How can you transfer a WinCC flexible project via Ethernet to a

How can you transfer a WinCC flexible project via Ethernet to a
Cover sheet
How can you transfer a WinCC
flexible project via Ethernet to a
Windows-based panel?
WinCC flexible
FAQ  November 2011
Service & Support
Answers for industry.
Question
This entry originates from the Service & Support Portal of Siemens AG, Sector
Industry, Industry Automation and Drive Technologies. The conditions of use
specified there apply (www.siemens.com/nutzungsbedingungen).
Go to the following link to download this document.
http://support.automation.siemens.com/WW/view/de/23800567
Caution
The functions and solutions described in this article confine themselves
predominantly to the realization of the automation task. Furthermore, please take
into account that corresponding protective measures have to be taken in the
context of Industrial Security when connecting your equipment to other parts of the
plant, the enterprise network or the internet. Further information can be found in
Entry ID: !50203404!.
http://support.automation.siemens.com/WW/view/de/50203404
Question
How can you transfer a WinCC flexible project via Ethernet to a Windows-based
panel?
Answer
Follow the instructions and notes listed in this document for a detailed answer to
the above question.
2
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
Contents
Contents
1
Instructions ........................................................................................... 4
2
Settings on the Operator Panel............................................................ 5
3
3.1
3.1.1
3.1.2
3.2
3.2.1
3.2.2
3.3
3.3.1
3.3.2
Settings on the Configuration Computer .............................................. 7
Settings in Windows 7 .......................................................................... 7
Non-integrated Project ......................................................................... 7
Integrated Project ................................................................................. 9
Settings in Windows XP ..................................................................... 12
Non-integrated Project ....................................................................... 12
Integrated Project ............................................................................... 14
Checking the Ethernet Connection .................................................... 17
Check the Connection to the Panel.................................................... 17
Check the Settings on the Operator Panel ........................................ 18
4
4.1.1
4.1.2
Settings in WinCC flexible .................................................................. 20
Non-integrated Project ....................................................................... 20
Integrated Project ............................................................................... 22
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
3
1 Instructions
1
Instructions
For transfer of a WinCC flexible configuration via Ethernet you must make settings
on the operator panel and on the configuration PC.
Notes
•
•
•
•
•
4
It is not possible to transfer a project to a Micro Panel, because the Micro Panel does
not have an Ethernet interface.
Transfer via Ethernet is possible with an OP270 / TP270. Since these two devices
have no onboard Ethernet interface you need an NE2000-compatible CF card with
Ethernet interface.
Information about which panels support Ethernet transfer is available in the relevant
manual of each operator panel or in the entry entitled "What transfer options are
available in the various operator panels?", Entry ID: 19109408
If you wish to integrate your configuration computer into an existing Ethernet network,
you must transfer the parameters of the existing Ethernet network. Please note that
the IP address of the PC on the Ethernet network must be unique.
In the case of a direct connection without any other active components such as hub,
switch or router you need a crossover patch cable.
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
2 Settings on the Operator Panel
2
Settings on the Operator Panel
The illustrations below are from MP 377 and might differ from operator panel to
operator panel, because not all the functions are available for each operator panel.
Table 2-1
No.
Action
1.
Open the "Transfer" dialog in the "Control
Panel".
2.
Transfer via Ethernet is enabled under
Channel 2. Select "Ethernet" for Channel 2.
For Channel 2 you also set a check mark for
"Enable Channel" and if you wish, "Remote
Control".
Screen
Notes
The "Remote Control" option permits
automatic termination of Runtime on the panel
when transfer is triggered via the development
environment of WinCC flexible. The panel
then automatically switches to Transfer mode.
3.
Open the advanced settings by clicking the
"Advanced" button.
4.
Double-click the "Ethernet driver".
5.
If you do not take the IP address from a
DHCP server, select "Specify an IP address"
and specify the IP address and the subnet
mask of the panel.
Note
The IP address must be unique, in other
words, it must not be used by any other node
in the network.
6.
Close the dialog box with "OK".
7.
Click the "System" icon to open the "System
Properties" dialog window.
Change the name of the operator panel
(“HMI_Panel_mp377", for example).
Note
If you are using multiple panels in one
Ethernet network, you should always change
the name of the panel. Note that the device
name must be unique, in other words, it must
not already be used by another device.
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
5
2 Settings on the Operator Panel
No.
6
Action
8.
Close the dialog box with "OK".
9.
Close the "Control Panel" as well.
10.
Select the "Transfer" button in the "Runtime
Loader".
Screen
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
3 Settings on the Configuration Computer
3
Settings on the Configuration Computer
Depending on your operating system you select either "Settings in Windows 7" or "Settings in
Windows XP".
3.1
Settings in Windows 7
The required settings on the configuration computer are described below.
3.1.1
Non-integrated Project
Table 3-1
No.
1.
Action
Screen
Open the "Network and Sharing Center" menu
in the Control Panel of your configuration
computer.
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
7
3 Settings on the Configuration Computer
No.
8
Action
2.
In the "Network and Sharing Center" you click
"Change adapter settings". Double-click the
relevant "Network" and then click the
"Properties" button to open the Properties
window of that network.
3.
Mark "Internet Protocol Version 4 (TCP/IPv4)"
and then click the "Properties" button.
Screen
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
3 Settings on the Configuration Computer
No.
4.
Action
Screen
Assign a valid IP address and subnet mask.
Note
The IP address must be unique. In other
words, it must not be used by another node
(socket) in the network.
5.
3.1.2
Close the Properties dialog and all other
dialogs with "OK".
Integrated Project
Table 3-2
No.
1.
Action
Screen
Open the "Set PG/PC Interface" menu in the
Control Panel of your configuration computer.
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
9
3 Settings on the Configuration Computer
No.
Action
2.
Alternatively you can also open the PG/PC
interface through the SIMATIC Manager.
3.
If you have an internal Ethernet interface, you
can select the TCP/IP adapter without CP.
Screen
You can use any NDIS Ethernet card
for transfer via Ethernet.
Note:
If none of the interfaces listed above is shown,
you can install them manually by clicking the
"Select..." button in the "Interfaces"
"Add/Remove:" field.
Click the "Properties" button.
4.
Enable "Fast Acknowledge" if you are
communicating with an S5 or S7 and are
operating less than 16 connections
simultaneously.
Click the "Network properties..." button.
10
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
3 Settings on the Configuration Computer
No.
Action
5.
Double-click the relevant "Network" and then
click the "Properties" button to open the
Properties window of that network.
6.
Mark "Internet Protocol Version 4 (TCP/IPv4)"
and then click the "Properties" button.
7.
Assign a valid IP address and subnet mask.
Screen
Note
The IP address must be unique. In other
words, it must not be used by another node
(socket) in the network.
8.
Close the Properties dialog and all other
dialogs with "OK".
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
11
3 Settings on the Configuration Computer
3.2
Settings in Windows XP
The required settings on the configuration computer are described below.
3.2.1
Non-integrated Project
Table 3-3
No.
1.
2.
3.
12
Action
Screen
Open the "Network Connections" menu in the
Control Panel of your configuration computer.
Right-click on the relevant Ethernet network
adapter (1) to open the adapter dialog
window.
Open the Ethernet adapter's Properties
window by clicking the "Properties" (2) button.
Mark "Internet Protocol (TCP/IP)" and click the
"Properties" button.
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
3 Settings on the Configuration Computer
No.
4.
Action
Screen
Assign a valid IP address and subnet mask.
Note
The IP address must be unique, in other
words, it must not be used by any other node
in the network.
5.
Close the Properties dialog and all other
dialogs with "OK".
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
13
3 Settings on the Configuration Computer
3.2.2
Integrated Project
Table 3-4
No.
Action
1.
Open the "Set PG/PC Interface" menu in the
Control Panel of your configuration computer.
2.
Alternatively you can also open the PG/PC
interface through the SIMATIC Manager.
3.
If you have an internal Ethernet interface, you
can select the TCP/IP adapter without CP.
Screen
You can use any NDIS Ethernet card
for transfer via Ethernet.
Note:
If none of the interfaces listed above is shown,
you can install them manually by clicking the
"Select..." button in the "Interfaces"
"Add/Remove:" field.
Click the "Properties" button.
14
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
3 Settings on the Configuration Computer
No.
4.
Action
Screen
Enable "Fast Acknowledge" if you are
communicating with an S5 or S7 and are
operating less than 16 connections
simultaneously.
Click the "Network properties..." button.
5.
Right-click on the relevant Ethernet network
adapter (1) to open the adapter dialog
window.
Open the Ethernet adapter's Properties
window by clicking the "Properties" (2) button.
6.
Mark "Internet Protocol (TCP/IP)" and click the
"Properties" button.
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
15
3 Settings on the Configuration Computer
No.
7.
Action
Screen
Assign a valid IP address and subnet mask.
Note
The IP address must be unique, in other
words, it must not be used by any other node
in the network.
8.
16
Close the Properties dialog and all other
dialogs with "OK".
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
3 Settings on the Configuration Computer
3.3
Checking the Ethernet Connection
3.3.1
Check the Connection to the Panel
Table 3-5
No.
Action
1.
Enter "CMD" in the Windows 7 dialog field
"Search programs and files". Click the result
found.
2.
Enter the "ping" command and the IP address
of the panel, "150.150.150.20", for example.
Confirm with "Enter".
You can see the assigned IP addresses in
Table 2.5.
Note
If you have already integrated the PLC into
the network, you should also verify this via the
"ping" command.
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
Screen
17
3 Settings on the Configuration Computer
No.
Action
Screen
3.
If the time is exceeded (no reply from node),
then check the following points:
•
Check and if necessary, replace the
Ethernet cable (uncrossed patch cable,
when using a hub or switch, for example).
•
Check the IP address and subnet mask
on the panel and on the configuration PC.
•
Select and enable the correct Ethernet
adapter.
•
Check the Transfer settings in "Control
Panel > Transfer Settings".
•
If necessary, check the firewall settings
on the configuration PC.
4.
If the time is not exceeded, the connection
configuration at operating system level is OK
and you can close the Windows command
console.
Table 3-6
IP address
3.3.2
Subnet mask
Node
150.150.150.10
255.255.255.0
Configuration computer
150.150.150.20
255.255.255.0
HMI operator panel
150.150.150.30
255.255.255.0
SIMATIC station (CPU, for
example)
Check the Settings on the Operator Panel
You can also test the Ethernet connection from the operator panel. Proceed as follows.
Table 3-7
No.
Action
1.
In Windows CE you open the panel's onscreen keyboard via "Start > Programs > Soft
keyboard".
Then start the Windows CE command console
via "Start > Programs > Command Prompt".
2.
Enter the "ping" command and the IP address
of the panel, "150.150.150.10", for example.
Confirm with the Enter key.
Screen
Note
If you have already integrated the PLC into
the network, you should also verify this via the
"ping" command.
3.
18
If the time is exceeded (no reply from node),
then check the following points:
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
3 Settings on the Configuration Computer
No.
Action
•
•
•
•
•
4.
Screen
Check and if necessary, replace the
Ethernet cable (uncrossed patch cable,
when using a hub or switch, for example).
Check the IP address and subnet mask
on the panel and on the configuration PC.
Select and enable the correct Ethernet
adapter.
Check the Transfer settings in "Control
Panel > Transfer Settings".
If necessary, check the firewall settings
on the configuration PC.
If the time is not exceeded, the connection
configuration at operating system level is OK
and you can close the Windows CE command
console.
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
19
4 Settings in WinCC flexible
4
Settings in WinCC flexible
As an option you can also integrate the WinCC flexible project into a STEP 7 project.
4.1.1
Non-integrated Project
Table 4-1
No.
1.
Action
Screen
In the project tree structure under
"Communication" you select the
"Connections" tab.
In WinCC flexible you insert a new connection
in the menu under "Insert > New Object Connection".
Alternatively you can double-click an empty
field in the table in the "Connections" tab and
create a new connection.
2.
Define the relevant parameters that you have
already specified in the panel and in the
PG/PC interface. For communication via
Ethernet you must change the interface in
WinCC flexible to "Ethernet" or "HMI IE".
Note
Also make sure that the expansion slot and
rack are also correctly specified for SIMATIC
stations and that the access point is correct.
3.
Note
If you do not implement an S7-300/400 CPU
as communications partner, then change the
communication driver.
The following communication drivers that
support the Ethernet protocol are available.
•
•
•
•
•
•
20
Modicon MODBUS TCP/IP
OPC
SIMATIC HMI http Protocol
SIMATIC S7200
SIMATIC S7 300/400
SIMOTION
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
4 Settings in WinCC flexible
No.
Action
4.
Open the dialog window under "Project >
Transfer > Transfer Settings...". Alternatively
you can also open the transfer settings via the
toolbar (1).
5.
In the "Transfer Settings" dialog you select the
relevant operator panel (2) - only necessary in
the case of multiple operator panels.
6.
Select Ethernet as the Transfer mode (3) and
enter the IP address or the computer
name/operator panel name.
Screen
Note
If you specify the device name of a Windows
CE panel, a DNS server is required, because
Windows CE does not directly support the
name resolution. The configuration computer
can also be used as DNS server. More
information is available in the entry entitled >
How do you integrate an HMI operator panel
into a local network?
Note
For the possible transfer options please refer
to the relevant operator panel manual or the
entry entitled >-What transfer options are
available in the various operator panels?
7.
With the "Transfer" button (4) you can now
transfer your configuration to the panel.
Note
If you do not want to transfer yet, you can
save the settings with "Apply". With the first
transfer of the project to an operator panel you
should disable the "Delta transfer" option and
enable the "Overwrite password list" option (if
necessary, also the "Overwrite recipe data
records" option).
Note
After transfer the panel applies the
parameters set in the "Connections" tab.
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
21
4 Settings in WinCC flexible
4.1.2
Integrated Project
Table 4-2
No.
Action
1.
If you have not already inserted the project in
the SIMATIC Manager, you can insert the
project from WinCC flexible into any STEP 7
project with the menu "Project > Integrate in
STEP 7...".
2.
For this in the SIMATIC Manager you open
the Hardware Configuration of the S7. Here
you mark the appropriate SIMATIC HMI
Station (1) and double-click "Configuration"
(2).
3.
Click and mark the fifth slot (1) of the panel.
4.
Insert the Ethernet module (2) under
"SIMATIC HMI Station > CP Industrial
Ethernet > HMI IE".
5.
Double-click the Ethernet module inserted in
the subrack to open the Properties window.
Enter the IP address and subnet mask (3) that
you have already specified in the panel.
6.
Link the HMI IE module with the existing
Ethernet network (4).
Screen
Note
You can use the "New..." button to add more
subnets. Note here that the HMI station and
associated SIMATIC station must be in the
same subnet. Project transfer via Ethernet
with S7 Routing is not supported.
7.
Close the dialog window with "OK".
8.
Save and compile your configuration via the
"Station > Save and compile..." menu.
22
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
4 Settings in WinCC flexible
No.
Action
9.
Via the corresponding subnet you select the
station with which the operator panel is to
communicate.
10.
Open the dialog window under "Project >
Transfer > Transfer Settings...". Alternatively
you can also open the transfer settings via the
toolbar (1).
11.
In the "Transfer Settings" dialog you select the
relevant operator panel (2) - only necessary in
the case of multiple operator panels.
12.
Select Ethernet as the Transfer mode (3) and
enter the IP address or the computer
name/operator panel name.
Note
If you specify the device name of a Windows
CE panel, a DNS server is required, because
Windows CE does not directly support the
name resolution. The configuration computer
can also be used as DNS server. More
information is available in the entry entitled
"How do you integrate an HMI operator panel
into a local network?" in Entry ID: 13336639
Screen
Note
For the possible transfer options please refer
to the relevant operator panel manual or the
entry entitled "What transfer options are
available in the various operator panels?" in
Entry ID: 19109408.
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
23
4 Settings in WinCC flexible
No.
13.
Action
Screen
With the "Transfer" button (4) you can now
transfer your configuration to the panel.
Note
If you do not want to transfer yet, you can
save the settings with "Apply". With the first
transfer of the project to an operator panel you
should disable the "Delta transfer" option and
enable the "Overwrite password list" option (if
necessary, also the "Overwrite recipe data
records" option).
Note
After transfer the panel applies the
parameters set in the "Connections" tab.
24
Ethernet Transfer bei WinCC flexible
Version V 1.0, Entry ID: 23800567
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF