Series AH1 Braided Hose

Victaulic

®

Vic-Flex™ Sprinkler Fittings

Series AH1 Braided Flexible Hose

10.95

1.0 PRODUCT DESCRIPTION

Available Sizes by Component

• Series AH1 Braided Hose:

31, 36, 48, 60, 72"/790, 914, 1220, 1525, 1830 mm. Note: length includes adapter nipple and 5.75"/140 mm straight reducer.

• Sprinkler Reducers:

½" and ¾"/15 and 20 mm sprinkler connections and 5.75"/140 mm, 9"/230 mm, 13"/330 mm straight lengths and short, long 90º elbows. Note: The short 90° elbow is typically used with concealed sprinklers while the long 90º elbow is typically used in the installation of recessed pendent sprinklers.

• Adapter Nipples:

1"/25 mm NPT or BSPT adapter nipples for attaching to pipe and fittings outlined in NFPA standards. ¾"/20 mm NPT or BSPT available for VdS. 1 ¼"/ 32mm BSPT available for LPCB.

• Brackets:

• Style AB1 for suspended and hard-lid ceilings, allows installation before ceiling tiles in place

• Style AB2 for suspended and hard-lid ceilings, allows for vertical sprinkler adjustment, and installation before

ceiling tiles in place

• Style AB3 for surface mount applications, wood, metal and block walls

• Style AB4 for hard-lid ceilings with hat furr ing channel grid systems, allows for vertical sprinkler adjustment

• Style AB5 for hard-lid ceilings, allows for vertical sprinkler adjustment

• Style AB6 for cold storage applications, refer to submittal 10.90

• Style AB7 for suspended and hard-lid ceilings

• Style AB7 Adjustable for suspended and hard-lid ceilings

• Style AB8 for hard-lid ceilings with CD 60/27 profile metal studs (regionally available)

• Style AB9 for hard-lid ceilings with hat furring channel grid systems

• Style AB10 for Armstrong

®

TechZone

ceilings

Maximum Working Temperature

• 225°F/107°C

Maximum Working Pressure

• 200 psi/1375 kPa (FM Approval)

• 175 psi/1206 kPa (cULus Listed)

• 1600 kPa/232 psi (VdS/LPCB Approved)

ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.

System No.

Submitted By

Location

Date

Spec Section

Approved

victaulic.com

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

1

Paragraph

Date

victaulic.com

1.0 PRODUCT DESCRIPTION (Continued)

Connections

• To adapter nipple (inlet) via 1"/25.4 mm NPT or BSPT male thread

OR

• To adapter nipple (inlet) via ¾"/20 mm BSPT male thread(VdS only)

• To sprinkler head (outlet) via ½" or ¾"/15 mm or 20 mm

Minimum Bend Radius

• 7"/178 mm (FM Approval)

• 3"/76.2 mm (cULus Listed)

• 3"/76.2 mm (VdS/LPCB Approved)

Maximum Allowable Sprinkler K-Factors

• FM (½"/15mm reducer) K5.6/8,1 (S.I.), (¾"/20mm reducer) K14.0/20,2 (S.I.)

• cULus (½"/15mm reducer) K8.0/11,5 (S.I.), (¾"/20mm reducer) K14.0/20,2 (S.I.)

• VdS/LPCB (½"/15mm reducer) K5.6/8,1 (S.I.), (¾"/20mm reducer) K8.0/11,5 (S.I.)

2.0 CERTIFICATION/LISTINGS

3.0 SPECIFICATIONS – MATERIAL

Series AH1

• Flexible Hose:

300-series Stainless Steel

• Collar/Weld Fitting:

300-series Stainless Steel

• Gasket Seal:

Victaulic EPDM

• Isolation Ring:

Nylon

• Nut and Nipple:

Carbon Steel, Zinc Plated

• Reducer (½ or ¾"):

Carbon Steel, Zinc-Plated

Brackets:

Carbon Steel, Zinc-Plated

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

2

victaulic.com

4.0 DIMENSIONS

Product Details - Series AH1 Braided Hose

5

1

6

A

Hose Length Dimensions

Hose Length

inches mm

31/790

36/915

48/1220

60/1525

72/1830

Standard Reducer

B

A

inches mm

25.25/641

31.25/794

42.25/1073

54.25/1378

66.25/1683

7

2

3

4

B

inches mm

31/790

36/915

48/1220

60/1525

72/1830

5.75"/140 mm straight reducer

Optional Reducers

9.0"/229 mm straight reducer

4.83"/

122.7 mm

13.0"/330 mm straight reducer

2.62"/

66.5 mm

2.62"/

66.5 mm

6.57"/

166.9 mm

Item

5

6

7

3

4

1

2

Description

Flexible Hose

Isolation Ring

Gasket

Nut

Branch Line Nipple

Braid

Collar/Weld Fitting

Short 90° elbow reducer Long 90° elbow reducer

NOTE

• The Short 90° elbow reducer is typically used with concealed sprinklers while the longer 90 elbow is typically used in the installation of recessed pendent sprinklers.

• FM/VdS Approved Only.

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

3

victaulic.com

4.1 DIMENSIONS

VicFlex Brackets

• Suspended Ceilings

• Hard-Lid Ceilings (FM Only)

Item

1

2

3

Description

24"/610 mm or 48"/1220 mm Square Bar*

Patented Center Bracket

End Bracket

* Both sizes FM/VdS/LPCB approved, cULus listed

• Suspended Ceilings

• Hard-Lid Ceilings

Item

1

2

3

Description

24"/610 mm or 48"/1220 mm Square Bar*

Patented Vertically Adjustable Center Bracket

End Bracket

* Both sizes FM/VdS/LPCB approved, cULus listed

3

3

2

1

3

2

1

3

• Surface Mount Applications

• FM Approved

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

4

victaulic.com

4.2 DIMENSIONS

VicFlex Brackets

• Hard-Lid Ceilings with Hat furring channel grid system

Item

1

2

3

Description

24"/610 mm or 48"/1220 mm Square Bar*

Patented Vertically Adjustable Center Bracket

End Bracket for Hat Furring Channel

*

Both sizes FM/VdS approved, cULus listed

3

• Hard-Lid Ceilings

Item

1

2

3

Description

24"/610 mm or 48"/1220 mm Square Bar*

Patented Vertically Adjustable Center Bracket

End Bracket

*

Both sizes FM/VdS approved, cULus listed

3

• Suspended Ceilings

• Hard-Lid Ceilings

Item

1

2

3

* Both sizes FM/VdS approved.

Description

24"/610 mm or 48"/1220 mm Square Bar*

Patented 1-Bee2® Center Bracket

End Bracket

• Suspended Ceilings

• Hard-Lid Ceilings

Item

1

2

3

* Both sizes FM/VdS approved.

Description

700 mm or 1400 mm Square Bar*

Patented 1-Bee2® Center Bracket

End Bracket (adjustable)

3

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

5

3

1

2

2

1

3

2

1

2

1

3

3

3

victaulic.com

4.3 DIMENSIONS

VicFlex Brackets

• Hard-Lid Ceilings

Item

1

2

3

*

Both sizes FM/VdS approved.

Description

700 mm or 1400 mm Square Bar*

Patented Vertically Adjustable Center Bracket

*Both sizes FM/VdS

• Hard-Lid ceilings with Hat furring channel grid system

Item

1

2

3

*

Both sizes FM/VdS approved.

Description

24"/610 mm or 48"/1220 mm Square Bar*

Patented 1-Bee2® Center Bracket

End Bracket for Hat Furring Channel

• Suspended ceilings

• Armstrong ® TechZone ™

Item

1

2

3

Description

6"/152 mm Square Bar*

Patented 1-Bee2® Center Bracket

End Bracket

* FM/VdS approved, cULus listed.

3

3

2

1

3

3

1

2

2

1

3

3

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

6

victaulic.com

4.4 DIMENSIONS

CLEARANCES ABOVE CEILING

Series AH1 Braided Hose and Style AB1 Bracket

Suspended Ceiling Grid with Recessed Sprinkler Suspended Ceiling Grid with Concealed Sprinkler

R

See chart

R

See chart

A

See Chart

Bracket assembly

Style AB1

4.4"/

113 mm

2/"/60 mm max. hole

2"/51 mm min. hole

/"/16 mm

Typical ceiling tile

1.7"/43 mm

Typical ceiling grid

See note

Finished ceiling face

24"/610 mm or 48"/1219 mm on Center

V2707 ¾"/19 mm MAX. RECESS

V2707 ¾"/19mm Max. Recess

V2707 MAX. EXTENSION

Hose Clearance Chart

R

A

Dimension

Minimum

Bend Radius

Min.

inches

mm inches

mm inches

mm inches

mm inches

mm inches

mm

2

50

10.8

273

3

80

11.8

298.5

4

100

12.8

324

5

125

13.8

349

6

150

14.8

375

7

175

15.8

400

Suspended Ceiling Grid with Recessed Sprinkler with

90° Elbow (Long)

A

See Chart

Bracket Assembly

Style AB1

4.4"/113 mm

2/"/68.3 mm max. hole

2/"/60.3 mm min. hole

/"/15.9 mm

Typical ceiling tile

1.7"/43 mm

Typical ceiling grid

See note

24"/610 mm or 48"/1219 mm on Center

Finished ceiling face

V3802 ½"/12.7 MM MAX. RECESS

V3802 ½"/12.7mm Max. Recess

V3802 MAX. EXTENSION

R

A

Hose Clearance Chart

Dimension

Minimum

Bend Radius

Min.

inches

mm inches

mm inches

mm inches

mm inches

mm inches

mm

2

50

10.1

269

3

80

11.1

281

4

100

12.1

307

5

125

13.1

333

6

150

14.1

358

7

175

15.1

383

Suspended Ceiling Grid with Concealed Sprinkler with

90° Elbow (Short)

Bracket assembly

Style AB1

A

See Chart

4.4"/

113 mm

2/"/60 mm max. hole

2"/51 mm min. hole

/"/16 mm

Typical ceiling tile

1.7"/43 mm

Typical ceiling grid

See note

A

24"/610 mm or 48"/1219 mm on Center

V2707 ¾" /19 mm MAX. RECESS

Finished ceiling face

V2707 ¾"/19mm Max. Recess

Hose Clearance Chart

Dimension

Min.

V2707 MAX. EXTENSION

inches

mm

8.0

200

A

See Chart

Bracket Assembly

Style AB1

4.4"/

113 mm

2/"/68 mm max. hole

2/"/60 mm min. hole

1.7"/43 mm

Typical ceiling grid

See note

/"/16 mm

Typical ceiling tile

24"/610 mm or

48"/1219 mm on Center

V3802 ½"/12.7 mm MAX. RECESS

Finished ceiling face

V3802 MAX. EXTENSION

A

V3802 ½"/12.7mm Max. Recess

Hose Clearance Chart

Dimension

Min.

inches

mm

5.8

147

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

7

victaulic.com

4.5 DIMENSIONS

CLEARANCES ABOVE CEILING

Series AH1 Braided Hose and Style AB2 Bracket

Hard-lid Ceiling with Concealed Sprinkler Hard-lid Ceiling with Recessed Sprinkler

R

See chart

R

See chart

A

See chart

A

See chart

#10 Screw Bracket assembly

Style AB2

1.8"/

45 mm

2" × 4" Stud

2" × 4" Stud

#10 Screw

Bracket assembly

Style AB2

1.8"/

45 mm

2¾"/68 mm max. hole

23⁄8"/59 mm min. hole

2⁄"/60 mm max. hole

2"/51 mm min. hole

3.5"/

89 mm

3.5"/

89 mm

16"/406 mm Stud C/C

Finished ceiling face

V3802 ½"/13 mm MAX. RECESS

V3802 ½"/12.7mm Max. Recess

V3802 MAX. EXTENSION

16"/406 mm Stud C/C

V2707 ¾"/19 mm MAX. RECESS

Finished ceiling face

V2707 ¾"/19mm Max. Recess

V2707 MAX. EXTENSION

Hose Clearance Chart Hose Clearance Chart

Dimension Dimension

R

A

Minimum

Bend Radius

Min.

inches

mm inches

mm inches

mm inches

mm inches

mm inches

mm

2

50

7.6

193

3

80

8.6

218

4

100

9.6

244

5

125

10.6

269

6

150

11.6

295

7

175

12.6

320

R

A

Minimum

Bend Radius

Min.

inches

mm

2

50

6.1

155 inches

mm inches

mm inches

mm inches

mm inches

mm

3

80

7.1

180

4

100

8.1

206

5

125

9.1

231

NOTE

• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.

6

150

10.1

256

7

175

11.1

282

Hard-lid Ceiling Grid with Concealed Sprinkler with

90° Elbow (Short)

Hard-lid Ceiling with Recessed Sprinkler with

90° Elbow (Long)

2" × 4" Stud

3.5"/

89 mm

#10 Screw Bracket assembly

Style AB2

A

See chart

1.8"/

45 mm

2¾"/68 mm max. hole

2⁄"/59 mm min. hole

2" × 4" Stud

3.5"/

89 mm

#10 Screw

Bracket assembly

Style AB2

1.8"/

45 mm

A

See chart

2⁄"/60 mm max. hole

2"/51 mm min. hole

A

16"/406 mm Stud C/C

V3802 ½"/13 mm MAX. RECESS

V3802 ½"/12.7mm Max. Recess

Finished ceiling face

Hose Clearance Chart

Dimension

Min.

inches

mm

5.0

127

V3802 MAX. EXTENSION

A

16"/406 mm Stud C/C

V2707 ¾"/19 mm MAX. RECESS

V2707 ¾"/19mm Max. Recess

Finished ceiling face

V2707 MAX. EXTENSION

Hose Clearance Chart

Dimension

Min.

inches

mm

3.6

91

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

8

victaulic.com

4.6 DIMENSIONS

CLEARANCES WITHIN SIDEWALL

Series AH1 Braided Hose and Style AB2 Bracket

Horizontal Sidewall Sprinkler Horizontal Sidewall Sprinkler with 90° Elbow (Long)

R

See chart

2" × 4" Stud

3.5"/

89 mm

#10 Screw Bracket assembly

Style AB2

A

See chart

1.8"/

45 mm

2⁄"/60 mm max. hole

2"/51 mm min. hole

Finished ceiling face

16"/406 mm Stud C/C

V2709 ¾"/19 mm MAX. RECESS

V2707 ¾"/19mm Max. Recess

V2709 MAX. EXTENSION

Hose Clearance Chart

R

A

Dimension

Minimum

Bend Radius

Min.

inches

mm inches

mm inches

mm inches

mm inches

mm inches

mm

2

50

6.1

155

3

80

7.1

180

4

100

8.1

206

5

125

9.1

231

6

150

10.1

256

7

175

11.1

282

2" × 4" Stud

3.5"/

89 mm

#10 Screw Bracket assembly

Style AB2

A

See chart

1.8"/

45 mm

2⁄"/60 mm max. hole

2"/51 mm min. hole

A

16"/406 mm Stud C/C

V2709 ¾"/19 mm MAX. RECESS

V2707 ¾"/19mm Max. Recess

Finished ceiling face

V2709 MAX. EXTENSION

Hose Clearance Chart

Dimension

Min.

inches

mm

3.6

91

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

9

victaulic.com

4.7 DIMENSIONS

CLEARANCES ABOVE CEILING

Series AH1 Braided Hose and Style AB4 Bracket

Hat Furring Channel Grid with Recessed Sprinkler

R

See chart

A

See Chart

2/"/60 mm max. hole

2"/51 mm min. hole

See note

Typical 16"/406 mm –

24"/610 mm on Center

/"/15.9 mm

Typical ceiling tile

Finished ceiling face

/"/23 mm

Typical ceiling grid

V2707 ¾"/19.1 MM MAX. RECESS

V2707 ¾"/19mm Max. Recess

V2707 MAX. EXTENSION

R

A

Hose Clearance Chart

Dimension

Minimum

Bend Radius

Min.

inches

mm inches

mm inches

mm inches

mm inches

mm inches

mm

2

50

10.3

262

3

80

11.3

287

4

100

12.3

313

5

125

13.3

338

6

150

14.3

363.5

7

175

15.3

389

Hat Furring Channel Grid with Recessed Sprinkler with

90° Elbow (Long)

Hat Furring Channel Grid with Concealed Sprinkler with

90° Elbow (Short)

A

See Chart

A

See Chart

2/"/60 mm max. hole

2"/51 mm min. hole

2/"/60 mm max. hole

2"/51 mm min. hole

See note

/"/16 mm

Typical ceiling tile

Finished ceiling face

/"/23 mm

Typical ceiling grid

Typical 16"/406 mm –

24"/610 mm on Center

V2707 ¾"/19.1 MM MAX. RECESS

V2707 ¾"/19mm Max. Recess

V2707 MAX. EXTENSION

See Note

/"/16 mm

Typical ceiling tile

16"/406 mm –

24"/610 mm on Center

V3802 ½"/12.7 mm MAX. RECESS

/"/23 mm

Typical ceiling grid

V2707 ¾"/19mm Max. Recess

V3802 MAX. EXTENSION

Hose Clearance Chart Hose Clearance Chart

Dimension Dimension

inches

mm inches

mm

A Min.

8.0

200

A Min.

NOTE

• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.

5.9

149

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

10

victaulic.com

4.8 DIMENSIONS

CLEARANCES ABOVE CEILING

Series AH1 Braided Hose and Style AB5 Bracket

Hard-lid Ceiling with Recessed Sprinkler Hard-lid Ceiling with Concealed Sprinkler

R

See chart

R

See chart

A

See chart

A

See chart

#10 Screw

Bracket assembly

Style AB5 Bracket assembly

Style AB5

2.3"/

57 mm

#10 Screw

2⁄"/60 mm max. hole

2"/51 mm min. hole

2.3"/

57 mm

2¾"/68 mm max. hole

2⁄"/59 mm min. hole

3.5"/

89 mm

2" × 4" Stud

3.5"/

89 mm

2" × 4" Stud

/"/16 mm

Typ. Drywall

Finished ceiling face

16"/406 mm Stud C/C

V2707 ¾"/19 mm MAX. RECESS

V2707 ¾"/19mm Max. Recess

V2707 MAX. EXTENSION

R

A

Hose Clearance Chart

Dimension

Minimum

Bend Radius

Min.

inches

mm inches

mm inches

mm inches

mm inches

mm inches

mm

2

50

6.1

155

3

80

7.1

180

4

100

8.1

206

5

125

9.1

231

6

150

10.1

256

7

175

11.1

282

Hard-lid Ceiling with Recessed Pendent with

90° Elbow (Long)

16"/406 mm Stud C/C

V3802 ½"/13 mm MAX. RECESS

/"/16 mm

Typ. Drywall

Finished ceiling face

V3802 ½"/13mm Max. Recess

V3802 MAX. EXTENSION

Hose Clearance Chart

R

A

Dimension

Minimum

Bend Radius

Min.

inches

mm inches

mm inches

mm inches

mm inches

mm inches

mm

2

50

7.6

193

3

80

8.6

218

4

100

9.6

244

5

125

10.6

269

6

150

11.6

295

7

175

12.6

320

Hard-lid Ceiling with Concealed Pendent with

90° Elbow (Short)

A

See chart

#10 Screw

Bracket assembly

Style AB5

A

See chart

2.3"/

57 mm

#10 Screw

Bracket assembly

Style AB5 2.3"/

57 mm

2⁄"/68 mm max. hole

2⁄"/59 mm min. hole

2⁄"/60 mm max. hole

2"/51 mm min. hole

3.5"/

89 mm

2" × 4"

Stud

/"/16 mm

Typ. Drywall

3.5"/

89 mm

2" × 4"

Stud

/"/16 mm

Typ. Drywall

16"/406 mm Stud C/C

V3802 ½"/13 mm MAX. RECESS

V3802 ½"/13mm Max. Recess

V3802 MAX. EXTENSION

Finished ceiling face

16"/406 mm Stud C/C

V2707 ¾"/19 mm MAX. RECESS

V2707 ¾"/19mm Max. Recess

V2707 MAX. EXTENSION

Hose Clearance Chart Hose Clearance Chart

Dimension Dimension

A Min.

inches

mm

3.6

91

A Min.

NOTE

• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.

inches

mm

3.3

84

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

11

victaulic.com

4.8 DIMENSIONS (Continued)

CLEARANCES ABOVE CEILING

Series AH1 Braided Hose and Style AB3 Bracket

Surface Mount Application with Recessed Sprinkler

R

C

3¾"/

95.3 mm

See Note

B

A

2/"/60 mm max. hole

2"/51 mm min. hole

Hose Clearances

Wall Thickness

"A"

Outlet Length

"B"

Hose

Clearance "C"

Bend Radius

"R"

5.75

146.1

11.6

294

2

50

9

228.6

14.8

376

13

330.2

18.8

478

5.75

146.1

9.6

243

4

100

9

228.6

13

330.2

12.8

325

7

175

16.8

427

9

228.6

10.8

275

6

150

13

330.2

14.8

376

8

200

13

330.2

12.8

325

10

250

13

330.2

10.8

275

5.75

146.1

12.6

319

2

50

9

228.6

15.8

402

13

330.2

19.8

503

5.75

146.1

10.6

268

4

100

9

228.6

13

330.2

13.8

351

8

200

17.8

452

9

228.6

11.8

300

6

150

13

330.2

15.8

402

8

200

13

330.2

13.8

351

10

250

13

330.2

11.8

300

NOTE

• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.

• See installation instructions for mounting screw type and size.

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

12

victaulic.com

5.0 PERFORMANCE – FRICTION LOSS DATA

Series AH1 Braided Hose with Stra ight 5.75" Reducers

Style AB1, AB2, AB4, AB5 and AB10 Brackets

Series AH1 Hose

Length of

Stainless Steel

Flexible Hose Outlet Size

Equivalent Length of 1"/33.7 mm

Sch. 40 Pipe (C=120)

Maximum

Number of

90° Bends at 3"/51 mm

Bend Radius

inches/mm

31/775

36/900

48/1200

60/1500

72/1800 inches/mm/type

½ " /15/Straight

¾ " /20/Straight

½ " /15/Straight

¾ " /20/Straight

½ " /15/Straight

¾ " /20/Straight

½ " /15/Straight

¾ " /20/Straight

½ " /15/Straight

¾ " /20/Straight

feet/meters

52/15.8

55/16.8

63/19.2

66/20.1

78/23.8

80/24.4

88/26.8

90/27.4

112/34.1

118/36.0

Series AH1 Braided Hose Equivalent Length Design Guide

Equivalent length values at various numbers of 90 degree bends at 3"/51 mm center line bend radius

3

4

5

4

4

4

4

3

4

5

Length of

Stainless

Steel Flexible

Hose

Outlet

Size

1

Bend

2

Bends

3

Bends

4

Bends

5

Bends

inches/mm

31/775

36/900

48/1200

60/1500

72/1800 inches/mm

½ " /15

¾ " /20

½ " /15

¾ " /20

½ " /15

¾ " /20

½ " /15

¾ " /20

½ " /15

¾ " /20

NOTES:

• Values for use with 5.75" straight reducers.

feet/meters

32/9.8

33/10.1

33/10.1

36/11.0

46/14.0

51/15.5

56/17.1

58/17.7

69/21.0

73/22.6

feet/meters

42/12.8

44/13.4

43/13.1

46/14.0

57/17.4

60/18.3

67/20.4

69/21.0

79/24.1

84/25.6

feet/meters

52/15.9

55/16.8

53/16.2

56/17.1

68/20.7

71/21.6

77/23.5

80/24.4

91/27.7

95/29.0

feet/meters

N.A

N.A

63/19.2

66/20.1

78/23.8

88/26.8

88/26.8

90/27.4

102/31.1

106/32.3

feet/meters

N.A

N.A

N.A

N.A

N.A

N.A

N.A

N.A

112/34.1

118/36.0

How to use this Design Guide:

• For some systems, it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the maximum allowable number of bends. In this case, the designer may select a design number of bends for the job and use the associated equivalent length from the design guide to determine the system hydraulics.

• It is possible that the actual installed condition of some of the flexible drops may have more bends than the designer selected. When this happens, the design guide may be used to find equivalent lengths based on the actual installed number of bends for particular sprinkler installations. The system hydraulics can be recalculated using actual equivalent lengths to verify the performance of the system.

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

13

victaulic.com

5.0 PERFORMANCE – FRICTION LOSS DATA

Series AH1 Braided Hose

Style AB1, AB2, AB3, AB4, AB5, AB7, AB7 Adj., AB8, AB9 and AB10 VicFlex Brackets

Equivalent

Length of

1"/33.7mm

Sch. 40 Pipe

Series AH1 Hose

Maximum

Number of 90° Bends at 7"/178mm

Bend Radius

inches/mm

31/775

36/900

48/1200

60/1500

72/1800

31/775

36/900

48/1200

60/1500

72/1800

31/775

36/900

48/1200

60/1500

72/1800

31/775

36/900

48/1200

60/1500

72/1800

Imperial/S.I.

5.6/8.1

5.6/8.1

5.6/8.1

5.6/8.1

5.6/8.1

8.0/11.5

8.0/11.5

8.0/11.5

8.0/11.5

8.0/11.5

11.2/16.1

11.2/16.1

11.2/16.1

11.2/16.1

11.2/16.1

14.0/20.2

14.0/20.2

14.0/20.2

14.0/20.2

14.0/20.2

inches/mm/type

½ " /15/Straight

½ " /15/90˚ Elbow

½ " /15/Straight

½ " /15/90˚ Elbow

½ " /15/Straight

½ " /15/90˚ Elbow

½ " /15/Straight

½ " /15/90˚ Elbow

½ " /15/Straight

½ " /15/90˚ Elbow

¾

"

/20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾

"

/20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow

¾ " /20/Straight

¾ " /20/90˚ Elbow feet/meters

53.8/16.4

53.8/16.4

63.7/19.4

63.1/19.2

87.9/26.8

85.8/26.1

112.2/34.1

108.4/33.0

136.5/41.6

131.1/39.9

44.4/13.5

47.6/14.5

55.6/16.9

57.5/17.5

82.8/25.2

81.7/24.9

110.1/24.9

105.9/32.2

137.3/41.8

130.2/39.7

45.5/13.8

47.1/14.3

66.3/20.2

57.5/17.5

82.7/25.2

82.8/25.2

109.1/33.2

108.1/32.9

135.5/41.3

133.4/40.6

44.3/13.5

46.4/14.1

55.5/16.9

56.7/17.3

83.0/25.3

82.1/25.0

110.4/33.6

107.5/32.7

137.9/42.0

132.8/40.4

2

2

3

4

4

2

2

3

4

4

2

2

3

4

4

2

2

3

4

4

FM NOTES:

• Series AH1 has been tested and Approved by FM Global for use in wet, dry and preaction systems per NFPA 13, 13R, and 13D and FM data sheets 2-0, 2-5, and 2-8. FM 1637 and Vds standards for safety include, but are not limited to, pressure cycling, corrosion resistance, flow characterisitics, vibration resistance, leakage, mechanical and hydrostatic strength.

• Differences in equivalent lengths are due to varying test methods, per FM 1637 and VdS standards. Refer to these standards for additional information regarding friction loss test methods.

• EXAMPLE: A 48-inch hose installed with two 30° bends and two 90° bends at a 7-inch bend radius is permitted and considered equivalent to the data in the table shown above. In this example, the total number of degrees is 240°, which is less than the allowable 270°.

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

14

victaulic.com

5.0 PERFORMANCE – FRICTION LOSS DATA

Series AH1 Braided Hose

Style AB1, AB2, AB4, AB5, AB7, AB7 Adj., AB8, AB9, and AB10 Brackets

Series AH1 Hose

Length of

Stainless Steel

Flexible Hose

Outlet

Size

mm/inches

790/31

915/36

1220/48

1525/60

1830/72

VDS CEILING MANUFACTURERS LIST

AB1, AB2, AB7, AB10

1. AMF

2. Armstrong

3. Chicago Metallic

4. Dipling

5. Durlum

6. Geipel

7. Gema-Armstrong

8. Hilti

9. Knauf

10. Lafarge

11. Linder

12. Odenwald

13. Richter

14. Rigips

15. Rockfon Pagos

16. Suckow & Fischer

17. USG Donn

AB4/9

No specific approval mm/inches/type

15mm/½ " /Straight

20 mm/¾ " /Straight

15mm/½ " /Straight

20 mm/¾ " /Straight

15mm/½ " /Straight

20 mm/¾ " /Straight

15mm/½ " /Straight

20 mm/¾ " /Straight

15mm/½ " /Straight

20 mm/¾ " /Straight

AB8

1. Hilti

2. Knauf

3. Lafarge

4. Lindner

5. Rigips

Series AH1 Braided Hose

Style AB1 Bracket

Series AH1 Hose

Equivalent Length of steel pipe according to

EN 10255 DN 20

(26,9 x 2,65)

meters/feet

4.0/12.9

4.6/15.0

6.1/20.0

7.6/25.0

9.2/30.0

Maximum Number of 90º Bends at

3"/76.2mm Bend

Radius

meters/feet

3

3

3

4

4

Series AH1 Hose

Length of

Stainless

Steel

Flexible

Hose

Outlet

Size

mm/inches

790/31

915/36

1220/48

1525/60

1830/72 mm/inches/type

15mm/½ " /Straight

20 mm/¾ " /Straight

15mm/½ " /Straight

20 mm/¾ " /Straight

15mm/½ " /Straight

20 mm/¾

"

/Straight

15mm/½ " /Straight

20 mm/¾ " /Straight

15mm/½ " /Straight

20 mm/¾ " /Straight

Equivalent Length of steel pipe according to

EN 10255 DN

(33,7 x 3,25)

Maximum

Number of

90º Bends at

3"/76.2mm

Bend Radius

meters/feet

12.7/41.8

2

16.4/53.8

19.6/64.3

24.0/78.8

28.5/93.4

3

3

3

3

Length of

Stainless

Steel

Flexible

Hose

Outlet

Size

mm/inches

790/31

915/36

1220/48

1525/60

1830/72 mm/inches/type

15mm/½ " /90 º Elbow

20 mm/¾ " /90 º Elbow

15mm/½ " /90 º Elbow

20 mm/¾ " /90 º Elbow

15mm/½ " /90 º Elbow

20 mm/¾

"

/90

º

Elbow

15mm/½ " /90 º Elbow

20 mm/¾ " /90 º Elbow

15mm/½ " /90 º Elbow

20 mm/¾ " /90 º Elbow

Equivalent Length of steel pipe according to

EN 10255 DN 25

(33,7 x 3,25)

Maximum

Number of

90º Bends at

3"/76.2mm

Bend Radius

meters/feet

13.6/44.6

2

16.9/55.4

19.9/65.1

24.5/80.2

27.8/91.1

3

3

3

3

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

15

victaulic.com

6.0 NOTIFICATIONS

WARNING

• It is the responsibility of the system designer to verify suitability of 300-series stainless steel flexible hose for use with the intended fluid media within the piping system and external environments.

• The effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on

300-series stainless steel flexible hose must be evaluated by the material specifier to confirm system life will be acceptable for the intended service.

Failure to follow these instructions could cause product failure, resulting in serious personal injury and/or property damage.

7.0 REFERENCE MATERIALS – CHARACTERISTICS

Flexible Hose In-Plane Bend Characteristics

One Bend Two Bends Three Bends

2X

Minimum bend radius

2X

Minimum bend radius

Minimum bend radius

OR

Minimum bend radius

90°

OR

Minimum bend radius

Minimum bend radius Minimum bend radius

Minimum bend radius

Minimum bend radius

NOTE

• For out-of-plane (three-dimensional) bends, care must be taken to avoid imparting torque on the hose.

User Responsibility for Product Selection and Suitability

Each user bears final responsibility for making a determination as to the suitability of

Victaulic products for a particular end-use application, in accordance with industry standards and project specifications, and the applicable building codes and related regulations as well as Victaulic performance, maintenance, safety, and warning instructions. Nothing in this or any other document, nor any verbal recommendation, advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions of sale, installation guide, or this disclaimer.

Intellectual Property Rights

No statement contained herein concerning a possible or suggested use of any material, product, service, or design is intended, or should be constructed, to grant any license under any patent or other intellectual property right of Victaulic or any of its subsidaries or affiliates covering such use or design, or as a recommendation for the use of such material, product, service, or design in the infringement of any patent or other intellectual property right. The terms “Patented” or “Patent Pending” refer to design or utility patents or patent applications for articles and/or methods of use in the United States and/or other countries.

10.95

8507 Rev D Updated 10/2016 © 2016 Victaulic Company. All rights reserved.

victaulic.com

16

Note

This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions.

Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.

Installation

Reference should always be made to I-VICFLEX-AB1-AB2-AB10, I-VICFLEX-AB4-AB9,

I-VICFLEX-AB7, or I-VICFLEX-AB8 for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com.

Warranty

Refer to the Warranty section of the current Price List or contact Victaulic for details.

Trademarks

Victaulic and all other Victaulic marks are the trademarks or registered trademarks of

Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries.