ICS Page/Party® Handset/Speaker Amplifier Station - GAI

ICS Page/Party® Handset/Speaker Amplifier Station - GAI
Pub. 42004-717L2I
GAI-TRONICS
®
CORPORATION
A HUBBELL COMPANY
Industrial Communications System
Page/Party® Handset/Speaker
Amplifier Station
TABLE
OF
CONTENTS
Confidentiality Notice .....................................................................................................................1
General Information .......................................................................................................................1
Product Overview ................................................................................................................................... 1
Features.................................................................................................................................................... 2
Options ..................................................................................................................................................... 2
Installation ......................................................................................................................................2
Important Safety Instructions................................................................................................................ 2
Mounting the Enclosure ......................................................................................................................... 3
Field Wiring............................................................................................................................................. 4
Speaker Jumper Impedance Configuration ......................................................................................... 5
Settings and Adjustments ................................................................................................................6
Opening the Station ................................................................................................................................ 6
Jumper Settings....................................................................................................................................... 7
Speaker Mute ........................................................................................................................................................ 7
Speaker Gain Setting............................................................................................................................................. 7
Level Adjustments .................................................................................................................................. 8
Transmit Level ...................................................................................................................................................... 8
Receiver Volume .................................................................................................................................................. 8
Speaker Volume .................................................................................................................................................... 8
Attach the Front Panel ........................................................................................................................... 8
Operation .........................................................................................................................................8
Options.............................................................................................................................................9
ICS SmartSeries ...................................................................................................................................... 9
General .................................................................................................................................................................. 9
Features ................................................................................................................................................................. 9
Installation and Adjustments ............................................................................................................................... 10
Opening the Station ........................................................................................................................................ 10
Installing the SmartSeries PCBA ................................................................................................................... 10
Setting the Address ......................................................................................................................................... 10
ALS Minimum Level ..................................................................................................................................... 10
ALS Offset Level ........................................................................................................................................... 11
SmartSeries VLC Level .................................................................................................................................. 11
GAI-Tronics Corporation 400 E. Wyomissing Ave. Mohnton, PA 19540 USA
610-777-1374  800-492-1212  Fax: 610-796-5954
VISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS
TABLE OF CONTENTS
Pub. 42004-717L2I
Speaker Impedance Supervision ..................................................................................................................... 11
FSK Signal Gain ............................................................................................................................................. 12
Attaching the Front Panel ............................................................................................................................... 12
Operation ............................................................................................................................................................ 12
Paging with ADVANCE Head End ................................................................................................................ 12
Paging without ADVANCE Head End ........................................................................................................... 12
Station Time-out Features .............................................................................................................................. 12
All Call Paging Utilizing a Merge/Isolate Cabinet ......................................................................................... 13
SmartSeries Dual Page All Call Utilizing ADVANCE Head End .................................................................. 13
Emergency Party Line (EPL) ......................................................................................................................... 14
Paging with Alternate Page Destination Utilizing ADVANCE Head End ..................................................... 14
VLC ........................................................................................................................................................ 15
General ................................................................................................................................................................ 15
Features ............................................................................................................................................................... 15
Installation and Adjustments ............................................................................................................................... 16
Opening the Station ........................................................................................................................................ 16
Installing the VLC PCBA ............................................................................................................................... 16
Audio Alignment ............................................................................................................................................ 16
Page Disable Control ...................................................................................................................................... 16
Remote Output Switching (Available with RTU Only) ................................................................................. 16
Attaching the Front Panel ............................................................................................................................... 16
RTU ........................................................................................................................................................ 17
General ................................................................................................................................................................ 17
Features ............................................................................................................................................................... 17
With SmartSeries PCBA and ADVANCE Head End..................................................................................... 17
With VLC PCBA ............................................................................................................................................ 17
With SmartSeries PCBA and Dual Page All Call with ADVANCE Head End ............................................. 18
Installation .......................................................................................................................................................... 18
Opening the Station ........................................................................................................................................ 18
Installing the RTU PCBA ............................................................................................................................... 18
Field Wiring ................................................................................................................................................... 18
Attaching the Front Panel ............................................................................................................................... 18
Non-supervised Output Wiring Configuration ............................................................................................... 19
Supervised Output Wiring Configurations with SmartSeries Option ............................................................. 19
Input 1 or 2 Wiring Configuration with the SmartSeries Option .................................................................... 20
Standard Station 70V/100V Speaker Output ..................................................................................... 21
General ................................................................................................................................................................ 21
Field Wiring ........................................................................................................................................................ 21
SmartSeries Station 70V/100V Speaker Line Monitor ...................................................................... 22
General ................................................................................................................................................................ 22
Field Wiring ........................................................................................................................................................ 22
RF Hookswitch ...................................................................................................................................... 24
Troubleshooting ............................................................................................................................25
Opening the Station .............................................................................................................................. 25
Front Panel PCBA Jumper Settings & Adjustments......................................................................... 25
P4 Standard Jumper Configuration ..................................................................................................................... 25
Attaching the Front Panel .................................................................................................................... 28
Specifications ................................................................................................................................29
Service and Spare Parts ................................................................................................................31
GAI-Tronics Corporation 400 E. Wyomissing Ave. Mohnton, PA 19540 USA
610-777-1374  800-492-1212  Fax: 610-796-5954
VISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS
Pub. 42004-717L2I
G AI-T RO NICS® CO RPO R AT IO N
A HUBBELL COMPANY
Industrial Communications System
Page/Party® Handset/Speaker
Amplifier Station
Confidentiality Notice
This manual is provided solely as an installation, operation, and maintenance guide, which contains
sensitive business and technical information, that is confidential and proprietary to GAI-Tronics.
GAI-Tronics retains all intellectual property and other rights in or to the information contained herein,
and such information may only be used in connection with the operation of your GAI-Tronics product or
system. This manual may not be disclosed in any form, in whole or in part, directly or indirectly, to any
third party.
General Information
Product Overview
The GAI-Tronics Industrial Communications System
(ICS) Page/Party® is a modular industrial
communications system that can include from two to
possibly hundreds of stations. All stations are wired in
parallel and additional stations can be added to the
system at any time.
The standard configuration of the ICS Page/Party®
station is an indoor, multi-party, handset/speaker
amplifier station using ac power. A number of options
are available to add to station capabilities. See Features
and Options below for more details.
The ICS Page/Party® station is similar to and compatible
with existing GAI-Tronics 700 series Page/Party®
systems. ICS Page/Party® stations can replace or be
added to existing Page/Party® systems.
Figure 1. ICS Station Front Panel with all
options
GAI-Tronics Corporation 400 E. Wyomissing Ave. Mohnton, PA 19540 USA
610-777-1374  800-492-1212  Fax: 610-796-5954
VISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 2 of 31
Features

Provides one-way page announcements over system speakers

Includes a high efficiency (>80%) Class D paging amplifier to provide up to 30 watts of speaker
output

Provides full-duplex party line communication

Includes universal ac power supply with power factor correction

Field upgradeable options

Durable, high visibility safety orange powder coat finish on indoor stations
Options
















Single party line operation
Speaker amplifier only (no handset)
Alternate page destination
Emergency party line (EPL)
Weatherproof and desktop stations
Auxiliary jack for headset operation
Hazardous area approvals
PVC or Hytrel® handset cords in 6-, 15-, or 25-foot lengths
Conformal coating for PCBA
24 V dc power
Volume Level Control (VLC) technology for alternate page volume
SmartSeries technology featuring Ambient Level Sensing (ALS) and available remote monitoring
Remote Terminal Unit (RTU) operation
70V/100V speaker output
All Call
RF Hookswitch
Installation
Important Safety Instructions

Read, follow, and retain instructions – All safety and operating instructions should be read and
followed before operating the unit. Retain instructions for future reference.

Heed warnings – Adhere to all warnings on the unit and in the operating instructions.

Attachments – Attachments not recommended by the product manufacturer should not be used, as
they may cause hazards.

Servicing – Do not attempt to service this unit by yourself. Opening or removing covers may expose
you to dangerous voltage or other hazards. Refer all servicing to qualified service personnel.

This permanently connected apparatus must have a UL Listed 15 amp circuit breaker incorporated in
the electrical installation of the building.
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 3 of 31
USA and Canada Consult the National Electrical Code (NFPA 70), Canadian Standards Association
(CSA 22.1), and local codes for specific requirements regarding your installation. Class 2 circuit wiring
must be performed in accordance with NEC 725.55.
WARNING
In 24 V dc systems: Under NO condition should this equipment be operated
from a battery charger without the batteries connected.
In 24 V dc systems, most chargers have an unloaded output of 35 to 45 volts that can quickly damage the
equipment designed for nominal 24 volts. The maximum battery voltage should never exceed the
maximum specified input voltage.
Mounting the Enclosure
Mount the enclosure using the four 0.312inch (8 mm) diameter holes located on the
mounting flanges with ¼-inch (M6)
hardware. The ICS Page/Party® Station is
not supplied with conduit or cable openings.
Remove the front panel and drill or punch
entry openings in the rear section of the
enclosure. Refer to Figure 2 for the
suggested locations. There must be a
minimum of ½ inch (13 mm) of material
between entry holes.
The station is suitable for top or bottom
entry per Figure 2. However, GAI-Tronics
recommends bottom entry only wherever
possible.
The standard orientation (shown in Figure 2)
locates the power supply housing in the
upper left corner. The orientation of the
enclosure can be rotated 180º to allow clear
access to the top. The Termination PCBA
can then be rotated for correct orientation.
For specific details including mounting hole
dimensions, refer to Figure 2. When
mounting the enclosure, use caution to avoid
damaging the internal components.
The suggested mounting height for all
station enclosures is 48 inches (1219 mm) to
the center of the bottom mounting holes of
the enclosure.
NOTE: In ICS Page/Party® stations with an
installed 70V/100V speaker output option,
bottom wire entry is limited on the bottom
left side of the enclosure. Refer to Figure 2.
Figure 2. Suggested Wire Entry Locations
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 4 of 31
Field Wiring
The ICS Page/Party® Station provides terminal blocks for field wiring. Each connection for the system
cable has two terminals for daisy-chain wiring. Attach #6 spade lugs to the wires before attachment to the
terminal blocks for the most secure connection. Torque the terminal block screws to 8 to 10 lbf⋅in (0.90
to 1.13 N⋅m) when attaching the spade lugs.
The terminal blocks on the Termination PCBA are labeled to coincide with the color code used on GAITronics 60029 series multi-party cable or 60038 series single party cable. Refer to Figure 3 for a sample
wiring diagram.
In certain circumstances where paging audio induces feedback, muting the speakers of two or more
stations during a page, referred to as mutual muting, can eliminate such feedback problems. This function
is enabled by connecting the spare orange wire between stations to terminal block TB4-2 or TB5-2.
Figure 3. Typical Page/Party® ICS Station Wiring Diagram
After all wiring and cable connections have been completed, place the front cover on the rear enclosure,
being careful not to pinch any cables. Secure the front cover using the four screws and washers provided.
Torque the screws to 10 to 12 lbf⋅in (1.13 to 1.36 N⋅m).
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 5 of 31
Speaker Jumper Impedance Configuration
Configure speaker jumpers P15 and P16 for the appropriate impedance for either 8-ohm or 16-ohm
speakers as shown in Figure 4 below.
Figure 4. Speaker Jumper Impedance Configuration Options for 8-ohm or 16-ohm Speakers
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 6 of 31
Settings and Adjustments
Opening the Station
Remove the four screws from the front panel and turn it to the right so that the interior surface faces you.
Allow the wiring and ribbon cables to remain connected. Using two of the screws just removed, mount
the front panel to the back box’s right-side mounting holes. The front panel interior surface and the back
box interior now face you. This configuration presents the easiest access for troubleshooting and setting
adjustments.
Figure 5. ICS Page/Party® Station Interior View and Maintenance Configuration
(AC Version shown)
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 7 of 31
Figure 6. 69557 Series Main PCBA
Jumper Settings
Speaker Mute
The station can mute the speaker amplifier during page operation to eliminate feedback. P11 in the EN
position (default) mutes the speaker during page activation. P11 in the DIS position allows broadcast to
the speaker during paging.
Speaker Gain Setting
P9 can limit the maximum speaker output level. P9 in the HI position (default) represents a 30-watt
maximum output. P9 in the LO position represents a 2-watt maximum output.
WARNING
Maximum output power may exceed rated speaker wattage resulting in speaker
damage.
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 8 of 31
Level Adjustments
Transmit Level
The Transmit Level potentiometer, R34, adjusts the signal level from the handset or optional auxiliary
headset microphone to the page or party lines.
Receiver Volume
The Receiver Volume potentiometer, R5, adjusts the signal level to the handset receiver from the page or
party lines. It does not adjust the signal level to the optional auxiliary headset.
Speaker Volume
The Speaker Volume potentiometer, R91, adjusts the signal level to the speaker from the page line. The
default setting is 4 watts for an 8-ohm speaker and 2 watts for a 16-ohm speaker.
Warning – Maximum output power may exceed rated speaker wattage resulting in speaker damage.
Attach the Front Panel
After all adjustments have been completed, place the front cover on the rear enclosure, being careful not
to pinch any cables. Secure the front cover using the four screws and washers provided. Torque the
screws to 10 to 12 lbfin (1.13 to 1.36 Nm).
Operation
For paging and subsequent party line conversation, the station operator lifts the handset or connects the
optional headset, selects a free party line using the five-position rotary selector switch (if equipped), and
presses the handset pressbar or headset page switch. The station operator pages the desired individual and
designates the party line on which that individual should respond. The individual then responds by
approaching the nearest ICS Page/Party® station, selecting the appropriate party line and lifting the
handset or connecting a headset. Full-duplex communication can then be held on the party line without
broadcasting over the speakers. After the conversation is complete, all parties should place the handset
back on hook or disconnect the headset.
NOTES:
1. For stations with an auxiliary jack, the Model 10401-201 Headset and 10416-103 Extension Cord
allows the user to be hands-free and mobile while maintaining communication. When connected, the
handset microphone is disabled.
2. The ICS Page/Party® station incorporates a noise-canceling microphone to reduce transmitted
ambient noise. This requires the user to place the microphone as close as possible to their mouth.
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 9 of 31
Options
The ICS Page/Party® Station options can be factory installed or field installed in some cases. The field
installable options include ICS SmartSeries, VLC, and RTU.
ICS SmartSeries
General
The 69552 SmartSeries PCBA adds microprocessor control to the ICS Page/Party® station, providing
additional sensor and monitoring capabilities. SmartSeries and VLC PCBAs cannot be installed in the
same station.
Features
When used with or without ADVANCE head-end equipment:
•
•
•
Ambient Level Sensing (ALS) circuitry automatically changes the local speaker’s paging volume in
response to varying background noise
Off-hook timeout prevents noise being introduced to a party line by electronically placing the handset
“on-hook” after 8 minutes
Page timeout limits a single page broadcast to two minutes, freeing the page line for emergencies
When used with ADVANCE head-end equipment:
•
•
Station monitoring of key components (including handset, amplifier and local speaker) provides fast
notification of any faults
Ability to accept supervised contact closure inputs and provide a supervised relay output (requires
RTU option)
Figure 7. 69552 SmartSeries PCBA
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 10 of 31
Installation and Adjustments
Opening the Station
Remove the four screws from the front panel and turn it to the right so that the interior surface faces you.
Allow the wiring and ribbon cables to remain connected. Using two of the screws just removed, mount
the front panel to the back box’s right-side mounting holes. The front panel interior surface and the back
box interior now face you. This configuration presents the easiest access for troubleshooting and setting
adjustments.
Installing the SmartSeries PCBA
Remove power from the station.
Remove all jumpers on the Main PCBA P4 connector.
Align the SmartSeries PCBA with four mounting holes to the right of the Main PCBA with the edge of
the SmartSeries board under the Main PCBA. Secure the SmartSeries PCBA with the four screws
provided.
Install the provided 34-pin ribbon cable from P4 of Main PCBA to P4 of SmartSeries PCBA.
Reapply power to the station.
Setting the Address
For the SmartSeries option to function properly, each station in an ADVANCE system zone must be
given a unique address using the hexadecimal switches, S1 (Hi Address) and S2 (Lo Address). Each
switch contains 16 settings, labeled 0–F. A small arrow on each switch indicates the setting.
The station address is determined by the high address setting followed by the low address setting. For
example, to assign an address of 05, the high station address is set to 0 and the low address is set to 5.
Valid address settings are 05 to FE. Record the address assigned for each station in the system for your
records. If the SmartSeries PCBA is installed in a system without an ADVANCE head end, set the
address to 04 (default).
ALS Minimum Level
The ALS minimum level is the lowest speaker output level that the station will maintain. To set the ALS
minimum level, turn R91 fully counterclockwise. Listen for a single beep from the speaker indicating the
speaker amplifier is in the Minimum Level Adjustment mode. If the page line is in use immediately after
the beep tone, the page signal should be used to make the minimum level adjustment. If the page line is
inactive following the beep tone, a continuous tone is activated to make the minimum level adjustment.
After the tone is activated, all page line activity is ignored until completion of the adjustment.
This test tone is used as a reference to adjust the speaker amplifier output level to the desired volume.
Adjust R91 to the desired output. The test tone automatically shuts off 5 seconds after the last
adjustment. The factory default setting for minimum level is 4.0 watts nominal into an 8-ohm load.
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 11 of 31
ALS Offset Level
The ALS offset level allows the output of the speaker amplifier to maintain a set difference or “offset”
between the ambient noise level and the speaker output level. To set the ALS offset level, turn R91 fully
clockwise and listen for the two beep tones indicating that the station is in the Offset Adjustment mode.
If the page line is in use immediately after the two beep tones are heard, the page signal should be used to
make the offset level adjustment. If the page line is inactive immediately following the beep tones, a
continuous tone is activated to make the offset level adjustment. After the tone is activated, all page line
activity is ignored until completion of the adjustment. Adjust R91 to the desired offset level.
NOTE: This adjustment should be made under maximum ambient noise level. The ALS offset level must
always be set higher than the ALS minimum level setting.
SmartSeries VLC Level
When activated, the VLC overrides the ALS minimum level setting allowing the speaker volume to
change to a preset level during an emergency page. To adjust the VLC Level, force the station into the
VLC mode by having someone execute a page from a station programmed by the MCU to activate the
VLC function. During the page, turn the R91 control fully counterclockwise, and listen for two beep
tones through the page speaker indicating the VLC Adjustment mode has been activated. After the two
beep tones, turn the R91 control to the desired speaker level using the live paging signal to adjust the
level. The station automatically exits the VLC Adjustment mode and reverts to normal operation 5
seconds after the last pot adjustment.
NOTE: The system must be equipped with an ADVANCE head end to activate the VLC function.
Speaker Impedance Supervision
When this feature is configured, the station will supervise the speaker line for changes in the speaker line
impedance. To perform this function the station must be calibrated for the impedance of the speaker(s)
attached. If the station has never been previously calibrated, the station will report a speaker fault within
15 minutes of being configured for this feature. The station may be calibrated either “locally” at the
station or “remotely” by a system command from the ADVANCE head end. See the ADVANCE System
Programming Manual for details of “remote” calibration.
To perform a “local” calibration, first ensure that the station is configured for speaker impedance
supervision. Next, set the station’s address to 0x02. Wait until you hear a single-beep tone at the
attached speaker. This should occur within 20 seconds. This tone indicates that a successful calibration
was performed.
If instead a double-beep tone is heard, this indicates that the station attempted to calibrate but was
unsuccessful (the attached impedance is out-of-range). If a tone is not heard, the station may not be
configured for speaker impedance supervision or there is an open connection to the speaker.
After hearing the single beep tone, set the address back to its original value to resume normal station
operation with the new calibration value.
NOTE: If this feature is used, then jumper P9 of the Main PCBA must be in the HI (default) position.
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 12 of 31
FSK Signal Gain
The FSK Signal Gain, R13, adjusts the FSK transmit signal strength. It is set at the factory and should
not be adjusted by the installer.
Attaching the Front Panel
After all adjustments have been completed, place the front cover on the rear enclosure, being careful not
to pinch any cables. Secure the front cover using the four screws and washers provided. Torque the
screws to 10 to 12 lbfin (1.13 to 1.36 Nm).
Operation
Paging with ADVANCE Head End
Paging and party line operation with the ICS SmartSeries option is similar to standard station operation.
The main differences are that when the handset pressbar or the headset page switch is pressed, a steady
“wait” tone will be heard in the handset/headset earpiece. When the “wait” tone ends, a preannouncement tone, if programmed, will sound, and the operator may place their page. If the system is
busy and the page is denied, the user will hear a busy tone in the handset/headset earpiece.
Paging without ADVANCE Head End
Paging and party line operation will be similar to standard station operation.
Station Time-out Features
The ICS SmartSeries option supports a page duration limit that sets the maximum duration of each page.
If the page is still active when the page duration limit is reached, the page will be terminated. When used
without an ADVANCE head end, the page duration limit is fixed at 2 minutes.
The ICS SmartSeries option supports an off-hook limit that sets the maximum duration that the station
may be kept off hook. If the off-hook limit is reached, the station will be placed electrically on hook. To
reset the timeout condition, the handset must be physically placed on hook momentarily. When used
without an ADVANCE head end, the off-hook limit is fixed at 8 minutes.
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 13 of 31
All Call Paging Utilizing a Merge/Isolate Cabinet
Merge/Isolate (M/I) cabinets contain switching relays that are energized by a control signal from
Page/Party® stations. When energized, the relays merge (connect together) the page lines of multiple
Page/Party® systems. This allows voice pages to be broadcast from all the systems connected to the M/I
cabinet. ICS handset stations with the All Call feature contain a push-button switch on the front panel for
activating an M/I cabinet. Refer to Figure 8.
SmartSeries Dual Page All Call Utilizing ADVANCE Head End
For stations with a Dual Page All Call option, a monitored dual page zone can be utilized for the All Call
push button. This Dual Page All Call option must be software configured in the Central Control cabinet
of a GAI-Tronics ADVANCE system. Refer to Figure 8.
Figure 8. All Call Selector Switch Location
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 14 of 31
Emergency Party Line (EPL)
When connected to an ADVANCE control cabinet, the EPL option enables the ICS SmartSeries Station
to automatically report the following information when the handset is taken off-hook.
•
Zone number
•
Station address
•
Party line (1 or 2)
Paging with Alternate Page Destination Utilizing ADVANCE Head End
For stations with the alternate page destination option, additional programmed page zones can be utilized
with the alternate page selector switch. Refer to Figure 9. These alternate page destinations must be
software configured in the central control cabinet of a GAI-Tronics ADVANCE system.
Figure 9. Alternate Page Selector Switch Location
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 15 of 31
VLC
General
The 69553 Volume Level Control (VLC) PCBA adds the capability of remotely controlling the local
speaker volume level. When VLC is activated, a remote device transmits a 50 kHz signal over the page
line. The station detects the 50 kHz signal and switches to an alternate speaker volume setting.
VLC and SmartSeries options cannot be used in the same station.
Features
•
Provides an “alternate” speaker volume setting that is activated by receiving a 50 kHz signal on the
page line.
•
Allows office or crew quarters speakers to be muted until a high priority message or alarm is
broadcast.
•
Prevents local handset paging during emergency situations.
•
Enables outdoor speaker volume to be reduced at night.
•
Adds the ability to provide a relay output (requires RTU option)
Figure 10. 69553 Series VLC PCBA
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 16 of 31
Installation and Adjustments
Opening the Station
Remove the four screws from the front panel and turn it to the right so that the interior surface faces you.
Allow the wiring and ribbon cables to remain connected. Using two of the screws just removed, mount
the front panel to the back box’s right-side mounting holes. The front panel interior surface and the back
box interior now face you. This configuration presents the easiest access for troubleshooting and setting
adjustments.
Installing the VLC PCBA
Remove power from the station.
Remove all jumpers on the Main PCBA P4 connector.
Align the VLC PCBA with four mounting holes to the right of the Main PCBA board. Secure the VLC
PCBA with the four screws provided. Install the provided 34-pin ribbon cable from P4 of Main PCBA to
P4 of VLC PCBA.
Reapply power to the station.
Audio Alignment
To set the normal speaker output level, set DIP switch SW2-1 to the “off” position. Set SW2-2 to the
“on” position to enable a reference test tone. Adjust R91 on the Main PCBA to the desired audio level.
To mute the audio, turn R91 fully counterclockwise.
NOTE: If LED2 on the VLC PCBA is on, indicating the system VLC tone is present, this adjustment
cannot be made.
To set the VLC controlled speaker output level, set SW2-1 to the “on” position. Set SW2-2 to the “on”
position to enable a reference test tone. Adjust R12 on the VLC PCBA to the desired audio level. To
mute the audio, turn R12 fully counterclockwise.
Set SW2-1 and SW2-2 to the “off” position to return to normal system operation.
Page Disable Control
To disable local paging when the system VLC tone is present, set SW2-3 to the “on” position.
Remote Output Switching (Available with RTU Only)
To activate the RTU relay when the system VLC tone is present, set SW2-4 to the “on” position.
Attaching the Front Panel
After all adjustments have been completed, place the front cover on the rear enclosure, being careful not
to pinch any cables. Secure the front cover using the four screws and washers provided. Torque the
screws to 10 to 12 lbfin (1.13 to 1.36 Nm).
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
Pub. 42004-717L2I
Page 17 of 31
®
ICS Page/Party Handset/Speaker Amplifier Station
RTU
General
The 69627 Remote Terminal Unit (RTU) PCBA adds remotely controlled dry relay contacts to an ICS
Page/Party® station equipped with either a VLC PCBA or a SmartSeries PCBA in conjunction with an
ADVANCE head end. When used with the SmartSeries PCBA in conjunction with ADVANCE head
end, two supervised inputs are also available.
The 69628 RTU and Smart 70V/100V Speaker Line Monitor PCBA adds a single remotely controlled dry
relay contact or a single supervised input to an ICS Page/Party® station equipped with a SmartSeries
PCBA in conjunction with an ADVANCE head end.
Figure 11. 69627 Series RTU PCBA
Figure 12. 69628 Series RTU & SmartSeries
70V/100V Speaker Line Monitor PCBA
Features
With SmartSeries PCBA and ADVANCE Head End
•
Two dry-contact input circuits (input cable supervision is optional) for 69627 Series RTU PCBA
•
One dry-contact input circuit (input cable supervision is optional) for 69628 Series RTU &
SmartSeries 70V/100V Speaker Line Monitor PCBA
•
Input status is monitored to trigger action in the ADVANCE head end.
•
Double pole, Form “C” relay contact (output cable supervision is available).
•
One fuse-protected relay contact.
With VLC PCBA
•
Double-pole, Form “C” relay contacts.
•
One fuse-protected relay contact.
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 18 of 31
With SmartSeries PCBA and Dual Page All Call with ADVANCE Head End

One dry-contact input circuit.

Input status is monitored to trigger action in the ADVANCE head end.

Double pole, Form “C” relay contact (output cable supervision is available).

One fuse-protected relay contact.
Installation
Opening the Station
Remove the four screws from the front panel and turn it to the right so that the interior surface faces you.
Allow the wiring and ribbon cables to remain connected. Using two of the screws just removed, mount
the front panel to the back box’s right-side mounting holes. The front panel interior surface and the back
box interior now face you. This configuration presents the easiest access for troubleshooting and setting
adjustments.
Installing the RTU PCBA
Remove power from the station.
Install the four provided standoffs onto the four studs located adjacent to the power supply.
Align the RTU PCBA with the four standoffs with TB7 oriented toward the Termination PCBA. See
Figure 5. Secure the RTU PCBA with the four screws provided.
Install the provided 6-conductor harness from P5 of the SmartSeries or VLC PCBA to P5 of RTU PCBA.
Reapply power to the station.
Field Wiring
The RTU PCBA provides terminal blocks for field wiring. Attach spade lugs to the wires before
attachment to the terminal blocks for the most secure connection.
OUTPUT 1A and OUTPUT 1B are activated by either the VLC or SmartSeries PCBA. OUTPUT 1B is
fused on the normally open (N. O.) contact with a T1.6 amp fuse.
Attaching the Front Panel
After all adjustments have been completed, place the front cover on the rear enclosure, being careful not
to pinch any cables. Secure the front cover using the four screws and washers provided. Torque the
screws to 10 to 12 lbfin (1.13 to 1.36 Nm).
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 19 of 31
Non-supervised Output Wiring Configuration
Figure 13. Non-supervised Output with the VLC or SmartSeries Option
Supervised Output Wiring Configurations with SmartSeries Option
Figure 14. Supervised Output Wiring with SmartSeries Option
*NOTE 1: Input 1 is used to monitor Output 1 and is not available for other functions.
**NOTE 2: Attention: 20-kilohm, 10-watt supervision resistor
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 20 of 31
Input 1 or 2 Wiring Configuration with the SmartSeries Option
Figure 15. Input 1 or 2 Wiring Configuration with the SmartSeries Option
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
Pub. 42004-717L2I
Page 21 of 31
®
ICS Page/Party Handset/Speaker Amplifier Station
Standard Station 70V/100V Speaker Output
General
The 70V/100V speaker output assembly provides the ability to connect several 70-volt or 100-volt
speakers to a single ICS Page/Party® station. Speakers are wired in parallel to the station. Refer to Figure
16 below and Figure 18 on page 22.
Field Wiring
For 100V speakers, connect wires to the terminal block TB8 - 100V and COM.
For 70V speakers, connect wires to the terminal block TB8 - 70V and COM.
Figure 16. Standard Station 70V/100V Speaker
Output Assembly
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
Figure 17. SmartSeries Station 70V/100V Speaker
Line Monitor Assembly
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 22 of 31
SmartSeries Station 70V/100V Speaker Line Monitor
General
The 70V/100V Speaker Line Monitor assembly provides the ability to connect several 70-volt or 100-volt
speakers to a single ICS SmartSeries Station. Speakers are wired in parallel to the station. When used
with an ADVANCE head-end cabinet, the speaker line can be monitored by looping it back to the ICS
SmartSeries Station. Refer to Figure 17 above and Figure 19 on Page 23.
NOTE: SmartSeries ALS and local speaker monitoring are not available when the 70V/100V
speaker output option is installed and must be disabled for this station in the system configuration.
Field Wiring
For 100V speakers, connect wires to the plug for TB8 - 100V and COM.
For 70V speakers, connect wires to the plug for TB8 - 70V and COM.
NOTE: Use of the 8/16-ohm speaker output or TB1 will affect maximum speaker power output.
Figure 18. 70 V / 100 V Speaker Connections
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Figure 19. 70 V / 100 V Monitored Speaker Connections
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
Pub. 42004-717L2I
Page 23 of 31
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 24 of 31
RF Hookswitch
The RF hookswitch option is available for stations to be located in areas where high magnetic fields
prohibit the use of the stations with the standard Page/Party® reed switch.
Figure 20. RF Hookswitch
The RF Hookswitch PCBA is mounted directly to the Main PCBA with interconnection wiring between
them. When control PCBA’s (SMART or VLC) are installed, the 34-pin control cable daisy-chains
through the RF Hookswitch.
The RF Hookswitch PCBA contains no customer adjustments.
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 25 of 31
Troubleshooting
Opening the Station
Remove the four screws from the front panel and turn it to the right so that the interior surface faces you.
Allow the wiring and ribbon cables to remain connected. Using two of the screws just removed, mount
the front panel to the back box’s right-side mounting holes. The front panel interior surface and the back
box interior now face you. This configuration presents the easiest access for troubleshooting and setting
adjustments.
Front Panel PCBA Jumper Settings & Adjustments
The front panel PCBAs are protected by a universal shield. Most potentiometer adjustments and jumper
settings can be made without removing the shield. Refer to Figure 21 for adjustment locations.
P4 Standard Jumper Configuration
For standard operation, without options, P4 requires jumper installation for proper operation. See Figure
21 for jumper locations.
Figure 21. P4 Jumper Default Settings
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
Pub. 42004-717L2I
Page 26 of 31
®
ICS Page/Party Handset/Speaker Amplifier Station
The following tables are provided to aid qualified service personnel in troubleshooting problems with the
ICS Page/Party® Station.
Table 1. General Troubleshooting
Problem
Station not
functional
Potential Cause


Refer to “Field Wiring” on Page 4 for proper terminations.
Verify incoming supply voltage at TB2 or TB3 on the Termination PCBA.

Verify regulated 24 V dc at P1 of Termination PCBA. Caution! Supply
voltage present at P2.
Excessive hum or
buzz during
station operation.
Inspect the Page/Party® lines for proper line terminations, shorts, and grounds.
Crosstalk occurs
between
Page/Party® lines.


Inspect the Page/Party® lines for proper line terminations, shorts, and
grounds.
Inspect the Page/Party® party line connections for crossing of the cable pairs.
Feedback occurs
during page.



Check location and orientation of speakers in the area.
Refer to “Field Wiring” related to mutual muting on Page 4.
Refer to “Speaker Mute” on Page 7.
Squeal in handset
receiver.


Ensure proper termination on Page/Party® lines.
Ensure system line balance is connected.
Handset
microphone audio
is too low/loud.








Disconnect headset, if connected.
Refer to “Transmit Level” on Page 8.
Check jumper settings or cable connections at P4.
Ensure proper termination on Page/Party® lines.
Check handset connections.
Check proper cable terminations between Termination and Main PCBAs.
Check operation of hookswitch.
Replace handset.
Handset receiver
audio is too
low/loud.






Refer to “Receiver Volume” on Page 8.
Check jumper settings or cable connections at P4.
Ensure proper termination on Page/Party® lines.
Check handset connections.
Check proper cable terminations between Termination and Main PCBAs.
Check operation of hookswitch.

Replace handset.
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
Pub. 42004-717L2I
Page 27 of 31
®
ICS Page/Party Handset/Speaker Amplifier Station
Table 2. Troubleshooting Standard/VLC Configurations
Problem
Speaker volume is
too low/loud.
Potential Cause





Cannot place a
page.





RTU output is not
functional.





RTU input does
not function.
Refer to “Speaker Volume” on Page 8; or for VLC, “Audio Alignment” on
Page 16.
Ensure P15 and P16 are in the correct position for the application.
Ensure the speaker wiring configuration is correct.
Ensure the nominal page line level is correct.
Replace the speaker or driver.
For VLC, refer to “Installing the VLC PCBA”, “Audio Alignment”, and
“Page Disable Control” on Page 16.
Check handset connections.
Check proper cable terminations between Termination and Main PCBAs.
Check jumper settings or cable connection at P4.
Replace handset.
Ensure the VLC PCBA is installed and operational. Refer to “Remote
Output Switching (Available with RTU Only)” on Page 16.
Check fuse F1 on RTU PCBA.
Check the cable connection at P5 on the RTU and VLC PCBA.
Check RTU terminal connections on TB7. Refer to Figure 13.
Check operation of connected device.
Inputs are only available with SmartSeries option.
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
Pub. 42004-717L2I
Page 28 of 31
®
ICS Page/Party Handset/Speaker Amplifier Station
Table 3. Troubleshooting SmartSeries Configurations
Problem
Speaker volume is
too low/loud.
Page/Party®
operation does not
function.
RTU output is not
functional.
RTU input does
not function.
Potential Cause


Refer to the “ALS Minimum Level:, “ALS Offset Level”, and “SmartSeries
VLC Level” sections.
Check cable connection at P4.



Ensure P15 and P16 are in the correct position for the application.
Ensure the speaker wiring configuration is correct.
Ensure the nominal Page line level is correct.

Replace the speaker or driver.




Refer to “Setting the Address” on Page 10.
Check cable connection at P4.
Check proper cable terminations between Termination and Main PCBAs.
Ensure proper termination on Page/Party® lines.





For supervised output, ensure no monitored output faults exist.
Check fuse F1 on RTU PCBA.
Check the cable connection at P5 on the RTU and SmartSeries PCBA.
Check RTU terminal connections on TB6 and TB7. Refer to Figure 13 and
Figure 14.
Check operation of connected device.




For supervised input, ensure no monitored input faults exist.
Check the cable connection at P5 on the RTU and SmartSeries PCBA.
Check RTU terminal connections on TB6. Refer to Figure 15.
Check operation of connected device.
Attaching the Front Panel
After all adjustments have been completed, place the front cover on the rear enclosure, being careful not
to pinch any cables. Secure the front cover using the four screws and washers provided. Torque the
screws to 10 to 12 lbfin (1.13 to 1.36 Nm).
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
Pub. 42004-717L2I
Page 29 of 31
®
ICS Page/Party Handset/Speaker Amplifier Station
Specifications
Power Requirements
AC/DC Input
AC Power Supply
Input voltage ........................................................................... 90 to 264 V ac (operating), 50/60 Hz
Power factor @ nominal 120 V ac .............................................................................................. 0.98
DC Power Supply
Input voltage ............................................................................................................ 24 V dc +/−20%
Current/Power requirements (+/−10%)
Power Consumed
(8-ohm load)
24 V DC
120 V AC
230 V AC
Idle
165 mA/4.0 W
70 mA/8.4 VA
90 mA/20.7 VA
4-watt output (default setting)
460 mA/11.0 W
120 mA/14.4 VA
110 mA/25.3 VA
12-watt output
900 mA/21.6 W
200 mA/24.0 VA
160 mA/36.8 VA
30-watt output
1.95 A/46.8 W
400 mA/48.0 VA
220 mA/50.6 VA
90 V AC
253 V AC
520 mA/46.5 VA
230 mA/61.0 VA
Maximum Current
Consumption (8-ohm load)
30-watt output
19.2 V DC
2.44 A/46.8 W
Handset
Microphone ............................................................................................................Dynamic, noise-canceling
Receiver ..................................................................................................... Dynamic, hearing aid compatible
Cord ............................................................................................................ Retractile, 6-foot extended, PVC
Material ................................................................................................................................................... ABS
External control............................................................................................... Push-to-page handset pressbar
Handset Amplifier
Output level (compression controlled) ...................................................... 1.5 V (RMS) nominal into 33 Ω load
Adjustable 0 to 2.1 V (RMS)
Frequency response................................................................ 250 to 6,500 Hz, +0/−3 dB reference to 1 kHz
Distortion .......................................................................... <1.5% THD @ 1 kHz (below compression level)
Receiver level............................................................................................................... 200 mV (RMS), nominal
Adjustable 150 to 400 mV (RMS)
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
®
ICS Page/Party Handset/Speaker Amplifier Station
Pub. 42004-717L2I
Page 30 of 31
Speaker Amplifier
Maximum output:
8-ohm speaker* ............................................................. 30 W into 8 Ω load with 1.5 V (RMS) input page level
Adjustable to 30 W; default: 4 W @ 8 Ω
16-ohm speaker ........................................................... 15 W into 16 Ω load with 1.5 V (RMS) input page level
Adjustable to 15 W; default: 2 W @ 16 Ω
Frequency response................................................................ 250 to 6,500 Hz, +0/−3 dB reference to 1 kHz
Distortion ........................................................................................................... <1% THD @1 kHz to 24 W
<3% THD @ 1 kHz to 30 W
Input impedance ............................................................................................................................... 50,000 Ω
16 kΩ with SmartSeries option
SmartSeries offset level adjustment range ..................................................................................... 0 to 30 dB
*See Figure 22 on Page 31.
Enclosure Specifications
Construction/finish................................................... 16-gauge cold-rolled steel; safety orange polyurethane
Mounting .................................................................. Wall or column, four 0.31 in (7.8 mm) mounting holes
Termination connections .......................................................................... Screw-type barrier terminal blocks
Dimensions
Enclosure ................................................... 12.0 H × 8.0 W × 5.0 D in (304.8 × 203.2 × 127.0 mm)
Overall ....................................................... 14.5 H × 8.0 W × 8.2 D in (368.3 × 203.2 × 208.3 mm)
External control.......................... Handset hookswitch and party line selector switch on multi-party stations
Shipping weight ...................................................................................................................... 12 lb (5.44 kg)
Net weight ............................................................................................................................... 11 lb (4.99 kg)
VLC Option Specifications
VLC minimum input level ............................................................................................................ 50 mV (RMS)
VLC tolerance .......................................................................................................................... 50 kHz +/−4%
All Call Option Specifications
All Call control output ..................................................................Sink 50 mA maximum to circuit common
pulled up to 24 V dc maximum
RTU Option Specifications
Output Control
Maximum load current ........................................................................................ 8 A OUTPUT1A (unfused)
1.6 A OUTPUT 1B (fused)
Maximum in-rush current ....................................................................................................................... 15 A
Maximum voltage ............................................................................................................................. 250 V ac
RTU Input Control (with SmartSeries Option)
Switch type.................................................... Normally open (N.O.) or normally closed (N.C.) dry contacts
End-of-line termination .......................................................................................... 20 kΩ, or 15 kΩ + 5.1 kΩ
Cable resistance .......................................................................................... 100 Ω maximum loop resistance
Contact closure resistance ...................................................................................................... 1 kΩ maximum
Open fault detection ............................................................................................................................ >65 kΩ
Short fault detection ............................................................................................................................ <200 Ω
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
Pub. 42004-717L2I
Page 31 of 31
®
ICS Page/Party Handset/Speaker Amplifier Station
70V/100V Speaker Output Option Specifications
Maximum output.................................................................................................................................... 24 W
Nominal output voltage......................................................................................................... 70.7 V or 100 V
Environmental
Temperature range (operation and storage) ............................................. −22 ºF to 158 ºF (−30 ºC to 70 ºC)
Humidity ....................................................................................................................... 95% non-condensing
NEMA 12
Approvals
NRTL Listed for USA and Canada ........................................................................................ UL/CSA 60950
CE Mark
Typical Continuous Speaker Output Power Derating
1kHz Sinewave into a 8-ohm Load
30
-30°C
25
25°C
20
Watts
40°C
15
50°C
60°C
10
70°C
5
0
0.1
1
10
100
Minutes
Figure 22. Typical Continuous Speaker Output Power Derating
1 kHz Sine Wave into an 8-ohm Load
Service and Spare Parts
If the equipment requires service or spare parts, contact your Regional Service Center for assistance. If
service is required, a return authorization number (RA#) will be issued. Equipment should be shipped
prepaid to GAI-Tronics with a return authorization number and a purchase order number. If the
equipment is under warranty, repairs or a replacement will be made in accordance with GAI-Tronics’
warranty policy. Please include a written explanation of all defects to assist our technicians in their
troubleshooting efforts. Call 800-492-1212 inside the USA or 610-777-1374 outside the USA for help
with identifying the Regional Service Center closest to you.
p:\standard ioms - current release\42004 instr. manuals\42004-717l2i.docx
08/16
Warranty
Equipment.
GAI-Tronics warrants for a period of one (1) year from the date of shipment, that any
GAI-Tronics equipment supplied hereunder shall be free of defects in material and workmanship, shall
comply with the then-current product specifications and product literature, and if applicable, shall be fit
for the purpose specified in the agreed-upon quotation or proposal document. If (a) Seller’s goods prove
to be defective in workmanship and/or material under normal and proper usage, or unfit for the purpose
specified and agreed upon, and (b) Buyer’s claim is made within the warranty period set forth above,
Buyer may return such goods to GAI-Tronics’ nearest depot repair facility, freight prepaid, at which time
they will be repaired or replaced, at Seller’s option, without charge to Buyer. Repair or replacement shall
be Buyer’s sole and exclusive remedy. The warranty period on any repaired or replacement equipment
shall be the greater of the ninety (90) day repair warranty or one (1) year from the date the original
equipment was shipped. In no event shall GAI-Tronics warranty obligations with respect to equipment
exceed 100% of the total cost of the equipment supplied hereunder. Buyer may also be entitled to the
manufacturer’s warranty on any third-party goods supplied by GAI-Tronics hereunder. The applicability
of any such third-party warranty will be determined by GAI-Tronics.
Services.
Any services GAI-Tronics provides hereunder, whether directly or through subcontractors,
shall be performed in accordance with the standard of care with which such services are normally
provided in the industry. If the services fail to meet the applicable industry standard, GAI-Tronics will
re-perform such services at no cost to buyer to correct said deficiency to Company's satisfaction provided
any and all issues are identified prior to the demobilization of the Contractor’s personnel from the work
site. Re-performance of services shall be Buyer’s sole and exclusive remedy, and in no event shall GAITronics warranty obligations with respect to services exceed 100% of the total cost of the services
provided hereunder.
Warranty Periods.
Every claim by Buyer alleging a defect in the goods and/or services provided
hereunder shall be deemed waived unless such claim is made in writing within the applicable warranty
periods as set forth above. Provided, however, that if the defect complained of is latent and not
discoverable within the above warranty periods, every claim arising on account of such latent defect shall
be deemed waived unless it is made in writing within a reasonable time after such latent defect is or
should have been discovered by Buyer.
Limitations / Exclusions.
The warranties herein shall not apply to, and GAI-Tronics shall not be
responsible for, any damage to the goods or failure of the services supplied hereunder, to the extent
caused by Buyer’s neglect, failure to follow operational and maintenance procedures provided with the
equipment, or the use of technicians not specifically authorized by GAI-Tronics to maintain or service the
equipment. THE WARRANTIES AND REMEDIES CONTAINED HEREIN ARE IN LIEU OF AND
EXCLUDE ALL OTHER WARRANTIES AND REMEDIES, WHETHER EXPRESS OR IMPLIED BY
OPERATION OF LAW OR OTHERWISE, INCLUDING ANY WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
Return Policy
If the equipment requires service, contact your Regional Service Center for a return authorization number
(RA#). Equipment should be shipped prepaid to GAI-Tronics with a return authorization number and a
purchase order number. If the equipment is under warranty, repairs or a replacement will be made in
accordance with the warranty policy set forth above. Please include a written explanation of all defects to
assist our technicians in their troubleshooting efforts.
Call 800-492-1212 (inside the USA) or 610-777-1374 (outside the USA) for help identifying the
Regional Service Center closest to you.
(Rev. 10/06)