Fume Hood Controller - Price Critical Controls

Fume Hood Controller - Price Critical Controls
MANUAL – INSTALLATION
Fume Hood Controller
FHC Series
v200 – Issue Date: 03/26/15
© 2015 Price Industries Limited. All rights reserved.
FUME HOOD CONTROLLER
TABLE OF CONTENTS
Section 1 - Introduction
Product Overview........................................................... 1
Fume Hood Controller (FHC) Features............................ 1
Section 4 - Balance & Verification
Balance & Verification................................................... 20
Section 5 - Display Navigation
Fume Hood Interface (FHI) Features............................... 2
FHI - Initial Start-up...................................................... 21
Sidewall Sensor (SWS) Features..................................... 2
Information Menu......................................................... 21
Sash Position Sensor (SPS) Features............................. 2
Controller..................................................................... 22
Section 2 - Installation & Mounting
Step-by-Step Installation................................................ 3
Service Menu............................................................... 22
Section 6 - Advanced
Fume Hood Location Considerations............................. 5
Setup Wizard Menu...................................................... 23
FHC Installation & Mounting........................................... 6
Service Menu Expanded.............................................. 26
Sidewall Sensor Installation & Mounting.......................... 7
Alarm Points Menu....................................................... 28
Sash Position Sensor Installation & Mounting................. 8
Occupancy Menu......................................................... 29
Wiring Diagram.............................................................. 9
Input Menu................................................................... 29
Section 3 - Sash, Sidewall & Hybrid Configuration
Output Menu................................................................ 29
Control Settings........................................................... 11
Network Menu............................................................. 30
A. Equipment Calibration - Sidewall.............................. 12
Occupancy Priorities.................................................... 30
B. Equipment Calibration - Sash.................................. 13
FHI Set-Up Menu......................................................... 31
C. Sidewall - Control Method....................................... 15
Diagnostic Menu.......................................................... 32
D. Sash - Control Method ........................................... 16
E. Hybrid - Control Method.......................................... 18
IMPORTANT NOTES
CAUTION
This mark indicates an important point for the proper
function of the fume hood and the FHC. Improper
installation or setup may cause unit failure and
contamination of the laboratory space. Pay close
attention to all caution points throughout this manual.
Application Support
678.578.7495
[email protected]
www.pricecriticalcontrols.com
FUME HOOD CONTROLLER
SECTION 1 - INTRODUCTION
Product Overview
Fume Hood Controller (FHC) Features
Laboratory fume hoods serve as
ventilation systems that efficiently
exhaust chemical vapors, mist, and
fumes. Fume hoods also provide a
barrier protecting occupants from
certain reactions, spills, and even fires.
In most cases special fans exhaust the
fumes outside, which greatly dilute their
concentration and reduce their harmful
effects. In some cases a specialized
scrubber is also required to remove the
vapors from the exhaust air.
The Fume Hood Controller can ensure a safe working environment by constantly
monitoring and adjusting the exhaust to maintain a correct face velocity. The
main control inputs are sash sensors and sidewall sensors. Sash sensors use a
potentiometer attached to the sash to measure the current height. Face velocity in
feet per minute (FPM) is calculated in real time. Sidewall sensors use an extremely
sensitive, low pressure sensor to measure the negative pressure in the hood
compared with the lab space.
Fume hoods require constant exhaust
airflow to ensure that none of the air
entering the fume hood ever escapes
back into the laboratory space. This
ensures the safety of the user and of
any other occupants of the room or
building. The exhaust airflow, measured
in cubic feet per minute (CFM), creates
a face velocity across the sash opening.
This is the industry standard measure
of fume hood safety. Typically the
face velocity of a fume hood must be
between 80 – 100 feet per minute
(FPM), but this can vary based on local
codes or the fume hood design. It is
important to note the required face
velocity for the hood you are using.
•
16 bit – high speed flash based microprocessor with watch dog timer, brown
out reset
•
Multi-stage surge protection against voltage spikes on 24 VAC input
•
Simple connections to sidewall sensors using RJ-12 jacks
•
3 Sash position inputs (10kΩ)
•
2 binary outputs rated at 0.5 amps each, protected with thermal fuse
(RED LED on trip)
•
1 binary output (dry contact)
•
2 analog outputs (0-10 VDC), configurable for actuator and pressure points
•
2 configurable binary inputs
•
Pluggable terminal blocks
•
Mnet high-speed fume hood network port
•
1 LM(X) Price Venturi Valve input
•
1 pressure port input, 0”- 5” w.c. (For measuring DP across Price Venturi Valve)
•
LED’s for Lnet data TX/RX, Lnet wiring fault, and RS-45 termination
CAUTION
A higher face velocity is not always
safer. Too high a face velocity can
cause turbulence within the fume hood,
which can cause issues with spillage/
blowback.
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
1
FUME HOOD CONTROLLER
SECTION 1 - INTRODUCTION
Fume Hood Interface
(FHI) Features
•
Backlit 14x2 LCD Interface with true
character display
•
LED side bars offer 180 degree
viewing of current room status
•
Variety of colors displayed to
indicate room status
•
Password protected menu
•
Easy to use MENU system for fast
and simple setup of system
•
Service port on back for use with
Price LINKER2 setup software
•
Included RJ45 plenum rated cable
for fast, error free hookup
•
Setup Wizard – walk through setup
of FHC when first powered up
FUME HOOD INTERFACE
SIDEWALL SENSOR
Sidewall Sensor (SWS) Features
•
Ultra Low flow digital temperature
compensated pressure transducer
•
25 ft. sensor cable with quickconnect installation
•
Sidewall assembly with easy-tomount hardware
Sash Position Sensor (SPS) Features
SASH POSITION SENSOR
•
Ultra long life potentiometer (over
250,000 cycles)
•
Stainless steel cable for stability
•
Metal mounting ring for stable
installation and reliability
•
Thick plastic cover for protection
against airborne chemical agents
2
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
FUME HOOD CONTROLLER
SECTION 2 - INSTALLATION & MOUNTING
Step-by-Step Installation
1. REQUIRED ITEMS
1.Fume Hood Controller
You will need the items shown.
a.Remove Fume Hood Controller
from packaging.
NOTE: The FHC will generally be
factory mounted on the vavle
if ordered with a Price Venturi
Valve.
NOTE: Installation & Mounting
instructions on page 6.
VENTURI VALVE
FUME HOOD CONTROLLER (FHC)
2. REQUIRED ITEMS
2. Price Fume Hood Interface
You will need the items shown.
a.Remove the Price Fume Hood
Interface from packaging.
b.Mount the interface to the front of
the fume hood.
c.Connect one end of the RJ-45
cable to the back of the FHI. The
other end connects to the FHC
mounted on the fume hood exhaust
venturi valve.
3.Sidewall Sensor (if available)
FUME HOOD INTERFACE (FHI)
RJ-45 PLENUM RATED FHI CABLE
3. REQUIRED ITEMS
You will need the items shown.
a.Remove the sidewall sensor from
packaging; Ensure you have all
parts required.
b.Using one of the hollowed bolts
provided, mount the sidewall sensor
5” up and 5” inwards from the
base of the fume hood sash in its
fully open position (not just the
working height).
c.Using the male pressure port
provided, mount the second
hollowed bolt to the front of the
fume hood (generally just above the
Fume Hood Interface).
SIDEWALL SENSOR
HOLLOWED BOLT (X2)
SENSOR CABLE
KINK-RESISTANT TUBING
MALE BRASS PRESSURE PORT (X1)
Continued on next page...
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
3
FUME HOOD CONTROLLER
SECTION 2 - INSTALLATION & MOUNTING
d.Connect this pressure port to the
port on the back of the sidewall
sensor using the rubber tubing
provided.
4. REQUIRED ITEMS
e.Connect the sensor cable (RJ12 connector to black circular
connector) to the back of the
sidewall sensor and run this cable
back to the FHC now mounted to
the venturi valve.
NOTE: Installation & Mounting
instructions on page 7.
4.Sash Position Sensor (if available)
You will need the items shown.
a.Remove the Sash Position Sensor
from packaging; Ensure the
stainless steel cable is in proper
working order. Do not let the
cable retract rapidly on its own.
b.Mount the sensor on the internal
sidewall of the fume hood. The
mounting location should be as
close to the sash as possible without
restricting the sash movement.
Ensure that the cable of the sensor
extends in the same direction as the
movement of the sash.
c.Screw the metal ring on the end
of the sensor cable to the sash.
Ensure that the cable does not
restrict the movement of the sash.
d.Run the sensor cable back to
the FHC now mounted to the
venturi valve.
NOTE: Installation & Mounting
instructions on page 8.
5. Fume Hood Controller Wiring
a.Connect all sensors to the FHC and
run high power lines to the venturi
valve control box.
NOTE: Installation & Mounting
instructions on page 9.
4
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
SASH POSITION SENSOR
FUME HOOD CONTROLLER
SECTION 2 - INSTALLATION & MOUNTING
Fume Hood Location
Considerations
•
Ensure supply/exhaust overhead
diffusers/returns are installed away
from fume hood. Direct airflow
running across the ceiling and then
down the face of the fume hood
will greatly affect the SIDEWALL
SENSOR and general performance
of the hood
•
Ensure hood is located away from
pedestrian traffic and doors
•
Ensure fume hood has all
components installed properly –
such as air foils and sills.
FUME HOOD LOCATION CONSIDERATION
DIFFUSER
CAUTION
The location of the fume hood
and overhead diffusers is critical
to proper safety and performance.
These guidelines will ensure the
effectiveness of the fume hood and
the FHC.
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
5
FUME HOOD CONTROLLER
SECTION 2 - INSTALLATION & MOUNTING
Fume Hood Controller (FHC)
Installation & Mounting
•
Open the controls enclosure on
the Price Venturi Valve currently
installed in the fume hood exhaust
duct.
•
Follow the wiring diagram found
on page 9 for the FHC electrical
installation.
INSTALLATION & MOUNTING
VENTURI
VALVE
DUCT
CAUTION
The Fume Hood Controller is factory
mounted on the valve when ordered
with a Price Venturi Valve. Only electrical
installation is required.
Ensure the valve is facing the
correct direction based on the
airflow and is also mounted in the
correct orientation (vertical or
horizontal).
6
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
HIGH
PRESSURE
PORT
LOW
PRESSURE
PORT
AIRFLOW
DIRECTION
FUME HOOD CONTROLLER
SECTION 2 - INSTALLATION & MOUNTING
Sidewall Sensor (SWS) Installation
& Mounting
•
Ensure the sash is in the fully open
position (not just to working height)
•
Inside the fume hood, with the
sash in the fully open position,
drill a 5/16” hole 5” above and 5”
inward from the base of the sash in
the fully open position. (Not just the
working height.)
•
Drill a second 5/16” hole on the
front of the fume hood near the
PSWS. The second hole must be
no more than 12” from the SWS.
•
Using the male brass pressure port
provided, attach one hollowed bolt
to the front of the fume hood so
that the rounded side faces out.
Attach the second hallowed bolt
to the inside of the fume hood,
securing the PSWS.
•
Use the kink-resistant tubing to
attach the brass pressure port from
the SWS to the brass pressure port
that was just mounted.
INSTALLATION & MOUNTING LOCATION
INSTALLATION & MOUNTING DETAILS
THE SIDEWALL SENSOR IS
MOUNTED BEHIND THE WALL, IN
THE FUME HOOD PLENUM, USING A
HOLLOWED BOLT PROVIDED.
CAUTION
Mounting position is critical to ensure
the accuracy of the PSWS. Ensure that
there are no sharp bends or kinks in the
tubing during the installation. Improper
installation will cause failure of the
PSWS.
HOLLOWED
BOLT #2
HOLLOWED
BOLT #1
KINK
RESISTANT
TUBING
BRASS
PRESSURE
PORT
BRASS
PRESSURE
PORT
SIDEWALL
SENSOR
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
7
FUME HOOD CONTROLLER
SECTION 2 - INSTALLATION & MOUNTING
Sash Position Sensor
Installation & Mounting
•
Mount the sash sensor on internal
sidewall of the hood so that it will
not interfere with the mechanical
operation of the fume hood sash.
•
Ensure the sensor is as close to the
sash as possible so that the cable is
completely parallel to the sash in all
positions.
•
Raise the sash to the fully open
position (not just the working
height). Screw the metal ring onto
the sash. Ensure that the point of
contact is chosen such that the
cable is long enough to allow the
sash to close fully.
•
INSTALLATION & MOUNTING
MOUNTED ON
THE INTERNAL
SIDE WALL
SASH POSITION
SENSOR CONNECTED
TO SASH BY SCREW
Once mounted, raise and lower the
sash several times to ensure that
the cable is clear of all obstructions
and moves freely with the sash.
CAUTION
The sash position sensor cable must
be parallel to the direction of sash
movement. Any angle in the cable could
cause severe sensitivity issues and
improper flow settings.
INSTALLATION & MOUNTING
PRICE SASH SENSOR
METAL RING
8
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
FUME HOOD CONTROLLER
SECTION 2 - INSTALLATION & MOUNTING
Wiring Diagram
Ensure proper voltage is available for the FHC transformer
in the enclosure. Double check all labels and wiring before
applying high voltage.
CAUTION
The FHC is a 24 VAC low voltage controller. Do not apply any
voltage above 24 VAC to controller.
1. Ensure disconnect switch is off. Route high voltage line to
L1/L2(N) terminal block using knockout/cable clamp
(by others).
3. Connect AO1 terminal block space to the damper
actuator on the exhaust duct of the unit.
4. Connect the sash sensor to the first Sash Position Sensor
location on the FHC.
5. Connect green RJ12 (telephone type 6 position) cable
to jack labeled Sidewall Sensor 1 on FHC. Connect the
other end with the black (locking) connector into Sidewall
Sensor 1. Ensure cable is not twisted, kinked or pinched
during installation. The green LED above Sidewall Sensor
1 on the FHC will be green when powered up and
functioning properly.
2. Connect blue RJ-45 (network type 8 position) plenumrated cable to jack labeled Interface on the FHC. Connect
the other end to the back of the FHI mounted on the side
of the fume hood.
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
9
FUME HOOD CONTROLLER
SECTION 2 - INSTALLATION & MOUNTING
WIRING DIAGRAM
10
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
FUME HOOD CONTROLLER
SECTION 3 - SASH, SIDEWALL & HYBRID CONFIGURATION
Control Settings
No Control
This choice disables all control.
CAUTION
Choosing this option will turn off all
control aspects of the FHC. The device
will now only monitor the face velocity of
the unit, but will not change the airflow
or face velocity of the unit.
Control Type
Response
Time
Accuracy
Face
Velocity
Airflow
Control
Stability
Sash
Sensor Control
Very Fast
Moderate
Calculated
Yes
Very Stable
Sidewall
Sensor Control
Moderate
Very High
Measured
Yes
Stable
Hybrid Control
Very Fast
Very High
Measured
Yes
Very Stable
Sidewall Sensor Control
This method measures the face velocity
through the fume hood by measuring
the pressure within the unit from the
sidewall sensor. This method will control
face velocity. Refer to Section 3A for
configuration.
Sash Sensor Control
This method calculates the face velocity
using the dimensions of the fume hood
opening and the current CFM. This
method will control face velocity. Refer
to Section 3A for configuration.
Hybrid Control
This method is an optimized
combination of both sidewall sensor
and sash sensor control. It is the most
effective method of fume hood control
and is recommended in all cases. Refer
to Section 3D for configuration.
This should only be chosen if both a
sidewall sensor and a sash sensor
are connected.
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
11
FUME HOOD CONTROLLER
SECTION 3 - SASH, SIDEWALL & HYBRID CONFIGURATION
A. Equipment Calibration - Sidewall
WELCOME!
SETUP WIZARD
DETECTED
EQUIPMENT
SIDEWALLSNSR1
DETECTED
SASH 1
NOT DETECTED
OPEN THE SASH
TO WORKHEIGHT
CAL VALVE
OK
The beginning of the setup wizard will detect the sash and sidewall sensors that are connected.
NOTE: For safety purposes if no sensors are detected the controller will open the valve fully open.
Determines if sidewall sensors are detected. (up to 2 devices).
Determines if sash sensors are detected. (up to 3 devices).
Open the sash to working height. Typically 18 inches.
Prompt confirming that controller will now calibrate the valve. Press Enter to continue.
Calibration takes 60 seconds. Do not move the sash during this time.
PUT TAPE OVER
SIDEWALLSNSOR
A message will prompt the installer to put tape over the sidewall sensors to being the calibration process.
ZERO SWSENSOR
OK
A count from 60 sec will indicate that the sidewall is zeroing. Ensure that tape is placed over the sidewall sensors both
inside and outside the fume hood. After the countdown is complete wait for the setting it to save to continue.
REMOVE TAPE
OK
OPEN THE SASH TO
WORKINGHEIGHT
STABLE?
100 FPM
After calibration is complete remove the tape. This concludes sidewall setup.
If sash sensors are detected (up to 3) a message prompting the installer to open the sash
to working height (typically 18”) will start the sash calibration process.
Wait for the airflow measurement to stabilize. Once you have a stable reading, press Enter to continue to the next sash sensor.
FPM AT SCALE
100 FPM
Comparing measurements made by an external airflow measurement device, such as a Short Ridge Instrument, and the
reading on the FHI, view if any adjustments are required to match the measurements made by the Short Ridge Instrument.
SENSOR SCALE
1.000
Comparing measurements made by an external airflow measurement device, such as a Short Ridge Instrument, and
the reading on the FHI, adjust the scale to match the measurements made by the Short Ridge Instrument.
FPM AT SCALE
100 FPM
Check your scale after adjusting sensor scale.
SW SCALE OK?
YES
Select yes if FPM are adequate or no to repeat scaling.
MIN CFM
0 CFM
12
At initial power up the installer will have to step through the wizard. Ensure that
all necessary sensors are installed and connected to the FHC
Minimum allowable cfm.
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
FUME HOOD CONTROLLER
SECTION 3 - SASH, SIDEWALL & HYBRID CONFIGURATION
A. Equipment Calibration - Sidewall Continued...
MAX CFM
3000 CFM
AIRFLOWSOURCE
KAVLICOSENSOR
K FACTOR
0
CONTROL METHOD
SIDEWALL CTRL
Maximum allowable cfm.
Configure where airflow is being measured, such as LM module, Kavlico sensor, or no source.
Contact Price Ltd for more information. Available with Kavlico Senor only.
Refer to Section 3C for Sidewall Control, or continue to Sash Calibration if a Hybrid configuration (Section 3E) is requested.
B. Equipment Calibration - Sash
WELCOME!
SETUP WIZARD
DETECTED
EQUIPMENT
SIDEWALLSNSR1
NOT DETECTED
SASH 1
DETECTED
OPEN THE SASH
TO WORKHEIGHT
CAL VALVE
OK
At initial power up the installer will have to step through the wizard. Ensure that
all necessary sensors are installed and connected to the FHC
The beginning of the setup wizard will detect the sash and sidewall sensors that are connected.
NOTE: For safety purposes if no sensors are detected the controller will open the valve.
Determines if sidewall sensors are detected. (up to 2 devices ).
Determines if sash sensors are detected. (up to 3 devices ).
Open the sash to working height. Typically 18 inches.
Prompt confirming that controller will now calibrate the valve. Press Enter to continue.
Calibration takes 60 seconds. Do not move the sash during this time.
MIN CFM
0 CFM
Minimum fume hood cfm.
MAX CFM
3000 CFM
Maximum fume hood cfm.
CALIBRATING
SASH #1
SASH TYPE
VERTICAL
Shows the sash that will be calibrated in the next steps. This section will repeat for
each sash if multiple sash sensors are connected to the FHC.
Choose the style of the sash being calibrated.
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
13
FUME HOOD CONTROLLER
SECTION 3 - SASH, SIDEWALL & HYBRID CONFIGURATION
B. Equipment Calibration - Sash Continued...
MAX HEIGHT
25.0 IN
Measure the height of the sash at its highest position and enter this value in inches.
MIN HEIGHT
1.0 IN
Measure the height of the sash at its lowest position and enter this value in inches.
FULLYOPENSASH
OK
Place the sash in the fully open position and press the Enter/Menu button to save this position in the FHC memory.
CLOSE SASH
OK
Place the sash in the fully closed position and press the Enter/Menu button to save this position in the FHC memory.
SASH WIDTH
60.0 IN
Measure the width of the sash and enter this value in inches. NOTE: Min Height, Max Height, and sash width are used
by the FHC to calculate face velocity. It is very important that these measurements are taken as accurately
as possible. Inaccurate measurements could cause unit failure and contamination of the laboratory space.
AIRFLOWSOURCE
KAVLICOSENSOR
K FACTOR
0
CONTROL METHOD
SASH
14
Configure where airflow is being measured, such as LM module, Kavlico sensor, or no source.
Contact Price Ltd for more information. Available with Kavlico Sensor.
Refer to Section 3D for Sash Control, or refer to Sidewall Calibration (Section 3C) if a Hybrid configuration
(Section 3E) is requested.
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
FUME HOOD CONTROLLER
SECTION 3 - SASH, SIDEWALL & HYBRID CONFIGURATION
C. Sidewall - Control Method
CONTROLMETHOD
SIDEWALL CTRL
OCC. SETPOINT
100 FPM
Control Method determines the devices used to control the airflow to and from the fume hood. See section 3 for a more details.
Set the minimum face velocity set point while room is occupied.
DEADBAND
10 FPM
Set the minimum face velocity while room is in dead band. Sets the sensitivity
of the FHC; a lower dead-band creates a higher sensitivity.
CAL VALVE
OK
This causes the valve to cycle through its range to calibrate the response. A countdown will
be displayed until the valve calibration is complete. Available with Linear Cal.
LOW FPM ALARM
80 FPM
Set the low alarm point for the face velocity of the fume hood.
HIGH FPM ALARM
120 FPM
Set the high alarm point for the face velocity of the fume hood.
NETWORK TYPE
MNET
Choose between Mnet and BACnet.
MNET ADDRESS
1
Set the unique network address of the FHC with a maximum of 16 devices.
EOL TERM
DISABLED
End of line termination - Enable this point if the current FHC is the final controller on the network
chain. Disable this point if the current FHC is not the final controller on the network chain.
CALIBRATION
COMPLETE
Calibration is complete.
PRESS MENU
TO EXIT
Exit to Service Menu.
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
15
FUME HOOD CONTROLLER
SECTION 3 - SASH, SIDEWALL & HYBRID CONFIGURATION
D. Sash - Control Method
CONTROLMETHOD
SASH CTRL
OCC. SETPOINT
100 FPM
DEADBAND
10 FPM
SETUP
SASH #1
SASHCTLMETHOD
LINEAR CAL.
CAL VALVE
OK
16
Control Method determines the devices used to control the airflow to and from the fume hood. See section 3 for a more details.
Set the minimum face velocity while room is occupied
Set the minimum face velocity while room is in dead band. Sets the sensitivity
of the FHC; a lower dead-band creates a higher sensitivity.
Choose a method to calibrate the sash you wish to calibrate.
Choose a method to calibrate the sash you wish to calibrate. Linear, Cal Manually, or Cal. From SW.
Only available with Linear Cal as the Sash Control Method.
OCCUPIED CAL.
OK
Repeats for 3”, 13”, 19”, and fully open sash heights. This menu will also repeat for Setback Cal, and is only available
with ‘Cal. Manually’ as the Sash Control Method. Manual Cal will have you enter an FPM instead of a Stable FPM.
CLOSE SASH
OK
Repeats for 3”, 13”, 19”, and fully open sash heights. This menu will also repeat for Setback Cal, and is only available
with ‘Cal. Manually’ as the Sash Control Method. Manual Cal will have you enter an FPM instead of a Stable FPM.
ENTER FPM
100 FPM
Repeats for 3”, 13”, 19”, and fully open sash heights. This menu will also repeat for Setback Cal, and is only available
with ‘Cal. Manually’ as the Sash Control Method. Manual Cal will have you enter an FPM instead of a Stable FPM.
OPEN SASH 3”
OK
Repeats for 3”, 13”, 19”, and fully open sash heights. This menu will also repeat for Setback Cal, and is only available
with ‘Cal. Manually’ as the Sash Control Method. Manual Cal will have you enter an FPM instead of a Stable FPM.
SETBACK CAL.
OK
Repeats for 3”, 13”, 19”, and fully open sash heights. This menu will also repeat for Setback Cal, and is only available
with ‘Cal. Manually’ as the Sash Control Method. Manual Cal will have you enter an FPM instead of a Stable FPM.
LOW FPM ALARM
80 FPM
Set the low alarm point for the face velocity of the fume hood.
HIGHFPM ALARM
120 FPM
Set the high alarm point for the face velocity of the fume hood.
FPM ALARMHGHT
3.0 IN
FPM Alarm Height: set the minimum height that allows for a height FPM alarm.
NETWORK TYPE
MNET
Choose between Mnet and BACnet.
MNET ADDRESS
1
Set the unique network address of the FHC with a maximum of 16 devices.
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
FUME HOOD CONTROLLER
SECTION 3 - SASH, SIDEWALL & HYBRID CONFIGURATION
D. Sash - Control Method Continued...
EOL TERM
DISABLED
End of line termination – Enable this point if the current FHC is the final controller on the network
chain. Disable this point if the current FHC is not the final controller on the network chain.
CALIBRATION
COMPLETE
Calibration is complete.
PRESS MENU
TO EXIT
Exit to Service Menu.
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
17
FUME HOOD CONTROLLER
SECTION 3 - SASH, SIDEWALL & HYBRID CONFIGURATION
E. Hybrid - Control Method
CONTROLMETHOD
HYBRID
Control Method determines the devices used to control the airflow to and from the fume hood. See section 3 for a more details.
MONITORMETHOD
SW MONITOR
Monitor Method determines the devices used to monitor the airflow to and from the fume hood.
OCC. SETPOINT
100 FPM
DEADBAND
10 FPM
SETUP
SASH #1
18
Set the minimum face velocity set point while room is occupied.
Set the minimum face velocity while room is in dead band. sets the sensitivity
of the FHC; a lower dead-band creates a higher sensitivity.
Choose a method to calibrate the sash you wish to calibrate.
SASHCTLMETHOD
CAL. FROM SW
Choose a calibration method for the sash you wish to calibrate. Linear Cal., Cal. Manually,
Cal. From SW. NOTE: For Hybrid configuration, use Cal. From SW.
CAL VALVE
OK
This causes the valve to cycle through its range to calibrate the response. A countdown will
be displayed until the valve calibration is complete. Available with Linear Cal.
OCCUPIED CAL.
OK
Repeats for 3”, 13”, 19”, and fully open. This menu will also repeat for Setback Cal, and available with Cal. Manually,
and Manual Cal, as the Sash Control Method. Manual Cal will have you enter an FPM instead of a Stable FPM.
CLOSE SASH
OK
Repeats for 3”, 13”, 19”, and fully open. This menu will also repeat for Setback Cal, and available with Cal. Manually,
and Manual Cal, as the Sash Control Method. Manual Cal will have you enter an FPM instead of a Stable FPM.
STABLE?
0 FPM
Repeats for 3”, 13”, 19”, and fully open. This menu will also repeat for Setback Cal, and available with Cal. Manually,
and Manual Cal, as the Sash Control Method. Manual Cal will have you enter an FPM instead of a Stable FPM.
OPEN SASH 3”
OK
Repeats for 3”, 13”, 19”, and fully open. This menu will also repeat for Setback Cal, and available with Cal. Manually,
and Manual Cal, as the Sash Control Method. Manual Cal will have you enter an FPM instead of a Stable FPM.
CAL SETBACK?
NO
Repeats for 3”, 13”, 19”, and fully open. This menu will also repeat for Setback Cal, and available with Cal. Manually,
and Manual Cal, as the Sash Control Method. Manual Cal will have you enter an FPM instead of a Stable FPM.
LOW FPM ALARM
80 FPM
Set the low alarm point for the face velocity of the fume hood.
HIGHFPM ALARM
120 FPM
Set the high alarm point for the face velocity of the fume hood.
LOPRESS ALARM
0.20 INH2O
Low pressure alarm set point in inches of water. Alarm will be triggered if pressure goes below this value.
HIPRESS ALARM
3.30 INH2O
High pressure alarm set point in inches of water. Alarm will be triggered if pressure goes above this value.
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
FUME HOOD CONTROLLER
SECTION 3 - SASH, SIDEWALL & HYBRID CONFIGURATION
E. Hybrid - Control Method Continued...
FPM ALARMHGHT
3.0 IN
FPM Alarm Height: set the minimum height that allows for a height FPM alarm.
NETWORK TYPE
MNET
Choose between Mnet and BACnet.
MNET ADDRESS
1
Set the unique network address of the FHC with a maximum of 16 devices.
EOL TERM
DISABLED
End of line termination – Enable this point if the current FHC is the final controller on the network
chain. Disable this point if the current FHC is not the final controller on the network chain.
CALIBRATION
COMPLETE
Calibration is complete.
PRESS MENU
TO EXIT
Exit to Service Menu.
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
19
FUME HOOD CONTROLLER
SECTION 4 - BALANCE & VERIFICATION
Balance & Verification
•
•
DIAGNOSTICS MENU
Turn on fume hood and open the fume hood to full
working height (typically 18”).
SERVICE MENU
Freeze the valve before taking measurements. Located
in the “Diagnostics Menu”. Enter the Service Menu using
the passcode and scroll down to “Diagnostics” and press
Enter, scroll down to “Freeze Valve” and select “Yes”.
FREEZE VALVE
YES
PRESS MENU
TO EXIT
NOTE: To access the service menu hold ‘Enter/Menu’ for
5 seconds. This menu is password protected for safety.
Please contact your local rep for Passcode or contact:
Price Critical Controls:
678-578-7495
[email protected]
•
Set the air flow measurement instrument (i.e. Alnor) to take
the average of all readings. Use the matrix airflow sensor
to take the readings.
•
Avoiding ~4” from the edges start taking measurements in a
zig-zag pattern take about ten readings (the more the better)
•
Depending on if a sidewall or a sash sensor is used
compare with the readings displayed on the FHI and
adjust the readings with the measurements taken.
MEASUREMENT PATTERNS - MATRIX FLOW SENSOR
SENSOR SCALE
SERVICE MENU
NOTE: These settings can also be initially set using the
Setup Wizard.
•
•
Use “Sensor Scale” to scale the readings to the
measurements made for Sidewall. Located in the
CTRL/Monitor Menu. Enter the Service Menu using the
passcode and scroll down to “CTRL/Monitor”, select
Sidewall, press Enter, and select “Sensor Scale”.
Use “Sensor Tweak” to tweak the readings to the
measurements made for Sash. Located in the CTRL/
Monitor Enter the Service Menu using the passcode and
scroll down to “CTRL/Monitor”, select Sash, press Enter,
and select “Sensor Tweak”.
SERVICE MENU
DIAGNOSTICS
CONTROL/MONITOR:
SIDEWALL
SENSOR SCALE
1.000
PRESS MENU
TO EXIT
SENSOR TWEAK
SERVICE MENU
CONTROL/MONITOR:
SASH
SENSOR TWEAK
1.000
PRESS MENU
TO EXIT
20
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
FUME HOOD CONTROLLER
SECTION 5 - DISPLAY NAVIGATION
FHI - Initial Start Up
Information Menu
When the FHI is first powered from the FHC controller, it will
display the following information: (Also press both UP/DOWN
at same time to show this screen anytime.)
Pressing the Enter/Menu button from the default display screen
will open this menu.
PRICE ELECTRONICS
FHI
STANDARD MODEL
Start-up screen
AIRFLOW
350 CFM
Displays the overall airflow
through the hood.
FHC Interface
SASH 1 HEIGHT
0.0 IN
Displays the current height of sash 1.
Fume Hood Interface - Firmware
Version V3.xx or higher
SASH 2 HEIGHT
0.0 IN
Displays the current height of sash 2.
Loading Screen – Thermostat
pulls in variables from FHC
SASH 3 HEIGHT
0.0 IN
Displays the current height of sash 3.
FHC
VERSION 1.XX
FHC Controller - Firmware
Version 1.XX or higher
VALVEPRESSURE
0.050 INH20
Displays the pressure
across the duct valve.
FACE VELOCITY
60 FPM
After start up LCD will display default
screens depending on mode of operation
VELOCITY TRGT
60 FPM
Displays the set-point for
the unit face velocity.
FHI
VERSION 3.XX
LOADING:
0-100 %
CONTROL METHOD
AUTO CONTROL
Displays the current control method
for face velocity of the fume hood.
OCCUPANCY
OCCUPIED
Displays whether the fume
hood is in use or not.
AO1 USAGE
ACTUATOR
Displays the current usage
of analog output 1.
AO1
10 VDC
Displays the current analog
output 1 voltage.
AO2
UNUSED
Displays the current usage
of analog output 2.
AO2
0.0 VDC
Displays the current analog
output 2 voltage.
PRESS MENU
TO EXIT
Exits back to the main
display default screen.
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
21
FUME HOOD CONTROLLER
SECTION 5 - DISPLAY NAVIGATION
Controller
CONTROLLER
Down Button
Used for menu selection and adjustment
– press both Up and Down arrows
at the same time to display interface
Startup screens.
Up Button
Used for menu selection and adjustment
– press both Up and Down arrows at
same time to display interface Startup
screens.
Menu/Enter
Used to Enter service menu(s). The
menu(s) are password protected.
Mute
Used to temporarily mute the local alarm
for a certain number of minutes.
Emergency
Used to trigger emergency mode. Local
Alarm will sound and BACnet point will
change to Alarm alerting the front end
system.
Service Menu
The service menu contains all setup and
configuration parameters. Each FHC
ships with factory defaults, but virtually
all settings can be adjusted in the field.
All MAIN menus are listed on this page.
Use the WIZARD and/or menus shown
to setup the FHC for your application.
NOTE: To access the service menu hold
‘Enter/Menu’ for 5 seconds. This menu
is password protected for safety. Please
contact your local rep for Passcode or
contact:
Price Critical Controls:
678-578-7495
[email protected]
22
SERVICE MENU
SERVICE MENU:
CTRL/MONITOR
Control/Monitor – Manual setup menu
for control and monitor methods
SERVICE MENU:
ALARM POINTS
Alarm Points – Manual setup menu for alarm points
SERVICE MENU:
OCCUPANCY
Occupancy Menu – To force occ, force setback, etc.
SERVICE MENU:
INPUTS
Inputs – Configure the functions of the FHC binary inputs
SERVICE MENU:
OUTPUTS
Outputs – Configure the functions of the
FHC binary and analog outputs
SERVICE MENU:
NETWORK
Network – Choose network type (BACnet, or Mnet)
SERVICE MENU:
FHI SETUP
FHI Setup – Configure the FHI such as display
options, LED color, alarm type, etc.
SERVICE MENU:
DIAGNOSTIC
Diagnostics – Provides manual control and
monitoring of important FHC variables.
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
FUME HOOD CONTROLLER
SECTION 6 - ADVANCED
Setup Wizard Menu
The first time the FHC is powered on the attached FHI will step through the setup wizard. This allows a quick setup of the
parameters needed. The Wizard can then be run at any time from the Service Menu.
SERVICE WIZARD
MENU
WELCOME
DETECTED
EQUIPMENT
Setup Wizard – Press Menu key to advance through the wizard.
This is the beginning of the list of detected equipment connected to the FHC.
SIDEWALLSNSR1
DETECTED
Shows the connection status of Price Sidewall Sensor 1.
SIDEWALLSNSR2
NOT DETECTED
Shows the connection status of Price Sidewall Sensor 2.
SASH 1
DETECTED
Shows the connection status of Price Sash Sensor 1.
SASH 2
NOT DETECTED
Shows the connection status of Price Sash Sensor 2.
SASH 3
NOT DETECTED
Shows the connection status of Price Sash Sensor 3.
OPEN THE SASH
TO WORKHEIGHT
Open the sash to working height. Typically 18 inches.
CAL VALVE
OK
PUT TAPE OVER THE
SIDEWALLSNSOR
ZERO SWSENSOR
OK
REMOVE TAPE
OK
OPEN SASH TO
WORKING HEIGHT
STABLE?
100 FPM
Prompt confirming that controller will now calibrate the valve. Press Enter to continue.
Calibration takes 60 seconds. Do not move the sash during this time.
Message instructing to “Put tape over the Sidewall sensor” to start calibration.
NOTE: Tape must be put over all Sidewall sensors. Ensure tape is tightly sealed over the Sidewall sensor.
Read the note below before pressing the Enter/Menu button to continue. This will calibrate the zero-pressure point of all
sidewall sensors simultaneously.
NOTE: Before calibrating the zero-pressure point of the sidewall sensors, do the following:
1. Turn off all fans connected to the fume hood.
2. Tape off both pressure ports of ALL sidewall sensors ensuring that port opening is completely sealed.
Remove the tape from all sensors.
Open sash to working height. Typically 18 inches.
Wait for the airflow measurment to stabilize. Once you have a stable
reading, press Enter to continue to the next sash sensor.
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
23
FUME HOOD CONTROLLER
SECTION 6 - ADVANCED
Setup Wizard Menu Continued...
FPM AT SCALE
100 FPM
Comparing measurements made by and external airflow measurement device, such as a Short Ridge Instrument, and the
reading on the FHI, view if any adjustments are required to match the measurements made by the Short Ridge Instrument.
SENSOR SCALE
1.000
Comparing measurements made by an external airflow measurement device, such as a Short Ridge Instrument, and the
reading on the FHI, adjust the scale to match the measurements made by the Short Ridge Instrument.
FPM AT SCALE
100 FPM
Comparing measurements made by an external airflow measurement device, such as a Short Ridge Instrument, and the
reading on the FHI, view if any adjustments are required to match the measurements made by the Short Ridge Instrument.
This is a secondary confirmation check to ensure that the face velocity reading is accurate.
SW SCALE OK?
YES
Confirm that sidewall sensor is at scale. If ‘Yes’, the Wizard will proceed with the setup process.
If ‘No’, the Wizard will repeat the Sensor Scaling/Stability process.
MIN CFM
0 CFM
Select the minimum scheduled CFM value that the fume hood will will be operating at.
This is not the minimum range of the valve.
MAX CFM
1500 CFM
Select the maximum scheduled CFM value that the fume hood will will be operating at.
This is not the maximum range of the valve.
CALIBRATING SASH
#1
SASH TYPE
VERTICAL
Choose the style of the sash being calibrated.
Select Vertical if the entire sash moves and operates in the vertical orientation.
Select Horizontal if the entire sash moves and operates in the horizontal orientation.
MAX HEIGHT
25.0 IN
Measure the height of the sash at its highest position and enter this value in inches.
This is the measurement from the base of the sash to the work surface of the fume hood.
NOTE: Ensure that the measurement is to the work surface and not the airfoil.
MIN HEIGHT
1.0 IN
Measure the height of the sash at its lowest position and enter this value in inches.
This is the measurement from the base of the sash to the work surface of the fume hood.
NOTE: Ensure that the measurement is to the work surface and not the airfoil.
FULLYOPENSASH
OK
Place the sash in the fully open position and press the Enter/Menu button to save this position in the FHC memory.
CLOSE SASH
OK
Place the sash in the fully closed position and press the Enter/Menu button to save this position in the FHC memory.
SASH WIDTH
60 IN
Measure the width of the sash and enter this value in inches.
NOTE: Min Height, Max Height, and Sash Width are used by the FHC to calculate face velocity. It is very important that
these measurements are taken as accurately as possible. Inaccurate measurements could cause unit failure and
contamination of the laboratory space.
AIRFLOWSOURCE
NO SOURCE
K FACTOR
0
24
Shows the sash that will be calibrated in the next steps.
This section will repeat for each sash if multiple sash sensors are connected to the FHC.
Configure where airflow is being measured, such as LM module, Kavlico Sensor, or no source.
NOTE: This option is not available with Venturi Valves.
Contact Price Ltd for more information.
NOTE: This option is not available with Venturi Valves.
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
FUME HOOD CONTROLLER
SECTION 6 - ADVANCED
Setup Wizard Menu Continued...
Provides a selection of control methods. This is the primary type of control that the fume hood will use.
CONTROL METHOD
SIDEWALL CTRL
FALLBACK CTRL
NO FALLBACK
Sash Sensor Control: This method calculates the face velocity using the dimensions of the fume hood opening and the current CFM. This method
will control face velocity.
Sidewall Sensor Control: This method measures the face velocity through the fume hood by measuring the pressure within the unit from the
sidewall sensor. This method will control face velocity.
Hybrid Control: This method is an optimized combination of both sidewall sensor and sash sensor control. It is the most effective method of fume
hood control and is recommended in all cases.
Provides a selection of fallback control methods.
This is the type of control the fume hood will use if the primary control method fails.
Sash Sensor Control: This method calculates the face velocity using the dimensions of the fume hood opening and the current CFM. This method
will control face velocity.
Provides a selection of monitor methods. This is how the face velocity of the fume hood is monitored and displayed.
MONITOR METHOD
SW MONITOR
OCC. SETPOINT
100 FPM
DEADBAND
10 FPM
SASHCTRLMETHOD
LINEAR CAL.
Sash Sensor Monitoring: The face velocity is monitored and displayed using the position of the sash and by calculating the open space area of the
fume hood.
Sidewall Sensor Monitoring: The face velocity is monitored and displayed using the Sidewall sensors. The Sidewall sensors calculates the face
velocity by measuring the difference in pressure between the outside of the fume hood and the inside work area of the fume hood.
Choose the default face velocity set point when the fume hood is occupied.
Sets the sensitivity of the FHC; a lower dead-band creates a higher sensitivity.
This is the minimum/maximum allowable deviation in face velocity before the FHC will make adjustments to the valve.
Choose a method to calibrate the sash you wish to calibrate. Linear, Cal Manually, or Cal from SW.
LOW FPM ALARM
80 FPM
Set the low alarm point for the face velocity of the fume hood.
If the face velocity drops below the user set value, the controller will go into alarm mode.
HIGHFPM ALARM
120 FPM
Set the high alarm point for the face velocity of the fume hood.
tIf the face velocity rises above the user set value, the controller will go into alarm mode.
FPM ALARM
HEIGHT 3.0 IN
FPM Alarm Height: set the minimum height that allows for a height FPM alarm.
NETWORK TYPE
MNET
This sets the communication protocol the FHC will use. Select BACnet if the controller is not being connected to a Price
Lab Space Controller (LSC) and is instead being connected directly to a BACnet front-end. Select MNET if the FHC will be
connected to a Price LSC.
MNET ADDRESS
1
Set the unique network address of the FHC with a maximum of 16 devices.
EOL TERM
DISABLED
End of Line Termination – Enable this point if the current FHC is the final controller on the network chain.
Disable this point if the current FHC is not the final controller on the network chain.
CALIBRATION
COMPLETE
Calibration Complete.
PRESS MENU
TO EXIT
Exit to service menu.
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
25
FUME HOOD CONTROLLER
SECTION 6 - ADVANCED
Service Menu
SERVICE MENU
CTRL/MONITOR
CONTROLMETHOD
HYBRID
Control Method determines the devices used to control the airflow to
and from the fume hood. Options are: No Control, Sidewall Control,
Sash Control, and Hybrid. See Section 3 for more details.
MONITORMETHOD
SW MONITOR
Monitor Method determines the devices used to monitor the airflow to and
from the fume hood. Options are: Sash Monitor and Sidewall Monitor.
OCC. SETPOINT
100 FPM
DEADBAND
10 FPM
Set the minimum face velocity set point while the room is occupied.
Set the minimum face velocity while the room is in dead band. Sets the
sensitivity of the FHC; A lower dead band creates a higher sensitivity.
SETBACKSETPNT
60 FPM
Set the minimum face velocity set point while the room is in Setback mode.
OFFDAMPERPOS.
0%
Actuator target (in %) when the fume hood is off.
MIN CFM
50 CFM
Set the minimum allowable CFM to the unit.
MAX CFM
1010 CFM
Set the maximum allowable CFM to the unit.
CTRL/MONITOR:
SIDEWALL
Configure control and monitoring options for the Sidewall sensor.
FREEZE VALVE
NO
This can be used to hold the vernturi valve in its
current position. Enabling freeze valve will disable
all control aspects of FHC while enabled.
SENSOR SCALE
1.000
Comparing measurements made by and external airflow
measurement device, such as a Short Ridge Instrument,
and the reading on the FHI, adjust the scale to match the
measurements made by the Short Ridge Instrument.
FACE VELOCITY
0 FPM
Displays the current face velocity of the fume hood in FPM.
SENSOR OFFSET
0 FPM
Full offset of the FPM that the sensor reads.
SIDEWALLMENU:
ZERO SWSENSOR
ZERO SWSENSOR
NO
SIDEWALLMENU:
SIDEWALL PID
PID RESPONSE
3
PRESS MENU
TO EXIT
26
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
Option to zero the
sidewall sensor.
Set the sensitivity of the
fume hood controller.
FUME HOOD CONTROLLER
SECTION 6 - ADVANCED
Service Menu Continued...
CTRL/MONITOR:
SASH
SASH MENU:
CALIBRATESASH
CALIBRATING
SASH #1
SASH TYPE
VERTICAL
Select the type of sash used for the
fume hood. Vertical or horizontal.
MAX HEIGHT
25.0 IN
Measure the height of the sash at its highest
position and enter this value in inches.
MIN HEIGHT
1.0 IN
Measure the height of the sash at its lowest
position and enter this value in inches.
FULLYOPENSASH
OK
SASH MENU:
SASH CTRL
Fully open the sash (not just to working height).
SASH WIDTH
60.0 IN
Measure the width of the sash and enter
this value in inches.
NOTE: Min Height, Max Height, and Sash Width are used
by the FHC to calculate face velocity. It is very important
that these measurements are taken as accurately as
possible. Inaccurate measurements could cause unit
failure and contamination of the laboratory space.
SASHCTLMETHOD
CAL. FROM SW
Select which device to you wish to calibrate the sash with.
SASHCTRLMENU:
OCCUPIED CAL
Calibrate the sash when the fume
hood is in occupied mode.
SASHCTRLMENU:
SETBACK CAL
Calibrate the sash when the fume
hood in in setback mode.
SASH TWEAK
0
Used to make a percentage change to the sash position sensor
reading to make the fume hood face velocity calculations match the
position of the sash. This in turn adjusts the airflow rate.
SASH OFFSET
0
Used to make an offset change to the sash position sensor reading
to make the fume hood face velocity calculations to match the
position of the sash. This in turn adjusts the airflow rate.
PRESS MENU
TO EXIT
CTRL/MONITOR:
CAL VALVE
PRESS MENU
TO EXIT
CAL VALVE
NO
Prompt requesting confirmation that controller will now calibrate
the valve. Select YES and press Enter to continue. Calibration takes
60 seconds. Do not move the sash during this time.
PRESS MENU
TO EXIT
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
27
FUME HOOD CONTROLLER
SECTION 6 - ADVANCED
Alarm Points Menu
SERVICE MENU:
ALARM POINTS
LOW FPM ALARM
DISABLED
Set the low alarm point for the face velocity of the fume hood.
HIGHFPM ALARM
120 FPM
Set the high alarm point for the face velocity of the fume hood.
SETBACKLOWFPM
60 FPM
Set the low alarm point for the face velocity of the fume hood when In in Setback mode.
SETBACK HIFPM
120 FPM
Set the high alarm point for the face velocity of the fume hood when In Setback mode.
FPM ALARMHGHT
3.0 IN
FPM Alarm Height: Set the minimum height that allows for a height FPM alarm.
SASHHGHTCAUTN
0.0 IN
If sash goes above this value, the controller goes into caution mode.
LOPRESS ALARM
DISABLED
Set the low alarm point for the pressure of the fume hood valve.
HIPRESS ALARM
3.30 INH2O
Set the high alarm point for the pressure of the fume hood valve.
LOW CFM ALARM
DISABLED
Set the low alarm point for the CFM of the unit.
HIGHCFM ALARM
DISABLED
Set the high alarm point for the CFM of the unit.
ALARM POINTS:
ALARM DELAYS
FACE VELOCITY
10 SEC.
Delay before face velocity alarm activates.
VALVEPRESSURE
10 SEC.
Delay before valve pressure alarm activates.
AIRFLOW
10 SEC.
SASHHGHTCAUTN
0 SEC.
PRESS MENU
TO EXIT
PRESS MENU
TO EXIT
28
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
Delay before airflow alarm activates.
Delay before sash height caution activates.
FUME HOOD CONTROLLER
SECTION 6 - ADVANCED
Occupancy Menu
SERVICE MENU:
OCCUPANCY
OCC OVERRIDE
NO OVERRIDE
Occupancy Override – Allows to Force setback, Force Occupancy, or Disable.
PRESS MENU
TO EXIT
Input Menu
SERVICE MENU:
INPUT
BI1 CONFIG
UNUSED
Configuration of the binary inputs.
Unused, Setback on Close, Setback on Open, Off on Closed, Off on Opened,
Alarm on Closed, Caution on Closed, Emergency Purge on Closed.
BI2 CONFIG
UNUSED
Configuration of the binary inputs.
Unused, Setback on Close, Setback on Open, Off on Closed, Off on Opened,
Alarm on Closed, Caution on Closed, Emergency Purge on Closed.
PRESS MENU
TO EXIT
Output Menu
SERVICE MENU:
OUTPUT
OUTPUT BINARY
OUTPUT
BO1 USAGE
FORCE OFF
Configuration of the binary outputs. Options are:
Unused, Force On, Force Off, Normal, Occupied, Setback,
Alarm, Caution, Follow BI 1, Follow BI 2, Emergency.
BO2 USAGE
FORCE OFF
Configuration of the binary outputs. Options are:
Unused, Force On, Force Off, Normal, Occupied, Setback,
Alarm, Caution, Follow BI 1, Follow BI 2, Emergency.
BO3 USAGE
FORCE OFF
Configuration of the binary outputs. Options are:
Unused, Force On, Force Off, Normal, Occupied, Setback,
Alarm, Caution, Follow BI 1, Follow BI 2, Emergency.
PRESS MENU
TO EXIT
OUTPUT ANALOG
OUTPUT
PRESS MENU
TO EXIT
AO1 USAGE
ACTUATOR
Configuration of the analog outputs. Options are:
Unused, Actuator, Alarm 5V, Face Velocity,
Valve Pressure, Valve Flow.
AO2 USAGE
VALVE FLOW
Configuration of the analog outputs. Options are:
Unused, Actuator, Alarm 5V, Face Velocity,
Valve Pressure, Valve Flow.
CURRENT A01
0.00 VDC
Displays the current value of AO1
CURRENT A02
0.00 VDC
Displays the current value of AO2
PRESS MENU
TO EXIT
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
29
FUME HOOD CONTROLLER
SECTION 6 - ADVANCED
Network Menu
SERVICE MENU:
NETWORK
NETWORK TYPE
MNET
This sets the communication protocol the FHc will use. Select BACnet if the controller is
not being connected to a Price Lab Space Controller (LSC) and is instead being connected
directly to a BACnet front-end. Select Mnet if the FHC will be connected to a Price LSC.
MNET ADDRESS
1
Set the unique network address of the FHC with a maximum of 16 devices
EOL TERM
DISABLED
End of Line Termination – Enable this point if the current FHC
is the final controller on the network chain. Disable this point if the
current FHC is not the final controller on the network chain.
PRESS MENU
TO EXIT
Occupancy Priorities
The Occupancy Priority list is a list that explains which occupancy sources take precedence over one another. 0 being the highest
priority, and 6 being lowest priority. The priority list is factory set and can not be edited.
Priority Level
30
Source
0
LCD FHI Force Occupied
Force Occupancy through the LCD FHI Occupancy Menu.
1
LCD FHI Force Setback
Force Setback through the LCD FHI Occupancy Menu.
2
LCD FHI Force Off
Turn occupancy off through the LCD FHI Occupancy Menu.
3
BACnet Force Occupied
Force Occupancy through BACnet. Can not Force Setback, or Force off,
this is to prevent the fumehood from being forced into setback, or forced off
remotely while in use.
4
Off Source (eg Bls)
Source to trigger Force Off.
5
Setback source (eg Bls)
Source to trigger Force Setback.
6
Occupied
When no other priorities are met the fumehood defaults into Occupancy.
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
FUME HOOD CONTROLLER
SECTION 6 - ADVANCED
FHI Setup Menu
Once in Service Menu, Scroll Down and press ‘Enter Menu’ to enter the FHC Service Menu.
SERVICE MENU:
FHI SETUP
DISPLAYOPTIONS
FACE VELOCITY
Choose what information is displayed on the FHI. Options are:
Face Velocity, Name + FPM, Safety, Name + Safety.
FUMEHOOD NAME
Choose a name for the fume hood.
ALARM TYPE
WAIL
Choose the alarm type. No Tone, Steady 2KHz, Wail, or Red Alert.
FHI MUTE TIME
240 SEC.
FHI Mute Time – This provides control over the length of
time the mute button will silence an alarm.
EMERG BUTTON
ENABLED
Enables or disables the Emergency button.
LITEBAR-NORM.
GREEN
Choose the light bar color for normal conditions.
LITEBAR-CAUT.
YELLOW
Choose the light bar color for caution conditions.
LITEBAR-ALARM
BLINK RED
Choose the light bar color for alarm conditions.
LITEBAR-STBCK
SKY BLUE
Choose the light bar color for setback conditions.
LITEBAR-OFF
SKY BLUE
Choose the light bar color when the fume hood is off.
PRESS MENU
TO EXIT
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
31
FUME HOOD CONTROLLER
SECTION 6 - ADVANCED
Diagnostic Menu
Once in Service Menu, Scroll Down and press ‘Enter Menu’ to enter the FHC Service Menu.
SERVICE MENU
DIAGNOSTIC
DIAGNOSTIC:
LOAD DEFAULTS
DIAGNOSTIC:
RESETCONTROLLER
Resets the controller to the factory defaults.
Manually resets the FHC.
SIDEWALLSNSR1
NOT DETECTED
Shows the connection status of Sidewall Sensor 1.
SIDEWALLSNSR2
NOT DETECTED
Shows the connection status of Sidewall Sensor 2.
A01 OVERRIDE
DISABLED
Analog Output 1 Override – Allows control over the output voltage of AO1.
A02 OVERRIDE
DISABLED
Analog Output 2 Override – Allows control over the output voltage of AO2.
FREEZE VALVE
NO
Freeze Valve – This can be used to hold the venturi valve in its current position.
NOTE: Enabling freeze valve will disable all control aspects of FHC while enabled.
K FACTOR
0
Contact Price Ltd for more information. Available with Kavlico Sensor only.
SASH 1
DETECTED
Shows the connection status of Sash 1.
SASH 2
NOT DETECTED
Shows the connection status of Sash 2.
SASH 3
NOT DETECTED
Shows the connection status of Sash 3.
SASH 1 HEIGHT
25.0 IN
Shows the current height of Sash 1 in inches.
PRESS MENU
TO EXIT
32
FUME HOOD CONTROLLER - Manual | pricecriticalcontrols.com
FUME HOOD CONTROLLER
NOTES
pricecriticalcontrols.com | FUME HOOD CONTROLLER - Manual
33
This document contains the most current product information as of this printing.
For the most up-to-date product information, please go to www.price-hvac.com.
© 2015 Price Industries Limited. All rights reserved.