- No category
advertisement
AL400ULXB2
UL Recognized Power Supply/Charger
Overview:
The AL400ULXB2 is a power supply/charger that converts a 115VAC 60Hz input into a Class 2 Rated power-limited
12VDC or 24VDC output (see specifications).
Specifications:
Agency Listings:
• UL Recognized component for: Access Control
System Units (UL 294), Power Supplies for use with
Burglar-Alarm Systems (UL 603), Hospital Signaling
and Nurse Call Equipment (UL 1069), Power Supplies
for Fire Protective Signaling Systems (UL 1481).
Input Rating:
• Input 115VAC 60Hz, 3.5A.
Output Rating:
• Class 2 Rated power-limited output.
• 12VDC or 24VDC selectable output.
• 12VDC @ 4A or 24VDC @ 3A continuous
supply current.
• Filtered and electronically regulated output.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 0.7A.
• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when switched over to battery backup.
Visual Indicators:
• AC input, DC output and Battery LED indicators.
Supervision:
• AC fail supervision (form “C” contacts).
• Low battery and battery presence supervision
(form “C” contacts).
Additional Features:
• Short circuit and thermal overload protection.
Board Dimensions (W x L x H approximate):
4.5” x 7.1” x 1.44” (114mm x 180mm x 37mm)
Power Supply Voltage Output Selections:
Fig. 1
Output Switch Position OFF - 24V
ON - 12V SW1
12VDC SW1 - ON (Fig. 1, on right)
24VDC SW1 - OFF (Fig. 1, on right)
Output
12VDC / 40AH Battery
24VDC / 12AH Battery
Stand-by Specifications:
4 hr. of Stand-by and
5 Minutes of Alarm
Stand-by = 4.0A
Alarm = 4.0A
--------
Stand-by = 3.0A
Alarm = 3.0A
24 hr. of Stand-by and
5 Minutes of Alarm
Stand-by = 1.0A
Alarm = 4.0A
Stand-by = 200mA
Alarm = 3.0A
Stand-by = 1.0A
Alarm = 3.0A
60 hr. of Stand-by and
5 Minutes of Alarm
Stand-by = 300mA
Alarm = 4.0A
--------
24VDC / 40AH Battery
J1
Stand-by = 300mA
Alarm = 3.0A
Installation Instructions:
The AL400ULXB2 should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 as well as all applicable Local Codes.
1. Mount the AL400ULXB2 in the desired location/enclosure.
Replace Fuses
15A 250V
2. Set the AL400ULXB2 to the desired DC output voltage by setting SW1 (Fig. 2, pg. 2) to the appropriate position
(refer to Power Supply Voltage Output Selections chart).
3. Connect AC power (115VAC 60Hz) to the terminals marked [L, G, N] (Fig. 2, pg. 2). Use 18 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power-limited circuits
(AC Fail/Low Battery reporting).
Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
4. Connect devices to be powered to the terminals marked [+ DC –] (Fig. 2, pg. 2).
5. Measure output voltage before connecting devices. This helps avoiding potential damage.
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
Connect battery to the terminals marked [+ BAT –] (Fig. 2, pg. 2). Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included).
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 2, pg. 2) supervisory relay outputs.
Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be utilized to visually indicate that AC power is on. To delay report for 6 hours cut “AC Delay” jumper (Fig. 2a, pg. 2).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(refer to Power Supply Voltage Output Specifications chart).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at the battery terminal and at the board terminals marked [+ BAT –] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharge is 0.7A.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.
Red (DC)
ON
ON
OFF
OFF
LED Diagnostics:
Green (AC) Power Supply Status
ON
OFF
Normal operating condition.
Loss of AC. Stand-by battery supplying power.
ON
OFF
No DC output.
Loss of AC. Discharged or no stand-by battery. No DC output.
Red (Bat)
ON
OFF
Battery Status
Normal operating condition.
Battery fail/low battery.
Terminal Identification:
Terminal Legend Function/Description
L, G, N
+ DC ---
Connect 115VAC 60 Hz to these terminals: L to hot, N to Neutral, G to ground.
12VDC @ 4A or 24VDC @ 3A continuous power-limited output.
AC Fail
NC, C, NO
OFF - 24V
ON - 12V
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. AC or brownout fail is reported within 1 minute of event. To delay reporting of up to 6 hrs., cut “AC delay” jumper and reset power to unit.
Bat Fail
NC, C, NO
+ BAT ---
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 28VDC.
Stand-by battery connections. Maximum charge current 0.7A.
SW1
Fig. 2
OFF - 24V
ON - 12V
SW1
J1
5A 250V
15A 250V
Risk of Fire,
Replace Fuses
As Marked
N
Risk of Fire,
Replace Fuses
As Marked
AC DC Bat
Bat Fail
AC DC Bat
NC C NO NC C NO AC Fail
L G
Altronix is not responsible for any typographical errors.
N
NC C NO NC C NO
IIAL400ULXB2 - Rev. 101112 E16P
AC Fail
Fig. 2a
J1
15A 250V
MEMBER
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project