Operating Instructions - ACS-Control
User manual M3
User
manual
M3
Direct voltage
shunt:
0-60/150/300/1000 mV
Operating Instructions
Direct voltage shunt: 0-60/150/300/1000 mV
DAL-311x3x0S
Direct voltage shunt: 0-60/150/300/1000 mV
Technical features:
Technical features:
• red display of -19999…99999 digits (optional: green, orange or blue display)
• minimal installation depth: 120 mm without plug-in terminal
• red display of -19999…99999 digits (optional: green, orange or blue display)
• min/max memory
• minimal installation depth: 120 mm without plug-in terminal
• 30 parameter driven setpoints
• min/max memory
• optical threshold value indication at threshold value exceedance / undercut
• 30 parameter driven setpoints
• [O]-key for triggering of Hold, Tara
• optical threshold value indication at threshold value exceedance / undercut
• permanent min/max-value recording
• [O]-key for triggering of Hold, Tara
• volume measurement (totaliser)
• permanent min/max-value recording
• arithmetic function
• volume measurement (totaliser)
• zero point slowdown
• arithmetic function
• programming interlock via access code
• zero point slowdown
• protection class IP65 at the front
• programming interlock via access code
• plug-in terminal
• protection class IP65 at the front
• option: digital input
• plug-in terminal
• option: 2 or 4 analog outputs
• option: digital input
• option: 2 or 4 relay outputs or 8 PhotoMos outputs
• option: 2 or 4 analog outputs
• option: interface RS232 or RS485
• option: 2 or 4 relay outputs or 8 PhotoMos outputs
• accessories: PC-based configuration kit PM-TOOL incl. CD and USB-adapter for devices
• option: interfacewithout
RS232keypad
or RS485
and for a simple adjustment of standard devices
• accessories: PC-based configuration kit PM-TOOL incl. CD and USB-adapter for devices
without keypad and for a simple adjustment of standard devices
M3_12GB.pdf update: 14.04.2015
96x48
M3_12GB.pdf update: 14.04.2015
96x48
Order code
Note
1)
sensor supply
only at 0/4...20 mA,
0...10V DC input
DAL-311
2
0
2
3
4
Y
power supply
100-240V AC
10...40V DC galvanic seperated
100-240V AC with sensor supply 24V DC/50mA and digital input 1)
10...40V DC galvanic seperated with sensor supply 24V DC/50mA and digital input
other voltages
3
function input
60 / 150 / 300 / 1000 mV
A
B
C
D
E
Y
function output
0
3
1)
display + 2 relay outputs (changeover)
display + 4 relay outputs
display with analog output 0-10V/4-20mA, switchable
display + 2 relay with analog output 0-10V/4-20mA, switchable
display + 4 relay with analog output 0-10V/4-20mA, switchable
others outputs
standard configuration
S
0
standard, protection IP65
S
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
Contents
1.
Short description
2
2.
Assembly
2
3.
Electrical connection
3
4.
Description of function and operation
4
4.1. Programming software PM-TOOL
5
Setting up the device
6
5.1. Switching on
6
5.2. Standard parameterisation (flat operation level)
6
5.
Value assignment for the control of the signal input
5.3. Programming interlock „RUN“
9
Activation/Deactivation of the programming interlock or change into professional operation level
/ back into flat operation level
5.4. Extended parameterisation (professional operation level)
5.4.1. Signal input parameters „INP“
9
9
Value assignment for the control of the signal input incl. linearisation
5.4.2. General device parameters „FCT“
13
Superior device functions like Hold, Tara, min/max permanent, setpoint function respectively
nominal value function, average determination, brightness control, as well as the control of the
digital input and the keyboard configuration
5.4.3. Safety parameters „COD“
17
Assignment of user and master code for locking or access to certain
parameters like e.g. analog output and alarms, etc.
5.4.4. Serial parameters „ser“
18
Parameter for the definition of the interface
5.4.5. Analog output parameters „Out“ and „OU2“
19
Analog output functions
5.4.6. Relay functions „rel“
22
Parameter for the definition of setpoints
5.4.7. Alarm parameters „AL1…AL4“
24
Acutator and dependcies of the alarms
5.4.8. Totaliser (Volume metering) „tot“
25
Parameters for the calculation of the sum function
6.
Reset to factory settings
27
Reset parameters to delivery state
7.
Alarms / Relay
28
Functional principle of the switching outputs
8.
Interfaces
29
Connection RS232 and RS485
9.
Sensor alignment
30
Functional sequence scheme for sensors with existing adjustable resistor
10.
Technical data
31
11.
Safety advices
33
12.
Error elimination
34
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden
l www.acs-controlsystem.de l [email protected]
1
3
1. Brief description
2. Assembly
1. Brief description
The panel meter instrument DAL-311 is a 5-digit device for direct current signals and a visual
The panel meter instrument M3-12 is a 5-digit device for direct voltage signals and a visual threshold value
threshold value monitoring via the display. The configuration happens via 4 keys at the front or via the
monitoring via the display. The configuration happens via four keys at the front or by the optional PC
optional PC software PM-TOOL. The integrated programming interlock prevents unrequested changes of
software PM-TOOL. The integrated programming interlock prevents unrequested chnages of parameters
parameters and can be unlocked again with an individual code. Optional the following functions are
and can be unlocked again with an individual code. Optional the following functions are available: a digital
available: a supply for the sensor, a digital input for triggering of Hold (Tara), two analog outputs and
input for triggering of Hold (Tara), two analog outputs and interfaces for further evaluating in the unit.
interfaces for further evaluating in the unit.
With help of the optional galvanic isolated setpoints, free adjustable limit values can be controlled and
With
of the master
galvanicdisplay.
isolated setpoints (optional), free adjustable limit values can be controlled and
reported
tohelp
a superior
reported
to
a
superior
master
The electrical connection is done viadisplay.
plug-in terminals on the back side.
The electrical
is done
terminals on the
back side. of the measuring signals, a
Selectable
functionsconnection
like e.g. the
recallvia
of plug-in
the min/max-value,
an averaging
Selectable
functions
like
e.g.
the
recall
of
the
min/max-value,
averaging
of the
measuring
signals,
nominal presetting or setpoint presetting, a direct threshold value an
regulation
during
operation
mode
and a
nominal
presetting
or
setpoint
presetting,
a
direct
threshold
value
regulation
during
operation
mode
and
further measuring setpoints for linearisation, complete the modern device concept.
further measuring setpoints for linearisation, complete the modern device concept.
2. Assembly
Please read the Safety advices on page 33 before installation and keep this user manual for future reference.
M3
48,0
3,0
Se
alin
g
9,0
13
Gap for physical unit
1.
2.
3.
After removing the fixing elements, insert the device.
Check the seal to make sure it fits securely.
Click the fixing elements back into place and tighten the clamping screws by hand. Then use a
screwdriver to tighten them another half a turn.
CAUTION! The torque should not exceed 0.1 Nm!
The dimension symbols can be exchanged before installation via a channel on the side!
2
4
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
3. Electrical connection
3. Electrical connection
Type DAL-311x3x0S
M3-1VR5B.0002.S70BD supply of 100-240 VAC, DC ± 10%
Type
Type DAL-311x3x0S
M3-1VR5B.0002.W70BD supply of 10-40 VDC galv. Isolated, 18-30 VAC
Type
DAL-311x3x0S with digital input and external
voltage source
3
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5
4. Function and operation description
4. Function and operation description
Operation
The operation is divided into three different levels.
Menu level (delivery status)
This level was designed for the standard settings of the device. Only menu items which are sufficent to set
the device into operation are displayed. To get into the professional level, run through the menu level and
parameterise prof under menu item RUN.
Menu group level (complete function volume)
Suited for complex applications as e.g. linkage of alarms, setpoint treatment, totaliser function etc. In this
level function groups which allow an extended parameterisation of the standard settings are availabe. To
leave the menu group level, run through this level and parameterise uloc under menu item RUN.
Parameterisation level:
Parameter deposited in the menu item can here be parameterised. Functions, that can be changed or
adjusted, are always signalised by a flashing of the display. Settings that are made in the parameterisation
level are confirmed with [P] and thus saved. Pressing the [O]-key leads to a break-off of the value input and
to a change into the menu level. All adjustments are saved automatically by the device and changes into
operating mode, if no further key operation is done within the next 10 seconds.
Level
Key
Description
Change to parameterisation level and deposited values.
Menu-level
Keys for up and down navigation in the menu level.
Change into operation mode.
To confirm the changes made at the parameterization level.
Parameterisationlevel
Adjustment of the value / the setting.
Change into menu level or break-off in value input.
Change to menu level.
Menu-group-level
Keys for up and down navigation in the menu group level.
Change into operation mode or back into menu level.
6
4
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
4. Function and operation description
Function chart:
4.1 Parameterisation software PM-TOOL:
Part of the PM-TOOL are the software on CD and an USB-cable with device adapter. The connection
happens via a 4-pole micromatch-plug on the back side of the device, to the PC-side the connection
happens via an USB plug.
System requirements: PC incl. USB interface
Software: Windows XP, Windows VISTA
With this tool the device configuration can be generated, omitted and saved on the PC. The parameters can
be changed via the easy to handle program surface, whereat the operating mode and the possible selection
options can be preset by the program.
5
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
7
5. Setting up the device
5. Setting up the device
5.1. Switching on
Once the installation is complete, start the device by applying the voltage supply. Before, check once again
that all electrical connections are correct.
Starting sequence
For 1 second during the switching-on process, the segment test (8 8 8 8 8) is displayed followed by an
indication of the software type and, after that, also for 1 second the software version. After the starting
sequence, the device switches to operation/display mode.
5.2. Standard parameterisation: (Flat operation level)
To parameterise the display, press the [P]-key in operating mode for 1 second. The display then changes to
the menu level with the first menu item TYPE.
Menu level
Parameterisation level
Selection of the input signal, TYPE:
Default: Su.060
There are several measuring input options: 60, 150, 300 or 1000 mV signals are available as
works calibration (without application of the sensor signal) and SU as sensor calibration (with the
sensor applied). Confirm the selection with [P] and the display switches back to menu level.
Setting the end value of the measuring range, END:
Default: 10000
Set the end value from the smallest to the highest digit with [▲] [▼] and confirm each digit with
[P]. A minus sign can only be parameterized on the highest value digit. After the last digit, the
display switches back to the menu level. If Sens was selected as input option, you can only
select between noca and cal. With noca, only the previously set display value is taken over, and
with cal, the device takes over both the display value and the analogue input value.
Setting the start/offset value of the measuring range, offs:
Default: 0
Enter the start/offset value from the smallest to the highest digit with [▲] [▼] and confirm each
digit with [P]. After the last digit the display switches back to the menu level. If Sens was
selected as input option, you can only select between noca and cal. With noca, only the
previously set display value is taken over, and with cal, the device takes over both the display
value and the analogue input value.
6
8
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
Menu level
Parameterisation level
Setting the decimal point, dot:
Default: 0
The decimal point on the display can be moved with [▲] [▼] and confirmed with [P]. The
display then switches back to the menu level again.
Setting up the display time, SEC:
Default: 1.0
then
The display time is set with [▲] [▼]. The display moves up in increments of 0.1 up to 1 second
and in increments of 1.0 up to 10.0 seconds. Confirm the selection by pressing the [P] button.
The display then switches back to the menu level again.
Selection of analog output, Out.rA:
Default: 4-20
Three output signals are available: 0-10 VDC, 0-20 mA and 4-20 mA, with this function, the
demanded signal is selected.
Setting up the final value of the analog output, Out.En:
Default: 10000
The final value is adjusted from the smallest digit to the highest digit with [▲] [▼] and digit by
digit confirmed with [P]. A minus sign can only be parameterised on the highest digit. After the
last digit, the device changes back into menu level.
Setting up the initial value of the analog output, Out.OF:
Default: 00000
The final value is adjusted from the smallest digit to the highest digit with [▲] [▼] and digit by
digit confirmed with [P]. A minus sign can only be parameterised on the highest digit. After the
last digit, the device changes back into menu level.
Threshold values / Limits, LI-1:
Default: 2000
This value defines the threshold, that activates/deactivates an alarm.
7
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
9
5. Setting up the device
Menu level
Parameterisation level
Hysteresis for limit values, HY-1:
Default: 00000
The delayed reaction of the alarm is the difference to the threshold value, which is defined by
the hysteresis.
Function for threshold value undercut / exceedance, Fu-1:
Default: high
A limit value undercut is selected with Louu (for LOW = lower limit value), a limit value
exceedance with High (for HIGH = higher limit value). If e.g. limit value 1 is on a threshold level
of 100 and allocated with function High, an alarm is activated by reaching of the threshold level.
If the threshold value was allocated to Low, an alarm will be activated by undercutting the
threshold value, as long as the hysteresis is zero.
The same applies to LI-2 !
User code (4-digit number-combination, free available), U.CodE:
Default: 0000
If this code was set (>0000), all parameters are locked for the user, if LOC has been selected
before under menu item run. By pressing [P] for 3 seconds in operation mode, the display
shows COde. The U.Code needs to be entered to get to the reduced number of parameter sets.
The code has to be entered befor each parameterisation, until the A.Code (Master code) unlocks
all parameters again.
Master code (4-digit number-combination, free available), A.CodE:
Default: 1234
All parameters can be unlocked with this code, after LOC has been activated under menu item
run. By pressing [P] for 3 seconds in operation mode, the display shows COde and enables the
user to reach all parameters by entering the A.codE. Under run the parameterisation can be
activated permanently by selecting ULOC or ProF, thus at an anew pushing of [P] in operation
mode, the code needs not to be entered again.
8
10
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
5.3 Programming interlock „RUN“
Menu level
Parameterisation level
Activation / deactivation of the programming lock or completion of the standard
parameterisation with change into menu group level (complete function range), run:
Default: uloc
With the navigation keys [▲] [▼], choose between the deactivated key lock Uloc (works
setting) and the activated key lock Loc, or the change into the menu group level ProF. Confirm
the selection with [P]. After this, the display confirms the settings with "- - - - -", and automatically switches to operating mode. If Loc was selected, the keyboard is locked. To get back
into the menu level, press [P] for 3 seconds in operating mode. Now enter the CODE (works
setting 1 2 3 4) that appears using [▲] [▼] plus [P] to unlock the keyboard. FAIL appears if the
input is wrong. To parameterise further functions ProF needs to be set. The device confirms this
setting with „- - - - -„ and changes automatically in operation mode. By pressing [P] for approx.
3 seconds in operation mode, the first menu group InP is shown in the display and thus confirms
the change into the extended parameterisation. It stays activated as long as ULOC or LOC is
entered in menu group RUN.
5.4. Extended parametrisation (Professional operation level)
5.4.1. Signal input parameters
Menu group level
Menu level
Menu level
Parameterisation level
Selection of the input signal, TYPE:
Default: Su.060
There are several measuring input options: 60, 150, 300 or 1000 mV signals are available as
works calibration (without application of the sensor signal) and SU as sensor calibration (with
the sensor applied). Confirm the selection with [P] and the display switches back to menu level.
9
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
11
5. Setting up the device
Menu level
Parameterisation level
Setting the end value of the measuring range, END:
Default: 10000
Set the end value from the smallest to the highest digit with [▲] [▼] and confirm each digit with
[P]. A minus sign can only be parameterized on the highest value digit. After the last digit, the
display switches back to the menu level. If Sens was selected as input option, you can only
select between noca and cal. With noca, only the previously set display value is taken over, and
with cal, the device takes over both the display value and the analogue input value.
Setting up the start/offset value of the measuring range, offs:
Default: 0
Enter the start/offset value from the smallest to the highest digit with [▲] [▼] and confirm each
digit with [P]. After the last digit the display switches back to the menu level. If Sens was
selected as input option, you can only select between noca and cal. With noca, only the
previously set display value is taken over, and with cal, the device takes over both the display
value and the analogue input value.
Setting the decimal point, dot:
Default: 0
The decimal point on the display can be moved with [▲] [▼] and confirmed with [P]. The
display then switches back to the menu level again.
Setting up the display time, SEC:
Default: 1.0
then
The display time is set with [▲] [▼]. The display moves up in increments of 0.1 up to 1 second
and in increments of 1.0 up to 10.0 seconds. Confirm the selection by pressing the [P] button.
The display then switches back to the menu level again.
Rescaling the measuring input values, EndA:
Default: 10000
With this function, you can rescale the input value of e.g. 55 mV (works setting) without
applying a measuring signal. If sensor calibration has been selected, these parameters are not
available.
12
10
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
Menu level
Parameterisation level
Rescaling the measuring input values, OFFA:
Default: 0
With this function, you can rescale the input value of e.g. 0.5 mV (works setting) without
applying a measuring signal. If sensor calibration has been selected, these parameters are not
available.
Setting up the tare/offset value, tArA:
Default: 0
The given value is added to the linearized value. In this way, the characteristic line can be
shifted by the selected amount.
Setting up the balance point, Adj.pt:
Default: 08000
The balance point for the final value can be chosen from the measuring range by su.xxx with
0…10 V or Sens.A with 0…20 mA in %. The preset 80.000% result from the widespread
detuning of the melt pressure sensors. The ADJ.PT is only used by the sensor alignment SE.CAL.
Setting up the physical unit, UnIt:
Default: no
One can choose between the above shown physical units. It will be displayed on the 5th digit of
the display.
Number of additional setpoints, SPCt:
Default: 00
30 additional setpoints can be defined to the initial- and final value, so linear sensor values are
not linearised. Only activated setpoint parameters are displayed.
Display values for setpoints, dIS.01 … dIS.30:
Under this parameter setpoints are defined according to their value. At the sensor calibration,
like at final value/offset, one is asked at the end if a calibration shall be activated.
11
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
13
5. Setting up the device
Menu level
Parameterisation level
Analog values for setpoints, InP.01 … InP.30:
The setpoints are always set according to the selected input signal. The desired analog values
can be freely parameterised in ascending order.
Device undercut, dI.Und:
Default: -i9999
With this function the device undercut (_ _ _ _ _) can be defined on a definite value. Exception is
input type 4-20 mA, it already shows undercut at a signal <1 mA, so a sensor failure is marked.
Display overflow, dI.OUE:
Default: 99999
_____
With this function the display overflow (
) can be defined on a definite value.
Input variable of process value, SIG.in:
Default: a.meas
With this parameter, the device can be controlled via the analog input signals a.meas = mV or
via the digital signals of the interface M.bus = RS232/RS485 (Modbus protocol). With [P] the
selection is confirmed and the device changes into menu level.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–INP–“.
14
12Eggenfelden l www.acs-controlsystem.de l [email protected]
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307
5. Setting up the device
5.4.2. General device parameters
Menu group level
Menu level
Menu level
Parameterisation level
Display time, DISEC:
Default: 01.0
then
The display is set up with [▲] [▼]. Thereby it switches up to 1 second in increments of 0.1
seconds and up to 10.0 seconds in increments of 1.0. With [P] the selection is confirmed and
the device changes into menu level.
Rounding of display values, round:
Default: 00001
This function is for instable display values, where the display value is changed in
increments of 1, 5, 10 or 50. This does not affect the resolution of the optional outputs. With [P]
the selection is confirmed and the device changes into menu level.
Arithmetic, ArItH:
Default: n0
Root
extraction
Reciprocal
Square
With this function the calculated value, not the measuring value, is shown in the display. With
no, no calculation is deposited. With [P] the selection is confirmed and the device changes into
menu level.
Sliding average determination, AVG:
Default: 1.0
Here, the number of the meterings that need to be averaged is preset. The time of averaging
results of the product of measuring time SEC and the averaged metering AVG. With the selection
of AVG in the menu level DISPL, the result will be shown in the display and evaluated via the
alarms.
13
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
15
5. Setting up the device
Menu level
Parameterisation level
Zero point slowdown, ZErO:
Default: 00
At the zero point slowdown, a value range around the zero point can be preset, so the display
shows a zero. If e.g. a 10 is set, the display would show a zero in the value range from -10 to
+10; below continue with -11 and beyond with +11. The maximum adjustable range of value is
99.
Definite contstant value, const:
Default: 0
The constant value can be evaluated via the alarms or via the analog output, like the current
measurand. The decimal place cannot be changed for this value and is taken over by the
current measurand. Like this a setpoint generator can be realised via the analog output by this
value. Furthermore it can be used for calculating the difference. At this the constant value is
substracted from the current measurand and the difference is evaluated in the alerting or by the
analog output. Thus regulations can be displayed quite easily.
Minimum constant value, con.mi:
Default: -i9999
The minimum constant value is adjusted from the smallest to the highest digit with the
navigation keys [▲] [▼] and confirmed digit per digit with [P]. A minus sign can only be
adjusted on the highest digit. After the last digit the display changes back into menu level.
Maximum constant value, con.ma:
Default: 99999
The maximum constant value is adjusted from the smallest to the highest digit with the
navigation keys [▲] [▼] and confirmed digit per digit with [P]. A minus sign can only be
adjusted on the highest digit. After the last digit the display changes back into menu level.
Display, dISPL:
Default: actua
With this function the current measuring value, min/max value, totaliser value or the processcontrolled Hold-value can be allocated to the display. With [P] the selection is confirmed and
the device changes into menu level.
14
16
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
Menu level
Parameterisation level
Brightness control, Light:
Default: 15
The brightness of the display can be adjusted in 16 levels from 00 = very dark to 15 = very
bright via this parameter or alternatively via the navigation keys from the outside. During the
start of the device the level that is deposited under this parameter will always be used, even
though the brightness has been changed via the navigation keys in the meantime.
Display flashing, FLASH:
Default: no
A display flashing can be added as additional alarm function either to single or to a combination
of off-limit condition. With no, no flashing is allocated.
Assignment (deposit) of key functions, tASt:
Default: no
For the operation mode, special functions can be deposited on the navigation keys [▲] [▼], in
particular this function is made for devices in housing size 48x24mm which do not have a 4th
key ([O]-key). If the min/max-memory was activated with EHtr, all measured min/max-values
are saved during operation and can be recalled via the navigation keys. The values get lost by
restart of the device. If the threshold value correction LI.12 or LI.34 was choosen, the values of the
threshold can be changed during operation without disturbing the operating procedure. With
tArA the device is tared to zero and saved permanently as offset. The device confirms the
correct taring by showing ooooo in the display. Set.tA switches into the offset value and can be
changed via the navigation keys [▲] [▼]. Via totAL the current value of the totaliser can be
displayed for approx.7 seconds, after this the device changes back on the parameterised
display value. If tot.rE is deposited, the totaliser can be set back by pressing of the navigation
keys [▲] [▼], the device acknowledges this with ooooo in the display. The configuration of
EHt.rE deletes the min/max-memory. Under ActuA the measurand is shown for approx. 7
seconds, after this the display returns to the parameterised display value. If AbS.UA (absolute
value) was selected, the display shows the value that has been measured since voltage
connection, without consideration of a previous taring. Via selection L1.1, L1.1-2, li.1-3, l1.1-4, in case
of 8 switching points li.1-5…li.1-8, threshold values can be addressed via the navigation keys;
they can be changed digit per digit or taken over by pushing the [P]-key. The adjustment is
taken over directly, an excisting limit value monitoring and the current measurement will not be
influenced by this. If no is selected, the navigation keys are without any function in the operation
mode.
15
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
17
5. Setting up the device
Menu level
Parameterisation level
Special function [O]-key, tASt.4:
Default: no
…
For the operation mode, special functions can be deposited on the [O]-key. This function is
activated by pressing the key. With tArA the device is set temporarily on a parameterised value.
The device acknowledges the correct taring with oo0oo in the display. Set.tA adds a defined
value on to the currently displayed value. Via totAL the current value of the totaliser can be
displayed for approx. 7 seconds, after this the device switches back on the parameterised
display value. If tot.rE is deposited, the totaliser can be set back by pressing of the navigation
keys [▲] [▼], the device acknowledges this with ooooo in the display. EHt.rE deletes the
min/max-memory. If HOLD has been selected, the moment can be hold constant by pressing the
[O]-key, and is updated by releasing the key. Advice: Hold is activated only, if HOLD was
selected under parameter DISPL. ActuA shows the measuring value for approx. 7 seconds, after
this the device switches back on the parameterised display value. The same goes for AVG, here
the sliding average values will be displayed. At AL-1…AL-4 an output can be set and therewith
e.g. a setpoint adjustment can be done. If no is selected, the [O]-key is without any function in
the operation mode.
Special function digital input, dIG.In:
Default: no
…
In operation mode, the above shown parameter can be laid on the optional digital input, too.
Function description see tASt.4.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–fct–“.
16
18
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
5.4.3. Safety parameters
Menu group level
Menu level
Menu level
Parameterisation level
User code U.Code:
Default: 0000
Via this code reduced sets of parameters can be set free. A change of the U.CodE can be done
via the correct input of the A.CodE (master code).
Master code, A.Code:
Default: 1234
By entering A.CodE the device will be unlocked and all parameters are released.
Release/lock analog output parameter, Out.LE:
Default: all
Analog output parameter can be locked or released for the user:
- En-oF: the initial or final value can be changed in operation mode
- Out.EO: the output signal can be changed from e.g. 0-20 mA to 4-20 mA or 0-10 VDC
- ALL: analog output parameters are released
- no: all analog output parameters are locked
Release/lock alarm parameters, AL.LEU:
Default: all
This parameter describes the user release/user lock of the alarm:
- LIMIt: here only the range of value of the threshold values 1-4 can be changed
- ALrM.L: here the range of value and the alarm trigger can be changed
- ALL: all alarm parameters are released
- no: all alarm parameters are locked
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–COD–“.
17
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
19
5. Setting up the device
5.4.4. Serial parameters
Menu group level
Menu level
Menu level
Parameterisation level
Device address, ADDR:
Default: 001
The device address is adjusted from the smallest to the largest digit with the navigation keys
[▲] [▼] and confirmed digit per digit with [P]. A device address up to max. 250 is available.
Interface data: Baudrate 9600 bit/s, 8 databyte, 1 stopbit, no parity (8n1).
ModBus operating modes, b.mode:
Default: ascii
There are two different types of operating modes: ASCII and rtu. Modbus transfers no binary
cycle, but the ASCII-Code. Thus it is directly readable, however the data throughput is smaller
in comparison to the RTU. Modbus RTU (RTU = Remote Terminal Unit) transfers the data in
binary-coded. This leads to a good data troughput, even though the data cannot be evaluated
directly, as they first need to be transfered into a readable format.
Timeout, tIout:
Default: 000
The monitoring of the data transfer is parameterised in seconds up to max. 100 seconds; there
is no monitoring with an input of 000. The timeout is adjusted from the smallest to the largest
digit with the navigation keys [▲] [▼] and confirmed digit per digit with [P]. After the last digit
the device changes back into menu level.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–SER–“.
18
20
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
5.4.5. Analog output parameters for analog output 1
Menu group level
Menu level
Menu level
Parameterisation level
Selection reference of analog output, OutPt:
Default: actua
The analog output signal can refer to different functions, in detail these are the current
measurand, the min-value, the max-value or the totaliser/sum function. If HoLd is selected, the
signal of the analog output will be kept. It can be continued processing after a deactivation of
Hold. With [P] the selection is confirmed and the device changes into menu level.
Selection analog output, Out.rA:
Default: 4-20
Three output signals are available 0-10 VDC, 0-20 mA and 4-20 mA. Select the desired signal
with this function.
Setting the final value of the analog output, Out.En:
Default: 10000
The final value is adjusted from the smallest to the highest digit with [▲] [▼] and confirmed
digit per digit with [P]. A minus sign can only be parameterised on the highest digit. After the
last digit the device changes back into menu level.
Setting the initial value of the analog output, Out.OF:
Default: 00000
The initial value is adjusted from the smallest to the highest digit with [▲] [▼] and confirmed
digit per digit with [P]. A minus sign can only be parameterised on the highest digit. After the
last digit the device changes back into menu level.
19
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
21
5. Setting up the device
Menu level
Parameterisation level
Overflow behaviour, O.FLoU:
Default: edge
To recognise and evaluate faulty signals, e.g. by a controller, the overflow behaviour of the
analog output can be defined. As overflow can be seen either EdGE, that means the analog
output runs on the set limits e.g. 4 and 20 mA, or to.OFF (input value smaller than initial value,
analog output switches on e.g. 4 mA), to.End (higher than final value, analog output switches on
e.g. 20 mA). If to.MIn or to.MAX is set, the analog output switches on the smallest or highest
possible binary value. This means that values of e.g. 0 mA, 0 VDC or values higher than 20 mA
or 10 VDC can be reached. With [P] the selection is confirmed and the device changes into
menu level.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–out–“.
Analog output parameters for analog output 2
Menu group level
Menu level
Menu level
Parameterisation level
Selection reference of analog output, Ou2Pt:
Default: actua
The analog output signal can refer to different functions, in detail these are the current
measurand, the min-value, the max-value or the totaliser function/sum function. If HoLd is
selected, the signal of the analog output will be kept. It can be continued processing after a
deactivation of Hold. With [P] the selection is confirmed and the device changes into menu
level.
20
22
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
Menu level
Parameterisation level
Selection analog output, Ou2.rA:
Default: 4-20
3 output signals are available 0-10 VDC, 0-20 mA and 4-20 mA. Select the desired signal with
this function.
Setting the final value of the analog output, Ou2.En:
Default: 10000
The final value is adjusted from the smallest to the highest digit with [▲] [▼] and confirmed
digit per digit with [P]. A minus sign can only be parameterised on the highest digit. After the
last digit the device changes back into menu level.
Setting the initial value of the analog output, Ou2.of:
Default: 00000
The initial value is adjusted from the smallest to the highest digit with [▲] [▼] and confirmed
digit per digit with [P]. A minus sign can only be parameterised on the highest digit. After the
last digit the device changes back into menu level.
Overflow behaviour, Ou2.fl:
Default: edge
To recognise and evaluate faulty signals, e.g. by a controller, the overflow behaviour of the
analog output can be defined. As overflow can be seen either EdGE, that means the analog
output runs on the set limits e.g. 4 and 20 mA, or to.OFF (input value smaller than initial value,
analog output switches on e.g. 4 mA), to.End (higher than final value, analog output switches on
e.g. 20 mA). If to.MIn or to.MAX is set, the analog output switches on the smallest or highest
possible binary value. This means that values of e.g. 0 mA, 0 VDC or values higher than 20 mA
or 10 VDC can be reached. With [P] the selection is confirmed and the device changes into
menu level.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–ou2–“.
21
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
23
5. Setting up the device
5.4.6. Relay functions
Menu group level
Menu level
Menu level
Parameterisation level
Alarm relay 1, rEL-1:
Default: al-1
The same applies for relays 2-4
….
….
Each setpoint (optional) can be linked up via 4 alarms (by default). This can either be inserted
at activated alarms Al-1/4 or deactivated alarms Aln1/4. If LOGIC is selected, logical links are
available in the menu level Log-1 and Com-1. Access to these two menu levels is via LOGic, at all
other selected functions, these two parameters are overleaped. Via On/OFF the setpoints can be
activated/deactivated, in this case the output and the setpoint display are set/not set on the
front of the device. With [P] the selection is confirmed and the device changes into menu level.
Logic relay 1, Log-1
Default: or
Here, the switching behaviour of the relay is defined via a logic link, the following schema
describes these functions with inclusion of AL-1 and AL-2:
A1 v A2
As soon as a selected alarm is activated, the relay
operates. Equates to operating current principle.
A1 v A2 = A1 Λ A2
The relay operates only, if no selected alarm is
active. Equates to quiescent current principle.
A1 Λ a2
The relay operates only, if all selected alarms are
active.
A1 Λ A2 = A1 v A2
As soon as a selected alarm is not activated, the
relay operates.
____ _ _
____ _ _
With [P] the selection is confirmed and the device changes into menu level.
Alarms for relay 1, CoM-1:
Default: a.i
….
The allocation of the alarms to relay 1 happens via this parameter, one alarm or a group of
alarms can be chosen. With [P] the selection is confirmed and the device changes into menu
level.
22
24
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
Menu level
Parameterisation level
Alarm relay 5, reL-5:
Default: al-5
The same applies for relays 6-8
….
….
Each setpoint (optional) can be linked up via 4 alarms (by default). This can either be inserted
at activated alarms AL6/8 or deactivated alarms ALN6/8. If LOGIC is selected, logical links are
available in the menu level LoG-1 and CoM-1. Access to these two menu levels is via LOGIC, at all
other selected functions, these two parameters are overleaped. Via On/OFF the setpoints can be
activated/deactivated, in this case the output and the setpoint display are set/not set on the
front of the device. With [P] the selection is confirmed and the device changes into menu level.
Logic relay 5, LoG-5:
Default: or
Here, the switching behaviour of the relay is defined via a logic link, the following schema
describes these functions with inclusion of AL-1 and AL-2:
A1 v A2
As soon as a selected alarm is activated, the relay
operates. Equates to operating current principle.
A1 v A2 = A1 Λ A2
The relay operates only, if no selected alarm is
active. Equates to quiescent current principle.
A1 Λ a2
The relay operates only, if all selected alarms are
active.
A1 Λ A2 = A1 v A2
As soon as a selected alarm is not activated, the
relay operates.
____ _ _
____ _ _
With [P] the selection is confirmed and the device changes into menu level.
Alarms for relay 5, CoM-5:
Default: a.5
….
The allocation of the alarms to relay 5 happens via this parameter, one alarm or a group of
alarms can be chosen. With [P] the selection is confirmed and the device changes into menu
level.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–rel–“.
23
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
25
5. Setting up the device
5.4.7. Alarm parameters
Menu group level
Menu level
Menu level
Parameterisation level
Dependency alarm 1, ALrM.1:
Default: actua
The dependency of alarm 1 can be related to special functions, in detail these are the current
measuring value, the min-value, the max-value or the totaliser/sum-value. If Hold was selected,
then the alarm is hold and processed just after deactivation of HOLD. EHtEr causes the
dependency either by pressing the [O]-key on the front of the housing or by an external signal
via the digital input. With [P] the selection is confirmed and the device changes into menu level.
Threshold values / limit values, LI-1:
Default: 2000
The limit value defines the threshold, that activates/deactivates an alarm.
Hysteresis for threshold values, HY-1:
Default: 00000
The delayed reaction of the alarm is the difference to the threshold value, which is defined by
the hysteresis.
Function for threshold value undercut / exceedance, Fu-1:
Default: high
A limit value undercut is selected with Louu (for LOW = lower limit value), a limit value
exceedance with High (for HIGH = higher limit value). If e.g. limit value 1 is on a threshold level
of 100 and allocated with function High, an alarm is activated by reaching of the threshold level.
If the threshold value was allocated to Low, an alarm will be activated by undercutting the
threshold value, as long as the hysteresis is zero.
26
24
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
Menu level
Parameterisation level
Switching-on delay, ton-1:
Default: 000
For limit value 1 one can preset a delayed switching-on of 0-100 seconds.
Switching-off delay, toF-1:
Default: 000
For limit value 1 one can preset a delayed switching-off of 0-100 seconds.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–Al1–“.
The same applies for Al2 to al8.
5.4.8. Totaliser (Volume metering)
Menu group level
Menu level
Menu level
Parameterisation level
Totaliser state, total:
Default: off
The totaliser makes measurements on a time base of e.g. l/h possible, at this the scaled input
signal is integrated by a time and steadily (select Stead) or temporarily (select temp) saved. If Off
was selected, the function is deactivated. With [P] the selection is confirmed and the device
changes into menu level.
25
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
27
5. Setting up the device
Menu level
Parameterisation level
Time base, t.base:
Default: sec
Under this parameter the time base of the measurement can be preset in seconds, minutes or
hours.
Totaliser factor, Facto:
Default: 10Π0
…
At this the factor (100…106) respectively the divisor for the internal calculation of the measuring
value is assigned.
Setting up the decimal point for the totaliser, tot.dt:
Default: 0
The decimal point of the device can be adjusted with the navigation keys [▲] [▼]. With [P] the
selection is confirmed and the device changes into menu level.
Totaliser reset, tot.re:
Default: 000
The reset value is adjusted from the smallest to the highest digit with the navigation keys
[▲] [▼] and digit per digit confirmed with [P]. After the last digit, the display switches back to
the menu level. The activator for the reset is parameter driven via the 4th key or via the optional
digital input.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–tot–“.
28
26
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
6. Reset to factory settings
Programming interlock, run:
Menu group level
Description see page 9, menu level run
6. Reset to factory settings
To return the unit to a defined basic state, a reset can be carried out to the default values.
The following procedure should be used:
• Switch off the power supply
• Press button [P]
• Switch on voltage supply and press [P]-button until „- - - - -“ is shown in the display.
With reset, the default values of the program table are loaded and used for subsequent operation. This puts
the unit back to the state in which it was supplied.
Caution! All application-related data are lost.
27
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
29
7. Alarms / Relays
7. Alarms / Relays
This device has 4 virtual alarms that can monitor one limit value in regard of an undercut or exceedance.
Each alarm can be allocated to an optional relay output S1-S2; furthermore alarms can be controlled by
events like e.g. Hold or min/max-value.
Function principle of alarms / relays
Alarm / Relay x
Deactivated, instantaneous value, min/max-value, hold-value, totaliser
value, sliding average value, constant value, difference between
instantaneous value and constant value or an activation via the digital
input
Switching threshold
Threshold / limit value of the change-over
Hysteresis
Broadness of the window between the switching thresholds
Working principle
Operating current / Quiescent current
Operating current
By operating current the alarm S1-S2 is
off below the threshold and on on
reaching the threshold.
Quiescent current
By quiescent current the alarm S1-S2 is
on below the threshold and switched off
on reaching the threshold.
Switching-on delay
The switching-on delay is activated via
an alarm and e.g. switched 10 seconds
after reaching the switching threshold, a
short-term exceedance of the switching
value does not cause an alarm,
respectively does not cause a switching
operation of the relay. The switching-off
delay operates in the same way, keeps
the alarm / the relay switched longer for
the parameterised time.
30
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
28
8. Interfaces RS232 and RS485
8. Interfaces RS232 and RS485
The interface RS485 is connected via a screened data line with twisted wires (Twisted-Pair). On each end
of the bus segment a termination of the bus lines needs to be connected. This is neccessary to ensure a
secure data transfer to the bus. For this a resistance (120 Ohm) is interposed between the lines Data B (+)
and Data A (–).
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
29
31
9. Sensor alignment offset / final value
9. Sensor alignment offset / final value
The device is equipped with a semi-automatic sensor calibration (Su.xxx). A switching output operates the
trimming resistor, which exists in some sensors. An adjustment of offset and final value takes place, after
which the sensor can be used directly. Depending on parameterisation, the calibration can be realized via
the 4th key or via the digital input. It is possible to key during the calibration steps. So, reference signals can
be connected manually. However the calibration will be interrupted after 30 seconds.
Press actuator for minimum 3
seconds.
Activate optional switching
output.
For calibration
problems or 30
seconds
holding time.
For minimum 1 measuring cycle, minimum
1s or maximum per actuator.
Current measuring range
value, e.g. 0.061
For minimum 1 measuring cycle
or with actuator.
Switch-off/switch-on optional
switching output, e.g. 7,132
For minimum 1 measuring cycle, minimum 1s
or maximum per actuator.
Current measuring range value.
For minimum 1 measuring cycle,
minimum 1s or maximum per
actuator.
For calibration
problems or 30
seconds
holding time.
Optional: switch-off switching output and
display for minimum 1 measuring cycle or
minimum 1s holding time.
Back to regular operation mode.
32
30
Back to regular operation mode,
after 1s or 1 measuring cycle.
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
10. Technical data
10. Technical data
Housing
Dimensions
96x48x120 mm (BxHxD)
96x48x139 mm (BxHxD) incl. plug-in terminal
Panel cut-out
92.0+0.8 x 45.0+0.6 mm
Wall thickness
to 15 mm
Fixing
screw elements
Material
PC Polycarbonate, black, UL94V-0
Sealing material
EPDM, 65 Shore, black
Protection class
standard IP65 (Front), IP00 (Back side)
Weight
approx. 300 g
Connection
plug-in terminal; wire cross section up to 2.5 mm2
Display
Digit height
14 mm
Segment colour
red (optional blue/green/orange)
Range of display
-19999 to 99999
Setpoints
one LED per setpoint
Overflow
horizontal bars at the top
Underflow
horizontal bars at the bottom
Display time
0.1 to 10.0 seconds
Input
Measuring range
Ri
Measuring error
Digit
-5…75 mV
0…60 mV
~12 kΩ
0.5 % of measuring range
±1
-15…180 mV
0…150 mV
~60 kΩ
0.5 % of measuring range
±1
-30…360 mV
0…300 mV
~30 kΩ
0.5 % of measuring range
±1
-100…1200 mV
0…1000 mV
~200 kΩ
0.5 % of measuring range
±1
Digital input
< 2.4 V OFF, > 10 V ON, max. 30 VDC
RI ~ 5 kΩ
Accuracy
Temperature drift
100 ppm / K
Measuring time
0.1…10.0 seconds
Measuring principle
U/F-converter
Resolution
approx. 18 bit at 1s measuring time
31
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
33
10. Technical data
Output
Analog output
0/4-20 mA / burden ≤ 500 Ω or 0-10 VDC / ≥ 10 kΩ, 16 bit
Switching outputs
Relay with change-over contacts
Switching cycles
250 VAC / 5 AAC; 30 VDC / 5 ADC
30 x 103 at 5 AAC, 5 ADC ohm resistive load
10 x 106 mechanically
Diversity according to DIN EN50178
/ Characteristics according to DIN EN60255
PhotoMos outputs
8 normally open (NO) contacts 30 VDC/AC, 0.4 A
Interface
Protocol
Modbus with ASCII or RTU-protocol
RS232
9.600 Baud, no parity, 8 databit, 1 stopbit,
wire length max. 3 m
RS485
9.600 Baud, no parity, 8 databit, 1 stopbit,
wire length max 1000 m
Power supply
100-240 VAC 50/60 Hz, DC ±10% (max. 15 VA)
10-40 VDC galv. isolated, 18-30 VAC 50/60 Hz (max. 15 VA)
Memory
EEPROM
Data life
≥ 100 years at 25°C
Ambient conditions
Working temperature
0…50°C
Storing temperature
-20…80°C
Climatic density
relative humidity 0-80% on years average without dew
EMV
EN 61326, EN 55011
CE-sign
Conformity to directive 2004/108/EG
Safety standard
EN 61010; EN 60664-1
34
32
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
11. Safety advices
11. Safety advices
Please read the following safety advices and the assembly chapter 2 before installation and keep
it for future reference.
Proper use
The M3-12-device
DAL-311--device
is designed
for the
evaluation
display
of sensor
signals.
The
is designed
for the
evaluation
andand
display
of sensor
signals.
Attention! Careless use or improper operation can result in
personal injury and/or cause damage to the equipment.
Control of the device
The panel meters are checked before dispatch and sent out in perfect condition. Should there be
any visible damage, we recommend close examination of the packaging. Please inform the
supplier immediately of any damage.
Installation
The M3-12-device
DAL-311-device
must
installed
a suitably
qualified
specialist(e.g.
(e.g.
with
qualification
The
must
be be
installed
by abysuitably
qualified
specialist
with
aa
qualification
in in
industrial
electronics).
industrial electronics).
Notes on installation
• There must be no magnetic or electric fields in the vicinity of the device, e.g. due to
transformers, mobile phones or electrostatic discharge.
• The fuse rating of the supply voltage should not exceed a value of 6A N.B. fuse.
• Do not install inductive consumers (relays, solenoid valves etc.) near the device and
suppress any interference with the aid of RC spark extinguishing combinations or free-wheeling
diodes.
• Keep input, output and supply lines separate from one another and do not lay them parallel with
each other. Position “go” and “return lines” next to one another. Where possible use twisted pair.
So, you receive best measuring results.
• Screen off and twist sensor lines. Do not lay current-carrying lines in the vicinity. Connect the
screening on one side on a suitable potential equaliser (normally signal ground).
• The device is not suitable for installation in areas where there is a risk of explosion.
• Any electrical connection deviating from the connection diagram can endanger human life
and/or can destroy the equipment.
• The terminal area of the devices is part of the service. Here electrostatic discharge needs to be
avoided. Attention! High voltages can cause dangerous body currents.
• Galvanic isolated potentials within one complex need to be placed on an appropriate point
(normally earth or machines ground). So, a lower disturbance sensibility against impacted
energy can be reached and dangerous potentials, that can occur on long lines or due to faulty
wiring, can be avoided.
33
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
35
12. Error elimination
12. Error elimination
Error description
Measures
1.
The unit permanently indicates
overflow.
• The input has a very high measurement, check
the measuring circuit.
• With a selected input with a low voltage signal,
it is only connected on one side or the input is
open.
• Not all of the activated setpoints are
parameterised. Check if the relevant
parameters are adjusted correctly.
2.
The unit permanently shows
underflow.
• The input has a very low measurement, check
the measuring circuit.
• With a selected input with a low voltage signal,
it is only connected on one side or the input is
open.
• Not all of the activated setpoints are
parameterised. Check if the relevant
parameters are adjusted correctly.
3.
The word HELP lights up in the
7-segment display.
• The unit has found an error in the configuration
memory. Perform a reset on the default values
and reconfigure the unit according to your
application.
4.
Program numbers for parameterising
of the input are not accessible.
• Programming lock is activated
• Enter correct code
5.
Err1 lights up in the 7-segment display
• Please contact the manufacturer if errors of this
kind occur.
6.
The device does not react as
expected.
• If you are not sure if the device has been
parameterised before, then follow the steps as
written in chapter 6 and set it back to its delivery
status.
M3_12GB.pdf
36
34
update: 14.04.2015
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
37

Pegel
Druck


Temperatur Durchfluss
Registrierung
Visualisierung
¸



Füllstand



Messumformer
Sensorik
USV
Wir erwarten Ihren Anruf.
ACS-CONTROL-SYSTEM GmbH
Lauterbachstr. 57
D- 84307 Eggenfelden
know how mit System
Ihr Partner für Messtechnik und Automation
¸
[email protected]
www.acs-controlsystem.de
Stand 04/2015
ACS-CONTROL-SYSTEM
Tel: +49 (0) 8721-9668-0
Fax: +49 (0) 8721-9668-30