loop-powered lcd indicator
PReview
5531
LOOP-POWERED LCD INDICATOR
ATEX
4-digit LCD display 48 x 96 mm
Loop-powered
Easy scalable from front keys
Backlight
Standard and ATEX Ex version
IP65 enclosure from front
Application:
The PReview 5531 indicator is ideal for local readout of
4...20 mA current signals scaled directly in process units.
• PReview does not need any external power supply as the
indicator is powered by the 4...20 mA loop signal.
• The Ex version 5531B can be used in hazardous areas
classified as zone 0, 1, or 2. • 5531B1 includes an Ex field
enclosure suitable for use in zones 2 and 22 without the
need for a barrier. • 5531B2 includes an Ex field enclosure
for use in zones 1, 2, 21, or 22.
Technical characteristics:
Input: 4...20 mA standard signal.
An adhesive label with process units may be attached to the
front below the digits.
Input voltage drop is ≤ 1.5 VDC, corresponding to a feedthrough resistance of 75 Ω (when backlight is switched off).
Reversed display readout is possible, see routing diagram
on the reverse.
Programming / scaling:
Dipswitch 1, switch 1 on the rear panel is used to enable /
disable the front keys thus facilitating scaling.
Scale mode: In scale mode the indicator may be scaled,
see routing diagram on the reverse of this data sheet.
Run mode: In run mode the indicator will display the actual
current according to the scaling.
Backlight: Dipswitch 1, switch 2 and 3 on the rear panel is
used to select backlight intensity, see programming on the
reverse of this data sheet. Please note that the input voltage
drop is dependent on backlight intensity.
Field enclosure type 8501:
The field enclosure type 8501 complies with industrial standards for efficient protection of process equipment in wet
areas up to IP65. When 8501 is delivered with a built-in
PReview 5531, the assembled unit is approved for installation in explosive gas atmospheres as well as in explosive
dust environments. The technical specifications of the field
enclosure can be found in the 8501 data sheet.
Electrical specifications:
Specifications range:
-20°C to +60°C
Common specifications:
Max. voltage drop at 20 mA:
Without backlight ..............................
Full backlight .....................................
Response time (0...90%) ...................
Calibration temperature ....................
Signal dynamics, input ......................
Temperature coefficient ....................
Linearity error ....................................
EMC immunity influence ...................
Screw terminal torsion.......................
Humidity ............................................
Dimensions (HxWxD) .........................
Cut-out dimensions (HxW) ................
Tightness (from front) ........................
Weight ...............................................
Input:
Measurement range ..........................
Display:
Display readout .................................
Digit height ........................................
Updating speed ................................
Ex / I.S. data:
Ui .......................................................
Ii .........................................................
Pi .......................................................
Ci .......................................................
Li ........................................................
EEx / I.S. approval:
5531B:
DEMKO 02ATEX132122 ....................
< 1.5 VDC
< 10.5 VDC
<1s
20...28°C
15 bit
< ±0.01% of span / °C
< ±0.1% of span
< ±0.5%
0.5 Nm
< 95% (non-cond.)
48 x 96 x 120 mm
44.5 x 91.5 mm
IP65
150 g
3.6...23 mA
±9999 (4 digits)
16 mm
500 ms
: 45 VDC
: 500 mA
: 0.9 W
: 0 µF
: 0 mH
II 1 G
EEx ia IIC T6
Applicable in zone ............................. 0, 1 or 2
5531B1:
KEMA 05ATEX1044 X........................ -5°C ≤ Ta ≤ +60°C
II 3 GD T85˚C
-20°C ≤ Ta ≤ +60°C II 3 G
EEx nL IIC T6
Applicable in zone ............................. 2 or 22
5531B2:
KEMA 05ATEX1105 X........................ -5°C ≤ Ta ≤ +60°C
II 2 GD T85˚C
-20°C ≤ Ta ≤ +60°C II 2 G
EEx ib IIC T6
Applicable in zone ............................. 1, 2, 21 or 22
Observed authority requirements: Standard:
EMC 2004/108/EC
Emission and immunity ............. EN 61326
ATEX 94/9/EF .................................... EN 50014, EN 50020, EN 60079-15,
EN 61241-0 and prIEC 61241-11
Of span = Of the presently selected range
Huvudkontor Order & Lager: Malux Sweden AB, Box 221, 891 25 Örnsköldsvik. Växel 0660-29 29 00, fax 0660-850 85.
För adresser till våra försäljningskontor: www.malux.se.
Order: 5531
Type
Version
5531
Field enclosure
Standard
:A
Type 8501
ATEX Ex
:B
None
8501 / EEx nL IIC
8501 / EEx ib IIC
:
:1
:2
Block diagram:
input +
2
4...20 mA
Ex
circuit
CPU
A/D
input -
DP 1
1
Only
version: B
2
1
4
DP 1
3
EEPROM
Backlight
Front buttons
3
5531
Programming:
DP 1
Front keyboard
SW ON
SW OFF
DP 1
Backlight
SW ON
SW OFF
Keys locked
-
1
Off
2
-
Keys NOT locked
1
-
Half intensity
3
2
Full intensity
-
2, 3
Routing diagram:
DP SW 1 must be ON to enable front buttons.
If no buttons are pressed for a period of 2 minutes,
display returns to stage 0.0
To store changes press
simultaneously.
Power On
Display type no. is shown