Overview
As a unique power supply system with complete integration in
Totally Integrated Automation (TIA), SITOP PSU8600 sets new
standards in industrial power supplies. The benefits of this
integration are not only apparent during engineering in TIA
Portal but also result in reliable operation. Voltage and current
response thresholds can be set individually for each output of
the power supply system, and selective monitoring of each
output for overload results in fast fault location. Depending on
requirements additional modules from the modular system, such
as are used for buffering short power failures, can be added
without wiring overhead.
Comprehensive diagnostic and maintenance information is
available via PROFINET. It can be evaluated directly in SIMATIC
S7 and visualized in SIMATIC WinCC. Optimal support is also
provided for energy management of plant or machines: From the
acquisition of energy data from individual outputs, the specific
activation and deactivation of outputs via PROFIenergy, to direct
integration in power management systems.
• Reduced space requirement and costs due to multiple
integrated outputs with selective monitoring
• Individually configurable outputs (no need for additional
power supply for 5 V, 12 V or 15 V)
• Compensation for power losses can be set separately for
each output
• Narrow width without lateral installation clearances
• Low temperature rise in the control cabinet due to very high
efficiency
• If required, extra units from the modular system (more outputs,
buffer module) can be added without wiring effort
• Reliable operation due to bridging of short-term power failures
• Two integrated Ethernet/PROFINET ports (no external switch
required)
• Complete integration in TIA requires less time and reduces
costs during configuration (TIA Portal) and in operation
• SIMATIC S7 function blocks for easy integration in STEP 7 user
programs
• Fast integration in operator control and monitoring with WinCC
faceplates
• Preventive maintenance reduces downtimes
• Energy savings during breaks through targeted switching of
outputs
• Easy integration in energy management systems 
(PROFIenergy protocol)
■ Application
The SITOP PSU8600 power supply system is used as the central
DC power supply of larger plants or machines with networked
automation systems. The PSU8600 can be directly integrated
into the LAN infrastructure by means of the two integrated
PROFINET ports.
SIMATIC
S7-1200/300/400/1500
Step 7
Panel / PC
WinCC
PC / PG
TIA Portal, Step 7
Controller
PROFINET
24 V DC
further monitored
load circuits
SITOP PSU8600
power supply system
G_KT01_XX_01047
7
■ Benefits
An extremely high level of reliability is achieved for the 
DC voltage supply by monitoring the individual DC branches for
overload and bridging short-term power failures (brownouts). 
Complete transparency and fast fault localization are achieved
by providing comprehensive diagnostic and maintenance 
information (e.g. load states of the outputs, phase/network 
failure, overtemperature) via PROFINET.
Energy-optimized operation is supported by measuring the 
current power and voltage values of the individual outputs as
well as the individual activation and deactivation of the 
DC outputs via PROFIenergy during break times.
7/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
Introduction
■ Design
Basic devices
• SITOP PSU8600, 3-phase power supply, 24 V DC/20 A/4x 5 A
with four outputs (max. 5 A per output) and two Ethernet/
PROFINET ports
• SITOP PSU8600, 3-phase power supply, 24 V DC/20 A 
with one output and two Ethernet/PROFINET ports
• SITOP PSU8600, 3-phase power supply, 24 V DC/40 A/
4x 10 A with four outputs (max. 10 A per output) and two
Ethernet/PROFINET ports
• SITOP PSU8600, 3-phase power supply, 24 V DC/40 A 
with one output and two Ethernet/PROFINET ports
Modular system, consisting of:
• SITOP CNX8600 4x 5 A 
(expansion module with 4 outputs at 5 A each)
• SITOP CNX8600 4x 10 A 
(expansion module with 4 outputs at 10 A each)
• SITOP BUF8600 100 ms/40 A 
(buffer module with 100 ms at 40 A)
• SITOP BUF8600 300 ms/40 A 
(buffer module with 300 ms at 40 A)
• SITOP BUF8600 4 s/40 A 
(buffer module with 4 s at 40 A)
• SITOP BUF8600 10 s/40 A 
(buffer module with 10 s at 40 A)
You can connect up to four CNX8600 expansion modules as well
as up to two BUF8600 buffer modules to the PSU8600 basic device. Connection takes place on top of the modules without any
wiring by means of the System Clip Link, a connecting plug for
system data and power supply. The order of the up to six possible add-on modules is random so that an existing configuration
does not have to be altered if a module is added later.
■ Function
Supply of connected loads
An individual supply voltage can be set at each output of the
power supply system. This means you can supply loads with
different rated voltages simultaneously with only one device.
Plus the voltage drop caused by the different cable lengths can
be compensated individually, which means each load can be
supplied with the optimum voltage.
■ Function (continued)
Communication
Comprehensive diagnostic information can be queried and
processed via the integrated Ethernet/PROFINET interface
during operation for both the device status as well as the status
of the individual outputs. This results in complete transparency,
minimal downtimes and quick fault location. The integrated web
server also permits remote monitoring of the power supply
system.
Buffering
In case of short-term power failure, the buffer module supplies
the load current for supplying the outputs by means of its energy
storage units Maintenance-free electrolytic capacitors or double-layer capacitors are used as energy-storage units.
■ Integration
Software for TIA-based automation systems
Different software components are available to facilitate easy
integration of the SITOP PSU8600 in the TIA environment.
Engineering is simple via the TIA Portal. Special function blocks
for SIMATIC S7-300, S7-400, S7-1200 and S7-1500 also support
integration in the STEP 7 user program.
The comprehensive operating and diagnostic data of the power
supply system can be visualized using ready-to-use PSU8600
faceplates for WinCC.
TIA Portal
• User-friendly, failsafe integration of SITOP PSU8600 in the
PROFINET network by means of drag-and-drop
• Convenient configuration of the PSU8600 basic units and
CNX8600 and BUF8600 add-on modules though simple
selection from the TIA Portal hardware catalog
• Free download of HSP (Hardware Support Package) for 
TIA Portal version V13 or higher available at 
http://support.automation.siemens.com/WW/view/en/102254062
• Free GSD file (Generic Station Description) for STEP 7 V 5.5
http://support.automation.siemens.com/WW/view/en/102254061
Monitoring of the outputs for overload
Each output of the power supply system is individually monitored for overload. If the load current exceeds the set response
threshold, the output is shut down according to specified 
time-current characteristics. All other outputs continue to be
supplied reaction-free.
Enabling and disabling the outputs
Each output can be manually enabled or disabled directly on the
device (e.g. for commissioning or service) and an overload
tripping can be reset. Outputs disabled due to overload can also
be reset remotely using a remote signal signal (24 V input).
Error-free establishment of the PROFINET connection between the
SITOP PSU8600 and the controller is easy with the TIA Portal
In addition, program-controlled enabling and disabling of the
outputs is possible using the integrated Ethernet/
PROFINET interface. This also means you can disable individual
outputs by means of PROFIenergy during breaks to save energy.
Siemens KT 10.1 · 2016
7/3
7
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
Introduction
■ Integration (continued)
STEP 7 function blocks
Web server
Function blocks are available for STEP 7 user programs on
SIMATIC S7-300/400/1200/1500. They allow further processing
of the PSU8600 operating data.
• Function blocks for STEP 7 V5.5
• Function blocks for STEP 7 V13
A web server is integrated in the PSU8600 basic unit for remote
monitoring of the power supply system.
Free download from:
http://support.automation.siemens.com/WW/view/en/102379345
Faceplates for WinCC
Ready-to-use faceplates save programming time during
visualization of the SITOP PSU8600. The faceplates show all
relevant statuses and values of the power supply system and the
individual outputs and are available for the following systems:
• Faceplates for WinCC V7.3
• Faceplates for WinCC flexible 2008 SP3
• Faceplates for WinCC Comfort/Advanced/ Professional V13
Remote monitoring of
• Hardware configuration data
• Operating data of the basic unit, all connected add-on
modules and the individual outputs
• Alarm messages
Remote access via
• Firefox V29, Internet Explorer 8, 10, 11
• IP address
• User name and password
Free download from:
http://support.automation.siemens.com/WW/view/en/102379345
7
The password-protected web server offers a view of the configuration
and operating data.
■ More information
Select the appropriate power supply quickly and easily with the
PSU8600 SITOP Selection Tool:
The pre-compiled WinCC faceplates show all the relevant data of the
power supply system in an easy-to-understand display.
7/4
Siemens KT 10.1 · 2016
http://www.siemens.de/sitop-selection-tool
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
3-phase, basic units 24 V DC (PSU8600)
■ Overview
SIMATIC S7 and visualized in SIMATIC WinCC. Energy
management is also optimally supported by collecting the
energy data for each output as well as individual activation and
deactivation of the outputs via PROFIenergy.
The ultra-slim 3-phase basic units of the SITOP PSU8600 power
supply system include one Ethernet/PROFINET interface as well
as one or four configurable outputs (voltage and current
threshold) with selective monitoring. Additional units from the
modular system can be added as required to the basic unit,
without wiring overhead, in order to increase the number of
outputs (CNX8600) or to extend the mains buffering time
(BUF8600). Comprehensive diagnostic and maintenance information is available via PROFINET. It can be evaluated directly in
Main product highlights
• 3-phase wide-range input 400 to 500 V 3 AC for global use
• Extremely slim design with very high efficiency of up to 94%
• Versions with a configurable output with up to 20 A or 40 A and
selective monitoring
• Versions with four integrated, individually configured outputs
with up to 5 A or 10 A each and selective monitoring
• Voltage and response threshold can be set separately and are
infinitely adjustable for each output
• Extra power with 1.5 times the rated current (5 s/min) for brief,
operational overload
• Integrated Ethernet/PROFINET interface (2 ports)
• Easy configuration in the TIA Portal
• Comprehensive diagnostic information during operation
• Outputs can be deactivated and activated in a targeted
manner with PROFIenergy
• Individual expansion options from the modular system
(expansion modules, buffer modules) without wiring overhead
■ Technical specifications
Article number
6EP3436-8SB00-2AY0
6EP3437-8SB00-2AY0
6EP3436-8MB00-2CY0
6EP3437-8MB00-2CY0
Product
SITOP PSU8600
SITOP PSU8600
SITOP PSU8600
SITOP PSU8600
Power supply, type
24 V/20 A
24 V/40 A
24 V/20 A/4x 5 A
24 V/40 A/4x 10 A
Input
3-phase AC
3-phase AC
3-phase AC
3-phase AC
Rated voltage value Vin rated
400 ... 500 V
400 ... 500 V
400 ... 500 V
400 ... 500 V
Voltage range AC
320 ... 575 V
320 ... 575 V
320 ... 575 V
320 ... 575 V
• Note
Derating 320 … 360 and
530 … 575 V
Derating 320 … 360 and
530 … 575 V
Derating 320 … 360 and
530 … 575 V
Derating 320 … 360 and
530 … 575 V
Wide-range input
Yes
Yes
Yes
Yes
Mains buffering at Iout rated, min.
15 ms; at Vin = 400 V;
Prioritized voltage supply at
power failure via DIP switch
can be selected (only with
expansion module CNX8600)
15 ms; at Vin = 400 V;
Prioritized voltage supply at
power failure via DIP switch
can be selected (only with
expansion module CNX8600)
15 ms; at Vin = 400 V;
Prioritized supply Output 1 at
power failure can be selected
via DIP switch
15 ms; at Vin = 400 V;
Prioritized supply Output 1 at
power failure can be selected
via DIP switch
Rated line frequency
50 ... 60 Hz
50 ... 60 Hz
50 ... 60 Hz
50 ... 60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 400 V
1.4 A
2.75 A
1.4 A
2.75 A
• at rated input voltage 500 V
1.1 A
2.2 A
1.1 A
2.2 A
Switch-on current limiting (+25 °C),
max.
14 A
14 A
14 A
14 A
I²t, max.
1.2 A²·s
2.24 A²·s
1.2 A²·s
2.24 A²·s
Built-in incoming fuse
none
none
none
none
Protection in the mains power input
(IEC 898)
Required: 3-pole connected
miniature circuit breaker
6 ... 16 A characteristic C 
or circuit breaker 
3RV2011-1DA10 (setting 3 A)
or 3RV2711-1DD10 (UL 489)
Required: 3-pole connected
miniature circuit breaker
10 ... 16 A characteristic C 
or circuit breaker 
3RV2011-1DA10 (setting 3 A)
or 3RV2711-1DD10 (UL 489)
Required: 3-pole connected
miniature circuit breaker
6 ... 16 A characteristic C 
or circuit breaker 
3RV2011-1DA10 (setting 3 A)
or 3RV2711-1DD10 (UL 489)
Required: 3-pole connected
miniature circuit breaker
10 ... 16 A characteristic C 
or circuit breaker 
3RV2011-1DA10 (setting 3 A)
or 3RV2711-1DD10 (UL 489)
Input
Input current
Siemens KT 10.1 · 2016
7/5
7
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
3-phase, basic units 24 V DC (PSU8600)
■ Technical specifications (continued)
Article number
6EP3436-8SB00-2AY0
6EP3437-8SB00-2AY0
6EP3436-8MB00-2CY0
6EP3437-8MB00-2CY0
Product
SITOP PSU8600
SITOP PSU8600
SITOP PSU8600
SITOP PSU8600
Power supply, type
24 V/20 A
24 V/40 A
24 V/20 A/4x 5 A
24 V/40 A/4x 10 A
Output
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Number of outputs
1
1
4
4
Rated voltage Vout DC
24 V
24 V
24 V
24 V
Output
Output voltage
7
• at output 1 at DC Rated value
24 V
24 V
24 V
24 V
• at output 2 at DC Rated value
-
-
24 V
24 V
• at output 3 at DC Rated value
-
-
24 V
24 V
• at output 4 at DC Rated value
-
-
24 V
24 V
Total tolerance, static ±
3%
3%
3%
3%
Static mains compensation, approx. 0.2 %
0.2 %
0.2 %
0.2 %
Static load balancing, approx.
0.1 %
0.1 %
0.1 %
0.1 %
Residual ripple peak-peak, max.
100 mV
100 mV
100 mV
100 mV
Spikes peak-peak, max. 
(bandwidth: 20 MHz)
200 mV
200 mV
200 mV
200 mV
Adjustment range
5 ... 28 V
5 ... 28 V
5 ... 28 V
5 ... 28 V
Product function 
Output voltage adjustable
Yes
Yes
Yes
Yes
Output voltage setting
via potentiometer; 
Derating > 24 V: 4%/V; 
max. 480 W overall system
via potentiometer; 
Derating > 24 V: 4%/V; 
max. 960 W overall system
via potentiometer; 
Derating > 24 V: 4%/V; 
max. 120 W per output, 
max. 480 W overall system
via potentiometer; 
Derating > 24 V: 4%/V; 
max. 240 W per output, 
max. 960 W overall system
Status display
3-color LED for operating
state device; LED for
operating mode 
manual/remote; 4 LEDs for
communication PROFINET;
3-color LED for operating
state output
3-color LED for operating
state device; LED for
operating mode 
manual/remote; 4 LEDs for
communication PROFINET;
3-color LED for operating
state output
3-color LED for operating
state device; LED for
operating mode 
manual/remote; 4 LEDs for
communication PROFINET;
3-color LED per output for
operating state output; LED
green for parallel operation
Output 1 and 2 / 3 and 4
3-color LED for operating
state device; LED for
operating mode 
manual/remote; 4 LEDs for
communication PROFINET;
3-color LED per output for
operating state output; LED
green for parallel operation
Output 1 and 2 / 3 and 4
Signaling
Relay contact (changeover
contact, contact current
capacity DC 60 V/0.3 A) for
"Operating state OK"
Relay contact (changeover
contact, contact current
capacity DC 60 V/0.3 A) for
"Operating state OK"
Relay contact (changeover
contact, contact current
capacity DC 60 V/0.3 A) for
"Operating state OK"
Relay contact (changeover
contact, contact current
capacity DC 60 V/0.3 A) for
"Operating state OK"
On/off behavior
No overshoot of Vout 
(soft start)
No overshoot of Vout 
(soft start)
No overshoot of Vout 
(soft start)
No overshoot of Vout 
(soft start)
Startup delay, max.
1s
1s
1 s; Without on-delay of the
outputs
1 s; Without on-delay of the
outputs
connection of outputs operating
Simultaneous connecting-in
of all outputs after device
booting or delay time of
25 ms, 100 ms or
"load-optimized" for
sequential cutting-in of the
outputs via DIP switches can
be set (only with expansion
module CNX8600)
Simultaneous connecting-in
of all outputs after device
booting or delay time of
25 ms, 100 ms or
"load-optimized" for
sequential cutting-in of the
outputs via DIP switches can
be set (only with expansion
module CNX8600)
Simultaneous connecting-in
of all outputs after device
booting or delay time of
25 ms, 100 ms or
"load-optimized" for
sequential cutting-in of the
outputs via DIP switches can
be set
Simultaneous connecting-in
of all outputs after device
booting or delay time of
25 ms, 100 ms or
"load-optimized" for
sequential cutting-in of the
outputs via DIP switches can
be set
Voltage increase time of the output
voltage maximum
500 ms
500 ms
500 ms
500 ms
Rated current value Iout rated
20 A
40 A
20 A
40 A
• per output
20 A
40 A
5A
10 A
• at output 1 Rated value
20 A
40 A
5A
10 A
• at output 2 Rated value
-
-
5A
10 A
• at output 3 Rated value
-
-
5A
10 A
• at output 4 Rated value
-
-
5A
10 A
Current range
0 ... 20 A
0 ... 40 A
0 ... 20 A
0 ... 40 A
• Note
+50 ... +60 °C: Derating
2.5%/K; no derating in
connection with expansion
module CNX8600 and total
load of the outputs at the
basic device max. 240 W
+50 ... +60 °C: Derating
2.5%/K; no derating in
connection with expansion
module CNX8600 and total
load of the outputs at the
basic device max. 480 W
+50 ... +60 °C: Derating
2.5%/K; no derating in
connection with expansion
module CNX8600 and total
load of the outputs at the
basic device max. 240 W
+50 ... +60 °C: Derating
2.5%/K; no derating in
connection with expansion
module CNX8600 and total
load of the outputs at the
basic device max. 480 W
Output current
7/6
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
3-phase, basic units 24 V DC (PSU8600)
■ Technical specifications (continued)
Article number
6EP3436-8SB00-2AY0
6EP3437-8SB00-2AY0
6EP3436-8MB00-2CY0
6EP3437-8MB00-2CY0
Product
SITOP PSU8600
SITOP PSU8600
SITOP PSU8600
SITOP PSU8600
Power supply, type
24 V/20 A
24 V/40 A
24 V/20 A/4x 5 A
24 V/40 A/4x 10 A
Supplied active power typical
480 W
960 W
480 W
960 W
Overcurrent overload capability in
normal operation
Total system overloadable
150% Ia rated to 5 s/min
Total system overloadable
150% Ia rated to 5 s/min
Total system overloadable
150% Ia rated to 5 s/min
Total system overloadable
150% Ia rated to 5 s/min
• at short-circuit during operation
typical
60 A
120 A
-
-
• Note
only in operation without
CNX8600 extension module
only in operation without
CNX8600 extension module
-
-
• at short-circuit during operation
25 ms
25 ms
-
-
Product feature parallel switching 
of outputs
-
-
Yes; Parallel circuit Output 1 Yes; Parallel circuit Output 1
with 2 or Output 3 with 4 can with 2 or Output 3 with 4 can
be selected via DIP switch
be selected via DIP switch
Parallel switching for enhanced
performance
Yes; suitable output characteristics via DIP switch can
be selected
Yes; suitable output characteristics via DIP switch can
be selected
No
No
2
-
-
Short-term overload current
Duration of overloading capability
for excess current
Numbers of parallel switchable units 2
for enhanced performance
Efficiency
Efficiency at Vout rated, Iout rated,
approx.
93 %
93 %
93 %
93 %
Power loss at Vout rated, Iout rated,
approx.
34 W
72 W
34 W
72 W
Power loss [W] during no-load
operation maximum
12 W
20 W
12 W
20 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
0.1 %
0.1 %
0.1 %
Dynamic load smoothing 
(Iout: 50/100/50 %), Uout ± typ.
0.4 %
0.4 %
0.4 %
0.4 %
Setting time maximum
10 ms
10 ms
10 ms
10 ms
Output overvoltage protection
< 35 V
< 35 V
< 35 V
< 35 V
Property of the output 
Short-circuit proof
Yes
Yes
Yes
Yes
Short-circuit protection
electronic overload cut-off;
optionally constant current
operation can be selected 
via DIP switches
electronic overload cut-off;
optionally constant current
operation can be selected 
via DIP switches
electronic overload cut-off;
optionally constant current
operation can be selected 
for Output 4 via DIP switches
electronic overload cut-off;
optionally constant current
operation can be selected 
for Output 4 via DIP switches
adjustable response value current of 2 ... 20 A
current-dependent overload trip
4 ... 40 A
0.5 ... 5 A
0.5 ... 10 A
type of threshold value setting
via potentiometer
via potentiometer
via potentiometer
via potentiometer
characteristics of electronic
overload switch-off
Ia >1.0…<1.5 x Ia threshold
permissible for 5 s; 
Ia limit (= 1.5 x Ia threshold) 
permissible for 200 ms
Ia >1.0…<1.5 x Ia threshold
permissible for 5 s; 
Ia limit (= 1.5 x Ia threshold) 
permissible for 200 ms
Ia >1.0…<1.5 x Ia threshold
permissible for 5 s; 
Ia limit (= 1.5 x Ia threshold) 
permissible for 200 ms
Ia >1.0…<1.5 x Ia threshold
permissible for 5 s; 
Ia limit (= 1.5 x Ia threshold)
permissible for 200 ms
characteristics of constant current
operation
Ia limit (= 1.5 x Ia threshold)
permissible for 5 s,
afterwards Ia threshold
continuous
Ia limit (= 1.5 x Ia threshold)
permissible for 5 s,
afterwards Ia threshold
continuous
Ia limit (= 1.5 x Ia threshold)
permissible for 5 s,
afterwards Ia threshold
continuous
Ia limit (= 1.5 x Ia threshold)
permissible for 5 s,
afterwards Ia threshold
continuous
Via sensor
Via sensor per output
Via sensor per output
7
Closed-loop control
Protection and monitoring
Reset
Via sensor
Remote reset
Non-electrically isolated 24 V Non-electrically isolated 24 V Non-electrically isolated 24 V Non-electrically isolated 24 V
input (signal level "high" 
input (signal level "high" 
input (signal level "high" 
input (signal level "high" 
at > 15 V)
at > 15 V)
at > 15 V)
at > 15 V)
Overload/short-circuit indicator
3-color LED for operating
state device; 3-color LED 
for operating state output
3-color LED for operating
state device; 3-color LED 
for operating state output
3-color LED for operating
state device; 3-color LED 
per output for operating state
output
3-color LED for operating
state device; 3-color LED 
per output for operating state
output
Ethernet/PROFINET
Ethernet/PROFINET
Ethernet/PROFINET
Ethernet/PROFINET
Interface
Specification interface
Siemens KT 10.1 · 2016
7/7
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
3-phase, basic units 24 V DC (PSU8600)
■ Technical specifications (continued)
Article number
6EP3436-8SB00-2AY0
6EP3437-8SB00-2AY0
6EP3436-8MB00-2CY0
6EP3437-8MB00-2CY0
Product
SITOP PSU8600
SITOP PSU8600
SITOP PSU8600
SITOP PSU8600
Power supply, type
24 V/20 A
24 V/40 A
24 V/20 A/4x 5 A
24 V/40 A/4x 10 A
Primary/secondary isolation
Yes
Yes
Yes
Yes
Galvanic isolation
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage Uout acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
Class I
Class I
• maximum
3.5 mA
3.5 mA
3.5 mA
3.5 mA
CE mark
Yes
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508,
CSA C22.2 No. 107.1), 
File E197259; cCSAus 
(CSA C22.2 No. 60950-1,
UL 60950-1)
cULus-Listed (UL 508,
CSA C22.2 No. 107.1), 
File E197259; cCSAus
(CSA C22.2 No. 60950-1,
UL 60950-1)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259; cCSAus 
(CSA C22.2 No. 60950-1,
UL 60950-1)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259; cCSAus 
(CSA C22.2 No. 60950-1,
UL 60950-1)
Explosion protection
IECEx Ex nA nC IIC T4 Gc;
IECEx Ex nA nC IIC T4 Gc;
IECEx Ex nA nC IIC T4 Gc;
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC ATEX (EX) II 3G Ex nA nC IIC ATEX (EX) II 3G Ex nA nC IIC ATEX (EX) II 3G Ex nA nC IIC
T4 Gc
T4 Gc
T4 Gc
T4 Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T4
FM approval
-
-
-
-
CB approval
Yes
Yes
Yes
Yes
Marine approval
GL; ABS in process
GL; ABS in process
GL; ABS in process
GL; ABS in process
Degree of protection (EN 60529)
IP20
IP20
IP20
IP20
Emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
EN 61000-3-2
EN 61000-3-2
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
-25 ... +60 °C
-25 ... +60 °C
-25 ... +60 °C
-25 ... +60 °C
with natural convection
with natural convection
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3,
no condensation
Climate class 3K3,
no condensation
Climate class 3K3, 
no condensation
Climate class 3K3, 
no condensation
Plug-in terminals with
screwed connection
Plug-in terminals with
screwed connection
Plug-in terminals with
screwed connection
Plug-in terminals with
screwed connection
• Supply input
L1, L2, L3, PE: Plug-in
terminal with 1 screwed
connection each for
0.08 ... 4 mm² single-wire/
fine stranded
L1, L2, L3, PE: Plug-in
terminal with 1 screwed
connection each for
0.08 ... 4 mm² single-wire/
fine stranded
L1, L2, L3, PE: Plug-in
terminal with 1 screwed
connection each for
0.08 ... 4 mm² single-wire/
fine stranded
L1, L2, L3, PE: Plug-in
terminal with 1 screwed
connection each for
0.08 ... 4 mm² single-wire/
fine stranded
• Output
Output: plug-in terminals with
2 screw connectors for
0.08 ... 4 mm²; 0 V: 
screw terminal with 3 screw
connectors for 0.08 ... 4 mm²
Output: plug-in terminals with
2 screw connectors for
0.2 ... 10 mm²; 0 V: 
screw terminal with 3 screw
connectors for 0.2 ... 10 mm²
1, 2, 3, 4: Two plug-in
terminals (1, 2 and 3, 4) with
2 screwed connections each
for 0.2 ... 2.5 mm²; 0 V: 
Plug-in terminal with 
3 screwed connections for
0.08 ... 4 mm²
1, 2, 3, 4: Two plug-in
terminals (1, 2 and 3, 4) with
2 screwed connections each
for 0.2 ... 2.5 mm²; 0 V: 
Plug-in terminal with 
3 screwed connections for
0.5 ... 10 mm²
• Auxiliary
RST (Reset): Plug-in terminal
(together with alarm signal)
with 1 screwed connection
for 0.2 ... 1.5 mm²
RST (Reset): Plug-in terminal
(together with alarm signal)
with 1 screwed connection
for 0.2 ... 1.5 mm²
RST (Reset): Plug-in terminal
(together with alarm signal)
with 1 screwed connection
for 0.2 ... 1.5 mm²
RST (Reset): Plug-in terminal
(together with alarm signal)
with 1 screwed connection
for 0.2 ... 1.5 mm²
• Signaling contact
11, 12, 14 (alarm signal):
Plug-in terminal (together
with Reset) with 1 screwed
connection each for
0.2 ... 1.5 mm²
11, 12, 14 (alarm signal):
Plug-in terminal (together
with Reset) with 1 screwed
connection each for
0.2 ... 1.5 mm²
11, 12, 14 (alarm signal):
Plug-in terminal (together
with Reset) with 1 screwed
connection each for
0.2 ... 1.5 mm²
11, 12, 14 (alarm signal):
Plug-in terminal (together
with Reset) with 1 screwed
connection each for
0.2 ... 1.5 mm²
• removable terminal at input
Yes
Yes
Yes
Yes
• removable terminal at output
Yes
Yes
Yes
Yes
Design of the interface for
communication
PROFINET/Ethernet: two
PROFINET/Ethernet: two
PROFINET/Ethernet: two
PROFINET/Ethernet: two
RJ45 sockets (2-port switch) RJ45 sockets (2-port switch) RJ45 sockets (2-port switch) RJ45 sockets (2-port switch)
Safety
Leakage current
7
EMC
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
Product function
7/8
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
3-phase, basic units 24 V DC (PSU8600)
■ Technical specifications (continued)
Article number
6EP3436-8SB00-2AY0
6EP3437-8SB00-2AY0
6EP3436-8MB00-2CY0
6EP3437-8MB00-2CY0
Product
SITOP PSU8600
SITOP PSU8600
SITOP PSU8600
SITOP PSU8600
Power supply, type
24 V/20 A
24 V/40 A
24 V/20 A/4x 5 A
24 V/40 A/4x 10 A
Suitability for interaction modular
system
Yes
Yes
Yes
Yes
Width of the enclosure
80 mm
125 mm
100 mm
125 mm
Height of the enclosure
125 mm
125 mm
125 mm
125 mm
Depth of the enclosure
150 mm
150 mm
150 mm
150 mm
• top
50 mm
50 mm
50 mm
50 mm
• bottom
50 mm
50 mm
50 mm
50 mm
• left
0 mm
0 mm
0 mm
0 mm
• right
0 mm
0 mm
0 mm
0 mm
Weight, approx.
1.8 kg
2.6 kg
2 kg
2.6 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Yes
Yes
Installation
Snaps onto DIN rail
EN 60715 35x15
Snaps onto DIN rail
EN 60715 35x15
Snaps onto DIN rail
EN 60715 35x15
Snaps onto DIN rail
EN 60715 35x15
Electrical accessories
Expansion modules
CNX8600, buffer modules
BUF8600
Expansion modules
CNX8600, buffer modules
BUF8600
Expansion modules
CNX8600, buffer modules
BUF8600
Expansion modules
CNX8600, buffer modules
BUF8600
Mechanical accessories
Device identification label
20 mm × 7 mm, 
TI-grey 3RT2900-1SB20
Device identification label
20 mm × 7 mm, 
TI-grey 3RT2900-1SB20
Device identification label
20 mm × 7 mm, 
TI-grey 3RT2900-1SB20
Device identification label
20 mm × 7 mm, 
TI-grey 3RT2900-1SB20
Specifications at rated input
voltage and ambient
temperature +25 °C (unless
otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C (unless
otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C (unless
otherwise specified)
Required spacing
226 272 h
MTBF at 40 °C
Other information
■ Ordering data
SITOP PSU8600 3-phase,
24 V DC/20 A with 
PN/IE connection
Article No.
6EP3436-8SB00-2AY0
SITOP CNX8600 4 x 10 A 
expansion module
6EP3437-8SB00-2AY0
6EP3436-8MB00-2CY0
Stabilized power supply
Input: 400 … 500 V 3 AC
Output: 24 V DC/40 A/4 x 10 A
6EP4437-8XB00-0CY0
6EP4297-8HB00-0XY0
For SITOP PSU8600
Buffer capacity 100 ms/40 A
SITOP BUF8600 300 ms 
buffer module
Stabilized power supply
Input: 400 … 500 V AC 3 AC
Output: 24 V DC/20 A/4 x 5 A
SITOP PSU8600 3-phase,
24 V DC/40 A/4 x 10 A with 
PN/IE connection
6EP4436-8XB00-0CY0
For SITOP PSU8600
Output: 24 V DC/4 x 10 A
SITOP BUF8600 100 ms 
buffer module
Stabilized power supply
Input: 400 … 500 V AC 3 AC
Output: 24 V DC/40 A
SITOP PSU8600 3-phase,
24 V DC/20 A/4 x 5 A with 
PN/IE connection
SITOP CNX8600 4 x 5 A 
expansion module
Article No.
For SITOP PSU8600
Output: 24 V DC/4 x 5 A
Stabilized power supply
Input: 400 … 500 V AC 3 AC
Output: 24 V DC/20 A
SITOP PSU8600 3-phase,
24 V DC/40 A with 
PN/IE connection
■ Accessories
Specifications at rated input
voltage and ambient
temperature +25 °C (unless
otherwise specified)
6EP4297-8HB10-0XY0
For SITOP PSU8600
Buffer capacity 300 ms/40 A
6EP3437-8MB00-2CY0
SITOP BUF8600 4 s 
buffer module
6EP4293-8HB00-0XY0
For SITOP PSU8600 
Buffer capacity 4 s/40 A
SITOP BUF8600 10 s 
buffer module
6EP4295-8HB00-0XY0
For SITOP PSU8600 
Buffer capacity 10 s/40 A
Device labeling plates
3RT1900-1SB20
Siemens KT 10.1 · 2016
7/9
7
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
Modular system, expansion of outputs (CNX8600)
■ Overview
The CNX8600 expansion modules are part of the SITOP
PSU8600 modular system and expand the basic unit by increasing the number of selectively monitored outputs.
You can connect up to four CNX8600 expansion modules to the
PSU8600 basic device. The connection takes place on top of the
modules without any wiring by means of the System Clip Link, a
connecting plug for system data and power supply.
Main product highlights
• Four integrated outputs with up to 5 A or 10 A each and
selective monitoring
• Voltage and response threshold can be set separately and are
infinitely adjustable for each output
• Comprehensive diagnostic information during operation via
the PSU8600 basic unit
• Outputs can be activated and deactivated in a targeted
manner with PROFIenergy via the PSU8600 basic unit
• Easy connection without wiring overhead
• Slim design
■ Technical specifications
7
Article number
6EP4436-8XB00-0CY0
6EP4437-8XB00-0CY0
Product
SITOP CNX8600
SITOP CNX8600
Power supply, type
4x 5 A
4x 10 A
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Number of outputs
4
4
Rated voltage Vout DC
24 V
24 V
Output
Output voltage
• at output 1 at DC Rated value
24 V
24 V
• at output 2 at DC Rated value
24 V
24 V
• at output 3 at DC Rated value
24 V
24 V
• at output 4 at DC Rated value
24 V
24 V
Total tolerance, static ±
3%
3%
Static mains compensation, approx.
0.2 %
0.2 %
Static load balancing, approx.
0.1 %
0.1 %
Residual ripple peak-peak, max.
100 mV
100 mV
Spikes peak-peak, max. 
(bandwidth: 20 MHz)
200 mV
200 mV
Adjustment range
5 ... 28 V
5 ... 28 V
Product function Output voltage
adjustable
Yes
Yes
Output voltage setting
via potentiometer; Derating > 24 V: 4%/V; 
max. 120 W per output
via potentiometer; Derating > 24 V: 4%/V; 
max. 240 W per output
Status display
3-color LED for operating state module; 
3-color LED per output for operating state output
3-color LED for operating state module; 
3-color LED per output for operating state output
Signaling
Relay contact (changeover contact, contact current
capacity DC 60 V/0.3 A) for "Operating state OK" at 
power supply unit PSU8600
Relay contact (changeover contact, contact current
capacity DC 60 V/0.3 A) for "Operating state OK" at 
power supply unit PSU8600
On/off behavior
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
Startup delay, max.
1.5 s; Without on-delay of the outputs
1.5 s; Without on-delay of the outputs
connection of outputs operating
Simultaneous connecting-in of all outputs after device
booting or delay time of 25 ms, 100 ms or "load-optimized"
for sequential cutting-in of the outputs via DIP switches at
power supply unit PSU8600 can be set
Simultaneous connecting-in of all outputs after device
booting or delay time of 25 ms, 100 ms or "load-optimized"
for sequential cutting-in of the outputs via DIP switches at
power supply unit PSU8600 can be set
Voltage increase time of the output
voltage maximum
500 ms
500 ms
Rated current value Iout rated
20 A
40 A
7/10
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
Modular system, expansion of outputs (CNX8600)
■ Technical specifications (continued)
Article number
6EP4436-8XB00-0CY0
6EP4437-8XB00-0CY0
Product
SITOP CNX8600
SITOP CNX8600
Power supply, type
4x 5 A
4x 10 A
• per output
5A
10 A
• at output 1 Rated value
5A
10 A
• at output 2 Rated value
5A
10 A
• at output 3 Rated value
5A
10 A
• at output 4 Rated value
5A
10 A
Current range
0 ... 20 A
0 ... 40 A
• Note
No increase in the maximum output power of the overall
system SITOP PSU8600 via the expansion module
SITOP CNX8600 possible
No increase in the maximum output power of the overall
system SITOP PSU8600 via the expansion module
SITOP CNX8600 possible
Supplied active power typical
480 W
960 W
Product feature parallel switching of
outputs
No
No
Parallel switching for enhanced
performance
No
No
Efficiency at Vout rated, Iout rated,
approx.
97 %
97 %
Power loss at Vout rated, Iout rated,
approx.
15 W
30 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
0.1 %
Dynamic load smoothing 
(Iout: 50/100/50 %), Uout ± typ.
0.4 %
0.4 %
Setting time maximum
10 ms
10 ms
Output overvoltage protection
< 35 V
< 35 V
Property of the output 
Short-circuit proof
Yes
Yes
Short-circuit protection
electronic overload cut-off
electronic overload cut-off
adjustable response value current of
current-dependent overload trip
0.5 ... 5 A
0.5 ... 10 A
type of threshold value setting
via potentiometer
via potentiometer
Output current
Efficiency
Closed-loop control
7
Protection and monitoring
characteristics of electronic overload Ia >1.0…<1.5 x Ia threshold permissible for 5 s; 
Ia limit (= 1.5 x Ia threshold) permissible for 200 ms
switch-off
Reset
Via sensor per output
Ia >1.0…<1.5 x Ia threshold permissible for 5 s; 
Ia limit (= 1.5 x Ia threshold) permissible for 200 ms
Via sensor per output
Remote reset
Non-electrically isolated 24 V input (signal level "high" 
at > 15 V) at power supply unit PSU8600
Non-electrically isolated 24 V input (signal level "high" 
at > 15 V) at power supply unit PSU8600
Overload/short-circuit indicator
3-color LED for operating state module; 
3-color LED per output for operating state output
3-color LED for operating state module; 
3-color LED per output for operating state output
Ethernet/PROFINET via power supply unit PSU8600
Ethernet/PROFINET via power supply unit PSU8600
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1
and EN 50178
Safety extra-low output voltage Uout acc. to EN 60950-1
and EN 50178
Protection class
Class III
Class III
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1), 
File E197259; cCSAus (CSA C22.2 No. 60950-1,
UL 60950-1)
cULus-Listed (UL 508, CSA C22.2 No. 107.1), 
File E197259; cCSAus (CSA C22.2 No. 60950-1,
UL 60950-1)
Explosion protection
IECEx Ex nA IIC T4 Gc; ATEX (EX) II 3G Ex nA IIC T4 Gc; IECEx Ex nA IIC T4 Gc; ATEX (EX) II 3G Ex nA IIC T4 Gc;
cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I,
Div. 2, Group ABCD, T4
Div. 2, Group ABCD, T4
FM approval
-
-
CB approval
Yes
Yes
Marine approval
GL; ABS in process
GL; ABS in process
Degree of protection (EN 60529)
IP20
IP20
Emitted interference
EN 55022 Class B
EN 55022 Class B
Noise immunity
EN 61000-6-2
EN 61000-6-2
Interface
Specification interface
Safety
EMC
Siemens KT 10.1 · 2016
7/11
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
Modular system, expansion of outputs (CNX8600)
■ Technical specifications (continued)
Article number
6EP4436-8XB00-0CY0
6EP4437-8XB00-0CY0
Product
SITOP CNX8600
SITOP CNX8600
Power supply, type
4x 5 A
4x 10 A
-25 ... +60 °C
-25 ... +60 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
Plug-in terminals with screwed connection
Plug-in terminals with screwed connection
1, 2, 3, 4: Two plug-in terminals (1, 2 and 3, 4) 
with 2 screwed connections each for 0.2 ... 2.5 mm²;
Ground: Plug-in terminal with 3 screwed connections 
for 0.2 ... 2.5 mm²
1, 2, 3, 4: Two plug-in terminals (1, 2 and 3, 4) 
with 2 screwed connections each for 0.2 ... 2.5 mm²;
Ground: Plug-in terminal with 3 screwed connections 
for 0.2 ... 2.5 mm²
• removable terminal at output
Yes
Yes
Type of connection to system
components
Via integrated connector
Via integrated connector
Width of the enclosure
60 mm
60 mm
Height of the enclosure
125 mm
125 mm
Depth of the enclosure
150 mm
150 mm
• top
50 mm
50 mm
• bottom
50 mm
50 mm
• left
0 mm
0 mm
• right
0 mm
0 mm
Weight, approx.
1.15 kg
1.15 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Installation
Snaps onto DIN rail EN 60715 35x15
Snaps onto DIN rail EN 60715 35x15
Mechanical accessories
Device identification label 20 mm × 7 mm, 
TI-grey 3RT2900-1SB20
Device identification label 20 mm × 7 mm, 
TI-grey 3RT2900-1SB20
MTBF at 40 °C
499 861 h
499 861 h
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
• Output
Product function
7
Required spacing
■ Ordering data
SITOP CNX8600 4 x 5 A 
expansion module
Article No.
6EP4436-8XB00-0CY0
For SITOP PSU8600
Output: 24 V DC/4 x 5 A
SITOP CNX8600 4 x 10 A 
expansion module
6EP4437-8XB00-0CY0
For SITOP PSU8600
Output: 24 V DC/4 x 10 A
7/12
Siemens KT 10.1 · 2016
■ Accessories
Device labeling plates
Article No.
3RT1900-1SB20
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
Modular system, buffer (BUF8600)
■ Overview
The BUF8600 buffer modules with maintenance free energy
storage units are part of the SITOP PSU8600 modular system
and are designed to bridge short-term power failures. They
automatically take over the DC power supply in case of a line
voltage failure. You can connect up to two BUF8600 buffer
modules to the PSU8600 basic unit. Connection takes place on
top of the modules without any wiring by means of the System
Clip Link, a connecting plug for system data and power supply.
Main product highlights
• Reliable bridging of short-term power failures up to maximum
20 s (at 24 V DC and full load)
• Buffer module with maintenance free electrolytic capacitors
for bridging short-term power failures (brownouts) between
100 ms and max. 600 ms (at 24 V DC/40 A)
• Buffer module with maintenance free double-layer capacitors
for bridging longer power failures between 4 s and max. 20 s
(at 24 V DC/40 A)
• The two buffer modules can be combined as required.
• Easy connection without wiring overhead
■ Technical specifications
Article number
6EP4297-8HB00-0XY0
6EP4297-8HB10-0XY0
6EP4293-8HB00-0XY0
6EP4295-8HB00-0XY0
product brand name
SITOP BUF8600
SITOP BUF8600
SITOP BUF8600
SITOP BUF8600
Type of current supply
100 ms/40 A
300 ms/40 A
4 s/40 A
10 s/40 A
Type of energy storage
electrolytic capacitors
electrolytic capacitors
Double-layer capacitors
Double-layer capacitors
Buffering time for rated value of the
output current in the event of power
failure
100 ms
300 ms
4s
10 s
40 A
40 A
40 A
40 A
Display version
3-color LED for operating
state module
3-color LED for operating
state module
3-color LED for operating
state module
3-color LED for operating
state module
• for normal operation
LED green for 
"buffer standby exist"
LED green for 
"buffer standby exist"
LED green for 
"buffer standby exist"
LED green for 
"buffer standby exist"
• in buffering mode
LED yellow for 
"buffered mode"
LED yellow for 
"buffered mode"
LED yellow for 
"buffered mode"
LED yellow for 
"buffered mode"
Ethernet/PROFINET via
Ethernet/PROFINET via
power supply unit PSU8600 power supply unit PSU8600
Ethernet/PROFINET via
power supply unit PSU8600
Ethernet/PROFINET via
power supply unit PSU8600
Protection class
Class III
Class III
Class III
Class III
CE marking
Yes
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259; cCSAus 
(CSA C22.2 No. 60950-1,
UL 60950-1)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259; cCSAus 
(CSA C22.2 No. 60950-1,
UL 60950-1)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259; cCSAus 
(CSA C22.2 No. 60950-1,
UL 60950-1)
cULus-Listed (UL 508, 
CSA C22.2 No. 107.1), 
File E197259; cCSAus 
(CSA C22.2 No. 60950-1,
UL 60950-1)
Explosion protection
IECEx nA IIC T5 Gc; ATEX
(EX) II 3G Ex nA IIC T5 Gc
IECEx nA IIC T5 Gc; ATEX
(EX) II 3G Ex nA IIC T5 Gc
IECEx nA IIC T5 Gc; ATEX
(EX) II 3G Ex nA IIC T5 Gc
IECEx nA IIC T5 Gc; ATEX
(EX) II 3G Ex nA IIC T5 Gc
CB approval
Yes
Yes
Yes
Yes
Shipbuilding approval
GL (ABS in process)
GL (ABS in process)
GL (ABS in process)
GL (ABS in process)
Protection class (EN 60529)
IP20
IP20
IP20
IP20
Emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
Mains buffering
Output
Output current
• Rated value
Signaling
Interface
Specification/Interface
Safety
EMC
Siemens KT 10.1 · 2016
7/13
7
© Siemens AG 2016
SITOP modular, PSU8600 power supply system
Modular system, buffer (BUF8600)
■ Technical specifications (continued)
Article number
6EP4297-8HB00-0XY0
6EP4297-8HB10-0XY0
6EP4293-8HB00-0XY0
6EP4295-8HB00-0XY0
product brand name
SITOP BUF8600
SITOP BUF8600
SITOP BUF8600
SITOP BUF8600
Type of current supply
100 ms/40 A
300 ms/40 A
4 s/40 A
10 s/40 A
• during operation
-25 ... +60 °C; 
with natural convection
-25 ... +60 °C; 
with natural convection
-25 ... +60 °C; 
with natural convection
-25 ... +60 °C;
with natural convection
• during transport
-40 ... +70 °C
-40 ... +70 °C
-40 ... +70 °C
-40 ... +70 °C
• during storage
-40 ... +70 °C
-40 ... +70 °C
-40 ... +70 °C
-40 ... +70 °C
Humidity class according to
EN 60721
Climate class 3K3, no
condensation
Climate class 3K3, no
condensation
Climate class 3K3, no
condensation
Climate class 3K3, no
condensation
Connection technology
-
-
Plug-in terminal with 
screw connectors
Plug-in terminal with 
screw connectors
• input
-
-
-
-
• output
-
-
-
-
• auxiliary contact and signaling
contacts
-
-
X1, X2 (control contact) and
13,14, 23, 24 (message
signals): 1 screw terminal
each for 0.2 ... 1.5 mm²
X1, X2 (control contact) and
13,14, 23, 24 (message
signals): 1 screw terminal
each for 0.2 ... 1.5 mm²
Type of connection 
to system components
Via integrated connector
Via integrated connector
Via integrated connector
Via integrated connector
Width of the enclosure
60 mm
125 mm
60 mm
125 mm
Height of the enclosure
125 mm
125 mm
125 mm
125 mm
Depth of the enclosure
150 mm
150 mm
150 mm
150 mm
• top
50 mm
50 mm
50 mm
50 mm
• bottom
50 mm
50 mm
50 mm
50 mm
• left
0 mm
0 mm
0 mm
0 mm
• right
0 mm
0 mm
0 mm
0 mm
Weight, approx.
1.33 kg
2.26 kg
1.25 kg
1.95 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Yes
Yes
Mounting
Snaps onto DIN rail
EN 60715 35x15
Snaps onto DIN rail
EN 60715 35x15
Snaps onto DIN rail
EN 60715 35x15
Snaps onto DIN rail
EN 60715 35x15
Mechanical accessories
Device identification label
20 mm × 7 mm, 
TI-grey 3RT2900-1SB20
Device identification label
20 mm × 7 mm, 
TI-grey 3RT2900-1SB20
Device identification label
20 mm × 7 mm, 
TI-grey 3RT2900-1SB20
Device identification label
20 mm × 7 mm, 
TI-grey 3RT2900-1SB20
MTBF at 40 °C
1 944 258 h
1 944 258 h
-
-
Other information
Specifications at rated input
voltage and ambient
temperature +25 °C (unless
otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C (unless
otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C (unless
otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C (unless
otherwise specified)
Operating data
Ambient temperature
Mechanics
7
Required spacing
■ Ordering data
SITOP BUF8600 100 ms 
buffer module
Article No.
6EP4297-8HB00-0XY0
For SITOP PSU8600
Buffer capacity 100 ms/40 A
SITOP BUF8600 300 ms 
buffer module
6EP4297-8HB10-0XY0
For SITOP PSU8600
Buffer capacity 300 ms/40 A
SITOP BUF8600 4 s 
buffer module
6EP4293-8HB00-0XY0
For SITOP PSU8600 
Buffer capacity 4 s/40 A
SITOP BUF8600 10 s 
buffer module
6EP4295-8HB00-0XY0
For SITOP PSU8600 
Buffer capacity 10 s/40 A
7/14
Siemens KT 10.1 · 2016
■ Accessories
Device labeling plates
Article No.
3RT1900-1SB20
8
© Siemens AG 2016
SITOP in the SIMATIC Design
8/2
8/3
8/9
8/11
8/14
Introduction
1-phase, 24 V DC
(for S7-300 and ET200M)
1-phase, 24 V DC (for S7-1200)
1-phase, 24 V DC
(for S7-1500 and ET200MP)
3-phase, 24 V DC (for ET200pro)
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP in the SIMATIC Design
Introduction
■ Overview
■ More information
Select the appropriate power supply quickly and easily with the
SITOP Selection Tool:
http://www.siemens.com/sitop-selection-tool
The optimum supply for SIMATIC S7 and more
The original SIMATIC power supplies harmonize perfectly with
the PLC network in terms of their design and functionality.
In addition to the following SIMATIC systems, they also supply
further loads reliably with 24 V.
• SIMATIC S7-300
• SIMATIC S7-1200
• SIMATIC S7-1500
• SIMATIC ET200M
• SIMATIC ET200MP
• SIMATIC ET 200pro
8
8/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-300 and ET200M)
■ Overview
■ Design
• The system and load current supplies are screwed directly
onto the S7-300 standard mounting rail and can be mounted
directly to the left of the CPU (no installation clearance
required)
• Diagnostic LED for indicating “Output voltage 24 V DC O.K."
• ON/OFF switches (operation/stand-by) for possible swapping
of modules
• Strain-relief assembly for input voltage connection cable
■ Function
The design and functionality of the SIMATIC PS 307 singlephase load power supply (system and load current supply) with
automatic range switchover of the input voltage is an optimal
match to the SIMATIC S7-300 PLC. By means of the connecting
comb that is supplied with the system and load current supply,
the supply to the CPU is quickly established. It is also possible
to provide a 24 V supply to other S7-300 system components,
input/output circuits of the input/output modules and, if
necessary, the sensors and actuators. Comprehensive certifications, such as UL, ATEX or GL facilitate universal use (does not
apply to outdoor use).
• Connection to all 1-phase 50/60 Hz networks (120 / 230 V AC)
through automatic range switching (PS307) or manual
switching (PS307, outdoor)
• Short-term power failure backup
• Output voltage 24 V DC, stabilized, short circuit-proof,
open circuit-proof
• Parallel connection of two power supplies for enhanced
performancee
8
■ Technical specifications
Article number
6ES7307-1BA01-0AA0
6ES7305-1BA80-0AA0
Product
PS 307
PS 305 Outdoor
Power supply, type
24 V/2 A
24 V/2 A
1-phase AC
DC voltage
• 1 at AC Rated value
120 V
-
• 2 at AC Rated value
230 V
-
• at DC
-
24 ... 110 V
• Note
Automatic range selection
-
• 1 at AC
85 ... 132 V
-
• 2 at AC
170 ... 264 V
-
• at DC
-
16.8 ... 138 V
Wide-range input
No
Yes
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
154 V; 0.1 s
Mains buffering at Iout rated, min.
20 ms; at Vin = 93/187 V
10 ms; at Vin rated
Rated line frequency 1
50 Hz
-
Rated line frequency 2
60 Hz
-
Rated line range
47 ... 63 Hz
-
• at rated input voltage 120 V
0.9 A
-
• at rated input voltage 230 V
0.5 A
-
• at rated input voltage 24 V
-
2.4 A
• at rated input voltage 110 V
-
0.6 A
Switch-on current limiting (+25 °C), max.
22 A
20 A
• maximum
3 ms
10 ms
I²t, max.
1 A²·s
5 A²·s
Built-in incoming fuse
T 1.6 A/250 V
(not accessible)
T 6.3 A/250 V
(not accessible)
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker:
from 3 A characteristic C
Recommended miniature circuit breaker:
from 10 A characteristic C, suitable for DC
Input
Input
Supply voltage
Input voltage
Input current
Duration of inrush current limiting at 25 °C
Siemens KT 10.1 · 2016
8/3
© Siemens AG 2016
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-300 and ET200M)
■ Technical specifications (continued)
Article number
6ES7307-1BA01-0AA0
6ES7305-1BA80-0AA0
Product
PS 307
PS 305 Outdoor
Power supply, type
24 V/2 A
24 V/2 A
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
24 V
Total tolerance, static ±
3%
3%
Static mains compensation, approx.
0.1 %
0.2 %
Static load balancing, approx.
0.2 %
0.4 %
Residual ripple peak-peak, max.
50 mV
150 mV
Residual ripple peak-peak, typ.
5 mV
30 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
150 mV
240 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
20 mV
150 mV
Product function
Output voltage adjustable
No
No
Output voltage setting
-
-
Status display
Green LED for 24 V OK
Green LED for 24 V OK
On/off behavior
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
Startup delay, max.
2s
3s
Voltage rise, typ.
10 ms
5 ms
Rated current value Iout rated
2A
2A
Current range
0 ... 2 A
0 ... 3 A
• Note
-
3 A up to +60°C at
Vin > 24 V
Supplied active power typical
48 W
48 W
• on short-circuiting during the start-up typical
9A
9A
• at short-circuit during operation typical
9A
9A
• on short-circuiting during the start-up
90 ms
270 ms
• at short-circuit during operation
90 ms
270 ms
Parallel switching for enhanced performance
Yes
Yes
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency at Vout rated, Iout rated, approx.
84 %
75 %
Power loss at Vout rated, Iout rated, approx.
9W
16 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
0.3 %
Dynamic load smoothing (Iout: 50/100/50 %),
Uout ± typ.
0.8 %
2.5 %
Load step setting time 50 to 100 %, typ.
0.5 ms
2.5 ms
Load step setting time 100 to 50 %, typ.
0.5 ms
2.5 ms
Setting time maximum
1 ms
5 ms
Output overvoltage protection
Additional control loop, shutdown at < 28.8 V,
automatic restart
Additional control loop, shutdown at approx. 30 V,
automatic restart
Current limitation
2.2 ... 2.6 A
3.3 ... 3.9 A
Property of the output
Short-circuit proof
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
• maximum
2A
2A
Overload/short-circuit indicator
-
-
Output
8
Short-term overload current
Duration of overloading capability for excess
current
Efficiency
Closed-loop control
Protection and monitoring
Enduring short circuit current RMS value
8/4
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-300 and ET200M)
■ Technical specifications (continued)
Article number
6ES7307-1BA01-0AA0
6ES7305-1BA80-0AA0
Product
PS 307
PS 305 Outdoor
Power supply, type
24 V/2 A
24 V/2 A
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra low output voltage Vout according to
EN 60950-1 and EN 50178, creepage distances and
clearances > 5 mm
Protection class
Class I
Class I
• maximum
3.5 mA
-
• typical
0.5 mA
-
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 142),
File E143289
UL-Listed (UL 508), File E143289,
CSA (CSA C22.2 No. 142)
Explosion protection
ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01,
CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4,
File E330455
-
FM approval
Class I, Div. 2, Group ABCD, T4
-
CB approval
No
No
Marine approval
In S7-300 system
-
Degree of protection (EN 60529)
IP20
IP20
Emitted interference
EN 55022 Class B
EN 55011 Class A
Supply harmonics limitation
not applicable
not applicable
Noise immunity
EN 61000-6-2
EN 61000-6-2
0 ... 60 °C
-25 ... +70 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation
Climate class 3K5, transient condensation permitted
screw-type terminals
screw-type terminals
• Supply input
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
single-core/finely stranded
L+1, M1, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
single-core/finely stranded
• Output
L+, M: 2 screw terminals each for 0.5 ... 2.5 mm²
L+, M: 3 screw terminals each for 0.5 ... 2.5 mm²
• Auxiliary
-
-
Width of the enclosure
40 mm
80 mm
Height of the enclosure
125 mm
125 mm
Depth of the enclosure
120 mm
120 mm
Weight, approx.
0.4 kg
0.57 kg
Product feature of the enclosure housing for
side-by-side mounting
Yes
Yes
Installation
Can be mounted onto S7 rail
Can be mounted onto S7 rail
Mechanical accessories
Mounting adapter for standard mounting rail
(6EP1971-1BA00)
Mounting adapter for standard mounting rail
(6ES7390-6BA00-0AA0)
MTBF at 40 °C
2 320 078 h
964 506 h
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Safety
Leakage current
EMC
Operating data
8
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
Siemens KT 10.1 · 2016
8/5
© Siemens AG 2016
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-300 and ET200M)
■ Technical specifications (continued)
Article number
6ES7307-1EA01-0AA0
6ES7307-1EA80-0AA0
6ES7307-1KA02-0AA0
Product
PS 307
PS 307 Outdoor
PS 307
Power supply, type
24 V/5 A
24 V/5 A
24 V/10 A
1-phase AC
1-phase AC
1-phase AC
Input
Input
Supply voltage
• 1 at AC Rated value
120 V
120 V
120 V
• 2 at AC Rated value
230 V
230 V
230 V
• Note
Automatic range selection
Set by means of selector switch on Automatic range selection
the device
Input voltage
• 1 at AC
85 ... 132 V
93 ... 132 V
85 ... 132 V
• 2 at AC
170 ... 264 V
187 ... 264 V
170 ... 264 V
Wide-range input
No
No
No
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
20 ms; at Vin = 93/187 V
20 ms; at Vin = 93/187 V
20 ms; at Vin = 93/187 V
Rated line frequency 1
50 Hz
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
Input current
• at rated input voltage 120 V
2.3 A
2.1 A
4.2 A
• at rated input voltage 230 V
1.2 A
1.2 A
1.9 A
• at rated input voltage 24 V
-
-
-
• at rated input voltage 110 V
-
-
-
Switch-on current limiting (+25 °C), max.
20 A
45 A
55 A
Duration of inrush current limiting at 25 °C
8
• maximum
3 ms
3 ms
3 ms
I²t, max.
1.2 A²·s
1.8 A²·s
3.3 A²·s
Built-in incoming fuse
T 3,15 A/250 V
(not accessible)
T 3,15 A/250 V
(not accessible)
T 6.3 A/250 V
(not accessible)
Protection in the mains power input (IEC 898)
Recommended miniature circuit
breaker: from 6 A characteristic C
Recommended miniature circuit
Recommended miniature circuit
breaker: from 10 A characteristic C breaker: from 10 A characteristic C
or from 6 A characteristic D
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
24 V
24 V
Total tolerance, static ±
3%
3%
3%
Static mains compensation, approx.
0.1 %
0.2 %
0.1 %
Static load balancing, approx.
0.5 %
0.4 %
0.5 %
Residual ripple peak-peak, max.
50 mV
150 mV
50 mV
Residual ripple peak-peak, typ.
10 mV
40 mV
15 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
150 mV
240 mV
150 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
20 mV
90 mV
60 mV
Product function
Output voltage adjustable
No
No
No
Output voltage setting
-
-
-
Status display
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
On/off behavior
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
Startup delay, max.
2s
3s
2s
Voltage rise, typ.
10 ms
100 ms
10 ms
Rated current value Iout rated
5A
5A
10 A
Current range
0 ... 5 A
0 ... 5 A
0 ... 10 A
120 W
120 W
240 W
• on short-circuiting during the start-up typical
20 A
20 A
38 A
• at short-circuit during operation typical
20 A
20 A
38 A
• Note
Supplied active power typical
Short-term overload current
Duration of overloading capability for excess
current
• on short-circuiting during the start-up
100 ms
180 ms
80 ms
• at short-circuit during operation
100 ms
80 ms
80 ms
Parallel switching for enhanced performance
Yes
No
Yes
8/6
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-300 and ET200M)
■ Technical specifications (continued)
Article number
6ES7307-1EA01-0AA0
6ES7307-1EA80-0AA0
6ES7307-1KA02-0AA0
Product
PS 307
PS 307 Outdoor
PS 307
Power supply, type
24 V/5 A
24 V/5 A
24 V/10 A
Efficiency at Vout rated, Iout rated, approx.
87 %
84 %
90 %
Power loss at Vout rated, Iout rated, approx.
18 W
23 W
27 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
0.3 %
0.1 %
Dynamic load smoothing (Iout: 50/100/50 %),
Uout ± typ.
1%
3%
2%
Load step setting time 50 to 100%, typ.
0.3 ms
0.2 ms
-
Load step setting time 100 to 50%, typ.
0.3 ms
0.2 ms
-
Setting time maximum
-
5 ms
0.1 ms
Efficiency
Closed-loop control
Protection and monitoring
Output overvoltage protection
Additional control loop, shutdown at Additional control loop, shutdown at Additional control loop, shutdown at
< 28.8 V, automatic restart
approx. 30 V, automatic restart
< 28.8 V, automatic restart
Current limitation
5.5 ... 6.5 A
5.5 ... 6.5 A
11 ... 12 A
Property of the output
Short-circuit proof
Yes
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic
restart
Electronic shutdown, automatic
restart
Electronic shutdown, automatic
restart
• maximum
7A
5A
12 A
Overload/short-circuit indicator
-
-
-
Yes
Yes
Enduring short circuit current RMS value
Safety
Primary/secondary isolation
Yes
Galvanic isolation
Safety extra-low output voltage Uout Safety extra low output voltage Vout Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178 according to EN 60950-1 and
acc. to EN 60950-1 and EN 50178
EN 50178, creepage distances and
clearances > 5 mm
Protection class
Class I
Class I
Class I
Leakage current
• maximum
3.5 mA
3.5 mA
3.5 mA
• typical
0.5 mA
0.3 mA
0.6 mA
CE mark
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508,
CSA C22.2 No. 142), File E143289
UL-Listed (UL 508), File E143289,
CSA (CSA C22.2 No. 142)
cULus-Listed (UL 508,
CSA C22.2 No. 142), File E143289
Explosion protection
ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01, CSA C22.2 No.213)
Class I, Div. 2, Group ABCD, T4,
File E330455
ATEX (EX) II 3G Ex nA II T4; cULus
(ISA 12.12.01, CSA C22.2 No.213)
Class I, Div. 2, Group ABCD, T4,
File E330455
FM approval
Class I, Div. 2, Group ABCD, T4
-
Class I, Div. 2, Group ABCD, T4
CB approval
No
No
No
Marine approval
In S7-300 system
-
In S7-300 system
Degree of protection (EN 60529)
IP20
IP20
IP20
EMC
Emitted interference
EN 55022 Class B
EN 55011 Class A
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
-
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
0 ... 60 °C
-25 ... +70 °C
0 ... 60 °C
with natural convection
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation Climate class 3K5, transient
condensation permitted
Operating data
Ambient temperature
• during operation
- Note
Climate class 3K3, no condensation
Siemens KT 10.1 · 2016
8/7
8
© Siemens AG 2016
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-300 and ET200M)
■ Technical specifications (continued)
Article number
6ES7307-1EA01-0AA0
6ES7307-1EA80-0AA0
6ES7307-1KA02-0AA0
Product
PS 307
PS 307 Outdoor
PS 307
Power supply, type
24 V/5 A
24 V/5 A
24 V/10 A
screw-type terminals
screw-type terminals
screw-type terminals
Mechanics
Connection technology
Connections
8
• Supply input
L, N, PE: 1 screw terminal each for L, N, PE: 1 screw terminal each for L, N, PE: 1 screw terminal each for
0.5 ... 2.5 mm² single-core/finely
0.5 ... 2.5 mm² single-core/finely
0.5 ... 2.5 mm² single-core/finely
stranded
stranded
stranded
• Output
L+, M: 3 screw terminals each for
0.5 ... 2.5 mm²
L+, M: 3 screw terminals each for
0.5 ... 2.5 mm²
L+, M: 4 screw terminals each for
0.5 ... 2.5 mm²
• Auxiliary
-
-
-
Width of the enclosure
60 mm
80 mm
80 mm
Height of the enclosure
125 mm
125 mm
125 mm
Depth of the enclosure
120 mm
120 mm
120 mm
Weight, approx.
0.6 kg
0.57 kg
0.8 kg
Product feature of the enclosure housing for
side-by-side mounting
Yes
Yes
Yes
Installation
Can be mounted onto S7 rail
Can be mounted onto S7 rail
Can be mounted onto S7 rail
Mechanical accessories
Mounting adapter for standard
mounting rail (6EP1971-1BA00)
Mounting adapter for standard
mounting rail
(6ES7390-6BA00-0AA0)
Mounting adapter for standard
mounting rail
(6EP1971-1BA00)
MTBF at 40 °C
2 480 589 h
2 231 610 h
1 504 280 h
Other information
Specifications at rated input voltage Specifications at rated input voltage Specifications at rated input voltage
and ambient temperature +25 °C
and ambient temperature +25 °C
and ambient temperature +25 °C
(unless otherwise specified)
(unless otherwise specified)
(unless otherwise specified)
■ Ordering data
Load current supply PS 307, 2A
Article No.
6ES7307-1BA01-0AA0
Incl. connection bracket
Input: 120/230 V AC
Output: 24 V DC/2 A
SIMATIC S7-300 Outdoor, 2A
6ES7305-1BA80-0AA0
6ES7307-1EA01-0AA0
6ES7307-1EA80-0AA0
Stabilized power supply PS307
Input: 120/230 V AC
Output: 24 V DC/5 A
PS 307 load power supply, 10 A
6ES7307-1KA02-0AA0
Input: 120/230 V AC
Output: 24 V DC/10 A
8/8
6EP1971-1BA00
Spare part
SIMATIC S7-300
mounting adapter
Incl. connection bracket
Input: 120/230 V AC
Output: 24 V DC/5 A
SIMATIC S7-300 Outdoor, 5A
SIMATIC S7-300
mounting adapter
Article No.
For snapping the new PS 307
onto a 35 mm DIN rail (EN 60715)
Stabilized power supply PS305
Input: 24 … 110 V DC
Output: 24 V DC/2 A
PS 307 load power supply, 5 A
■ Accessoires
Siemens KT 10.1 · 2016
for snapping the PS307 onto 35 mm
DIN rails
6ES7390-6BA00-0AA0
© Siemens AG 2016
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-1200)
■ Overview
■ Technical specifications
Article number
6EP1332-1SH71
Product
S7-1200 PM1207
Power supply, type
24 V/2.5 A
Input
Input
1-phase AC
Supply voltage
• 1 at AC Rated value
120 V
• 2 at AC Rated value
230 V
• Note
Automatic range selection
Input voltage
In terms of design and functionality, the SIMATIC PM 1207
single-phase load power supply (PM = power module) with
automatic range selection of the input voltage is an optimal
match to the SIMATIC S7-1200 PLC. It provides the supply to
CPUs with 24 V input as well as to signal modules, and to 24 V
loads connected to the modules. Comprehensive certifications,
such as UL, ATEX and GL facilitate universal use.
■ Design
• The load current supplies are directly fastened to the S7-1200
mounting rail (without connection to the backplane bus) and
can be mounted directly to the left of the CPU (no installation
clearance required)
• LED for status indicator "24 V OK"
• Two 24 V DC output terminals for connection of 24 V
consumers
■ Function
• Connection to all 1-phase networks (120 V AC/230 V AC)
through automatic range switching
• Short-term power failure backup
• Parallel connection of two load current supplies for enhanced
performance
• 1 at AC
85 ... 132 V
• 2 at AC
176 ... 264 V
Wide-range input
No
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
20 ms; at Vin = 93/187 V
Rated line frequency 1
50 Hz
Rated line frequency 2
60 Hz
Rated line range
47 ... 63 Hz
Input current
• at rated input voltage 120 V
1.2 A
• at rated input voltage 230 V
0.67 A
Switch-on current limiting (+25 °C),
max.
13 A
Duration of inrush current limiting at
25 °C
• maximum
3 ms
I²t, max.
0.5 A²·s
Built-in incoming fuse
T 3,15 A/250 V (not accessible)
Protection in the mains power input
(IEC 898)
Recommended miniature circuit
breaker: 16 A characteristic B or
10 A characteristic C
Output
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
Total tolerance, static ±
3%
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
0.2 %
Residual ripple peak-peak, max.
150 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
240 mV
Product function Output voltage
adjustable
No
Output voltage setting
-
Status display
Green LED for 24 V OK
On/off behavior
No overshoot of Vout (soft start)
Startup delay, max.
6 s; 2 s at 230 V, 6 s at 120 V
Voltage rise, typ.
10 ms
Rated current value Iout rated
2.5 A
Current range
0 ... 2.5 A
Supplied active power typical
60 W
Short-term overload current
• on short-circuiting during the
start-up typical
6A
• at short-circuit during operation
typical
6A
Duration of overloading capability
for excess current
• on short-circuiting during the
start-up
100 ms
• at short-circuit during operation
100 ms
Parallel switching for enhanced
performance
Yes
Numbers of parallel switchable units
for enhanced performance
2
Siemens KT 10.1 · 2016
8/9
8
© Siemens AG 2016
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-1200)
■ Technical specifications (continued)
Article number
6EP1332-1SH71
Article number
6EP1332-1SH71
Product
S7-1200 PM1207
Product
S7-1200 PM1207
Power supply, type
24 V/2.5 A
Power supply, type
24 V/2.5 A
Efficiency
EMC
Efficiency at Vout rated, Iout rated,
approx.
83 %
Power loss at Vout rated, Iout rated,
approx.
12 W
EN 55022 Class B
Supply harmonics limitation
not applicable
Noise immunity
EN 61000-6-2
Operating data
Closed-loop control
Dynamic mains compensation
(Vin rated ±15 %), max.
0.3 %
Dynamic load smoothing
(Iout: 50/100/50 %), Uout ± typ.
3%
Load step setting time 50 to 100 %,
typ.
Ambient temperature
• during operation
- Note
0 ... 60 °C
with natural convection
• during transport
-40 ... +85 °C
5 ms
• during storage
-40 ... +85 °C
Load step setting time 100 to 50 %,
typ.
5 ms
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Setting time maximum
5 ms
Protection and monitoring
Output overvoltage protection
< 33 V
Current limitation, typ.
2.65 A
Property of the output
Short-circuit proof
Short-circuit protection
Mechanics
Connection technology
screw-type terminals
Connections
• Supply input
L, N, PE: 1 screw terminal each for
0.5 ... 2.5 mm²
Yes
• Output
L+, M: 2 screw terminals each for
0.5 ... 2.5 mm²
Constant current characteristic
• Auxiliary
-
Width of the enclosure
70 mm
Height of the enclosure
100 mm
Depth of the enclosure
75 mm
Weight, approx.
0.3 kg
Yes
Enduring short circuit current
RMS value
8
Emitted interference
• typical
2.7 A
Overload/short-circuit indicator
-
Safety
Primary/secondary isolation
Yes
Product feature of the enclosure
housing for side-by-side mounting
Galvanic isolation
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Installation
Snaps onto DIN rail EN 60715
35x7.5/15, wall mounting
Protection class
Class I
MTBF at 40 °C
1 492 537 h
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Leakage current
• maximum
3.5 mA
CE mark
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259; cURusRecognized (UL 60950-1, CSA
C22.2 No. 60950-1) File E151273
Explosion protection
ATEX (EX) II 3G Ex nA II T4; cULus
(ISA 12.12.01, CSA C22.2 No.213)
Class I, Div. 2, Group ABCD, T4,
File E330455
FM approval
Class I, Div. 2, Group ABCD, T4
CB approval
Yes
Marine approval
GL, ABS, BV, DNV, LRS, NK
Degree of protection (EN 60529)
IP20
■ Ordering data
SIMATIC S7-1200 PM 1207
Article No.
6EP1332-1SH71
Input: 120/230 V AC
Output: 24 V DC/2.5 A
8/10
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-1500 and ET200MP)
■ Overview
■ Design
• The load current supplies are directly fastened to the S7-1500
mounting rail (without connection to the backplane bus) and
can be mounted directly to the left of the CPU (no installation
clearance required)
• Diagnostics LEDs to indicate status and faults: Operation,
Fault, Stand-by
• ON/OFF switches (operation/stand-by) in case of swapping
modules
• Mains connection plug with touch protection and strain relief
for connection of input voltage (enables permanent wiring)
• Plug-in 24 V DC output terminal with reverse polarity
protection for connection of 24 V loads (enables permanent
wiring)
■ Function
The design and functionality of the SIMATIC PM 1507 singlephase load power supply (PM = power module) with automatic
range selection of the input voltage makes it an optimal match to
the SIMATIC S7-1500 PLC. It supplies the S7-1500 system
components such as CPU, system power supply (PS), I/O
circuits of the input and output modules and, if necessary, the
sensors and actuators with 24 V DC.
• Connection to all 1-phase 50/60 Hz networks (120 / 230 V AC)
through automatic range switching
• Short-term mains buffering
• Output voltage of 24 V DC that is limited to maximum 28 V DC
(prevents any damages in 24 V loads if input voltage is too
high)
• 50% "Extra Power" for 5 seconds per minute for short-term
overloads, for example, when switching on 24V consumers
■ Technical specifications
Article number
6EP1332-4BA00
6EP1333-4BA00
Product
S7-1500 PM1507
S7-1500 PM1507
Power supply, type
24 V/3 A
24 V/8 A
1-phase AC
1-phase AC
8
Input
Input
Supply voltage
• 1 at AC Rated value
120 V
120 V
• 2 at AC Rated value
230 V
230 V
• Note
Automatic range selection
Automatic range selection
Input voltage
• 1 at AC
85 ... 132 V
85 ... 132 V
• 2 at AC
170 ... 264 V
170 ... 264 V
Wide-range input
No
No
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
20 ms; at Vin = 93/187 V
20 ms; at Vin = 93/187 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
45 ... 65 Hz
45 ... 65 Hz
Input current
• at rated input voltage 120 V
1.4 A
3.7 A
• at rated input voltage 230 V
0.8 A
1.7 A
Switch-on current limiting (+25 °C),
max.
23 A
62 A
Duration of inrush current limiting at
25 °C
• maximum
3 ms
3 ms
I²t, max.
1.3 A²·s
12 A²·s
Built-in incoming fuse
T 3,15 A/250 V (not accessible)
T 6.3 A/250 V (not accessible)
Protection in the mains power input
(IEC 898)
Recommended miniature circuit breaker:
10 A characteristic B or 6 A characteristic C
Recommended miniature circuit breaker:
16 A characteristic B or 10 A characteristic C
Siemens KT 10.1 · 2016
8/11
© Siemens AG 2016
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-1500 and ET200MP)
■ Technical specifications (continued)
Article number
6EP1332-4BA00
6EP1333-4BA00
Product
S7-1500 PM1507
S7-1500 PM1507
Power supply, type
24 V/3 A
24 V/8 A
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
24 V
Total tolerance, static ±
1%
1%
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
0.1 %
0.1 %
Residual ripple peak-peak, max.
50 mV
50 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
150 mV
150 mV
Product function
Output voltage adjustable
No
No
Status display
LED green for 24 V OK; LED red for error;
LED yellow for stand-by
LED green for 24 V OK; LED red for error;
LED yellow for stand-by
On/off behavior
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
Startup delay, max.
1.5 s
1.5 s
Voltage rise, typ.
10 ms
10 ms
Rated current value Iout rated
3A
8A
Current range
0 ... 3 A
0 ... 8 A
Supplied active power typical
72 W
192 W
• on short-circuiting during the
start-up typical
12 A
35 A
• at short-circuit during operation
typical
12 A
35 A
• on short-circuiting during the
start-up
70 ms
70 ms
• at short-circuit during operation
70 ms
70 ms
Parallel switching for enhanced
performance
No
No
Efficiency at Vout rated, Iout rated,
approx.
87 %
90 %
Power loss at Vout rated, Iout rated,
approx.
11 W
21 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
0.1 %
Dynamic load smoothing
(Iout: 50/100/50 %), Uout ± typ.
1%
2%
Dynamic load smoothing
(Iout: 10/90/10 %), Uout ± typ.
3%
3%
Short-term overload current
8
Duration of overloading capability for
excess current
Efficiency
Closed-loop control
Load step setting time 10 to 90%, typ. 5 ms
5 ms
Load step setting time 90 to 10%, typ. 5 ms
5 ms
Setting time maximum
5 ms
5 ms
Output overvoltage protection
Additional control loop, limitation (closed loop control)
at < 28.8 V
Additional control loop, limitation (closed loop control)
at < 28.8 V
Current limitation
3.15 ... 3.6 A
8.4 ... 9.6 A
Current limitation, typ.
3.4 A
9A
Property of the output
Short-circuit proof
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
Overload/short-circuit indicator
-
-
Protection and monitoring
8/12
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-1500 and ET200MP)
■ Technical specifications (continued)
Article number
6EP1332-4BA00
6EP1333-4BA00
Product
S7-1500 PM1507
S7-1500 PM1507
Power supply, type
24 V/3 A
24 V/8 A
Safety
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1
and EN 50178 and EN 61131-2
Safety extra-low output voltage Uout acc. to EN 60950-1
and EN 50178 and EN 61131-2
Protection class
Class I
Class I
Leakage current
• maximum
3.5 mA
3.5 mA
• typical
0.4 mA
1.3 mA
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
Explosion protection
IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC
T4 Gc; cULus (ISA 12.12.01, CSA C22.2 No.213)
Class I, Div. 2, Group ABCD, T4, File E330455
IECEx Ex nA nC IIC T3 Gc; ATEX (EX) II 3G Ex nA nC IIC
T3 Gc; cULus (ISA 12.12.01, CSA C22.2 No.213)
Class I, Div. 2, Group ABCD, T3, File E330455
FM approval
Class I, Div. 2, Group ABCD, T4
Class I, Div. 2, Group ABCD, T4
CB approval
Yes
Yes
Marine approval
GL, ABS, BV, DNV
GL, ABS, BV, DNV
Degree of protection (EN 60529)
IP20
IP20
EMC
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
0 ... 60 °C
0 ... 60 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
Screw-/spring clamp connection
Screw-/spring clamp connection
• Supply input
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
• Output
L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm²
L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm²
Operating data
Ambient temperature
• during operation
- Note
8
Mechanics
Connection technology
Connections
Product function
• removable terminal at input
Yes
Yes
• removable terminal at output
Yes
Yes
Width of the enclosure
50 mm
75 mm
Height of the enclosure
147 mm
147 mm
Depth of the enclosure
129 mm
129 mm
Weight, approx.
0.45 kg
0.74 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Installation
Can be mounted onto S7-1500 rail
Can be mounted onto S7-1500 rail
MTBF at 40 °C
1 611 993 h
1 362 918 h
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
■ Ordering data
SIMATIC PM 1507
Article No.
6EP1332-4BA00
Stabilized power supply for
SIMATIC S7-1500
Input: 120/230 V AC
Output: 24 V DC/3 A
SIMATIC PM 1507
■ Accessories
Power connector
Article No.
6ES7590-8AA00-0AA0
With coding element for power
supply module; spare part,
10 units per packaging unit
6EP1333-4BA00
Stabilized power supply for
SIMATIC S7-1500
Input: 120/230 V AC
Output: 24 V DC/8 A
Siemens KT 10.1 · 2016
8/13
© Siemens AG 2016
SITOP in the SIMATIC Design
3-phase, 24 V DC (for ET200pro)
■ Overview
■ Technical specifications
Article number
6ES7148-4PC00-0HA0
Product
SIMATIC ET200pro PS
Power supply, type
24 V/8 A
Input
Input
3-phase AC
Rated voltage value Vin rated
400 ... 480 V
Voltage range AC
340 ... 550 V
• Note
320 ... 340 V for max. 1 min
Wide-range input
Yes
Overvoltage resistance
Implemented internally with varistors
Mains buffering at Iout rated, min.
15 ms; at Vin = 400 V
Rated line frequency 1
50 Hz
Rated line frequency 2
60 Hz
Rated line range
45 ... 66 Hz
Input current
The SIMATIC ET200pro PS power supply unit with degree of
protection IP67 is used as the electronics/encoder supply and
load voltage supply of the new SIMATIC ET 200pro distributed
I/O system for use close to the machine without a cabinet. With
a signaling contact for "24 V OK" and "Overtemperature", as well
as a second plug-in connector for input voltage loop-through.
• at rated input voltage 400 V
0.5 A
Switch-on current limiting (+25 °C),
max.
40 A
I²t, max.
3.5 A²·s
Built-in incoming fuse
T4A
Protection in the mains power input
(IEC 898)
Required: Circuit breaker
3RV2011-1DA10 or 3RV2711-1DD10
(UL 489)
Output
8
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
Total tolerance, static ±
3%
Static mains compensation, approx.
0.5 %
Static load balancing, approx.
0.5 %
Residual ripple peak-peak, max.
200 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
250 mV
Product function
Output voltage adjustable
No
Output voltage setting
-
Status display
Green LED for 24 V OK
Signaling
max. 30 V, 10 mA; Power-Good
(High-Pegel 1L+ for Vout in range
21.3 ... 29 V); Overtemperature
warning at least 30 s before
switch-off (high level 1L+ when the
max. internal temperature is
exceeded)
On/off behavior
Overshoot of Vout < 2 %
Startup delay, max.
1.5 s
Voltage rise, typ.
40 ms
Rated current value Iout rated
8A
Current range
0 ... 8 A
Supplied active power typical
192 W
Short-term overload current
• on short-circuiting during the
start-up typical
50 A
• at short-circuit during operation
typical
50 A
Duration of overloading capability for
excess current
8/14
Siemens KT 10.1 · 2016
• on short-circuiting during the
start-up
100 ms
• at short-circuit during operation
100 ms
Parallel switching for enhanced
performance
No
© Siemens AG 2016
SITOP in the SIMATIC Design
3-phase, 24 V DC (for ET200pro)
■ Technical specifications (continued)
Article number
6ES7148-4PC00-0HA0
Article number
6ES7148-4PC00-0HA0
Product
SIMATIC ET200pro PS
Product
SIMATIC ET200pro PS
Power supply, type
24 V/8 A
Power supply, type
24 V/8 A
Efficiency
EMC
Efficiency at Vout rated, Iout rated,
approx.
88 %
Power loss at Vout rated, Iout rated,
approx.
25 W
Emitted interference
EN 55022 Class A
Supply harmonics limitation
-
Noise immunity
EN 61000-6-2
Operating data
Closed-loop control
Dynamic mains compensation
(Vin rated ±15 %), max.
0.5 %
Dynamic load smoothing
(Iout: 50/100/50 %), Uout ± typ.
1%
Setting time maximum
Ambient temperature
• during operation
- Note
-25 ... +55 °C
with natural convection
• during transport
-40 ... +70 °C
2 ms
• during storage
-40 ... +70 °C
Climate class 3K3, no condensation
Output overvoltage protection
< 33 V
Humidity class according to
EN 60721
Current limitation, typ.
9.4 A
Mechanics
Property of the output
Short-circuit proof
Yes
Connection technology
Short-circuit protection
Electronic shutdown,
automatic restart
Protection and monitoring
screw-type terminals
Connections
Enduring short circuit current
RMS value
• maximum
10 A
Overload/short-circuit indicator
-
Safety
• Supply input
L1, L2, L3, PE: Plug connector
HAN Q4/2 (counterpart see
"Electrical accessories")
• Output
L+, M: 2 x 1.5 mm² each
(4-pole cable for +/- with open,
labeled ends, 4 x 1.5 mm²)
• Auxiliary
Alarm signals: M12 plug-in
connector 5-pin
Primary/secondary isolation
Yes
Width of the enclosure
310 mm
Galvanic isolation
Protective extra low output voltage
Vout according to EN 60950-1 and
EN 50178
Height of the enclosure
135 mm
Depth of the enclosure
90 mm
Class I
Weight, approx.
2.8 kg
Product feature of the enclosure
housing for side-by-side mounting
No
Installation
Can be mounted onto ET200pro
mounting rail
Electrical accessories
Power connector
(Input: 3RK1911-2BE30 (6 mm²))
(Output: 3RK1911-2BF10 (4 mm²))
MTBF at 40 °C
196 354 h
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Protection class
Leakage current
• maximum
3.5 mA
• typical
0.4 mA
CE mark
Yes
UL/cUL (CSA) approval
UL-Listed (UL 508) according to
NFPA compatibility (National Fire
Protection Association),
see operating instructions
Explosion protection
No
FM approval
-
CB approval
Yes
Marine approval
No
Degree of protection (EN 60529)
IP67, enclosure type 4 indoor
Siemens KT 10.1 · 2016
8
8/15
© Siemens AG 2016
SITOP in the SIMATIC Design
3-phase, 24 V DC (for ET200pro)
■ Ordering data
SIMATIC ET 200pro PS
Article No.
6ES7148-4PC00-0HA0
Stabilized power supply in
distributed I/O system design,
permitting the loop-through of
energy to further modules; with
degree of protection IP67;
Input: 400-480 V 3 AC
Output: 24 V DC/8 A
■ Accessories
Article No.
Power connector
For connecting to the distributed
I/O system
• For X1 (6 mm2)
• For X2 (4 mm2)
3RK1911-2BE30
3RK1911-2BF10
National Fire Protection
Association compatible
These devices are only approved
for installation in industrial
machinery according to the
NFPA79 Electrical Standard for
Industrial Machinery.
• for X1 SIMATIC ET200pro PS
61 88 201 1003.xx (AWG10)*
• for X1 SITOP PSU300P
61 88 201 1000.xx /
61 88 201 1002.xx (AWG14)*
• for X2 SIMATIC ET200pro PS
61 88 202 1010.xx (AWG10)*
supplied blanking cap for X2
* http://www.harting.com/en/home
3RK1902-0CK00
• for X3
Phoenix-Contact
SAC-5P-M12-M12FS
supplied blanking cap for X3
Sealing cap
For 9-pole power sockets
• X2 (1 unit)
• X2 (10 units)
8
8/16
Siemens KT 10.1 · 2016
3RK1902-0CJ0
3RK1902-0CK00
9
© Siemens AG 2016
Special designs, 
special uses
9/2
9/3
9/4
9/7
9/11
9/11
9/14
9/16
9/16
9/18
9/21
9/21
9/23
9/25
9/25
9/27
9/29
9/31
9/33
9/33
9/36
Introduction
Wall mounting
1-phase, 12 V DC (PSU100D)
1-phase, 24 V DC (PSU100D)
High degree of protection
1-phase, 24 V DC (SITOP PSU100P, IP67)
3-phase, 24 V DC (ET200pro PS, IP67)
Battery charging
3-phase, 12 V DC
3-phase, 24 V DC
Alternative output voltages
1-phase, 2 x 15 V DC (SITOP dual)
1-phase, 3-52 V DC (SITOP flexi 120 W)
DC/DC converters
48-220V DC / 24 V DC/0,375 A
48-110V DC / 24 V DC/2 A
24 V DC / 12 V DC/2,5 A
200-900 V DC / 24 V DC/20 A
Special applications
1-phase, 24 V DC
3-phase, 24 V DC (SITOP PSU300E)
Siemens KT 10.1 · 2016
© Siemens AG 2016
Special designs, special uses
Introduction
■ Overview
■ More information
Select the appropriate power supply quickly and easily with the
SITOP Selection Tool:
http://www.siemens.com/sitop-selection-tool
Well prepared for special tasks and conditions
Whether restricted installation conditions, harsh ambient conditions, or special input or output voltages are concerned: These
standard power supply units ensure a reliable and efficient supply of power, even when subject to extraordinary demands.
Thanks to their compact design they can be integrated perfectly
into existing installations.
9
9/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
Special designs, special uses
Wall mounting
Introduction
■ Overview
Main product highlights
• For 12-V standard applications from 3 A to 8.3 A
• For 24 V standard applications from 2.1 A to 12.5 A
• Compact metal enclosure
• Wide-range input
• Green LED for "24 V OK"
• Certification in accordance with CE and UL
• Adjustable output voltage from 22 to 28 V or from 11 to 14 V
for compensating voltage drops
• Temperature range from -10 °C to +70 °C
Low-cost power supply for wall mounting
The PSU100D switch mode power supplies extend the Siemens
power supply portfolio to include single-phase devices for direct
wall mounting using screws. The flat and rugged aluminum enclosure with IP20 degree of protection can be installed in various
orientations and is therefore ideal for installation locations with
limited space or for mounting in control cabinets and enclosures
without a DIN rail. The low-cost devices meet all the basic requirements for a power supply, typical applications being apparatus, automated equipment and automation solutions.
9
Siemens KT 10.1 · 2016
9/3
© Siemens AG 2016
Special designs, special uses
Wall mounting
1-phase, 12 V DC (PSU100D)
■ Overview
The single-phase PSU100Ds are switch mode power supplies
for direct wall mounting using screws. The flat and rugged aluminum enclosure with IP20 degree of protection can be installed
in various orientations and is therefore ideal for installation locations with limited space or for mounting in control cabinets and
enclosures without a DIN rail. The low-cost devices meet all the
basic requirements for a power supply, typical applications being apparatus, automated equipment and automation solutions.
Main product highlights
• 12 V DC, 3 A and 8.3 A
• Compact metal enclosure
• Wide-range input
• Green LED for "24 V OK"
• Certification in accordance with CE and UL
• Adjustable output voltage from 22 to 28 V or from 11 to 14 V
for compensating voltage drops
• Temperature range from -10 °C to +70 °C
■ Technical specifications
Article number
6EP1321-1LD00
6EP1322-1LD00
Product
PSU100D
PSU100D
Power supply, type
12 V/3 A
12 V/8.3 A
Input
1-phase AC
1-phase AC
Rated voltage value Vin rated
100 ... 240 V
100 ... 240 V
Voltage range AC
85 ... 264 V
85 ... 264 V
Wide-range input
Yes
Yes
Mains buffering at Iout rated, min.
15 ms; at Vin = 115/230 V
15 ms; at Vin = 115/230 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 100 V
0.75 A
2A
• at rated input voltage 240 V
0.5 A
1.1 A
Switch-on current limiting (+25 °C), max.
60 A
75 A
I²t, max.
1.2 A²·s
5.5 A²·s
Built-in incoming fuse
internal
internal
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker: from 10 A
characteristic C or from 16 A characteristic B
Recommended miniature circuit breaker: from 10 A
characteristic C or from 16 A characteristic B
Input
9
Input current
9/4
Siemens KT 10.1 · 2016
© Siemens AG 2016
Special designs, special uses
Wall mounting
1-phase, 12 V DC (PSU100D)
■ Technical specifications (continued)
Article number
6EP1321-1LD00
6EP1322-1LD00
Product
PSU100D
PSU100D
Power supply, type
12 V/3 A
12 V/8.3 A
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
12 V
12 V
Total tolerance, static ±
2%
2%
Static mains compensation, approx.
0.5 %
0.5 %
Static load balancing, approx.
1%
1%
Residual ripple peak-peak, max.
100 mV
100 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
100 mV
100 mV
Adjustment range
11 ... 14 V
11 ... 14 V
Product function Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
Status display
Green LED for 12 V OK
Green LED for 12 V OK
On/off behavior
Overshoot of Vout < 2 %
Overshoot of Vout < 2 %
Startup delay, max.
2.5 s
1s
Voltage increase time of the output voltage
maximum
30 ms
30 ms
Rated current value Iout rated
3A
8.3 A
Current range
0 ... 3 A
0 ... 8.3 A
• Note
+50 ... +70 °C: Derating 2.5%/K
+50 ... +70 °C: Derating 2.5%/K
Supplied active power typical
36 W
100 W
Parallel switching for enhanced performance
Yes
Yes
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency at Vout rated, Iout rated, approx.
84 %
84 %
Power loss at Vout rated, Iout rated, approx.
6.5 W
19 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.5 %
0.5 %
Dynamic load smoothing (Iout: 50/100/50 %),
Uout ± typ.
5%
5%
Output overvoltage protection
< 17.6 V
< 17.6 V
Current limitation, typ.
3.6 A
9.9 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
• typical
6A
10 A
Overload/short-circuit indicator
-
-
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra low output voltage Vout according to
EN 60950-1
Safety extra low output voltage Vout according to
EN 60950-1
Protection class
Class I
Class I
• maximum
3.5 mA
3.5 mA
• typical
1 mA
1 mA
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cURus (UL 60950-1, CSA C22.2
No. 60950-1), File E151273
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cURus (UL 60950-1, CSA C22.2
No. 60950-1), File E151273
Explosion protection
-
-
FM approval
-
-
CB approval
Yes
Yes
Marine approval
-
-
Degree of protection (EN 60529)
IP20
IP20
Output
Efficiency
Closed-loop control
9
Protection and monitoring
Enduring short circuit current RMS value
Safety
Leakage current
Siemens KT 10.1 · 2016
9/5
© Siemens AG 2016
Special designs, special uses
Wall mounting
1-phase, 12 V DC (PSU100D)
■ Technical specifications (continued)
Article number
6EP1321-1LD00
6EP1322-1LD00
Product
PSU100D
PSU100D
Power supply, type
12 V/3 A
12 V/8.3 A
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
not applicable
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
-10 ... +70 °C
-10 ... +70 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
screw-type terminals
screw-type terminals
• Supply input
L, N, PE: 1 screw terminal each for
0.3 ... 1.3 mm² single-core/finely stranded
L, N, PE: 1 screw terminal each for
0.3 ... 1.3 mm² single-core/finely stranded
• Output
+, -: 1 screw terminal each for 0.3 ... 1.3 mm²
+, -: 2 screw terminals each for 0.3 ... 1.3 mm²
• Auxiliary
-
-
Width of the enclosure
97 mm
97 mm
Height of the enclosure
98 mm
158 mm
Depth of the enclosure
38 mm
38 mm
Weight, approx.
0.37 kg
0.57 kg
Installation
Wall mounting
Wall mounting
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
EMC
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
■ Ordering data
9
PSU100D 1-phase, 12 V DC/3 A
Article No.
6EP1321-1LD00
Stabilized power supply 35 W,
for wall mounting
Input: 100 ... 240 V AC
Output: 12 V DC/3 A
PSU100D 1-phase, 12 V DC/8.3 A
6EP1322-1LD00
Stabilized power supply 100 W,
for wall mounting
Input: 100 ... 240 V AC
Output: 12 V DC/8.3 A
9/6
Siemens KT 10.1 · 2016
© Siemens AG 2016
Special designs, special uses
Wall mounting
1-phase, 24 V DC (PSU100D)
■ Overview
The single-phase PSU100Ds are switch mode power supplies
for direct wall mounting using screws. The flat and rugged aluminum enclosure with IP20 degree of protection can be installed
in various orientations and is therefore ideal for installation locations with limited space or for mounting in control cabinets and
enclosures without a DIN rail. The low-cost devices meet all the
basic requirements for a power supply, typical applications being apparatus, automated equipment and automation solutions.
Main product highlights
• 24 V DC/ 2.1 A and 3.1 A, 4.1 A, 6.2 A and 12.5 A
• Compact metal enclosure
• Wide-range input
• Green LED for "24 V OK"
• Certification in accordance with CE and UL
• Adjustable output voltage from 22 to 28 V or from 11 to 14 V
for compensating voltage drops
• Temperature range from -10 °C to +70 °C
■ Technical specifications
Article number
6EP1331-1LD00
6EP1332-1LD00
6EP1332-1LD10
6EP1333-1LD00
6EP1334-1LD00
Product
PSU100D
PSU100D
PSU100D
PSU100D
PSU100D
Power supply, type
24 V/2.1 A
24 V/3.1 A
24 V/4.1 A
24 V/6.2 A
24 V/12.5 A
Input
Input
1-phase AC
1-phase AC
1-phase AC
1-phase AC
1-phase AC
Rated voltage value Vin rated
100 ... 240 V
100 ... 240 V
100 ... 240 V
100 ... 240 V
100 ... 240 V
Voltage range AC
85 ... 264 V
85 ... 264 V
85 ... 264 V
85 ... 264 V
85 ... 264 V
Wide-range input
Yes
Yes
Yes
Yes
Yes
Mains buffering at Iout rated, min.
15 ms;
at Vin = 115/230 V
15 ms;
at Vin = 115/230 V
15 ms;
at Vin = 115/230 V
15 ms;
at Vin = 115/230 V
15 ms;
at Vin = 115/230 V
Rated line frequency 1
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
9
Input current
• at rated input voltage 100 V
1.1 A
1.5 A
2A
3.1 A
4A
• at rated input voltage 240 V
0.7 A
1A
1.1 A
2A
2A
Switch-on current limiting
(+25 °C), max.
60 A
60 A
75 A
75 A
60 A
I²t, max.
1.2 A²·s
1.2 A²·s
4 A²·s
6.5 A²·s
1.1 A²·s
Built-in incoming fuse
internal
internal
internal
internal
internal
Protection in the mains power input
(IEC 898)
Recommended
miniature circuit
breaker: from 10 A
characteristic C or
from 16 A
characteristic B
Recommended
miniature circuit
breaker: from 10 A
characteristic C or
from 16 A
characteristic B
Recommended
miniature circuit
breaker: from 10 A
characteristic C or
from 16 A
characteristic B
Recommended
miniature circuit
breaker: from 10 A
characteristic C or
from 16 A
characteristic B
Recommended
miniature circuit
breaker: from 10 A
characteristic C or
from 16 A
characteristic B
Siemens KT 10.1 · 2016
9/7
© Siemens AG 2016
Special designs, special uses
Wall mounting
1-phase, 24 V DC (PSU100D)
■ Technical specifications (continued)
Article number
6EP1331-1LD00
6EP1332-1LD00
6EP1332-1LD10
6EP1333-1LD00
6EP1334-1LD00
Product
PSU100D
PSU100D
PSU100D
PSU100D
PSU100D
Power supply, type
24 V/2.1 A
24 V/3.1 A
24 V/4.1 A
24 V/6.2 A
24 V/12.5 A
Output
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Rated voltage Vout DC
24 V
24 V
24 V
24 V
24 V
Total tolerance, static ±
2%
2%
2%
2%
2%
Static mains compensation, approx.
0.5 %
0.5 %
0.5 %
0.5 %
0.5 %
Static load balancing, approx.
1%
1%
1%
1%
0.5 %
Residual ripple peak-peak, max.
100 mV
100 mV
100 mV
100 mV
100 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
100 mV
100 mV
100 mV
100 mV
100 mV
Adjustment range
22 ... 28 V
22 ... 28 V
22 ... 28 V
22 ... 28 V
22 ... 28 V
Product function Output voltage
adjustable
Yes
Yes
Yes
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
via potentiometer
via potentiometer
via potentiometer
Status display
Green LED for 24 V OK Green LED for 24 V OK Green LED for 24 V OK Green LED for 24 V OK Green LED for 24 V OK
Output
-
Signaling
9
On/off behavior
Overshoot of
Vout < 2 %
Overshoot of
Vout < 2 %
Overshoot of
Vout < 2 %
Overshoot of
Vout < 2 %
Overshoot of
Vout < 2 %
Startup delay, max.
1s
2.5 s
1s
1s
1s
Voltage increase time of the output
voltage maximum
30 ms
30 ms
30 ms
30 ms
30 ms
Rated current value Iout rated
2.1 A
3.1 A
4.1 A
6.2 A
12.5 A
Current range
0 ... 2.1 A
0 ... 3.1 A
0 ... 4.1 A
0 ... 6.2 A
0 ... 12.5 A
• Note
+50 ... +70 °C:
Derating 2.5%/K
+50 ... +70 °C:
Derating 2.5%/K
+50 ... +70 °C:
Derating 2.5%/K
+50 ... +70 °C:
Derating 2.5%/K
+50 ... +70 °C:
Derating 2.5%/K
Supplied active power typical
50 W
75 W
100 W
150 W
300 W
Parallel switching for enhanced
performance
Yes
Yes
Yes
Yes
Yes
Numbers of parallel switchable units
for enhanced performance
2
2
2
2
2
Efficiency at Vout rated, Iout rated,
approx.
86 %
86 %
86 %
86 %
86 %
Power loss at Vout rated, Iout rated,
approx.
8W
12 W
16 W
24 W
48 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.5 %
0.5 %
0.5 %
0.5 %
0.5 %
Dynamic load smoothing
(Iout 50/100/50 %), Uout ± typ.
5%
5%
5%
5%
5%
Efficiency
Closed-loop control
Protection and monitoring
Output overvoltage protection
< 35 V
< 35 V
< 35 V
< 35 V
< 35 V
Current limitation, typ.
2.5 A
3.7 A
4.9 A
7.4 A
15 A
Property of the output Short-circuit
proof
Yes
Yes
Yes
Yes
Yes
Short-circuit protection
Electronic shutdown,
automatic restart
Electronic shutdown,
automatic restart
Electronic shutdown,
automatic restart
Electronic shutdown,
automatic restart
Electronic shutdown,
automatic restart
• typical
6A
6A
10 A
16 A
15 A
Overload/short-circuit indicator
-
-
-
-
-
Enduring short circuit current RMS
value
9/8
Siemens KT 10.1 · 2016
© Siemens AG 2016
Special designs, special uses
Wall mounting
1-phase, 24 V DC (PSU100D)
■ Technical specifications (continued)
Article number
6EP1331-1LD00
6EP1332-1LD00
6EP1332-1LD10
6EP1333-1LD00
6EP1334-1LD00
Product
PSU100D
PSU100D
PSU100D
PSU100D
PSU100D
Power supply, type
24 V/2.1 A
24 V/3.1 A
24 V/4.1 A
24 V/6.2 A
24 V/12.5 A
Yes
Yes
Yes
Yes
Safety
Primary/secondary isolation
Yes
Galvanic isolation
Safety extra low output Safety extra low output Safety extra low output Safety extra low output Safety extra low output
voltage Vout according voltage Vout according voltage Vout according voltage Vout according voltage Vout according
to EN 60950-1
to EN 60950-1
to EN 60950-1
to EN 60950-1
to EN 60950-1
Protection class
Class I
Class I
Class I
Class I
Class I
Leakage current
• maximum
3.5 mA
3.5 mA
3.5 mA
3.5 mA
3.5 mA
• typical
1 mA
1 mA
1 mA
1 mA
1 mA
CE mark
Yes
Yes
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259; cURus
(UL 60950-1, CSA
C22.2 No. 60950-1),
File E151273
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259; cURus
(UL 60950-1, CSA
C22.2 No. 60950-1),
File E151273
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259; cURus
(UL 60950-1, CSA
C22.2 No. 60950-1),
File E151273
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259; cURus
(UL 60950-1, CSA
C22.2 No. 60950-1),
File E151273
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259; cURus
(UL 60950-1, CSA
C22.2 No. 60950-1),
File E151273
Explosion protection
-
-
-
-
-
FM approval
-
-
-
-
-
CB approval
Yes
Yes
Yes
Yes
Yes
Marine approval
-
-
-
-
-
Degree of protection (EN 60529)
IP20
IP20
IP20
IP20
IP20
EMC
Emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
not applicable
EN 61000-3-2
EN 61000-3-2
-
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
-10 ... +70 °C
-10 ... +70 °C
-10 ... +70 °C
-10 ... +70 °C
-10 ... +70 °C
Operating data
Ambient temperature
• during operation
- Note
with natural convection with natural convection with natural convection with natural convection with forced convection
(ventilator)
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
screw-type terminals
screw-type terminals
screw-type terminals
screw-type terminals
screw-type terminals
• Supply input
L, N, PE: 1 screw
terminal each for
0.3 ... 1.3 mm² singlecore/finely stranded
L, N, PE: 1 screw
terminal each for
0.3 ... 1.3 mm² singlecore/finely stranded
L, N, PE: 1 screw
terminal each for
0.3 ... 1.3 mm² singlecore/finely stranded
L, N, PE: 1 screw
terminal each for
0.3 ... 1.3 mm² singlecore/finely stranded
L, N, PE: 1 screw
terminal each for
0.5 ... 1.3 mm² singlecore/finely stranded
• Output
+, -:
+, -:
+, -:
+, -:
+, -:
1 screw terminal each 1 screw terminal each 2 screw terminals each 2 screw terminals each 2 screw terminals each
for 0.3 ... 1.3 mm²
for 0.3 ... 1.3 mm²
for 0.3 ... 1.3 mm²
for 0.3 ... 1.3 mm²
for 0.5 ... 1.3 mm²
• Auxiliary
-
-
-
-
-
Width of the enclosure
97 mm
97 mm
97 mm
97 mm
105 mm
Height of the enclosure
128 mm
128 mm
158 mm
178 mm
199 mm
Depth of the enclosure
38 mm
38 mm
38 mm
38 mm
41 mm
Weight, approx.
0.35 kg
0.37 kg
0.5 kg
0.55 kg
0.81 kg
Installation
Wall mounting
Wall mounting
Wall mounting
Wall mounting
Wall mounting
Other information
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Mechanics
Connection technology
Connections
Siemens KT 10.1 · 2016
9/9
9
© Siemens AG 2016
Special designs, special uses
Wall mounting
1-phase, 24 V DC (PSU100D)
■ Ordering data
PSU100D 1-phase, 24 V DC/2.1 A
Article No.
6EP1331-1LD00
Stabilized power supply 50 W,
for wall mounting
Input: 100 ... 240 V AC
Output: 24 V DC/2.1 A
PSU100D 1-phase, 24 V DC/3.1 A
6EP1332-1LD00
Stabilized power supply 75 W,
for wall mounting
Input: 100 ... 240 V AC
Output: 24 V DC/3.1 A
PSU100D 1-phase, 24 V DC/4.1 A
6EP1332-1LD10
Stabilized power supply 100 W,
for wall mounting
Input: 100 ... 240 V AC
Output: 24 V DC/4.1 A
PSU100D 1-phase, 24 V DC/6.2 A
6EP1333-1LD00
Stabilized power supply 150 W,
for wall mounting
Input: 100 ... 240 V AC
Output: 24 V DC/6.2 A
PSU100D 1-phase, 24 V DC/12.5 A
6EP1334-1LD00
Stabilized power supply 300 W,
for wall mounting
Input: 100 ... 240 V AC
Output: 24 V DC/12.5 A
9
9/10
Siemens KT 10.1 · 2016
© Siemens AG 2016
Special designs, special uses
High degree of protection
1-phase, 24 V DC (SITOP PSU100P, IP67)
■ Overview
The SITOP PSU100P 1-phase power supplies for wall mounting,
with their rugged design and IP 67 degree of protection are ideal
for distributed applications outside the control cabinet.
Main product highlights
• 24 V DC/ 5 A and 8 A
• Automatic switchover of the input voltage
• Temperature range from -25 °C to +60 °C without derating
• High efficiency of 93 % for low internal power consumption
• Isolated relay contact "24 V OK"
• Operation display on the device by means of LED
(green = "24 V OK", flashing red = overload)
■ Technical specifications
Article number
6EP1333-7CA00
6EP1334-7CA00
Product
SITOP PSU100P
SITOP PSU100P
Power supply, type
24 V/5 A
24 V/8 A
1-phase AC
1-phase AC
• 1 at AC Rated value
120 V
120 V
• 2 at AC Rated value
230 V
230 V
• Note
Automatic range selection
Automatic range selection
• 1 at AC
85 ... 132 V
85 ... 132 V
• 2 at AC
170 ... 264 V
170 ... 264 V
Wide-range input
No
No
Overvoltage resistance
Implemented internally with varistor
Implemented internally with varistor
Input
Input
Supply voltage
Input voltage
9
Mains buffering at Iout rated, min.
40 ms; at Vin = 120/230 V
40 ms; at Vin = 120/230 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 120 V
2.25 A
3.5 A
• at rated input voltage 230 V
1.24 A
1.52 A
Switch-on current limiting (+25 °C), max.
15 A
15 A
I²t, max.
0.6 A²·s
0.6 A²·s
Built-in incoming fuse
T 3.15 A
T 6.3 A
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker:
from 6 A characteristic C/B
Recommended miniature circuit breaker:
from 6 A characteristic C/B
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
24 V
Total tolerance, static ±
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
0.2 %
0.2 %
Residual ripple peak-peak, max.
50 mV
50 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
100 mV
100 mV
Product function Output voltage adjustable
No
No
Status display
Green LED: 24 V OK;
red LED flashing: "overload/short-circuit"
Green LED: 24 V OK;
red LED flashing: "overload/short-circuit"
Signaling
Relay contact (NO contact, rating 30 V AC/ 0.5 A;
30 V DC/1 A) for 24 V OK
Relay contact (NO contact, rating 30 V AC/ 0.5 A;
30 V DC/1 A) for 24 V OK
Input current
Output
Siemens KT 10.1 · 2016
9/11
© Siemens AG 2016
Special designs, special uses
High degree of protection
1-phase, 24 V DC (SITOP PSU100P, IP67)
■ Technical specifications (continued)
Article number
6EP1333-7CA00
6EP1334-7CA00
Product
SITOP PSU100P
SITOP PSU100P
Power supply, type
24 V/5 A
24 V/8 A
On/off behavior
Overshoot of Vout < 3 %
Overshoot of Vout < 3 %
Startup delay, max.
1.5 s
1.5 s
Voltage rise, typ.
22 ms
23 ms
Voltage increase time of the output voltage
maximum
100 ms
100 ms
Rated current value Iout rated
5A
8A
Current range
0 ... 5 A
0 ... 8 A
Supplied active power typical
133 W
206 W
Short-term overload current
• on short-circuiting during the start-up typical 20 A
30 A
20 A
30 A
• on short-circuiting during the start-up
50 ms
50 ms
• at short-circuit during operation
50 ms
50 ms
Parallel switching for enhanced performance
Yes; Symmetric wiring required
Yes; Symmetric wiring required
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency at Vout rated, Iout rated, approx.
90 %
93.6 %
Power loss at Vout rated, Iout rated, approx.
12.9 W
13.1 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.2 %
0.2 %
Dynamic load smoothing (Iout 50/100/50 %),
Uout ± typ.
1%
1%
Setting time maximum
2 ms
2 ms
Output overvoltage protection
< 29 V
< 29 V
Current limitation, typ.
5.5 A
9A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
• maximum
6A
9A
• typical
5A
8A
Overload/short-circuit indicator
Red LED flashing for "overload/short-circuit"
Red LED flashing for "overload/short-circuit"
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
• maximum
3.5 mA
3.5 mA
• typical
1 mA
1 mA
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1)
cULus-Listed (UL 508, CSA C22.2 No. 107.1)
Explosion protection
No
No
FM approval
-
-
CB approval
No
No
Marine approval
No
No
Degree of protection (EN 60529)
IP67, enclosure type 4 indoor
IP67, enclosure type 4 indoor
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
• at short-circuit during operation typical
Duration of overloading capability for excess
current
Efficiency
Closed-loop control
Protection and monitoring
9
Enduring short circuit current RMS value
Safety
Leakage current
EMC
9/12
Siemens KT 10.1 · 2016
© Siemens AG 2016
Special designs, special uses
High degree of protection
1-phase, 24 V DC (SITOP PSU100P, IP67)
■ Technical specifications (continued)
Article number
6EP1333-7CA00
6EP1334-7CA00
Product
SITOP PSU100P
SITOP PSU100P
Power supply, type
24 V/5 A
24 V/8 A
-25 ... +60 °C
-25 ... +60 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to EN 60721
3K6 without direct sunlight
3K6 without direct sunlight
screw-type terminals
screw-type terminals
• Supply input
L1, N, PE: Plug connector 7/8"
(counterpart see "Operating Instructions (compact)")
L1, N, PE: Plug connector 7/8"
(counterpart see "Operating Instructions (compact)")
• Output
+, -: Plug connector 7/8"
(counterpart see "Operating Instructions (compact)")
+, -: Plug connector 7/8"
(counterpart see "Operating Instructions (compact)")
• Auxiliary
Alarm signals: M12 plug-in connector 4-pin
Alarm signals: M12 plug-in connector 4-pin
• removable terminal at input
Yes
Yes
• removable terminal at output
Yes
Yes
Width of the enclosure
120 mm
120 mm
Height of the enclosure
181 mm
181 mm
Depth of the enclosure
60.5 mm
60.5 mm
Weight, approx.
1.1 kg
1.3 kg
Product feature of the enclosure housing for
side-by-side mounting
Yes
Yes
Installation
Wall mounting
Wall mounting
MTBF at 40 °C
1 500 000 h
800 000 h
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
Product function
■ Ordering data
SITOP PSU100P 1-phase,
24 V DC/5 A
Article No.
6EP1333-7CA00
Stabilized power supply with IP67
degree of protection
Input: 120/230 V AC
Output: 24 V DC/5 A
SITOP PSU100P 1-phase,
24 V DC/8 A
9
■ More information
Select the appropriate power supply quickly and easily with the
SITOP Selection Tool:
http://www.siemens.com/sitop-selection-tool
6EP1334-7CA00
Stabilized power supply with IP67
degree of protection
Input: 120/230 V AC
Output: 24 V DC/8 A
Siemens KT 10.1 · 2016
9/13
© Siemens AG 2016
Special designs, special uses
High degree of protection
3-phase, 24 V DC (ET200pro PS, IP67)
■ Overview
■ Technical specifications
Article number
6ES7148-4PC00-0HA0
Product
SIMATIC ET200pro PS
Power supply, type
24 V/8 A
Input
Input
3-phase AC
Rated voltage value Vin rated
400 ... 480 V
Voltage range AC
340 ... 550 V
• Note
320 ... 340 V for max. 1 min
Wide-range input
Yes
Overvoltage resistance
Implemented internally with varistors
Mains buffering at Iout rated, min.
15 ms; at Vin = 400 V
Rated line frequency 1
50 Hz
Rated line frequency 2
60 Hz
Rated line range
45 ... 66 Hz
Input current
The SIMATIC ET200pro PS power supply unit with degree of
protection IP67 is used as the electronics/encoder supply and
load voltage supply of the new SIMATIC ET 200pro distributed
I/O system for use close to the machine without a cabinet. With
a signaling contact for "24 V OK" and "Overtemperature", as well
as a second plug-in connector for input voltage loop-through.
• at rated input voltage 400 V
0.5 A
Switch-on current limiting
(+25 °C), max.
40 A
I²t, max.
3.5 A²·s
Built-in incoming fuse
T4A
Protection in the mains power input
(IEC 898)
Required: Circuit breaker
3RV2011-1DA10 or
3RV2711-1DD10 (UL 489)
Output
9
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
Total tolerance, static ±
3%
Static mains compensation, approx.
0.5 %
Static load balancing, approx.
0.5 %
Residual ripple peak-peak, max.
200 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
250 mV
Product function Output voltage
adjustable
No
Output voltage setting
-
Status display
Green LED for 24 V OK
Signaling
max. 30 V, 10 mA; Power-Good
(High-Pegel 1L+ for Vout in range
21.3 ... 29 V); Overtemperature
warning at least 30 s before switchoff (high level 1L+ when the max.
internal temperature is exceeded)
On/off behavior
Overshoot of Vout < 2 %
Startup delay, max.
1.5 s
Voltage rise, typ.
40 ms
Rated current value Iout rated
8A
Current range
0 ... 8 A
Supplied active power typical
192 W
Short-term overload current
• on short-circuiting during the
start-up typical
50 A
• at short-circuit during operation
typical
50 A
Duration of overloading capability for
excess current
9/14
Siemens KT 10.1 · 2016
• on short-circuiting during the
start-up
100 ms
• at short-circuit during operation
100 ms
Parallel switching for enhanced
performance
No
© Siemens AG 2016
Special designs, special uses
High degree of protection
3-phase, 24 V DC (ET200pro PS, IP67)
■ Technical specifications (continued)
Article number
6ES7148-4PC00-0HA0
Article number
6ES7148-4PC00-0HA0
Product
SIMATIC ET200pro PS
Product
SIMATIC ET200pro PS
Power supply, type
24 V/8 A
Power supply, type
24 V/8 A
Width of the enclosure
310 mm
Height of the enclosure
135 mm
Depth of the enclosure
90 mm
Weight, approx.
2.8 kg
Product feature of the enclosure
housing for side-by-side mounting
No
Efficiency
Efficiency at Vout rated, Iout rated,
approx.
88 %
Power loss at Vout rated, Iout rated,
approx.
25 W
Closed-loop control
Dynamic mains compensation
(Vin rated ±15 %), max.
0.5 %
Installation
Can be mounted onto ET200pro
mounting rail
Dynamic load smoothing
(Iout: 50/100/50 %), Uout ± typ.
1%
Electrical accessories
Setting time maximum
2 ms
Power connector
(Input: 3RK1911-2BE30 (6 mm²))
(Output: 3RK1911-2BF10 (4 mm²))
MTBF at 40 °C
196 354 h
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Protection and monitoring
Output overvoltage protection
< 33 V
Current limitation, typ.
9.4 A
Property of the output Short-circuit
proof
Yes
Short-circuit protection
Electronic shutdown, automatic
restart
Enduring short circuit current RMS
value
SIMATIC ET 200pro PS
• maximum
10 A
Overload/short-circuit indicator
-
Safety
Primary/secondary isolation
Yes
Galvanic isolation
Protective extra low output voltage
Vout according to EN 60950-1 and
EN 50178
Protection class
Class I
Leakage current
3.5 mA
• typical
0.4 mA
CE mark
Yes
UL/cUL (CSA) approval
UL-Listed UL 508 (only with cable
acc NFPA79)
Explosion protection
No
FM approval
-
CB approval
Yes
Marine approval
No
Degree of protection (EN 60529)
IP67, enclosure type 5 indoor
EMC
Emitted interference
EN 55022 Class A
Supply harmonics limitation
-
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature
- Note
-25 ... +55 °C
with natural convection
• during transport
-40 ... +70 °C
• during storage
-40 ... +70 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Mechanics
Connection technology
Article No.
6ES7148-4PC00-0HA0
Stabilized power supply in distributed I/O system design, permitting
the loop-through of energy to
further modules; with degree of
protection IP67;
Input: 400-480 V 3 AC
Output: 24 V DC/8 A
■ Accessories
Article No.
Power connector
• maximum
• during operation
■ Ordering data
screw-type terminals
For connecting to the distributed
I/O system
• For X1 (6 mm2)
• For X2 (4 mm2)
9
3RK1911-2BE30
3RK1911-2BF10
National Fire Protection
Association compatible
These devices are only approved
for installation in industrial machinery according to the NFPA79
Electrical Standard for Industrial
Machinery.
• for X1 SIMATIC ET200pro PS
61 88 201 1003.xx (AWG10)*
• for X1 SITOP PSU300P
61 88 201 1000.xx /
61 88 201 1002.xx (AWG14)*
• for X2 SIMATIC ET200pro PS
61 88 202 1010.xx (AWG10)*
supplied blanking cap for X2
• for X3 Phoenix-Contact
SAC-5P-M12-M12FS
* http://www.harting.com/en/home
3RK1902-0CK00
supplied blanking cap for X3
Sealing cap
For 9-pole power sockets
• X2 (1 unit)
• X2 (10 units)
3RK1902-0CJ0
3RK1902-0CK00
Connections
• Supply input
L1, L2, L3, PE: Plug connector
HAN Q4/2 (counterpart see
"Electrical accessories")
• Output
L+, M: 2 x 1.5 mm² each
(4-pole cable for +/- with open,
labeled ends, 4 x 1.5 mm²)
• Auxiliary
Alarm signals: M12 plug-in
connector 5-pin
Siemens KT 10.1 · 2016
9/15
© Siemens AG 2016
Special designs, special uses
Battery charging
3-phase, 12 V DC
■ Overview
The SITOP PSU3800 3-phase power supplies are suitable for
battery charging, thanks to their constant-current characteristic.
For other applications, the output characteristic can also be
switched to latching shutdown. The three-phase, wide-range
input enables them to be used worldwide. The slim design
requires little space on the DIN rail. Installation gaps are not
required.
■ Technical specifications
Article number
6EP3424-8UB00-0AY0
Article number
6EP3424-8UB00-0AY0
Product
SITOP PSU3800
Product
SITOP PSU3800
Power supply, type
12 V/20 A
Power supply, type
12 V/20 A
Signaling
Relay contact (NO contact, rating
60 V DC/ 0.3 A) for 12 V OK
Input
9
Input
3-phase AC
Rated voltage value Vin rated
400 ... 500 V
On/off behavior
No overshoot of Vout (soft start)
Voltage range AC
320 ... 575 V
Startup delay, max.
2.5 s
Wide-range input
Yes
500 ms
Mains buffering at Iout rated, min.
15 ms; at Vin = 400 V
Voltage increase time of the output
voltage maximum
Rated line frequency 1
50 Hz
Rated current value Iout rated
20 A
Rated line frequency 2
60 Hz
Current range
0 ... 20 A
Rated line range
47 ... 63 Hz
• Note
+60 ... +70 °C: Derating 2%/K
Supplied active power typical
240 W
Input current
• at rated input voltage 400 V
0.7 A
• at rated input voltage 500 V
0.6 A
Switch-on current limiting (+25 °C),
max.
Constant overload current
• on short-circuiting during the startup typical
22 A
16 A
Parallel switching for enhanced
performance
Yes; switchable characteristic
I²t, max.
0.8 A²·s
none
Numbers of parallel switchable units
for enhanced performance
2
Built-in incoming fuse
Protection in the mains power input
(IEC 898)
Required: 3-pole connected
miniature circuit breaker 6 ... 16 A
characteristic C or circuit breaker
3RV2011-1DA10 (setting 3 A) or
3RV2711-1DD10 (UL 489)
Output
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
12 V
Total tolerance, static ±
3%
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
0.2 %
Residual ripple peak-peak, max.
100 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
Efficiency
Efficiency at Vout rated, Iout rated,
approx.
91 %
Power loss at Vout rated, Iout rated,
approx.
24 W
Closed-loop control
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
Dynamic load smoothing
(Iout: 50/100/50 %), Uout ± typ.
1%
Load step setting time 50 to
100%, typ.
0.2 ms
200 mV
Load step setting time 100 to
50%, typ.
0.2 ms
Adjustment range
12 ... 14 V
Dynamic load smoothing
(Iout: 10/90/10 %), Uout ± typ.
2%
Product function Output voltage
adjustable
Yes
Load step setting time 10 to 90%, typ. 0.2 ms
Output voltage setting
via potentiometer; max. 240 W
Status display
Green LED for 12 V OK
9/16
Siemens KT 10.1 · 2016
Load step setting time 90 to 10%, typ. 0.2 ms
Setting time maximum
10 ms
© Siemens AG 2016
Special designs, special uses
Battery charging
3-phase, 12 V DC
■ Technical specifications (continued)
Article number
6EP3424-8UB00-0AY0
Article number
6EP3424-8UB00-0AY0
Product
SITOP PSU3800
Product
SITOP PSU3800
Power supply, type
12 V/20 A
Power supply, type
12 V/20 A
Protection and monitoring
Mechanics
Output overvoltage protection
< 18 V
Connection technology
Current limitation, typ.
22 A
Connections
Property of the output Short-circuit
proof
Yes
• Supply input
Short-circuit protection
Alternatively, constant current
characteristic approx. 22 A or
latching shutdown
L1, L2, L3, PE: 1 screw terminal each
for 0.2 ... 4 mm² single-core/finely
stranded
• Output
+, -: 2 screw terminals each for
0.2 ... 4 mm²
• Auxiliary
13, 14 (alarm signal):
1 screw terminal each for
0.14 ... 1.5 mm²; 15, 16 (Remote):
1 screw terminal each for
0.14 ... 1.5 mm²
Width of the enclosure
70 mm
Height of the enclosure
125 mm
Depth of the enclosure
125 mm
Enduring short circuit current RMS
value
• typical
22 A
Overload/short-circuit indicator
LED yellow for "overload",
LED red for "latching shutdown"
Safety
Primary/secondary isolation
Yes
Galvanic isolation
Safety extra low output voltage Vout
according to EN 60950-1
Protection class
Class I
screw-type terminals
Required spacing
• top
50 mm
Leakage current
• bottom
50 mm
• maximum
3.5 mA
• left
0 mm
• typical
0.9 mA
• right
0 mm
CE mark
Yes
Weight, approx.
1.2 kg
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259
Product feature of the enclosure
housing for side-by-side mounting
Yes
Explosion protection
ATEX (EX) II 3G Ex nA nC IIC T4;
cCSAus (CSA C22.2 No. 213,
ANSI/ISA-12.12.01) Class I, Div. 2,
Group ABCD, T4
Installation
Snaps onto DIN rail EN 60715
35x7.5/15
Electrical accessories
Buffer module
Mechanical accessories
Device identification label
20 mm × 7 mm, pale turquoise
3RT1900-1SB20
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
FM approval
-
CB approval
Yes
Marine approval
GL, ABS
Degree of protection (EN 60529)
IP20
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature
• during operation
- Note
-25 ... +70 °C
with natural convection
• during transport
-40 ... +85 °C
• during storage
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
■ Ordering data
SITOP PSU3800, 3-phase,
12 V DC/20 A
Article No.
6EP3424-8UB00-0AY0
Stabilized power supply
Input: 400 … 500 V 3 AC
Output: 12 V DC/20 A
Siemens KT 10.1 · 2016
9/17
9
© Siemens AG 2016
Special designs, special uses
Battery charging
3-phase, 24 V DC
■ Overview
SITOP PSU3800 3-phase power supplies (24 V DC/17 A and
30 A) are suitable for battery charging, thanks to their constantcurrent characteristic. For other applications the output characteristic can also be switched to latching shutdown. The threephase, wide-range input enables them to be used worldwide.
The slim design requires little space on the DIN rail. Installation
gaps are not required.
■ Technical specifications
Article number
6EP3436-8UB00-0AY0
6EP1437-3BA20
Product
SITOP PSU3800
SITOP PSU300B
Power supply, type
24 V/17 A
24 V/30 A
Input
3-phase AC
3-phase AC
Rated voltage value Vin rated
400 ... 500 V
400 ... 500 V
Voltage range AC
320 ... 575 V
320 ... 575 V
Wide-range input
Yes
Yes
Mains buffering at Iout rated, min.
15 ms; at Vin = 400 V
20 ms; at Vin = 400 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 400 V
1.1 A
1.6 A
• at rated input voltage 500 V
0.9 A
1.3 A
Switch-on current limiting (+25 °C), max.
16 A
56 A
I²t, max.
0.8 A²·s
2.24 A²·s
Built-in incoming fuse
none
none
Protection in the mains power input (IEC 898)
Required: 3-pole connected miniature circuit breaker
6 ... 16 A characteristic C or
circuit breaker 3RV2011-1DA10 (setting 3 A) or
3RV2711-1DD10 (UL 489)
Required: 3-pole connected miniature circuit breaker
10 ... 16 A characteristic C or
circuit breaker 3RV2011-1DA10 (setting 3 A) or
3RV2711-1DD10 (UL 489)
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
24 V
Total tolerance, static ±
3%
3%
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
0.2 %
0.1 %
Residual ripple peak-peak, max.
100 mV
100 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
200 mV
200 mV
Adjustment range
24 ... 28 V
24 ... 28.8 V
Product function Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer; max. 480 W
via potentiometer
Status display
Green LED for 24 V OK
Green LED for 24 V OK
Signaling
Relay contact (NO contact, rating 60 V DC/ 0.3 A)
for "24 V OK"
Relay contact (NO contact, rating 60 V DC/ 0.3 A)
for "24 V OK"
Input
9
Input current
Output
9/18
Siemens KT 10.1 · 2016
© Siemens AG 2016
Special designs, special uses
Battery charging
3-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP3436-8UB00-0AY0
6EP1437-3BA20
Product
SITOP PSU3800
SITOP PSU300B
Power supply, type
24 V/17 A
24 V/30 A
On/off behavior
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
Startup delay, max.
2.5 s
2.5 s
Voltage increase time of the output voltage
maximum
500 ms
500 ms
Rated current value Iout rated
17 A
30 A
Current range
0 ... 17 A
0 ... 30 A
• Note
+60 ... +70 °C: Derating 2%/K
+60 ... +70 °C: Derating 1.7%/K
Supplied active power typical
408 W
960 W
Constant overload current
• on short-circuiting during the start-up typical 19 A
32 A
• at short-circuit during operation typical
-
32 A
Parallel switching for enhanced performance
Yes; switchable characteristic
Yes; switchable characteristic
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency at Vout rated, Iout rated, approx.
94 %
93 %
Power loss at Vout rated, Iout rated, approx.
26 W
50 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.1 %
1%
Dynamic load smoothing (Iout: 50/100/50 %),
Uout ± typ.
1%
3%
Load step setting time 50 to 100%, typ.
0.2 ms
-
Load step setting time 100 to 50%, typ.
0.2 ms
-
Dynamic load smoothing (Iout: 10/90/10 %),
Uout ± typ.
2%
-
Load step setting time 10 to 90%, typ.
0.2 ms
-
Load step setting time 90 to 10%, typ.
0.2 ms
-
Setting time maximum
10 ms
10 ms
Output overvoltage protection
< 32 V
< 35 V
Current limitation, typ.
19 A
32 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Alternatively, constant current characteristic approx.
19 A or latching shutdown
Alternatively, constant current characteristic approx.
32 A or latching shutdown
• typical
19 A
32 A
Overload/short-circuit indicator
LED yellow for "overload", LED red for "latching
shutdown"
LED yellow for "overload", LED red for "latching
shutdown"
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra low output voltage Vout according to
EN 60950-1
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
• maximum
3.5 mA
3.5 mA
• typical
0.9 mA
-
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259
Explosion protection
ATEX (EX) II 3G Ex nA nC IIC T4; cCSAus
(CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I,
Div. 2, Group ABCD, T4
-
FM approval
-
-
CB approval
Yes
No
Marine approval
GL, ABS
-
Degree of protection (EN 60529)
IP20
IP20
Efficiency
Closed-loop control
9
Protection and monitoring
Enduring short circuit current RMS value
Safety
Leakage current
Siemens KT 10.1 · 2016
9/19
© Siemens AG 2016
Special designs, special uses
Battery charging
3-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP3436-8UB00-0AY0
6EP1437-3BA20
Product
SITOP PSU3800
SITOP PSU300B
Power supply, type
24 V/17 A
24 V/30 A
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
-25 ... +70 °C
-25 ... +70 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
screw-type terminals
screw-type terminals
EMC
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
• Supply input
L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 4 mm² L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 4 mm²
single-core/finely stranded
single-core/finely stranded
• Output
+, -: 2 screw terminals each for 0.2 ... 4 mm²
+, -: 2 screw terminals each for 0.33 ... 10 mm²
• Auxiliary
13, 14 (alarm signal):
1 screw terminal each for 0.14 ... 1.5 mm²; 15, 16
(Remote): 1 screw terminal each for 0.14 ... 1.5 mm²
13, 14 (alarm signal):
1 screw terminal each for 0.14 ... 1.5 mm²
Width of the enclosure
70 mm
150 mm
Height of the enclosure
125 mm
125 mm
Depth of the enclosure
125 mm
150 mm
• top
50 mm
-
• bottom
50 mm
-
• left
0 mm
-
• right
0 mm
-
Weight, approx.
1.2 kg
3.4 kg
Product feature of the enclosure housing for
side-by-side mounting
Yes
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
Snaps onto DIN rail EN 60715 35x15
Electrical accessories
Buffer module
Buffer module
Mechanical accessories
Device identification label 20 mm × 7 mm,
pale turquoise 3RT1900-1SB20
Device identification label 20 mm × 7 mm,
pale turquoise 3RT1900-1SB20
Required spacing
9
885 739 h
MTBF at 40 °C
Other information
■ Ordering data
SITOP PSU3800 3-phase,
24 V DC/17 A
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Article No.
6EP3436-8UB00-0AY0
Stabilized power supply
Input: 400 ... 500 V 3 AC
Output: 24 V DC/17 A
SITOP PSU300B 3-phase,
24 V DC/30 A
6EP1437-3BA20
Stabilized power supply
Input: 400 ... 500 V 3 AC
Output: 24 V AC/30 A
9/20
Siemens KT 10.1 · 2016
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
© Siemens AG 2016
Special designs, special uses
Alternative output voltages
1-phase, 2 x 15 V DC (SITOP dual)
■ Overview
Article number
6EP1353-0AA00
Product
SITOP dual
Power supply, type
2 x 15 V/3.5 A
Output
The industrial power supply with two 15 V outputs that can be
switched in parallel and in series; can be used, for example, to
supply electronic loads with ±15 V.
■ Technical specifications
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
15 V
Output voltage
2 x 15 V DC
• at output 1 at DC Rated value
15 V
• at output 2 at DC Rated value
15 V
Total tolerance, static ±
2%
Static mains compensation, approx.
0.2 %
Static load balancing, approx.
0.2 %
Residual ripple peak-peak, max.
50 mV
Residual ripple peak-peak, typ.
20 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
150 mV
Adjustment range
14.5 ... 17 V
Product function Output voltage
adjustable
Yes
Output voltage setting
via potentiometer
Status display
Green LED grün for Vout >10 V
(summation display)
Signaling
-
On/off behavior
Overshoot of Vout < 3 %
Startup delay, max.
1s
Rated current value Iout rated
3.5 A
Output current
• at output 1 Rated value
3.5 A
• at output 2 Rated value
3.5 A
Current range
0 ... 3.5 A
Article number
6EP1353-0AA00
• Note
+45 ... +60 °C: Derating 2%/K
Product
SITOP dual
Supplied active power typical
105 W
Power supply, type
2 x 15 V/3.5 A
Parallel switching for enhanced
performance
Yes
Input
1-phase AC
2
Rated voltage value Vin rated
120 ... 230 V
Numbers of parallel switchable units
for enhanced performance
Voltage range AC
93 ... 264 V
Wide-range input
Yes
Efficiency at Vout rated, Iout rated,
approx.
80 %
Overvoltage resistance
Surge voltage in accordance with
EN 61000-6-2 Table 4
Power loss at Vout rated, Iout rated,
approx.
27 W
Mains buffering at Iout rated, min.
10 ms; at Vin = 120 V,
40 ms at Vin = 187 V
Protection and monitoring
Rated line frequency 1
50 Hz
Rated line frequency 2
60 Hz
Rated line range
47 ... 63 Hz
Input
Input current
9
Efficiency
Output overvoltage protection
Yes, according to EN 60950-1
Current limitation
4.9 A
Current limitation
Limit point < 4.9 A;
switch-off point < 6 A
1.9 A
Property of the output Short-circuit
proof
Yes
• at rated input voltage 120 V
• at rated input voltage 230 V
1.15 A
Short-circuit protection
Switch-on current limiting (+25 °C),
max.
30 A
Electronic shutdown, automatic
restart
Overload/short-circuit indicator
-
Safety
Duration of inrush current limiting
at 25 °C
Primary/secondary isolation
Yes
Galvanic isolation
Safety extra low output voltage Vout
according to EN 60950-1
T 4 A/250 V (not accessible)
Protection class
Class I
Recommended miniature circuit
breaker:
from 10 A characteristic C or
from 16 A characteristic B
Leakage current
• typical
3 ms
I²t, max.
3 A²·s
Built-in incoming fuse
Protection in the mains power input
(IEC 898)
• maximum
3.5 mA
CE mark
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2
No. 142), File E179336
Explosion protection
-
FM approval
-
CB approval
No
Marine approval
-
Degree of protection (EN 60529)
IP20
Siemens KT 10.1 · 2016
9/21
© Siemens AG 2016
Special designs, special uses
Alternative output voltages
1-phase, 2 x 15 V DC (SITOP dual)
■ Technical specifications (continued)
Article number
6EP1353-0AA00
Product
SITOP dual
Power supply, type
2 x 15 V/3.5 A
EMC
Emitted interference
EN 55011 Class A
Supply harmonics limitation
-
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature
• during operation
- Note
0 ... 60 °C
with natural convection
• during transport
-40 ... +70 °C
• during storage
-40 ... +70 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Mechanics
Connection technology
screw-type terminals
Connections
9
• Supply input
L1, N, PE: 1 screw terminal each for
0.5 ... 2.5 mm² single-core/finely
stranded
• Output
P15_1, GND_1, GND_2:
1 screw terminal each for
0.5 ... 2.5 mm²;
P15_2: 2 screw terminals for
0.5 ... 2.5 mm²
• Auxiliary
-
Width of the enclosure
75 mm
Height of the enclosure
125 mm
Depth of the enclosure
125 mm
Weight, approx.
0.75 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Installation
Snaps onto DIN rail EN 60715
35x7.5/15
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
9/22
Siemens KT 10.1 · 2016
■ Ordering data
SITOP power 15 V
Dual output
Stabilized power supply
Input: 120 ... 230 V AC
Output: 2 x 15 V DC/3.5 A
Article No.
6EP1353-0AA00
© Siemens AG 2016
Special designs, special uses
Alternative output voltages
1-phase, 3-52 V DC (SITOP flexi 120 W)
■ Overview
Article number
6EP1353-2BA00
Product
SITOP flexi
Power supply, type
3-52 V/2-10 A
Output
The power supply with flexible output voltage from 3 to 52 V;
suitable for all application areas requiring a special voltage other
than 24 V.
■ Technical specifications
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
Output voltage
3-52 V DC
Total tolerance, static ±
1%
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
0.2 %
Sense line connection max. voltage
control per line
0.5 V
Residual ripple peak-peak, max.
50 mV
Residual ripple peak-peak, typ.
20 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
100 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
80 mV
Adjustment range
3 ... 52 V
Product function Output voltage
adjustable
Yes
Output voltage setting
via potentiometer or analog control
voltage signal 0 ... 2.5 V
Status display
Green LED for 24 V OK
Signaling
Power-Good via relay contact,
current monitor signal 0 … 2.5 V
On/off behavior
No overshoot of Vout (soft start)
Startup delay, max.
3s
Voltage rise, typ.
80 ms
Rated current value Iout rated
10 A
• min.
2A
Article number
6EP1353-2BA00
• max.
10 A
Product
SITOP flexi
Current range
0 ... 10 A
Power supply, type
3-52 V/2-10 A
• Note
max. 120 W
Supplied active power typical
120 W
Input
Input
9
1-phase AC
Constant overload current
120 V
• on short-circuiting during the startup typical
10 A
• 1 at AC Rated value
• 2 at AC Rated value
230 V
120 ... 230 V
• at short-circuit during operation
typical
10 A
Rated voltage value Vin rated
• Note
Set via wire jumper
Parallel switching for enhanced
performance
Yes
85 ... 132 V
Numbers of parallel switchable units
for enhanced performance
2
• 1 at AC
• 2 at AC
170 ... 264 V
Efficiency
Wide-range input
No
2.3 × Vin rated, 1.3 ms
Efficiency at Vout rated, Iout rated,
approx.
84 %
Overvoltage resistance
Mains buffering at Iout rated, min.
10 ms; at Pout = 120 W and
Vin = 93/187 V
Power loss at Vout rated, Iout rated,
approx.
23 W
Rated line frequency 1
50 Hz
Protection and monitoring
Rated line frequency 2
60 Hz
Output overvoltage protection
Yes, according to EN 60950-1
Rated line range
47 ... 63 Hz
Current limitation
2 ... 10 A
Current limitation
2 ... 10 A, adjustable using
potentiometer or analog control
voltage signal 0 ... 2.5 V
Property of the output Short-circuit
proof
Yes
Short-circuit protection
Electronic current limiting (2 ... 10 A)
in the range 3 ... 12 V or power
limiting (120 W) in the range
12 ... 52 V
Overcurrent overload capability in
normal operation
According to the adjusted current
regulation 2 ... 10 A
Overload/short-circuit indicator
Red LED for current or power limiting
Supply voltage
Input voltage
Input current
• at rated input voltage 120 V
2.2 A
• at rated input voltage 230 V
0.9 A
Switch-on current limiting (+25 °C),
max.
32 A
I²t, max.
0.8 A²·s
Built-in incoming fuse
T 3,15 A/250 V (not accessible)
Protection in the mains power input
(IEC 898)
Recommended miniature circuit
breaker: from 6 A characteristic C
Siemens KT 10.1 · 2016
9/23
© Siemens AG 2016
Special designs, special uses
Alternative output voltages
1-phase, 3-52 V DC (SITOP flexi 120 W)
■ Technical specifications (continued)
Article number
6EP1353-2BA00
Product
SITOP flexi
Power supply, type
3-52 V/2-10 A
Safety
Primary/secondary isolation
Yes
Galvanic isolation
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Protection class
Class I
Leakage current
• maximum
3.5 mA
CE mark
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2
No. 142), File E143289
Explosion protection
-
FM approval
-
CB approval
No
Marine approval
-
Degree of protection (EN 60529)
IP20
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature
• during operation
9
0 ... 60 °C
with natural convection
- Note
• during transport
-40 ... +85 °C
• during storage
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Mechanics
Connection technology
screw-type terminals
Connections
• Supply input
L1, N, PE: 1 screw terminal each for
0.5 ... 2.5 mm² single-core/finely
stranded
• Output
L+: 1 screw terminal for
0.5 ... 2.5 mm²;
M: 2 screw terminals for
0.5 ... 2.5 mm²
• Auxiliary
Alarm signals, control inputs:
1 screw terminal each for
0.14 ... 1.5 mm²
Width of the enclosure
75 mm
Height of the enclosure
125 mm
Depth of the enclosure
125 mm
Weight, approx.
0.9 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Installation
Snaps onto DIN rail EN 60715
35x7.5/15
MTBF at 40 °C
1 196 172 h
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
9/24
Siemens KT 10.1 · 2016
■ Ordering data
SITOP power flexi
Stabilized power supply
Input: 120 ... 230 V AC
Output: 3-52 V DC / 2-10 A, 120 W
Article No.
6EP1353-2BA00
© Siemens AG 2016
Special designs, special uses
DC/DC converters
48-220V DC / 24 V DC/0.375 A
■ Overview
Article number
6EP1731-2BA00
Product
SITOP power
Power supply, type
24 V/0.375 A
Output
The optimum power supply for automation solutions in the lower
performance range; with wide-range input for 48-220 V DC;
thanks to their compact and slim design, they are particularly
suitable for solutions where space is limited and in conjunction
with low-voltage switchgear.
■ Technical specifications
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
Total tolerance, static ±
3%
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
0.1 %
Residual ripple peak-peak, max.
150 mV
Residual ripple peak-peak, typ.
50 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
240 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
50 mV
Product function Output voltage
adjustable
No
Output voltage setting
-
Status display
Green LED for 24 V OK
On/off behavior
No overshoot of Vout (soft start)
Startup delay, max.
2.5 s
Voltage rise, typ.
90 ms
Rated current value Iout rated
0.375 A
Current range
0 ... 0.375 A
• Note
+60 ... +70 °C: Derating 3%/K
Supplied active power typical
9W
Short-term overload current
Article number
6EP1731-2BA00
Product
SITOP power
Power supply, type
24 V/0.375 A
Duration of overloading capability for
excess current
DC voltage
• at short-circuit during operation
200 ms
Parallel switching for enhanced
performance
No
Input
Input
Supply voltage
• at DC
48 ... 220 V
Voltage range AC
30 ... 187 V
Input voltage
• at short-circuit during operation
typical
2.7 A
Efficiency at Vout rated, Iout rated,
approx.
66 %
4.6 W
• at DC
30 ... 264 V
Wide-range input
Yes
Power loss at Vout rated, Iout rated,
approx.
Overvoltage resistance
-
Closed-loop control
Mains buffering at Iout rated, min.
10 ms; at Vin = 220 V
Dynamic mains compensation
(Vin rated ±15 %), max.
0.3 %
• at rated input voltage 48 V
0.3 A
0.4 %
• at rated input voltage 220 V
0.06 A
Dynamic load smoothing
(Iout: 50/100/50 %), Uout ± typ.
35 A
Load step setting time 50 to 100%,
typ.
2 ms
Switch-on current limiting (+25 °C),
max.
Load step setting time 100 to 50%,
typ.
2 ms
Input current
Duration of inrush current limiting at
25 °C
9
Efficiency
Protection and monitoring
• typical
3 ms
Output overvoltage protection
Yes, according to EN 60950-1
I²t, max.
1.2 A²·s
Current limitation
0.41 ... 0.49 A
Built-in incoming fuse
F 4 A/250 V (not accessible)
Yes
Protection in the mains power input
(IEC 898)
Recommended miniature circuit
breaker: from 6 A characteristic C,
suitable for DC
Property of the output Short-circuit
proof
Short-circuit protection
Electronic shutdown, automatic
restart
Enduring short circuit current RMS
value
• maximum
0.9 A
Overload/short-circuit indicator
-
Siemens KT 10.1 · 2016
9/25
© Siemens AG 2016
Special designs, special uses
DC/DC converters
48-220V DC / 24 V DC/0.375 A
■ Technical specifications (continued)
Article number
6EP1731-2BA00
Product
SITOP power
Power supply, type
24 V/0.375 A
Safety
Primary/secondary isolation
Yes
Galvanic isolation
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Protection class
Class I
Leakage current
• maximum
3.5 mA
CE mark
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2
No. 142), File E143289, cURusRecognized (UL 60950, CSA C22.2
No. 60950), File E151273
Explosion protection
-
FM approval
-
CB approval
No
Marine approval
-
Degree of protection (EN 60529)
IP20
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
not applicable
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature
• during operation
9
-25 ... +70 °C
with natural convection
- Note
• during transport
-40 ... +70 °C
• during storage
-40 ... +70 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Mechanics
Connection technology
screw-type terminals
Connections
• Supply input
L+1, M1, PE: 1 screw terminal each
for 0.5 ... 2.5 mm² single-core/finely
stranded
• Output
+: 1 screw terminal for
0.5 ... 2.5 mm²;
-: 2 screw terminals for
0.5 ... 2.5 mm²
• Auxiliary
-
Width of the enclosure
22.5 mm
Height of the enclosure
80 mm
Depth of the enclosure
91 mm
Weight, approx.
0.14 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Installation
Snaps onto DIN rail EN 60715
35x7.5/15
MTBF at 40 °C
1 466 123 h
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
9/26
Siemens KT 10.1 · 2016
■ Ordering data
SITOP power 0.375 A
DC/DC stabilized power supply
Input: DC 48 … 220 V
Output: 24 V DC/0.375 A
6EP1731-2BA00
© Siemens AG 2016
Special designs, special uses
DC/DC converters
48-110V DC / 24 V DC/2 A
■ Overview
Article number
6EP1732-0AA00
Product
SITOP power
Power supply, type
24 V/2 A
Output
The DC/DC converter for supply from battery and DC systems;
with a wide input voltage range from 38 V to 121 V DC.
■ Technical specifications
Article number
6EP1732-0AA00
Product
SITOP power
Power supply, type
24 V/2 A
24 V
Total tolerance, static ±
1%
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
0.4 %
Residual ripple peak-peak, max.
100 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
300 mV
Adjustment range
23.5 ... 26.5 V
Product function Output voltage
adjustable
Yes
Output voltage setting
via potentiometer
Status display
Green LED for 24 V OK
On/off behavior
Overshoot of Vout on startup
max. 25 V
Startup delay, max.
3s
Voltage rise, typ.
30 ms
Rated current value Iout rated
2A
Current range
0 ... 2 A
Supplied active power typical
48 W
Parallel switching for enhanced
performance
Yes
Numbers of parallel switchable units
for enhanced performance
2
DC voltage
Efficiency at Vout rated, Iout rated,
approx.
84 %
48 ... 110 V
Power loss at Vout rated, Iout rated,
approx.
9W
Supply voltage
• at DC
Controlled, isolated DC voltage
Rated voltage Vout DC
Efficiency
Input
Input
Output
Input voltage
Closed-loop control
• at DC
38 ... 121 V
Wide-range input
Yes
Overvoltage resistance
-
Mains buffering at Iout rated, min.
5 ms; at Vin = 48 V
Input current
Dynamic mains compensation
(Vin rated ±15 %), max.
0.3 %
Dynamic load smoothing
(Iout: 50/100/50 %), Uout ± typ.
0.8 %
Load step setting time 50 to
100%, typ.
2.5 ms
2.5 ms
• at rated input voltage 48 V
1.2 A
• at rated input voltage 110 V
0.5 A
Load step setting time 100 to
50%, typ.
Switch-on current limiting (+25 °C),
max.
33 A
Protection and monitoring
Built-in incoming fuse
T 2.5 A (not accessible)
Protection in the mains power input
(IEC 898)
Recommended miniature circuit
breaker: 10 to 25 A characteristic B
or 6 to 25 A characteristic C, suitable
for DC
9
Output overvoltage protection
Yes, suppressor diode at output
Current limitation
2.1 ... 3 A
Property of the output Short-circuit
proof
Yes
Short-circuit protection
Electronic shutdown, automatic
restart
Enduring short circuit current RMS
value
• maximum
2A
Overload/short-circuit indicator
-
Siemens KT 10.1 · 2016
9/27
© Siemens AG 2016
Special designs, special uses
DC/DC converters
48-110V DC / 24 V DC/2 A
■ Technical specifications (continued)
Article number
6EP1732-0AA00
Product
SITOP power
Power supply, type
24 V/2 A
Safety
Primary/secondary isolation
Yes
Galvanic isolation
Safety extra low output voltage Vout
according to EN 60950-1
Protection class
Class I
Leakage current
• maximum
3.5 mA
• typical
0.7 mA
CE mark
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2
No. 142), File E179336
Explosion protection
-
FM approval
-
CB approval
No
Marine approval
-
Degree of protection (EN 60529)
IP20
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
not applicable
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature
• during operation
9
0 ... 70 °C
with natural convection
- Note
• during transport
-40 ... +70 °C
• during storage
-40 ... +70 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Mechanics
Connection technology
screw-type terminals
Connections
• Supply input
L+, M1, PE: 1 screw terminal each
for 2 x 0.5 ... 2.5/1.5 mm² single-core/
finely stranded
• Output
L+, M: 1 screw terminal each for
2 x 0.5 ... 2.5 mm²
• Auxiliary
-
Width of the enclosure
80 mm
Height of the enclosure
135 mm
Depth of the enclosure
120 mm
Weight, approx.
0.5 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Installation
Snaps onto DIN rail EN 60715 35x15
MTBF at 40 °C
1 580 078 h
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
9/28
Siemens KT 10.1 · 2016
■ Ordering data
SITOP power 2 A
DC/DC stabilized power supply
Input: DC 48/60/110 V
Output: 24 V DC/2 A
Article No.
6EP1732-0AA00
© Siemens AG 2016
Special designs, special uses
DC/DC converters
24 V DC / 12 V DC/2.5 A
■ Overview
■ Technical specifications
Article number
6EP1621-2BA00
Product
SITOP DC/DC
Power supply, type
12 V/2.5 A
Input
Input
DC voltage PELV/SELV
Supply voltage
• at DC
24 ... 24 V
Input voltage
• at DC
18.5 ... 30.2 V
Wide-range input
No
Input current
• at rated input voltage 24 V
2.5 A
Switch-on current limiting (+25 °C),
max.
20 A
Duration of inrush current limiting
at 25 °C
DC/DC converter for connection to 24 V DC networks. Output
voltage 12 V DC; floating, short circuit-proof, open circuit-proof.
• typical
5 ms
Built-in incoming fuse
not accessible
Protection in the mains power input
(IEC 898)
Recommended miniature circuit
breaker: 10 A characteristic B
Output
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
12 V
Total tolerance, static ±
3%
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
0.4 %
Residual ripple peak-peak, max.
100 mV
Residual ripple peak-peak, typ.
50 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
200 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
50 mV
Adjustment range
12 ... 14 V
Product function Output voltage
adjustable
Yes
Output voltage setting
via potentiometer; max. 120 W
Status display
Green LED for 12 V OK
Startup delay, max.
0.5 s
Voltage rise, typ.
300 ms
Rated current value Iout rated
2.5 A
Current range
0 ... 2.5 A
9
Short-term overload current
• on short-circuiting during the
start-up typical
3.3 A
• at short-circuit during operation
typical
3.3 A
Constant overload current
• on short-circuiting during the
start-up typical
3.3 A
• at short-circuit during operation
typical
3.3 A
Parallel switching for enhanced
performance
Yes
Numbers of parallel switchable units
for enhanced performance
2
Siemens KT 10.1 · 2016
9/29
© Siemens AG 2016
Special designs, special uses
DC/DC converters
24 V DC / 12 V DC/2.5 A
■ Technical specifications (continued)
Article number
6EP1621-2BA00
Article number
6EP1621-2BA00
Product
SITOP DC/DC
Product
SITOP DC/DC
Power supply, type
12 V/2.5 A
Power supply, type
12 V/2.5 A
• Output
+, -: 2 screw terminals each for
0.5 ... 2.5 mm²
• Auxiliary
-
Width of the enclosure
32.5 mm
Height of the enclosure
125 mm
Depth of the enclosure
125 mm
Efficiency
Efficiency at Vout rated, Iout rated,
approx.
83 %
Power loss at Vout rated, Iout rated,
approx.
6.1 W
Closed-loop control
Dynamic mains compensation
(Vin rated ±15 %), max.
0.5 %
Weight, approx.
0.32 kg
Dynamic load smoothing
(Iout: 50/100/50 %), Uout ± typ.
3%
Product feature of the enclosure
housing for side-by-side mounting
Yes
Load step setting time 50 to
100%, typ.
5 ms
Installation
Snaps onto DIN rail EN 60715
35x7.5/15
Load step setting time 100 to
50%, typ.
2 ms
MTBF at 40 °C
563 793 h
Other information
Setting time maximum
5 ms
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Protection and monitoring
Output overvoltage protection
< 24 V
Current limitation
3 ... 3.6 A
Current limitation, typ.
3.3 A
Property of the output Short-circuit
proof
Yes
Short-circuit protection
Constant current characteristic
approx. 3.2 A
Enduring short circuit current RMS
value
• typical
3.2 A
Overload/short-circuit indicator
LED red for "overload"
Safety
9
Primary/secondary isolation
Yes
Galvanic isolation
Safety extra low output voltage Vout
according to EN 60950-1
Protection class
Class II
CE mark
Yes
UL/cUL (CSA) approval
cCSAus (UL 508, CSA22.2-107,
UL60950-1, CSA22.2-60950-1)
Explosion protection
-
FM approval
-
CB approval
No
Marine approval
-
Degree of protection (EN 60529)
IP20
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
-
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature
• during operation
0 ... 60 °C
with natural convection
- Note
• during transport
-40 ... +85 °C
• during storage
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Mechanics
Connection technology
screw-type terminals
Connections
• Supply input
9/30
+, -: 1 screw terminal each for
0.5 ... 2.5 mm²
Siemens KT 10.1 · 2016
■ Ordering data
SITOP 2.5 A, DC/DC converter
Stabilized power supply
Input: 24 V DC
Output: 12 V DC/2.5 A
Article No.
6EP1621-2BA00
© Siemens AG 2016
Special designs, special uses
DC/DC converters
200-900 V DC / 24 V DC/20 A
■ Application
The SITOP PSU400M power supply with a 600 V DC input is
suitable as an efficient DC/DC converter for drive and battery
systems; large input range and temperature range, high
efficiency; slim design; with 50% extra power for 5 s/min.
■ Technical specifications
Article number
6EP1536-3AA00
Product
SITOP PSU400M
Power supply, type
24 V/20 A
Adjustment range
24 ... 28.8 V
Product function Output voltage
adjustable
Yes
Output voltage setting
via potentiometer; max. 480 W
Status display
Green LED for 24 V OK,
green flashing LED for start delay
Signaling
Relay contact (NO contact, rating
60 V DC/ 0.3 A; 30 V DC/1 A) for
24 V OK
On/off behavior
No overshoot of Vout (soft start)
Startup delay, max.
0.1 s; 10 s adjustable using switch
Voltage increase time of the output
voltage maximum
150 ms
Rated current value Iout rated
20 A
Current range
0 ... 20 A
• Note
+60 ... +70 °C: Derating 5.5%/K
Supplied active power typical
480 W
Short-term overload current
• on short-circuiting during the
start-up typical
40 A
• at short-circuit during operation
typical
60 A
Duration of overloading capability for
excess current
Article number
6EP1536-3AA00
Product
SITOP PSU400M
Power supply, type
24 V/20 A
Input
• on short-circuiting during the
start-up
150 ms
• at short-circuit during operation
25 ms
Constant overload current
DC voltage
• on short-circuiting during the startup typical
23 A
600 ... 600 V
Parallel switching for enhanced
performance
Yes; switchable characteristic
• at DC
• Note
startup from 340 V DC; derating
necessary at 300 ... 400 V DC and
824 ... 900 V DC
Numbers of parallel switchable units
for enhanced performance
2
Efficiency
300 ... 900 V
Efficiency at Vout rated, Iout rated,
approx.
95 %
• at DC
Overvoltage resistance
Shutdown at Vin > 900 V DC
Power loss at Vout rated, Iout rated,
approx.
25 W
Input
Supply voltage
Input voltage
Input current
9
Closed-loop control
• at DC at rated input voltage 600 V
0.85 A
Switch-on current limiting (+25 °C),
max.
8A
Dynamic mains compensation
(Vin rated ±15 %), max.
1.5 %
I²t, max.
0.02 A²·s
Dynamic load smoothing
(Iout: 50/100/50 %), Uout ± typ.
1.5 %
Built-in incoming fuse
yes, cut-off capacity 20 kA;
L/R < 2 ms ("+" and "-" input)
Load step setting time 50 to
100%, typ.
1 ms
Controlled, isolated DC voltage
Load step setting time 100 to
50%, typ.
1 ms
Output
Rated voltage Vout DC
24 V
Setting time maximum
5 ms
Total tolerance, static ±
3%
Protection and monitoring
Static mains compensation, approx.
0.3 %
Output overvoltage protection
< 33 V
Static load balancing, approx.
0.3 %
Current limitation, typ.
22 A
Residual ripple peak-peak, max.
150 mV
Yes
Residual ripple peak-peak, typ.
30 mV
Property of the output Short-circuit
proof
Spikes peak-peak, max.
(bandwidth: 20 MHz)
200 mV
Short-circuit protection
Alternatively, constant current
characteristic approx. 22 A or
latching shutdown
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
100 mV
Output
Enduring short circuit current RMS
value
• typical
22 A
Overcurrent overload capability in
normal operation
overload capability 150 % Iout rated
up to 5 s/min
Overload/short-circuit indicator
LED yellow for "overload", LED red
for "latching shutdown", red LED
flashing for "Overtemperature"
Siemens KT 10.1 · 2016
9/31
© Siemens AG 2016
Special designs, special uses
DC/DC converters
200-900 V DC / 24 V DC/20 A
■ Technical specifications (continued)
Article number
6EP1536-3AA00
Product
SITOP PSU400M
Power supply, type
24 V/20 A
Safety
Primary/secondary isolation
Yes
Galvanic isolation
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Protection class
Class I
CE mark
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259
Explosion protection
-
FM approval
-
CB approval
Yes
Marine approval
GL
Degree of protection (EN 60529)
IP20
EMC
Emitted interference
EN 55022 Class A (emission)
Supply harmonics limitation
-
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature
• during operation
-25 ... +70 °C
with natural convection
- Note
• during transport
-40 ... +85 °C
• during storage
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Mechanics
Connection technology
9
screw-type terminals
Connections
• Supply input
DC input, +, -, PE:
1 screw terminal each for
0.2 ... 6/4 mm² single-core/finely
stranded
• Output
+, -: 2 screw terminals each for
0.2 ... 6/4 mm² single-core/finely
stranded
• Auxiliary
Alarm signals: 2 screw terminals for
0.14 ... 1.5 mm² single-core/finely
stranded
Width of the enclosure
90 mm
Height of the enclosure
125 mm
Depth of the enclosure
125 mm
Weight, approx.
1.2 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Installation
Snaps onto DIN rail EN 60715
35x7.5/15
Mechanical accessories
Device identification label
20 mm × 7 mm, pale turquoise
3RT1900-1SB20
MTBF at 40 °C
622 277 h
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
9/32
Siemens KT 10.1 · 2016
■ Ordering data
SITOP PSU 400M 1-phase,
24 V DC/20 A
Article No.
6EP1536-3AA00
Stabilized power supply
Input: 600 V AC
Output: 24 V DC/20 A
Accessories
Device labels
3RT1900-1SB20
© Siemens AG 2016
Special designs, special uses
Special applications
1-phase, 24 V DC
■ Overview
The 24 V/5 A and 10 A power supplies in a compact metal
enclosure can be accommodated where only limited installation
depth is available. For example, in covered machine supports or
hinged frames.
■ Technical specifications
Article number
6EP1333-1AL12
6EP1334-1AL12
Product
SITOP power
SITOP power
Power supply, type
24 V/5 A
24 V/10 A
1-phase AC
1-phase AC
• 1 at AC Rated value
120 V
120 V
• 2 at AC Rated value
230 V
230 V
• Note
Set by means of selector switch on the device
Set by means of selector switch on the device
• 1 at AC
85 ... 132 V
85 ... 132 V
• 2 at AC
170 ... 264 V
170 ... 264 V
Wide-range input
No
No
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
2.3 × Vin rated, 1.3 ms
Input
Input
Supply voltage
Input voltage
9
Mains buffering at Iout rated, min.
20 ms; at Vin = 93/187 V
20 ms; at Vin = 93/187 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
• at rated input voltage 120 V
2.2 A
4A
• at rated input voltage 230 V
1.2 A
2.5 A
Switch-on current limiting (+25 °C), max.
32 A
65 A
• maximum
3 ms
3 ms
I²t, max.
0.8 A²·s
3.3 A²·s
Built-in incoming fuse
T 3,15 A/250 V (not accessible)
T 6.3 A/250 V (not accessible)
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker:
from 6 A characteristic C
Recommended miniature circuit breaker:
from 10 A characteristic C
Input current
Duration of inrush current limiting at 25 °C
Siemens KT 10.1 · 2016
9/33
© Siemens AG 2016
Special designs, special uses
Special applications
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1333-1AL12
6EP1334-1AL12
Product
SITOP power
SITOP power
Power supply, type
24 V/5 A
24 V/10 A
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
24 V
Total tolerance, static ±
1%
1%
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
0.5 %
0.5 %
Residual ripple peak-peak, max.
150 mV
150 mV
Residual ripple peak-peak, typ.
40 mV
50 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
240 mV
240 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)
100 mV
200 mV
Adjustment range
22 ... 29 V
22 ... 29 V
Product function Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
Status display
Green LED for 24 V OK
Green LED for 24 V OK
On/off behavior
No overshoot of Vout (soft start)
No overshoot of Vout (soft start)
Startup delay, max.
2s
2s
Voltage rise, typ.
40 ms
40 ms
Rated current value Iout rated
5A
10 A
Current range
0 ... 5 A
0 ... 10 A
Supplied active power typical
120 W
240 W
Output
Short-term overload current
• on short-circuiting during the start-up typical 20 A
35 A
• at short-circuit during operation typical
20 A
35 A
• on short-circuiting during the start-up
500 ms
700 ms
• at short-circuit during operation
500 ms
700 ms
Parallel switching for enhanced performance
Yes
Yes
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency at Vout rated, Iout rated, approx.
88 %
89 %
Power loss at Vout rated, Iout rated, approx.
17 W
30 W
Dynamic mains compensation
(Vin rated ±15 %), max.
0.3 %
0.3 %
Dynamic load smoothing
(Iout: 50/100/50 %), Uout ± typ.
0.5 %
0.6 %
Load step setting time 50 to 100%, typ.
0.1 ms
0.1 ms
Load step setting time 100 to 50%, typ.
0.1 ms
0.2 ms
Output overvoltage protection
Additional control loop, shutdown at approx. 33 V,
automatic restart
Additional control loop, shutdown at approx. 33 V,
automatic restart
Current limitation
5.5 ... 6.5 A
11 ... 13 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
• maximum
5A
10 A
Overload/short-circuit indicator
-
-
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Safety extra-low output voltage Uout acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
• maximum
3.5 mA
3.5 mA
• typical
0.26 mA
0.27 mA
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259
Duration of overloading capability for excess
current
9
Efficiency
Closed-loop control
Protection and monitoring
Enduring short circuit current RMS value
Safety
Leakage current
9/34
Siemens KT 10.1 · 2016
© Siemens AG 2016
Special designs, special uses
Special applications
1-phase, 24 V DC
■ Technical specifications (continued)
Article number
6EP1333-1AL12
6EP1334-1AL12
Product
SITOP power
SITOP power
Power supply, type
24 V/5 A
24 V/10 A
Explosion protection
-
-
FM approval
-
-
CB approval
No
No
Marine approval
-
-
Degree of protection (EN 60529)
IP20
IP20
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
-
-
Noise immunity
EN 61000-6-2
EN 61000-6-2
0 ... 60 °C
0 ... 60 °C
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
screw-type terminals
screw-type terminals
• Supply input
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
single-core/finely stranded
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
single-core/finely stranded
• Output
L+, M: 3 screw terminals each for 0.5 ... 2.5 mm²
L+, M: 3 screw terminals each for 0.5 ... 2.5 mm²
• Auxiliary
-
-
Width of the enclosure
160 mm
160 mm
Height of the enclosure
130 mm
130 mm
Depth of the enclosure
60 mm
60 mm
Weight, approx.
0.6 kg
0.72 kg
Product feature of the enclosure housing for
side-by-side mounting
Yes
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
Snaps onto DIN rail EN 60715 35x7.5/15
MTBF at 40 °C
1 250 000 h
1 176 471 h
Other information
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
Specifications at rated input voltage and ambient
temperature +25 °C (unless otherwise specified)
EMC
Operating data
Ambient temperature
• during operation
- Note
Mechanics
Connection technology
Connections
■ Ordering data
SITOP power 1-phase,
24 V DC/5 A
Article No.
6EP1333-1AL12
SITOP power mounting bracket
Article No.
6EP1971-1AA01
90 degree 35 mm DIN rail,
M5 fixing screws,
for Special Line flat
Special Line
stabilized power supply
Input: 120 ... 230 V AC
Output: 24 V DC/5 A
SITOP power 1-phase,
24 V DC/10 A
■ Accessories
9
6EP1334-1AL12
Special Line
Stabilized power supply
Input: 120 ... 230 V AC
Output: 24 V DC/10 A
Siemens KT 10.1 · 2016
9/35
© Siemens AG 2016
Special designs, special uses
Special applications
3-phase, 24 V DC (SITOP PSU300E)
■ Overview
Article number
6EP1433-0AA00
Product
SITOP PSU300E
Power supply, type
24 V/5 A
Output
Slimline 3-phase power supply for low power ratings
The SITOP PSU300E 3-phase power supply is designed with a
5 A output current for 24 V applications with low power requirements. The metal enclosure is only 42 mm wide and does not require any lateral gap to other devices on the DIN rail. This is
made possible by the low heat dissipation (90% efficiency). The
wide-range input from 320 V to 550 V AC permits mains buffering
times of 50 ms and thus allows the supply to be used in unstable
three-phase networks, thanks to UL certification also in North
America. The removable plug-in terminals simplify the AC and
DC connection.
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
Total tolerance, static ±
3%
Static mains compensation, approx.
3%
Static load balancing, approx.
3%
Residual ripple peak-peak, max.
150 mV
Residual ripple peak-peak, typ.
35 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
240 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
70 mV
Adjustment range
24 ... 29 V
Product function Output voltage
adjustable
Yes
Output voltage setting
via potentiometer; max. 120 W
Status display
Green LED for 24 V OK
Signaling
Relay contact (NO contact, rating
60 V DC/ 0.3 A) for "24 V OK"
On/off behavior
Overshoot of Vout approx. 3 %
Startup delay, max.
0.5 s
Voltage rise, typ.
10 ms
Voltage increase time of the output
voltage maximum
100 ms
Rated current value Iout rated
5A
Current range
0 ... 5 A
Supplied active power typical
120 W
Short-term overload current
■ Technical specifications
9
Output
• on short-circuiting during the
start-up typical
33 A
• at short-circuit during operation
typical
28 A
Article number
6EP1433-0AA00
Product
SITOP PSU300E
Power supply, type
24 V/5 A
Duration of overloading capability
for excess current
3-phase AC
• on short-circuiting during the
start-up
140 ms
Input
Rated voltage value Vin rated
400 ... 500 V
• at short-circuit during operation
135 ms
Voltage range AC
320 ... 550 V
No
Wide-range input
Yes
Parallel switching for enhanced
performance
Input
Mains buffering at Iout rated, min.
50 ms; at Vin = 400 V
Rated line frequency 1
50 Hz
Rated line frequency 2
60 Hz
Rated line range
47 ... 63 Hz
Input current
Efficiency
Efficiency at Vout rated, Iout rated,
approx.
90 %
Power loss at Vout rated, Iout rated,
approx.
13 W
Closed-loop control
• at rated input voltage 400 V
0.36 A
• at rated input voltage 500 V
0.29 A
Switch-on current limiting (+25 °C),
max.
Dynamic mains compensation
(Vin rated ±15 %), max.
3%
15 A
Dynamic load smoothing
(Iout: 50/100/50 %), Uout ± typ.
5%
I²t, max.
0.9 A²·s
1 ms
Built-in incoming fuse
none
Load step setting time 50 to
100%, typ.
Protection in the mains power input
(IEC 898)
Required: 3-pole connected
miniature circuit breaker 6 A characteristic B or C or circuit breaker
3RV2011-1DA10 (setting 3 A) or
3RV2711-1DD10 (UL 489)
Load step setting time 100 to
50%, typ.
1 ms
Dynamic load smoothing
(Iout: 10/90/10 %), Uout ± typ.
1%
Load step setting time 10 to 90%, typ. 1 ms
Load step setting time 90 to 10%, typ. 1 ms
Setting time maximum
9/36
Siemens KT 10.1 · 2016
30 ms
© Siemens AG 2016
Special designs, special uses
Special applications
3-phase, 24 V DC (SITOP PSU300E)
■ Technical specifications (continued)
Article number
6EP1433-0AA00
Product
SITOP PSU300E
Power supply, type
24 V/5 A
Protection and monitoring
Output overvoltage protection
Yes, according to EN 60950-1
Current limitation, typ.
11 A
Property of the output Short-circuit
proof
Yes
Short-circuit protection
Electronic shutdown, automatic
restart
■ Ordering data
SITOP PSU300E 3-phase,
24 V/5 A DC
Article No.
6EP1433-0AA00
Stabilized power supply
Input: 400 ... 500 V 3 AC
Output: 24 V DC/5 A
Enduring short circuit current RMS
value
• maximum
7.5 A
Safety
Primary/secondary isolation
Yes
Galvanic isolation
Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178
Protection class
Class I
CE mark
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259
Explosion protection
-
FM approval
-
CB approval
Yes
Marine approval
-
Degree of protection (EN 60529)
IP20
EMC
Emitted interference
EN 55022 Class A
Supply harmonics limitation
EN 61000-3-2
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature
• during operation
- Note
9
0 ... 60 °C
with natural convection
• during transport
-40 ... +85 °C
• during storage
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Mechanics
Connection technology
screw-type terminals
Connections
• Supply input
L1, L2, L3, PE: Removable screw
terminal for 0.5 ... 2.5 mm² singlecore/finely stranded
• Output
+, -: 2 screw terminals each for
0.5 ... 2.5 mm²
• Auxiliary
13, 14 (alarm signal): 1 screw
terminal each for 0.5 ... 2.5 mm²
Product function
• removable terminal at input
Yes
• removable terminal at output
Yes
Width of the enclosure
42 mm
Height of the enclosure
125 mm
Depth of the enclosure
125 mm
Weight, approx.
0.6 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Installation
Snaps onto DIN rail EN 60715
35x7.5/15
MTBF at 40 °C
2 389 441 h
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Siemens KT 10.1 · 2016
9/37
© Siemens AG 2016
Special designs, special uses
Notes
9
9/38
Siemens KT 10.1 · 2016
10
© Siemens AG 2016
Add-on modules
10/2
10/3
10/6
10/10
10/12
Introduction
Redundancy module
Selectivity module
Buffer module
Inrush current limiter
Siemens KT 10.1 · 2016
© Siemens AG 2016
Add-on modules
Introduction
■ Overview
Selectivity modules – for protection of 24 V feeds
Selectivity
module
PLC
HMI
Actuators Sensors
G_KT01_XX_00122
Power
supply unit
24 V DC
SITOP selectivity module
A power supply unit on its own cannot guarantee fault-free 24 V
supply. Power failures, extreme variations in the mains voltage,
or a faulty load can bring plant operation to a standstill and
cause high costs. The add-on modules offer everything from
extensive protection against interference on the primary and
secondary side right up to complete all-round protection.
Redundancy modules – for doubling system availability
Redundancy
module
24 V DC
Power
supply unit
G_KT01_XX_00121
Power
supply unit
Advantages of selectivity modules
• Reliable detection of overload or short-circuit in the 24 V
circuit
• Reliable shutdown in case of overload regardless of cable
lengths or cross-sections
• Four load feeders per module
• Versions with adjustable threshold from 0.5 to 3 A or 3 to 10 A
• Sequential connection of feeds is possible to reduce inrush
current
• Diagnostics via group signaling contact or single-channel
signaling
• Evaluation via free-of-charge SIMATIC S7 function blocks for
modules with single-channel signaling
Buffer module – bridging power failures for as long as
seconds
SITOP modular
SITOP smart
power supply
SITOP redundancy module
10
Advantages of the redundancy modules
• High availability of the 24 V supply thanks to redundant
configuration
• Power is reliably supplied even when a power supply fails
• Compact redundancy modules for power supplies up to 40 A
• Redundancy module 24 V/NEC Class 2 with limiting to 100 VA
• Diagnostic signal via LED and signaling contacts
• Adjustable switching threshold for LED and signaling contacts
Buffer
module
24 V DC
G_KT01_XX_00123
Expansion modules for increasing system availability
SITOP buffer module
Advantages of the buffer module
Power failures normally only last for fractions of a second, but
they can still cause costly and time-consuming damage in sensitive production areas. In combination with SITOP smart and
SITOP modular power supply units, the buffer module bridges
short voltage dips of this type with its electrolytic capacitors and
ensures uninterrupted operation.
■ More information
Select the appropriate power supply quickly and easily with the
SITOP Selection Tool:
http://www.siemens.com/sitop-selection-tool
10/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
Add-on modules
Redundancy module
■ Overview
■ Application
The redundancy module decouples two 24 V power supplies of
the same type so that the loads are still supplied by the second
power supply (1 + 1 redundancy) in case one of the two power
supplies fails.
Redundancy modules support parallel switching of power
supplies of the same type to increase performance while offering
redundancy at the same time (N + 1 redundancy).
You can use the NEC Class 2 redundancy module to implement
a redundant 24 V supply limited to an output power of 100 VA.
The SITOP PSE202U redundancy modules are the optimal
extension for all 24 V power supplies to ensure additional
protection from failure of the 24 V supply. The redundancy
module continuously monitors the power supply units and, in the
event that one unit fails, the other unit automatically takes over
the 24 V power supply. Additionally, a signal is sent via a
signaling contact that can be evaluated by a controller, PC, or
control system.
■ Benefits
• High availability of the 24 V supply thanks to redundant configuration
• Power is reliably supplied even when a power supply fails
• Compact redundancy modules for power supply units up to
40 A
• Redundancy module 24 V/NEC Class 2 with limiting to 100 VA
• Diagnostic signal via LED and signaling contacts
• Adjustable switching threshold for LED and signaling contacts
Redundancy
module
Power
supply unit
G_KT01_XX_00121
Power
supply unit
24 V DC
■ Design
For redundant configuration of a 24 V supply, the redundancy
module decouples two SITOP 24 V power supplies of the same
type by means of diodes in parallel operation. Depending on the
output current of the power supplies, 1 to 2 redundancy modules
may be required.
■ Function
Monitoring
The redundancy module continuously monitors the output voltage of the connected power supplies. The switching threshold
of 20 to 25 V can be set on the device. A signal indicates if the
output voltage of one of the two power supplies sinks to the set
value or below.
Signaling
The LED on the device and a changeover contact signal a faulty
power supply.
Siemens KT 10.1 · 2016
10/3
10
© Siemens AG 2016
Add-on modules
Redundancy module
■ Technical specifications
Article number
6EP1962-2BA00
6EP1964-2BA00
6EP1961-3BA21
Product
SITOP PSE202U
SITOP PSE202U
SITOP PSE202U
DC voltage
DC voltage
DC voltage
24 ... 24 V
24 ... 24 V
24 ... 24 V
19 ... 29 V
19 ... 29 V
24 ... 28.8 V
Input
Input
Supply voltage
• at DC
Input voltage
• at DC
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
24 V
24 V
Output voltage
Vin - approx. 0.5 V
Vin - approx. 0.5 V
Vin - approx. 0.5 V
Product function Output voltage
adjustable
No
No
No
Status display
Green LED for "both input voltages >
switching threshold"; red LED for
"at least one input voltage < switching
threshold" or "output switched off"
Green LED for "both Input voltages >
switching threshold"; red LED: for
"at least one input voltage < switching
threshold"
Green LED for "both Input voltages >
switching threshold"; red LED: for
"at least one input voltage < switching
threshold"
Signaling
Isolated relay contact (contact rating
6 A/42 V AC, 30 V DC, but max.
100 VA): Contact closed if one or both
input voltages < switching threshold or
output is switched off. Setting range of
switching threshold 20 V ±0.5 V to 25 V
±0.5 V
Isolated relay contact (contact rating
6 A/42 V AC, 30 V DC): Contact closed
if both input voltages > switching
threshold, setting range of switching
threshold 20 V ± 0.5V to 25 V ± 0.5V
Isolated relay contact (changeover
contacts, rating 8 A/240 V AC,
24 V DC): Signals OK if both input
voltages > switching threshold, setting
range of threshold 20 ... 25 V
Rated current value Iout rated
3.8 A
10 A
40 A
Current range
4.6 A
10 A
40 A
• Note
Maximum aggregate current in the
event of an error according to
NEC class 2 limit 8 A
max. aggregate current 10 A
max. aggregate current 40 A
Efficiency at Vout rated, Iout rated,
approx.
94.8 %
97.1 %
-
Power loss at Vout rated, Iout rated,
approx.
5W
3.6 W
-
Power loss [W] during no-load
operation maximum
2W
1W
-
Galvanic isolation
yes, SELV acc. to EN 60950-1
(relay contact)
yes, SELV acc. to EN 60950-1
(relay contact)
yes, SELV acc. to EN 60950-1
(relay contact)
Protection class
Class III
Class III
Class I
CE mark
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259; UL-Recognized (UL 60950-1, NEC class 2),
File E151273
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259
cULus-Listed (UL 508, CSA C22.2
No. 107.1), File E197259
Explosion protection
-
-
IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II
3G Ex nAC IIC T4; cCSAus (CSA
C22.2 No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD, T4
FM approval
-
-
-
CB approval
No
No
No
Marine approval
-
-
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
IP20
Emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
-20 ... +70 °C
-20 ... +70 °C
-25 ... +60 °C
with natural convection
with natural convection
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Humidity class according to
EN 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
Climate class 3K3, no condensation
Efficiency
Safety
10
EMC
Operating data
Ambient temperature
• during operation
- Note
10/4
Siemens KT 10.1 · 2016
© Siemens AG 2016
Add-on modules
Redundancy module
■ Technical specifications (continued)
Article number
6EP1962-2BA00
6EP1964-2BA00
6EP1961-3BA21
Product
SITOP PSE202U
SITOP PSE202U
SITOP PSE202U
screw-type terminals
screw-type terminals
screw-type terminals
• Supply input
Input, output and ground:
removable screw terminal,
each 1 x 0.5 ... 2.5 mm² single-core/
finely stranded
Input, output and ground:
removable screw terminal,
each 1 x 0.5 ... 2.5 mm² single-core/
finely stranded
Input, output and ground:
1 screw terminal each for
0.33 ... 10 mm² single-core/finely
stranded
• Auxiliary
Relay contact: 2 screw terminal
for 0.5 ... 2.5 mm² single-core/
finely stranded
Relay contact: 2 screw terminal
for 0.5 ... 2.5 mm² single-core/
finely stranded
Relay contact: 3 screw terminal
for 0.5 ... 2.5 mm² single-core/
finely stranded
Width of the enclosure
30 mm
30 mm
70 mm
Height of the enclosure
80 mm
80 mm
125 mm
Depth of the enclosure
100 mm
100 mm
125 mm
Weight, approx.
0.125 kg
0.125 kg
0.5 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Yes
Installation
Snaps onto DIN rail EN 60715
35x7.5/15
Snaps onto DIN rail EN 60715
35x7.5/15
Snaps onto DIN rail EN 60715
35x7.5/15
Electrical accessories
Removable spring-type terminal
6EP1971-5BA00
Removable spring-type terminal
6EP1971-5BA00
-
MTBF at 40 °C
678 210 h
3 273 000 h
6 471 654 h
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Mechanics
Connection technology
Connections
■ Ordering data
SITOP PSE202U
redundancy module
Article No.
6EP1961-3BA21
■ Accessories
Device labeling plates
Article No.
3RT1900-1SB20
Input/output: 24 V DC/40 A
suitable for decoupling two
SITOP power supplies with a
maximum of 20 A output current
SITOP PSE202U
redundancy module
6EP1962-2BA00
Input/output: 24 V DC/NEC Class 2
suitable for decoupling two
SITOP power supplies output power
limited < 100 VA
SITOP PSE202U
redundancy module
10
6EP1964-2BA00
Input/output: 24 V DC/10 A
suitable for decoupling two
SITOP power supplies with a
maximum of 5 A output current
Siemens KT 10.1 · 2016
10/5
© Siemens AG 2016
Add-on modules
Selectivity module
■ Overview
■ Application
The selectivity module is used in conjunction with 24 V power supplies to distribute the load current over several feeders and to monitor the individual currents. Faults in individual circuits caused by
overload or short-circuit are detected and selectively switched off
so that further load current paths remain unaffected by the fault.
This achieves fast fault diagnostics and minimizes downtimes.
Selectivity
module
PLC
HMI
24 V DC
Selectivity and rapid fault localization in 24 V feeders
The SITOP PSE200U and SITOP select selectivity modules are
the optimal expansion for all 24 V power supplies to distribute
the load current to several feeders and to monitor it. Overload
and short-circuit in one or more feeders is reliably detected and
signaled.
The electronics permit brief current peaks caused, for example,
by high inrush currents, but disconnects feeders in the event of
an extended overload. This is ensured even on high-resistance
lines and in the case of "creeping" short-circuits. In such cases,
miniature circuit breakers fail to trip, or trip too late, even if the
power supply unit could deliver the required tripping current.
The SITOP expansion module continues to supply the intact
feeders with 24 V absolutely free of interruptions and feedback
– a feature which avoids a possible total system failure.
■ Benefits
10
• Reliable shutdown in case of overload regardless of cable
lengths or cable cross-sections
• 4 load feeders per module with individually adjustable
response threshold for each output
• Two versions for remote diagnostics: Group signaling contact
or single-channel signaling
• Evaluation via free-of-charge SIMATIC S7 function blocks
(S7-1500/1200/300/400) for modules with single-channel
signaling (PSE200U)
• LEDs for rapid on-site fault localization
• Remote reset possible from a central location (PSE200U)
• Simple commissioning thanks to manual switch on/off of
outputs (PSE200U)
• Sequential connection of feeders to reduce total inrush current
• Sealable transparent cover over adjusters for currents and
times protects against maladjustment (PSE200U)
Actuators Sensors
G_KT01_XX_00122
Power
supply unit
■ Design
The selectivity module is specially designed for the response of
switched-mode power supply units and the 24 V DC feeders to
be supplied. Individual setting of the current allows optimum
adaptation to the respective feeder.
■ Function
Monitoring
The current per output is monitored by the selectivity modules;
if the set threshold of the output is exceeded, the output is
switched off according to a predefined time-current characteristic curve. In addition, the supplying 24 V input voltage is constantly being monitored. As soon as this voltage threatens to fail,
the path with a higher current than the set threshold is disconnected immediately. All other feeders continue to be supplied
without interruption.
Signaling
Signaling of the faulty feeder takes place by the LEDs on the
device as well as via group signaling contact or single-channel
signaling. The selectivity module with single-channel signaling
outputs the status of the 4 outputs cyclically by means of a serial
code which can be read in by a digital PLC input.
Free function blocks for SIMATIC S7-300/400/1200/1500 for
STEP 7 and TIA Portal as well as SIMOTION CPUs with
SIMOTION SCOUT are available for evaluation. This enables
simple integration into the S7 diagnostics and host control or
HMI systems.
More information, as well as the function blocks for download,
can be found at:
SIMATIC S7:
http://support.automation.siemens.com/WW/view/en/61450284
SIMOTION:
http://support.automation.siemens.com/WW/view/en/82555461
Connection and disconnection of the outputs
During device startup you can select between simultaneous
connection of all outputs as well as sequential connection or
load-dependent connection of the outputs (to reduce the peak
inrush currents).
Each output can be manually connected and disconnected on
the device (for example, for commissioning or service). Disconnected outputs can be connected by means of remote reset
(24 V input). Prerequisite is that the outputs were not disconnected manually on the device.
10/6
Siemens KT 10.1 · 2016
© Siemens AG 2016
Add-on modules
Selectivity module
■ Technical specifications
Article number
6EP1961-2BA11
6EP1961-2BA31
6EP1961-2BA21
6EP1961-2BA41
6EP1961-2BA00
Product brand name
SITOP PSE200U
SITOP PSE200U
SITOP PSE200U
SITOP PSE200U
SITOP select
Type of current supply
Selectivity module,
4 x 3 A Common
signal contact
Selectivity module,
4 x 3 A Singlechannel signaling
Selectivity module,
4 x 10 A Common
signal contact
Selectivity module,
4 x 10 A Singlechannel signaling
Diagnosis module,
4 x 10 A
Input
Input
Controlled DC voltage Controlled DC voltage Controlled DC voltage Controlled DC voltage Controlled DC voltage
(SITOP select is not
designed for operation
with DC UPS module
40 A (6EP1 931-2FC21/
-2FC42)
Supply voltage at DC Rated value
24 V
24 V
24 V
24 V
24 V
Input voltage at DC
22 ... 30 V
22 ... 30 V
22 ... 30 V
22 ... 30 V
22 ... 30 V
Overvoltage resistance
35 V
35 V
35 V
35 V
35 V; 100 ms
Input current
12 A
12 A
40 A
40 A
40 A
Output
Output
controlled DC voltage
controlled DC voltage
controlled DC voltage
controlled DC voltage
controlled DC voltage
Output voltage
Vin - approx. 0.2 V
Vin - approx. 0.2 V
Vin - approx. 0.2 V
Vin - approx. 0.2 V
Vin - approx. 0.3 V
Overall tolerance
In accordance with the In accordance with the In accordance with the In accordance with the In accordance with the
supplying input
supplying input
supplying input
supplying input
supplying input
voltage
voltage
voltage
voltage
voltage
Number of outputs
4
Output current up to 60 °C per output 3 A
4
4
4
4
3A
10 A
10 A
10 A
Adjustable pick-up value current of
the current-dependent overload
release
0.5 ... 3 A
0.5 ... 3 A
3 ... 10 A
3 ... 10 A
2 ... 10 A
Type of response value setting
via potentiometer
via potentiometer
via potentiometer
via potentiometer
via potentiometer
Product feature parallel switching of
outputs
No
No
No
No
No
Product feature bridging of
equipments
Yes
Yes
Yes
Yes
Yes
Type of outputs connection
Simultaneous
connection of all
outputs after power up
of the supply voltage
> 20 V, delay time of
25 ms, 100 ms or
adjustable "load
optimised" via DIP
switch for sequential
connection
Simultaneous
connection of all
outputs after power up
of the supply voltage
> 20 V, delay time of
25 ms, 100 ms or
adjustable "load
optimised" via DIP
switch for sequential
connection
Simultaneous
connection of all
outputs after power up
of the supply voltage
> 20 V, delay time of
25 ms, 100 ms or
adjustable "load
optimised" via DIP
switch for sequential
connection
Simultaneous
connection of all
outputs after power up
of the supply voltage
> 20 V, delay time of
25 ms, 100 ms or
adjustable "load
optimised" via DIP
switch for sequential
connection
Simultaneous
connection of all
outputs after power up
of the supply voltage,
delay time of 24 ms or
100 ms programmable for sequential
connection
Efficiency in percent
97 %
97 %
99 %
99 %
97 %
Power loss at rated output current
typical
9W
9W
10 W
10 W
30 W
• of the excess current
Iout = 1.0 ...1.5 x set
value, switch-off after
approx. 5 s
Iout = 1.0 ...1.5 x set
value, switch-off after
approx. 5 s
Iout = 1.0 ...1.5 x set
value, switch-off after
approx. 5 s
Iout = 1.0 ...1.5 x set
value, switch-off after
approx. 5 s
Iout = 1.0 ...1.3 x set
value, switch-off after
approx. 5 s
• of the current limitation
Iout = 1.5 x set value,
switch-off not before
typ. 100 ms
Iout = 1.5 x set value,
switch-off not before
typ. 100 ms
Iout = 1.5 x set value,
switch-off not before
typ. 100 ms
Iout = 1.5 x set value,
switch-off not before
typ. 100 ms
Iout = 1.3 x set value,
switch-off after approx.
50 ... 100 ms
• of the immediate switch-off
Iout > set value and
Vin < 20 V, switch-off
after approx. 0.5 ms
Iout> set value and
Vin < 20 V, switch-off
after approx. 0.5 ms
Iout > set value and
Vin < 20 V, switch-off
after approx. 0.5 ms
Iout > set value and
Vin < 20 V, switch-off
after approx. 0.5 ms
Iout > set value and
Vin < 20 V, switch-off
after approx. 0.5 ms
Design of the reset device/resetting
mechanism
via sensor per output
via sensor per output
via sensor per output
via sensor per output
Remote reset
Non-electrically
isolated 24 V input
(signal level "high" at >
15 V)
Non-electrically
isolated 24 V input
(signal level "high" at >
15 V)
Non-electrically
isolated 24 V input
(signal level "high" at >
15 V)
Non-electrically
isolated 24 V input
(signal level "high" at >
15 V)
Efficiency
Switch-off characteristic per output
Switching characteristic
20 mA
Residual current at switch-off typical
Using keys on the
module
Siemens KT 10.1 · 2016
10/7
10
© Siemens AG 2016
Add-on modules
Selectivity module
■ Technical specifications (continued)
Article number
6EP1961-2BA11
6EP1961-2BA31
6EP1961-2BA21
6EP1961-2BA41
6EP1961-2BA00
Product brand name
SITOP PSE200U
SITOP PSE200U
SITOP PSE200U
SITOP PSE200U
SITOP select
Type of current supply
Selectivity module,
4 x 3 A Common
signal contact
Selectivity module,
4 x 3 A Singlechannel signaling
Selectivity module,
4 x 10 A Common
signal contact
Selectivity module,
4 x 10 A Singlechannel signaling
Diagnosis module,
4 x 10 A
Built-in fuse
5 A per output
(not accessible)
5 A per output
(not accessible)
15 A per output
(not accessible)
15 A per output
(not accessible)
Blade-type fuse per
output (equipped
when delivered with
15 A fuse)
Status display
Three-color LED per
output: green LED for
"Output switched
through"; yellow LED
for "Output switched
off manually"; red LED
for "Output switched
off due to overcurrent"
Three-color LED per
output: green LED for
"Output switched
through"; yellow LED
for "Output switched
off manually"; red LED
for "Output switched
off due to overcurrent"
Three-color LED per
output: green LED for
"Output switched
through"; yellow LED
for "Output switched
off manually"; red LED
for "Output switched
off due to overcurrent"
Three-color LED per
output: green LED for
"Output switched
through"; yellow LED
for "Output switched
off manually"; red LED
for "Output switched
off due to overcurrent"
Two-color LED per
output: green LED for
"Output switched
through"; red LED for
"Output switched off
due to overcurrent"
Signaling contact
Common signal
contact (changeover
contact, rating 0.1 A/
24 V DC)
Status signal output
(pulse/pause signal,
can be evaluated via
SIMATIC function
block)
Common signal
contact (changeover
contact, rating 0.1 A/
24 V DC)
Status signal output
(pulse/pause signal,
can be evaluated via
SIMATIC function
block)
Common signal
contact (NO contact,
rating 0.5 A/24 V DC)
Galvanic isolation between input and No
output at switch-off
No
No
No
No
Protection class
Class III
Class III
Class III
Class III
Class III
CE marking
Yes
Yes
Yes
Yes
Yes
UL/cUL (CSA) approval
UL-Recognized (UL
2367) File E328600;
cULus-Listed (UL 508,
CSA C22.2 No. 107.1)
File E197259
UL-Recognized (UL
2367) File E328600;
cULus-Listed (UL 508,
CSA C22.2 No. 107.1)
File E197259
UL-Recognized (UL
2367) File E328600;
cULus-Listed (UL 508,
CSA C22.2 No. 107.1)
File E197259
UL-Recognized (UL
2367) File E328600;
cULus-Listed (UL 508,
CSA C22.2 No. 107.1)
File E197259
UL-Recognized (UL
2367) File E328600;
cULus-Listed (UL 508,
CSA C22.2 No. 107.1)
File E197259; cURus
(UL 60950, CSA C22.2
No. 60950) File
E151273
Standard for safety
according to
EN 60950-1 and
EN 50178
according to
EN 60950-1 and
EN 50178
according to
EN 60950-1 and
EN 50178
according to
EN 60950-1 and
EN 50178
according to
EN 60950-1 and
EN 50178
Explosion protection
IECEx Ex nA nC IIC T4
Gc; ATEX (EX) II 3G Ex
nA nC IIC T4 Gc;
cCSAus Class I, Div. 2,
Group ABCD, T4
IECEx Ex nA IIC T4
Gc; ATEX (EX) II 3G Ex
nA IIC T4 Gc; cCSAus
Class I, Div. 2, Group
ABCD, T4
IECEx Ex nA nC IIC T4
Gc; ATEX (EX) II 3G Ex
nA nC IIC T4 Gc;
cCSAus Class I, Div. 2,
Group ABCD, T4
IECEx Ex nA IIC T4
Gc; ATEX (EX) II 3G Ex
nA IIC T4 Gc; cCSAus
Class I, Div. 2, Group
ABCD, T4
ATEX (EX) II 3G Ex
nAC IIC T4 U; cCSAus
Class I, Div. 2, Group
ABCD, T4
Shipbuilding approval
GL, ABS
GL, ABS
GL, ABS
GL, ABS
-
Protection class (EN 60529)
IP20
IP20
IP20
IP20
IP20
Emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
Noise immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
0 ... 60 °C
0 ... 60 °C
0 ... 60 °C
0 ... 60 °C
0 ... 60 °C
Protection and monitoring
Safety
10
EMC
Operating data
Ambient temperature
• during operation
with natural convection with natural convection with natural convection with natural convection with natural convection
- Note
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Environmental category acc. to
IEC 60721
Climate class 3K3,
no condensation
Climate class 3K3,
no condensation
Climate class 3K3,
no condensation
Climate class 3K3,
no condensation
Climate class 3K3,
no condensation
10/8
Siemens KT 10.1 · 2016
© Siemens AG 2016
Add-on modules
Selectivity module
■ Technical specifications (continued)
Article number
6EP1961-2BA11
6EP1961-2BA31
6EP1961-2BA21
6EP1961-2BA41
6EP1961-2BA00
Product brand name
SITOP PSE200U
SITOP PSE200U
SITOP PSE200U
SITOP PSE200U
SITOP select
Type of current supply
Selectivity module,
4 x 3 A Common
signal contact
Selectivity module,
4 x 3 A Singlechannel signaling
Selectivity module,
4 x 10 A Common
signal contact
Selectivity module,
4 x 10 A Singlechannel signaling
Diagnosis module,
4 x 10 A
Mechanics
Type of electrical connection
screw-type terminals
screw-type terminals
screw-type terminals
screw-type terminals
screw-type terminals
• at input
+24 V: 2 screw
terminals for
0.5 ... 10 mm²;
0 V: 2 screw terminals
for 0.5 ... 4 mm²
+24 V: 2 screw
terminals for
0.5 ... 10 mm²;
0 V: 2 screw terminals
for 0.5 ... 4 mm²
+24 V: 2 screw
terminals for
0.5 ... 10 mm²;
0 V: 2 screw terminals
for 0.5 ... 4 mm²
+24 V: 2 screw
terminals for
0.5 ... 10 mm²;
0 V: 2 screw terminals
for 0.5 ... 4 mm²
+24 V: 2 screw
terminals for
0.33 ... 10 mm²;
0 V: 2 screw terminals
for 0.22 ... 4 mm²
• at output
Output 1 ... 4: 1 screw Output 1 ... 4: 1 screw Output 1 ... 4: 1 screw Output 1 ... 4: 1 screw Output 1 ... 4: 1 screw
terminal each for
terminal each for
terminal each for
terminal each for
terminal each for
0.5 ... 4 mm²
0.5 ... 4 mm²
0.5 ... 4 mm²
0.5 ... 4 mm²
0.22 ... 4 mm²
• for signaling contact
3 screw terminals for
0.5 ... 4 mm²
1 screw terminals for
0.5 ... 4 mm²
3 screw terminals for
0.5 ... 4 mm²
1 screw terminals for
0.5 ... 4 mm²
2 screw terminals for
0.22 ... 4 mm²
• for auxiliary contacts
Remote reset:
1 screw terminal for
0.5 ... 4 mm²
Remote reset:
1 screw terminal for
0.5 ... 4 mm²
Remote reset:
1 screw terminal for
0.5 ... 4 mm²
Remote reset:
1 screw terminal for
0.5 ... 4 mm²
-
Width of the enclosure
72 mm
72 mm
72 mm
72 mm
72 mm
Height of the enclosure
80 mm
80 mm
80 mm
80 mm
90 mm
Depth of the enclosure
72 mm
72 mm
72 mm
72 mm
90 mm
Installation width
72 mm
72 mm
72 mm
72 mm
72 mm
Mounting height
180 mm
180 mm
180 mm
180 mm
190 mm
Net weight
0.2 kg
0.2 kg
0.2 kg
0.2 kg
0.4 kg
Mounting type
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Product component belonging to
-
-
-
-
4x blade-type fuse
15 A
Mechanical accessories
Device identification
label 20 mm × 7 mm,
pale turquoise
3RT1900-1SB20
Device identification
label 20 mm × 7 mm,
pale turquoise
3RT1900-1SB20
Device identification
label 20 mm × 7 mm,
pale turquoise
3RT1900-1SB20
Device identification
label 20 mm × 7 mm,
pale turquoise
3RT1900-1SB20
-
MTBF at 40 °C
755 915 h
755 915 h
540 979 h
540 979 h
378 928 h
Other information
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
■ Ordering data
Article No.
SITOP PSE200U 3 A
4-channel selectivity module
Input: 24 V AC
Output: 24 V DC/3A per channel
output current adjustable 0.5 ... 3 A
• With common alarm signal
• With single-channel signaling
■ Accessories
Device labels
Article No.
3RT1900-1SB20
6EP1961-2BA11
6EP1961-2BA31
SITOP PSE200U 10 A
4-channel selectivity module
Input: 24 V AC
Output: 24 V DC/10 A per channel
output current adjustable 3 ... 10 A
• With common alarm signal
• With single-channel signaling
6EP1961-2BA21
6EP1961-2BA41
SITOP select
6EP1961-2BA00
4-channel
Input: 24 V DC
Output: 24 V DC/10 A per channel
Adjustable output current 2 ... 10 A
Siemens KT 10.1 · 2016
10/9
10
© Siemens AG 2016
Add-on modules
Buffer module
■ Overview
■ Application
With short-term power failures, the load current is backed up
without interruption via the buffer module in combination with a
SITOP smart or SITOP modular 24 V stabilized power supply.
Buffer times:
• 200 ms at 40 A
• 400 ms at 20 A
• 800 ms at 10 A
You can connect up to 8 buffer modules in parallel to extend the
buffer time (max. 10 s).
The SITOP PSE201U buffer module bypasses short-term power
failures lasting a few seconds and can be used with all 24 V
power supplies of the SITOP smart or SITOP modular product
lines. The buffer module is equipped with maintenance-free
capacitors and automatically takes over the 24 V power supply
in case of a power supply failure.
The SITOP DC UPS modules offer protection in the event of
extended power failures. The maintenance-free DC UPS with
capacitors are able to reliably supply 24 V for several minutes,
and the DC UPS with battery modules for several hours.
■ Benefits
10
Buffer
module
24 V DC
■ Design
The buffer module is connected in parallel to the output of the
SITOP smart or SITOP modular power supply. The connection to
the power supply takes place via only 2 cables.
■ Function
• Bridging of short-term power failures in the time range of
seconds
• Totally maintenance-free capacitors as energy storage
• Short charging times
• Parallel switching of several buffer modules possible
• Fast mounting onto standard rail and simple wiring
Buffering
In case of a power failure, the buffer module supplies the load
current for the 24 V power supply by means of its energy storage
units. Maintenance-free capacitors are used as energy storage
units.
Signaling
The LED on the device signals a supply voltage > 20.5 V.
10/10
G_KT01_XX_00123
SITOP modular
SITOP smart
power supply
Siemens KT 10.1 · 2016
© Siemens AG 2016
Add-on modules
Buffer module
■ Technical specifications
Article No.
■ Ordering data
6EP1961-3BA01
SITOP PSE201U buffer module
SITOP PSE201U buffer module
Input/Output
Stabilized, isolated
DC voltage
For SITOP smart and
SITOP modular
buffer time 100 ms to 10 s
dependent on load current
Rated voltage Uin rated
24 V DC
Accessories
Voltage range
24 ... 28.8 V
Device labeling plates
Control input
-
Rated output voltage Uout rated
Uin – approx. 1 V
Rated current Iout rated
40 A
Mains buffering
Backup time:
• With 40 A load current: 200 ms
• With 20 A load current: 400 ms
• With 10 A load current: 800 ms
• With 5 A load current: 1.6 s
Article No.
6EP1961-3BA01
3RT1900-1SB20
Reduces the backup time by 100 ms
in combination with 6EP1 437-3BA10.
Buffering time, max.
10 s
Protection and monitoring
Current limiting, static
Typ. 40 A
Short-circuit protection
Electronically
Signaling/alarm signals
Status display
Green LED for
"Supply voltage > 20.5 V"
Signaling
-
Safety
Galvanic isolation
Yes, SELV acc. to EN 60950-1
Safety class
Class I
Safety test
Yes
CE marking
Yes
UL/cUL (CSA) approval
UL-Listed (UL 508) File E197259,
CSA (CSA C22.2 No. 14,
CSA C22.2 No. 107.1)
Explosion protection
-
Degree of protection (EN 60529)
IP20
10
EMC
Emitted interference
EN 55022 Class B
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature range
0 ... +60 °C with natural convection
Transport and storage temperature
range
-40 ... +85°C
Humidity class
Climate class 3K3 according to
EN 60721, no condensation
Mechanics
Connections
One screw-type terminal each for
+ and - for 0.5 ... 10 mm2
solid/finely stranded
Dimensions (W x H x D) in mm
70 x 125 x 125
Weight, approx.
1.2 kg
Mounting
Can be snapped onto standard
mounting rail EN 60715 35x7.5/15
Siemens KT 10.1 · 2016
10/11
© Siemens AG 2016
Add-on modules
Inrush current limiter
■ Overview
■ Technical specifications
Article number
6EP1967-2AA00
Input
AC voltage 1-phase, 2-phase,
50/60 Hz
Rated voltage Uin rated
100 ... 480 V AC
Voltage range
85 ... 575 V AC
Output
Rated voltage Uout rated
In accordance with the supply
voltage
Rated current Iout rated
Max. 10 A
Parallel switching for enhanced
performance
No
Protection and monitoring
Current limiting, static
-
Short-circuit protection
Must be ensured with an upstream
protective device
Signaling/alarm signals
The SITOP inrush current limiter is used to reliably reduce the
starting currents that are caused, for example, by transformers
or with pulse-controlled power supplies by the rectifier circuit on
the input side with capacitor charging.
In 1-phase AC networks, it is supplied with rated voltages of
100 V, 120 V or 230 V and in 2-phase and 3-phase AC networks
with rated voltages of 208 V to 480 V on the line side upstream
of transformers or power supplies and it limits the inrush current
independent of temperature, for example, up to 10 A at 230 V by
means of an installed fixed resistor. In static operation, the limit
resistance is bypassed after approx. 120 ms to reduce the
power losses generated.
Status display
Green LED
Alarm signals
-
Safety
In accordance with EN 60950-1 and
EN 50178
Galvanic isolation
No
Safety class
Class II
CE marking
Yes
UL/cUL (CSA) approval
Yes, cULus-listed (UL 508, CSA
C22.2 No. 107.1), File E197259
Degree of protection (EN 60529)
IP20
EMC
Emitted interference
EN 61000-6-3
Noise immunity
EN 61000-6-2
Operating data
10
Ambient temperature range
0 ... +60 °C with natural convection
Transport and storage temperature
range
-40 ... +85 °C
Humidity class
Climate class 3K3 according to
EN 60721, no condensation
Mechanics
Connections
Input and output (L1, N): One screw
terminal each for 0.2 ... 2.5 mm2,
solid/finely stranded
Dimensions (W x H x D) in mm
22.5 x 80 x 91
Weight, approx.
0.12 kg
Mounting
Can be snapped onto standard
mounting rail EN 60715 35x7.5/15
■ Ordering data
SITOP making current limiter
Ballast for SITOP power supplies
Input:
100 … 480 V AC, 10 A max
Output:
100 … 480 V AC, 10 A max
10/12
Siemens KT 10.1 · 2016
Article No.
6EP1967-2AA00
11
© Siemens AG 2016
SITOP DC UPS 
uninterruptible power supplies
11/2
Introduction
11/3
DC UPS with capacitors
11/10
11/10
11/18
11/22
11/28
DC UPS with battery modules
SITOP UPS1600 DC UPS modules
SITOP UPS1100 battery modules
SITOP DC UPS
DC UPS battery modules
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
Introduction
■ Overview
SITOP offers a comprehensive portfolio to protect against power
failures with durations from a few seconds to several hours,
ranging from buffer modules to system-integrated DC UPS units.
Selection is based on the energy storage unit used, the associated ambient conditions, performance and functionality.
The selection matrix should help you to find the right 24 V buffering for your application:
Buffer module 1)
UPS500
UPS1600
DC UPS
24 V buffering up to
10 s
Minutes
Hours
Hours
Storage medium
Electrolytic capacitors
Double-layer capacitors
Lead-gel batteries,
rechargeable lithium iron
phosphate batteries
Lead-gel batteries
… +50 °C: > 8 years
+20 … +40 °C:
4 ... 1 years
(high-temperature
rechargeable battery:
+20 …+60 °C:
> 10 ... 1 years)
+20 … +40 °C:
4 ... 1 years
(high-temperature
rechargeable battery:
+20 … +60 °C:
> 10 ... 1 years)
SITOP modules for 24 V buffering
Energy storage units
0 … +50 °C: > 8 years
Lifetime dependent on temperature.
The specified time refers to a fall to 50 %
of the original capacity in the case of lead
batteries and 80 % in the case of capacitors.
Temperature range
0 … +60 °C
0 … +60 °C
0 … +40 °C
(high-temperature
rechargeable battery:
-40°…+60°C)
0 … +40 °C
(high-temperature
rechargeable battery:
-40°…+60°C)
Ventilation required
-
-
•
•
Degree of protection
IP20
IP20/ IP65 (UPS500P)
IP00
IP00
Degree of protection
IP20
IP20/ IP65 (UPS500P)
IP20
IP20
Max. rated output current
40 A
15 A
40 A
40 A
Max. dynamic overload current
40 A (200 ms)
25 A (200 ms)
120 A (30 ms) / 60 A
(5 s/min)
56 A (80 ms)
Interfaces
-
I/O, USB
I/O, USB,
Ethernet/ PROFINET
I/O, serial, USB
Information about operation and
diagnostics via
• Signaling contact
• OPC servers
• Web server
• S7 function blocks
• WinCC faceplate
-
•
•
-
•
•
•
•
•
•
•
-
Shutdown of multiple PCs/ PLCs
-
-
•
-
Starting from the battery, without supply
voltage (stand-alone mode)
-
-
•
-
-
•
-
•
•
•
-
UPS module/electronics
11
Engineering via
• Software tool (PC)
• TIA Portal
1)
for SITOP smart and SITOP modular power supply units
■ More information
The SITOP Selection Tool offers detailed selection guidance
according to criteria such as the required backup time, nominal
current or peak current:
http://www.siemens.com/sitop-selection-tool
11/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with capacitors
Power supply
SITOP
SITOP
UPS500S
24 V DC unbuffered
SITOP
UPS501S
Industrial PC
24 V DC buffered
HMI
SITOP 24V power supplies can be expanded with a SITOP
UPS500 uninterruptible DC power supply (DC UPS) for bridging
short-term power failures in the order of minutes. For PC-based
automation solutions, the high-capacity double-layer capacitors
of the SITOP UPS500 supply enough energy to back up the
operation and application data and to shut down software applications in a defined manner. You can increase the buffer times
using SITOP PSU501S expansion modules (up to 3).
The IP65 version SITOP UPS500P in long metal housing is
ideally suited to distributed use.
■ Benefits
• 24 V buffering for a few minutes to allow data to be backed up
and applications to be closed.
• Absolutely maintenance-free
• Long lifetime, even at high temperatures
• High ambient temperatures up to +60 °C
• Short charging times
• No ventilation is required since no gas is emitted
• Distributed applications possible without control cabinet
• Software tool, free of charge, for easy configuring and
integrating in PC-based systems
Actuators
(e.g. motor
controls
and valves)
Distributed
I/O with
sensors
Indicator
light
G_KT01_XX_00758
■ Overview
Configuration with SITOP UPS500S:
24 V buffering for backing up process data and performing a controlled
shutdown of a PC. To relieve the load on the UPS, the actuators are
supplied directly from the power supply unit.
■ Design
SITOP UPS500S
• Compact 24 V/ 15 A basic units with integrated energy
storage units of 2.5 or 5 kW
• Digital inputs/outputs and USB interface
• For combination with up to three UPS501S expansion modules
(5 kW each) to extend the buffering time
• Metal housing in IP20 degree of protection for mounting on
standard rails
■ Application
The high-capacitance double-layer capacitors bridge power
failures for a few minutes. The time is normally sufficient, for example, for the safe shutdown of PC-based automation systems.
The USB interface and a free software tool enable easy communication with the PC.
The capacitors have an extremely long life even at high temperature, and can be used at ambient temperatures of up to 60 °C.
SITOP UPS500P in IP65 degree of protection can also be installed outside the control cabinet in a distributed configuration.
11
SITOP UPS501S expansion module
• Additional energy storage (5 kW)
• Up to 3 expansion modules can be connected to a
SITOP UPS500S to extend the buffer times
• Can be easily connected to SITOP UPS500S via a
user-friendly plug-in system
• Complete with balancing and safety circuits
SITOP UPS500P
• 24 V/ 7 A basic units with integrated energy storage units of
5 or 10 kW
• USB interface
• Rugged aluminum housing in IP65 degree of protection for
distributed applications
• Screw mounting in all mounting positions
Siemens KT 10.1 · 2016
11/3
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with capacitors
■ Function
SITOP DC UPS software tool
Via the USB interface, all relevant messages about the status of
the uninterruptible DC power supply can be transmitted to a PC
(e.g. SIMATIC IPC). The DC UPS can also be configured via the
USB interface.
The SITOP DC UPS software provides the user with a free tool
that is extremely easy to use for the purpose of monitoring and
configuring the DC UPS. Signals sent from the uninterruptible
DC power supply can be processed on the PC. In monitoring
mode, the statuses of the uninterruptible DC power supply are
visualized on the PC.
Safe shutdown in the event of a power failure and automatic
PC restart are supported. It is also possible to freely define
responses to the different operating states of the uninterruptible
DC power supply, so that extremely flexible integration into a
wide variety of applications is possible.
Overview of configuration possibilities:
• Times for shutting down the PC
• UPS switch-off
• Further processing of all signals, e.g. linking to proprietary
software or WinCC flexible
• Monitoring and display of UPS operating status
• OPC server for linking signals to proprietary applications
• Automatic restarting of IPCs when power is restored during
shutdown
The software runs under the operating systems Windows 2000,
Windows XP, Windows Vista and Windows 7. Free download
from:
http://support.automation.siemens.com/WW/view/en/48946053
11
11/4
Siemens KT 10.1 · 2016
Monitoring and configuration window of software V3 for SITOP DC UPS
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with capacitors
■ Technical specifications
The UPS500S can be extended to 20 kW using UPS501S expansion modules to extend the buffering time.
The table shows the maximum buffering time for the possible
configurations and the two UPS500P units for different load
currents.
The charging current can be set to 1 A or 2 A with the UPS500S.
Selection table SITOP UPS500 (optional with SITOP UPS501S expansion module) and mains buffering times
Buffering and charging times
SITOP UPS500S/501S configurations
UPS500P
Basic unit
2.5 kW
5 kW
2.5 kW
5 kW
2.5 kW
5 kW
2.5 kW
5 kW
5 kW
10 kW
Expansion
modules
-
-
1 × 5 KWs
1 × 5 KWs
2 × 5 KWs
2 × 5 KWs
3 × 5 KWs
3 × 5 KWs
-
-
Total energy
2.5 kW
5 kW
7.5 kW
10 kW
12.5 kW
15 kW
17.5 kW
20 kW
5 kW
10 kW
Load current Buffer times
0.5 A
134 s
236 s
390 s
478 s
632 s
748 s
851 s
1007 s
284 s
647 s
0.8 A
90 s
167 s
266 s
346 s
440 s
527 s
580 s
706 s
190 s
435 s
1A
75 s
138 s
219 s
296 s
365 s
414 s
490 s
572 s
153 s
351 s
2A
38 s
76 s
122 s
156 s
203 s
230 s
265 s
306 s
80 s
152 s
3A
26 s
52 s
82 s
106 s
136 s
159 s
186 s
213 s
53 s
108 s
4A
19 s
39 s
61 s
81 s
101 s
120 s
139 s
160 s
40 s
84 s
5A
15 s
31 s
49 s
65 s
81 s
95 s
111 s
130 s
30 s
68 s
6A
12 s
26 s
40 s
55 s
67 s
80 s
94 s
106 s
25 s
57 s
7A
10 s
21 s
34 s
47 s
58 s
69 s
81 s
82 s
21 s
49 s
8A
8s
18 s
29 s
40 s
50 s
59 s
69 s
79 s
-
-
10 A
6s
15 s
23 s
32 s
39 s
47 s
54 s
62 s
-
-
12 A
4s
12 s
19 s
26 s
32 s
38 s
44 s
52 s
-
-
15 A
3s
9s
14 s
20 s
25 s
30 s
35 s
40 s
-
-
Charing
current
Charging times
2A
54 s
120 s
158 s
223 s
263 s
318 s
355 s
417 s
130 s
360 s
1A
110 s
205 s
311 s
425 s
503 s
625 s
695 s
816 s
-
-
Important information for selecting the energy storage units:
When the mains buffering times were determined, the discharge
period of new or non-aged, completely charged capacitors was
used as a basis.
At a continuous ambient temperature of +50 °C, a loss of capacity of approx. 20% must be considered after a service life of
8 years.
11
Siemens KT 10.1 · 2016
11/5
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with capacitors
■ Technical specifications (continued)
Article number
6EP1933-2EC41
6EP1933-2EC51
6EP1933-2NC01
6EP1933-2NC11
Product brand name
SITOP UPS500S
SITOP UPS500S
SITOP UPS500P
SITOP UPS500P
Type of current supply
Basic unit 2.5 kWs
Basic unit 5 kWs
Basic unit 5 kWs
Basic unit 10 kWs
Input
Supply voltage at DC Rated value 24 V
24 V
24 V
24 V
Voltage curve at input
DC
DC
DC
DC
input voltage range
22 ... 29 V DC
22 ... 29 V DC
22.5 ... 29 V DC
22.5 ... 29 V DC
Adjustable response value
voltage for buffer connection
preset
22.5 V
22.5 V
22.5 V
22.5 V
Adjustable response value
voltage for buffer connection
22 ... 25.5 V; Adjustable in
0.5 V increments
22 ... 25.5 V; Adjustable in
0.5 V increments
-
-
Input current at rated input
voltage 24 V Rated value
15.2 A; + approx. 2.3 A
with empty energy storage
(capacitor)
15.2 A; + approx. 2.3 A
with empty energy storage
(capacitor)
7 A; + approx. 2 A
with empty energy storage
(capacitor)
7 A; + approx. 2 A
with empty energy storage
(capacitor)
Type of energy storage
with capacitors
with capacitors
with capacitors
with capacitors
Design of the mains power cut
bridging-connection
15 A for 3 s or 10 A for 6 s
or 5 A for 15 s
or 2 A for 38 s; longer
buffering times with
expansion modules
15 A for 9 s or 10 A for 15 s
or 5 A for 31 s
or 2 A for 76 s; longer
buffering times with
expansion modules
7 A for 49 s or 5 A for 68 s
or 3 A for 108 s
or 1 A for 351 s
7 A for 49 s or 5 A for 68 s
or 3 A for 108 s
or 1 A for 351 s
5 kW.s
5 kW.s
10 kW.s
Mains buffering
Energy content of energy storage 2.5 kW.s
Charging current
•1
1A
1A
2A
2A
•2
2A
2A
-
-
adjustable charging current
maximum Note
factory setting approx. 1 A
factory setting approx. 1 A
permanently set
permanently set
• in normal operation at DC
Rated value
24 V
24 V
24 V
24 V
• in buffering mode at DC
Rated value
24 V
24 V
24 V
24 V
Formula for output voltage
24 V ± 3 %
24 V ± 3 %
24 V ± 3 %
24 V ± 3 %
ON-delay time typical
0.6 s
0.6 s
0.6 s
0.6 s
Voltage increase time of the
output voltage typical
25 ms
25 ms
25 ms
25 ms
24 ... 24.7 V
24 ... 24.7 V
24 ... 24.7 V
Output
Output voltage
Output voltage in buffering mode 24 ... 24.7 V
at DC
Output current
11
• Rated value
15 A
15 A
7A
7A
• in normal operation
0 ... 15 A
0 ... 15 A
0 ... 7 A
0 ... 7 A
• in buffering mode
0 ... 15 A
0 ... 15 A
0 ... 7 A
0 ... 7 A
Peak current
25 A
25 A
22.5 A
22.5 A
Supplied active power typical
360 W
360 W
168 W
168 W
• at rated output current at rated 97.5 %
output current typical
97.5 %
96.5 %
96.5 %
9W
5.2 W
5.2 W
Efficiency
Efficiency in percent
Power loss [W]
• at rated output current at rated 9 W
output current typical
Protection and monitoring
Product function
• reverse polarity protection
against energy storage unit
polarity reversal
Yes
Yes
Yes
Yes
• reverse polarity protection
against input voltage polarity
reversal
Yes
Yes
Yes
Yes
11/6
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with capacitors
■ Technical specifications (continued)
Article number
6EP1933-2EC41
6EP1933-2EC51
6EP1933-2NC01
6EP1933-2NC11
Product brand name
SITOP UPS500S
SITOP UPS500S
SITOP UPS500P
SITOP UPS500P
Type of current supply
Basic unit 2.5 kWs
Basic unit 5 kWs
Basic unit 5 kWs
Basic unit 10 kWs
• for normal operation
Normal operation:
LED green (OK), floating
changeover contact "OK/Bat"
to setting "OK" ("OK" means:
Voltage of the supplying
power supply unit is greater
than cut-in threshold set at the
DC UPS module); lack of
buffer standby: LED red
(ALARM), floating
changeover contact
"ALARM/BAT" to setting
"ALARM"; energy storage
> 85%: LED green
(BAT > 85%), floating NO
contact "BAT > 85" closed;
permissible contact current
capacity: DC 60 V/1 A or
AC 30 V /1 A
Normal operation:
LED green (OK), floating
changeover contact "OK/Bat"
to setting "OK" ("OK" means:
Voltage of the supplying
power supply unit is greater
than cut-in threshold set at the
DC UPS module); lack of
buffer standby: LED red
(ALARM), floating
changeover contact
"ALARM/BAT" to setting
"ALARM"; energy storage
> 85%: LED green
(BAT > 85%), floating NO
contact "BAT > 85" closed;
permissible contact current
capacity: DC 60 V/1 A or
AC 30 V /1 A
Normal operation:
LED green (OK);
Lack of buffer standby:
LED red (ALARM);
Energy storage > 85%:
LED green (CAP. > 85%)
Normal operation:
LED green (OK);
Lack of buffer standby:
LED red (ALARM);
Energy storage > 85%:
LED green (CAP. > 85%)
• in buffering mode
Buffered mode: LED yellow
(BAT), floating changeover
contact "OK/BAT" to setting
"BAT"; Prewarning buffer
end after expiry of 80% of the
available buffer time:
LED red (ALARM),
floating changeover contact
"ALARM/BAT" to setting
"ALARM"; Energy storage
> 85%: LED green
(BAT > 85%), floating NO
contact "BAT > 85" closed
Buffered mode: LED yellow
(BAT), floating changeover
contact "OK/BAT" to setting
"BAT"; Prewarning buffer end
after expiry of 80% of the
available buffer time:
LED red (ALARM),
floating changeover contact
"ALARM/BAT" to setting
"ALARM"; Energy storage
> 85%: LED green
(BAT > 85%), floating NO
contact "BAT > 85" closed
Buffered mode: LED yellow
(BAT); Prewarning buffer end
after expiry of 80% of the
available buffer time:
LED red (ALARM);
Energy storage > 85%:
LED green (CAP. > 85%)
Buffered mode: LED yellow
(BAT); Prewarning buffer end
after expiry of 80% of the
available buffer time:
LED red (ALARM);
Energy storage > 85%:
LED green (CAP. > 85%)
Signaling
Display version
Interface
Product component PC interface Yes
Yes
Yes
Yes
USB
USB
USB
USB
Galvanic isolation between
entrance and outlet
No
No
No
No
Operating resource protection
class
Class III
Class III
Class III
Class III
• CE marking
Yes
Yes
Yes
Yes
• as approval for USA
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259
-
-
• relating to ATEX
-
-
-
-
• C-Tick
Yes
Yes
No
No
Shipbuilding approval
GL, ABS
GL, ABS
-
-
Protection class IP
IP20
IP20
IP65
IP65
• for emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
• for interference immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
• during operation
0 ... 60 °C;
with natural convection
0 ... 60 °C;
with natural convection
0 ... 55 °C;
with natural convection
0 ... 55 °C;
with natural convection
• during transport
-40 ... +70 °C
-40 ... +70 °C
-40 ... +70 °C
-40 ... +70 °C
• during storage
-40 ... +70 °C
-40 ... +70 °C
-40 ... +70 °C
-40 ... +70 °C
Environmental category acc. to
IEC 60721
Climate class 3K3,
no condensation
Climate class 3K3,
no condensation
Climate class 3K3,
no condensation
Climate class 3K3,
no condensation
Type of electrical connection
screw-type terminals
screw-type terminals
Plug-in connection
Plug-in connection
• at input
24 V DC: 2 screw terminals
for 1 ... 4 mm²/17 ... 11 AWG
24 V DC: 2 screw terminals
for 1 ... 4 mm²/17 ... 11 AWG
via connector set
via connector set
• at output
24 V DC: 4 screw terminals
for 1 ... 4 mm²/17 ... 11 AWG
24 V DC: 4 screw terminals
for 1 ... 4 mm²/17 ... 11 AWG
via connector set
via connector set
Design of the interface
Safety
Certificate of suitability
11
EMC
Standard
Operating data
Ambient temperature
Mechanics
Siemens KT 10.1 · 2016
11/7
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with capacitors
■ Technical specifications (continued)
Article number
6EP1933-2EC41
6EP1933-2EC51
6EP1933-2NC01
6EP1933-2NC11
Product brand name
SITOP UPS500S
SITOP UPS500S
SITOP UPS500P
SITOP UPS500P
Type of current supply
Basic unit 2.5 kWs
Basic unit 5 kWs
Basic unit 5 kWs
Basic unit 10 kWs
• for battery module
-
-
-
-
• for control circuit and status
message
10 screw terminals for
10 screw terminals for
0.5 ... 2.5 mm²/20 ... 13 AWG 0.5 ... 2.5 mm²/20 ... 13 AWG
-
Width of the enclosure
120 mm
120 mm
400 mm
470 mm
Height of the enclosure
125 mm
125 mm
80 mm
80 mm
Depth of the enclosure
125 mm
125 mm
80 mm
80 mm
• top
50 mm
50 mm
-
-
• bottom
50 mm
50 mm
-
-
• left
0 mm
0 mm
0 mm
0 mm
• right
0 mm
0 mm
0 mm
0 mm
Net weight
1 kg
1 kg
1.9 kg
2.2 kg
Product feature of the enclosure
housing
for side-by-side mounting
Yes
Yes
No
No
Mounting type
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Screw mounting
Screw mounting
Electrical accessories
Extension module
SITOP UPS501S
Extension module
SITOP UPS501S
Connector set
Connector set
MTBF at 40 °C
638 570 h
459 137 h
8 760 h
8 760 h
Equipment marking acc. to
DIN EN 81346-2
T
T
T
T
Other information
Specifications at rated input
voltage and ambient
temperature +25 °C
(unless otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C
(unless otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C
(unless otherwise specified)
Specifications at rated input
voltage and ambient
temperature +25 °C
(unless otherwise specified)
Mechanics (continued)
Required spacing
Article number
6EP1935-5PG01
Article number
6EP1935-5PG01
Product brand name
SITOP UPS501
Product brand name
SITOP UPS501
Type of current supply
Extension module
Type of current supply
Extension module
Input
Mechanics
Voltage curve at input
DC
Mains buffering
Type of energy storage
with capacitors
Energy content of energy storage
5 kW.s
Signaling
11
Display version
• for normal operation
-
Interface
Product component PC interface
No
Design of the interface
without
Safety
Operating resource protection class
Class III
Certificate of suitability
• CE marking
Yes
• as approval for USA
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259
Type of electrical connection
screw-type terminals
• at output
can be connected to SITOP
UPS500S via a plug-in system
• for control circuit and status
message
-
Width of the enclosure
70 mm
Height of the enclosure
125 mm
Depth of the enclosure
125 mm
Required spacing
• top
50 mm
• bottom
50 mm
• left
0 mm
• right
0 mm
Net weight
0.7 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Mounting type
Snaps onto DIN rail
EN 60715 35x7.5/15
MTBF at 40 °C
7 142 857 h
T
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
• relating to ATEX
-
• C-Tick
Yes
Shipbuilding approval
GL, ABS
Equipment marking acc. to DIN EN
81346-2
Protection class IP
IP20
Other information
Operating data
Ambient temperature
• during operation
0 ... 60 °C;
with natural convection
• during transport
-40 ... +70 °C
• during storage
-40 ... +70 °C
Environmental category
acc. to IEC 60721
Climate class 3K3, no condensation
11/8
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with capacitors
■ Ordering data
Article No.
SITOP UPS500S
DC UPS basic device 15 A
• with USB interface and 2.5 kW
• with USB interface and 5 kW
6EP1933-2EC41
6EP1933-2EC51
■ More information
The SITOP Selection Tool offers detailed selection guidance
according to criteria such as the required backup time, nominal
current or peak current. Available at:
http://www.siemens.com/sitop-selection-tool
SITOP UPS501S
Expansion module 5 kW for
UPS500S
6EP1935-5PG01
SITOP UPS500P
DC UPS basic device 7 A
• with USB interface and 5 kW
• with USB interface and 10 kW
■ Accessories
Connector set for UPS500P
6EP1933-2NC01
6EP1933-2NC11
Article No.
6EP1975-2ES00
consisting of connector for input
and output with pre-assembled
USB cable (2 m long)
11
Siemens KT 10.1 · 2016
11/9
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1600 DC UPS modules
■ Overview
■ Benefits
By combining one DC UPS module SITOP UPS1600 with at least
one UPS1100 battery module and a SITOP power supply unit,
longer power failures can be bridged without any interruption.
The intelligent battery management automatically detects the
UPS1100 energy storage unit, ensures optimized temperaturespecific charging and continuous monitoring. The compact
DC UPS modules have overload capability, for example, to
supply the inrush current of industrial PCs. In stand-alone mode,
they support starting from the battery.
The DC UPS communicates openly over a USB or Ethernet/
PROFINET port. It is easily integrated into the PC or PLC environment over the two Ethernet/PROFINET ports. Total integration in
TIA provides user-friendly engineering in the TIA Portal and is
supported with ready-to-use function blocks for S7 user programs and WinCC faceplates for fast visualization.
SITOP UPS Manager supports easy monitoring and configuration in PC systems, e.g. shutdown of several PCs in accordance
with the master-slave principle. The integrated web server
supports remote monitoring of the DC UPS.
11
11/10
Siemens KT 10.1 · 2016
• 24 V buffering for a few hours for the purpose of continuing
processes
• Open communication over USB or two Ethernet/PROFINET
ports
• High-performance DC UPS modules in space-saving,
slim design
• High overload capability for mains and buffering operation
• Starting from the battery module supports stand-alone mode,
e.g. for starting generators
• Easy configuration thanks to automatic detection of battery
modules
• High reliability and availability due to monitoring of the operational readiness, battery feeder, aging and charging status
• Battery protecting charging due to temperature-specific
charging characteristic
• Defined shutdown of several PCs or controllers on one UPS
(versions with Ethernet/PROFINET)
• Remote monitoring via integrated web server
(versions with Ethernet/PROFINET)
• Time-saving engineering in PC-based systems via SITOP UPS
Manager (versions with USB or Ethernet/PROFINET)
• SITOP UPS Manager with OPC UA server facilitates flexible,
multi-vendor communication with other systems
• Full integration in TIA saves time and costs during the
planning stage and in operation (versions with Ethernet/
PROFINET)
• User-friendly engineering in the TIA Portal
• SIMATIC S7 function blocks for easy integration in STEP 7 user
programs
• Fast integration in operator control and monitoring with WinCC
faceplates
• Direct integration in SIMATIC PCS 7 via SITOP library
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1600 DC UPS modules
■ Application
The battery modules that can be connected in parallel bridge
power failures for a few hours. This supports the continued
operation of processes or parts of them. The function "Starting
from the battery" means that the UPS1600 can also be used in
stand-alone mode without connection to the supply.
Depending on the communication requirements between the
DC UPS and the automation components to be protected
against power failure, the version of UPS1600 can be selected
accordingly.
Buffering of simple automation applications
In simple applications with mini PLCs (e.g. obstruction lights,
stand-alone hydro-electric plants), 24 V buffering is performed
by the UPS1600 without a communications interface. The status
messages are transferred to the PLC via the digital outputs
(isolated).
Communication over Ethernet/PROFINET offers the most
comprehensive possibilities for diagnostics and system
integration. The UPS1600 can be directly integrated into the
LAN infrastructure over its two ports.
Buffering of applications with networked
(Industrial Ethernet) automation computers
The UPS1600 with Industrial Ethernet interface protects complex
PC-based applications from power failure. Configuration and
monitoring is performed using the PC software SITOP UPS
Manager. It also supports defined shutdown of several PCs in
accordance with the master-slave principle.
Control
Industrial PC
Controlling, configurating, monitoring
Industrial PC
PC
Controlling
LOGO!
SIMATIC S7-1200
Industrial Ethernet
24 V DC
Energy Storage Link
24 V DC
Power
supply
SITOP
PM1207
SITOP
UPS1600
SITOP
UPS1100
Uninterruptible 24 V power supply
G_KT01_XX_00802
Energy Storage Link
Buffering of applications with automation computer
The UPS1600 with a USB interface is used to buffer automation
solutions that are controlled by an industrial PC. All operating
and configuring data is communicated over the PC interface.
Controlling, configurating, monitoring
Power
supply
SITOP
SITOP
UPS1600
SITOP
UPS1100
G_KT01_XX_00796
5
Uninterruptible 24 V power supply
Buffering of applications with networked (PROFINET)
automation components
For buffering sensitive plant components (e.g. a pumping station
with telecontrol) or complete controller solutions (e.g. machine
tools) that are integrated into a networked automation solution,
the UPS1600 with PROFINET is the perfect choice. Total integration in TIA offers unique advantages for engineering and operation (e.g. diagnostics or visualization). For example, in buffer
mode, several controllers can be brought to a defined independently of each other.
11
Industrial PC
Control
Human Machine Interface
Engineering
SIMATIC S7300/400/
1200/1500,
STEP 7
Panel PC/ PC PC WinCC,
SIMATIC HMI, SCADA
WinCC
system
PG/ PC, TIA Portal,
Step 7
24 V DC
USB
SITOP
UPS1600
Uninterruptible 24 V power supply
SITOP
UPS1100
PROFINET
24 V DC
Energy Storage Link
Power
supply
SITOP
SITOP
UPS1600
SITOP
UPS1100
Uninterruptible 24 V power supply
Siemens KT 10.1 · 2016
G_KT01_XX_00797
Power
supply
SITOP
G_KT01_XX_00803
Energy Storage Link
11/11
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1600 DC UPS modules
■ Design
SITOP UPS1600 software
Software tools support convenient integration of the SITOP
UPS1600 in both PC-based and PLC-based systems. They
make configuring and visualizing the DC UPS easier and the
user benefits from the high performance of the SITOP UPS1600.
Software for open, PC-based automation systems
SITOP UPS Manager
• Compact DC UPS modules UPS1600 24 V/10 A, 20A and
40 A with digital inputs and outputs, optionally with USB
interface or two Ethernet/PROFINET ports
• UPS1100 battery modules 1.2 Ah, 3.2 Ah, 7 Ah and 12 Ah with
lead rechargeable batteries, UPS1100 2.5 Ah battery module
with pure-lead rechargeable batteries and UPS1100 5 Ah
battery module with lithium-ion technology.
■ Function
SITOP UPS1600 web server
The SITOP UPS1600 with Ethernet/PROFINET has an integrated
web server that supports remote monitoring and control of the
uninterruptible power supply. Using HTTPS ensures encrypted
and safe data transmission.
Configuration and monitoring is performed easily using the free
PC software SITOP UPS Manager. It enables the reactions of the
PC to the operating states of the DC UPS to be freely selected and
offers comprehensive diagnostic options:
• Configuration
- Connection via USB or Ethernet
- All the relevant parameters can be configured in UPS
Manager and transferred to the UPS1600
- Configuration of "non-coded" rechargeable batteries is
possible
- The reactions of the PC to the operating states of the UPS can
be freely selected, e.g. termination of software applications
- Support for reliable downloading of several PCs according to
the master-slave principle
- The configurations can be saved locally
- Integrated OPC UA server
- Updating of the UPS1600 firmware is possible
- Assignment of IP addresses and device names of the
UPS1600
- Can run under Windows XP, Windows 7 (32-bit and 64-bit)
operating systems
• Monitoring
- Readout and display of alarms, statuses and operating variables of the UPS1600 and the connected energy storage unit
- Tracing of history in trend diagrams
Remote monitoring and control of:
• Hardware configuration data
• Remote monitoring
• Operating data of the UPS1600 basic unit and the
connected UPS1100 battery module
• Alarm messages
11
Remote access via:
• Firefox 34 or higher, or Internet Explorer 10, 11
(IE 8 with charging of SVG player)
• IP address
• Password
Monitor window for battery status in SITOP UPS Manager
The password-protected web server supports viewing of the configuring
and operating data.
Trend diagram for load current in SITOP UPS Manager
11/12
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1600 DC UPS modules
■ Function (continued)
Software for TIA-based automation systems
Faceplates for WinCC
For convenient integration of the DC UPS in the TIA environment,
different software modules are available.
Ready-to-use faceplates save programming time for visualization of the uninterruptible power supply. The faceplates show all
relevant statuses and values of the DC UPS. They are available
for the following systems:
• Faceplates for WinCC V7.2
• Faceplates for WinCC flexible 2008 SP3
• Faceplates for WinCC Comfort/Advanced/Professional V12
Engineering is simple via the TIA Portal. The data for UPS1600
is stored in the hardware catalog version V14 and higher. Special
function blocks for SIMATIC S7-300, S7-400, S7-1200 and
S7-1500 also support integration in the STEP 7 user program.
The comprehensive diagnostics data of the UPS1600 power
supply can be visualized using prepared UPS faceplates for
WinCC.
Free download:
http://support.automation.siemens.com/WW/view/en/75854608
TIA Portal
• Convenient and fail-safe integration of SITOP UPS1600 in the
PROFINET network by means of drag-and-drop
• Convenient configuration of SITOP UPS1600 basic units with
Ethernet/PROFINET and the UPS1100 battery module simply
by selecting from the TIA Portal hardware catalog
• Free download of HSP (Hardware Support Package) for TIA
Portal version V12 SP1 or higher available at
http://support.automation.siemens.com/WW/view/en/75854606
• Free GSD file (Generic Station Description) for STEP 7 V 5.5
http://support.automation.siemens.com/WW/view/en/75854605
The pre-compiled WinCC faceplates show all the relevant UPS data in
a clearly comprehensible display. An icon with color coding for the
operating state is also available
Software for SIMATIC PCS 7 process control system
Establishing the PROFINET connection between the SITOP UPS1600
and the controller is easy and fail-safe in the TIA Portal
STEP 7 function blocks
Function blocks are available for STEP 7 user programs on
SIMATIC S7-300/400/1200/1500. They allow further processing
of the DC UPS operating data.
• Function blocks for STEP 7 V5.5
• Function blocks from STEP 7 V12 and higher
Free download:
http://support.automation.siemens.com/WW/view/en/75854608
The SITOP library is available with blocks and faceplates for
direct integration into SIMATIC PCS 7. The SW blocks in the
SIMATIC S7 supply the faceplate on the user interface of the
process control system with operating and diagnostics data,
generate messages and ensure connection to the maintenance
system of PCS 7. This means that PCS 7 users automatically
receive information about operating state conditions, maintenance requirements (e.g. battery replacement) and disturbances (e.g. power failures). This ensures constant transparency of the 24V supply in the control system. The SITOP library
supports the following SIMATIC PCS 7 versions:
• SIMATIC PCS 7 V8.0 with SP2
• SIMATIC PCS 7 V8.1
• SIMATIC PCS7 V8.1 with SP1
• SIMATIC PCS7 V8.2 available soon
Free download at:
https://support.industry.siemens.com/cs/ww/en/view/109476154
Siemens KT 10.1 · 2016
11/13
11
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1600 DC UPS modules
■ Technical specifications
The table shows the maximum buffering times for the SITOP
UPS1100 battery modules for different load currents:
Product brand
name
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
Type of power
supply
24 V/1.2 Ah
24 V/2.5 Ah
high temperature
24 V/3.2 Ah
24 V/5 Ah LiFePo
24 V/7 Ah
24 V/12 Ah
Article No.
6EP4131-0GB00-0AY0 6EP4132-GB00-0AY0
Load current
Buffer times
6EP4133-0GB00-0AY0 6EP4133-0JB00-0AY0 6EP4134-0GB00-0AY0 6EP4135-0GB00-0AY0
1A
34 min
1.7 h
2.5 h
5.2 h
5.4 h
10.3 h
2A
15 min
54.6 min
1h
2.5 h
2.6 h
4.8 h
3A
9 min
32.9 min
39 min
1.7 h
1.6 h
3h
4A
6 min
20.6 min
27 min
1.25 h
1.2 h
2.3 h
6A
3.5 min
14.3 min
17.5 min
50.6 min
41 min
1.4 h
8A
2 min
10.5 min
12 min
37.8 min
28 min
1h
10 A
1 min
7.2 min
9 min
30.2 min
22 min
48.6 min
12 A
-
6 min
7 min
25.1 min
17 min
40.3 min
14 A
-
4.5 min
5 min
21.6 min
15 min
33.6 min
16 A
-
4.1 min
4 min
18.8 min
12.5 min
26 min
20 A
-
2.9 min
1 min
12.9 min
9.1 min
19.6 min
30 A
-
-
-
-
4.6 min
12.1 min
40 A
-
-
-
-
2.8 min
8.5 min
Important information for selecting the battery capacity:
Determination of the mains buffering times is based on the discharge period of new or non-aged, completely charged battery
modules at a battery temperature not below +25 °C to the shutdown of the DC UPS.
Battery aging reduces the still available battery capacity up until
the end of the service life to typically around 50% of the original
capacity value when new (1.2 Ah/3.2 Ah/7 Ah, etc.) and the internal resistance increases. When the message "Battery charge
> 85%" appears, only around 50% x 85% = approx. 43% of the
originally available capacity can be assumed at the end of the
battery service life.
11
The SITOP Selection Tool offers detailed selection guidance
according to criteria such as the required backup time, load
current, peak current and battery connection threshold:
http://www.siemens.com/sitop-selection-tool
At battery temperatures below +25 °C, the available capacity
drops approximately by another 30% at +5 °C battery temperature, to approximately 70% of the approximately remaining 43%.
There is then only around 30% of the original capacity available.
A significantly larger battery capacity must therefore be selected
when configuring the plant: A drop to approx. 50% is compensated for by selecting 1 / approx. 0.5 = approx. double the
battery capacity (required as per the table for the relevant load
current and the relevant buffering time). Available capacity of
approx. 43% is compensated for by selecting 1 / approx.
0.43 = approx. 2.33 times the battery capacity. Available capacity of approx. 30% is compensated for by selecting 1 / approx.
0.3 = approx. 3.33 times the battery capacity.
Recommendation:
Instead of installing double the battery capacity, regular battery
replacement halfway through the expected service life (reduction of capacity to approx. 50%) can be more advisable for the
following reasons: Capacity does not drop below 100% until the
halfway point of the expected battery life (or slightly beyond).
With regular replacement after this point, only the single battery
capacity (instead of double capacity) must be installed due to
aging (-> neutral in price with regard to battery module costs,
but only requires half the space).
11/14
Siemens KT 10.1 · 2016
Replacing the battery after half its service life dispenses above
all with the large scatter range of the residual capacity at the end
of the service life, which is not accurately defined by battery
manufacturers (after the full time, many batteries are above, but
many are also below the average 50% residual capacity, that is
to say, even if double the capacity is installed, the influence of
aging at the end of service life is not reliably compensated for,
rather only typically) -> When replacing after half the expected
service life, the configured buffering time is maintained with
considerably greater reliability.
In the case of batteries stored in cool conditions (not above
+25 °C) and for not longer than approximately 4 months, the
following service life can be assumed, strongly dependent on
battery temperature:
Battery
temperature
Drop to approx.
50% of residual
capacity
Recommendation: Replace
(at 100% of
residual
capacity) all
+20 °C
4 years
2 years
+30 °C
2 years
1 year
+40 °C
1 year
0.5 years
Alternative
recommendation
Install double
capacity and
replace
(1 x per year)
In normal cases (installation in the coolest location in the control
cabinet at approx. +30 °C), the battery should be replaced with
single installed battery capacity in accordance with the selection
table after 1 year of operation!
After a power failure, the battery module is disconnected from
the loads at the end of the selected buffering time either automatically or electronically by opening the On/Off control circuit,
and as soon as the 24 V input voltage is available again, it is
quickly re-charged with the charge current of the relevant DC
UPS module (with I-U charge characteristic: First constant
current I for fast charging, and changeover to constant voltage
U to maintain the charge when the battery is almost full).
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1600 DC UPS modules
■ Technical specifications (continued)
Article number
6EP4134-3AB00-0AY0
6EP4136-3AB00-0AY0
6EP4137-3AB00-0AY0
6EP4134-3AB00-1AY0
6EP4136-3AB00-1AY0
6EP4137-3AB00-1AY0
6EP4134-3AB00-2AY0
6EP4136-3AB00-2AY0
6EP4137-3AB00-2AY0
Product brand name
SITOP UPS1600
SITOP UPS1600
SITOP UPS1600
Type of current supply
DC UPS 24 V/10 A
DC UPS 24 V/20 A
DC UPS 24 V/40 A
Input
Supply voltage at DC Rated value
24 V
24 V
24 V
Voltage curve at input
DC
DC
DC
input voltage range
22 ... 29 V DC
22 ... 29 V DC
22 ... 29 V DC
Adjustable response value voltage
for buffer connection preset
22.5 V
22.5 V
22.5 V
Adjustable response value voltage
for buffer connection
21 ... 25 V; Adjustable: 21 V, 21.5 V,
22 V, 22.5 V, 23 V, 24 V, 25 V DC
or via software
21 ... 25 V; Adjustable: 21 V, 21.5 V,
22 V, 22.5 V, 23 V, 24 V, 25 V DC
or via software
21 ... 25 V; Adjustable: 21 V, 21.5 V,
22 V, 22.5 V, 23 V, 24 V, 25 V DC
or via software
Input current at rated input voltage
24 V Rated value
14 A; for max. charging current (3 A)
25 A; for max. charging current (4 A)
46 A; for max. charging current (5 A)
Type of energy storage
with batteries
with batteries
with batteries
Design of the mains power cut
bridging-connection
Adjustable range using rotary coding
switch: 0.5 min, 1 min, 2 min, 5 min,
10 min, 20 min, max. buffering time
or via software
Adjustable range using rotary coding
switch: 0.5 min, 1 min, 2 min, 5 min,
10 min, 20 min, max. buffering time
or via software
Adjustable range using rotary coding
switch: 0.5 min, 1 min, 2 min, 5 min,
10 min, 20 min, max. buffering time
or via software
•1
0.1 A
0.1 A
0.1 A
•2
3A
4A
5A
Automatically depending on battery
module
Automatically depending on battery
module
24 V
24 V
24 V
• in buffering mode at DC Rated value 24 V
Mains buffering
Charging current
adjustable charging current maximum Automatically depending on battery
module
Note
Output
Output voltage
• in normal operation at DC Rated
value
24 V
24 V
Formula for output voltage
Vin - approx. 0.01 x I
Vin - approx. 0.01 x I
Vin - approx. 0.01 x I
ON-delay time typical
60 s
60 s
60 s
Voltage increase time of the output
voltage typical
60 ms
60 ms
60 ms
Output voltage in buffering mode
at DC
19 ... 28.5 V
19 ... 28.5 V
19 ... 28.5 V
Output current
• Rated value
10 A
20 A
40 A
• in normal operation
0 ... 30 A
0 ... 60 A
0 ... 120 A
• in buffering mode
0 ... 30 A
0 ... 60 A
0 ... 120 A
Peak current
30 A
60 A
120 A
Property of the output Short-circuit
proof
Yes
Yes
Yes
Design of short-circuit protection
Limitation to 3 x I rated for 30 ms/min;
through-conductivity for 1.5 x I rated
for 5 sec/min
Limitation to 3 x I rated for 30 ms/min;
through-conductivity for 1.5 x I rated
for 5 sec/min
Limitation to 3 x I rated for 30 ms/min;
through-conductivity for 1.5 x I rated
for 5 sec/min
Supplied active power typical
240 W
480 W
960 W
• at rated output current at rated
output current typical
97.7 %
98.2 %
98.8 %
• in case of accumulator operation
typical
97.7 %
98.2 %
98.8 %
• at rated output current at rated
output current typical
5.6 W
8.6 W
12 W
• in case of accumulator operation
typical
5.6 W
8.6 W
12 W
11
Efficiency
Efficiency in percent
Power loss [W]
Siemens KT 10.1 · 2016
11/15
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1600 DC UPS modules
■ Technical specifications (continued)
Article number
6EP4134-3AB00-0AY0
6EP4136-3AB00-0AY0
6EP4137-3AB00-0AY0
6EP4134-3AB00-1AY0
6EP4136-3AB00-1AY0
6EP4137-3AB00-1AY0
6EP4134-3AB00-2AY0
6EP4136-3AB00-2AY0
6EP4137-3AB00-2AY0
Product brand name
SITOP UPS1600
SITOP UPS1600
SITOP UPS1600
Type of current supply
DC UPS 24 V/10 A
DC UPS 24 V/20 A
DC UPS 24 V/40 A
• reverse polarity protection against Yes
energy storage unit polarity reversal
Yes
Yes
• reverse polarity protection against
input voltage polarity reversal
Yes
Yes
Yes
• for normal operation
Normal operation: LED green (OK),
floating changeover contact "Bat/OK"
to setting "OK" ("OK" means: Voltage
of the supplying power supply unit is
greater than cut-in threshold set at the
DC UPS module); Lack of buffer
standby: LED red (alarm), floating
changeover contact "Alarm/Bat" to
setting "Alarm"; Battery replacement
required: LED red (alarm) flashing with
approx. 0.25 Hz, floating changeover
contact "Alarm/Bat" switching with
approx. 0.25 Hz; Energy storage
> 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed;
Permissible contact current capacity:
DC 60 V/1 A or AC 30 V /1 A
Normal operation: LED green (OK),
floating changeover contact "Bat/OK"
to setting "OK" ("OK" means: Voltage
of the supplying power supply unit is
greater than cut-in threshold set at the
DC UPS module); Lack of buffer
standby: LED red (alarm), floating
changeover contact "Alarm/Bat" to
setting "Alarm"; Battery replacement
required: LED red (alarm) flashing with
approx. 0.25 Hz, floating changeover
contact "Alarm/Bat" switching with
approx. 0.25 Hz; Energy storage
> 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed;
Permissible contact current capacity:
DC 60 V/1 A or AC 30 V /1 A
Normal operation: LED green (OK),
floating changeover contact "Bat/OK"
to setting "OK" ("OK" means: Voltage
of the supplying power supply unit is
greater than cut-in threshold set at the
DC UPS module); Lack of buffer
standby: LED red (alarm), floating
changeover contact "Alarm/Bat" to
setting "Alarm"; Battery replacement
required: LED red (alarm) flashing with
approx. 0.25 Hz, floating changeover
contact "Alarm/Bat" switching with
approx. 0.25 Hz; Energy storage
> 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed;
Permissible contact current capacity:
DC 60 V/1 A or AC 30 V /1 A
• in buffering mode
Buffered mode: LED yellow (Bat),
floating changeover contact "OK/Bat"
to setting "Bat"; Prewarning battery
voltage < 20.4 VDC: LED red (alarm),
floating changeover contact "Alarm/
Bat" to setting "Alarm"; Energy storage
> 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed
Buffered mode: LED yellow (Bat),
floating changeover contact "OK/Bat"
to setting "Bat"; Prewarning battery
voltage < 20.4 VDC: LED red (alarm),
floating changeover contact "Alarm/
Bat" to setting "Alarm"; Energy storage
> 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed
Buffered mode: LED yellow (Bat),
floating changeover contact "OK/Bat"
to setting "Bat"; Prewarning battery
voltage < 20.4 VDC: LED red (alarm),
floating changeover contact "Alarm/
Bat" to setting "Alarm"; Energy storage
> 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed
Product component PC interface
No
No
Yes
Design of the interface
without
without
without
Galvanic isolation between entrance
and outlet
No
No
No
Operating resource protection class
Class III
Class III
Class III
Protection and monitoring
Product function
Signaling
Display version
Interface
Safety
11
Certificate of suitability
• CE marking
Yes
Yes
Yes
• as approval for USA
cULus-Listed (UL 508,
CSA C22.2 No. 107.1), File E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1), File E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1), File E197259
• relating to ATEX
IECEx Ex nA nC IIC T4 Gc; cCSAus
(CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2013) Class I,
Div. 2, Group ABCD, T4
IECEx Ex nA nC IIC T4 Gc; cCSAus
(CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2013) Class I,
Div. 2, Group ABCD, T4
IECEx Ex nA nC IIC T4 Gc; cCSAus
(CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2013) Class I,
Div. 2, Group ABCD, T4
• C-Tick
Yes
Yes
Yes
Type of certification CB-certificate
Yes
Yes
Yes
Shipbuilding approval
GL, ABS
GL, ABS
GL, ABS
Protection class IP
IP20
IP20
IP20
• for emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
• for interference immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
• during operation
-25 ... +70 °C;
with natural convection
-25 ... +70 °C;
with natural convection
-25 ... +70 °C;
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Environmental category acc. to
IEC 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
Climate class 3K3, no condensation
EMC
Standard
Operating data
Ambient temperature
11/16
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1600 DC UPS modules
■ Ordering data Article No. (continued)
Article number
6EP4134-3AB00-0AY0
6EP4136-3AB00-0AY0
6EP4137-3AB00-0AY0
6EP4134-3AB00-1AY0
6EP4136-3AB00-1AY0
6EP4137-3AB00-1AY0
6EP4134-3AB00-2AY0
6EP4136-3AB00-2AY0
6EP4137-3AB00-2AY0
Product brand name
SITOP UPS1600
SITOP UPS1600
SITOP UPS1600
Type of current supply
DC UPS 24 V/10 A
DC UPS 24 V/20 A
DC UPS 24 V/40 A
Mechanics
Type of electrical connection
screw-type terminals
screw-type terminals
screw-type terminals
• at input
24 V DC: 2 screw terminals for
0.2 ... 6 mm²/24 ... 13 AWG
24 V DC: 2 screw terminals for
0.2 ... 6 mm²/24 ... 13 AWG
24 V DC: 2 screw terminals for
0.5 ... 16 mm²/20 ... 6 AWG
• at output
24 V DC: 2 screw terminals for
0.2 ... 6 mm²/24 ... 13 AWG
24 V DC: 2 screw terminals for
0.2 ... 6 mm²/24 ... 13 AWG
24 V DC: 2 screw terminals for
0.5 ... 16 mm²/20 ... 6 AWG
• for battery module
24 V DC: 2 screw terminals for
0.2 ... 6 mm²/24 ... 13 AWG
24 V DC: 2 screw terminals for
0.2 ... 6 mm²/24 ... 13 AWG
24 V DC: 2 screw terminals for
0.5 ... 16 mm²/20 ... 6 AWG
• for control circuit and status
message
14 screw terminals for
0.2 ... 1.5 mm²/24 ... 16 AWG
14 screw terminals for
0.2 ... 1.5 mm²/24 ... 16 AWG
14 screw terminals for
0.2 ... 1.5 mm²/24 ... 16 AWG
Width of the enclosure
50 mm
50 mm
70 mm
Height of the enclosure
125 mm
125 mm
125 mm
Depth of the enclosure
125 mm
125 mm
150 mm
Required spacing
• top
50 mm
50 mm
50 mm
• bottom
50 mm
50 mm
50 mm
• left
0 mm
0 mm
0 mm
• right
0 mm
0 mm
0 mm
Net weight
0.38 kg
0.39 kg
0.65 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Yes
Mounting type
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Electrical accessories
Battery module
Battery module
Battery module
MTBF at 40 °C
415 574 h
408 654 h
372 738 h
Equipment marking acc. to
DIN EN 81346-2
T
T
T
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
■ Ordering data
Article No.
SITOP UPS1600 24 V/ 10 A
• With USB interface
• With 2 Ethernet/ PROFINET
interfaces
6EP4134-3AB00-0AY0
6EP4134-3AB00-1AY0
6EP4134-3AB00-2AY0
SITOP UPS1600, 24 V/ 20 A
• With USB interface
• With 2 Ethernet/ PROFINET
interfaces
6EP4136-3AB00-0AY0
6EP4136-3AB00-1AY0
6EP4136-3AB00-2AY0
SITOP UPS1600 24 V/ 40 A
• With USB interface
• With 2 Ethernet/ PROFINET
interfaces
6EP4137-3AB00-0AY0
6EP4137-3AB00-1AY0
6EP4137-3AB00-2AY0
11
Siemens KT 10.1 · 2016
11/17
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1100 battery modules
■ Overview
SITOP UPS1100 maintenance-free battery module with 1.2 Ah to
12 Ah and choice of different capacitors (lead, pure lead, lithium
iron phosphate = LiFePo) for SITOP UPS1600 DC UPS module.
The intelligent UPS1600 battery management charges the
UPS1100 with the optimal, temperature-controlled charging
characteristics and monitors the status (operating data and diagnostics information) via the energy storage link of the connected battery modules. For longer buffer times, up to six battery
modules can be connected in parallel. Mounting onto standard
mounting rail or directly to the wall.
■ Technical specifications
Article number
6EP4131-0GB000AY0
6EP4132-0GB000AY0
6EP4133-0GB000AY0
6EP4133-0JB000AY0
6EP4134-0GB000AY0
6EP4135-0GB000AY0
Product
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
Product type
Lead battery
Pure-lead battery
Lead battery
LiFePo battery
Lead battery
Lead battery
Battery capacity
1.2 Ah
2.5 Ah
3.2 Ah
5 Ah
7 Ah
12 Ah
• at -10 °C
recommended
28.02 V
28.02 V
28.02 V
28.8 V
28.02 V
28.02 V
• at 0 °C
recommended
28.02 V
28.02 V
28.02 V
28.8 V
28.02 V
28.02 V
• at 10 °C
recommended
27.8 V
27.8 V
27.8 V
28.8 V
27.8 V
27.8 V
• at 20 °C
recommended
27.3 V
27.3 V
27.3 V
28.8 V
27.3 V
27.3 V
• at 30 °C
recommended
26.8 V
26.8 V
26.8 V
28.8 V
26.8 V
26.8 V
• at 40 °C
recommended
26.6 V
26.6 V
26.6 V
28.8 V
26.6 V
26.6 V
• at 50 °C
recommended
26.3 V
26.3 V
26.3 V
28.8 V
26.3 V
26.3 V
• at 60 °C
recommended
-
26 V
-
-
-
-
Permissible charging 0.3 A
current, max.
5A
0.8 A
2.1 A
1.75 A
3A
Rated voltage
Vout DC
24 V
24 V
24 V
24 V
24 V
24 V
Rated current value
Iout rated
10 A
20 A
20 A
20 A
40 A
40 A
Short-circuit
protection
Battery fuse
15 A/32 V (solid-state
circuitry blade-type
fuse + support)
Battery fuse
25 A/32 V (solid-state
circuitry blade-type
fuse + support)
Battery fuse
25 A/32 V (solid-state
circuitry blade-type
fuse + support)
Battery fuse
25 A/32 V (FKS
blade-type fuse +
holder); overcurrent
switch-off at
60 A > 30 ms/min
and 24 A > 5 s/min
Battery fuse
2x 25 A/32 V
(solid-state circuitry
blade-type fuse +
support)
Battery fuse
2x 25 A/32 V
(solid-state circuitry
blade-type fuse +
support)
Design of the
overload protection
Valve control
Valve control
Valve control
Valve control
Valve control
Valve control
Status display
LED green: Battery
OK; LED flashing
green: Error or
warning; OFF: No
communication
LED green: Battery
OK; LED flashing
green: Error or
warning; OFF: No
communication
LED green: Battery
OK; LED flashing
green: Error or
warning; OFF: No
communication
LED green: Battery
OK; LED flashing
green: Error or
warning; OFF: No
communication
LED green: Battery
OK; LED flashing
green: Error or
warning; OFF: No
communication
LED green: Battery
OK; LED flashing
green: Error or
warning; OFF: No
communication
Charging current
charging voltage
End-of-charge
voltage at DC
11
Safety
11/18
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1100 battery modules
■ Technical specifications (continued)
Article number
6EP4131-0GB000AY0
6EP4132-0GB000AY0
6EP4133-0GB000AY0
6EP4133-0JB000AY0
6EP4134-0GB000AY0
6EP4135-0GB000AY0
Product
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
Product type
Lead battery
Pure-lead battery
Lead battery
LiFePo battery
Lead battery
Lead battery
Battery capacity
1.2 Ah
2.5 Ah
3.2 Ah
5 Ah
7 Ah
12 Ah
Protection class
Class III
Class III
Class III
Class III
Class III
Class III
CE mark
Yes
Yes
Yes
Yes
Yes
Yes
UL/cUL (CSA)
approval
cURus-Recognized
(UL 1778, CSA C22.2
No. 107.1), File
E219627
cURus-Recognized
(UL 1778, CSA C22.2
No. 107.1), File
E219627
cURus-Recognized
(UL 1778, CSA C22.2
No. 107.1), File
E219627
cURus-Recognized
(UL 1778, CSA C22.2
No. 107.1), File
E219627
cURus-Recognized
(UL 1778, CSA C22.2
No. 107.1), File
E219627
cURus-Recognized
(UL 1778, CSA C22.2
No. 107.1), File
E219627
Explosion protection
IECEx Ex nA nC IIC
T4 Gc; cCSAus (CSA
C22.2 No. 213M1987, ANSI/ISA12.12.01-2013) Class
I, Div. 2, Group
ABCD, T4
IECEx Ex nA nC IIC
T4 Gc; cCSAus (CSA
C22.2 No. 213M1987, ANSI/ISA12.12.01-2013) Class
I, Div. 2, Group
ABCD, T4
IECEx Ex nA nC IIC No
T4 Gc; cCSAus (CSA
C22.2 No. 213M1987, ANSI/ISA12.12.01-2013) Class
I, Div. 2, Group
ABCD, T4
IECEx Ex nA nC IIC
T4 Gc; cCSAus (CSA
C22.2 No. 213M1987, ANSI/ISA12.12.01-2013) Class
I, Div. 2, Group
ABCD, T4
IECEx Ex nA nC IIC
T4 Gc; cCSAus (CSA
C22.2 No. 213M1987, ANSI/ISA12.12.01-2013) Class
I, Div. 2, Group
ABCD, T4
Marine approval
GL, ABS
GL, ABS
GL, ABS
GL, ABS
GL, ABS
GL, ABS
IP20
IP20
IP20
IP20
IP20
For storage,
mounting and
operation of leadacid batteries, the
relevant DIN/VDE
regulations or
country-specific
regulations (e.g.
VDE 0510 Part 2/
EN 50272-2) must be
observed. You must
ensure that the
battery site is sufficiently ventilated.
Possible sources of
ignition must be at
least 50 cm away.
For storage,
mounting and
operation of leadacid batteries, the
relevant DIN/VDE
regulations or
country-specific
regulations (e.g.
VDE 0510 Part 2/
EN 50272-2) must be
observed. You must
ensure that the
battery site is sufficiently ventilated.
Possible sources of
ignition must be at
least 50 cm away.
For storage,
mounting and
operation of leadacid batteries, the
relevant DIN/VDE
regulations or
country-specific
regulations (e.g.
VDE 0510 Part 2/
EN 50272-2) must be
observed. You must
ensure that the
battery site is sufficiently ventilated.
Possible sources of
ignition must be at
least 50 cm away.
For storage,
mounting and
operation of
batteries, the relevant
DIN/VDE regulations
or country-specific
regulations (e.g.
VDE 0510 Part 2/
EN 50272-2) must be
observed.
For storage,
mounting and
operation of leadacid batteries, the
relevant DIN/VDE
regulations or
country-specific
regulations (e.g.
VDE 0510 Part 2/
EN 50272-2) must be
observed. You must
ensure that the
battery site is sufficiently ventilated.
Possible sources of
ignition must be at
least 50 cm away.
For storage,
mounting and
operation of leadacid batteries, the
relevant DIN/VDE
regulations or
country-specific
regulations (e.g.
VDE 0510 Part 2/
EN 50272-2) must be
observed. You must
ensure that the
battery site is sufficiently ventilated.
Possible sources of
ignition must be at
least 50 cm away.
• during operation
-15 ... 50 °C
-40 ... +60 °C
-15 ... 50 °C
-20 ... +50 °C
-15 ... 50 °C
-15 ... 50 °C
• during transport
-20 ... +50 °C
-40 ... +60 °C
-20 ... +50 °C
-40 ... +80 °C
-20 ... +50 °C
-20 ... +50 °C
• during storage
-20 ... +50 °C
-40 ... +60 °C
-20 ... +50 °C
-40 ... +35 °C
-20 ... +50 °C
-20 ... +50 °C
3%
3%
3%
3%
3%
Safety
Degree of protection IP20
(EN 60529)
Operating data note
Operating data note
Ambient temperature
3%
Relative temporary
capacity loss at 20 °C
in a month typical
11
Service life
Service life of energy
storage
• typical remark
capacity falls to 50 % capacity falls to 50 % capacity falls to 50 % capacity falls to 50 % capacity falls to 50 % capacity falls to 50 %
of original capacity
of original capacity
of original capacity
of original capacity
of original capacity
of original capacity
• at 20 °C typical
4 years
10 years
4 years
15 years
4 years
4 years
• at 30 °C typical
2 years
7 years
2 years
10 years
2 years
2 years
• at 40 °C typical
1 year
3 years
1 year
9 years
1 year
1 years
• at 50 °C typical
0.5 years
1.5 years
0.5 years
2 years
0.5 years
0.5 years
• at 60 °C typical
-
1 year
-
-
-
-
Siemens KT 10.1 · 2016
11/19
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1100 battery modules
■ Technical specifications (continued)
Article number
6EP4131-0GB000AY0
6EP4132-0GB000AY0
6EP4133-0GB000AY0
6EP4133-0JB000AY0
6EP4134-0GB000AY0
6EP4135-0GB000AY0
Product
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
Product type
Lead battery
Pure-lead battery
Lead battery
LiFePo battery
Lead battery
Lead battery
Battery capacity
1.2 Ah
2.5 Ah
3.2 Ah
5 Ah
7 Ah
12 Ah
Along with the
storage and
operating
temperature, other
factors such as the
duration of the
storage period and
the charge status
during storage have
a decisive influence
on the possible useful
life. Batteries should
therefore be stored
as briefly as possible,
always fully charged,
and within the
temperature range
0 to +20 °C.
Along with the
storage and
operating
temperature, other
factors such as the
duration of the
storage period and
the charge status
during storage have
a decisive influence
on the possible useful
life. Batteries should
therefore be stored
as briefly as possible,
always fully charged,
and within the
temperature range
0 to +20 °C.
Along with the
storage and
operating
temperature, other
factors such as the
duration of the
storage period and
the charge status
during storage have
a decisive influence
on the possible useful
life. Batteries should
therefore be stored
as briefly as possible,
always fully charged,
and within the
temperature range
0 to +20 °C.
Along with the
storage and
operating
temperature, other
factors such as the
duration of the
storage period and
the charge status
during storage have
a decisive influence
on the possible useful
life. Batteries should
therefore be stored
as briefly as possible,
always fully charged,
and within the
temperature range
0 to +20 °C.
Along with the
storage and
operating
temperature, other
factors such as the
duration of the
storage period and
the charge status
during storage have
a decisive influence
on the possible useful
life. Batteries should
therefore be stored
as briefly as possible,
always fully charged,
and within the
temperature range
0 to +20 °C.
Ambient temperature Along with the
during storage Note storage and
operating
temperature, other
factors such as the
duration of the
storage period and
the charge status
during storage have
a decisive influence
on the possible useful
life. Batteries should
therefore be stored
as briefly as possible,
always fully charged,
and within the
temperature range
0 to +20 °C.
Mechanics
Connection
technology
11
screw-type terminals screw-type terminals screw-type terminals screw-type terminals screw-type terminals screw-type terminals
Connection for power 1 screw terminal
supply unit
each for 0.2 ... 6 mm²
for + BATT and BATT
1 screw terminal
each for 0.2 ... 6 mm²
for + BATT and BATT
1 screw terminal
each for 0.2 ... 6 mm²
for + BATT and BATT
1 screw terminal
each for 0.5 ... 16
mm² for + BATT and BATT
1 screw terminal
each for 0.5 ... 16
mm² for + BATT and BATT
1 screw terminal
each for 0.5 ... 16
mm² for + BATT and BATT
1 screw terminal
Type of electrical
connection for control each for
0.14 ... 4 mm²
circuit and status
message
1 screw terminal
each for
0.14 ... 4 mm²
1 screw terminal
each for
0.14 ... 4 mm²
1 screw terminal
each for
0.14 ... 4 mm²
1 screw terminal
each for
0.14 ... 4 mm²
1 screw terminal
each for
0.14 ... 4 mm²
Product component
belonging to
Accessories pack
with solid-state
circuitry fuse 15 A
Accessories pack
with solid-state
circuitry fuse 25 A
Accessories pack
with solid-state
circuitry fuse 25 A
Accessories pack
with solid-state
circuitry fuse 15 A
Accessories pack
with solid-state
circuitry fuse 25 A
Accessories pack
with solid-state
circuitry fuse 25 A
Width of the
enclosure
89 mm
265 mm
190 mm
189 mm
186 mm
253 mm
Height of the
enclosure
130.3 mm
115 mm
169.3 mm
186 mm
186 mm
186 mm
Depth of the
enclosure
106.7 mm
76 mm
78.7 mm
112.7 mm
110.3 mm
110.3 mm
Installation width
89 mm
265 mm
190 mm
189 mm
186 mm
253 mm
Installation height
145.3 mm
130 mm
184.3 mm
201 mm
201 mm
201 mm
Weight, approx.
1.9 kg
3.7 kg
3.8 kg
3.4 kg
6.1 kg
9.8 kg
Installation
snaps onto DIN rail
EN 60715 35x7.5/15
or keyhole mounting
for hooking in to M4
screws
snaps onto DIN rail
EN 60715 35x7.5/15
or keyhole mounting
for hooking in to M4
screws
snaps onto DIN rail
EN 60715 35x15 or
keyhole mounting for
hooking in to M4
screws
snaps onto DIN rail
EN 60715 35x7.5/15
or keyhole mounting
for hooking in to M4
screws
can be screwed onto
flat surface (keyhole
mounting for hooking
in to M4 screws)
can be screwed onto
flat surface (keyhole
mounting for hooking
in to M4 screws)
Number of cells
12
12
12
16
12
12
Equipment marking
acc. to
DIN EN 81346-2
G
G
G
G
G
G
Other information
Specifications at
rated input voltage
and ambient
temperature +25 °C
(unless otherwise
specified)
Specifications at
rated input voltage
and ambient
temperature +25 °C
(unless otherwise
specified)
Specifications at
rated input voltage
and ambient
temperature +25 °C
(unless otherwise
specified)
Specifications at
rated input voltage
and ambient
temperature +25 °C
(unless otherwise
specified)
Specifications at
rated input voltage
and ambient
temperature +25 °C
(unless otherwise
specified)
Specifications at
rated input voltage
and ambient
temperature +25 °C
(unless otherwise
specified)
11/20
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1100 battery modules
■ Ordering data
SITOP UPS 1100 battery module
1.2 Ah
Article No.
6EP4131-0GB00-0AY0
With maintenance-free,
sealed lead-acid rechargeable
batteries for DC UPS module
SITOP UPS1600, 10 A
SITOP UPS 1100 battery module
3.2 Ah
6EP4133-0GB00-0AY0
With maintenance-free,
sealed lead-acid rechargeable
batteries for DC UPS module
SITOP UPS1600, 10 A and 20 A
SITOP UPS 1100 battery module
5 Ah, LiFePo
6EP4133-0JB00-0AY0
With maintenance-free,
sealed rechargeable lithium iron
phosphate batteries for DC UPS
module SITOP UPS1600,
10 A and 20 A
SITOP UPS 1100 battery module
7 Ah
6EP4134-0GB00-0AY0
With maintenance-free,
sealed rechargeable lead-acid
batteries for DC UPS module
SITOP UPS1600, 10 A,
20 A and 40 A
SITOP UPS 1100 battery module
12 Ah
6EP4135-0GB00-0AY0
with maintenance-free,
sealed rechargeable lead-acid
batteries for DC UPS module
SITOP UPS1600, 20 A and 40 A
SITOP UPS 1100 battery module
2.5 Ah, high temperature
6EP4132-0GB00-0AY0
With maintenance-free, sealed
rechargeable pure lead batteries
for DC UPS module
SITOP UPS1600, 10 A and 20 A
11
Siemens KT 10.1 · 2016
11/21
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP DC UPS
Power
supply
SITOP
DC UPS
Battery
module
PLC
Converter Switch Indicator
light
24 V DC buffered
24 V DC
unbuffered
Actuators
(e.g. motor
controls
and valves)
Sensors
(e.g. temperature,
proximity switch)
Motor with
incremental
encoder
G_KT01_XX_00757
■ Overview
Configuration with SITOP DC UPS and battery module: 24 V buffering
to maintain communication, signaling and sensor measured values.
To relieve the load on the UPS, the actuators are supplied directly from
the power supply unit.
By combining a DC UPS module with at least one 24 V battery
module and a SITOP power supply unit, longer power failures
can be bridged without any interruption. Even if a greater
buffering current is required, the DC UPS with maintenance-free
lead battery provides optimum safety. It spans power failures up
to several hours long and delivers up to 40 A.
■ Design
• DC UPS modules 24 V/6 A, 15 A, 40 A
• Digital inputs/outputs, optionally with serial or USB interface
■ Benefits
• 24 V buffering for a few hours for the purpose of continuing
processes
• Maintenance-free battery modules from 1.2 to 12 Ah
• High reliability and availability due to monitoring of the operational readiness, battery feeder, aging and charging status
• Long operating life of loads and batteries due to integrated
battery management
• Settings by means of DIP switches: Battery connection
threshold, end-of-charge voltage, charging current, bridging
time
• SW tool, free of charge, for easy configuring and integrating
in PC-based systems
11
■ Application
These battery modules that can be connected in parallel bridge
power failures for a few hours. This enables processes or parts
of them to be continued, measured values to be recorded without interruption and communication to be maintained. Highperformance industrial PCs that have to be shut down also have
somewhat higher energy demands. Especially if a large panel
continues to be operated during the shutdown. The DC UPS
is used, for example, in machine tool production, in the textile
industry, in all types of production lines, bottling plants or also for
the obstacle lights of wind power plants.
The serial or USB interface and a free software tool enable easy
communication with a PC.
11/22
Siemens KT 10.1 · 2016
• Battery modules 1.2 Ah, 3.2 Ah, 7 Ah, 12 Ah with lead
rechargeable batteries of corrosion-resistant lead-calcium
high-performance grid plates and glass fiber
• Battery module 2.5 Ah with "high-temperature battery"
of pure lead
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP DC UPS
■ Function
SITOP DC UPS software tool
Via the USB interface, all relevant messages about the status of
the uninterruptible DC power supply can be transmitted to a PC
(e.g. SIMATIC IPC). The DC UPS can also be configured via the
USB interface.
The SITOP DC UPS software provides the user with a free tool
that is extremely easy to use for the purpose of monitoring and
configuring the DC UPS. Signals sent from the uninterruptible
DC power supply can be processed on the PC. In monitoring
mode, the statuses of the uninterruptible DC power supply are
visualized on the PC.
Safe shutdown in the event of a power failure and automatic PC
restart are supported. It is also possible to freely define responses to the different operating states of the uninterruptible
DC power supply, so that extremely flexible integration into a
wide variety of applications is possible.
Overview of configuration possibilities:
• Times for shutting down the PC
• UPS switch-off
• Further processing of all signals, e.g. linking to proprietary
software or WinCC flexible
• Monitoring and display of UPS operating status
• OPC server for linking signals to proprietary applications
• Automatic restarting of IPCs when power is restored during
shutdown
Monitoring and configuration window of software V3 for SITOP DC UPS
The software runs under the operating systems Windows 2000,
Windows XP, Windows Vista and Windows 7. Free download
from:
http://support.automation.siemens.com/WW/view/en/48946053
11
Siemens KT 10.1 · 2016
11/23
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP DC UPS
■ Technical specifications
The table shows the maximum buffering times for the battery
modules for different load currents.
Load current
Battery module 1.2 Ah
(6EP1935-6MC01)
Battery module 3.2 Ah
(6EP1935-6MD11)
Battery module 7 Ah
(6EP1935-6ME21)
Battery module 12 Ah
(6EP1935-6MF01)
Battery module 2.5 Ah
(6EP1935-6MD31)
1A
34.5 min
2.6 h
5.4 h
9h
2h
2A
15 min
1h
2.6 h
4.6 h
1h
3A
9 min
39.3 min
1.6 h
2.9 h
37.5 min
4A
6.5 min
27.1 min
1.2 h
2.2 h
27 min
6A
3.5 min
17.5 min
41 min
1.2 h
17.6 min
8A
2 min
12.1 min
28.6 min
53.3 min
12.5 min
10 A
1 min
9 min
21.8 min
43.5 min
8.8 min
12 A
-
7 min
17.3 min
33.3 min
6.8 min
14 A
-
5 min
15.1 min
27.5 min
5.1 min
16 A
-
4 min
12.5 min
23.8 min
4.3 min
20 A
-
1 min
9.1 min
20.1 min
-
25 A
-
-
-
12.6 min
-
30 A
-
-
-
9.1 min
-
35 A
-
-
-
17.1 min. (2 x 12 Ah)
-
40 A
-
-
-
13.5 min. (2 x 12 Ah)
-
Important information for selecting the battery capacity:
Determination of the mains buffering times is based on the discharge period of new or non-aged, completely charged battery
modules at a battery temperature not below +25 °C to the shutdown of the DC UPS.
Battery aging reduces the still available battery capacity up until
the end of the service life to typically around 50% of the original
capacity value when new (1.2 Ah/3.2 Ah/7 Ah, etc.) and the internal resistance increases. When the message "Battery charge
> 85%" appears, only around 50% x 85% = approx. 43% of the
originally available capacity can be assumed at the end of the
battery service life.
11
The SITOP Selection Tool offers detailed selection guidance
according to criteria such as the required backup time, load
current, peak current and battery connection threshold:
http://www.siemens.com/sitop-selection-tool
At battery temperatures below +25 °C, the available capacity
drops approximately by another 30% at +5 °C battery temperature, to approximately 70% of the approximately remaining 43%.
There is then only around 30% of the original capacity available.
A significantly larger battery capacity must therefore be selected
when configuring the plant: A drop to approx. 50% is compensated for by selecting 1 / approx. 0.5 = approx. double the
battery capacity (required as per the table for the relevant load
current and the relevant buffering time). Available capacity
of approx. 43% is compensated for by selecting 1 / approx.
0.43 = approx. 2.33 times the battery capacity. Available capacity of approx. 30% is compensated for by selecting 1 / approx.
0.3 = approx. 3.33 times the battery capacity.
Recommendation:
Instead of installing double the battery capacity, regular battery
replacement halfway through the expected service life (reduction of capacity to approx. 50%) can be more advisable for the
following reasons: Capacity does not drop below 100% until the
halfway point of the expected battery life (or slightly beyond).
With regular replacement after this point, only the single battery
capacity (instead of double capacity) must be installed due to
aging (-> neutral in price with regard to battery module costs,
but only requires half the space).
11/24
Siemens KT 10.1 · 2016
Replacing the battery after half its service life dispenses above
all with the large scatter range of the residual capacity at the end
of the service life, which is not accurately defined by battery
manufacturers (after the full time, many batteries are above, but
many are also below the average 50% residual capacity, that is
to say, even if double the capacity is installed, the influence of
aging at the end of service life is not reliably compensated for,
rather only typically) -> When replacing after half the expected
service life, the configured buffering time is maintained with
considerably greater reliability.
In the case of batteries stored in cool conditions (not above
+25 °C) and for not longer than approximately 4 months, the
following service life can be assumed, strongly dependent on
battery temperature:
Battery
temperature
Drop to approx.
50% of residual
capacity
Recommendation: Replace
(at 100% of
residual
capacity) all
+20 °C
4 years
2 years
+30 °C
2 years
1 year
+40 °C
1 year
0.5 years
Alternative
recommendation
Install double
capacity and
replace
1 x per year
In normal cases (installation in the coolest location in the control
cabinet at approx. +30 °C), the battery should be replaced with
single installed battery capacity in accordance with the selection
table after 1 year of operation!
• On the DC UPS module 40 A, at least 2 battery modules of
7 Ah or higher must be connected in parallel for output
currents > 30 A. When connecting battery modules in parallel,
you must ensure identical capacity and aging.
• After a power failure, the battery module is disconnected from
the loads at the end of the selected buffering time either
automatically or electronically by opening the On/Off control
circuit, and as soon as the 24 V input voltage is available
again, it is quickly re-charged with the charging current of the
relevant DC UPS module (with I-U charge characteristic:
First constant current I for fast charging, and changeover to
constant voltage U to maintain the charge when the battery
is almost full).
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP DC UPS
■ Technical specifications (continued)
Article number
6EP1931-2DC21
6EP1931-2EC21
6EP1931-2FC21
6EP1931-2DC31
6EP1931-2EC31
6EP1931-2FC42
6EP1931-2DC42
6EP1931-2EC42
Product brand name
SITOP DC UPS module
SITOP DC UPS module
SITOP DC UPS module
Type of current supply
DC UPS 24 V/6 A
DC UPS 24 V/15 A
DC UPS 24 V/40 A
Input
Supply voltage at DC Rated value
24 V
24 V
24 V
Voltage curve at input
DC
DC
DC
input voltage range
22 ... 29 V DC
22 ... 29 V DC
22 ... 29 V DC
Adjustable response value voltage
for buffer connection preset
22.5 V
22.5 V
22.5 V
Adjustable response value voltage
for buffer connection
22 ... 25.5 V; Adjustable in
0.5 V increments
22 ... 25.5 V; Adjustable in
0.5 V increments
22 ... 25.5 V; Adjustable in
0.5 V increments
Input current at rated input voltage
24 V Rated value
6 A; + approx. 0.6 A
with empty battery
15 A; + approx. 1 A
with empty battery
40 A; + approx. 2.6 A
with empty battery
Type of energy storage
with batteries
with batteries
with batteries
Design of the mains power cut
bridging-connection
Dependent on connected battery
and load current, see selection table
battery module and mains buffering
times as well as the relevant important
information notes!
Dependent on connected battery
and load current, see selection table
battery module and mains buffering
times as well as the relevant important
information notes!
Dependent on connected battery
and load current, see selection table
battery module and mains buffering
times as well as the relevant important
information notes!
•1
0.2 A
0.35 A
1A
•2
0.4 A
0.7 A
2A
factory setting approx. 0.7 A
factory setting approx. 2 A
24 V
24 V
24 V
• in buffering mode at DC Rated value 24 V
Mains buffering
Charging current
adjustable charging current maximum factory setting approx. 0.4 A
Note
Output
Output voltage
• in normal operation at DC Rated
value
24 V
24 V
Formula for output voltage
Vin - approx. 0.5 V
Vin - approx. 0.5 V
Vin - approx. 0.5 V
ON-delay time typical
1s
1s
1s
Voltage increase time of the output
voltage typical
60 ms
60 ms
360 ms
Output voltage in buffering mode
at DC
19 ... 28.5 V
19 ... 28.5 V
19 ... 28.5 V
Output current
• Rated value
6A
15 A
40 A
• in normal operation
0 ... 6 A
0 ... 15 A
0 ... 40 A
• in buffering mode
0 ... 6 A
0 ... 15 A
0 ... 40 A
Peak current
6.3 A
15.7 A
42 A
Property of the output Short-circuit
proof
Yes
Yes
Supplied active power typical
144 W
360 W
960 W
• at rated output current at rated
output current typical
95 %
96.2 %
97.2 %
• in case of accumulator operation
typical
94.5 %
96 %
96.9 %
• at rated output current at rated
output current typical
7W
14 W
28.6 W
• in case of accumulator operation
typical
8W
15 W
33.6 W
• reverse polarity protection against Yes
energy storage unit polarity reversal
Yes
Yes
• reverse polarity protection against
input voltage polarity reversal
Yes
Yes
11
Efficiency
Efficiency in percent
Power loss [W]
Protection and monitoring
Product function
Yes
Siemens KT 10.1 · 2016
11/25
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP DC UPS
■ Technical specifications (continued)
Article number
6EP1931-2DC21
6EP1931-2EC21
6EP1931-2FC21
6EP1931-2DC31
6EP1931-2EC31
6EP1931-2FC42
6EP1931-2DC42
6EP1931-2EC42
Product brand name
SITOP DC UPS module
SITOP DC UPS module
SITOP DC UPS module
Type of current supply
DC UPS 24 V/6 A
DC UPS 24 V/15 A
DC UPS 24 V/40 A
• for normal operation
Normal operation: LED green (OK),
floating changeover contact "Bat/OK"
to setting "OK" ("OK" means: Voltage
of the supplying power supply unit is
greater than cut-in threshold set at
the DC UPS module); Lack of buffer
standby: LED red (alarm), floating
changeover contact "Alarm/Bat" to
setting "Alarm"; Battery replacement
required: LED red (alarm) flashing with
approx. 0.25 Hz, floating changeover
contact "Alarm/Bat" switching with
approx. 0.25 Hz; Energy storage
> 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed;
Permissible contact current capacity:
DC 60 V/1 A or AC 30 V /1 A
Normal operation: LED green (OK),
floating changeover contact "Bat/OK"
to setting "OK" ("OK" means: Voltage
of the supplying power supply unit is
greater than cut-in threshold set at the
DC UPS module); Lack of buffer
standby: LED red (alarm), floating
changeover contact "Alarm/Bat" to
setting "Alarm"; Battery replacement
required: LED red (alarm) flashing with
approx. 0.25 Hz, floating changeover
contact "Alarm/Bat" switching with
approx. 0.25 Hz; Energy storage
> 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed;
Permissible contact current capacity:
DC 60 V/1 A or AC 30 V /1 A
Normal operation: LED green (OK),
floating changeover contact "Bat/OK"
to setting "OK" ("OK" means: Voltage
of the supplying power supply unit is
greater than cut-in threshold set at the
DC UPS module); Lack of buffer
standby: LED red (alarm), floating
changeover contact "Alarm/Bat" to
setting "Alarm"; Battery replacement
required: LED red (alarm) flashing with
approx. 0.25 Hz, floating changeover
contact "Alarm/Bat" switching with
approx. 0.25 Hz; Energy storage
> 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed;
Permissible contact current capacity:
DC 60 V/1 A or AC 30 V /1 A
• in buffering mode
Buffered mode: LED yellow (Bat),
floating changeover contact "OK/Bat"
to setting "Bat"; Prewarning battery
voltage < 20.4 VDC: LED red (alarm),
floating changeover contact "Alarm/
Bat" to setting "Alarm"; Energy storage
> 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed
Buffered mode: LED yellow (Bat),
floating changeover contact "OK/Bat"
to setting "Bat"; Prewarning battery
voltage < 20.4 VDC: LED red (alarm),
floating changeover contact "Alarm/
Bat" to setting "Alarm"; Energy storage
> 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed
Buffered mode: LED yellow (Bat),
floating changeover contact "OK/Bat"
to setting "Bat"; Prewarning battery
voltage < 20.4 VDC: LED red (alarm),
floating changeover contact "Alarm/
Bat" to setting "Alarm"; Energy storage
> 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed
Product component PC interface
No
No
No
Design of the interface
without
without
without
Galvanic isolation between entrance
and outlet
No
No
No
Operating resource protection class
Class III
Class III
Class III
Signaling
Display version
Interface
Safety
Certificate of suitability
11
• CE marking
Yes
Yes
Yes
• as approval for USA
cULus-Listed (UL 508,
CSA C22.2 No. 107.1), File E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1), File E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1), File E197259
• relating to ATEX
-
-
-
• C-Tick
No
No
No
Shipbuilding approval
GL, ABS
GL, ABS
GL, ABS
Protection class IP
IP20
IP20
IP20
• for emitted interference
EN 55022 Class B
EN 55022 Class B
EN 55022 Class B
• for interference immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
• during operation
-25 ... +60 °C;
with natural convection
-25 ... +60 °C;
with natural convection
-25 ... +60 °C;
with natural convection
• during transport
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
• during storage
-40 ... +85 °C
-40 ... +85 °C
-40 ... +85 °C
Environmental category acc. to
IEC 60721
Climate class 3K3, no condensation
Climate class 3K3, no condensation
Climate class 3K3, no condensation
EMC
Standard
Operating data
Ambient temperature
11/26
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP DC UPS
■ Technical specifications (continued)
6EP1931-2DC21
6EP1931-2EC21
6EP1931-2FC21
6EP1931-2DC31
6EP1931-2EC31
6EP1931-2FC42
6EP1931-2DC42
6EP1931-2EC42
Product brand name
SITOP DC UPS module
SITOP DC UPS module
SITOP DC UPS module
Type of current supply
DC UPS 24 V/6 A
DC UPS 24 V/15 A
DC UPS 24 V/40 A
Type of electrical connection
screw-type terminals
screw-type terminals
screw-type terminals
• at input
24 V DC: 2 screw terminals for
1 ... 4 mm²/17 ... 11 AWG
24 V DC: 2 screw terminals for
1 ... 4 mm²/17 ... 11 AWG
24 V DC: 2 screw terminals for
0.33 ... 10 mm²/22 ... 7 AWG
• at output
24 V DC: 4 screw terminals for
1 ... 4 mm²/17 ... 11 AWG
24 V DC: 4 screw terminals for
1 ... 4 mm²/17 ... 11 AWG
24 V DC: 2 screw terminals for
0.33 ... 10 mm²/22 ... 7 AWG
• for battery module
24 V DC: 2 screw terminals for
1 ... 4 mm²/17 ... 11 AWG
24 V DC: 2 screw terminals for
1 ... 4 mm²/17 ... 11 AWG
24 V DC: 2 screw terminals for
0.33 ... 10 mm²/22 ... 7 AWG
• for control circuit and
status message
10 screw terminals for
0.5 ... 2.5 mm²/20 ... 13 AWG
10 screw terminals for
0.5 ... 2.5 mm²/20 ... 13 AWG
10 screw terminals for
0.5 ... 2.5 mm²/20 ... 13 AWG
Width of the enclosure
50 mm
50 mm
102 mm
Height of the enclosure
125 mm
125 mm
125 mm
Depth of the enclosure
125 mm
125 mm
125 mm
• top
50 mm
50 mm
50 mm
• bottom
50 mm
50 mm
50 mm
• left
0 mm
0 mm
0 mm
• right
0 mm
0 mm
0 mm
Net weight
0.4 kg
0.4 kg
1.1 kg
Product feature of the enclosure
housing for side-by-side mounting
Yes
Yes
Yes
Mounting type
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Snaps onto DIN rail
EN 60715 35x7.5/15
Electrical accessories
Battery module
Battery module
Battery module
MTBF at 40 °C
1 085 776 h
791 139 h
522 739 h
Equipment marking acc. to
DIN EN 81346-2
T
T
T
Other information
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Specifications at rated input voltage
and ambient temperature +25 °C
(unless otherwise specified)
Article number
Mechanics
Required spacing
■ Ordering data
Article No.
DC UPS module 6 A
• with serial interface
• with USB interface
6EP1931-2DC21
6EP1931-2DC31
6EP1931-2DC42
DC UPS module 15 A
• with serial interface
• with USB interface
6EP1931-2EC21
6EP1931-2EC31
6EP1931-2EC42
DC UPS module 40 A
• with USB interface
6EP1931-2FC21
6EP1931-2FC42
11
Siemens KT 10.1 · 2016
11/27
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
DC UPS battery modules
■ Overview
Maintenance-free battery modules with 1.2 Ah up to 12 Ah
(lead-gel accumulator) for ambient temperatures from 0 to +40 °C
as well as high-temperature battery module with 2.5 Ah (pure-lead
accumulator) for ambient temperatures of –40 °C to +60 °C. The
battery modules are completely prewired with battery retainer and
terminals. For longer buffer times, the battery modules can be
connected in parallel. Mounting onto standard mounting rail or
directly to the wall.
■ Technical specifications
Article number
6EP1935-6MC01
Product
SITOP Battery module SITOP Battery module SITOP Battery module SITOP Battery module SITOP Battery module
6EP1935-6MD31
6EP1935-6MD11
6EP1935-6ME21
6EP1935-6MF01
Product type
Battery module 1.2 Ah Battery module 2.5 Ah Battery module 3.2 Ah Battery module 7 Ah
Battery module 12 Ah
Charging current charging voltage
End-of-charge voltage at DC
• at -10 °C recommended
-
29 V
-
-
-
• at 0 °C recommended
-
28.6 V
-
-
-
• at 10 °C recommended
27.8 V
28.3 V
27.8 V
27.8 V
27.8 V
• at 20 °C recommended
27.3 V
27.9 V
27.3 V
27.3 V
27.3 V
• at 30 °C recommended
26.8 V
27.5 V
26.8 V
26.8 V
26.8 V
• at 40 °C recommended
26.6 V
27.2 V
26.6 V
26.6 V
26.6 V
• at 50 °C recommended
26.3 V
26.8 V
26.3 V
26.3 V
26.3 V
• at 60 °C recommended
-
26.4 V
-
-
-
Permissible charging current, max.
0.3 A
5A
0.8 A
1.75 A
3A
Rated voltage Vout DC
24 V
24 V
24 V
24 V
24 V
Short-circuit protection
Battery fuse 7.5 A/32 V
(solid-state circuitry
blade-type fuse
+ support)
Battery fuse 15 A/32 V
(solid-state circuitry
blade-type fuse
+ support)
Battery fuse 15 A/32 V
(solid-state circuitry
blade-type fuse
+ support)
Battery fuse 20 A/32 V
(solid-state circuitry
blade-type fuse
+ support)
Battery fuse 20 A/32 V
(solid-state circuitry
blade-type fuse
+ support)
Design of the overload protection
Valve control
Valve control
Valve control
Valve control
Valve control
Safety
11
Safety
Protection class
Class III
Class III
Class III
Class III
Class III
CE mark
Yes
Yes
Yes
Yes
Yes
UL/cUL (CSA) approval
cURus-Recognized
(UL 1778,
CSA C22.2 No. 107.1),
File E219627
cURus-Recognized
(UL 1778,
CSA C22.2 No. 107.1),
File E219627
cURus-Recognized
(UL 1778,
CSA C22.2 No. 107.1),
File E219627
cURus-Recognized
(UL 1778,
CSA C22.2 No. 107.1),
File E219627
cURus-Recognized
(UL 1778,
CSA C22.2 No. 107.1),
File E219627
Marine approval
GL, ABS
GL, ABS
GL, ABS
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP00
IP00
IP00
IP00
IP00
11/28
Siemens KT 10.1 · 2016
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
DC UPS battery modules
■ Technical specifications (continued)
Article number
6EP1935-6MC01
Product
SITOP Battery module SITOP Battery module SITOP Battery module SITOP Battery module SITOP Battery module
6EP1935-6MD31
6EP1935-6MD11
6EP1935-6ME21
6EP1935-6MF01
Product type
Battery module 1.2 Ah Battery module 2.5 Ah Battery module 3.2 Ah Battery module 7 Ah
Battery module 12 Ah
For storage, mounting
and operation of
lead-acid batteries,
the relevant DIN/VDE
regulations or countryspecific regulations
(e.g. VDE 0510 Part
2/EN 50272-2) must be
observed. You must
ensure that the battery
site is sufficiently
ventilated. Possible
sources of ignition
must be at least 50 cm
away.
For storage, mounting
and operation of
lead-acid batteries,
the relevant DIN/VDE
regulations or countryspecific regulations
(e.g. VDE 0510 Part
2/EN 50272-2) must be
observed. You must
ensure that the battery
site is sufficiently
ventilated. Possible
sources of ignition
must be at least 50 cm
away.
For storage, mounting
and operation of
lead-acid batteries,
the relevant DIN/VDE
regulations or countryspecific regulations
(e.g. VDE 0510 Part
2/EN 50272-2) must be
observed. You must
ensure that the battery
site is sufficiently
ventilated. Possible
sources of ignition
must be at least 50 cm
away.
For storage, mounting
and operation of
lead-acid batteries,
the relevant DIN/VDE
regulations or countryspecific regulations
(e.g. VDE 0510 Part
2/EN 50272-2) must be
observed. You must
ensure that the battery
site is sufficiently
ventilated. Possible
sources of ignition
must be at least 50 cm
away.
For storage, mounting
and operation of
lead-acid batteries,
the relevant DIN/VDE
regulations or countryspecific regulations
(e.g. VDE 0510 Part
2/EN 50272-2) must be
observed. You must
ensure that the battery
site is sufficiently
ventilated. Possible
sources of ignition
must be at least 50 cm
away.
Operating data note
Operating data note
Ambient temperature
• during operation
-15 ... +50 °C
-40 ... +60 °C
-15 ... +50 °C
-15 ... +50 °C
-15 ... +50 °C
• during transport
-20 ... +50 °C
-40 ... +60 °C
-20 ... +50 °C
-20 ... +50 °C
-20 ... +50 °C
• during storage
-20 ... +50 °C
-40 ... +60 °C
-20 ... +50 °C
-20 ... +50 °C
-20 ... +50 °C
Relative temporary capacity loss at
20 °C in a month typical
3%
3%
3%
3%
3%
• typical remark
capacity falls to 50 %
of original capacity
capacity falls to 50 %
of original capacity
capacity falls to 50 %
of original capacity
capacity falls to 50 %
of original capacity
capacity falls to 50 %
of original capacity
• at 20 °C typical
4 years
10 years
4 years
4 years
4 years
• at 30 °C typical
2 years
7 years
2 years
2 years
2 years
• at 40 °C typical
1 year
3 years
1 year
1 year
1 year
• at 50 °C typical
0.5 years
1.5 years
0.5 years
0.5 years
0.5 years
• at 60 °C typical
-
1 year
-
-
-
Ambient temperature
during storage Note
Along with the storage
and operating
temperature, other
factors such as the
duration of the storage
period and the charge
status during storage
have a decisive
influence on the
possible useful life.
Batteries should
therefore be stored
as briefly as possible,
always fully charged,
and within the
temperature range
0 to +20 °C.
Along with the storage
and operating
temperature, other
factors such as the
duration of the storage
period and the charge
status during storage
have a decisive
influence on the
possible useful life.
Batteries should
therefore be stored
as briefly as possible,
always fully charged,
and within the
temperature range
0 to +20 °C.
Along with the storage
and operating
temperature, other
factors such as the
duration of the storage
period and the charge
status during storage
have a decisive
influence on the
possible useful life.
Batteries should
therefore be stored
as briefly as possible,
always fully charged,
and within the
temperature range
0 to +20 °C.
Along with the storage
and operating
temperature, other
factors such as the
duration of the storage
period and the charge
status during storage
have a decisive
influence on the
possible useful life.
Batteries should
therefore be stored
as briefly as possible,
always fully charged,
and within the
temperature range
0 to +20 °C.
Along with the storage
and operating
temperature, other
factors such as the
duration of the storage
period and the charge
status during storage
have a decisive
influence on the
possible useful life.
Batteries should
therefore be stored
as briefly as possible,
always fully charged,
and within the
temperature range
0 to +20 °C.
Service life
Service life of energy storage
Siemens KT 10.1 · 2016
11/29
11
© Siemens AG 2016
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
DC UPS battery modules
■ Technical specifications (continued)
Article number
6EP1935-6MC01
Product
SITOP Battery module SITOP Battery module SITOP Battery module SITOP Battery module SITOP Battery module
6EP1935-6MD31
6EP1935-6MD11
6EP1935-6ME21
6EP1935-6MF01
Product type
Battery module 1.2 Ah Battery module 2.5 Ah Battery module 3.2 Ah Battery module 7 Ah
Battery module 12 Ah
Connection technology
spring-loaded
terminals
spring-loaded
terminals
Connection for power supply unit
1 screw terminal each 1 screw terminal each 1 screw terminal each 1 screw terminal each 1 screw terminal each
for 0.08 ... 2.5 mm² for for 0.08 ... 2.5 mm² for for 0.08 ... 2.5 mm² for for 0.08 ... 4 mm² for + for 0.08 ... 4 mm² for +
+ BATT and - BATT
+ BATT and - BATT
+ BATT and - BATT
BATT and - BATT
BATT and - BATT
Product component belonging to
Accessories pack
with solid-state
circuitry fuse 7.5 A
Accessories pack
with solid-state
circuitry fuse 15 A
Accessories pack
with solid-state
circuitry fuse 15 A
Accessories pack
with solid-state
circuitry fuse 20 A and
30 A
Accessories pack
with solid-state
circuitry fuse 20 A and
30 A
Width of the enclosure
96 mm
265 mm
190 mm
186 mm
253 mm
Height of the enclosure
106 mm
151 mm
151 mm
168 mm
168 mm
Depth of the enclosure
108 mm
91 mm
82 mm
121 mm
121 mm
Installation width
116 mm
285 mm
210 mm
206 mm
273 mm
Installation height
126 mm
171 mm
171 mm
188 mm
188 mm
Weight, approx.
1.8 kg
3.8 kg
3.2 kg
6 kg
9 kg
Installation
snaps onto DIN rail
EN 60715 35x7.5/15
or keyhole mounting
for hooking in to M4
screws
snaps onto DIN rail
EN 60715 35x15
or keyhole mounting
for hooking in to M4
screws
snaps onto DIN rail
EN 60715 35x7.5/15
or keyhole mounting
for hooking in to M4
screws
can be screwed onto
flat surface (keyhole
mounting for hooking
in to M4 screws)
can be screwed onto
flat surface (keyhole
mounting for hooking
in to M4 screws)
Number of cells
12
12
12
12
12
Equipment marking acc. to
DIN EN 81346-2
G
G
G
G
G
Other information
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Specifications at rated
input voltage and
ambient temperature
+25 °C (unless
otherwise specified)
Mechanics
■ Ordering data
Battery module 1.2 Ah
Article No.
6EP1935-6MC01
for DC UPS module 6 A
Battery module 2.5 Ah
6EP1935-6MD31
for DC UPS module 6 A and 15 A
Battery module 3.2 Ah
6EP1935-6MD11
for DC UPS module 6 A and 15 A
11
Battery module 7 Ah
6EP1935-6ME21
for DC UPS modules 6 A,
15 A and 40 A
Battery module 12 Ah
6EP1935-6MF01
for DC UPS modules 6 A,
15 A and 40 A
11/30
Siemens KT 10.1 · 2016
spring-loaded
terminals
spring-loaded
terminals
spring-loaded
terminals
12
© Siemens AG 2016
Accessories
12/2
Accessories
Siemens KT 10.1 · 2016
© Siemens AG 2016
Accessories
Accessories
■ Overview
■ Technical specifications
Mounting bracket 90° for SITOP power Standard 24 V
For a depth of 320 mm
6EP1971-2BA00
Dimensions (W x H x D) in mm
100 x 150 x 320
Sheet thickness
1.5 mm
Mounting rail, attached
Standard mounting rail EN 60715
35x15
Weight, approx.
0.9 kg
Mounting
Can be screwed onto a flat surface
(keyhole mounting for hooking onto
M6 screws, drill hole distance 90 mm
height, 50 mm side)
Accessories, included
4 M6 combi screws
Suitable, for example, for
SITOP 24 V/20 A
(6EP1336-3BA00, 6EP1436-3BA00)
Mounting bracket
SITOP 24 V/40 A
(6EP1437-3BA00,6EP1437-3BA00)
The combination of a SITOP power supply and a 90° mounting
bracket results in a minimum surface area requirement on the
rear panel of the control cabinet (the width of the power supply
becomes the depth, and the depth becomes the width). The
mounting bracket is suitable for control cabinets with a depth
of 320 mm or more.
SITOP 48 V/20 A (6EP1457-3BA00)
Mounting adapter for standard mounting rail
The 1-phase 24 V/2 A (6ES7305-1BA80-0AA0) and 24 V/5 A
(6ES7307-1EA80-0AA0) power supplies are special mechanical
versions for SIMATIC S7-300 and can be mounted on S7 rails.
■ Ordering data
SITOP modular signaling module
Article No.
6EP1961-3BA10
For 6EP1XXX-3BA00
signaling contacts: Output voltage
ok, operational availability ok,
remote ON/OFF
SITOP power mounting bracket
A mounting adapter (6ES7390-6BA00-0AA0) for mounting on
the standard mounting rail EN 60715 35x15 is separately
available as an accessory.
90 degrees, for Article No.'s.
6EP1336-3BA00, 6EP1436-3BA00,
6EP1337-3BA00, 6EP1437-3BA00,
6EP1457-3BA00
6EP1971-2BA00
The 24 V/ 2 A (6ES7307-1BA01-0AA0), 24 V/ 5 A (6ES73071EA01-0AA0) and 10 A (6ES7307-1KA02-0AA0) power supplies
are variants for SIMATIC S7-300 and can be mounted on S7 rails.
SIMATIC S7-300 mounting
adapter
6EP1971-1BA00
A mounting adapter (6EP1971-1BA00) for installation on DIN rail
EN 60715 35×15/7.5 is separately available as an accessory.
Connection plug for devices with degrees of protection IP65
and IP67
For the maintenance-free SITOP UPS500P DC UPS modules
(6EP1933-2NC01, 6EP1933-2NC11) in IP65 degree of protection, a connector set (6EP1975-2ES00) for input and output and
with a pre-assembled USB cable (2 m long) is available as an
accessory.
12
Mounting bracket
Article number
Device labels
Blank device labeling plates (20 mm x 7 mm, pastel turquoise)
with Art. No.'s 3RT1 900-1SB20 can be used for identification of
the power supplies. The package unit comprises 340 labels on
frames, 20 labels per frame. For usability, refer to "Accessories"
in the technical data of the respective power supplies.
12/1
Siemens KT 10.1 · 2016
For snapping the PS 307 onto
standard mounting rail
35x15/7.5 mm
suitable for 6ES7307-1BA01*, 1EA01*, -1KA02* and higher
Connector set
6EP1975-2ES00
For UPS500P 6EP1933-2NC01
and 6EP1933-2NC11
degree of protection IP65
Contents: input plug, output plug,
USB cable connection, length 2 m
SIMATIC S7-300 mounting
adapter
6ES7390-6BA00-0AA0
for snapping the PS307 onto 35 mm
standard rails
Device labels
3RT1900-1SB20
13
© Siemens AG 2016
SIPLUS power supplies
13/2
Introduction
13/3
Ordering data
Siemens KT 10.1 · 2016
© Siemens AG 2016
SIPLUS power supplies
Introduction
■ Overview
Ambient conditions
Conformal coating
Coating of the printed circuit boards and the
electronic components
Technical specifications
The technical data of the standard product applies
except for the ambient conditions.
Relative humidity
100%, condensation/frost permitted. 
No commissioning in bedewed state.
Biologically active
Class 3B2 mold and fungal spores (excluding
substances, compliance fauna). The supplied plug covers must remain in
with EN 60721-3-3
place over the unused interfaces during operation!
Chemically active
Class 3C4 incl. salt spray in accordance with
substances, compliance EN60068-2-52 (degree of severity 3). The supplied
with EN 60721-3-3
plug covers must remain in place over the unused
interfaces during operation!
Mechanically active
Class 3S4 incl. conductive sand, dust. 
substances, compliance The supplied plug covers must remain in place
over the unused interfaces during operation!
with EN 60721-3-3
Particularly harsh industrial environments demand products with
special characteristics - products that are more rugged than
standard products.
Siemens offers the perfect answer to these requirements with
SIPLUS extreme.
SIPLUS product variants are based on the SITOP, LOGO!Power
standard power supplies and the power supplies for SIMATIC S7
and expansion modules, and feature the following characteristics:
• Extended ambient temperature range (e.g. -40 … +70 °C) 
and conformal coating as protection against extreme and
difficult conditions and contact with substances
• DIN EN 50155:
Conforms with standard for electronic equipment used on
rolling stock (EN 50155, temperature T1, category)
13
13/2
Siemens KT 10.1 · 2016
Air pressure (depending
on the highest positive
temperature range
specified)
1080 ... .795 hPa (-1000 ... +2000 m) 
see ambient temperature range
795 ... 658 hPa (+2000 ... +3500 m) 
derating 10 K
658 … 540 hPa (+3500 … +5000 m) 
derating 20 K
For further technical specifications, see the standard products,
or visit www.siemens.com/siplus-extreme
© Siemens AG 2016
SIPLUS power supplies
Ordering data
■ Ordering data
Article No.
SIPLUS LOGO!Power
SIPLUS LOGO!Power 24 V 1.3 A
SIPLUS S7 design
6AG1331-1SH03-7AA0
Input: 100 ... 240 V AC
Output: 24 V DC, 1.3 A
6AG1332-1SH43-7AA0
6AG1332-1SH52-7AA0
SIPLUS S7-300 PS 305 10 A
Extended temperature range and
exposure to media
SIPLUS smart
6AG1334-2BA20-4AA0
6AG1307-1KA02-7AA0
Incl. connection bracket
Input: 120/230 V AC
Output: 24 V DC/10 A
(dimensions 80 x 125 x 120)
Extended temperature range and
exposure to media
Stabilized power supply
Input: 120/230 V AC
Output: 24 V DC/10 A
For rolling stock railway applications
SIPLUS S7-300 PS 305
Extended temperature range and
Exposure to media
6AG1434-2BA10-7AA0
6AG1305-1BA80-2AA0
Input: 24 … 110 V DC
Output: 24 V DC/2 A
Conforms to EN 50155
Stabilized power supply
Input: 400 … 500 V 3 AC
Output: 24 V DC/20 A
Extended temperature range and
exposure to media
Exposure to media
SIPLUS S7-1200 PM 1207
power supply
SIPLUS PSU300S 3-phase,
24 V DC/20 A
6AG1307-1EA01-7AA0
Incl. connection bracket
Input: 120/230 V AC
Output: 24 V DC/5 A
Extended temperature range and
exposure to media
Input: 100 ... 240 V AC
Output: 24 V DC, 4 A
SIPLUS PSU300S 3-phase,
24 V DC/10 A
Extended temperature range and
exposure to media
SIPLUS S7-300 PS 305 5 A
Extended temperature range and
exposure to media
SIPLUS PSU100S 24 V/10 A
6AG1305-1BA80-2AA0
Input: 24 … 110 V DC
Output: 24 V DC/2 A
Input: 100 ... 240 V AC
Output: 24 V DC, 2.5 A
SIPLUS LOGO!Power 24 V 4 A
For industrial applications with particularly demanding ambient
conditions
SIPLUS S7-300 PS 305
Extended temperature range and
exposure to media
SIPLUS LOGO!Power 24 V 2.5 A
Article No.
6AG1436-2BA10-7AA0
Stabilized power supply
Input: 400 … 500 V 3 AC
Output: 24 V DC/20 A
Extended Temperature range and
exposure To media
SIPLUS modular
Input: 120/230 V AC
Output: 24 V DC, 2.5 A;
Derating from + 55 °C to + 70 °C
1.2 A output current
• Ambient temperature
-25 ... +70 °C
6AG1332-1SH71-7AA0
• Ambient temperature
0... +60 °C
6AG1332-1SH71-4AA0
Extended temperature range and
exposure to media
SIPLUS Modular 40 A
Stabilized power supply
Input: 120/230 V AC
Output: 24 V DC/40 A
SIPLUS S7-1500 PM 1507
Input: 120/230 V AC
• Exposure to media
6AG1337-3BA00-4AA0
• Output: 24 V DC, 3 A
6AG1332-4BA00-7AA0
• Extended temperature range and
exposure to media
6AG1337-3BA00-7AA0
• Output: 24 V DC, 8 A
6AG1333-4BA00-7AA0
Extended temperature range and
exposure to media
SIPLUS PS PSU200M 1-phase
and 2-phase, 24 V DC/5 A
SIPLUS S7-1500 system
power supply
Stabilized power supply
Input:
120 ... 230 V/230 … 500 V AC
6AG1333-3BA10-7AA0
• Output: 24 V DC / 10 A
6AG1334-3BA10-7AA0
• 24 V DC input voltage,
power 25 W
6AG1505-0KA00-7AB0
• 24/48/60 V DC input voltage,
power 60 W
6AG1505-0RA00-7AB0
6AG1437-3BA10-7AA0
• 120/230 V AC input voltage,
power 60 W
6AG1507-0RA00-7AB0
Exposure to media
SIPLUS PS PSU8200 3-phase,
24 V DC/40 A
Stabilized power supply
Input: 400 … 500 V 3 AC
Output: 24 V DC/20 A
13
For supplying the backplane bus
of the S7-1500
• Output: 24 V DC/5 A
Extended temperature range and
exposure to media
Exposure to media
Siemens KT 10.1 · 2016
13/3
© Siemens AG 2016
SIPLUS power supplies
Ordering data
■ Ordering data
Article No.
Article No.
SIPLUS DC/DC converter
SIPLUS modular buffer module
SIPLUS PS 24V/0.375A
For 6AG1961-3BA01-7AA0;
buffer time 100 ms to 10 s,
dependent on load current
6AG1931-2BA00-3AA0
DC/DC stabilized power supply
Input: 48 … 220 V DC
Output: 24 V DC/0.375 A
condensation permissible
SIPLUS PS signaling module
modular
SIPLUS add-on modules
SIPLUS PS E202U
redundancy module
Extended temperature range and
exposure to media
Input/output: 24 V DC/40 A
suitable for decoupling two SITOP
power supplies with a maximum
of 20 A output current
SIPLUS SITOP signaling module
• Extended temperature range and
exposure to media
6AG1961-3BA21-7AX0
• Exposure to media
6AG1961-3BA21-4AX0
SIPLUS PSE200U 3 A
6AG1961-2BA31-7AA0
6AG1961-3BA10-6AA0
Hard gold-plated contacts;
for 6AG1XXX-3BA00 -XXXX
signaling contacts:
Output voltage ok,
operational availability ok,
remote ON/OFF
SIPLUS DC-UPS, uninterruptible power supply
4-channel selectivity module
Input: 24 V DC
Output: 24 V DC/3A per channel
output current adjustable 0.5 ... 3 A
SIPLUS PS DC UPS module 15 A
Exposure to media
6AG1961-2BA41-7AA0
4-channel selectivity module
Input: 24 V DC
Output: 24 V DC/10 A per channel
output current adjustable 3 ... 10 A
Exposure to media
13
Siemens KT 10.1 · 2016
6AG1931-2EC21-2AA0
Uninterruptible power supply
without interface
Input: 24 V DC/16 A,
Output: 24 V DC/15 A
Extended temperature range and
exposure to media
SIPLUS PS DC UPS module 40 A
Uninterruptible power supply
without interface;
Input: 24 V DC/43 A,
Output: 24 V DC/40 A
Extended temperature range and
exposure to media
13/4
6AG1961-3BA10-7AA0
For 6AG1XXX-3BA00 -XXXX
signaling contacts:
Output voltage ok,
operational availability ok,
remote ON/OFF
Exposure to media
SIPLUS PSE200U 10 A
6AG1961-3BA01-7AA0
6AG1931-2FC21-7AA0
14
© Siemens AG 2016
Power supplies for AS interface
14/2
14/3
1-phase / 1-2-phase / DC, 
AS-i 30 V (with data decoupling)
1-phase, 30 V DC 
(without data decoupling)
Siemens KT 10.1 · 2016
© Siemens AG 2016
Power supplies for AS interface
1-phase / 1-2-phase / DC, AS-i 30 V (with data decoupling)
■ Overview
■ Benefits
AS-Interface power supply unit for 3 A
AS-Interface power supply units feed 30 V DC into the 
AS-Interface cable and supply the AS-Interface components.
They contain performance-optimized data decoupling for
separating communication signals and supply voltage. As the
result, AS-Interface is able to convey both data and power along
a single line. The power packs are overload and short-circuit
proof.
Dimensions
AS-Interface power supply units have compact dimensions in
widths of 50 / 70 / 120 mm. No clearance to other devices is
required when mounting.
14
Features
• Higher rating: The power supply units deliver currents 
of 2.6 to 8 A.
• Integrated data decoupling: As the result, AS-Interface is able
to convey both data and power along a single line.
• Integrated ground-fault detection: The power supply units
perform the reliable detection and signaling of ground faults
according to IEC 60204-1. The AS-Interface voltage can be
disconnected automatically in the event of a ground fault.
• Integrated overload detection: An output overload is identified
and signalized over a diagnostics LED.
• Diagnostics memory: Any ground faults or overloads on the
output side are stored in a diagnostics memory until the
device is RESET.
• Remote RESET and remote signaling: A ground fault can be
signalized and evaluated by relay contacts over a central
control and/or indicator light.
• Diagnostics LEDs: Three different LEDs indicate the status of
the AS-Interface power supply locally at the power supply unit.
• Ultra-wide input range / 2-phase connection: The ultra-wide
input range of 120 to 500 V of the 8 A version means that the
supply units can be used in virtually any network worldwide.
In addition, this version dispenses with the need for an N
conductor as the device can be connected directly between
2 phases of a network.
• Operation with 24 V DC: The 3 A power supply unit is also
available as a version with a 24 V DC input. This power supply
unit is suitable for use in battery-operated plants or plants with
uninterrupted power supply (UPS).
• Removable terminal blocks in spring-type connection: The
power supply units are equipped with three removable
terminal blocks for simple device replacement: for the input
side, for the output side and for Signal/RESET connections.
• Complete solution for supplying AS-Interface networks while
making full use of the maximum possible cable length per 
AS-i segment
• Only AS-i masters and AS-i slaves need to be connected to
the AS-Interface cable to operate AS-Interface
• Compact, room-saving footprint
• Reliable power supply even for large numbers of AS-Interface
modules with high power requirements
• Increased safety and savings on additional components
owing to the integrated ground fault and overload detection
• Fast fault detection and reduced downtimes thanks to
diagnostics memory, remote signaling and remote RESET
• Reduced downtimes as the result of removable terminal
blocks which enable the fast exchanging of devices
• Ultra-wide input range of the 8 A version permits single-phase
and two-phase operation and removes the need for an N
conductor
• Can be used world-wide thanks to, for example, UL/CSA
approval (UL 508)
• With the 2.6 A version, the output power is restricted to max.
100 W for use in Class 2 circuits in accordance with NEC
(National Electrical Code)
■ Ordering data
Article No.
AS-Interface 
power supply units, IP20
• AS-i single output 30 V DC
• With integrated ground-fault
detection
• With spring-type terminals, 
removable terminals,
• 2.6 A version with output power
restricted to max. 100 W 
(for Class 2 circuits 
in accordance with NEC)
Dimensions:
Width: 
50 mm (2.6 A / 3 A), 
70 mm (5 A), 
120 mm (8 A);
Height: 125 mm;
Depth: 125 mm
• Output current: 
2.6 A / max. 100 W
Input voltage:
120 / 230 V AC (selectable)
3RX9501-2BA00
• Output current: 
3 A
Input voltage:
120 / 230 V AC (selectable)
3RX9501-0BA00
• Output current: 
3 A
Input voltage:
24 V DC
3RX9501-1BA00
• Output current: 
5 A
Input voltage:
120 / 230 V AC (selectable)
3RX9502-0BA00
• Output current: 
8 A
Input voltage:
120 / 230 ... 500 V AC
(selectable)
3RX9503-0BA00
■ More information
More information on AS-Interface, see Catalog IC 10, 
Chapter 2 "Industrial Communication".
14/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
Power supplies for AS interface
1-phase, 30 V DC (without data decoupling)
■ Overview
■ Application
PSN130S 30 V power supply units for 3 A, 4 A and 8 A
Data decoupling modules S22.5 and DCM 1271
The PSN130S 30 V power supplies feed 30 V DC into the 
AS-Interface cable and supply the AS-Interface components,
but do not include data decoupling. Additional data decoupling
units are needed to separate communication signals and supply
voltage, see "S22.5 Data Decoupling Modules" or "DCM 1271
Data Decoupling Module", see Accessories, page 14/4
A data decoupling module is also required in order to use a
PSN130S 30 V power supply unit for AS-Interface.
The power supplies are overload and short-circuit proof.
Dimensions
The 30 V power supply units have compact dimensions in widths
of 50 and 70 mm. No distances to other devices must be observed during the installation.
Features
• Primary-clocked power supplies for connecting to a singlephase AC power supply system
• Power for currents of 3 A, 4 A and 8 A
• The output voltage is floating, and resistant to short-circuits
and no-load operation. In the event of an overload, the output
voltage will be reduced or switched off. After a short-circuit or
overload the devices will start up again automatically.
• In the event of a device fault, the output voltage will be limited
to max. 37 V.
• Modular installation devices in degree of protection IP20 and
safety class I
• Diagnostics: With an output voltage > 26.5 V DC, the green
LED (30V O.K.) is lit and the signaling contact 13-14 is closed.
With the aid of the data decoupling module, the 
AS-Interface network can be supplied with 30 V DC from a standard power supply unit and the transmission of data and power
can be realized along one cable.
Alternatively, it is also possible to use a standard 24 V DC power
supply unit (AS-i Power24V). However, in this case please note
that all components involved must be designed for the reduced
voltage and that the maximum length of an AS-i Power24V
network is limited to 50 m.
The power supply units must comply with the PELV (Protective
Extra Low Voltage) or SELV (Safety Extra Low Voltage) standards,
have a residual ripple of < 250 mVpp and in the event of a fault,
must limit the output voltage to a maximum of 40 V.
The combination of data decoupling modules and standard power
supply units is therefore a cost-efficient alternative to the serviceproven AS-Interface power supply units.
The quality of the data signals and the reliable operation of the
AS-i network are not negatively affected as the result.
Configuration examples of AS-Interface networks 
with a 30 V power supply unit
PROFINET
■ Benefits
PSN130S
30 V power
supply unit
IC01_00221
• Low-cost alternative solution for supplying AS-Interface
networks while making full use of the maximum possible cable
length per AS-i segment
• Cost advantage particularly for multiple networks
• Compact, space-saving dimensions
• Reliable power supply even for large numbers of AS-Interface
modules with high power requirements
• Can be used worldwide thanks to, for example, UL/CSA
approval (UL 508)
IE/AS-i LINK PN IO double master
and
double data decoupling module
AS-Interface
AS-Interface
Configuration of AS-Interface multiple networks, each with one PSN130S
30 V power supply unit (examples with schematic representation):
Double network based on S22.5 double data decoupling module and
double master IE/AS-i LINK PN IO
Siemens KT 10.1 · 2016
14/3
14
© Siemens AG 2016
Power supplies for AS interface
1-phase, 30 V DC (without data decoupling)
■ Ordering data
■ Application (continued)
Article No.
PSN130S 30 V DC 
power supply units 
(without AS-i data decoupling)
S7-1200 and
CM 1243-2 multiple AS-i master with
DCM 1271 data decoupling module
IC01_00222
Output voltage 30 V DC, 
with screw terminals,
Dimensions: 
Width: 50 mm (3 A / 4 A), 70 mm (8 A);
Height: 125 mm; Depth: 126.5 mm
PSN130S
30 V power supply unit
AS-Interface
• Output current: 3 A
Input voltage:120 / 230 V AC 
(automatic selection)
3RX9511-0AA00
AS-Interface
• Output current: 4 A
Input voltage: 120 / 230 V AC 
(automatic selection)
3RX9512-0AA00
AS-Interface
• Output current: 8 A
Input voltage: 120 / 230 V AC 
(automatic selection)
3RX9513-0AA00
Configuration of AS-Interface multiple networks, each with one PSN130S
30 V power supply unit (examples with schematic representation):
Triple network based on SIMATIC S7-1200 with DCM 1271 data
decoupling modules and CM 1243-2 communication processors
■ Accessories
■ Technical specifications
PSN130S 30 V DC 
power supply unit
3A
4A
8A
Product
Version
Input data
• Input voltage, rated value Ue
V AC
• Input voltage range
V AC
• Mains frequency
Hz
• Power consumption at full load, typ. W
Output data
• Output voltage, rated value Ua
V DC
• Residual ripple
mVss
• Output current, rated value 
A
at -20 ... +60 °C
• Max. output current at +60 ... +70 °C A
Degree of efficiency in rated conditions
• Degree of efficiency
%
• Power loss, typ.
W
Protection and monitoring
• Output overvoltage protection
V
• Current limit, typ.
A
Safety
• Electrical separation 
primary / secondary
14
• Protection class
• Degree of protection
Approvals
• UL
• Pollution degree
• Overvoltage category and 
electrical separation
EMC
• Emitted interference (class B)
• Line harmonics limit
• Interference immunity
Operating data
Ambient temperature
• Operation
• Transport / storage
Pollution degree
Humidity class
Dimensions and weight
• Width
• Height x depth
• Weight
14/4
120 / 230 V, single-phase,
automatic selection
85 ... 132 / 174 ... 264
50 / 60
103
139
270
30
< 150
3
4
8
3
3
4
87
12
88
17
90
25
< 37
4
5,5
11
Data decoupling modules in enclosure, 22.5 mm
S22.5 data decoupling modules
With screw terminals, 
removable terminals, 
Dimensions: 
Width: 22.5 mm;
Height: 101 mm; Depth: 115 mm
• Single data decoupling module, 
1x4A
3RK1901-1DE12-1AA0
• Double data decoupling module, 
2x4A
3RK1901-1DE22-1AA0
With spring-type terminals, 
removable terminals, 
Dimensions: 
Width: 22.5 mm;
Height: 105 mm; Depth: 115 mm
• Single data decoupling module, 
1x4A
3RK1901-1DG12-1AA0
• Double data decoupling module, 
2x4A
3RK1901-1DG22-1AA0
Data decoupling modules in enclosure for S7-1200
Output voltage PELV / SELV
according to IEC 60950 
and EN 50178
I
IP20
UL 508 / CSA 22.2
IEC 60950
EN 50178 and IEC 61558
DCM 1271 data decoupling module 3RK7271-1AA30-0AA0
With screw terminals, 
removable terminals
(included in the scope of supply), 
Dimensions:
Width: 30 mm; 
Height: 100 mm; Depth: 75 mm
Screw terminals (replacement) 
for AS-i DCM 1271 data 
decoupling module
• 5-pole
IEC 61000-6-3
IEC 61000-3-2
IEC 61000-6-2
°C
°C
mm
mm
kg
Siemens KT 10.1 · 2016
Article No.
-20 ... +70
-40 ... +85
2
Climate class according to 
DIN 50010, relative air humidity
max. 100 %, without condensation
50
50
125 x 126.5
0.4
0.4
3RK1901-3MA00
• 3-pole
3RK1901-3MB00
for connecting the power supply unit
70
0.7
■ More information
For operating instructions and other technical information see
http://support.automation.siemens.com/WW/view/en/64364000.
More information on AS-Interface, see Catalog IC 10, 
Chapter 2 "Industrial Communication".
15
© Siemens AG 2016
Technical information
and configuration
15/2
15/5
15/8
15/9
SITOP
V1
+
Load
-
SITOP
V2
+
15/10
15/11
15/12
15/13
15/18
15/19
Power supplies general
Supply systems data, 
line-side connection
Possible mains disturbances and causes
Installation guidelines, mouning areas
and fixing options
Parallel connection
Series connection to increase the voltage
Battery charging with SITOP
Fusing of the output circuit 24 V DC, 
selectivity
Standards and approvals
Certificates
G_KT01_EN_00017
Siemens KT 10.1 · 2016
© Siemens AG 2016
Technical information and configuration
Power supplies general
■ Overview
Power supplies
Non-stabilized DC power supplies
In plant building or mechanical equipment manufacture, or in
any other situations in which electrical controls are used, a safe
and reliable power supply is needed to supply the process with
power.
The AC mains voltage is transformed using 50 Hz/60 Hz safety
transformers to a protective extra-low voltage and smoothed
with down-circuit rectification and capacitor filtering.
The operational reliability of electronic controls and associated
reliable operation of automated plants is extremely closely linked
to the resistance of the load current supply to failure. Final control elements as well as input and output modules will only
respond to command signals if the power supply is operating
reliably.
In addition to requirements such as safety, particular demands
are placed on the electromagnetic compatibility (EMC) of the
power supply with reference to the tolerance range of the output
voltage, as well as its ripple.
Important factors that determine problem-free implementation
are, in particular:
• An input current with a low harmonic content
• Low emitted interference
• Adequate immunity (noise immunity) to interference
EMC
Interference phenomena
Emission (emitted interference)
Interference caused by television
and radio reception
In the case of non-stabilized DC power supplies, the DC output
voltage is not stabilized at a specific value, but the value is varied in accordance with the variation in (mains) input voltage and
the loading.
The ripple is in the Volt range and is dependent on the loading.
The value for the ripple is usually specified as a percentage of
the DC output voltage level. Non-stabilized DC power supplies
are characterized by their rugged, uncomplicated design that is
limited to the important factors and focused on a long service
life.
Line isolation
Rectification
50 Hz
~
Filtering
+
Vout
Interference coupling on data lines
or power supply cables
Noise immunity (immunity to interference)
Faults on the power cable due to
switching non-resistive loads such
as motors or contactors
G_KT01_EN_00067
Static discharge due to lightning
strikes
Block diagram of a non-stabilized power supply
Electrostatic discharge through
the human body
Stabilized DC power supplies
Conducted interference induced
by radio frequencies
Selected interference phenomena
General notes on DC power supplies
The DC power supply is a static device with one or more inputs
and one or more outputs that converts a system of AC voltage
and AC current and/or DC voltage and DC current to a system
with different DC voltage and DC current values by means of
electromagnetic induction for the purpose of transmitting electrical energy.
The type of construction of a DC power supply is primarily
decided by its intended use.
Stabilized DC power supplies have electronic control circuits
that maintain the DC voltage at the output at a specific value with
as little variation as possible. Effects such as variation in input
voltage or changes in load at the output are electrically compensated in the specified function area.
The ripple in the output voltage for stabilized DC power supplies
lies in the millivolt range and is mainly dependent on the loading
at the outputs.
Stabilized DC power supplies can be implemented on different
functional principles. The most common types of circuit are:
• Linear stabilized power supplies
• Magnetic voltage stabilizers
• Secondary pulsed switched-mode power supplies
• Primary pulsed switched-mode power supplies
The most suitable principle for a particular application case will
depend mainly on the application. The objective is to generate a
DC voltage to supply the specific load as inexpensively and as
accurately as possible.
15
15/2
Siemens KT 10.1 · 2016
© Siemens AG 2016
Technical information and configuration
Power supplies general
■ Overview (continued)
The complete transformer comprises two components. The
"ferro resonator" and a series-connected auxiliary regulator. The
input winding and the resonance winding of the magnetic stabilizer are decoupled to a large extent by means of the air gap.
The magnetic stabilizer supplies a well-stabilized AC voltage.
This is rectified and filtered. The transformer itself is operated in
the saturation range.
Power supplies with in-phase regulation
Rectifier
Actuator
Filtering
Transformer
Stabilized
Unstabilized
mains
Uout
Load
The magnetic stabilizer technique is reliable and rugged but is
also large-volume, heavy and relatively expensive.
G_KT01_EN_00177
Block diagram Transformer with in-phase regulation
The transformer with in-phase regulation operates according to
a conventional principle. The supply is provided from an AC supply system (one, two or three conductor supply).
A transformer is used to adapt it to the required secondary voltage.
The rectified and filtered secondary voltage is converted to a stabilized voltage at the output in a regulation section. The regulation
section comprises a final control element and a control amplifier.
The difference between the stabilized output voltage and the nonstabilized voltage at the filter capacitor is converted into a thermal
loss in the final control element. The final control element functions
in this case like a rapidly changeable ohmic impedance. The thermal loss that arises in each case is the product of output current
and voltage drop over the final control element.
This system is extremely adaptable. Even without further modifications, several output voltages are possible. In the case of multiple
outputs, the individual secondary circuits are usually generated
from separate secondary windings of the input transformer. Some
applications can only be resolved in accordance with this circuit
principle. Especially when highly accurate regulation, minimal
residual ripple and fast compensation times are required.
The efficiency is, however, poor and the weight and volume are
considerable. The transformer with in-phase regulation is therefore only an economical alternative at low power ratings.
Advantages:
• Simple, well-proven circuit principle
• Good to excellent control characteristics
• Fast compensation time
Disadvantages:
• Relatively high weight and large construction volume due to
the 50 Hz transformer
• Poor efficiency, heat dissipation problems
• Low storage time
Magnetic stabilizer
Unstabilized
mains
in case of
readjustment
Stabilized
output
voltage
stabiUoutlized
Load
Block diagram: Magnetic stabilizer
G_KT01_XX_00178
Ferroresonator
The ferro resonator frequently has a transformer with in-phase
regulation connected downstream to improve the control accuracy. Secondary pulsed switched-mode regulators are frequently also connected downstream.
Advantages:
• Good to excellent control characteristics in combination with
transformer with in-phase regulation connected downstream
• Significantly better efficiency than a transformer with in-phase
regulation alone
Disadvantages:
• The ferro resonator is frequency dependent
• The power supplies are large and heavy due to the magnetic
components
Secondary pulsed switched-mode power supplies:
Filtering
Secundary
Switching switched-mode
Rectification transistor
regulator
Transformer
Unstabilized
mains
Uout stabilized
Load
Control
G_KT01_EN_00179
Block diagram Secondary pulsed switched-mode power supplies
Isolation from the supply system is implemented in this case with
a 50 Hz transformer. Following rectification and filtering, the energy is switched at the output by means of pulsing through a
switching transistor in the filtering and storage circuit. Thanks to
the transformer at the input that acts as an excellent filter, the
mains pollution is low.
The efficiency of this circuit is extremely high.
This concept offers many advantages for power supplies with
numerous different output voltages.
To protect the connected loads, however, care must be taken; in
the event of the switching transistor breaking down, the full, nonstabilized DC voltage of the filter capacitor will be applied to the
output. However, this danger also exists in the case of linear
stabilized power supplies.
Advantages:
• Simple design and high efficiency
• Multiple outputs, also galvanically isolated from one another,
are easily implemented by means of several secondary
windings
• Fewer problems with interference than with primary pulsed
switched-mode power supplies
Disadvantages:
• The 50 Hz transformer makes the power supplies relatively
large and heavy
• The output ripple (spikes) correspond to those of a primary
pulsed switched-mode power supply
Siemens KT 10.1 · 2016
15/3
15
© Siemens AG 2016
Technical information and configuration
Power supplies general
■ Overview (continued)
Primary pulsed switched-mode power supplies:
The term SMPS (Switch Mode Power Supply) or primary
switched-mode regulator is often used in the literature.
Single-ended-forward
stabilized
UOUT
Load
Unstabilized
mains
G_KT01_EN_00180
Control
Block diagram: Single-ended forward converter
The primary switched-mode regulators are available in many different circuit versions. The most important basic circuits are single-ended forward converters, flyback converters, half-bridge
converters, full-bridge converters, push-pull converters and resonance converters.
The general principle of operation of the primary switched-mode
regulator is shown in the block diagram of the single-ended forward converter:
The non-stabilized supply voltage is first rectified and filtered.
The capacitance of the capacitor in the DC link determines the
storage time of the power supply on failure of the input voltage.
The voltage at the DC link is approximately 320 V DC for a 230 V
supply. A single-ended converter is then supplied with this
DC voltage and transfers the primary energy through a transformer to the secondary side with the help of a pulse width regulator at a high switching frequency. The switching transistor has
low power losses when functioning as a switch so that the power
balance lies between > 70% and at least 90%, depending on the
output voltage and current.
The volume of the transformer is small in comparison with a
50 Hz transformer due to the high switching frequency because
the transformer size, taking into account the higher switching
frequency, is smaller. Using modern semiconductors, clock
frequencies of 100 kHz and above can be achieved. However,
switching losses increase at excessively high clock frequencies
so that in each case a compromise has to be made between
high efficiency and the largest possible clock frequency. In most
applications, the switching frequencies lie between approximately 20 kHz and 250 kHz depending on the output power.
The voltage from the secondary winding is rectified and filtered.
The system deviation at the output is fed back to the primary
circuit through an optocoupler. By controlling the pulse width
(conducting phase of the switching transistor in the primary
circuit), the necessary energy is transferred to the secondary
circuit and the output voltage is regulated. During the nonconducting phase of the switching transistor, the transformer is
demagnetized through an auxiliary winding. Exactly the same
amount of energy is transferred as is removed at the output. The
maximum pulse width for the pulse duty factor for these circuits
is < 50%.
15
15/4
Siemens KT 10.1 · 2016
Advantages:
• Small magnetic components (transformer, storage reactor,
filter) thanks to the high operating frequency
• High efficiency thanks to pulse width regulation
• Compact equipment units
• Forced-air cooling is not necessary up to the kW range
• High storage times are possible in case of power failure by
increasing the capacitance in the DC link
• Large input voltage range possible
Disadvantages:
• High circuit costs, many active components
• High costs for interference suppression
• The mechanical design must be in accordance with HF
criteria
Primary switched-mode power supplies have taken over from
the other switching modes in recent years. This is due, in particular, to their compact size, minimal weight, high efficiency and
excellent price/performance ratio.
Summary
The most important characteristics of the circuit types described
above are summarized in the table.
Comparison
criteria
Connection methods
Primaryswitched
mode
Secondaryswitched
mode
Transformer Magnetic
with in-phase stabilizer
regulation
Input voltage
range
Very large
Average
Very small
Large
Regulation
speed
Average
Average
Very fast
Slow
Storage time
after power
failure
Very long
Long
Very short
Long
Residual
ripple
Average
Average
Very low
Average
Power loss
Very small
Small
Large
Very small
Size
Very small
Average
Very large
Large
Weight
Very light
Average
Heavy
Very heavy
Interference
suppression
overhead
Very large
Average
Low
Average
Comparison criteria for basic circuit versions
© Siemens AG 2016
Technical information and configuration
Supply systems data, line-side connection
■ Overview
Supply systems data
When dimensioning and selecting plant components, the supply
systems data, supply system conditions and operating modes
must be taken into account for these components.
The most important data for a supply system include the rated
voltage and rated frequency. These data for the supply system
are designated as rated values in accordance with international
agreements.
International supply voltages and frequencies in low-voltage
systems
Country
Line voltage
Western Europe:
Belgium
50 Hz 230/400 – 127-220 V
Denmark
50 Hz 230/400 V
Germany
50 Hz 230/400 V
Usual rated voltages and rated frequencies
Finland
50 Hz 230/400-5001) – 6601) V
In Europe the EN 60038 standard "CENELEC standard voltages"
applies.
France
50 Hz 127/220 – 230/400 – 5001)
– 380/6601) – 525/9101) V
Greece
50 Hz 230/400 – 127/2202) V
Great Britain
50 Hz 230/400 V
Ireland
50 Hz 230/400 V
Iceland
50 Hz 127/2202) – 230/400 V
Italy
50 Hz 127/220 – 230/400 V
Luxembourg
50 Hz 230/400 V
The Netherlands
50 Hz 230/400 – 6601) V
Northern Ireland
50 Hz 230/400 – Belfast 220/380 V
Norway
50 Hz 230-230/400-5001) – 6901) V
Austria
50 Hz 230/400 – 5001) – 6901) V
Portugal
50 Hz 230/400 V
Sweden
50 Hz 230/400 V
Switzerland
50 Hz 230/400 – 5002) V
Spain
50 Hz 230/400 V
The international standard IEC 60038, Edition 7, 2009, "IEC standard voltages" was substantially included in this standard.
The IEC 60038 standard is the result of an international agreement to reduce the diverse rated voltage values that are in use
for electrical supply networks and traction power supplies, load
installations and equipment.
In the low-voltage range, it is emphasized in IEC 60038 that
the 220 V/380 V voltages (formerly in continental Europe) and
240 V/415 V voltages (formerly in the UK) for three-phase electricity supplies have been replaced by a single standardized
value of 230 V/400 V. The network frequency in Europe is 50 Hz.
The tolerances for the rated voltages of the supply systems that
were specified for the transition period up to 2003 were intended
to ensure that equipment rated for the existing voltages could be
operated safely until the end of its service life.
Year
Rated voltage
Tolerance range
Up to 1987
220 V/380 V
-10% to +10%
1988 to 2003
230 V/400 V
-10% to + 6%
Since 2003
230 V/400 V
-10% to +10%
Conversion of low-voltage systems
Supply voltages in excess of 400 V (e.g. 500 V, 690 V) are only
used in Europe in large industrial concerns.
The IEC recommendation 230 V/400 V has been implemented as
a national regulation in the most important countries, as far as
the conditions in the country allow.
In North and Central America and some northern nations in
South America the rated value of the AC mains supply is 120 V;
the doubled mains voltage of 240 V is common among larger
consumers. As a rule, the low-voltage networks in these countries are implemented as single-phase three-wire networks. A
three-phase alternating current is often not available to smaller
users, if at all, so the voltage is 208 V or 415 V, while three-phase
networks at 480 V are usual for larger consumers. The network
frequency is 60 Hz.
Eastern Europe:
Albania
50 Hz 230/400 V
Bulgaria
50 Hz 230/400 V
Russian Federation
50 Hz 230/400 – 6901) V
Croatia
50 Hz 230/400 V
Poland
50 Hz 230/400 V
Romania
50 Hz 230/400 V
Serbia
50 Hz 230/400 V
Slovakia
50 Hz 230/400 – 5001) – 6901) V
Slovenia
50 Hz 230/400 V
Czech Republic
50 Hz 230/400 – 5001) – 6901) V
Hungary
50 Hz 230/400 V
1)
2)
Industry only
No further expansion
In Asia AC mains voltages of 100 V or 110 V (50 Hz or 60 Hz) are
also the norm.
In addition, numerous country-specific and regional peculiarities
exist around the world, details of which can be obtained from the
local operators if necessary.
15
Siemens KT 10.1 · 2016
15/5
© Siemens AG 2016
Technical information and configuration
Supply systems data, line-side connection
■ Overview (continued)
Country
Line voltage
Country
Middle East:
Line voltage
North America:
Afghanistan
50 Hz 220/380 V
Canada
60 Hz 600 – 120/240 – 460 – 575 V
Bahrain
50 Hz 230/400 V
USA
Cyprus
50 Hz 240/415 V
60 Hz 120/208 – 120/240
– 277/480 – 6001) V
Iraq
50 Hz 220/380 V
Israel
50 Hz 230/400 V
Central America:
50 Hz 220/380 V
Jordan
Kuwait
50 Hz 240/415 V
Bahamas
60 Hz 115/200 – 120/208 V
Barbados
50 Hz 110/190 – 120/208 V
Belize
60 Hz 110/220 – 220/440 V
Costa Rica
60 Hz 120/2082) – 120/240 – 127/220
– 254/4402) – 227/4801) V
Lebanon
50 Hz 110/190 – 220/380 V
Oman
50 Hz 220/380 – 240/415 V
Dominican Republic
60 Hz 120/208 – 120/240 – 4801) V
Qatar
50 Hz 240/415 V
Guatemala
Saudi Arabia
60 Hz 127/220 – 220/380 – 4801) V
(220/380 – 240/415 V 50 Hz:
a few remaining areas only)
60 Hz 120/208 – 120/240 – 127/220
– 277/4801) – 4801) – 5501) V
Haiti
50 Hz 220/380 V (Jacmel), 60 Hz
110/220 V
Honduras
60 Hz 110/220 – 127/220 – 277/480 V
Jamaica
50 Hz 110/220 – 4401) V
Cuba
60 Hz 120/240 – 220/380 – 277/4801)
– 4401) V
Mexico
60 Hz 127/220 – 4401) V
Nicaragua
60 Hz 110/220 – 120/240 – 127/220
– 220/440 – 254/401) V
Panama
60 Hz 120/2081) – 120/240
– 254/4401 – 277/4801) V
Syria
50 Hz 115/200 – 220-380 – 4001) V
Turkey
50 Hz 220/380 V (parts of Istanbul:
110/190 V)
United Arab Emirates
(Abu Dhabi; Ajman; Dubai; Fujairah;
Ras al Khaymah; Sharjah;
Um al Qaywayn)
50 Hz 220/380 – 240/415 V
Yemen (North)
50 Hz 220/380 V
Yemen (South)
50 Hz 230/400 V
Far East:
50 Hz 230/400 V
Bangladesh
Burma
50 Hz 230/400 V
People's Republic of China
50 Hz 127/220 – 220/380 V
(in mining: 1140 V)
Puerto Rico
60 Hz 120/208 – 480 V
El Salvador
60 Hz 110/220 – 120/208 – 127/220
– 220/440 – 240/4801) – 254/4401) V
Trinidad
60 Hz 110/220 – 120/240 – 230/400 V
South America:
Hong Kong
50 Hz 200/346 V
India
50 Hz 220/380 – 230/400 – 240/415 V
1)
Indonesia
50 Hz 127/220 – 220/380 – 400 V
Japan
50 Hz 100/200 – 4001) V
South Honshu, Shikoku, Kyushu,
Hokkaido, North Honshu
60 Hz 110/220 – 4401) V
Cambodia
50 Hz 120/208 V – Phnom Penh
220/238 V
Argentina
50 Hz 220/380 V
Bolivia
60 Hz 220/380 – 480 V, 50 Hz 110/220
– 220/380 V (exception)
Brazil
60 Hz 110/220 – 220/440 – 127/220
– 220/380 V
Chile
50 Hz 220/380 V
Ecuador
60 Hz 120/208 – 127/220 V
Guyana
50 Hz 110/220 V (Georgetown), 60 Hz
110/220 – 240/480 V
Korea (North)
60 Hz 220/380 V
Korea (South)
60 Hz
100/2002)
Columbia
60 Hz 110/220 – 150/260 – 440 V
Malaysia
50 Hz 240/415 V
Paraguay
60 Hz 220/380 – 220/440 V
People's Republic of Mongolia
50 Hz 220/380 V
Peru
60 Hz 220 – 220/380/440 V
Pakistan
50 Hz 230/400 V
Surinam
60 Hz 115/230 – 127/220 V
Philippines
60 Hz 110/220 – 440 V
Uruguay
50 Hz 220 V
Singapore
50 Hz 240/415 V
Venezuela
Sri Lanka
50 Hz 230/400 V
60 Hz 120/208 – 120/240 – 208/416
– 240/480 V
Taiwan
60 Hz 110/220 – 220 – 440 V
Thailand
50 Hz 220/380 V
Vietnam
50 Hz 220/380 V
15
15/6
Siemens KT 10.1 · 2016
– 220/380 –
4401)
V
1)
2)
Industry only
No further expansion
© Siemens AG 2016
Technical information and configuration
Supply systems data, line-side connection
■ Overview (continued)
Country
Line voltage
Africa:
Egypt
50 Hz 110/220 – 220/380 V
Ethiopia
50 Hz 220/380 V
Algeria
50 Hz 127/220 – 220/380 V
Angola
50 Hz 220/380 V
Benin
50 Hz 220/380 V
Ivory Coast
50 Hz 220/380 V
Gabon
50 Hz 220/380 V
Ghana
50 Hz 127/220 – 220/380 V
Guinea
50 Hz 220/380 V
Kenya
50 Hz 220/380 V
Cameroon
50 Hz 127/220 – 220/380 V
Congo
50 Hz 220/380 V
Liberia
60 Hz 120/208 – 120/240 V
Libya
50 Hz 127/2202) – 220/380 V
Madagascar
50 Hz 127/220 – 220/380 V
Malawi
50 Hz 220/380 V
Mali
50 Hz 220/380 V
Morocco
50 Hz 115/200 – 127/220 – 220/380
– 5001) V
Mauritius
50 Hz 240/415 V
Mozambique
50 Hz 220/380 V
Namibia
50 Hz 220/380 V
Niger
50 Hz 220/380 V
Nigeria
50 Hz 220/415 V
Rwanda
50 Hz 220/380 V
Zambia
50 Hz 220/380 V – 415 – 5501) V
Senegal
50 Hz 127/220 – 220/380 V
Sierra Leone
50 Hz 220/380 V
Somalia
50 Hz 220-220/440 V
Sudan
50 Hz 240/415 V
South Africa
50 Hz 220/380 – 5001) – 550/9501) V
Swaziland
50 Hz 220/380 V
Tanzania
50 Hz 230/400 V
Togo
50 Hz 127/220 – 220/380 V
Tunisia
50 Hz 115/200 – 220/380 V
Uganda
50 Hz 240/415 V
Zaire
50 Hz 220/380 V
Zimbabwe
50 Hz 220/380 V
1)
2)
Connection and fusing on the line side
All SITOP and LOGO!Power supplies are built-in devices. Compliance with the pertinent country-specific regulations is essential for installation and electrical connection of the devices.
During installation, protective gear and isolating gear must be
provided for activating the power supply.
Power supply units cause a current inrush immediately after connection of the input voltage due to charging of the load capacitor, however, it falls back to the rated input current level after a
few milliseconds. Aside from the internal impedances of the
power supply, the inrush current is dependent on the size of the
input voltage applied as well as the source impedance of the
supply network and the line impedance of the supply line. The
maximum inrush current for the power supplies is specified in
the applicable technical data. It is important for dimensioning
upstream protective devices.
Single-phase SITOP and LOGO!Power supplies are equipped
with internal device protection (fuses). For connection to the
supply system, only one protective device (fuse or MCB) must
be provided for line protection in accordance with the rated current of the installed cable. The circuit-breakers recommended in
the data sheets and operating instructions have been selected
such that even during the maximum current inrush that can occur under worst-case conditions on switching on the supply voltage, the circuit-breaker will not trip. A two-pole connected miniature circuit-breaker is required for the connection of certain
device types.
3-phase SITOP power supplies do not have internal device
protection. The up-circuit protective device (3-phase coupled
miniature circuit breaker or motor protection switch) protects the
cables and devices. The protective devices specified in the data
sheets and operating instructions are optimized to the characteristics of the relevant power supplies.
Industry only
No further expansion
15
Siemens KT 10.1 · 2016
15/7
© Siemens AG 2016
Technical information and configuration
Possible mains disturbances and causes
■ Overview
The quality of the mains voltage has become a decisive factor in
the functioning, reliability, maintenance costs and service life of
highly sensitive electronic installations and devices (computers,
industrial controls, instrumentation, etc.).
Mains disturbances cause system failures and affect the function of plants as well as electronic loads. They can also result in
total failure of the installation or equipment.
The most frequent types of disturbance are:
• Long-term overvoltages
• Long-term undervoltages
• Interference pulses and transients
• Voltage dips and surges
• Electrical noise
• Momentary network failure
• Long-term network failure
Mains disturbances can be caused by a number of things, e.g.:
• Switching operations in the supply system
• Long cable paths in the supply system
• Environmental influences such as thunderstorms
• Mains overloads
Typical causes of mains disturbances generated in-house are:
• Thyristor-controlled drives
• Elevators, air-conditioning, photocopiers
• Motors, reactive-power compensation systems
• Electrical welding, large machines
• Switching of lighting equipment
Disturbances in mains voltages can occur individually or in combination. Possible reasons for these disturbances, their effects
and countermeasures can include:
System disturbances
Percentage of total
disturbance
Result
Measure
Overvoltage
Approx. 15% - 20%
Can result in overheating and even
thermal destruction of individual
components. Causes total failure.
SITOP power supplies with their
wide operating voltage range offer
sufficient protection against minor
network overvoltages outside the
permissible tolerance
Approx. 20% - 30%
Can result in undefined operating
states of loads. Causes data errors.
Use of a SITOP DC-UPS
(uninterruptible DC power supply)
see Section 11
Approx. 30% - 35%
Can result in undefined operating
Use of surge protectors, see
states of the loads and can lead to the Catalog LV 10.1 2013, Section 6
destruction of components.
Approx. 15% - 30%
Can result in undefined operating
Thanks to their internal buffer time,
states and destruction of components. SITOP power supplies offer suffiCause data errors.
cient protection against short
power failures
Approx. 20% - 35%
Can result in undefined operating
states of loads. Causes data errors.
Due to internal switching measures,
SITOP power supplies offer sufficient immunity to electromagnetic
interference
Approx. 8% - 10%
Can result in undefined operating
states of loads, especially those with
insufficient mains buffering. Causes
data errors.
Use of a SITOP buffer module
(in connection with SITOP smart
or SITOP modular)
see Section 10
Approx. 2% - 5%
Can result in undefined operating
states of loads, especially those with
insufficient mains buffering. Causes
data errors.
Use of a SITOP DC-UPS
(uninterruptible DC power supply)
see Section 11
The supply voltage is exceeded by more than
+6% for a prolonged period (acc. to IEC 60038)
Line undervoltage
The supply voltage is undershot by more
than –10% for a prolonged period
(acc. to DIN IEC 60038)
Interference pulses
Energy-rich pulses (e.g. 700 V/1 ms) and
energy-poor transients (e.g. 2500 V/20 µs) result
from switching operations in the supply system
Voltage dips and surges
The voltage level changes suddenly and in an
uncontrolled manner, e.g. due to changes in
loading and long cable routes
Electrical noise
A mix of frequencies superimposed on the mains
due to bad grounding and/or strong HF emitters
such as radio transmitters or thunderstorms
Voltage interruption
Short-term interruption of the supply voltage
(up to approx. 100 ms) due to short-circuiting
in neighboring supply systems or starting of
large electrical machines.
Voltage interruption
Long interruption of the supply voltage
(longer than approx. 100 ms)
15
15/8
Siemens KT 10.1 · 2016
© Siemens AG 2016
Technical information and configuration
Installation guidelines, mouning areas and fixing options
■ Overview
Installation guidelines
Everything for project planning
SITOP und LOGO!Power power supplies are mostly built-in
devices. They must be mounted vertically so that the supply air
can enter the ventilation slots at the bottom of the devices and
leave through the upper part of the devices. The minimum clearances specified in the relevant product documentation (operating instructions, device manuals) for the top and bottom of the
devices must be observed to ensure free air convection. Side
clearance is not required.
Comprehensive information is available for mechanical and
electrical engineering, for example, 3D data, circuit diagram
macros, device manuals, product data sheets and certificates.
The information is available for download via the CAx Download
Manager.
Further information is available on the Internet at
http://www.siemens.com/cax
The option of mounting on standard mounting rails, wall mounting or mounting in non-vertical positions with the appropriate
derating is specified in the respective device manuals.
15
Siemens KT 10.1 · 2016
15/9
© Siemens AG 2016
Technical information and configuration
Parallel connection
■ Overview
Parallel connection for redundant operation
General information on selection of diodes:
Two SITOP power supplies of the same type can be connected
in parallel through diodes for a redundant configuration. 100%
redundancy only exists for two power supplies when the total
load current is no higher than that which one power supply can
supply alone and when the supply for the primary side is also implemented redundantly (i.e. a short-circuit on the primary side
will not trigger a shared fuse which would disconnect both
power supplies from the mains).
The diodes must be dimensioned for the maximum dynamic
current. This can be the dynamic current during power-up in the
short-circuit case, or the dynamic current during a short-circuit
in operation (the larger of the two values should be taken from
the relevant technical specifications).
Parallel connection with decoupling diodes for redundant operation is permitted for all SITOP power supplies. The diodes V1
and V2 are used for decoupling. They must have a blocking voltage of at least 40 V (when decoupling from 24 V power supplies)
and it must be possible to load them with a current equal to or
greater than the maximum output current of the respective
SITOP power supply. For diode dimensioning, see the following
note "General information on selection of diodes".
The ready-to-use add-on "SITOP PSE202U modular redundancy
modules" are available as a simple alternative to diode dimensioning (Article number: 6EP1962-2BA00, 6EP1964-2BA00,
6EP1961-3BA21) for redundant connection of two power
supplies.
SITOP
V1
+
Load
-
SITOP
To dissipate the significant power loss of the decoupling diodes
(sustained short-circuit current x diode conductive-state voltage), the diodes must be equipped with suitably dimensioned
heat sinks.
An additional safety margin is recommended, because the
output capacitor integral to the power supply generates an
additional peak current in the short-circuit case. This additional
current flows only for a few milliseconds so it is within the period
in which diodes are permitted to be loaded with a multiple of the
rated current (8.3 ms, known as the permissible surge current for
diodes).
Example
Two 1-phase SITOP modular power supplies with 10 A rated output current (Article number: 6EP1334-3BA10) are connected in
parallel. The dynamic current in the event of a short-circuit
during operation is approx. 30 A for 25 ms.
The diodes should therefore have a loading capability of 40 A to
be safe, the common heat sink for both diodes must be dimensioned for the maximum possible current of approximately 24 A
(sustained short-circuit current) x diode conductive-state voltage.
Parallel connection for performance enhancement
V2
+
G_KT01_EN_00017
Parallel connection of two SITOP power supplies for redundant operation
To enhance performance, identical types of most SITOP power
supplies can be connected in parallel galvanically (the same
principle as parallel connection for redundant operation, but
without decoupling diodes):
The types permitted for direct galvanic parallel connection are
listed in the relevant technical specifications under "Output,
parallel connection for performance enhancement".
Requirement:
• The output cables connected to terminals "+" and "-" of every
power supply should be installed with an identical length and
cross-section (or the same impedance) to the common
external linking point.
• The power supplies connected in parallel must be switched
simultaneously using a common switch in the mains supply
line (e.g. using the main switch available in control cabinets).
• The output voltages of the power supplies must be measured
under no-load operation before they are connected in parallel
and are permitted to differ by up to 50 mV. This usually corresponds to the factory default setting. If the output voltage is
changed in case of variable power supplies, the "-" terminals
should first be connected and then the voltage difference
between the "+" output terminals measured under no-load
conditions before they are connected. The voltage difference
must not exceed 50 mV.
Note
With a direct galvanic connection in parallel of more than two
SITOP power supplies, further circuit measures may be necessary for short-circuit and overload protection!
15
15/10
Siemens KT 10.1 · 2016
© Siemens AG 2016
Technical information and configuration
Series connection to increase the voltage
■ Overview
Series connection to increase the voltage
Example:
To generate a load voltage of e.g. 48 V DC, two 24 V SITOP
power supplies of the same type can be connected in series.
The SITOP outputs "+" and "–" are isolated up to at least 60 V DC
against PE (creepages and clearances as well as radio interference suppression capacitors on "+" and "–" against PE), so that
with this type of series connection (see Figure), the following
points can be grounded:
• "–" of the lower power supply (results in +48 V DC against PE)
• Midway "+"/ "–" between both power supplies (results in ±24 V
DC against PE)
• "+" of the upper power supply (results in -48 V DC against PE)
Two 1-phase SITOP power supplies with 10 A rated output current (Article number: 6EP1334-1AL12) should be connected in
series to increase the voltage. They supply approximately 35 A
dynamically for 700 ms on power-up in the short-circuit case or
also, for example, with loads with a high-capacity input capacitor that momentarily act as a short-circuit at the start.
SITOP power
+
Suitable diodes for V1 and V2 are, for example, of Type SB 3401)
(Schottky diode in axially wired enclosure DO-201AD with
approximately 5.3 mm diameter and approximately 9.5 mm
length of body).
40 V are permissible as the blocking voltage, and the stationary
direct current load capacity IF AV is 3 A. The dynamic surge current loading capacity IF SM important in this case is sufficient for
the selected SITOP power supply at more than 100 A for 8.3 ms.
For SITOP power supplies with a lower rated output current, this
diode can also be used, but it is over-dimensioned.
1)
-
We do not accept any liability for this diode recommendation.
Load
SITOP power
+
-
G_KT01_EN_00059
Series connection of two SITOP power units to double the voltage
Note:
If two devices are connected in parallel, it cannot be guaranteed
that the voltage will remain below the maximum permissible
SELV voltage of 60 V DC in the event of a fault.
The purpose of diodes V1 and V2 is to protect the electrolytic
output capacitor integrated in the power supply against reverse
voltages > 1 V. As a result of the not absolutely simultaneous
power-up (even when a common mains switch is used for
switching on, differences of a few tens of milliseconds can occur
between the various startup-up delays), the power supply which
starts up more quickly supplies current from output "–" of the
slower power supply whose output electrolytic capacitor is then
theoretically impermissibly discharged.
The internal LC filter causes the internal rectifier diode on the
secondary side of the slower-starting power supply to accept
this current a few milliseconds later; this means that the external
diode connected with its anode to "–" and cathode to "+" is essential on each power supply. These diodes are, however, only
loaded dynamically so that the 8.3 ms surge current loading capability (specified in the data sheets for suitable diodes) can be
used as a basis for dimensioning and it is not usually necessary
to cool the diodes using heat sinks.
15
Siemens KT 10.1 · 2016
15/11
© Siemens AG 2016
Technical information and configuration
Battery charging with SITOP
■ Overview
Battery charging with SITOP power supplies
The SITOP PSU300B 12 V/20 A (article number
6EP1424-3BA00), 24 V/17 A (article number 6EP1436-3BA20)
and 24 V/30 A (article number 6EP1437-3BA20) power supplies
are suitable for charging lead-acid batteries. In the case of a
V/I characteristic set for parallel operation, the battery will be
charged with a constant current until approximately 95% of the
set SITOP output voltage has been achieved. The charging current is then continuously reduced from 1.2 x rated current at 95%
of the set voltage to approximately 0 A or the self-discharge
_current of the battery at 100% of the set output voltage, that is,
resistance characteristic in this range.
As reverse voltage protection and polarity reversal protection,
we recommend that a diode suitable for at least 1.2 x rated current of the power supply with a blocking voltage of at least 40 V
is connected in series with the "+" output (anode connected to
"+" output of the SITOP PSU300B and cathode connected to
positive pole of the battery).
The output voltage of the power supply must be set at no-load to
the end-of-charge voltage plus the voltage drop at the diode. For
an end-of-charge voltage of e.g. 27.0 V DC (usual at 20 °C to
30 °C battery temperature; specifications of the battery manufacturer must be observed!) and 0.8 V voltage drop at the diode,
the power supply must be set to 27.8 V during no-load operation.
15
15/12
Siemens KT 10.1 · 2016
General note for using SITOP power supplies as a
battery-charging unit
When using SITOP as a battery charging unit, VDE 0510 or
relevant national regulations must be observed, and adequate
ventilation of the battery location provided. SITOP power
supplies are designed as rack-mounting units, and protection
against electric shock should therefore be provided by installation in an appropriate housing.
The value recommended by the battery manufacturer must be
set as the end-of-charge voltage (depending on the battery temperature). An ideal temperature for the lead-acid battery is between +20 °C to +30 °C and the recommended end-of-charge
voltage in this case is usually about 27 V.
© Siemens AG 2016
Technical information and configuration
Fusing of the output circuit 24 V DC, selectivity
■ Overview
Fusing of 24 V power supply circuits and selectivity
With non-stabilized rectifiers (power transformer equipped with
rectifier) the output usually had to be protected with a suitable
fuse so that its rectifier diodes would not fail in the event of an
overload or a short-circuit (this would destroy the DC loads due
to the resulting alternating voltage and lead to serious damage
in most cases).
On the other hand, the stabilized SITOP power supplies are
provided with integral electronic short-circuit protection that
automatically protects both the power supply and the supplied
24 V DC circuits against an excess current in the event of an
overload/short-circuit. A distinction must be made between the
following three cases with respect to fusing on the secondary
side:
Example 1: No fusing
Fusing the secondary side (24 V DC) for protecting the load circuits and lines is not required if the respective cross-sections are
selected for the maximum possible output current RMS value.
Depending on the event (short-circuit or overload) this may either be the short-circuit RMS value or the current limitation value.
Example SITOP modular 10 (article number: 6EP1334-3BA10)
• 10 A rated current
• Current limitation typ. 12 A
• Short-circuit current rms value approximately 12 A
The technical specifications usually specify typical values, maximum values are approximately 2 A above the typical value. In
the example here, a maximum possible output current rms value
of approximately 14 A must therefore be used for line dimensioning.
Example 2: Reduced conductor cross-sections
If smaller conductor cross-sections are used than are specified
in the relevant standards (e.g. EN 60204-1), the affected 24 V
load infeed cables must be protected with a suitable line
protection.
It is then unimportant whether the power supply enters current
limiting mode (overload) or delivers the maximum short-circuit
current (low-resistance short-circuit). The load supply is in any
case protected against an overload by the line protection
matched to the conductor cross-section.
Example 3: Selectivity
In cases where a load which has failed (e.g. because of a shortcircuit) has to be rapidly detected or where it is essential to
selectively switch it off before the power supply enters current
limiting mode (with current limiting mode, the voltage would also
fall for all remaining 24 V DC loads), there are two possibilities for
the secondary side connection:
• Use of a SITOP PSE200U selectivity module or the SITOP
select diagnostics module for distributing the 24 V DC supply
among up to 4 load feeders.
Each output can be set between 0.5 A and 3 A
(Article number: 6EP1961-2BA11, -2BA31) or 3 A and 10 A
(Article number: 6EP1961-2BA21, -2BA41) or 2 A and 10 A
(Article number: 6EP1961-2BA00).
• Series connection of appropriate 24 V DC fuses or miniature
circuit breakers
The basis for selection of the 24 V DC fuse or miniature circuit
breaker is the short-circuit current above the rated current which
the SITOP power supplies deliver in the event of a short-circuit
during operation (values are specified in the respective technical specifications under "Output, dynamic V/I on short-circuit
during operation").
It is not easy to calculate the amount of the short-circuit current
flowing into the usually not ideal "short-circuit" and the amount
flowing into the remaining loads. This depends on the type of
overload (high-resistance or low-resistance short-circuit) and
the type of load connected (resistive, inductive and capacitive/
electronic loads).
However, it can be assumed with a first approximation in the
average case encountered in practice that the difference of
dynamic overcurrent minus 50 % SITOP rated output current is
available for the immediate tripping of a circuit breaker within a
typical time of 12 ms (with 14 times the rated DC with a circuit
breaker characteristic C acc. to IEC 60898, or with 7 times the
rated DC with a circuit breaker characteristic B or with 5 times
the rated DC with a circuit breaker characteristic A). Please refer
to the following tables for circuit-breakers appropriate for selected fusing according to this assumption.
15
Siemens KT 10.1 · 2016
15/13
© Siemens AG 2016
Technical information and configuration
Fusing of the output circuit 24 V DC, selectivity
■ Overview (continued)
List of ordering data and tripping characteristics of single-pole circuit-breakers 5SY4...
acc. to IEC 60898 / EN 60898, for use up to 60 V DC (250 V AC, switching capacity 10000 A)
Rated current
Tripping
characteristic
Article number
Range for immediate tripping
Required DC for
< 100 ms for operation with direct immediate tripping
current (alternating current)
in < 100 ms
Required DC for
immediate tripping
in approx. 12 ms
1A
Type A
5SY4 101-5
DC: 2 ... 5
(AC: 2 ... 3) x IRated
2 ... 5 A DC
5 A DC
1A
Type C
5SY4 101-7
DC: 5 ... 14
(AC: 5 ... 10) x IRated
5 ... 14 A DC
14 A DC
1.6 A
Type A
5SY4 115-5
DC: 2 ... 5
(AC: 2 ... 3) x IRated
3.2 ... 8 A DC
8 A DC
1.6 A
Type C
5SY4 115-7
DC: 5 ... 14
(AC: 5 ... 10) x Irated
8 ... 22.4 A DC
22.4 A DC
2A
Type A
5SY4 102-5
DC: 2 ... 5
(AC: 2 ... 3) x IRated
4 ... 10 A DC
10 A DC
2A
Type C
5SY4 102-7
DC: 5 ... 14
(AC: 5 ... 10) x IRated
10 ... 28 A DC
28 A DC
3A
Type A
5SY4 103-5
DC: 2 ... 5
(AC: 2 ... 3) x IRated
6 ... 15 A DC
15 A DC
3A
Type C
5SY4 103-7
DC: 5 ... 14
(AC: 5 ... 10) x IRated
15 ... 42 A DC
42 A DC
4A
Type A
5SY4 104-5
DC: 2 ... 5
(AC: 2 ... 3) x IRated
8 ... 20 A DC
20 A DC
4A
Type C
5SY4 104-7
DC: 5 ... 14
(AC: 5 ... 10) x IRated
20 ... 56 A DC
56 A DC
6A
Type A
5SY4 106-5
DC: 2 ... 5
(AC: 2 ... 3) x IRated
12 ... 30 A DC
30 A DC
6A
Type B
5SY4 106-6
DC: 3 ... 7
(AC: 3 ... 5) x IRated
18 ... 42 A DC
42 A DC
6A
Type C
5SY4 106-7
DC: 5 ... 14
(AC: 5 ... 10) x IRated
30 ... 84 A DC
84 A DC
8A
Type A
5SY4 108-5
DC: 2 ... 5
(AC: 2 ... 3) x IRated
16 ... 40 A DC
40 A DC
8A
Type C
5SY4 108-7
DC: 5 ... 14
(AC: 5 ... 10) x IRated
40 ... 112 A DC
112 A DC
10 A
Type A
5SY4 110-5
DC: 2 ... 5
(AC: 2 ... 3) x IRated
20 ... 50 A DC
50 A DC
10 A
Type B
5SY4 110-6
DC: 3 ... 7
(AC: 3 ... 5) x IRated
30 ... 70 A DC
70 A DC
10 A
Type C
5SY4 110-7
DC: 5 ... 14
(AC: 5 ... 10) x IRated
50 ... 140 A DC
140 A DC
13 A
Type A
5SY4 113-5
DC: 2 ... 5
(AC: 2 ... 3) x IRated
26 ... 65 A DC
65 A DC
13 A
Type B
5SY4 113-6
DC: 3 ... 7
(AC: 3 ... 5) x IRated
39 ... 91 A DC
91 A DC
13 A
Type C
5SY4 113-7
DC: 5 ... 14
(AC: 5 ... 10) x IRated
65 ... 182 A DC
182 A DC
16 A
Type A
5SY4 116-5
DC: 2 ... 5
(AC: 2 ... 3) x IRated
32 ... 80 A DC
80 A DC
16 A
Type B
5SY4 116-6
DC: 3 ... 7
(AC: 3 ... 5) x IRated
48 ... 112 A DC
112 A DC
16 A
Type C
5SY4 116-7
DC: 5 ... 14
(AC: 5 ... 10) x IRated
80 ... 224 A DC
224 A DC
15
15/14
Siemens KT 10.1 · 2016
© Siemens AG 2016
Technical information and configuration
Fusing of the output circuit 24 V DC, selectivity
■ Overview (continued)
Miniature circuit breakers acc. to EN 60898 (DIN VDE 0641-11) in 24 V DC circuits,
which are powered by SITOP modular or SITOP smart power supplies1)
Article No.
Iout rated
Iout dyn.
Characteristic A
1A
1.6 A
2A
3A
4A
6A
8A
10 A
13 A
16 A
6EP1332-2BA20
2.5 A
9 A/
800 ms


•
X
X
X
X
X
X
X
6EP1333-2BA20
5A
18 A/
800 ms




•
X
X
X
X
X
6EP1333-3BA10
5A
15 A/
25 ms



•
•
X
X
X
X
X
6EP3333-8SB00-0AY0 5 A
15 A/
25 ms



•
•
X
X
X
X
X
6EP1334-2BA20
10 A
32 A/
1000 ms






•
X
X
X
6EP1334-3BA10
10 A
30 A/
25 ms






•
X
X
X
6EP3334-8SB00-0AY0 10 A
30 A/
25 ms






•
X
X
X
6EP1434-2BA10
10 A
16 A/
100 ms




•
X
X
X
X
x
6EP1336-2BA10
20 A
35 A/
100 ms






•
•
X
X
6EP1336-3BA10
20 A
60 A/
25 ms








•
•
6EP3436-8SB00-0AY0 20 A
60 A/
25 ms








•
•
35 A/
100 ms






•
•
X
X
120 A/
25 ms










6EP1436-2BA10
20 A
6EP3337-8SB00-0AY0 40 A
6EP1437-2BA20
40 A
65 A/
120 ms









•
6EP1437-3BA10
40 A
120 A/
25 ms










Iout rated: Rated output current
Iout dyn: Dynamic overcurrent with short-circuit during operation
: instantaneous tripping, as dynamic overcurrent on short-circuit
> limit current of electromagnetic tripping.
•: instantaneous tripping probable, as dynamic overcurrent on shortcircuit at least 50% within tolerance range of the tripping characteristic.
1) The selection of miniature circuit breakers that can be tripped is based
on the consideration of the maximum possible short-circuit current of
the power supply and the respective tripping characteristic at +20 °C.
Further parameters that may be relevant in practice, such as selfheating, increased ambient temperature, line impedance and
possibly currents flowing in parallel feeders, have not been taken into
consideration.
X: no instantaneous tripping.
15
Siemens KT 10.1 · 2016
15/15
© Siemens AG 2016
Technical information and configuration
Fusing of the output circuit 24 V DC, selectivity
■ Overview (continued)
Article No.
Iout rated
Iout dyn.
Characteristic B
6A
10 A
13 A
16 A
6EP1332-2BA20
2.5 A
9 A/
800 ms
X
X
X
X
6EP1333-2BA20
5A
18 A/
800 ms
X
X
x
X
6EP1333-3BA10
5A
15 A/
25 ms
X
X
X
X
6EP3333-8SB00-0AY0
5A
15 A/
25 ms
X
X
X
X
6EP1334-2BA20
10 A
32 A/
1000 ms
•
X
X
X
6EP1334-3BA10
10 A
30 A/
25 ms
•
X
X
X
6EP3334-8SB00-0AY0
10 A
30 A/
25 ms
•
X
X
X
6EP1434-2BA10
10 A
16 A/
100 ms
X
X
X
X
6EP1336-2BA10
20 A
35 A/
100 ms
•
X
X
X
6EP3436-8SB00-0AY0
20 A
60 A/
25 ms

•
X
X
6EP1336-3BA10
20 A
60 A/
25 ms

•
X
X
6EP1436-2BA10
20 A
35 A/
100 ms
•
X
X
X
6EP3337-8SB00-0AY0
40 A
120 A/
25 ms




6EP1437-2BA20
40 A
65 A/
120 ms

•
•
X
6EP1437-3BA10
40 A
120 A/
25 ms




Iout rated: Rated output current
Iout dyn: Dynamic overcurrent with short-circuit during operation
: instantaneous tripping, as dynamic overcurrent on short-circuit
> limit current of electromagnetic tripping.
•: instantaneous tripping probable, as dynamic overcurrent on shortcircuit at least 50% within tolerance range of the tripping characteristic.
X: no instantaneous tripping.
15
15/16
Siemens KT 10.1 · 2016
© Siemens AG 2016
Technical information and configuration
Fusing of the output circuit 24 V DC, selectivity
■ Overview (continued)
Article No.
Iout rated
Iout dyn.
Characteristic C
1A
1.6 A
2A
3A
4A
6A
8A
10 A
13 A
16 A
6EP1332-2BA20
2.5 A
9 A/
800 ms
X
X
X
X
X
X
X
X
X
X
6EP1333-2BA20
5A
18 A/
800 ms

•
X
X
X
X
X
X
X
X
6EP1333-3BA10
5A
15 A/
25 ms

X
X
X
X
X
X
X
X
X
6EP3333-8SB00-0AY0 5 A
15 A/
25 ms

X
X
X
X
X
X
X
X
X
6EP1334-2BA20
10 A
32 A/
1000 ms



•
X
X
X
X
X
X
6EP1334-3BA10
10 A
30 A/
25 ms



•
X
X
X
X
X
X
6EP3334-8SB00-0AY0 10 A
30 A/
25 ms



•
X
X
X
X
X
X
6EP1434-2BA10
10 A
16 A/
100 ms

•
X
X
X
X
X
X
X
X
6EP1336-2BA10
20 A
35 A/
100 ms



•
X
X
X
X
X
X
6EP1336-3BA10
20 A
60 A/
25 ms





•
X
X
X
X
6EP3436-8SB00-0AY0 20 A
60 A/
25 ms





•
X
X
X
X
35 A/
100 ms



•
X
X
X
X
X
X
120 A/
25 ms







•
X
X
6EP1436-2BA10
20 A
6EP3337-8SB00-0AY0 40 A
6EP1437-2BA20
40 A
65 A/
120 ms





•
X
X
X
X
6EP1437-3BA10
40 A
120 A/
25 ms







•
X
X
15
Siemens KT 10.1 · 2016
15/17
© Siemens AG 2016
Technical information and configuration
Standards and approvals
■ Overview
Overview of important standards and approvals
EN
European standards
EN 50178
Electronic equipment for use in power installations
EN 55022
Information technology equipment – Radio disturbance characteristics – Limits and methods of measurement
EN 60079
Electrical apparatus for explosive gas atmospheres
EN 60529
Degrees of protection provided by enclosures (IP-Code)
EN 60721
Classification of environmental conditions
EN 60950-1
Information technology equipment – Safety
EN 61000-3-2
Electromagnetic compatibility (EMC) – Part 3-2: Limits for harmonic current emissions
(equipment input current 16 A per phase)
EN 61000-6-2
Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity for industrial environments
EN 61000-6-3
Electromagnetic compatibility (EMC) – Part 6-3: Generic standards – Emission standard for residential, commercial
and light industrial environments
UL
Underwriters Laboratories
UL 508
Industrial control equipment
UL 1604
Electrical equipment for use in class I and class II, division 2, and class III hazardous (classified) locations
UL 1778
Uninterruptible Power Supply Equipment
UL 2367
Solid State Overcurrent Protectors
UL 60079
Electrical apparatus for explosive gas atmospheres
UL 60950 -1
Information technology equipment – Safety
ANSI
American National Standards Institute
ANSI/ISA –12.12.01
Non-Incendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1 and 2 Hazardous
(Classified) Locations
NEC
Class 2 Secondary circuit supplied by a power source complying with Article 725,
Part C of the National Electrical Code (NEC), ANSI/NFPA 70
CSA
Canadian Standards Association
CSA C22.2 No. 14
Industrial control equipment
CSA C22.2 No. 142
Process control equipment
CSA C22.2 No. 107.1
General Use Power Supplies
CSA C22.2 No. 213
Non-Incendive Electrical Equipment for Use in Class I, Division 2 Hazardous Locations
CSA C22.2 No. 60079
Electrical apparatus for explosive gas atmospheres
CSA C22.2 No. 60950-1
Information technology equipment – Safety
ATEX
Equipment and protective systems intended for use in Potentially Explosive Atmospheres
IECEx
Equipment for use in Explosive Atmospheres
FM
Factory Mutual Research
SEMI
F47 Specification for semiconductor processing equipment - Voltage sag immunity
ABS
American Bureau of Shipping
BV
Bureau Veritas
DNV GL
Det Norske Veritas, Germanischer Lloyd
LR
Lloyd‘s Register
NK
Nippon Kaiji Kyokai
15
15/18
Siemens KT 10.1 · 2016
© Siemens AG 2016
Technical information and configuration
Certificates
■ Certificates
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
6EP1332-1LB00
X
X
X
6EP1333-1LB00
X
X
X
6EP1334-1LB00
X
X
X
6EP1322-2BA00
X
X
X
X
X
X
X
X
6EP1323-2BA00
X
X
X
X
X
X
X
X
6EP1332-2BA20
X
X
X
X
X
X
X
X
X
6EP1333-2BA20
X
X
X
X
X
X
X
X
X
6EP1334-2BA20
X
X
X
X
X
X
X
X
X
6EP1336-2BA10
X
X
X
X
X
X
X
X
6EP1433-2BA20
X
X
X
X
X
X
X
6EP1434-2BA10
X
X
X
X
X
X
X
6EP1436-2BA10
X
X
X
X
X
X
X
6EP1437-2BA20
X
X
X
X
X
X
X
X
X
X
6EP1331-5BA10
X
X
X
X
6EP1332-5BA00
X
X
X
X
6EP1332-5BA20
X
X
X
X
6EP1332-5BA10
X
X
X
6EP1311-1SH03
X
X
X
X
X
6EP1311-1SH13
X
X
X
X
6EP1321-1SH03
X
X
X
X
6EP1322-1SH03
X
X
X
6EP1351-1SH03
X
X
6EP1352-1SH03
X
6EP1331-1SH03
X
6EP1332-1SH43
6EP1332-1SH52
ATEX
cULus-Listed (UL 508,
CSA C22.2 No 107.1)
X
X
cURus-Recognized
(UL 1778,
CSA C22.2 No. 107.1)
CB-Scheme
X
X
UL-Recognized
(UL 2367)
CE (LVD, EMC)
X
6EP1331-5BA00
SEMI F47
X
X
6EP1322-5BA10
NK (Nippon Kaiji Kyokai)
LR (Lloyd’s Register)
X
X
X
FM (Class I, Div. 2)
X
X
X
cCSAus Class I, Div. 2
(CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2007)
X
X
cULus Class I, Div. 2
(ANSI/ISA-12.12.01-2007,
CSA C22.2 No. 213-M1987)
X
6EP1321-5BA00
IECEx
X
NEC class 2 (acc. UL 1310)
X
cCSAus
(CSA C22.2 No. 60950-1,
UL 60950-1)
X
cURus-Recognized
(UL 60950-1,
CSA 22.2 No. 60950-1)
BV (Bureau Veritas)
Shipbuilding
ABS (American Bureau
of Shipping)
EX
DNV GL (Det Norske Veritas
Germanischer Lloyd)
UL, CSA
SITOP compact
X
X
X
LOGO!Power
SITOP lite
SITOP smart
i. p.
i. p.
i. p.
i. p.
X
X
X
X
15
Siemens KT 10.1 · 2016
15/19
© Siemens AG 2016
Technical information and configuration
Certificates
■ Certificates (continued)
6EP3334-8SB00-0AY0
X
X
X
X
X
6EP1336-3BA10
X
6EP1337-3BA00
X
6EP1333-3BA10
X
X
6EP1333-3BA10-8AC0
X
6EP1334-3BA10
X
6EP1334-3BA10-8AB0
SEMI F47
X
NK (Nippon Kaiji Kyokai)
X
LR (Lloyd’s Register)
ABS (American Bureau
of Shipping)
X
BV (Bureau Veritas)
DNV GL (Det Norske Veritas
Germanischer Lloyd)
X
FM (Class I, Div. 2)
X
cCSAus Class I, Div. 2
(CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2007)
IECEx
X
cULus Class I, Div. 2
(ANSI/ISA-12.12.01-2007,
CSA C22.2 No. 213-M1987)
ATEX
X
NEC class 2 (acc. UL 1310)
X
cCSAus
(CSA C22.2 No. 60950-1,
UL 60950-1)
X
cURus-Recognized
(UL 1778,
CSA C22.2 No. 107.1)
X
UL-Recognized
(UL 2367)
6EP3333-8SB00-0AY0
cURus-Recognized
(UL 60950-1,
CSA 22.2 No. 60950-1)
cULus-Listed (UL 508,
CSA C22.2 No 107.1)
Shipbuilding
CB-Scheme
EX
CE (LVD, EMC)
UL, CSA
SITOP modular
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
6EP3436-8SB00-0AY0
X
X
X
X
X
X
X
X
6EP1437-3BA10
X
X
X
X
X
X
X
X
X
6EP3446-8SB10-0AY0
X
X
X
X
X
6EP1456-3BA00
X
X
X
X
X
6EP1457-3BA00
X
X
X
X
X
X
X
X
X
SITOP modular, power
supply system
PSU8600
6EP3436-8SB00-2AY0
X
X
X
X
X
X
X
X
i. p.
i. p.
6EP3437-8SB00-2AY0
X
X
X
X
X
X
X
X
i. p.
i. p.
6EP3436-8MB00-2CY0
X
X
X
X
X
X
X
X
i. p.
i. p.
6EP3437-8MB00-2CY0
X
X
X
X
X
X
X
X
i. p.
X
6EP4436-8XB00-0CY0
X
X
X
X
X
X
X
X
i. p.
X
6EP4437-8XB00-0CY0
X
X
X
X
X
X
X
X
i. p.
X
6EP4297-8HB00-0XY0
X
X
X
X
X
X
X
X
i. p.
X
6EP4297-8HB10-0XY0
X
X
X
X
X
X
X
X
i. p.
X
6EP4293-8HB00-0XY0
X
X
X
X
X
X
X
X
i. p.
i. p.
6EP4295-8HB00-0XY0
X
X
X
X
X
X
X
X
i. p.
i. p.
SITOP in the SIMATIC
Design
15
6ES7307-1BA01-0AA0
X
X
6ES7305-1BA80-0AA0
X
X
6ES7307-1EA01-0AA0
X
X
6ES7307-1EA80-0AA0
X
X
6ES7307-1KA02-0AA0
X
6EP1332-1SH71
X
X
X
6EP1332-4BA00
X
X
X
6EP1333-4BA00
X
X
X
6ES7148-4PC00-0HA0
X
X
i.p. - in preparation
15/20
Siemens KT 10.1 · 2016
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
© Siemens AG 2016
Technical information and configuration
Certificates
■ Certificates (continued)
X
X
X
X
X
X
X
6EP1333-1LD00
X
X
X
X
6EP1334-1LD00
X
X
X
X
SEMI F47
X
6EP1332-1LD10
NK (Nippon Kaiji Kyokai)
6EP1332-1LD00
LR (Lloyd’s Register)
X
X
FM (Class I, Div. 2)
X
X
cCSAus Class I, Div. 2
(CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2007)
X
X
cULus Class I, Div. 2
(ANSI/ISA-12.12.01-2007,
CSA C22.2 No. 213-M1987)
6EP1437-3BA20
X
IECEx
X
X
6EP1331-1LD00
ATEX
X
X
X
X
NEC class 2 (acc. UL 1310)
X
X
X
X
cCSAus
(CSA C22.2 No. 60950-1,
UL 60950-1)
X
X
X
X
cURus-Recognized
(UL 1778,
CSA C22.2 No. 107.1)
X
X
X
6EP1322-1LD00
UL-Recognized
(UL 2367)
X
X
cURus-Recognized
(UL 60950-1,
CSA 22.2 No. 60950-1)
X
X
cULus-Listed (UL 508,
CSA C22.2 No 107.1)
X
X
CB-Scheme
X
6EP3436-9UB00-0AY0
CE (LVD, EMC)
6EP3424-8UB00-0AY0
6EP1321-1LD00
BV (Bureau Veritas)
Shipbuilding
ABS (American Bureau
of Shipping)
EX
DNV GL (Det Norske Veritas
Germanischer Lloyd)
UL, CSA
Special designs,
special uses
Wall mounting
High degree of
protection
6EP1333-7CA00
X
X
6EP1334-7CA00
X
X
6ES7148-4PC00-0HA0
X
X
Battery charging
Alternative
output voltages
6EP1353-0AA00
X
X
6EP1353-2BA00
X
X
DC/DC converters
6EP1731-2BA00
X
X
6EP1732-0AA00
X
X
6EP1621-2BA00
X
X
6EP1536-3AA00
X
X
X
X
X
X
Special
applications
6EP1333-1AL12
X
6EP1334-1AL12
X
6EP1433-0AA00
X
X
X
X
X
Add-on modules
6EP1961-3BA21
X
X
X
X
X
X
X
6EP1962-2BA00
X
X
6EP1964-2BA00
X
X
6EP1961-2BA11
X
X
X
6EP1961-2BA31
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
6EP1961-2BA21
X
X
6EP1961-2BA41
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
6EP1961-2BA00
X
X
6EP1961-3BA01
X
X
X
X
X
X
6EP1967-2AA00
X
X
X
X
X
15
X
X
X
Siemens KT 10.1 · 2016
15/21
© Siemens AG 2016
Technical information and configuration
Certificates
■ Certificates (continued)
X
X
X
X
6EP1933-2NC11
X
6EP4134-3AB00-0AY0
X
X
X
X
X
X
X
X
6EP4134-3AB00-1AY0
X
X
X
X
X
X
X
X
6EP4134-3AB00-2AY0
X
X
X
X
X
X
X
X
6EP4136-3AB00-0AY0
X
X
X
X
X
X
X
X
6EP4136-3AB00-1AY0
X
X
X
X
X
X
X
X
6EP4136-3AB00-2AY0
X
X
X
X
X
X
X
X
6EP4137-3AB00-0AY0
X
X
X
X
X
X
X
X
6EP4137-3AB00-1AY0
X
X
X
X
X
X
X
X
6EP4137-3AB00-2AY0
X
X
X
X
X
X
X
X
6EP4131-0GB00-0AY0
X
X
X
X
X
X
X
6EP4133-0GB00-0AY0
X
X
X
X
X
X
X
6EP4134-0GB00-0AY0
X
X
X
X
X
X
X
6EP4135-0GB00-0AY0
X
X
X
X
X
X
X
6EP4132-0GB00-0AY0
X
X
X
X
X
X
X
6EP4133-0JB00-0AY0
X
X
X
X
6EP1931-2DC21
X
X
6EP1931-2DC31
X
X
6EP1931-2DC42
X
X
6EP1931-2EC21
X
X
6EP1931-2EC31
X
X
6EP1931-2EC42
X
X
6EP1931-2FC21
X
X
6EP1931-2FC42
X
X
6EP1935-6MC01
X
X
6EP1935-6MD31
X
X
6EP1935-6MD11
X
X
6EP1935-6ME21
X
X
6EP1935-6MF01
X
X
15
15/22
Siemens KT 10.1 · 2016
SEMI F47
X
NK (Nippon Kaiji Kyokai)
X
X
LR (Lloyd’s Register)
ABS (American Bureau
of Shipping)
X
6EP1933-2NC01
SITOP DC-USV uninterruptible power supplies
BV (Bureau Veritas)
DNV GL (Det Norske Veritas
Germanischer Lloyd)
6EP1935-5PG01
FM (Class I, Div. 2)
X
cCSAus Class I, Div. 2
(CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2007)
X
X
cULus Class I, Div. 2
(ANSI/ISA-12.12.01-2007,
CSA C22.2 No. 213-M1987)
X
X
IECEx
X
X
ATEX
X
X
NEC class 2 (acc. UL 1310)
X
X
cCSAus
(CSA C22.2 No. 60950-1,
UL 60950-1)
X
X
cURus-Recognized
(UL 1778,
CSA C22.2 No. 107.1)
X
6EP1933-2EC51
UL-Recognized
(UL 2367)
6EP1933-2EC41
cURus-Recognized
(UL 60950-1,
CSA 22.2 No. 60950-1)
cULus-Listed (UL 508,
CSA C22.2 No 107.1)
Shipbuilding
CB-Scheme
EX
CE (LVD, EMC)
UL, CSA
16
© Siemens AG 2016
Appendix
16/2
Siemens Training
16/3
16/4
16/4
Partner at Siemens
Partner at Industry
Siemens Partner Programm
16/5
Siemens Automation Cooperates
with Education
Simplify your education in automation
16/5
16/7
16/7
16/8
Online Services
Information and Ordering Options 
on the Internet and DVD
Information and Download Center,
Social Media, Mobile Media
16/9
16/10
16/12
Industry Services
Industry Services – Portfolio overview
Online Support
16/13
Subject index
16/15
Article number index
16/18
Conditions of sale and delivery
16/18
Export regulations
Siemens KT 10.1 · 2016
© Siemens AG 2016
Appendix
SITRAIN – Training for Industry
Your benefit from practical training directly from the manufacturer
SITRAIN – Training for Industry – provides you with comprehensive support in solving your tasks.
Training directly from the manufacturer enables you to make correct decisions with confidence.
Increased profits and lower costs:
• Shorter times for commissioning, maintenance and servicing
• Optimized production operations
• Reliable configuration and startup
• Shorten commissioning times, reduce downtimes, and faster
troubleshooting
• Exclude expensive faulty planning right from the start.
• Flexible plant adaptation to market requirements
• Compliance with quality standards in production
• Increased employee satisfaction and motivation
• Shorter familiarization times following changes in technology
and staff
Contact
Visit our site on the Internet at:
www.siemens.com/sitrain
or let us advise you personally. You can request our latest
training catalog from:
SITRAIN – Training for Industry
SITRAIN Customer Support Germany:
16
Tel.: +49 911 895-7575
Fax: +49 911 895-7576
Email: [email protected]
16/2
Siemens KT 10.1 · 2016
Your benefits with SITRAIN – Training for Industry
Certified top trainers
Our trainers are skilled specialists with practical experience.
Course developers have close contact with product development, and pass on their knowledge to the trainers and then to
you.
Practical application with practice
Practice, practice, practice! We have designed the trainings
with an emphasis on practical exercises. They take up to half of
the course time in our trainings. You can therefore implement
your new knowledge in practice even faster.
300 courses in more than 60 countries
We offer a total of about 300 classroom-based courses. You can
find us at more than 50 locations in Germany, and in 62 countries
worldwide. You can find which course is offered at which location at:
www.siemens.com/sitrain
Skills development
Do you want to develop skills and fill in gaps in your knowledge?
Our solution: We will provide a program tailored exactly to your
personal requirements. After an individual requirements analysis, we will train you in our training centers near you or directly
at your offices. You will practice on the most modern training
equipment with special exercise units. The individual training
courses are optimally matched to each other and help with the
continuous development of knowledge and skills. After finishing
a training module, the follow-up measures make success certain, as well as the refreshment and deepening of the knowledge
gained.
© Siemens AG 2016
Appendix
Partner at Siemens
At Siemens we are resolutely pursuing the same goal: long-term
improvement of your competitive ability.
We are committed to this goal. Thanks to our commitment,
we continue to set new standards in automation and drive
technology. In all industries – worldwide.
At your service locally, around the globe for consulting, sales,
training, service, support, spare parts ... on the entire Industry
Automation and Drive Technologies range.
Your personal contact can be found in our Contacts Database at:
www.siemens.com/automation/partner
You start by selecting
• the required competence,
• products and branches,
• a country,
• a city
or by a
• location search or
• person search.
16
Siemens KT 10.1 · 2016
16/3
© Siemens AG 2016
Appendix
Partner at Industry
Siemens Partner Program
■ Overview
Siemens Solution und Approved Partners
Partner Finder
Highest competence in automation and drive technology as well
as power distribution
In the Siemens global Solution Partner program, customers are
certain to find the optimum partner for their specific requirements - with no great effort. The Partner Finder is basically a
comprehensive database that showcases the profiles of all our
solution partners.
Siemens works closely together with selected partner companies around the world in order to ensure that customer requirements for all aspects of automation and drives, as well as power
distribution, are fulfilled as best as possible – wherever you are,
and whatever the time. It is for this reason that we systematically
train and keep our partners well prepared, in addition to certifying them in specific technologies. It is our declared intention and
goal to train and prepare our partners to the same standards as
our own employees.
This approach is based on contractually agreed quality criteria
as well as optimum support for our partners by providing clearlydefined processes. This ensures that they possess all the qualities to meet customer requirements optimally. The partner emblem is the guarantee and indicator of proven quality.
Solution Partners and Approved Partners
The Siemens Partner Program distinguishes between Solution
Partners and Approved Partners.
At present we are working with more than 1,400 Solution Partners worldwide. They represent countless tailored and futureproof automation and drive solutions in the most diverse industries.
With their extensive technical product knowledge, Siemens
Approved Partners offer a combination of goods and services
that include specialist technologies, customized modifications
and the provision of high-quality system and product packages.
They also provide qualified technical support and assistance
16
16/4
Siemens KT 10.1 · 2016
Easy selection:
Set filters in the search screen form according to the criteria that
are relevant to you. You can also directly enter the name of an
existing partner.
Skills at a glance:
Gain a quick insight into the specific competencies of any particular partner with the reference reports.
Direct contact option:
Use our electronic query form:
www.siemens.com/partnerfinder
Additional information on the Siemens Solution Partner Program
is available online at:
www.siemens.com/partner-program
© Siemens AG 2016
Appendix
Siemens Automation Cooperates with Education
Simplify your education in automation
■ Unique support for educators and students in educational institutions
• The new TIA Portal training materials for SIMATIC S7-1500 /
S7-1200 / S7-300 are available in English, German, French,
Italian, Spanish, Portuguese and Chinese for download.
www.siemens.com/sce/curriculums
Trainer packages for hands-on learning
Siemens Automation Cooperates with Education (SCE)
offers a global system for sustained support of technical skills.
SCE supports educational institutions in their teaching assignment in the industrial automation sector and offers added value
in the form of partnerships, technical expertise, and know-how.
As the technological leader, our comprehensive range of services can support you in the knowledge transfer for Industry 4.0.
Our services at a glance
• Training curriculums for your lessons
• Trainer packages for hands-on learning
• Courses convey up-to-date specialist knowledge
• Support for your projects / textbooks
• Complete didactic solutions from our partners
• Personal contact for individual support
Training curriculums for your lessons
Use our profound industrial know-how for practiceoriented and
individual design of your course. We offer you more than 100 didactically prepared training curriculums on the topics of automation and drives technology free of charge. These materials
are perfectly matched to your curricula and syllabuses, and
optimally suited for use with our trainer packages. This takes into
account all aspects of a modern industrial solution: installation,
configuration, programming, and commissioning. All documents, including projects, can be individually matched to your
specific requirements.
Particular highlights:
• The new SIMATIC PCS 7 curriculums and trainer packages.
Using plant simulation, you can pass on basic, practiceoriented PCS 7 knowledge at universities within about
60 hours (= 1 semester).
Our SCE trainer packages offer a specific combination of original industrial components which are perfectly matched to your
requirements and can be conveniently used in your course.
These price-reduced bundles available exclusively to schools
include innovative and flexible hardware and software packages.
SCE currently offers more than 80 SCE trainer packages including related equipment e.g. Micro Memory. These cover both the
factory and process automation sectors. You can use them to impart the complete course contents on industrial automation at a
very low cost.
Trainer packages are available for:
• Introduction to automation technology with LOGO! logic
module
• PLC engineering with SIMATIC S7 hardware and STEP 7
software (S7-1500, S7-1200, S7-300 and TIA Portal)
• Operator control and monitoring with SIMATIC HMI
• Industrial networking over bus systems with SIMATIC NET
(PROFINET, PROFIBUS, IO-Link)
• Sensor systems with VISION, RFID and SIWAREX
• Process automation with SIMATIC PCS 7
• Networked drive and motion technologies with
SINAMICS/SIMOTION
• Power Monitoring Devices SENTRON PAC 4200
• Motor Management SIMOCODE
• CNC programming with SinuTrain
Important ordering notes:
Only the following institutions are authorized to obtain trainer
packages: vocational schools, Colleges and Universities,
in-house vocational training departments, non commercial research institutions and non commercial training departments.
To purchase a trainer package, you require a specific end-use
certificate, which you can obtain from your regional sales office.
www.siemens.com/sce/tp
Siemens KT 10.1 · 2016
16/5
© Siemens AG 2016
Appendix
Siemens Automation Cooperates with Education
Simplify your education in automation
■ Unique support for educators and students in educational institutions (continued)
Courses convey up-to-date specialist knowledge
As a particular service, SCE supports technical authors with our
know-how as well as with intensive technical consulting.
Siemens library of special textbooks covering the industrial
automation sector provides an additional resource for you and
your students. These can be found at the SCE web site.
www.siemens.com/sce/contact
www.siemens.com/sce/books
Complete didactic solutions from our partners
Profit from our excellent know-how as the leader in industrial
technologies. We offer you specific courses for automation and
drive technology worldwide. These support you in the practiceoriented transferring of product and system know-how, are in
conformance with curriculums, and derived from the training
fields. Compact technical courses especially for use at universities are also available.
Our range of courses comprises a wide variety of training
modules based on the principle of Totally Integrated Automation
(TIA). The focus is on the same subject areas as with the SCE
trainer packages.
Our partners for learning systems offer a wide range of training
systems and solutions for use in your courses or laboratory.
Every PLC and drive course is oriented on state-of-the-art technology. Your graduates can thus be prepared optimally for their
future professional life.
These models have been designed based on our trainer packages and thus save you the time and cost of selfconstruction
of individual components. The Partner systems provide you with
simple and effective help in the fulfillment of your teaching
assignment.
In some countries we are offering classes based on our training
curriculums. Please inquire with your SCE contact partner.
www.siemens.com/sce/partner
www.siemens.com/sce/courses
Contact for individual support
Support for your projects/textbooks
You can find your personal SCE contact on our Internet site. Your
local SCE Promoter will answer all your questions concerning the
complete SCE offering, and provide you with timely and competent information about innovations. When you encounter challenges, you can profit from our global team of excellence.
If a direct SCE contact is not listed for your country, please contact your local Siemens office.
www.siemens.com/sce/contact
SCE Support Finder for your Internet request
You are an educator and need support on the topic of industry
automation? Send us your request:
www.siemens.com/sce/supportfinder
Automation and drive technology is characterized by continuous
and rapid developments. Service and Support therefore play an
important role.
We can provide you with consulting for selected projects and
support from your personal SCE contact as well as our webbased and regional Customer Support.
16/6
Siemens KT 10.1 · 2016
© Siemens AG 2016
Appendix
Online Services
Information and Ordering Options on the Internet and DVD
■ The Future of Manufacturing on the Internet
Detailed knowledge of the range of products and services
available is essential when planning and engineering automation systems. It goes without saying that this information must
always be as up-to-date as possible.
Industry is on the threshold of the fourth industrial revolution as
digitization now follows after the automation of production. The
goals are to increase productivity and efficiency, speed, and
quality. In this way, companies can remain competitive on the
path to the future of industry.
You will find everything you need to know about products,
systems and services on the internet at:
www.siemens.com/industry
■ Product Selection Using the Interactive CA 01 Automation and Drives Catalog
Detailed information together with user-friendly interactive
functions:
The CA 01 interactive catalog covers more than 100,000
products, thus providing a comprehensive overview of the
product range provided by Siemens.
You will find everything you need here for solving tasks in the
fields of automation, switching, installation and drives.
All information is provided over a user interface that is both
user-friendly and intuitive.
You can order the CA 01 product catalog from your Siemens
sales contact or in the Information and Download Center:
www.siemens.com/industry/infocenter
Information about the CA 01 interactive catalog can be found on
the Internet at:
www.siemens.com/automation/ca01
or on DVD.
■ Easy Shopping with the Industry Mall
The Industry Mall is the electronic ordering platform of Siemens
AG on the Internet. Here you have online access to a huge range
of products presented in an informative and attractive way.
Data transfer via EDIFACT allows the whole procedure, from
selection through ordering to tracking and tracing, to be carried
out online. Availability checks, customer-specific discounts and
bid creation are also possible.
Numerous additional functions are provided for your support.
For example, powerful search functions make it easy to select
the required products. Configurators enable you to configure
complex product and system components quickly and easily.
CAx data types are also provided here.
You can find the Industry Mall on the Internet at:
www.siemens.com/industrymall
16
Siemens KT 10.1 · 2016
16/7
© Siemens AG 2016
Appendix
Online Services
Information and Download Center, Social Media, Mobile Media
■ Downloading Catalogs
In addition to numerous other useful documents, you can also
find the catalogs listed on the back inside cover of this catalog
in the Information and Download Center. You can download
these catalogs in PDF format without having to register.
The filter dialog above the first catalog displayed makes it
possible to carry out targeted searches. If you enter "MD 3" for
example, you will find both the MD 30.1 and MD 31.1 catalogs.
If you enter "IC 10", both the IC 10 catalog and the associated
news or add-ons are displayed.
Visit us at:
www.siemens.com/industry/infocenter
■ Social and Mobile Media
Connect with Siemens through social media: visit our social
networking sites for a wealth of useful information, demos on
products and services, the opportunity to provide feedback, to
exchange information and ideas with customers and other
Siemens employees, and much, much more. Stay in the know
and follow us on the ever-expanding global network of social
media.
To find out more about Siemens' current social media activities,
visit us at:
www.siemens.com/socialmedia
Or via our product pages at:
www.siemens.com/automation or www.siemens.com/drives
Connect with Siemens Industry at our central access point to
read all the news on the future of manufacturing, watch current
videos and inform yourself about all the latest industry
developments:
www.siemens.com/future-of-manufacturing/news.html
Discover the world of Siemens.
We are also constantly expanding our offering of cross-platform
apps for smartphones and tablets. You will find the current
Siemens apps at the App Store (iOS) or at Google Play
(Android):
https://itunes.apple.com/en/app/siemens/id452698392?mt=8
https://play.google.com/store/search?q=siemens
The Siemens app, for example, tells you all about the history,
latest developments and future plans of the company – with
informative pictures, fascinating reports and the most recent
press releases.
16
16/8
Siemens KT 10.1 · 2016
© Siemens AG 2016
Appendix
Industry Services
■ Overview
Unleash potential – with services from Siemens
Support and
Consulting
Services
Training
Services
Plant Data
Services
Service
Programs and
Agreements
Spare Parts
Services
Repair
Services
Field and
Maintenance
Services
Retrofit and
Modernization
Services
G_DA65_XX_00272
Increase your performance – with Industry Services
Optimizing the productivity of your equipment and operations
can be a challenge, especially with constantly changing market
conditions. Working with our service experts makes it easier.
We understand your industry’s unique processes and provide
the services needed so that you can better achieve your
business goals.
You can rely on our highly dedicated team of engineers, technicians and specialists to deliver the services you need – safely,
professionally and in compliance with all regulations. We are
there for you, where you need us, when you need us.
You can count on us to maximize your uptime and minimize your
downtime, increasing your operations’ productivity and reliability. When your operations have to be changed quickly to meet a
new demand or business opportunity, our services give you the
flexibility to adapt. Of course, we take care that your production
is protected against cyber threats. We assist in keeping your
operations as energy and resource efficient as possible and reducing your total cost of ownership. As a trendsetter, we ensure
that you can capitalize on the opportunities of digitalization and
by applying data analytics to enhance decision making: You can
be sure that your plant reaches its full potential and retains this
over the longer lifespan.
16
Siemens KT 10.1 · 2016
16/9
© Siemens AG 2016
Appendix
Industry Services
Industry Services – Portfolio overview
■ Overview
Plant Data
Services
Support and
Consulting
Services
Make your industrial processes transparent to gain improvements in productivity, asset availability, and energy efficiency.
Industry Online Support site for comprehensive information,
application examples, FAQs and support requests.
Production data is generated, filtered and translated with intelligent analytics to enhance decision-making.
Technical and Engineering Support for advice and answers
for all inquiries about functionality, handling, and fault
clearance.
This is done whilst taking data security into consideration and
with continuous protection against cyber attack threats.
www.industry.siemens.com/services/global/en/portfolio/
plant-data-services/Pages/index.aspx
Information & Consulting Services, e.g. SIMATIC System
Audit; clarity about the state and service capability of your automation system or Lifecycle Information Services; transparency
on the lifecycle of the products in your plants.
www.industry.siemens.com/services/global/en/portfolio/
support-consulting/Pages/index.aspx
Training
Services
From the basics and advanced to specialist skills, SITRAIN
courses provide expertise right from the manufacturer – and
encompass the entire spectrum of Siemens products and
systems for the industry.
Worldwide, SITRAIN courses are available wherever you need a
training course in more than 170 locations in over 60 countries.
www.industry.siemens.com/services/global/en/portfolio/
training/Pages/index.aspx
Spare Parts
Services
Are available worldwide for smooth and fast supply of spare
parts – and thus optimal plant availability. Genuine spare parts
are available for up to ten years. Logistic experts take care of
procurement, transport, custom clearance, storage and order
management. Reliable logistics processes ensure that components reach their destination as needed.
Asset optimization services help you design a strategy for parts
supply where your investment and carrying costs are reduced
and the risk of obsolescence is avoided.
www.industry.siemens.com/services/global/en/portfolio/
spare_parts/Pages/index.aspx
16
16/10
Siemens KT 10.1 · 2016
© Siemens AG 2016
Appendix
Industry Services
Industry Services – Portfolio overview
■ Overview (continued)
Repair
Services
Are offered on-site and in regional repair centers for fast restoration of faulty devices’ functionality.
Also available are extended repair services, which include additional diagnostic and repair measures, as well as emergency
services.
www.industry.siemens.com/services/global/en/portfolio/
repair_services/Pages/index.aspx
Retrofit and
Modernization
Services
Provide a cost-effective solution for the expansion of entire
plants, optimization of systems or upgrading existing products
to the latest technology and software, e.g. migration services for
automation systems.
Service experts support projects from planning through commissioning and, if desired over the entire extended lifespan, e.g.
Retrofit for Integrated Drive Systems for an extended lifetime of
your machines and plants
www.industry.siemens.com/services/global/en/portfolio/
retrofit-modernization/Pages/index.aspx
Field and
Maintenance
Services
Siemens specialists are available globally to provide expert field
and maintenance services, including commissioning, functional
testing, preventive maintenance and fault clearance.
All services can be included in customized service agreements
with defined reaction times or fixed maintenance intervals.
www.industry.siemens.com/services/global/en/portfolio/
field_service/Pages/index.aspx
Service
Programs and
Agreements
A technical Service Program or Agreement enables you to easily
bundle a wide range of services into a single annual or multiyear agreement.
You pick the services you need to match your unique requirements or fill gaps in your organization’s maintenance capabilities.
Programs and agreements can be customized as KPI-based
and/or performance-based contracts.
www.industry.siemens.com/services/global/en/portfolio/
service_programs/Pages/index.aspx
16
Siemens KT 10.1 · 2016
16/11
© Siemens AG 2016
Appendix
Industry Services
Online Support
■ Overview
Online Support is a comprehensive information system for all
questions relating to products, systems, and solutions that
Siemens has developed for industry over time. With more than
300,000 documents, examples and tools, it offers users of automation and drive technology a way to quickly find up-to-date
information. The 24-hour service enables direct, central access
to detailed product information as well as numerous solution
examples for programming, configuration and application.
The content, in six languages, is increasingly multimedia-based
– and now also available as a mobile app. Online support’s
“Technical Forum” offers users the opportunity to share information with each other. The “Support Request” option can be used
to contact Siemens’ technical support experts.
The latest content, software updates, and news via newsletters
and Twitter ensure that industry users are always up to date.
www.siemens.com/industry/onlinesupport
Online Support App
s
Using the Online Support app, you can access over 300,000
documents covering all Siemens industrial products – anywhere,
any time. Regardless of whether you need help implementing
your project, fault-finding, expanding your system or are planning a new machine.
You have access to FAQs, manuals, certificates, characteristic
curves, application examples, product notices (e.g. announcements of new products) and information on successor products
in the event that a product is discontinued.
Just scan the product code printed on the product directly using
the camera of your mobile device to immediately see all technical information available on this product at a glance.
The graphical CAx information (3D model, circuit diagrams or
EPLAN macros) is also displayed. You can forward this information to your workplace using the e-mail function.
The search function retrieves product information and articles
and supports you with a personalized suggestion list. You can
find your favorite pages – articles you need frequently – under
“mySupport”. You also receive selected news on new functions,
important articles or events in the News section.
16
16/12
Siemens KT 10.1 · 2016
Scan the QR code
for information on
our Online Support
app.
The app is available free of charge from the Apple App Store
(iOS) or from Google Play (Android).
https://support.industry.siemens.com/cs/ww/en/sc/2067
© Siemens AG 2016
Appendix
Subject index
Numerics
C
1- and 2-phase, 24 V DC ........................................................................... 6/8
1-phase / 1-2-phase / DC, AS-i 30 V (with data decoupling) .................. 14/2
1-phase, 12 V DC ........................................................................ 2/3, 3/6, 5/3
1-phase, 12 V DC (PSU100D) .................................................................. 9/4
1-phase, 15 V DC ...................................................................................... 3/9
1-phase, 2 x 15 V DC (SITOP dual) ......................................................... 9/21
1-phase, 24 V DC ............................................... 2/6, 3/12, 4/2, 5/7, 6/3, 9/33
1-phase, 24 V DC (for S7-1200) ................................................................ 8/9
1-phase, 24 V DC (for S7-1500 and ET200MP) ....................................... 8/11
1-phase, 24 V DC (for S7-300 and ET200M) ............................................. 8/3
1-phase, 24 V DC (PSU100D) ................................................................... 9/7
1-phase, 24 V DC (SITOP PSU100P, IP67) ............................................... 9/11
1-phase, 30 V DC (without data decoupling) ...........................................14/3
1-phase, 3-52 V DC (SITOP flexi 120 W) .................................................. 9/23
1-phase, 5 V DC ......................................................................................... 3/3
200-900 V DC / 24V DC/20A..................................................................... 9/31
24 V DC / 12 V DC/2.5 A........................................................................... 9/29
3-phase, 12 V DC ..................................................................................... 9/16
3-phase, 24 V DC ................................................................... 5/13, 6/13, 9/18
3-phase, 24 V DC (ET200pro PS, IP67) .................................................... 8/14
3-phase, 24 V DC (for ET200pro) ............................................................. 9/14
3-phase, 24 V DC (SITOP PSU300E)........................................................ 9/36
3-phase, 36 V DC ..................................................................................... 6/17
3-phase, 48 V DC ..................................................................................... 6/19
3-phase, basic units 24 V DC (PSU8600)................................................... 7/5
48-110V DC / 24 V DC/2 A........................................................................ 9/27
48-220V DC / 24 V DC/0.375 A................................................................. 9/25
Certificates ............................................................................................. 15/19
Conditions of sale and delivery .............................................................. 16/18
Customized SITOP products ...................................................................... 1/8
A
M
Accessories .............................................................................................. 12/2
Add-on modules ....................................................................................... 10/1
Alternative output voltages .............................................................. 9/21, 9/23
Article number index............................................................................... 16/15
Modular system, buffer (BUF8600) .......................................................... 7/13
Modular system, expansion of outputs (CNX8600).................................. 7/10
D
DC UPS battery modules ....................................................................... 11/28
DC UPS with battery modules ............................... 11/10, 11/18, 11/22, 11/28
DC UPS with capacitors ........................................................................... 11/3
DC/DC converters ......................................................... 9/25, 9/27, 9/29, 9/31
E
Export regulations .................................................................................. 16/18
F
Fusing of the output circuit 24 V DC, selectivity..................................... 15/13
H
High degree of protection ............................................................... 9/11, 9/14
I
Industry Services...................................................................................... 16/9
Industry Services – Portfolio ................................................................... 16/10
Information and Download Center, Social Media, Mobile Media ............. 16/8
Information and Ordering Options on the Internet and DVD.................... 16/7
Inrush current limiter............................................................................... 10/12
Installation guidelines, mouning areas and fixing options ....................... 15/9
L
LOGO!Power (BUF8600)............................................................................ 3/1
B
Battery charging .............................................................................. 9/16, 9/18
Battery charging with SITOP................................................................... 15/12
Buffer module ......................................................................................... 10/10
16
Siemens KT 10.1 · 2016
16/13
© Siemens AG 2016
Appendix
Subject index
N
T
Notes....................................................................................................... 16/17
Technical information and configuration .................................................. 15/1
The product range at a glance................................................................... 1/3
O
Online Services......................................................................................... 16/7
Online Support........................................................................................ 16/12
Ordering......................................................................................................... 3
Ordering data ........................................................................................... 13/3
P
Parallel connection ................................................................................. 15/10
Partner at Industry ....................................................................................16/4
Partner at Siemens.................................................................................... 16/3
Possible mains disturbances and causes ................................................ 15/8
Power supplies for AS interface................................................................ 14/1
Power supplies general ............................................................................ 15/2
R
Redundancy module ................................................................................ 10/3
S
Selection tables for power supplies............................................................ 1/6
Selectivity module..................................................................................... 10/6
Series connection to increase the voltage.............................................. 15/11
Siemens Automation Cooperates with Education............................ 16/5, 16/6
Siemens Partner Program......................................................................... 16/4
Siemens Training....................................................................................... 16/2
Simplify your education in automation...................................................... 16/5
SIPLUS power supplies introduction .........................................................13/2
SIPLUS power supplies ordering data ......................................................13/3
SITOP compact........................................................................................... 2/1
SITOP DC UPS........................................................................................ 11/22
SITOP DC UPS uninterruptible power supplies........................................ 11/1
SITOP in the SIMATIC Design..................................................................... 8/1
SITOP lite .................................................................................................... 4/1
SITOP modular............................................................................................ 6/1
SITOP modular, PSU8600 power supply system 7/1
SITOP Selection Tool ...................................................................................1/4
SITOP smart................................................................................................ 5/1
SITOP UPS1100 battery modules........................................................... 11/18
SITOP UPS1600 DC UPS modules......................................................... 11/10
Special applications ........................................................................ 9/33, 9/36
Special designs, special uses .....................................................................9/1
Standards and approvals ....................................................................... 15/18
Subject index .......................................................................................... 16/13
Supply systems data, line-side connection .............................................. 15/5
16
16/14
Siemens KT 10.1 · 2016
W
Wall mounting ............................................................................... 9/3, 9/4, 9/7
© Siemens AG 2016
Appendix
Article number index
3RK1
6EP1
3RK1901-1DE12-1AA0 ............................................................................. 14/4
3RK1901-1DE22-1AA0 ............................................................................. 14/4
3RK1901-1DG12-1AA0............................................................................. 14/4
3RK1901-1DG22-1AA0............................................................................. 14/4
3RK1901-3MA00....................................................................................... 14/4
3RK1901-3MB00....................................................................................... 14/4
3RK1902-0CJ0................................................................................. 8/16, 9/15
3RK1902-0CK00 ..............................................................................8/16, 9/15
3RK1911-2BE30 .............................................................................. 8/16, 9/15
3RK1911-2BF10............................................................................... 8/16, 9/15
3RK7271-1AA30-0AA0 ............................................................................. 14/4
6EP1311-1SH03 ......................................................................................... 3/5
6EP1311-1SH13 ......................................................................................... 3/5
6EP1321-1LD00 ......................................................................................... 9/6
6EP1321-1SH03 ......................................................................................... 3/8
6EP1321-5BA00 ......................................................................................... 2/5
6EP1322-1LD00 ......................................................................................... 9/6
6EP1322-1SH03 ......................................................................................... 3/8
6EP1322-2BA00 ......................................................................................... 5/6
6EP1322-5BA10 ......................................................................................... 2/5
6EP1323-2BA00 ......................................................................................... 5/6
6EP1331-1LD00 ....................................................................................... 9/10
6EP1331-1SH03 ....................................................................................... 3/16
6EP1331-5BA00 ....................................................................................... 2/12
6EP1331-5BA10 ....................................................................................... 2/12
6EP1332-1LB00.......................................................................................... 4/6
6EP1332-1LD00 ....................................................................................... 9/10
6EP1332-1LD10 ....................................................................................... 9/10
6EP1332-1SH43 ....................................................................................... 3/16
6EP1332-1SH52 ....................................................................................... 3/16
6EP1332-1SH71 ....................................................................................... 8/10
6EP1332-2BA20 ....................................................................................... 5/12
6EP1332-4BA00 ....................................................................................... 8/13
6EP1332-5BA00 ....................................................................................... 2/12
6EP1332-5BA10 ....................................................................................... 2/12
6EP1332-5BA20 ....................................................................................... 2/12
6EP1333-1AL12........................................................................................ 9/35
6EP1333-1LB00.......................................................................................... 4/6
6EP1333-1LD00 ....................................................................................... 9/10
6EP1333-2BA20 ....................................................................................... 5/12
6EP1333-3BA10 ....................................................................................... 6/12
6EP1333-3BA10-8AC0 ............................................................................. 6/12
6EP1333-4BA00 ....................................................................................... 8/13
6EP1333-7CA00 ....................................................................................... 9/13
6EP1334-1AL12........................................................................................ 9/35
6EP1334-1LB00.......................................................................................... 4/6
6EP1334-1LD00 ....................................................................................... 9/10
6EP1334-2BA20 ....................................................................................... 5/12
6EP1334-3BA10 ....................................................................................... 6/12
6EP1334-3BA10-8AB0 ............................................................................. 6/12
6EP1334-7CA00 ....................................................................................... 9/13
6EP1336-2BA10 ....................................................................................... 5/12
6EP1336-3BA10 ......................................................................................... 6/7
6EP1337-3BA00 ......................................................................................... 6/7
6EP1351-1SH03 ....................................................................................... 3/11
6EP1352-1SH03 ....................................................................................... 3/11
6EP1353-0AA00 ....................................................................................... 9/22
6EP1353-2BA00 ....................................................................................... 9/24
6EP1433-0AA00 ....................................................................................... 9/37
6EP1433-2BA20 ....................................................................................... 5/16
6EP1434-2BA20 ....................................................................................... 5/16
6EP1436-2BA10 ....................................................................................... 5/16
6EP1437-2BA20 ....................................................................................... 5/16
6EP1437-3BA10 ....................................................................................... 6/16
6EP1437-3BA20 ....................................................................................... 9/20
6EP1456-3BA00 ....................................................................................... 6/22
6EP1457-3BA00 ....................................................................................... 6/22
3RT1
3RT1900-1SB20 ..............................................................5/16, 6/7, 6/12, 6/16, 
.......................................................................6/18, 6/22, 7/9, 7/12, 7/14, 9/32, 
......................................................................................10/5, 10/9, 10/11, 12/2
3RX9
3RX9501-0BA00 .......................................................................................
3RX9501-1BA00 .......................................................................................
3RX9501-2BA00 .......................................................................................
3RX9502-0BA00 .......................................................................................
3RX9503-0BA00 .......................................................................................
3RX9511-0AA00 .......................................................................................
3RX9512-0AA00 .......................................................................................
3RX9513-0AA00 .......................................................................................
14/2
14/2
14/2
14/2
14/2
14/4
14/4
14/4
6AG1
6AG1305-1BA80-2AA0............................................................................. 13/3
6AG1307-1EA01-7AA0 ............................................................................. 13/3
6AG1307-1KA02-7AA0............................................................................. 13/3
6AG1331-1SH03-7AA0............................................................................. 13/3
6AG1332-1SH43-7AA0............................................................................. 13/3
6AG1332-1SH52-7AA0............................................................................. 13/3
6AG1332-1SH71-4AA0............................................................................. 13/3
6AG1332-1SH71-7AA0............................................................................. 13/3
6AG1332-4BA00-7AA0............................................................................. 13/3
6AG1333-4BA00-7AA0............................................................................. 13/3
6AG1333-3BA10-7AA0............................................................................. 13/3
6AG1334-2BA20-4AA0............................................................................. 13/3
6AG1334-3BA10-7AA0............................................................................. 13/3
6AG1337-3BA00-4AA0............................................................................. 13/3
6AG1337-3BA00-7AA0............................................................................. 13/3
6AG1434-2BA10-7AA0............................................................................. 13/3
6AG1436-2BA10-7AA0............................................................................. 13/3
6AG1437-3BA10-7AA0............................................................................. 13/3
6AG1505-0KA00-7AB0............................................................................. 13/3
6AG1505-0RA00-7AB0............................................................................. 13/3
6AG1507-0RA00-7AB0............................................................................. 13/3
6AG1931-2BA00-3AA0............................................................................. 13/4
6AG1931-2EC21-2AA0............................................................................. 13/4
6AG1931-2FC21-7AA0 ............................................................................. 13/4
6AG1961-2BA31-7AA0............................................................................. 13/4
6AG1961-2BA41-7AA0............................................................................. 13/4
6AG1961-3BA01-7AA0............................................................................. 13/4
6AG1961-3BA10-6AA0............................................................................. 13/4
6AG1961-3BA10-7AA0............................................................................. 13/4
6AG1961-3BA21-4AX0 ............................................................................. 13/4
6AG1961-3BA21-7AX0 ............................................................................. 13/4
16
Siemens KT 10.1 · 2016
16/15
© Siemens AG 2016
Appendix
Article number index
6EP1 (Fortsetzung)
6EP3
6EP1536-3AA00........................................................................................ 9/32
6EP1621-2BA00........................................................................................ 9/30
6EP1731-2BA00........................................................................................ 9/26
6EP1732-0AA00........................................................................................ 9/28
6EP1931-2DC21 ..................................................................................... 11/27
6EP1931-2DC31 ..................................................................................... 11/27
6EP1931-2DC42 .....................................................................................11/27
6EP1931-2EC21...................................................................................... 11/27
6EP1931-2EC31...................................................................................... 11/27
6EP1931-2EC42...................................................................................... 11/27
6EP1931-2FC21...................................................................................... 11/27
6EP1931-2FC42...................................................................................... 11/27
6EP1933-2EC41........................................................................................ 11/9
6EP1933-2EC51........................................................................................ 11/9
6EP1933-2NC01 ....................................................................................... 11/9
6EP1933-2NC11 ....................................................................................... 11/9
6EP1935-5PG01 ....................................................................................... 11/9
6EP1935-6MC01..................................................................................... 11/30
6EP1935-6MD11..................................................................................... 11/30
6EP1935-6MD31..................................................................................... 11/30
6EP1935-6ME21 ..................................................................................... 11/30
6EP1935-6MF01 ..................................................................................... 11/30
6EP1961-2BA00........................................................................................ 10/9
6EP1961-2BA11..................................................... 2/12, 3/16, 4/6, 5/12, 5/16,
..........................................................................................6/7, 6/12, 6/16, 10/9
6EP1961-2BA21................................................................ 4/6, 5/12, 5/16, 6/7,
.................................................................................................6/12, 6/16, 10/9
6EP1961-2BA31..................................................... 2/12, 3/16, 4/6, 5/12, 5/16,
..........................................................................................6/7, 6/12, 6/16, 10/9
6EP1961-2BA41................................................................ 4/6, 5/12, 5/16, 6/7,
.................................................................................................6/12, 6/16, 10/9
6EP1961-3BA01........................................... 5/12, 5/16, 6/7, 6/12, 6/16, 10/11
6EP1961-3BA10................................................................................. 6/7, 12/2
6EP1961-3BA21....................................................................... 5/12, 5/16, 6/7,
.................................................................................................6/12, 6/16, 10/5
6EP1962-2BA00..................................................... 2/12, 3/16, 4/6, 5/12, 5/16,
..........................................................................................6/7, 6/12, 6/16, 10/5
6EP1964-2BA00..................................................... 2/12, 3/16, 4/6, 5/12, 5/16,
..........................................................................................6/7, 6/12, 6/16, 10/5
6EP1967-2AA00...................................................................................... 10/12
6EP1971-1AA01........................................................................................ 9/35
6EP1971-1BA00................................................................................. 8/8, 12/2
6EP1971-2BA00........................................................................................ 12/2
6EP1971-5BA00................................................................................. 2/5, 2/12
6EP1975-2ES00 ............................................................................... 11/9, 12/2
6EP3333-8SB00-0AY0 ................................................................................ 6/7
6EP3334-8SB00-0AY0 ................................................................................ 6/7
6EP3424-8UB00-0AY0.............................................................................. 9/17
6EP3436-8MB00-2CY0............................................................................... 7/9
6EP3436-8SB00-0AY0 .............................................................................. 6/16
6EP3436-8SB00-2AY0 ................................................................................ 7/9
6EP3436-8UB00-0AY0.............................................................................. 9/20
6EP3437-8MB00-2CY0............................................................................... 7/9
6EP3437-8SB00-2AY0 ................................................................................ 7/9
6EP3446-8SB10-0AY0 .............................................................................. 6/18
16
16/16
Siemens KT 10.1 · 2016
6EP4
6EP4131-0GB00-0AY0 ........................................................................... 11/21
6EP4132-0GB00-0AY0 ........................................................................... 11/21
6EP4133-0GB00-0AY0 ........................................................................... 11/21
6EP4133-0JB00-0AY0 ............................................................................ 11/21
6EP4134-0GB00-0AY0 ........................................................................... 11/21
6EP4134-3AB00-0AY0............................................................................ 11/17
6EP4134-3AB00-1AY0............................................................................ 11/17
6EP4134-3AB00-2AY0............................................................................ 11/17
6EP4135-0GB00-0AY0 ........................................................................... 11/21
6EP4136-3AB00-0AY0............................................................................ 11/17
6EP4136-3AB00-1AY0............................................................................ 11/17
6EP4136-3AB00-2AY0............................................................................ 11/17
6EP4137-3AB00-0AY0............................................................................ 11/17
6EP4137-3AB00-1AY0............................................................................ 11/17
6EP4137-3AB00-2AY0............................................................................ 11/17
6EP4293-8HB00-0XY0 ...................................................................... 7/9, 7/14
6EP4295-8HB00-0XY0 ...................................................................... 7/9, 7/14
6EP4297-8HB00-0XY0 ...................................................................... 7/9, 7/14
6EP4297-8HB10-0XY0 ...................................................................... 7/9, 7/14
6EP4436-8XB00-0CY0 ...................................................................... 7/9, 7/12
6EP4437-8XB00-0CY0 ...................................................................... 7/9, 7/12
6ES7
6ES7148-4PC00-0HA0 .................................................................... 8/16, 9/15
6ES7305-1BA80-0AA0 ............................................................................... 8/8
6ES7307-1BA01-0AA0 ............................................................................... 8/8
6ES7307-1EA01-0AA0 ............................................................................... 8/8
6ES7307-1EA80-0AA0 ............................................................................... 8/8
6ES7307-1KA02-0AA0 ............................................................................... 8/8
6ES7390-6BA00-0AA0 ...................................................................... 8/8, 12/2
6ES7590-8AA00-0AA0 ............................................................................. 8/13
© Siemens AG 2016
Appendix
Notes
16
Siemens KT 10.1 · 2016
16/17
© Siemens AG 2016
Appendix
Conditions of sale and delivery
■ 1. General Provisions
By using this catalog you can acquire hardware and software
products described therein from Siemens AG subject to the
following Terms and Conditions of Sale and Delivery (hereinafter
referred to as "T&C"). Please note that the scope, the quality and
the conditions for supplies and services, including software
products, by any Siemens entity having a registered office
outside Germany, shall be subject exclusively to the General
Terms and Conditions of the respective Siemens entity. The
following T&C apply exclusively for orders placed with Siemens
Aktiengesellschaft, Germany.
1.1 For customers with a seat or registered office in
Germany
For customers with a seat or registered office in Germany, the
following applies subordinate to the T&C:
• the "General Terms of Payment"1) and,
• for software products, the "General License Conditions for
Software Products for Automation and Drives for Customers
with a Seat or Registered Office in Germany"1) and,
• for other supplies and services, the "General Conditions for
the Supply of Products and Services of the Electrical and
Electronics Industry"1).
1.2 For customers with a seat or registered office outside
Germany
For customers with a seat or registered office outside Germany,
the following applies subordinate to the T&C:
• the "General Terms of Payment"1) and,
• for software products, the "General License Conditions for
Software Products for Automation and Drives for Customers
with a Seat or Registered Office outside of Germany"1) and
• for other supplies and/or services, the "General Conditions for
Supplies of Siemens Industry for Customers with a Seat or
Registered Office outside of Germany"1).
■ 2. Prices
16
The prices are in € (Euro) ex point of delivery, exclusive of
packaging.
The sales tax (value added tax) is not included in the prices. It
shall be charged separately at the respective rate according to
the applicable statutory legal regulations.
Prices are subject to change without prior notice. We will charget
the prices valid at the time of delivery.
To compensate for variations in the price of raw materials (e.g.
silver, copper, aluminum, lead, gold, dysprosium and neodym),
surcharges are calculated on a daily basis using the so-called
metal factor for products containing these raw materials. A
surcharge for the respective raw material is calculated as a
supplement to the price of a product if the basic official price of
the raw material in question is exceeded.
The metal factor of a product indicates the basic official price
(for those raw materials concerned) as of which the surcharges
on the price of the product are applied, and with what method of
calculation.
An exact explanation of the metal factor can be downloaded at:
www.siemens.com/automation/salesmaterial-as/catalog/en/
terms_of_trade_en.pdf
To calculate the surcharge (except in the cases of dysprosium
and neodym), the official price from the day prior to that on which
the order was received or the release order was effected is used.
To calculate the surcharge applicable to dysprosium and
neodym ("rare earths"), the corresponding three-month basic
average price in the quarter prior to that in which the order was
received or the release order was effected is used with a onemonth buffer (details on the calculation can be found in the
explanation of the metal factor).
16/18
Siemens KT 10.1 · 2016
■ 3. Additional Terms and Conditions
The dimensions are in mm. In Germany, according to the
German law on units in measuring technology, data in inches
apply only to devices for export.
Illustrations are not binding.
Insofar as there are no remarks on the individual pages of this
catalog - especially with regard to data, dimensions and weights
given - these are subject to change without prior notice.
■ 4. Export regulations
We shall not be obligated to fulfill any agreement if such
fulfillment is prevented by any impediments arising out of
national or international foreign trade or customs requirements
or any embargoes and/or other sanctions.
Export of goods listed in this catalog may be subject to licensing
requirements. We will indicate in the delivery details whether
licenses are required under German, European and US export
lists. Goods labeled with "AL" not equal to "N" are subject to
European or German export authorization when being exported
out of the EU. Goods labeled with "ECCN" not equal to "N" are
subject to US re-export authorization.
The export indications can be viewed in advance in the
description of the respective goods on the Industry Mall, our
online catalog system. Only the export labels "AL" and "ECCN"
indicated on order confirmations, delivery notes and invoices
are authoritative.
Even without a label, or with label "AL:N" or "ECCN:N", authorization may be required i .a. due to the final disposition and
intended use of goods.
If you transfer goods (hardware and/or software and/or
technology as well as corresponding documentation, regardless
of the mode of provision) delivered by us or works and services
(including all kinds of technical support) performed by us to a
third party worldwide, you must comply with all applicable
national and international (re-)export control regulations.
If required for the purpose of conducting export control checks,
you (upon request by us) shall promptly provide us with all information pertaining to the particular end customer, final disposition and intended use of goods delivered by us respectively
works and services provided by us, as well as to any export
control restrictions existing in this relation.
The products listed in this catalog may be subject to
European/German and/or US export regulations. Any export
requiring approval is therefore subject to authorization by the
relevant authorities.
Errors excepted and subject to change without prior notice.
1) The text of the Terms and Conditions of Siemens AG can be
downloaded at
www.siemens.com/automation/salesmaterial-as/catalog/en/
terms_of_trade_en.pdf
© Siemens AG 2016
Catalogs
Digital Factory, Process Industries and Drives and Energy Management
Further information can be obtained from our branch offices listed at www.siemens.com/automation/partner
Interactive Catalog on DVD
Products for Automation and Drives
Building Control
GAMMA Building Control
Drive Systems
SINAMICS G130 Drive Converter Chassis Units
SINAMICS G150 Drive Converter Cabinet Units
SINAMICS GM150, SINAMICS SM150
Medium-Voltage Converters
SINAMICS PERFECT HARMONY GH180
Medium-Voltage Air-Cooled Drives
Germany Edition
SINAMICS G180
Converters – Compact Units, Cabinet Systems,
Cabinet Units Air-Cooled and Liquid-Cooled
SINAMICS S120 Chassis Format Units and
Cabinet Modules
SINAMICS S150 Converter Cabinet Units
SINAMICS DCM DC Converter, Control Module
SINAMICS DCM Cabinet
SINAMICS Inverters for Single-Axis Drives and
SIMOTICS Motors
SINAMICS G120P and SINAMICS G120P Cabinet
pump, fan, compressor converters
LOHER VARIO High Voltage Motors
Flameproof, Type Series 1PS4, 1PS5, 1MV4 and 1MV5
Frame Size 355 to 1000, Power Range 80 to 7100 kW
Three-Phase Induction Motors SIMOTICS HV,
SIMOTICS TN
• Series H-compact
• Series H-compact PLUS
High Voltage Three-phase Induction Motors
SIMOTICS HV Series A-compact PLUS
Three-Phase Induction Motors SIMOTICS HV,
Series H-compact
Synchronous Motors with Permanent-Magnet
Technology, HT-direct
DC Motors
SIMOREG DC MASTER 6RA70 Digital Chassis
Converters
SIMOREG K 6RA22 Analog Chassis Converters
Digital: SIMOREG DC MASTER 6RM70 Digital
Converter Cabinet Units
SIMOVERT PM Modular Converter Systems
SIEMOSYN Motors
MICROMASTER 420/430/440 Inverters
MICROMASTER 411/COMBIMASTER 411
Catalog
CA 01
ET G1
D 11
D 12
D 15.1
D 18.1
D 21.3
D 23.1
D 23.2
D 31
D 35
D 83.2
D 84.1
D 84.9
D 86.1
D 86.2
DA 12
DA 21.1
DA 21.2
DA 22
DA 45
DA 48
DA 51.2
DA 51.3
Low-Voltage Three-Phase-Motors
SIMOTICS Low-Voltage Motors
SIMOTICS FD Low-Voltage Motors
LOHER Low-Voltage Motors
MOTOX Geared Motors
SIMOGEAR Geared Motors
SIMOGEAR Gearboxes with adapter
D 81.1
D 81.8
D 83.1
D 87.1
MD 50.1
MD 50.11
Mechanical Driving Machines
FLENDER Standard Couplings
FLENDER High Performance Couplings
FLENDER Backlash-free Couplings
FLENDER SIP Standard industrial planetary gear units
MD 10.1
MD 10.2
MD 10.3
MD 31.1
Process Instrumentation and Analytics
Digital: Field Instruments for Process Automation
Digital: SIPART Controllers and Software
Products for Weighing Technology
Digital: Process Analytical Instruments
Digital: Process Analytics, Components for Continuous
Emission Monitoring
Low-Voltage Power Distribution and
Electrical Installation Technology
Catalog
SENTRON · SIVACON · ALPHA
Protection, Switching, Measuring and Monitoring
Devices, Switchboards and Distribution Systems
Standards-Compliant Components for
Photovoltaic Plants
Electrical Components for the Railway Industry
TÜV-certified Power Monitoring System
Components for Industrial Control Panels according
to UL Standards
3WT Air Circuit Breakers up to 4000 A
3VT Molded Case Circuit Breakers up to 1600 A
Digital: SIVACON System Cubicles, System Lighting
and System Air-Conditioning
Digital: ALPHA Distribution Systems
ALPHA FIX Terminal Blocks
SIVACON S4 Power Distribution Boards
SIVACON 8PS Busbar Trunking Systems
Digital: DELTA Switches and Socket Outlets
LV 10
Motion Control
SINUMERIK 840
Equipment for Machine Tools
SINUMERIK 808
Equipment for Machine Tools
SINUMERIK 828
Equipment for Machine Tools
SIMOTION, SINAMICS S120 & SIMOTICS
Equipment for Production Machines
Digital: Drive and Control Components for Cranes
LV 11
LV 12
LV 14
LV 16
LV 35
LV 36
LV 50
LV 51
LV 52
LV 56
LV 70
ET D1
NC 62
NC 81.1
NC 82
PM 21
CR 1
Power Supply
SITOP Power supply
KT 10.1
Safety Integrated
Safety Technology for Factory Automation
SI 10
SIMATIC HMI / PC-based Automation
Human Machine Interface Systems/
PC-based Automation
ST 80/
ST PC
SIMATIC Ident
Industrial Identification Systems
ID 10
SIMATIC Industrial Automation Systems
Products for Totally Integrated Automation
SIMATIC PCS 7 Process Control System
System components
SIMATIC PCS 7 Process Control System
Technology components
Add-ons for the SIMATIC PCS 7
Process Control System
ST 70
ST PCS 7
ST PCS 7 T
ST PCS 7 AO
SIMATIC NET
Industrial Communication
IK PI
SIRIUS Industrial Controls
Digital: SIRIUS Industrial Controls
IC 10
Digital: These catalogs are only available as a PDF.
FI 01
MP 31
WT 10
AP 01
AP 11
Information and Download Center
Digital versions of the catalogs are available on the Internet at:
www.siemens.com/industry/infocenter
There you’ll find additional catalogs in other languages.
Please note the section “Downloading catalogs” on page
“Online services” in the appendix of this catalog.
© Siemens AG 2016
Security information
Siemens provides products and solutions with
industrial security functions that support the
secure operation of plants, systems, machines
and networks.
In order to protect plants, systems, machines
and networks against cyber threats, it is necessary
to implement – and continuously maintain – a
holistic, state-of-the-art industrial security
concept. Siemens’ products and solutions only
form one element of such a concept.
Customer is responsible to prevent unauthorized
access to its plants, systems, machines and networks. Systems, machines and components should
only be connected to the enterprise network or
the internet if and to the extent necessary and
with appropriate security measures (e.g. use of
firewalls and network segmentation) in place.
Additionally, Siemens’ guidance on appropriate
security measures should be taken into account.
For more information about industrial security,
please visit
http://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends to apply product
updates as soon as available and to always use
the latest product versions. Use of product versions that are no longer supported, and failure
to apply latest updates may increase customer’s
exposure to cyber threats.
To stay informed about product updates, subscribe
to the Siemens Industrial Security RSS Feed under
http://www.siemens.com/industrialsecurity.
Siemens AG
Process Industries and Drives
Process Automation
Postfach 48 48
90026 NÜRNBERG
GERMANY
www.siemens.com/automation
Subject to change without prior notice
Article No. E86060-K2410-A101-B2-7600
W-FPN6Z-PD-PAK13 / Dispo 10001
KG 0616 2. S 248 En / IWI TSTP
Printed in Germany
© Siemens AG 2016
The information provided in this catalog contains merely general
descriptions or characteristics of performance which in case of actual
use do not always apply as described or which may change as a result
of further development of the products. An obligation to provide the
respective characteristics shall only exist if expressly agreed in the
terms of contract. Availability and technical specifications are subject
to change without notice.
All product designations may be trademarks or product names
of Siemens AG or supplier companies whose use by third parties
for their own purposes could violate the rights of the owners.
Token fee: 3.00 €
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement