Model SZ60 EV2000 Series
Model SZ60
EV2000 Series
SPECIFICATIONS
Wattage output
Voltage output
Speaker impedance
Voltage supply
Current stand-by
Current loaded
Fuse rating
Alert tone
Evacuation tone 2220
Evacuation tone T3
60watts
100 volt line
166 ohms max
23-30vdc
140mA
3.8 Amps
Tone generator 3A / Amplifier 4A m205
Stepped 420 Hz on-off 6.25secs
Increasing 500-1200 Hz for 3.25 secs @ 4 secs
Temporal pattern - 3 x 0.5s pulses 500-1200 Hz for 3 secs off for 1.5 secs
Note T3 replaces 2220 Evacuation tone on units marked T3 on micro.
220mm L x 210mm W x 100mm H
Dimensions Unit
CIRCUIT DIAGRAM
100V CA N BE TAKEN
DIRECTLY FROM HERE
OR RETU RN TO T.G.
FOR MO NITORING
SPA RE
JUMP ERS
100V
100V
TONE
GENERATOR
1 00V IN
10 0V IN
TB4
G T.G
TB5
SPEA KER SHORT (RE D)
REG
TIMER
COM FLT
+
TB 3
PA2
SPEAK ER O PEN (YEL LOW)
CO NT
O FF
DS1232
22uF
BI-P OLAR
CAPA CITOR
NOTE "NOCF" LINK MUST BE IN IF NO
SPEAKER CAPACITORS A RE FIT TED
NOCF
M/MAN
ON
FLT
FLT
AL IND (0V SW)
RELAY
EV IND (0V SW)
R ELAY
CON (0V SW)
+24
RELAY
ALERT STROBE R ELAY
EVAC STROBE RELAY
CONTROL RELAY
GND
ALAR M
}F.I.B
INPUT N.O
ALM
TB2
ID C
TLO74
VOLUME CONTROL S
PWR
MIC2 MIC 1
M2- 1mV
TB1
405 2
PAU PEV
EV
PINK
AU TO WHITE
(MESSAGE CARD OPTIONA L)
A LERT E VA C
60 WATT AMP
FAULT N.O.
} COMMON
CONTACTS TO F.I.B.
MIC RO
A LM
22K
100V
LIN E E.O.L
+24 BATT
GND
C/F LT
RELAY
AL
EV
(TYPICAL SPEAKER)
MONITORED SPK OUT
MONITOR ED SPK OUT
F USE
3A
PA1
- B ATT GND
+ BATT +24VDC
+
GND
BLUE
PA1
RED
M1
GND
YELLOW OR WHI TE
AUTO
O FF
P.T. T
SHEILD
M2
PA2
EVAC
KEY
SWITCH
HAND
MIC
DESK
MIC
P.T.T
KEY-SWITCH & MIC CONNECTION
FO R HAND MIC TO ALSO WORK
IN AUTO, PAU JUM PER MUS T BE IN.
NOTE – TYPICAL REDBACK MICROPHONE CONNECTIONS
EV2000
C-0333 MIC (UNBALANCED) C-0335 MIC (BALANCED)
GND
SHIELD/BLUE
SHIELD/WHITE/BLACK
M1 (MIC AUDIO) WHITE
RED
PA1 (0V P.T.T)
RED
BLUE
INPUT
-G+
AMP VOLUME
Speaker load guide
EV2000 Series
CONNECTIONS
Maximum Impedance
250 watt = 40 ohms
120 watt = 83 ohms
60 watt = 166 ohms
40 watt = 250 ohms
15 watt = 665 ohms
All models
TB1
PA2
M2
GND
M1
PA1
Mic 2 control-input ground to activate (non-latching)
Auxiliary input mic level 1mVor music level 100mV.
Ground for microphones.
Microphone input, mic level only1mV.
Mic 1 control-input, ground to activate (non-latching PAU in, latching PEV in).
TB2
GND
AUT
EV
AL
ALM
GND
Key switch or selector switch common.
Auto input, ground to activate (cancels any latching).
Evacuate input, ground to activate (latching).
Alert input ground to activate (latching).
FIB input, ground to activate (non-latching).
FIB common.
TB3
24 OUT
AL IND
EV IND
CON OUT
FLT
FLT
GND
+24
Fused +24vdc output, use to run relays/ strobe relays etc.
Alert strobe output, 0v switch, to drive strobe relays 800mA max! - use Evactron strobe relay card.
Evacuate strobe output, 0v switch, to drive strobe relays 800mA max! - use Evactron strobe relay card.
Control output, 0v switch with system activation, to add PA2 link PA2 CONT, 800mA max!
N.O contacts, close on speaker fault or power off, run to master alarm if required.
N.O contacts, close on speaker fault or power off, run to master alarm if required.
Battery ground in.
Battery + 24vdc in.
TB4
SPK OUT
SPK OUT
100v monitored speaker output \
100v monitored speaker output /
To speaker circuit, use 22k “end of line resistor ”
for speaker circuit if using monitoring.
100V IN
100V IN
100v in, from line transformer \
100v in, from line transformer /
Take 100v directly from line transformer to
speakers if monitoring is not required.
B- T.G
A- GND
1 volt audio output (SZ60, 120 & 250) or 8 ohm to speaker transformer (SZ40 only)
Spare (SZ60, 120 & 250) or common to speaker transformer (SZ40 only)
See diagram
TB5
JUMPERS
Place jumpers in board for following
•
•
•
•
•
Spares jumpers, located at end of the circuit board (5 way holder)
PAU- Place in if you are using a key switch.
PEV- Place in if you are using a selector switch or facia control.
M2 1mV- Place in to make M2 input at mic level (1mV) leave out for M2 at line level (100vV) ie music etc
NOCF- Place in to disable a speaker short from muting the amplifier.
PA2 CONT- Place in ,to link PA2 input to the control output.
TIMER SETTINGS
TIMER SETTINGS IN ALARM MODE (ALERT TO EVAC ) CHANGEOVER TIME IN MINUTES
Dip
Switch
SW1
SW2
SW3
SW4
Straight
to Evac
On
On
On
On
30
sec.
On
Off
Off
Off
1
1½
2
2½
3
3½
4
4½
5
6
7
8
9
Stay in
Alert
Off
On
Off
Off
On
On
Off
Off
Off
Off
On
Off
On
Off
On
Off
Off
On
On
Off
On
On
On
Off
Off
Off
Off
On
On
Off
Off
On
Off
On
Off
On
On
On
Off
On
Off
Off
On
On
On
Off
On
On
Off
On
On
On
Off
Off
Off
Off
Was this manual useful for you? yes no