RFK5500 PK5500 RFK5501 PK5501 RFK5508

Add to my manuals
17 Pages

advertisement

RFK5500 PK5500 RFK5501 PK5501 RFK5508 | Manualzz

PK55XX/RFK55XX-433

Installation Instructions, Instructions d’Installation , Instrucciones de instalación, Instruções de instalação

English, Français, Español, Português

7

*

4

1

8

0

2

5

9

#

3

6

7

*

4

1

8

0

2

5

9

#

3

6

7

*

4

1

8

0

2

5

9

#

3

6

7

*

4

1

8

0

2

5

9

#

3

6

RFK5500 RFK5501

RFK5508 RFK5516

WARNING:

Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer.

NOTE:

These instructions shall be used in conjunction with the system Installation Manual of the Control Panel with which this equipment is intended to be used.

ATTENTION:

Ce manuel contient des informations sur les restrictions concernant le fonctionnement et l’utilisation du produit et des informations sur les restrictions en ce qui concerne la responsabilité du fabricant. La totalité du manuel doit être lu attentivement.

NOTE:

Ce manuel doit être utilisé en conjonction avec le Manuel d'installation du Panneau de contrôle.

ATENCIÓN:

Consulte el Manual de instalación del sistema para obener información sobre las limitaciones del uso y funciones del producto, así como las limitaciones de la responsabilidad del fabricante.

NOTA:

Estas instrucciones deberán utilizarse conjuntamente con el Manual de instalación del sistema del Panel de control con el que se vaya a utilizar este equipo.

AVISO:

Consulte o Manual de instalação do sistema para obter informações acerca das limitações relativas à utilização do produto e funções e informações acerca das limitações relativas à imputação de responsabilidades ao fabricante.

NOTA:

Estas instruções devem ser utilizadas em conjunto com o Manual de instalação do sistema do painel de controlo com o qual este equipamento se destina a ser utilizado.

2 9 0 0 7 2 0 3 R0 0 2

English

Installation Instructions

The PK55XX\RFK55XX keypads can be used on security systems with up to 64 zones. These keypads are compatible with the following DSC security systems:

•PC580

•PC1616

•PC5008

•PC5020

•PC585

•PC1832

•PC5010

•PC1555MX

•PC1864

•PC5015

•PC1565

•PC5005

•PC5016

The RFK55XX keypads combine a wireless receiver with the respective

PK55XX keypad.

Specifications

• Temperature range: -10°C to +55°C (14°F to 131°F), Temperature range for UL/ULC: 0°C to +49°C (32°F to 120°F)

• Humidity (MAX): 93%R.H.

• Plastic enclosure protection degree: IP30, IK04

• Voltage rating: 12V

DC

nominal

• Connects to control panel via 4-wire Keybus

• 1 keypad zone input/PGM output*

• PK55XX Current draw: 50mA (standby)/125mA (maximum)

• RFK55XX Current draw: 75mA (standby)/135mA (maximum)

• Wall mount tamper

• 5 programmable function keys

• Ready (Green LED), Armed (Red LED), Trouble (Yellow LED), AC

(Green LED)

• Low temperature sensor

• Frequency: 433.92MHz

(RFK55XX-433 Only)

• Up to 32 wireless zones

(RFK55XX Only)

NOTE: * Zone not to be programmed as Fire type or 24h type.

Unpacking

The Power keypad package includes the following parts:

•One Power keypad

•Four mounting screws

•Keypad inner door labels

•1 tamper switch

•2 end-of-line resistors

Mounting

•Installation Instructions

You should mount the keypad where it is accessible to designated points of entry and exit. Once you have selected a dry and secure location, perform the following steps to mount the keypad.

Disassemble Keypad

1. Removing the keypad from the backplate for the first time.

(a) Position the keypad as indicated, insert screwdriver and rotate.

Disasembling

(Free-standing)

1.

Hooks

2.

Swing to engage

2. Rotate 90°

3. Repeat steps

1. and 2. for

left side

1. Insert the screwdriver into

slot at an angle and push

2. Removing the keypad from backplate once mounted.

(a) Open door, holding it 90° to the keypad, as shown below.

(b) Insert screwdriver into slot located under the door hinge and rotate the screwdriver.

Disasembling

(Wall-Mounted)

Knock Out

Hooks

3. Repeat steps 1.

and 2. for right side

1. Insert the screwdriver into

slot at an angle and push

Mount and Wire Keypad

2. Rotate 90°

Knock Out

Wiring Slot

Knock Out

Tamper

3.

Tamper

4.

Press to snap

1. Secure Keypad to wall using mounting holes. Use all 4 screws provided unless mounting on a single gang box.

2. Place keypad into hooks on the backplate and swing down to engage.

3. Run wire through wiring slot or knockouts. Connect Keybus and PGM/Zone wiring to keypad. Place tamper switch into tamper hole on backplate.

4. Remove keypad from hooks. Place keypad into backplate, ensure the wire is pushed back into the wall as much as possible. Route the wire inside the keypad ensuring high components are avoided. Snap the front assembly closed, ensuring that there is no pressure to the keypad from the wire below.

NOTE: If any tension found between the front keypad assembly and wiring, please open the keypad reroute the wire and close again. Repeat these steps until the keypad is closed properly.

Wiring

1. Before wiring the unit, ensure that all power (AC transformer and battery) is disconnected from the control panel.

2. Connect the four Keybus wires from the con-

PK55XX\RFK55XX trol panel (red, black, yellow and green) to the keypad terminals. Refer to diagram:

RED R

3. If programmed as an input, you can connect a device - such as a door contact - to

BLK

YEL

B

Y the ‘P/Z’ terminal of the keypad. This eliminates the need to run wires back to the

GRN

To zone or

PGM output

G

P/Z control panel for the device. To connect the zone, run one wire from the device to the ‘P/Z’ terminal and the other wire from the device to the B (black) terminal. For powered devices, run the red wire to the R (positive) terminal and the black wire to the B (negative) terminal. When using end of line supervision, connect the zone according to one of the configurations outlined in your system’s Installation Manual.

4. If the ‘P/Z’ terminal is programmed as an output, the output follows the

PGM programmed in Section [080]. A small relay, buzzer or other DC

operated device may be connected between the positive supply voltage and the ‘P/Z’ terminal (maximum load is 50mA).

NOTE: For UL Residential Fire Installations use at least one additional DSC compatible keypad in conjunction with an RFK55XX-

433 keypad or install the RFK55XX-433 keypads within 3 feet from the control unit and mechanically protect the keybus wires

Applying Power

Once all wiring is complete, and the equipment is secured to the building structure with at least two screws apply power to the control panel:

1. Connect the battery leads to the battery.

2. Connect the AC transformer.

For more information on control panel power specifications, see the control panel Installation Manual.

Programming the Keypad

There are several programming options available for the keypad. These are described below. Programming the keypad is similar to programming the rest of the system. When you are in the keypad pro-

1 4

Toggle Option

1 _ _ 4 _ _ _ _ gramming sections, the keypad will display which options are turned on along the top of the display. To turn an option on or off, press the number corresponding to the option on the number pad. The numbers of the options that are currently turned ON will be displayed. For example, if options 1 and 4 are on, the display will look like this on the different keypad displays:

For information on programming the rest of your security system, please refer to your system’s Installation Manual.

Broadcasting LCD Labels

All LCD programming is done per keypad. If more than one LCD keypad is present on the system, labels programmed at one keypad can be broadcast to all other LCD keypads. Perform the following procedure in order to broadcast labels:

Step 1 - Program one LCD keypad completely.

Step 2 - Make sure all LCD keypads are connected to the Keybus.

Step 3 - Enter keypad programming by pressing [

,][8][Installer

Code][

,], then enter section [998] at the keypad that was programmed. The keypad will now broadcast all the information programmed to all the other LCD keypads on the system.

Step 4 - When the keypad is finished press the [#] key to exit.

NOTE: Label broadcast from this keypad is only compatible with other

PK5500 and RFK5500 Keypads.

Language Programming

(PK5500\RFK5500 Only)

Hold (<>) keys for 2 seconds to enter language programming, scroll to the desired language and Press [

,

] to select.

NOTE: If section [077] option 4 is OFF, language programming can only be performed while in installers programming.

Enrolling the Keypad

The keypad will need to be assigned to a partition and slot if supervision or keypad zones are being used. Keypad assignments and keypad option programming must be done at each keypad individually.

The 1st digit of keypad assignment is used to determine partition assignment (1 to 8). If partitioning is not used, enter [1]. For Global

Keypads, enter [0].

NOTE: LED and ICON keypads cannot be programmed as Global Keypads

The 2nd digit of keypad assignment is used to determine slot assignment for keypad supervision. Each keypad will be assigned a different slot number from 1 to 8. PK5500 and RFK5500 LCD keypads come defaulted in slot 8. If LCD keypads are used one LCD keypad must remain in slot 8.

NOTE: The RFK55XX enrolls as two modules:

Light 1 = keypad section of the RFK55XX

Light 17 = receiver section of the RFK55XX

NOTE: Deleting all wireless devices from the RFK55XX or defaulting the

RFK55XX will cause a supervisory fault.

Enter the following at each keypad installed on the system:

1. Enter Installer Programming by pressing [

,][8][Installer’s Code]

2. Press [000] for Keypad Programming

3. Press [0] for Partition and Slot Assignment

4. Enter the 1st digit (0 to 8 for partition assignment)

5. Enter the 2nd digit (1 to 8 for slot assignment supervision)

6. Press the [#] key twice to exit programming.

7. After assigning all keypads, perform a supervisory reset by entering

[

,][8][Installer’s Code][902] and wait for 60 seconds.

8. Press the [#] key to exit programming after 60 seconds.

Programming Labels

(PK5500\RFK5500 Only)

1. Enter keypad programming by pressing [

,][8][Installer Code][,].

Enter the 3-digit section number for the label to be programmed.

2. Use the arrow keys (<>) to move the underline bar underneath the letter to be changed.

3. Press the number keys [1] to [9] corresponding to the letter you require. The first time you press the number the first letter will appear. Pressing the number key again will display the next letter.

[1] - A, B, C, 1 [4] - J, K, L, 4 [7] - S, T, U, 7 [0] - Space

[2] - D, E, F, 2 [5] - M, N, O, 5 [8] - V, W, X, 8

[3] - G, H, I, 3 [6] - P, Q, R, 6 [9] - Y, Z, 9,0

4. When the required letter or number is displayed use the arrow keys

(<>) to scroll to the next letter.

5. When you are finished programming the Zone Label, press the [

,

] key, scroll to “Save,” then press [

,

].

6. Continue from Step 2 until all Labels are programmed.

NOTE: Label Programming can also be accessed from the [

,][6] User

Functions Menu

ASCII Characters

Changing Brightness/Contrast

LCD Keypads

1. Press [

,][6][Master code].

2. Use the [<][>] keys to scroll to either Brightness Control or Contrast Control.

3. Press [

,] to select the setting you want to adjust.

4. a) ‘Brightness Control’: There are multiple backlighting levels. Use the [<][>] keys to scroll to the desired level.

5. b) ‘Contrast Control’: There are 10 different display contrast levels. Use the

[<][>] keys to scroll to the desired contrast level.

6. To exit, press [#].

LED/ICON Keypads

1. Press [

,][6][Master Code].

2. Use the [>] key to move through the 4 different backlighting levels.

3. The level is automatically saved when you press [#] to exit.

Changing the Buzzer Level

LCD Keypads

1. Press [

,][6][Master Code].

2. Use the [<][>] keys to scroll to Buzzer Control.

3. There are 21 different levels, use the [<][>] keys to scroll to the desired level.

4. To exit, press [#].

LED/ICON Keypads

1. Press [

,][6][Master Code].

2. Use the [<] key to move through the 21 different buzzer levels.

3. The level is automatically saved when you press [#] to exit.

Limited Warranty

Digital Security Controls warrants that for a period of 12 months from the date of purchase, the product shall be free of defects in materials and workmanship under normal use and that in fulfilment of any breach of such warranty, Digital

Security Controls shall, at its option, repair or replace the defective equipment upon return of the equipment to its repair depot. This warranty applies only to defects in parts and workmanship and not to damage incurred in shipping or handling, or damage due to causes beyond the control of Digital Security Controls such as lightning, excessive voltage, mechanical shock, water damage, or damage arising out of abuse, alteration or improper application of the equipment.

The foregoing warranty shall apply only to the original buyer, and is and shall be in lieu of any and all other warranties, whether expressed or implied and of all other obligations or liabilities on the part of Digital Security Controls. Digital Security Controls neither assumes responsibility for, nor authorizes any other person purporting to act on its behalf to modify or to change this warranty, nor to assume for it any other warranty or liability concerning this product.

In no event shall Digital Security Controls be liable for any direct, indirect or consequential damages, loss of anticipated profits, loss of time or any other losses incurred by the buyer in connection with the purchase, installation or operation or failure of this product.

Warning: Digital Security Controls recommends that the entire system be completely tested on a regular basis. However, despite frequent testing, and due to, but not limited to, criminal tampering or electrical disruption, it is possible for this product to fail to perform as expected.

Important Information:Changes or modifications not expressly approved by Digital Security Controls could void the user’s authority to operate this equipment.

FCC Compliance Statement

Caution: Changes or modifications not expressly approved by Digital Security Controls could void your authority to use this equipment.

This equipment generates and uses radio frequency energy and if not installed and used properly, in strict accordance with the manufacturer’s instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the limits for Class B device in accordance with the specifications in Subpart

“B” of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in any residential installation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to television or radio reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

• Re-orient the receiving antenna

• Relocate the alarm control with respect to the receiver

• Move the alarm control away from the receiver

• Connect the alarm control into a different outlet so that alarm control and receiver are on different circuits.

If necessary, the user should consult the dealer or an experienced radio/television technician for additional suggestions. The user may find the following booklet prepared by the FCC helpful: “How to Identify and Resolve Radio/Television Interference Problems”. This booklet is available from the

U.S. Government Printing Office, Washington,

D.C. 20402, Stock # 004-000-00345-4.

This Class B digital apparatus complies with

Canadian ICES-003.

Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.

IC:160A-RFK55XX4

The term IC before the radio certification number signifies that the Industry Canada technical specifications were met.

EN5131-1 Grade2/Class II

Operating Instructions shall be made available to the user.

©2006 Digital Security Controls, Toronto, Canada • www.dsc.com

Tech. Support, Centre d’aide: 1-800-387-3630 (Canada, US), 905-760-3036

Keypad Enrollment

Enter keypad programming by pressing [

,][8][Installer’s Code][000].

[0] Partition / Slot Assignment

Digit Option

1st Partition Assignment (0=Global Keypad)

2nd Slot Assignment

Valid Range Default

0 to 8 1 I_____I

1 to 8 LED,ICON=1/LCD=8 I_____I

[1]-[5] Function Key Assignment

Function Key Button Valid Range Default Function

[1] Function Key 1 Assignment

[2] Function Key 2 Assignment

[3] Function Key 3 Assignment

[4] Function Key 4 Assignment

[5] Function Key 5 Assignment

Keypad Function Keys

Please see your system installation manual for a complete list of all the function key options available for your system.

[00] - Null [08] - Bypass Mode [17] - Activate Stay/Away [28] - Partition 4 Select

[01] - Partition 1 Select [09] - Trouble Display [19] - Command Output 3 [29] - Partition 5 Select

[02] - Partition 2 Select [10] - Alarm Memory [21] - Command Output 4 [30] - Partition 6 Select

[03] - Stay Arm

[04] - Away Arm

[11] - User Programming [22] - Activate Camera

[12] - User Functions [23] - Bypass Recall

[31] - Partition 7 Select

[32] - Partition 8 Select

[05] - No Entry Arm [13] - Command Output 1 [24] - Bypass Group Recall

[06] - Chime On/Off [14] - Command Output 2 [26] - Time & Date Program

[07] - System Test [16] - Quick Exit [27] - Partition 3 Select

Keypad Programming

Enter keypad programming by pressing [

,][8][Installer Code][,]

[001]-[064] Zone Label 1 to 64

(PK5500\RFK5500 Only) ex. For Zone 1 enter section [001], for Zone 2 enter section [002] etc. Default: “Zone 1” - “Zone 64”

Section Zone

00 to 32

00 to 32

00 to 32

00 to 32

00 to 32

03

04

06

14 Command Output 2 I_____I_____I

16

Label

Stay Arm I_____I_____I

Away Arm I_____I_____I

Chime On/Off I_____I_____I

Quick Exit I_____I_____I

[001] to [064] 1 to 64

I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I

I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I

[065] Fire Alarm Label (28 Characters)

(PK5500\RFK5500 Only)

Default:“Fire Zone”

I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I

[065]

I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I

[066] Fail to Arm Event Message

(PK5500\RFK5500 Only)

Default: “System Has Failed to Arm”

I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I

[066]

I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I

[067] Alarm When Armed Event Message

(PK5500\RFK5500 Only)

Default: “Alarm Occurred While Armed < >”

I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I

[067]

I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I

[071] First User Display Mask

Default Option ON OFF

ON I____I 1 Hold [P]anic Key prompt ON Hold [P]anic Key prompt OFF

ON I____I 2 Auto-arm Control/Time prompt ON Auto-arm Control/Time prompt OFF

ON I____I 3 Quick Arm prompt ON

ON

I____I

4 Interior Arm prompt ON

OFF

I____I

5 Quick Exit prompt ON

OFF I____I 6 Thermostat Control prompt ON

Quick Arm prompt OFF

Interior Arm prompt OFF

Quick Exit prompt OFF

Thermostat Control prompt OFF

OFF I____I 7 ACK All Trouble Prompt ON

OFF

I____I

8 Music Input prompt ON

[072] Second User Display Mask

ACK All Trouble Prompt OFF

Music Input prompt OFF

Default Option ON

ON I____I 1 User-initiated Call-up prompt ON

OFF I____I 2 For Future Use

OFF

I____I

3 Walk Test prompt ON

ON

I____I

4 Command Output#1 prompt ON

ON I____I 5 Command Output#2 prompt ON

OFF

User-initiated Call-up prompt OFF

Walk Test prompt OFF

Command Output#1 prompt OFF

Command Output#2 prompt OFF

OFF I____I 6 Command Output#3 prompt ON

OFF

I____I

7 Command Output#4 prompt ON

Command Output#3 prompt OFF

Command Output#4 prompt OFF

OFF

I____I

8 For Future Use

[073] Download LCD Message Duration

(PK5500\RFK5500 Only)

Default: 003 I_____I_____I_____I (Valid entries are 000-255), 000=Unlimited Message Disp.

This number represents the number of times the Downloaded message is cleared by pressing any key while the message is up after timeout).

[074] Key Options

Default Option ON

ON

I____I

1 [F]ire Key Enabled

ON I____I 2 [A]uxiliary Key Enabled

ON I____I 3 [P]anic Key Enabled

OFF

I____I

4-8 For Future Use

[076] First Keypad Options

OFF

[F]ire Key Disabled

[A]uxiliary Key Disabled

[P]anic Key Disabled

Default Option ON

ON I____I 1 Display Code when Programming

OFF

Display “Xs” when Programming

ON I____I 2 Local Clock Display ON

OFF

I____I

3 Local Clock Displays 24-hr Time

Local Clock Display OFF

Local Clock Displays AM/PM

ON I____I 4 Auto Alarm Memory Scroll Enabled Auto Alarm Memory Scroll Disabled

OFF I____I 5 Local Display of Temperature ON Local Display of Temperature OFF

Bypass Options prompt OFF ON I____I 6 Bypass Options prompt ON

OFF

I____I

7 For Future Use

OFF

I____I

8 Auto-Scroll Open Zones ON Auto-Scroll Open Zones OFF

[120]-[151] Command Output Labels

(PK5500\RFK5500 Only)

Default: “Command_O/P_1” - “Command_O/P_4”

For Partition 1 Command O/P 1 to 4 enter [120] to [123] For Partition 5 Command O/P 1 to 4 enter [136] to [139]

For Partition 2 Command O/P 1 to 4 enter [124] to [127] For Partition 6 Command O/P 1 to 4 enter [140] to [143]

For Partition 3 Command O/P 1 to 4 enter [128] to [131] For Partition 7 Command O/P 1 to 4 enter [144] to [147]

For Partition 4 Command O/P 1 to 4 enter [132] to [135] For Partition 8 Command O/P 1 to 4 enter [148] to [151]

Section Part

Cmd.

Output

Label

I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I

[120]-[151]1to8 1to4

I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I

[201]-[264] Door Chime Sound Programming

You can program the keypad to make up to four different door chime sounds for individual zones.

ex. For Zone 1 enter section [201], for Zone 2 enter section [202] etc.

[077] Second Keypad Options

Default Option ON OFF

ON I____I 1 Chime Enabled for Zone Openings

ON

I____I

2 Chime Enabled for Zone Closings

Chime Disabled for Zone Openings

Chime Disabled for Zone Closings

OFF

I____I

3 5th Terminal is Keypad PGM Output 5th Terminal is Keypad Zone Input

ON I____I 4 Language Selection from Any Menu Language Selection From Installer's

OFF I____I 5 Power LED Enabled

ON

I____I

6 Power LED indicates AC present

Power LED Disabled

Power LED indicates AC absent

ON

I____I

7 Alarms always Displayed When Armed Alarms not Displayed When Armed

OFF I____I 8 Low Temperature Warning Enabled Low Temperature Warning Disabled

[080] PGM Terminal 1

Default: 01 I_______I _______I PGM Output Number

[101]-[108] Partition Labels

(PK5500\RFK5500 Only) ex. For Partition 1 enter section [101], for Partition 2 enter section [102] etc.

Section Partition Label

I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I

[101] to [108] 1 to 8

I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I

NOTE: Partition 1 Label is also used as the System Label

Default Option ON

ON I____I 1 6 Beeps

OFF

I____I

2 “Bing-Bing” Sound

OFF

I____I

3 “Ding-Dong” Sound

OFF I____I 4 Alarm Tone

Disabled

Disabled

Disabled

Disabled

OFF

OFF I____I 5-8 For Future Use

[995][

,] Reset Keypad Options to Factory Default

[996][

,] Label Default (PK5500\RFK5500 Only)

[997] View Software Version (PK5500\RFK5500 Only)

[998][

,] Initiate Global Label Broadcast (PK5500\RFK5500 Only)

[999][

,] Reset Keypad EEPROM to Factory Defaults

Keypad Display Symbols

2

12

1

7

8

11

9

10

1

8

2

7

1 Fire – Indicates that there are fire alarms in memory.

3

4

5

6

2 Memory – Indicates that there are alarms in memory.

3

Ready Light (green) – If the Ready light is on, the system is ready for arming.

4

Armed Light (red) – If the Armed light is on, the system has been armed successfully.

5 System Trouble – Indicates that a system trouble is active.

6 AC – Indicates that AC is present at the main panel.

7

Program – Indicates that the system is in Installer’s Programming, or the keypad is busy.

8

Bypass – Indicates that there are zones automatically or manually bypassed.

9 For Future Use

10 Arm Mode – Indicates the mode the panel is armed in.

11

Stay – Indicates that the panel is armed in the Stay

Mode. It will turn on at the beginning of the Exit

Delay

Away – Indicates that the panel is armed in the Away

Mode. It will turn on at the beginning of the Exit

Delay

Chime – This icon turns on when Door Chime is enabled on the system and will turn off when Door Chime is disabled.

12

Open – When zones are opened, this icon will turn on, and

7 segment displays 1 and 2 will scroll through the open zones.

Wireless Integration

(RFK55XX Only)

Compatible Wireless Devices

(RFK55XX-433 Only)

The RFK55XX can receive signals from the following devices:

•WLS914-433 Pet Immune PIR •WLS912L-433 Glass Break Detector

•WS4965 Tri-Zone Contact

•WS4938 Panic Button

•WS4916 Smoke Detector

•WLS904(P)L-433 Pet Immune PIR

•WLS925L-433 Mini Door/Window Contact

•WS49X9 Wireless Keys

Downloading

The RFK55XX product has an integrated wireless receiver. When downloading to this keypad, please select the PC5132-433 v5.1 file.

DLS2002 and greater must be used in order to have the capability of downloading to this keypad.

Testing Wireless Devices

1. Temporarily put the wireless devices in the places you want to mount them.

2. At a system keypad, enter [

,][8][Installer Code].

3. Enter programming section [904], then enter the two digit zone number.

NOTE: If global placement test is enabled (Section [90], option 8

ON) enter [01] to test all zones.

4. Activate the device being tested until a result is displayed on the keypad or sounded by the keypad or bell

Result LED/ICON Keypad LCD Keypad Bell/Buzzer

Good Light 1 ON Steady

Bad Light 3 ON Steady

Good

Bad

1 Beep/Squawk

3 Beeps/Squawks

Activate the device until you get 3 good results in a row. Wait 10 seconds between each test on the same device. You may mount wireless devices where results were good.

Devices indicating a bad result must be moved to another location.

You may only have to move the device a few inches to correct a bad result.

NOTE: Do not mount any device where a “bad” test result was indicated.

Testing Portable Device Reception

To test portable devices (e.g., WS4938, WS4939) press the button(s) at several different points in the installation, to confirm the coverage area. If these devices do not operate from all points in the installation, you will need to move the RFK55XX.

Replacing Wireless Device

Batteries

1. Remove the cover of the device from its backplate. This creates a tamper condition on the zone.

2. Refer to the battery installation instructions on the Installation

Sheet of each component. Be sure to note the proper orientation of the batteries as you install them.

3. When the fresh batteries are in place, re-attach the cover to the backplate. The tamper is restored and the zone sends a battery trouble restoral signal to the receiver. The battery trouble is now clear and the device should function normally.

NOTE: When batteries in one device need to be replaced, the batteries in all devices should be replaced at the same time.

Troubleshooting

1. When I enter the 2-digit zone number when adding a wireless device, the keypad gives me a long beep.

• You cannot enter ESNs unless the RFK55XX is properly connected to the Keybus.

2. I have entered the ESN for the device but when I violate the device, the zone does not show open on the keypad.

Check the following:

• Ensure the ESN has been entered correctly

• Ensure that the zone is enabled for the partition (if partition programming is used).

• Ensure that the wireless zone is not assigned to a zone used by

PC5108 modules, an on-board zone or a keypad zone.

• Ensure that the zone is programmed for something other than

“Null Operation” and that the wireless zone attribute is turned on.

3. When I try a module placement test I get no result or “Bad” results.

Check the following:

• Verify that you are testing the correct zone

• Verify that the correct ESN was entered when the device was enrolled

• Verify that the device is in range of the RFK55XX. Try testing the device in the same room as the receiver.

• Confirm that the RFK55XX is properly connected to the Keybus.

• Check that you are testing the zone correctly. Refer to the instructions that came with the zone.

• Check that the batteries are working and installed correctly.

• Look for large metal objects that may be preventing the signal from reaching the RFK55XX.

• The device must be located where consistent “Good” results are obtained. If several devices show “Bad” results, or if panic pendants and wireless keys operate inconsistently, move the receiver.

4. The LED on the motion detector does not turn on when I walk in front of the unit.

• The LED on the motion detector is for walk test purposes only. See your WLS904-433/WLS904P(L)-433 Instruction Sheet for walk test instructions.

Notes

:

Wireless Programming

(RFK55XX Only)

Enter Wireless programming by pressing [

,][8][Installer’s Code][804]

[01]-[32] Wireless Device Serial Number

Zone Serial Numbers Default = 000000

[01] Zone 1 I_____I_____I_____I_____I_____I_____I [17] Zone 17 I_____I_____I_____I_____I_____I_____I

[02] Zone 2 I_____I_____I_____I_____I_____I_____I [18] Zone 18 I_____I_____I_____I_____I_____I_____I

[03] Zone 3 I_____I_____I_____I_____I_____I_____I [19] Zone 19 I_____I_____I_____I_____I_____I_____I

[04] Zone 4 I_____I_____I_____I_____I_____I_____I [20] Zone 20 I_____I_____I_____I_____I_____I_____I

[05] Zone 5 I_____I_____I_____I_____I_____I_____I [21] Zone 21 I_____I_____I_____I_____I_____I_____I

[06] Zone 6 I_____I_____I_____I_____I_____I_____I [22] Zone 22 I_____I_____I_____I_____I_____I_____I

[07] Zone 7 I_____I_____I_____I_____I_____I_____I [23] Zone 23 I_____I_____I_____I_____I_____I_____I

[08] Zone 8 I_____I_____I_____I_____I_____I_____I [24] Zone 24 I_____I_____I_____I_____I_____I_____I

[09] Zone 9 I_____I_____I_____I_____I_____I_____I [25] Zone 25 I_____I_____I_____I_____I_____I_____I

[10] Zone 10 I_____I_____I_____I_____I_____I_____I [26] Zone 26 I_____I_____I_____I_____I_____I_____I

[11] Zone 11 I_____I_____I_____I_____I_____I_____I [27] Zone 27 I_____I_____I_____I_____I_____I_____I

[12] Zone 12 I_____I_____I_____I_____I_____I_____I [28] Zone 28 I_____I_____I_____I_____I_____I_____I

[13] Zone 13 I_____I_____I_____I_____I_____I_____I [29] Zone 29 I_____I_____I_____I_____I_____I_____I

[14] Zone 14 I_____I_____I_____I_____I_____I_____I [30] Zone 30 I_____I_____I_____I_____I_____I_____I

[15] Zone 15 I_____I_____I_____I_____I_____I_____I [31] Zone 31 I_____I_____I_____I_____I_____I_____I

[16] Zone 16 I_____I_____I_____I_____I_____I_____I [32] Zone 32 I_____I_____I_____I_____I_____I_____I

[41]-[56] Wireless Key Serial Number

Wireless Key Serial Numbers Default = 000000

[41] Key 1 I_____I_____I_____I_____I_____I_____I [49] Key 9 I_____I_____I_____I_____I_____I_____I

[42] Key 2 I_____I_____I_____I_____I_____I_____I [50] Key 10 I_____I_____I_____I_____I_____I_____I

[43] Key 3 I_____I_____I_____I_____I_____I_____I [51] Key 11 I_____I_____I_____I_____I_____I_____I

[44] Key 4 I_____I_____I_____I_____I_____I_____I [52] Key 12 I_____I_____I_____I_____I_____I_____I

[45] Key 5 I_____I_____I_____I_____I_____I_____I [53] Key 13 I_____I_____I_____I_____I_____I_____I

[46] Key 6 I_____I_____I_____I_____I_____I_____I [54] Key 14 I_____I_____I_____I_____I_____I_____I

[47] Key 7 I_____I_____I_____I_____I_____I_____I [55] Key 15 I_____I_____I_____I_____I_____I_____I

[48] Key 8 I_____I_____I_____I_____I_____I_____I [56] Key 16 I_____I_____I_____I_____I_____I_____I

[61]-[68] Wireless Function Key Options

Function Key Key 1 Default Key 2 Default Key 3 Default Key 4 Default

[61] Partition 1 I_____I_____I 03

I_____I_____I 04 I_____I_____I 27 I_____I_____I 30

[62] Partition 2 I_____I_____I 03 I_____I_____I 04 I_____I_____I 27 I_____I_____I 30

[63] Partition 3 I_____I_____I 03 I_____I_____I 04 I_____I_____I 27 I_____I_____I 30

[64] Partition 4 I_____I_____I 03

I_____I_____I 04 I_____I_____I 27 I_____I_____I 30

[65] Partition 5 I_____I_____I 03

I_____I_____I 04 I_____I_____I 27 I_____I_____I 30

[66] Partition 6 I_____I_____I 03 I_____I_____I 04 I_____I_____I 27 I_____I_____I 30

[67] Partition 7 I_____I_____I 03 I_____I_____I 04 I_____I_____I 27 I_____I_____I 30

[68] Partition 8 I_____I_____I 03

I_____I_____I 04 I_____I_____I 27 I_____I_____I 30

Keypad Function Keys

Please see your system installation manual for a complete list of all the function key options available for your system.

[00] - Null [06] - Chime On/Off [16] - Quick Exit [27] - Disarm

[03] - Stay Arm

[04] - Away Arm

[07] - System Test [17] - Activate Stay/Away [28] - Fire Alarm

[13] - Command Output 1 [19] - Command Output 3 [29] - Auxiliary Alarm

[05] - No Entry Arm [14] - Command Output 2 [21] - Command Output 4 [30] - Panic Alarm

[69] Wireless Keys (1-16) Partition Assignments

Default = 01

Key 1

I_____I_____I

Key 5

I_____I_____I

Key 9

I_____I_____I Key 13 I_____I_____I

Key 2 I_____I_____I Key 6 I_____I_____I Key 10 I_____I_____I Key 14 I_____I_____I

Key 3

I_____I_____I

Key 7

I_____I_____I Key 11 I_____I_____I Key 15 I_____I_____I

Key 4

I_____I_____I

Key 8

I_____I_____I Key 12 I_____I_____I Key 16 I_____I_____I

[81] Wireless supervisory Window

Default: [NA] 96 = 24 hours / [EU] 10 =2.5 hours I_____I_____I

The window is programmed in 15 minute increments. Valid entries are 10 to 96, equal to 2.5 to 24 hours.

[82]-[85] Zone Device Supervision Options

Default ON

[82]

Zone

Supervision

ON/OFF

[83]

Zone

Supervision

ON/OFF

[84]

Zone

Supervision

ON/OFF

[85]

Zone

Supervision

ON/OFF

Option 1 1 I_____I 9 I_____I 17 I_____I 25 I_____I

Option 2 2 I_____I 10 I_____I 18 I_____I 26 I_____I

Option 3 3 I_____I 11 I_____I 19 I_____I 27 I_____I

Option 4 4 I_____I 12 I_____I 20 I_____I 28 I_____I

Option 5 5 I_____I 13 I_____I 21 I_____I 29 I_____I

Option 6 6 I_____I 14 I_____I 22 I_____I 30 I_____I

Option 7 7 I_____I 15 I_____I 23 I_____I 31 I_____I

Option 8 8 I_____I 16 I_____I 24 I_____I 32 I_____I

[90] Other Options

NA Default EU Default

OFF

ON

OFF

I____I

Option ON

1-4 For Future Use

OFF

OFF I____I 5 RF Delinquency Disabled RF Delinquency Enabled

OFF

ON

OFF I____I 6 For Future Use

OFF

I____I

7 RF Jam Detect Disabled RF Jam Detect Enabled

OFF OFF

I____I

8 Global Placement Test Individual Placment Test

NOTE: For UL Listed installations, the RF Jam detect feature must be enabled.

NOTE: For DD243 installations, the RF delinquency feature should be enabled.

NOTE: Supervision must be enabled for RF Delinquency.

[93] RF Jam Detect Zone

Default: 00 I_____I_____I Valid entries = 01 - 32, 00 = No RF Jam tone selected.

Select an unused zone that will be set to the tamper state when a jamming signal is detected.

Project: Concord Gardens PH1 - Shop Drawings List

Section 5 Suite Alarm System

1. DSC PC1616 Control Panel

2. DSC RFK5508 Keypad

3. DSC LC-100-PI PIR

4. DSC Vanishing Door/Window Contact

Enclosure box is

11.3"x11.7"x3"

Mounted beside or below suite's communications box

PowerSeries v4.6

Control Panels

Features That

Make a Difference:

• Convenience of easy wireless device enrollment process

• Additional wireless zones – up to

64 in total

• Library of over 250 pre-configured labels

• Compatible with C24 Interactive

Standard

PowerSeries

Features:

• Template Programming

• Account Code Error Checking

• Alternate Communications via

GPRS and IP

• Local and Remote Downloading

• Programmable Daylight Savings

Time

• Automatic CID

• 2-way Audio

• 1 Time Use Code

• Keypad Lockout

PC1616

PC1832

PC1864

PowerSeries v4.6 Control

Panels: Simply Powerful

Introducing the new PowerSeries v4.6

Control Panel from DSC. This featurerich and reliable intrusion alarm control panel easily integrates with an array of compatible components to deliver a scalable solution. PowerSeries v4.6 makes installation easy, simple and fast without compromising flexibility of design.

Even More Available

Wireless Zones

To accommodate the move to more and more wireless devices and detectors, the PowerSeries PC 1864 has 64 wireless zones – double the capacity of earlier versions. This provides the scalability and flexibility a control panel needs to support requirements both now and in the future.

Label Programming

Made Easy with

Pre-loaded Library

With a library of over 250 commonlyused names in English, French and

Spanish, label programming is now a snap with the PowerSeries v4.6. Installers can now assign a unique 3-digit code to display a full descriptive label (e.g., code 190 displays ‘Window’), avoiding time and mistakes with more conventional keypad entry. For additional customization, other pertinent details can also be added, such as the zone or floor to make it easy for the owner to identify faults (e.g., ‘Bedroom

Window’).

Convenient Wireless

Device Enrollment

Reduces Installation Time

Enrolling wireless devices and detectors is quick and easy with the

PowerSeries v4.6 – reducing onsite installation time. With the wireless device enrollment process, installers are not required to manually program serial numbers or wireless attributes.

Instead, enrollment is completed by confirming the confirm Electronic

Serial Numbers (ESN), zone numbers and zone type through a series of user friendly screens. panels, keypads & modules

Contact your DSC distributor.

www.dsc.com | 1-888-888-7838

Compatible with C24 Interactive

The PowerSeries v4.6 Control Panel is compatible with the innovative C24 Interactive product line. Integrating these two lines provides accountability and control to end users with a scalable solution. C24 Interactive offers a range of pre-defined security options from simple notification to automated ‘control and connect’. Ideal for both new and existing end users, C24 Interactive options can be easily added as requirements evolve, creating long-term and entrenched revenue streams today and tomorrow – all supported by PowerSeries v4.6.

Simply Powerful

Put the PowerSeries v4.6 Control Panel to work at the centre of any security installation from small residential to mediumsized commercial installations. Designed with users in mind, installers now have an easy-to-install system with a range of features all backed by DSC’s proven reputation. Simply powerful.

Specifications

Power Supply

Current Draw (Panel)

Auxiliary & Output

Bell Output

Operating Environment

Relative Humidity

16.5 VAC/40 VA @ 50/60 Hz

110 mA (Nominal)

13.75 ± 5% Vdc /700 mA

13.75 ± 5% Vdc /700 mA

32° to 120° F (0° to 49° C)

93%

PowerSeries v4.6 Features

Features

On-Board Zones

Hardwired Zones

Wireless Zones

Keypad Zone Support

On-board PGM Outputs

PGM Expansion

Keypads

Partitions

User Codes

Event Buffer

Battery Required

Bell Output

PC1616

6

16 (1 x PC5108)

32

Yes

PGM 1 = 50 mA

PGM 2 = 300 mA

8 x 50 mA (PC5208)

4 x 500 mA (PC5204)

8

2

47+ Master Codes

500 Events

4 Ah / 7 Ah / 14 AHr

12 V / 700 mA (cont)

Compatibility

• User Interfaces - LED, Icon and Full Message LCD,

NEW PTK Touchscreen

• C24 Interactive

• Wireless Receivers, Devices and Detectors

• Audio Alarm Verification

• Telephone Interface/Automation Control

• High & Low Current Output Expansion

• Alternate Communication Options

• Hardwired Expansion and Detectors

• Addressable Expansion and Detectors

• Windows™ Software for PC Downloading

• Access Control Integration

PC1832

8

32 (1 x PC5108)

32

Yes

PGM 1 = 50 mA

PGM 2 = 300 mA

8 x 50 mA (PC5208)

4 x 500 mA (PC5204)

8

4

71+ Master Codes

500 Events

4 Ah / 7 Ah / 14 AHr

12 V / 700 mA (cont)

PC1864

8

64 (1 x PC5108)

64

Yes

PGM 1,3,4 = 50 mA

PGM 2 = 300 mA

8 x 50 mA (PC5208)

4 x 500 mA (PC5204)

8

8

94+ Master Codes

500 Events

4 Ah / 7 Ah / 14 AHr

12 V / 700 mA (cont) panels, keypads & modules

For product information www.dsc.com

Product specifications and availability subject to change without notice. Certain product names mentioned herein may be trade names and/or registered trademarks of other companies.

©2012 2012-06

DSC PowerSeries

Keypads

With Built-in Wireless Receivers

Features that make a difference:

Common to all Keypads:

• Modern, slim-line landscape keypads

• Large, backlit keypad buttons

• 5 programmable function keys

• Programmable Input/Output terminal

• Individual FAP keys

• Multiple door chime per zone

• Adjustable backlight and keypad buzzer

• Wire channel

• Dual wall-mount and front cover tamper

• Easy-to-install mounting hinge

• Surface or single-gang box mount

Wireless Convenience in an

Attractive Package

DSC continues to lead the industry with its wireless solutions. No where is this commitment more clear than with the PowerSeries high-quality, slimprofile keypads with built-in wireless receivers.

With four optionsw to choose from, these keypads are designed with a clean, unobtrusive look that homeowners welcome and installers will appreciate for their easy programming and installation. They include all of the same features as their hardwired equivalents and are able to support

32 wireless zones and 16 wireless keys without taking up a wireless zone slot.

Contact your DSC distributor www.dsc.com | 1-888-888-7838

RFK5500 RFK5501 RFK5508 RFK5516 panels, keypads & modules

Feature Rich

The keypads feature an input/output terminal that can be programmed to operate as a zone input, programmable output or as a low temperature sensor. The keypads also include adjustable backlit keys that address low-light situations. The RFK5500 64-zone full-message keypad supports eight languages, global partition status and full,

32-character programmable phrases.

Easy To Use

To simplify usage, the keypads feature five programmable keys for easy one-button activation of system functions.

The default tasks assigned to the five function keys are stay arming, away arming, door chime, smoke detector reset and quick exit. With the quick exit function there’s no need to disarm and re-arm the system every time an occupant leaves the house or lets the dog out, for example.

Wireless Convenience

DSC offers a large portfolio of reliable wireless devices and detectors to help make your toughest installations simpler. The integrated DSC approach has resulted in an unparalleled spectrum of unique interchangeable component alternatives. They can be configured for every circumstance, providing safe, reliable protection.

• Revolutionary reliability

• Long-life lithium batteries

• Attractive, compact designs

• New technology for greater signal range and accuracy

Some products you will definitely want to consider are:

• WS4945 Wireless Door/Window Contact

• EV-DW4975 Vanishing Contact

• EV-DW4917 Wireless Recessed Door Transmitter

• WS4916 Wireless Photoelectric Smoke Detector

• WLS914-433 Wireless Pet-Immune Passive Infrared

Detector

• WS4965 Tri-Zone Wireless Door/Window Contact

• WS4913 Wireless Carbon Monoxide Detector

• WS4939 4-Button Wireless Key

And many more. Ask your distributor for details.

Compatibility

The keypads are compatible with all PowerSeries control panels and all 433 MHz wireless devices from DSC.

Specifications

Dimensions ............................... 6 1/16” x 4 7/16” x 13/16”

.........................................

(154 mm x 113 mm x 20.5 mm)

LCD Viewable Area ...................................3 9/10” x 15/16”

...............................................................

(99 mm x 24 mm)

Current Draw ................................................125 mA (Max)

Voltage .....................................................12 VDC Nominal

Operating Environment ..................................32° to 120° F

.......................................................................

(0° to 49° C)

Relative Humidity ................................................. 5 to 93%

Full message LCD Keypad languages supported:

Croatian, Czech, Danish, Dutch, English, Estonian, Finnish, French, German, Greek, Hungarian,

Italian, Latvian, Lithuanian, Norwegian, Polish, Portuguese, Slovak, Spanish, Swedish

Ordering Information:

RFK5500 ................................. 433 MHz Wireless 64-Zone

Full-Message LCD Keypad

RFK5501 ................................. 433 MHz Wireless 64-Zone

LCD Picture ICON Keypad

RFK5516 .............433 MHz Wireless 16-Zone LED Keypad

RFK5508 ...............433 MHz Wireless 8-Zone LED Keypad panels, keypads & modules

For product information www.dsc.com

Product specifications and availability subject to change without notice. Certain product names mentioned herein may be trade names and/or registered trademarks of other companies.

©2011 2011-06

Digital PIR Detector with Pet Immunity

LC-100-PI

Features That

Make a Difference:

• Form ‘A’ alarm contact and tamper switch

• Digital signal analysis

• Slim profile design

• Features ABS plastic for shock and impact protection

• Exceptional white light immunity

• Pet immunity up to 55 lbs (25 kg)

• Quad Linear Imaging Technology for sharp analysis of body dimensions and differentiation from backgrounds and pets

• Advanced ASIC-based electronics Compact design for residential installations

• Adjustable variable pulse count

• PIR sensitivity adjustment

• Height installation calibration free

• Available in packages of 6

(LC-100-PI-6PK)

Whether it’s a residential or commercial installation, the

LC series of detection devices readies a security system for the unexpected by providing protection for every room, corner and corridor.

The LC-100-PI effectively blends performance with competitive pricing. The detector features intelligent signal analysis for reliable detection, pet immunity up to 55 lbs (25 kg) and a slim design that complements any décor.

Contact your DSC distributor www.dsc.com | 1-888-888-7838 sensors and accessories

Reliable Protection

Advanced ASIC-based processing provides both superior detection and false alarm rejection to help keep people and possessions secure. Quad Linear Imaging Technology provides sharp analysis of body dimensions and differentiation from backgrounds and pets.

Digital Signal Processing

Effective motion detection is dependent on a sensor’s ability to identify intruders and provide true false alarm resistance. The LC series of detection devices pinpoints intruders through digital signal processing. Digital information is more accurately analyzed using software and is not subject to signal degradation caused by amplification, noise, distortion or signal clipping.

Pet Immunity

Highly accurate sensors are able to provide quality detection while at the same time ignoring pets weighing up to 55 lbs (25 kg).

Fast and Easy Installation

Once the detector is installed at the recommended height, installers simply conduct a brief walk-test, make any necessary adjustments, and the unit is ready to perform.

Highly visible LEDs can be viewed at a glance and help the installer identify the detection range from any distance or angle within the coverage pattern.

Locating the Detector

When choosing a location for the detector, be sure to consider the following:

• Do not aim the detector at reflective surfaces

• Avoid locations that are subject to direct high air flow

• Do not locate the detector in the path of direct or reflected sunlight

• Do not place next to large obstructions that may limit the coverage area

Coverage Pattern

Detection Range Adjustment

The detection range of the motion detector is adjustable to from 16' to 49' (5 m to 15 m). A potentiometer can be adjusted clockwise or counter-clockwise to increase or decrease the range respectively. For optimum performance, range should be adjusted so that it effectively protects the dimensions of the intended area.

Specifications

Dimensions ........................................ 3.62" x 2.46" x 1.57"

(92 mm x 62.5 mm x 40 mm)

Weight ....................................................... . 58 gr (2.04 oz)

Detection Method ........................ Quad (Four Element) PIR

Power Input ................................................ 9.6 to 16 VDC

Current Draw (Standby) .................................. 8 mA (± 5%)

Current Draw (Active) ................................... 12 mA (± 5%)

Tamper Switch: Contact Rating ........... 0.1 Amp @ 28 VDC

RFI Protection ......10 V/m plus 80% AM from 80-2000 MHz sensors and accessories

For product information www.dsc.com

Product specifications and availability subject to change without notice. Certain product names mentioned herein may be trade names and/or registered trademarks of other companies.

©2013 2013-12

From Tyco Security Products

Wireless Vanishing

Door/Window Contact

EV-DW4975

Features That

Make a Difference:

• Wafer-thin profile

• Long-life lithium battery included

• 5/8˝ (16 mm) maximum magnet gap

• Double-sided tape (included)

• Smooth-back plastics

• Reliable 433 MHz technology

Installs in Seconds

& Virtually Vanishes

Among the smallest wireless door/ window contact currently available, the wafer-thin profile of the EV-

DW4975 provides a streamlined, practically non-existent look once installed. The contact can be easily mounted to a window frame with double-sided tape, eliminating the need for drilling.

This not only reduces installation times but also retains the integrity of window warranties. A generous magnet gap of 5/8˝ (16 mm) easily accommodates larger door or window frames. The EV-DW4975 is built with reliable 433 MHz technology and is compatible with all current DSC wireless receivers.

Value Added

Significantly smaller than competitor door/window contacts, the EV-

DW4975 is housed within a compact casing that allows it to be used for the tightest-fitting installations. Once installed, the contact is inconspicuous and complements the décor of most homes. It is built with reliable 433

MHz technology, uses a long-life lithium battery and is compatible with all current DSC wireless receivers.

Contact your DSC distributor www.dsc.com | 1-888-888-7838 sensors and accessories

Compatibility

The EV-DW4975 is compatible with the following receivers:

• IMPASSA Self-Contained 2-Way Wireless Security

System

• ALEXOR 2-Way Wireless Security System

• SCW9045/9047 Self-Contained Wireless Security

System

• PowerSeries Wireless Receivers PC5132-433 /

RF5132-433 / RF5108-433 / TR5164-433

• PowerSeries RFK Keypads RFK55XX-433

• MAXSYS Wireless Receivers PC4164-433 /

RF4164-433

• WS4920 Wireless Repeater

From

Tyco Security Products

Specifications

Dimensions ..............................................2

1/4

˝ x 1˝ x 15/64˝

(57 mm x 25.4 mm x 5.9 mm)

Battery ...............................................CR2032 (3V Lithium)

Battery Life .............................................5-8 Years (Typical)

Operating Temperature ............ -10° to 50°C (14° to 122°F)

Relative Humidity .............................................. 5% to 93% sensors and accessories

For product information www.dsc.com

Product specifications and availability subject to change without notice. Certain product names mentioned herein may be trade names and/or registered trademarks of other companies.

©2013 Tyco Security Products. 2013-01

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement