IPE Series - Emergi-Lite

IPE Series - Emergi-Lite
Project/Location:
IPE
Series
Contractor:
Date:
Prepared by:
IP65 Linear Fluorescent Fixtures
Features
Typical Specification
Polycarbonate enclosure and lens, vandal resistant and
UV stabilized
Supply and install Emergi-Lite IPE Series of fluorescent fixtures as specified. The luminaire shall operate from
120Vac to 277Vac or 347Vac and use high quality instant start or 3-step programmed rapid start high efficiency
electronic ballasts.
IP65 rated for wet and damp locations
Rust proof hardware
Ceiling, surface or pendant mounting
Low profile, less than 4” deep
Ultra efficient specular reflector with optimized shape
32W T8 or 54W T5HO
The body and lens shall be constructed of UV stabilized industrial grade vandal resistant polycarbonate. A durable
formed gasket shall be provided between the enclosure and the lens and shall be designed specifically for hostile
environments. The reflector shall be made of highly specular material and formed to maximize light output efficiency.
All parts shall be corrosion resistant. A metal plate used to retain the ballast and reflector also serves to dissipate
heat, therefore lengthening ballast life.
90 minutes of emergency operation when installed with
our FPSI or FPSU inverters
Lamps shall be as specified, either T8 or T5 HO linear fluorescent lamps, 32W or 54W. The lamps shall not be
supplied with the luminaire. Models with an inverter from the FPSI/FPSU series and illuminate one or two lamps
during emergency operation for at least 90 minutes upon AC failure. During power outage, dual voltage source
(AC/DC) models with an inverter from the 48 Series, shall illuminate one lamp while the DC voltage is present.
Suitable for wet locations
The fixture shall be CSA approved and meet IP65 designation requirements.
Emergency operation from external DC low voltage power
source when installed with our 48 Series inverters
The inverters of Series 48 shall be CSA approved.
The inverters of the FSPI series shall be CSA or cUL approved.
The fixture shall be Emergi-Lite model: __________________
Wire Guards
Dimensions
Wall or Ceiling Mount
13” [142cm]
33⁄4” [15cm]
460.0105-E
Ordering Code
AC Specs
IPE8
120/277Vac
0.54 / 0.23 Amp
PF > 0.9
IPE83
347Vac
0.19 Amp
PF > 0.9
IPE5
120/277Vac
1.03 / 0.143 Amp
PF > 0.9
IPE53
347Vac
0.35 Amp
PF > 0.9
63⁄4” [26cm]
Power Consumption
503⁄4” [200cm]
Ordering Information
Series
IPE= 48" (122cm)
linier fluorescent
Lamp type*
8= 2x lamps 32 watts T8
5= 2x lamps 54 watts T5HO
Voltage
Accessories
Blank= AC only 120/277Vca
3= A.C. only 347Vca
SELF-POWERED, ONE LAMP EMERGENCY
FPSI-32= inverter for IPE8 (complete code = IPE8FPSI-32)
FPSI⁄U-3= inverter for IPE8-3 (complete code = IPE8-3FPSI⁄U-3)
FPSI⁄U= inverter for IPE5 (complete code= IPE5FPSI⁄U)
SELF-POWERED, TWO LAMPS EMERGENCY
FPSU-28= inverter for IPE8 (complete code= IPE8FPSu-28)
FPSI⁄U-3= inverter for IPE8-3 (complete code= IPE8-3FPSI⁄U-3)
Two lamp model not available for T5 bulb (IPE5)
AC⁄DC OPTION, USING A REMOTE BATTERY, ONE LAMP ONLY IN EMERGENCY MODE:
4806100= 6 volts, 120Vac
4832100= 32 volts, 120Vac
4806100-3= 6 volts, 347Vac
4832100-3= 32 volts, 347Vac
4812100= 12 volts, 120Vac
4848100= 48 volts, 120Vac
4812100-3= 12 volts, 347Vac
4848100-3= 48 volts, 347Vac
4824100= 24 volts, 120Vac
48120100= 120 volts, 120Vac
4824100-3= 24 volts, 347Vac
48120100-3= 120 volts, 347Vac
081282-E= Stainless Steel Clips Kit (10)
*Lamps not included.
Consult factory for DC operation
For more information on the 48 Series, please refer to
Options & Accessories in your Emergi-Lite catalogue.
EXAMPLE: IPE8