advertisement
ENMET
680 Fairfield Court
Ann Arbor, MI 48108
734.761.1270 Fax 734.761.3220 www.enmet.com
CP-10
Control Panel
Operation and Maintenance Manual
CP-10
ENMET
Table of Contents
List of Figures
List of Tables
Reference Information:
N
OTE
: [important information about use of instrument]
C
AUTION
: [affects equipment – if not followed may cause damage to instrument, sensor etc.…]
W
ARNING
: [affects personnel safety – if not followed may cause bodily injury or death.]
Earth Ground
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 1
CP-10
1.0 Introduction
ENMET
The CP-10 Control Unit can monitor one channel of gas detection when connected to a Sensor Transmitter(S/T). The CP-10 is N
OT
in an enclosure rated for use in a Class I, Div. 1, Groups B, C, D classified area and cannot be installed in a hazardous location.
Features of the CP-10:
continuous monitoring of the target gas and continuous LCD display of gas and vapor concentrations
menu driven operational and maintenance controls
audio and visual alarms indicate unsafe conditions
alarm relay contacts available on terminals
a fault relay and visual fault alarm
alarm acknowledgement capability including audio defeat
mA outputs for target gas
N
OTE
: All specifications stated in this manual may change without notice.
1.1 Unpack
Unpack the CP-10 and examine it for shipping damage. If such damage is observed, notify both ENMET customer service personnel and the commercial carrier involved immediately.
Regarding Damaged Shipments
N
OTE
: It is your responsibility to follow these instructions. If they are not followed, the carrier will not honor any claims for
damage.
• This shipment was carefully inspected, verified and properly packaged at ENMET and delivered to the carrier in good condition.
• When it was picked up by the carrier at ENMET, it legally became your company’s property.
• If your shipment arrives damaged: o
Keep the items, packing material, and carton “As Is.” Within 5 days of receipt, notify the carrier’s local office and request immediate inspection of the carton and the contents. o
After the inspection and after you have received written acknowledgment of the damage from the carrier, contact ENMET
Customer Service for return authorization and further instructions. Please have your Purchase Order and Sales Order numbers available.
• ENMET either repairs or replaces damaged equipment and invoices the carrier to the extent of the liability coverage, usually
$100.00. Repair or replacement charges above that value are your company’s responsibility.
• The shipping company may offer optional insurance coverage. ENMET only insures shipments with the shipping company when asked to do so in writing by our customer. If you need your shipments insured, please forward a written request to
ENMET Customer Service.
Regarding Shortages
If there are any shortages or questions regarding this shipment, please notify ENMET Customer Service within 5 days of receipt at the following address:
ENMET
680 Fairfield Court
Ann Arbor, MI 48108
734-761-1270 Fax 734-761-3220
Toll Free: 800-521-2978
1.2 Check Order
Check, the contents of the shipment against the purchase order. Verify that the CP-10 is received as ordered. Each CP-10 is labeled with its target gas. If there are accessories on the order, ascertain that they are present. Check the contents of calibration kits. Notify ENMET customer service personnel of any discrepancy immediately.
1.3 Serial Numbers
Each CP-10 is serialized. These numbers are on tags on the equipment and are on record in an ENMET database.
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 2
CP-10
2.0 Components of the CP-10
2.1 CP-10 elements
See Figure 1 for location of elements:
Feature
Enclosure
Front Cover
ENMET
Description
A polycarbonate box, approximately 7 x 5 x 3, with a detachable front cover.
4 holes for mounting the enclosure to a vertical surface. Located at the corners of the bottom of the enclosure, directly beneath the 4-front cover retaining screws. See Figure 3
Detachable front cover of CP-10 with Display Panel. See Section 2.2 and Figure 1
There are 4 Screws that hold the front cover in place.
2.2 CP-10 Operational Features
The Display Panel is attached by a cable and is released by unscrewing the 4 screws located in the corners. After releasing the panel, it is swung upward, exposing the interior of the enclosure. See Figure 1 for location of features.
Feature Description
Display
Audio Alarm(Horn)
Visual:
Indicators and Alarms
Membrane Switches
A single line, 8-character LCD with backlight. Indicates the level of gas detected by sensor.
The numerical value of gas concentration and other information is displayed.
Audio alarm (105 dB at 30cm/12in). The audio alarm is activated when the unit is in alarm.
LED indicators:
Power / Fault Indicator LED, Green / Red
Alarm (3) Indicator LED, Red
2 Pushbutton Switches on front panel, control the instrument maintenance functions. The pushbutton switch locations are indicated by:
M
ENU
: Advances the instrument display through operation information and maintenance menus
S
ELECT
: Disables audio alarm temporally and Selects the maintenance menu operations.
See Section 4.0 and 5.0 for operational and maintenance flow charts.
Three alarm points are preprogrammed into the CP-10. At each alarm point, an LED on the front panel is activated. There are 4,
10 Amp relay contacts at each alarm point, plus a fault relay. See Section 3.2 for wiring information.
Visual Indicator
Power/Fault
Visual Indicators:
Alarm1, Alarm2, Alarm3
Sensor/Remote Sensor
Wiring Access
Menu Select
Pushbutton/Membrane
Switches
Audio Alarm
Front Cover
Retaining Screws 4
places
Power Wiring
Strain Relief
Figure 1: External CP-10 Features
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 3
CP-10
ENMET
2.3 Circuit Board Features
The Display Panel is attached by a cable and is released by unscrewing the 4 screws located in the corners. After releasing the panel, it is swung upward, exposing the interior of the enclosure. The Circuit Board is mounted at the back surface of the enclosure interior. Features are shown in Figure 2.
Feature Description
Relay Terminals:
J14, J15, J16, J17
Terminal J12
Sensor Terminal J18
Data Terminal J19
Potentiometer 2, 3 & 4
This group of terminals is located on the Circuit Board.
For the contacts for each of three alarm relays, and for the contacts of a fault relay. See
Section 3.3
For V
DC
back-up power in and the 4-20 mA output. See Section 3.1.2
Sensor/Transmitter connection, See Section 3.2
RS-485 input/output
Not used in CP-10 Do Not Adjust
Sensor/Transmitter Connection
Terminal J18
RS-485 Input/ Output
Terminal J19
POT 2
Relay Terminals
J14, J15, J16, J17
Relays
K1, K2, K3, K4
Terminal J12
DC Power In
4-20mA Output
POT 3
Sensor Heater Voltage
Adjustment POT 4
Figure 2: CP-10 Circuit Board Features
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 4
CP-10
3.0 Installation of the CP-10
ENMET
The CP-10 is supplied with a strain relief for a power line cord. Use this fitting or connect a conduit fitting when supplying power to the unit.
N
OTE
: This control panel is
NOT
rated for hazardous locations. The control panel must be in a Non-Hazardous area.
3.1 Mounting CP-10
Mount the CP-10 instrument on an appropriate vertical surface, leaving room for lid to be opened, using the mounting holes provided. Avoid areas with excessive vibration or temperature extremes. The holes in the bottom of the enclosure are 0.18 inch in diameter and form a 6.44 x 4.47 rectangle. See Figure 3
It is recommended to use #8 drywall anchors and screws for mounting the CP-10 to a drywall/sheetrock surface.
Cover Inside View
Opened Upward
Attached to Base
Sensor Heater Voltage Label
Access for Sensor / Remote Sensor Wiring
R
IGHT
S
IDE
V
IEW
Figure 3: Mounting CP-10
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 5
CP-10
ENMET
3.1.1 Wiring the CP-10
The electrical installation should conform to appropriate electrical codes, such as the National Electrical Code in the United
States.
W
ARNING
: The compliance of the installation to appropriate codes is not ENMET’s responsibility.
The CP-10 should be powered through appropriately sized circuit breakers. See Section 6.0 Technical Data.
3.1.2 Power Supply
The input power can vary from 100 to 240 V
AC
, 50/60 Hz. Power should be connected to the Power Input Terminal TB1 and the Ground screw. See Figure 4 for location.
For DC wiring 24V
DC
may be wired to J12, (J12-1) position 1 + with ground connected to (J12-2) position 2.
Upon supplying power to the CP-10:
The green power on LED is lit.
The display backlight is lit, and instrument will step through a start-up sequence: unit serial number and software revision may be shown on the display.
The instrument may go into alarm briefly, but the sensors stabilize quickly. If the instrument persists in alarm, acknowledge the alarm by pressing the S
ELECT
button. If alarm persists longer than 30 minutes, call ENMET customer service personnel.
W
ARNING
: Continuous gas detection and alarm systems (110V
AC
/220V
AC
/ 24V
DC
/12V
DC
powered) become inoperative upon
loss of primary power. Contact factory for specifications and pricing of backup battery systems.
Sensor/Transmitter Terminal: J18
Position Function
Cover Inside View
Opened Upward
1, V+
2, G
3, Sig
Power +24 V
DC
Power Ground
Signal/Return to Ground
AC Power Supply Terminal: TB1
Label on PCB
110V
AC
TB1 ACN
TB1 ACL
Ground
Screw
Function
Neutral
Line
AC GND
220V
AC
TB1 ACN
Optional
TB1 ACL
Ground
Screw
C
AUTION
: 110/220 V
AC
when applied
DC Power Supply/4-20mA
Terminal: J12
Position Function
1 +
2
3
24 V
DC power
GND
4 - 20 mA out
Neutral
Line
AC GND
1 2 3
Figure 4: Power Terminal Connections CP-10
Caution: 110/220 V
when applied
AC
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 6
CP-10
ENMET
3.2 Sensor/Transmitter Connection
Sensor/Transmitters are connected to the CP-10 control unit with two or three-conductor wiring, use the correct oil tight fitting.
Size of wire depends on the distance between the sensor/transmitter and the control unit.
See Recommended Wire Gauge Table below.
2 Wire for Sensors/Transmitter
3 Wire for Sensors/Transmitter
1, V+
2, G
3, Sig
Position Function
Power +24 V
DC
Not Used
Signal/Return to Ground
1, V+
Position
2, G
3, Sig
Function
Power +24 V
DC
Power Ground
Signal
Recommended Wire Gauge
Distance from Sensor to Control Unit Recommended Wire Gauge
< 500 feet 16 AWG
501 – 800 feet
Longer Distances
14 AWG
Contact Factory
N
OTE
: Sensor Location
Gases have different densities. Some are heavier than air and concentrate at the bottom of a space. Some are lighter than air and gather at the top. Consider the density of the gas you want the sensor to detect when you install the sensor. Some examples are given below.
Heavier than Air Gas Sensor Location
Bottled LP (liquefied petroleum) Interior wall; 18-24" from floor.
Propane
D
O
N
OT locate directly above or beside gas appliances (ovens,
Butane heaters).
Gasoline
Avoid locating anywhere near a vent or window or near an outside
Trichloroethylene doorway.
Vaporized hydrocarbons
Hydrogen sulfide
Lighter than Air Gas Sensor Location
Natural gas (methane)
Ammonia
Hydrogen
Near ceiling.
D
O
N
OT locate directly above appliances where it is subject to direct exposure to heat or steam.
Same Density as Air Gas Sensor Location
Carbon Monoxide 4-6 feet above the (generally uniform) floor.
D
O
N
OT locate in direct air currents of windows, doors, or vents.
If you have a question involving the location of a unit or sensor, please contact your distributor or ENMET personnel. A technician will analyze the question and recommend a location.
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 7
CP-10
ENMET
3.3 Relay Contacts
Relay contacts are available for each alarm; these are SPDT, rated at 10Amp at 110V
AC
, and may be latching or non-latching as required by the application.
They are accessed on the terminals next to each relay see Figure 5. The contact positions are noted on the circuit board next to each terminal.
The following table is for the relays in their un-energized state. This is also the alarm condition state. Non-failsafe configured relays in the alarm state, are the reverse of the PC board labeling. Note that the Fault(FLT) relay cannot be set to operate in a Non-
Failsafe mode. Please see Table 1 below:
Alarm
Table 1: Relay Failsafe Settings
Position
Alarm 1
Alarm 2
Alarm 3
Fault Alarm
J14 (K1) Relay 1 - NO Normally Open
J14 (K1) Relay 1 - NC Normally Closed
J14 (K1) Relay 1 - COM Common
J15 (K2) Relay 2 - NO Normally Open
J15 (K2) Relay 2 - NC Normally Closed
J15 (K2) Relay 2 - COM Common
J16 (K3) Relay 3 - NO Normally Open
J16 (K3) Relay 3 - NC Normally Closed
J16 (K3) Relay 3 - COM Common
J17 (K4) Relay 4 - NO Normally Open
J17 (K4) Relay 4 - NC Normally Closed
J17 (K4) Relay 4 - COM Common
These relay contacts can be used to operate auxiliary alarms or other functions. The relay contacts are DRY, power must be supplied. It is recommended that power for auxiliary equipment be supplied from an independent power source separate from the
CP-10. Use the existing hole in the enclosure for wire to enter and exit and use appropriate cable fittings. Wiring should be grouped together, V
AC
wires should be separated for V
DC
wires.
Sensor/Transmitter
Terminal J18
Relay Terminals
J14, J15, J16, J17
Relays
K1, K2, K3, K4
Figure 5: Relay Terminal Connections CP-10
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 8
CP-10
4.0 Operation
ENMET
When the CP-10 is installed as described in Section 3, and in clean air, the POWER green LED is on, the display is lit and the information on the display is measurement of the target detected by the CP-10.
The red alarm and fault LEDs are not lit.
4.1 Start Up CP-10
When the CP-10 is first powered up, it goes through a series of momentary screens, which identify the instrument model number, serial number and software revision. After all the momentary screens have been displayed, the instrument arrives at the Main Gas
Display showing the gas concentration and unit of measurement in ppm, % or %LEL.
Depending on transmitter configuration and calibration condition, the furthest right character in the display may flash a letter indicating the instrument status. See the Section 4.1.1 below
4.1.1 Typical Start Up
When power is supplied to the CP-10, the instrument will display the following sequence of information:
Typical start up sequence of information displayed.
Example of Typical Start Up Display Function
The instrument: Model CP-10
CP-10
Example for reference only The instrument: Serial Number
130-1256
Example for reference only
S/W X.X
IF the right most character is a flashing W
0ppW
The instrument: Software Revision
The instrument is in Warm-up mode
This should last about 1 minute
The Signal Output is held at 4mA during warm-up
0ppm
20.9%
0LEL
The instrument: Normal Display Mode
Measurement of the target gas
PPM Parts Per Million
% Percent by Volume
LEL Lower Explosive Limit
F Fault, Sensor/Transmitter is not connected or wiring is not correct
N
OTE
: Software revision may cause variations of display output.
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 9
CP-10
ENMET
4.2 Normal Display Mode
When the CP-10 is installed as described in section 3, the POWER green LED is on, the display is lit and the measurement designator: ppm, LEL or % is displayed by the CP-10.
The red alarm and fault LEDs are not lit.
To advance through displays of operational information press the M
ENU
button.
N
OTE
: Software revision may cause variations of display output.
See sequence of operational information below:
Example:
Display Measurement of the target gas
Press M
ENU
button
0ppm
Select
Menu
Display indicates Alarm 1 Set point
Press M
ENU
button
A1:
Menu
05
Select
Display indicates Alarm 2 Set point
Press M
ENU
button
A2:
Menu
10
Select
Display indicates Alarm 3 Set point
Press M
ENU
button
A3:
Menu
20
Select
Display indicates mA Span range
(Full Scale)
mA:
Press M
ENU
button
Display returns to gas measurent
Menu
Operatio nal Display Flo w Chart
50
Select
4.2.1 Alarm Conditions CP-10
There are three alarm set points available. These alarm points are normally set at established safety levels, such as the OSHA
Permissible Exposure Limit (PEL) for toxic gases or recognized standards below the Lower Explosive Limit for combustible gases.
The alarm set points can be changed within limits; see the maintenance section of this manual for the procedure.
When the Oxygen, Toxic or combustible gas concentration reaches the alarm set point, the associated red LED is lit, the associated relay changes state, and the audio alarm is activated.
Pressing the S
ELECT
button can temporally disable the Audio Alarm. The horn will be disabled for about five minutes. If a second alarm condition occurs during this time the horn will re-activate. If the alarm condition(s) have ended during this time the horn will not re-activate.
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 10
CP-10
5.0 Maintenance
ENMET
The CP-10 maintenance menus that are accessed by pressing the M
ENU
button and
S
ELECT
button as described in the maintenance menu section.
5.1 Maintenance Menus
Pushbutton switches control the
M
ENU
and S
ELECT
functions. The M
ENU
and S
ELECT
button locations are indicated on the display panel, see Figure 1. The M
ENU
button is used to display the various menu options and make incremental changes to numbers such as alarm points. The S
ELECT
button is used to select the option and move the cursor.
To enter the maintenance menu, press and hold the M
ENU
button for 2 to 4 seconds
Table 2 indicates the maintenance menu sequence see Figure 6 for a detailed maintenance menu flow chart.
N
OTE
: Software revision may cause variations of display output.
Table 2: CP-10 Maintenance Menus Sequence
Example of Display Function
5ppm
Measurement of CO
Normal Display Mode
Press and hold the M
ENU
button for 2 – 4 seconds to enter the Maintenance Menu
The Power/Fault LED will flash Green – Red to indicate the CP-10 is in Maintenance Mode
Exit
To exit the maintenance Menu and return to the
Normal Display Mode:
If intended function Press S
ELECT
button
Press the M
ENU
button to advance to 4 & 20 Setup procedures
420Setup
For adjusting the 4 and 20 mA circuit:
If Intended function, press S
ELECT
button
Press the M
ENU
button to advance to each Alarm set point procedures
Alarm1
Alarm2
For adjusting the Alarm 1, 2 and 3 set points:
If Intended function, press S
ELECT
button
Alarm3
Press the M
ENU
button to advance the mA Span set point procedure mA Span
For adjusting the mA Span set point:
If intended function Press S
ELECT
button
Pressing the M
ENU
button without pressing the S
ELECT
button will allow you to cycle through the menu options.
You must Press the S
ELECT
button to initiate the desired operation.
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 11
CP-10
ENMET
5ppm
Normal Gas Display
Menu Press and H
OLD
the M
ENU
button for 2 – 4 seconds to enter the Maintenance Menus
Exit
Select
Press the Select button to return to the Normal Gas Display. See Section 5.2.1
Menu
Press the Menu button to cycle through Maintenance Menus
420Setup
Menu
Select
Select
Select
Scale4mA
Menu
Scal20mA
Menu
mA Trim
Menu
Select
0
Press Select button to set low end of scale:
The Select button locks underscored digit and moves to next digit
The Menu button changes digit indicated by underscore cursor
When last digit is entered CP-10 will advance to full scale set up
Select
50
Press Select button to advance to full scale
To set full scale :
The Select button locks underscored digit and moves to next digit
The Menu button changes digit indicated by underscore cursor
When last digit is entered CP-10 will advance to display trim
Select
0 Cal OK
Press Select button to advance to display trim
To adjust display of CP-10 to match S/T display
The Select button locks underscored digit and moves to next digit
The Menu button changes digit indicated by underscore cursor
When the last digit has been locked in place, Cal OK will appear briefly than the
CP-10 will advance to the next menu, Alarm 1
See Section 5.2.2
Alarm1
M
ENU
Alarm2
M
ENU
Alarm3
M
ENU
S
ELECT
Λ 5
SetTDsec
0
S
ELECT
Λ 10
SetTDsec
0
S
ELECT
Λ 20
SetTDsec
0
To change Alarm set points:
Press Menu switch until Alarm to be changed is displayed
Press Select switch to display the set point
The M
ENU
switch: changes digit indicated by underscore cursor
The S
ELECT
switch: locks in the underscored digit and moves to next digit
If change is not within range display returns to first digit
If change is within range display moves to Set Time Delay
Use M
ENU
and S
ELECT
switches as above to change time delay.
Between 0 and 5 seconds is allowed
If change is within range display moves to next menu
See Section 5.2.3
Λ - Indicates increasing alarm
V - Indicates decreasing alarm mA Span
Menu
Select
0050
To change mA Span set point:
Press Menu button until mA Span is displayed
Press Select button to display the set point
The Menu button changes digit indicated by underscore cursor
The Select button locks underscored digit and moves to next digit
See Section 5.2.4
To return to Normal Gas Display:
Press M
ENU
button until EXIT is displayed
Then press S
ELECT
button
N
OTE
: Software revision may cause variations of display output.
Figure 6: CP-10 Maintenance Menu Flow Chart - Gas
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 12
CP-10
20.9%
Normal Gas Display
Menu Press and H
OLD
the M
ENU
button for 2 – 4 seconds to enter the Maintenance Menus
Exit
Select
Press the Select button to return to the Normal Gas Display. See Section 5.2.1
Menu
Press the Menu button to cycle through Maintenance Menus
420Setup
Menu
Select
Select
Select
Scale4mA
Menu
Scal20mA
Menu
mA Trim
Menu
Select
0.0
Press Select button to set low end of scale:
The Select button locks underscored digit and moves to next digit
The Menu button changes digit indicated by underscore cursor
When last digit is entered CP-10 will advance to full scale set up
Select
30.0
Press Select button to advance to full scale
To set full scale:
The Select button locks underscored digit and moves to next digit
The Menu button changes digit indicated by underscore cursor
When last digit is entered CP-10 will advance to display trim
Select
20.9
Cal OK
Press Select button to advance to display trim
To adjust display of CP-10 to match S/T display
The Select button locks underscored digit and moves to next digit
The Menu button changes digit indicated by underscore cursor
When the last digit has been locked in place, Cal OK will appear briefly than the
CP-10 will advance to the next menu, Alarm 1
See Section 5.2.2
Alarm1
M
ENU
Alarm2
M
ENU
Alarm3
M
ENU
S
ELECT
V 17.0
SetTDsec
0
S
ELECT
V 19.5
SetTDsec
0
S
ELECT
Λ 23.5
SetTDsec
0
To change Alarm set points:
Press Menu switch until Alarm to be changed is displayed
Press Select switch to display the set point
The M
ENU
switch: changes digit indicated by underscore cursor
The S
ELECT
switch: locks in the underscored digit and moves to next digit
If change is not within range display returns to first digit
If change is within range display moves to Set Time Delay
Use M
ENU
and S
ELECT
switches as above to change time delay.
Between 0 and 5 seconds is allowed
If change is within range display moves to next menu
See Section 5.2.3
Λ - Indicates increasing alarm
V - Indicates decreasing alarm mA Span
Menu
Select
30.0
To change mA Span set point:
Press Menu button until mA Span is displayed
Press Select button to display the set point
The Menu button changes digit indicated by underscore cursor
The Select button locks underscored digit and moves to next digit
See Section 5.2.4
To return to Normal Gas Display:
Press M
ENU
button until EXIT is displayed
Then press S
ELECT
button
N
OTE
: Software revision may cause variations of display output.
Figure 7: CP-10 Maintenance Menu Flow Chart – Oxygen
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
ENMET
P a g e | 13
CP-10
5.2 CP-10 Maintenance Adjustments
To set alarm points and 4-20mA span range enter the CP-10 maintenance menu.
To enter the maintenance menu, press and hold the M
ENU
button for 2 to 4 seconds
N
OTE
: Software revision may cause variations of display output.
ENMET
5.2.1 Exit Maintenance Menu
Exit maintenance, by pressing the Exit appears on the display. Press the S
ELECT
button to return to the instrument Normal Gas
Display.
Example of Exit menu:
Exit
Select
Press the Select button to return to the Normal Gas Display.
Menu
Press the Menu button to cycle through Maintenance Menus
5.2.2 Set Up 4 and 20 Scale
The CP-10 4 mA low scale (the low end of range) and 20 mA full scale (the high end of range) is set at the factory. The mA
Trim is for the adjustment of minor differences that may occur between the CP-10 control and the S/T display.
To Set up the low and full scale mA values or the trim of the readings:
Enter the maintenance menu as shown in Figure 6 & Figure 7 CP-10 Maintenance Menu flow chart.
1. Press the M
ENU
button until to 420Setup is displayed.
2. Press the S
ELECT button to enter 4 mA low end of scale set up.
Note: to advance to the next menu without changing this scale setting Press the M
ENU
button
3. Press the S
ELECT button to initiate 4 mA low end of scale set up.
4. Press the S
ELECT
button to move the cursor to the next digit.
5. Press the M
ENU
button to change the digit indicated by the underscore cursor.
Repeat steps 4 & 5, When last digit is entered the CP-10 will advance to the next menu.
Note: when mA Trim last digit has been entered, Cal OK will be displayed briefly and CP-10will advance to Alarm 1.
6. Press the M
ENU
button to advance to the next menu
Example of 4 – 20 mA Scale Setup menus:
420Setup
Select
Scale4mA
Menu
Menu
Select
0
Press Select button to set low end of scale:
The Select button locks underscored digit and moves to next digit
The Menu button changes digit indicated by underscore cursor
When last digit is entered CP-10 will advance to full scale set up
Select
Scal20mA
Select
50
Menu
Press Select button to advance to full scale
To set full scale:
The Select button locks underscored digit and moves to next digit
The Menu button changes digit indicated by underscore cursor
When last digit is entered CP-10 will advance to display trim
Select
mA Trim
Select
0
Cal OK
Men u
Press Select button to advance to display trim
To adjust display of CP-10 to match S/T display
The Select button locks underscored digit and moves to next digit
The Menu button changes digit indicated by underscore cursor
When the last digit has been locked in place, Cal OK will appear briefly than the
CP-10 will advance to the next menu, Alarm 1
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 14
CP-10
ENMET
5.2.3 Alarm Set Points
The CP-10 has three alarm set points set at the factory. These alarm points are normally set at established safety levels. Alarm set points can be changed within limits. To change any of the three alarm points:
Enter the maintenance menu as shown in Figure 6 & Figure 7 CP-10 Maintenance Menu flow chart.
1. Press the M
ENU
button until to display Alarm1 is displayed.
2. Press the S
ELECT button to initiate alarm set point change
3. Press the M
ENU
button to change the digit indicated by the underscore cursor
Λ - Indicates increasing alarm
V - Indicates decreasing alarm
4. Press the S
ELECT
button to move the cursor to the next digit
When last digit is entered the CP-10 will advance to the next menu
5. Use M
ENU
and S
ELECT
switches as above to change time delay. Between 0 and 5 seconds is allowed.
6. Press the M
ENU
button to advance to the next menu
N
OTE
: Alarms 2 and 3 cannot be set below the Alarm 1 setting.
Example of Alarm Set Point menus:
Gas OR Oxygen
Alarm1
S
ELECT
Λ 5
V 17.0
M
ENU
Alarm2
M
ENU
S
ELECT
SetTDsec
0
Λ 10
SetTDsec
0
SetTDsec
0
V 19.5
SetTDsec
0
To change Alarm set points:
Press Menu switch until Alarm to be changed is displayed
Press Select switch to display the set point
The M
ENU
switch: changes digit indicated by underscore cursor
The S
ELECT
switch: locks in the underscored digit and moves to next digit
If change is not within range display returns to first digit
If change is within range display moves to Set Time Delay
Use M
ENU
and S
ELECT
switches as above to change time delay.
Between 0 and 5 seconds is allowed
If change is within range display moves to next menu
Λ - Indicates increasing alarm
V - Indicates decreasing alarm
Alarm3
S
ELECT
Λ 20
Λ 23.5
M
ENU
SetTDsec
SetTDsec
0
0
N
OTE
: Software revision may cause variations of display output.
5.2.4 mA Span Set
The CP-10 4-20mA span range is set at the factory, normally to the full scale of the measurement and can be changed within limits. To change the span range:
Enter the maintenance menu as shown in Figure 6 CP-10 Maintenance Menu flow chart.
1. Press the M
ENU
button until to display Span is displayed.
2. Press the S
ELECT button to initiate the mA Span menu
3. Press the M
ENU
button to change the digit indicated by the underscore cursor
4. Press the S
ELECT
button to move the cursor to the next digit
When last digit is entered the CP-10 will advance to the next menu
5. Press the M
ENU
button to advance to the next menu
Example of mA Span menu:
Select
mA Span
Menu
0050
To change mA Span set points:
Press Menu button until mA Span is displayed
Press Select button to display the set point
The Menu button changes digit indicated by underscore cursor
The Select button locks underscored digit and moves to next digit
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 15
CP-10
6.0 Technical Data and Specifications
The CP-10 technical data and specifications:
15 Amp fused branch circuit
Electrical Power
100-240 V
AC
0.45A, 50/60 Hz
0.6A, 24V
DC
Storage and Transport
Operation
Mechanical
Temperature:
preferred
Relative Humidity
Atmospheric Pressure
Temperature:
Relative Humidity
Atmospheric Pressure
Dimensions:
Weight:
Material:
Strain relief:
-20 to +60C (-4 to +140F)
0 to +20C (32 to 68F)
10-99% RH, non-condensing
20 to 36 inHg (68 to 133 kPa)
-15 to +40C (5 to +104F)
10-99% RH, non-condensing
20 to 36 inHg (68 to 133 kPa)
7.1 x 5.1 x 3 in(180x130x75mm)
2 lbs (0.9 kg)
Polycarbonate
0.20 – 0.35 in(5 - 8.8mm)
Outputs
Relays:
Analog:
Digital:
Audio:
N
OTE
: All specifications stated in this manual may change without notice.
SPDT
Resistive Load Inductive Load
10A at 110 V
AC
7.5A at 110 V
AC
10A at 30 V
DC
5A at 30 V
DC
4-20mA
RS-485-modbus
105 dB at 30cm/12in
Notes:
ENMET
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 16
CP-10
7.0 Terms and Conditions
7.1 Ordering Information
Address orders to:
ENMET
Attention: Customer Service Department
680 Fairfield Court
Ann Arbor, MI 48108
Email Orders: [email protected]
Phone: 734-761-1270
Fax: 734-761-3220
You may also contact our customer service department by email [email protected]. MINIMUM ORDER IS $50.00.
ENMET
7.2 Shipping Terms
All shipments are F.O.B. ENMET’s facility in Ann Arbor, MI, USA or Bowling Green, KY, USA. Shipping and handling charges are prepaid and added, and must be paid by the customer. Shipping and handling charges may be billed to VISA, MasterCard,
American Express, or to the customer’s preferred carrier account number. Delivery to the carrier constitutes delivery to the customer, and risk of loss passes to the customer at that time, however, title shall remain with ENMET until payment is received in full. Claims for shortages and damage must be made by the customer to the carrier within 5 days of receipt. Refer to section “1.1
Unpack” for more information on this matter.
A special service of $50.00, or more, may be assessed on expedited shipments.
NOTE: Calibration gases are classified as Dangerous Goods for transportation purposes, and shipping companies charge a hazardous material fee for processing the documentation required for handling such items. Also, other restrictions apply to shipment of Danger Goods by air. Check with ENMET for clarification and additional information.
7.3 Payment
Open accounts must be established in advance with ENMET’s Accounting department.
Address Payments to:
ENMET
680 Fairfield Court
Ann Arbor, MI 48108
Phone: 734-761-1270
We accept payments by VISA, MasterCard, and American Express. Payment by credit card must be specified at time of order placement. Your credit card will be charged on the date of shipment.
ENMET invoices for products that are shipped on open account are due and payable 30 days from the date of shipment from the
ENMET site. ENMET may institute collection services should any bona fide invoice remain unpaid with no payment schedule negotiated by the customer with the ENMET Accounting Department. Any cost incurred by ENMET for professional collection services or legal fees to collect on a customer invoice will be added to any future business conducted between ENMET and that customer.
7.4 Warranty Information and Guidelines
Equipment must be returned prepaid to the point of origin, and ENMET will prepay the return transportation charges.
Transportation prepaid by ENMET will be by most economical means (e.g. FedEx Ground). If an expedient means of transportation is requested during the warranty period, the customer must pay the difference between the most economical means and the expedient mode. ENMET warrants new instruments to be free from defects in workmanship and material under normal use for a calibration and expendable parts such as filters, detector tubes, batteries, etc. In addition, some oxygen cells and other sensors are limited to a warranty period of six months from date of shipment. Refer to the instrument manual for specific warranty details. If the inspection by ENMET confirms that the product is defective, it will be repaired or replaced at no charge, within the stated limitations, and returned prepaid by FedEx Ground to any location in the United States. ENMET shall not be liable for any loss or damage caused by the improper use or installation of the product. The purchaser indemnifies and holds harmless the company with respect to any loss or damagers that may arise through the use by the purchaser or others of this equipment. This warranty is expressly given in lieu of all other warranties, either expressed or implied, including that of merchantability, and all other obligations, or liabilities of ENMET which may arise in connection with this equipment. ENMET neither assumes nor authorizes any representatives or other persons to assume for it any obligation or liability other than that which is set forth herein.
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 17
CP-10
ENMET
If a component is purchased and installed in the field, and fails within the warranty term, it can be returned to ENMET and will be replaced, free of charge. If the entire instrument is returned to ENMET with the defective item installed, it will be replaced at no cost, but the instrument will be subject to labor charges at half of the standard rate.
NOTE: When returning an instrument to the ENMET for service: o Be sure to include all paperwork (the “Request for Service” form). o Include any specific instructions. o For warranty service, include the date of purchase. o If you require an Estimate, please contact ENMET.
The “Request for Service” form is on the final page of this manual. This form can be copied or used as needed. For service requests, outside of the warranty period, please refer to the “Returning an Instrument for Service Instruction” found later in this section.
7.5 Return Policy
All returns for credit must be approved by ENMET and identified with a “Return Material Goods” number. Such returns are subject to a minimum of a $50.00 or 20% restocking fee, whichever is greater. Approval of equipment for return is fully at
the discretion of ENMET. All requests for return/exchange must be made no later than 30 days of the original shipping date from ENMET. The actual amount of any resulting credit will not be determined prior to a complete inspection of the equipment by ENMET. Calibration gas cylinders cannot be returned or restocked due to the Department of Transportation refill restrictions.
Air Filtration Systems (AFS series & parts) cannot be returned or restocked because their internal surfaces and filters are not amenable to re-inspection.
Certain products, such as stationary systems, or instruments with custom sensor configuration (non-standard) are built to
order, and cannot be returned. Cancellation of orders for custom-built products, prior to shipment, will result in the assessment of a cancellation fee. The amount of the cancellation fee will be based upon the size and complexity of the order, and the percentage of total cost expended prior to cancellation.
7.6 Returning an Instrument for Service Instructions
Contact the ENMET Service Department for all service requests.
Phone: 734-761-1270
Email: [email protected]
Fill out the “Service Request Form” found at the end of this manual and return with your instrument for all needs. Please send your instrument for service to the site in which the product was purchased. A new “Service Request Form” may be requested if the one found in the manual is not available. All instruments should be shipped prepaid to ENMET.
Address for Service:
Michigan Location:
ENMET
Attention: Service Department
680 Fairfield Court
Ann Arbor, MI 48108
Kentucky Location:
ENMET
62 Corporate Court
Bowling Green, KY 42103
Providing the “Service Request Form” assists in the expedient service and return of your unit and failure to provide this information can result in processing delays. ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the closest tenth of an hour. All instruments sent to ENMET are subject to a minimum evaluation fee, even if returned unrepaired. Unclaimed instruments that ENMET has received without appropriate paperwork or attempts to advise repair costs that have been unanswered after a period of 60 days may, be disposed of or returned unrepaired COD and the customer will be expected to pay the evaluation fee. Serviced instruments are returned by UPS/FedEx Ground and are not insured unless otherwise specified. If expedited shipping methods or insurance is required, it must be stated in your paperwork.
NOTE: Warranty of customer installed components.
For Warranty Repairs, please reference ENMET’s “Warranty Information and Guidelines” (found earlier in this section).
Manual Revision Date – February 22, 2017
Manual Part No. – 80003-502
P a g e | 18
Mailing/Shipping Address:
ENMET
680 Fairfield Court
Ann Arbor, MI 48108
[email protected]
Product Name or Number:
Product Serial Number:
Describe Problem or Needed Service:
Service Request Form
Phone: 734.761.1270
Fax: 734.761.3220
Warranty Claim?
☐ Yes ☐ No
Billing Address:
Contact Name:
Email:
PO/Reference
#:
CUSTOMER INFORMATION
Shipping Address:
Phone #:
Fax #:
☐ COD
Card Number
Name as it Appears on
Card:
PAYMENT METHOD
☐ VISA/MasterCard
Exp. Date
☐ American Express
Security Code:
☐ UPS Ground
RETURN SHIPPING METHOD
☐ UPS 3 Day ☐ UPS Next Day ☐ UPS ND Air
Select Air Saver
UPS Account #:
☐ FedEx Ground ☐ FedEx Air
Express Saver
FedEx Account #:
Insure Shipment:
☐ Yes ☐ No
☐ FedEx Air
Overnight Std.
☐ FedEx Air 2
Day
Insurance
Amount:
$
☐ UPS 2 Day Air
☐ FedEx Air
Overnight P-1
ENMET
Service Request Form
Rev.2 – 9/15/2016
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project