E Power On-line 3 Phase UPS
E Power On-line 3 Phase UPS
Features
Ÿ
Fully Digitized microprocessor control
Ÿ
Wide input voltage range
Ÿ
Galvanic Isolation Output
Ÿ
Interactive LCD/LED display
Ÿ
N + X parallel redundancy available
Ÿ
Advanced battery management
Ÿ
Internal manual bypass
Ÿ
Lightning and surge protection
Ÿ
Short circuit and overload protection
Ÿ
Optional extension battery pack
Ÿ
EMI / RFI noise filter
Ÿ
Smart RS232 with monitoring software
Ÿ
SNMP option available
$$$$
Camera
Surveillance
Display
Gates
Telephone
Systems
Computer
Servers
Point of Sale
Industrial
Medical
Mining
Relay PCB Functions
Ÿ
AC failure
2
Ÿ
Battery low voltage
1
Ÿ
UPS fault
4
Ÿ
Bypass
3
LED Functions:
1 Input Voltage
2 Bypass Active
3 Battery
4 Inverter Active
Options
LCD Functions:
Ÿ
Input/Output Voltage
Ÿ
Frequency
Ÿ
Power
Ÿ
Power Factor
Ÿ
Battery Voltage
Ÿ
Current
Ÿ
Battery Status
Ÿ
Load Percentage
Ÿ
UPS Status
Ÿ
History Record
Ÿ
Set Parameters
Ÿ
SNMP capability
Ÿ
External manual bypass
Ÿ
Harmonic Filter
Specifications
Model
EP160
Capacity (VA)
160kVA
Power Rating (W)
144kW
Input
Voltage range
380V/400V/415V ± 25% Three - Phase, Four wire
Frequency range
50/60Hz ± auto-sensing
Power factor
0.8-0.9 Load dependant
Rated current
240A
Output
Voltage range
Frequency
Output waveform
Power factor
Distortion
Overload capacity
Crest factor
Efficiency
380V, 400VA, 415V ± 1% user selectable
50/60Hz ± auto-sensing
Sine wave
0.9
Linear load < 3%, Non-Linear < 5%
125% for 10 minutes, 150% for 60 seconds
3:1 (max)
92%
Bypass
Rated voltage
Bypass voltage range
Rated frequency
380/400/415VAC
Upper limit: +10%, +15%, +20% selectable; Lower limit: -10%, -20%, -30%, -40% selectable
50/60 Hz (auto-sensing )
Bypass frequency range
+/-2% , +/-10%, +/-20% selectable
Transfer time to bypass
0ms
Overload capacity
1500% for 10ms, 500% for 5s
Battery
Type
12V sealed lead acid, maintenance free
Standard Configuration
40
Min Amount of Batteries
38
Max Amount of Batteries
40
Comms & Management
Ports
Software
Relay contact and RS232 standard
Windows 95/98/NT/2000/XP/Vista/7, Windows Server 2003/2008
Linux Debian, Redhat, Fedora, Suse, Ubuntu, CentOS, Novell, Mac, FreeBSD
LCD
Display input/output voltage, frequency, power, power factor, battery voltage, current, battery status,
load percentage, UPS status, history record, set parameters
LED
Indicate the status of input, inverter, bypass, battery, output
Options
Harmonic filter, SNMP adapter, Battery temperature sensor, Manual Bypass
Environment
Operating temperature
Humidity
0 - 40°C
0 ~95% Non-condensing
Storage temperature
-25°C - 55°C
Noise
72dB @ 1m
Physical characteristics
Net (kg)
1300
Gross (kg)
1400
Dimension (W*D*H)
Safety & EMC
1420*750*1805
IEC 62040-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, CE, C-Tick
Specifications subject to change without prior notice.