Service Manual PTAC PD Series (Electronic Controls) Packaged Terminal Air Conditioners Packaged Terminal Heat Pumps • Standard Unit • Seacoast Protected Unit • Remote Thermostat Unit P2KPD 1-05 TABLE OF CONTENTS Introduction ............................................................................................................................................................ 3 Typical Unit Components ....................................................................................................................................... 3 Unit Identification ................................................................................................................................................... 4 Unit Specifications ................................................................................................................................................. 5 Sequence Of Operation ......................................................................................................................................... 6 Electrical Rating Tables ......................................................................................................................................... 7 Power Cord Information ......................................................................................................................................... 7 Digital Control Operation ....................................................................................................................................... 8 Digital Control Features .................................................................................................................................... 9-10 Remote Thermostat / Low Voltage Control Connections .....................................................................................11 Digital Control User Input Configuration .............................................................................................................. 12 Digital Control Diagnostics and Test Mode ......................................................................................................... 13 Calculating the Approximate CFM ....................................................................................................................... 14 Refrigerant Charging....................................................................................................................................... 14-16 Metering Device ................................................................................................................................................... 17 Reversing Valve Description/Operation .............................................................................................................. 17 Testing the Coil .................................................................................................................................................... 18 Compressor Checks ....................................................................................................................................... 19-21 Capacitors ............................................................................................................................................................ 21 Routine Maintenance ........................................................................................................................................... 22 Troubleshooting Charts...................................................................................................................................23-24 Wiring Diagram - Cooling Without Electric Heat ................................................................................................. 25 Wiring Diagram - Cooling With Electric Heat ...................................................................................................... 26 Wiring Diagram - Heat Pump With Electric Heat ................................................................................................ 27 2 INTRODUCTION This service manual is designed to be used in conjunction with the installation manuals provided with each air conditioning system component. This service manual was written to assist the professional HVAC service technician to quickly and accurately diagnose and repair any malfunctions of this product. This manual, therefore, will deal with all subjects in a general nature. (i.e. All text will pertain to all models). IMPORTANT: It will be necessary for you to accurately identify the unit you are servicing, so you can be certain of a proper diagnosis and repair. (See Unit Identification.) Typical Unit Components Discharge Air Grille Blower Wheel Indoor Blower Housing Gasket Control Door Condenser Fan Blade Outdoor Grille Condenser Shroud Filters Condenser Coil Return Air Grille Evaporator Coil Front Cover Control Panel Compressor Wall Sleeve Gasket Basepan The information contained in this manual is intended for use by a qualified service technician who is familiar with the safety procedures required in installation and repair, and who is equipped with the proper tools and test instruments. Installation or repairs made by unqualified persons can result in hazards subjecting the unqualified person making such repairs to the risk of injury or electrical shock which can be serious or even fatal not only to them, but also to persons being served by the equipment. If you install or perform service on equipment, you must assume responsibility for any bodily injury or property damage which may result to you or others. Friedrich Air Conditioning Company will not be responsible for any injury or property damage arising from improper installation, service, and/or service procedures. 3 UNIT IDENTIFICATION Model Number Code PD H 07 K 3 S B A Series PD = P Series Digital PTAC Engineering Digit Design Series System X = Accessory E = Cooling with or without electric heat H = Heat Pump with Auxiliary Heat Options S = Standard R = Remote Thermostat C = Seacoast Protection X = Seacoast / Remote Nominal Cooling Capacity 07 = 7000 BTUh 09 = 9000 BTUh 12 = 12000 BTUh 15 = 15000 BTUh Nominal Heater Size (@ 230V or 265V) 0 = No Heater 2 = 2.5KW 3 = 3.4KW 5 = 5.0KW Voltage K = 208/230V - 1Ph. - 60Hz. R = 265V - 1Ph. - 60Hz. PTAC Serial Number Identification Guide Serial Number Decade Manufactured L=0 C=3 F=6 A=1 D=4 G=7 B=2 E=5 H=8 Year Manufactured A=1 D=4 G=7 B=2 E=5 H=8 C=3 F=6 J=9 L J=9 K=0 Month Manufactured A=Jan D=Apr G=Jul K=Oct B=Feb E=May H=Aug L=Nov C=Mar F=Jun J=Sep M=Dec 4 E A P 00000 Production Run Number PRODUCT LINE R=RAC P=PTAC E=EAC V=VPAK H=Split SPECIFICATIONS GENERAL INFORMATION – PDE SERIES Model PDE07K PDE07R PDE09K PDE09R PDE12K PDE12R PDE15K PDE15R POWER VOLTAGE (1 PHASE, 60 Hz) 230/208 265 230/208 265 230/208 265 230/208 265 VOLT RANGE 253-198 292-239 253-198 292-239 253-198 292-239 253-198 292-239 POWER (WATTS) 615/598 615 800/783 800 1091/1073 1091 1579/1578 1579 CURRENT (AMPS) 3 3 3.9 3.9 5.1 5.1 6.6 6.6 POWER FACTOR 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 AMPS L.R. 18 18 22.2 22.2 26.3 26.3 38 38 AMPS F.L. 3 3 3.9 3.9 5.1 5.1 6.8 6.8 1/15. 1/15. 1/12. 1/12. 1/10. 1/10. 1/10. 1/10. 27 27 30 30 28 28 28 28 7500/7300 7500 9200/9000 9200 12000/11800 12000 15000/14800 15000 INDOOR CFM 250 250 300 300 325 325 350 350 SENSIBLE HEAT RATIO 0.79 0.79 0.76 0.76 0.76 0.76 0.75 0.75 60 60 60 60 70 70 70 70 PDH07K PDH07R PDH09K PDH09R PDH12K PDH12R PDH15K PDH15R VOLTAGE (1 PHASE, 60 Hz) 230/208 265 230/208 265 230/208 265 230/208 265 VOLT RANGE 253-198 292-239 253-198 292-239 253-198 292-239 253-198 292-239 POWER (WATTS) 590/574 590 791/774 791 1121/1023 1121 1581/1559 1559 HORSEPOWER R-22 CHARGE (OZ) PERFORMANCE COOLING BTUh VENT CFM GENERAL INFORMATION – PDH SERIES Model POWER CURRENT (AMPS) 3 3 3.9 3.9 5.1 5.1 6.6 6.6 POWER FACTOR 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 AMPS L.R. 18 18 22.2 22.2 26.3 26.3 38 38 AMPS F.L. 3 3 3.9 3.9 5.1 5.1 6.8 6.8 1/15. 1/15. 1/12. 1/12. 1/10. 1/10. 1/10. 1/10. 27 27 32 32 34.5 34.5 33 33 COOLING BTUh 7200/7000 7000 9100/8900 9100 12000/11800 12000 14700/14500 14700 REVERSE HEATING BTUh HORSEPOWER R-22 CHARGE (OZ) PERFORMANCE 6400/6200 6400 8100/7900 8100 10800/10600 10800 13500/13300 13500 INDOOR CFM 250 250 300 300 325 325 350 350 SENSIBLE HEAT RATIO 0.79 0.79 0.76 0.76 0.76 0.76 0.75 0.75 60 60 60 60 70 70 70 70 VENT CFM 5 SEQUENCE OF OPERATION A good understanding of the basic operation of the refrigeration system is essential for the service technician. Without this understanding, accurate troubleshooting of refrigeration system problems will be more difficult and time consuming, if not (in some cases) entirely impossible. The refrigeration system uses four basic principles (laws) in its operation they are as follows: 1. "Heat always flows from a warmer body to a cooler body." 2. "Heat must be added to or removed from a substance before a change in state can occur" 3. "Flow is always from a higher pressure area to a lower pressure area." 4. "The temperature at which a liquid or gas changes state is dependent upon the pressure." The refrigeration cycle begins at the compressor. Starting the compressor creates a low pressure in the suction line which draws refrigerant gas (vapor) into the compressor. The compressor then "compresses" this refrigerant, raising its pressure and its (heat intensity) temperature. The refrigerant leaves the compressor through the discharge Line as a hot High pressure gas (vapor). The refrigerant enters the condenser coil where it gives up some of its heat. The condenser fan moving air across the coil's finned surface facilitates the transfer of heat from the refrigerant to the relatively cooler outdoor air. When a sufficient quantity of heat has been removed from the refrigerant gas (vapor), the refrigerant will "condense" (i.e. change to a liquid). Once the refrigerant has been condensed (changed) to a liquid it is cooled even further by the air that continues to flow across the condenser coil. The PTAC design determines at exactly what point (in the condenser) the change of state (i.e. gas to a liquid) takes place. In all cases, however, the refrigerant must be totally condensed (changed) to a Liquid before leaving the condenser coil. Suction Line Evaporator Coil The refrigerant leaves the condenser Coil through the liquid line as a warm high pressure liquid. It next will pass through the refrigerant drier (if so equipped). It is the function of the drier to trap any moisture present in the system, contaminants, and large particulate matter. The liquid refrigerant next enters the metering device. The metering device is a capillary tube. The purpose of the metering device is to "meter" (i.e. control or measure) the quantity of refrigerant entering the evaporator coil. In the case of the capillary tube this is accomplished (by design) through size (and length) of device, and the pressure difference present across the device. Since the evaporator coil is under a lower pressure (due to the suction created by the compressor) than the liquid line, the liquid refrigerant leaves the metering device entering the evaporator coil. As it enters the evaporator coil, the larger area and lower pressure allows the refrigerant to expand and lower its temperature (heat intensity). This expansion is often referred to as "boiling". Since the unit's blower is moving indoor air across the finned surface of the evaporator coil, the expanding refrigerant absorbs some of that heat. This results in a lowering of the indoor air temperature, hence the "cooling" effect. The expansion and absorbing of heat cause the liquid refrigerant to evaporate (i.e. change to a gas). Once the refrigerant has been evaporated (changed to a gas), it is heated even further by the air that continues to flow across the evaporator coil. The particular system design determines at exactly what point (in the evaporator) the change of state (i.e. liquid to a gas) takes place. In all cases, however, the refrigerant must be totally evaporated (changed) to a gas before leaving the evaporator coil. The low pressure (suction) created by the compressor causes the refrigerant to leave the evaporator through the suction line as a cool low pressure vapor. The refrigerant then returns to the compressor, where the cycle is repeated. Discharge Line Condenser Coil Compressor Metering Device Refrigerant Drier Liquid Refrigerant Line Strainer 6 ELECTRICAL RATING TABLES NOTE: Use Copper Conductors ONLY. Wire sizes are per NEC, check local codes for overseas applications. Table 1 250 V Receptacles and Fuse Types AMPS 15 20* 30 WIRE SIZE Use ONLY wiring size recommended for single outlet branch circuit. FUSE/CIRCUIT BREAKER Use ONLY type and size fuse or HACR circuit breaker indicated on unit’s rating plate. Proper current protection to the unit is the responsibility of the owner. NOTE: A time delay fuse is provided with 265V units. GROUNDING Unit MUST be grounded from branch circuit through service cord to unit, or through separate ground wire provided on permanently connected units. Be sure that branch circuit or general purpose outlet is grounded. The field supplied outlet must match plug on service cord and be within reach of service cord. Refer to Table 1 for proper receptacle and fuse type. Do NOT alter the service cord or plug. Do NOT use an extension cord. RECEPTACLE The field supplied outlet must match plug on service cord and be within reach of service cord. Refer to Table 1 for proper receptacle and fuse type. Do NOT alter the service cord or plug. Do NOT use an extension cord. WIRE SIZING Use recommended wire size given in Table 2 and install a single branch circuit. All wiring must comply with local and national codes. NOTE: Use copper conductors only. RECEPTACLE TIME-DELAY TYPE FUSE (or HACR circuit breaker) 15 20 30 HACR – Heating, Air Conditioning, Refrigeration * May be used for 15 Amp applications if fused for 15 Amp NOTE: 265 volt units are hard wired. Table 2 Recommended branch circuit wire sizes* NAMEPLATE / MAXIMUM CIRCUIT BREAKER SIZE AWG WIRE SIZE** 15 20 30 14 12 10 AWG – American Wire Gauge * Single circuit from main box ** Based on copper wire, single insulated conductor at 60°C ELECTRIC SHOCK HAZARD! Turn off electric power before service or installation. All electrical connections and wiring MUST be installed by a qualified electrician and conform to the National Electrical Code and all local codes which have jurisdiction. Failure to do so can result in property damage, personal injury and/or death. POWER CORD INFORMATION (230/208V MODELS ONLY) All Friedrich 230/208V PTAC units are shipped from the factory with a Leakage Current Detection Interrupter (LCDI) equipped power cord. The LCDI device meets the UL and NEC requirements for cord connected air conditioners effective August 2004. To test your power supply cord: 1. Plug power supply cord into a grounded 3 prong outlet. 2. Press RESET. NOTE: The LCDI device is not intended to be used as a switch. Once plugged in the unit will operate normally without the need to reset the LCDI device. If the LCDI device trips and requires resetting the cause of the trip should be identified prior to further use of the PTAC. If the device fails to trip when tested or if the power supply cord is damaged it must be replaced with a new supply cord obtained from the product manufacturer, and must not be repaired. 3. Press TEST (listen for click; Reset button trips and pops out). 4. Press and release RESET (listen for click; Reset button latches and remains in). The power supply cord is ready for operation. 30A LCDI Device 7" 4.1" 15/20A LCDI Device TEST 2" RESET 2" Test Button Reset Button Test Button Reset Button 7 DIGITAL CONTROL OPERATION Temperature Display The Friedrich digital PTAC is shipped from the factory to display the desired room temperature on the LED readout. Digital Control Panel The unit can be configured to display the room temperature by simultaneously pressing the ‘Cool’ and ‘High Fan’ buttons for three seconds the display will show an ‘R’ for one seconds to acknowledge the change. The unit will display the setpoint or buttons are pressed and then whenever the ‘Temp’ switch back to room temperature. To revert back to displaying the setpoint only press the ‘Cool’ and ‘Low Fan’ buttons for three seconds simultaneously, the unit will display an ‘S’ for one seconds to acknowledge the change. ºF vs. ºC Display The unit is factory configured to display all temperatures in degrees Fahrenheit (º F). To switch to degrees Celsius press the ‘Fan Only’ and ‘Low Fan’ buttons simultaneously for three seconds. The display will show a ‘C’ as acknowledgement of the change. To revert back to º F press the ‘Fan Only’ and ‘Low Fan’ buttons simultaneously for three seconds. The display will show an ‘F’ as acknowledgement of the change. Cooling Mode Pressing the ‘Cool’ button while the unit is in any mode, including off, will put the unit into cooling mode. Adjust the temperature readout to the desired room temperature and the unit will cycle the compressor on and off to maintain a comfortable room. The compressor will come on anytime that the room temperature is 1.8°F above the desired temperature. The fan operation is dependent on the fan mode selected, either continuous or cycling. See page 16 for fan cycle control. Heating Mode Pressing the ‘Heat’ button while the unit is in any mode, including off, will put the unit into heating mode. Heat Pump Models (PDH) When the ‘Heat’ button is pressed initially the unit will energize the electric resistance heat to quickly bring the room to the set temperature. When the desired room temperature falls 1.8°F below the desired set temperature the unit will cycle the compressor on and operate as a heat pump to maintain the room temperature while running more efficiently than resistance heat only models. If the room temperature should fall more than 5°F from the set temperature the unit will run the resistance heater. The fan operation is dependent on the fan mode selected, either continuous or cycling. Dip switch 5 controls the fan mode, see page 16 for setting. When the outdoor coil temperature falls below 30°F for more than 2 minutes the unit will operate the resistance heaters 8 and not the compressor. When the outdoor coil temperature reaches 45°F the compressor will be allowed to operate again. Heat/Cool Models (PDE) After pressing the ‘Heat’ button, adjust the temperature readout to the desired room temperature and the unit will cycle the resistance heat on and off to maintain a comfortable room. The heater will come on anytime that the room temperature is 1.8°F below the desired temperature. The fan operation is dependent on the fan mode selected, either continuous or cycling. Dip switch 5 controls the fan mode, see page 16 for setting. Emergency Heat Operation In the event of a compressor failure in heat pump mode the compressor may be locked out to provide heat through the resistance heater. This feature ensures that even in the unlikely event of a compressor failure the room temperature can be maintained until the compressor can be serviced. Dip switch 7 controls the emergency heat setting, see page 16. Fan Mode Fan Only Pressing the ‘Fan Only’ button will run the fan to allow for air circulation in the room without operating the compressor or heater regardless of the room or set temperature. The fan speed selection is made by pressing either the ‘High Fan’ or ‘Low Fan’ button. Cycle/Continuous The owner may choose between fan cycling or fan continuous mode based on property preference. (Note: Even heat monitoring and quiet start/stop fan delay only operate in fan cycle mode) Fan continuous mode is used to keep constant airflow circulation in the room during all times the unit is ‘ON’. Fan cycle will conserve energy by only operating the fan while the compressor or electric heater is operating. Dip switch 5 controls the fan mode, see page 16 for setting. FRIEDRICH DIGITAL CONTROL FEATURES The new Friedrich digital PTAC has state of the art features to improve guest comfort, indoor air quality and conserve energy. Through the use of specifically designed control software for the PTAC industry Friedrich has accomplished what other Manufacturer’s have only attempted – a quiet, dependable, affordable and easy to use PTAC. Below is a list of standard features on every Friedrich PTAC and their benefit to the owner. Digital Temperature Readout By digitally monitoring desired room temperature the room is controlled more precisely than conventional systems. The large, easy to read LED display can show either set-point or actual room temperature as selected by owner. One-Touch Operation When the unit is powered off the unit can be returned directly to heating or cooling mode by pressing the ‘Heat’ or ‘Cool’ buttons without the confusing power up sequence of some controls. One-touch control takes guesswork out of unit control delivering a more enjoyable experience and eliminating front-desk calls. Individual Mode and Fan Control Buttons By having separate control buttons and indicators for both fan and mode settings the Friedrich digital control eliminates the confusion of previous digital PTACs. The accurate temperature setting provides greater guest comfort than other systems. Quiet Start/Stop Fan Delay The fan start and stop delays prevent abrupt changes in room acoustics due to the compressor energizing or stopping immediately. Upon call for cooling or heating the unit fan will run for five seconds prior to energizing the compressor. Also, the fan off delay allows for “free cooling” by utilizing the already cool indoor coil to its maximum capacity by running for 30 seconds after the compressor. Remote Thermostat Operation Some applications require the use of a wall mounted thermostat. All new Friedrich PTACs may be switched from unit control to remote thermostat control easily without the need to order a special model or accessory kit. Wireless Remote Control Ready Guests can adjust the temperature and mode of the unit through the use of an optional hand held wireless remote, improving guest comfort and relaxation. Internal Diagnostic Program The new Friedrich digital PTAC features a self diagnostic program that can alert maintenance to component failures or operating problems. The internal diagnostic program saves properties valuable time when diagnosing running problems. Service Error Code Storage The self diagnosis program will also store error codes in memory if certain conditions occur and correct themselves such as extreme high or low operating conditions or activation of the room freeze protection feature. Storing error codes can help properties determine if the unit faced obscure conditions or if an error occurred and corrected itself. Constant Comfort Room Monitoring The on-board processor monitors time between demand cycles (heat or cool) and will cycle the fan every 9 minutes to sample the room condition and determine if the desired conditions are met. This allows the room to have similar benefits to a remote mounted stat without the complication or cost of a wall mounted thermostat. Electronic Temperature Limiting By limiting the operating range the property can save energy by eliminating “max cool” or “max heat” situations common with older uncontrolled systems. The new electronic control allows owners to set operating ranges for both heating and cooling independently of one another. Room Freeze Protection When the PTAC senses that the indoor room temperature has fallen to 40°F the unit will cycle on high fan and the electric strip heat to raise the room temperature to 46°F then cycle off again. This feature works regardless of the mode selected and can be turned off. The control will also store the Room Freeze cycle in the service code memory for retrieval at a later date. This feature ensures that unoccupied rooms do not reach freezing levels where damage can occur to plumbing and fixtures. Random Compressor Restart Multiple compressors starting at once can often cause electrical overloads and premature unit failure. The random restart delay eliminates multiple units from starting at once following a power outage or initial power up. The compressor delay will range from 180 to 240 seconds. Digital Defrost Thermostat The new Friedrich PTAC uses a digital thermostat to accurately monitor the outdoor coil conditions to allow the heat pump to run whenever conditions are correct. Running the PTAC in heat pump mode save energy and reduces operating costs. The digital thermostat allows maximization of heat pump run time. 9 FRIEDRICH DIGITAL CONTROL FEATURES CONTINUED 10 Instant Heat Heat Pump Mode Heat pump models will automatically run the electric heater to quickly bring the room up to temperature when initially energized, then return to heat pump mode. This ensures that the room is brought up to temperature quickly without the usual delay associated with heat pump units. Even Heat Monitoring The digital control monitors indoor conditions to ensure that the room temperature is within five degrees of the setpoint. If necessary the unit will cycle the electric heat to maintain the temperature. This feature ensures guest comfort by delivering the heating benefits of an electric heater while maintaining the efficiency benefits of a heat pump. Fan Cycle Control The owner may choose between fan cycling or fan continuous mode based on property preference. (Note: Even heat monitoring and quiet start/stop fan delay only operate in fan cycle mode) Fan continuous mode is used to keep constant airflow circulation in the room during all times the unit is ‘ON’. Fan cycle will conserve energy by only operating the fan while the compressor or electric heater is operating. Emergency Heat Override In the event of a compressor failure in heat pump mode the compressor may be locked out to provide heat through the resistance heater. This feature ensures that even in the unlikely event of a compressor failure the room temperature can be maintained until the compressor can be serviced. Desk Control Ready All Friedrich digital PTACs have low voltage terminals ready to connect a desk control energy management system. Controlling the unit from a remote location like the front desk can reduce energy usage and requires no additional accessories at the PTAC. Indoor Coil Frost Sensor The frost sensor protects the compressor from damage in the event that airflow is reduced or low outdoor temperatures cause the indoor coil to freeze. When the indoor coil reaches 30°F the compressor is diabled and the fan continues to operate based on demand. Once the coil temperature returns to 45°F the compressor returns to operation. Ultra-Quiet Air System The new Friedrich PD series units feature a indoor fan system design that reduces sound levels without lowering airflow and preventing proper air circulation. High Efficiency The Friedrich PTAC benefits quality components and extensive development to ensure a quiet, efficient and dependable unit. Single Motor Friedrich’s single-motor design allows for enhanced outdoor airflow and simplifies the unit design without the need for redundant components. Rotary Compressor High efficiency rotary compressors are used on all Friedrich PTACs to maximize durability and efficiency. Auxiliary Fan Ready The Friedrich PTAC features a 24V AC terminal for connection to an auxiliary fan that may be used to transfer air to adjoining rooms. Auxiliary fans can provide conditioning to multiple rooms without the requirement of multiple PTAC units. Aluminum Endplates All Friedrich PTACs are built with .04" endplates made from aluminum as opposed to steel. The endplates are typically the most susceptible area for corrosion and aluminum is far more resistant to corrosion than even coated steel. Seacoast Protection Optional Seacoast protection is available to protect the outdoor coil from harsh environments. The Friedrich Seacoast process includes dipping the entire outdoor coil in a 7-step coating process that provides superior protection to only coating the fins of the coil. Top Mounted Antimicrobial Air Filters All Friedrich PTAC return air filters feature an anti-microbial element that has proven to prevent mold and bacterial growth in laboratory testing. PDXFT replacement filter kits feature the same anti-microbial agent. All filters are washable and reusable and are easily accessed from the top of the unit without the removal of the front cover. Filtered Fresh Air Intake Friedrich PTAC units are capable of introducing up to 70 CFM of outside air into the conditioned space. The outdoor air passes through a washable mesh filter to prevent debris from entering the airstream. REMOTE THERMOSTAT AND LOW VOLTAGE CONTROL CONNECTIONS Room Thermostats Location Room thermostats are available from several different manufacturers in a wide variety of styles. They range from the very simple Bimetallic type to the complex electronic setback type. In all cases, no matter how simple or complex, they are simply a switch (or series of switches) designed to turn equipment (or components) "ON" or "OFF" at the desired conditions. The thermostat should not be mounted where it may be affected by drafts, discharge air from registers (hot or cold), or heat radiated from the sun or appliances. An improperly operating, or poorly located room thermostat can be the source of perceived equipment problems. A careful check of the thermostat and wiring must be made then to insure that it is not the source of problems. Mercury bulb type thermostats MUST be level to control temperature accurately to the desired set-point. Electronic digital type thermostats SHOULD be level for aesthetics. Remote Thermostat All Friedrich PD model PTAC units are factory configured to be controlled by either the chassis mounted Smart Center or a 24V single stage remote wall mounted thermostat. The thermostat may be auto or manual changeover as long as the control configuration matches that of the PTAC unit. The thermostat should be located about 5 Ft. above the floor in an area of average temperature, with good air circulation. Close proximity to the return air grille is the best choice. Thermostat Location To control the unit with a wall mounted thermostat follow the steps below: 1) With the front cover removed locate the low voltage terminal strip at the lower portion of the Smart Center. 2) Remove the jumper between the ‘GL’ and GH’ terminals. 3) The control is now configured for control by a wall thermostat. The Smart Center will no longer control the unit. 4) If desired the accessory escutcheon kit (PDXRT) is to be used, install it over the existing control panel. Note: To revert back to the Smart Center control of the unit replace the jumper wire between the ‘GL’ and ‘GH’ terminals that was removed in step 1. Thermostat Connections C W Y R GL GH B = = = = = = = Common Ground Call for Heating Call for Cooling 24V Power from Unit Call for Low Fan Call for High Fan Reversing Valve Energized in heating mode (PDH Models Only) *If only one G terminal is present on thermostat connect to GL for low fan or to GH for high fan operation. 11 DIGITAL CONTROL USER INPUT CONFIGURATION The adjustable control dip switches are located at the lower left hand portion of the digital Smart Center. The inputs are only visible and accessible with the front cover removed from the PTAC. Dip Switch Setting 1) Electronic Temperature Limiting – Switches 1-4 The digital control is set from the factory to allow a temperature range between 60°F and 90°F in both heating and cooling mode. Dip Switches 1-4 can be used to set high and low limits for either heating or cooling or both. From the factory all four switches are in the up ‘ON’ position. The charts to the right show the available electronic limiting ranges. 2) Fan Cycle Control – Switch 5 All PTACs are shipped from the factory with Dip Switch 5 in the ‘OFF’ position to cycle the fan only when there is a demand for the compressor or heater. As an option the fan may be set to ‘continuous’ mode by switching Dip Switch 5 to ‘ON’ position to run the fan continuously while the unit is powered on. To ensure that the room temperature is maintained evenly while in fan cycle mode the Even Temp Load Anticipation feature is enabled. Quiet Fan Delay is also enabled in fan cycle mode to lessen the acoustical change between compressor start up and shut off by running the fan for 5 seconds before each demand cycle, and 30 seconds after cooling or 15 seconds after heating cycles. Heating Range Switches 1 & 2 Temperature Range Low 60 60 60 60 High 90 87 84 81 Dip Switch 1 On Off Off On 2 On On Off Off Cooling Range Switches 3 & 4 Temperature Range Low 60 63 66 69 High 90 90 90 90 Dip Switch 3 On On Off Off 4 On Off Off On Factory Dip Switch Configuration 3) Room Freeze Protection – Switch 6 Units are shipped from the factory with the room freeze protection disabled. Room Freeze Protection can be switched on at the owner’s preference by moving Dip Switch 6 to ‘ON’. This feature will monitor the indoor room conditions and in the event that the room falls below 40°F the unit will cycle on high fan with the electric heater. This occurs regardless of mode. 4) Emergency Heat Override – Switch 7 In the unlikely event of a compressor failure a heat pump unit may be switched to operate in only the electric heat mode until repairs can be made. Moving Dip Switch 7 to ‘ON’. Note: PTAC must be disconnected from power supply when making any configuration changes. 12 O 1 2 3 4 5 6 7 8 N DIGITAL CONTROL DIAGNOSTICS AND TEST MODE Diagnostics Test Mode The Friedrich Smart Center continuously monitors the PTAC unit operation and will store service codes if certain conditions are witnessed. In some cases the unit may take action and shut the unit off until conditions are corrected. For service and diagnostic use only, the built-in timers and delays on the PTAC may be bypassed by pressing the ‘Cool’ and ‘Low Fan’ buttons simultaneously for three seconds while in any mode to enter the test mode. TE will be displayed when entering test mode, and DE will be displayed when exiting. The test mode will automatically be exited 30 minutes after entering it or by pressing the ‘Cool’ and ‘Low Fan’ buttons simultaneously for three seconds. To access the error code menu press the ‘Heat’ and ‘High Fan’ buttons simultaneously for three seconds. If error codes are present they will be displayed. If multiple codes exist you can toggle between messages using the temp button. To clear all codes press the temp button for three seconds while in the error code mode. To exit without changing codes press the ‘Low Fan’ button. The chart below lists the possible error codes and their description: ERROR CODE CODE TRANSLATION ACTION TAKEN BY UNIT POSSIBLE CAUSE 01 NOT USED 02 An extreme low voltage condition exists <198V for 230V units and <239V for 265V units. Shut down unit. Display Error code and flash. Once voltage rises to normal level system power is restored. • Inadequate power supply • Defective breaker • Blown fuse 03 Return air thermistor sensor open or short circuit Set return air sensor = 75°F. Alternate flash set point and error code. Leave unit running. • Defective sensor 04 Indoor coil thermistor sensor open Or short circuit Set ID coil temp = 40°F. Alternate flash set point and error code. Leave unit running. • Defective sensor 05 Outdoor coil thermistor sensor open Or short circuit Set OD coil temp = 20°F. Alternate flash set point and error code. Automatically change over to Electric heat Mode only. Leave unit running. • Defective sensor 06 If O.D. coil Temperature > 175 Deg F for 2 consecutive minutes. (Heat Pump models only) Alternate flash set point and error code. Shut unit down for 5 minutes, then try again 2 times, if fails the 3rd time, then shut down unit. 07 NONE • • • • Dirty coil Fan motor failure Restricted air flow Non-condensables in refrigeration system I.D coil temperature <30 Deg F for 2 consecutive minutes. Alternate flash set point and error code. Continue fan operation while the compressor is locked out until the indoor coil thermistor reaches 45° F, and then energize the compressor. However, compressor must still wait a lockout time of 180 to 240 seconds. • • • • • • Dirty filters Dirty coil Fan motor failure Restricted airflow Improper refrigerant charge Restriction in refrigerant circuit 08 If unit cycles (Heat or Cool demand)> 9 times per hour Alternate flash set point and error code. Keep unit running. • Unit oversized • Low load conditions 09 If unit cycles (Heat or Cool demand)< 3 times per hour Alternate flash set point and error code. Keep unit running. • Unit undersized • High load conditions 10 Room Freeze Protection triggered Alternate flash set point and error code. Keep unit running. • Room temperature fell below 40°F 13 CALCULATING THE APPROXIMATE CFM The approximate CFM actually being delivered can be calculated by using the following formula: EXAMPLE: Measured voltage to unit (heaters) is 230 volts. Measured Current Draw of strip heaters is 11.0 amps. 230 x 11.0 = 2530 2530/1000 = 2.53 Kilowatts 2.53 x 3413 = 8635 KILOWATTS x 3413 Temp. Rise x 1.08 DO NOT simply use the Kilowatt Rating of the heater (i.e. 2.5, 3.4, 5.0) as this will result in a less-than-correct airflow calculation. Kilowatts may be calculated by multiplying the measured voltage to the unit (heater) times the measured current draw of all heaters (ONLY) in operation to obtain watts. Kilowatts are then obtained by dividing by 1000. Supply Air Return Air Temperature Rise 95°F 75°F 20° 20 x 1.08 = 21.6 = CFM 8635 = 400 CFM 21.6 REFRIGERANT CHARGING NOTE: Because The Ptac System Is A Sealed System, Service Process Tubes Will Have To Be Installed. First Install A Line Tap And Remove Refrigerant From System. Make Necessary Sealed System Repairs And Vacuum System. Crimp Process Tube Line And Solder End Shut. Do Not Leave A Service Valve In The Sealed System. Proper refrigerant charge is essential to proper unit operation. Operating a unit with an improper refrigerant charge will result in reduced performance (capacity) and/or efficiency. Accordingly, the use of proper charging methods during servicing will insure that the unit is functioning as designed and that its compressor will not be damaged. Too much refrigerant (overcharge) in the system is just as bad (if not worse) than not enough refrigerant (undercharge). They both can be the source of certain compressor failures if they remain uncorrected for any period of time. Quite often, other problems (such as low air flow across evaporator, etc.) are misdiagnosed as refrigerant charge problems. The refrigerant circuit diagnosis chart will assist you in properly diagnosing these systems. An overcharged unit will at times return liquid refrigerant (slugging) back to the suction side of the compressor eventually causing a mechanical failure within the compressor. This mechanical failure can manifest itself as valve failure, bearing failure, and/or other mechanical failure. The specific type of failure will be influenced by the amount of liquid being returned, and the length of time the slugging continues. Not enough refrigerant (undercharge) on the other hand, will cause the temperature of the suction gas to increase to the point where it does not provide sufficient cooling for the compressor motor. When this occurs, the motor winding 14 temperature will increase causing the motor to overheat and possibly cycle open the compressor overload protector. Continued overheating of the motor windings and/or cycling of the overload will eventually lead to compressor motor or overload failure. Method Of Charging The acceptable method for charging the PTAC system is the Weighed in Charge Method. The weighed in charge method is applicable to all units. It is the preferred method to use, as it is the most accurate. The weighed in method should always be used whenever a charge is removed from a unit such as for a leak repair, compressor replacement, or when there is no refrigerant charge left in the unit. To charge by this method, requires the following steps: 1. Install a piercing valve to remove refrigerant from the sealed system. (Piercing valve must be removed from the system before recharging.) 2. Recover Refrigerant in accordance with EPA regulations. 3. Install a process tube to sealed system. 4. Make necessary repairs to system. 5. Evacuate system to 300 microns or less. 6. Weigh in refrigerant with the property quantity of R-22 refrigerant. 7. Start unit, and verify performance. 8. Crimp the process tube and solder the end shut. NOTE: In order to access the sealed system it will be necessary to install Schrader type fittings to the process tubes on the discharge and suction of the compressor. Proper recovery refrigerant procedures need to be adhered to as outlined in EPA Regulations. THIS SHOULD ONLY BE ATTEMPTED BY QUALIFIED SERVICE PERSONNEL. Undercharged Refrigerant Systems An undercharged system will result in poor performance (low pressures, etc.) in both the heating and cooling cycle. Whenever you service a unit with an undercharge of refrigerant, always suspect a leak. The leak must be repaired before charging the unit. To check for an undercharged system, turn the unit on, allow the compressor to run long enough to establish working pressures in the system (15 to 20 minutes). During the cooling cycle you can listen carefully at the exit of the metering device into the evaporator; an intermittent hissing and gurgling sound indicates a low refrigerant charge. Intermittent frosting and thawing of the evaporator is another indication of a low charge, however, frosting and thawing can also be caused by insufficient air over the evaporator. Checks for an undercharged system can be made at the compressor . If the compressor seems quieter than normal, it is an indication of a low refrigerant charge. A check of the amperage drawn by the compressor motor should show a lower reading. (Check the Unit Specification.) After the unit has run 10 to 15 minutes, check the gauge pressures. Gauges connected to system with an undercharge will have low head pressures and substantially low suction pressures. Overcharged Refrigerant Systems Compressor amps will be near normal or higher. Noncondensables can also cause these symptoms. To confirm, remove some of the charge, if conditions improve, system may be overcharged. If conditions don’t improve, Noncondensables are indicated. Whenever an overcharged system is indicated, always make sure that the problem is not caused by air flow problems. Improper air flow over the evaporator coil may indicate some of the same symptoms as an overcharged system. An over charge can cause the compressor to fail, since it would be "slugged" with liquid refrigerant. The charge for any system is critical. When the compressor is noisy, suspect an overcharge, when you are sure that the air quantity over the evaporator coil is correct. Icing of the evaporator will not be encountered because the refrigerant will boil later if at all. Gauges connected to system will usually have higher head pressure (depending upon amount of overcharge). Suction pressure should be slightly higher. 15 Restricted Refrigerant System Troubleshooting a restricted refrigerant system can be difficult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions. A partial restriction allows some of the refrigerant to circulate through the system. With a complete restriction there is no circulation of refrigerant in the system. Restricted refrigerant systems display the same symptoms as a "low-charge condition." When the unit is shut off, the gauges may equalize very slowly. Gauges connected to a completely restricted system will run in a deep vacuum. When the unit is shut off, the gauges will not equalize at all. A quick check for either condition begins at the evaporator. With a partial restriction, there may be gurgling sounds at the metering device entrance to the evaporator. The evaporator in a partial restriction could be partially frosted or have an ice ball close to the entrance of the metering device. Frost may continue on the suction line back to the compressor. Often a partial restriction of any type can be found by feel, as there is a temperature difference from one side of the restriction to the other. With a complete restriction, there will be no sound at the metering device entrance. An amperage check of the compressor with a partial restriction may show normal current when compared to the unit specification. With a complete restriction the current drawn may be considerably less than normal, as the compressor is running in a deep vacuum (no load.) Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored there. The following conditions are based primarily on a system in the cooling mode. 16 METERING DEVICE Capillary Tube Systems All units are equipped with capillary tube metering devices. 3. Switch the unit to the heating mode and observe the gauge readings after a few minutes running time. If the system pressure is lower than normal, the heating capillary is restricted. 4. If the operating pressures are lower than normal in both the heating and cooling mode, the cooling capillary is restricted. Checking for restricted capillary tubes. 1. Connect pressure gauges to unit. 2. Start the unit in the cooling mode. If after a few minutes of operation the pressures are normal, the check valve and the cooling capillary are not restricted. REVERSING VALVE DESCRIPTION/OPERATION The Reversing Valve controls the direction of refrigerant flow to the indoor and outdoor coils. It consists of a pressure-operated, main valve and a pilot valve actuated by a solenoid plunger. The solenoid is energized during the heating cycle only. The reversing valves used in the PTAC system is a 2-position, 4-way valve The single tube on one side of the main valve body is the high-pressure inlet to the valve from the compressor. The center tube on the opposite side is connected to the low pressure (suction) side of the system. The other two are connected to the indoor and outdoor coils. Small capillary tubes connect each end of the main valve cylinder to the "A" and "B" ports of the pilot valve. A third capillary is a common return line from these ports to the suction tube on the main valve body. Four-way reversing valves also have a capillary tube from the compressor discharge tube to the pilot valve. The piston assembly in the main valve can only be shifted by the pressure differential between the high and low sides of the system. The pilot section of the valve opens and closes ports for the small capillary tubes to the main valve to cause it to shift. NOTE: System operating pressures must be near normal before valve can shift. DANGER OF BODILY INJURY OR DEATH FROM ELECTRICAL SHOCK The reversing valve solenoid is connected to high voltage. Turn off electrical power before disconnecting or connecting high voltage wiring or servicing valve. 17 TESTING THE COIL 1. Turn off high voltage electrical power to unit. 2. Unplug line voltage lead from reversing valve coil. 3. Check for electrical continuity through the coil. If you do not have continuity replace the coil. 4. Check from each lead of coil to the copper liquid line as it leaves the unit or the ground lug. There should be no continuity between either of the coil leads and ground; if there is, coil is grounded and must be replaced. 5. If coil tests okay, reconnect the electrical leads . 6. Make sure coil has been assembled correctly. Checking the Reversing Valve NOTE: You must have normal operating pressures before the reversing valve can shift. Check for proper refrigerant charge. Sluggish or sticky reversing valves can sometimes be remedied by reversing the valve several time with the airflow restricted to increase system pressure. To raise head pressure during the cooling season the airflow through the outdoor coil can be restricted . During heating the indoor air can be restricted by blocking the return air. Dented or damaged valve body or capillary tubes can prevent the main slide in the valve body from shifting. If you determine this is the problem, replace the reversing valve. After all of the previous inspections and checks have been made and determined correct, then perform the "Touch Test" on the reversing valve. Reversing Valve in Heating Mode Touch Test in Heating/Cooling Cycle The only definite indications that the slide is in the mid-position is if all three tubes on the suction side of the valve are hot after a few minutes of running time. NOTE: A condition other than those illustrated above, and on Page 28, indicate that the reversing valve is not shifting properly. Both tubes shown as hot or cool must be the same corresponding temperature. Procedure For Changing Reversing Valve 1. Install Process Tubes. Recover refrigerant from sealed system. PROPER HANDLING OF RECOVERED REFRIGERANT ACCORDING TO EPA REGULATIONS IS REQUIRED. 2. Remove solenoid coil from reversing valve. If coil is to be reused, protect from heat while changing valve. Never energize the coil when it is removed from the valve as a coil burnout will result. 3. Unbraze all lines from reversing valve. 4. Clean all excess braze from all tubing so that they will slip into fittings on new valve. 5. Remove solenoid coil from new valve. 6. Protect new valve body from heat while brazing with plastic heat sink (ThermoTrap) or wrap valve body with wet rag. 7. 18 Fit all lines into new valve and braze lines into new valve. Make sure that the ends of the lead do not touch the compressor shell since this will cause a short circuit. Determine L.R.V. Start the compressor with the voltmeter attached; then stop the unit. Attempt to restart the compressor within a couple of seconds and immediately read the voltage on the meter. The compressor under these conditions will not start and will usually kick out on overload within a few seconds since the pressures in the system will not have had time to equalize. Voltage should be at or above minimum voltage of 197 VAC, as specified on the rating plate. If less than minimum, check for cause of inadequate power supply; i.e., incorrect wire size, loose electrical connections, etc. Reversing Valve in Cooling Mode 8. Pressurize sealed system with a combination of R-22 and nitrogen and check for leaks, using a suitable leak detector. Recover refrigerant per EPA guidelines. 9. Once the sealed system is leak free, install solenoid coil on new valve and charge the sealed system by weighing in the proper amount and type of refrigerant as shown on rating plate. Crimp the process tubes and solder the ends shut. Do not leave Schrader or piercing valves in the sealed system. DANGER OF BODILY INJURY OR DEATH FROM ELECTRICAL SHOCK When working on high voltage equipment - turn the electrical power off before attaching test leads. Use test leads with alligator type clips - clip to terminals, turn power on, take reading - turn power off before removing leads. Amperage (L.R.A.) Test The running amperage of the compressor is the most important of these readings. A running amperage higher than that indicated in the performance data indicates that a problem exists mechanically or electrically. Single Phase Running and L.R.A. Test NOTE: Consult the specification and performance section for running amperage. The L.R.A. can also be found on the rating plate. Select the proper amperage scale and clamp the meter probe around the wire to the "C" terminal of the compressor. Turn on the unit and read the running amperage on the meter. If the compressor does not start, the reading will indicate the locked rotor amperage (L.R.A.). External Overload The compressor is equipped with an external overload which senses both motor am per age and winding temperature. High motor temperature or amperage heats the overload causing it to open, breaking the common circuit within the compressor. Locked Rotor Voltage (L.R.V.) Test Heat generated within the compressor shell, usually due to recycling of the motor, is slow to dissipate. It may take anywhere from a few minutes to several hours for the overload to reset. Locked rotor voltage (L.R.V.) is the actual voltage available at the compressor under a stalled condition. Checking the External Overload COMPRESSOR CHECKS Single Phase Connections Disconnect power from unit. Using a voltmeter, attach one lead of the meter to the run "R" terminal on the compressor and the other lead to the common "C" terminal of the compressor. Restore power to unit. With power off, remove the leads from com pressor terminals. If the compressor is hot, allow the overload to cool before starting check. Using an ohmmeter, test continuity across the terminals of the external overload. If you do not have continuity; this indicates that the overload is open and must be replaced. 19 Single Phase Resistance Test Remove the leads from the compressor terminals and set the ohmmeter on the lowest scale (R x 1). Touch the leads of the ohmmeter from terminals common to start ("C" to "S"). Next, touch the leads of the ohmmeter from terminals common to run ("C" to "R"). Add values "C" to "S" and "C" to "R" to geth er and check resistance from start to run terminals ("S" to "R"). Resistance "S" to "R" should equal the total of "C" to "S" and "C" to "R." In a single phase PSC compressor motor, the highest value will be from the start to the run connections (“S” to "R"). The next highest resistance is from the start to the common connections ("S" to "C"). The lowest resistance is from the run to common. ("C" to "R") Before replacing a compressor, check to be sure it is defective. Check the complete electrical system to the compressor and compressor internal electrical system, check to be certain that compressor is not out on internal overload. Complete evaluation of the system must be made whenever you suspect the compressor is defective. If the compressor has been operating for some time, a careful examination must be made to determine why the compressor failed. 20 Many compressor failures are caused by the following conditions: 1. Improper air flow over the evaporator. 2. Overcharged refrigerant system causing liquid to be returned to the compressor. 3. Restricted refrigerant system. 4. Lack of lubrication. 5. Liquid refrigerant returning to compressor causing oil to be washed out of bearings. 6. Noncondensables such as air and mois ture in the system. Moisture is extremely destructive to a refrigerant system. Recommended procedure for compressor replacement NOTE: Be sure power source is off, then disconnect all wiring from the compressor. 1. Be certain to perform all necessary electrical and refrigeration tests to be sure the compressor is actually defective before replacing . 2. Recover all refrigerant from the sys tem though the pro cess tubes. PROPER HAN DLING OF RECOVERED REFRIGERANT ACCORDING TO EPA REGULATIONS IS REQUIRED. Do not use gauge manifold for this purpose if there has been a burnout. You will contaminate your manifold and hoses. Use a Schrader valve adapter and copper tubing for burnout failures. 3. After all refrigerant has been recovered, disconnect suction and discharge lines from the compressor and remove compressor. Be certain to have both suction and discharge process tubes open to atmosphere. 4. Carefully pour a small amount of oil from the suction stub of the de fec tive com pres sor into a clean container. 5. Using an acid test kit (one shot or conventional kit), test the oil for acid content according to the instructions with the kit. 6. If any evidence of a burnout is found, no matter how slight, the system will need to be cleaned up following proper procedures. 7. Install the replacement compressor. 8. Pressurize with a combination of R-22 and nitrogen and leak test all connections with an electronic or Halide leak detector. Recover refrigerant and repair any leaks found. 9. Evacuate the system with a good vacuum pump capable of a final vacuum of 300 microns or less. The system should be evacuated through both liquid line and suction line gauge ports. While the unit is being evacuated, seal all openings on the defective compressor. Compressor manufacturers will void warranties on units received not properly sealed. Do not distort the manufacturers tube connections. 10. Recharge the system with the correct amount of refrigerant. The proper refrigerant charge will be found on the unit rating plate. The use of an accurate measuring device, such as a charging cylinder, electronic scales or similar device is necessary. Repeat Step 8 to insure no more leaks are present. CAPACITORS Many motor capacitors are internally fused. Shorting the terminals will blow the fuse, ruining the capacitor. A 20,000 ohm 2 watt resistor can be used to discharge capacitors safely. Remove wires from capacitor and place resistor across terminals. When checking a dual capacitor with a capacitor analyzer or ohmmeter, both sides must be tested. Capacitor Check with Capacitor Analyzer Hazard of shock and electrocution. A capacitor can hold a charge for long periods of time. A service technician who touches these terminals can be injured. Never discharge the capacitor by shorting across the terminals with a screwdriver. The capacitor analyzer will show whether the capacitor is "open" or "shorted." It will tell whether the capacitor is within its microfarads rating and it will show whether the capacitor is operating at the proper power-factor percentage. The instrument will automatically discharge the capacitor when the test switch is released Capacitor Connections The starting winding of a motor can be damaged by a shorted and grounded running capacitor. This damage usually can be avoided by proper connection of the running capacitor terminals. From the supply line on a typical 230 volt circuit, a 115 volt potential exists from the "R" terminal to ground through a possible short in the capacitor. However, from the "S" or start terminal, a much higher potential, possibly as high as 400 volts, exists because of the counter EMF generated in the start winding. Therefore, the possibility of capacitor failure is much greater when the identified terminal is connected to the “S" or start terminal. The identified terminal should always be connected to the supply line, or "R" terminal, never to the "S" terminal. When connected properly, a shorted or grounded running-capacitor will result in a direct short to ground from the "R" terminal and will blow the line fuse. The motor protector will protect the main winding from excessive temperature. 21 ROUTINE MAINTENANCE NOTE: Units are to be inspected and serviced by qualified service personnel only. 1. Clean the unit air intake filter at least every 300 to 350 hours of operation. Clean the filters with a mild detergent in warm water and allow to dry thoroughly before reinstalling. 2. The indoor coil (evaporator coil), the outdoor coil (condenser coil) and base pan should be inspected periodically (yearly or bi-yearly) and cleaned of all debris (lint, dirt, leaves, paper, etc.). Clean the coils and base pan with a soft brush and compressed air or vacuum. If using a pressure washer, be careful not to bend the aluminium fin pack. Use a sweeping up and down motion in the direction of the vertical aluminum fin pack when pressure cleaning coils. Cover all electrical components to protect them from water or spray. Allow the unit to dry thoroughly before reinstalling it in the sleeve. NOTE: Do not use a caustic coil cleaning agent on coils or base pan. Use a biodegradable cleaning agent and degreaser. Inspect the indoor blower housing, evaporator blade, condenser fan blade, and condenser shroud periodically (yearly or bi-yearly) and clean of all debris (lint, dirt, mold, fungus, etc.) Clean the blower housing area and blower wheel with an antibacterial / antifungal cleaner. Use a biodegradable cleaning agent and degreaser on condenser fan and condenser shroud. Use warm or cold water when rinsing these items. Allow all items to dry thoroughly before reinstalling them. 3. Periodically (at least yearly or bi-yearly): inspect all control components, both electrical and mechanical, as well as the power supply. Use proper testing instruments (voltmeter, ohmmeter, ammeter, wattmeter, etc.) to perform electrical tests. Use an air conditioning or refrigeration thermometer to check room, outdoor and coil operating temperatures. Use a sling psychrometer to measure wet bulb temperatures indoors and outdoors. 4. Inspect the surrounding area (inside and outside) to ensure that the units' clearances have not been compromised or altered. 5. Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and debris. Clean both areas with an antibacterial and antifungal cleaner. Rinse both items thoroughly with water and ensure that the drain outlets are operating correctly. Check the sealant around the sleeve and reseal areas as needed. 6. Clean the front cover when needed. Use a mild detergent. Wash and rinse with warm water. Allow it to dry thoroughly before reinstalling it in the chassis. Discharge Air Grille Condenser Fan Blade Blower Wheel Indoor Blower Housing Gasket Control Door Outdoor Grille Condenser Shroud Filters Condenser Coil Return Air Grille Evaporator Coil Front Cover 22 Control Panel Compressor Gasket Basepan Wall Sleeve TROUBLESHOOTING CHART — COOLING REFRIGERANT SYSTEM DIAGNOSIS COOLING Low Suction Pressure High Suction Pressure Low Head Pressure High Head Pressure Low Load Conditions High Load Conditions Low Load Conditions High Load Conditions Low Air Flow Across Indoor Coil High Air Flow Across Indoor Coil Refrigerant System Restriction Low Air Flow Across Outdoor Coil Refrigerant System Restriction Reversing Valve not Fully Seated Reversing Valve not Fully Seated Overcharged Undercharged Overcharged Undercharged in System Noncondendsables (air) Moisture in System Defective Compressor Defective Compressor TROUBLESHOOTING CHART - HEATING REFRIGERANT SYSTEM DIAGNOSIS – HEATING Low Suction Pressure High Suction Pressure Low Head Pressure High Head Pressure Low Airflow Across Outdoor Coil Outdoor Ambient Too High for Operation in Heating Refrigerant System Restriction Outdoor Ambient Too High For Operation In Heating Refrigerant System Restriction Reversing Valve not Fully Seated Reversing Valve not Fully Seated Low Airflow Across Indoor Coil Undercharged Overcharged Undercharged Overcharged Moisture in System Defective Compressor Defective Compressor Non-condensables (air) in System 23 ELECTRICAL TROUBLESHOOTING CHART - HEAT PUMP HEAT PUMP SYSTEM COOLS WHEN HEATING IS DESIRED. Is Line Voltage Present at the Solenoid Valve? NO Is the Selector Switch Set for Heat? YES Is the Solenoid Coil Good? NO YES Reversing Valve Stuck Replace the Reversing Valve 24 Replace the Solenoid Coil WIRING DIAGRAM - COOLING WITHOUT ELECTRIC HEAT 25 WIRING DIAGRAM - COOLING WITH ELECTRIC HEAT 26 WIRING DIAGRAM - HEAT PUMP WITH ELECTRIC HEAT 27 FRIEDRICH AIR CONDITIONING CO. Post Office Box 1540 · San Antonio, Texas 78295-1540 4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212 (210) 357-4400 · FAX (210) 357-4480 www.friedrich.com Printed in the U.S.A. P2KPD 1-05
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement