Eaton EGSX 50L12, 50L12R, 100A, 100NSEA, 100L24RA, 150NSEA, 200A, 200NSEA, 400NSEA, EGSU 100ACA, 100NSEACA, 100L24RACA, 150NSEACA, 200ACA, 200NSEACA, 400NSEACA, ATC, ATV, ATH Generator Sizing guide

Eaton EGSX 50L12, 50L12R, 100A, 100NSEA, 100L24RA, 150NSEA, 200A, 200NSEA, 400NSEA, EGSU 100ACA, 100NSEACA, 100L24RACA, 150NSEACA, 200ACA, 200NSEACA, 400NSEACA, ATC, ATV, ATH Generator Sizing guide
Add to My manuals

Below you will find brief information for Generator EGSX 50L12, Generator EGSX 50L12R, Generator EGSX 100A, Generator EGSX 100NSEA, Generator EGSX 100L24RA, Generator EGSU 100ACA, Generator EGSU 100NSEACA, Generator EGSU 100L24RACA, Generator EGSX 150NSEA, Generator EGSU 150NSEACA.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Eaton Generator Sizing Guide - EGSX50L12, EGSX50L12R,  EGSX100A, EGSX100NSEA | Manualzz

Technical Data TD00405018E

Effective April 2017

Supersedes August 2009

Generator sizing guide

Contents

Description Page

Table 1. Motor load reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Table 2. Non-motor load reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Table 3. Surge capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Table 4. Fuel pipe sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Table 5. LP vapor (LPV) tank sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

UPS—generator compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Table 6. Online estimating sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

On-site estimating sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Typical single-phase generator/transfer switch combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

NEC (700, 701, 702) comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Electrical formulas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Weights and measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Technical Data TD00405018E

Effective April 2017

Generator sizing guide

Important notice

This booklet is designed to familiarize estimators and installers with proper sizing guidelines for residential and commercial generators.

The information is not comprehensive, nor does it replace or supersede any material contained in any of the written documents shipped with the equipment. This booklet should only be used in conjunction with the Owner’s Manual, Installation Manual, and other technical documents shipped with each product. Always read all accompanying documentation carefully before attempting to install any generator, transfer switch, or related equipment.

How to use this booklet

Within this booklet, you will find electrical load information, plus an outline of generator surge capability, fuel pipe sizing, liquid propane tank sizing, and UPS/generator compatibility. The worksheet pages can be removed from the book and photocopied to create additional

On-site Estimating Sheets for use with individual jobs.

Safety information

Proper sizing of the generator is crucial to the success of any installation and requires a good working knowledge of electricity and its characteristics, as well as the varying requirements of the electrical equipment comprising the load. When analyzing the electrical load, consult the manufacturer’s nameplate on each major appliance or piece of equipment to determine its starting and running requirements in terms of watts, amps, and voltage.

When choosing the generator output for commercial or industrial applications, select a rating that is approximately 20 to 25% higher than the peak load (for example, if the load is about 40 kilowatts, select a 50 kW genset). A higher rated generator will operate comfortably at approximately 80% of its full capacity and will provide a margin of flexibility if the load increases in the future.

For safety reasons, Eaton recommends that the backup power system be installed, serviced, and repaired by an Eaton Authorized Service

Dealer or a competent, qualified electrician or installation technician who is familiar with applicable codes, standards, and regulations.

It is essential to comply with all regulations established by the

Occupational Safety & Health Administration (OSHA) and strict adherence to all local, state, and national codes is mandatory.

Before selecting a generator, check for municipal ordinances that may dictate requirements regarding placement of the unit (setback from building and/or lot line), electrical wiring, gas piping, fuel storage

(for liquid propane or diesel tanks), sound and exhaust emissions.

If you have a technical question regarding sizing or installation, contact EatonCare’s Technical Resource Center toll free at

1-877-386-2273, option 2 during normal business hours

(8 a.m. to 4 p.m. CST).

2

EATON www.eaton.com

Generator sizing guide Technical Data TD00405018E

Effective April 2017

Table 1. Motor load reference

ac and heat pumps

Description

1 ton (12,000 BTU)

2 ton (24,000 BTU)

3 ton (36,000 BTU)

4 ton (48,000 BTU)

5 ton (60,000 BTU)

hp

1

2

3

4

5

7.5 ton (85,000 BTU) 7.5

10 ton (120,000 BTU) a

5 (x2)

10 ton (120,000 BTU) 10

15 ton (180,000 BTU) a

7.5 (x2) 15

15 ton (180,000 BTU) 15 15

20 ton (240,000 BTU) a

10 (x2) 20

7.5

10

10

3

4

5

1

2

Running load

Single-phase Three-phase

Running kW

Amps at

240 V

Amps at

208 V

Amps at

240 V

5

10

3

7

3

6

15

20

25

37

49

49

74

74

98

10

13

16

24

33

33

49

49

65

8

11

14

21

28

28

42

42

57

20 ton (240,000 BTU)

25 ton (300,000 BTU)

20

25

30 ton (360,000 BTU)

a

15 (x2)

30 ton (360,000 BTU) 30

40 ton (480,000 BTU) a

20 (x2)

40 ton (480,000 BTU) 40

50 ton (480,000 BTU)

a

25 (x2)

50 ton (480,000 BTU)

General residential

50

20

25

30

30

40

40

50

50

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

65

82

98

98

131

131

163

163

57

71

85

85

113

113

142

142

Single-phase

Running kW

0.5

Amps at 120 V

4.9

4.9 amps at 240 V

2.5

Description

Refrigerator pump, sump, furnace, garage opener

hp

0.5

Freezer, washer, septic grinder

0.75

General 1 hp 1

Well and septic lift pump 2

0.75

1

2

7.4

9.8

19.6

3.7

4.9

9.8

a

For multiple motor configurations, sequence starting is assumed.

28

35

42

21

21

28

42

57

57

71

71

11

14

14

4

6

7

1

3

Amps at

480 V

219

375

250

500

625

375

750

500

1000

625

1250

100

117

145

219

145

250

Starting load

Single-phase Three-phase

LR amps at 240 V

LR amps at 208 V

LR amps at 240 V

33

67

22

44

19

38

67

78

97

146

97

167

58

67

84

126

84

144

146

250

167

333

416

250

500

333

666

416

833

126

217

144

289

361

217

433

289

577

361

722

63

108

72

144

180

108

217

144

289

180

361

63

42

72

29

34

42

LR amps at 480 V

10

19

17

30

20

17

12.5

20

kW

2.5

5

7.5

10

12.5

40

50

30

60

40

80

50

100

Single-phase

LR amps at 240 V

13

19

25

50

LR amps at 120 V

25

38

50

100

kW

1.5

2.3

3

6

m CAUTION

DO NOT SIZE THE GENERATOR BASED ON STARTING KW ALONE.YOU

MUST COMPARE LR AMPS TO GENERATOR SURGE CAPABILITY (TABLE 3).

SIZE THE GENERATOR BY FOLLOWING THE SIZING INSTRUCTIONS.

EATON www.eaton.com

3

Technical Data TD00405018E

Effective April 2017

Table 2. Non-motor load reference

Residential

Description

Running load a

Single-phase

Running kW

Amps at

120 V

Amps at

240 V

Electric heat per 1000 ft

2

Heat pump elements per 1000 ft 2

Dryer

Hot tub

Range oven/stove top per burner

Hot water

General lighting and receptacles per 1000 ft

2

12

7

5.5

10

8

4.5

3

N/A

N/A

N/A

N/A

N/A

N/A

24.9

50

29

23

50

30

19

N/A

Blow dryer

Dishwasher

Microwave

Toasters

1.25

1.5

1

1

10.4

12.5

8.3

8.3

N/A

N/A

N/A

N/A

Home entertainment center

Computer

Kitchen

1

1

8.3

8.3

N/A

N/A

Laundry

Commercial

1.5

1.5

12.5

12.5

N/A

N/A

Please refer to equipment data plate and/or billing history for commercial details.

a

Always check data plate for actual running amps.

Generator sizing guide

4

EATON www.eaton.com

Generator sizing guide Technical Data TD00405018E

Effective April 2017

35

45

60

70

80

100

150

17

18

20

25

30

8

10

13

14

16

35

36

40

22

25

27

30

45

48

70

80

Table 3. Surge capability

Generators (operating at less than 3600 RPM)

Rated output (running amps)

Size (kW)

Single-phase

240 V 208 V

Three-phase

240 V 480 V

7

92

104

113

125

146

150

167

188

200

292

333

29

76

87

94

104

121

125

139

156

167

243

278

N/A

N/A

75

81

90

105

108

120

135

144

210

240

100

130

417

542

347

451

Generators (operating at 3600 RPM)

300

390

N/A

52

54

60

N/A

38

41

45

68

72

105

120

150

195

N/A

33

42

54

58

67

71

75

83

104

125

146

188

250

292

333

417

625

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

87

104

121

156

208

243

278

347

520

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

75

90

105

135

180

210

240

300

451

N/A

N/A

N/A

38

45

N/A

N/A

N/A

N/A

N/A

52

68

90

105

120

150

226

Commercial (LR amps at 15% voltage dip)

Single-phase Three-phase

240 V 208 V 240 V 480 V

71

71

100

100

113

113

129

146

163

275

275

369

546

113

146

179

275

275

369

63

67

73

71

100

558

23

26

31

48

52

59

48

48

67

67

75

75

86

98

109

164

183

222

364

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

48

67

75

98

120

164

183

222

372

N/A

46

58

65

60

65

75

94

94

159

159

214

315

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

46

60

60

94

103

142

158

214

322

43

44

49

N/A

30

33

43

57

57

95

106

128

209

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

30

43

43

57

69

95

106

128

215

Residential (LR amps at 30% voltage dip)

Single-phase Three-phase

240 V 208 V 240 V 480 V

134

138

153

205

225

225

254

292

321

550

550

738

1088

46

51

63

95

102

117

125

133

145

138

205

225

292

350

550

550

738

1121

92

92

137

137

150

151

169

195

214

330

366

441

724

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

92

137

150

195

234

330

366

441

747

N/A

91

118

130

118

131

147

168

185

318

318

426

628

118

168

204

286

318

426

N/A

N/A

N/A

91

130

647

N/A

N/A

N/A

N/A

N/A

N/A

87

87

97

N/A

59

64

87

112

112

190

212

255

419

87

112

136

190

212

255

N/A

N/A

N/A

60

87

431

N/A

N/A

N/A

N/A

N/A

N/A

N otee:

All nominal ratings based upon LP fuel. Refer to specification sheet for NG ratings and deration adjustments for ambient temperature and altitude.

EATON www.eaton.com

5

Technical Data TD00405018E

Effective April 2017

70

80

100

130

150

20

22

25

27

30

Table 4. Fuel pipe sizing

Natural gas (values are maximum pipe run in ft) kW Pipe size (in inches)

0.75

1 1.25

7–8

10

55

20

200

85

820

370

10

22

25

27

13–14

16–17

20

50

40

20

15

10

245

190

130

115

95

85

45

48

50

30

35–36

40

60

35

25

15

60

70

80

100

130

150

LP vapor (values are maximum pipe run in ft) kW Pipe size (in inches)

0.75

1 1.25

7–8

10

13–14

16–17

165

70

45

25

570

255

170

130

1000

690

540

35–36

40

45

48

50

60

15 115

85

60

55

40

20

15

480

365

275

260

195

125

107

82

70

70

45

20

15

1.5

60

50

30

605

575

435

290

250

195

165

160

115

1.5

60

50

50

147

95

75

25

5

800

545

425

305

260

220

203

2 2.5

3

260

230

220

145

75

65

40

945

799

739

552

565

370

315

2

915

790

650

585

560

390

225

195

140

50

30

2.5

1185

710

630

460

215

150

3

1030

890

725

620

610

445

260

230

165

70

45

1095

660

590

430

205

150

1305

660

490

Generator sizing guide

LP

LPG: 8.55 ft

3

/lb, 4.24 lb/gal,

2500 btu/ft 3

LPG: 36.3 ft

3

= 1 gal

Natural gas

1 cubic foot = 1,000 BTU

1 therm = 100,000 BTU

Gas consumption = 13,000–

16,000 BTU per kW/hr

Pressure

1 inch mercury = 13.61 inches water column

1 inch water column =

0.036 psi

5–14 inches water column =

0.18 psi to 0.50 psi

Notee:

Pipe sizing is based on 0.5 in

H

2

O pressure drop

Sizing includes a nominal number of elbows and tees

Please verify adequate service and meter sizing

6

EATON www.eaton.com

Generator sizing guide Technical Data TD00405018E

Effective April 2017

Table 5. LP vapor (LPV) tank sizing

Vapor withdrawal (dimensions are given in inches)

Tank capacity total (gal)

Tank capacity useable (gal)

Minimum temp (°F)

120 72

150

250

325

500

850

1000

90

150

195

300

510

600

40

20

0

40

20

0

40

20

0

40

20

0

40

20

0

40

20

0

40

20

0

90

100

110

120

130

140

150

200

300

50

60

70

80

30

35

40

Load (kW)

5

10

15

20

25

BTU/hr

110,000

176,400

231,800

267,100

352,800

418,300

467,400

550,000

675,000

836,600

1,035,700

1,170,000

1,200,000

1,280,000

1,550,000

1,675,000

1,800,000

1,925,000

2,050,000

2,800,000

4,100,000

LP gal/hr

1.2

2

2.5

2.8

3.8

4.5

5.1

6.1

7.5

9

11

12.7

13

13.8

17.1

18.5

19.5

21.3

22.7

30.9

45.3

NG ft

3

/hr

110

156

220

262

316

417

485

550

675

862

1,020

1,154

1,200

1,260

1,550

1,675

1,786

1,925

2,050

2,800

4,100

N otee:

Operating cost per hour = NG therms/hr x cost of NG therms.

12.0

12.6

15.5

16.7

17.8

19.2

20.5

28.0

49.0

4.2

4.8

5.5

6.7

8.6

10.2

11.5

NG therms/hr

1.1

1.6

2.2

2.6

3.2

Tank capacity

(btu/hr)

246,240

164,160

82,080

293,760

195,840

97,920

507,600

338,400

169,200

642,600

428,400

214,200

792,540

528,360

264,180

1,217,700

811,800

405,900

1,416,960

944,640

472,320

Length

57

68

94

119

119

165

192

Diameter

24

24

30

30

37

41

41

Overall height

33

33

39

39

46

50

50

Gas required for common appliances

Appliance

Warm air furnace

  Single family

  Multifamily, per unit

Hydronic boiler, space heating

  Single family

  Multifamily, per unit

Hydronic boiler, space and water heating

  Single family

  Multifamily, per unit

Range, free standing, domestic

Built-in oven or broiler unit, domestic

Built-in top unit, domestic

Water heater, automatic storage, 30 to 40 gal. tank

Water heater, automatic storage, 50 gal. tank

Water healer, automatic storage, instantaneous

  2 gpm

  4 gpm

  6 gpm

Water heater, domestic, circulating or side-arm

Refrigerator

Clothes dryer, Type 1 (domestic)

Gas fireplace direct vent

Gas log

Barbecue

Gas light

Incinerator, domestic

Approximate input (btu/hr)

100,000

60,000

100,000

60,000

120,000

75,000

65,000

25,000

40,000

35,000

50,000

142,800

285,000

428,000

35,000

3,000

35,000

40,000

80,000

40,000

2,500

35,000

N otee:

Tank BTU capacity and generator run times based upon maintaining a minimum tank fuel level of 20%. Tanks are typically filled to 80% full. Typical fuel consumption based on a generator 100% loaded.

EATON www.eaton.com

7

Technical Data TD00405018E

Effective April 2017

Generator sizing guide

UPS—generator compatibility

Passive (also referenced as standby or offline) and line-interactive

These technologies are most common for personal workstations and point-of-sale applications. They are typically single-phase equipment with size ranges of 350–2000 VA for passive and

500 VA to 5000 VA for line-interactive.

Passive UPSs are the simplest type. Under normal conditions, ac power passes straight through to the UPS load. When the input power supply goes outside of specifications, the UPS transfers the load from input power to the internal dc to ac power inverter.

Passive UPSs do not correct for voltage or frequency deviations under “normal” operation.

Line-interactive is similar to the passive technology except it has circuitry that attempts to correct for standard voltage deviations.

Frequency deviations under “normal” power operation are not corrected.

Equipment notes

These devices tend to be electrically/harmonically very noisy. A single small UPS is not a significant concern, but applications with multiple UPSs can be problematic.

Passive UPS technology typically has normal tolerances of 10–25% on voltage and 3 Hz on frequency. If the input source goes outside of these tolerances, the UPS will switch onto the UPS battery source. Some line-interactive units may have frequency tolerances factory set to 0.5 Hz. These units will need to have their frequency tolerance increased to a minimum of 2 Hz.

Generator sizing recommendation

Limit the total UPS loading to 15%–20% of the generator capacity

Double-conversion

This technology is most common for critical load applications.

Double-conversion UPSs constantly rectify ac to dc and then invert the dc back into ac. This configuration results in an output that corrects for voltage and frequency deviations.

There are single- and three-phase models covering small to large applications. Most UPS applications larger than 5000 VA use doubleconversion technology. This approach is also the preferred technology for generator applications.

Equipment notes

Double-conversion UPSs that are single-phase or unfiltered three-phase models tend to create a significant level of electrical/ harmonic noise. This is illustrated by harmonic current distortions that are greater than 35%. Minuteman UPS products could have current distortion of 8%. When three-phase models are supplied with harmonic filters (current distortion less than 10%), this concern is no longer an issue.

Generator sizing recommendations

Single-phase models: Limit the total UPS loading to 25% of the generator capacity

Single-phase Minuteman UPS models: Limit the total UPS loading to 50% of the generator capacity

Three-phase models without filters (current distortion > 30%):

Limit the UPS loading to 35% of the generator capacity

Three-phase models with filters (current distortion < 10%):

Limit the UPS loading to 80% of the generator capacity

Supplier(s)

Powerware

Minuteman UPS

APC

Liebert

Passive (standby)

3000 series

Enspire

Back-UPS Series

PowerSure PST & PSP

Line-interactive

5000 series

Enterprise Plus

Smart-UPS Series

PowerSure PSA & PSI

Double-conversion

9000 series

Endeavor

Symmetra Series

UPStation & Nfinity

8

EATON www.eaton.com

Generator sizing guide Technical Data TD00405018E

Effective April 2017

Table 6. Online estimating sheet

Contractor: ______________________________________________ Email: ____________________________________

Phone: (___) ________________ Fax: (___) _________________

Job name: __________________________________________________________________________________________

Date: ___ / ___ / __________ Location: _____________________________________________________________

Voltage

Type

Electric service

120/240 1 Ø

Natural gas

100 amp

120/208 3 Ø

LP vapor (LPV)

200 amp

120/240 3 Ø 277/480 3 Ø

400 amp 600 amp Other: _____________

N otee:

Before installation, contact local jurisdiction to confirm all requirements are met. Jurisdictions may vary.

Eaton recommends contacting local authorities prior to installation.

Loadse: Look for heavy building loads such as refrigeration, air conditioning, pumps or UPS systems.

Motor load table (refer to Table 1) Use the following for sizing and determining generator kW.

Device hp RA LRA kW running (= hp) Starting kW

Applications

The QT Series does not meet the necessary requirements for the following applications:

NEC 695 fire pumps

NEC 700 emergency systems

NFPA 20 fire pumps

NFPA 99 healthcare

NFPA 110 emergency systems

Reference codes

Related codes and standards:

NEC 225 branch circuits and feeders

NEC 240 overcurrent protection

NEC 250 grounding

NEC 445 generators

NEC 700 Emergency Systems

NEC 701 legally required standby

NEC 702 optional standby

NFPA 37 installation and use of stationary engines

NFPA 54 national fuel gas code

NFPA 58LP gas code

Starting kW for hp < 7.5 starting kW = hp x 3

Starting kW for hp > 7.5 starting kW = hp x 2

Starting kW for loading with no listed hp, calculate hp based on running amps in the chart on the right

Non-motor load table (refer to Table 2)

Use the following for sizing and determining generator kW.

Device Amps kW

Install notes

Suggested concrete pad minimum thickness of 4 inches with

6 inches overhang on all sides. Composite pad included with air-cooled products

Consult manual for installation recommendations

Consult local authority having jurisdiction for local requirements

Transfer switch availability

Single-phase a

Service Entrance

Non-Service Entrance

Three-phase

Service Entrance

Non-Service Entrance

Amps

100, 200, 400, 600, 800

50, 100, 200, 400, 600, 800

100, 225, 300, 400, 600, 800

100, 200, 300, 400, 600, 800 a

Single-phase ATSs from 100 to 400 amps have intelligent load management standard.

To calculate kW

120 V, single-phase

240 V, single-phase

208 V, three-phase

240 V, three-phase

480 V, three-phase

Amps x 120/1000 = kW

Amps x 240/1000 = kW

(Amps x 208 x 1.732 x PF) /1000 = kW

(Amps x 240 x 1.732 x PF) /1000 = kW

(Amps x 480 x 1.732 x PF) /1000 = kW

Recommended generator size

Refer to “Generator sizing instructions” on other side of this sheet.

EATON www.eaton.com

9

Technical Data TD00405018E

Effective April 2017

Generator sizing guide

On-site estimating sheet

Generator sizing instructions

There is not a single correct sizing solution. Following are several methods that, when mixed with good judgement, should result in an appropriately sized generator. Remember to consider load growth, seasonality, and effects of starting motors.

Always check with the local inspection department to confirm which

NEC code cycle will affect your install.

Never add amps when sizing a generator. Convert amps to kW and add kW to determine the required generator size. Power factors for various motor loads vary widely. Adding amps without properly accounting for the power factor and/or mixing voltages will result in improperly sizing the generator.

When motors start, they create a current surge that step loads the generator and creates a voltage dip. After selecting a generator,

reference the generator’s surge capability using Table 3. Verify

that voltage dip is adequate for the application. Most commercial applications should be limited to about 15% voltage dip and residential applications should be limited to a 30% voltage dip.

Some applications utilize an uninterruptible power supply (UPS) to back up critical loads. Please read sizing guide for this load type.

Measurement method

Use a clamp-on amp meter or power analyzer to measure facility load levels. Clamp each leg separately and take the measurement during peak usage levels.

240 V, single-phase applicationse: To determine peak usage in kW,

add the highest amp readings from the two legs, multiply by 120 and divide by 1000.

(L1 + L2)120 / 1000

Size the generator 10 to 20% larger than the peak measured load.

Three-phase applicationse: Add the peak amp readings from all

three legs and divide by 3 to determine peak amps. Multiply peak amps by volts, multiply the result by 1.732 (square root of 3), and then divide by 1000 to convert amps to kW.

Peak Amps = (L1 + L2 + L3) / 3 kW = [(Peak Amps x Volts) x 1.732] / 1000 a a

Assumes power factor of 1.0

Size the generator 20 to 25% larger than the peak measured load.

Peak Amps = _____________        Peak kW= _____________

Project layout

Billing history method commercial

Many commercial customers have a utility rate structure that has a peak demand charge. Using a year’s worth of electric bills, size the generator 25% larger than the largest peak demand.

Verify motor and UPS load compatibility: Peak Demand = _______

Load summation method

Enter running kW for all motor loads (except the largest) expected

to run during peak load levels into Table 6. Refer to Table 1 for

typical motor load sizes and electrical requirements.

Enter kW for all non-motor loads expected to run during peak load

levels into Table 2. Refer to Table 2 for typical residential loads

and rules of thumb.

Add the running motor load kW, non-motor load kW, and the starting kW of the largest motor load.

Motor load running total (minus largest motor): ____________ kW

(ref. Table 6)

Non-motor load total: (ref. Table 2):

Starting load from largest cycling motor::

(ref. Table 6)

Total electrical loads: =

____________ kW

____________ kW

____________ kW

Select generator: Commercial (add 20 to 25% to total kW)

Residential (add 10 to 20% to total kW)

Confirm that voltage dip is within acceptable limits by comparing

motor LRA to generator surge capability (see Table 3)

Confirm UPS compatibility (see Table 4)

Ball park estimates (do not use for final sizing)

Estimate based on 60% service size: (commercial)

240 V, single-phase: __________   Amps x 0.15 = __________ kW

208 V, three-phase: ___________  Amps x 0.22 = __________ kW

240 V, three-phase: ___________  Amps x 0.25 = __________ kW

480 V, three-phase: ___________  Amps x 0.50 = __________ kW

Estimate based on 40% service size: (residential)

240 V, single-phase: __________   Amps x 0.10 = __________ kW

208 V, three-phase: ___________  Amps x 0.15 = __________ kW

240 V, three-phase: ___________  Amps x 0.17 = __________ kW

480 V, three-phase: ___________  Amps x 0.34 = __________ kW

Estimate based on square footage

Fast food, convenience stores, restaurants, grocery stores

Other commercial applications

Square footage = __________ kW = 50 kW + 10 watts/sq ft kW = 30 kW + 5 watts/sq ft

Estimated kW = __________

Amps to kW rule-of-thumb (assumes .8 pf)

For 480 V

For 208 V

  Amps = kW x 1.5

  Amps = kW x 3.5

For 240 V, three-phase systems   Amps = kW x 3

For 240 V, single-phase systems   Amps = kW x 4

10

EATON www.eaton.com

Generator sizing guide

Typical single-phase generator/transfer switch combinations

Air-cooled generators kW Transfer switch

9

11

16

20

EGSX50L12

EGSX50L12R

EGSX100A

EGSX100NSEA

EGSX100L24RA

EGSU100ACA

EGSU100NSEACA

EGSU100L24RACA

EGSX50L12

EGSX50L12R

EGSX100A

EGSX100NSEA

EGSX100L24RA

EGSU100ACA

EGSU100NSEACA

EGSU100L24RACA

EGSX100A

EGSX100NSEA

EGSX100L24RA

EGSX150NSEA

EGSU100ACA

EGSU100NSEACA

EGSU100L24RACA

EGSU150NSEACA

EGSU200ACA

EGSU200NSEACA

EGSX150NSEA

EGSX200A

EGSX200NSEA

EGSU150NSEACA

EGSU200ACA

EGSU200NSEACA

22

25

27

EGSX150NSEA

EGSX200A

EGSX200NSEA

EGSU150NSEACA

EGSU200ACA

EGSU200NSEACA

EGSX150NSEA

EGSX200A

EGSX200NSEA

EGSX400NSEA

EGSU150NSEACA

EGSU200ACA

EGSU200NSEACA

EGSU400NSEACA

30 EGSX150NSEA

EGSX200A

EGSX200NSEA

EGSX400NSEA

EGSU150NSEACA

EGSU200ACA

EGSU200NSEACA

EGSU400NSEACA

70–150 ATC, ATV and ATH switches EGSX150NSEA

EGSX200A

EGSX200NSEA

EGSX400NSEA

EGSU150NSEACA

EGSU200ACA

EGSU200NSEACA

EGSU400NSEACA

Liquid-cooled generators kW Transfer switch

22 EGSX150NSEA

EGSX200A

EGSX200NSEA

EGSU150NSEACA

EGSU200ACA

EGSU200NSEACA

Technical Data TD00405018E

Effective April 2017

EATON www.eaton.com

11

Technical Data TD00405018E

Effective April 2017

Generator sizing guide

NEC (700, 701, 702) comparison

NEC Comparison Table to be used as a general guideline in determining the proper generator for specific applications.

Refer to architectural documents for final selection.

Scope

Article 700 emergency

Legally required life safety

For emergency / (UL 2200)

Article 701 standby

Legally required critical support

(fire fighting, health hazards, etc)

For intended use / (UL 2200)

Article 702 optional standby

Protect property and facilities

For intended use / (UL 2200) / Not in 2008 Equipment approval

Testing

Witness testing (on-sight)

Periodic testing

Battery maintenance

Maintenance records

Load testing

Capacity

At install and periodically

Yes

Yes

Yes

Yes

All loads

Yes with load shedding

Yes

At install

Yes

Yes

Yes

Yes

None

None

None

None

None

All loads intended to operate at one time All loads intended to operate at one time

Not in 2008

Yes with load shedding

Yes

2008—yes with load shedding

Yes

Other standby loads allowed

Peak shaving allowed

Transfer switch

Automatic

Equipment approval

Means to permit bypass

Elect. operated—mech. held

Other loads

Max. fault current capable

Signals (audible and visual)

Derangement

Carrying load

Battery charger failed

Ground fault indication

NFPA 110 signaling

Signs

At service

At neutral to ground bonding

Wiring kept independent

Fire protection (ref 700-9d)

Maximum power outage

Retransfer delay

Automatic starting

On-site fuel requirements

Battery charger

Ground fault

Yes

For emergency / (UL 1008)

Yes

Yes

No

Yes

Yes / standard common alarm

Yes / displayed at ATS

Yes

Yes (480 V and 1000 A)

Yes / optional annunciator

Yes / type and location

Yes (if remote)

Yes

Yes (1000 persons or 75 ft building)

10 sec

15 min. setting

Yes

2 hours (see NFPA 110)

Yes

Indication only

Yes

For standby / (UL 1008)

No

No

Yes with load shedding

Yes

Yes / standard common alarm

Yes / displayed at ATS

Yes

No

Yes / optional annunciator

Yes / type and location

Yes (if remote)

No

No

60 sec

15 min. setting

Yes

2 hours

Yes

No

No

For intended use / (UL 1008)

No

No

N/A

Yes

Yes / standard common alarm

Yes / displayed at ATS

No

No

No

Yes / type and location

Yes (if remote)

No

No

N/A

No

No

None

No

No

12

EATON www.eaton.com

Generator sizing guide

Electrical formulas

To find:

KILOWATTS (kW)

KVA

AMPERES

WATTS

NO. OF ROTOR POLES

FREQUENCY

RPM kW (required for motor)

RESISTANCE

VOLTS

AMPERES

E = VOLTS

I = AMPERES

R = RESISTANCE (OHMS)

PF = POWER FACTOR

Known values

Volts, current, power factor

Volts, current kW, volts, power factor

Volts, amps, power factor

Frequency, RPM

RPM, no. of rotor poles

Frequency, no. of rotor poles

Motor horsepower, efficiency

Volts, amperes

Ohms, amperes

Ohms, volts

Single-phase

E x I

1000

E x I

1000 kW x 1000

E

Volts x amps

2 x 60 x frequency

RPM

I

E

I x R

E

R

RPM x poles

2 x 60

2 x 60 x frequency

Rotor poles hp x 0.746

Efficiency

Technical Data TD00405018E

Effective April 2017

Three-phase

E x I x 1.73 x PF

1000

E x I x 1.73

1000 kW x 1000

E x 1.73 x PF

E x I x 1.73 x PF

2 x 60 x frequency

RPM

I

E

I x R

E

R

RPM x poles

2 x 60

2 x 60 x frequency

Rotor poles hp x 0.746

Efficiency

EATON www.eaton.com

13

Technical Data TD00405018E

Effective April 2017

Weights and measures

U.S. weights and measures

Linear measurements

12 inches

3 feet

5.5 yards

=

=

=

1 inch

1 foot

1 yard

1 rod

40 rods

8 furlongs

=

=

Mile measurements

1 Statute =

1 Scots =

1 Irish =

1 furlong =

1 mile =

5,280 feet

5,952 feet

6,720 feet

=

=

=

=

1 Russian

1 Italian

=

=

3,504 feet

4,401 feet

1 Spanish = 15,084 feet

Other linear measurements

1 hand

1 span

1 chain

=

=

=

4 inches

9 inches

22 yards

2.540 centimeters

3.048 decimeters

9.144 decimeters

5.029 meters

2.018 hectometers

1.609 kilometers

1 link =

1 fathom =

1 furlong =

1 cable =

Square measurements

144 square inches

9 square feet

30

1/4 yards

40 rods

4 roods

640 acres

1 square mile

36 sections

Cubic or solid measure

1 cu foot

1 cu yard

1 cu foot

1 gallon (water)

1 gallon (U.S.)

1 gallon (Imperial)

=

=

=

=

=

=

=

=

=

=

=

=

=

=

1 square foot

1 square yard

1 square rod

1 rood

1 acre

1 square mile

1 section

1 township

1728 cu inches

27 cu feet

7.48 gallons

8.34 lb

231 cu inches of water

277

1/4

cu inches or water

7.92 inches

6 feet

10 chains

608 feet

Generator sizing guide

Metric system

Cube measure (The unit is the meter = 39.37 inches)

1 cu centimeter

1 cu decimeter

=

=

1000 cu millimeters

1000 cu centimeters

1 cu meter = 1000 cu decimeters

= 1 steer

1 cu centimeter (water) = 1 gram

=

=

=

=

0.06102 cu inches

61.02374 cu inches

35.31467 cu feet

1.30795 cu yards

1000 cu centimeter

(water)

= 1 liter

1 cu meter (1000 liters) = 1 metric ton

Measures of weight (The unit is the gram = 0.035274 ounces)

1 milligram = 0.015432 grains

= 1 kilogram

1 centigram

1 decigram

1 gram

1 dekagram

1 hectogram

1 kilogram

1 myriagram

=

=

=

10 milligrams

= 10 centigrams

= 10 decigrams

10 grains

= 10 dekagrams

= 10 hectograms

10 kilograms

= 0.15432 grains

= 1.5432 grains

= 15.4323 grains

= 5.6438 drams

= 3.5274 ounces

= 2.2046223 pounds

= 22.046223 pounds

1 quintal

1 metric ton

= 10 myriagrams

= 10 quintal

= 1.986412 cwt.

= 2,2045.622 pounds

1 gram

1 dram

1 metric ton

= 0.056438 drams

= 1.77186 grams

27.3438 grains

= 2,204.6223 pounds

Measures of capacity (The unit is the liter = 1.0567 liquid quarts)

1 centiliter

1 deciliter

1 liter

1 dekaliter

1 hectoliter

1 kiloliter

=

=

=

=

=

=

10 milliliters

10 centiliters

10 deciliters

10 liters

10 dekaliters

10 hectoliters

=

=

=

=

=

=

0.338 fluid ounces

3.38 fluid ounces

33.8 fluid ounces

0.284 bushel

2.84 bushels

264.2 gallons

N otee:

14

EATON www.eaton.com

Generator sizing guide

Weights and measures, continued

Metric system

Prefixes

a. mega b. kilo c. hecto

= 1,000,000

= 1,000

= 100 e. deci f. centi g. milli

= 0.1

= 0.01

= 0.001

d. deka = 10 h. micro = 0.000001

Linear measurement (the unit is the meter = 39.37 inches)

1 centimeter

1 decimeter

1 meter

=

=

=

10 millimeters

10 centimeters

10 decimeters

= 0.3937011 inches

= 3.9370113 inches

= 1.0936143 yards

3.2808429 feet

= 10.936143 yards 1 dekameter

1 hectometer

1 kilometer

1 myriameter

= 10 meters

= 10 dekameters

= 10 hectometers

= 10,000 meters

=

=

109.36143 yards

0.62137 mile

Square measurement (the unit is the square meter = 1549.9969 square inches)

1 sq centimeter = 100 sq millimeters = 0.1550 sq inches

1 sq decimeter

1 sq meter

=

=

100 sq centimeters

100 sq decimeters

=

=

15.550 sq inches

10.7639 sq feet

= 119.60 sq yards 1 sq dekameter = 100 sq meters

1 sq hectometer = 100 sq dekameters

1 sq kilometer = 100 sq hectometers

(The unit is the “are” = 100 square meters)

1 centiare

1 deciare

1 are

1 dekare

1 hektare

1 sq kilometer

= 10 milliares

= 10 centiares

= 10 deciares

= 10 ares

= 10 dekares

= 100 hektares

= 10.7643 sq feet

= 11.96033 sq yards

= 119.6033 sq yards

= 0.247110 acres

= 2.471098 acres

= 0.38611 sq mile

Cubic measure (the unit is the “stere” = 61,025.38659 cubic inches)

1 decistere = 10 centisteres = 3.531562 cubic inches

1 stere

1 dekastere

=

=

10 decisteres

10 steres

=

=

1.307986 cubic yards

13.07986 cubic yards

Technical Data TD00405018E

Effective April 2017

Metric designator and trade sizes

Metric designator

12 16

Grade size

27 35 41 53 63 78 91 103 129 155

3/8 1/2 1 1

1/4

1

1/2

2 2

1/2

3 3

1/2

4 5 6

U.S. weights and measures / metric equivalent chart

1 inch = 1

1 foot =

1 yard =

1 cm =

12

36

.3937

1

3

1 mile = 63,360 5,280

.333

1

1,760

1 mm = .03937

.0032808 1.0936 x

10-3

1.894 x

10-4

5.6818 x

10-4

1

6.2137 x

10-7

.0328084 .0109361 6.2137 x

10-6

304.8

914.4

1,609,344 160,934.4 1,690.344 1.609344

1

10

30.48

91.44

0.1

1

.3048

.9144

0.001

0.01

3.048 x

10-4

9.144 x

10-4

0.000001

0.00001

1 m =

1 km =

In

39.37

Ft

.0833

Yd

.0278

Mile

1.578 x

10-5

3.28084 1.09361 6.2137 x

10-4

mm

25.4

1000

cm

2.54

100

m

.0254

1

39,370 3,280.84 1,093.61 0.62137 1,000,000 100,000 1,000

km

2.54 x

10-5

0.001

1

Scientific notation

A way of expressing very large or very small numbers in a more compact format. Any number can be expressed as a number between 1 and 10, multiplied by a power of 10 (which indicates the correct position of the decimal point in the original number).

Numbers greater than 10 have positive powers of 10, and numbers less than 1 have negative powers of 10.

Useful conversions / equivalents

1 BTU

1 gram calorie

1 circular mil

1 sq mil

1 mil

Raises 1 lb of water 1 °F

Raises 1 gram of water 1 °C

= 0.7854 sq mil

= 1.27 cir mils

= 0.001

Generator and transfer switch products are supported by an unparalleled service network and sales force.

24-hour support 7 days a week

For pre-sale support, contact Eaton’s Technical Resource Center at 1-877-ETN-CARE

For installation and technical support, contact Eaton’s Aftermarket

Support team at 1-800-975-8331

Eaton generator and transfer switch products are backed by competitive warranties

For additional information or to place an order, contact your local

Eaton representative or visit us at httpe://generators.eaton.com

EATON www.eaton.com

15

Technical Data TD00405018E

Effective April 2017

Generator sizing guide

Eaton

1000 Eaton Boulevard

Cleveland, OH 44122

United States

Eaton.com

© 2017 Eaton

All Rights Reserved

Printed in USA

Publication No. TD00405018E / Z19452

April 2017

For additional information or to place an order, contact your local Eaton representative or visit us at

http://generators.eaton.com

Eaton is a registered trademark.

All other trademarks are property of their respective owners.

advertisement

Key Features

  • Surge capability
  • Fuel pipe sizing
  • Liquid propane tank sizing
  • UPS-generator compatibility
  • Online estimating sheet
  • On-site estimating sheet
  • NEC (700, 701, 702) comparison
  • Electrical formulas
  • Weights and measures

Frequently Answers and Questions

What is the maximum pipe run for a 10 kW generator with natural gas?
The maximum pipe run for a 10 kW generator with natural gas is 255 feet.
What is the surge capability of a 25 kW generator?
The surge capability of a 25 kW generator is 75 running amps at 240 volts, 38 running amps at 208 volts, 38 running amps at 240 volts and 46 running amps at 480 volts.
How do I size a generator for a commercial application?
For commercial applications, size the generator 20 to 25% larger than the peak load. For residential applications, size the generator 10 to 20% larger than the peak load.
What is the difference between NEC 700 and NEC 702?
NEC 700 covers legally required life safety systems, while NEC 702 covers optional standby systems. NEC 700 requires witness testing at installation and periodically, while NEC 702 does not. NEC 700 requires battery maintenance and maintenance records, while NEC 702 does not. NEC 700 requires load testing, while NEC 702 does not.
What is the maximum power outage for a legally required emergency system?
The maximum power outage for a legally required emergency system is 10 seconds.

Related manuals