Smart-UPS® VT ISX PDU Installation Important Safety Instructions

Smart-UPS® VT ISX PDU Installation Important Safety Instructions
of a Second PDU
1 Installation
in the UPS
PDU II. PDU II has 5 breaker sets. The top 2 breaker sets protect any 3-
phased equipment that may be connected to the PDU. Each of the top
breaker sets operates as a unit and will switch ON/OFF all 3 phases and
Neutral (L1, L2, L3, N) when operated. The breaker sets protect the 2
CEE32 outlets (under the red cover). Each of the 3 other breakers protect
the 3 single-phased IEC 309 16A outlets (under the blue covers).
OFF
1
C19
outlet
OFF
CEE
outlet

Remove the two M4 torx screws
from the lower cover plate of the
PDU.

Remove the two screws from the
bottom installation area. Keep the
screws for later use.

Position the two rear sets of holes
of the PDU over the provided
screws in the side panel, and push
down.

Attach the bottom end of the PDU
to the UPS, using the two screws
removed in step 2.
1
phased equipment that may be connected to the PDU. The top breaker set
operates as a unit and will switch ON/OFF all 3 phases + N (L1, L2, L3,
N) when operated. Each of the 4 other breaker sets protects the 3 singlephased C19 outlets (L1, L2, L3) beneath the actual breaker set. The left
breaker in each row protects L1, the middle breaker protects L2, and the
right breaker protects L3.
Important Safety Instructions SAVE THESE INSTRUCTIONS
OFF
OFF
PDU I. PDU I has 5 breaker sets. The top breaker set protects any 3-
Installation
OFF
OFF
At the rear, the UPS contains one Power Distribution Unit (PDU) as
standard (PDU I). A second PDU can be installed on the right side. The
second PDU will either be another PDU I or a PDU II.
Smart-UPS® VT ISX PDU
OFF
OFF


AC and ground cable landings

The installation procedures for PDU I and II are identical.
Installing the PDU
The right side panel of the UPS is provided with two sets of screws for the
attachment of the second PDU.
PDU II
PDU I




Always read the separate Safety 990-2822A sheet prior to the
installation.


Note
Warning
Warning
All electrical power and power control wiring must be installed by
a qualified electrician, and must comply with local and national
regulations for maximum power rating.
The UPS is be supplied from a 380Y/220 V 4W + GND 50/60 Hz or
400Y/230 V 4W + GND 50/60 Hz or 415Y/240 V 4 W + GND 50/60
Hz source.
990-2811A
*990-2811*
05/2006
 Set the PDU breaker to the OFF position.
 Using a torx screwdriver, remove the four M4 screws from the top
plate of the left pre-installed PDU.


 Attach the PDU cables (L1,L2,L3,N) to the terminals. Fasten the
cables with cable ties (not provided).
 Attach the Ground cable to the ground stud and fasten with cable tie.
Smart-UPS® VT ISX PDU, 400 V, Installation
Connecting load to the 3-phased breaker
 Reinstall the top plate removed in step 2.
 Use cable ties to tie the cables together.



L1

L2
L3
N



Cables
from
the
second
PDU




Set the PDU breaker to the
OFF position.

Using a torx screwdriver,
remove the four M4 screws
from the top plate of PDU.
Remove the plate.

Loosen the M6 screws, and
connect L1, L2, L3 and N to
the terminals. Tighten the
screws firmly. Fasten cables
with cable ties.




 Attach the ground cable to the stud (labeled Earth) and fasten with



Loosen (do not remove) the two screws from the bottom cover of the
PDU and slide the cover outwards to uncover the cable entrance hole
in the bottom cover plate of the second PDU.
 Feed the cables from the left pre-installed PDU through the cable
entrance hole.
 Attach the PDU cables (L1, L2, L3, N) to the terminals in the second
PDU. Fasten the cables with cable ties.
 Attach the ground cable to the designated stud (labeled Earth).
Fasten the cable with a cable tie.
 Remove the cable landing cover from the UPS.
 Attach the PDU cables (L1, L2, L3, N) to the terminals in the second
PDU, and fasten with cable ties.
 Attach the ground cable to the designated stud (labeled Earth) and
fasten with cable ties.
Warning
 Use a torx screwdriver to reinstall the top plate removed in step 2.
 Feed the cable through the cable outlet in the top cover.
Connecting 1-phase load to PDU I
 Reinstall the cable landing cover using the removed screws.


2 Connecting Load to the PDU

Preparing to connect the load to the PDU(s)
 Reinstall the cover plate using the two removed M4 screws.
Connecting a PDU to the UPS busbars
cable tie.
Note
Always carry out the Total-Power-Off procedure prior to
the connection of the PDU to the output terminals of the
UPS. Refer to the separate Safety sheet 990-2822A for
instructions.
Note
The PDU can also be connected to the right connection area of the output
busbars of the UPS.
Note
Connect the load equipment evenly between the 3 phases to
avoid overloading the PDU. The total PDU output capacity is
about twice the output capability of the UPS. This means that
the UPS would be over-loaded if all PDU outlets were loaded
to their rating. The load status on the individual phases can be
found through the UPS display or through the web interface.
1
2
3


Equipment connected to the 3-phased output may require
overcurrent protection with a lower rating than the 3-phased
output.
 Set the applicable breaker to the OFF position.
For 3-phased output, the highest current may be in the Neutral
conductor at non-linear loads (up to 173%).
 Insert the plug from the load into the C19 outlet.
 Guide the load cable down through the top hole.
 Secure the plug by inserting the locking brackets.
 Set the applicable breaker to the ON position.
Smart-UPS® VT ISX PDU, 400 V, Installation
Smart-UPS® VT ISX PDU, 400 V, Installation
Connecting 3-phase load to PDU II

Disconnecting the load from the PDU(s)
To disconnect the load, set the applicable breaker(s) to the OFF position.


Set the applicable breaker set
to the OFF position.


Guide the load cable down
through the top hole.
PDU output breaker ratings
Nominal breaker rating
OFF
OFF
OFF
OFF
OFF
1
OFF
OFF
OFF
1



Lift up the receptacle cover
and connect the load to the
CEE 32A outlet.
Set the breaker set to the ON
position.
Rear of unit
Ambient temperature
in front of unit ºC
16
32
40
50
Free exhaust
20
16
32
40
50
Free exhaust
30
14.4
30.4
38
47.5
Free exhaust
40
12.8
27.2
34
42.5
Hot aisle
containment
25
14.4
30.4
38
47.5
3 Contact Information
Connecting 1-phase load to PDU II

OFF
OFF
OFF

Set the applicable breaker to
the OFF position.

Guide the load cable down
through the top hole.

Lift up the receptacle cover
and connect the load to the
CEE 16A outlet.

Reset the breaker to the ON
position.
OFF
1
OFF
OFF
OFF
OFF
1



Smart-UPS® VT ISX PDU, 400 V, Installation
If a problem occurs, phone Technical Support at +353 91 702 479 or go to
Web Support: [email protected] For local country-specific centers: go to
www.apc.com/support/contact.
Smart-UPS® VT ISX PDU, 400 V, Installation