The FRC FDA700 for Delta Winding is a three-phase generator output display panel rated for 50/60 Hz generators from 10 to 135 kW. It displays generator frequency, voltage, and current, and has a built-in hourmeter. The display module is waterproof and can be mounted anywhere on the electrical panel, while the signal interface module is mounted close to the current sensors and voltage transformers for short cable runs.

The FDA700 has several safety features, including voltage fluctuation, current overload, and high-temperature warnings. It also has an optional audible alarm buzzer and temperature sensor.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
FRC FDA700 for Delta Winding Instruction manual | Manualzz

FDA700 Rev160509

Document Number:

XE-FDA7PM-R0A

FROG-D 3P

FREQUENCY READOUT OF GENERATOR

THREE PHASE

GENERATOR DISPLAY

MODELS: FDA700 for Delta Winding

FDA710 for Star Winding

FIRE RESEARCH CORPORATION

www.fireresearch.com

26 Southern Blvd., Nesconset, NY 11767

TEL 631.724.8888 FAX 631.360.9727 TOLL FREE 1.800.645.0074

1

FDA700 Rev160509

CONTENTS

Table of Contents

CONTENTS ................................................................................................................ 2

INTRODUCTION ...................................................................................................... 3

Overview ................................................................................................................ 3

Features .................................................................................................................. 3

Specifications ......................................................................................................... 3

GENERAL DESCRIPTION ....................................................................................... 4

Components ........................................................................................................... 4

Controls and Indicators .......................................................................................... 5

INSTALLATION ........................................................................................................ 6

Install Display Module........................................................................................... 6

Install Signal Interface Module.............................................................................. 6

Install Current Sensor ............................................................................................ 8

Install Voltage Transformer .................................................................................... 8

Install Optional Temperature Sensor ..................................................................... 8

Install Optional Buzzer .......................................................................................... 8

OPERATION ............................................................................................................ 10

WIRING .................................................................................................................... 12

Connectors and Cables......................................................................................... 12

Voltage Transformers ........................................................................................... 14

Current Sensors .................................................................................................... 15

Star Winding Connections ................................................................................... 16

Delta Winding Connections ................................................................................. 17

List of Figures/Table

Figure 1. Controls and Indicators ............................................................................... 5

Figure 2. Display Module Mounting Dimensions ..................................................... 7

Figure 3. Signal Interface Module Mounting Dimensions ........................................ 7

Figure 4. Current Sensor ............................................................................................ 9

Figure 5. Voltage Transformer ................................................................................... 9

Table 1. Line Displays ............................................................................................. 11

Figure 6. Display Module Wiring ............................................................................ 12

Figure 7. Signal Interface Module Wiring .............................................................. 13

Figure 8. Voltage Transformer Wiring ..................................................................... 14

Figure 9. Current Sensor Wiring .............................................................................. 15

Figure 10. Star Winding Connections ...................................................................... 16

Figure 11. Delta Winding Connections .................................................................... 17

2

FDA700 Rev160509

INTRODUCTION

Overview

The three phase generator output display panel is rated for 50/60 Hz generators from 10 to 135 kW with delta or star windings.

The display module has ultra-brite LEDs that show the generator frequency, voltage, and current. When the generator is off line the display shows total accumulated generator hours.

The signal interface module is mounted close to the current sensors and voltage transformers so that cable runs are short. Current and voltage information is passed to the display module over a two wire datalink.

Built in safety features include voltage fluctuation, current overload and high temperature warnings.

Features

Generator Hourmeter

Audible Alarm Buzzer (Optional)

Temperature Sensor (Optional)

Specifications

Display Module

Dimensions:

Control Box

Supply Power:

Supply Current:

Dimensions:

Current Sensor

Winding Ratio:

Voltage Transformer

4 1/4" Wide by 4 1/4" High

12 VDC

1.25 Amps

5 7/8" by 3 3/4" by 1 7/8"

150 : 5

Output: 12/24 VAC @ 0.2A

3

FDA700 Rev160509

GENERAL DESCRIPTION

Components

The three phase generator display consist of the following components:

Display Module

Signal Interface Module

Three (3) Current Sensors

Three (3) Voltage Transformers

Temperature Sensor (Optional)

Audible Alarm Buzzer (Optional)

Cables

Display Module

The display module is waterproof and can be mounted anywhere on the electrical panel. The display module has a square flange with overall dimensions of 4 1/4" by 4 1/4".

A cutout hole of 3 3/4" in diameter is required.

Signal Interface Module

The signal interface module is waterproof with overall dimensions of 5 7/8" by

3 3/4" by 1 7/8". Clearance for the cables is required. This module is mounted close to the current sensors and voltage transformers so the cable runs are short. Current and voltage information is passed to the display module over a two wire datalink.

Current Sensor

The current sensors are used to measure current flow through a wire by electromagnetic induction. Each phase wire to the main circuit breaker is run through a current sensor opening (hole); one wire through each current sensor.

Voltage Transformer

The voltage transformers supplied work with 120 or 240 volt AC systems.

The transformers should be securely mounted inside the electrical box.

Temperature Sensor (Optional)

The optional temperature sensor is installed as required.

Audible Alarm Buzzer (Optional)

The optional buzzer is installed as required.

Cables

Refer to the Wiring Section.

4

FDA700 Rev160509

Controls and Indicators

There is a STATUS LED located on the control box. All other controls and indicators are located on the front of the display module.

FREQUENCY Hz Display

Shows generator frequency in hertz.

LINE Displays

Shows a number that corresponds to a line in the chart to the left of the display.

VAC VOLTAGE Display

Shows the generator output in volts of the selected line.

AMPS CURRENT Display

Shows the current in amperes of the selected line.

MODE Button

Press to show total generator hours and sensor temperature.

LINE Button

Selects the line from the chart that is shown on the voltage and current displays.

See Operation Section for complete description.

Line Selected for Voltage

Display

Line Selected for Current

Display

LINE

Button

FREQUENCY

Display

VAC

VOLTAGE

Display

AMPS

CURRENT

Display

MODE

Button

FDA700 Rev160509

INSTALLATION

Ensure that the generator power rating and the display rating match. Refer to

Programming Section.

Install Display Module

1. Measure and mark mounting location for display module panel cutout and mounting screw holes. Make sure there is clearance behind the panel for the module and cables before cutting holes. Refer to Figure 2 for layout and dimensions.

2. Cut out a 3 3/4" mounting hole in panel.

3. Drill four holes, clearance or tapped, for #10 mounting screws.

4. Place display module in position and secure with screws.

5. Connect cable at rear of the display module. (Refer to Wiring Section.)

Install Signal Interface Module

This module is mounted close to the current sensors and voltage transformers so the cable runs are short. Current and voltage information is passed to the display module over a two wire datalink.

1. Measure and mark mounting location for control box mounting screw holes.

Make sure there is clearance for the box and cables before drilling. Refer to

Figure 3 for layout and dimensions.

2. Drill four holes, clearance or tapped, for #8 mounting screws.

4. Place box in position and secure with screws.

5. Connect cables at top of the box. (Refer to Wiring Section.)

6

Display Module

3/4"

Panel Cutout

3 3/4" Diameter

Module extends behind panel less than 1/2".

Mounting holes are clearance or tapped for #10 screws.

4 1/4"

3 1/2"

FDA700 Rev160509

3 1/2"

4 1/4"

Control Box

Figure 2. Display Module Mounting Dimensions

48mm

148mm

134.5mm

Mounting holes are clearance or tapped for #8 screws.

67mm

94mm

Figure 3. Signal Interface Module Mounting Dimensions

7

FDA700 Rev160509

Install Current Sensor

Three current sensors are supplied. It is best to mount the sensors in the circuit breaker box. For each phase that is to be monitored, run the wire from the generator through the current sensor opening (hole) to the input side of the circuit breaker.

(Refer to Wiring Section.)

Install Voltage Transformer

The voltage transformers supplied will work for 120 or 240 volt AC systems. The transformers should be securely mounted inside the electrical box.

Each transformer will be connect to show line voltage phase and neutral or phase to phase for star or delta windings of the generator. (Refer to Wiring Section.)

Install Optional Temperature Sensor

The temperature sensor is installed as required. (Refer to Wiring Section.)

Install Optional Buzzer

Install the buzzer close to the control module so the audible warning is easily associated with the visual warning on the display. The optional buzzer provided by

FRC requires a cutout hole of 1-1/8" (1.125"). (Refer to Wiring Section.)

8

FDA700 Rev160509

Current Sensor

Ratio: 150 : 5

Dimensions

A = 1.13"

B = 2.46"

C = 1.05"

Figure 4. Current Sensor

Voltage Transformer

Input:

Output:

120/240 VAC

12/24 VAC @ 0.2A

Dimensions

D = 1 1/2"

H = 1 3/8"

W = 2 3/8"

MW = 2"

Figure 5. Voltage Transformer

9

FDA700 Rev160509

OPERATION

On power-up the display shows the kW rating and the winding type (delta or star) for three seconds.

MODE Button

During normal operations the mode button is used to display the accumulated hours and hydraulic oil temperature if this option is installed.

The first time the MODE button is pressed, the display shows generator hours.

Generator Operating Time is:

50 hours

Pressing the MODE button again switches the display to show sensor temperature.

Hydraulic Oil Temperature is:

150 °

Pressing the MODE button again returns the display to normal operations.

Over Current Warning

When the generator is operating outside the range of its rated capacity, the current display flashes. An optional audible buzzer can also be connected for audio warning.

Voltage Out-Of-Range Warning

If the output voltage (120/240 VAC) is below 80/200 VAC or above 140/270 VAC, the voltage display flashes. This gives the operator an indication that the generator output falls outside the safe operating level. There is no audible alarm for the voltage out of range warning.

Temperature Sensor(Optional )

This warning is activated if the temperature sensor rises above 180 °F. The frequency readout flashes OIL to warn the operator and the audio alarm is activated.

10

FDA700 Rev160509

LINE Displays and Button

On power up the LINE displays are set to auto.

In auto the displays scroll continuously through all selectable options and show the corresponding voltages and currents in the display windows.

To read the voltage and current for a specific line press and hold the LINE button until the number corresponding to the desired selection shows in the LINE window.

(Refer to the chart next to the LINE window.)

Note: When line selections 4, 5, and 6 are active the AMPS window shows

3 dashes.

Leave the display in auto during normal operations to monitor all voltage and current levels.

Line Window Chart

1. A-N

2. B-N

3. C-N

4. A-B

5. B-C

6. C-A

7. Auto

Table 1. Line Displays

Description

Shows Voltage Phase A to Neutral

Shows Voltage Phase B to Neutral

Shows Voltage Phase C to Neutral

Shows Voltage Phase A to Phase B

Shows Voltage Phase B to Phase C

Shows Voltage Phase C to Phase A

Scroll Continuously Through All

Selectable Options

1. A

2. B

3. C

Shows Current on Phase A

Shows Current on Phase B

Shows Current on Phase C

11

FDA700 Rev160509

WIRING

The following figures include the schematics, wiring diagrams, block diagrams, and cables for the three phase generator display system.

Connectors and Cables

6 Pin Connector and Cable

Pin Wire Color Description

1 Red

2 Black

3

4

5

6

White

Green

Blue

Brown

+12 VDC

–12 VDC

Datalink (+)

Datalink (–)

Buzzer +12 VDC

Buzzer Ground

Notes

1The 6-Pin connector from the display module is wired to the signal interface module 4-Pin connector.

The two buzzer wires are pig-tailed off.

2—Power is supplied to the display unit from the signal interface module.

4-Pin Plug

Connected to the Signal Interface Module

Dual Display

For a dual display configuration a 4-Pin Y-cable (FRC P/N XE-XXDLY4-C1A) is connected to the signal interface module 4-Pin connector. Two display extension cables (FRC P/N XE-FD7DISP2-C10A) and two display modules can be connected.

Figure 6. Display Module Wiring

12

FDA700 Rev160509

4 Pin Connector and Cable

Pin Wire Color Description

1 Red

2 Black

3 White

4 Green

+12 VDC Supply to the Display

–12 VDC Supply to the Display

Datalink (+)

Datalink (–)

Note: The 4-Pin connector from the signal interface module is wired to the display module 6-Pin connector.

Pin Wire Color Description

1

2

Gray 12 Pin A Connector and Cable

Orange

Green

Temperature Sensor Supply

Temperature Sensor Signal

3 Black Temperature Sensor Ground

4 N/C

5 N/C

6 N/C

7 N/C

8 N/C

9 N/C

10

11 Red

12 Black

+12 VDC Supply

Ground Supply

Black 12 Pin B Connector and Cable

Pin Wire Color Description

1

2

Green

Blue

Voltage Transformer 1

Voltage Transformer 1

3 Orange Voltage Transformer 2

4 White

5

6

7

8

9

10

11

12

Purple

Tan

Pink

Gray

Yellow

Brown

Red

Black

Voltage Transformer 2

Voltage Transformer 3

Voltage Transformer 3

Current Sensor 1

Current Sensor 1

Current Sensor 2

Current Sensor 2

Current Sensor 3

Current Sensor 3

1

1

Voltage Transformer

(See Figure 8)

Current Sensors

(See Figure 9)

A

B

1

Optional Temperature Sensor

Red—Pin 1

Green—Pin 2

Black—Pin 3

Figure 7. Signal Interface Module Wiring

13

FDA700 Rev160509

Voltage Transformers

Voltage Transformer Cable

(Refer to Figure 7)

Green Wire

Blue Wire

Orange Wire

White Wire

Purple Wire

Tan Wire

Secondary AC Output

12/24 VAC

To FROG

Blue Wires

Blue Wires

Primary AC Input

120/240 VAC

From Generator

(Phase A)

Black Wires

(Phase B)

Black Wires

Blue Wires

(Phase C)

Black Wires

Note: Refer to Star or

Delta windings diagrams for generator connections.

Figure 8. Voltage Transformer Wiring

14

FDA700 Rev160509

Current Sensors

Current Sensor Cable

(Refer to Figure 7)

Pink Wire

Gray Wire

Yellow Wire

Brown Wire

Red Wire

Black Wire

White Wire

Black Wire

(Phase A)

White Wire

Black Wire

(Phase B)

White Wire

Black Wire

(Phase C)

From

Generator.

Figure 9. Current Sensor Wiring

15

FDA700 Rev160509

Star Winding Connections

From Generator

N C B A

Voltage

Transformers

N C B A

To Load

A

Current

Sensors

N

120v

C

120v

Star Circuit

B

Figure 10. Star Winding Connections

16

12-Pin Deutsch

Receptacle to

Gray Connector

Refer to Figure 7.

Delta Winding Connections

From Generator

N C B A

Voltage

Transformers

FDA700 Rev160509

12-Pin Deutsch

Receptacle to

Gray Connector

Refer to Figure 7

Current

Sensors

N C B A

To Load

C

240v

208v

A

240v

120v

120v

B

Recommended Delta Circuit

Reference Wiring

N

Note 1:

If the voltage reading needs

Calibration, adjust

AB (line-4),

BC (line-5),

CA (line-6).

Ref. OEM Calibration Guide

Note 2:

If the phase A & C is split for

Neutral, reverse the wiring for phase B & C.

If the phase B & C is split for

Neutral, reverse the wiring for phase A & C.

Figure 11. Delta Winding Connections

17

FDA700 Rev160509

NOTES

18

NOTES

FDA700 Rev160509

19

FDA700 Rev160509

20