Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Two Style ‘B’ initiating circuit
One Style ‘Y’ indicating circuit (1.25 Amps)
Individual Zone Silence/Disconnect switches
Powerful 3 mA capacity per zone for 2-wire smoke
detectors
Common alarm Relay contact, Form C, 28 VDC @
3 AMP (Resistive)
Selectable ‘N.O’ or ‘N.C’ common trouble contact 28
VDC @ 3 Amp(Resistive)
A.C. ON LED (Green)
Zone Alarm LED (Amber)
Signal Trouble LED (Amber)
Ground Fault LED (Amber)
Battery Fault LED (Amber)
Alarm Silenced LED (Amber)
Common Trouble LED & Silence switch
Remote Trouble Indicator output
Remote A.C. On output
Selectable 1 minute Signal silence inhibit
Extensive Transient Protection on all circuits
Red exterior colour
Description
The Mircom FA-102U panel is designed for noncoded fire alarm systems in small commercial,
institutional and industrial occupancies. A slim-line
design and a neutral beige exterior colour offers
an unobtrusive appearance to complement any
interior.
The FA-102UA includes one circuit board providing
all the essentials for a complete fire alarm system.
Two Class ‘B’ initiating circuit and one Style ‘Y’
indicating circuit are provided by the FA-102A. The
indicating circuit is protected from shorts by selfrestoring circuitry.
Supervision includes ground fault detection, battery
low level or open wire fault, initiating and indicating
circuit wiring faults and loss of A.C. power. Initiating
circuits are supervised for opens and power.
Indicating circuits are supervised for opens and
ground faults. Indicating circuits are supervised for
opens, shorts and ground faults. LED indicators
are provided for Zone Alarm, Zone Trouble, A.C.
On, Battery Fault, Ground Fault, Common Trouble,
Signal Trouble and Silence Silenced. Switches are
provided for Zone disconnect/silence, trouble silence
and reset.
Upon a trouble condition, the trouble LED will flash
and the trouble audible signal will pulse. Activating
the “Trouble Silence” switch silences the trouble
signal and the “Trouble “ LED remains flashing.
When the trouble condition clears, the common
trouble LED restores to normal and the common
trouble buzzer resounds steady until the Trouble
signal silence switch is returned to normal. The
alarm signals cannot be silenced for one minute
if the one minute inhibit feature has been selected
(cut jumper).
The common alarm relay can follow the signal circuit
or lock on until the Alarm has been reset. This option
is jumper selectable.
The FA-102A controls are behind a durable locked
door. The cabinet will accommodate a 4 or 6 AH
battery pack.
S7010
MEA
approved
7165-1477:102
313-97-E
CATALOGUE NUMBER
NOT TO BE USED FOR INSTALLATION PURPOSES.
5011
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
Wiring Diagrams
INITIATING AND INDICATING WIRING INSTRUCTION
ALARM AND TROUBLE RELAY CONTACTS AND REMOTE
ANNUNCIATION WIRING INSTRUCTION
Technical Specifications
Initiating Circuits
Output Voltage
Current Limited
Supervisory Current
Loop Resistance
End of Line Resistor
22 VDC, filtered and regulated.
50 mA
3 mA (up to 30, 2-wire smoke detectors @ 100 uA each)
100 ohms, max
3.9Kohm ± 5%, 1/2W
Indicating Circuits
Output Voltage
Output Current
End of Line Resistor
Auxiliary Contacts
Dimensions
24 VDC
1.25A
3.9Kohm ± 5%, 1/2W
28 VDC, 3A (Resistive)
13.7”(347mm)W x 12.7”(322mm)H x 2.8”(71mm)D
Ordering Information
Model
FA-102U
RTI-1
FA-102TR
BA-104
BA-1065
Description
Two Zone Fire Alarm Panel
Remote Trouble indicator, mounts onto a single gang electrical box
Flush Mounting Trim Ring
Gel-Cell 12V / 4.0 AH Battery (2 required)
Gel-Cell 12V / 6.5 AH Battery (2 required)
NOT TO BE USED FOR INSTALLATION PURPOSES.
Distributed by:
Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: (905) 660-4655
Fax: (905) 660-4113
Web page: http://www.mircom.com
U.S.A.
60 Industrial Parkway
Cheektowaga, New York 14227
Toll Free: (888) 660-4655
Fax Toll Free: (888) 660-4113
Email: [email protected]
CAT. 5011
Rev. 3
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement