1
POWER LINE DISTURBANCES
Dip (Sag): is a short term decrease in line voltage. Usually it results from a short circuit in the power line or a sudden increase in electrical
load on the line (start up of large loads), utility switching or equipment failure.
Surge: is the exact opposite of a dip. It is a temporary increase in line voltage that lasts at least one cycle (approx. 16mS). It can be triggered
off by rapid reduction in power loads or by utility switching.
Spike (transient): is similar to a surge except that it lasts less than a full cycle (often only a few milliseconds). It can be 100% or more above
nominal voltage.
Electrical Noise: probably the most common type of disturbance, which is a random high voltage, or high frequency interference on the
power line caused mostly by non-linear loads. There are two types of noise, usually referred to as common mode (noise between power
connection and ground) and transverse mode (noise between power connections).
Brownout: is a deliberate reduction in AC line voltage by the utility company during periods of unusual high demand or insufficient load
capacity. The power line supply does not have the full capacity to supply the load which results in load sharing.
Blackout: this is the ultimate power disturbance. It is a complete cut in the power line supply (power failure). Typically described as “zero-volt”
condition lasting longer than half a cycle. Can be caused by utility equipment failure, lightning etc . . . the list is long.
Businesses are becoming more and more reliant on a utility power supply that is pushed beyond its capacity. Despite advances in the
capabilities of modern personal computers, a momentary power outage is still all it takes to lose your data.
More dangerous is the loss of previously written files, or even an entire hard disk, which can occur should a power problem strike while your
computer is saving a file. Network file-servers constantly writing to disk are particularly susceptible.
Some African countries, including South Africa, have resorted to power rationing as a way to meet increasing demand. In these cases, the
question of whether or not to use power conditioning, is no longer a choice.
How Power Problems Can Be Avoided
Below is a table of power problems and how to solve them.
Equipment
Available
Automatic
Voltage
Regulator (AVR)
Line
Conditioner
Offline UPS
Line
Interactive UPS
True Online UPS
Frequency
Converter
Surges
Limited
Protection (MOV)
Full
Protection
None or Limited
Protection (MOV)
Limited
Protection
Good
Protection
Good
Protection
Spikes
Limited
Protection
Full
Protection
None or Limited
Protection (MOV)
Limited
Protection
Good
Protection
Good
Protection
Sags
Good
Protection
Full
Protection
None or Limited
Protection
Limited
Protection
Full
Protection
Full
Protection
Noise
Limited
Protection
Good
Protection
None or Limited
Protection
Limited
Protection
Good
Protection
Full
Protection
Blackout
(Power Failure)
No
Protection
No
Protection
Good Protection
4ms-8ms Changeover
Good Protection
Full
Protection (no break)
No
Protection
Frequency
Variation
No
Protection
Good
Protection
No Protection
Limited
Protection
Full
Protection
Full
Protection
Waveform
Distortion
No
Protection
Good
Protection
No Protection
Limited
Protection
Full
Protection
Full
Protection
Cable Selection Chart
Cable Size
Armoured Cable Free Air
Wired
Unarmoured Cable Free
Air Wired
Cable Size
Armoured Cable Free Air
Wired
Unarmoured Cable Free
Air Wired
2.5mm2
27 Amps
24 Amps
50mm2
150 Amps
140 Amps
4.0mm2
35 Amps
32 Amps
70mm2
180 Amps
175 Amps
6.0mm2
43 Amps
41 Amps
95mm2
225 Amps
215 Amps
2
10mm
60 Amps
55 Amps
120mm
2
260 Amps
250 Amps
16mm2
70 Amps
72 Amps
150mm2
290 Amps
280 Amps
25mm2
100 Amps
94 Amps
185mm2
340 Amps
330 Amps
35mm
125 Amps
115 Amps
240mm
400 Amps
385 Amps
2
2
2
POWER CONDITIONING & UPS
OVERVIEW OF DIFFERENT UPS TYPES
Most of the critical applications in data processing and other industries are now protected by Uninterruptible Power Supplies (UPS). It is
essential that the different types and performance levels are covered by international standards (IEC).
UPS systems are intended to improve the quality of AC power and provide a redundant (back-up) power source. Power quality defects which
may be improved by a UPS include surges, noise or sags.
Simplified Diagram of an “On-Line Double Conversion“ UPS
AC
Input
Static
Switch
~=
Battery
Rectifier/
Charger
=~
Load
Inverter
In this type of UPS the load is isolated from the mains, hence all the power to the load flows through the inverter, offering continuous
protection and full isolation against surges, noise and sags. It offers true on line protection.
Simplified Diagram of an “Offline“ UPS
AC
Input
Filter
~=
Battery
Rectifier/
Charger
Load
=~
Inverter
This type of UPS is not suitable for all applications because it does not use a static switch bypass and the switching times are longer. There
is no isolation between the load and the mains. There is also no output frequency control.
Simplified Diagram of an “Line-Interactive“ UPS
AC
Input
Transfer
Switch
Inverter
AVR
=~
Load
Battery
This type of UPS does not provide isolation between the mains and the load. There is poor protection against spikes and poor efficiency.
There is no output frequency control but it has voltage regulation on the output.
3
UPS - ACCESSORIES
SNMP CARDS
● Internal units to be used with UPS’s equipped with an intelligent slot
● External units to be used with UPS’s already equipped with RS232 communications
● Web server interface
● Linux, MAC and Windows compatible
● Remotely control UPS’s
● Battery management features for UPS’s being monitored
● SMS and Email capable for several UPS alarms and statuses
● Shut down multiple PC’s and/or servers during a power outage
GSM INTERFACE CARD
● Easy setup with any terminal
● Emulator software
● Flexible messages
● Dedicated standalone operation
● 10 SMS alarm recipients
● No need to use a PC
REMOTE ALARMS PANEL FOR UPS
● LED Indications for Mains Present, Mains Fail, Low Battery and UPS on Bypass
● To be used with UPS’s equipped with potential free alarm contacts
● Audible alarm
● Alarm can be cancelled with a push button
BATTERY CABINETS
● Used for all battery types
● In 7 different sizes, selection matrix below for
battery size and cabinet sizing requirements
4
No. of
Batteries
7.2Ah
8Ah
9Ah
12Ah
17Ah
20Ah
24Ah
28Ah
33Ah
45Ah
75Ah
100Ah
A1
6
6
6
4
4
4
2
3
2
2
1
1
A2
12
12
12
8
8
8
4
6
4
4
2
2
A4
24
24
24
16
20
20
8
12
12
8
4
4
A8
60
60
60
40
40
40
16
24
24
16
12
8
A12
90
90
90
60
60
60
24
36
36
24
18
12
A20
150
150
150
100
100
100
40
60
60
40
30
20
A35
270
270
270
180
180
180
80
110
105
70
50
35
UPS - LINE INTERACTIVE
MODIFIED SINEWAVE
T1X SERIES (650VA-2kVA)
● Compact size
● Excellent microprocessor control guarantees
high reliability
● Boost and buck AVR for voltage stabilisation
● Auto restart with AC recovery
● Simulated sinewave inverter output
● Off-mode charging
● Cold start function
● USB comm. standard with RJ11 telephone protection
Model
Capacity
1
ST1006X
ST1010X
ST1015X
ST1020X
650VA/360W
1000VA/600W
1500VA/900W
2000VA/1200W
Input
Voltage
110/120VAC or 220/230/240VAC
Voltage Range
81-145VAC or 162-290VAC
Frequency Range
50Hz or 60Hz (auto-sensing)
Output
Ac Voltage Regulation (Batt. Mode)
± 10%
Frequency Range (Batt. Mode)
50Hz or 60Hz ± 1Hz
Transfer Time
Typical 1-6ms, 10ms Max
Battery
Battery Type & Number
Backup Time (1 PC @ 120W load)
12V/7Ah x 1
12V/7Ah x 2
10 min.
30 min.
Typical Recharge Time
12V/9Ah x 2
40 min.
42 min.
4-6 hours recovery to 90%
Indicators
AC Mode
Battery Mode
Green LED on
Green LED Flashes
The right green LED is on and LED’s 2-5 indicate load level
Yellow LED Flashes
Fault
The right green LED flashes and LED’s 2-5
indicate battery capacity
Red LED Flashes
Protection
Full Protection
Overload, discharge and overcharge protection
Alarm
Battery Mode
Sounds every 10 seconds
Low Battery
Sounds every second
Overload
Sounds every 0.5 seconds
Battery Replacement Alarm
Sounds every 2 seconds
Fault
Continuously sounds
Physical
Dimension, D x W x H (mm)
Net Weight (kg)
287 x 100 x 142
350 x 146 x 160
4.25
8.0
230 x 500 x 280
11.1
11.5
Operating Environment
Humidity
Noise
0-90% RH @ 0-400C (non-condensing)
Less than 40dB
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
5
UPS - LINE INTERACTIVE
MODIFIED SINEWAVE
T1 SERIES (500VA-1kVA)
● Compact and stylish, ideal for office or home
● Excellent performance and reliability, designed for maximum equipment protection
● Advanced MCU control technology, enhancing UPS performance
● 500VA, 700VA and 1kVA, powerful enough for desktop PC’s
● Conforms to all necessary safety and CE specifications
● No noise, place it on your desktop
● Simple, easy to read LCD display
● Fast, low voltage protection buck and boost
● Predicting mains failure
● Automatic voltage regulation saving battery power
● Low battery protection preventing deep discharge
● Advanced battery management
● Modem, phone line and peripheral equipment protection
● Hot battery swap, no need to switch off UPS (except for 1kVA)
ST1005
Model
Capacity
500VA/300W
ST1007
700VA/420W
ST1010
1000VA/600W
Input
Input Voltage Range
220/230/240VAC (+25% / -30%)
Input Frequency
44Hz ~ 56Hz
Output
Output Voltage
220/230/240VAC ± 10% (On Battery Mode)
Output Voltage Regulation
± 10%
Output Frequency (Battery Mode)
Overload Capability
50 ± 0.1Hz
Delayed protection when the output is > 150% overload
Battery
Number of Batteries
1 cell
Recharge Time to 90%
1 cell
2 cells
< 10 hours
Transfer time
AC to DC
< typical 6 ms
Indication
LCD
AC Mode, Battery Mode, Output Status, Battery Capacity, Overload, UPS Fault
Audible Alarm
Battery Mode
Long beeping
Low Battery
Continuous beeping
Overload
Short beeping
Dimensions
W x H x D (mm)
90 x 165 x 325
90 x 165 x 325
120 x 210 x 380
6.3
6.6
15
Weight
Net Weight w/ Battery (kgs)
Environmental
Operating Temperature
-5 ~ +400 C
Relative Humidity
Audible Noise
< 90% (Non-Condensing)
<45dBA @ 1 Meter
<50dBA @ 1 Meter
<55dBA @ 1 Meter
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
6
UPS - LINE INTERACTIVE
PURE SINEWAVE
T2 SERIES (1kVA-3kVA)
Launched in 2005 and superseding the highly regarded PHD IP Series UPS, the T2 Series benefits from the latest
microprocessor Control Unit (MCU) technology, and now offers even greater value for money.
The T2 is aimed at users that require protection from line voltage fluctuations and require a
reliable and constant power source.The T2 is a sophisticated unit utilizing full digital control
technology. Available with power rating of 1kVA, 2kVA and 3kVA each with LCD display and
audible alarm keeping you quickly updated on mains and battery status. The T2 is also fitted
with an intelligent test button enabling a self-test routine which also prevents the UPS from being
inadvertently switched off.
1
FEATURES:
•
•
•
•
•
•
•
Extensive log files
Scheduled battery and inverter testing
Scheduled system shutdown/restart
User-Customisable commands and messages
Multiple UPS control from a single computer
Remote Console Command module for remote multiple server shutdown
Internal SNMP sub-agent for integration into existing NMS (e.g. HP OpenView, CA)
Model
ST2010
ST2020
ST2030
1000VA/700W
2000VA/1400W
3000VA/2100W
Capacity
Maximum Capacity
Input
Input Voltage Range
220/230/240VAC ± 25% Singe Phase w/Ground
Input Frequency
44Hz ~ 56Hz
Output
Output Voltage
220/230/240VAC ± 2%
Output THD
< 3%
Efficiency (Battery Mode)
82%
Output Frequency (Battery Mode)
50 ± 0.1Hz
Overload Capability (Normal Mode)
Sustaining 5 min @ 100 – 200%; 3 sec @ > 200%
Overload Capability (Battery Mode)
Sustaining 30 sec @ > 100%; 1 sec @ 150%
Battery
Number of Batteries
2 cells
4 cells
Recharge Time to 90%
6 cells
< 8 hours (adjustable)
Charge Current of Long Standby
Model *
5A
Indication
LCD
AC Mode, Battery Mode, Output Status, Battery Capacity, Overload, UPS Fault
Audible Alarm
Battery Mode, Low Battery, Overload
Long beeping, Continuous beeping, Short beeping
Physical
W x H x D (mm), Weight
150 x 220 x 460, 19kg
220 x 330 x 487, 32kg
220 x 330 x 487, 42kg
Environmental
Operating Temperature
Relative Humidity
Audible Noise
Communication Port
-5 ~400 C
< 95% (Non-Condensing)
<45dBA @ 1 meter
Standard RS232; USB or SNMP/HTTP (optional)
* All T2 models have a long standby option with no built in batteries, this is the charge current of the long standby models.
For long standby models, add “-L“ to the part number.
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
7
UPS - LINE INTERACTIVE
PURE SINEWAVE
T2R SERIES (2kVA-10kVA)
Features
• True Bi-Lateral Converter Line-interactive UPS
• Pure Sinewave and suitable for linear and nonlinear loads
• Rack and Tower Convertible
• Standard and long backup time models available
• Multi-Interface slot for RS232, SNMP, USB, RS485,
Modbus, Dry Contact and customised interfaces
• Various communication options selectable and all
can be available at the same time
• Complete protection for overload, overheat,
surges, spikes, short circuit and over charge
• Detachable two-way dialogue interactive dot-matrix
LCD control panel
• Real time remaining backup time calculations
• User friendly, swappable battery replacement design
• Built-in powerful charger with power factor
correction
• Emergency Power Off (EPO) available
• Intelligent fan speed control
• Cold start (DC start) function
• Compatible with generators
8
UPS - LINE INTERACTIVE
PURE SINEWAVE
Model
Capacity
ST2R20
ST2R30
ST2R50
ST2R75
ST2R100
2kVA/1250W
3kVA/1875W
5kVA/3125W
7.5kVA/4688W
10kVA/6250W
Input
Voltage
220/230/240VAC
Voltage Range
170VAC~300VAC
Frequency Range
45Hz~70Hz Auto-Sensing
Output
Voltage
220/230/240VAC ± 3% settable on the LCD
Frequency Range
50Hz or 60Hz ± 0.1Hz
Wave Form
Pure Sinewave
Efficiency (Line Mode / Battery Mode)
98% / 80%
Overload (Line Mode)
> 110% Buzzer alarms and Amber LED blinks continuously
Overload (Batt. Mode)
110%-150% for 30sec, > 150% for 200ms, then UPS shuts down
Battery
Battery Voltage
Battery Quantity
36Vdc
3 x 9Ah
48Vdc
6 x 7.2Ah
Charge Current of Long Standby Models **
8 x 9Ah
16 x 7.2Ah *
16 x 9Ah *
> 10A
N/A
Other
Transfer Time
< 4ms
Communication Interface
USB standard, RS232, RS485, SNMP, Dry Contact and AS400 available
Physical and Environmental
Operating Temperature
00C-400C
Relative Humidity
0-95% non-condensing
Audible Noise
Dimensions (W x H x D, mm)
< 55dBA (@ 1m)
440 x 88 x 465
440 x 132 x 465
440 x 132 x 620
Weight (kg)
24.5
36.9
49.8
IEC Outputs
6
10
10 + 1 Terminal
Block
440 x 132 x 465 (UPS),
440 x 132 x 465 (Battery Box)
34.6
(UPS only)
36.6
(UPS Only)
5 + 1 Terminal Block
Safety Standards
Safety
EN62040-1-1
EMC
EN62040-2
Marks
CE, UL, cUL
* Batteries on these models are external to the UPS cabinet
** Models from 2kVA - 7.5kVA have long standby models available, add “-L” to the model no. Charge currents on these of
up to 30A available on request.
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
9
UPS - LINE INTERACTIVE
PURE SINEWAVE (LONG STANDBY)
T2X SERIES (800W-8kW)
The Star T2X UPS is an All-In-One user friendly UPS, easy to
handle, suitable and compatible for almost all Home/Office
applications (Linear and non-linear loads including Air
Conditioners! ).
Being a line interactive UPS, it can produce clean and perfect
PURE SINEWAVES, by providing the best power quality for all your
electric equipment.
The traditional UPS supplies power only for a limited few minutes,
the T2X can function as an efficient GENERATOR! With an Auto
Transfer Switch, it can easily handle any critical power failure
situations.
Also, the T2X Series has a powerful charger that can supply a
capacity over 500 Ah, it can adapt itself and charge without any
damage to any type of battery. Its Solar Power Server allows the
UPS to work with solar panels to supplement the built in battery
charger of the UPS.
The Star T2X Series: an ecologic solution for homes and offices!
Feature:
Multiple microprocessor design base
powerful charger
Compatible with linear and non-linear load
Stronger charger to support batteries 500AH
and up
24 hours operation on the inverter
Auto transfer switch
Parameter presentable
DC start and automatic self-diagnostic
function
THD less than 3%
Pure sinewave
High efficiency design to save electricity
Low heat dissipation in long time operation
Designed to operate under harsh
environment
sinewave inverter
LCD Panel Control
Controllable & Removable panel with LCD
Wall Mounted Design or 19” Rack
solar power server
10
UPS - LINE INTERACTIVE
PURE SINEWAVE (LONG STANDBY)
Specification of Super Home UPS
A Positive DC connector
B Negative DC connector
C Cooling Fan
D AC Output Fuse
E AC Output Terminal Block
F Solar Panel Input
Capacity
1
Model
ST2008X
ST2010X
ST2020X
ST2040X
ST2060X
ST2080X
Watt/Amps
800W/3.6A
1600W/7.2A
2400W/10.9A
4000W/18.1A
6000W/27.2A
8000W/36.3A
Normal
Voltage
Acceptable
Voltage
220Vac / 110Vac
220Vac
120-275Vac / 60-135Vac
120Vac-275Vac
Frequency
Input
Voltage
Range
Output
50Hz / 60Hz (45Hz- 70Hz)
Line Low
Transfer
120Vac +-2% /60VAC +- 2%
120Vac+-2%
Line Low
Return
130Vac +-2% /65Vac +-2%
130Vac+-2%
Line High
Transfer
275Vac +-2% / 135Vac +-2%
275Vac+-2%
Line High
Return
260Vac+-2% / 130Vac +-2%
260Vac+-2%
220Vac (230V or 240 Vac re-settable via LCD panel);
110Vac (115V or 120Vac re-settable via LCD panel)
230Vac (220V
or 240Vac
re-settable via
LCD panel)
Voltage
Voltage Regulation (Batt
Mode)
<3% RMS for entire battery voltage range
Frequency
50Hz or 60 Hz
Frequency Regulation
(Batt Mode)
+-0.1 Hz
Power Factor
0.67
0.6
Waveform
Transfer
Time
Typical
Battery Voltage
Battery
Solar Power
< 8ms
12Vdc
24Vdc
Backup Time (at full load)
Max Charging
Current (3 steps
selectable )
0.62
Pure Sinewave
48Vdc
Long time available
>40A
Solar Power Server 50A
(Option)
>50A
>60A
Optional*
Standard
LCD Extended LCD
Display LCD Remote Control
(optional)
UPS status,I/P &O/P Voltage Frequency, Load%, Battery Voltage & %, Temperature, Model
LED
Normal (Green), Warning (Yellow), Fault (Red)
Battery Mode
Audible
Alarm
Beeping every 4 seconds
Low Battery
Beeping every second
UPS Fault
Beeping Continuously
Overload
Beeping twice per second. UPS will shutdown automatically in 30 seconds if overload is over
105~ 150% and up to 150 % will shutdown immediately.
Operation
Temperature
0-40 degree C; 32-104 degree F
Relative Humidity
0-95% non-condensing
Environment
Audible Noise
14
21
23
49.2
51.4
53.6
Physical
Dimension (WxHxD)mm
Rack Mount
440*132*290
440*132*360
440*132*360
N/A
N/A
N/A
Wall Mounted(W*H*D)mm
298*400*150
298*450*190
298*450*190
415*600*260
415*600*260
415*600*260
Net Weight (Kgs)
Less than 55dBA (at 1M)
* Add “S“ to the part number for the solar server option
Different specifications required are available
All specifications mentioned above are subject to change without prior notice.
11
UPS - ONLINE (TRANSFORMERLESS)
1 PHASE INPUT, 1 PHASE OUTPUT
•TRUE ON-LINE DOUBLE CONVERSION
TECHNOLOGY FOR HIGH LEVEL OF PROTECTION
•DSP TECHNOLOGY (FOR 6-10kVA MODELS)
•PARALLEL REDUNDANCY CAPABILITY (FOR 6-10kVA MODELS AS STANDARD)
•INTEGRATED SMARTCARD SLOT PROVIDING A CHOICE OF
COMMUNICATIONS
INTERFACES
•OPTIONAL SPECIALISED
UPS MANAGEMENT
SOFTWARE
•USER FRIENDLY LCD
DISPLAY
•FAILSAFE INTERNAL
BYPASS
•SWITCH WITH MANUAL CONTROL
•LONG RUNTIME
AVAILABILITY
T3 SERIES (1kVA-10kVA)
The T3 is a physically small On-Line double conversion UPS but
retains all the features normally associated with On-Line
technology, but what is On-Line double conversion technology and
why does it matter? Simply put “double conversion” is where the
mains supply is rectified to a clean DC voltage and rebuilt into a
very clean and regulated AC voltage, at all times your critical load
runs from this clean no break supply.
Line-Interactive and Off-Line UPS’s are single conversion, put in its
crudest form your computer runs on semi regulated mains and will
always suffer a small break in supply whilst the UPS moves from
mains mode to battery mode in a mains fail situation.
PARALLEL
A big advantage offered by the T3 6kVA to 10kVA is that by means
of a simple cable the machines can be linked together to form a
parallel N+1 system. This offers the client the opportunity to be
either a fail safe system or the option to expand the power as the
network grows. Up to three machines can be connected in this way
making the T3 a flexible and versatile solution.
UPS MANAGEMENT SOFTWARE
The UPS management software is installed on a server or
workstation connected to each UPS via the serial or USB port.
Power failure, power restored, battery failure or eight events will
be detected and the user informed. A shutdown will be initiated
when the batteries are exhausted or a technical problem occurs
with the UPS. The UPS management software disconnects, logs
out users and closes open applications(subject to application/
operating system support) before shutting down the operating
system itself.
SIMPLE NETWORK MANAGEMENT
PROTOCOL (SNMP)
The T3 SNMP external agent can be located up to 5 metres
away from the UPS. Initial configuration is carried out by
serial comms using any suitable terminal application (e.g.
Hyperterminal for Windows).
The embedded HTTP server presents an HTML
interface to the network, which can be accessed
from any web browser. All system parameters can be
configured from here including scheduled shutdown.
A sophisticated JAVA applet provides full monitoring
in real time, along with comprehensive events and
history logs.
12
UPS - ONLINE (TRANSFORMERLESS)
1 PHASE INPUT, 1 PHASE OUTPUT
Model
ST3010
ST3020
Topology
ST3030
ST3060
ST3100
6000VA/ 4200W
10000VA/7000W
True On-Line, Double Conversion
On-battery Waveform
Pure Sine Wave
Input
Maximum Capacity (VA/W)
1000VA/ 700W
2000VA/ 1400W
3000VA/ 2100W
Nominal Input
230VAC
Input Voltage Regulation
160~300 VAC Single Phase w/ Ground
Nominal Input Frequency
1
170~285 VAC Single Phase w/Ground
50/60 ± 4Hz
Input PFC
≥0.95
≥0.98
Input Short Protection
Circuit Breaker
Output
Nominal Output
220/230/240 VAC nominal
Output Regulation
Output T.H.D
± 2%
≤3% (Linear Load)
≤6% (Non-Linear Load)
± 1%
≤4% THD (Linear Load)
≤7% THD (Non-Linear Load)
High Efficiency Mode (AC to DC)
85%
85%
High Efficiency Mode (DC to AC)
83%
83%
Crest Factor
≤2% THD (Linear Load)
≤6% THD (Non-Linear Load)
88%
> 88%
83%
> 88%
3:1
Start on Battery
Yes
Output Frequency
50 Hz ± 0.2 Hz
50 Hz ± 0.5 Hz
Battery
Typical Backup Time (at full load)
16 minutes
Battery Type
Number of Batteries
20 minutes
15 minutes
18 minutes
14 minutes
Sealed Lead-Acid maintenance-free 12VDC/7Ah per cell
3 cells
12VDC/9Ah per
cell
8 cells
Recharge Time to 90%
20 cells
5 hours
Charge Current of Long Standby
Model *
7 hours
8A
8 hours
4.2A **
Advanced Warning
Diagnostics
Front Panel Indication – LCD
UPS Status, I/P Voltage & Frequency, O/P Voltage & Frequency,
Battery Voltage, Battery Capacity, Loading %, Temperature, History Alarm.
Front Panel Indication – LED
Normal (Green), Warning (Yellow), Fault (Red)
Audible Alarms
Battery Mode, Low Battery, Overload, Fault
Communication
Interface
Communication Port
RS232 (Standard), DB9 or USB or AS400 or SNMP / HTTP (Optional)
Environmental
Audible Noise
< 45dBA @1 meter
< 50dBA @1 meter
< 55dBA @1 meter
160 x 220 x 400
200 x 352 x 450
260 x 717 x 570
Mechanical
Dimensions (W x H x D mm)
Weight (Net Weight with Battery)
(kgs)
15
34
35
90
93
* All T3 models have a long standby option with no built in batteries, this is the charge current of the long standby models. For long standby
models, add “-L“ to the part number.
** 6 and 10kVA models can have up to 25A charging capabilities when connected in parallel with the ST-CHARGER external super charger.
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
13
UPS - ONLINE (TRANSFORMER)
1 PHASE INPUT, 1 PHASE OUTPUT
T3T SERIES (10kVA - 15kVA)
The T3T is a transformer isolated On-Line double conversion UPS but what is On-Line
double conversion technology and why does it matter? Simply put “double conversion” is
where the mains supply is rectified to a clean DC voltage and rebuilt into a very clean and
regulated AC voltage, at all times your critical load runs from this clean no break supply and
is isolated from the input.
•TRUE ON-LINE DOUBLE CONVERSION
TECHNOLOGY FOR HIGH LEVEL OF PROTECTION
•DSP TECHNOLOGY
•PARALLEL REDUNDANCY CAPABILITY (OPTIONAL)
•INTEGRATED SMARTCARD SLOT PROVIDING A CHOICE OF
COMMUNICATIONS
INTERFACES
•OPTIONAL SPECIALISED
UPS MANAGEMENT
SOFTWARE
•USER FRIENDLY LCD
DISPLAY
•FAILSAFE INTERNAL
BYPASS
•SWITCH WITH MANUAL CONTROL
•LONG RUNTIME
AVAILABILITY
14
Line-Interactive and Off-Line UPS’s are single conversion, put in its crudest form your
computer runs on semi regulated mains and will always suffer a small break in supply whilst
the UPS moves from mains mode to battery mode in a mains fail situation.
PARALLEL
A big advantage offered by the T3T is that by means of a simple cable the machines can
be linked together to form a parallel N+1 system (only for 10kVA and 15kVA models). This
offers the client the opportunity to be either a fail safe system or the option to expand the
power as the network grows. Up to three machines can be connected in this way making
the T3T a flexible and versatile solution.
UPS MANAGEMENT SOFTWARE
The UPS management software is installed on a server or workstation connected to
each UPS via the serial or USB port. Power failure, power restored, battery failure or
eight events will be detected and the user informed. A shutdown will be initiated when
the batteries are exhausted or
a technical problem occurs with
the UPS. The UPS management
software disconnects, logs out users
and closes open applications(subject
to application/operating system
support) before shutting down the
operating system itself.
SIMPLE NETWORK
MANAGEMENT
PROTOCOL (SNMP)
The T3T SNMP external agent can
be located up to 5 metres away
from the UPS. Initial configuration
is carried out by serial comms using
any suitable terminal application
(e.g. Hyperterminal for Windows).
The embedded HTTP server
presents an HTML interface to the
network, which can be accessed
from any web browser. All system
parameters can be configured from
here including scheduled shutdown.
A sophisticated JAVA applet
provides full monitoring in real time,
along with comprehensive events
and history logs.
UPS - ONLINE (TRANSFORMER)
1 PHASE INPUT, 1 PHASE OUTPUT
Model*
ST3020T
Topology
ST3030T
ST3050T
ST3060T
ST3100T
ST3150T
True Online Double Conversion, Isolated Transformer Output
Input
Maximum Capacity (kVA/kW)
2/1.4
3/2.1
5/3.5
Input Voltage Regulation
10/7
15/10.5
220VAC ±25%
Nominal Input Frequency
Battery Voltage
6/4.2
1
50Hz ± 5%
48VDC
96VDC
192VDC
Output
Output Regulation
220VAC ± 2%
Waveform
Sinewave, ≤3% THD
Switch Time
0ms
Overload Capacity
125% for 60 seconds, 150% for 0.5 seconds
Crest Factor
3:1
Start on Battery
Output Frequency
Yes
Automatic synchronous tracing when power supply normal, at 50Hz ± 0.5% when power supply
abnormal
Battery
Back up time**
Battery efficiency
Charging***
15 mins
25 mins
10 mins
>80%
10 mins
Any backup time
>87%
>89%
Intellectual MMBM battery control technique, unique multi-charging mode improving the reliability and
lengthening the life of the batteries
Other Features
Panel Display
Input voltage, Output voltage, Load capacity, Battery voltage
LED indicating lights show the working status
Alarm
Protection Function
Mains supply abnormal, Low battery, Overload
Protection for low battery, overload, over temperature, short circuit, output over voltage, output low
voltage
Parallel function*
N/A
Random extending or N+1
redundancy parallel connection
Communication Interface
Communication Function
Remote Control (Optional)
RS232 communication port supports UPSilon 2000 software (standard). Supports SNMP adapter for
network management (optional).
Independent digital remote control at the distance of 1000 meters supported by RS485, which supports
remote monitoring
Dry connection
The port allows a 2A current, convenient and safe
Environmental
Audible Noise
< 55dBA @1 meter
< 60dBA @1 meter
Work Temperature, Relative Humidity
0~40 C, 0~95%(no condensation)
Altitude
Meet GB/T 7260.3-2003 standard
0
Mechanical
Dimensions (W x L x H mm)
Weight (with & without batteries) (kgs)
230 x 620 x
470
65/52
230 x 635 x 690
82/58
90/57
400 x 800 x 1180
108/61
210/92
250/140
* T3T10kVA and 15kVA models have a parallel redundant option, add “-P“ to the part number.
** T3T 2kVA-15kVA models have a long standby option with no built in batteries, add “L“ to the part number for these models.
*** 5-15kVA models can have up to 15A charging capabilities when connected in parallel with the ST-CHARGER external super charger.
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations. Specification or
design can be changed at anytime without prior notice.
15
UPS - ONLINE (TRANSFORMERLESS)
1 PHASE INPUT, 1 PHASE OUTPUT
•EXTENSIVE LOG FILES
•SCHEDULED BATTERY AND
INVERTER TESTING
•SCHEDULED SYSTEM
SHUTDOWN/RESTART
•USER-CUSTOMISABLE
COMMANDS AND
MESSAGES
•MULTIPLE UPS CONTROL
FROM A SINGLE
COMPUTER
•REMOTE CONSOLE
COMMAND MODULE FOR
REMOTE MULTIPLE SERVER
SHUTDOWN
•INTERNAL SNMP
SUB-AGENT FOR
INTEGRATION INTO
EXISTING NMS (E.G. HP
OPENVIEW, CA
UNICENTER
T3R SERIES (1kVA-10kVA)
With ever greater demands being made on valuable floor space, many IT managers
are moving towards computer rack solutions rather than conventional floor standing
options offered in the past. The same philosophy has affected the UPS industry with
many UPS now being located with the computer inside the rack cabinet. On-Line
UPS have historically been handicapped in this particular market sector, essentially
for two reasons, size and price.
Most IT managers have dealt with this problem by moving to Line-Interactive and
Off-Line topologies. As these technologies have fewer fail safe features and for the
most part only work when a problem occurs. With the introduction of the T3R series
these past limitations are no longer valid.
The T3R is a physically small On-Line double conversion UPS but retains all the
features normally associated with On-Line technology, but what is On-Line double
conversion technology and why does it matter? Simply put, “double conversion”
is where the mains supply is rectified to a clean DC voltage and rebuilt into a very
clean and regulated AC voltage, at all times your critical load runs from this clean
no break supply. Line-Interactive and Off-Line UPS are single conversion, put in its
crudest form, your computer runs on semi regulated mains and will always suffer a
small break in supply whilst the UPS moves from mains mode to battery mode in a
mains fail situation. The T3R offers a competitive price, even against the more basic
technologies, but unlike these technologies you will get as standard an LCD screen,
RS232, USB port options, battery extension options, battery monitoring, no-break
supply, static switch, wide voltage input without using batteries, optional software,
comms slot for SNMP, Relays or Optocoupler.
SIMPLE NETWORK MANAGEMENT
PROTOCOL (SNMP)
The T3R SNMP external agent can be located up to 5 metres away from the UPS.
Initial configuration is carried out by serial comms using any suitable terminal
application (e.g. Hyperterminal for Windows). The embedded HTTP server presents
an HTML interface to the network, which can be accessed from any web browser.
All system parameters can be configured from here including scheduled shutdown.
A sophisticated JAVA applet provides full monitoring in real time, along with
comprehensive events and history logs.
UPS MANAGEMENT SOFTWARE
The UPS management software is installed on a server or workstation connected to
each UPS via the serial or USB port. Power failure, power restored, battery failure
or eight events will be detected and the user informed.
A shutdown will be initiated when the batteries are exhausted or a
technical problem occurs with the UPS. The UPS management
software disconnects, logs out users and closes open
applications(subjet to app/os support) before shutting down the
operating system itself.
16
UPS - ONLINE (TRANSFORMERLESS)
1 PHASE INPUT, 1 PHASE OUTPUT
Model
ST3R10
ST3R20
Topology
ST3R30
ST3R60
ST3R100
True On-Line, Double Conversion
Output Waveform
Pure Sine Wave
Input
Maximum Capacity (VA/W)**
1000VA/700W
2000VA/1400W
Nominal Input Voltage
Input Regulation Voltage
3000VA/2100W
6000VA/4200W
10000VA/7kW
1
230 VAC
160~300 VAC Single Phase w/ Ground
Nominal Input Frequency
160~300 VAC Single Phase w/ Ground
50/60 ± 4Hz
Input PFC
≥0.95
≥0.98
Input Short Protection
Circuit Breaker
Output
Nominal Output Voltage
220/230/240 VAC nominal
Output Voltage Regulation
Output T.H.D
± 2%
≤3% (Linear Load)
≤6% (Non-Linear Load)
≤4% THD (Linear Load)
≤7% THD (Non-Linear Load)
≤2% THD (Linear Load)
≤6% THD (Non-Linear Load)
High Efficiency Mode (AC to DC)
85%
85%
88%
> 88%
High Efficiency Mode (DC to AC)
83%
83%
83%
> 88%
Crest Factor
3:1
Start on Battery
Yes
Output Frequency
50 Hz ± 0.2 Hz
50 Hz ± 0.5 Hz
Battery
Typical Backup Time
Battery Type
Number of Batteries
16 minutes
20 minutes
15 minutes
18 minuts
Sealed Lead-Acid maintenance-free 12VDC/7Ah per cell
3 cells
8 cells
Recharge Time to 90%
20 cells
5 hours
Charge Current of Long Standby Model *
14 minutes
12VDC/9Ah per cell
7 hours
8A
8 hours
4.2A **
Advanced Diagnostics
Front Panel Indication – LCD
UPS Status, I/P Voltage & Frequency, O/P Voltage & Frequency,
Battery Voltage, Battery Capacity, Loading %, Temperature, History Alarm.
Front Panel Indication – LED
Normal (Green), Warning (Yellow), Fault (Red)
Audible Alarms
Battery Mode, Low Battery, Overload, Fault
Communication Interface
Communication Port
RS232 (Standard), DB9 or USB or AS400 or SNMP / HTTP (Optional)
Environmental
Operation Temperature
0-400 C
Storage Temperature
-150C to 500C
Relative Humidity
Audible Noise
20% to 90% non-condensing
< 45 dBA @ 1 meter
< 50 dBA @ 1 meter
< 55 dBA @ 1 meter
440 x 88 x 465
(with internal batteries)
440 x 88 x 465 (UPS only)
440 x 88 x 465 (External Battery)
440 x 132 x 640 (UPS Only)
440 x 132 x 640 (External Battery)
Mechanical
Dimensions (W x H x D mm)
Weight (Net Weight with Batteries) (kgs)
15.5
35
36
85
88
* All T3R models have a long standby option with no built in batteries, this is the charge current of the long standby models. For long
standby models, add “-L“ to the part number.
** 6 and 10kVA models can have up to 25A charging capabilities when connected in parallel with the ST-CHARGER external super charger.
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
17
UPS - ONLINE (TRANSFORMERLESS)
1 PHASE INPUT, 1 PHASE OUTPUT
FP SERIES (1kVA-6kVA)
•TRUE ON-LINE DOUBLE CONVERSION
TECHNOLOGY FOR HIGH LEVEL OF PROTECTION
The FP series UPS is a true on-line double conversion UPS offering rack and tower
placements. It is a reliable and effective system to protect critical systems from power
outages and sags. The FP series is designed for optimising power quality with the ease
of installation.
•CONTINUOUS BATTERY
CHARGER AND INVERTER
FOR PRIMARY POWER PATH
•
•
•
•
•
•CONSTANT BATTERY
CONNECTION TO INVERTER
AND LOAD
•GUARANTEES FULL POWER
OPERATION DURING
POWER FAILURE
•NO VOLTAGE DROP AND
ZERO TRANSFER TIME
•LIGHT WEIGHT UNIT
•HOT-SWAPPABLE BATTERY
•USER-FRIENDLY GRAPHIC
LCD DISPLAY
•FLEXIBLE MOUNTING
ORIENTATION
•ROTATABLE LCD DISPLAY
FOR TOWER OR 19” RACK
CONCEPT
APPLICATIONS
FEATURES
•
•
•
•
•
•
•
•
Flexible Mounting Orientation: Allows system integrators more flexibility in
designing their backup power system to maximize space. With the rotatable
LCD design, installers can mount the UPS vertically or horizontally.
User-Friendly Graphic LCD: This robust LCD display enables field service
engineers to easily troubleshoot the UPS without opening the box, thus
reducing downtime.
Single Voltage Battery Pack Design: A 48VDC
standard battery pack design comprised of 4 x 12V7AH is used in all FP series
UPS models and is interchangeable with each other.
Hot-Swappable Battery: The standard 48VDC battery pack allows installers to
take the headache out of battery installation. Installers can now simply slide the
used battery pack out of the unit and replace it with a new pack. All FP battery
packs are interchangeable reducing the risk of system failures.
Light Weight Design: The FP model is specifically designed for field
installation. The light weight design requires only a single installer to put the
system in place. This will significantly reduce on-the-job injuries and installation
fees.
User-Remote Interface / Cruiser: The off-site user can now test, set
parameters, monitor power status, save file, and shutdown the system all via
remote inerface. The user-remote interface includes SNMP/HTTP Card, RS232,
USB, DB9, and AS400 interface.
STANDARD ACCESSORIES
•
Mounting Feet: Two (2) mounting feet for tower
configuration are supplied with the FP Series
UPS 1KVA to 1.6KVA. All other models 2.2KVA to
3.2KVA are self supporting.
•
Racking Ears: Standard 19” rack mounting ears
are available for all FP Series UPS models.
•USER REMOTE INTERFACE/
CRUISER
18
Computers
Network Servers
Workstations
Wireless Communications
Other Electronic Peripherals
UPS - ONLINE (TRANSFORMERLESS)
1 PHASE INPUT, 1 PHASE OUTPUT
FP1600
Model
FP2500
Topology
On-battery Waveform
FP3200
FP6000
True On-Line, Double Conversion
Pure Sine Wave
Input
Maximum Capacity (VA/W)
1600VA / 1120W
2500VA / 1750W
Nominal Input (Voltage Regulation) *
3200VA / 2240W
6000VA / 4200W
1
230VAC (160VAC-276VAC)
Nominal Input Frequency
50/60 ± 5Hz
Input PFC
> 0.98 @ Full Load
Input Short Protection
Circuit Breaker
Output
Nominal Output (Voltage Regulation)
208/220/230/240 VAC nominal (Rated Voltage ± 2%)
Output T.H.D
< 3% @ Linear Load
High Efficiency Mode (AC to AC)
> 88%
Crest Factor
Output Frequency
Overload Capability
90%
3:1
50 / 60Hz (Autotracking)
Sustaining 50sec @ 108% Load; 28sec @ 110-120% Load; 15sec @ 120-130% Load; 9sec
@ 140-145% Load; Immediate Response @ 150% Load
Battery (Extendible in 2U High Modules) **
User Replaceable Battery
Typical Backup Time (Full / Half Load)
48V (1 x 48VDC
Battery Pack)
96V (2 x 48VDC
Battery Pack)
96V (2 x 48VDC
Battery Pack)
96V (2 x 48VDC Battery
Pack)
7 / 18 min
8 / 20 min
6 / 17 min
4 / 10 min
Battery Type
Sealed VRLA 12V7Ah; Hot Swap
Recharge Time to 90%
8 hours
4 hours
Advanced Warning Diagnostics
Front Panel Indication
Audible Alarms
Front panel menu driven LCD monitoring and control panel for all functions
DC Mode, Low battery, Voltage / Frequency Error, Charger Fail, High Temp, Overload, Fault,
PFC Overload
Communication Interface
Communication Port
RS232 (Standard), DB9 or USB or AS400 or SNMP / HTTP (Optional), SNMP (Optional)
Environmental
Operation Temperature
0 ~ +400 C
Storage Temperature
-15 ~ +500 C
Relative Humidity
0% - 95% non-condensing
Audible Noise
< 45dBA @ 1 meter from surface of the unit
Mechanical
Dimensions (W x H x D mm) - Rack Position
Weight (UPS / Battery Packs)
426 x 88 x 500
426 x 176 x 500
426 x 88 x 500
426 x 176 x 500
12kg / 11.2kg
13.2kg / 31.2kg
13.4 / 31.4kg
16kg / 31.4kg
Conformance
EMI / RFI Compatibility
Safety Certifications
EN50091-2 Class B, EN55022B
CE, TUV / GS
* 110V systems available on request
** Each battery module comprises 2 x 48VDC battery packs in a 2U box.
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
19
UPS - ONLINE (TRANSFORMERLESS)
3 PHASE INPUT, 1 PHASE OUTPUT
The T4 is a physically small On-Line UPS but retains all the
features normally associated with double conversion technology.
Simply put "double-conversion" is where the mains supply is
rectified to a DC voltage and rebuilt into a very clean and regulated
AC voltage, at all times your critical load runs from this clean no
break supply.
•DSP TECHNOLOGY
PARALLEL
•PARALLEL REDUNDANCY
CAPABILITY AS STANDARD
•IGBT INVERTER
TECHNOLOGY
•SNMP/HTTP OPTION FOR
REMOTE MANAGEMENT &
INTEGRATION INTO NMS
A big advantage offered by the T4 10kVA to 20kVA is that by means
of a simple cable the machines can be linked together to form a
parallel N+1 system. This offers the client the opportunity to either
have a fail safe system or the option to expand the power as the
network grows. Up to three machines can be connected in this way
making the T4 a flexible and versatile solution.
ULTRA COMPACT
With a very small footprint you will find a ready home for the T4 in
even the most hard-pressed data center. Installing such a compact
free-standing UPS avoids taking up valuable rack space without
significantly reducing the available floor area.
•SMART RS232 AS
STANDARD
DISPLAY PANEL
•INTEGRATED SMARTCARD
SLOT PROVIDING
A CHOICE OF
COMMUNICATIONS
INTERFACES
ADVANCED BATTERY MANAGEMENT
•OPTIONAL SPECIALISED UPS
MANGEMENT SOFTWARE
•USER FRIENDLY LCD
DISPLAY
•FAILSAFE INTERNAL BYPASS
SWITCH WITH MANUAL
CONTROL
•LONG RUNTIME
AVAILABILITY
20
T4 SERIES (10kVA-20kVA)
•TRUE ON-LINE DOUBLE CONVERSION
TECHNOLOGY
FOR ULTIMATE POWER
PROTECTION
LCD display and audible alarms actively let you know if the unit is
on battery, the battery charge is low, or there is an overload
condition. Loading and battery information via the LCD prevent you
from exceeding the UPS capacity and allow you to assess the
remaining runtime before battery reserves are depleted.
A variable boost charger ensures quick battery recharge. This
means that the T4 UPS is fully prepared for duty with a minimum
recovery time in the event of a power failure. Active
battery management intelligently monitors the battery
set with automatic battery and circuitry self-tests,
this feature increases both battery life and system
reliability.
UPS MANAGEMENT
One standard management tool can be used to
monitor and control all your UPS’s from one central
location. This means power management can now
be integrated into your existing network or building
management strategy. Alarms (‘traps’) can be
configured to ensure automatic notification of events
such as low battery, mains failure or overload. Two
such tools can be used with the T4: Simple Network
Management Protocol (SNMP) and UPS Management
Software via RS232.
UPS - ONLINE (TRANSFORMERLESS)
3 PHASE INPUT, 1 PHASE OUTPUT
Model
ST4100
ST4150
Topology
ST4200
True On-Line, Double Conversion
On-battery Waveform
Pure Sine Wave
Input
Maximum Capacity (kVA/kW)
10kVA/ 7kW
15kVA/ 10.5kW
Nominal Input Voltage
1
380VAC Three Phase (3 Φ 4W + G)
Input Voltage Regulation
304 ~ 478 VAC
Nominal Input Frequency
50/60 ± 4Hz
Input PFC
Input Short Protection
20kVA/ 14kW
≥0.95 @ full load
50A Circuit Breaker
100A Circuit Breaker
Output
Nominal Output Voltage
220/230/240 VAC Single Phase (1 Φ 2W + G)
Output Voltage Regulation
± 1%
Output T.H.D
≤2% THD (Linear Load), ≤6% THD(Non-Linear Load)
Efficiency – Normal Mode
88%
Efficiency – Battery Mode
88%
Crest Factor
3:1
Start on Battery
Yes
Overload Capability (Normal Mode)
Sustaining 10 min @ 105% ~ 130% load; 1sec @ > 130% load
Overload Capability (Battery Mode)
Shut down UPS after 10 sec @ > 150% load
Output Frequency
50/60 Hz ± 0.05 Hz (Battery Mode)
Battery
Battery Type
Sealed Lead-Acid maintenance-free 12VDC/7Ah per cell
Number of Batteries
40 cells
Typical Backup Time at Full Load
22 mins
40 cells
40 cells
15 mins
11 mins
Recharge Time to 90%
< 8 hours
Charger Current (Max)
4.2A *
Advanced Diagnostics
Front Panel
Indication – LCD
UPS Status, I/P Voltage & Frequency, O/P Voltage & Frequency,
Battery Voltage, Battery Capacity, Loading %, Temperature, History Alarm.
Front Panel Indication – LED
Normal (Green), Warning (Yellow), Fault (Red)
Audible Alarms
Battery Mode, Low Battery, Overload, Fault
Communication Interface
Communication Port
RS232 (Standard), DB9 or USB or AS400 or SNMP / HTTP (Optional)
Environmental
Audible Noise
< 55dBA @ 1 meter
Mechanical
UPS Dimensions (W x H x D mm)
260 x 717 x 570
Battery Cabinet Dimensions
(W x H x D mm)
260 x 717 x 570
UPS Weight (kgs)
39
55
55
Battery Cabinet (w/battery) (kgs)
143
143
143
Total Weight (kgs)
182
198
198
* All T4 models can have up to 25A charging capabilities when connected in parallel with the ST-CHARGER external super
charger.
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
21
UPS - ONLINE (TRANSFORMER)
3 PHASE INPUT, 1 PHASE OUTPUT
T4T SERIES (10kVA-50kVA)
The T4T Series UPS is an online sine wave UPS mainly designed for major equipment used in
large-scaled data centers (such as measurement equipment, industrial automation equipment,
etc.) with high performance. Its high reliability provides necessary protection on load for
the users in finance, communication, traffic, tax, forces, security, power source, education,
government and enterprise etc. The T4T Series UPS is true double conversion on-line
UPS. With IGBT power units, SPWM inverter, intellectual multi modes battery management
technique, advanced tech and power management software.
TRUE ONLINE DOUBLE CONVERSION UPS
Output is fully isolated by a transformer, with IGBT power units used to solve problems on the
electric system such as lightning strikes, power blackouts, etc.
EMC COMPLIANT
All products are EMC compliant. Testing points include conducting disturbance, radiant
disturbance, conducting ant-disturbance, radiant ant-disturbance, power fault, mass pules, ESD
etc. Excellent EMC features make the T-UK Series capable of high frequency communication
and video & audio broadcasting.
COLD START FUNCTION
Because of special current limiting circuits on the UPS, the user can start the
UPS directly on its battery bank without mains being available. The UPS has
a more powerful cold starting capability and is able to run on full load.
PERFECT PROTECTION MEASURES
Protection for over output voltage and current, low battery, quick current
limit and short-circuit to avoid stoppages caused by the user’s incorrect
operation.
INTELLIGENT BATTERY MANAGEMENT TECHNOLOGY
Equipped with patented intellectual battery management technique. With
proffessional management design on battery charging or discharging, the
user can get high battery reliability and running life. At the same time the
intellectual charging module can select the right charging power according
to different battery configurations making sure that there is rapid power
compensation on the battery bank.
FLEXIBLE NETWORK SUPERVISION
Flexible network supervising ability to realize intellectual monitoring of the
UPS. Including close point-to-point communication supervising, middle
range communication supervising, and remote network management. Based
on these, there are many UPS functions such as real time supervising over
running status and features, automatic call, sending e-mail, cell phone text
messaging, voice function, remote on/off for the UPS etc.
CURRENT EQUALISATION CONTROL TECHNIQUE
Current equalisation control technique, for N units parallel redundancy or
N+1 redundant parallel connection, digitized current equalisation control,
reliability and redundancy of the system is higher than traditional parallel
systems and field installation and debugging is simple. UPS unit can be
switched on or be on line on standby mode, to enable hot maintenance on
line of parallel system.
22
UPS - ONLINE (TRANSFORMER)
3 PHASE INPUT, 1 PHASE OUTPUT
1
Model
ST4100T
ST4150T
ST4200T
ST4300T
ST4400T
ST4500T
Input
Voltage Range
400VAC (-25%~+25%)
Frequency Range
50Hz / 60Hz ± 5%
Phase
Battery Voltage
Three phases, five wires
16 x 12Vdc = 192Vdc
29 × 12Vdc = 348Vdc
Output
Rated Power - kVA/kW
10/7
15/10.5
Voltage Range
20/16
30/24
40/32
50/40
230VAC ± 2%
Frequency
50Hz ± 1%(battery mode)
Waveform
THD ≤ 3%(linear load)
Battery Efficiency
≥ 90% (100% linear load)
Overload Capacity
10min at 105%, 1min at 125%, 0.5s at 150%
Crest Factor
3:1
Parallel Equal Current
≤ 5%(only applicable to the parallel models)
Other
Parallel Function
Random extending or N+1 redundancy parallel connection (only applicable to the parallel models)
LCD Display
Input voltage, Output voltage,
Load capacity, Battery voltage
LED Display
Alarm Function
Operation status
Mains supply abnormal, Low
battery, Overload
Communication Function
Low battery, Overload, Overheat, Output short circuit, Output over voltage
Audible Noise
< 60dBA @ 1m
00C-400C, 0-95% (no condensation)
Working Temperature,
Relative Humidity
Weight (kg)
Overload, AC input abnormal, Low battery, Failure, Overtemperature
RS232/RS485, dry connection communication signal
Protection Function
Dimension (W x D x H)
(mm)
Input voltage, Frequency, Output voltage, Battery voltage, Load,
DC current etc.
740 x 300 x
100
135
800 x 400 x 1180
160
205
225
280
305
10-15kVA models can have up to 15A charging capabilities when connected in parallel with the ST-CHARGER external super charger.
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
23
UPS - ONLINE (TRANSFORMER)
3 PHASE INPUT, 3 PHASE OUTPUT
T5 SERIES (10kVA-400kVA)
ST5 (10kVA-400kVA) features true on line double conversion and zero sec. transfer time.
Intellectual blocking design, adopts advanced power apparatus IGBT, predominantly a
SPWM inverter. It also features MMBM intellectual multi-modes battery management and
intellectual monitoring and management software. The parallel capacity can extend the on
line parallel redundancy or N+1 for upgradeability.
TRUE ONLINE DOUBLE CONVERSION
Output is isolated by a transformer, with IGBT power units used, making sure a safe
working environment for all equipment. Isolation between N and G, and anti-impact from all
kinds of surgres and disturbances in power.
3 output phases can be adjusted independently, thus allowing 3 phase 100% unbalanced
load, flexible load capacity and high system reliability. Especially fit for
computer rooms, communication etc.
RELIABLE EMC FEATURES
All products have passed the EMC tests. Testing includes conducting
disturbance, radiant disturbance, conducting anti-disturbance, radiant
anti-disturbance, power fault, mass pulse, surge, ESD etc. Excellent
EMC features allow the ST5 series to be capable of high frequency
communication and video & audio broadcasting.
COLD START FUNCTION
Due to a special current limiting circuit on the UPS, the user can start the
UPS directly from the battery bank connected for emergency stituations
in a no mains situation. The UPS can run on cold start on full load.
FULL FUNCTION LCD DISPLAY
All ST5 series products above 20KVA are equipped with large LCD
Displays. They also feature real time surveillance on UPS running
parameters and status, FE and daily maintenance.
The ST5 features an Intelligent battery management system while
batteries are being charged and discharged for longer operational life
and higher reliability of the batteries.
FLEXIBLE NET PROJECT MONITORING
(OPTIONAL)
Independent digital remote control, supported by RS485, with a range of
1000 meters or SNMP network adapter
ADVANCED NON-MASTER-SLAVE SELFADAPTIVE CONTROL TECHNOLOGY (PARALLEL
TYPE)
ST5 series parallel UPS features a powerful parallel capacity. There is no
need to set the parallel units. The User can extend the parallel capacity
as needed for N+1 parallel redundancy. This increases the reliability of
the power system.
24
UPS - ONLINE (TRANSFORMER)
3 PHASE INPUT, 3 PHASE OUTPUT
Model
ST5
010
ST5
020
ST5
030
ST5
040
ST5
050
ST5
060
ST5
080
ST5
100
ST5
120
ST5
160
ST5
200
ST5
300
ST5
400
Input
Voltage *
380/400VAC ± 25%
Rectifier Frequency
Range
1
40Hz~65Hz
SYNC Frequency
Tracking Range
50Hz ± 5% (± 10% option)
Phase
3φ4W+PE
Battery
12Vdc × 29 = 348Vdc / 12vDC x 30 = 360Vdc
Charge Current (Max)
5~40A (adjustable)
5~80A (adjustable)
Charge DC Voltage
Regulation
395V ± 5Vdc
DC Ripple Voltage
<1%
Output
Capacity (kVA)
10
20
30
40
50
60
80
Power Factor
100
120
160
200
300
400
0.8
Phase
3φ4W+PE
Voltage *
L-N: 220VAC ±1%, L-L: 380VAC ± 1%
Frequency
Utility normal, follow in phase automatically, Utility fault, output frequency at 50Hz ± 0.2%
Parallel mode
(optional)
None-principle-subordinate Adaptive Control Technique, User can extend parallel capacity as needed for N+1
parallel redundancy
3 phase 100% load unbalance voltage stability
≤2%, allows 100% unbalance
Waveform
Sinewave THD ≤ 3% (linear load)
Crest Factor
3:1
Efficiency
90%
Static Bypass
Transfer Time
0ms
Overload Capacity
110% load for 30 min,125% load for 10 min,150% load for 1min
Regulation no load to
full load steady state
±2%
Other
Panel Display
LCD Display indicates 3 phase input voltage, input frequency, 3 phase output voltage, load, battery voltage, battery
charging and discharging etc. LED indicates running status
Battery Self-Testing
Automatically sounds an alarm and estimates battery status in battery abnormal status
Lightning Protection
Complies with IEC 1312
Operating Temp.,
Humidity
Dimension
(W x D x H) (mm)
Weight (kg)
0 C-400C, 95% (non-condensing)
0
500 x 800 x 1180
185
205
235
800 x 800 x 1600
430
450
470
1000 x 800 x 1800
680
705
745
1800 x
1000 x
2000
805
1400
2200 x 1000 x 2000
2350
2380
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
25
UPS - ONLINE (TRANSFORMER)
3 PHASE INPUT, 3 PHASE OUTPUT
FEATURES
• Wide input range,
robust design for harsh
environments
• DC start function, can
be started without AC
• Intelligent, safe
and unique battery
management system
• Variety of accessories
• Parallel operation
available
• Specifications can be
customised
• Frequency converter
option available
T6 SERIES 10kVA-1MVA
The AEC Star T6 series UPS is an on-lne double conversion three phase UPS with a fully
digitised intelligent galvanic isolation design. Single unit ratings of up to 1MVA are available
and parallel capability is also available. The UPS can also be cusomised for various input
voltages allowing them to be used in various applications (e.g. mining).
FEATURES AND ADVANTAGES
Advanced Technology DSP, IGBT and Switching
Components
To increase reliability and efficiency.
True Galvanic Isolation Design
An isolation transformer is used on the output. This can solve numerous problems such as
poor input grounding, different grounds between input and output and ground leakage currents.
The user also has the benefit of attenuation of common mode noise from the output isolation
transformer.
Multi-CPU design and Software/Hardware Cooperate Control
Several CPU’s are employed in the control circuitry, critical functions are designed to employ
parallel redundancy to improve reliability.
Redundant Power Supply
An extra power supply is connected redundantly to supply power to the static switch, so that,
there will be AC ouput no matter what happens to the UPS.
Plug and Play Modular Design
The power circuit is seperated into several modules plugged into slots in the UPS,
which is easy to remove, allowing for quick maintenance and easier troubleshooting.
Each Phase with Individual Inverter Support
Allowing for 100% unblanced load.
Protection Against Detached or Floating Neutral of
the Input
MOV’s are used at the input and provide sufficient protection to both the UPS and
the load from any lightning or surges casued by neighbouring large loads.
Large Charging Power (Selectable)
The charge power is selectable according to the Ah of the battery bank. Ah ratings
to allow for 8 hours backup time can be supported with no additional
external chargers needed.
Various Interface Options
Remote control panel, 3 phase software for PC monitoring, auto dialling module,
battery monitoring module, 3 Phase SNMP card, emergency stop switch.
12-Pulse Fully Controlled Rectifier (Optional)
In order to further improve the power factor and reduce harmonic current drawn
by the rectifier, the UPS from 120kVA uses a 12-pulse fully controlled rectifier.
The total harmonic current can be reduced to around 10% and the power
factor improved to over 0.8. A phase shift transformer is added to achieve the
performance. The input inductor is retained to obtain the best result. This is a
more rugged topology.
Parallel Operation (Optional)
To increase the capacity and reliability of the UPS. The load is equally shared
between the paralleled units. When there is a fault with one of the units, the other
units continue running without output interruption.
26
UPS - ONLINE (TRANSFORMER)
3 PHASE INPUT, 3 PHASE OUTPUT
Model
kVA
ST6
010
ST6
015
ST6
020
ST6
030
ST6
040
ST6
050
ST6
060
ST6
080
ST6
100
ST6
120
ST6
160
ST6
240
ST6
320
ST6
400
10
15
20
30
40
50
60
80
100
120
160
240
320
400
Input (Rectifier)
Input Voltage
190V / 208V / 380V / 400V / 415V / 440V / 480V / 600V, 3P4W or 3P3W
Input Range
± 20% (> 20% available on request)
Input Frequency
50Hz / 60Hz ± 5Hz
Power Walk In
0% - 100% : 20sec
1
Battery
DC Voltage
Maximum Charge
Current
29 x 12Vdc = 348Vdc
5
8
10
15
20
25
30
40
50
60
80
120
160
200
17.4
21.7
Inverter
Output Voltage
Regulation
190V / 208V / 380V / 400V / 415V / 440V / 480V / 600V, 3P4W or 3P3W ± 1%
Output Power Factor
0.8
Output Frequency
50Hz / 60Hz ± 3Hz (lock range), 50Hz / 60Hz ± 0.1Hz (free running)
Phase Shift
< 0.50 at 100% unbalanced load
THD (Linear Load)
< 2%
Overload
< 110% Continuous, 110%-125% 15mins, 125%-150% 10mins, > 150% 30sec
Efficiency at 100%
Load
93%
93.5%
94%
94.5%
95%
92.5
93
Overall Characteristics
Overall Efficiency
91
Maximum Heat
Dissipation (kW)
1.1
1.3
Dimensions (L x W x
H) (mm)
Weight (kg)
91.5
1.9
2.6
92
3
3.5
4.6
550 x 800 x 1600
270
300
Audible Noise
Temperature / Humidity
350
400
480
FCC Class A,
EN50091-1, -2
Short Circuit Protection
Lightning / EMC Filter
6.5
8.7
1100 x 800 x 1600
550
680
820
950
< 65dBA (at 1m)
1180
13
2200 x 800 x
1600
1450
1950
2450
3300 x
800 x
1600
3100
< 67dBA (at 1m)
00C-400C, 320F-1040F / 0-90% (Non-condensing)
Altitude
12 Pulse Rectifier
5.4
< 1500m above sea level
Optional
Standard
Yes
Rectifier, Reserve and Bypass
MOV / Input & Output
Galvanic Isolation
Output true Galvanic Isoation (input available on request)
Indicator & Alarm
LCD, LED, Mimic Display, Buzzer
Remote Control
/ Communication
Interface
Monitoring 1-99 UPS simultaneously / Dry Contact, RS232, RS485
Bigger sizes up to 1000kVA available
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
27
UPS - ONLINE (TRANSFORMER)
3 PHASE INPUT, 3 PHASE OUTPUT
T2000 SERIES (20kVA-600kVA)
With many thousands of units sold, the PHD T2000 series UPS is now legendary. Chosen
by major enterprises around the world for its reliability and performance, words simply can’t
explain its phenomenal success. But we don’t rest on our laurels, the T2000 has been
modified and updated and now offers even greater performance. With a Mean Time Before
Failure of power to the load in excess of 20 years the T2000 is even better value for money.
And with power ratings from 50kVA to 600kVA and higher, the T2000 is engineered to
offer power protection sufficient to support a whole building if required. And as your power
requirements grow, more T2000 units can be added, offering superb flexibility.
EXPANDABLE TO PROTECT
For genuinely redundant power protection, UPS can be installed in either active parallel
or hot standby mode, ready to take over the load automatically in the event of a critical
component failure. The T2000 can be configured to function in either active parallel or hot
standby mode, with up to 6 units in the array. In active parallel mode, the load is balanced
across all the configured units, ensuring that no single member of the array is overstressed.
If a unit needs to be shutdown for maintenance or repair, the remaining units in the array
will rebalance the load and continue to provide uninterrupted protection. It is even possible
to remove a unit from the array during an outage without affecting the load while the
remaining units retain sufficient battery runtime. In hot-standby mode, one or more units
support the load, while the remaining members of the array functions as standby unit. The
standby unit is continually on-line, but only takes over the load when one of the primary
units is no longer active. This means that there is no break when power is transferred, and
the load continues to be supported without disturbance.
MANUAL AND STATIC BYPASS TO PROTECT
A manual by-pass switch allows power to be transferred directly to the mains without
disturbance to the load. The UPS can then be safely powered down for maintenance or
repair, on completion of the work the UPS can be powered up and the load once again
transferred back to the UPS with no interruption in service. If the power demand of your
equipment exceeds the overload level of the UPS the static switch defaults to
the mains ensuring continuous power in the event of system abuse or short term
overload conditions.
TIME TO PROTECT
In addition to providing sufficient run-time to save files and shutdown operating
systems, autonomies of up to 8 hours are available allowing you the option to
complete a day’s work without disturbance to your equipment, even during a power
cut!
UPS MANAGEMENT SOFTWARE
The UPS management software is installed on a server or workstation connected
to each UPS via the serial port. Power failure, power restored, battery failure or
eight events will be detected and the user informed. A shutdown will be initiated
when the batteries are exhausted or a technical problem occurswith the UPS. The
UPS management software disconnects network connections, logs out users and
closes open applications (subject to app/os support) before shutting down the
operating system itself.
SIMPLE NETWORK MANAGEMENT PROTOCOL (SNMP)
The T2000 SNMP external agent can be located up to 5 metres away from the
UPS. Initial configuration is carried out by serial comms using any suitable terminal
application (e.g. Hyperterminal for Windows). The embedded HTTP server
presents an HTML interface to the network, which can be accessed from any web
browser. All system parameters can be configured from here, including scheduled
shutdown. A sophisticated Java applet provides full monitoring in real time, along
with comprehensive event and history logs.
28
UPS - ONLINE (TRANSFORMER)
3 PHASE INPUT, 3 PHASE OUTPUT
1
Model*
ST20003360
ST20003380
ST200033100
ST200033120
ST200033150
ST200033200
60
80
100
120
150
200
Input Rectifier
Nominal Capacity - kVA
Input Nominal Voltage
200/208 V 3P or 380/400/415 V 3P + N or 440/465/480 V 3P
Nominal Frequency
50 / 60 Hz (Can be used as frequency converter)
Frequency Range
+ - 5%
P.F. @ 400V at Nominal
0,83 or 0,93 with Input Filter/PFC
Soft Start time
20-30 seconds
Battery
Charge Current (Max)
12Vdc x 32 = 384Vdc
20A
30A
40A
60A
Inverter Input
Nominal Voltage
192 V for 200/208 V – 384 V for 380/480 V
Inverter Output
Nominal Voltage
Current at p.f 0.8
200/208 V 3P or 380/400/415 V 3P + N or 440/465/480 V 3P
86.71
115.6
144
174
Nominal Frequency
50/60 Hz
THD Linear load
=<1,5%
THD at Non Linear load with Crest Factor 3:1
=<5%
Static Voltage Regulation
+ - 1%
Dynamic Voltage Regulation 0-100%
+ - 5%
221
287
Output Frequency Regulation
With Mains
Synchronisation (%)
+/- 1; 1,5 ;2,4
With Internal Micro
+ - 0,001%
Load Crest (Ipk/lrms)
Better than 3 : 1
Overload
110% for 60 min -- 125% for 10 min -- 150% for 1 min
Efficiency AC-AC @ 100%
93.4
93.5
94.1
95.1
Mechanical Data
Dimensions (W x H x D) (mm)
Weight (kg)
800 x 750 x 1200
580
630
1400 x 750 x 1200
670
700
900
1100
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
29
UPS - ONLINE (TRANSFORMERLESS)
3 PHASE INPUT, 3 PHASE OUTPUT
HOT SWAPPABLE SERIES
HOT SWAPPABLE SERIES
10kVA-100kVA
Power+ is a state-of-the-art modular UPS system based on the true on-line battery topology. The
Power+’s modular design makes scalability simple; its high power density provides the benefits
of a small footprint and low heat dissipation. The Power+’s rich management and communication
capabilities include remote monitoring and control over the Internet or via cellphone. Its hybrid
static switch ensures high reliability and compliance with IEC standards.
•TRUE ON-LINE
THE UPS THAT GROWS WITH YOUR BUSINESS
•PARALLEL
Power+ is a true modular, user-upgradeable system. As load increases you can insert up to
a total of ten 10kVA hot-swap plug-in modules, each weighing only 9kg. The power+ can be
configured in parallel for N+1 or N+2 redundancy.
•REDUNDANT
•DOUBLE CONVERSION
•MODULAR
•GREEN AND CLEAN POWER
•HIGH EFFICIENCY
TRUE ON-LINE
BATTERY
The Power+ inverter
complies with the IEC62040-3 standard by its
ability to take its input
power from either the ac
input (via the rectifier) or
the battery, and supply
power to the load. The
battery is galvanically
connected between the
rectifier output and the
inverter input on a common
DC link.
PARALLEL
POWER+ SYSTEMS
Connecting two or more
Power+ units in a parallel
configuration provides
increased reliability and/
or greater output power
capacity. Power+ units
equipped with the optional
parallel kit share the load
equally.
30
UPS - ONLINE (TRANSFORMERLESS)
1 PHASE INPUT, 1 PHASE OUTPUT
SPECIFICATIONS
10kVA
20kVA
30kVA
Topology
40kVA
50kVA
60kVA
70kVA 80kVA
90kVA
100kVA
True Online Battery, Double Conversion VFI
Construction
Modular parallel hot-plugged modules, continuous operation
Input
Voltage
1
3 x 380/400/415V+N+PE (5 wires system)
Voltage Range
-27% to +20%
Current
15A per phase for a single module, no inrush current at startup
Frequency
47-63Hz
Power Factor
1
THDI
< 5%
Output
Rated Power
10kVA/8kW to 100kVA/80kW
Frequency Tracking Range
±0.5, ±1, ±2, ±3, ±4Hz (selectable)
Frequency (in free-running mode)
50/60Hz ± 0.1%
Slew Rate
1Hz/Sec
Voltage
3 x 380/400/415V+N+PE (selectable)
Static Regulation
±1%
Regulation for unbalanced load
±1% for 100% unbalanced load
Dynamic Response to 100% Load Step
±2%, < 1ms recovery time
Overload
110% for 10min., 125% for 60sec, 1000% for cycle 1
Waveform
Sinusoidal
THD
Less than 2% for linear load
Load CF (max)
6:1
AC-AC Efficiency (nominal)
Up to 96%
DC-AC Efficiency (nominal)
Up to 98%
Batteries
DC-Link Voltage
±432V
Number of Batteries
64 x 12V
General
Maximum Power Dissipation (Po=8kW)
333W (1136 BTU/h) for a single module
Ambient Temperature, Relative Humidity
-10 to +40 (operating); -200 to +600 (storage), 95% max non-condensing
Acoustic Noise dBA (half load and full load)
0
48/51
52/54
0
53/55
54/57
55/58
56/59
56/59
57/60
58/61
58/61
Standards
EMC
EN50091-2 Class A; IEC 62040-2
Safety
EN50091-1; IEC 62040-1-1
Design
EN50091-3; IEC 62040-3
Low Magnetic Field Radiation
EMF as per ICNIRP
Weight and Dimensions
10kVA Module (H x W x D)
88mm (2U) x 483mm (19”) x 455mm
Weight
Power+ System
9kg
Height (cm)
69
79
88
97
107
Width (cm)
60
Depth (cm)
69
Power+ System Weight (kg)
98
113
128
143
158
116
125
135
144
154
173
188
203
218
233
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
31
INVERTER/CHARGERS
MODIFIED SINEWAVE
IG Series - Inverter/Charger (600VA-2kVA)
● Simulated sinewave inverter
● Selectable input voltage range for home appliances and personal computers
● Auto restart with AC recovery
● Overload, and short circuit protection
● Cold start function
● Generator and Computer-related products compatible
● Reverse polarity protection
Model
Capacity
IG600
IG1000
IG2000
600VA/300W
1000VA/600W
2000VA/1200W
Input
Voltage
Selectable Voltage Range
220/230/240VAC
140-300VAC
90-280VAC (wide range), 170-280VAC (narrow range)
Frequency Range
50Hz/60Hz (auto-sensing)
Output
AC Voltage Regulation (Batt. Mode)
±10% (battery mode)
Frequency Range (Batt. Mode)
50Hz/60Hz ±1Hz
Transfer Time
10ms Typical
Battery
Battery Voltage
12Vdc
24Vdc
Floating Charge Voltage
13.7Vdc ±2%
26.8Vdc ±2%
Low Battery Alarm Voltage
10.2Vdc ±2%
21.6Vdc ±2%
Shutdown Voltage
9.9Vdc ±2%
20.0Vdc ±2%
Overcharge Protection
15Vdc ±2%
30Vdc ±2%
Maximum Charge Current
13A
10A or 20A optional
Alarm
Low Battery
Sounding every second
Overload
Sounding evry 0.5 seconds
Fault
Continuously sounding
Physical
Dimensions, L x W x H (mm)
Net Weight (kg)
358.5 x 96.8 x 146.5
5.8
232 x 293 x 82.5
2.35
Operating Environment
Humidity
Operating Temperature
Storage Temperature
0-90% Relative Humidity (Non-Condensing)
00C-500C
-150C-700C
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
32
2.55
INVERTER/CHARGERS
MODIFIED SINEWAVE
SKX-M Series - Modified Sinewave Inverter (150W-3kW)
● Modified sinewave output
● With or Without Battery Charger
● High Surge Rating
● Hot Swappable Fuse
● Reverse Polarity Protection (Fuse)
2
Model
Capacity (Watts)
SKX150-MXX
SKX300-MXX
SKX500-MXX
SKX600-MXX
SKX1000M-XX
SKX1500M-XX
SKX2000M-XX
SKX2500M-XX
SKX3000M-XX
150
300
500
600
1000
1500
2000
2500
3000
Output Waveform
Modified Sinewave
Continuous Power (Watts)
150
300
500
600
1000
1500
2000
2500
3000
Surge Power (Watts)
300
600
1000
1200
2000
3000
4000
5000
6000
DC Input Voltage
10-15Vdc (12V Version) / 20-30Vdc (24V Version) / 40-60Vdc (48V Version)
AC Output Voltage
220-240VAC ± 10%
Output Frequency
50/60Hz ± 1Hz
Efficiency
No Load Current Draw
> 85%
< 0.25A
< 0.3A
< 0.8A
< 0.9A
< 0.95A
Protection
Low Voltage Alarm
10Vdc ± 0.2V / 20Vdc ±0.3V / 40Vdc ± 0.4V
Low Voltage Shutdown
9.5Vdc ± 0.2V / 19Vdc ± 0.3V / 38Vdc ± 0.4V
Over Voltage Shutdown
15.5V / 30.5V / 61.2V
Overload
Shut Off Output
Over Temperature
Shut Off Output
Environment
Operating Temperature
-100C - 500C
Operating Relative Humidity
20% - 90% RH non-condensing
-300C - 700C
Storage Temperature
Turns on above 450C
Automatic Cooling Fan
Dimensions (mm)
Net Weight (kg)
Battery Charger Specs Model
Charging Current
Automatic Transfer Time
140 x
105 x
55
0.5
SKX150MC-XX
3A
150 x
105 x
55
0.6
180 x 105 x 55
0.8
0.8
SKXSKXSKX300500600MC-XX MC-XX MC-XX
5A
10A
X Denotes the DC Voltage - 12Vdc, 24Vdc and 48Vdc available
X
10A
210 x
150 x
70
1.7
SKX1000MC-XX
10A
310 x 150 x 70
2.4
2.6
340 x 150 x 152
5.9
SKXSKXSKX15002000- 2500MC-XX MC-XX MC-XX
15A
20A
20A
6.1
SKX3000MC-XX
30A
< 40ms
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at any time without prior notice.
33
INVERTER/CHARGERS
PURE SINEWAVE
Solar Inverters - Pure Sinewave (150W-3kW)
● True sinewave output
● Power ON-OFF remote control
● Advanced microprocessor
● Input polarity / under voltage / over voltage protection
● Output short circuit / overload / over temperature protection
● Capable of driving highly reactive and capacitive loads
● Three color LED indicators
Model*
Rated Power/Surge Power
S150-X
S300-X
S600-X
150W/200W
300W/400W
600W/800W
SK1000-X SK1500-X
1kW/2kW
SK2000-X
SK3000-X
2kW/4kW
3kW/6kW
1.5kW/3kW
Output
AC Voltage
220/230/240VAC
Waveform
True Sinewave (THD < 6%)
True Sinewave (THD < 3%)
Frequency
50Hz / 60Hz
50Hz / 60Hz selectable by DIP switch
AC Regulation
± 5%
± 3%
Power Factor Allowed
cosѲ(-90 ) - cosѲ(+90 )
0
LED Indicator
0
Input voltage level, output load level and fault status
Input
DC Voltage
No Load Current Draw
Voltage Ramge
Efficiency (typ. %)
12/24
0.22/0.16
12/24/48
0.26/0.28
0.83/0.43/0.22
1.2/0.6/0.28
10.5-15/21-30
87/88
89/89
1.4/0.7/0.4
2.64/1.32/0.65
2.8/1.5/0.7
10.5-15/21-30/42-60
90/93/94
91/93/94
90/93/94
91/94/95
90/93/94
Protection
Bat. Low Alarm
Bat. Low Shutdown
N/A
11V / 22V / 44V
10 ± 0.5V / 20 ± 1V
Overload
Over Voltage
10.5V / 21V / 42V
Shut off output voltage, re-power on to recover
15V-16V / 30V-32V
Over Temperature
15.3V / 30.6V / 61.2V
Shut off output voltage, recovers automatically after temperature goes down
Output Short
Shut off output voltage, re-power on to recover
Bat. Polarity Reverse
Fuses will become open
Environment
Working Temp.
0-400C
Working Humidity
20% - 90% RH non-condensing
Storage Temp. & Humidity
-300C-700C / -220F-1580F / 10%-95%
Safety & EMC
Isolation Resistance
EMI Conduction and Radiation
I/P - O/P: 100M Ohms / 500VDC
Compliance EN55022
class B
EMS Immunity
Compliance EN55022 class A
Compliance EN61000-3 -2, 3
LVD
Compliance EN60950-1
e-Mark
Compliance to e-13 * 72/245/EEC, 95/54/EC
Other
Dimensions, L x W x H (mm)
200 x 132
x 72
237 x 155
x 72
295 x 180
x 72
383 x 182
x 88
415 x 191
x 88
422 x 208 x
166
* X denotes the DC Voltage
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
34
452 x 208 x
166
INVERTER/CHARGERS
PURE SINEWAVE
SKX-S Series - Pure Sinewave Inverter (300W-5kW)
● Pure sinewave output
● With or Without Battery Charger
● High Surge Rating
● Hot Swappable Fuse
● Reverse Polarity Protection (Fuse)
● Remote Control Option: Control at a distance
2
Model
Capacity (Watts)
SKX300-SXX
SKX500-SXX
SKX600-SXX
SKX1000S-XX
SKX1500S-XX
SKX2000S-XX
SKX2500S-XX
SKX3000S-XX
SKX5000-SXX
300
500
600
1000
1500
2000
2500
3000
5000
Output Waveform
Pure Sinewave (THD < 4%)
Continuous Power (Watts)
300
500
600
1000
1500
2000
2500
3000
5000
Max Constant Power Start
(Watts)
360
600
720
1200
1800
2400
3000
3600
6000
Surge Power (Watts)
600
1000
1200
2000
3000
4000
5000
6000
10000
DC Input Voltage
10-15Vdc (12V Version) / 20-30Vdc (24V Version) / 40-60Vdc (48V Version)
AC Output Voltage
220-240VAC ± 10%
Output Frequency
50/60Hz ± 1Hz
Efficiency
> 90%
No Load Current Draw
< 0.6A
< 0.8A
< 0.9A
< 0.95A
< 1.5A
Protection
Low Voltage Alarm
10Vdc ± 0.2V / 20Vdc ±0.3V / 40Vdc ± 0.4V
Low Voltage Shutdown
9.5Vdc ± 0.2V / 19Vdc ± 0.3V / 38Vdc ± 0.4V
Over Voltage Shutdown
15.5V / 30.5V / 61.2V
Overload
Shut Off Output
Over Temperature
Shut Off Output
Environment
Operating Temperature
-100C - 500C
Operating Relative Humidity
20% - 90% RH non-condensing
-300C - 700C
Storage Temperature
Turns on above 450C
Automatic Cooling Fan
Dimensions (mm)
135 x
150 x
53
Net Weight (kg)
0.85
1.4
SKX300SC-XX
5A
Battery Charger Specs Model
Charging Current
Automatic Transfer Time
220 x 150 x 70
280 x
150 x
70
290 x
220 x
88
320 x
220 x
88
1.5
2.5
2.8
3
SKX500SC-XX
SKX600SC-XX
SKX1000SC-XX
SKX1500SC-XX
SKX2000SC-XX
10A
10A
10A
15A
20A
X
X Denotes the DC Voltage - 12Vdc, 24Vdc and 48Vdc available
410 x 150 x 70
5.9
6.1
480 x
220 x
146
14
SKXSKX2500- 3000SC-XX SC-XX
20A
< 40ms
30A
N/A
N/A
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at any time without prior notice.
35
SWITCH MODE RECTIFIERS
1 PHASE & 3 PHASE
ES1948 SERIES - Switching Mode Rectifier
FEATURES:
• Innovative single phase
and three phase input
stage with wide input range
(90-275VAC, 310-480VAC)
• Power factor > 0.99
• High efficiency
• Microprocessor based
• Active or passive load
sharing
• Rear “push in to plug in“
connection for AC, DC and communications link
• Weight less than 1.9kg
• Exceptional power density (>18W/in3)
APPLICATIONS:
• Telephone Exchanges
• Cellular Phone/ Radio Base Stations
• Satellite Base Stations
• Microwave Links Remote Multiplexes
• Rural Telecomunications
• PABX’s
• Railway Switching Controls
• Transmission and ISDN
Equipment
• Power Plants
• Airport, Hospital, Banks
The PHD ES1948-48V/39.6A is a switched mode rectifier (SMR) module designed to provide
up to 39.6A of output current into a 48V nominal system. This rectifier has been designed
especially to be used in conjunction with a battery to provide an uninterruptable DC power
system. The low noise and high reliability make it ideally suited to telecommunications
applications. The rectifiers are designed to slide and plug into a single magazine-SR1948-9,
designed for a 19” rack, which can accommodate up to 9 rectifiers and up to 32 rectifiers can
be configured as a system using one control and supervisory unit (MCSU2048).
The ES1948 Switching Mode Rectifiers are highly compact, highly efficient, fully featured
switch mode rectifiers which can operate in a modular rack environment with overall control
from the control and supervisory unit MCSU2048. With overall control, such features as
active current sharing, accurate battery voltage regulation, battery recharging current limit
control, automatic battery equalization and battery temperature compensation are achieved.
The ES1948 rectifier modules incorporate a microcontroller-based control card which
incorporates the control and supervisory facilities of the SMR. The microcontroller
enables digital communications to the MCSU2048 as well as to the outside world (via the
MCSU2048), so that it is possible to examine the operating parameters and, if necessary
change them to suit a particular situation, from a remote location, even a distant one if a
modem is used. This method of monitoring and control opens up entirely new methods of
routine and emergency maintenance procedures.
INTERFACE BOARD AND OPTIONAL ACCESSORIES
MUIB: PHD’s MUIB board combined with MCSU, external transducers and digital or analog
I/O contacts to control and monitor a 24V or 48V or 110V DC power system. It provides a
basic interface between the MCSU and the system environment.
MMIB (optional): PHD’s MMIB board is an add-on module for the MCSU. It is used to
monitor external AC power sources in either single phase or three phase configurations
during operation.
BCM (optional): PHD’s BCM board is an add-on module for the MCSU. It is used to monitor
individual cells of a batteries during either float, equalize operation, or discharge. Each BCM
board is capable of monitoring up to 24 cells(BCM) or 96 cells(BCM2).
SMM (optional): PHD’s SMM board is an expansion of the MCSU. It allows the user to
monitor the status of equipment that is external to PHD’s DC power system. It can also be
used to monitor a 3rd party DC power system. Using the same communication link and
winCSU2000 software, the SMM can supervise numerous off-site systems from a central
monitoring station.
WinCSU2000: PHD’s WinCSU2000 software is an intuitive program designed for the
Windows 95,98 and NT environments. Working through MCSU and interface boards, you can
monitor and control PHD’s DC power system either locally or remotely through a modem.
MCSU NetAgent ǁ: PHD has integrated various
communication protocols over networking to enable
the equipment’s real-time remote monitoring and
management via MCSU NetAgent ǁ. It is equipped
with a UTP RJ45 plug for 10Base-T or 100M fast
Ethernet connecting through TCP/IP, UDP, HTTP,
Telnet, SNTP, PPP or SMTP protocol to LAN and
WAN. It also has a RS232 port to connect with an
external modem to dial in via the PPP protocol to
access an internet connection.
36
SWITCH MODE RECTIFIERS
1 PHASE & 3 PHASE
ES1948
Model
Input
Voltage
Wide Input Range: 90-275Vac or 310-480Vac
Frequency
Input Protection
44~66 Hz
13A HRC fuses at input of SMR(line and neutral); power circuit is turned off if the AC voltage exceeds
275Vac or falls to less than 90Vac
Current
Power Factor
THD
Efficiency
<12A rms
>0.99 at full load; sinusoidal wave shape
<5% at full load; satisfies requirements of EN61000-3-2
>91% at nominal mains voltage
Output
Voltage
Float: -Adjustable 48~59V; Equalise: -Adjustable 50~61V
Current Limit
Adjustable 5~40A
Power (Max)
1900W at 48~60Vdc(input>185Vac); 900W at 48~60Vdc(input 90~185Vac)
Load Sharing
Better than ±5% of full scale with active current sharing from MCSU2048
Protection
Static Regulation
Dynamic Regulation
Output Noise
3
Overvoltage - only faulty unit shuts down
Overcurrent - can sustain short circuit at output terminals indefinitely
Over-temperature - gradual reduction of current limit if heat-sink temperature exceeds pre-set limit
Line- +0.1%; Load- +1.0%
+3% for 10~90% or 90~10% load variation; +1% for +25% step change in AC input voltage
< 2mVrms Psophometric weighting; < 10mVrms 10kHz - 100MHz; < 100mV peak to peak 0~30MHz
bandwidth
Other
Surge Protection
EMC
Inrush Current
Voltage Withstand Test
EN 61000-4-5
Emission: EN 61000-6-3,Immunity: EN61000-6-1
<12 Arms peak at nominal mains voltage
3.0 kVac – input and output (4.25 kVdc primary-secondary); 1.5 kVac – input earth (2.12 kVdc
primary-ground); 0.75 kVdc – output earth
Environmental
Audible Noise @ 1m
Operating Temperature
< 65dBA
Operating range -40 C ~ 700C; derated power at 500C ~ 700C
0
Cooling
Two fan cooled, speed controlled and alarmed
Humidity
0~95% non-condensing
Mechanical
Dimension (W x H x D)
Weight
41mm x 144mm x 287mm
<1.9kgs(4.19lbs)
Alarms
Alarm & Status LED
indication on SMR
Rectifier Alarms
On (Green) - SMR functioning normally
Alarm (Yellow) - Blinking when any SMR alarm is present.
Shutdown (Red) - Stays on when SMR has turned off due to a signal from the MCSU2048 or an
internal fault
Low/High output voltage alarm; Over voltage shutdown alarm; Current limit alarm; Fan Alarm;
Temperature alarm; Rectifier failure alarm
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
37
BATTERY CHARGER
FOR 192VDC & 240VDC SYSTEMS
External Battery Super Charger
DESCRIPTION:
The PHD external battery charger is suitable for any 192Vdc and 240Vdc system (16 and 20 batteries in series). It is designed for 192Vdc
and 240Vdc UPS systems to enable longer standby times for them. The 240Vdc version can be used with PHD’s T3 Series (6-10kVA models) and T4 Series (10-20kVA models) and the 192Vdc version can be used with PHD’s T3T Series (5-15kVA) and T4T Series (10-15kVA).
It is easy to install as it is connected in parallel to the UPS’s existing battery charger.
FEATURES:
•
•
•
•
Compact and light
Easy to install
Battery overcharge protection
Input surge protection
Model
ST-CHARGER-10A
ST-CHARGER-12A
Input
Voltage
(176 -276)VAC @ Full Load
Frequency
(46 - 75)Hz for 50Hz system
Power Factor
≥[email protected] full load
THD
<20%@ full load
Output
Current
10A Nom. / 10A Max.
12A Nom. / 21A Max.
Voltage
160V Minimum, 218V Nominal, 224V Maximum
200V Minimum, 273V Nominal, 280V Maximum
Voltage Ripple
1%@ full load
Current Ripple
10% of Ah CAP @ full load
Efficiency
90%
Fault Protection
Output Reverse Polarity Protection
Fuse will open when reversing
Short-circuit Protection
Input Protection
Yes
276Vac(+/- 2%) Over Voltage, 176 Vac(+/- 2%) Under Voltage, 110%,1s Open Circuit
Fault Protection
00C - 400C
Working and Storage Temperature
Humidity
<95% (No condensing)
Altitude
< 1000m
Fault Protection
ESD
IEC 61000-4-2 Level 4
RS
IEC 61000-4-3 Level 3
EFT
IEC 61000-4-4 Level 4
Surge
IEC 61000-4-5 Level 4
Conduction
IEC/EN 62040-2 Category C3
Radiation
IEC 61000-3-2
Safety
IEC 60950-1/EN 60950-1
Drop, Variation
ISTA Procedure 2A
Mechanical Characteristics
Inlet, Outlet
Dimensions (W x D x H) (mm)
Net Weight (kg)
38
Terminal Block
200 x 352 x 450
340 x 250 x 110
15
6
BATTERY CHARGERS
MISCELLANEOUS
AC-DC Battery Chargers
FEATURES:
•
•
•
•
•
•
•
•
•
•
•
Multi step charger setup and auto shutdown (tri step)
Fast charge, normal charge and average charge
Voltage with auto sensor battery
Full charge with auto shutdown
Output short circuit protection
Universal input voltage suitable for worldwide operation
Anti-reverse voltage protect device
Fast charge transferred into slow charge
Overload protection
LED status display
Suitable for lead acid battery
Model
3
Input Voltage
Input
Frequency
Output
Current
Output
Equaliser
DC Voltage
Output
Floating
DC Voltage
Dimensions
(L x W x H) mm
Net
Weight
AC0212A
100-240VAC
50/60Hz
2A
14.6Vdc
13.7Vdc
120 x 61.6 x 37.4
0.5kg
AC0224A
100-240VAC
50/60Hz
2A
29.2Vdc
27.4Vdc
120 x 61.6 x 37.4
0.5kg
AC0312A
110/220Vdc ±10% AUTO SW
50/60Hz
3A
14.6Vdc
13.7Vdc
186 x 88 x 47.5
0.8Kg
AC0324A
110/220Vdc ±10% AUTO SW
50/60Hz
3A
29.2Vdc
27.4Vdc
186 x 88 x 47.5
0.8Kg
AC0412A
110/220Vdc ±10% AUTO SW
50/60Hz
4A
14.6Vdc
13.7Vdc
186 x 88 x 47.5
0.8Kg
AC0424A
110/220Vdc ±10% AUTO SW
50/60Hz
4A
29.2Vdc
27.4Vdc
186 x 88 x 47.5
0.8Kg
AC0512A
110/220Vdc ±10% AUTO SW
50/60Hz
5A
14.6Vdc
13.7Vdc
186 x 88 x 47.5
0.8Kg
AC0524A
110/220Vdc ±10% AUTO SW
50/60Hz
5A
29.2Vdc
27.4Vdc
186 x 88 x 47.5
0.8Kg
AC0612A
110/220Vdc ±10% AUTO SW
50/60Hz
6A
14.6Vdc
13.7Vdc
186 x 88 x 47.5
0.8Kg
AC0624A
110/220Vdc ±10% AUTO SW
50/60Hz
6A
29.2Vdc
27.4Vdc
186 x 88 x 47.5
0.8Kg
AC0712A
110/220Vdc ±10% AUTO SW
50/60Hz
7A
14.6Vdc
13.7Vdc
186 x 88 x 47.5
0.8Kg
AC0724A
110/220Vdc ±10% AUTO SW
50/60Hz
7A
29.2Vdc
27.4Vdc
186 x 88 x 47.5
0.8Kg
AC0812A
110/220Vdc ±10% AUTO SW
50/60Hz
8A
14.6Vdc
13.7Vdc
186 x 88 x 47.5
0.8Kg
AC1012A
110/220Vdc ±10% AUTO SW
50/60Hz
10A
14.6Vdc
13.7Vdc
186 x 88 x 47.5
0.8Kg
AC1212A
110/220Vdc ±10% AUTO SW
50/60Hz
12A
14.6Vdc
13.7Vdc
186 x 88 x 47.5
0.8Kg
AM0236A
100-240VAC
50/60Hz
2A
44.5Vdc
41.3Vdc
164 x 90 x 50
0.5kg
AM0424A
100-240VAC
50/60Hz
4A
29.6Vdc
27.4Vdc
164 x 90 x 50
0.5kg
AM0612A
100-240VAC
50/60Hz
6A
14.8Vdc
13.6Vdc
164 x 90 x 50
0.5kg
Other currents and voltages available on request
39
GENERATORS
1 PHASE & 3 PHASE
Standby Diesel Generator Sets (10kVA-2000kVA)
FEATURES:
All units complete with exhaust systems, 12 hour fuel tanks (larger tanks available), batteries, automatic mains failure control panels
and prime power base load control panels. The panels include standard metering switchgear, control gear and engine protection. Both
single and three phase versions available.
APPLICATIONS:
•
•
•
•
•
•
•
•
Agriculture
Cold Rooms
Banking
Airports
Building Services
Hospitals
Hotels and Entertainment
Engineering
SPECIFICATIONS:
Engine Types
Alternator Types
Sizes
Voltage Ranges
Frequencies
Engine Speeds
Generator Sets
: Caterpillar, Cummins, Daimler Chrysler
MTU, Detroit Diesel VM Sun, Deutz, Hatz, John Deere,
Kirloskar, Lister, Lombardini, Perkins, Scania, Volvo and
Yanmar
: Leroy Somer, Marelli and Mecc Alte
: Petrol powered up to 10KVA Single Phase;
Diesel Powered from 10KVA to 2000KVA Three Phase
: 110V-525V
: 50/60Hz
: 3000 or 1500 RPM
: Available with Base Load and
Automatic Mains Failure Control Panels mounted on
open steel frame. Weatherproof Silent Canopy. Mobile
Trailer mounted
300KVA Automatic mains failure
100KVA, 25KVA, 13KVA remote start/stop and AMF
30KVA Automatic mains failure soundproof Generator Set. Standard soundproof canopy with sound
levels of 65dB(A) at 7 metres in an open field.
1000KVA Automatic mains failure Generator Set.
MTU 16V 2000 G62 / Leroy Somer (Installed at the
Capital Alliance Building, Johannesburg)
All engines and alternators used in the manufacture of Power Generation Equipment conform to the following specifications:
ENGINES: B.S. 5514 1982; ISO 30461; 1DIN6271.
ALTERNATORS: B.S. 5000; VDE 30; IEC 23; UTE 5100; NEC 51-111; NEMA – IEEE CSA.
Where applicable alternators specified for Marine Applications will conform to:
BUREAU VERITAS; LLOYDS REGISTER; AMERICAN BUREAU OF SHIPPING; DNV; RINA; GERMANISHER LLOYDS;
KOREAN REGISTER OF SHIPPING; NKK.
40
CONSTANT VOLTAGE TRANSFORMERS
1 PHASE
Constant Voltage Transformers (150VA-20kVA)
Features:
•
•
•
•
•
•
•
•
•
Input Voltage: Single Phase, 230V (184-276). Other voltage on request
Supply Frequency: 50Hz
Output Voltage: 230V. Other voltages on request
Output Accuracy: Btter than 3% (1% option available)
Harmonic Distortion: Typically less than 2%
Effect of Frequency Change: 1% change in frequency produces approximately 2.5% change in output voltage
Response: Typically 1-2 cycles (20-40ms)
Overload: Short circuit limited
Efficiency: Approximately 85% at full load
4
5
Model*
Input/Output
Rating
Current
Dimensions (W x H x D) mm
Mass
SC150S
230V/230V
120W
0.52A
290 x 231 x 400
17kg
SC250S
230V/230V
200W
0.87A
290 x 231 x 400
18kg
SC500S
230V/230V
400W
1.74A
290 x 231 x 400
21kg
SC750S
230V/230V
600W
2.61A
290 x 231 x 400
24kg
SC1000S
230V/230V
800W
3.48A
290 x 231 x 400
26kg
SC1500S
230V/230V
1200W
5.22A
290 x 231 x 400
36kg
SC2000S
230V/230V
1600W
7.27A
400 x 263 x 550
55kg
SC2500S
230V/230V
2000W
9.09A
400 x 263 x 555
59kg
SC3000S
230V/230V
2400W
10.91A
400 x 263 x 565
65kg
SC4000S
230V/230V
3200W
14.55A
400 x 263 x 600
83kg
SC5000S
230V/230V
4000W
18.18A
400 x 263 x 600
90kg
SC6000S
230V/230V
4800W
21.82A
540 x 365 x 908
154kg
SC7500S
230V/230V
6000W
27.27A
540 x 365 x 925
172kg
SC10000S
230V/230V
8000W
36.36A
540 x 365 x 970
212kg
SC12000S
230V/230V
9600W
43.64A
450 x 890 x 1100
290kg
SC15000S
230V/230V
12000W
54.55A
450 x 890 x 1100
340kg
SC18000S
230V/230V
14400W
65.45A
450 x 890 x 1100
435kg
SC20000S
230V/230V
16000W
72.73A
450 x 890 x 1100
450kg
41
SERVO TYPE
1 PHASE
Servo Type Fully Automatic Voltage Stabiliser (Single Phase)
DESCRIPTION:
The SVC fully automatic voltage regulator consists of a contact voltage regulator, samplingcontrol circuit and service motor as well. It
features small waveform distortion, high efficiency and high power factor. It is also not affected by input frequency variations. It can be
widely used in most situations where voltage stabilisation is required.
Model
500VA
1kVA
Input Voltage
1.5kVA
2kVA
3kVA
150V-250V
10kVA
15kVA
20kVA
30kVA
150V-250V
220V ± 3%
Frequency
50Hz/60Hz
Response Time
< 1s (against 10% input voltage deviation)
Efficiency
> 90%
-100C ~ +400C
Ambient
Temperature
Relative Humidity
< 90%
Power Factor
0.8
Insulation
Resistance
> 5MΩ
18.5
21
21
27.5
29
45
47
47
42
42
42
38
Width (cm)
15
18
18
23.5
23
24
26
26
38
38
Height (cm)
12.5
14.5
14.5
18.5
22
18.5
22
22
73
73
83
Weight (kg)
4.6
6.5
7
10.5
13.6
22.4
40
43
75.5
80
87
Append “SVC-” to the model above for the full part number
42
7.5kVA
160V-250V
Output Voltage
Length (cm)
5kVA
SERVO TYPE
3 PHASE
Servo Type Fully Automatic Voltage Stabiliser (Three Phase)
DESCRIPTION:
•
•
•
•
•
•
•
•
•
Microprocessor DSP control
Automatic Voltage Regulation
Protection against Brownouts and Overvoltages
Short Circuit & Overload Protection
Digital meter indicates line voltage and regulated voltage
LED indicators to show status of working input and output
Selectable Delay Time
Built-in transformer, Square transformer or Servo motor
Surge, Spike & Lightning Protection
5
Model*
10kVA
15kVA
20kVA
30kVA
Input Voltage
50kVA
80kVA
100kVA
150kVA
200kVA
260-430VAC
Input Frequency
50/60Hz
Output Voltage
380/400/415VAC
Output Precision
± 3%
Efficiency
98%
LED Display
Input Voltage / Output Voltage
LED Input Status
Blue; indicating phase voltage normal/abnormal
LED Power Status
Red; indicating Power ON/OFF
LED Delay Status
Yellow; during delay the LED flashes
LED Output Status
Blue; indicating output voltage ON/OFF
Protection
High Voltage, Low Voltage, Overload, High Temp.
Safety Standards
CE, EN60950, EN55024
00C-400C / -150C-450C
Operating/Storage Temp.
Operating Humidity
10% RH - 102% RH, non-condensing
Dimensions, L x W x H
(mm)
443 x 483 x 858
Weight (kg)
57.8
62.3
503 x 553 503 x 553
x 888
x 938
88.4
108.4
1250 x
525 x 650
200
1020 x 620 x 1360
250
285
1200 x 680 x 1760
305
350
* Append “PDR-“ to the model above for the full part number
Bigger ratings available on request
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at any time without prior notice.
43
ELECTRONIC WITH ISOLATION
1 PHASE & 3 PHASE
Voltage Stabilisers - Electronic (15kVA-30kVA)
FEATURES:
•
•
•
•
•
•
•
•
•
Wideband voltage regulation range (±25%)
True RMS voltage sensing ensures accurate regulation even with distorted mains (eg diesel generator)
Regulates individual phases to within 5% with input variations of up to ±25%
High capability to temporary overloads (eg aircon units, power supplies etc)
Over/Under voltage cut-out protects sensitive loads
TVSS Surge protection
Volt meter (optional)
High efficiency - approximately 98% at full load
Rugged and reliable
APPLICATIONS:
•
•
•
•
•
•
•
•
•
•
•
Transmissions and telecommunications
Radar systems in naval or air navigation
Process controls
Computer data processing & numerical control machines
Photography controls and processes
Laboratory equipment
Test equipment
Electric furnaces
Illumination
Medical equipment
Any electrical or electronic sensitive to voltage variations
SPECIFICATIONS:
Nominal Input Voltage
Nominal Output Voltage
Over Voltage Cut-off at
Under Voltage Cut-off at
Output Voltage Accuracy
Overload Rating
Efficiency
Earthing
Speed Correction
Waveform Distortion
Effect of load Power Factor
Maximum Continuous Voltage
Nominal Discharge Current
Impulse Current Limp (10/350us)kA
Voltage Protective Level
Response Time
Environment
Ambient Operating Temperature
Operating Elevation
Model
APS-15kVA-ID
: 400/230vac 50/60 Hz +/- 25% (3 Wire)
: 400/230vac 50/60 Hz +/- 5% (4 Wire)
: 290V input voltage under normal operation (L-N) (U out 230V)
250V input voltage under bypass operation (L-N) (U out 230V)
: 160V input voltage under normal operation (L-N) (U out 230V)
200V input voltage under bypass operation (L-N) (U out 230V)
: 5%
: 120% for 60mins; 200% for 10 sec
: 98% at full load
: The input earth is bonded to the enclosure
: +/- 20 milliseconds
: Negligible
: None
: 300V
: 40kA
: 12kA
: ≤ 2.0
: ≤ 100ns
: Protection class IP21 (indoor enclosure);
IP54 (outdoor enclosure)
: 0°C to +45°C
: 1000m, over 1000m derate by 2.5% for each 500m
Description
Rating
Current
Dimensions (L x W x D mm)
Weight
Indoor - 15kVA
15kW
66A (Max)
700 x 385 x 1100
210kg
Indoor - 22.5kVA
22.5kW
96A (Max)
700 x 385 x 1100
226kg
APS-30kVA-ID
Indoor - 30kVA
30kW
132A (Max)
700 x 385 x 1100
236kg
APS-15kVA-OD
Outdoor - 15kVA
15kW
66A (Max)
775 x 465 x 1210
216kg
Outdoor - 22.5kVA
22.5kW
96A (Max)
775 x 465 x 1210
232kg
Outdoor 30kVA
30kW
132A (Max)
775 x 465 x 1210
242kg
APS-22.5kVA-ID
APS-22.5kVA-OD
APS-30kVA-OD
Note: Higher ratings available on request
44
ELECTRONIC
1 PHASE & 3 PHASE
Voltage Stabilisers - Electronic (1kVA-75kVA)
FEATURES:
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
No Load Energy
Consumption Relationship
High Efficiency
20-25%
High Power Factor
High Reliability
Low Harmonic Distortion
Low Environmental Pollution
1.5%
Low Electro Magnetic Interference
APS Range of Products Solve Over 95% of Your Power Problems
Micro Processor Control
SCR Phase
APS
Micro Size - Quarter the size / weight of traditinal AVR.
Control
Modular Design - Circuit designed in PCB modules, easy for maintenance.
High Efficiency - η ≥ 98% at Full Load.
Transductor
High Input Power Factor - Input Power Factor 0.95 ~ 1
Principle
Extra Low No Load Power Consumption - No Load Power Consumption ≤ 1.5%.
Automatic Electronic Bypass - Electronic Bypass, Automatic in Overload / Abnormal conditions
Low Audible Noise - Audible noise 35 dB at 1 m
Flexibility for Loads - Suitable for Pure Capacitive / Inductive Load
No Load Electricity
Cost Relationship
30%
Ferroresonant
Transformer
CVT
±R30 000
5
±R20 000
±R1 600
APS
Model
Ferroresonant
Transformer
Transductor
Principle
CVT
Calculation Based on typical South African
Electricity Cost, 10 hours per day
APS Single Phase Models
APS-1KB
SCR Phase
Control
KVA
Output Regulation
Type
Current (A) (1 Phase)
Dimensions (H x W x D) (mm)
Weight (kg)
1
±3% Typical
B
4.5
120 x 220 x 360
10
APS-2KB
2
±3% Typical
B
9.1
120 x 220 x 360
13
APS-3KB
3
±3% Typical
B
14.0
200 x 380 x 450
21.5
APS-5KB
5
±3% Typical
B
23.0
200 x 380 x 450
26
APS-7KB
7
±3% Typical
B
32.0
200 x 370 x 550
33
APS-10KB
10
±3% Typical
B
45.0
200 x 370 x 550
39
APS-15KB
15
±2% Max
B
68.0
200 x 370 x 550
45
APS-20KB
20
±2% Max
B
91.0
355 x 835 x 650
50
APS-30KB
30
±2% Max
B
137.0
355 x 835 x 650
55
APS Three Phase Models
Model
KVA
Output Regulation
Type
Current (A) (per Phase)
Dimensions (H x W x D) (mm)
Weight (kg)
APS-10KZ
10
±3% Typical
Z
15
355 x 835 x 650
70
APS-15KZ
15
±3% Typical
Z
23
355 x 835 x 650
85
APS-22KZ
22
±3% Typical
Z
33
355 x 835 x 650
100
APS-30KZ
30
±3% Typical
Z
45
355 x 835 x 650
115
APS-45KZ
45
±2% Max
Z
68
355 x 835 x 650
130
APS-60KZ
60
±2% Max
Z
91
450 x 955 x 800
160
APS-75KZ
75
±2% Max
Z
114
450 x 955 x 800
185
Note: Higher ratings available on request
45
ELECTRONIC
Industrial Inductive Type
Voltage Stabilisers - Inductive (100kVA-1500kVA)
FEATURES:
• Strong, durable and high reliability - No contact point. Capable of sustaining spikes, surges or impulses
from non-lionear loads. Long equipment life.
• Protection - Redundant circuit control. Event history log for up to 200 events. Phase loss and phase reverse
protection. Output over voltage and under voltage protection. Output overload protection.
• High overload capability - 100% continuous load. 200% transient current up to 5 minutes. Maximum
tolerable transient start current of up to 500%
• LCD user interface - Blue backlight, wording in white. RS-485 communication port. Push buttons are lit for
convenience in the dark. Remote signal for measurements and control functions to monitor and control your
equipment.
• 1500kVA capacity - The inductive type voltage stabiliser can have a maximum capacity of 1500kVA in one
unit.
APPLICATIONS:
• Communication Systems - TV stations, ADSL,
Coaxial cable TV systems and components, Radio
communication equipment and systems, Satellite and
communication equipment, Fiber-optics systems, Lan
servers.
• IT - Home electrical appliances, Information appliances,
Office IT equipment, POS systems.
• Computer and Computer Peripherals - Electronic
data processing (EDP) centres, Server / Data storage
systems, Industrial PC’s.
• General Lab - Program control systems, Electronic test
equipment.
• F / A - Production lines, IC (integrated circuit) field, CNC
machines, SMT equipment, Auto-Insertion equipment,
PCB assembly equipment, Semiconductors (BGA,
CSP, Flip Chip, LCD), Production process and control
equipment, Printing industry.
• Medical and Military - Electronic and Medical
equipment, Medical monitoring systems, Airport x-ray
scanning equipment, Airport facilities, Airport control
tower facilities.
• Other - Bioscience, Gas stations, Opto-electronic
industry.
46
ELECTRONIC
Industrial Inductive Type
Model**
Capacity (kVA)
0100
0125
0150
0200
0250
0300
100
125
150
200
250
300
Circuit Type
0350
0400
0500
0600
0800
1000
1250
1500
350
400
500
600
800
1000
1250
1500
Inductive Voltage Regulator
Input
Phase
3P3W / 3P4W
Voltage Range*
-13% - +17% (option: -22% - +30%)
Frequency
47Hz - 63Hz
Output
Phase
3P3W / 3P4W
Voltage
200V / 208V / 220V, 380V / 400V / 415V ± 2% (±1%-±5% adjustable)
Voltage Modulation
< 4 V/s
Overload
125%-40min; 150%-20min; 175%-10min; 200%-5min
Total Harmonic Distortion
< 1% (compared with input)
VA Efficiency
>97%
Measurement
Measurements
5
Input line voltage and frequency, Output line voltage, Phase voltage, Line current and frequency, VA, W, PF, Load
rate, Internal temperature
Protection
Protection Functions
Phase loss, phase reverse, output over voltage & under voltage, output overload, over temperature, over current,
redundant cicuit control. Event history log for 200 events.
User Interface
Operation
LCD and Push buttons
Alarm
Alarm 1. Audio. Alarm 2. Activate
Communication
RS-485
Software
Remote control and monitor
Environment
Working Temperature
-50C-400C
Storage Temperature
-300C-500C
Humidity
< 95% (non-condensing)
Altitude
< 1000 meters
Cooling System
Type
Fan cooling
Other
Noise
Optional
< 60dB
Auto transformer, full time lightning & surge protection, output on & off electromagnetic contactor
* Other input ranges on request
** Prefic the model no. with APH-33 for the full part number.
Custom made specifications on request
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specification or design can be changed at anytime without prior notice.
47
FREQUENCY CONVERTERS
1 PHASE & 3 PHASE
Frequency Converters (500VA-300kVA)
FEATURES:
•
•
•
•
•
•
•
•
•
Wide Application: Allows users to simulate Worldwide voltage and frequency for commercial applications (47-63Hz) and Military /
Avionics / Marine applications at 400Hz.
Pure Sinewave Output: All models generate very clean sine waveforms output. It is not only a superior power source for R&D and
Laboratory, but also a standard power source for EMI/EMC/Safety testing.
Superior Stability: Output Load Voltage regulation ±1%, Output Frequency ≤ 0.01%.
Quick & Convenient 3 Scales of Preset Voltage for High and Low Voltage Simulation:
High (Surge): +10% ~ +25% of Present voltage
Medium: Preset voltage
Low (Sag): -10% ~ -30% of Preset voltage.
Direct Select of Six Scales Output Frequency: 47~63Hz, 50Hz, 60Hz, 2xF (F = Input Frequency), 4xF (F = Input Frequency),
400Hz.
2F or 4F Output Testing Frequency for Layer Short Test of Coils Products.
High Overload Capability: 100% full load continuously; withstand 3 times of inrush current.
Protections: Input Circuit Breaker, Output Circuit Breaker, Instant Trip Circuits for Overload, Over Voltage, Short Circuit, Over
Temperature protection and Alarm system.
Suitable for Any Load: Resistive, Capacitive, Inductive and Non-linear load use.
APPLICATIONS:
Industrial:
•
•
•
•
Home Electrical Appliances, Manufacturers of: Washing Machines, Refrigerators, Vacuum Cleaners, Microwave Ovens, Air
Conditioners, Blenders.
Electronic Manufacturers of: Switching Power Supply Testing, Ballasts (in Bulbs, Fluorescent Lamps), Uninterruptible Power
Supplies, Chargers, Relays, Passive components.
Electric Machinery Manufacturers of: Compressors, Transformers, AC Fans, Motors.
IT Field: OA Equipment (Fax Machines, Copy Machines, Shredders, etc), Computer & Monitors, Printers, Scanners & Peripherals.
General Laboratory:
•
•
•
•
•
•
AC Power Source Testing
Life & Safety Testing
EMC Testing
OQC (FQC) Testing
Product Testing
Product Researches & Developments.
400Hz Output Frequency:
•
•
•
•
•
•
•
•
•
•
48
AFC-SERIES
500VA-60kVA
Single Phase
Aerospace
Airport Grounding Facilities, including Airport Terminals, Control Towers, Aprons
Avionics Equipment
Air Force System Diagnostics
Military System Diagnostics
AFC-SERIES
Navy System Diagnostics
60kVA-300kVA
Marine Systems
Satellite Navigation
Three Phase
Switching Power Supply of Super Computers
400Hz Equipment & Instruments
FREQUENCY CONVERTERS
1 PHASE & 3 PHASE
AFC SERIES - SINGLE PHASE SPECIFICATIONS:
Model
Capacity (kVA)
Voltage
AFC-500
AFC-11001
AFC-11003
AFC-11005
AFC-11010
AFC-11015
AFC-31020
AFC-31030
AFC-31045
AFC-31060
0.5
1
3
5
10
15
20
30
45
60
110V or 220V ±15%, 1 Phase
220V ±15%, 1 Phase
Frequency
Output
(AC)
50Hz ± 3Hz, 60Hz ± 3Hz
Phase
Voltage
380V ±15%, 3 Phase 3 or 4 wire
Single Phase
Low
0~150V
5V ~ 150V (L-N)
High
0~300V
10V ~ 300V (L-N)
Frequency
47 ~ 63Hz, 50Hz, 60Hz, 400Hz, 2F (2 x Input Frequency), 4F (4 x Input Frequency)
Option: 40 ~ 500Hz
Maximum Current
Low
4.2A
8.4A
25A
42A
84A
126A
168A
250A
375A
500A
High
2.1A
4.2A
12.5A
21A
42A
63A
84A
125A
188A
250A
Frequency Stability
≤0.01%
Load Regulation
±0.2%
±1% (linear load)
Total Harmonic Distortion
±0.2%
±2% (linear load)
Transient Response
Meter /
Res.
50us Max.
Res. 0.1Hz
4 Dig. Voltmeter
Digit Ammeter
4 Dig. Wattmeter
Protection
Envionment
2ms Max.
4 Dig. Freq. Met.
Res. 0.1V
0.001A
0.01A
0.1W
1W
4 Digit Ammeter / Res. 0.1A
5 Digit Ammeter / Res.0.1A
Option
Input Circuit Breaker, Output Circuit Breaker, Electronic Circuits Instant Trp for Over Voltage, Over Load, Over Temperature, Short Circuit Protection and
Alarm System
Ambient Temp.
0°C ~ 45°C
Relative Hum.
0 ~ 90% Non-condensing
Altitude
6
1500 meter
Dimensions W x H x D (mm)
430x520x200
Net Weight (kg)
430x520x720
44
89
73
430x750x990
89
150
171
600x970x1240
280
333
800x600x1600
418
571
AFC SERIES - THREE PHASE SPECIFICATIONS:
Model
Capacity (kVA)
AFC-33006
AFC-33010
AFC-33020
AFC-33030
AFC-33045
AFC-33060
AFC-33075
AFC-33100
AFC-33150
AFC-33180
6
10
20
30
45
60
75
100
150
180
Voltage
380V ±15%, 3 Phase 3 or 4 wire
Frequency
Output
(AC)
50Hz ± 3Hz, 60Hz ± 3Hz
Phase
Voltage
Three Phase
Low
5V ~ 150V (L-N)
High
10V ~ 300V (L-N)
Frequency
47 ~ 63Hz, 50Hz, 60Hz, 400Hz, 2F (2 x Input Frequency), 4F (4 x Input Frequency)
Option: 40 ~ 500Hz
Maximum Current
Low
16.7A
27.8A
55.6A
83.3A
125A
167A
208A
278A
417A
500A
High
8.3A
13.9A
27.8A
41.7A
62.5A
83.3A
104A
139A
208A
250A
Frequency Stability
≤0.01%
Load Regulation
≤ ±1% (linear load)
Total Harmonic Distortion
≤ ±2% (linear load)
Transient Response
Meter /
Res.
2ms Max.
4 Dig. Freq. Met.
Res. 0.1Hz
4 Dig. Voltmeter
Res. 0.1V
Digit Ammeter
4 Digit Ammeter / Res. 0.1A
5 Digit Ammeter / Res.0.1A
4 Dig. Wattmeter
Option
Load Balance or No Load: ≤ 1°, 100% Unbalance: ≤ 2° (measured at 50Hz or 60Hz)
Protection
Envionment
Input Circuit Breaker, Output Circuit Breaker, Electronic Circuits Instant Trp for Over Voltage, Over Load, Over Temperature, Short Circuit Protection and
Alarm System
Ambient Temp.
0°C ~ 45°C
Relative Hum.
0 ~ 90% Non-condensing
Altitude
Dimensions W x H x D (mm)
Net Weight (kg)
1500 meter
430x750x990
150
600x970x1240
175
345
385
800x1090x1600
528
635
700
800x600x1600
1000
1350
1620
49
GROUND MILITARY UNITS
1 PHASE & 3 PHASE
Ground - Military Power Units (500VA-300kVA)
400Hz Frequency Converters & 28VDC Power Supplies
28VDC Power Supply
FEATURES:
•
•
•
•
•
•
•
•
•
Used as a DC power supply unit or voltage simulating test for GPU / Military Unit.
28VDC ±10% Standard Output Voltage; 100Amp to 2,000Amp Output Current.
Automatic Input Line Monitoring.
Output Voltage and Output Current Monitoring.
Current Limit Adjustable.
Auto Feedback Control Circuits. Capable to adjust input and output automatically for constant voltage.
Automatic Line Drop Compensation.
Fixed voltage Fixed current. Interchangeable to have control and protection features.
Protection:
Input Line Loop: Auto detection and trip for Over Current, Over Voltage, Loss Phase, Phase Reversed.
Output Circuit: Electronic-controlled Short Circuit Protection.
400Hz Solid State Frequency Converter
FEATURES:
•
•
•
•
•
•
•
•
•
Small, Light & Space Saving: Typically, 1/4 size of motor-generator sets of the same power output rating.
High Efficiency, Optimum Stability, Superior Heat Dissipation.
Economical Cost of Ownership
Modular design permits quick and easy replacement:
Typical motor-generator sets downtime is four times greater, often resulting in costly delays, maint. and production schedules.
High efficiency features reduce operating costs through 25% and upward utility savings compared to motor-generator sets.
On-site repairs are easily accomplished.
Motor-generator sets quite often must be removed from location for repairs, resulting in costly rigging and transport charges.
Low Noise: Solid State frequency converters have no moving mechanical parts generating a loud noise and eliminates the need for
expensive sound insulation.
Individual
Phase Regulation at Output: Excellent voltage regulation under 100% unbalanced load.
Output
Isolation Transformer: capable of sustaining CEMF (counter-electromotive force).
Option:
36VAC input voltage or acc. to customer’s specifications.
“Add on module” of Solid State frequency converter and 28VDC power supply.
Low Harmonic Distortion at 3% maximum.
APPLICATIONS FOR BOTH:
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
50
Provides DC current for Airlines / Spacecraft starting.
Working current on avionics or simply provide ground support maintenance.
Provides clean DC power that meets MIL-STD-704 standard for aircraft power.
Input Power Supply Simulating Test of air materials.
Aircraft Manufacturers.
Aerospace Equipment Manufacturers.
Hangars.
Air Force Bases.
Passenger Boarding Bridges (PBB).
Aprons.
Control Towers.
Meter Control Centers.
Air Force System Diagnostics.
Military System Diagnostics.
Navy System Diagnostics.
R&D Dept. of Military, Defense.
Military Equipment.
Power Supply for Warships.
Power Supply for Radars.
Rotary Engineer Manufacturers.
GROUND MILITARY UNITS
1 PHASE & 3 PHASE
AMF SERIES - SINGLE PHASE SPECIFICATIONS:
Model
Capacity (kVA)
AMF-500
AMF-11001
AMF-11003
AMF-11005
AMF-11010
AMF-31020
AMF-31030
AMF-31045
AMF-31060
AMF-31100
0.5
1
3
5
10
20
30
45
60
100
Circuit Type
Input
(AC)
IGBT / Pulse Width Modulation Type
Phase
Voltage
1 Phase 2W+G
110V (B) or 220V (G) ±15%
3 Phase 3W+G(Δ) or 3 Phase 3W+N+G(Y)
220V (G) ±15%
220V (G) ±15% or 220V/380V (T) ±15%
Frequency
Output
(AC)
50Hz ±3Hz, 60Hz ±3Hz
Phase
1 Phase 2 W+G
Voltage
115V (C) or 220V (G), 230V (H) Output Voltage ±10% Adjustable
Frequency
2-Step Output Frequency: 1. 400Hz Fixed, 2. 350Hz-450Hz adjustable (*can comply with customer’s specs)
Frequency Stability
≤0.01%
Load Regulation
Total Harmonic Distortion
Meter /
Res.
≤±1%
≤±1.5%
≤±2% (linear load)
≤±3% (linear load)
4 Dig. Freq. Met.
Res. 0.1Hz
4 Dig. Voltmeter
Digit Ammeter
Res. 0.1V
0.001A
0.01A
4 Digit Ammeter / Res. 0.1A
Overload Capability
Protection
5 Digit Ammeter / Res.0.1A
120% / 1hr - 150% / 1min. - 200% / 15sec. (25% duty cycle)
Input Circuit Breaker, Output Circuit Breaker, Electronic Circuits for fast detection and trip off protection for Over Current, Over Voltage, Over Load, Over
Temperature, Short Circuit and Alarm system
Isolation Resistance
≥500Vdc 20MΩ
Withstand Voltage
1800Vac / 5mA / 1min
Cooling System
Air Forced Fan
Ambient Temperature
-20°C ~ 45°C
Relative Humidity
0 ~ 90% Non-condensing
Dimensions W x H x D (mm)
Net Weight (kg)
430x520x200
44
430x520x720
60
430x750x990
73
89
150
600x970x1240
280
800x1090x1600
333
418
800x600x1600
571
6
898
AMF SERIES - THREE PHASE SPECIFICATIONS:
Model
Capacity (kVA)
AMF-33006
AMF-33010
AMF-33020
AMF-33030
AMF-33045
AMF-33060
AMF-33075
AMF-33100
AMF-33150
AMF-33180
6
10
20
30
45
60
75
100
150
180
Circuit Type
Input
(AC)
IGBT / Pulse Width Modulation Type
Phase
3 Phase 3W+G (Δ) or 3 Phase 3W+N+G(Y)
Voltage
3W+G : 220V (G) or 3W+N+G : 220V/380V (T) ±15%
Frequency
Output
(AC)
50Hz ±3Hz, 60Hz ±3Hz
Phase
3 Phase 3 W+N+G (Y)
Voltage
200V/115V (P) Output Voltage ±10% Adjustable
Frequency
2-Step Output Frequency: 1. 400Hz Fixed, 2. 350Hz-450Hz adjustable (*can comply with customer’s specs)
Frequency Stability
≤0.01%
Load Regulation
Total Harmonic Distortion
Meter /
Res.
≤±1%
≤±1.5%
≤±2% (linear load)
≤±3% (linear load)
4 Dig. Freq. Met.
Res. 0.1Hz
4 Dig. Voltmeter
Res. 0.1V
Digit Ammeter
4 Digit Ammeter / Res. 0.1A
Phase Shift
Overload Capability
Protection
5 Digit Ammeter / Res.0.1A
Balanced Load / Empty Load: ±2° : 100% Unbalanced Load: ±4°
120% / 1hr - 150% / 1min. - 200% / 15sec. (25% duty cycle)
Input Circuit Breaker, Output Circuit Breaker, Electronic Circuits for fast detection and trip off protection for Over Current, Over Voltage, Over Load, Over
Temperature, Short Circuit and Alarm system
Isolation Resistance
≥500Vdc 20MΩ
Withstand Voltage
1800Vac / 5mA / 1min
Cooling System
Air Forced Fan
Ambient Temperature
-20°C ~ 45°C
Relative Humidity
Dimensions W x H x D (mm)
Net Weight (kg)
0 ~ 90% Non-condensing
430x750x990
150
600x970x1240
175
345
385
800x1090x1600
528
635
700
800x600x1600 (x3)
1000
1350
1620
51
SOLAR
PHOTOVOLTAIC PANELS
Solar Panels and Green Energy Systems
Powerhouse Distributions has launched a reliable, high performance and
high quality range of:
• Solar panels
• Solar charge controllers (MPPT)
• Pure and modified sinewave inverters
• Solar water pumps
• Wind turbines
• Deep cycle (solar) batteries
Solar in Southern Africa
In the past few years, the number of solar system installations in Africa
has grown at a tremendous rate. We at Powerhouse Distribution strive to
always come up with new ideas and be at the forefront of the renewable
energy sector. We stock a very comprehensive range of solar products
and equipment.
Solar Panels
We have a high grade range of solar panels in the poly and monocrystalline range designed for high efficiency solar systems. Our panels
are available in 12V or 24V from 50W up to and including 200W.
Inverters
Powerhouse only distributes the highest quality equipment and our solar
inverters are no exception. We offer units from 150W up to and including
3000W in the pure sinewave and modified sinewave range.
Solar Charge Controllers
Powerhouse has a comprehensive range of solar charge controllers
including the state of the art maximum power point tracking units from
AEC. These allow your solar panels to operate at their optimum power
output voltage, providing higher efficiency up to 97% with lower power
losses.
52
SOLAR
CHARGE CONTROLLERS
Sunmax-1500W Solar MPPT Controller
The Sunmax-1500W developed by AEC can be used universally for 12, 24, 36 and 48V. Its broad DC input voltage range makes sensible
system configuration possible for almost all PV modules. Thanks to the integrated MPP tracking, the charger guarantees an energy yield
that is 15-30% higher than that of conventional shunt and serial charge controllers. Auto-selection four-stage (Bulk/Pulse/Float1/Float2)
charge mode to reduce the charge time by a third and maximise the system’s performance. What is unique about charge controllers of this
power range is the high protection class, and the broad temperature range that makes worldwide use, even in harsh ambient conditions,
possible. The easy installation and completely automatic customisation of the controller’s settings by the SA series make its commissioning
very simple.
Features
Model
● Parallel capable
● MCU controlled
● LCD display
● High efficiency
● Battery temperature compensated
● Four-stage charging
Sunmax-1500W
Input
Rated Voltage
40-120Vdc
Current (Max.)
35A
Max. PV Array Open Circuit Voltage
150Vdc
Output
Nominal Battery Voltage
12/24/36/48Vdc
Max. Charger / Output Current
60A
Physical Characteristics
Dimensions (L x H x D, mm)
Input/Output Connectors
165 x 85 x 330
Hardwired (Terminal Block)
Weight (kg)
3.2
Computer Interface
Model
Capacity
Type
GTI-3KW
3kW
DC Input
Maximum DC Voltage
500VDC
MPPT Voltage Range
110VDC - 450VDC
DC Nominal Voltage
Start-up Voltage / Initial Feeding Voltage
Maximum Input Current
360VDC
125VDC / 125VDC
13A
RS-232
Grid-tie PV Inverter
● Pure sinewave output
● Microprocessor controlled to guarantee stable charging
system
● Multiple operations: Grid tie, Off grid and grid-tie with
backup
● LCD display panel for comrehensive information
● Multiple communications
● User-adjustable charging current up to 25A
● Built-in MPPT solar charger
7
AC Input
Acceptable Voltage Range
170 - 280VAC
Maximum Input Current
20A
AC Grid Frequency Range
47.5 - 50.2Hz
AC Output
Output Voltage, Frequency
Efficiency
220VAC, 50Hz
90%
Battery & Charger
Nominal DC Voltage, Max Charging
Current
48VDC, 25A
Interface
Communication Port
Intelligent Slot
Wireless Connection
RS-485/RS-232/USB
Optional SNMP card or
Modbus card available
Optional Zigbee card and
wireless device available
53
POWER SUPPLIES
MEANWELL
Meanwell Power Supplies
Enclosed Single Output Power Supplies
Features
•
•
•
•
•
Universal AC Input/Full range
Protections: Short Circuit / Overload / Over Voltage
Cooling by free air convection
100% full load burn-in test
2 year warranty
Additional Features of the RS-25
•
•
•
•
•
•
All using 1050C long life electrolytic capacitors
Withstand 300VAC surge input for 5 seconds
High Operating temperature up to 700C
Withstand 5G vibration test
No load power consumption < 0.5W
3 year warranty
Model
S-60-12
NES-35-12
NES-35-24
RS-25-24
Output
DC Voltage
12V
Current Range
0-5A
Rated Power
60W
24V
0-3A
0-1.5A
0-1.1A
35W
25W
Input
Voltage Range
85-264VAC, 120-370VDC
Frequency Range
Efficiency (Typ.)
AC Current (Typ.)
88-264VAC, 125-373VDC
47-63Hz
76%
81%
85%
86%
2A/115VAC, 1A/230VAC
0.75A/115VAC, 0.5A/230VAC
0.7A/115VAC,
0.4A/230VAC
105-150% rated output
power
110-150% rated output power
110-180% rated output
power
Protection
Overload
Over Voltage
13.8-16.2V
27.6-32.4
Protection type: Hiccup mode, recovers automatically after fault condition is removed
Environment
Working Temp.
-10-600C
Working Humidity
Vibration
-20-700C
20-90% RH non-condensing
10-500Hz, 2G 10min./1 cycle, period for 60min. each along X, Y, Z axes
10-500Hz, 5G 10min./1
cycle, period for 60min.
each along X, Y, Z axes
Other
MTBF
Dimensions
Weight
316.2K hrs min. MIL-HDBK217F (250C)
394K hrs min. MIL-HDBK-217F (250C)
309.7K hrs min. MILHDBK-217F (250C)
159*97*38mm (L x W x H)
99*97*36mm (L x W x H)
78*51*28mm (L x W x H)
0.51kg
0.36kg
0.2kg
* All other Meanwell power supply models available, please enquire for further information
54
POWER SUPPLIES
MEANWELL
Meanwell Power Supplies
Din Rail Single Output Power Supplies
Features - DR-60
•
•
•
•
•
•
•
•
•
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air conversion
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
Isolation class II
LED indicator for power on
100% full load burn-in test
3 year warranty
Features - DR-120
•
•
•
•
•
•
•
•
•
AC input range selectable by switch
Protections: Short circuit / Overload / Over voltage
Cooling by free air conversion
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
Fixed switching frequency at 55KHz
LED indicator for power on
100% full load burn-in test
3 year warranty
Model
DR-60-24
DR-120-24
Output
DC Voltage
Current Range
Rated Power
24V
0-2.5A
0-5A
60W
120W
88-264VAC, 120-370VDC
88-132VAC / 176-164VAC by switch, 248-370VDC
8
Input
Voltage Range
Frequency Range
47-63Hz
Efficiency (Typ.)
AC Current (Typ.)
84%
1.2A/115VAC, 0.8A/230VAC
2.6A/115VAC, 1.6A/230VAC
105-160% rated output power
105-150% rated output power
27.6-32.4V
29-33V
Protection
Overload
Over Voltage
Protection type: Hiccup mode, recovers automatically after fault condition is removed
Environment
Working Temp.
-20-600C
Working Humidity
Vibration
-10-600C
20-90% RH non-condensing
10-500Hz, 2G 10min./1 cycle, period for 60min. each along X, Y, Z axes
Other
MTBF
Dimensions
Weight
216.2K hrs min. MIL-HDBK-217F (250C)
136.8K hrs min. MIL-HDBK-217F (250C)
78*93*56mm (L x W x H)
65.5*125.2*100mm (L x W x H)
0.3kg
0.79kg
* All other Meanwell power supply models available, please enquire for further information
55
ISOLATION TRANSFORMERS
1 PHASE & 3 PHASE
Isolation Transformer (10kVA-40kVA)
DESCRIPTION:
This interface transformer has been specifically designed for use in Africa, where conditions vary from country to country and site to site.
The input of the transformer has an easily adjustable tap changer, allowing for voltage variation of 380VAC ~ 415VAC nominal. The output
is designed to offer 400VAC as this is the European standard, three phase voltage, of which 95% of equipment manufactured in Europe
and Southern Africa require.
The input winding has been designed to withstand high input voltages, often found in African conditions, without experiencing permanent
damage. The overall transformer has been designed to tolerate the type of harmonic distortion often associated with non linear loads, like
x-ray and telecommunications equipment. The inter-winding screens offer high attenuation of interwinding voltages and good commonmode and differential-mode protection (0V between neutral and earth). Due to the delta primary, phase shifting is eliminated.
The overall, oil-cooled packaging allows for outdoor installation. This feature becomes handy when space and cooling in existing
installations are limited. Finally, because of the double wound design and the electro-static screen, you have complete isolation between
primary and secondary, providing additional safety between the installation and the uitility.
FEATURES:
•
•
•
•
•
•
•
Interface Isolation Transformer designed for Harsh African conditions.
Easily adjustable tap changer 380V-415V.
Withstands high input voltages.
For non-linear loads.
High attenuation of inter-winding voltages.
Outdoor installation.
Complete Isolation between primary and secondary.
SPECIFICATIONS:
Input Voltages
Frequency
Output Voltage
Cooling
Application
Nominal Power Range
Enclosing
Vector Group
Temperature Class
Environment
Model
: Single Phase 230V; Three phase 380, 400, 415V Delta
: 48-63Hz; 0.95%
: Single Phase 230VAC; Three Phase 400VAC Star
: Oil Cooled
: Outdoor
: From 10kVA 1P; From 20kVA to 40kVA 3P
: Weatherproof powder-coated mild steel
: Dyn 11
:H
: Ambient 0-45°C;
Humidity 0-95%;
Altitude Max 3000m, no die-rating
Input/Output
Rating
Connection
Dimensions (W x H x D mm)
Weight
10kVA/IS
230/230
10kW
Stud
450 x 535 x 425
120kg
20kVA/IS
400/400
20kW
Stud
515 x 840 x 696
250kg
25kVA/IS
400/400
25kW
Stud
515 x 840 x 696
250kg
30kVA/IS
400/400
30kW
Stud
515 x 840 x 696
250kg
40kVA/IS
400/400
40kW
Stud
515 x 840 x 696
265kg
Note: Other ratings available on request
56
BATTERIES
SEALED & SEMI-SEALED
Batteries - Sealed Maintenance Free
Model
Design Life
Volts
Capacity at 20Hr Rate (Ah)
Dimensions (L x W x H) mm
Mass (kg)
12V7
3-5 years
12V
7.2Ah
151 x 65 x 100
2.5
12V8
3-5 years
12V
8Ah
151 x 65 x 100
2.6
12V12
3-5 years
12V
12Ah
151 x 98 x 101
3.9
12V17
3-5 years
12V
17Ah
181 x 77 x 167
5.9
12V24
10 years
12V
24Ah
166 x 175 x 125
9
12V28
10 years
12V
28Ah
165 x 125 x 175
9.7
12V45
10 years
12V
45Ah
197 x 165 x 170
14.8
12V100
3-5 years
12V
100Ah
330 x 171 x 220
27.9
Batteries - Semi Sealed Maintenance Free
9
Model
Volts
Capacity (Ah)
Dimensions (L x W x H) mm
Mass (kg)
12V36
12V
36Ah
207 x 175 x 175
11.5
12V45
12V
45Ah
207x 175 x 175
12.1
12V55
12V
55Ah
242 x 175 x 190
14.1
12V66
12V
66Ah
277 x 175 x 175
16.4
12V88
12V
88Ah
381 x 175 x 190
19.5
12V102
12V
102Ah
330 x 175 x 240
26
* Other battery capacities available
57
SURGE PROTECTION
Din Mount Class 2 Surge Protection
1Pole, 2Pole and 4 Pole, 20kA - 40kA
Surge Protected Plug Tops
Standard and Dedicated
Din Mount Class 1 Surge Protection
1Pole, 2Pole and 4 Pole, 200kA
PABX and Telephone Protection
1 way and 10 Way
Power Protection and Filtering
Ethernet Protection
1 Port and 24 Port
58
NOTES
59
CATEGORY PRODUCT
INDEX
Cat. Code
Description
01 Uninterruptible Power
Supplies
Sub Cat. Code
Description
UPS Accessories
Page
4
011 Line Interactive, Modified
Sinewave
Star T1X Series
5
Star T1 Series
6
012 Line Interactive, Pure Sinewave
Star T2 Series
Star T2R Series
Super Home UPS
7
8
10
013 Online, 1 Phase Input, 1 Phase Output
Star T3 Series
12
Star T3T Series
14
Star T3R Series
16
FP Series
18
014 Online, 3 Phase Input, 1 Phase Output
Star T4 Series
20
Star T4T Series
22
015 Online, 3 Phase Input, 3 Phase Output
02 Inverter/Chargers
Star T5 Series
24
Star T6 Series
26
Star T2000 Series
28
Hot Swappable Series
30
021 Modified Sinewave
IG Series
32
SKX-M Series
33
022 Pure Sinewave
03 Battery Chargers & Rectifiers
Solar Inverters
34
SKX-S Series
35
031 Switching Mode Rectifiers
36
032 Battery Chargers
38
04 Generators
041 Diesel & Petrol, 1 Phase & 3 Phase
40
05 Voltage Stabilisers
051 Transfomer Type
Constant Voltage Transformers
41
Servo Type, 1 Phase & 3 Phase
42
052 Electronic
06 Frequency Converters
60
Electrovolt with Isolation Transformer
44
Excluding Isolation Transformer
45
Industrial Inductive Type
46
061 Frequency Converters, 1 Phase & 3
Phase
48
062 Ground Military Power Units
50
07 Solar Products
071 Solar Panels and Charge Controllers
52
08 Power Supplies
081 Meanwell Power Supplies
54
09 Transformers & Batteries
091 Isolation Transformers
56
092 Batteries
57
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement