KNX Technical Reference Manual
ABB i-bus® KNX
KNX Sensors
KNX Technical Reference Manual
ABB i-bus® KNX
1
Quick-Start-Guide
Additional key
Set value minus (1)
Operating mode - On/Off (3)
Operate sensor 6128/01-500 as a normal sensor with the
freely programmable functions. To reach the setting level of
the 6128/01-500 press the additional key once. The
6124/01-500 is located in this level from the start.
Set value plus (2)
Fan level (4)
Use the top rocker switch (1/2) in the RTC setting level to
adjust the set value. Use the bottom rocker switch (3/4) to
adjust the operating modes. With a long press on the left
button (3) the device is switched on and off. With the right
right button you switch through the fan steps.
By pressing the additional key in the RTC setting level view
you reach the main menu
Menu
- Unit
- Contrast
- Language
- Jump-back time
- Text-change time
- Systeminfo
- Factory settings
Note
For a detailed description please read the
chapter "Operating the room thermostat".
2 | 0073-1-7704 | KNX Technical Reference Manual
2
Safety instructions
Work on the 230 V power supply system must
only be performed by specialist staff.
Disconnect the mains power supply prior to
mounting and/or disassembly!
Failure to observe the installation and
operating instructions may result in fire or
other hazards.
3
Disclaimer
The content of this printed material has been
checked for compliance with hardware and
software. However, no liability can be assumed
for any deviations that may still occur. Any
necessary corrections will be implemented in
future versions of this manual.
Please advise us of any suggestions
concerning the manual's improvement you may
have.
Technical data
Attribute
Power supply
Value
KNX
24 V DC, via the bus
Use
-5 °C to 45 °C
Storage
-25 °C to 55 °C
Transport
-25 °C to 70 °C
Protection
Ambient temperature range
IP 20, according to DIN EN 60529
Licence
KNX certified
CE marking
According to EMC and low-voltage guideline
Note
A detailed parameter description can be found in the ETS plug-in software.
KNX Technical Reference Manual | 0073-1-7704 | 3
KNX Technical Reference Manual
ABB i-bus® KNX
4
Connection
5
Dimensional drawings
Sensors
Connection to Twisted Pair
Dimensions
The sensors for installing in the frame that are
listed in this manual have the same
dimensions.
4 | 0073-1-7704 | KNX Technical Reference Manual
6
Overview of applications
Applications
KNX function
Control
Pushbutton
Control
Busch-
Room
elements with
coupler
elements for
Watchdog® ,
thermostat
bus coupler
flush-mounted
(6124/01-500),
bus coupler
Page
(incl. 6128/01-
object range
500)
(6108/03-500)
Switching, rocker total
●
●
●
-
-
See page 24
Switching rocker switch left/right
-
●
●
-
-
See page 24
Dimming rocker switch total
●
●
●
-
-
See page 24
Dimming rocker switch left/right
-
●
●
-
-
See page 25
Venetian blind switch rocker total
●
●
●
-
-
See page 25
Blind rocker switch left/right
-
●
●
-
-
See page 26
Short-long operation, rocker switch
-
●
●
-
-
See page 26
Value sender rocker switch total
-
●
●
-
-
See page 27
Value sender rocker switch left/right
-
●
●
-
-
See page 27
LED functionality
●
●
●
-
-
See page 28
Setting RTC operation mode
-
●
●
-
-
See page 28
Value sender, 2 objects, rocker
●
●
●
-
-
See page 29
●
●
●
-
-
See page 29
Step-type switch rocker switch total
-
●
●
-
-
See page 30
Step-type switch rocker switch
-
●
●
-
-
See page 30
-
●
●
-
-
See page 31
left/right
switch left/right
Light scene extension unit with
memory function
left/right
Multiple operation
Features
Control elements
Pushbutton
Control elements
Busch-Watchdog® ,
Room thermostat
with bus coupler
coupler
for bus coupler
flush-mounted
(6124/01-500),
(incl. 6128/01-500)
object range
(6108/03-500)
Temperature reading
-
-
●
-
●
RTC setting
-
-
●
-
●
Illuminated display
-
-
●
-
-
FanCoil operation for
-
-
●
-
●
-
-
●
●
●
-
-
-
●
-
heating and cooling
General KNX functions
(incl. light scenes)
Busch-Watchdog®, 4
channels
KNX Technical Reference Manual | 0073-1-7704 | 5
KNX Technical Reference Manual
ABB i-bus® KNX
7
Program Overview
7.1
Sensors
The 1gang, 2gang and 4gang control element forms the
basic sensory system of the new KNX sensor program. It
is supplied with the matching bus coupler.
6125/01-500 control element, 1gang with bus coupler
6126/01-500 control element, 2gang with bus coupler
6127/01-500 control element, 4gang with bus coupler
6 | 0073-1-7704 | KNX Technical Reference Manual
Function:
•
Switching
•
Dimming
•
Blind
•
Value transmitter, 2 objects
•
Light scene extension unit
•
LED status display
•
among others
Features:
•
Status illumination
•
Orientation illumination
•
Write-on rockers
•
Anti-theft protection
•
Freely programmable
•
Two-colour LED
7.2
Pushbutton couplers
6108/01-500
6108/02-500
6108/04-500
Design without limits
The pushbutton coupler with centre setting opens the
entire diversity of the KNX switch range.
Rocker switches from all switch ranges can now be
converted to a KNX push button with a simple push-on,
and can not only switch on and off but also dim or show
the status with an LED (6108/01-500 and 6108/05-500
only). 1gang and 2gang models for single and series
rocker switches are available.
Function:
•
Switching
•
Dimming
•
Blind
•
Value transmitter, 2 objects
•
Light scene extension unit
•
LED status display
•
among others
KNX – water protected (6108/04-500 and 6108/05-500)
The use of the pushbutton coupler also makes special
products usable for KNX. Special models for waterprotected installation allow covers from, for example, the
®
ocean flush-mounted range to be used. This makes the
KNX sensory system also suitable for use in the cellar, on
the terrace or in the commercial sector.
Temperature range: –25 °C to +45 °C.
6108/05-500
KNX Technical Reference Manual | 0073-1-7704 | 7
KNX Technical Reference Manual
ABB i-bus® KNX
7.3
Control elements
The controlelements are freely programmable and
additionally have separate logic and value objects. Ech
rocker switch can be doubly occupied. They are suitable
for Twisted Pair.
6125/02-500 control element, 1/2gang multifunction
6126/02-500 control element, 2/4gang multifunction
6127/02-500 control element, 4/8gang multifunction
6129/01-500 3gang with IR reception
8 | 0073-1-7704 | KNX Technical Reference Manual
Function:
•
Switching
•
Dimming
•
Blind
•
Value sender
•
Setting the RTC
operating mode
•
Light scene extension
unit
•
Logic functions
•
LED colour concept
•
Switching sequences
•
Multiple operation
•
and others
General functions:
•
Light scene actuator'
•
Sequence
•
Logic
•
Delay
•
Staircase lighting
•
Preset
•
Cyclical telegram
•
Flashing
•
Gate
•
Min/max value
transducer
•
Threshold value /
Hysteresis
•
PWM inverter
•
Priority
Features:
•
Function illumination
•
Orientation illumination
•
Write-on rockers
•
Anti-theft protection
•
Freely programmable
•
Colour concept
•
10-pin plug connector
•
Installed on flush-mounted insert
7.4
Movement detector
Features:
•
4 channels
•
General KNX functions incl. light
scenes
•
Opening angle 180°
•
Protection IP 20
•
1 bis 150 Lux
6122/01-500 Busch-Watchdog ® 180, flushmounted sensor
Standard select
7.4.1
6122/02-500 Busch-Watchdog ® 180, flushmounted sensor
Comfort II multi-lens
Detection levels and detection ranges
Detection range
Multi-lens
Select lens
Detection levels
7.4.2
Operating modes
The motion detector can operate in the following modes: "Signaling", "Automatic time control", "Semi-automatic" or
"Automatic". A description of the application for the movement detector is found under "Description of application".
KNX Technical Reference Manual | 0073-1-7704 | 9
KNX Technical Reference Manual
ABB i-bus® KNX
7.5
Room thermostat
The room thermostat has an LCD display which indicates
the current room temperature and the respective
operating status.
RTC function:
•
Set / actual temperature
•
Comfort/standby
•
Night mode
•
Frost protection
•
Heat protection
•
Heating
•
Cooling
•
Fan control
•
Logic functions
6124/01-500 Room thermostat
6128/01-500 Room thermostat with 2gang control element
In addition to the room thermostat function the 6128
control elements can be occupied with additional
applications.
Function:
•
Switching
•
Dimming
•
Blind
•
Value transmitter
•
Setting the RTC operating mode
•
Light scene extension unit
•
Logic functions
•
LED colour concept
•
Switching sequences
•
Multiple operation
•
and others
The flush-mounted room thermostat for the object range is
used wherever operation is not required. The control is
effected via the bus. Aside form commercially available
actuating drives the fans can be controlled with up to five
steps. This controller also has numerous additional
general KNX functions.
6108/03-500 Room thermostat for object range
10 | 0073-1-7704 | KNX Technical Reference Manual
8
Operating the room thermostat
8.1
Standard view
Alarm
8.2
Rocker switches
8.2.1
Function of rocker switches during heating
AND cooling
Text/Value display
Actual or
specified
temperature
Operating mode
Operating state
The display of the room thermostat in the standard view
shows either the actual or the specified value for the
temperature, depending on the parameterization.
The current operating state is shown in the right area of the
display and the current operating mode in the centre.
1
 Temperature  Switchover
2
3
 Comfort
 On/Off
4
 Brief press of the
button
 Temperature +
 Switchover
 Standby
 Long press of the
button
The set values for heating and cooling can be changed in
the setting level of the RTC.
The set values for heating are displayed to the right of the
symbol for "heating" and the set value for cooling to the right
of the symbol for "cooling".
The value selected is stored.
With a long press of the button the selection jumps to the
next set value. This one can now also be adjusted with a
short press of the button.
KNX Technical Reference Manual | 0073-1-7704 | 11
KNX Technical Reference Manual
ABB i-bus® KNX
8.2.2
1
3
Function of rocker switches during heating OR
cooling
 Temperature  Comfort
 On/Off
 Brief press of the
button
2
4
 Temperature +
 Standby
 Long press of the
button
The two buttons of the control element are used to operate
the room thermostat. To reach the setting level of the 6128,
press the additional key once. The adjustment is made with
the upper rocker switch of the control element. A short press
of the left side lowers the setpoint, a short press of the right
side raises the setpoint.
8.2.3
1
3
Function of the rocker switches for the fan
step
 Temperature  Comfort
 On/Off
 Brief press of the
button
2
4
 Temperature +
 FanCoil step
 Long press of the
button
If the room thermostat is programmed for the control of a fan
step, the fan step switchover is located on the right button of
the second rocker switch from the top. You switch over
between three steps and manual mode with a brief press.
The left button is used for the switchover between operating
modes comfort and standby.
12 | 0073-1-7704 | KNX Technical Reference Manual
8.2.4
In the view menu
↓
↑
Back
OK
You reach the view menu by pressing the additional key in
the setting level again.
Navigate with the top two rocker switches (see above).
Unit
Choose between °C and °F.
Contrast
The contrast can be adjusted in three steps.
Language
German, English, French
Jump-back time
Select a time between 5 seconds and 5 minutes or manual
jump-back.
Text-change time
Select a time between 3 seconds and 1 minute or inactive.
Systeminfo
Allow the current firmware version be displayed.
Factory settings
Reset the device to the factory settings. You must first
acknowledge before performing the reset.
8.3
Symbols
Standby: Standby mode lowers the
temperature below the value of
comfort mode. This saves energy
and does not cool down the room
even during an extended absence.
Comfort: Comfort mode regulates
the temperature to suit the
occupants while present. It can be
called up time-controlled or via a
telegram.
Dew point: If an appropriate
telegram is received from a dew
point sensor, the room thermostat
will display the corresponding
symbol and cease cooling and
merely protect against the heat.
Alarm: The alarm can be freely
parameterized. For example, it can
occur when an external temperature
sensor no longer sends values.
On/Off: The room thermostat can be
turned on and off. When turned off,
this icon is shown in the display. The
divice operates in frost protection
mode.
Night setback: The temperature
can be reduced during the night.
This saves energy and makes the
night's rest comfortable. The heating
starts again automatically the next
morning to reach a comfortable
temperature for rising.
Frost protection: If parameterized,
frost protection will ensure that the
temperature does not drop below
the desired value. It is the lowest
setpoint.
Heat protection: If parameterized,
heat protection will ensure that the
temperature does not exceed the
desired value. It is the highest
setpoint.
Condensate: The operation of a fan
coil may cause condensate water,
which is collected in a container. If
the fan coil sends out a telegram
when the container is full, the
symbol for condensate mode is
displayed. The room thermostat
immediately switches into heat
protection mode.
KNX Technical Reference Manual | 0073-1-7704 | 13
KNX Technical Reference Manual
ABB i-bus® KNX
9
Planner support for RTC
9.1
Operating modes
The room thermostat has four operating modes:
•
Frost protection mode (for heating): The room temperature control is inactive; heating is only carried out when the
temperature in the room drops to the point where the heating system could sustain damage through freezing.
Heat protection mode (for cooling): The room temperature control is inactive; cooling is only carried out when the
temperature has risen to the point where the heat in the room becomes unbearable.
•
Comfort mode (for heating and cooling): The setpoint for the room temperature is set to a value that makes the
temperature of the room comfortable during "normal use".
•
Standby mode (for heating): The room temperature is reduced to the point where heating costs are saved (e.g. during
temporary absence), but can be quickly raised to comfort temperature again.
Standby mode (for cooling): The room temperature is only raised to the point where energy costs are saved (e.g. during
temporary absence), but can be quickly increased to comfort temperature again.
•
Night mode (for heating and cooling): Rooms are not used for longer periods during the night hours; the room
temperature is set a comfortable night-time value and can be quickly raised again to the comfort setpoint in the morning.
A switchover between these operating modes can take place either by means of a switching telegram (parameter "Operating
mode switchover": "1 bit (3x)") or with 1-byte value telegrams (parameter "Operating mode switchover": "1 byte (2x)").
9.1.1
Operating mode switchover, 1 bit
Frost/heat protection has the highest priority; i.e., switchover to a different mode cannot take place in this case. The
frost/heat protection must first be deactivated; by closing an open window, for example. Night mode has the next highest
priority, followed by comfort mode. If none of these three operating modes are active, the room thermostat is in standby
mode.
9.1.2
Operating mode switchover, 1 byte
Two 1-byte communication objects are made available with operation mode switchover via 1 byte.
The two 1-byte communication objects have different behaviours for receipt of telegram. One object evaluates received
telegrams as "normal". This means, for example, if a comfort telegram is received, the room thermostat switches to comfort
mode. If a night telegram is received, the room thermostat switches to night mode. This object is controlled, for example, by
time switches.
The second object ("Operating mode switchover OMO") can "overwrite" the first. This means, for example, if a frost/heat
protection telegram is received, the room thermostat switches to frost or heat protection mode. If frost or heat protection is
reset after receipt of a new telegram, the room thermostat activates the mode that is pending on the "normal" object. As a
result, it is capable of memorising operating modes. This object is controlled, for example, by binary inputs that record
information from window contacts.
The following conditions apply for both 1-byte communication objects:
0 = Auto (only for "Operating mode switchover OMO“)
1 = Comfort
2 = Standby
3 = Night
4 = Frost/Heat protection
5 – 255 = not allowed
14 | 0073-1-7704 | KNX Technical Reference Manual
9.2
Temperature measurement
The room thermostat with display can record the temperature via an internal sensor. Additionally, values can be received
from an external sensor or an external temperature sensor via communication objects. The incoming values can be
monitored and, if necessary, adjusted. The functions are explained in greater detail in the following.
9.2.1
Internal temperature sensor
The device has an integrated temperature sensor. The measured value enters the control as actual value. The value can
also be shown on the display.
In addition, the measured temperature can be transferred to the bus via the 2-byte communication object "Send actual value
- temperature sensor", to be shown on the display, for example. Sending takes place in dependence of parameters "Send
actual value for change greater than" and "Send actual value cyclically". By default, both parameters are deactivated. This
means that at least one setting must be activated if the actual temperature is to be sent.
The setting "Send actual value for change greater than" has the advantage of being able to transmit the smallest change in
the measured temperature, adjustable from 0.1 k to 1.0 K, to the bus. The disadvantage is, for example, that at a setting of
0.1 K and a lot of room thermostats within an installation, the load on the bus increases.
The parameter "Send actual value cyclically" has the advantage that the current actual value is sent out continuously, even
when the measured value does not change. The disadvantage is that rapid changes may not be registered because the
cycle time selected is too large. It should also not be small because of the extreme load the bus is subjected to.
9.2.2
External temperature sensor
In open-plan offices it can be difficult to control the temperature with only a single thermostat. That is why it would be
advantageous to divide the room into zones with an additional room thermostat.
To integrate the temperature value of the additional temperature sensor into the temperature control, the parameter "Room
temperature measurement" must be set on "Internal and external". The the temperature measured inside and outside can
then be additionally weighted. The setting for weighting depend on the local circumstances. If the room thermostat and the
additional measuring sensor are positioned equal distances from the heater, in the case of panel heaters, a 50% / 50%
setting should provide good control results.
9.3
Monitoring
The "Temperature measurement monitoring" parameter specifies whether the external temperature sensor and the outside
temperature are to be monitored. This means that the room thermostat has to receive at least one telegram with the current
temperature on the associated communication object within an adjustable time ("Monitoring time of external temperature"
and "Monitoring time of outside temperature").
If no telegram is received during monitoring time, the room thermostat assumes that the measuring sensor for the outside
temperature or external temperature is defective or no longer connected to the bus.
The room thermostat will then terminate its control and send a predefined control value ("Control value during temperature
measurement error") so that the room to be controlled does not overheat or cool down. This control value is sent out until the
room thermostat again receives a temperature telegram via the bus and reactivates the control.
KNX Technical Reference Manual | 0073-1-7704 | 15
KNX Technical Reference Manual
ABB i-bus® KNX
9.3.1
Adjustment
If the measured temperature is distorted, such as by the inherent heat of the bus coupler, an "Offset room temperature
measurement" can be set.
If additional external temperature recording has been activated and the measured value becomes distorted through the
influence of cold or heat, here, too, an offset can be entered.
9.4
Controller
The room thermostat can be used exclusively for heating, exclusively for cooling or for heating and cooling.
If the room thermostat is to heat or cool, the switchover from heating to cooling or cooling to heating can occur automatically
by means of the room thermostat. The controller detects automatically whether a control value for heating or cooling is to be
sent out. If the automatic switchover is not required, the switchover between heating and cooling can take place by means of
an external, central control via the 1-bit object "Switchover heating/cooling". In this setup, the heat and cooling icons are
continuously displayed in the respective mode. The object is enabled via parameter "Switchover between heating/cooling".
The control value for heating and/or cooling can be sent out on a common communication object "Heating/cooling control
value" or on two individual communication objects "Heating control value" and "Cooling control value". If a common object is
used, it may be necessary to inform the actuator whether the control value is for heating or cooling. For this, a 1-bit
communication object "Switchover heating/cooling" can be enabled via parameter "Switchover between heating and cooling"
with setting "Automatic and sending". For activation of heating operating mode a "1" is sent to the bus, for activation of
cooling mode a "0".
A common communication object for heating and cooling is required to activate two two-pipe systems, i.e., the same pipeline
is used for heating and cooling. Two single communication objects are used for four-pipe systems. Heating and cooling each
have their own pipeline system.
Parameter "Number of output channels" specifies whether an object ("1 channel (two-pipe system) for heating and cooling")
or two objects ("2 channels (four-pipe system) for heating and cooling") are to be displayed.
Separate control types can be configured each for heating and cooling. One of the following control types can be selected:
•
2-point
•
PWM
•
Continuous
•
Fan coil
The individual control types are described in greater detail in the following.
16 | 0073-1-7704 | KNX Technical Reference Manual
9.4.1
2-point controller
A 2-point controller has two output states that alternate in dependence of the actual value. If the actual value is above the
parameterised setpoint, control value "0" is sent on the bus. If the actual value is below the parameterised setpoint, control
value "1" is sent.
A 2-point controller should be used when the control value is to alternate only between the two states ON and OFF, such as
an electrothermal valve that is connected to a switch actuator, for example. A 2-point controller can quickly correct control
variations in case of large changes in the control variable, but never comes to rest.
To avoid rapid oscillations of the output states, the 2-point controllers always have a built-in hysteresis that varies around
the setpoint. The hysteresis can have different size parameters. For example, if the setpoint during heating mode is 21 °C
and the hysteresis is 1.0 K, the controller switches on when the value falls below 20.5 °C and switches off again when
exceeding 21.5 °C. The "Hyteresis" parameter to be set, on the one hand responds to how quickly the heating can heat the
room or how quickly the air-conditioning cools the room, and on the other hand to the desired temperature of the people in
the room. The hysteresis should not be set too small, otherwise the switching actuator will constantly open and close. The
hysteresis should also not be set too large, otherwise the temperature fluctuations in the room will be too large.
9.4.2
Continuous controller
A continuous controller has a continuously changing control value which can accept values between 0 and 100%. For the
KNX this control value signal is converted to a 1-byte value, which means that control value 0% corresponds to value "0" and
control value 100% to value "255".
Continuous controllers with a 1-byte control value, for example, can be used to activate electromotive actuating drives. They
translate the value received directly into the valve position via an installed motor. This results in optimum control.
The 1-byte control value of a continuous controller can also be sent to KNX heating actuators which convert the 1-byte signal
into a PWM size. This allows electrothermal valves to be activated. Here it is practical to limit the dynamic range since
electrothermal valves require time to open and close. This takes place via parameters "Minimum control value" or "Maximum
control value". If, for example, a maximum control value of 80% is specified, the control will always automatically send the
value 255 when the control value of 204 has been exceeded.
To protect the bus from unnecessary loads the change of the control value that is permitted to be sent to the bus can be set.
The setting is in percent. The control value sent, unless it has changed, is specified by means of a cycle time. The cycle time
selected should not be too small (e.g. every 10 min.).
KNX Technical Reference Manual | 0073-1-7704 | 17
KNX Technical Reference Manual
ABB i-bus® KNX
9.4.3
PWM controller
The PWM controller has the same continuous control as the continuous controller. The difference is that with a PWM
controller the 1-byte control value (0...255) is converted into an On/OFF switching relationship (0 and 1). If, for example, a
control value of 70% is to be issued, at a pre-set cycle time of 10 minutes the switch-on time will be 7 minutes and the
switch-off time 3 minutes.
This transfers the advantages of the continuous control (control at the desired setpoint, no overshooting) to drives which are
designed only for On/Off switching signals, such as electrothermal drives.
To optimise the controlling characteristics of the heating/cooling system, the "PWM control value cycle time" can be set. To
set a practical cycle time, the type of heating or cooling as well as the actuating drive used should be taken into
consideration. The following recommendations can be used:
•
Electrothermal actuating drive
To fully open an electrothermal control valve takes approximately 2-3 minutes. That is why a cycle time of less than 15
minutes is not practical.
•
Floor heating
The time constant of floor heating is rather large. That is why a cycle time of 20 minutes is sufficient.
•
Hot water heating
Her electrothermal drives are generally used. A cycle time of 15 minutes will produce excellent control results.
•
Electro-convector heating
Cycle times of between 10 and 15 minutes are recommended, depending on the electric heating system and the spatial
circumstances.
9.4.4
Fan coil
With the selection of fan coil for "Control types" the control value output takes place in the same way as described under
Continuous control.
With 'fan coil' there is the additional option of activating fan stages via a 1-byte or three 1-bit communication objects.
The added connection of the fan stages heats or cools the room correspondingly faster.
Which fan stage is to be active at which control value is specified on a separate tab "Fan coil heating" or "Fan coil cooling".
Here it should be ensured that threshold value stage 1 must always be smaller than threshold value stage 2, which in turn
must be smaller than threshold value stage 3.
9.4.5
Control parameter for PWM controller and continuous controller (Fan coil)
For continuous control behaviour and for a switching PWM controller, the preset control parameters can be used via the
installation type of the heating or cooling system. If different control parameters are required, they should be set individually
via user parameterization. User parameterization should only be used by persons with adequate experience in control
technology.
The setting "User parameterization" can be used to set the "Proportional range (Xp)" and the "Readjust time (Tn". The
proportional range lies below and above the preset setpoint and determines the regulating speed. The readjust time amounts
to three times the delay time. The delay time is determined by the reversing tangent of the heating curve of the room. In
general, the more inactive the overall system, the larger the parameterization values should be.
18 | 0073-1-7704 | KNX Technical Reference Manual
9.4.6
Two-stage heating / cooling
In specific instances such as when using underfloor heating, it may be necessary to install a quick additional stage for the
heat control in order to warm up the room rapidly. When the room thermostat is preset to "Additional heating stage active", it
has a second heating system with switching control that regulates with the 1-byte values 0% and 100%.
The parameters "Distance of the additional stage" and "Hysteresis (one-sided)" enable you to specify when the additional
stage switches on and off. For instance, if the setpoint for the additional stage is 18 °C and the hysteresis is 0.5 K (onesided), the controller switches on at 18 °C and off again at 18.5 °C.
The settings for the additional heating stage apply equally to the additional cooling stage, the only difference being that in
the case of cooling, when a set temperature has been exceeded, an additional cooling stage is switched on to cool the room
faster.
Since several actuating drives close (opened de-energised) at a 1-bit value of "1" or a 1-byte value of "255" and open at "0",
the mode of the control value can be changed via "Invert control value".
9.5
Set values
The room thermostat can operate with dependent or individual set values. Both versions are explained in greater detail in the
following.
9.5.1
Dependent setpoints
In case of dependent setpoints there are two basic setpoints, one for heating ("Heating setpoint comfort operation" and one
for cooling ("Cooling setpoint comfort operation").
The settings "...lowering standby/night mode" or "...raising standby/night mode". This means, for example, when 21 °C has
been set for "Heating setpoint comfort mode" and 2 K was specified for "Lower heating setpoint standby", the heating
setpoint in standby mode is lowered by 2 K to 19 °C. If 4 K has been specified for "Lower heating setpoint standby", the
setpoint for "Heating setpoint for night mode" is 17 °C.
The dependence of the setpoints are also maintained after a manual setpoint shift. For example, when the user has effected
a setpoint shift of 1 K upward to 22 °C for the parameterized temperature "Heating setpoint comfort mode", this value will be
lowered by 2 K to 20 °C when comfort mode is activated. When night mode is called up, the value will be lowered by 4 K,
resulting in a setpoint of 18 °C.
The user can manually change the parameterized setpoints via the two buttons "Raise temperature" or "Lower temperature".
The change between "Heating setpoint comfort mode" and Cooling setpoint comfort mode" is made via a long press (approx.
1 sec.) of button "Raise temperature" to heating setpoint and on button "Lower temperature" to cooling setpoint.
The two specified setpoints for heating and cooling can also be changed as often as desired via the bus without the ETS.
Here a 2-byte temperature value must be sent to the communication object "Base setpoint - control". Depending on whether
heating or cooling is currently active, the value is stored as "Heating setpoint comfort mode" or "Cooling setpoint comfort
mode". The values received are stored in the memory of the device and are retained in case of bus power failure and
subsequent return of bus voltage. This makes it possible to send new base setpoints to the device via a visualization when
the use of a room changes, for example.
New parameterization is not required. In case of a manual adjustment and dependent setpoints the reference base setpoint
is taken into consideration. This is used to specify whether the base setpoint refers to the comfort temperature for heating,
cooling or the mid-range temperature between heating and cooling.
"Setpoint heating" is the default setting. In regions where the cooling function is more important, it is recommended that you
change this parameter to "Setpoint cooling". This makes it easier to set the room thermostat and raise the cooling setpoint
(standby temperature cooling and night setback cooling).
KNX Technical Reference Manual | 0073-1-7704 | 19
KNX Technical Reference Manual
ABB i-bus® KNX
9.5.2
Individual setpoints
When individual setpoints are used, individual setpoints are defined for each operating mode ("Heating setpoint comfort
mode", Heating setpoint standby", "Heating setpoint night mode", "Cooling setpoint standby" and "Cooling setpoint night
mode".
Different to the dependent setpoints, the individual setpoints are also maintained after a manual setpoint shift. For example,
when the user has effected a setpoint shift of the parameterized temperature "Heating setpoint comfort mode" upward or
downward, the parameterized value "Heating setpoint standby" will always be called up when standby mode is activated.
This means that only the fixed setpoints that are stored will be called up for the individual operating modes.
The user can manually change the parameterized setpoints via the two buttons "Raise temperature" or "Lower temperature".
The change between "Heating setpoint comfort mode" and "Cooling setpoint comfort mode" is made via a long press
(approx. 1 sec.) of button "Raise temperature" to heating setpoint and on button "Lower temperature" to cooling setpoint.
The specified setpoints can be changed as often as desired via the bus also without the ETS. For this, a 2-byte temperature
value must be sent to the corresponding communication object "Setpoint heating comfort", "Setpoint heating standby",
Setpoint heating night mode", "Setpoint frost protection", "Setpoint cooling comfort", "Setpoint cooling standby", "Setpoint
cooling night mode" or "Setpoint heat protection". The values received are stored in the memory of the device and are
retained in case of bus power failure and subsequent return of bus voltage. This makes it possible to send new setpoints to
the device via a visualization when the use of a room changes, for example. New parameterization is not required.
9.5.3
Minimum distance
The adjustable parameter "Minimum distance between heating and cooling" is active both for the dependent and the
individual setpoints.
The minimum distance is always between "Heating setpoint comfort mode" and "Cooling setpoint comfort mode". It serves as
a buffer zone to prevent the the two setpoints from interfering with each other.
Example:
Individual setpoints has been selected. The "Heating setpoint comfort mode" is 21 °C and the "Cooling setpoint comfort
mode" is set on 26 °C. The dead zone between heating and cooling is 3 K. If a heating setpoint is now shifted upwards, the
dead zone also shifts upwards. If the shift exceeds a temperature of 23 °C, the "Cooling setpoint comfort mode" will also
shift upwards so that a minimum distance of 3 K is always guaranteed between heating and cooling.
If a cooling setpoint is shifted downwards, the dead zone also shifts downwards. If the shift exceeds a temperature of 24 °C,
the "Heating setpoint comfort mode" will also shift downwards so that a minimum distance is also guaranteed in this case.
20 | 0073-1-7704 | KNX Technical Reference Manual
9.6
Fan coil, general
The ventilation convectors, also called fan convectors or fan coil units, are used for decentralized heating and cooling. They
are installed in the room and supplied via a central heating and cooling system. There are two-pipe and four-pipe systems.
There are multi-stage ventilators within a fan coil unit that enable fast adjustment to the room temperature to be made
according to individual requirements. The fan coil room thermostat with display can activate up to three fan stages either
manually or automatically.
The fan stages can be activated in three ways:
•
via 1-bit values,
i.e., a 1-bit communication object "Fan coil stage ... switching" is made available for each fan stage. This required for
"normal switch actuators. ((When using KNX switch actuators and fan coil units, the connecting instructions for the fan
coil unit are to be observed).
•
via 1-byte object as numerical value 0-3,
i.e. there is a 1-byte communication object "Fan stage manual 1 byte" which is connected with a corresponding
communication object of a fan coil actuator. Here the value 0 = OFF 1 = stage 1 2 = stage 2 3 = stage 3
•
via 1-byte object as constant value 0-100%,
i.e. there is a 1-byte communication object "Fan stage manual 1 byte" which is connected with a corresponding
communication object of a fan coil actuator. During manual stage switchover the stage threshold values that are set on
tab heating or cooling are sent out. In heating mode the threshold values for heating, in cooling mode the threshold
values for cooling. To ensure that the fan coil unit switches the fan stages, the parameters of the associated fan coil
actuator must be set accordingly.
Via parameter "Evaluate fan stage status byte" a 1-byte communication object "Fan coil operating state", which is connected
with a corresponding object of a fan coil actuator, can be enabled. This allows the fan coil room thermostat evaluate which
fan stage is actually active on the fan coil actuator. The display corresponds to the value of the communication object (0 =
OFF, 1 = stage 1, 2 = stage 2, 3 = stage 3).
The parameter "Evaluate operation status byte" activates a 1-bit communication object "Receive during operation - actuator
monitoring". Cyclical telegrams from the fan coil actuator can be received and evaluated on this object. This allows the room
thermostat to check whether the fan coil actuator is still operating and can be activated. If the fan coil actuator has a problem
and can no longer send cyclical telegrams, the room thermostat will indicate this on the display with the "Error" symbol. If the
error on the fan coil actuator has been rectified and cyclical telegrams can be received, the "Error" on the display is removed
and the room thermostat will again function as "Normal".
The cycle time setting "In operation" in the fan coil actuator should be selected at least twice as large as the monitoring time
in the room thermostat ("Sending cycle time of actuator in sec."). A practical cycle time for the actuator is approximately 60
seconds with a monitoring time of 120 seconds for the room thermostat.
To prevent an excessive noise level in hotel rooms during the silent period in the night, a "Stage limitation for night mode"
can be set. This means that during night mode only the fan stage that has been set is automatically switched to. All fan
stages can be activated again when changing to a different operating mode.
Parameter "Stage limitation for night mode" can be used to set a limit to "Stage 2" or "Stage 1" or the ventilation can be
completely deactivated.
KNX Technical Reference Manual | 0073-1-7704 | 21
KNX Technical Reference Manual
ABB i-bus® KNX
9.6.1
Summer compensation
To save energy and to maintain a reasonable temperature difference when entering an air-conditioned building, the room
temperature should be adjusted in relation to the external temperature (summer compensation according to DIN 1946). The
room temperature is raised by adjusting the "Cooling setpoint comfort mode".
Raising the room temperature does not, however, mean that you heat up the room. Rather the adjustment is intended to
allow the room temperature without cooling to increase to a specified value. This prevents the cooling system from further
reducing the room temperature to 24 °C with an external temperature of 35 °C.
However, the activation of summer compensation makes an external temperature sensor necessary that sends its measured
value to the KNX for evaluation by the room thermostat with display.
The following parameters are available for summer compensation:
•
"Summer compensation lower outside temperature value"
•
"Summer compensation upper outside temperature value"
•
“Summer compensation lower setpoint offset"
•
“Summer compensation upper setpoint offset"
The value of the lower and upper temperature is used to specify from and to which temperature value a setpoint correction is
to be made.
The lower and upper setpoint offset is used to specify by how many Kelvin the setpoint specified in the parameters or by the
user via a manual shift is to be adjusted during summer compensation.
Typical values for the summer compensation are:
•
20 °C: lower outside temperature value
•
32 °C: upper outside temperature value
•
0 K: lower setpoint offset
•
4 K: upper setpoint offset
That means that a flowing setpoint increase of 0 to 4 K occurs if the outside temperature increases from 20°C to 32°C.
Example:
In the lower diagram 25 °C has been parameterized for "Cooling setpoint comfort". When the outside temperature rises, the
parameterized setpoint is raised starting from an outside temperature of 20 °C flowing from 25 °C to 29 °C. The 29 °C are
reached at an outside temperature of 32 °C. After this the setpoint is no longer raised even though the outside temperature
rises.
Note:
When compensation is active, CO is shown on the display of the room thermostat.
22 | 0073-1-7704 | KNX Technical Reference Manual
Objects, room thermostat
No.
Object name
Data type
Flags
0
Control ON/OFF
1 Bit / DPT_switch
C, W, T, U
0
Current temperature
2 Byte / DPT_Value_2_Float
C, W, U
0
Fault, actual temperature
1 Bit / DPT_switch
C, W, T, U
0
Actual setpoint
2 Byte / DPT_Value_2_Float
C, T
0
Frost/heat protection
1 Bit / DPT_switch
C, W, T, U
0
Comfort
1 Bit / DPT_switch
C, W, T, U
0
Night mode
1 Bit / DPT_switch
C, W, T, U
0
Heating control value
1 Bit / DPT_switch
C, W, T, U
1 Byte / DPT_scaling
0
Status heating
1 Bit / DPT_switch
C, W, T, U
0
Additional Heating Stage
1 Bit / DPT_switch
C, T
1 Byte / DPT_scaling
0
Cooling control value
1 Bit / DPT_switch
C, W, T, U
1 Byte / DPT_scaling
0
Status cooling
1 Bit / DPT_switch
C, W, T, U
0
Additional Cooling Stage
1 Bit / DPT_switch
C, T
1 Byte / DPT_scaling
0
Switchover heating (1) / cooling (0)
1 Bit / DPT_switch
C, W, T, U
0
Basic set value heating frost protection
2 Byte / DPT_Value_2_Float
C, W, T, U
0
Basic set value heating comfort
2 Byte / DPT_Value_2_Float
C, W, T, U
0
Basic set value heating standby
2 Byte / DPT_Value_2_Float
C, W, T, U
0
Basic set value heating night mode
2 Byte / DPT_Value_2_Float
C, W, T, U
0
Basic set value cooling frost protection
2 Byte / DPT_Value_2_Float
C, W, T, U
0
Basic set value cooling comfort
2 Byte / DPT_Value_2_Float
C, W, T, U
0
Basic set value cooling standby
2 Byte / DPT_Value_2_Float
C, W, T, U
C, W, T, U
0
Basic set value cooling night mode
2 Byte / DPT_Value_2_Float
0
Reset onsite operation
1 Bit / DPT_switch
C, W, U
0
Dew point alarm
1 Bit / DPT_switch
C, W, U
0
Condensate water alarm
1 Bit / DPT_switch
C, W, U
0
Outside temperature
2 Byte / DPT_Value_2_Float
C, W, U
0
Shading
1 Bit / DPT_updown
C, T
0
Summer compensation
1 Bit / DPT_switch
C, T
0
Units switchover
1 Bit / DPT_switch
C, W, U
0
Current set value for heating
2 Byte / DPT_Value_2_Float
C, W, T, U
0
Current set value for cooling
2 Byte / DPT_Value_2_Float
C, W, T, U
0
Basic set value for group master operation
2 Byte / DPT_Value_2_Float
C, W
0
Superimposed operating mode
8 Bit / DPT_HVAC_mode
C, W, T, U
0
Operating mode
8 Bit / DPT_HVAC_mode
C, W, T, U
0
FanCoil manual/automatic
1 Bit / DPT_switch
C, W, T, U
0
FanCoil step
8 Bit / DPT_Value_1_u_Ucount
C, W, T, U
KNX Technical Reference Manual | 0073-1-7704 | 23
KNX Technical Reference Manual
ABB i-bus® KNX
10
Description of application
10.1
Switching, rocker total
With the "Switch, rocker total" application, an operation of the right or left side of the rocker sends out a switch telegram.
The "Switch, rocker total" application differentiates here between whether the rocker is operated on the left or right side.
Switching objects, rocker total
No.
Object name
Data type
Flags
0
Switching
1 Bit EIS1 / DPT 1.001
C, W, T, U
10.2
Switching, rocker left/right
With the application "Switching, rocker left/right" a switch telegram is sent when the rocker is actuated and/or released.
"Rocker left/right" does not differentiate whether the rocker is actuated on the right or the left side. In each case, the
application makes a separate set of parameters and communication objects available for the right and left side of the rocker.
The application enables a switching function to be implemented with one side of the rocker and to assign an additional
"button-oriented" function to the other side of the rocker.
Switching objects, rocker left/right
No.
Object name
Data type
Flags
0
Switching
1 Bit EIS1 / DPT 1.001
C, W, T, U
10.3
Dimming, rocker total
With the "Dimming, rocker total" application, a rocker has communication objects for switching and for dimming. A distinction
is made between short and long button contact.
The "Dimming, rocker total" application differentiates between whether the rocker is operated on the left or right side. The
"Principle of operation of the rocker for …" parameter allows adjustment of whether the left or right side switches on or off or
whether it is dimmed brighter or darker.
Dimming objects, rocker total
No.
Object name
Data type
Flags
0
Switching
1 Bit EIS2 / DPT 1.001
C, W, T, U
1
Relative dimming
4 Bit EIS2 / DPT 3.007
C, T
24 | 0073-1-7704 | KNX Technical Reference Manual
10.4
Dimming, rocker left/right
With the "Dimming, rocker left/right" application, a rocker switch has communication objects for switching and for dimming. A
distinction is made between short (switching) and long (dimming) button contact.
The "Dimming, rocker left/right" application does not differentiate between whether the rocker is operated on the left or right
side. In each case, the application makes a separate set of parameters and communication objects available for the right
and left side of the rocker.
The application makes it possible to dim a light via one side of the rocker and to assign an additional "button-orientated"
function to the other side.
Dimming objects, rocker left/right
No.
Object name
Data type
Flags
0
Switching
1 Bit EIS2 / DPT 1.001
C, W, T, U
1
Relative dimming
4 Bit EIS2 / DPT 3.007
C, T
10.5
Blind, rocker total
Via the application "Blind, rocker total", blind movement and/or slat adjustment commands can be sent to connected shutting
actuators with a short or long contact of the rocker. A short button contact always triggers a slat adjustment or stop
command and a long button contact always triggers a move command.
The control always remembers the last action performed on the side of the rocker switch that is assigned with the "Blind,
rocker total" application. If a blind was lowered and halted at half height via a short button contact, then a renewed long
button contact will raise the blind.
Blind objects, rocker total
No.
Object name
Data type
Flags
0
Adjusting(1 Bit)
1 Bit EIS7 / DPT 1.008
C, T
0
Adjusting (1 Byte)
1 Byte EIS6 / DPT 5.001
C, T
1
Move (1 Bit)
1 Bit EIS7 / DPT 1.007
C, T
1
Move(1 Byte)
1 Byte EIS6 / DPT 5.001
C, T
KNX Technical Reference Manual | 0073-1-7704 | 25
KNX Technical Reference Manual
ABB i-bus® KNX
10.6
Blind, rocker left/right
Via the application "Blind, rocker left/right", blind movement and/or slat adjustment commands can be sent to connected
shutting actuators with short or long actuation of the rocker. A short button contact always triggers a move command and a
long button contact always triggers a slat adjustment or stop command.
The application "Blind, rocker left/right" makes a separate set of parameters and communication objects available in each
case for the right or left side of the rocker. This facilitates control of a Venetian blind with one side of the rocker and
assigning an additional "Rocker, left/right" function to the other side of the rocker.
The control always remembers the last action performed on the side of the rocker that is assigned with the "Blind, rocker
left/right" application. If a blind was lowered and halted at half height via a long button contact, then a renewed short button
contact will raise the blind.
Blind objects, rocker left/right
No.
Object name
Data type
0
Adjusting (1 Bit)
1 Bit EIS7 / DPT 1.007
C, W, T, U
0
Adjusting(1 Byte)
1 Byte EIS6 / DPT 5.001
C, W, T, U
1
Moving(1 Bit)
1 Bit EIS7 / DPT 1.008
C, W, T, U
1
Moving(1 Byte)
1 Byte EIS6 / DPT 5.001
C, W, T, U
10.7
Flags
Short/long operation, rocker left/right
Via the application "Short/long operation, rocker left/right", different values can be sent out with a short and/or long actuation
of the rocker switch.
The "Short/long operation, rocker left/right" application does not differentiate between whether the rocker is actuated on the
left or right side. In each case, the application makes a separate set of parameters and communication objects available for
the right and left side of the rocker.
The application facilitates making two separate functions available on one side of the rocker that can be called up via a short
or long button contact and assigning the other side of the rocker switch with an additional "button-orientated" function.
Short/long operation objects, rocker left/right
No.
Object name
Data type
Flags
0
Adjusting(1 Bit)
1 Bit EIS7 / DPT 1.007
C, W, T, U
0
Adjusting(1 Byte)
1 Byte EIS6 / DPT 5.001
C, W, T, U
1
Moving (1 Bit)
1 Bit EIS7 / DPT 1.008
C, W, T, U
1
Moving (1 Byte)
1 Byte EIS6 / DPT 5.001
C, W, T, U
26 | 0073-1-7704 | KNX Technical Reference Manual
10.8
Value sender, rocker total
With the "Value sender, rocker total" application, a telegram with the predefined value is sent out at an actuation of the right
or left side of the rocker.
The "Value sender, rocker total" application differentiates here between whether the rocker is actuated on the left or right
side.
Value sender objects, rocker total
No.
Object name
Data type
Flags
0
Switching value(1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, T, U
0
Switching value(1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T, U
0
Switching value(1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W, T, U
0
Switching value(2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W, T, U
0
Switching value(2 Byte Signed)
2 Byte EIS10 / DPT 7.001
C, W, T, U
0
Switching value (2 Byte Unsigned)
2 Byte EIS10 / DPT 8.001
C, W, T, U
0
Switching value (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W, T, U
0
Switching value (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, W, T, U
0
Switching value (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, W, T, U
10.9
Value sender, rocker left/right
With the "Value sender, rocker left/right" application, a telegram with a predefined value is sent out at an actuation or release
of the rocker.
The "Value sender, rocker left/right" application does not differentiate between whether the rocker is actuated on the left or
right side. In each case, the application makes a separate set of parameters and communication objects available for the
right and left side of the rocker.
The application enables realising a switching function via one rocker side, while the other rocker side can be assigned with
an additional "button-orientated" function.
Value sender objects, rocker left/right
No.
Object name
Data type
Flags
0
Switching (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, T, U
0
Switching (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T, U
0
Switching (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W, T, U
0
Switching (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W, T, U
0
Switching (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, W, T, U
0
Switching (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W, T, U
0
Switching (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W, T, U
0
Switching (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, W, T, U
0
Switching (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, W, T, U
KNX Technical Reference Manual | 0073-1-7704 | 27
KNX Technical Reference Manual
ABB i-bus® KNX
10.10
LED function
With the "LED function" application, the LED of the rocker can be used for orientation lighting, for status indication or for
function display. The LED can light up in different colours. The LED can also flash for alarm display and/or scene storage
display.
LED function objects
No.
Object name
Data type
Flags
0
Status (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
0
Status (1 Byte 0..100 %)
1 Bit EIS6 / DPT 5.001
C, W, U
1
Day / Night mode (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
2
Proximity (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
3
Alarm (DPT_Alarm)
1 Bit / DPT_Alarm
C, W, U
4
Scene storage (DPT_Scene_Control)
1 Byte / DPT 18.001
C, W, U
10.11
Setting RTC operation mode
With the "Setting the RTC operation mode" application, an operation mode switchover for connected room temperature
controllers can be carried out via an actuation of a rocker side.
Depending on the setting of the "Object type for output" parameter, the application offers either three 1-bit communication
objects "Operation mode comfort", "Operation mode night", and "Operation mode frost" or a 1-byte communication object
"Operation mode".
The selection "1-bit" is used for the control of room temperature controllers that have 1-bit communication objects for
operation mode switchover. The "1-byte" selection is used for the control of room temperature controllers that have a 1-byte
communication object for operation mode switchover to KNX. In this case, the values mean
0 = Auto
1 = Comfort
2 = Standby
3 = Night
4 = Frost / Heat protection
The function can be temporarily blocked via a 1-bit "Enable" communication object.
Setting RTC operation mode objects
No.
Object name
Data type
Flags
0
Enable
1 Bit EIS1 / DPT 1.001
C, W, U
1
Operation mode Comfort(1 Bit)
1 Bit EIS1 / DPT 1.001
C, T
2
Operation mode Night(1 Bit)
1 Bit EIS1 / DPT 1.001
C, T
3
Operation mode Frost(1 Bit)
1 Bit EIS1 / DPT 1.001
C, T
4
Operation mode (1 Byte)
1 Byte / DPT 20.102
C, T
28 | 0073-1-7704 | KNX Technical Reference Manual
10.12
Value sender, 2 objects, rocker left/right
With the "Value sender, 2 objects, rocker left/right" application, two telegrams with predefined values from two different
communication objects can be sent out by actuation and/or upon release of the rocker.
The application "Value sender, 2 objects, rocker left/right" makes a separate set of parameters and communication objects
available in each case for the right or left side of the rocker.
For example, the application facilitates the sending out of a switching function and a floating point value with the actuation of
one rocker side and assigning an additional "button orientated" function to the other side of the rocker.
Value sender objects, 2 objects, rocker left/right
No.
Object name
Data type
Flags
0
Switching (rising flank) (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, T, U
0
Switching (rising flank) (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T, U
0
Switching (rising flank) (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W, T, U
0
Switching (rising flank) (2 Byte Float)
2 Byte EIS5 / DPT 1.xxx
C, W, T, U
0
Switching (rising flank) (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, W, T, U
0
Switching (rising flank) (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W, T, U
0
Switching (rising flank) (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W, T, U
0
Switching (rising flank) (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, W, T, U
0
Switching (rising flank) (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, W, T, U
1
Switching (falling flank) (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, T, U
1
Switching (falling flank) (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T, U
1
Switching (falling flank) (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W, T, U
1
Switching (falling flank) (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W, T, U
1
Switching (falling flank) (2 Byte Signed)
2 Byte EIS10 / DPT 7.001
C, W, T, U
1
Switching (falling flank) (2 Byte Unsigned)
2 Byte EIS10 / DPT 8.001
C, W, T, U
1
Switching (falling flank) (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W, T, U
1
Switching (falling flank) (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, W, T, U
1
Switching (falling flank) (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, W, T, U
10.13
Light scene extension unit with memory function
Via the application "Light scene extension unit with memory function", a predefined light scene number is called up when the
rocker is actuated.
The application "Light scene extension unit with memory function" makes a separate set of parameters and communication
objects available in each case for the right or left side of the rocker.
The application facilitates calling up a light scene via a rocker side while the other rocker side can be assigned an additional
"button orientated" function.
The user has the option to trigger a light scene memory command with a long button contact.
Light scene extension unit objects with memory function
No.
Object name
Data type
Flags
0
Switching
1 Byte EIS1 / DPT 1.001
C, W, T, U
KNX Technical Reference Manual | 0073-1-7704 | 29
KNX Technical Reference Manual
ABB i-bus® KNX
10.14
Step switch, rocker total
The application "Step switch, rocker total" facilitates step-type switching. This means that the user can trigger different
switching processes with each new operation of the left or right side of the rocker.
Example:
First operation (right rocker side) switches lamp 1 on.
Second operation (right rocker side) switches lamp 1 off and lamp 2 on.
Third operation (right rocker side) switches lamp 2 off and lamp 3 on.
Fourth operation (left rocker side) switches lamp 3 off and lamp 2 on.
Fifth operation (left rocker side) switches lamp 2 off and lamp 1 on.
etc.
The application differentiates between whether the left or right side of the rocker was operated. Depending on the setting,
one lower or one higher step can be switched to.
Up to five switching steps can be activated.
Step switch objects, rocker total
No.
Object name
Data type
Flags
0
Switching step 1
1 Bit EIS1 / DPT 1.001
C, W, T
1
Switching step 2
1 Bit EIS1 / DPT 1.001
C, W, T
2
Switching step 3
1 Bit EIS1 / DPT 1.001
C, W, T
3
Switching step 4
1 Bit EIS1 / DPT 1.001
C, W, T
4
Switching step 5
1 Bit EIS1 / DPT 1.001
C, W, T
10.15
Step switch, rocker left/right
The application "Step switch, rocker left/right" facilitates step-type switching. This means that the user can trigger different
switching processes with each new operation of the rocker switch.
Example:
First operation switches lamp 1 on.
Second operation switches lamp 1 off and lamp 2 on.
Third operation switches lamp 2 off and lamp 3 on.
Fourth operation switches lamp 3 off and lamp 1 on.
etc.
Up to five switching steps can be activated.
In each case, the application "Step switch, button oriented" makes a separate set of parameters and communication objects
available for the right or left side of the rocker.
The application enables realising switching functions via one rocker side while the other rocker side can be assigned with an
additional "button orientated" function.
Step switch objects, rocker left/right
No.
Object name
Data type
Flags
0
Switching step 1
1 Bit EIS1 / DPT 1.001
C, W, T
1
Switching step 2
1 Bit EIS1 / DPT 1.001
C, W, T
2
Switching step 3
1 Bit EIS1 / DPT 1.001
C, W, T
3
Switching step 4
1 Bit EIS1 / DPT 1.001
C, W, T
4
Switching step 5
1 Bit EIS1 / DPT 1.001
C, W, T
30 | 0073-1-7704 | KNX Technical Reference Manual
10.16
Multiple operation, rocker left/right
With the "Multiple actuation, rocker left/right" application, a differentiation can be made between a single, double, triple,
quadruple or quintuple actuation of the rocker. Different values can be sent out for every operation: single, double, triple,
quadruple, or quintuple.
The application "Multiple actuation, rocker left/right" makes a separate set of parameters and communication objects
available in each case for the right or left side of the rocker. It is therefore possible to realise a multiple operation via one
side of the rocker and assigning a "button-orientated" function to the other side of the rocker.
Multiple actuation objects, rocker left/right
No.
Object name
Data type
Flags
0
Switching 1, multiple actuation (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, T
0
Switching 1, multiple actuation (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T
0
Switching 1, multiple actuation (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W, T
0
Switching 1, multiple actuation (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W, T
0
Switching 1, multiple actuation (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, W, T
0
Switching 1, multiple actuation (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W, T
0
Switching 1, multiple actuation (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W, T
0
Switching 1, multiple actuation (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, W, T
0
Switching 1, multiple actuation (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, W, T
1
Switching 2, multiple actuation (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, T
1
Switching 2, multiple actuation (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T
1
Switching 2, multiple actuation (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W, T
1
Switching 2, multiple actuation (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W, T
1
Switching 2, multiple actuation (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, W, T
1
Switching 2, multiple actuation (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W, T
1
Switching 2, multiple actuation (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W, T
1
Switching 2, multiple actuation (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, W, T
1
Switching 2, multiple actuation (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, W, T
2
Switching 3, multiple actuation (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, T
2
Switching 3, multiple actuation (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T
2
Switching 3, multiple actuation (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W, T
2
Switching 3, multiple actuation (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W, T
2
Switching 3, multiple actuation (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, W, T
2
Switching 3, multiple actuation (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W, T
2
Switching 3, multiple actuation (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W, T
2
Switching 3, multiple actuation (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, W, T
2
Switching 3, multiple actuation (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, W, T
3
Switching 4, multiple actuation (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, T
3
Switching 4, multiple actuation (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T
3
Switching 4, multiple actuation (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W, T
3
Switching 4, multiple actuation (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W, T
3
Switching 4, multiple actuation (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, W, T
3
Switching 4, multiple actuation (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W, T
3
Switching 4, multiple actuation (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W, T
3
Switching 4, multiple actuation (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, W, T
3
Switching 4, multiple actuation (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, W, T
KNX Technical Reference Manual | 0073-1-7704 | 31
KNX Technical Reference Manual
ABB i-bus® KNX
Multiple actuation objects, rocker left/right, continued
No.
Object name
Data type
Flags
4
Switching 5, multiple actuation (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, T
4
Switching 5, multiple actuation (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T
4
Switching 5, multiple actuation (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W, T
4
Switching 5, multiple actuation (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W, T
4
Switching 5, multiple actuation (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, W, T
4
Switching 5, multiple actuation (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W, T
4
Switching 5, multiple actuation (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W, T
4
Switching 5, multiple actuation (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, W, T
4
Switching 5, multiple actuation (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, W, T
10.17
Delay
Telegrams can be received via the "Input" object using the "Delay" application. The telegrams received are sent out on the
"Output" object with a set delay time.
The object types for "Input" and "Output" can be collectively parameterised for different applications.
Delay objects
No.
Object name
Data type
Flags
0
Input (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W
0
Input (1 Bit)
1 Bit EIS7 / DPT 1.008
C, W
0
Input (1 Bit)
1 Bit EIS7 / DPT 1.007
C, W
0
Input (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W
0
Input (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W
0
Input (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W
0
Input (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, W
0
Input (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W
0
Input (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W
0
Input (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, W
0
Input (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, W
1
Output (1 Bit)
1 Bit EIS1 / DPT 1.001
C, T
1
Output (1 Bit)
1 Bit EIS7 / DPT 1.008
C, T
1
Output (1 Bit)
1 Bit EIS7 / DPT 1.007
C, T
1
Output (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, T
1
Output (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, T
1
Output (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, T
1
Output (2 Byte Signed)
2 Byte EIS10 / DPT 7.001
C, T
1
Output (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, T
1
Output (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, T
1
Output (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, T
1
Output (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, T
2
Delay time (2 Byte)
2 Byte EIS10 / DPT 7.001
C, R, W
32 | 0073-1-7704 | KNX Technical Reference Manual
10.18
Staircase lighting
With the "Staircase lighting" application, switching telegrams or value telegrams can be provided with a light-on time.
Depending on the parameterisation, the application shows different communication objects:
- a 1-bit object for input and output
If an ON telegram is received via the "Input/Output" object, the light-on time is started immediately. This can be a light-on
time of 00:10 min to 88:45 min, which is adjustable in 0.1 s steps. After expiration of the light-on time, the "Input/Output"
object sends an OFF telegram.
- two 1-bit objects for input and output
- and two 1-byte objects for input and output
If a telegram is received via the "Input" object, the light-on time is started immediately and a telegram with the same value of
the telegram received on the input is sent out on the "Output" object. This can be a light-on time of 00:10 min to 88:45 min,
which is adjustable in 0.1 s steps. After expiration of the light-on time, the "Output" object sends out an OFF telegram (1-bit)
or a telegram with the value "0" (1-byte).
Via two additional communication objects, it is possible to specify the light-on time and the switch-off prewarning time. The
2-byte values received are written to the memory of the device and are retained even after a bus power failure and
subsequent return of voltage.
Staircase lighting objects
No.
Object name
Data type
0
Input (1 Bit)
1 Bit EIS1 / DPT 1.001
Flags
C, W
0
Input (1 Byte)
1 Bit EIS14 / DPT 5.010
C, W
0
Input_Output (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, T
1
Light-on time (2 Byte)
2 Byte EIS10 / DPT 7.001
C, R, W
2
Switch-off pre-warning
2 Byte EIS10 / DPT 7.001
C, R, W
3
Output (1 Bit)
1 Bit EIS1 / DPT 1.001
C, T
3
Output (1 Byte)
1 Bit EIS14 / DPT 5.010
C, T
KNX Technical Reference Manual | 0073-1-7704 | 33
KNX Technical Reference Manual
ABB i-bus® KNX
10.19
Light scene actuator
With the "Light scene actuator" application, it is possible to call up scenes that are stored in the device via the receipt of a
scene number on the 1-byte communication object "Scene call-up". A maximum of eight scenes with up to eight actuator
objects can be created.
For triggering different actuators, the size of the actuator groups communication objects can be set under the "Actuator
group type" parameter.
The user has the option of saving the scenes himself. A corresponding save telegram must be received for this (see the
description of the individual parameters).
Light scene actuator objects
No.
Object name
Data type
Flags
0
Light scene call-up (1 Byte)
1 Byte / DPT18.001
C, W, U
1…10
Actuator group A [B…J] (1-bit switching)
1 Bit EIS1 / DPT 1.001
C, W, T, U
1…10
Actuator group A [B…J] (1-bit Venetian blind)
1 Bit EIS7 / DPT 1.008
C, W, T, U
1…10
Actuator group A [B…J] (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T, U
1…10
Actuator group A [B…J] (1-byte light scene number)
1 Byte / DPT 18.001
C, W, T, U
1…10
Actuator group A [B…J] (Temperature value absolute)
2 Byte EIS5 / DPT 9.001
C, W, T, U
10…19
Enable scene 1 [Scene 2 … Scene 10]
1 Bit EIS1 / DPT 1.001
C, W, T
10.20
Sequence
With the "Sequence " application it is possible to send out multiple telegrams with different values in a predefined sequence
consecutively over the same object.
In contrast to the scene, the "Sequence" application has only one communication object on which up to twelve individual
values are consecutively sent in twelve firmly set times. The times can be freely set from 1 s to 12 h. The "Sequence"
application lends itself to controlling showrooms for example.
The function can be temporarily blocked via an enable object.
Sequence objects
No.
Object name
Data type
Flags
0
Sequence value (1-bit switching)
1 Bit EIS1 / DPT 1.001
C, W, T, U
0
Sequence value (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W, T, U
0
Sequence value (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W, T, U
0
Sequence value (1-byte light scene number)
1 Byte / DPT 18.001
C, W, T, U
0
Sequence value (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W, T, U
0
Sequence value (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W, T, U
1
Sequence start
1 Bit EIS1 / DPT 1.001
C, W
2
Sequence status
1 Bit EIS1 / DPT 1.001
C, T
4
Enable
1 Bit EIS1 / DPT 1.001
C, W
34 | 0073-1-7704 | KNX Technical Reference Manual
10.21
Cyclic telegram
Via the "Cyclic telegram" application and after receipt of a telegram on the "Input" object, a telegram with the same volume is
cyclically sent out on the "Cyclic output" object.
The object types for "Input" and "Output" can be collectively parameterised for the different applications.
The times for cyclic sending on the "Output" object are adjustable.
Via an additional "Enable" object, there is the option of temporarily blocking the function.
Cyclic telegram objects
No.
Object name
Data type
Flags
0
Input (1-bit switching)
1 Bit EIS1 / DPT 1.001
C, W
0
Input (1-bit alarm)
1 Bit EIS1 / DPT 1.001
C, W
0
Input (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W
0
Input (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W
0
Input (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W
0
Input (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, W
0
Input (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W
0
Input (2-byte temperature)
2 Byte EIS5 / DPT 9.001
C, W
0
Input (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W
0
Input (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, W
0
Input (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, W
1
Output (1-bit switching)
1 Bit EIS1 / DPT 1.001
C, T
1
Output (1-bit alarm)
1 Bit EIS1 / DPT 1.001
C, T
1
Output (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, T
1
Output (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, T
1
Output (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, T
1
Output (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, T
1
Output (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, T
1
Output (2-byte temperature)
2 Byte EIS5 / DPT 9.001
C, T
1
Output (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, T
1
Output (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, T
1
Output (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, T
2
Enable
1 Bit EIS1 / DPT 1.001
C, W
10.22
Flashing
In order to trigger a flashing sequence on the output object, a telegram must be received on the input object beforehand.
The "Flashing" parameter specifies whether the flashing sequence is started with an ON or an OFF telegram on the input
object. Alternatively, the flashing sequence can be also be started with a "Change of state", i.e. if the input signal switches
from "0" to "1" or from "1" to "0".
Flashing objects
No.
Object name
Data type
Flags
0
Input
1 Bit EIS1 / DPT 1.001
C, W
1
Output
1 Bit EIS1 / DPT 1.001
C, T
KNX Technical Reference Manual | 0073-1-7704 | 35
KNX Technical Reference Manual
ABB i-bus® KNX
10.23
Logic
Logic objects
No.
Object name
Data type
0
Output (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, T
0
Output (1 Byte)
1 Byte EIS14 / DPT 5.010
C, W, T
1
Input 1 (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
1
Input 1 (1 Byte)
1 Byte EIS14 / DPT 5.010
C, W, U
2
Input 2 (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
2
Input 2 (1 Byte)
1 Byte EIS14 / DPT 5.010
C, W, U
3
Input 3 (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
3
Input 3 (1 Byte)
1 Byte EIS14 / DPT 5.010
C, W, U
4
Input 4 (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
4
Input 4 (1 Byte)
1 Byte EIS14 / DPT 5.010
C, W, U
5
Input 5 (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
5
Input 5 (1 Byte)
1 Byte EIS14 / DPT 5.010
C, W, U
6
Input 6 (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
6
Input 6 (1 Byte)
1 Byte EIS14 / DPT 5.010
C, W, U
7
Input 7 (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
7
Input 7 (1 Byte)
1 Byte EIS14 / DPT 5.010
C, W, U
8
Input 8 (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
8
Input 8 (1 Byte)
1 Byte EIS14 / DPT 5.010
C, W, U
9
Input 9 (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
9
Input 9 (1 Byte)
1 Byte EIS14 / DPT 5.010
C, W, U
10
Input 10 (1 Bit)
1 Bit EIS1 / DPT 1.001
C, W, U
10
Input 10 (1 Byte)
1 Byte EIS14 / DPT 5.010
C, W, U
10.24
Flags
Gate
The "Gate" application allows specific signals to be filtered and the signal flow to be temporarily blocked. The function has
three communication objects: "Control input", "Input" and "Output".
The input or output object can assume different sizes.
The bit size can be freely assigned with the "Not assigned" setting. This means that the first internal or external group
address/action that is assigned and already connected to some other communication object will specify the size.
The control can occur from "Input to output" or also from "Output to input", provided the control input allows this. Enabling
via the control input can occur via an ON or an OFF telegram.
If, for example, the "Control input" setting is set to "ON telegram", only telegrams from the input are transmitted to the
output, if prior to this the control input has received an ON telegram.
It is also possible to block signals via the "Filter function" setting. Either "nothing is filtered out" or the signal "ON is filtered
out" or the signal "OFF is filtered out". This function is always necessary, for example, when only the ON telegram is
interesting for a sensor and the sensor does not offer any filter function in its application program.
Gate objects
No.
Object name
Data type
Flags
0
Input
-
C, W, T
1
Output
-
C, W, T
2
Control input
1 Bit EIS1 / DPT 1.001
C, W
36 | 0073-1-7704 | KNX Technical Reference Manual
10.25
Min/Max value transducer
Up to eight input values can be compared with each other using the "Min/max value transducer" application. The application
can output the highest input value, the smallest input value or the average of all input values on the output.
The size of the input objects, and with it also the size of the output object can be adapted for the most diverse applications.
You can select from the following object types:
- 1-byte 0..100 %, for comparison of percent values
- 1-byte 0..255, for the comparison of decimal values between 0 and 255
- 2-byte float, for the comparison of 2-byte floating point values (physical values such as temperature, brightness value etc.)
- 2-byte signed, for the comparison of decimal values between -32,768 and +32,767
- 2-byte unsigned, for the comparison of decimal values between 0 and 65,535
- 4-byte float, for the comparison of 4-byte floating point values (physical values such as acceleration, electrical current,
work etc.)
- 4-byte signed, for the comparison of decimal values between -2,147,483,648 and 2,147,483,647
- 4-byte unsigned, for the comparison of decimal values between 0 and 4,294,967,295
Hint:
With whole numbers the average value is rounded.
Min/Max value transducer objects
No.
Object name
Data type
Flags
0
Output (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, T
0
Output (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, T
0
Output (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, T
0
Output (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, T
0
Output (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, T
0
Output (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, T
0
Output (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, T
0
Output (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, T
1…10
Input 1 [2…10] (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, W
1…10
Input 1 [2…10] (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W
1…10
Input 1 [2…10] (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W
1…10
Input 1 [2…10] (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, W
1…10
Input 1 (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W
1…10
Input 1 [2…10] (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W
1…10
Input 1 [2…10] (4 Byte Signed)
4 Byte EIS11 / DPT 13.001
C, W
1…10
Input 1 [2…10] (4 Byte Unsigned)
4 Byte EIS11 / DPT 12.001
C, W
KNX Technical Reference Manual | 0073-1-7704 | 37
KNX Technical Reference Manual
ABB i-bus® KNX
10.26
Threshold value / hysteresis
With the "Threshold value / Hysteresis" application, value telegrams can be received on an input communication object and
compared with threshold values specified in the device.
Predefined values are sent out on the communication "Output" communication object if the upper or lower thresholds are
exceeded. The size of the object can be adjusted for different applications.
The function can be temporarily blocked via an enable object.
If the value of the lower threshold lies above the value for the upper threshold, the function is not executed.
Threshold value / hysteresis objects
No.
Object name
Data type
0
Input (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
Flags
C, W
0
Input (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W
0
Input (2 Byte Float)
2 Byte EIS5 / DPT 9.xxx
C, W
0
Input (2 Byte Signed)
2 Byte EIS10 / DPT 8.001
C, W
0
Input (2 Byte Unsigned)
2 Byte EIS10 / DPT 7.001
C, W
0
Input (4 Byte Float)
4 Byte EIS9 / DPT 14.xxx
C, W
0
Input (4 Byte Signed)
4 Byte EIS11 / DPT 12.001
C, W
0
Input (4 Byte Unsigned)
4 Byte EIS11 / DPT 13.001
C, W
1
Output (1 Bit)
1 Bit EIS1 / DPT 1.001
C, T
1
Output (1 Byte 0..100 %)
1 Byte EIS6 / DPT 5.001
C, T
1
Output (1 Byte 0..255)
1 Byte EIS14 / DPT 5.010
C, T
2
Enable
1 Bit EIS1 / DPT 1.001
C, W
10.27
Priority
The "Priority" application has 3 communication objects, a 1-bit object "Switch input", a 2-bit object "Input priority" and a 1-bit
object "Output". The telegrams received on the "Switch input" are transferred to the "Output" depending on the state of the
"Input priority" object.
The 2-bit object "Input priority" can receive and differentiate between four different values (0, 1, 2 and 3). Here, the "Output"
object is positively driven. Three different states are differentiated:
- "Input priority" has value "3": the value that is present on "Switch input" has no meaning. The "Output" is switched to
positively driven and has the value "1".
– "Input priority" has the value "2". The value that is present on "Switch input" has no meaning. The "Output" is switched off
positively driven and has the value "0".
– "Input priority" has the value "1" or "0". The "Output" is not positively driven. The "Switch input" is linked to the status bit of
the priority object OR and transferred to the "Output".
During a positive drive, changes of the "Switch input" object are saved, even if the current state on the "Output" object does
not immediately change through this. If the positive drive is terminated, a telegram transmission on the "Output" occurs
according to the current value of the "Switch input" object.
Priority objects
No.
Object name
Data type
Flags
0
Switch input
1 Bit EIS1 / DPT 1.001
C, W
1
Priority input
2 Bit EIS8 / DPT 2.001
C, W
2
Output
1 Bit EIS1 / DPT 1.001
C, T
38 | 0073-1-7704 | KNX Technical Reference Manual
A member of the ABB Group
Busch-Jaeger Elektro GmbH
PO box
58505 Lüdenscheid
Freisenbergstraße 2
58513 Lüdenscheid
Germany
www.BUSCH-JAEGER.com
[email protected]
Central sales service:
Phone:
+49 180 5 669900
Fax:
+49 180 5 669909
Notice
We reserve the right to at all times make technical
changes as well as changes to the contents of this
document without prior notice.
The detailed specifications agreed to at the time of
ordering apply to all orders. ABB accepts no
responsibility for possible errors or incompleteness in
this document.
We reserve all rights to this document and the topics
and illustrations contained therein. The document and
its contents, or extracts thereof, must not be
reproduced, transmitted or reused by third parties
without prior written consent by ABB.