MI 2392_Power QPlus_prospekt.cdr
PowerQPlus
MI 2392
Advanced, handheld, easy to use 3-phase power quality analyser
• PowerQ Plus is a genuine, portable 3phase power quality analyser which
favorably competes with higher priced
instruments and can be easily
implemented in a variety of different
situations.
• PowerQ Plus is due to its small
dimensions and ease of use ideally
suited for routine or complex power
quality assesment in heavy duty
industrial environments.
Standards
Instrument is developed and
manufactured in accordance with
following standards
Safety:
IEC/EN 61010-1
EMC:
IEC/EN 61326-1
Measurements: IEC/EN 50160
• Pre-set logging screens allow on-site
evaluation of all major power quality
parameters (U,I, P, PF, cosφ
, THD,
individual harmonics componets, phase
shifts, etc.).
• Windows compatible PowerQ Link
software package expands a versatility
Target applications
•Power quality assesment and troubleshooting in low voltage electrical systems.
• Balancing phase currents in 3-phase systems.
• Checking power correction equipment performance.
• Harmonics spectrum analysis for selection of harmonic filters.
• Capturing inrush currents e.g. motor's start up currents.
• Voltage deviations recording.
• Consumption recording.
Phase diagram helps at connecting the
instrument on the power network and is
effectively used at indivual phase
conditions assesment.
Main features
• Simultaneous analysis of basic power quality parameters (U,I,P,Q,S, PF)
• Harmonics analysis up to 50th component
• Phase diagram
• Voltage unbalance calculation for 3-phase systems
• On-line scope function
• Lightweight design
• Downloading software package PowerQ Link
PowerQ Plus enables on-screen evaluation
of various pre-set loggers. This is an
example of a logger for U, I and f.
General Technical specification
Technical specification
AC voltages
Current harmonics measurement
Three-phase AC voltage input
(3 differential inputs, L1-N1, L2-N2, L3-N3).
Input voltage range: 3-550 VRMS L-N
3-550 VRMS L-L
Resolution:
0.1V
Accuracy:
±1% of reading ±2.5V
Crest factor:
< 1.4
Frequency range: 45 ÷ 66Hz
Measuring range:
IM > 3%IN
Resolution:
0.1%
Accuracy:
5% IM (3% for DC)
Measuring range:
IM < 3%IN
Resolution:
0.1%
Accuracy:
0.15% IN
IN: nominal range (TRMS)
IM: measured harmonic current hM = 1st ÷ 50th
AC currents
Three-phase AC input for connection to current
transducers with voltage output.
Range 1:
Input current: 0.04 ÷ 0.1 VRMS for current range 4 100A
Resolution: 0.1A
Accuracy:
±(2% of reading + 0.3A)
Crest factor: < 2.3
Range 2:
Input current: 0.04 0.1 VRMS for current range 40 ÷
1000 A
Resolution: 0.1A
Accuracy:
±(2 % of reading + 3 A)
Crest factor: < 2.3
Power measurements
Loggers
Voltage and current logger
Signals:
selectable U1, U2, U3, I1, I2, I3
Interval:
selectable, (1,2,5,15,30)
seconds or
(1,2,5,10,15,30) minutes
Displayed data:
average, min and max value of
the interval
Power logger
Signals:
Interval:
Displayed data:
selectable L1, L2, L3
selectable, (1,2,5,15,30)
seconds or
(1,2,5,10,15,30) minutes
average, min and max value of
the interval (for all four
Working temperature range:
Storage temperature range:
Max. Humidity:
-10 C ÷ +55 C
-20 C ÷ +70 C
95 % RH (0 C ÷ 40 C), noncondensing
Pollution degree:
2
Protection classification:
double insulation
Overvoltage category:
voltage inputs: CAT III 600 V
Protection degree:
IP 42
Display:
graphic liquid crystal display
with backlight,
160 x 160 dots.
External DC supply:
12 V, 400 mA
Maximum power consumption: 360 mA
Communication:
RS232 serial interface
Baud rate:
1200 baud ÷ 115200 baud
Connector:
9 pin D-type
Dimensions:
(220 x 115 x 90) mm
Weight (without accessories): 0.65 kg
Ordering information
Standard set
Part No. MI 2392
quadrants)
Measured parameters:
- Active power (P)
- Reactive power (Q)
- Apparent power (S)
- Power factor
Harmonics logger
Signals:
THDI3,
- Cos j
- Energy (Wh, Vah, Varh)
Accuracy:
Power:
± (3% + 3dig)
Power factor:
± 0.03
Energy:
±3%
All measurements are performed in four quadrants:
load or generator with capacitive or inductive
character.
Voltage harmonics measurement
selectable THDI1, THDI2,
Interval:
seconds or
THDU1, THDU2, THDU3,
selectable, (1,2,5,15,30)
(1,2,5,10,15,30) minutes
Inrush currents
Signals:
Interval:
Trigger channels:
Trigger level:
range
selectable U1, U2, U3, I1, I2, I3
selectable, (10, 20, 100, 200) ms
I1, I2, I3
electable, 2% ÷ 100% of current
(in steps of 0.1 % of current
Measuring range: UM > 3%UN
Resolution:
0.1%
Accuracy:
5% UM (3% for DC)
Measuring range: UM < 3%UN
Resolution:
0.1%
Accuracy:
0.15% UN
UN:
nominal voltage (TRMS)
UM:
measured harmonic voltage hM = 1st ÷ 50th
range)
Displayed data:
the interval
average, min and max value of
- Instrument PowerQPlus
- Current clamp 1000A/1V, 3 pcs
- Test tips, 3 pcs
- Alligator clips, 4 pcs
- Voltage measurement clips, 4 pcs
- PC SW Package PowerQ Link on CD with RS232 cable
- Power supply adapter
- Rechargeable batteries, 6pcs
- Soft carrying bag
- User manual
- Product verification data
- Declaration of conformity
- Declaration of warranty
Accuracy
Optional accessories
Voltage
Measuring range
Range 1: 5.0 VRMS
Range 2: 10.0 VRMS
Range 3: 20.0 VRMS
Range 4: 30.0 VRMS
÷ 70.0 VRMS
÷ 130.0 VRMS
÷ 300.0 VRMS
÷ 550.0 VRMS
Resolution
0.1 V
Accuracy
±(5 % + 1 V)
±(5 % + 1.5 V)
±(5 % + 3 V)
±(5 % + 5 V)
Crest factor
1.4 min
A 1020
A 1137
Current
Measuring range
Range 1: 4.0 (0.0) mVRMS ÷ 100 mVRMS (4 ÷ 100) A
Range 2: 0.04 (0.00) VRMS ÷ 1 VRMS (40 ÷ 1000) A
Resolution
0.1 A
Accuracy
±(5 % + 0.6 A)
±(5 % + 6 A)
Crest factor
2.3 min
A 1099
Voltage
A 1039
A 1069, A 1122
Voltage events
Signals:
Swell limit:
Dip limit:
Interruption limit:
Logging time:
Hysteresis:
Measuring range
Range 1: 5.0 VRMS
Range 2: 10.0 VRMS
Range 3: 20.0 VRMS
Range 4: 30.0 VRMS
selectable U1, U2, U3
1% ÷ 35% UN
-35% ÷ -1% UN
1% ÷ 20% UN
manual stop, (1, 2, 5, 10, 30) minutes or (1, 2, 5, 10, 30, 50, 75) hours
1% UN
÷ 70.0 VRMS
÷ 130.0 VRMS
÷ 300.0 VRMS
÷ 550.0 VRMS
Resolution
0.1 V
Accuracy
±(5 % + 1 V)
±(5 % + 1.5 V)
±(5 % + 3 V)
±(5 % + 5 V)
Crest factor
1.4 min
Logger lengths depend on selected interval. Maximum recording time is displayed automatically.
Duncan Instruments Canada Ltd.
121 Milvan Drive Toronto, Ontario M9L 1Z8
Tel.: 416-742-4448; Fax: 416-749-5053
http://www.duncaninstr.com; E-mail: [email protected]
A 1120
A 1020
A 1037
A 1039
A 1069
A 1099
A 1120
A 1122
S 2014
S 2015
S 2014
S 2015
- Small soft carrying bag
- Current transformer 5 A/1 V
- Clamp adapter
- Mini clamp 100 A / 1 V
- Current clamp 3000 A / 1 V
- 3-phase flex-kit, 45 cm, 3000 A/1 V
- Mini clamp 5 A /1 V
- Safety fuse adapters
- Safety flat clamps