SSV7RRT INSTRUCTIONS
INSTALLATION INSTRUCTIONS
CONTROLLER MOUNTING:
Find a suitable location to mount the control box. Ideally, as with all pool equipment it should be installed out of direct weather and no closer than 3m from the waters edge. Lift up the two mounting tabs and use two appropriate screws to mount the control box to the wall, keeping in mind that the power cable is 1.9m long and should be plugged directly into a general power outlet, not into extension leads.
All units should be plugged into an appropriate power out.
POOL SENSOR:
For retro-fit systems the pool sensor must be fitted in the suction line of the main filter pump or between the outlet of the filter and the ‘T’ fitting before the solar boost pump. It is recommended that a
14.5mm hole be drilled in the PVC pipe; this can be carried out using a 14.5mm drill-bit spinning in a counter clockwise direction to minimise the chance of shattering pipe. The sensor plug is to be fitted to the left hand socket.
SSV7RRT REMOTE (ROOF) SENSOR:
As the unit operates in a UHF radio band, reflections and moving objects can cause a transmission to be corrupted with a subsequent indication “MISSED RECEPTION” on the display. Up to 10 transmissions can be missed before pump action will occur and the solar pump will turn off. If this occurs, and if the solar conditions are still favourable, the solar pump will not turn on again and resume normal operation unless it has received a valid transmission.
The remote roof transceiver obtains its operating power from a solar panel, it will not operate if there is no sun or if there is significant cloud cover. Obviously solar heating would not occur in such conditions.
Due to the possibility of reception ghosting and electrical interference the transmitter may be required to be moved to an alternative position, this may be as little as two meters and keep in mind that the roof sensor cable may be extended 20 meters if required. The main controller should be mounted away from other electrical appliances as far as possible to reduce the chance of interference. If the unit is to be installed in a metal shed there may be reception issues and the controller may need to be optioned with a remote antenna or moved outside.
A power substitute cable is supplied for installation testing on cloudy days - simply clip a 9Volt
Transistor Battery onto the Battery Snap supplied and substitute the left hand green plug marked PV.
Remember to refit original plug when testing is over.
OPERATING INSTRUCTIONS
SETTINGS MENU
To enter the SETTINGS MENU push either the UP or DOWN buttons and the following will be displayed;
SETTINGS MENU
1) MANUAL MODE
Use UP/DOWN buttons to scroll to the option you wish to change. Press the ENTER button to select the currently displayed menu item.
All menu items are shown below;
SETTINGS MENU
1) MANUAL MODE
2) FILTER TIMER
3) TEMPERATURE
4) HEAT DEMAND
5) MODE
6) CLOCK
7) SAVE & EXIT
1) MANUAL MODE
MANUAL PUMP MODE
UP=ON DOWN=OFF
MANUAL MODE allows you to manually set the aux pump to ‘on’ by pressing the UP button or ‘off’ by pressing the DOWN button.
Pressing ENTER will return you to the SETTINGS MENU. You can also keep pressing ENTER to toggle the filter pump from ‘on’ to ‘off’ and vice versa.
MANUAL MODE will time out, after 24 hours the SSV7RRT will return to normal operation.
2) FILTER TIMER
FILTER TIMER
(ON or OFF/V7STD)
FILTER TIMER can be set to ON or OFF/V7STD, this controls the power out of the left hand socket, if
OFF/V7STD is selected the left hand socket will be permanently powered and the right hand socket will control the solar pump, when the FILTER TIMER is set to ON the left hand power socket runs a filter pump on a timer with the following settings;
SINGLE CYCLE
DUAL CYCLE
Single cycle sub menu
SINGLE CYCLE
START TIME X:XX
SINGLE CYCLE
END TIME X:XX
Dual cycle sub menus
FIRST CYCLE
START TIME X:XX
FIRST CYCLE
END TIME X:XX
SECOND CYCLE
START TIME X:XX
SECOND CYCLE
END TIME X:XX
When you enter the FILTER SETUP menu you will need to select SINGLE CYCLE or DUAL CYCLE, the selected option will be flashing, you can use the UP/DOWN buttons to change to the selected option, once you select the required cycle by pressing SELECT you will be prompted to set the cycle
START TIME and END TIME, modify these by pressing the UP/DOWN buttons, press SELECT to accept the setting.
SINGLE CYCLE will run the filter pump once per day. DUAL CYCLE will run the filter pump twice per day. When DUAL CYCLE is selected, the 2nd cycle start and end times will be preset not to conflict with the 1st cycle time, you are also prevented from setting the cycle 2 times to conflict with the 1st cycle, this means you cannot view previously set times for cycle 2.
Factory Default is ON, DUAL CYCLE from 09:00 to 13:00 and 16:00 to 20:00
NOTE: Note that the maximum combined rated current is 10 Amps (2400W at 240VAC).
3) TEMPERATURE
TEMPERATURE
SOL LIMIT XX.X°
When you enter the TEMPERATURE menu you may change the solar heater temperature limit setting
(SOL LIMIT) by pressing the UP/DOWN buttons, if no change is required simply push ENTER.
Factory default is for SOL LIMIT is 30°C.
TEMPERATURE
AUX LIMIT XX.X°
AUX LIMIT sets the temperature the auxiliary heater will heat the swimming pool to you can use
UP/DOWN to change the selected temperature, press ENTER to accept (default is 25°C).
NOTE 1:
NOTE 2:
AUX LIMIT setting will only be shown if heat demand is turned on.
For maximum efficiency it is advisable that the solar limit (SOL LIMIT) be set higher than the auxiliary limit (AUX LIMIT)
4) HEAT DEMAND (only set ON if auxiliary heating fitted)
HEAT DEMAND
ON/OFF
When you enter the HEAT DEMAND you will need to select ON or OFF, the selected option will be flashing, you can use UP/DOWN to change the selected option, ENTER to accept.
If OFF is selected you will return to the menu, If ON is selected you will be prompted for START and
END time, modify values by using the UP/DOWN buttons, use ENTER to accept the values. Factory default is ‘heat demand off’.
HEAT DEMAND TIME HEAT DEMAND TIME
START TIME X:XX END TIME X:XX
NOTE: If a 24 hour continuous run time is required then set the start time and end time to the same value (e.g. Start 12:00, End 12:00)
IF LIMIT ACTIVE
SAMPLE AT XXXX
Sets the sampling period once the pool has reached the auxiliary temperature limit, options are 15 min, 30 min, 1 hour, 2 hours. Once the pool reaches the aux temperature limit and the filter pump is turned off it will not be turned on until the sample period expires, the filter pump will then run for a minimum period of 3 mins so that water can flow past the pool temperature sensor and obtain an accurate reading. Should heating be required the filter pump will remain on to heat the pool.
Factory default for HEAT DEMAND is OFF (06:00 to 22:00, sample @ 1 hour)
5) MODE
MODE
SUMMER MODE/WINTER MODE/TROPICAL MODE
You can use UP/DOWN to change the selected option, ENTER to accept.
SUMMER Mode is the normal operation of heating the swimming pool.
TROPICAL Mode is selected if you wish to cool the swimming pool, the solar pump will run if the roof temperature is colder than the pool until SOL LIMIT is obtained; note that this is most likely to occur at night.
WINTER Mode, when selected you will be prompted to select the start month and end month of winter
(inclusive), this assists in the systems off-season maintenance and saves energy as solar gain may be available but swimming temperature cannot be achieved. If heat demand is set to OFF a 3 minute flush of the solar matting occurs between 10:00 and 16:00 providing the roof temperature is equal or greater than the pool, but if that condition does not occur a solar system flush will be forced to occur at
16:00.
If heat demand is ON the system operates similar to normal mode but solar pump activity is monitored and will force a 3 minute flush if solar has not been active for seven days, note the unit may flush if winter mode is selected on the day of install.
6) CLOCK
TO CHANGE CLOCK TO CHANGE CLOCK TO CHANGE CLOCK TO CHANGE CLOCK
SET MINS XX SET HOURS XX SET DATE XX SET MONTH XX
When you enter the CLOCK menu you will be prompted to change the MINS settings, adjust minutes by pressing the UP/DOWN buttons, to accept the setting press the ENTER button.
You will then be prompted to change the HOURS, adjust by pressing the UP/DOWN buttons, to accept the setting press the ENTER button.
You will then be prompted to change the DATE, adjust by pressing the UP/DOWN buttons, to accept the setting press the ENTER button.
You will then be prompted to change the MONTH, adjust by pressing the UP/DOWN buttons, to accept the setting press the ENTER button.
7) SAVE & EXIT
When this menu is selected, push Enter to save ALL settings, the unit will return to normal operation automatically.
Note: If any of the menu items are left unattended for 3-4 minutes the menu will time out and automatically save all settings and return to operation.
The Enter button
FOR MANUAL MODE
PRESS ENTER NOW
Pressing the ENTER button once will display the above message for approximately 3 seconds, simply wait and the unit will return to normal operation.
If the ENTER button is pressed for a second time within a 3 second period, the display will indicate you have entered Manual mode, operation is the same as manual mode in the menu with the only difference being the timeout value is 4 hours.
NOTES:
1. If a sensor fault is detected the SSV7RRT will display which sensor and what the fault is.
2. Should power be interrupted for any reason, the SSV7RRT will resume normal operation when power is restored, all information will have been kept.
3. Temperature sensors used with this unit are digital and are accurate to 0.5°C, no calibration is required.
4. The sensor cable with the thin trace is the positive and is usually fitted to the right hand side of the green plug, incorrect polarity will be displayed.
5. If auxiliary heater interlock switching is used the maximum load is 5A at 32VAC max.
6. Solar start and end times may be changed by holding the up button while power is applied.
WARRANTY - SSV7RRT
This range of product is covered by a limited 3 year warranty against component failure or faulty workmanship from the date of installation.
A faulty unit should be returned in the first instance to the dealer from which the unit was purchased.
Damage to the unit due to misuse, power surges, lightning strikes or installation that is not in accordance with the manufacturer’s instruction may void the warranty.
Warranty does not cover travel costs to or from installation site.
Return to supplier for repair
Customer Record (to be retained by the customer)
Dealer/Installer Name: _________________________________________________________
SSV7RRT __________ Model Number:
Serial Number: _________________________________________________________
Date Installed: _________________________________________________________
For service assistance phone 1300 130 693
Dontek Electronics Pty Ltd
PO Box 239
Bayswater, Victoria 3153 www.dontekelectronics.com.au
Return to Manufacturer for repair