Potter 50RU User guide


Add to my manuals
8 Pages

advertisement

Potter 50RU User guide | Manualzz

22318.18.05-EN

Reflective

Optical Beam Smoke Detector

User Guide

1. Installation

IMPORTANT NOTE: The infrared beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the system initiating a Fire or Fault signal

 Detector installation must comply with local regulations. UL listed products must comply with NFPA72

 Ensure clear line of sight between Detector and Reflector – it is recommended at least

0.5m radius of clear space be maintained around the centre of the beam path

 Mount securely to solid structural surfaces

 Position beam as high as possible, but with a minimum distance of 0.5m from Detector to ceiling. For installations complying with UL268/NFPA72, the maximum distance of

Detector and Reflector from the ceiling must be 10% of the distance between floor and ceiling

 Mount Detector and Reflector directly opposite each other

 Do NOT position Detector where personnel or objects can enter beam path

 Do NOT position two Detectors facing each other

 For ranges between 5m and 50m, use a 50m Detector with 1 Reflector.

 For ranges between 50m and 100m, use a 100m Detector with 4 Reflectors.

2. User Configuration Settings

Access to the configuration settings is through the back plate of the Detector Head. Factory default configuration settings are marked .

Auto Reset Fire Relay (5 seconds)

Latching Fire Relay

Fire Relay Enable, On Compensation Limit

Fire Relay Disable, On Compensation Limit

50% Threshold

35% Threshold

ON

OFF

OFF

ON

OFF OFF

OFF ON

25% Threshold

12% Threshold (Use for extreme sensitivity

ON OFF

ON ON requirements)

 The Detector is set to Latching Mode or Auto Reset Mode using DIP Switch 1. If in Auto

Reset Mode, the Detector will automatically recover from a Fire state when the fire condition has been removed. If in Latching Mode, it will remain in Fire state until either the

Detector is placed in Prism Targeting Mode or Alignment Mode, then back to Operating

Mode, OR power is removed from the Detector for 10 seconds.

 Fire Relay Enable/Disable on Compensation Limit is set with DIP Switch 2. This mode selects whether Fire activation is still enabled during an AGC Compensation Fault.

 The Sensitivity of the Detector is set using DIP Switches 3 and 4.

 Do not use the 12% or 25% Alarm threshold for UL listed 100m Detectors, as this will not conform to UL268

3. Wiring Diagram

For connection of a single conventional Detector to a zone:

Detector

Fire Relay

Trouble Relay

10.2 to 30 Volts DC (RED)

0V (BLACK)

NO (YELLOW)

COM (BLUE)

COM (WHITE)

NC (GREEN)

PSU ZONE WIRING

See note 1

EOL

Note 1 – This component is the Fire Resistor, and its value is specified by the Fire Control

Panel Manufacturer. For US installations it is typically a short circuit.

EOL – End of Line component – supplied by the Fire Control Panel manufacturer

For Analogue Addressable variants:

Fire Panel

Connections

Detector

Loop Output

Unused Address switches

Input to

Next Unit

In Line

For connection of multiple conventional Detectors to a zone:

Detector

Fire Relay

Trouble Relay

10.2 to 30 Volts DC (RED)

0V (BLACK)

NO (YELLOW)

COM (BLUE)

COM (WHITE)

NC (GREEN)

PSU ZONE WIRING

See note 1

See note 2

Detector

Fire Relay

Trouble Relay

10.2 to 30 Volts DC (RED)

0V (BLACK)

NO (YELLOW)

COM (BLUE)

COM (WHITE)

NC (GREEN)

See note 1

EOL

Note 1 – This component is the Fire Resistor, and its value is specified by the Fire Control

Panel Manufacturer. For US installations it is typically a short circuit.

Note2 – Schottky Diode (60Volt, 1 Amp typical; must be UL listed for installations meeting

NFPA72)

EOL – End of Line component – supplied by the Fire Control Panel manufacturer

4. Prism Targeting Mode

Apply power to the Detector. After 5 seconds the RED LED will flash once to indicate that the model is a 50m detector, or twice to indicate a 100m detector.

The Detector operating mode is selected using the Mode Switch, situated on the rear of the unit. It can be accessed by sliding a finger between the body of the unit and the wall.

Do NOT remove the detector from the wall when accessing the Mode Switch

Select Prism Targeting Mode by moving the Mode Switch to the upper position.

Find the prism by adjusting the horizontal and vertical thumbwheels until the AMBER LED is continuously ON. The AMBER LED will be OFF when no signal is being received, then will flash at an incrementing rate to determine the target position. The faster the flash the nearer you are to the target (prism).

At this point it is essential to test that the prism and not another surface is reflecting

the beam. Cover the prism with a non-reflective material and confirm that the AMBER LED turns OFF.

5. Alignment Mode

Select Alignment Mode by moving Mode Switch to the middle position. The Detector will automatically adjust its infrared beam power and receiver sensitivity to give an optimum receiver signal strength. The progress of this is indicated by the LEDs on the front of the detector:

CONTINUOUSLY AMBER : The Detector is not receiving a signal. Go back to prism

targeting mode.

FLASHING RED : The Detector is receiving too much signal and is attempting to reduce the infrared power output to compensate. Wait at this point until the LED is OFF, this may take up to 20 seconds depending on the distance between Detector and Prism, the shorter the distance the longer the time.

FLASHING AMBER : The Detector is receiving a weak signal and is attempting to increase the infrared power output.

OFF : The Detector has optimised the infrared power and receiver gain for the current orientation of the Detector and Prism. This does not mean that the Detector to Prism

alignment is at its optimum, i.e. if the power is too high, a misaligned Detector may be receiving a fringe reflection from another object.

FLICKERING RED/AMBER : This state can occur sometimes. It means that the infrared power is stepping through the optimum setting.

Continue to flow diagram for procedure.

Alignment Process Flow Diagram:

Return to Prism

Targeting Mode

Constant

AMBER

Amber

Reverse the direction of the thumbwheel

Repeat the process for the other thumbwheel

Select alignment mode AMBER

LED will illuminate for

5 seconds

Wait until both LED’s stop flashing (up to 30 seconds)

Slowly adjust a thumbwheel in one direction and observe the

LEDs

No

LED flashing?

Both thumbwheels adjusted?

Yes

For optimum alignment, deflection of the beam in all four planes should cause the Amber LED to flash first

Exit Alignment

Mode and enter

Operating Mode

Red

Amber

Stop turning the thumbwheel and wait for the Red LED to stop flashing

Slowly turn the thumbwheel in the same direction

LED flashing?

Neither

Stop turning the thumbwheel

Red

6. Operating Mode

Select Operating Mode by moving the Mode Switch to its lower position.

On exiting alignment mode the Detector will perform an internal calibration check. Do not

block the beam whilst this internal calibration takes place. The Amber LED will flash once a second, for up to sixty seconds, and then go out. If this fails, which would be due to bad alignment or either electrical/optical noise, the detector will indicate a Fault condition. In this case the alignment procedure must be repeated.

If the internal calibration check completes satisfactory, the Detector will now be in normal operating mode.

7. System Testing

After successful installation and alignment the System will require testing for both alarm and fault conditions.

Fault (Trouble) Test

Using a non-reflective object, quickly cover the entire prism(s). The Detector will indicate a fault within 10 seconds by activating the FAULT LED and operating the Fault Relay.

The fault condition will automatically reset when the obstruction is removed.

Alarm (Smoke) Test

Taking note of the threshold selected during installation, select obscuration mark on filter to correspond with the Detector Alarm threshold (see fig. 3).

Place the filter over the receiver optics (Top of Detector Head

 opposite end to the status indication LED’s) at the correct obscuration value determined by the threshold selected. For example, if a threshold of 35% has been selected position the filter just past the 35% obscuration value on the filter (see fig 3.). Take care not to cover the transmitter optics.

Align filter for correct obscuration/threshold setting

 Obscuration value

Receiver Optics

RED AMBER

Transmitter Optics

Alignment/Status

Indication LED’s

Fig. 3.

8. Servicing and Maintenance

During Operating Mode, the following states will be indicated:

 Normal (no Fault or Fire) – Amber LED will flash every 10 seconds (EN approved model) or not flash at all (UL approved model)

 Fire/Alarm – Red LED will be on continuously, and Fire Relay will close

 Fault – Amber LED on continuously, and Fault Relay will open

 Compensation Fault – Amber LED flashes every 2 seconds

A Compensation Fault will occur when the Detector can no longer compensate for signal loss due to dust/dirt build-up on the lenses and/or Reflector. A Compensation Fault can be cleared by cleaning the Reflector and Detector lenses using a dry lint-free cloth, and then realigning the beam. Compensation Faults can be avoided by periodic cleaning of the Reflector and Detector before compensation limit is reached.

9. Technical Data

 Operating Range (50 metre Detector)

5 to 50 metres

 Operating Range (100 metre Detector)

 Supply Voltage limits

50 to 100 metres

10.2Vdc to 30Vdc

 Quiescent Current (no LED’s illuminated) <4mA

 Power Down Reset Time

 Operating Temperature (EN)

 Operating Temperature (UL)

10 seconds

-10

C to 55C

32

F to 100F

 Tolerance to Beam Misalignment at 35% Detector  1.0, Prism  5.0

 Head Maximum Size

Width 130mm, Height 210mm, Depth 120mm

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Reliable smoke detection in challenging environments
  • Reflective beam technology for precise detection
  • Minimal maintenance and false alarms
  • Range of 5 to 50 meters (16 to 164 feet)
  • Sensitivity adjustment for various applications
  • Built-in self-test and fault monitoring
  • Easy installation and alignment
  • IP50-rated enclosure for durability

Related manuals

Frequently Answers and Questions

What are the key features of the EDWARDS 50RU?
The EDWARDS 50RU is designed for reliable smoke detection in challenging environments, utilizing reflective beam technology for precise detection with minimal maintenance and false alarms.
What is the operating range of the EDWARDS 50RU?
The EDWARDS 50RU has an operating range of 5 to 50 meters (16 to 164 feet).
How do I adjust the sensitivity of the EDWARDS 50RU?
The EDWARDS 50RU has adjustable sensitivity to suit various applications.
Does the EDWARDS 50RU have any self-monitoring features?
Yes, the EDWARDS 50RU has built-in self-test and fault monitoring capabilities.
What type of enclosure does the EDWARDS 50RU have?
The EDWARDS 50RU has an IP50-rated enclosure for durability.
Download PDF

advertisement