1-Phase Intelligent PDU Outlets for 230V
Inspired by Your Data Center
1-Phase Intelligent PDU
Outlets for 230V
Intelligent kWh PDU - W series
Power Efficiency Management
With today’s increasing demand for high technology power management solutions, PDU kWh
measurement and the associated software allow data center managers to make key decisions
regarding the most efficient use of power. The need to maximize power efficiency to reduce cost is high
up the corporate agenda. For 24x7x365 operation, a small increase in efficiency can result in major
savings in running cost. W series PDUs provide the kWh measurement for an effective planning on the
power capacity. Models with outlet level kWh measurement are also available.
Uptime and Productivity Improvements
Uptime and productivity improvements are achieved through the remote management. W series PDUs
support daisy chain connections allowing up to 16 PDUs to be cascaded via Cat6 cables. All the PDUs
are remotely accessed via only one network IP address. The GUI software provides easy-to-learn tools
for the PDU remote management. It is simply accessed via the web browser to access all the connected
PDUs in anywhere around the world. Ultimately, this can help reducing manpower and travel costs by
negating the need for staff to actually be at the equipment location.
Green Data Center Movement
Growth of data center development increases power requirements and hence causes not only operation
cost issues but also environmental concerns. It needs to monitor, measure and manage power
consumption in order to get you on the path toward power saving for green data center operation.
The kWh energy consumption measurement provided by W Series PDU solutions helps driving the green
data center movement by enhancing the power distribution management on data center.
Monitored
W Intelligent PDU series
W
Switched
Wi
WS
WSi
Outlet AMP - kWh Measurement
Outlet Switch ON / OFF
Hot-Swap Meter
1.8" Color LCD
Circuit Amp - kWh Measurement
Temp-Humid Sensor port x 2
16 PDU Levels in Single Daisy Chain
One IP Access up to 16 PDU Levels
SNMP Capability v2 / v3
Free Management Software
Lockable IEC Outlet Model
Individually Fused Outlet Model
63A Model ( only for 230V PDU )
Local Meter
Tool-less Mounting for Vertical PDU
0U / 1U / 2U Form Factors
Hydraulic MCB / Resettable Fuse Option
Voltage 230V / 208V / 110V
Operating Temperature Range -5°C to 60°C
Outlet Types : IEC C13
IEC C19
IEC C13 + C19
IEC Lockable
IEC Individually Fused
NEMA
UK
/ UK
+ IEC
SCH / SCH + IEC
* For selective high density outlet & 63A configurations, 2.8" touchscreen display will be applied.
1
Key Benefits
Field Replaceable Meter
The 1.8" LCD color display provides a sharp and highly visible reading of energy
consumption, power, current, temp-humid, etc. Local setup can be made by
using a membrane switch indicating ‘up’, ’down’, ‘enter’ and ‘back’ options.
The field replaceable display design helps eliminating maintenance downtime
by simply replacing a possible defective meter without a service interruption.
The connection ports for the PDU daisy chain as well as the temperature &
humidity sensors are conveniently positioned for easy access.
* For selective high density outlet & 63A configurations, 2.8" touchscreen display will be applied.
Reduce IP Address Costs within the Network
The patented hot pluggable IP dongle provides a highly cost effective method
to access W series intelligent PDUs. It is designed to support daisy chain
connections allowing up to 16 PDUs to be cascaded via Cat6 cables - all the
PDUs are remotely accessed via a single network IP address.
Ultra Density PDU Management
W series PDUs are designed to support daisy chain connections, up to 16 PDUs
can be remotely accessed via one single IP. InfraPower Manager, IPM-04,
supports up to 50 IP groups, and hence centralized management for 800 PDUs
can be achieved.
Software Functionality
Free IPM-04 allows an advanced PDU remote management for up to 800 PDUs.
Features include kWh / Amp monitoring, outlet switched on / off, outlet
measurement, outlet scheduling, temp & humid monitoring, reporting, alarm
setting, etc. PPS-02-S preloaded by the IPD-02-S provides an easy and
simple PDU monitoring for PDU technical management.
Broadest Portfolio of Intelligent PDUs
In addition to supplying cost-effective standard PDU models with a great delivery schedule, competitive custom PDU configurations for specific user
requirements are also available on short lead-times.
2
Key Benefits
Colored PDU Casings & Power Cords
Colored PDU casings and power cables provide the simplest way to enhance
the cable management and visualize the power sources. Users can simply
distinguish the PDU from which power source according to the color of the PDU
casing or power cable.
Short Length Vertical Casing Design
The short length vertical casing design of InfraPower maximizes the number
of outlets. W series PDU with standard 1650mm / 65 inches casing supports
20 x UK outlets ( 1425mm / 56 inches for 20 x Schuko ) thus saving space
within the rack.
Wide Range Configurations
The PDUs range from 6 to 20 UK or 8 to 20 Schuko outlets giving customers
the flexibility to meet budget and application demands.
63A PDUs
In part due to the popularity of ultra-thin blade servers, sometimes a tremendous
amount of computing power is required for equipment mounted in a single rack.
63A models are available for such high power usage requirements.
* only available for 230V W Monitored models
PDU Mounting Options
Button
InfraPower PDUs are supplied with 2 types of mounting kits; Vertical Button
Mounting Kit & Vertical Bracket Mounting Kit. The tool-less kits can be used on
the majority of global branded racks.
Bracket
3
W
- Outlets for 230V
Monitored kWh PDU
W PDU - kWh as a Standard
The InfraPower W monitored PDU is a rackmount industrial grade PDU for mission critical data centers and remote install sites.
The W PDU meter is designed with a 1.8" color LCD display. It provides a sharp and highly visible reading for the local strip
level reading of current(Amp), voltage(Volt), power(kVA, kW), energy consumption(kWh), power factor, as well as temperature
and humidity. This also allows remote monitoring with the use of an IP dongle via a simple, secure web based GUI management
interface. W PDU can be cascaded up to a maximum of 16 PDUs using a low cost Cat6 patch cord allowing access control and
monitoring via a single IP address over an Ethernet network. The real time monitoring provided by the W PDU cannot only help
by reducing manpower and related travel costs, but can also help users with capacity planning and improving the overall
efficiency of the data center.
Key Features
Temperature
Humidity
Monitoring
Power
Factor
Monitoring
Power
(kVA, kW)
Monitoring
Voltage
(V)
Monitoring
Current
(A)
Monitoring
Energy
(kWh)
Monitoring
cUL certified for specific configurations
Vertical
Horizontal
1 inch = 25.4 mm
UK - 10A / 13A / 16A / 20A / 32A
UK + IEC - 16A / 20A / 32A
Schuko
- 16A / 20A / 32A
SCH + IEC - 16A / 20A / 32A
Length
UK
20
16
12
8
4
4
4
4
4
C13
C19
mm
6
4
4
4
4
1650
1425
1200
900
1800
1800
1650
1425
1200
20
20
16
12
8
Length
SCH C13
20
16
12
8
4
4
4
4
4
20
20
16
12
8
mm
UK
6
4
4
4
4
1425
1200
1200
900
1800
1650
1650
1425
1200
8
6
8
8
8
C13
C19
U
4
2
4
2U
1U
2U
2U
2U
8
8
6
10A Inlet
mm
SCH
20A Inlet
1800
1650
1650
1425
20
16
SCH C13
8
8
8
8
*
*
230V PDU bundled with Resettable Fuse
Optional upgrade to MCB is available
U
4
2
4
2U
2U
2U
2U
IEC320
C20
IEC 60309
2P+E
32A / 63A Inlet
Open
end
All are aluminum extrusion
8
8
6
C19
16A Inlet
IEC320
C14
Length
20
16
Height
Height
C19
UK
- 63A
Schuko - 63A
UK
Schuko
- 16A / 20A / 32A
SCH + IEC - 16A / 20A / 32A
UK - 10A / 13A / 16A / 20A / 32A
UK + IEC - 16A / 20A / 32A
IEC 60309
2P+E
Intelligent PDU Product Code
Austin Hughes has designed a simple but informative InfraPower product code builder
in order to let our clients determine the desired PDU configuration to meet their needs.
Code Structure
UK
SCH
Digit
Indication
Examples
Form Factor
V = Vertical
Outlet nos
UK
: 20 / 16 / 12 / 8 / 6
UK + IEC : 4
SCH
: 20 / 16 / 12 / 8
UK + SCH : 4
° degree
: 45° / 135°
Vertical
Horizontal : 90°
W
W
(only for UK PDU)
V
UK
V
SCH
C13
C19
W
GF
Amp
UK
UK + IEC
SCH
SCH + IEC
Product Code Example
Circuit Protection
V4UK45/20C13/6C19-32A-W/F_EN/3B-4
1-Phase W series Vertical PDU with UK (45°) x 4 & IEC C13 x 20 & C19 x 6 / 32A /
Resettable Fuse / 3M cordset + Inlet IEC60309 2P+E / Bottom Feed / Blue Casing
CR = Hydraulic Magnetic Circuit Breaker ( MCB )
F = Resettable Fuse
Inlet
C14
C20
EN
OE
Cordset
3 = 3M / 9.84' ( except 63A )
2 = 2M / 5.56' ( 63A only ) * Custom length on request
Bottom or top feed
B = Bottom feed
C13
C19
W
GF
V16SCH-63A-W/CR_EN/2B-2
1-Phase W series Vertical PDU with Schuko outlet x 16 / 63A / Circuit Breaker /
2M cordset + Inlet IEC60309 2P+E / Bottom Feed / White Casing
H8UK90/8C13/4C19-20A-W/CR_OE/3B-1
1-Phase W series 2U Horizontal PDU with UK (90°) x 8 & IEC C13 x 8 & C19 x 4 / 20A /
Circuit Breaker / 3M cordset + Inlet Open End / Black Casing
For more information, please visit www.austin-hughes.com
4
H = Horizontal
: 10A / 13A / 16A / 20A / 32A / 63A
: 16A / 20A / 32A
: 16A / 20A / 32A / 63A
: 16A / 20A / 32A
: IEC320 C14
: IEC320 C20
: IEC 60309
: Open end
T = Top feed
(only for vertical PDU)
Colored PDU casing
(only for vertical PDU)
1 = Black
3 = Red
2 = White
4 = Blue
WS
- Outlets for 230V
Switched kWh PDU
WS PDU - Mission Critical Essential
Besides kWh and current remote monitoring, the ability to switch on / off per outlet is another key requirement for intelligent
PDU. Especially for the data center with 24/7 operation, it needs the remote outlet switching function so that the unresponsive
IT equipment can be rebooted remotely to minimize the downtime. As a result, switched PDU is an essential cabinet
component for mission critical data center. InfraPower WS includes all the power monitoring features of W model. In addition,
it allows individual outlet switch on / off remotely through the InfraPower management software. By applying the top edition
of IPM-03, outlet switching on / off scheduling can be achieved for an advanced switching management.
Key Features
Temperature
Humidity
Monitoring
Power
Factor
Monitoring
Power
(kVA, kW)
Monitoring
Voltage
(V)
Monitoring
Current
(A)
Monitoring
Energy
(kWh)
Monitoring
ON / OFF
Outlet
Switching
cUL certified for specific configurations
Vertical
Horizontal
1 inch = 25.4 mm
UK - 10A / 13A / 16A / 20A / 32A
UK + IEC - 16A / 20A / 32A
Schuko
- 16A / 20A / 32A
SCH + IEC - 16A / 20A / 32A
Length
UK
20
16
12
8
4
4
4
4
4
*
*
C13
20
20
16
12
8
C19
mm
6
4
4
4
4
1650
1425
1200
1200
1800
1800
1650
1425
1200
Length
SCH C13
20
16
12
8
4
4
4
4
4
20
20
16
12
8
Schuko
- 16A / 20A / 32A
SCH + IEC - 16A / 20A / 32A
UK - 10A / 13A / 16A / 20A / 32A
UK + IEC - 16A / 20A / 32A
Height
Height
C19
mm
UK
6
4
4
4
4
1425
1200
1200
1200
1800
1800
1650
1425
1200
8
6
8
8
8
C13
C19
U
4
2
4
2U
1U
2U
2U
2U
8
8
6
10A Inlet
All are aluminum extrusion
SCH C13
8
8
8
8
20A Inlet
U
4
2
4
2U
2U
2U
2U
16A Inlet
IEC320
C14
230V PDU bundled with Resettable Fuse
Optional upgrade to MCB is available
8
8
6
C19
IEC320
C20
IEC 60309
2P+E
32A Inlet
Open
end
IEC 60309
2P+E
Intelligent PDU Product Code
Austin Hughes has designed a simple but informative InfraPower product code builder
in order to let our clients determine the desired PDU configuration to meet their needs.
Code Structure
UK
SCH
Digit
Indication
Examples
Form Factor
V = Vertical
Outlet nos
UK
: 20 / 16 / 12 / 8 / 6
UK + IEC : 4
SCH
: 20 / 16 / 12 / 8
UK + SCH : 4
° degree
: 45° / 135°
Vertical
Horizontal : 90°
WS
WS
(only for UK PDU)
V
UK
V
SCH
C13
C19
WS
GF
H = Horizontal
Amp
UK
UK + IEC
SCH
SCH + IEC
Product Code Example
Circuit Protection
V4SCH/16C13/4C19-32A-WS/CR_EN/3B-4
1-Phase WS series Vertical PDU with Schuko x 4 & IEC C13 x 16 & C19 x 4 / 32A /
Circuit Breaker / 3M cordset + Inlet IEC60309 2P+E / Bottom Feed / Blue Casing
CR = Hydraulic Magnetic Circuit Breaker ( MCB )
F = Resettable Fuse
Inlet
C14
C20
EN
OE
Cordset
3 = 3M / 9.84'
Bottom or top feed
B = Bottom feed
C13
C19
WS
GF
V20UK135-13A-WS/F_BS/2B-2
1-Phase WS series Vertical PDU with UK (135°) outlet x 20 / 13A / Resettable Fuse /
3M cordset + Inlet BS1363 / Bottom Feed / White Casing
H8SCH/8C13/2C19-20A-WS/CR_OE/3B-1
1-Phase WS series 2U Horizontal PDU with Schuko x 8 & IEC C13 x 8 & C19 x 2 / 20A /
Circuit Breaker / 3M cordset + Inlet Open End / Black Casing
: 10A / 13A / 16A / 20A / 32A
: 16A / 20A / 32A
: 16A / 20A / 32A
: 16A / 20A / 32A
: IEC320 C14
: IEC320 C20
: IEC 60309
: Open end
* Custom length on request
T = Top feed
(only for vertical PDU)
Colored PDU casing
(only for vertical PDU)
1 = Black
3 = Red
2 = White
4 = Blue
For more information, please visit www.austin-hughes.com
5
Wi
- Outlets for 230V
Monitored kWh PDU with Outlet Measurement
Wi PDU - Necessity for Co-location
For the data centers which are providing co-location services, the ability to remotely monitor kWh consumption per outlet is a
necessity. Co-location rental requires outlet level kWh information to estimate the energy consumption of each co-located rack
space, or even each rackmount equipment. The Wi PDU meter is designed with a 1.8" color LCD display. It provides a sharp
and highly visible reading for the local individual outlet level reading of current(Amp), voltage(Volt), power(kVA, kW), energy
consumption(kWh), power factor, as well as temperature and humidity. With the use of an IP dongle via a simple, secure web
based GUI management interface, this allows remote individual socket monitoring. The Wi PDU can be cascaded up to a
maximum of 16 PDUs using a low cost Cat6 patch cord allowing access control and monitoring via a single IP address over an
Ethernet network.The real time monitoring provided by the Wi PDU can help users with capacity planning and improving the
overall efficiency of the data center.
Key Features
Vertical
Temperature
Humidity
Monitoring
Power
Factor
Monitoring
Power
(kVA, kW)
Monitoring
Voltage
(V)
Monitoring
Current
(A)
Monitoring
Energy
(kWh)
Monitoring
Schuko
- 16A / 20A / 32A
SCH + IEC - 16A / 20A / 32A
Length
UK
20
16
12
8
4
4
4
4
4
*
*
C13
20
20
16
12
8
C19
mm
6
4
4
4
4
1650
1425
1200
1200
1800
1800
1650
1425
1200
cUL certified for specific configurations
Horizontal
1 inch = 25.4 mm
UK - 10A / 13A / 16A / 20A / 32A
UK + IEC - 16A / 20A / 32A
Outlet
Level
Measurement
Length
SCH C13
20
16
12
8
4
4
4
4
4
20
20
16
12
8
Schuko
- 16A / 20A / 32A
SCH + IEC - 16A / 20A / 32A
UK - 10A / 13A / 16A / 20A / 32A
UK + IEC - 16A / 20A / 32A
Height
Height
C19
mm
UK
6
4
4
4
4
1425
1200
1200
1200
1800
1800
1650
1425
1200
8
6
8
8
8
C13
C19
U
4
2
4
2U
1U
2U
2U
2U
8
8
6
10A Inlet
All are aluminum extrusion
SCH C13
8
8
8
8
20A Inlet
U
4
2
4
2U
2U
2U
2U
16A Inlet
IEC320
C14
230V PDU bundled with Resettable Fuse
Optional upgrade to MCB is available
8
8
6
C19
IEC320
C20
IEC 60309
2P+E
32A Inlet
Open
end
IEC 60309
2P+E
Intelligent PDU Product Code
Austin Hughes has designed a simple but informative InfraPower product code builder
in order to let our clients determine the desired PDU configuration to meet their needs.
UK
SCH
Digit
Indication
Examples
Form Factor
V = Vertical
Outlet nos
UK
: 20 / 16 / 12 / 8 / 6
UK + IEC : 4
SCH
: 20 / 16 / 12 / 8
UK + SCH : 4
° degree
: 45° / 135°
Vertical
Horizontal : 90°
Wi
Wi
(only for UK PDU)
V
UK
V
SCH
C13
C19
Wi
GF
Amp
UK
UK + IEC
SCH
SCH + IEC
Product Code Example
Circuit Protection
V4UK135/8C13/4C19-20A-Wi/CR_OE/3B-4
1-Phase Wi series Vertical PDU with UK (135°) x 4 & IEC C13 x 8 & C19 x 4 / 20A /
Circuit Breaker / 3M cordset + Inlet Open End / Bottom Feed / Blue Casing
CR = Hydraulic Magnetic Circuit Breaker ( MCB )
F = Resettable Fuse
Inlet
C14
C20
EN
OE
Cordset
3 = 3M / 9.84'
Bottom or top feed
B = Bottom feed
C13
C19
Wi
GF
V8SCH-32A-Wi/CR_EN/2B-2
1-Phase Wi series Vertical PDU with Schuko outlet x 8 / 32A / Circuit Breaker /
3M cordset + Inlet IEC60309 2P+E / Bottom Feed / White Casing
H6UK90-13A-Wi/CR_BS/3B-1
1-Phase Wi series 1U Horizontal PDU with UK (90°) outlet x 6 / 13A / Circuit Breaker /
3M cordset + Inlet BS1363 / Black Casing
For more information, please visit www.austin-hughes.com
6
H = Horizontal
: 10A / 13A / 16A / 20A / 32A
: 16A / 20A / 32A
: 16A / 20A / 32A
: 16A / 20A / 32A
: IEC320 C14
: IEC320 C20
: IEC 60309
: Open end
* Custom length on request
T = Top feed
(only for vertical PDU)
Colored PDU casing
(only for vertical PDU)
1 = Black
3 = Red
2 = White
4 = Blue
WSi
- Outlets for 230V
Switched kWh PDU with Outlet Measurement
WSi PDU - High Level Achievement
WSi Outlet Level Switched kWh PDU is the most feature rich model in InfraPower W Series PDU family. It combines all the W
PDU series features : Monitoring of current, voltage, power, kWh energy consumption; Environmental temp. & humidity
monitoring; Outlet level measurement ; plus individual outlet remote switch on / off. Same as other models in W series,
16 x WSi in daisy chain only require 1 x IP for remote access. WSi is the sophisticated PDU model designed for data center
professionals with desire on high level PDU specification. By using the InfraPower management software IPM-03, WSi
achieves the highly featured power distribution management for energy efficiency initiatives and capacity planning.
Key Features
Vertical
Temperature
Humidity
Monitoring
Power
Factor
Monitoring
Power
(kVA, kW)
Monitoring
Outlet
Level
Measurement
Voltage
(V)
Monitoring
Current
(A)
Monitoring
Energy
(kWh)
Monitoring
ON / OFF
Outlet
Switching
Horizontal
1 inch = 25.4 mm
UK - 10A / 13A / 16A / 20A / 32A
UK + IEC - 16A / 20A / 32A
Schuko
- 16A / 20A / 32A
SCH + IEC - 16A / 20A / 32A
Length
UK
20
16
12
8
4
4
4
4
4
*
*
C13
20
20
16
12
8
C19
mm
6
4
4
4
4
1650
1425
1200
1200
1800
1800
1650
1425
1200
cUL certified for specific configurations
Length
SCH C13
20
16
12
8
4
4
4
4
4
20
20
16
12
8
Schuko
- 16A / 20A / 32A
SCH + IEC - 16A / 20A / 32A
UK - 10A / 13A / 16A / 20A / 32A
UK + IEC - 16A / 20A / 32A
Height
Height
C19
mm
UK
6
4
4
4
4
1425
1200
1200
1200
1800
1800
1650
1425
1200
8
6
8
8
8
C13
C19
U
4
2
4
2U
1U
2U
2U
2U
8
8
6
10A Inlet
All are aluminum extrusion
SCH C13
8
8
8
8
20A Inlet
U
4
2
4
2U
2U
2U
2U
16A Inlet
IEC320
C14
230V PDU bundled with Resettable Fuse
Optional upgrade to MCB is available
8
8
6
C19
IEC320
C20
IEC 60309
2P+E
32A Inlet
Open
end
IEC 60309
2P+E
Intelligent PDU Product Code
Austin Hughes has designed a simple but informative InfraPower product code builder
in order to let our clients determine the desired PDU configuration to meet their needs.
Code Structure
UK
SCH
Digit
Indication
Examples
Form Factor
V = Vertical
Outlet nos
UK
: 20 / 16 / 12 / 8 / 6
UK + IEC : 4
SCH
: 20 / 16 / 12 / 8
UK + SCH : 4
° degree
: 45° / 135°
Vertical
Horizontal : 90°
WSi
WSi
(only for UK PDU)
V
UK
V
SCH
C13
C19
WSi
GF
H = Horizontal
Amp
UK
UK + IEC
SCH
SCH + IEC
Product Code Example
Circuit Protection
V4SCH/12C13/4C19-16A-WSi/CR_EN/3B-4
1-Phase WSi series Vertical PDU with Schuko x 4 & IEC C13 x 12 & C19 x 4 / 16A /
Circuit Breaker / 3M cordset + Inlet IEC60309 2P+E / Bottom Feed / Blue Casing
CR = Hydraulic Magnetic Circuit Breaker ( MCB )
F = Resettable Fuse
Inlet
C14
C20
EN
OE
Cordset
3 = 3M / 9.84'
Bottom or top feed
B = Bottom feed
C13
C19
WSi
GF
V16UK45-13A-WSi/F_BS/2B-2
1-Phase WSi series Vertical PDU with UK (45°) outlet x 20 / 13A / Resettable Fuse /
3M cordset + Inlet BS1363 / Bottom Feed / White Casing
H8SCH-20A-WSi/CR_OE/3B-1
1-Phase WSi series 2U Horizontal PDU with Schuko outlet x 8 / 20A / Circuit Breaker /
3M cordset + Inlet Open End / Black Casing
: 10A / 13A / 16A / 20A / 32A
: 16A / 20A / 32A
: 16A / 20A / 32A
: 16A / 20A / 32A
: IEC320 C14
: IEC320 C20
: IEC 60309
: Open end
* Custom length on request
T = Top feed
(only for vertical PDU)
Colored PDU casing
(only for vertical PDU)
1 = Black
3 = Red
2 = White
4 = Blue
For more information, please visit www.austin-hughes.com
7
Connection & Remote Access
High Density PDU Management
InfraPower features a high density flexible PDU system coupled with an equally
flexible management software.
The W series PDUs support daisy chain connections and up to 16 PDUs can be
cascaded via Cat6 cables. All the PDUs in the daisy chain can be accessed by
one single network IP address.
PDU Daisy Chain Cascades up to 16 Levels
The W meter built-in not only provides the local power monitoring, but also the connection ports for the PDU daisy
chain. For daisy chain connection, each PDU just simply to be connected in series to the next by Cat5/6 cables.
Maximum 16 PDUs are supported in one daisy chain group.
IP dongle
Network hub
Cascades up to 16 PDU levels using low cost Cat5/6 cables
Cat 5 / 6 cable
Up to 20M
1st level
PDU meter
Cat 5 / 6 cable
Up to 20M
2nd level
PDU meter
3rd level
PDU meter
IP Dongle Access to 16 PDU Levels
The patented hot-pluggable IP Dongle provides IP remote access to the PDUs
using a single IP address chain. Only one IP dongle is required to access a
maximum of 16 PDUs in a daisy chain.
The hot-pluggable design facilitates the IP dongle installation. Simply integrate
the IP Dongle to the 1st PDU, then the entire daisy chain group can be remote
accessed over IP.
Hence, administrator can remotely access all PDUs in the daisy chain group by
one single IP via the IP Dongle.
IP Dongle models with SNMP support are available.
8
Final level
PDU meter
Connection & Remote Access
Management Software
InfraPower provides FREE software editions - IPM-04 / PPS-02-S
Each edition supports different capacity of PDU management and concurrent users.
Ultra High Density PDU Remote Management
W Series combines the edges of high efficient hardware connection and software remote management for an Ultra High
Density PDU Remote Management.
IP Dongle on the
first PDU level
‡ For IP PDU access simply connect 1 x IP dongle
‡ 1 x IP dongle allows access to 16 x PDU
‡ Only 1 x IP for 16 x PDU access
‡ Daisy chain by Cat5/6 cable
‡ Max. distance between 2 PDUs is 20M
‡ The PDUs can be cascaded up to 16 levels
Remote access by
web-based GUI
from anywhere
around the world
Remote Management by InfraPower Manager GUI
IPM-04 :
50 x IP dongle group (800 x PDU)
5 x concurrent user
PPS-02-S : 1 x IP dongle group (16 x PDU,
via IPD-02-S)
9
Field Replaceable Meter
Local PDU Management
W Meter - Advanced & Sophisticated
All W series PDUs are supplied with a W meter that provides the cascade ports
for daisy chain up to 16 x PDUs. Furthermore, for IP PDU access, simply
connect 1 x IP Dongle for all daisy chain PDUs. This allows use of a single IP
address throughout the power network. Two sensor ports are integrated for
temperature & humidity monitoring. Creatively, the 1.8" color LCD display offers
a real time local monitoring and detailed PDU status.
By Field Replaceable Meter
For mission critical data centers where no amount of downtime or disruption is acceptable. The field replaceable ‘W’
Meter can be simply swapped without the need to power down.
Local Management by Meter
Display 1
Display 2
Display 3
Display 4
Display 5
Display 6
Display 6.1
Display 6.2
Display 6.3
Display 6.4
Display 7
Display 8
Display 9.3
Display 9.4
Display for PDU Moniforing
‡$PS9ROW3RZHU)DFWRU
‡N:K(QHUJ\&RQVXPSWLRQ
‡$FWLYH$SSDUHQW3RZHU
‡7HPS+XPLGLW\
Display for Outlet Level
Measurement
(Wi and WSi series PDUs only)
‡2XWOHW$PS
‡2XWOHWN:K
W Meter provides the buttons to select the displays
Up
Down
Enter
Display 9
Back
Display 9.1
Display 9.2
Display for Local PDU
Setting
‡3'8/HYHO
‡0HWHUEX]]HU
‡0HWHUVFUHHQ
‡3'82XWOHW21
* For selective high density outlet & 63A configurations, 2.8" touchscreen display will be applied.
10
Management Software
IPM-04 - Free but Powerful
InfraPower Manager IPM-04 is the free, powerful and user friendly PDU management software
provided with W Series PDUs.
The Administrator can remotely manage the PDUs and the temperature / humidity sensors via the
web browser. The Windows based software consolidates management of max. 800 single & three
phase PDUs via 50 IP dongles. 5 concurrent user access licences are part of the IPM-04 bundle,
for achieving the demand of multi-user requirements in data center operations.
IPM-04 provides complete PDU monitoring / control and reporting functions for your data center.
800
PDUs
One IP
16 PDUs
IPM-04
50 IP
Groups
5
Users
Man Hour
Saving
Quality
Budget
Saving
PDU Monitoring
Features
Capacity
IP Dongle Group ( Just 1 for 16 PDU levels )
50
PDU Number
800
5
Concurrent Users
Enhanced
Features
Efficiency
Outlet Level kWh & Amp Measurement
Outlet Scheduling
Energy Consumption ( kWh ) Monitoring
Apparent Power ( kVA ) Monitoring
Power Factor Measurement
Temp. & Humid. Monitoring
Circuit Breaker ( MCB ) Monitoring
Basic
Features
Aggregate Current ( Amp ) Monitoring
Individual Outlet Switch ON / OFF
Temp-Humid Monitoring
Alarm Threshold Setting
Rising Alert Threshold
Remote Access via Web
Graphic User Interface
Reporting
Reporting
PDU Series
Support
Single & 3 Phase W
- Monitored PDU
Single & 3 Phase WI
- Monitored PDU ( Outlet Measurement )
Single & 3 Phase WS - Switched PDU
Single & 3 Phase WSI - Switched PDU ( Outlet Measurement )
11
Accessories
IP Dongle for Vertical PDU
IP Dongle for Horizontal PDU
• Patented design
IPD-02-S
IPD-H02-S
• External sensor with 2M or 4M
cord
Vertical
• Hot pluggable for easy integration
• Plug & Play
• Allows IP remote access to the
PDUs by a single network IP
• Low profile design with magnetic
base for easy affixing to the
cabinet
• One IP dongle supports max. 16
PDUs in daisy chain
Horizontal
• Highly cost effective method to
access the intelligent PDUs
Temp. & Humid. Sensor
Temp. Sensor
• Pair of sensors can be connected
to one single W series PDU meter
• SNMP capability v2 / v3
MCB
Resettable Fuse
• Hydraulic magnetic circuit breaker
• Protect load segments for increased
reliability
• Overload switch
• Designed to prevent accidental
on / off operation
• Safety Regulatory :
UL / cUL / TUV / CE
• 10A 13A 16A 20A 32A 63A -
1-pole
1-pole
1-pole
1-pole
1-pole
1-pole
10A MCB
13A MCB
16A MCB
20A MCB
16A MCB
16A MCB
x
x
x
x
x
x
1
1
1
1
2
4
• Overload reset buttons
• Safety Regulatory :
UL / cUL / CSA / TUV / CCC / VDE
• 10A 13A 16A 20A 32A 63A -
1-pole
1-pole
1-pole
1-pole
1-pole
1-pole
x
x
x
x
x
x
1
1
1
1
2
4
Surge Protector
EMI Filter
• Enhances the device protection
• Suppresses conducted interference
on a signal / power line
• Grounds unwanted voltages above
safe threshold
• Line frequency : 50 / 60 Hz
• Attenuation
Surge suppression
Max surge current
Max surge voltage
Response Time
Earth Red
LED
2,700 Joules
75,000 Amps
6,000 Volts
1 nanosecond
Normal - on
Faulty - off
Protect Green LED : Normal - on
Faulty - off
12
10A Fuse
13A Fuse
16A Fuse
20A Fuse
16A Fuse
16A Fuse
:
:
:
:
:
: Up to 50 dB
• 16A - EMI filter x 1
20A - EMI filter x 1
32A - EMI filter x 2
IG-TH01-2M / 4M
IG-T01-2M / 4M
Accessories
Colored Power Cords
Colored PDU Casing
• Enhance cable management
and visualize power sources
• Visualize power sources
C13 - C14 6ft
EC-6PC1314-B
EC-6PC1314-R
EC-6PC1314-O
EC-6PC1314-G
( 1.0 mm² )
Blue
Red
Orange
Light Grey
Color
Blue
Red
Light Grey
C13 - C14 10ft
EC-10PC1314-B
EC-10PC1314-R
EC-10PC1314-O
EC-10PC1314-G
( 1.0 mm² )
Blue
Red
Orange
Light Grey
IEC Secure Sleeves
C19 - C20 6ft ( 1.5 mm² )
EC-6PC1920-B Blue
EC-6PC1920-R Red
IPP-SS-C13
IPP-SS-C19
Sleeve attached to C14 power cord inlet :
IPP-SS-C13 ( pack of 200 )
External PDU Display
IP-ED-02
• Support two PDU displays with
amp. and temp.
• Adjustable Mounting Kit for easy
installation to cabinet door
• Secure the power cord connections
to the PDU IEC outlets
• Bundled 3m RJ-11 cable x 2
• Simple and cost efficient
• Quick and Tool-less integration
simplifies PDU installation
• Designed for particular global
branded cabinet with key hole
type mounting holes on rear verticals
Suggested Combination :
Blue + Red
Light Grey + Standard Black
• Plug & Play
Sleeve attached to C20 power cord inlet :
IPP-SS-C19 ( pack of 100 )
Vertical Button Mounting Kit
Part No.
CC-B
CC-R
CC-LG
• For 2.8" touchscreen meter only
VMS
Vertical Bracket Mounting Kit
VMB
• Universal mounting kit supports
all cabinet models
• Easy integration by mounting the
PDU to the cabinet cable tray
13
Founded in 1995, Austin Hughes Electronics Ltd is a design and manufacturing group that offers a broad
range of solutions based around 19 inch rackmount technology. These solutions include InfraSolution remote
access control and locking, InfraPower intelligent remote management power solutions, CyberView LCD
Keyboard and KVM drawers & InfraCool intelligent remote cooling system.
Austin Hughes has ISO14001 and ISO9001 approved design, manufacturing, assembly and test
facilities in Hong Kong and China. Austin Hughes supports a worldwide customer base, through its global
locations in the Americas, EMEA and APAC and through its extensive authorized channel partner support
network.
APAC
Americas
Austin Hughes Electronics Ltd.
Austin Hughes Solutions Inc.
Unit 3608-12, Cable TV Tower
9 Hoi Shing Road, Tsuen Wan
Hong Kong
41320 Boyce Road, Fremont
CA 94538
USA
Email:
Email:
[email protected]
[email protected]
China
EMEA
Austin Hughes Electronics (China) Ltd.
Austin Hughes Europe Ltd.
Hexi Road No.2, Jinxia Industrial Area
Changan Town, Dongguan City
Guangdong Province 523850
China
Unit 1, Chancery Gate Business Centre
Manor House Avenue
Southampton, SO15 0AE
United Kingdom
Email:
Austin Hughes has an extensive distribution network,
including the Americas, EMEA and APAC.
Contact your nearest sales office for details of local representation
[email protected]
Distributed by:
www.austin-hughes.com
Please ask for details of other products from Austin Hughes. Every effort has been made to ensure that the information
contained herein is correct. There is a possibility that the image(s) shown may not be exactly the same as the final product.
The company reserves the right to modify product specifications without prior notice and assumes no responsibility for any
error which may appear in this publication.
All brand names, logo and registered trademarks are properties of their respective owners.
Copyright 2017 Austin Hughes Electronics Ltd. All rights reserved.
Distributor by country on application
InfraPower-W-EURO-230V-SinglePhase-Q117V1