Bosch FCP-OC 500-P is an advanced fire detector that combines optical and chemical sensing technologies to provide reliable fire detection in various environments. With its multi-sensor design, it can detect both smoke and carbon monoxide (CO), making it ideal for residential and commercial applications. The device features a sleek and compact design with color-matching inserts, allowing it to blend seamlessly with different interior aesthetics. It utilizes scattered light measurement and combustion gas measurement to accurately identify fire hazards.
Advertisement
Advertisement
Fire Alarm Systems | FCP‑500 Conventional Automatic Fire Detectors
FCP‑500 Conventional Automatic Fire
Detectors
▶ Modern, ultra-flat design
▶ Matches the surrounding decor by using color toning inserts
▶ Smooth, easily-cleaned detector surface
▶ Innovative fastening mechanism
▶ High reliability
FCP‑500 Conventional Automatic Fire Detectors satisfy the most demanding aesthetic requirements owing to their flat design, which offers flush ceiling mounting and the option of color matching.
The FCP‑500 is available as a scattered light smoke detector or as a multi-sensor detector with an additional gas sensor. The respective versions of the detectors are available in white or transparent with color inserts.
Functions
The smooth, flush-installation surface means the FCP‑500 detectors can be installed in areas with high aesthetic requirements. In addition, the fire detectors are suitable for areas with heightened dust exposure.
The detectors and trim rings in the "transparent with color inserts" version are always supplied complete with reversible printed color rings, which offer a choice of
16 colors for individual color matching.
Sensor technology and signal processing
All detectors in the FCP‑500 series are equipped with two optical sensors and a pollution sensor. The FCP‑OC 500 multisensor detector contains a gas sensor as an additional detection channel.
All sensor signals are constantly analyzed by the internal signal evaluation electronics and are linked with each other through algorithms.
www.boschsecurity.com
2 | FCP‑500 Conventional Automatic Fire Detectors
By linking the optical sensors and the gas sensor, the OC detector can also be used in places where the work carried out gives rise to small amounts of smoke, steam or dust. The alarm will only be triggered automatically if the signal combination corresponds with the detector’s characteristic diagram. Consequently, a very high reliability against false alarms is obtained.
Optical sensor (smoke sensor)
The optical sensor (1) operates according to the scattered light method. The LEDs (3) transmit light at a defined angle into the scattered light area (7).
2 3
7
In case of fire, the light is scattered by the smoke particles and strikes the photo diodes (2), which transform the quantity of light into a proportional electrical signal.
4
1
3
2
5
6
2
3
1
Interference effects from daylight and commercial lighting sources are filtered out with an optical daylight filter and by the use of electronic filtering and phase-locked rectification (ambient light stability: glare test
DIN EN 54‑7).
The various light-emitting and photo diodes of the sensor are individually controlled by the detector electronics.
Consequently, signal combinations are produced that are independent of each other and ideally suitable for the detection of smoke, which makes it possible to differentiate between smoke and interference agents
(insects, objects). In addition, the time characteristics and the correlation of the optical sensor signals for the fire or interference detection are evaluated.
Moreover, plausibility checking of the various signals makes it possible to detect errors in the analysis electronics and the LEDs.
Chemical sensor (CO gas sensor)
The gas sensor (4) detects mainly the carbon monoxide
(CO) that is produced by a fire, but it also detects hydrogen (H) and nitrogen monoxide (NO).
The basic measuring principle is CO oxidation on an electrode and the measurable current that arises from this. The sensor signal value is proportional to the concentration of gas.
The gas sensor delivers additional information to effectively suppress deceptive values.
Depending on the service life of the gas sensor, the
FCP‑OC 500 detector switches off the C sensors after five years of operation. The detector will continue to function as an O detector. The detector should then be exchanged immediately in order to be able to keep using the higher reliability of detection of the OC detector.
Pollution sensor
The contamination level on the detector surface is continually measured by the pollution sensor (6); the result is evaluated and indicated.
Contamination of the detector surface leads to active adaptation of the threshold value (closed-circuit value correction).
Further performance characteristics
Various operating states are indicated on the detector by means of a clearly visible two-color LED. In the event of an alarm, the LED flashes red.
The innovative detector locking, which operates on the ballpoint-pen principle, provides fast and simple insertion and replacement of the detector. We recommend the specially developed FAA‑500‑RTL exchanger device, especially in the case of high installation heights.
To allow convenient detector testing, the FAA‑500‑TTL test adapter with magnet and additional service accessories is available.
Certifications and Approvals
Comply with:
• EN54-7:2000/A1:2002/A2:2006
Region
Germany
Europe
Certification
VdS G 205124 FCP-O 500/500-P
G 205118 FCP-OC 500/500-P
CE
CPD
FCP-500
0786-CPD-20203 FCP-O 500 / 500-P
0786-CPD-20204 FCP-OC500 / 500-P
Installation/Configuration Notes
• Can be connected to:
-
Conventional Fire Panel BZ 1012/1016/1024/1060
Universal Fire Panel UEZ 1000
Universal Fire Panel UGM 2020
FCP‑500 Conventional Automatic Fire Detectors | 3
-
Other panels or their receiver modules with identical connection conditions
UEZ 2000 LSN, BZ 500 LSN, FPA‑5000 and
FPA‑1200 via appropriate interfaces
• The detectors and detector bases can be used together with the „Rotaris” lamp by Philips.
•
The FCP‑OC 500, like the FCP‑O 500, is planned according to the guidelines for optical detectors (see
DIN VDE 0833 Part 2 and VDS 2095).
• The detectors must be installed exclusively in the
FCA‑500 bases provided. In addition, the detector base must be installed in an FAA‑500‑BB ceiling mount back box or in FAA‑500‑SB surface mount back box.
Note For flush ceiling mounting with FAA‑500‑BB:
The false ceiling may have a maximum thickness of
Note 32 mm. Above the false ceiling, a free height of at least 110 mm is required.
• FCP‑500 detectors are not intended for outdoor use.
A hemispherical space with a radius of 50 cm must remain free below the detectors.
2 1
3
1
2
3
Detector
Ceiling hemispherical space below the detector
•
Care must be taken to ensure that neither people, larger animals, plants nor any objects intrude into this area and that no parts of the detector surface become covered.
•
The detectors may only be installed in a position which is out of arm's reach. We therefore recommend a minimum installation height of 2.70 m.
•
The detectors may not be installed in rooms in which data is transmitted by means of high-intensity infrared light (e. g. in rooms with IR systems for interpreters).
•
The detectors must be mounted so that they are not exposed to any direct sunlight.
• A minimum distance of 50 cm from lamps must be maintained. The detectors may not be mounted in a cone of light from lamps.
• The bases are equipped as standard with a spring which is suitable for installation of the detector in false ceilings. When the detector is installed in concrete or wooden ceilings, these need to be replaced by the stronger springs FAA‑500‑SPRING with red markings.
• Maximum permitted air speed: 20 m/s
Country-specific standards and guidelines must be observed during the planning phase.
• Technical Specifications
Parts Included
Detector type
FCP-O 500
FCP-O 500-P
FCP-OC 500
FCP-OC 500-P
Qty.
Components
1
1
1
1
Optical Smoke Detector, White
Optical Smoke Detector, Transparent with
Color Inserts
Multisensor Detector Optical/Chemical,
White
Multisensor Detector Optical/Chemical,
Transparent with Color Inserts
Technical Specifications
Electrical
8.5 V DC bis 33 V DC Operating voltage
Standby current
• FCA-500-EU
• FCA-500-E-EU
Alarm current
Fault current
• FCA-500-EU
• FCA-500-E-EU
Alarm resistance
Fault relay output
Indicator output
Mechanics
3 mA
24 mA
47 mA
52 mA
58 mA
0 Ω (UL application) or 680 Ω
NC / C
Relay connects 0 V over 1.5 kΩ
Individual display Two-color LED, red (alarm), green (test mode)
Dimensions
Detector
Detector with trim ring
Detector with cover, base and ceiling mount back box
Housing material
Ø 113 x 55 mm
Ø 150 x 55 mm
Ø 150 x 110 mm
Housing color
Front plate color
Polycarbonate
Signal white, RAL 9003
FCP‑O 500/ FCP‑OC 500 Signal white matt
FCP‑O 500‑P/ FCP‑OC 500‑P Transparent/silver-gray
Weight
FCP-OC 500(-P)
FCP-O 500(-P)
Trim Ring
Without / with packaging
180 g / 370 g
170 g / 360 g
30 g / 60 g www.boschsecurity.com
4 | FCP‑500 Conventional Automatic Fire Detectors
Environmental conditions
Protection class as per
EN 60529
FCP‑O 500 (‑P)
FCP‑OC 500 (‑P)
Permissible operating temperature
IP 53
IP 33
FCP‑O 500 (‑P)
FCP‑OC 500 (‑P)
-20 °C bis +65 °C
-10 °C bis +50 °C
Permissible relative humidity 95% (non-condensing)
Permissible air speed 20 m/s
Planning
Monitoring area Max. 120 m 2
(Heed local guidelines!)
Maximum installation height Max. 16 m
(Heed local guidelines!)
Minimum installation height Out of arm's reach
Minimum installation height recommended by BOSCH: 2.70 m
In the case of flush ceiling mounting with ceiling mount back box
Thickness of the false ceiling Max. 32 mm
Required bored hole
Installation depth
Ø 130 mm (-1 mm bis +5 mm)
110 mm
Note: Above the false ceiling, a free height of at least 110 mm is required.
Minimum distance to lamps 0.5 m
Special features
Detection principle
• FCP‑O 500 (‑P) Scattered light measurement
• FCP‑OC 500 (‑P) Combination of scattered light measurement and combustion gas measurement
Features
• All FCP‑500 detectors
•
In addition, for
FCP‑OC 500(-P)
Contamination detection
Drift compensation (optical section)
Drift compensation in the gas sensor section
Response sensitivity
• FCP‑O 500 (‑P) < 0.18 dB/m ( EN 54‑7)
• FCP‑OC 500 (‑P) Optical section: < 0.36 dB/m (EN 54‑7)
Gas sensor section: in ppm range
Ordering Information
FCP‑O 500 Optical Smoke Detector, White ultra-flat design, conventional technology
FCP‑O 500‑P Optical Smoke Detector,
Transparent with Color Inserts ultra-flat design, conventional technology
FCP‑OC 500 Multisensor Detector Optical/
Chemical, White ultra-flat design, conventional technology
FCP‑OC 500‑P Multisensor Detector
Optical/Chemical, Transparent with Color
Inserts ultra-flat design, conventional technology
Accessories
FAA‑500‑TR-W Trim Ring, White for 500 and 520 Series Fire Detectors
FAA‑500‑TR‑P Trim Ring, Transparent with
Color Inserts for 500 and 520 Series Fire Detectors
FCA‑500‑EU Conventional Base for the FCP‑-500 Series detectors
FCA‑500‑E‑EU Conventional Base EOL for the FCP‑500 Series detectors, with integrated EOL resistor
FAA‑500‑BB Ceiling Mount Back Box for ceiling flush installation in false ceilings when mounting 500 and 520 Series Bases and Fire Detectors
FAA‑500‑CB Built-in Housing for Concrete
Ceilings for installing 500 and 520 Series Fire Detectors in concrete ceilings. In addition, you need to order a FAA‑500‑BB Ceiling Mount
Back Box, which contains the base and the detector.
FAA‑500‑SB Surface Mount Back Box for special applications where it is not possible to flush-mount the 500 and 520 Series
Fire Detectors in a ceiling
FAA‑500‑SB-H Surface Mount Back Box with Damp Room Seal for special applications where it is not possible to flush-mount the 500 and 520 Series
Fire Detectors in a ceiling
FAA‑500‑SPRING for Concrete/Wooden
Ceilings
(DU = 10 units)
FCP-O 500
FCP-O 500-P
FCP-OC 500
FCP-OC 500-P
FAA-500-TR-W
FAA-500-TR-P
FCA-500-EU
FCA-500-E-EU
FAA-500-BB
FAA-500-CB
FAA-500-SB
FAA-500-SB-H
FAA-500-SPRING
FCP‑500 Conventional Automatic Fire Detectors | 5
FCP-500 Conventional Automatic Fire Detectors
Detector type
Operating voltage
Current consumption
- Standby current
- Alarm current
- Fault current
FCP-O 500 optical
8.5 V DC . . . 33 V DC
FCA-500-EU: 3 mA
FCA-500-E-EU: 24 mA
47 mA
FCA-500-EU: 52 mA
FCA-500-E-EU: 58 mA
IP 53
-20 °C . . . +65 °C
Protection category
Permissible operating temperature
Monitoring area
Maximum installation height
Color max. 120 m²
16 m white
FCP-O 500-P optical
8.5 V DC . . . 33 V DC
FCA-500-EU: 3 mA
FCA-500-E-EU: 24 mA
47 mA
FCA-500-EU: 52 mA
FCA-500-E-EU: 58 mA
IP 53
-20 °C . . . +65 °C max. 120 m²
16 m transparent with color inserts
FCP-OC 500 optical/chemical
8.5 V DC . . . 33 V DC
FCA-500-EU: 3 mA
FCA-500-E-EU: 24 mA
47 mA
FCA-500-EU: 52 mA
FCA-500-E-EU: 58 mA
IP 33
-10 °C . . . +50 °C max. 120 m²
16 m white
FCP-OC 500-P optical/chemical
8.5 V DC . . . 33 V DC
FCA-500-EU: 3 mA
FCA-500-E-EU: 24 mA
47 mA
FCA-500-EU: 52 mA
FCA-500-E-EU: 58 mA
IP 33
-10 °C . . . +50 °C max. 120 m²
16 m transparent with color inserts www.boschsecurity.com
6 | FCP‑500 Conventional Automatic Fire Detectors
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180 [email protected]
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330 [email protected]
www.boschsecurity.com
© Bosch Security Systems 2011 | Data subject to change without notice
T1644324107 | Cur: en-US, V18, 29 Jun 2011
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698 [email protected]
www.boschsecurity.asia
Represented by
Advertisement
Key features
- Combines optical and gas sensors for reliable fire detection
- Advanced algorithms and signal processing minimize false alarms
- Easy to install and maintain
- Flush mount design with color-matching inserts for aesthetic appeal
- Suitable for areas with high dust exposure
- Pollution sensor for automatic adaptation of threshold
- Various operating states indicated by clearly visible two-color LED
- Innovative detector locking for fast and simple insertion and replacement