Description
ASHRAE 90.1 COMPLIANT
ZU/ZW/ZK units are convertible single packages with a
common footprint cabinet and common roof curb for all 3
through 12.5 ton models. All 6.5 through 12.5 ton units have
two compressors with independent refrigeration circuits to
provide 2 stages of cooling. The units were designed for light
commercial applications and can be easily installed on a roof
curb, slab, or frame.
All ZU/ZW/ZK units are self-contained and assembled on rigid
full perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
All units in all tonnage sizes are convertible between side
airflow and down airflow, with corresponding economizer if
economizer option is desired.
Units are available in the following configurations: cooling only,
cooling with electric heat, cooling with gas heat, reheat only,
reheat with electric heat and reheat with gas heat. Electric
heaters are available as factory-installed options or fieldinstalled accessories.
ZU/ZW/ZK 3 THROUGH 10 TON
All units provide constant supply air volume. A variable air
volume (VAV) option, which features a variable frequency drive
(VFD), is available on 6.5 through 12.5 ton ZU/ZW models only.
Tested in accordance with:
ZU/ZW/ZK 12.5 TON
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5123247-TTG-A-0515
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Component Location
Cooling With Gas Heat (3 Through 5 Ton)
Simplicity® SE Control board w/
screw connectors for T-stat
wiring and Network
Connections
Disconnect location
(optional disconnect switch)
Filter access
(2" or 4”
filter options)
Filter drier (solid core)
3-5 Ton Reheat
Micro-Channel Aluminum
Tube/Aluminum Fin
Condenser
(Single Orifice System shown.
See Actual Model Physical Data for details)
Slide out motor and
blower assembly for
easy adjustment
and service
Filter drier (solid core)
3-5 Ton Cooling
Second model nameplate
inside hinged access
panel
Belt-drive blower
motor
Base rails w/
forklift slots
(three sides)
and lifting
holes
Roof curbs in eight-and
fourteen-inch heights.
Roof curbs for transitioning
from DHB/DUC/DHC/DUS
footprint to the ZU/ZW/ZK Series
footprint are available
(field-installed accessory)
Compressor access (highefficiency compressor)
Power ventor
motor
20-gauge aluminized
steel tubular heat
exchanger for long life
(stainless steel option)
Side entry power
and control wiring
knockouts
Toolless door
latch
2
Slide-out drain pan
with ¾" NPT
connection
One or Two stage gas heating to
maintain warm, comfortable
temperature
Intelligent control board
for safe and efficient
operation
Johnson Controls Unitary Products
5123247-TTG-A-0515
Cooling With Gas Heat (6.5 Through 10 Tons)
Simplicity® control board
Disconnect location
w/screw connector for T-stat
wiring and network connections (optional disconnect switch)
Filter access
(2” or 4” filter options)
Filter drier
(solid core)
Micro-Channel Aluminu
Tube/Aluminum Fin
Condenser
Terminal block for
hi-voltage connection
Second model
nameplate
inside hinged
access panel
Slide-out motor and
blower assembly for
easy adjustment
and service
Belt-drive
blower motor
Dual stage
cooling for
maximum
comfort
VFD location (optio
Power ventor motor
Compressor #2
access (highefficiency
compressor)
20-gauge aluminized steel tubular
heat exchanger for
long life (stainless
steel option)
Base rails w/forklift
slots (three sides)
and lifting holes
Roof curbs in eight- and
fourteen-inch heights. Roof
curbs for transitioning from
DHB/DUC/DHC/DUS
footprint to the ZU/ZW/ZK
Series footprints are also
Johnson Controls Unitary Products
Slide-out drain pan
with 3/4” NPT,
female connection
Toolless
door latch
Side entry power
and control wiring
knockouts
Two-stage gas
heating to maintain
warm, comfortable
temperature
Intelligent control
board for safe and
efficient operation
Compressor #1 access
(high-efficiency compressor)
3
5123247-TTG-A-0515
Nomenclature
3-12.5 Ton Model Number Nomenclature
Z U T10 N 18 A 2 A A C 2 1 B A 7
Product Category
Product Generation
7 = Seventh Generation
Z = A/C, Single Pkg., R-410A
Coated Coils
Product Identifier
A = Un-Coated
B = E-Coat Cond & Evap Coils
C = E-Coat Condenser Coil
D = E-Coat Evaporator Coil
U = 11.7-11.8 EER
W = 12.2 EER
K = Reheat
Nominal Cooling Capacity
Additional Options
A = No Options
B = Phase Monitor (PM)
C = Coil Guard (CG)
D = Dirty Filter Switch (DFS)
E = PM & CG
F = PM & DFS
G = CG & DFS
H = PM, CG, & DFS
TA3 = 3 Ton
TA4 = 4 Ton
TA5 = 5 Ton
T06 = 6.5 Ton
T07 = 7.5 Ton
T08 = 8.5 Ton
T10 = 10.0 Ton
T12 = 12.5 Ton
Configuration Options
Heat Type
1 = Bottom Drain Composite-STD
2 = Hot Gas Bypass
3 = SS Drain Pan No/HGB
4 = SS Drain Pan W/HGB
C = Cooling Only. No heat installed
A = Alum Steel, Single Stage
B = Stainless Steel Single Stage
N = Alum Steel, Two Stage
S = Stainless Steel Two Stage
Filter Options
1 = 2" Throwaway Filters
2 = 2" Pleated Filters (Merv 7)
3 = 2" Cleanable Filters
4 = 4" Pleated Filters (Merv 13)
Nominal Heat Capacity (Unit Size Allowed)
Cooling
00 = Cooling Only
Natural Gas Heat Options
VFD Options
06 = 60 MBH Input (TA3, TA4)
08 = 80 MBH Input (TA3, TA4, TA5)
11 = 120 MBH Input (TA3, TA4, TA5)
16 = 160 MBH Input (TA5)
12 = 120 MBH Input(T06,T07,T08)
18 = 180 MBH Input(T06,T07,T08,T10,T12)
24 = 240 MBH Input(T10,T12)
A = None
B = VFD,VAV
C = VFD, w/Bypass, VAV
D = Cust Sup VFD,VAV
E = VFD, IntelliSpeed
F = VFD ,w/Bypass, Intellispeed
G = Cust Sup VFD, Intellispeed
Electric Heat Options
03 = 3 KW (TA3)
06 = 6 KW (TA3, TA4, TA5)
08 = 9 KW (TA3, TA4, TA5)
09 = 9 KW (T06, T07, T08)
15 = 15 KW (TA3, TA4, TA5)
18 = 18 KW (T06, T07, T08, T10, T12)
20 = 20 KW (TA4, TA5)
23 = 24 KW (TA5)
24 = 24 KW (T06, T07, T08, T10, T12)
36 = 36 KW (T06, T07, T08, T10, T12)
54 = 54 KW (T10, T12)
Airflow
A = Std. Motor
D = Std. Motor/Motorized Damper (Downflow Only)
H = Std Motor/Low Leak Econ/Barometric Relief (Downflow
& Horizontal End Return Only)
J = Std Motor/Low Leak Econ/Power Exhaust (Downflow
& Horizontal End Return Only)
N = Hi Static
R = Hi Static/Motorized Damper (Downflow Only)
V = Hi Static Mtr/Low Leak Econ/Barometric Relief
(Downflow & Horizontal End Return Only)
W = Hi Static Mtr/Low Leak Econ/Power Exhaust
(Downflow & Horizontal End Return Only)
Control Options
A = None
C = BACnet MSTP,Modbus,N2 COM Card
F = FDD
H = Hnywll Excel 10 Ctrl, DFS, APS
N = Novar UCM Ctrl, DFS, APS
P = CPC Control, DFS, APS
R = Commercial Control System (CCS) Single Zone
S = Commercial Control System (CCS) Change over bypass
Installation Options
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
4
Johnson Controls Unitary Products
5123247-TTG-A-0515
Features and Benefits
Standard Features
• High Efficiency – High efficiency units reach as high as
12.2 EER. Gas/electric units have electronic spark ignition
and power vented combustion with steady state efficiencies
of 80%. These efficiencies exceed all legislated minimum
levels and provide low operating costs.
• Service Friendly - The ZU/ZW/ZK Series units
incorporates a number of key features for ease of
serviceability.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
Service time is reduced through the use of hinged,
toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other
unauthorized persons. It is recommended that the panels
be secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access to
the condenser coils for cleaning or inspection.
The Simplicity® SE control board provides alarm
messages to help quickly identify any faults.
All units use four filters of the same standard size. This
standardization simplifies selections for filter replacement.
The non-corrosive drain pan slides out of the unit to permit
easy cleaning. The drain pan is accessed by removing the
drain pan cover plate on the rear of the unit. Once the plate is
removed, the drain pan slides out through the rear of the unit.
All ZU/ZW/ZK Series units have a second model
nameplate located inside the control access door. This is
to prevent deterioration of the nameplate through
weathering.
• Coil Technology – All ZU/ZW condensers utilize MicroChannel “all-aluminum” condensers which provide
improved heat transfer capabilities and reduced charge
volumes. All evaporators utilize a conventional copper
tube/aluminum fin design for proven reliability and
performance. ZKTA3 thru TA5 models utilize MicroChannel condenser coils, ZKT06 thru T12 models utilize
copper tube/aluminum fin or Micro-Channel condenser
coils. For specific unit model information see Physical
Data Tables.
Johnson Controls Unitary Products
• Environmentally Aware - For improved Indoor Air
Quality, a combination of aluminum foil faced and
elastometric rubber insulations are used exclusively
throughout the units.
• Balanced Heating - The ZU/ZW/ZK Series two stage gas
heating offers "Ultimate Heating Comfort" with a balance
between 1st and 2nd stage gas heating to provide a well
maintained desired temperature.
Unit Tonnage
1st. Stage
2nd. Stage
3-5 Ton
70 to 75% of Heating
Capacity
100% of Heating
Capacity
6.5 - 12.5 Ton
60% of Heating
Capacity
100% of Heating
Capacity
• Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/
return is desired, the installer simply removes the two side
duct covers from the outside of the unit and installs them
over the down shot openings. No panel cutting is required.
Convertible airflow design allows maximum field flexibility
and minimum inventory.
• System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frosting
when the economizer operates at low outdoor air
temperatures while the compressors are running. Every unit
has solid-core liquid line filter-driers and high and lowpressure switches. Internal compressor protection is
standard on all compressors. Scroll compressors do not
require crankcase heaters. Phase Monitors are standard on
units with scroll compressors. This accessory monitors the
incoming power to the unit and protects the unit from phase
loss and reversed phase rotation.
• Advanced Controls - Simplicity® SE control boards have
standardized a number of features previously available only
as options or by utilizing additional controls.
The Simplicity® SE control board used in this
product will effectively operate the cooling system
down to 0°F when this product is applied in a comfort
cooling application for people. An economizer is
typically included in this type of application. When
applying this product for process cooling applications
(computer rooms, switchgear, etc.), please
reference applications bulletin AE-011-07 or call the
applications department for Unitary Products @ 1877-UPG-SERV for guidance. Additional
accessories may be needed for stable operation at
temperatures below 30°F.
5
5123247-TTG-A-0515
voltage supplied to the unit and will protect the unit if low
voltage due to a brown out, or other electrical issue
occurs.
• Low Ambient - An integrated low-ambient control allows
units to operate in the cooling mode down to 0°F outdoor
ambient without additional components or intervention.
Optionally, the control board can be programmed to
lockout the compressors when the outdoor air
temperature is low or when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life, an
anti- short cycle delay is incorporated into the standard
control. Compressor reliability is further ensured by
programmable minimum run times. For testing, the antishort cycle delay can be temporarily overridden with the
push of a button.
• Units will come with the new state of the art Simplicity
SE (Smart Equipment) control system. The new unit
control incorporates the best of the already proven
Simplicity™ unitary controls and creates a more robust,
intelligent control. The goal of this control is to utilize
cutting edge technology making the equipment easier to
install, operate, and service. All units are Factory
commissioned, configured, and run tested.
• Versatile - The Simplicity SE control can be configured to
use with a standard thermostat (easy to connect screw
terminals), A zone sensor, or can be setup to
communicate with multiple BAS communication protocols
to integrate with building automation systems.
• Reduce field installed complexity - Each unit will comes
equipped with factory installed supply air, return air, and
outdoor air temperature sensors providing key
temperature readings thus reduce field installed
complexity.
• On-board USB Port - The new control comes with a long
list of features including data logging, current and
previous system faults and software update capabilities
using the on board USB port and common flash drive.
Energy use monitoring capabilities allow custom tailoring
to allow a system to work more efficiently at all times and
occupancy levels. Self test and start-up reports also
available from the board VIA the USB port.
• Embedded LCD Display - The board has a easy to read,
built-in LCD display and easy to use navigation joystick
and buttons allowing the user to quickly navigate the
menus displaying unit status, options, current function,
supply, return and outdoor temperatures, fault codes and
other information.
• Safety Monitoring - The control monitors the outdoor,
supply, and return air temperatures and the high and low
pressure switch status on the independent refrigerant
circuits. On units with heating the gas valve and high
temperature limit switches are monitored on gas and
electric heating units. The control also monitors the
6
• Fan Delays - Fan on and fan off delays are fully
programmable. Furthermore, the heating and cooling fan
delay times are independent of one another. All units are
programmed with default values based upon their
configuration of cooling and/or heating capacity.
• Nuisance Trip Protection and Three Strikes - To
prevent nuisance calls, the control board uses a three
times, you're out philosophy. The high, low-pressure
switch, anti-freeze protection, low voltage or heating high
limit must trip three times within two hours before the unit
control board will lock out the associated compressor.An
alarm message will be displayed on the LCD screen.
• Lead-Lag - An integrated Lead-Lag option allows equal
run time hours on all compressors, thereby extending the
life of all compressors. This option is selectable on the unit
control board.
• Low Limit Control (LLC) - To prevent the supply air from
dropping below a specified set point, when there is a
demand for cooling during cold outside conditions.
(Programmable Set point)
• Reliable - From the beginning - All units undergo
computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term - All
units are painted with a long lasting, powder paint that
stands up over the life of the unit. The paint used has
been proven by a 1000 hour salt spray test.
• Full Perimeter Base Rails - The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer rigging
holes so that an overhead crane can be used to place the
units on a roof.
• Easy Installation - Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the
unit. Utility connections can be made quickly and with a
minimum amount of field labor. All units are shipped with
2" throw-away filters installed.
• Wide Range of Indoor Airflows - All supply air blowers
are equipped with a belt drive that can be adjusted to
meet the exact requirements of the job. A high static drive
option is available for applications with a higher CFM and/
or static pressure requirement.
Johnson Controls Unitary Products
5123247-TTG-A-0515
• Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
(10 yr.) and stainless steel tubular heat exchangers carry
a 15- year warranty.
Factory Installed Options
TempMaster offers several equipment options factory installed,
for the ZU/ZW/ZK Seriesline.
• Optional Factory Installed Economizers - ZU/ZW/ZK
units offer a variety of optional factory installed
economizers with low leak dampers. The outdoor air dry
bulb sensor enables economizer operation if the outdoor
air temperature is less than the set point of the economizer
logic module. See economizer options section to
determine the correct economizer for your application.
• Down flow / End Return Economizers (with
barometric relief and fresh air hood) - All units offer a
variety of optional factory installed down flow
economizers that are shipped, installed and wired with
low leak dampers designed to meet ASHRAE 90.12010, AMCA 511 Class 1A damper, and the
International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of
3 cfm/sq. ft. at 1" of static pressure. Each economizer
goes through a rigorous 60,000 cycle test. Dry bulb,
single enthalpy, and dual enthalpy (with field installed
kit) can be selected. The economizer has spring return,
fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to
economizer operation is regulated by the outdoor air dry
bulb temperature or the outdoor air enthalpy input. The
optional (field installed) single or dual enthalpy kits
provide additional inputs to monitor outdoor air/ or return
air humidity and temperature for true enthalpy control.
The installer needs only to assemble the outdoor air
hood, attach the enthalpy control the hood and mount
the hood to the unit (Hood and control are provided).
• Power Exhaust - This factory option allows down flow or
horizontal end return economizer operation. The power
exhaust must be removed from the unit and mounted
in the horizontal end return duct work when applying
the product in the horizontal, end return
configuration.
• Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly
with an outdoor air hood and filters. The outdoor air
dampers open to the preset position when the indoor fan
motor is energized. The damper has a range of 0% to
100% outdoor air entry.
• Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
• Variable Air Volume (VAV; 6.5 through 12.5 ton, only) A factory-installed variable frequency drive (VFD),
mounted in the Blower Access compartment, is used to
Johnson Controls Unitary Products
control the speed of the indoor blower motor in order to
maintain a constant static pressure in the supply duct. A
duct pressure transducer is provided with the unit. The
drive comes completely wired and pre-programmed from
the factory.
An optional, factory-installed manual bypass switch
available with factory-installed VFD can be found in the
Blower Motor Access compartment. The switch can be
used to either route power to the VFD for modulating
control of the blower motor, to bypass the drive and
operate the motor at full speed, or to power the drive (and
not the motor) for diagnostic purposes.
VAV is not available with the factory-installed 3rd. party
BAS controllers. VAV is only factory installed with the
Simplicity SE Controller.
A 'VFD-ready' option provides the provisions for a
customer-installed drive. The unit comes with a mounting
bracket installed in the Blower Access compartment which
may accommodate other vendor's drives depending on
their size. In order to utilize the unit's mounting bracket,
the maximum recommended drive dimensions are limited
to approximately 9" H x 5" W x 7.5" D.
If the drive will not fit in the allotted space, then it will have
to be mounted elsewhere; either within the building on a
perpendicular wall which is not subjected to excessive
temperature, vibration, humidity, dust, corrosive gas,
explosive gas, etc., or within an appropriate enclosure
rated for outside installation to safeguard against
moisture, dust and excessive heat. A terminal block
located in the control box is provided for field connection
of the VFD controls.
• IntelliSpeed™ Supply Fan Control Option (ASHRAE
90.1 compliant, section 6.4.3.10) - Units configured with
the IntelliSpeed™ Supply Fan Option will contain a VFD
for multi-speed supply fan operation. This option allows
the supply fan RPM to vary based on the number of
compressors or heating stages energized. The
economizer's minimum position will also be configurable
to vary based on the supply fan VFD frequency output.
• Aluminized Steel Gas Heat Exchanger - For
applications in non-corrosive environments.
• Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
• Stainless Steel Drain Pan - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
• Electric Heaters - The electric heaters range from 3kW to
54kW and are available in all the voltage options of the
base units. All heaters are intended for single point power
supply.
• Disconnect Switch - For gas heat units and cooling units
with electric heat, a HACR breaker sized to the unit is
provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
• Convenience Outlet - (Non-Powered/Powered) - This
option locates a 120V single-phase GFCI outlet with cover,
on the corner of the unit housing adjacent to the
7
5123247-TTG-A-0515
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source and
wiring. The “Powered” option is powered by a stepdown
transformer in the unit. Factory installed option only.
• Smoke Detectors - The smoke detectors stop operation
of the unit and provide a fault message to the control
board. Smoke detectors are available for both the supply
and/or return air configurations.
• Filters - 2” Pleated MERV 7 or 4” Pleated MERV 13 are
available to meet LEED requirements. A 2” Throwaway is
shipped as standard.
Factory-installed smoke detectors may be subjected to
extreme temperatures during "off" times due to outside air
infiltration. These smoke detectors have an operational
limit of -4°F to 158°F. Smoke detectors installed in areas
that could be outside this range will have to be relocated to
prevent false alarms.
• Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition. (Standard on units with Scroll Compressors.)
• Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally, this
kit stops animals and foreign objects from entering the
space between the inner condenser coil and the main
cabinet. This is not a hail guard kit.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or
field installed accessory.
• Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• E-coat Condenser Coils - The condenser coils are
coated with an epoxy polymer coating to protect against
corrosion.
• E-coat Evaporator Coils - The evaporator coils are
coated with an epoxy polymer coating to protect against
corrosion.
• Hot Gas Bypass - Allows operation during low load
conditions while avoiding coil frosting and damage to
compressor. When suction pressure falls below valve
setpoint, the valve modulates hot gas to the inlet of the
evaporator. HGBP is standard on all units with VAV and
optional with constant-volume units.
Control Options
• Simplicity® SE with Communication Option Control The TempMaster Simplicity® SE with Communication
Option Control is factory installed. It includes all the
features of the Simplicity® SE control with an additional
8
gateway to BACnet MS/TP (programmable to Modbus or
N2 protocols).
• Novar® BAS Control - The Novar® building automation
system controller is factory installed. Includes supply air
sensor, return air sensor, dirty filter indicator switch, and
air proving switch.
• CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building
automation system controller is factory installed. Includes
supply air sensor, return air sensor, with optional dirty
filter indicator switch and air proving switch.
• Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, with optional
dirty filter indicator switch, and air proving switch.
Field Installed Accessories
TempMaster offers several equipment accessories for field
installation, for the ZU/ZW/ZK Series line.
• Down flow and End Return Economizers (with fresh air
hood and barometric relief) - All units offer a variety of
optional factory installed down flow economizers that are
shipped, installed and wired with low leak dampers designed
to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper,
and the International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of 3
cfm/sq. ft. at 1" of static pressure. Each economizer goes
through a rigorous 60,000 cycle test. Dry bulb, single
enthalpy, and dual enthalpy (with field installed kit) can be
selected. The economizer has spring return, fully modulating
damper actuators and is capable of introducing up to 100%
outdoor air. As the outdoor air intake dampers open, the
return air dampers close. The changeover from mechanical
refrigeration to economizer operation is regulated by the
outdoor air dry bulb temperature or the outdoor air enthalpy
input. The dual enthalpy kit provides a second input used to
monitor the return air (field installed). The installer needs only
to assemble the outdoor air hood, attach the enthalpy control
the hood and mount the hood to the unit (Hood and control
are provided).
• Single or Dual Enthalpy Control, Accessories - These
kits contain the required components to convert a dry bulb
economizer to a single enthalpy and/or dual enthalpy
economizer.
• Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed economizers.
• Power Exhaust - This accessory installs in the unit with a
down flow or horizontal end return economizer. Power
exhaust plugs into the connector in the unit bulkhead.
User must purchase the 1EH0408 barometric relief
and hood kit when applying the product in a
horizontal flow application. The power exhaust must
be mounted in the horizontal end return ductwork.
• Manual Outdoor Air Damper - Like the motorized outdoor
air damper, each manual outdoor air damper includes a
slide-in damper assembly with an outdoor air hood and
filters. Customers have a choice of dampers with ranges of
0% to 100% or 0% to 35% outdoor air entry.
Johnson Controls Unitary Products
5123247-TTG-A-0515
• Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly with
an outdoor air hood and filters. The outdoor air dampers
open to the preset position when the indoor fan motor is
energized. The damper has a range of 0% to 100% outdoor
air entry. Factory installed option or field installed accessory.
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
• CO2 Sensor - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
preset limits.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters.
• Coil Guard - Field installed decorative wire coil guard.
• Hail Guard - This kit includes a sloped hood which installs
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only.
• Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can be
installed to prevent the flue exhaust from entering nearby
fresh air intakes.
• -60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
valve and controls will continue to function properly at
extremely low temperatures.
• Gas Heat High Altitude Kit - This kit converts a gas heat
unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and propane.
Johnson Controls Unitary Products
• Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains the
main burner orifices and gas valve replacement springs.
• Gas Piping Kit - Contains pipe nipples, fittings and gas cock
required for gas supply connection with external shut off.
• Electric Heaters - The electric heaters range from 3kW to
54kW and are available in all the voltage options of the
base units. The 54kW/208-240 volt, field-installed heater
kit is not available with VAV units due to a lack of space to
accommodate the heater’s fuse block accessory.
All heaters are dual staged. Cooling units include an
adapter panel for easy installation of the electric heaters.
Necessary hardware and connectors are included with the
heaters. All heaters are intended for single point power
supply.
• Metal Frame Filter Kit - Metal frame with polyester filter
medium.
• Permanent Filters - Permanent filters are available.
• Roof Curbs - The roof curbs have insulated decks and are
shipped disassembled The roof curbs are available in 8” and
14” heights. For applications with security concerns, burglar
bars are available for the duct openings of the roof curbs.
• Roof Curb Transition - Single Piece Adapter (10” High) Roof curbs for transitioning from DHB/DUC/DHC/DUS
units to ZU/ZW/ZK units. Fits 7.5 to 12.5 Sunline™ roof
curbs only.
• Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
• Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All 6.5
thru 12.5 ton ZU/ZW units and all 3 thru 12.5 ton ZK units
(with or without an economizer) operate with two-stage
heat/two-stage cool or two-stage cooling only
thermostats, depending upon unit configuration.
9
5123247-TTG-A-0515
Accessories
Field Installed Accessories - Non-Electrical
MODEL
1BD0408
VOLTAGE DESCRIPTION
All
Burglar Bars, Downflow
1CG0419
1CG0420
1CG0427
1CG0428
All
All
All
All
Coil Guard
Coil Guard
Coil Guard
Coil Guard
1HG0411
1HG0415
1FE0412
1FF0414
1FF0415
1FL0402
1FL0423
1GP0405
1HA0442
1HA0450
1HA0451
1HA0443
1HA0452
1HA0453
1NP0442
1NP0454
1NP0455
1RC0470
1RC0471
1RC0472
All
All
All
All
All
All
All
All
All
All
All
All
All
All
All
All
All
All
All
All
1WC0412
1LN0407
1LN0408
All
All
All
Hail Guard Kit
Hail Guard Kit
Flue Exhaust Extension Kit
2" only Metal Filter Frame Kit
2" only Metal Filter Frame Kit
Permanent 2" only Filter Kit Includes (4) Four Filters)
Permanent 2" only Filter Kit (Includes (4) four Filters)
Gas Piping Kit
High Altitude Kit for Natural Gas
High Altitude Kit for Natural Gas
High Altitude Kit for Natural Gas
High Altitude Kit for Propane
High Altitude Kit for Propane
High Altitude Kit for Propane
Propane Conversion Kit
Propane Conversion Kit
Propane Conversion Kit
Roof Curb, 8" Height
Roof Curb, 14" Height
Roof Curb, Transition (7.5 T thru 12.5T to 3- 12T)
Wooden Crate for extra protection during shipping and
handling
Low NOx Kit
Low NOx Kit
10
WHERE USED
All Cabinets
(Electric / Electric Models), 50” Tall Standard
Cabinets
(Gas / Electric Models), 50" Tall Standard Cabinets
(Electric / Electric Models), 42” Tall Cabinets
(Gas / Electric Models), 42" Tall Cabinets
All Tall (50") Standard Cabinets, (Excludes 12.5T
"V" cabinets)
All Short (42") Standard Cabinets
All Cabinets
All Tall 50" Cabinets
All Tall 42" Cabinets
All Tall 50" Cabinets
All Tall 42" Cabinets
All Cabinets
All 6 - 12T Cabinets
3 - 5T (80, 120 & 160 MBH Input)
3 - 4T (60 MBH Input)
All 6 - 12T Cabinets
3 - 5T (80, 120 & 160 MBH Input)
3 - 4T (60 MBH Input)
All 6 - 12T Cabinets
3 - 5T (80, 120 & 160 MBH Input)
3 - 4T (60 MBH Input)
All Cabinets
All Cabinets
All Cabinets
Standard Cabinets Only (not applicable to units
119" in length)
3 - 5T (80, 120 & 160 MBH Input)
3 - 5T (60 MBH Input)
Johnson Controls Unitary Products
5123247-TTG-A-0515
Accessories (Continued)
Field Installed Accessories - Electric Heat
MODEL
2TP04520925
2TP04520946
2TP04520958
2TP04531825
2TP04531846
2TP04521858
2TP04532425
2TP04532446
2TP04522458
2TP04533625
2TP04533646
2TP04523658
2TP04525425
2TP04525446
2TP04525458
2TP04540925
2TP04540946
2TP04540958
2TP04541825
2TP04541846
2TP04541858
2TP04542425
2TP04542446
2TP04542458
2TP04543625
2TP04543646
2TP04543658
2TP04510325
2TP04510346
2TP04510625
2TP04510646
2TP04510825
2TP04510846
2TP04510858
2TP04511525
2TP04511546
2TP04511558
2TP04512025
2TP04512046
2TP04512058
2TP04512325
2TP04512346
2TP04512358
VOLTAGE
230
460
575
230
460
575
230
460
575
230
460
575
230
460
575
230
460
575
230
460
575
230
460
575
230
460
575
230
460
230
460
230
460
575
230
460
575
230
460
575
230
460
575
DESCRIPTION
WHERE USED
9kW Electric Heat
All 50" Cabinet 6.5 and 8.5 Ton Models
18kW Electric Heat
All 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models
24kW Electric Heat
All 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models
36kW Electric Heat
All 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models
54kW Electric Heat
All 50" 10 and 12.5 Ton Models
9kW Electric Heat
All 42" Cabinet 6.5, 7.5 and 8.5 Ton Models
18kW Electric Heat
All 42" 6.5, 7.5 and 8.5 Ton Models
24kW Electric Heat
All 42" Cabinet 6.5, 7.5 and 8.5 Ton Models
36kW Electric Heat
All 42" Cabinet 6.5, 7.5 and 8.5 Ton Models
3kW Electric Heat
All 42" Cabinet 3 Ton Models
6kW Electric Heat
All 42" Cabinet 3, 4 and 5 Ton Models
9kW Electric Heat
All 42" Cabinet 3, 4 and 5 Ton Models
15kW Electric Heat
All 42" Cabinet 3, 4 and 5 Ton Models
20kW Electric Heat
All 42" 4 and 5 Ton Models
24kW Electric Heat
All 42" Cabinet 5 Ton Models
Johnson Controls Unitary Products
11
5123247-TTG-A-0515
Accessories (Continued)
Field Installed Accessories - Fresh Air
MODEL
1FA0413
1FA0414
1EH0408
2EC0401
2EC0402
VOLTAGE
All
All
All
All
All
DESCRIPTION
Manual Outside Air Damper 0-35%, Downflow
Manual Outside Air Damper 0-100%, Downflow
Barometric Relief Kit for Power Exhaust, Horizontal Application
Single Enthalpy Control
Dual Enthalpy Control (Includes 2 Sensors)
WHERE USED
All Cabinets
All Cabinets
All Cabinets
All Cabinets
All Cabinets
2EE04707624
All
Economizer for Downflow, End Return Horizontal, or ERV
Applications. Includes FA Hood, Exhaust Hood w/Baro Relief
All 50" Cabinets
2EE04707424
All
Economizer for Downflow, End Return Horizontal, or ERV
Applications. Includes FA Hood, Exhaust Hood w/Baro Relief
All 42" Cabinets
2EE04706924
2MD04703824
2MD04703924
2PE04704706
2PE04704746
2PE04704758
All
All
All
230
460
575
Horizontal Economizer without Barometric Relief
Motorized Damper, Downflow without Barometric Relief
Motorized Damper, Horizontal without Barometric Relief
Power Exhaust 230V Downflow or Horizontal
Power Exhaust 460V Downflow or Horizontal
Power Exhaust 575V Downflow or Horizontal
All Cabinets
All Cabinets
All Cabinets
All Cabinets
All Cabinets
All Cabinets
Field Installed Accessories - Controls
MODEL
2AP0401
2AQ04700324B
2AQ04700424C
2DF0402
VOLTAGE
All
All
All
All
2SH0401
All
2SD04700824
2SD04700924
2SD04701024
S1-YKMAP1810-0P
All
All
All
S1-MP-PRTKIT0P
All
All
DESCRIPTION
Air Proving Switch
CO² Space Accessory
CO² Unit Accessory
Dirty Air Switch
Wall Mounted humidity sensor-For use with MagnaDry Reheat
or space humidity input to Simplicity SE board.
Smoke Detector for Supply
Smoke Detector for Return
Smoke Detector for Supply and Return
MAP (Mobile Access Portal) Gateway- For use with Simplicity
SE Control.
MAP (Mobile Access Portal) Gateway Kit- Replacement MAP
gateway protective case, lanyard and communication cable.
Use only to replace worn or damaged components.
WHERE USED
All Units
All Units
All Units
All Units
All Cabinets
All Gen 5 and greater units with 2" & 4" Filters
All Gen 5 and greater units with 2" & 4" Filters
All Gen 5 and greater units with 2" & 4" Filters
All Units
All Units
Field Installed Accessories - Electrical
MODEL
2BC04700106
2BC04700151
2BC04700154
2LA04704632
2LA04704633
2LA04704632
VOLTAGE
230
460
575
All
All
All
DESCRIPTION
Gas heat kit, -60ºF
Gas heat kit, -60ºF
Gas heat kit, -60ºF
Low Ambient Kit
Low Ambient Kit
Low Ambient Kit
Guide Specifications
GENERAL
Units shall be manufactured by Johnson Controls in an ISO
9001 certified facility. ZU/ZW/ZK Series units are convertible
single packages with a common footprint cabinet and common
roof curb for all 3 through 12.5 ton models. All 6.5 through 12.5
ton units have two compressors with independent R-410A
refrigeration circuits to provide 2 stages of cooling. The units
were designed for light commercial applications and can be
easily installed on a roof curb, slab, or frame. All ZU/ZW/ZK
units are self-contained and assembled on rigid full perimeter
base rails allowing for 3-way forklift access and overhead
rigging. Every unit is completely charged with R-410A, wired,
piped, and tested at the factory to provide a quick and easy
field installation. All units are convertible between side and
12
WHERE USED
All Units
All Units
All Units
All 3 - 10T units (excludes ZT Units)
All 12.5T cabinets
All 3 - 5T Reheat Units Only
down airflow. Independent economizer designs are used on
side and down discharge applications, as well as all tonnage
sizes. ZU/ZW/ZK units are available in the following
configurations: cooling only, cooling with electric heat, cooling
with gas heat, reheat only, reheat with electric heat and reheat
with gas heat. Electric heaters are available as factory-installed
options or field-installed accessories.
DESCRIPTION
Units shall be factory assembled, single package, (Elec/Elec, Gas/
Elec), designed for outdoor installation. They shall have built in
field convertible duct connections for down discharge supply/return
or horizontal discharge supply/return and be available with factory
installed options or field installed accessories. The units shall be
factory wired, piped and charged with R-410A refrigerant and
factory tested prior to shipment. All unit wiring shall be both
Johnson Controls Unitary Products
5123247-TTG-A-0515
numbered and color coded. The cooling performance shall be
rated in accordance with DOE and AHRI test procedures. Units
shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No.
236-M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hour salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up to
1” thick insulation coated on the airside. Either aluminum foil
faced or elastometric rubber insulation shall be used in the
unit’s compartments and be fastened to prevent insulation from
entering the air stream. Cabinet doors shall be hinged with
toolless access for easy servicing and maintenance. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, fork truck access and proper
sealing on roof curb applications. Disposable 2” filters shall be
furnished as standard and be accessible through hinged access
door. Fan performance measuring ports shall be provided on
the outside of the cabinet to allow accurate air measurements
of evaporator fan performance without removing panels or
creating bypass of the coils. Condensate pan shall be slide out
design, constructed of a non corrosive material, internally
sloped and conforming to ASHRAE 62-B9 standards.
Condensate connection shall be a minimum of ¾” I.D. female
and be rigid mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall not
exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service
factor. Fan wheel shall be double inlet type with forward curve
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
volume. Bearings shall be sealed and permanently lubricated
for longer life and no maintenance. Entire blower assembly and
motor shall be slide out design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge air
vertically, have aluminum blades riveted to corrosion resistant
steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently
lubricated bearings internally protected against overload
conditions and staged independently. A cleaning window shall be
provided on two sides of the units for coil cleaning.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or –
10% of the unit nameplate voltage.
g. Control board shall monitor each refrigerant safety switch
Johnson Controls Unitary Products
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed. Special Phenolic
coating shall be available as a factory option.
b. Evaporator coils shall be of the direct expansion, drawthru design.
c. Condenser coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed or Micro-Channel
aluminum tube, aluminum fins.
d. Condenser coils shall be of the draw-thru design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice
expansion devices.
or
thermally
operated
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
d. The 6.5 through 12.5 ton unit shall have two independent
refrigerant circuits, equally split in 50% capacity
increments.
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit,
should any of the following standard safety devices trip
and shut off compressor.
1. Loss-of-charge/Low-pressure switch.
2. High-pressure switch.
3. Freeze condition sensor on evaporator coil. If any of
these safety devices trip, the LCD screen will display
the alarm message.
c. Unit shall incorporate "AUTO RESET" compressor over
temperature, over current protection.
d. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
e. Unit control board shall have on-board diagnostics and
fault message display.
f. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
a selectable value as low as 0 °F.
independently.
13
5123247-TTG-A-0515
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of
aluminized steel, and be designed with induced draft combustion with post purge logic, energy saving direct spark ignition,
and redundant main gas valve. The heat exchanger shall be of
the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 40 ºF. Burners shall be of the in-shot type,
constructed of aluminum-coated steel. All gas piping shall enter
the unit cabinet at a single location, through either the side or
bottom, without any field modifications. An integrated control
board shall provide timed control of evaporator fan functioning
and burner ignition. Heating section shall be provided with the
following minimum protection:
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft pressure sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls.
e. All two stage gas units shall have two independent
stages of capacity as shown on Page 5.
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 3 thru 54KW. The heating section shall have a primary limit control(s) (automatic reset) to prevent the heating element system from operating at an
excessive temperature. The Heating Section assembly shall
slide out of the unit for easy maintenance and service. Units
with Electric Heating Sections shall be wired for a single point
power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor
temperature, exceeding maximum load criteria of AHRI Standard 340/360. The compressor, with standard controls, shall be
capable of operation down to 0 ºF outdoor temperature. Unit
shall be provided with fan time delay to prevent cold air delivery
before heat exchanger warms up. (Gas heat only)
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES - Compressor – 5 Years,
Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years,
Parts – 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available by either/
or):
• DRY BULB AUTOMATIC ECONOMIZER - Outdoor and
return air dampers that are interlocked and positioned by
a fully-modulating, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall be designed to meet ASHRAE 90.1-2010, AMCA
14
511 Class 1A damper, and the International Energy
Conservation Code (IECC) certification requirements by
achieving leakage rates of 3 cfm/sq. ft. at 1" of static
pressure. Changeover from compressor to economizer
operation shall be provided by an integral electronic
enthalpy control that feeds input into the basic module.
The outdoor intake opening shall be covered with a rain
hood that matches the exterior of the unit. Water
eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
Available with barometric relief and power exhaust.
• MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and
return air dampers that are interlocked and positioned by
a 2- position, spring-return damper actuator. A unitmounted potentiometer shall be provided to adjust the
outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions
- regardless of the outdoor air enthalpy. Dampers return to
the fully closed position when the indoor fan motor is deenergized. Dampers shall fully close on power loss.
ADDITIONAL FACTORY INSTALLED OPTIONS
• ALTERNATE INDOOR BLOWER MOTOR – For
applications with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
• VARIABLE AIR VOLUME (VAV) - The VAV option using
a variable frequency drive (VFD) shall be available on
6.5 through 12.5 ton models for applications requiring a
constant supply-duct static pressure. Units equipped for
VAV shall be controlled by a duct pressure transducer
with a 0 - 5" WC pressure range. The pressure transducer
shall provide a 0 - 5 VDC output signal to a VAV control
board which, in turn shall provide a 2 - 10 VDC speed
reference signal to the VFD. The control board shall
operate using factory-installed Supply Air, Return Air and
Outside Air Temperature Sensors with a nominal
resistance of 10,000 Ohms. Units equipped with VFD's
shall have factory-installed manual bypass as an option.
• CONVENIENCE OUTLET (POWERED/NON-POWERED)–
Unit can be provided with an optional 120VAC GFCI outlet
with cover on the corner of the unit housing the compressors.
• ELECTRIC HEAT - Electric Heaters range from 3kW to
54kW and are available in all the voltage options of the
base unit.
• PHASE MONITOR - Designed to prevent damage in outof-phase condition.
• COIL GUARD - Designed to prevent condenser coil
damage.
• BAS CONTROLS HARDWARE - Include supply air
sensor, return air sensor, dirty filter indicator and air
proving switch.
Johnson Controls Unitary Products
5123247-TTG-A-0515
• DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally highpressure drop across the filters.
• BREAKER – An HACR breaker can be factory installed
on gas heat units or cooling units with electric heat.
• DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest
electric heat available.
• STAINLESS STEEL HEAT EXCHANGER – For
applications in a corrosive environment, this option
provides a full stainless steel heat exchanger assembly.
• SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
• ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
• BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
• PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
• -60ºF GAS HEAT KIT – Provides an electric heat kit for
the gas compartment for use in extreme low ambient
conditions.
• ECONOMIZER (Downflow and Horizontal flow)
• POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
• DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
Johnson Controls Unitary Products
15
5123247-TTG-A-0515
Physical Data
ZUTA3 thru TA5 Single Stage Gas Physical Data
Models
Component
ZUTA3
ZUTA4
ZUTA5
3.0
4.0
5.0
Gross Capacity @ AHRI A point (MBh)
37000
50000
61000
AHRI net capacity (MBh)
36000
48000
58000
11.8
11.8
11.8
SEER
14
14
14
IPLV
-
-
-
CFM
1200
1600
2000
System power (KW)
3.05
4.07
4.90
R-410A
R-410A
R-410A
System 1
7-4
6-14
7-12
System 2
-
-
-
Nominal Tonnage
AHRI COOLING PERFORMANCE
EER
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
(A,B)06
(A,B)08
(A,B)11
(A,B)06
(A,B)08
(A,B)11
(A,B)08
(A,B)11
(A,B)16
Heat input (K Btu)
60
80
120
60
80
120
80
120
160
Heat output (K Btu)
49
65
97
49
65
97
65
97
129
-
-
-
-
81
81.5
81
81
81
80.5
AFUE %
-
Steady state efficiency (%)
81.5
81
81
-
No. burners
4
4
6
4
4
6
4
6
8
No. stages
1
1
1
1
1
1
1
1
1
Temperature Rise Range (ºF)
Gas Limit Setting (ºF)
Gas piping connection (in.)
20-50°F 25-65°F 50-80°F 20-50°F 25-65°F 40-70°F 25-65°F 35-65°F 45-75°F
235°F
200°F
255°F
235°F
200°F
255°F
200°F
245°F
240°F
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
DIMENSIONS (inches)
Length
89
89
89
Width
59
59
59
Height
42
42
42
723
763
864
Recip
Recip
Recip
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
1
1
1
100
100
100
21.1
CONDENSER COIL DATA
Face area (Sq. Ft.)
11.9
18.5
Rows
1
1
1
Fins per inch
23
23
23
Tube diameter (in./MM)
Circuitry Type
1/25
.71/18
.71/18
2-pass Microchannel
2-pass Microchannel
2-pass Microchannel
10.6
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
8
8
Rows
3
3
3
Fins per inch
15
15
15
Tube diameter
0.375
0.375
0.375
Refrigerant control
TXV
TXV
TXV
16
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUTA3 thru TA5 Single Stage Gas Physical Data (Continued)
Models
Component
Nominal Tonnage
ZUTA3
ZUTA4
ZUTA5
3.0
4.0
5.0
1
1
2
CONDENSER FAN DATA
Quantity of fans
Fan diameter (Inch)
24
24
24
Type
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
1
1
2
1/3
1/3
1/3
Quantity of motors
Motor HP each
No. speeds
1
1
1
RPM
850
850
850
Total CFM
3300
3700
6700
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
12 x 9
12 x 9
12 x 9
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM34
1VL44
1VM34
1VL44
1VL40
1VP56
Blower Sheave
AK69
AK69
AK56
AK56
AK61
AK74
Belt
A47
A47
A47
A47
A47
A51
Motor HP each
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
RPM
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
Frame size
FILTERS
Quantity - Size
4 - (24 x 16 x 2)1,2
3
4 - (24 x 16 x 4)
4 - (24 x 16 x 2)1,2
3
4 - (24 x 16 x 4)
4 - (24 x 16 x 2)1,2
4 - (24 x 16 x 4)3
1. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value)
2. 2 In. Pleated, Optional, MERV 7.
3. 4 In. Pleated, Optional, MERV 13.
Johnson Controls Unitary Products
17
5123247-TTG-A-0515
ZUTA3 thru TA5 Two Stage Gas Physical Data
Models
Component
ZUTA3
ZUTA4
ZUTA5
3.0
4.0
5.0
Gross Capacity @ AHRI A point (MBh)
37000
50000
61000
AHRI net capacity (MBh)
36000
48000
58000
11.8
11.8
11.8
SEER
14
14
14
IPLV
-
-
-
CFM
1200
1600
2000
System power (KW)
3.05
4.07
4.90
R-410A
R-410A
R-410A
System 1
7-4
6-14
7-12
System 2
-
-
-
Nominal Tonnage
AHRI COOLING PERFORMANCE
EER
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
(N,S)06
(N,S)08
(N,S)11
(N,S)06
(N,S)08
(N,S)11
(N,S)08
(N,S)11
(N,S)16
Heat input (K Btu)
60
80
120
60
80
120
80
120
160
Heat output (K Btu)
49
65
97
49
65
97
65
97
129
-
-
-
-
81
81.5
81
81
81
80.5
AFUE %
-
Steady state efficiency (%)
81.5
81
81
-
No. burners
4
4
6
4
4
6
4
6
8
No. stages
21
22
22
21
22
22
22
22
22
Temperature Rise Range (ºF)
Gas Limit Setting (ºF)
Gas piping connection (in.)
20-50°F 25-65°F 50-80°F 20-50°F 25-65°F 40-70°F 25-65°F 35-65°F 45-75°F
235°F
200°F
255°F
235°F
200°F
255°F
200°F
245°F
240°F
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
DIMENSIONS (inches)
Length
89
89
89
Width
59
59
59
Height
42
42
42
723
763
864
Recip
Recip
Recip
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
1
1
1
100
100
100
21.1
CONDENSER COIL DATA
Face area (Sq. Ft.)
11.9
18.5
Rows
1
1
1
Fins per inch
23
23
23
Tube diameter (in./MM)
Circuitry Type
1/25
.71/18
.71/18
2-pass Microchannel
2-pass Microchannel
2-pass Microchannel
10.6
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
8
8
Rows
3
3
3
Fins per inch
15
15
15
Tube diameter
0.375
0.375
0.375
Refrigerant control
TXV
TXV
TXV
18
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUTA3 thru TA5 Two Stage Gas Physical Data (Continued)
Models
Component
Nominal Tonnage
ZUTA3
ZUTA4
ZUTA5
3.0
4.0
5.0
1
1
2
CONDENSER FAN DATA
Quantity of fans
Fan diameter (Inch)
24
24
24
Type
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
1
1
2
1/3
1/3
1/3
Quantity of motors
Motor HP each
No. speeds
1
1
1
RPM
850
850
850
Total CFM
3300
3700
6700
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
12 x 9
12 x 9
12 x 9
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM34
1VL44
1VM34
1VL44
1VL40
1VP56
Blower Sheave
AK69
AK69
AK56
AK56
AK61
AK74
Belt
A47
A47
A47
A47
A47
A51
Motor HP each
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
RPM
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
Frame size
FILTERS
Quantity - Size
1.
2.
3.
4.
5.
4 - (24 x 16 x 2)3,4
5
4 - (24 x 16 x 4)
4 - (24 x 16 x 2)3,4
5
4 - (24 x 16 x 4)
4 - (24 x 16 x 2)3,4
4 - (24 x 16 x 4)5
1st Stage Capacity is 75% of Full Capacity.
1st Stage Capacity is 70% of Full Capacity.
2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value)
2 In. Pleated, Optional, MERV 7.
4 In. Pleated, Optional, MERV 13.
Johnson Controls Unitary Products
19
5123247-TTG-A-0515
ZUT06 thru T12 Physical Data
Models
Component
ZUT06
ZUT07
ZUT08
ZUT10
ZUT12
6.5
7.5
8.5
10
12.5
Gross Capacity @ AHRI A point (Btu)
81000
93000
107000
125000
156000
AHRI net capacity (Btu)
78000
90000
102000
120000
150000
11.71/11.52
11.71/11.52
11.71/11.52
11.7
11.71/11.52
Nominal Tonnage
AHRI COOLING PERFORMANCE
EER
SEER
-
-
-
-
-
IEER
12.81/12.62
12.81/12.62
12.81/12.62
12
12.81/12.62
IPLV
13.7
13
13.5
12.9
14.1
CFM
2600
2700
3400
4000
3750
System power (KW)
6.69
7.70
9.0
10.40
12.80
R-410A
R-410A
R-410A
R-410A
R-410A
System 1
7-0
5-10
7-6
8-0
8-2
System 2
6-0
5-13
7-2
7-7
8-2
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
(N,S)12
(N,S)18
(N,S)12
(N,S)18
(N,S)12
(N,S)18
(N,S)18
(N,S)24
(N,S)18
(N,S)24
Heat input (K Btu)
120
180
120
180
120
180
180
240
180
240
Heat output (K Btu)
96
144
96
144
96
144
144
192
144
192
-
-
-
-
-
-
-
-
-
-
80
80
80
80
80
80
80
80
80
80
AFUE %
Steady state efficiency (%)
No. burners
4
6
4
6
4
6
6
8
6
8
No. stages
23
23
23
23
23
23
23
23
23
23
20-50
35-65
15-45
30-60
10-40
25-55
20-50
35-65
10-40
25-55
Gas Limit Setting (ºF)
165
165
165
165
215
195
195
160
195
160
Gas piping connection (in.)
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
Temperature Rise Range (ºF)
DIMENSIONS (inches)
Length
89
89
89
89
Width
59
59
59
59
59
Height
42
42
50-3/4
50-3/4
50-3/4
910
910
1047
1090
1280
Recip
Recip
Recip
Scroll
Scroll
2
2
2
2
2
50 / 100
50 / 100
50 / 100
50 / 100
50 / 100
47.5
OPERATING WT. (lbs.)
119-1/2
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)
23.8
23.8
29.0
29.0
Rows
1
1
1
1
1
Fins per inch
23
23
23
23
23
1/25
1/25
1/25
1/25
.71/18
Tube diameter (in./MM)
Circuitry Type
2-pass Microchannel 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
10.6
10.6
13.2
13.2
Rows
3
3
3
4
13.2
4
Fins per inch
15
15
15
15
15
Tube diameter
0.375
0.375
0.375
0.375
0.375
Circuitry Type
Intertwined
Intertwined
Intertwined
Intertwined
Intertwined
TXV
TXV
TXV
TXV
TXV
Refrigerant control
20
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUT06 thru T12 Physical Data (Continued)
Models
Component
ZUT06
ZUT07
ZUT08
ZUT10
ZUT12
6.5
7.5
8.5
10
12.5
2
2
2
2
4
Nominal Tonnage
CONDENSER FAN DATA
Quantity of fans
Fan diameter (Inch)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
2
2
2
2
4
1/3
3/4
3/4
3/4
1/3
Quantity of motors
Motor HP each
No. speeds
1
1
1
1
1
RPM
850
1110
1110
1110
850
Total CFM
6700
8600
9400
9400
14000
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
1
1
12 x 12
12 x 12
15 x 15
15 x 15
15 x 15
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
AK74
AK64
AK74
AK61
AK94
AK74
AK84
AK74
AK74
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
2
1-1/2
3
2
3
2
3
3
5
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
56
56
56
184T
Frame size
FILTERS
Quantity - Size
1.
2.
3.
4.
5.
6.
4 - (24 x 16 x 2)4,5
4 - (24 x 16 x 4)
6
4 - (24 x 16 x 2)4,5
4 - (24 x 16 x 4)
6
4 - (24 x 20 x 2)4,5
6
4 - (24 x 20 x 4)
4 - (24 x 20 x 2)4,5
6
4 - (24 x 20 x 4)
4 - (24 x 20 x 2)4,5
4 - (24 x 20 x 4)6
Cooling Only Unit
Cooling Unit with Gas or Electric Heat
1st Stage 60% of Full Capacity.
2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
2 In. Pleated, Optional, MERV 7.
4 In. Pleated, Optional, MERV 13.
Johnson Controls Unitary Products
21
5123247-TTG-A-0515
ZWTA3 thru TA5 Single Stage Gas Heat Physical Data
Models
Component
ZWTA3
ZWTA4
ZWTA5
3.0
4.0
5.0
Gross Capacity @ AHRI A point (MBh)
37000
50000
62000
AHRI net capacity (MBh)
36000
48000
60000
12.2
12.2
12.2
SEER
15
15
15
IPLV
-
-
-
CFM
1300
1600
2000
System power (KW)
2.95
3.95
4.90
R-410A
R-410A
R-410A
System 1
6-12
7-8
8-4
System 2
-
-
-
Nominal Tonnage
AHRI COOLING PERFORMANCE
EER
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
(A,B)06
(A,B)08
(A,B)11
(A,B)06
(A,B)08
(A,B)11
(A,B)08
(A,B)11
(A,B)16
Heat input (K Btu)
60
80
120
60
80
120
80
120
160
Heat output (K Btu)
49
65
97
49
65
97
65
97
129
-
-
-
-
81
81.5
81
81
81
80.5
AFUE %
-
Steady state efficiency (%)
81.5
81
81
-
No. burners
4
4
6
4
4
6
4
6
8
No. stages
1
1
1
1
1
1
1
1
1
Temperature Rise Range (ºF)
Gas Limit Setting (ºF)
Gas piping connection (in.)
20-50°F 25-65°F 50-80°F 20-50°F 25-65°F 40-70°F 25-65°F 35-65°F 45-75°F
235°F
200°F
255°F
235°F
200°F
255°F
200°F
245°F
240°F
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
DIMENSIONS (inches)
Length
89
89
89
Width
59
59
59
Height
42
42
42
740
775
770
Recip
Recip
Recip
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
1
1
1
100
100
100
23.8
CONDENSER COIL DATA
Face area (Sq. Ft.)
18.5
23.8
Rows
1
1
1
Fins per inch
23
23
23
Tube diameter (in./MM)
Circuitry Type
.71/18
.71/18
.71/18
2-pass Microchannel
2-pass Microchannel
2-pass Microchannel
10.5
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
7.9
10.5
Rows
3
3
3
Fins per inch
15
15
15
Tube diameter
0.375
0.375
0.375
Refrigerant control
TXV
TXV
TXV
22
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWTA3 thru TA5 Single Stage Gas Heat Physical Data (Continued)
Models
Component
Nominal Tonnage
ZWTA3
ZWTA4
ZWTA5
3.0
4.0
5.0
1
1
2
CONDENSER FAN DATA
Quantity of fans
Fan diameter (Inch)
24
24
24
Type
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
1
1
2
1/3
1/3
1/3
Quantity of motors
Motor HP each
No. speeds
1
1
1
RPM
850
850
850
Total CFM
3300
3700
6300
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
12 x 9
12 x 9
12 x 9
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM34
1VL44
1VM34
1VL44
1VL40
1VP56
Blower Sheave
AK69
AK69
AK56
AK56
AK61
AK74
Belt
A47
A47
A47
A47
A47
A51
Motor HP each
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
RPM
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
Frame size
FILTERS
Quantity - Size
4 - (24 x 16 x 2)1,2
3
4 - (24 x 16 x 4)
4 - (24 x 16 x 2)1,2
3
4 - (24 x 16 x 4)
4 - (24 x 16 x 2)1,2
4 - (24 x 16 x 4)3
1. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value)
2. 2 In. Pleated, Optional, MERV 7.
3. 4 In. Pleated, Optional, MERV 13.
Johnson Controls Unitary Products
23
5123247-TTG-A-0515
ZWTA3 thru TA5 Two Stage Gas Heat Physical Data
Models
Component
ZWTA3
ZWTA4
ZWTA5
3.0
4.0
5.0
Gross Capacity @ AHRI A point (MBh)
37000
50000
62000
AHRI net capacity (MBh)
36000
48000
60000
12.2
12.2
12.2
SEER
15
15
15
IPLV
-
-
-
CFM
1300
1600
2000
System power (KW)
2.95
3.95
4.90
R-410A
R-410A
R-410A
System 1
6-12
7-8
8-4
System 2
-
-
-
Nominal Tonnage
AHRI COOLING PERFORMANCE
EER
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
(N,S)06
(N,S)08
(N,S)11
(N,S)06
(N,S)08
(N,S)11
(N,S)08
(N,S)11
(N,S)16
Heat input (K Btu)
60
80
120
60
80
120
80
120
160
Heat output (K Btu)
49
65
97
49
65
97
65
97
129
-
-
-
-
81
81.5
81
81
81
80.5
AFUE %
-
Steady state efficiency (%)
81.5
81
81
-
No. burners
4
4
6
4
4
6
4
6
8
No. stages
21
22
22
21
22
22
22
22
22
Temperature Rise Range (ºF)
Gas Limit Setting (ºF)
Gas piping connection (in.)
20-50°F 25-65°F 50-80°F 20-50°F 25-65°F 40-70°F 25-65°F 35-65°F 45-75°F
235°F
200°F
255°F
235°F
200°F
255°F
200°F
245°F
240°F
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
DIMENSIONS (inches)
Length
89
89
89
Width
59
59
59
Height
42
42
42
740
775
770
Recip
Recip
Recip
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
1
1
1
100
100
100
23.8
CONDENSER COIL DATA
Face area (Sq. Ft.)
18.5
23.8
Rows
1
1
1
Fins per inch
23
23
23
Tube diameter (in./MM)
Circuitry Type
.71/18
.71/18
.71/18
2-pass Microchannel
2-pass Microchannel
2-pass Microchannel
10.5
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
7.9
23.8
Rows
3
3
3
Fins per inch
15
15
15
Tube diameter
0.375
0.375
0.375
Refrigerant control
TXV
TXV
TXV
24
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWTA3 thru TA5 Two Stage Gas Heat Physical Data (Continued)
Models
Component
Nominal Tonnage
ZWTA3
ZWTA4
ZWTA5
3.0
4.0
5.0
1
1
2
CONDENSER FAN DATA
Quantity of fans
Fan diameter (Inch)
24
24
24
Type
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
1
1
2
1/3
1/3
1/3
Quantity of motors
Motor HP each
No. speeds
1
1
1
RPM
850
850
850
Total CFM
3300
3700
6300
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
12 x 9
12 x 9
12 x 9
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM34
1VL44
1VM34
1VL44
1VL40
1VP56
Blower Sheave
AK69
AK69
AK56
AK56
AK61
AK74
Belt
A47
A47
A47
A47
A47
A51
Motor HP each
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
RPM
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
Frame size
FILTERS
Quantity - Size
1.
2.
3.
4.
5.
4 - (24 x 16 x 2)3,4
5
4 - (24 x 16 x 4)
4 - (24 x 16 x 2)3,4
5
4 - (24 x 16 x 4)
4 - (24 x 16 x 2)3,4
4 - (24 x 16 x 4)5
1st Stage Capacity is 75% of Full Capacity.
1st Stage Capacity is 70% of Full Capacity.
2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value)
2 In. Pleated, Optional, MERV 7.
4 In. Pleated, Optional, MERV 13.
Johnson Controls Unitary Products
25
5123247-TTG-A-0515
ZWT06 thru T12
Models
Component
ZWT06
ZWT07
ZWT08
ZWT10
ZWT12
6.5
7.5
8.5
10
12.5
Gross Capacity @ AHRI A point (Btu)
80000
93000
106000
124000
154000
AHRI net capacity (Btu)
78000
90000
102000
120000
150000
12.21/12.02
12.21/12.02
12.21/12.02
12.0
12.0
SEER
-
-
-
-
-
IEER
14.0
13.1
12.2
12.8
13
IPLV
14.9
14.18
13.6
13.4
14.1
CFM
2600
2400
2800
3400
3500
Nominal Tonnage
AHRI COOLING PERFORMANCE
EER
System power (KW)
6.40
7.38
8.30
9.80
12.50
R-410A
R-410A
R-410A
R-410A
R-410A
System 1
5-10
7-12
8-8
7-14
10-8
System 2
5-12
7-10
8-12
7-14
9-12
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
(N,S)12
(N,S)18
(N,S)12
(N,S)18
(N,S)12
(N,S)18
(N,S)18
(N,S)24
(N,S)18
(N,S)24
Heat input (K Btu)
120
180
120
180
120
180
180
240
180
240
Heat output (K Btu)
96
144
96
144
96
144
144
192
144
192
-
-
-
-
-
-
-
-
-
-
80
80
80
80
80
80
80
80
80
80
AFUE %
Steady state efficiency (%)
No. burners
4
6
4
6
4
6
6
8
6
8
No. stages
23
23
23
23
23
23
23
23
23
23
20-50
35-65
15-45
30-60
10-40
25-55
20-50
35-65
10-40
25-55
Gas Limit Setting (ºF)
165
165
165
165
215
195
195
160
195
160
Gas piping connection (in.)
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
Temperature Rise Range (ºF)
DIMENSIONS (inches)
Length
89
89
89
89
Width
59
59
59
59
59
Height
50-3/4
50-3/4
50-3/4
50-3/4
50-3/4
1030
1050
1060
1070
1280
Recip
Recip
Recip
Scroll
Scroll
2
2
2
2
2
50 / 100
50 / 100
50 / 100
50 / 100
50 / 100
47.5
OPERATING WT. (lbs.)
119-1/2
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)
29.0
23.8
29.0
29.0
Rows
1
1
1
1
1
Fins per inch
23
23
23
23
23
.71/18
1/25
1/25
1/25
.71/18
Tube diameter (in./MM)
Circuitry Type
2-pass Microchannel 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
13.2
13.2
13.2
13.2
Rows
3
4
4
4
13.2
4
Fins per inch
15
15
15
15
15
Tube diameter
0.375
0.375
0.375
0.375
0.375
Circuitry Type
Intertwined
Intertwined
Intertwined
Intertwined
Intertwined
TXV
TXV
TXV
TXV
TXV
Refrigerant control
26
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWT06 thru T12 (Continued)
Models
Component
ZWT06
ZWT07
ZWT08
ZWT10
ZWT12
6.5
7.5
8.5
10
12.5
2
2
2
2
4
Nominal Tonnage
CONDENSER FAN DATA
Quantity of fans
Fan diameter (Inch)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
2
2
2
2
4
1/3
3/4
3/4
3/4
1/3
Quantity of motors
Motor HP each
No. speeds
1
1
1
1
1
RPM
850
1110
1110
1110
850
Total CFM
7400
8000
9000
9400
14000
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
1
1
15 x 15
15 x 15
15 x 15
15 x 15
15 x 15
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VL40
1VM50
1VL40
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
AK74
AK74
AK69
AK69
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A53
A54
A52
A54
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
2
1-1/2
3
2
3
2
3
3
5
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
56
56
56
184T
Frame size
FILTERS
Quantity - Size
1.
2.
3.
4.
5.
6.
4 - (24 x 20 x 2)4,5
4 - (24 x 20 x 4)
6
4 - (24 x 20 x 2)4,5
4 - (24 x 20 x 4)
6
4 - (24 x 20 x 2)4,5
4 - (24 x 20 x 4)
6
4 - (24 x 20 x 2)4,5
4 - (24 x 20 x 4)
6
4 - (24 x 20 x 2)4,5
4 - (24 x 20 x 4)6
Cooling Only Unit
Cooling Unit with Gas or Electric Heat
1st Stage 60% of Full Capacity.
2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
2 In. Pleated, Optional, MERV 7.
4 In. Pleated, Optional, MERV 13.
Johnson Controls Unitary Products
27
5123247-TTG-A-0515
ZKTA3 thru TA5 Single Stage Gas Heat Physical Data
Models
Component
Nominal Tonnage
ZKTA3
ZKTA4
ZKTA5
3
4
5
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu)
36500
49000
62000
AHRI net capacity (Btu)
35500
47500
60000
12.2
12.2
12.2
15
15
14.7
EER
SEER
IPLV
-
-
-
CFM
1200
1600
2000
System power (KW)
2.88
3.32
4.83
R-410A
R-410A
R-410A
System 1
12-8
12-0
11-0
System 2
-
-
-
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
(A,B)06
(A,B)08
(A,B)11
(A,B)06
(A,B)08
(A,B)11
(A,B)08
(A,B)11
(A,B)16
Heat input (K Btu)
60
80
120
60
80
120
80
120
160
Heat output (K Btu)
49
65
97
49
65
97
65
97
129
-
-
-
-
81
81.5
81
81
81
80.5
AFUE %
-
Steady state efficiency (%)
81.5
81
81
-
No. burners
4
4
6
4
4
6
4
6
8
No. stages
1
1
1
1
1
1
1
1
1
Temperature Rise Range (ºF)
Gas Limit Setting (ºF)
Gas piping connection (in.)
20-50°F 25-65°F 35-80°F 20-50°F 25-65°F 35-80°F 25-65°F 35-80°F 45-75°F
200°F
235°F
290°F
200°F
235°F
290°F
235°F
290°F
240°F
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
DIMENSIONS (inches)
Length
89
89
Width
59
59
59
Height
42
42
42
867
880
867
Recip
Recip
Recip
1
1
1
100
100
100
11.9
OPERATING WT. (lbs.)
89
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)
11.9
11.9
Rows
1
1
1
Fins per inch
23
23
23
Tube diameter (in./MM)
Circuitry Type
.98/25
.98/25
.71/18 - .98/25
2-pass Microchannel
2-pass Microchannel
2-pass Microchannel
10.56
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
10.56
10.56
Rows
3
3
4
Fins per inch
15
15
12
Tube diameter
0.375
0.375
0.375
Refrigerant control
TXV
TXV
TXV
8.9
REHEAT COIL DATA
Face area (Sq. Ft.)
8.9
8.9
Rows
2
2
2
Fins per inch
15
15
15
Tube diameter
Refrigerant control
28
0.375
0.375
0.375
Solenoid
Solenoid
Solenoid
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKTA3 thru TA5 Single Stage Gas Heat Physical Data (Continued)
Models
Component
Nominal Tonnage
ZKTA3
ZKTA4
ZKTA5
3
4
5
CONDENSER FAN DATA
Quantity of fans
1
2
2
Fan diameter (Inch)
24
24
24
Type
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Quantity of motors
1
2
2
Motor HP each
1/3
1/3
1/3
No. speeds
Var.
Var.
Var.
RPM (max.)
850
850
850
Total CFM
3500
7000
7000
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
12 x 9
12 x 9
12 x 9
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VP34
1VL44
1VP34
1VL44
1VP34
1VL44
Blower Sheave
AK61
AK59
AK61
AK59
AK61
AK59
Belt
A47
A47
A47
A47
A47
A47
Motor HP each
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
RPM
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
Frame size
FILTERS
Quantity - Size
4 - (24 x 16 x 2)1, 2
4 - (24 x 16 x 2) 1, 2
4 - (24 x 16 x 2)1, 2
4 - (24 x 16 x 4) 3
4 - (24 x 16 x 4) 3
4 - (24 x 16 x 4) 3
1. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value)
2. 2 In. Pleated, Optional, MERV 7.
3. 4 In. Pleated, Optional, MERV 13.
Johnson Controls Unitary Products
29
5123247-TTG-A-0515
ZKTA3 thru TA5 Two Stage Gas Heat Physical Data
Models
Component
Nominal Tonnage
ZKTA3
ZKTA4
ZKTA5
3
4
5
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu)
36500
49000
62000
AHRI net capacity (Btu)
35500
47500
60000
12.2
12.2
12.2
15
15
14.7
EER
SEER
IPLV
-
-
-
CFM
1200
1600
System power (KW)
2.88
3.32
4.83
R-410A
R-410A
R-410A
Refrigerant type
2000
Refrigerant charge (lb-oz)
System 1
12-8
System 2
12-0
-
11-0
-
-
AHRI HEATING PERFORMANCE
Heating model
(N,S)06
(N,S)08
(N,S)11
(N,S)06
(N,S)08
(N,S)11
Heat input (K Btu)
60
80
120
60
80
120
80
120
160
Heat output (K Btu)
49
65
97
49
65
97
65
97
129
-
-
-
-
81
81.5
81
81
81
80.5
AFUE %
-
Steady state efficiency (%)
81.5
81
81
(N,S)08 (N,S)11
(N,S)16
-
No. burners
4
4
6
4
4
6
4
6
8
No. stages
21
22
22
21
22
22
22
22
22
20-50°F
25-65°F
35-80°F
20-50°F
200°F
235°F
290°F
200°F
235°F
290°F
235°F
290°F
240°F
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
Temperature Rise Range (ºF)
Gas Limit Setting (ºF)
Gas piping connection (in.)
25-65°F 35-80°F 25-65°F 35-80°F 45-75°F
DIMENSIONS (inches)
Length
89
89
Width
59
59
59
Height
42
42
42
867
880
867
Recip
Recip
Recip
1
1
1
100
100
100
11.9
OPERATING WT. (lbs.)
89
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)
11.9
11.9
Rows
1
1
1
Fins per inch
23
23
23
Tube diameter (in./MM)
Circuitry Type
.98/25
.98/25
.71/18 - .98/25
2-pass Microchannel
2-pass Microchannel
2-pass Microchannel
10.56
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
10.56
10.56
Rows
3
3
4
Fins per inch
15
15
12
Tube diameter
0.375
0.375
0.375
Refrigerant control
TXV
TXV
TXV
8.9
REHEAT COIL DATA
Face area (Sq. Ft.)
8.9
8.9
Rows
2
2
2
Fins per inch
15
15
15
Tube diameter
Refrigerant control
30
0.375
0.375
0.375
Solenoid
Solenoid
Solenoid
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKTA3 thru TA5 Two Stage Gas Heat Physical Data (Continued)
Models
Component
Nominal Tonnage
ZKTA3
ZKTA4
ZKTA5
3
4
5
CONDENSER FAN DATA
Quantity of fans
1
2
2
Fan diameter (Inch)
24
24
24
Type
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Quantity of motors
1
2
2
Motor HP each
1/3
1/3
1/3
No. speeds
Var.
Var.
Var.
RPM
850
850
850
Total CFM
3500
7000
7000
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
12 x 9
12 x 9
12 x 9
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VP34
1VL44
1VP34
1VL44
1VP34
1VL44
Blower Sheave
AK61
AK59
AK61
AK59
AK61
AK59
Belt
A47
A47
A47
A47
A47
A47
Motor HP each
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
RPM
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
Frame size
FILTERS
Quantity - Size
4 - (24 x 16 x 2)3,4
4 - (24 x 16 x
4)5
4 - (24 x 16 x 2)3,4
4 - (24 x 16 x
4)5
4 - (24 x 16 x 2)3,4
4 - (24 x 16 x 4)5
1. 1st Stage Capacity is 75% of Full Capacity.
2. 1st Stage Capacity is 70% of Full Capacity.
3. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value)
4. 2 In. Pleated, Optional, MERV 7.
5. 4 In. Pleated, Optional, MERV 13.
Johnson Controls Unitary Products
31
5123247-TTG-A-0515
ZKT06 thru T12 Physical Data
Models
Component
ZKT06
ZKT07
ZKT08
ZKT10
ZKT12
6.5
7.5
8.5
10
12.5
Gross Capacity @ AHRI A point (Mbh)
80000
90000
105000
124000
157000
AHRI net capacity (Mbh)
Nominal Tonnage
AHRI COOLING PERFORMANCE
78000
87000
102000
120000
150000
EER
11.2
11.2
11.2
11.2
11.2
IEER
12.51/12.32
11.5
12.2
11.3
11.0
IPLV
13.0
CFM
2200
2775
3350
3750
4450
System power (KW)
6.96
7.77
9.11
10.71
13.39
R-410A
R-410A
R-410A
R-410A
R-410A
System 1
9-0
6-12
11-10
8-11
20-0
System 2
5-8
6-0
10-3
7-8
19-0
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
(N,S)12
(N,S)18
(N,S)12
(N,S)18
(N,S)12
(N,S)18
(N,S)18
(N,S)24
(N,S)18
(N,S)24
Heat input (K Btu)
120
180
120
180
120
180
180
240
180
240
Heat output (K Btu)
96
144
96
144
96
144
144
192
144
192
-
-
-
-
-
-
-
-
-
-
80
80
80
80
80
80
80
80
80
80
AFUE %
Steady state efficiency (%)
No. burners
4
6
4
6
4
6
6
8
6
8
No. stages
23
23
23
23
23
23
23
23
23
23
Temperature Rise Range (ºF)
20-50
35-65
15-45
30-60
10-40
25-55
20-50
35-65
10-40
25-55
Gas Limit Setting (ºF)
165
165
165
165
215
195
195
160
195
160
Gas piping connection (in.)
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
DIMENSIONS (inches)
Length
89
89
89
89
119-7/16
Width
59
59
59
59
59
Height
42
42
50-3/4
50-3/4
50-3/4
957
965
1200
1200
1465
Scroll
Scroll
Scroll
Scroll
Scroll
2
2
2
2
2
50 / 100
50 / 100
50 / 100
50 / 100
50 / 100
Face area (Sq. Ft.)
23.8
23.8
29.0
29.0
47.5
Rows
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
2/1
1
2
1
2
Fins per inch
20
23
20
23
15
Tube diameter (in.)
3/8
-
3/8
-
3/8
-
1/25
-
1/25
-
Split-face
2-pass
Microchannel
Split-face
2-pass
Microchannel
Split-face
13.2
Tube diameter (in.)/MM
Circuitry Type
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
10.6
10.6
13.2
13.2
Rows
3
3
4
4
4
Fins per inch
15
15
15
15
15
Tube diameter
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Split-face
Split-face
Split-face
Split-face
Split-face
TXV
TXV
TXV
TXV
TXV
Refrigerant control
32
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT06 thru T12 Physical Data (Continued)
Models
Component
ZKT06
ZKT07
ZKT08
ZKT10
ZKT12
6.5
7.5
8.5
10
12.5
6.66
6.66
10
10
10
Nominal Tonnage
REHEAT COIL DATA
Face area (Sq. Ft.)
Rows
2
2
2
2
2
Fins per inch
13
13
13
13
13
Tube diameter (in.)
3/8
3/8
3/8
3/8
3/8
CONDENSER FAN DATA
Quantity of Fans
2
2
2
2
4
Fan diameter (Inch)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
Quantity of motors
Motor HP each
2
2
2
2
4
1/3
1/3
1/3
3/4
1/3
No. speeds
1
1
1
1
1
850
850
850
1110
850
6800
6800
6800
9500
14000
RPM
Total CFM
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
1
1
12 x 12
12 x 12
15 x 15
15 x 15
15 x 15
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
2
1-1/2
3
2
3
2
3
3
5
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
56
56
56
184T
Frame size
FILTERS
Quantity - Size
1.
2.
3.
4.
5.
6.
4 - (24 x 16 x 2)4,5 4 - (24 x 16 x 2)4,5 4 - (24 x 20 x 2)4,5 4 - (24 x 20 x 2)4,5 4 - (24 x 20 x 2)4,5
4 - (24 x 16 x 4)6
4 - (24 x 16 x 4)6
4 - (24 x 20 x 4)6
4 - (24 x 20 x 4)6
4 - (24 x 20 x 4)6
Cooling Only or Cooling with Electric Heat Unit
Cooling with Gas Heat Unit
1st Stage 60% of 2nd Stage
2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
2 In. Pleated, Optional, MERV 7.
4 In. Pleated, Optional, MERV 13.
Johnson Controls Unitary Products
33
5123247-TTG-A-0515
ZU/ZW/ZKTA3 thru T12 Unit Limitations
Unit Limitations
Size
(Tons)
TA3
(3)
TA4
(4)
TA5
(5)
T06
(6.5)
T07
(7.5)
T08
(8.5)
T10
(10)
T12
(12.5)
34
Model
ZU/ZW/ZK
ZU/ZW/ZK
ZU/ZW/ZK
ZU/ZW/ZK
ZU/ZW/ZK
ZU/ZW/ZK
ZU/ZW/ZK
ZU/ZW/ZK
Unit Voltage
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
Johnson Controls Unitary Products
5123247-TTG-A-0515
Capacity Performance
ZUTA3 thru T12 Cooling Capacities
ZUTA3 (3.0 Ton)
Air on
Evaporator Coil
CFM
750
900
1050
1200
1350
1500
750
900
1050
1200
1350
1500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
49.1
44.4
39.6
35.4
51.2
46.2
41.3
36.9
35.4
53.3
48.1
43.0
38.3
36.8
55.4
50.0
44.6
39.8
38.3
50.1
44.7
39.9
38.3
50.1
44.8
39.9
38.4
2.3
2.2
2.2
2.3
2.2
2.2
2.2
2.3
2.3
2.2
2.2
2.2
2.3
2.3
2.2
2.2
2.2
2.3
2.2
2.2
2.2
2.3
2.2
2.2
2.2
2.3
2.3
20.2
25.1
30.0
35.4
22.9
28.2
33.6
36.9
35.4
25.5
31.4
37.3
38.3
36.8
28.2
34.6
41.0
39.8
38.3
37.2
42.9
39.9
38.3
39.7
44.8
39.9
38.4
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
44.0
39.0
34.1
29.8
45.2
40.1
35.1
30.6
30.9
46.5
41.2
36.0
31.5
31.8
47.7
42.3
37.0
32.3
32.6
42.9
37.5
32.7
33.0
43.4
37.9
33.1
33.5
2.7
2.7
2.7
2.6
2.7
2.7
2.7
2.7
2.7
2.8
2.7
2.7
2.7
2.7
2.8
2.8
2.8
2.7
2.7
2.8
2.7
2.7
2.7
2.8
2.7
2.7
2.7
18.0
22.7
27.4
29.8
20.3
25.4
30.5
30.6
30.9
22.5
28.1
33.7
31.5
31.8
24.7
30.8
36.9
32.3
32.6
33.6
37.4
32.7
33.0
36.3
37.9
33.1
33.5
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
16.8
13.4
46.5
2.5
21.7
18.4
15.0
41.7
2.5
26.6
23.3
19.9
16.5
36.9
2.5
32.8
27.8
24.5
21.1
17.8
32.6
2.5
18.8
14.8
48.2
2.5
24.2
20.2
16.1
43.2
2.5
29.6
25.6
21.5
17.5
38.2
2.5
35.1
30.6
26.5
22.5
18.5
33.7
2.5
35.4
32.4
28.4
24.3
20.3
33.2
2.5
20.8
16.1
49.9
2.5
26.7
22.0
17.3
44.7
2.5
32.6
27.9
23.2
18.5
39.5
2.5
37.5
33.3
28.6
23.9
19.2
34.9
2.5
36.8
35.3
30.6
25.9
21.2
34.3
2.5
22.8
17.5
51.5
2.5
29.2
23.8
18.4
46.2
2.5
35.6
30.2
24.8
19.4
40.8
2.5
39.8
36.1
30.7
25.3
19.9
36.1
2.5
38.3
38.3
32.9
27.5
22.1
35.5
2.5
31.3
25.4
19.5
46.5
2.5
38.1
32.2
26.3
20.4
41.1
2.5
39.9
38.0
32.1
26.3
20.4
36.3
2.5
38.3
38.3
32.4
26.6
20.7
35.7
2.5
33.4
27.0
20.6
46.8
2.5
40.6
34.2
27.8
21.5
41.3
2.5
39.9
39.9
33.6
27.2
20.8
36.5
2.5
38.4
38.4
32.0
25.6
19.2
35.9
2.5
95°F
14.7
11.3
40.2
3.0
19.3
16.0
12.6
35.5
2.9
24.0
20.7
17.3
13.9
30.8
2.9
29.8
24.7
21.4
18.0
14.7
27.0
2.8
16.3
12.4
41.2
3.0
21.5
17.6
13.6
36.4
3.0
26.6
22.7
18.8
14.9
31.5
2.9
30.6
27.2
23.3
19.4
15.4
27.7
2.9
30.9
28.0
24.1
20.2
16.2
28.2
2.9
18.0
13.5
42.2
3.0
23.6
19.1
14.7
37.2
3.0
29.2
24.8
20.3
15.8
32.3
3.0
31.5
29.7
25.2
20.7
16.2
28.3
2.9
31.8
30.5
26.1
21.6
17.1
28.9
2.9
19.7
14.7
43.2
3.1
25.8
20.7
15.7
38.1
3.0
31.8
26.8
21.8
16.7
33.1
3.0
32.3
32.1
27.1
22.0
17.0
29.0
2.9
32.6
33.1
28.0
23.0
17.9
29.6
2.9
27.9
22.3
16.6
38.5
3.0
34.4
28.8
23.2
17.5
33.4
3.0
32.7
32.6
27.0
21.3
15.7
29.3
2.9
33.0
33.3
27.6
22.0
16.4
29.9
2.9
30.1
23.8
17.6
39.0
3.0
37.1
30.8
24.6
18.4
33.8
3.0
33.1
33.1
26.9
20.7
14.4
29.6
2.9
33.5
33.5
27.2
21.0
14.8
30.2
2.9
90
19.1
23.9
28.7
32.6
21.6
26.8
32.1
33.7
33.2
24.0
29.8
35.5
34.9
34.3
26.5
32.7
38.9
36.1
35.5
35.4
40.1
36.3
35.7
38.0
41.3
36.5
35.9
15.8
21.2
26.6
27.0
18.9
23.8
28.7
27.7
28.2
21.9
26.4
30.9
28.3
28.9
24.9
28.9
33.0
29.0
29.6
31.7
33.4
29.3
29.9
34.4
33.8
29.6
30.2
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
15.7
12.4
20.5
17.2
13.8
25.3
22.0
18.6
15.2
31.3
26.3
22.9
19.6
17.6
13.6
22.8
18.9
14.9
28.1
24.1
20.2
16.2
32.9
28.9
24.9
20.9
33.2
30.2
26.2
22.3
19.4
14.8
25.2
20.6
16.0
30.9
26.3
21.7
17.1
34.5
31.5
26.9
22.3
34.3
32.9
28.3
23.7
21.3
16.1
27.5
22.3
17.1
33.7
28.5
23.3
18.1
36.1
34.1
28.9
23.7
35.5
35.7
30.5
25.2
29.6
23.8
18.1
36.3
30.5
24.7
19.0
36.3
35.3
29.6
23.8
35.7
35.8
30.0
24.3
31.7
25.4
19.1
38.8
32.5
26.2
19.9
36.5
36.5
30.2
23.9
35.9
35.9
29.6
23.3
105°F
13.5
10.2
18.0
14.7
11.4
22.4
19.2
15.9
12.7
27.0
23.2
20.0
16.7
15.0
11.2
20.0
16.2
12.4
24.9
21.1
17.3
13.5
27.7
25.6
21.8
17.9
28.2
26.0
22.2
18.4
16.6
12.3
22.0
17.6
13.3
27.4
23.0
18.7
14.3
28.3
27.9
23.5
19.2
28.9
28.4
24.0
19.7
18.2
13.3
24.0
19.1
14.2
29.9
25.0
20.1
15.1
29.0
30.2
25.3
20.4
29.6
30.7
25.8
20.9
26.2
20.7
15.2
31.6
27.0
21.5
16.0
29.3
29.9
24.4
18.9
29.9
30.5
25.0
19.5
28.3
22.2
16.1
33.4
29.0
22.9
16.8
29.6
29.6
23.6
17.5
30.2
30.2
24.1
18.0
65
16.2
17.0
18.3
17.7
19.2
18.5
20.0
18.0
18.5
17.6
17.0
13.5
14.1
14.6
14.8
15.3
15.5
16.0
13.4
14.0
11.4
11.9
35
5123247-TTG-A-0515
ZUTA3 (3.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
750
900
1050
1200
1350
1500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
36.4
31.9
27.4
24.2
37.2
32.6
28.0
24.7
25.4
37.9
33.2
28.6
25.2
26.0
38.7
33.9
29.1
25.7
26.5
34.2
29.4
25.9
26.7
34.5
29.7
26.2
26.9
3.3
3.2
3.1
3.0
3.3
3.2
3.2
3.1
3.1
3.3
3.2
3.2
3.1
3.1
3.3
3.3
3.2
3.1
3.1
3.3
3.2
3.1
3.1
3.3
3.2
3.2
3.2
13.7
19.7
25.8
24.2
17.4
22.2
26.9
24.7
25.4
21.2
24.6
28.0
25.2
26.0
25.0
27.1
29.1
25.7
26.5
29.8
29.4
25.9
26.7
32.5
29.7
26.2
26.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
12.3
9.1
32.6
3.5
16.6
13.4
10.3
28.4
3.4
20.9
17.7
14.6
11.4
24.1
3.4
24.2
21.7
18.6
15.4
12.3
21.4
3.2
13.8
10.1
33.1
3.6
18.5
14.8
11.1
28.8
3.5
23.2
19.5
15.8
12.1
24.5
3.4
24.7
23.9
20.2
16.5
12.8
21.7
3.3
25.4
24.0
20.3
16.6
12.9
22.7
3.3
15.2
11.0
33.7
3.6
20.4
16.2
11.9
29.2
3.5
25.6
21.3
17.1
12.9
24.8
3.4
25.2
26.1
21.9
17.6
13.4
22.1
3.3
26.0
26.2
22.0
17.7
13.5
23.0
3.3
16.7
11.9
34.2
3.6
22.3
17.5
12.7
29.7
3.5
27.9
23.1
18.3
13.6
25.2
3.4
25.7
28.3
23.5
18.8
14.0
22.4
3.3
26.5
28.4
23.6
18.9
14.1
23.4
3.3
24.4
19.1
13.7
29.9
3.6
28.8
25.2
19.8
14.4
25.4
3.5
25.9
27.2
21.9
16.5
11.2
22.5
3.3
26.7
27.7
22.3
17.0
11.6
23.5
3.4
26.5
20.6
14.7
30.1
3.6
29.7
27.2
21.2
15.3
25.5
3.5
26.2
26.2
20.2
14.3
8.3
22.7
3.4
26.9
26.9
21.0
15.1
9.1
23.7
3.4
90
12.4
18.2
24.1
21.4
16.7
20.6
24.5
21.7
22.7
20.9
22.9
24.8
22.1
23.0
25.2
25.2
25.2
22.4
23.4
27.9
25.4
22.5
23.5
30.1
25.5
22.7
23.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
10.7
8.1
15.2
12.2
9.1
19.3
16.3
13.2
10.2
21.4
21.4
17.2
14.1
12.5
8.9
17.0
13.4
9.8
21.5
17.9
14.4
10.8
21.7
21.7
18.7
15.1
22.7
22.0
18.4
14.8
14.2
9.7
18.8
14.7
10.6
23.7
19.6
15.5
11.4
22.1
22.1
20.2
16.1
23.0
23.0
19.9
15.8
15.9
10.5
20.6
15.9
11.3
25.2
21.3
16.6
12.0
22.4
22.4
21.8
17.1
23.4
23.4
21.5
16.8
22.7
17.4
12.2
25.4
23.3
18.1
12.9
22.5
22.5
19.3
14.1
23.5
23.5
19.7
14.4
24.8
19.0
13.2
25.5
25.4
19.6
13.8
22.7
22.7
16.9
11.1
23.7
23.7
17.9
12.1
65
11.1
11.5
11.3
12.0
11.7
12.5
12.2
8.9
9.2
5.3
6.3
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
36
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUTA4 (4.0 Ton)
Air on
Evaporator Coil
CFM
1000
1200
1400
1600
1800
2000
1000
1200
1400
1600
1800
2000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
65.4
59.2
53.0
47.0
68.3
61.8
55.3
49.1
48.9
71.2
64.4
57.7
51.1
51.0
74.1
67.1
60.0
53.2
53.1
69.2
62.0
54.9
54.8
71.4
63.9
56.6
56.5
3.0
3.0
2.9
2.9
3.0
3.0
2.9
2.9
2.9
3.0
3.0
2.9
2.9
2.9
3.0
3.0
2.9
2.9
2.9
3.0
3.0
3.0
2.9
3.1
3.0
3.0
3.0
28.0
34.8
41.6
47.0
30.8
38.0
45.3
49.1
48.9
33.6
41.3
49.0
51.1
51.0
36.4
44.6
52.8
53.2
53.1
48.1
58.3
54.9
54.8
51.6
63.9
56.6
56.5
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
55.3
49.9
44.5
39.3
57.5
51.9
46.4
40.9
40.6
59.8
54.0
48.2
42.5
42.2
62.0
56.0
50.0
44.1
43.8
57.6
51.4
45.3
45.0
59.1
52.7
46.5
46.2
3.6
3.6
3.5
3.4
3.6
3.6
3.5
3.4
3.5
3.7
3.6
3.6
3.5
3.5
3.7
3.6
3.6
3.5
3.5
3.7
3.6
3.5
3.6
3.7
3.7
3.6
3.6
22.2
28.9
35.5
39.3
25.1
32.4
39.8
40.9
40.6
27.9
35.9
44.0
42.5
42.2
30.8
39.5
48.2
44.1
43.8
42.7
50.5
45.3
45.0
46.0
52.7
46.5
46.2
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
23.5
19.1
60.3
3.3
30.3
25.9
21.4
54.5
3.3
37.1
32.7
28.3
23.8
48.8
3.2
47.0
40.3
35.9
31.4
27.0
43.1
3.2
25.6
20.4
62.9
3.3
32.9
27.7
22.5
56.9
3.3
40.1
35.0
29.8
24.6
50.9
3.2
49.1
43.1
38.0
32.8
27.6
45.0
3.2
48.9
47.1
42.0
36.8
31.6
44.8
3.2
27.7
21.8
65.5
3.3
35.4
29.5
23.6
59.2
3.3
43.1
37.3
31.4
25.5
52.9
3.2
51.1
46.0
40.1
34.2
28.3
46.8
3.2
51.0
50.3
44.4
38.5
32.6
46.6
3.2
29.8
23.2
68.1
3.4
38.0
31.4
24.7
61.5
3.3
46.1
39.5
32.9
26.3
55.0
3.3
53.2
48.8
42.1
35.5
28.9
48.7
3.2
53.1
53.4
46.8
40.2
33.5
48.4
3.2
40.9
33.6
26.4
63.4
3.4
49.6
42.4
35.2
28.0
56.7
3.3
54.9
52.7
45.5
38.3
31.1
50.1
3.3
54.8
54.9
47.7
40.5
33.3
49.9
3.2
43.7
35.9
28.1
65.2
3.4
53.1
45.3
37.5
29.7
58.3
3.3
56.6
56.6
48.8
41.0
33.2
51.6
3.3
56.5
56.5
48.6
40.8
33.0
51.4
3.3
95°F
18.0
13.8
50.6
4.0
24.7
20.5
16.3
45.4
3.9
31.3
27.1
22.9
18.7
40.1
3.8
39.3
33.9
29.7
25.5
21.3
36.2
3.7
20.1
15.2
52.4
4.0
27.5
22.6
17.6
47.0
3.9
34.8
29.9
25.0
20.0
41.5
3.8
40.9
37.3
32.4
27.4
22.5
37.5
3.7
40.6
37.4
32.4
27.5
22.6
37.1
3.7
22.3
16.6
54.3
4.0
30.3
24.6
19.0
48.6
3.9
38.3
32.6
27.0
21.3
43.0
3.8
42.5
40.7
35.1
29.4
23.7
38.8
3.8
42.2
40.8
35.1
29.5
23.8
38.4
3.8
24.4
18.0
56.1
4.1
33.1
26.7
20.3
50.2
4.0
41.8
35.4
29.0
22.6
44.4
3.9
44.1
44.1
37.8
31.4
25.0
40.1
3.8
43.8
44.2
37.8
31.5
25.1
39.7
3.8
35.7
28.7
21.7
51.6
4.0
45.1
38.0
31.0
24.0
45.6
3.9
45.3
45.3
38.3
31.3
24.3
41.2
3.8
45.0
45.2
38.2
31.2
24.2
40.8
3.8
38.3
30.7
23.0
53.0
4.1
48.3
40.7
33.0
25.3
46.8
4.0
46.5
46.5
38.9
31.2
23.6
42.2
3.9
46.2
46.2
38.6
30.9
23.2
41.8
3.9
90
25.1
31.8
38.6
43.1
27.9
35.2
42.5
45.0
44.8
30.7
38.6
46.5
46.8
46.6
33.6
42.0
50.5
48.7
48.4
45.4
54.4
50.1
49.9
48.8
58.3
51.6
51.4
19.3
26.7
34.2
36.2
22.9
30.1
37.3
37.5
37.1
26.6
33.5
40.4
38.8
38.4
30.3
36.9
43.5
40.1
39.7
40.1
45.2
41.2
40.8
43.3
46.8
42.2
41.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
20.8
16.4
27.5
23.2
18.9
34.2
29.9
25.6
21.3
43.1
37.1
32.8
28.5
22.9
17.8
30.2
25.1
20.1
37.5
32.4
27.4
22.3
45.0
40.2
35.2
30.1
44.8
42.3
37.2
32.2
25.0
19.2
32.9
27.1
21.3
40.7
35.0
29.2
23.4
46.8
43.3
37.6
31.8
46.6
45.5
39.8
34.0
27.1
20.6
35.5
29.0
22.5
44.0
37.5
31.0
24.5
48.7
46.5
40.0
33.5
48.4
48.8
42.3
35.8
38.3
31.2
24.0
47.4
40.2
33.1
26.0
50.1
49.0
41.9
34.8
49.9
50.1
43.0
35.8
41.0
33.3
25.6
50.7
43.0
35.2
27.5
51.6
51.6
43.9
36.1
51.4
51.4
43.6
35.9
105°F
16.2
12.1
22.7
18.6
14.5
29.1
25.1
21.0
16.9
36.2
30.9
26.9
22.8
18.2
13.4
25.3
20.5
15.7
32.5
27.7
22.9
18.1
37.5
34.2
29.4
24.6
37.1
33.8
29.0
24.2
20.1
14.6
28.0
22.5
17.0
35.8
30.3
24.8
19.3
38.8
37.4
31.9
26.4
38.4
37.0
31.4
25.9
22.1
15.9
30.6
24.4
18.2
39.2
32.9
26.7
20.5
40.1
40.7
34.4
28.2
39.7
40.2
33.9
27.7
33.2
26.3
19.5
41.9
35.5
28.6
21.8
41.2
41.5
34.6
27.7
40.8
41.0
34.1
27.2
35.8
28.3
20.7
44.6
38.1
30.6
23.1
42.2
42.2
34.7
27.2
41.8
41.8
34.3
26.8
65
24.1
25.1
27.1
26.0
28.2
27.0
29.3
27.7
28.7
28.4
28.1
18.7
19.8
19.4
20.9
20.4
22.0
21.5
20.8
20.4
19.6
19.2
37
5123247-TTG-A-0515
ZUTA4 (4.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1000
1200
1400
1600
1800
2000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
46.0
40.8
35.6
33.1
47.4
42.0
36.7
34.0
33.6
48.7
43.2
37.8
35.0
34.6
50.1
44.4
38.8
36.0
35.5
45.6
39.9
37.0
36.5
46.8
40.9
37.9
37.4
4.3
4.2
4.1
4.0
4.4
4.2
4.1
4.0
4.0
4.4
4.3
4.1
4.1
4.1
4.4
4.3
4.2
4.1
4.1
4.4
4.2
4.1
4.1
4.4
4.3
4.2
4.2
16.4
24.6
32.8
33.1
20.8
27.8
34.8
34.0
33.6
25.3
31.0
36.8
35.0
34.6
29.7
34.3
38.8
36.0
35.5
37.5
39.9
37.0
36.5
40.6
40.9
37.9
37.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
14.3
10.4
41.4
4.7
20.6
16.7
12.7
36.3
4.5
26.9
23.0
19.0
15.1
31.2
4.3
33.1
28.0
24.1
20.1
16.2
29.9
4.3
16.2
11.5
42.3
4.7
23.1
18.5
13.8
37.1
4.5
30.1
25.5
20.8
16.2
31.9
4.4
34.0
31.1
26.4
21.8
17.1
30.6
4.3
33.6
30.2
25.5
20.8
16.2
30.1
4.3
18.0
12.6
43.2
4.8
25.7
20.3
14.9
37.9
4.6
33.3
28.0
22.6
17.2
32.5
4.4
35.0
34.1
28.8
23.4
18.0
31.3
4.3
34.6
33.1
27.8
22.4
17.0
30.7
4.3
19.9
13.8
44.1
4.8
28.2
22.1
16.0
38.7
4.6
36.5
30.5
24.4
18.3
33.2
4.4
36.0
37.2
31.1
25.0
19.0
31.9
4.4
35.5
36.1
30.0
23.9
17.9
31.4
4.4
30.7
24.0
17.2
39.7
4.7
38.7
33.0
26.3
19.6
34.1
4.5
37.0
37.6
30.8
24.1
17.4
32.8
4.4
36.5
36.8
30.0
23.3
16.5
32.2
4.4
33.2
25.8
18.4
40.7
4.8
40.9
35.6
28.2
20.8
35.0
4.6
37.9
37.9
30.5
23.1
15.7
33.6
4.5
37.4
37.4
30.0
22.6
15.2
33.1
4.5
90
13.7
22.4
31.2
29.9
19.1
25.5
31.9
30.6
30.1
24.6
28.6
32.5
31.3
30.7
30.1
31.7
33.2
31.9
31.4
34.8
34.1
32.8
32.2
38.0
35.0
33.6
33.1
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
12.1
8.7
18.6
14.8
11.0
24.7
20.9
17.1
13.2
29.9
25.1
21.3
17.5
14.2
9.7
21.0
16.5
11.9
27.8
23.3
18.7
14.2
30.6
28.0
23.5
19.0
30.1
26.6
22.0
17.5
16.2
10.7
23.4
18.1
12.9
30.8
25.6
20.4
15.2
31.3
30.9
25.6
20.4
30.7
29.3
24.1
18.8
18.3
11.7
25.7
19.8
13.9
33.2
28.0
22.1
16.2
31.9
31.9
27.8
21.9
31.4
31.4
26.1
20.2
28.2
21.6
15.0
34.1
30.5
23.9
17.3
32.8
32.8
27.1
20.5
32.2
32.2
25.9
19.3
30.7
23.4
16.2
35.0
33.0
25.8
18.5
33.6
33.6
26.4
19.1
33.1
33.1
25.8
18.5
65
13.7
14.4
13.0
15.2
13.6
16.0
14.2
13.9
12.7
11.8
11.2
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
38
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUTA5 (5.0 Ton)
Air on
Evaporator Coil
CFM
1250
1500
1750
2000
2250
2500
1250
1500
1750
2000
2250
2500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
82.5
74.3
66.2
59.3
84.7
76.3
68.0
60.9
61.6
86.9
78.4
69.8
62.5
63.3
89.2
80.4
71.6
64.1
64.9
83.6
74.5
66.7
67.5
86.9
77.3
69.3
70.0
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
36.6
43.9
51.1
59.3
40.0
48.4
56.7
60.9
61.6
43.5
52.8
62.2
62.5
63.3
47.0
57.3
67.7
64.1
64.9
61.7
72.5
66.7
67.5
66.1
77.3
69.3
70.0
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
69.3
62.3
55.2
49.7
71.7
64.4
57.1
51.4
48.8
74.0
66.5
58.9
53.0
50.4
76.3
68.6
60.8
54.7
52.0
68.8
61.0
54.9
52.2
69.0
61.2
55.0
52.3
4.3
4.3
4.2
4.1
4.3
4.3
4.2
4.2
4.2
4.3
4.3
4.2
4.2
4.2
4.4
4.3
4.2
4.2
4.2
4.3
4.2
4.2
4.2
4.3
4.2
4.2
4.2
29.2
37.9
46.5
49.7
33.3
42.3
51.3
51.4
48.8
37.3
46.7
56.0
53.0
50.4
41.4
51.1
60.8
54.7
52.0
55.2
61.0
54.9
52.2
59.4
61.2
55.0
52.3
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
30.6
25.1
75.9
3.9
38.3
32.8
27.3
68.3
3.8
46.0
40.5
35.0
29.4
60.7
3.8
59.3
49.5
43.9
38.4
32.9
54.5
3.8
33.6
27.1
78.2
3.9
41.9
35.4
29.0
70.4
3.9
50.2
43.8
37.3
30.8
62.5
3.8
60.9
53.4
47.0
40.5
34.1
56.1
3.8
61.6
54.9
48.4
41.9
35.5
55.2
3.8
36.5
29.1
80.5
3.9
45.5
38.1
30.7
72.4
3.9
54.4
47.0
39.6
32.2
64.4
3.8
62.5
57.4
50.0
42.6
35.2
57.8
3.8
63.3
58.9
51.6
44.2
36.8
56.8
3.8
39.5
31.2
82.7
3.9
49.0
40.7
32.4
74.5
3.9
58.6
50.3
41.9
33.6
66.2
3.8
64.1
61.4
53.1
44.7
36.4
59.4
3.8
64.9
63.0
54.7
46.4
38.1
58.5
3.8
52.7
43.6
34.5
76.2
3.9
62.9
53.8
44.7
35.7
67.7
3.8
66.7
65.3
56.3
47.2
38.1
60.8
3.8
67.5
66.5
57.5
48.4
39.3
59.8
3.8
56.3
46.5
36.6
77.9
3.9
67.3
57.3
47.5
37.7
69.3
3.8
69.3
69.3
59.5
49.6
39.8
62.2
3.8
70.0
70.0
60.2
50.4
40.5
61.2
3.8
95°F
24.1
18.6
62.5
4.7
32.4
26.9
21.4
55.9
4.6
40.6
35.1
29.6
24.1
49.4
4.6
49.7
43.0
37.5
32.0
26.5
44.7
4.5
26.8
20.4
64.8
4.8
35.8
29.4
23.0
58.0
4.7
44.8
38.4
32.0
25.6
51.1
4.6
51.4
47.1
40.6
34.2
27.8
46.3
4.5
48.8
46.3
39.8
33.4
27.0
44.1
4.5
29.5
22.2
67.1
4.8
39.3
31.9
24.6
60.0
4.7
49.1
41.7
34.4
27.0
52.9
4.6
53.0
51.1
43.8
36.4
29.0
47.9
4.5
50.4
50.2
42.9
35.5
28.2
45.7
4.5
32.2
23.9
69.3
4.8
42.8
34.5
26.2
62.0
4.7
53.3
45.0
36.8
28.5
54.7
4.6
54.7
55.2
46.9
38.6
30.3
49.6
4.5
52.0
54.2
45.9
37.7
29.4
47.2
4.5
46.0
36.9
27.7
62.0
4.7
57.3
48.2
39.0
29.8
54.7
4.6
54.9
55.1
45.9
36.7
27.6
49.5
4.5
52.2
53.3
44.1
34.9
25.7
47.2
4.6
49.3
39.2
29.2
62.0
4.7
61.2
51.3
41.2
31.1
54.7
4.6
55.0
55.0
45.0
34.9
24.8
49.5
4.5
52.3
52.3
42.3
32.2
22.1
47.2
4.6
90
32.9
40.9
48.8
54.5
36.6
45.3
54.0
56.1
55.2
40.4
49.8
59.1
57.8
56.8
44.2
54.2
64.3
59.4
58.5
58.5
66.8
60.8
59.8
62.7
69.3
62.2
61.2
25.5
35.3
45.0
44.7
31.0
39.6
48.2
46.3
44.1
36.5
44.0
51.5
47.9
45.7
42.0
48.4
54.7
49.6
47.2
52.4
54.7
49.5
47.2
56.4
54.7
49.5
47.2
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
27.4
21.9
35.3
29.8
24.3
43.3
37.8
32.3
26.8
54.5
46.2
40.7
35.2
30.2
23.8
38.9
32.4
26.0
47.5
41.1
34.6
28.2
56.1
50.2
43.8
37.4
55.2
50.6
44.1
37.7
33.0
25.7
42.4
35.0
27.6
51.7
44.4
37.0
29.6
57.8
54.3
46.9
39.5
56.8
54.6
47.2
39.8
35.9
27.6
45.9
37.6
29.3
56.0
47.7
39.3
31.0
59.4
58.3
50.0
41.7
58.5
58.6
50.3
42.0
49.3
40.2
31.1
60.1
51.0
41.9
32.7
60.8
60.2
51.1
42.0
59.8
59.9
50.8
41.7
52.8
42.8
32.9
64.2
54.3
44.4
34.4
62.2
62.2
52.2
42.3
61.2
61.2
51.2
41.3
105°F
21.7
16.3
29.9
24.5
19.0
38.1
32.6
27.2
21.8
44.7
40.1
34.7
29.3
24.3
17.9
33.3
26.9
20.5
42.3
35.9
29.5
23.2
46.3
44.2
37.8
31.4
44.1
42.1
35.7
29.4
26.8
19.5
36.7
29.3
22.0
46.5
39.2
31.8
24.5
47.9
48.3
40.9
33.6
45.7
45.9
38.6
31.3
29.4
21.1
40.1
31.8
23.5
50.7
42.4
34.1
25.9
49.6
52.4
44.1
35.8
47.2
49.7
41.4
33.2
43.2
34.0
24.9
52.7
45.5
36.3
27.1
49.5
50.9
41.8
32.6
47.2
48.5
39.3
30.1
46.4
36.3
26.3
54.7
48.5
38.5
28.4
49.5
49.5
39.5
29.4
47.2
47.2
37.1
27.1
65
29.7
30.9
31.2
32.1
32.5
33.4
33.7
32.8
32.5
32.3
31.3
23.8
25.1
23.0
26.3
23.9
27.5
24.9
23.4
21.0
19.4
17.0
39
5123247-TTG-A-0515
ZUTA5 (5.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1250
1500
1750
2000
2250
2500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
55.7
49.6
43.5
39.7
57.9
51.6
45.2
41.3
39.4
60.1
53.5
46.9
42.8
40.9
62.3
55.5
48.6
44.4
42.4
55.2
48.4
44.2
42.2
54.9
48.2
44.0
42.0
5.2
5.0
4.9
4.8
5.2
5.1
4.9
4.8
4.9
5.2
5.1
5.0
4.9
4.9
5.3
5.1
5.0
4.9
4.9
5.1
5.0
4.9
4.9
5.2
5.0
4.9
5.0
21.9
32.7
43.5
39.7
28.8
37.0
45.2
41.3
39.4
35.7
41.3
46.9
42.8
40.9
42.7
45.6
48.6
44.4
42.4
49.5
48.4
44.2
42.2
53.5
48.2
44.0
42.0
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
19.2
13.9
48.9
5.6
27.4
22.0
16.7
43.3
5.4
35.5
30.2
24.9
19.5
37.6
5.3
39.7
37.2
31.8
26.5
21.2
34.7
5.1
21.7
15.4
51.1
5.6
30.7
24.4
18.1
45.2
5.5
39.7
33.4
27.1
20.8
39.2
5.3
41.3
41.3
35.0
28.7
22.3
36.2
5.2
39.4
37.9
31.6
25.3
19.0
34.7
5.2
24.1
16.8
53.2
5.7
34.0
26.7
19.4
47.1
5.5
43.9
36.6
29.3
22.0
40.9
5.3
42.8
45.4
38.1
30.8
23.5
37.8
5.2
40.9
41.6
34.3
27.0
19.7
36.2
5.3
26.6
18.3
55.4
5.7
37.4
29.1
20.8
49.0
5.5
48.1
39.8
31.5
23.3
42.5
5.4
44.4
49.5
41.2
33.0
24.7
39.3
5.2
42.4
45.2
36.9
28.7
20.4
37.6
5.3
40.4
31.2
22.1
48.4
5.6
48.1
42.8
33.6
24.5
42.1
5.4
44.2
46.7
37.6
28.4
19.3
38.9
5.3
42.2
43.6
34.5
25.3
16.2
37.2
5.3
43.4
33.4
23.4
47.9
5.6
48.2
45.7
35.7
25.7
41.6
5.4
44.0
44.0
34.0
23.9
13.9
38.5
5.3
42.0
42.0
32.0
22.0
11.9
36.9
5.4
90
22.6
30.1
37.6
34.7
29.5
34.4
39.2
36.2
34.7
36.4
38.6
40.9
37.8
36.2
43.3
42.9
42.5
39.3
37.6
46.7
42.1
38.9
37.2
47.9
41.6
38.5
36.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
15.3
11.5
24.9
19.6
14.4
33.4
27.7
22.5
17.3
34.7
34.7
29.0
23.8
19.1
12.9
28.1
21.9
15.6
37.1
30.9
24.6
18.4
36.2
36.2
32.1
25.9
34.7
33.8
27.5
21.3
22.9
14.2
31.4
24.1
16.9
40.9
34.1
26.8
19.5
37.8
37.8
35.3
28.0
36.2
36.2
30.0
22.7
26.7
15.5
34.6
26.4
18.1
42.5
37.2
28.9
20.7
39.3
39.3
38.4
30.1
37.6
37.6
32.4
24.2
37.6
28.4
19.3
42.1
40.1
31.0
21.8
38.9
38.9
33.4
24.3
37.2
37.2
29.6
20.5
40.5
30.5
20.5
41.6
41.6
33.0
23.0
38.5
38.5
28.4
18.4
36.9
36.9
26.8
16.8
65
18.5
19.6
15.0
20.7
15.5
21.9
15.9
15.1
11.4
8.4
6.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
40
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUT06 (6.5 Ton)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
100.1
92.7
85.4
74.8
105.7
97.9
90.1
79.0
77.8
111.4
103.1
94.8
83.3
82.0
117.0
108.3
99.5
87.5
86.2
110.3
101.4
89.1
87.7
112.3
103.3
90.7
89.3
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.8
4.7
4.7
4.7
4.7
4.8
4.7
4.7
4.7
4.8
4.7
4.7
4.7
4.7
4.7
4.7
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
96.1
86.0
75.9
70.3
98.3
88.0
77.7
71.9
72.8
100.5
89.9
79.4
73.5
74.5
102.6
91.9
81.1
75.1
76.1
95.2
84.0
77.8
78.8
98.5
87.0
80.5
81.6
5.9
5.8
5.8
5.8
6.0
5.9
5.8
5.8
5.7
6.0
5.9
5.8
5.8
5.7
6.0
5.9
5.8
5.8
5.8
5.9
5.8
5.8
5.8
5.9
5.9
5.9
5.8
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
90
85
80
75
70
65
75°F
38.5
33.6
28.8
98.1
5.3
49.4
44.5
39.7
34.9
89.4
5.3
60.2
55.4
50.6
45.7
40.9
80.6
5.2
74.8
69.6
61.2
56.4
51.6
46.7
72.6
5.2
47.6
39.7
31.8
102.0
5.3
59.7
51.8
43.9
35.9
92.9
5.3
71.7
63.8
55.9
48.0
40.1
83.9
5.3
79.0
75.6
67.6
59.7
51.8
43.9
75.5
5.2
77.8
79.4
72.1
64.2
56.3
48.4
75.3
5.2
56.8
45.8
34.8
105.9
5.3
70.0
59.0
48.0
37.0
96.5
5.3
83.2
72.2
61.2
50.2
39.2
87.1
5.3
83.3
81.5
74.1
63.1
52.1
41.1
78.4
5.2
82.0
82.8
78.9
67.9
56.9
46.0
78.2
5.2
66.0
51.9
37.8
109.8
5.3
80.3
66.2
52.2
38.1
100.1
5.3
94.6
80.5
66.5
52.4
38.4
90.3
5.3
87.5
87.5
80.5
66.4
52.4
38.3
81.3
5.2
86.2
86.2
85.7
71.7
57.6
43.6
81.1
5.2
82.3
69.0
55.6
42.3
102.7
5.3
99.0
84.2
70.9
57.6
44.2
92.7
5.3
89.1
89.1
85.6
72.3
58.9
45.6
83.4
5.3
87.7
87.7
87.5
74.2
60.9
47.5
83.3
5.2
84.4
71.7
59.1
46.5
105.4
5.3
103.3 88.0
75.3
62.7
50.1
95.1
5.3
90.7
90.7
90.7
78.1
65.5
52.8
85.6
5.3
89.3
89.3
89.3
76.7
64.1
51.4
85.4
5.3
95°F
41.0
32.2
23.5
87.2
6.5
52.3
43.5
34.8
26.0
78.4
6.3
63.6
54.8
46.1
37.3
28.6
69.5
6.2
70.3
67.6
56.5
47.7
39.0
30.2
63.1
6.1
41.8
33.8
25.8
89.3
6.5
54.3
46.2
38.2
30.2
80.2
6.4
66.7
58.7
50.6
42.6
34.6
71.2
6.3
71.9
70.1
62.1
54.1
46.0
38.0
64.6
6.2
72.8
71.3
63.3
55.3
47.2
39.2
67.1
6.2
42.7
35.4
28.1
91.3
6.5
56.3
49.0
41.7
34.4
82.1
6.4
69.8
62.5
55.2
47.9
40.6
72.8
6.3
73.5
72.6
67.7
60.4
53.1
45.8
66.1
6.2
74.5
73.7
69.0
61.7
54.4
47.1
68.7
6.2
43.6
37.0
30.4
93.4
6.5
58.2
51.7
45.1
38.5
83.9
6.4
72.9
66.3
59.8
53.2
46.6
74.5
6.3
75.1
75.1
73.3
66.7
60.2
53.6
67.5
6.2
76.1
76.1
74.7
68.1
61.6
55.0
70.2
6.2
66.8
57.4
48.0
38.7
86.3
6.5
79.9
73.0
63.7
54.3
45.0
76.6
6.3
77.8
77.8
76.9
67.5
58.2
48.8
69.4
6.2
78.8
78.8
78.1
68.8
59.4
50.1
72.2
6.3
75.3
63.1
51.0
38.8
88.6
6.5
87.0
79.7
67.6
55.4
43.3
78.6
6.4
80.5
80.5
80.5
68.4
56.2
44.1
71.3
6.3
81.6
81.6
81.6
69.4
57.3
45.1
74.1
6.3
90
39.7
50.8
61.9
72.6
44.7
57.0
69.2
75.5
75.3
49.8
63.1
76.5
78.4
78.2
54.8
69.3
83.8
81.3
81.1
74.5
89.4
83.4
83.3
79.8
95.1
85.6
85.4
36.1
48.5
60.8
63.1
39.9
51.9
64.0
64.6
67.1
43.6
55.4
67.2
66.1
68.7
47.4
58.9
70.4
67.5
70.2
65.6
74.5
69.4
72.2
72.3
78.6
71.3
74.1
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
32.9
26.1
44.0
37.2
30.4
55.1
48.3
41.5
34.7
68.6
58.8
52.1
45.3
36.8
28.8
49.0
41.0
33.1
61.2
53.3
45.3
37.3
72.8
64.9
56.9
48.9
75.3
67.7
59.7
51.7
40.6
31.5
54.0
44.8
35.7
67.3
58.2
49.1
39.9
77.1
70.9
61.7
52.6
78.2
74.0
64.8
55.7
44.5
34.1
58.9
48.6
38.3
73.4
63.1
52.8
42.5
81.3
76.9
66.6
56.3
81.1
80.2
69.9
59.6
63.2
51.8
40.5
78.6
67.3
55.9
44.6
83.4
81.2
69.9
58.5
83.3
82.8
71.5
60.1
67.4
55.0
42.7
83.8
71.4
59.1
46.7
85.6
85.6
73.2
60.8
85.4
85.4
73.1
60.7
105°F
29.5
21.5
40.4
32.4
24.4
51.4
43.4
35.4
27.4
61.7
53.8
45.8
37.8
31.7
23.6
43.8
35.7
27.6
55.9
47.8
39.7
31.5
63.7
59.2
51.1
43.0
66.3
58.2
50.1
41.9
34.0
25.8
47.2
38.9
30.7
60.4
52.1
43.9
35.7
65.6
64.6
56.4
48.1
68.3
63.5
55.3
47.0
36.3
27.9
50.6
42.2
33.8
64.8
56.5
48.1
39.8
67.5
70.0
61.6
53.3
70.2
68.8
60.5
52.1
55.3
45.1
34.8
69.9
60.4
50.1
39.9
69.4
70.7
60.4
50.2
72.2
71.5
61.2
51.0
60.1
48.0
35.8
75.0
64.2
52.1
40.0
71.3
71.3
59.2
47.1
74.1
74.1
62.0
49.9
65
38.5
41.0
43.8
43.5
46.5
45.9
49.3
47.2
48.8
48.4
48.3
29.8
34.8
33.8
39.9
38.8
44.9
43.7
39.9
40.7
34.9
37.7
41
5123247-TTG-A-0515
ZUT06 (6.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
78.3
70.7
63.2
55.8
80.3
72.5
64.7
57.2
61.4
82.2
74.2
66.3
58.6
62.9
84.1
76.0
67.9
60.0
64.4
77.4
69.1
61.1
65.6
78.8
70.3
62.2
66.7
7.0
6.8
6.7
6.5
7.0
6.9
6.7
6.6
6.6
7.1
6.9
6.8
6.6
6.7
7.1
7.0
6.8
6.6
6.7
7.0
6.8
6.7
6.7
7.0
6.9
6.7
6.8
31.2
44.7
58.1
55.8
37.9
49.6
61.4
57.2
61.4
44.6
54.6
64.6
58.6
62.9
51.3
59.6
67.9
60.0
64.4
64.4
69.1
61.1
65.6
69.2
70.3
62.2
66.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
26.7
19.5
69.4
7.5
37.4
30.1
22.9
63.1
7.3
48.0
40.8
33.5
26.2
56.8
7.1
55.8
51.1
43.9
36.6
29.3
48.6
6.9
29.7
21.4
71.3
7.6
41.4
33.2
24.9
64.8
7.4
53.1
44.9
36.7
28.5
58.3
7.2
57.2
56.3
48.1
39.9
31.6
49.9
6.9
61.3
53.1
44.9
36.7
28.4
55.7
7.1
32.6
23.4
73.1
7.6
45.4
36.2
27.0
66.4
7.4
58.2
49.1
39.9
30.7
59.7
7.3
58.6
61.5
52.3
43.1
34.0
51.2
7.0
62.9
58.0
48.8
39.6
30.5
57.1
7.1
35.5
25.4
74.9
7.7
49.4
39.3
29.1
68.1
7.5
63.3
53.2
43.1
32.9
61.2
7.3
60.0
66.7
56.6
46.4
36.3
52.4
7.1
64.4
62.9
52.8
42.6
32.5
58.5
7.2
53.3
42.1
31.0
68.5
7.5
66.8
57.0
45.9
34.8
61.6
7.3
61.1
64.4
53.3
42.2
31.0
52.7
7.1
65.6
64.8
53.7
42.5
31.4
58.9
7.2
57.1
45.0
32.9
68.9
7.6
70.3
60.9
48.8
36.6
62.0
7.4
62.2
62.2
50.0
37.9
25.8
53.0
7.1
66.7
66.7
54.6
42.5
30.3
59.3
7.2
90
24.9
40.9
56.8
48.6
36.4
47.3
58.3
49.9
55.7
47.8
53.8
59.7
51.2
57.1
59.3
60.2
61.2
52.4
58.5
63.2
61.6
52.7
58.9
66.2
62.0
53.0
59.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
23.7
17.5
34.3
27.8
21.3
44.7
38.1
31.6
25.1
48.6
48.6
41.9
35.4
27.6
19.3
39.0
30.7
22.3
50.4
42.1
33.7
25.4
49.9
49.9
45.1
36.8
55.7
48.0
39.7
31.4
31.5
21.1
43.6
33.5
23.4
56.1
46.0
35.9
25.7
51.2
51.2
48.3
38.2
57.1
52.5
42.4
32.3
35.4
22.9
48.3
36.4
24.5
61.2
49.9
38.0
26.0
52.4
52.4
51.5
39.6
58.5
57.0
45.1
33.1
51.2
39.2
27.2
61.6
53.7
41.7
29.7
52.7
52.7
46.2
34.2
58.9
58.2
46.1
34.1
54.1
42.0
29.9
62.0
57.6
45.5
33.3
53.0
53.0
40.9
28.8
59.3
59.3
47.2
35.1
65
28.9
28.5
23.1
28.0
22.1
27.6
21.2
22.1
22.1
16.7
23.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
42
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUT07 (7.5 Ton)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
113.8
106.0
98.1
86.5
121.4
112.9
104.5
92.2
90.4
128.9
119.9
110.9
97.9
96.1
136.5
126.9
117.3
103.6
101.8
128.9
119.1
105.2
103.4
130.9
121.0
106.8
104.9
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.9
5.9
5.8
5.8
5.8
5.9
5.9
5.9
5.8
5.8
5.9
5.8
5.8
5.8
5.8
5.8
49.0
62.6
76.2
86.5
54.8
69.7
84.6
92.2
90.4
60.6
76.8
93.0
97.9
96.1
66.4
83.9
101.4
103.6
101.8
88.3
110.1
105.2
103.4
92.7
118.7
106.8
104.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
110.3
99.9
89.5
81.3
112.2
101.6
91.0
82.7
84.9
114.1
103.3
92.5
84.1
86.3
115.9
105.0
94.0
85.5
87.8
108.3
97.0
88.2
90.5
111.6
100.0
90.9
93.3
7.1
7.0
7.0
6.9
7.1
7.1
7.0
6.9
6.9
7.2
7.1
7.0
6.9
6.9
7.2
7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.2
7.1
7.0
7.0
44.2
57.2
70.2
81.3
49.0
63.2
77.4
82.7
84.9
53.8
69.2
84.6
84.1
86.3
58.6
75.2
91.7
85.5
87.8
81.4
95.9
88.2
90.5
87.7
100.0
90.9
93.3
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
41.0
33.1
112.1
6.5
54.6
46.7
38.7
102.9
6.4
68.3
60.3
52.3
44.4
93.8
6.4
80.4
71.9
64.0
56.0
48.1
83.9
6.4
45.5
36.3
116.8
6.5
60.4
51.2
41.9
107.3
6.4
75.3
66.1
56.8
47.5
97.7
6.4
88.1
78.8
69.6
60.3
51.0
87.5
6.4
91.7
85.4
76.2
66.9
57.6
87.7
6.4
50.0
39.4
121.5
6.5
66.2
55.6
45.0
111.6
6.5
82.4
71.9
61.3
50.7
101.7
6.4
95.8
85.7
75.1
64.5
54.0
91.0
6.4
96.8
92.9
82.3
71.7
61.1
91.2
6.4
54.5
42.6
126.2
6.5
72.0
60.1
48.2
115.9
6.5
89.5
77.6
65.7
53.8
105.6
6.5
103.6 92.6
80.7
68.8
56.9
94.5
6.4
101.8 100.4 88.5
76.6
64.6
94.8
6.4
75.7
63.2
50.6
118.6
6.5
94.1
81.6
69.0
56.4
108.1
6.5
105.2 99.6
87.0
74.4
61.8
96.7
6.4
103.4 102.6 90.1
77.5
64.9
96.9
6.4
79.5
66.2
53.0
121.2
6.5
98.7
85.5
72.2
59.0
110.5
6.5
106.8 106.5 93.2
80.0
66.7
98.9
6.4
104.9 104.9 91.7
78.4
65.2
99.1
6.4
95°F
36.2
28.1
103.5
7.7
49.2
41.1
33.0
93.1
7.6
62.2
54.1
46.0
37.9
82.7
7.5
77.5
65.0
57.0
48.9
40.8
78.3
7.4
39.8
30.7
103.5
7.8
54.0
44.9
35.7
93.1
7.7
68.2
59.1
49.9
40.7
82.7
7.5
80.2
71.0
61.8
52.7
43.5
78.2
7.4
83.7
74.5
65.3
56.1
47.0
80.0
7.4
43.5
33.2
103.5
7.8
58.9
48.6
38.4
93.1
7.7
74.3
64.0
53.8
43.5
82.7
7.6
82.8
77.0
66.7
56.4
46.2
78.2
7.5
85.7
80.8
70.5
60.2
49.9
79.9
7.5
47.2
35.8
103.4
7.9
63.8
52.4
41.0
93.1
7.7
80.4
69.0
57.6
46.3
82.7
7.6
85.5
83.0
71.6
60.2
48.8
78.1
7.5
87.8
87.0
75.7
64.3
52.9
79.9
7.5
68.9
56.4
43.8
97.2
7.8
86.7
74.2
61.7
49.1
86.4
7.6
88.2
86.9
74.4
61.9
49.3
81.6
7.5
90.5
90.2
77.7
65.1
52.6
83.5
7.5
74.0
60.3
46.6
101.3
7.8
93.1
79.4
65.7
52.0
90.0
7.7
90.9
90.9
77.2
63.5
49.9
85.1
7.5
93.3
93.3
79.7
66.0
52.3
87.0
7.5
90
46.6
59.9
73.2
83.9
51.9
66.5
81.0
87.5
87.7
57.2
73.0
88.8
91.0
91.2
62.5
79.5
96.6
94.5
94.8
84.9
103.0
96.7
96.9
90.2
109.4
98.9
99.1
38.5
54.2
69.8
78.3
45.5
59.6
73.7
78.2
80.0
52.4
65.0
77.6
78.2
79.9
59.4
70.5
81.6
78.1
79.9
76.7
85.8
81.6
83.5
82.8
90.0
85.1
87.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
38.6
30.6
51.9
43.9
35.9
65.2
57.2
49.2
41.2
79.0
68.5
60.5
52.5
42.7
33.5
57.2
48.0
38.8
71.8
62.6
53.3
44.1
84.1
74.9
65.7
56.5
87.7
80.0
70.7
61.5
46.8
36.3
62.6
52.1
41.7
78.4
67.9
57.5
47.1
89.3
81.4
70.9
60.5
91.2
86.8
76.4
66.0
50.8
39.2
67.9
56.3
44.6
85.0
73.3
61.7
50.0
94.5
87.8
76.1
64.5
94.8
93.7
82.1
70.4
72.3
59.8
47.2
90.4
77.9
65.3
52.8
96.7
93.2
80.7
68.1
96.9
96.4
83.9
71.3
76.7
63.3
49.8
95.9
82.4
69.0
55.5
98.9
98.7
85.2
71.8
99.1
99.1
85.7
72.2
105°F
33.2
25.2
46.2
38.2
30.3
59.2
51.2
43.3
35.3
75.8
62.2
54.2
46.2
36.5
27.4
50.6
41.5
32.5
64.7
55.7
46.6
37.6
76.6
67.5
58.5
49.5
78.7
69.7
60.7
51.6
39.7
29.6
54.9
44.8
34.7
70.2
60.1
50.0
39.9
77.4
72.9
62.8
52.7
79.3
75.2
65.1
55.0
43.0
31.8
59.3
48.1
37.0
75.7
64.5
53.3
42.1
78.1
78.2
67.1
55.9
79.9
80.8
69.6
58.4
64.4
52.1
39.8
81.1
69.8
57.5
45.2
81.6
81.7
69.4
57.1
83.5
83.9
71.6
59.3
69.4
56.0
42.6
86.6
75.0
61.6
48.2
85.1
85.1
71.7
58.3
87.0
87.0
73.6
60.2
65
44.4
47.3
52.3
50.1
55.5
52.9
58.8
55.6
58.8
58.3
58.7
38.3
40.4
42.6
42.6
44.9
44.7
47.2
44.8
47.0
44.9
46.8
43
5123247-TTG-A-0515
ZUT07 (7.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
96.7
86.3
75.9
75.3
94.8
84.6
74.4
73.8
75.0
92.9
82.9
72.9
72.3
73.5
91.0
81.2
71.4
70.8
72.0
86.1
75.7
75.1
76.4
91.0
80.1
79.4
80.7
8.4
8.2
8.0
7.9
8.4
8.2
8.1
7.9
7.9
8.5
8.3
8.1
8.0
8.0
8.5
8.3
8.2
8.0
8.0
8.4
8.2
8.1
8.1
8.4
8.2
8.1
8.1
32.9
51.1
69.4
75.3
42.0
56.0
70.0
73.8
75.0
51.1
60.9
70.7
72.3
73.5
60.2
65.8
71.4
70.8
72.0
71.9
75.7
75.1
76.4
78.0
80.1
79.4
80.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
30.3
22.4
89.9
9.0
43.3
35.4
27.5
79.5
8.8
56.2
48.4
40.5
32.6
69.1
8.5
74.0
59.3
51.5
43.6
35.7
72.2
8.4
33.1
24.2
86.1
9.1
47.1
38.2
29.3
76.1
8.8
61.1
52.2
43.3
34.4
66.1
8.6
73.0
64.1
55.2
46.3
37.4
69.3
8.4
73.8
64.9
56.0
47.1
38.2
70.1
8.5
35.9
26.0
82.3
9.1
51.0
41.0
31.1
72.7
8.9
66.0
56.1
46.2
36.2
63.1
8.6
71.9
68.8
58.9
48.9
39.0
66.4
8.5
72.9
69.7
59.8
49.8
39.9
67.1
8.5
38.7
27.8
78.5
9.2
54.8
43.9
32.9
69.3
8.9
70.9
60.0
49.0
38.0
60.1
8.7
70.8
73.5
62.6
51.6
40.6
63.5
8.5
72.0
74.5
63.5
52.5
41.6
64.1
8.6
59.9
47.8
35.7
75.0
9.0
75.5
65.3
53.3
41.2
65.1
8.7
75.1
76.5
64.4
52.3
40.3
68.6
8.6
76.4
77.6
65.5
53.5
41.4
69.3
8.6
64.9
51.7
38.5
80.7
9.0
80.1
70.7
57.5
44.4
70.1
8.8
79.4
79.4
66.2
53.1
39.9
73.6
8.6
80.7
80.7
67.6
54.4
41.2
74.4
8.6
90
27.0
48.1
69.1
72.2
38.7
52.4
66.1
69.3
70.1
50.5
56.8
63.1
66.4
67.1
62.2
61.2
60.1
63.5
64.1
67.2
65.1
68.6
69.3
73.2
70.1
73.6
74.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
24.2
19.6
40.3
32.5
24.8
53.3
45.5
37.8
30.0
72.2
56.5
48.7
40.9
29.7
20.9
43.7
34.9
26.1
57.6
48.8
40.1
31.3
69.3
60.6
51.8
43.1
68.9
60.1
51.3
42.6
35.2
22.3
47.0
37.2
27.5
61.9
52.1
42.4
32.6
66.4
64.7
54.9
45.2
66.5
64.2
54.4
44.6
40.6
23.7
50.4
39.6
28.8
60.1
55.5
44.7
33.9
63.5
63.5
58.1
47.3
64.1
64.1
57.5
46.7
55.3
43.5
31.7
65.1
60.9
49.1
37.2
68.6
68.6
59.4
47.5
69.3
69.3
59.5
47.6
60.3
47.4
34.5
70.1
66.3
53.4
40.5
73.6
73.6
60.7
47.8
74.4
74.4
61.5
48.6
65
33.2
34.3
33.8
35.4
34.8
36.5
35.9
35.7
35.8
34.9
35.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
44
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUT08 (8.5 Ton)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
136.4
127.5
118.6
103.1
142.1
132.8
123.4
107.3
103.7
147.8
138.0
128.1
111.6
107.8
153.6
143.2
132.9
115.8
111.9
145.4
135.0
117.5
113.5
147.6
137.0
119.3
115.2
6.4
6.3
6.3
6.3
6.4
6.3
6.3
6.4
6.3
6.4
6.4
6.3
6.4
6.3
6.4
6.4
6.3
6.4
6.3
6.4
6.3
6.4
6.3
6.4
6.3
6.4
6.3
58.7
74.7
90.7
103.1
65.3
82.7
100.2
107.3
103.7
71.8
90.7
109.6
111.6
107.8
78.4
98.7
119.0
115.8
111.9
105.1
128.0
117.5
113.5
111.5
137.0
119.3
115.2
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
133.1
118.2
103.3
95.6
134.7
119.6
104.5
96.7
93.6
136.3
121.0
105.8
97.8
94.7
137.9
122.4
107.0
99.0
95.8
125.8
109.9
101.7
98.4
129.2
112.9
104.4
101.0
7.7
7.6
7.6
7.4
7.7
7.7
7.6
7.5
7.5
7.8
7.7
7.7
7.5
7.6
7.8
7.8
7.7
7.6
7.6
7.8
7.7
7.6
7.6
7.8
7.8
7.6
7.7
56.1
69.6
83.1
95.6
61.8
76.3
90.8
96.7
93.6
67.5
83.0
98.5
97.8
94.7
73.2
89.7
106.2
99.0
95.8
96.9
109.5
101.7
98.4
104.1
112.9
104.4
101.0
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
49.1
39.5
134.8
7.0
65.1
55.5
45.9
122.9
7.0
81.1
71.5
61.9
52.3
111.0
6.9
94.8
83.2
73.6
64.0
54.4
99.3
6.9
54.2
43.1
138.4
7.1
71.6
60.6
49.5
126.2
7.0
89.1
78.0
66.9
55.8
114.0
6.9
101.8 90.7
79.6
68.6
57.5
102.0
6.9
103.7 95.2
84.1
73.1
62.0
98.6
6.9
59.3
46.7
142.1
7.1
78.1
65.6
53.0
129.5
7.0
97.0
84.5
71.9
59.4
117.0
7.0
108.8 98.3
85.7
73.2
60.6
104.7
7.0
107.8 103.1 90.6
78.0
65.5
101.2
6.9
64.3
50.3
145.7
7.1
84.7
70.6
56.6
132.8
7.1
105.0 91.0
76.9
62.9
120.0
7.0
115.8 105.8 91.8
77.7
63.7
107.4
7.0
111.9 111.0 97.0
83.0
68.9
103.8
7.0
89.8
74.5
59.1
135.6
7.1
111.2 95.9
80.6
65.3
122.5
7.0
117.5 112.6 97.2
81.9
66.6
109.6
7.0
113.5 113.1 97.8
82.5
67.2
106.0
7.0
94.9
78.3
61.7
138.4
7.1
117.5 100.9 84.2
67.6
124.9
7.0
119.3 119.3 102.7 86.1
69.5
111.8
7.0
115.2 115.2 98.6
82.0
65.4
108.1
7.0
95°F
46.7
37.3
116.2
8.5
60.2
50.8
41.4
104.5
8.3
73.7
64.3
54.9
45.5
92.7
8.2
91.1
77.1
67.7
58.3
48.9
84.7
8.0
50.9
40.0
118.6
8.5
65.4
54.5
43.6
106.6
8.4
79.9
69.0
58.1
47.2
94.6
8.2
93.7
82.8
71.9
61.0
50.1
86.5
8.1
93.6
84.4
73.5
62.6
51.7
84.8
8.1
55.1
42.7
121.0
8.6
70.6
58.2
45.8
108.8
8.4
86.1
73.7
61.3
48.9
96.5
8.3
96.3
88.5
76.1
63.7
51.3
88.3
8.1
94.7
90.2
77.8
65.4
53.0
86.5
8.2
59.4
45.5
123.4
8.6
75.8
62.0
48.1
110.9
8.5
92.3
78.4
64.5
50.7
98.5
8.3
99.0
94.1
80.2
66.4
52.5
90.0
8.2
95.8
95.9
82.1
68.2
54.3
88.3
8.2
81.7
66.6
51.4
112.9
8.5
99.4
84.2
69.1
53.9
100.2
8.4
101.7 99.3
84.1
68.9
53.7
91.6
8.2
98.4
98.5
83.3
68.1
52.9
89.8
8.3
87.6
71.2
54.7
114.8
8.6
106.6 90.1
73.6
57.1
101.9
8.4
104.4 104.4 87.9
71.4
54.9
93.1
8.3
101.0 101.0 84.5
68.0
51.5
91.3
8.3
90
57.4
72.2
86.9
99.3
63.5
79.5
95.5
102.0
98.6
69.7
86.9
104.0
104.7
101.2
75.8
94.2
112.6
107.4
103.8
101.0
118.8
109.6
106.0
107.8
124.9
111.8
108.1
48.4
63.9
79.5
84.7
56.1
70.9
85.7
86.5
84.8
63.9
77.9
91.9
88.3
86.5
71.6
84.8
98.1
90.0
88.3
91.2
100.0
91.6
89.8
97.6
101.9
93.1
91.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
47.9
38.4
62.7
53.1
43.6
77.4
67.9
58.4
48.9
92.9
80.2
70.6
61.1
52.6
41.6
68.5
57.5
46.5
84.5
73.5
62.5
51.5
97.8
86.8
75.8
64.8
98.6
89.8
78.8
67.8
57.2
44.7
74.4
61.9
49.4
91.6
79.1
66.6
54.1
102.6 93.4
80.9
68.4
101.2 96.7
84.2
71.7
61.8
47.9
80.2
66.3
52.3
98.6
84.7
70.7
56.8
107.4 100.0 86.0
72.0
103.8 103.5 89.5
75.6
85.8
70.5
55.2
105.3 90.1
74.8
59.6
109.6 105.9 90.7
75.4
106.0 105.8 90.6
75.3
91.3
74.7
58.2
112.0 95.5
78.9
62.4
111.8 111.8 95.3
78.7
108.1 108.1 91.6
75.0
105°F
41.1
31.9
54.7
45.5
36.2
68.3
59.0
49.8
40.5
82.5
69.4
60.1
50.9
45.3
34.6
60.1
49.3
38.5
74.9
64.1
53.3
42.5
85.0
75.3
64.5
53.7
84.8
76.0
65.2
54.4
49.6
37.3
65.5
53.2
40.9
81.5
69.2
56.8
44.5
87.5
81.2
68.9
56.5
86.5
82.0
69.6
57.3
53.8
39.9
71.0
57.1
43.2
88.1
74.2
60.3
46.5
90.0
87.1
73.2
59.4
88.3
87.9
74.1
60.2
76.2
61.1
46.1
93.4
79.5
64.4
49.4
91.6
90.1
75.1
60.0
89.8
89.6
74.6
59.5
81.4
65.2
49.0
98.7
84.7
68.5
52.3
93.1
93.1
76.9
60.7
91.3
91.3
75.1
58.9
65
51.6
53.8
56.8
55.9
59.2
58.1
61.6
60.1
60.0
62.2
58.5
41.6
42.9
43.6
44.2
45.0
45.5
46.3
45.0
44.5
44.5
42.7
45
5123247-TTG-A-0515
ZUT08 (8.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
99.3
90.7
82.0
73.9
102.5
93.6
84.7
76.3
76.1
105.7
96.5
87.3
78.7
78.4
108.9
99.4
90.0
81.1
80.8
99.9
90.4
81.5
81.2
100.4
90.8
81.9
81.6
9.3
9.0
8.8
8.6
9.4
9.1
8.8
8.7
8.7
9.4
9.1
8.9
8.7
8.8
9.5
9.2
8.9
8.8
8.8
9.3
9.0
8.9
8.9
9.4
9.1
9.0
9.0
40.7
58.3
75.8
73.9
50.5
65.5
80.5
76.3
76.1
60.2
72.7
85.3
78.7
78.4
69.9
79.9
90.0
81.1
80.8
85.5
90.4
81.5
81.2
91.0
90.8
81.9
81.6
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
35.5
26.4
82.4
10.1
49.2
40.1
31.0
76.9
9.7
62.9
53.8
44.7
35.6
71.4
9.4
73.9
61.6
52.5
43.4
34.3
63.1
9.2
39.8
29.1
86.4
10.2
54.8
44.1
33.5
80.6
9.8
69.9
59.2
48.5
37.8
74.8
9.4
76.3
67.7
57.1
46.4
35.7
66.1
9.3
76.1
67.6
56.9
46.2
35.6
67.3
9.3
44.0
31.8
90.4
10.2
60.5
48.2
35.9
84.3
9.8
76.9
64.6
52.3
40.0
78.1
9.5
78.7
73.9
61.7
49.4
37.1
69.1
9.3
78.4
73.8
61.5
49.2
36.9
70.3
9.4
48.3
34.4
94.4
10.3
66.1
52.2
38.3
87.9
9.9
83.9
70.0
56.1
42.3
81.5
9.5
81.1
80.1
66.2
52.4
38.5
72.1
9.4
80.8
79.9
66.0
52.2
38.3
73.3
9.4
70.6
55.7
40.8
87.0
10.0
87.4
74.7
59.8
44.9
80.6
9.6
81.5
81.0
66.1
51.2
36.3
71.4
9.5
81.2
80.8
65.9
51.0
36.1
72.6
9.6
75.1
59.2
43.3
86.0
10.1
90.8
79.4
63.5
47.6
79.8
9.8
81.9
81.9
66.0
50.1
34.2
70.6
9.6
81.6
81.6
65.7
49.8
33.9
71.9
9.7
90
33.8
52.6
71.4
63.1
45.4
60.1
74.8
66.1
67.3
57.1
67.6
78.1
69.1
70.3
68.7
75.1
81.5
72.1
73.3
79.8
80.6
71.4
72.6
84.5
79.8
70.6
71.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
29.9
21.0
43.7
34.8
25.9
57.5
48.5
39.6
30.7
63.1
53.8
44.9
35.9
34.2
23.7
49.5
39.0
28.4
64.9
54.3
43.7
33.2
66.1
60.2
49.7
39.1
67.3
59.2
48.6
38.0
38.5
26.3
55.4
43.2
30.9
72.3
60.0
47.8
35.6
69.1
66.7
54.4
42.2
70.3
65.5
53.3
41.1
42.8
28.9
61.2
47.3
33.5
79.6
65.8
51.9
38.1
72.1
72.1
59.2
45.4
73.3
71.9
58.0
44.2
65.0
50.3
35.6
80.6
69.9
55.2
40.5
71.4
71.4
57.1
42.4
72.6
71.9
57.2
42.4
68.9
53.3
37.6
79.8
74.1
58.5
42.9
70.6
70.6
55.0
39.4
71.9
71.9
56.3
40.7
65
27.0
28.5
27.5
30.0
28.9
31.5
30.3
27.6
27.7
23.8
25.1
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
46
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUT10 (10 Ton)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
148.4
138.6
128.8
119.6
155.1
144.8
134.6
124.9
122.1
161.8
151.1
140.3
130.3
127.3
168.5
157.3
146.1
135.7
132.6
157.8
146.6
136.1
133.0
158.3
147.1
136.6
133.4
7.2
7.0
6.7
6.7
7.2
7.0
6.7
6.7
6.7
7.2
6.9
6.7
6.7
6.7
7.2
6.9
6.7
6.6
6.6
7.0
6.8
6.8
6.8
7.2
6.9
6.9
6.9
37.9
56.2
74.4
103.4
54.6
74.7
94.8
114.1
116.9
71.2
93.2
115.1
124.9
124.7
87.9
111.7
135.4
135.7
132.6
102.0
126.3
136.1
133.0
92.4
117.2
136.6
133.4
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
142.1
129.8
117.5
110.7
146.4
133.7
121.1
114.0
111.4
150.6
137.6
124.6
117.3
114.6
154.9
141.5
128.1
120.7
117.9
142.7
129.1
121.6
118.8
143.8
130.2
122.6
119.8
8.5
8.5
8.5
8.4
8.5
8.5
8.6
8.5
8.5
8.5
8.6
8.6
8.5
8.5
8.6
8.6
8.6
8.5
8.5
8.6
8.6
8.5
8.5
8.6
8.6
8.5
8.5
32.5
50.0
67.4
97.7
49.2
68.3
87.5
105.4
105.8
65.8
86.7
107.6
113.0
111.9
82.5
105.1
127.6
120.7
117.9
95.3
118.5
121.6
118.8
85.5
109.4
122.6
119.8
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
39.0
40.1
145.3
7.9
57.2
58.3
59.4
134.2
7.7
75.5
76.5
77.6
78.7
123.2
7.6
95.5
94.1
95.2
96.2
97.3
115.1
7.6
49.4
44.1
150.7
7.9
69.4
64.2
59.0
139.3
7.8
89.5
84.3
79.0
73.8
127.8
7.6
108.9 103.6 98.4
93.2
87.9
119.5
7.6
111.7 106.4 101.2 95.9
90.7
116.7
7.6
59.7
48.2
156.2
7.9
81.6
70.1
58.6
144.3
7.8
103.6 92.0
80.5
68.9
132.5
7.6
122.3 113.2 101.6 90.1
78.6
123.8
7.6
122.1 116.2 104.7 93.1
81.6
121.0
7.6
70.1
52.2
161.7
7.9
93.8
76.0
58.2
149.4
7.8
117.6 99.8
81.9
64.1
137.1
7.7
135.7 122.7 104.9 87.0
69.2
128.2
7.6
132.6 126.0 108.1 90.3
72.5
125.2
7.6
89.8
77.6
65.4
150.2
7.8
114.1 101.9 89.7
77.5
137.9
7.7
136.1 125.3 113.1 100.9 88.7
128.9
7.6
133.0 128.9 116.7 104.5 92.3
125.9
7.6
85.8
79.3
72.7
151.1
7.9
110.6 104.1 97.5
91.0
138.6
7.8
136.6 128.0 121.4 114.9 108.3
129.6
7.7
133.4 131.8 125.2 118.6 112.1
126.6
7.7
95°F
34.3
36.0
130.2
9.7
51.7
53.4
55.2
120.3
9.7
69.2
70.9
72.6
74.4
110.4
9.7
90.5
87.2
88.9
90.7
92.4
104.5
9.6
44.3
39.5
133.8
9.8
63.5
58.7
53.8
123.6
9.7
82.7
77.8
73.0
68.1
113.4
9.7
100.5 95.7
90.8
86.0
81.2
107.3
9.6
101.0 96.2
91.3
86.5
81.6
104.7
9.6
54.4
43.0
137.3
9.8
75.3
63.9
52.4
126.9
9.8
96.1
84.7
73.3
61.9
116.5
9.7
110.6 104.2 92.8
81.3
69.9
110.2
9.7
109.4 104.7 93.3
81.9
70.4
107.4
9.6
64.5
46.5
140.9
9.8
87.1
69.1
51.1
130.2
9.8
109.6 91.6
73.6
55.6
119.5
9.8
120.7 112.7 94.7
76.7
58.7
113.0
9.7
117.9 113.2 95.2
77.2
59.2
110.2
9.6
83.2
71.2
59.1
131.2
9.8
106.5 94.4
82.3
70.3
120.4
9.8
121.6 116.1 104.0 92.0
79.9
113.9
9.7
118.8 116.5 104.5 92.4
80.3
111.0
9.6
79.4
73.3
67.1
132.2
9.8
103.3 97.2
91.1
84.9
121.3
9.8
122.6 119.5 113.4 107.3 101.1
114.8
9.7
119.8 119.8 113.7 107.5 101.4
111.9
9.6
90
35.2
53.1
70.9
100.5
51.9
71.5
91.1
109.7
111.4
68.5
89.9
111.3
118.9
118.3
85.2
108.4
131.5
128.2
125.2
98.7
122.4
128.9
125.9
89.0
113.3
129.6
126.6
26.3
46.3
66.3
92.5
45.2
64.6
84.0
99.4
99.7
64.0
82.8
101.6
106.2
105.0
82.8
101.0
119.2
113.0
110.2
91.1
112.4
113.9
111.0
81.2
105.5
114.8
111.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
36.6
38.0
54.5
55.9
57.3
72.3
73.7
75.1
76.5
93.0
90.7
92.1
93.5
46.8
41.8
66.5
61.4
56.4
86.1
81.0
76.0
71.0
104.7 99.7
94.6
89.6
106.3 101.3 96.3
91.2
57.1
45.6
78.5
67.0
55.5
99.8
88.4
76.9
65.4
116.4 108.7 97.2
85.7
115.8 110.4 99.0
87.5
67.3
49.4
90.4
72.5
54.6
113.6 95.7
77.8
59.9
128.2 117.7 99.8
81.8
125.2 119.6 101.7 83.8
86.5
74.4
62.3
110.3 98.2
86.0
73.9
128.9 120.7 108.6 96.5
125.9 122.7 110.6 98.4
82.6
76.3
69.9
107.0 100.6 94.3
87.9
129.6 123.8 117.4 111.1
126.6 125.8 119.4 113.1
105°F
30.7
32.7
48.4
50.4
52.5
66.1
68.2
70.2
72.3
85.6
82.2
84.3
86.3
40.5
35.9
59.9
55.3
50.6
79.3
74.7
70.0
65.4
94.7
90.1
85.4
80.8
95.1
90.4
85.8
81.1
50.3
39.0
71.4
60.1
48.7
92.5
81.2
69.8
58.5
103.9 97.9
86.6
75.2
102.6 98.3
87.0
75.6
60.2
42.1
83.0
64.9
46.8
105.7 87.7
69.6
51.6
113.0 105.8 87.7
69.7
110.2 106.2 88.1
70.1
79.1
67.1
55.1
102.7 90.7
78.7
66.7
113.9 109.4 97.4
85.4
111.0 109.0 97.1
85.1
75.3
69.4
63.4
99.6
93.7
87.8
81.9
114.8 113.0 107.1 101.2
111.9 111.9 106.0 100.1
65
94.9
84.5
86.2
74.2
76.0
63.9
65.8
84.3
86.3
104.7
106.7
88.4
76.1
76.5
63.9
64.3
51.6
52.0
73.5
73.1
95.3
94.2
47
5123247-TTG-A-0515
ZUT10 (10 Ton) (Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
118.3
110.8
103.3
98.3
121.2
113.5
105.8
100.7
97.9
124.0
116.2
108.3
103.0
100.2
126.9
118.9
110.8
105.4
102.5
119.7
111.6
106.2
103.3
120.5
112.4
106.9
104.0
11.0
10.9
10.9
10.8
11.0
10.9
10.9
10.8
10.7
11.0
10.9
10.9
10.8
10.7
11.0
11.0
10.9
10.8
10.7
10.9
10.9
10.8
10.7
10.9
10.9
10.8
10.7
20.1
42.7
65.2
87.3
41.1
60.8
80.4
93.4
93.6
62.1
78.9
95.6
99.4
98.1
83.1
97.0
110.8
105.4
102.5
86.9
106.2
106.2
103.3
76.8
101.6
106.9
104.0
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
27.1
29.5
106.4
12.3
45.0
47.4
49.8
101.3
12.2
63.0
65.4
67.8
70.2
96.2
12.0
80.7
77.2
79.6
82.0
84.4
92.1
12.0
36.7
32.2
108.6
12.3
56.3
51.9
47.4
103.4
12.1
76.0
71.5
67.1
62.6
98.2
12.0
88.9
84.5
80.0
75.6
71.1
94.0
12.0
89.1
84.7
80.2
75.8
71.3
91.2
11.8
46.3
35.0
110.7
12.3
67.6
56.3
45.0
105.5
12.1
88.9
77.6
66.3
55.0
100.2
12.0
97.2
91.7
80.4
69.1
57.8
95.9
12.0
95.8
91.9
80.6
69.4
58.1
93.0
11.8
55.8
37.7
112.9
12.3
78.8
60.7
42.6
107.5
12.1
101.8 83.7
65.6
47.5
102.2
12.0
105.4 98.9
80.8
62.6
44.5
97.8
12.0
102.5 99.2
81.0
62.9
44.8
94.9
11.8
75.0
63.1
51.2
108.2
12.1
98.9
87.0
75.1
63.2
102.8
12.0
106.2 102.7 90.8
78.9
67.0
98.4
12.0
103.3 101.6 89.7
77.8
65.9
95.5
11.8
71.1
65.5
59.8
108.9
12.1
95.9
90.2
84.6
78.9
103.5
12.0
106.9 106.6 100.9 95.2
89.5
99.0
12.0
104.0 104.0 98.3
92.6
86.9
96.1
11.8
90
13.8
39.0
64.1
82.1
37.1
57.0
76.9
87.3
87.5
60.4
75.0
89.7
92.6
91.2
83.6
92.9
102.2
97.8
94.9
82.7
100.1
98.4
95.5
72.5
97.7
99.0
96.1
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
23.5
26.2
41.7
44.4
47.1
59.9
62.6
65.4
68.1
75.7
72.3
75.0
77.7
32.8
28.6
52.7
48.5
44.2
72.6
68.4
64.1
59.8
83.1
78.8
74.6
70.3
83.2
79.0
74.7
70.4
42.2
31.0
63.7
52.5
41.3
85.3
74.1
62.8
51.6
90.4
85.4
74.2
63.0
89.1
85.5
74.3
63.1
51.5
33.3
74.7
56.6
38.4
98.0
79.8
61.6
43.4
97.8
92.0
73.8
55.6
94.9
92.1
73.9
55.8
70.9
59.1
47.2
95.1
83.3
71.4
59.6
98.4
96.0
84.2
72.4
95.5
94.1
82.3
70.5
67.0
61.5
56.1
92.2
86.8
81.3
75.8
99.0
99.0
94.6
89.2
96.1
96.1
90.6
85.2
65
80.4
66.1
66.2
51.8
51.9
37.4
37.6
60.6
58.6
83.7
79.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
48
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUT12 (12.5 Ton)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
204.4
186.6
168.8
153.0
210.2
191.8
173.5
157.2
152.9
215.9
197.1
178.3
161.5
157.1
221.6
202.3
183.0
165.8
161.2
206.6
186.9
169.3
164.7
210.9
190.8
172.9
168.1
9.6
9.3
9.1
9.0
9.7
9.4
9.1
9.0
8.9
9.7
9.4
9.2
9.1
9.0
9.8
9.5
9.2
9.1
9.0
9.5
9.2
9.2
9.0
9.5
9.3
9.2
9.0
82.4
106.6
130.7
153.0
89.0
114.7
140.4
157.2
152.9
95.5
122.8
150.1
161.5
157.1
102.1
130.9
159.8
165.8
161.2
140.7
174.9
169.3
164.7
150.5
190.0
172.9
168.1
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
180.0
165.5
151.0
136.9
184.8
169.9
155.0
140.5
141.0
189.6
174.3
159.0
144.2
144.6
194.4
178.7
163.0
147.8
148.3
180.4
164.5
149.2
149.7
182.1
166.1
150.6
151.1
11.6
11.4
11.3
11.0
11.7
11.5
11.4
11.1
11.0
11.8
11.6
11.5
11.2
11.1
11.9
11.7
11.6
11.3
11.2
11.7
11.6
11.3
11.2
11.8
11.6
11.3
11.3
71.9
94.9
117.8
136.9
79.6
104.6
129.6
140.5
141.0
87.3
114.3
141.4
144.2
144.6
94.9
124.1
153.2
147.8
148.3
131.9
159.6
149.2
149.7
139.7
166.1
150.6
151.1
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
68.5
54.6
192.2
10.6
92.6
78.7
64.8
176.1
10.4
116.8 102.9 88.9
75.0
159.9
10.2
143.5 127.2 113.3 99.4
85.5
144.9
10.0
73.6
58.1
197.5
10.7
99.3
83.9
68.4
180.9
10.5
125.0 109.6 94.2
78.7
164.3
10.2
150.9 135.5 120.1 104.7 89.3
148.9
10.1
152.9 144.1 128.7 113.3 97.8
146.9
10.0
78.6
61.7
202.8
10.8
105.9 89.0
72.1
185.7
10.5
133.2 116.3 99.4
82.5
168.6
10.3
158.4 143.8 126.9 110.0 93.1
152.8
10.1
157.1 152.9 136.0 119.1 102.2
150.8
10.1
83.7
65.3
208.0
10.8
112.6 94.2
75.8
190.5
10.6
141.4 123.0 104.6 86.2
173.0
10.4
165.8 152.1 133.7 115.3 96.9
156.8
10.2
161.2 161.8 143.4 125.0 106.6
154.8
10.1
121.0 101.3 81.6
193.5
10.6
152.0 132.3 112.6 92.9
175.7
10.4
169.3 162.5 142.8 123.1 103.4
159.3
10.2
164.7 165.0 145.3 125.6 105.8
157.2
10.1
129.4 108.4 87.4
196.5
10.6
162.7 141.6 120.6 99.6
178.4
10.4
172.9 172.9 151.8 130.8 109.8
161.7
10.2
168.1 168.1 147.1 126.1 105.0
159.6
10.2
95°F
58.7
45.5
169.2
13.1
81.7
68.5
55.2
155.1
13.0
104.6 91.4
78.2
65.0
140.9
12.8
133.3 113.0 99.8
86.6
73.4
128.7
12.5
64.6
49.6
173.5
13.2
89.6
74.6
59.6
159.0
13.0
114.6 99.6
84.6
69.6
144.5
12.8
138.1 123.1 108.1 93.1
78.1
131.9
12.6
141.0 126.3 111.3 96.3
81.3
131.4
12.6
70.5
53.7
177.8
13.2
97.5
80.7
63.9
162.9
13.1
124.6 107.8 91.0
74.2
148.1
12.9
143.0 133.3 116.5 99.7
82.9
135.2
12.6
144.6 136.7 119.9 103.1 86.3
134.6
12.6
76.3
57.7
182.0
13.3
105.5 86.9
68.3
166.8
13.1
134.6 116.0 97.4
78.8
151.6
12.9
147.8 143.4 124.8 106.2 87.6
138.4
12.7
148.3 147.1 128.5 109.9 91.3
137.8
12.7
112.0 92.2
72.3
168.0
13.2
142.9 123.1 103.2 83.3
152.7
13.0
149.2 147.0 127.1 107.3 87.4
139.4
12.7
149.7 149.1 129.2 109.4 89.5
138.8
12.7
118.6 97.4
76.3
169.2
13.2
151.3 130.1 109.0 87.9
153.7
13.0
150.6 150.6 129.5 108.3 87.2
140.4
12.7
151.1 151.1 130.0 108.8 87.7
139.8
12.7
90
77.2
100.7
124.3
144.9
84.3
109.7
135.0
148.9
146.9
91.4
118.6
145.8
152.8
150.8
98.5
127.5
156.5
156.8
154.8
136.3
167.3
159.3
157.2
145.1
178.0
161.7
159.6
68.8
91.6
114.3
128.7
76.3
100.7
125.1
131.9
131.4
83.9
109.9
135.9
135.2
134.6
91.5
119.1
146.7
138.4
137.8
127.6
150.2
139.4
138.8
136.0
153.7
140.4
139.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
63.6
50.0
87.2
73.6
60.0
110.7 97.1
83.6
70.0
138.4 120.1 106.6 93.0
69.1
53.9
94.4
79.2
64.0
119.8 104.6 89.4
74.2
144.5 129.3 114.1 98.9
146.9 135.2 120.0 104.8
74.5
57.7
101.7 84.9
68.0
128.9 112.0 95.2
78.3
150.7 138.5 121.7 104.8
150.8 144.8 128.0 111.1
80.0
61.5
109.0 90.5
72.0
138.0 119.5 101.0 82.5
156.8 147.8 129.3 110.8
154.8 154.5 136.0 117.5
116.5 96.7
76.9
147.5 127.7 107.9 88.1
159.3 154.7 135.0 115.2
157.2 157.0 137.2 117.5
124.0 102.9 81.8
157.0 135.9 114.8 93.7
161.7 161.7 140.6 119.6
159.6 159.6 138.5 117.4
105°F
56.1
43.0
78.5
65.5
52.4
100.9 87.9
74.9
61.8
126.9 108.9 95.8
82.8
61.6
46.8
86.0
71.2
56.5
110.4 95.6
80.9
66.1
130.7 118.4 103.7 88.9
131.4 118.3 103.5 88.8
67.1
50.6
93.4
77.0
60.5
119.8 103.3 86.9
70.4
134.6 128.0 111.5 95.0
134.6 127.8 111.4 94.9
72.6
54.4
100.9 82.7
64.5
129.2 111.0 92.9
74.7
138.4 137.5 119.3 101.1
137.8 137.4 119.2 101.0
107.9 88.2
68.6
137.8 118.5 98.8
79.1
139.4 138.9 119.3 99.6
138.8 138.6 118.9 99.3
114.9 93.8
72.6
146.3 125.9 104.8 83.6
140.4 140.4 119.2 98.1
139.8 139.8 118.6 97.5
65
79.4
83.7
89.6
88.0
94.3
92.3
99.0
95.4
97.7
98.5
96.4
69.8
74.1
74.0
78.5
78.4
82.9
82.8
80.0
79.6
77.0
76.4
49
5123247-TTG-A-0515
ZUT12 (12.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
158.4
144.6
130.9
120.5
162.2
148.1
134.0
123.3
121.8
165.9
151.5
137.1
126.2
124.6
169.7
155.0
140.2
129.1
127.4
155.6
140.8
129.6
127.9
156.2
141.4
130.1
128.4
14.6
14.5
14.3
14.0
14.7
14.5
14.3
14.1
14.1
14.7
14.5
14.3
14.1
14.1
14.7
14.5
14.3
14.1
14.2
14.6
14.4
14.1
14.2
14.6
14.4
14.2
14.2
65.6
88.2
110.9
120.5
73.1
96.9
120.6
123.3
121.8
80.6
105.5
130.4
126.2
124.6
88.1
114.2
140.2
129.1
127.4
123.2
140.8
129.6
127.9
132.3
141.4
130.1
128.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
53.5
40.6
147.6
16.1
75.4
62.5
49.6
134.2
16.0
97.3
84.4
71.5
58.7
120.9
15.8
120.5 104.7 91.9
79.0
66.1
112.3
15.6
58.6
44.1
150.8
16.1
82.4
67.9
53.3
137.2
16.0
106.1 91.6
77.1
62.6
123.5
15.8
123.3 113.7 99.2
84.7
70.2
114.8
15.6
121.8 110.3 95.8
81.2
66.7
112.1
15.6
63.7
47.6
154.1
16.1
89.4
73.2
57.1
140.1
15.9
115.0 98.9
82.7
66.6
126.2
15.8
126.2 122.7 106.5 90.4
74.2
117.2
15.5
124.6 119.0 102.8 86.7
70.5
114.6
15.6
68.8
51.0
157.3
16.1
96.4
78.6
60.8
143.1
15.9
123.9 106.1 88.3
70.5
128.9
15.7
129.1 131.7 113.9 96.1
78.3
119.7
15.5
127.4 127.7 109.9 92.1
74.3
117.0
15.6
103.8 84.3
64.9
143.2
16.0
132.6 113.9 94.4
74.9
128.9
15.8
129.6 130.9 111.4 92.0
72.5
119.8
15.6
127.9 128.1 108.6 89.1
69.7
117.0
15.6
111.2 90.1
69.0
143.3
16.0
141.4 121.6 100.5 79.4
129.0
15.8
130.1 130.1 109.0 87.9
66.8
119.9
15.6
128.4 128.4 107.3 86.2
65.1
117.1
15.7
90
60.0
84.9
107.4
112.3
69.9
93.0
116.2
114.8
112.1
79.7
101.1
125.0
117.2
114.6
89.6
109.2
128.9
119.7
117.0
118.9
128.9
119.8
117.0
128.6
129.0
119.9
117.1
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
50.8
38.1
72.2
59.5
46.8
93.6
80.9
68.2
55.5
112.3 100.7 87.9
75.2
55.6
41.3
78.7
64.5
50.2
101.9 87.6
73.4
59.1
114.8 109.0 94.7
80.5
112.1 102.2 88.0
73.7
60.3
44.5
85.3
69.5
53.6
110.2 94.4
78.6
62.7
117.2 117.2 101.6 85.7
114.6 110.1 94.3
78.4
65.1
47.7
91.8
74.4
57.0
118.6 101.1 83.7
66.3
119.7 119.7 108.4 91.0
117.0 117.0 100.6 83.2
99.7
80.4
61.2
127.5 109.3 90.0
70.8
119.8 119.8 103.6 84.3
117.0 117.0 98.3
79.0
107.5 86.4
65.3
129.0 117.4 96.3
75.2
119.9 119.9 98.8
77.7
117.1 117.1 96.0
74.9
65
62.5
66.2
59.4
69.9
62.6
73.6
65.7
65.1
59.8
56.5
53.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
50
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWTA3 thru T12 Cooling Capacities
ZWTA3 (3.0 Ton)
Air on
Evaporator Coil
CFM
750
900
1050
1200
1350
1500
750
900
1050
1200
1350
1500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
49.2
43.8
38.4
33.2
51.6
45.9
40.3
34.8
29.4
54.0
48.1
42.2
36.4
30.8
56.4
50.2
44.1
38.1
32.2
51.5
45.1
39.0
33.0
52.7
46.2
39.9
33.8
2.1
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
19.7
24.5
29.4
33.2
22.2
27.6
33.0
34.8
29.4
24.8
30.7
36.6
36.4
30.8
27.4
33.8
40.2
38.1
32.2
36.7
43.2
39.0
33.0
39.6
46.2
39.9
33.8
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
41.1
36.5
31.9
27.6
43.3
38.5
33.6
29.0
28.3
45.4
40.4
35.3
30.5
29.7
47.6
42.3
37.0
32.0
31.2
43.0
37.6
32.4
31.6
43.6
38.1
32.9
32.1
2.6
2.5
2.4
2.4
2.6
2.5
2.4
2.4
2.4
2.6
2.5
2.5
2.4
2.4
2.6
2.5
2.5
2.4
2.4
2.5
2.5
2.4
2.4
2.5
2.5
2.4
2.4
16.4
21.0
25.6
27.6
18.9
24.1
29.3
29.0
28.3
21.4
27.2
32.9
30.5
29.7
23.9
30.2
36.6
32.0
31.2
32.8
37.4
32.4
31.6
35.4
38.1
32.9
32.1
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
16.4
13.1
45.1
2.3
21.2
17.9
14.6
40.2
2.3
26.1
22.8
19.5
16.2
35.2
2.2
33.2
27.2
23.9
20.6
17.3
30.4
2.2
18.3
14.5
47.4
2.3
23.7
19.8
15.9
42.2
2.3
29.1
25.2
21.3
17.4
37.0
2.2
34.8
30.1
26.2
22.3
18.4
31.9
2.2
29.4
31.7
27.8
23.9
20.0
28.9
2.2
20.3
15.8
49.7
2.3
26.2
21.7
17.3
44.2
2.3
32.1
27.6
23.2
18.7
38.7
2.2
36.4
33.0
28.5
24.0
19.5
33.5
2.2
30.8
38.9
32.1
29.9
25.4
30.3
2.2
22.3
17.2
52.0
2.3
28.7
23.7
18.6
46.3
2.3
35.2
30.1
25.0
19.9
40.5
2.2
38.1
35.9
30.8
25.7
20.6
35.0
2.2
32.2
46.0
36.4
35.8
30.7
31.7
2.2
31.0
25.4
19.7
47.2
2.3
37.9
32.3
26.6
20.9
41.3
2.2
39.0
37.9
32.2
26.6
20.9
35.7
2.2
33.0
39.9
31.9
28.6
22.9
32.3
2.2
33.3
27.1
20.9
48.1
2.3
40.7
34.4
28.2
22.0
42.2
2.2
39.9
39.9
33.7
27.4
21.2
36.4
2.2
33.8
33.8
27.5
21.3
15.0
32.9
2.2
95°F
13.3
10.2
36.8
2.8
17.9
14.8
11.7
32.9
2.7
22.5
19.4
16.3
13.2
28.9
2.7
27.6
23.3
20.2
17.1
14.0
24.9
2.6
15.2
11.5
38.6
2.8
20.4
16.7
13.0
34.5
2.7
25.6
21.9
18.1
14.4
30.3
2.7
29.0
26.2
22.5
18.8
15.1
26.1
2.6
28.3
26.0
22.3
18.6
14.9
25.5
2.6
17.1
12.7
40.4
2.8
22.8
18.5
14.2
36.1
2.8
28.6
24.3
20.0
15.7
31.7
2.7
30.5
29.1
24.8
20.5
16.2
27.3
2.6
29.7
29.0
24.6
20.3
16.0
26.7
2.6
19.0
14.0
42.2
2.9
25.3
20.4
15.5
37.7
2.8
31.7
26.8
21.8
16.9
33.1
2.7
32.0
32.1
27.2
22.2
17.3
28.5
2.6
31.2
31.9
27.0
22.0
17.1
27.9
2.7
27.4
21.9
16.5
38.2
2.8
34.2
28.7
23.3
17.9
33.6
2.7
32.4
32.5
27.1
21.6
16.2
28.9
2.7
31.6
32.0
26.6
21.1
15.7
28.3
2.7
29.4
23.4
17.5
38.7
2.8
36.7
30.7
24.8
18.8
34.0
2.7
32.9
32.9
27.0
21.0
15.1
29.3
2.7
32.1
32.1
26.2
20.2
14.2
28.7
2.7
90
18.0
22.8
27.5
30.4
20.6
25.9
31.1
31.9
28.9
23.1
28.9
34.8
33.5
30.3
25.6
32.0
38.4
35.0
31.7
34.8
40.3
35.7
32.3
37.5
42.2
36.4
32.9
13.8
19.3
24.9
24.9
16.9
22.2
27.6
26.1
25.5
20.0
25.1
30.2
27.3
26.7
23.1
28.0
32.9
28.5
27.9
30.5
33.5
28.9
28.3
32.9
34.0
29.3
28.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
14.8
11.6
19.6
16.4
13.2
24.3
21.1
17.9
14.7
30.4
25.3
22.0
18.8
16.8
13.0
22.1
18.3
14.4
27.3
23.5
19.7
15.9
31.9
28.2
24.4
20.6
28.9
28.9
25.1
21.3
18.7
14.3
24.5
20.1
15.7
30.4
26.0
21.6
17.2
33.5
31.1
26.7
22.3
30.3
33.9
28.4
25.1
20.6
15.6
27.0
22.0
17.0
33.4
28.4
23.4
18.4
35.0
34.0
29.0
24.0
31.7
38.9
31.7
28.9
29.2
23.6
18.1
36.1
30.5
24.9
19.4
35.7
35.2
29.6
24.1
32.3
35.9
29.3
24.8
31.4
25.3
19.2
38.7
32.6
26.5
20.4
36.4
36.4
30.3
24.2
32.9
32.9
26.8
20.7
105°F
11.6
8.6
16.3
13.3
10.3
21.0
18.0
15.0
12.0
24.9
21.8
18.8
15.8
13.3
9.7
18.6
15.0
11.4
24.0
20.4
16.8
13.2
26.1
24.6
21.0
17.4
25.5
23.6
20.0
16.4
15.0
10.8
20.9
16.8
12.6
26.9
22.7
18.5
14.3
27.3
27.4
23.3
19.1
26.7
26.4
22.2
18.0
16.7
11.9
23.3
18.5
13.7
29.8
25.0
20.3
15.5
28.5
30.3
25.5
20.7
27.9
29.1
24.3
19.5
25.2
19.9
14.6
31.6
27.0
21.7
16.4
28.9
29.8
24.5
19.2
28.3
28.9
23.6
18.3
27.1
21.3
15.5
33.3
28.9
23.0
17.2
29.3
29.3
23.5
17.6
28.7
28.7
22.9
17.0
65
15.6
16.8
17.5
17.9
20.7
19.0
23.9
18.5
19.3
18.1
14.6
12.8
13.8
12.8
14.9
13.8
15.9
14.7
13.9
13.0
11.8
11.2
51
5123247-TTG-A-0515
ZWTA3 (3.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
750
900
1050
1200
1350
1500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
32.6
29.2
25.9
22.2
34.0
30.5
27.0
23.1
22.8
35.4
31.8
28.1
24.1
23.7
36.8
33.0
29.2
25.0
24.7
33.4
29.6
25.3
24.9
33.8
29.9
25.6
25.2
3.1
3.0
2.9
2.8
3.1
3.0
2.9
2.8
2.8
3.1
3.0
2.9
2.8
2.9
3.1
3.0
2.9
2.8
2.9
3.0
2.9
2.9
2.9
3.1
3.0
2.9
2.9
11.2
17.7
24.2
22.2
14.9
20.4
25.9
23.1
22.8
18.7
23.1
27.5
24.1
23.7
22.4
25.8
29.2
25.0
24.7
28.2
29.6
25.3
24.9
30.5
29.9
25.6
25.2
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
9.9
7.0
28.3
3.3
14.8
11.8
8.9
25.6
3.2
19.6
16.6
13.7
10.8
22.9
3.1
22.2
20.3
17.4
14.4
11.5
19.5
3.0
11.4
7.9
29.4
3.4
16.9
13.4
9.9
26.5
3.2
22.4
18.9
15.4
11.9
23.7
3.1
23.1
23.0
19.5
16.0
12.5
20.2
3.0
22.8
21.2
17.8
14.3
10.8
20.0
3.1
12.9
8.9
30.4
3.4
19.1
15.0
10.9
27.5
3.3
25.2
21.1
17.0
13.0
24.5
3.1
24.1
25.7
21.7
17.6
13.6
20.9
3.0
23.7
23.8
19.7
15.6
11.6
20.7
3.1
14.5
9.8
31.4
3.4
21.2
16.6
12.0
28.4
3.3
28.0
23.3
18.7
14.1
25.4
3.1
25.0
28.5
23.8
19.2
14.6
21.6
3.0
24.7
26.3
21.6
17.0
12.4
21.4
3.1
23.0
17.9
12.7
28.6
3.3
28.9
25.2
20.0
14.9
25.6
3.2
25.3
27.0
21.9
16.7
11.6
21.8
3.1
24.9
25.7
20.6
15.4
10.3
21.6
3.1
24.8
19.2
13.5
28.9
3.3
29.9
27.0
21.3
15.6
25.8
3.2
25.6
25.6
19.9
14.3
8.6
22.0
3.1
25.2
25.2
19.6
13.9
8.2
21.8
3.2
90
9.2
16.0
22.9
19.5
13.4
18.6
23.7
20.2
20.0
17.6
21.1
24.5
20.9
20.7
21.9
23.6
25.4
21.6
21.4
25.9
25.6
21.8
21.6
28.1
25.8
22.0
21.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
7.9
5.4
13.2
10.3
7.5
18.1
15.3
12.4
9.6
19.5
19.5
16.0
13.1
9.6
6.2
15.2
11.8
8.4
20.8
17.4
14.0
10.6
20.2
20.2
18.0
14.7
20.0
18.8
15.5
12.1
11.3
7.0
17.2
13.2
9.3
23.4
19.5
15.6
11.7
20.9
20.9
20.1
16.2
20.7
20.7
17.2
13.3
12.9
7.7
19.1
14.7
10.2
25.4
21.6
17.2
12.7
21.6
21.6
21.6
17.7
21.4
21.4
19.0
14.5
20.9
15.9
10.9
25.6
23.4
18.4
13.4
21.8
21.8
19.3
14.3
21.6
21.6
17.6
12.6
22.6
17.0
11.5
25.8
25.1
19.6
14.0
22.0
22.0
16.4
10.9
21.8
21.8
16.2
10.7
65
10.3
11.3
8.7
12.2
9.4
13.2
10.0
9.3
7.6
5.4
5.2
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
52
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWTA4 (4.0 Ton)
Air on
Evaporator Coil
CFM
1000
1200
1400
1600
1800
2000
1000
1200
1400
1600
1800
2000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
79.0
68.7
58.4
54.5
78.9
68.5
58.2
54.4
54.2
78.8
68.4
58.0
54.4
54.2
78.7
68.2
57.8
54.3
54.1
62.0
52.4
49.5
49.3
55.8
47.0
44.6
44.6
3.0
2.9
2.8
2.9
3.0
2.9
2.8
2.9
2.9
2.9
2.9
2.8
2.8
2.8
2.9
2.9
2.8
2.8
2.8
3.2
3.1
3.2
3.2
3.5
3.5
3.5
3.5
29.4
35.7
42.0
54.5
32.6
39.4
46.2
54.4
54.2
35.8
43.0
50.3
54.4
54.2
38.9
46.7
54.5
54.3
54.1
44.6
50.8
49.5
49.3
42.4
47.0
44.6
44.6
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
52.8
47.4
41.9
36.1
56.2
50.4
44.6
38.4
37.7
59.6
53.4
47.3
40.7
40.0
63.0
56.5
50.0
43.0
42.3
56.7
50.1
43.2
42.4
56.9
50.3
43.3
42.6
3.4
3.4
3.4
3.3
3.5
3.5
3.4
3.3
3.3
3.5
3.5
3.5
3.4
3.4
3.6
3.5
3.5
3.4
3.4
3.5
3.5
3.4
3.4
3.5
3.5
3.4
3.4
23.9
29.8
35.7
36.1
27.2
33.7
40.3
38.4
37.7
30.5
37.7
44.9
40.7
40.0
33.8
41.6
49.4
43.0
42.3
44.9
49.9
43.2
42.4
48.3
50.3
43.3
42.6
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
25.1
20.7
65.9
3.2
31.3
27.0
22.6
58.0
3.2
37.6
33.3
28.9
24.5
50.1
3.1
51.1
39.9
35.5
31.2
26.8
45.3
3.1
27.5
22.4
67.5
3.2
34.3
29.2
24.1
59.5
3.2
41.1
36.0
30.9
25.8
51.4
3.1
52.2
43.1
38.0
32.9
27.8
46.4
3.1
54.2
46.4
41.3
36.2
31.1
46.0
3.1
29.9
24.1
69.2
3.2
37.2
31.4
25.5
60.9
3.2
44.5
38.7
32.8
27.0
52.6
3.1
53.2
46.3
40.5
34.7
28.8
47.5
3.1
54.2
50.0
44.1
38.3
32.4
47.1
3.1
32.4
25.8
70.8
3.2
40.1
33.6
27.0
62.3
3.2
47.9
41.4
34.8
28.2
53.9
3.1
54.3
49.6
43.0
36.4
29.8
48.7
3.1
54.1
53.5
46.9
40.3
33.8
48.2
3.1
37.0
29.5
22.0
59.3
3.4
43.8
36.2
28.7
21.2
51.3
3.3
49.5
47.0
39.5
32.0
24.5
46.3
3.3
49.3
49.0
41.5
34.0
26.5
45.9
3.3
33.9
25.5
17.0
56.3
3.5
39.6
31.1
22.7
14.2
48.7
3.5
44.6
44.4
36.0
27.5
19.1
44.0
3.5
44.6
44.6
36.1
27.6
19.2
43.6
3.5
95°F
19.7
15.5
49.1
3.8
25.6
21.5
17.3
43.6
3.8
31.6
27.4
23.2
19.0
38.1
3.7
36.1
33.7
29.6
25.4
21.2
33.9
3.6
22.2
17.2
51.6
3.9
28.8
23.8
18.8
45.8
3.8
35.3
30.3
25.4
20.4
40.0
3.7
38.4
37.4
32.4
27.4
22.4
35.6
3.6
37.7
36.8
31.9
26.9
21.9
35.2
3.6
24.7
18.9
54.0
3.9
31.9
26.1
20.3
48.0
3.8
39.1
33.3
27.5
21.7
42.0
3.8
40.7
41.0
35.2
29.4
23.7
37.3
3.7
40.0
40.4
34.6
28.8
23.1
36.8
3.7
27.2
20.6
56.5
3.9
35.0
28.4
21.8
50.2
3.9
42.8
36.2
29.6
23.0
43.9
3.8
43.0
44.7
38.1
31.5
24.9
39.0
3.7
42.3
44.0
37.4
30.8
24.2
38.5
3.7
37.6
30.3
23.0
49.9
3.9
46.0
38.7
31.4
24.0
43.7
3.8
43.2
44.0
36.7
29.4
22.1
38.7
3.7
42.4
43.3
36.0
28.7
21.3
38.3
3.7
40.3
32.2
24.2
49.7
3.9
49.1
41.1
33.1
25.1
43.4
3.8
43.3
43.3
35.3
27.3
19.2
38.5
3.7
42.6
42.6
34.5
26.5
18.5
38.1
3.7
90
26.7
32.8
38.9
45.3
29.9
36.6
43.2
46.4
46.0
33.1
40.4
47.6
47.5
47.1
36.4
44.2
52.0
48.7
48.2
44.7
50.3
46.3
45.9
45.3
48.7
44.0
43.6
19.3
27.0
34.7
33.9
24.5
31.1
37.7
35.6
35.2
29.6
35.1
40.7
37.3
36.8
34.7
39.2
43.6
39.0
38.5
42.3
43.5
38.7
38.3
45.4
43.4
38.5
38.1
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
22.4
18.1
28.5
24.2
20.0
34.6
30.3
26.1
21.8
43.6
36.8
32.6
28.3
24.8
19.8
31.5
26.5
21.4
38.2
33.1
28.1
23.1
45.3
40.3
35.2
30.2
46.0
41.6
36.6
31.6
27.3
21.5
34.5
28.7
22.9
41.8
36.0
30.2
24.3
47.0
43.7
37.9
32.1
47.1
45.2
39.4
33.6
29.8
23.2
37.6
31.0
24.4
45.4
38.8
32.2
25.6
48.7
47.1
40.5
33.9
48.2
48.7
42.1
35.6
37.3
29.9
22.5
44.9
37.5
30.0
22.6
46.3
45.5
38.1
30.7
45.9
46.1
38.7
31.3
37.1
28.9
20.6
44.4
36.1
27.9
19.6
44.0
43.9
35.6
27.4
43.6
43.6
35.3
27.1
105°F
16.9
13.0
22.9
18.9
14.8
28.9
24.7
20.7
16.6
33.9
29.9
25.8
21.8
19.5
14.6
26.1
21.2
16.2
32.7
27.8
22.8
17.9
35.6
33.6
28.7
23.7
35.2
33.2
28.3
23.3
22.1
16.1
29.3
23.5
17.7
36.5
30.8
25.0
19.2
37.3
37.3
31.5
25.6
36.8
36.9
31.0
25.2
24.7
17.7
32.5
25.8
19.1
40.3
33.9
27.2
20.5
39.0
41.0
34.3
27.6
38.5
40.5
33.8
27.1
35.1
27.6
20.2
41.6
36.3
28.9
21.5
38.7
39.7
32.3
24.9
38.3
39.3
31.9
24.4
37.6
29.5
21.3
42.8
38.7
30.6
22.4
38.5
38.5
30.4
22.2
38.1
38.1
29.9
21.8
65
24.0
25.1
26.5
26.2
27.8
27.4
29.0
23.3
23.9
19.1
18.8
17.7
18.8
18.4
19.8
19.4
20.9
20.4
17.5
17.0
14.1
13.6
53
5123247-TTG-A-0515
ZWTA4 (4.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1000
1200
1400
1600
1800
2000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
45.4
39.8
34.3
31.6
46.9
41.2
35.5
32.7
32.6
48.5
42.6
36.7
33.8
33.7
50.1
43.9
37.8
34.9
34.8
43.2
37.2
34.3
34.2
42.4
36.5
33.7
33.6
4.2
4.1
4.0
3.9
4.3
4.1
4.0
3.9
3.9
4.3
4.2
4.1
4.0
4.0
4.3
4.2
4.1
4.0
4.0
4.2
4.1
4.0
4.0
4.3
4.1
4.0
4.0
14.8
24.2
33.7
31.6
21.7
28.4
35.1
32.7
32.6
28.7
32.6
36.4
33.8
33.7
35.7
36.8
37.8
34.9
34.8
39.6
37.2
34.3
34.2
42.4
36.5
33.7
33.6
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
14.2
10.4
41.7
4.6
20.2
16.3
12.3
36.1
4.4
26.3
22.1
18.1
14.1
30.5
4.3
31.6
26.1
22.1
18.1
14.2
29.4
4.2
16.8
11.9
42.3
4.6
23.5
18.6
13.7
36.6
4.5
30.1
25.2
20.3
15.4
30.9
4.3
32.7
29.8
24.9
20.0
15.1
29.9
4.2
32.6
29.6
24.7
19.8
14.9
30.0
4.2
19.5
13.4
43.0
4.7
26.7
20.9
15.0
37.1
4.5
34.0
28.4
22.5
16.7
31.3
4.3
33.8
33.5
27.7
21.8
16.0
30.3
4.3
33.7
33.3
27.4
21.6
15.7
30.5
4.3
22.1
14.9
43.6
4.7
30.0
23.2
16.4
37.7
4.5
37.8
31.5
24.7
17.9
31.8
4.4
34.9
37.3
30.5
23.7
16.9
30.8
4.3
34.8
37.0
30.2
23.4
16.6
31.0
4.3
32.5
25.0
17.4
36.5
4.6
37.2
33.9
26.4
18.9
30.7
4.4
34.3
35.5
27.9
20.4
12.9
29.9
4.3
34.2
35.3
27.8
20.2
12.7
30.1
4.3
35.0
26.7
18.5
35.2
4.6
36.5
36.3
28.1
19.8
29.7
4.4
33.7
33.7
25.4
17.2
8.9
28.9
4.4
33.6
33.6
25.3
17.0
8.8
29.1
4.4
90
12.4
21.4
30.5
29.4
20.6
25.7
30.9
29.9
30.0
28.8
30.1
31.3
30.3
30.5
37.0
34.4
31.8
30.8
31.0
36.5
30.7
29.9
30.1
35.2
29.7
28.9
29.1
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
9.6
7.9
17.5
13.6
9.8
23.8
19.4
15.5
11.6
29.4
22.3
18.4
14.5
14.1
9.3
20.9
16.0
11.1
27.6
22.7
17.8
12.9
29.9
26.0
21.1
16.3
30.0
26.0
21.1
16.2
18.7
10.7
24.2
18.3
12.4
31.3
25.9
20.0
14.1
30.3
29.8
23.9
18.0
30.5
29.7
23.9
18.0
23.2
12.0
27.5
20.6
13.7
31.8
29.2
22.3
15.4
30.8
30.8
26.7
19.8
31.0
31.0
26.6
19.7
29.9
22.3
14.7
30.7
30.7
23.9
16.3
29.9
29.9
23.6
15.9
30.1
30.1
23.7
16.0
32.4
24.0
15.6
29.7
29.7
25.5
17.1
28.9
28.9
20.5
12.1
29.1
29.1
20.7
12.3
65
10.6
11.4
11.3
12.1
12.1
12.9
12.8
8.3
8.4
3.7
3.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
54
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWTA5 (5.0 Ton)
Air on
Evaporator Coil
CFM
1250
1500
1750
2000
2250
2500
1250
1500
1750
2000
2250
2500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
79.8
72.2
64.6
57.1
83.4
75.5
67.5
59.7
59.9
87.0
78.8
70.5
62.3
62.4
90.6
82.0
73.4
64.9
65.0
84.2
75.4
66.6
66.8
86.4
77.3
68.4
68.5
3.1
3.1
3.2
3.1
3.1
3.2
3.2
3.1
3.2
3.2
3.2
3.2
3.1
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
35.0
42.9
50.8
57.1
38.6
47.8
57.1
59.7
59.9
42.3
52.8
63.3
62.3
62.4
45.9
57.7
69.5
64.9
65.0
62.2
73.4
66.6
66.8
66.8
77.3
68.4
68.5
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
68.5
62.1
55.7
50.1
71.1
64.5
57.8
52.0
49.8
73.7
66.8
59.9
53.9
51.6
76.3
69.2
62.0
55.8
53.4
70.6
63.3
57.0
54.5
72.0
64.6
58.1
55.7
4.1
4.1
4.0
4.0
4.1
4.1
4.1
4.0
4.0
4.2
4.1
4.1
4.0
4.0
4.2
4.1
4.1
4.0
4.0
4.2
4.1
4.0
4.0
4.2
4.1
4.0
4.0
29.0
37.6
46.2
50.1
33.4
42.4
51.5
52.0
49.8
37.8
47.3
56.7
53.9
51.6
42.2
52.1
62.0
55.8
53.4
56.4
63.3
57.0
54.5
60.7
64.6
58.1
55.7
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
28.5
22.5
74.2
3.6
36.9
30.9
24.9
67.2
3.6
45.3
39.3
33.2
27.2
60.1
3.6
57.1
47.4
41.4
35.4
29.4
53.6
3.5
31.7
24.8
77.3
3.6
40.9
34.0
27.1
70.0
3.6
50.1
43.2
36.3
29.3
62.7
3.6
59.7
52.2
45.2
38.3
31.4
55.9
3.5
59.9
55.9
49.0
42.0
35.1
54.8
3.6
34.9
27.0
80.4
3.7
44.9
37.1
29.2
72.8
3.7
55.0
47.1
39.3
31.4
65.2
3.6
62.3
56.9
49.1
41.2
33.4
58.1
3.6
62.4
61.0
53.2
45.3
37.5
57.0
3.6
38.0
29.3
83.5
3.7
48.9
40.2
31.4
75.6
3.7
59.8
51.1
42.3
33.6
67.7
3.7
64.9
61.7
52.9
44.2
35.4
60.4
3.6
65.0
66.1
57.4
48.6
39.9
59.2
3.6
52.6
43.0
33.4
77.4
3.7
64.3
54.7
45.1
35.5
69.3
3.7
66.6
65.0
55.4
45.8
36.2
61.8
3.6
66.8
67.3
57.7
48.1
38.5
60.7
3.6
56.3
45.9
35.5
79.2
3.7
68.8
58.3
47.9
37.5
70.9
3.7
68.4
68.4
57.9
47.5
37.1
63.2
3.6
68.5
68.5
58.1
47.6
37.2
62.1
3.6
95°F
23.9
18.2
63.5
4.5
32.0
26.4
20.8
57.3
4.4
40.1
34.5
28.9
23.3
51.0
4.4
50.1
41.9
36.3
30.7
25.1
46.7
4.3
26.8
20.3
65.8
4.5
35.9
29.3
22.7
59.3
4.5
44.9
38.3
31.8
25.2
52.8
4.4
52.0
46.6
40.0
33.4
26.9
48.4
4.3
49.8
44.8
38.2
31.7
25.1
46.4
4.3
29.8
22.3
68.1
4.6
39.7
32.2
24.7
61.4
4.5
49.7
42.2
34.7
27.2
54.7
4.5
53.9
51.2
43.7
36.2
28.7
50.1
4.4
51.6
49.3
41.8
34.2
26.7
48.1
4.4
32.8
24.3
70.4
4.6
43.6
35.2
26.7
63.5
4.5
54.5
46.0
37.5
29.1
56.5
4.5
55.8
55.9
47.4
38.9
30.5
51.8
4.4
53.4
53.7
45.3
36.8
28.4
49.7
4.4
47.1
37.7
28.4
64.6
4.6
58.7
49.4
40.1
30.7
57.6
4.5
57.0
57.0
47.7
38.3
29.0
52.8
4.4
54.5
54.7
45.4
36.0
26.7
50.6
4.4
50.5
40.3
30.1
65.8
4.6
63.0
52.8
42.6
32.4
58.6
4.5
58.1
58.1
48.0
37.8
27.6
53.7
4.4
55.7
55.7
45.5
35.3
25.1
51.5
4.4
90
32.0
40.3
48.5
53.6
36.0
45.1
54.3
55.9
54.8
40.0
50.0
60.0
58.1
57.0
44.0
54.9
65.7
60.4
59.2
59.3
68.3
61.8
60.7
63.7
70.9
63.2
62.1
25.6
35.7
45.7
46.7
31.5
40.4
49.3
48.4
46.4
37.3
45.1
52.9
50.1
48.1
43.1
49.8
56.5
51.8
49.7
54.1
57.6
52.8
50.6
58.3
58.6
53.7
51.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
26.2
20.4
34.4
28.6
22.8
42.7
36.9
31.1
25.3
53.6
44.7
38.9
33.0
29.3
22.5
38.4
31.6
24.9
47.5
40.8
34.0
27.3
55.9
49.4
42.6
35.9
54.8
50.3
43.6
36.9
32.3
24.7
42.3
34.7
27.0
52.3
44.7
37.0
29.3
58.1
54.1
46.4
38.7
57.0
55.1
47.5
39.8
35.4
26.8
46.3
37.7
29.1
57.1
48.5
39.9
31.3
60.4
58.8
50.2
41.5
59.2
59.9
51.3
42.7
49.9
40.4
30.9
61.5
52.0
42.6
33.1
61.8
61.0
51.5
42.1
60.7
61.0
51.5
42.1
53.4
43.1
32.8
65.9
55.6
45.2
34.9
63.2
63.2
52.9
42.6
62.1
62.1
51.8
41.5
105°F
22.1
16.6
30.1
24.6
19.1
38.1
32.6
27.1
21.5
46.7
38.4
32.8
27.3
25.0
18.5
33.9
27.4
20.9
42.8
36.3
29.8
23.3
48.4
42.7
36.2
29.7
46.4
41.7
35.2
28.7
27.8
20.4
37.7
30.2
22.7
47.5
40.0
32.5
25.1
50.1
47.1
39.6
32.1
48.1
45.9
38.5
31.0
30.7
22.3
41.4
33.0
24.6
52.1
43.7
35.3
26.9
51.8
51.4
43.0
34.6
49.7
50.2
41.7
33.3
44.8
35.5
26.2
55.0
47.0
37.8
28.5
52.8
52.6
43.3
34.0
50.6
50.8
41.6
32.3
48.2
38.0
27.9
57.8
50.4
40.2
30.1
53.7
53.7
43.6
33.4
51.5
51.5
41.4
31.2
65
27.2
29.1
30.1
31.0
32.1
32.9
34.1
32.6
32.6
32.3
31.1
21.8
23.2
22.2
24.7
23.5
26.2
24.9
24.7
23.0
23.3
21.1
55
5123247-TTG-A-0515
ZWTA5 (5.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1250
1500
1750
2000
2250
2500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
58.5
52.4
46.3
43.3
60.5
54.2
47.9
44.8
43.1
62.5
56.0
49.5
46.3
44.5
64.5
57.8
51.1
47.8
45.9
58.7
51.9
48.6
46.7
59.6
52.7
49.3
47.4
4.9
4.8
4.7
4.7
4.9
4.9
4.8
4.7
4.7
5.0
4.9
4.8
4.7
4.7
5.0
5.0
4.9
4.8
4.8
5.0
4.9
4.8
4.8
5.0
4.9
4.8
4.8
22.3
33.7
45.1
43.3
29.6
38.3
47.1
44.8
43.1
36.8
43.0
49.1
46.3
44.5
44.1
47.6
51.1
47.8
45.9
51.8
51.9
48.6
46.7
55.9
52.7
49.3
47.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
20.4
14.9
53.4
5.3
28.3
22.8
17.4
47.6
5.2
36.1
30.7
25.2
19.8
41.7
5.1
43.3
34.8
29.3
23.9
18.4
40.0
5.0
23.1
16.7
55.1
5.3
31.9
25.5
19.0
49.1
5.3
40.7
34.3
27.8
21.4
43.0
5.2
44.8
38.9
32.4
26.0
19.6
41.2
5.1
43.1
38.5
32.1
25.7
19.2
39.7
5.1
25.9
18.4
56.8
5.4
35.6
28.1
20.7
50.6
5.3
45.3
37.8
30.4
23.0
44.3
5.2
46.3
42.9
35.5
28.1
20.7
42.5
5.1
44.5
42.6
35.1
27.7
20.3
40.9
5.1
28.6
20.2
58.5
5.5
39.2
30.8
22.4
52.1
5.4
49.8
41.4
33.0
24.6
45.6
5.3
47.8
47.0
38.6
30.2
21.8
43.8
5.2
45.9
46.6
38.2
29.8
21.4
42.2
5.2
42.5
33.3
24.0
52.7
5.4
51.3
44.7
35.5
26.2
46.2
5.3
48.6
48.2
38.9
29.6
20.4
44.3
5.2
46.7
47.0
37.7
28.5
19.2
42.7
5.2
45.8
35.7
25.6
53.4
5.4
52.7
48.0
37.9
27.7
46.8
5.3
49.3
49.3
39.2
29.1
19.0
44.9
5.2
47.4
47.4
37.3
27.1
17.0
43.3
5.2
90
21.9
31.8
41.7
40.0
29.6
36.3
43.0
41.2
39.7
37.4
40.8
44.3
42.5
40.9
45.1
45.4
45.6
43.8
42.2
49.5
46.2
44.3
42.7
53.4
46.8
44.9
43.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
17.7
13.3
26.4
21.0
15.6
34.1
28.7
23.4
18.0
40.0
31.2
25.8
20.5
21.3
14.9
29.9
23.6
17.2
38.6
32.2
25.8
19.5
41.2
35.0
28.6
22.3
39.7
35.4
29.0
22.6
24.8
16.5
33.5
26.1
18.7
43.0
35.7
28.3
20.9
42.5
38.8
31.4
24.1
40.9
39.2
31.8
24.5
28.4
18.1
37.0
28.6
20.3
45.6
39.2
30.8
22.4
43.8
42.6
34.2
25.9
42.2
42.2
34.7
26.3
40.2
31.0
21.8
46.2
42.4
33.1
23.9
44.3
43.7
34.5
25.3
42.7
42.7
33.9
24.7
43.4
33.4
23.3
46.8
45.6
35.5
25.4
44.9
44.9
34.8
24.7
43.3
43.3
33.2
23.1
65
15.1
15.9
16.3
16.7
17.1
17.5
17.9
16.1
15.5
14.6
13.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
56
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWT06 (6.5 Ton)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
106.7
97.0
87.2
78.3
109.7
99.7
89.6
80.4
83.1
112.6
102.3
92.1
82.6
85.3
115.6
105.0
94.5
84.8
87.6
107.5
96.7
86.7
89.6
109.9
98.8
88.7
91.6
4.6
4.5
4.5
4.6
4.6
4.6
4.5
4.6
4.6
4.6
4.6
4.5
4.6
4.6
4.6
4.6
4.5
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
46.4
57.0
67.6
78.3
50.9
62.4
73.9
80.4
83.1
55.3
67.8
80.3
82.6
85.3
59.8
73.2
86.6
84.8
87.6
78.5
92.7
86.7
89.6
83.7
98.8
88.7
91.6
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
89.6
81.5
73.4
65.8
92.3
84.0
75.6
67.8
65.4
95.0
86.4
77.8
69.8
67.2
97.6
88.8
80.0
71.7
69.1
90.7
81.7
73.3
70.6
92.7
83.5
74.8
72.1
5.6
5.5
5.5
5.4
5.6
5.6
5.5
5.5
5.4
5.7
5.6
5.5
5.5
5.5
5.7
5.6
5.6
5.5
5.5
5.7
5.6
5.5
5.5
5.7
5.6
5.5
5.5
38.5
49.3
60.2
65.8
43.2
55.0
66.8
67.8
65.4
48.0
60.7
73.4
69.8
67.2
52.7
66.4
80.0
71.7
69.1
70.9
81.7
73.3
70.6
75.4
83.5
74.8
72.1
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
38.6
31.0
98.2
5.1
49.4
41.7
34.1
89.3
5.0
60.1
52.4
44.8
37.2
80.3
5.0
71.0
62.1
54.4
46.8
39.1
72.1
5.0
42.2
33.4
101.0
5.1
53.7
45.0
36.2
91.8
5.1
65.2
56.5
47.8
39.1
82.6
5.0
75.6
66.9
58.1
49.4
40.7
74.1
5.0
83.1
72.0
63.2
54.5
45.8
74.2
5.0
45.7
35.9
103.8
5.1
58.0
48.2
38.4
94.4
5.1
70.4
60.6
50.8
41.0
84.9
5.0
80.2
71.7
61.9
52.1
42.3
76.2
5.0
85.3
77.1
67.3
57.5
47.7
76.3
5.0
49.2
38.3
106.6
5.2
62.3
51.4
40.6
96.9
5.1
75.5
64.6
53.7
42.9
87.2
5.1
84.8
76.5
65.6
54.7
43.8
78.2
5.1
87.6
82.3
71.4
60.6
49.7
78.4
5.0
66.6
54.8
43.0
99.1
5.1
80.7
68.8
57.0
45.2
89.2
5.1
86.7
82.6
70.8
58.9
47.1
80.0
5.1
89.6
87.0
75.2
63.3
51.5
80.1
5.1
70.9
58.2
45.4
101.3
5.1
85.8
73.1
60.3
47.5
91.2
5.1
88.7
88.7
75.9
63.2
50.4
81.8
5.1
91.6
91.6
78.9
66.1
53.3
81.9
5.1
95°F
31.4
24.3
80.9
6.2
42.2
35.0
27.9
73.1
6.1
52.9
45.8
38.6
31.5
65.3
6.0
64.2
53.3
46.1
39.0
31.8
58.3
5.9
34.9
26.6
83.8
6.2
46.7
38.4
30.1
75.7
6.1
58.5
50.2
41.9
33.6
67.7
6.0
66.7
58.4
50.1
41.8
33.5
60.4
5.9
65.4
61.9
53.6
45.3
37.0
61.0
5.9
38.4
29.0
86.7
6.3
51.2
41.8
32.3
78.4
6.1
64.0
54.6
45.1
35.7
70.1
6.0
69.2
63.5
54.1
44.6
35.2
62.5
5.9
67.2
67.3
57.9
48.4
39.0
63.2
6.0
41.9
31.3
89.7
6.3
55.8
45.1
34.5
81.0
6.2
69.6
59.0
48.4
37.8
72.4
6.1
71.7
68.7
58.1
47.5
36.8
64.6
6.0
69.1
72.8
62.2
51.6
40.9
65.3
6.0
59.4
47.9
36.5
82.6
6.2
74.1
62.7
51.2
39.7
73.8
6.1
73.3
71.7
60.3
48.8
37.4
65.9
6.0
70.6
72.5
61.0
49.5
38.1
66.6
6.0
63.1
50.7
38.4
84.2
6.2
78.6
66.3
54.0
41.7
75.2
6.1
74.8
74.8
62.5
50.2
37.9
67.1
6.0
72.1
72.1
59.8
47.5
35.2
67.8
6.0
90
42.4
53.2
63.9
72.1
47.1
58.7
70.4
74.1
74.2
51.7
64.2
76.8
76.2
76.3
56.3
69.8
83.3
78.2
78.4
74.7
87.2
80.0
80.1
79.5
91.2
81.8
81.9
33.0
45.5
57.9
58.3
40.0
51.4
62.8
60.4
61.0
46.9
57.2
67.6
62.5
63.2
53.8
63.1
72.4
64.6
65.3
67.2
73.8
65.9
66.6
71.3
75.2
67.1
67.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
35.0
27.6
45.8
38.4
31.0
56.5
49.1
41.7
34.3
67.6
57.7
50.3
42.9
38.5
30.0
50.2
41.7
33.2
61.9
53.3
44.8
36.3
71.1
62.6
54.1
45.6
74.2
66.9
58.4
49.9
42.0
32.4
54.6
45.0
35.4
67.2
57.6
47.9
38.3
74.7
67.6
58.0
48.3
76.3
72.2
62.6
53.0
45.5
34.8
59.0
48.3
37.6
72.5
61.8
51.1
40.3
78.2
72.6
61.8
51.1
78.4
77.6
66.8
56.1
63.0
51.4
39.7
77.4
65.7
54.1
42.5
80.0
77.2
65.5
53.9
80.1
79.7
68.1
56.4
67.0
54.5
41.9
82.2
69.7
57.2
44.6
81.8
81.8
69.2
56.7
81.9
81.9
69.3
56.8
105°F
28.4
21.5
38.6
31.8
25.0
48.9
42.1
35.2
28.4
57.5
47.9
41.1
34.2
31.9
23.9
43.3
35.3
27.2
54.7
46.7
38.6
30.5
59.9
53.1
45.0
37.0
61.0
55.7
47.7
39.6
35.5
26.2
48.0
38.7
29.4
60.5
51.2
42.0
32.7
62.2
58.3
49.0
39.7
63.2
61.2
51.9
42.6
39.0
28.5
52.6
42.2
31.7
66.3
55.8
45.3
34.8
64.6
63.5
53.0
42.5
65.3
66.6
56.1
45.7
55.9
44.7
33.4
69.5
59.1
47.8
36.6
65.9
65.3
54.0
42.7
66.6
67.2
55.9
44.7
59.2
47.2
35.1
72.8
62.4
50.4
38.3
67.1
67.1
55.1
43.0
67.8
67.8
55.7
43.7
65
35.5
37.1
41.4
38.7
43.4
40.3
45.3
42.2
44.8
44.1
44.3
27.4
28.9
31.6
30.5
33.4
32.0
35.2
31.5
33.4
30.9
31.6
57
5123247-TTG-A-0515
ZWT06 (6.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
72.1
64.6
57.2
50.7
75.3
67.5
59.8
53.0
56.6
78.5
70.4
62.3
55.3
59.1
81.7
73.3
64.9
57.5
61.5
74.5
65.9
58.5
62.5
75.7
67.0
59.4
63.5
6.8
6.6
6.4
6.3
6.8
6.6
6.5
6.4
6.4
6.8
6.7
6.5
6.4
6.4
6.9
6.7
6.6
6.4
6.5
6.7
6.6
6.5
6.5
6.8
6.6
6.5
6.5
27.6
41.6
55.6
50.7
36.7
47.7
58.7
53.0
56.6
45.8
53.8
61.8
55.3
59.1
54.9
59.9
64.9
57.5
61.5
63.6
65.9
58.5
62.5
67.3
67.0
59.4
63.5
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
25.3
18.8
63.3
7.3
35.1
28.6
22.1
56.2
7.1
44.9
38.4
31.9
25.4
49.1
6.9
50.7
42.5
36.0
29.5
23.0
43.2
6.8
28.9
21.1
66.8
7.4
39.9
32.1
24.3
59.3
7.2
50.9
43.1
35.3
27.5
51.8
7.0
53.0
47.8
40.0
32.2
24.4
45.6
6.8
56.6
49.6
41.8
34.0
26.2
52.3
6.9
32.5
23.4
70.2
7.4
44.7
35.6
26.6
62.4
7.2
56.9
47.8
38.8
29.7
54.6
7.0
55.3
53.0
43.9
34.9
25.8
48.0
6.8
59.1
55.0
46.0
36.9
27.8
55.0
6.9
36.1
25.7
73.7
7.5
49.5
39.2
28.8
65.5
7.2
62.9
52.6
42.2
31.9
57.3
7.0
57.5
58.3
47.9
37.5
27.2
50.4
6.9
61.5
60.5
50.1
39.7
29.4
57.6
7.0
52.5
41.4
30.3
66.4
7.3
65.0
55.6
44.5
33.4
58.0
7.1
58.5
58.8
47.7
36.6
25.5
51.1
6.9
62.5
62.0
50.9
39.8
28.7
58.4
7.0
55.4
43.6
31.8
67.2
7.3
67.0
58.5
46.7
34.9
58.8
7.1
59.4
59.4
47.6
35.8
23.9
51.7
7.0
63.5
63.5
51.7
39.8
28.0
59.2
7.1
90
26.5
37.8
49.1
43.2
36.3
44.1
51.8
45.6
52.3
46.1
50.3
54.6
48.0
55.0
56.0
56.6
57.3
50.4
57.6
59.9
58.0
51.1
58.4
63.2
58.8
51.7
59.2
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
21.1
16.1
31.6
25.4
19.2
40.9
34.7
28.5
22.3
43.2
37.2
31.0
24.8
25.9
18.4
36.5
29.0
21.4
47.1
39.6
32.1
24.5
45.6
42.5
34.9
27.4
52.3
43.4
35.9
28.4
30.7
20.7
41.5
32.6
23.7
53.4
44.5
35.6
26.7
48.0
47.8
38.9
30.0
55.0
48.9
40.0
31.1
35.5
23.0
46.4
36.2
25.9
57.3
49.4
39.1
28.9
50.4
50.4
42.8
32.6
57.6
54.3
44.1
33.8
49.0
38.1
27.2
58.0
52.0
41.1
30.2
51.1
51.1
41.5
30.6
58.4
56.8
45.8
34.9
51.6
40.0
28.4
58.8
54.7
43.1
31.5
51.7
51.7
40.1
28.5
59.2
59.2
47.6
36.0
65
18.6
19.8
20.8
21.1
22.2
22.3
23.6
19.6
24.0
16.9
24.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
58
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWT07 (7.5 Ton)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
125.0
113.1
101.1
88.8
131.0
118.5
106.0
93.1
93.6
137.0
123.9
110.8
97.3
97.8
142.9
129.3
115.7
101.6
102.1
132.4
118.4
104.0
104.6
135.5
121.2
106.4
107.0
5.7
5.6
5.6
5.5
5.7
5.7
5.6
5.6
5.5
5.7
5.7
5.6
5.6
5.6
5.8
5.7
5.7
5.6
5.6
5.7
5.7
5.6
5.6
5.7
5.7
5.6
5.6
53.1
65.8
78.5
88.8
59.5
73.4
87.3
93.1
93.6
65.8
80.9
96.1
97.3
97.8
72.1
88.5
104.9
101.6
102.1
95.5
113.0
104.0
104.6
102.5
121.2
106.4
107.0
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
107.8
97.6
87.4
77.1
111.8
101.2
90.6
79.9
81.1
115.7
104.8
93.8
82.8
84.0
119.7
108.3
97.0
85.6
86.8
110.7
99.2
87.5
88.8
113.1
101.3
89.4
90.7
7.0
6.9
6.7
6.6
7.1
6.9
6.8
6.7
6.6
7.1
7.0
6.8
6.7
6.7
7.2
7.0
6.9
6.8
6.7
7.0
6.9
6.8
6.7
7.0
6.9
6.8
6.8
45.3
58.6
71.9
77.1
50.8
65.4
79.9
79.9
81.1
56.3
72.1
88.0
82.8
84.0
61.8
78.9
96.0
85.6
86.8
86.0
98.6
87.5
88.8
93.0
101.3
89.4
90.7
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
44.4
35.6
116.4
6.3
57.1
48.3
39.5
105.3
6.2
69.8
61.0
52.2
43.5
94.3
6.1
88.8
73.3
64.6
55.8
47.0
83.0
6.1
49.2
39.0
121.4
6.4
63.2
52.9
42.7
109.8
6.3
77.1
66.8
56.6
46.4
98.3
6.2
93.1
80.4
70.2
59.9
49.7
86.5
6.1
93.6
87.2
77.0
66.8
56.5
87.3
6.1
54.1
42.4
126.3
6.4
69.3
57.6
45.9
114.3
6.3
84.4
72.7
61.0
49.3
102.3
6.2
97.3
87.5
75.8
64.1
52.4
90.0
6.1
97.8
94.9
83.2
71.5
59.8
90.9
6.1
59.0
45.8
131.3
6.5
75.4
62.2
49.1
118.8
6.4
91.7
78.6
65.4
52.3
106.3
6.3
101.6 94.5
81.3
68.2
55.0
93.6
6.2
102.1 102.5 89.4
76.2
63.1
94.5
6.2
80.9
66.2
51.6
121.6
6.4
98.3
83.7
69.0
54.4
108.8
6.3
104.0 100.5 85.8
71.2
56.6
95.7
6.2
104.6 104.8 90.1
75.5
60.9
96.7
6.2
86.4
70.3
54.2
124.3
6.4
104.8 88.7
72.7
56.6
111.2
6.3
106.4 106.4 90.3
74.2
58.2
97.9
6.2
107.0 107.0 90.9
74.8
58.7
98.8
6.2
95°F
36.6
27.9
99.1
7.6
49.9
41.2
32.5
89.4
7.5
63.2
54.5
45.8
37.1
79.6
7.3
77.1
67.2
58.4
49.7
41.0
70.5
7.1
40.7
30.5
102.3
7.7
55.2
45.1
35.0
92.2
7.5
69.8
59.7
49.5
39.4
82.2
7.3
79.9
73.5
63.4
53.2
43.1
72.7
7.2
81.1
72.4
62.2
52.1
42.0
75.0
7.2
44.7
33.2
105.4
7.8
60.6
49.0
37.4
95.1
7.6
76.4
64.8
53.3
41.7
84.7
7.4
82.8
79.9
68.3
56.8
45.2
75.0
7.2
84.0
78.6
67.1
55.5
43.9
77.3
7.2
48.8
35.8
108.6
7.8
65.9
52.9
39.9
97.9
7.6
83.0
70.0
57.0
44.0
87.3
7.4
85.6
86.3
73.3
60.3
47.3
77.2
7.3
86.8
84.9
71.9
58.9
45.9
79.6
7.3
71.5
57.0
42.5
99.7
7.7
89.9
75.4
60.9
46.4
88.9
7.5
87.5
87.8
73.3
58.8
44.3
78.7
7.3
88.8
87.8
73.3
58.8
44.3
81.1
7.3
77.0
61.0
45.0
101.6
7.7
96.7
80.7
64.7
48.7
90.5
7.5
89.4
89.4
73.4
57.4
41.4
80.1
7.3
90.7
90.7
74.7
58.7
42.7
82.5
7.3
90
49.2
62.2
75.2
83.0
55.1
69.4
83.6
86.5
87.3
61.1
76.5
92.0
90.0
90.9
67.0
83.7
100.4
93.6
94.5
90.7
105.8
95.7
96.7
97.7
111.2
97.9
98.8
39.5
55.1
70.7
70.5
47.3
61.7
76.1
72.7
75.0
55.1
68.3
81.4
75.0
77.3
62.9
74.8
86.7
77.2
79.6
81.7
88.6
78.7
81.1
88.6
90.5
80.1
82.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
40.5
31.7
53.5
44.7
36.0
66.5
57.7
49.0
40.3
83.0
70.3
61.5
52.8
45.0
34.8
59.2
49.0
38.8
73.4
63.3
53.1
42.9
86.5
77.0
66.8
56.6
87.3
79.8
69.6
59.4
49.4
37.8
64.9
53.3
41.7
80.4
68.8
57.1
45.5
90.0
83.7
72.0
60.4
90.9
86.8
75.1
63.5
53.9
40.8
70.6
57.6
44.5
87.4
74.3
61.2
48.1
93.6
90.4
77.3
64.2
94.5
93.7
80.6
67.6
76.2
61.6
47.0
94.1
79.5
65.0
50.4
95.7
94.1
79.6
65.0
96.7
96.3
81.7
67.2
81.7
65.7
49.6
100.8 84.7
68.7
52.7
97.9
97.9
81.9
65.8
98.8
98.8
82.8
66.8
105°F
33.4
24.8
46.5
37.9
29.3
59.6
51.0
42.4
33.8
70.5
63.1
54.5
45.9
37.3
27.3
51.7
41.7
31.6
66.0
56.0
46.0
36.0
72.7
69.3
59.3
49.3
75.0
66.9
56.9
46.9
41.1
29.7
56.8
45.4
34.0
72.5
61.1
49.6
38.2
75.0
75.5
64.1
52.7
77.3
72.9
61.5
50.1
45.0
32.2
62.0
49.1
36.3
79.0
66.1
53.3
40.4
77.2
81.8
68.9
56.0
79.6
78.9
66.1
53.2
67.4
53.0
38.6
83.6
71.3
57.0
42.6
78.7
80.9
66.6
52.2
81.1
80.7
66.4
52.0
72.8
56.9
41.0
88.2
76.5
60.7
44.8
80.1
80.1
64.3
48.4
82.5
82.5
66.7
50.8
65
44.0
46.4
49.2
48.8
51.9
51.2
54.5
50.5
52.6
49.8
50.7
37.3
39.3
36.9
41.2
38.6
43.2
40.4
37.9
37.7
32.5
34.9
59
5123247-TTG-A-0515
ZWT07 (7.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
90.4
81.1
71.9
63.9
92.7
83.2
73.7
65.6
68.8
95.1
85.4
75.6
67.2
70.6
97.5
87.5
77.5
68.9
72.3
88.7
78.6
69.9
73.4
90.0
79.7
70.9
74.4
8.3
8.0
7.8
7.6
8.3
8.1
7.9
7.7
7.7
8.4
8.2
7.9
7.7
7.8
8.5
8.2
8.0
7.8
7.9
8.3
8.0
7.8
7.9
8.3
8.1
7.9
7.9
33.6
51.6
69.5
63.9
43.8
58.0
72.2
65.6
68.8
53.9
64.4
74.8
67.2
70.6
64.0
70.8
77.5
68.9
72.3
77.5
78.6
69.9
73.4
84.3
79.7
70.9
74.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
30.2
21.8
81.7
8.9
43.1
34.6
26.2
72.9
8.6
56.0
47.5
39.0
30.6
64.1
8.3
63.9
59.0
50.5
42.0
33.6
57.3
8.1
33.9
24.0
83.2
9.0
48.1
38.2
28.3
74.3
8.7
62.3
52.4
42.5
32.6
65.3
8.4
65.6
65.1
55.2
45.3
35.4
58.4
8.2
68.8
61.5
51.6
41.7
31.8
62.7
8.3
37.5
26.3
84.8
9.1
53.1
41.8
30.5
75.7
8.8
68.6
57.3
46.0
34.7
66.5
8.5
67.2
71.2
59.9
48.6
37.3
59.5
8.2
70.6
67.2
55.9
44.6
33.3
63.9
8.4
41.2
28.5
86.4
9.1
58.1
45.4
32.6
77.1
8.8
74.9
62.2
49.5
36.8
67.8
8.6
68.9
77.2
64.5
51.8
39.1
60.6
8.3
72.3
73.0
60.3
47.6
34.8
65.1
8.4
63.3
49.1
34.8
77.7
8.9
77.3
67.3
53.1
38.8
68.3
8.6
69.9
74.1
59.8
45.6
31.4
61.1
8.4
73.4
73.7
59.5
45.2
31.0
65.7
8.5
68.5
52.8
37.0
78.4
8.9
79.7
72.4
56.6
40.9
68.9
8.6
70.9
70.9
55.1
39.4
23.6
61.6
8.4
74.4
74.4
58.7
42.9
27.2
66.3
8.5
90
32.0
48.1
64.1
57.3
43.2
54.3
65.3
58.4
62.7
54.4
60.5
66.5
59.5
63.9
65.7
66.7
67.8
60.6
65.1
73.3
68.3
61.1
65.7
78.4
68.9
61.6
66.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
25.5
18.7
39.7
31.4
23.0
52.4
44.0
35.7
27.3
57.3
57.3
46.5
38.2
30.5
20.7
44.5
34.8
25.0
58.5
48.8
39.0
29.3
58.4
58.4
51.1
41.3
62.7
56.0
46.3
36.5
35.5
22.8
49.3
38.2
27.0
64.7
53.5
42.4
31.2
59.5
59.5
55.6
44.5
63.9
61.5
50.4
39.2
40.5
24.8
54.1
41.6
29.0
67.8
58.3
45.8
33.2
60.6
60.6
60.2
47.6
65.1
65.1
54.4
41.9
59.2
45.1
31.0
68.3
63.3
49.2
35.1
61.1
61.1
53.1
39.0
65.7
65.7
52.5
38.4
64.3
48.6
33.0
68.9
68.2
52.6
37.0
61.6
61.6
46.0
30.4
66.3
66.3
50.6
35.0
65
29.8
31.6
26.8
33.3
28.0
35.0
29.3
24.9
24.3
14.8
19.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
60
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWT08 (8.5 Ton)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
136.0
124.0
112.1
99.3
141.0
128.6
116.2
102.9
99.4
146.0
133.1
120.3
106.5
102.9
151.0
137.7
124.4
110.2
106.5
141.1
127.5
112.9
109.1
144.5
130.6
115.6
111.7
6.1
6.0
5.9
6.2
6.1
6.0
5.9
6.2
8.7
6.1
6.0
5.9
6.1
8.7
6.0
5.9
5.8
6.1
8.7
6.0
5.9
6.2
8.7
6.1
6.0
6.2
8.8
61.5
74.1
86.7
99.3
67.2
82.2
97.3
102.9
99.4
72.8
90.4
107.9
106.5
102.9
78.5
98.5
118.5
110.2
106.5
105.2
124.6
112.9
109.1
112.0
130.6
115.6
111.7
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
119.3
107.9
96.5
84.0
123.1
111.4
99.7
86.7
87.7
127.0
114.9
102.8
89.5
90.5
130.9
118.5
106.0
92.2
93.3
121.0
108.3
94.2
95.3
123.5
110.5
96.2
97.3
7.4
7.3
7.2
7.3
7.5
7.4
7.2
7.3
7.1
7.5
7.4
7.3
7.4
7.2
7.6
7.4
7.3
7.4
7.2
7.5
7.3
7.4
7.2
7.5
7.4
7.5
7.3
51.1
66.3
81.5
84.0
58.8
74.2
89.7
86.7
87.7
66.6
82.2
97.8
89.5
90.5
74.3
90.2
106.0
92.2
93.3
97.1
108.3
94.2
95.3
104.1
110.5
96.2
97.3
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
49.5
38.6
127.6
6.8
63.2
52.4
41.5
116.0
6.7
77.0
66.1
55.3
44.4
104.3
6.6
95.1
77.6
66.8
55.9
45.0
91.6
6.7
54.7
42.3
132.1
6.8
69.8
57.4
44.9
120.0
6.7
84.9
72.5
60.0
47.6
107.9
6.6
100.1 85.0
72.6
60.1
47.7
94.8
6.7
99.4
91.2
78.7
66.3
53.8
93.6
6.5
60.0
46.0
136.5
6.8
76.4
62.4
48.4
124.0
6.7
92.8
78.8
64.8
50.8
111.6
6.6
105.1 92.4
78.4
64.4
50.4
98.0
6.7
102.9 99.1
85.1
71.1
57.1
96.7
6.5
65.2
49.7
141.0
6.8
82.9
67.4
51.8
128.1
6.7
100.6 85.1
69.5
53.9
115.2
6.6
110.2 99.8
84.3
68.7
53.1
101.2
6.8
106.5 107.0 91.5
75.9
60.3
99.9
6.5
88.2
71.1
54.0
131.1
6.7
106.8 89.8
72.7
55.6
117.9
6.6
112.9 107.7 90.6
73.6
56.5
103.5
6.8
109.1 109.4 92.3
75.2
58.2
102.2
6.6
93.4
74.8
56.3
134.0
6.8
113.0 94.5
75.9
57.3
120.6
6.7
115.6 115.6 97.0
78.4
59.9
105.9
6.8
111.7 111.7 93.2
74.6
56.0
104.5
6.6
95°F
41.8
31.4
108.3
8.2
55.9
45.4
35.0
97.7
8.0
69.9
59.5
49.1
38.6
87.1
7.8
84.0
70.3
59.9
49.5
39.1
77.3
7.9
46.7
34.5
111.8
8.2
62.1
49.9
37.7
100.9
8.1
77.5
65.3
53.1
41.0
90.0
7.9
86.7
77.2
65.1
52.9
40.7
79.8
7.9
87.7
79.5
67.4
55.2
43.0
80.7
7.8
51.5
37.6
115.3
8.3
68.3
54.4
40.5
104.1
8.1
85.1
71.2
57.2
43.3
92.8
7.9
89.5
84.1
70.2
56.3
42.4
82.3
7.9
90.5
86.6
72.7
58.8
44.9
83.2
7.8
56.3
40.7
118.9
8.3
74.5
58.8
43.2
107.3
8.1
92.7
77.0
61.3
45.7
95.7
8.0
92.2
91.0
75.4
59.7
44.1
84.8
8.0
93.3
93.8
78.1
62.4
46.8
85.8
7.8
80.1
63.0
46.0
109.5
8.2
99.5
82.5
65.4
48.4
97.7
8.0
94.2
93.6
76.5
59.5
42.5
86.6
8.0
95.3
95.5
78.5
61.4
44.4
87.5
7.9
85.6
67.2
48.8
111.7
8.2
106.4 87.9
69.5
51.1
99.6
8.0
96.2
96.2
77.7
59.3
40.8
88.4
8.0
97.3
97.3
78.8
60.4
41.9
89.3
7.9
90
56.3
70.2
84.1
91.6
63.0
78.2
93.5
94.8
93.6
69.7
86.3
102.9
98.0
96.7
76.4
94.3
112.3
101.2
99.9
101.2
116.4
103.5
102.2
108.0
120.6
105.9
104.5
44.7
62.2
79.6
77.3
55.2
70.1
85.0
79.8
80.7
65.6
78.0
90.3
82.3
83.2
76.1
85.9
95.7
84.8
85.8
92.8
97.7
86.6
87.5
99.6
99.6
88.4
89.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
45.7
35.0
59.6
48.9
38.3
73.5
62.8
52.2
41.5
89.5
74.0
63.3
52.7
50.7
38.4
65.9
53.6
41.3
81.2
68.9
56.6
44.3
93.4
81.1
68.8
56.5
93.6
85.3
73.0
60.7
55.7
41.8
72.3
58.4
44.4
88.9
75.0
61.0
47.0
97.3
88.3
74.3
60.4
96.7
92.9
78.9
65.0
60.8
45.2
78.7
63.1
47.5
96.6
81.0
65.4
49.8
101.2 95.4
79.8
64.2
99.9 100.4 84.8
69.2
84.1
67.1
50.0
103.2 86.1
69.1
52.0
103.5 100.7 83.6
66.5
102.2 102.4 85.4
68.3
89.5
71.0
52.5
109.7 91.2
72.7
54.2
105.9 105.9 87.4
68.9
104.5 104.5 86.0
67.5
105°F
38.5
28.3
52.0
41.8
31.6
65.5
55.3
45.1
34.9
77.3
65.1
54.9
44.7
43.2
31.2
58.1
46.2
34.2
73.0
61.1
49.1
37.2
79.8
71.9
60.0
48.0
80.7
72.5
60.5
48.6
47.9
34.2
64.3
50.6
36.9
80.6
66.9
53.2
39.5
82.3
78.8
65.1
51.4
83.2
79.4
65.7
51.9
52.6
37.2
70.4
55.0
39.5
88.2
72.7
57.3
41.8
84.8
85.6
70.2
54.7
85.8
86.3
70.8
55.3
75.9
59.0
42.1
92.9
78.1
61.2
44.3
86.6
87.0
70.1
53.2
87.5
87.8
70.9
54.0
81.3
63.0
44.7
97.6
83.4
65.1
46.8
88.4
88.4
70.1
51.7
89.3
89.3
71.0
52.7
65
42.0
44.2
48.4
46.4
51.0
48.6
53.6
49.5
51.3
50.4
49.0
34.5
36.1
36.6
37.6
38.2
39.2
39.9
36.3
37.1
33.4
34.4
61
5123247-TTG-A-0515
ZWT08 (8.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
97.3
87.5
77.8
70.6
100.5
90.4
80.3
72.9
73.6
103.6
93.2
82.8
75.2
75.9
106.8
96.1
85.3
77.5
78.3
98.0
87.0
79.0
79.8
99.9
88.8
80.6
81.4
9.0
8.7
8.5
8.4
9.0
8.8
8.5
8.4
8.4
9.1
8.8
8.6
8.5
8.4
9.1
8.9
8.6
8.5
8.4
8.9
8.7
8.6
8.5
8.9
8.7
8.6
8.5
38.3
58.0
77.8
70.6
51.5
65.9
80.3
72.9
73.6
64.7
73.7
82.8
75.2
75.9
77.9
81.6
85.3
77.5
78.3
88.4
87.0
79.0
79.8
95.2
88.8
80.6
81.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
35.1
25.1
86.3
9.7
48.0
38.1
28.1
77.4
9.4
61.0
51.1
41.1
31.1
68.4
9.1
70.6
59.8
49.8
39.8
29.9
63.9
9.0
39.7
28.0
89.1
9.8
54.1
42.4
30.7
79.9
9.5
68.6
56.9
45.1
33.4
70.6
9.2
72.9
66.6
54.9
43.1
31.4
66.0
9.0
73.6
65.4
53.7
41.9
30.2
66.6
10.4
44.3
30.8
91.9
9.8
60.2
46.7
33.2
82.4
9.5
76.2
62.7
49.2
35.7
72.8
9.2
75.2
73.4
59.9
46.4
32.9
68.0
9.0
75.9
72.1
58.6
45.1
31.6
68.7
10.4
48.9
33.7
94.7
9.9
66.3
51.1
35.8
84.9
9.6
83.8
68.5
53.2
38.0
75.0
9.3
77.5
80.2
64.9
49.7
34.4
70.1
9.1
78.3
78.8
63.5
48.2
33.0
70.7
10.5
71.7
55.0
38.2
86.5
9.6
86.3
73.7
57.0
40.3
76.4
9.3
79.0
80.4
63.7
46.9
30.2
71.4
9.1
79.8
80.1
63.4
46.6
29.9
72.1
10.5
77.0
58.8
40.7
88.1
9.7
88.8
78.9
60.7
42.5
77.9
9.4
80.6
80.6
62.4
44.2
26.0
72.8
9.2
81.4
81.4
63.2
45.0
26.9
73.5
10.6
90
39.4
53.9
68.4
63.9
52.8
61.7
70.6
66.0
66.6
66.2
69.5
72.8
68.0
68.7
79.6
77.3
75.0
70.1
70.7
84.0
76.4
71.4
72.1
88.1
77.9
72.8
73.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
29.5
21.9
44.1
34.4
24.6
56.6
46.8
37.1
27.4
63.9
54.5
44.8
35.0
36.2
24.7
50.2
38.7
27.1
64.2
52.6
41.1
29.6
66.0
61.3
49.8
38.2
66.6
58.3
46.8
35.3
42.9
27.4
56.2
42.9
29.6
71.7
58.4
45.2
31.9
68.0
68.0
54.7
41.5
68.7
64.8
51.5
38.2
49.5
30.2
62.3
47.2
32.1
75.0
64.2
49.2
34.1
70.1
70.1
59.7
44.7
70.7
70.7
56.2
41.1
67.5
50.9
34.4
76.4
69.3
52.8
36.2
71.4
71.4
57.2
40.7
72.1
72.1
55.8
39.2
72.7
54.7
36.6
77.9
74.4
56.3
38.3
72.8
72.8
54.7
36.7
73.5
73.5
55.4
37.4
65
25.3
26.7
23.8
28.2
24.9
29.6
26.1
24.1
22.7
18.6
19.3
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
62
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWT10 (10 Ton)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
159.5
145.9
132.2
123.1
164.8
150.7
136.6
127.2
125.9
170.1
155.5
140.9
131.2
129.9
175.4
160.3
145.3
135.3
133.9
164.1
148.7
138.4
137.0
167.8
152.0
141.6
140.1
7.3
7.2
7.1
7.0
7.4
7.2
7.1
7.0
7.0
7.4
7.3
7.1
7.1
7.0
7.4
7.3
7.2
7.1
7.1
7.4
7.2
7.1
7.1
7.4
7.3
7.2
7.2
63.5
83.1
102.7
123.1
71.2
92.6
114.0
127.2
125.9
78.9
102.1
125.4
131.2
129.9
86.6
111.7
136.7
135.3
133.9
118.0
144.4
138.4
137.0
124.3
152.0
141.6
140.1
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
136.9
126.4
115.8
106.6
142.5
131.5
120.5
110.9
111.2
148.1
136.7
125.3
115.3
115.6
153.7
141.9
130.0
119.6
120.0
143.9
131.8
121.3
121.7
145.9
133.7
123.0
123.4
9.0
8.9
8.9
8.8
9.0
9.0
8.9
8.8
8.8
9.1
9.0
9.0
8.9
8.9
9.1
9.0
9.0
8.9
8.9
9.1
9.0
8.9
8.9
9.1
9.0
8.9
8.9
58.8
77.3
95.9
106.6
66.0
86.3
106.7
110.9
111.2
73.2
95.4
117.5
115.3
115.6
80.4
104.4
128.3
119.6
120.0
113.1
131.0
121.3
121.7
121.9
133.7
123.0
123.4
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
52.6
41.7
148.2
8.2
72.2
61.3
50.4
136.1
8.1
91.8
80.9
70.0
59.1
124.0
8.0
118.4 99.0
88.1
77.2
66.3
114.8
7.9
58.4
45.5
153.7
8.2
79.8
67.0
54.2
141.1
8.1
101.2 88.4
75.6
62.8
128.6
8.0
124.1 108.2 95.4
82.6
69.8
119.0
7.9
125.9 113.4 100.6 87.8
75.0
118.5
7.9
64.2
49.4
159.1
8.2
87.4
72.7
57.9
146.1
8.1
110.6 95.9
81.2
66.5
133.1
8.1
129.7 117.5 102.7 88.0
73.3
123.3
8.0
129.9 123.1 108.3 93.6
78.9
122.7
7.9
70.0
53.3
164.5
8.3
95.0
78.4
61.7
151.1
8.2
120.1 103.4 86.8
70.1
137.6
8.1
135.3 126.7 110.0 93.4
76.7
127.5
8.0
133.9 132.7 116.1 99.4
82.8
126.9
8.0
100.1 82.2
64.4
154.0
8.2
126.4 108.5 90.7
72.8
140.3
8.1
138.4 134.1 116.3 98.4
80.5
129.9
8.0
137.0 136.4 118.6 100.7 82.8
129.3
8.0
105.2 86.1
67.0
156.8
8.2
132.7 113.6 94.5
75.5
142.9
8.1
141.6 141.6 122.5 103.4 84.3
132.3
8.0
140.1 140.1 121.0 101.9 82.9
131.7
8.0
95°F
47.9
37.1
125.0
10.0
66.5
55.6
44.8
115.5
10.0
85.0
74.1
63.3
52.4
105.9
10.0
106.6 92.2
81.4
70.5
59.7
98.2
9.9
53.4
40.7
131.1
10.1
73.7
61.1
48.5
121.1
10.0
94.1
81.4
68.8
56.2
111.1
10.0
110.9 101.3 88.7
76.0
63.4
102.9
9.9
111.2 100.9 88.2
75.6
63.0
103.1
9.9
58.8
44.4
137.1
10.1
80.9
66.5
52.1
126.7
10.1
103.1 88.7
74.3
59.9
116.2
10.1
115.3 110.4 96.0
81.6
67.2
107.7
10.0
115.6 109.9 95.5
81.1
66.7
107.9
9.9
64.2
48.0
143.2
10.2
88.2
72.0
55.8
132.3
10.2
112.2 96.0
79.8
63.7
121.4
10.1
119.6 119.4 103.3 87.1
70.9
112.5
10.0
120.0 118.9 102.7 86.6
70.4
112.6
10.0
95.2
77.3
59.4
133.6
10.1
121.0 103.1 85.2
67.3
122.6
10.1
121.3 121.2 103.3 85.4
67.5
113.6
10.0
121.7 121.1 103.2 85.3
67.5
113.8
10.0
102.3 82.7
63.1
134.9
10.1
129.8 110.2 90.6
71.0
123.8
10.1
123.0 123.0 103.4 83.8
64.2
114.7
10.0
123.4 123.4 103.7 84.1
64.5
114.9
10.0
90
61.1
80.2
99.3
114.8
68.6
89.5
110.4
119.0
118.5
76.0
98.7
121.5
123.3
122.7
83.5
108.0
132.5
127.5
126.9
115.6
137.7
129.9
129.3
123.1
142.9
132.3
131.7
52.9
73.3
93.6
98.2
62.3
82.5
102.6
102.9
103.1
71.7
91.6
111.6
107.7
107.9
81.1
100.8
120.5
112.5
112.6
109.0
122.2
113.6
113.8
117.2
123.8
114.7
114.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
50.3
39.4
69.3
58.4
47.6
88.4
77.5
66.6
55.8
112.5 95.6
84.8
73.9
55.9
43.1
76.7
64.0
51.3
97.6
84.9
72.2
59.5
117.5 104.8 92.1
79.3
118.5 107.1 94.4
81.7
61.5
46.9
84.2
69.6
55.0
106.9 92.3
77.7
63.2
122.5 113.9 99.3
84.8
122.7 116.5 101.9 87.3
67.1
50.7
91.6
75.2
58.8
116.1 99.7
83.3
66.9
127.5 123.0 106.6 90.2
126.9 125.8 109.4 93.0
97.7
79.8
61.9
123.7 105.8 87.9
70.1
129.9 127.7 109.8 91.9
129.3 128.8 110.9 93.0
103.7 84.4
65.0
131.3 111.9 92.6
73.2
132.3 132.3 112.9 93.6
131.7 131.7 112.4 93.0
105°F
44.3
33.5
62.5
51.7
40.9
80.7
69.9
59.1
48.3
98.2
86.0
75.2
64.5
49.7
37.2
69.9
57.3
44.7
90.0
77.5
64.9
52.3
102.9 95.3
82.7
70.2
103.1 93.2
80.6
68.0
55.1
40.8
77.3
62.9
48.5
99.4
85.0
70.7
56.3
107.7 104.6 90.3
75.9
107.9 102.3 87.9
73.5
60.5
44.4
84.7
68.5
52.3
108.8 92.6
76.4
60.3
112.5 113.9 97.8
81.6
112.6 111.3 95.2
79.0
91.2
73.5
55.7
115.3 99.4
81.6
63.8
113.6 114.3 96.6
78.8
113.8 113.1 95.4
77.6
97.8
78.5
59.1
121.9 106.1 86.8
67.4
114.7 114.7 95.4
76.1
114.9 114.9 95.5
76.2
65
63.0
66.6
69.0
70.2
72.8
73.8
76.6
74.0
75.1
74.2
73.7
53.7
57.6
55.5
61.5
59.2
65.4
62.8
61.1
59.8
56.7
56.8
63
5123247-TTG-A-0515
ZWT10 (10 Ton) (Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
113.0
104.5
96.0
89.7
119.6
110.6
101.6
94.9
94.9
126.1
116.6
107.2
100.1
100.1
132.7
122.7
112.7
105.3
105.3
123.4
113.3
105.9
105.9
124.0
113.9
106.5
106.4
11.0
11.0
11.0
11.0
11.1
11.1
11.1
11.0
11.0
11.2
11.2
11.2
11.1
11.0
11.3
11.3
11.3
11.2
11.1
11.2
11.2
11.2
11.1
11.2
11.2
11.2
11.1
47.0
69.2
91.4
89.7
58.6
78.6
98.5
94.9
94.9
70.2
87.9
105.6
100.1
100.1
81.8
97.3
112.7
105.3
105.3
104.9
113.3
105.9
105.9
112.5
113.9
106.5
106.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
40.7
30.0
101.1
12.1
58.5
47.8
37.1
93.6
12.1
76.3
65.6
55.0
44.3
86.1
12.1
89.7
79.8
69.1
58.4
47.7
81.3
12.1
46.1
33.6
108.1
12.1
66.1
53.5
41.0
100.1
12.2
86.0
73.5
61.0
48.5
92.1
12.2
94.9
89.3
76.8
64.3
51.8
87.0
12.2
94.9
85.5
73.0
60.5
47.9
86.7
12.0
51.5
37.2
115.1
12.2
73.6
59.3
44.9
106.6
12.3
95.7
81.4
67.0
52.7
98.1
12.3
100.1 98.9
84.6
70.2
55.9
92.6
12.3
100.1 94.6
80.3
66.0
51.6
92.3
12.1
56.9
40.8
122.2
12.3
81.1
65.0
48.8
113.1
12.4
105.4 89.2
73.1
56.9
104.1
12.4
105.3 108.4 92.3
76.1
60.0
98.2
12.4
105.3 103.7 87.6
71.5
55.3
98.0
12.2
87.3
69.6
52.0
113.1
12.3
109.7 95.6
78.0
60.4
104.1
12.3
105.9 107.5 89.8
72.2
54.6
98.2
12.3
105.9 105.1 87.5
69.9
52.2
98.0
12.2
93.4
74.3
55.2
113.1
12.3
113.9 102.0 82.9
63.8
104.1
12.3
106.5 106.5 87.4
68.3
49.2
98.2
12.3
106.4 106.4 87.3
68.3
49.2
98.0
12.1
90
44.1
65.1
86.1
81.3
57.2
74.7
92.1
87.0
86.7
70.3
84.2
98.1
92.6
92.3
83.4
93.7
104.1
98.2
98.0
100.8
104.1
98.2
98.0
107.8
104.1
98.2
98.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
37.0
26.4
54.5
43.9
33.3
72.0
61.4
50.8
40.2
81.3
74.1
63.0
52.3
42.5
30.0
62.2
49.8
37.3
82.0
69.5
57.1
44.6
87.0
83.3
70.9
58.4
86.7
77.8
65.3
52.9
47.9
33.6
69.9
55.6
41.3
92.0
77.7
63.4
49.1
92.6
92.6
78.8
64.6
92.3
87.0
72.7
58.4
53.3
37.1
77.6
61.5
45.3
102.0 85.8
69.7
53.6
98.2
98.2
86.8
70.7
98.0
96.2
80.0
63.9
83.3
65.8
48.3
104.0 91.9
74.4
56.9
98.2
98.2
83.1
65.6
98.0
97.1
79.6
62.1
89.0
70.1
51.3
104.1 97.9
79.1
60.3
98.2
98.2
79.4
60.6
98.0
98.0
79.1
60.3
65
41.7
46.0
40.4
50.3
44.1
54.5
47.8
48.1
44.6
41.7
41.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
64
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWT12 (12.5 Ton)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
191.5
178.7
165.9
149.9
201.3
187.9
174.5
157.6
152.3
211.1
197.0
183.0
165.3
159.7
221.0
206.2
191.5
173.0
167.2
215.4
200.0
180.7
174.6
224.6
208.5
188.4
182.0
9.8
9.5
9.2
9.1
9.8
9.5
9.3
9.1
9.1
9.8
9.6
9.3
9.1
9.1
9.9
9.6
9.3
9.1
9.1
9.6
9.3
9.2
9.1
9.6
9.3
9.2
9.2
80.3
103.3
126.3
149.9
89.4
114.7
140.0
157.6
152.3
98.5
126.2
153.8
165.3
159.7
107.6
137.6
167.5
173.0
167.2
150.0
185.5
180.7
174.6
162.3
203.5
188.4
182.0
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
177.5
163.9
150.3
136.4
185.6
171.4
157.2
142.6
139.4
193.7
178.9
164.0
148.8
145.4
201.8
186.3
170.8
155.0
151.5
193.8
177.7
161.2
157.6
201.2
184.5
167.4
163.6
11.6
11.4
11.2
11.0
11.7
11.5
11.3
11.1
11.1
11.8
11.6
11.4
11.2
11.2
11.9
11.7
11.5
11.3
11.3
11.8
11.6
11.3
11.4
11.9
11.7
11.4
11.5
71.6
94.8
118.0
136.4
80.8
106.5
132.2
142.6
139.4
89.9
118.1
146.4
148.8
145.4
99.1
129.8
160.6
155.0
151.5
142.1
172.5
161.2
157.6
154.4
184.5
167.4
163.6
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
66.9
53.5
184.5
10.7
89.9
76.4
63.0
171.3
10.5
112.8 99.4
86.0
72.6
158.1
10.2
139.5 122.9 109.5 96.1
82.7
143.1
10.1
74.2
58.9
193.5
10.7
99.5
84.2
69.0
179.6
10.5
124.8 109.5 94.3
79.1
165.8
10.3
150.7 135.4 120.2 105.0 89.7
150.1
10.1
152.3 140.7 125.5 110.2 95.0
145.8
10.1
81.5
64.4
202.4
10.8
109.1 92.0
75.0
187.9
10.6
136.7 119.7 102.6 85.5
173.5
10.3
161.8 148.0 130.9 113.8 96.8
157.0
10.1
159.7 153.7 136.6 119.6 102.5
152.6
10.2
88.8
69.9
211.4
10.9
118.7 99.8
80.9
196.3
10.6
148.7 129.8 110.9 92.0
181.2
10.4
173.0 160.5 141.6 122.7 103.8
164.0
10.2
167.2 166.7 147.8 129.0 110.1
159.3
10.2
129.1 108.3 87.5
204.6
10.7
161.6 140.8 119.9 99.1
188.8
10.4
180.7 174.4 153.6 132.8 111.9
170.9
10.2
174.6 174.4 153.5 132.7 111.9
166.1
10.3
139.5 116.7 94.0
212.9
10.7
174.5 151.8 129.0 106.2
196.5
10.5
188.4 188.4 165.6 142.8 120.0
177.9
10.3
182.0 182.0 159.2 136.5 113.7
172.8
10.3
95°F
58.3
45.1
168.0
12.8
81.5
68.2
55.0
154.2
12.7
104.7 91.4
78.1
64.9
140.3
12.6
132.1 112.1 98.9
85.6
72.3
128.6
12.4
65.4
50.0
175.2
12.9
91.1
75.7
60.3
160.8
12.8
116.8 101.4 86.0
70.6
146.4
12.7
139.7 124.3 109.0 93.6
78.2
134.1
12.5
139.4 127.2 111.8 96.5
81.1
131.5
12.5
72.4
54.9
182.4
13.0
100.6 83.1
65.6
167.4
12.9
128.8 111.3 93.8
76.3
152.4
12.8
147.4 136.6 119.1 101.5 84.0
139.6
12.6
145.4 139.7 122.2 104.7 87.2
136.9
12.6
79.4
59.8
189.6
13.1
110.2 90.5
70.9
174.0
13.0
140.9 121.3 101.7 82.0
158.5
12.9
155.0 148.8 129.2 109.5 89.9
145.1
12.7
151.5 152.2 132.6 113.0 93.4
142.3
12.7
120.4 98.6
76.9
180.7
13.1
153.9 132.1 110.4 88.7
164.5
13.0
161.2 158.1 136.4 114.6 92.9
150.7
12.8
157.6 157.9 136.2 114.5 92.7
147.8
12.8
130.6 106.7 82.9
187.3
13.2
166.8 143.0 119.2 95.3
170.5
13.1
167.4 167.4 143.6 119.7 95.9
156.2
12.9
163.6 163.6 139.8 116.0 92.1
153.2
12.9
90
76.0
99.0
122.1
143.1
85.1
110.6
136.1
150.1
145.8
94.2
122.1
150.1
157.0
152.6
103.3
133.7
164.1
164.0
159.3
146.0
179.0
170.9
166.1
158.4
194.0
177.9
172.8
67.5
90.8
114.2
128.6
77.1
102.2
127.2
134.1
131.5
86.7
113.5
140.3
139.6
136.9
96.3
124.8
153.3
145.1
142.3
136.9
161.9
150.7
147.8
149.0
170.5
156.2
153.2
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
62.6
49.3
85.7
72.3
59.0
108.8 95.4
82.1
68.7
135.8 117.5 104.2 90.8
69.8
54.5
95.3
80.0
64.6
120.8 105.5 90.1
74.8
145.2 129.9 114.6 99.3
145.8 134.0 118.7 103.3
76.9
59.6
104.9 87.6
70.3
132.8 115.5 98.2
80.9
154.6 142.3 125.0 107.7
152.6 146.7 129.4 112.2
84.1
64.8
114.4 95.2
75.9
144.8 125.5 106.3 87.0
164.0 154.6 135.4 116.1
159.3 159.5 140.2 121.0
124.7 103.5 82.2
157.7 136.5 115.2 93.9
170.9 166.3 145.0 123.7
166.1 166.2 144.9 123.6
135.1 111.7 88.4
170.7 147.4 124.1 100.8
177.9 177.9 154.6 131.3
172.8 172.8 149.5 126.2
105°F
55.1
42.0
77.7
64.5
51.4
100.2 87.1
73.9
60.8
126.4 106.8 93.6
80.5
61.9
46.7
86.9
71.7
56.5
112.0 96.8
81.6
66.4
132.7 118.7 103.5 88.2
131.5 118.9 103.7 88.5
68.6
51.3
96.2
78.9
61.6
123.8 106.5 89.2
71.9
138.9 130.6 113.3 96.0
136.9 130.9 113.6 96.3
75.4
56.0
105.5 86.1
66.8
135.6 116.2 96.9
77.5
145.1 142.5 123.2 103.8
142.3 142.8 123.4 104.1
115.4 94.0
72.5
148.3 126.8 105.3 83.9
150.7 149.3 127.9 106.4
147.8 148.0 126.5 105.0
125.4 101.8 78.2
161.0 137.4 113.8 90.2
156.2 156.2 132.6 109.0
153.2 153.2 129.6 106.0
65
77.5
83.9
88.0
90.4
94.9
96.9
101.7
102.4
102.3
108.0
102.9
67.3
73.0
73.3
78.7
79.0
84.5
84.7
84.9
83.6
85.4
82.4
65
5123247-TTG-A-0515
ZWT12 (12.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
158.4
144.4
130.4
120.7
164.8
150.2
135.6
125.6
123.7
171.1
156.0
140.8
130.4
128.4
177.5
161.8
146.1
135.3
133.2
167.6
151.3
140.1
138.0
173.4
156.5
145.0
142.7
14.0
14.0
14.0
13.8
14.1
14.1
14.1
13.9
13.9
14.2
14.2
14.2
14.0
14.0
14.4
14.3
14.3
14.1
14.1
14.4
14.4
14.2
14.2
14.5
14.5
14.3
14.3
63.3
86.9
110.4
120.7
73.4
97.9
122.3
125.6
123.7
83.5
108.8
134.2
130.4
128.4
93.6
119.8
146.1
135.3
133.2
131.7
151.3
140.1
138.0
143.6
156.5
145.0
142.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
51.9
38.9
148.8
15.3
73.8
60.8
47.8
134.6
15.3
95.8
82.7
69.7
56.7
120.4
15.4
120.7 101.4 88.4
75.3
62.3
112.9
15.2
58.4
43.3
154.3
15.4
82.8
67.8
52.7
139.6
15.4
107.3 92.2
77.2
62.1
124.8
15.5
125.6 113.0 98.0
82.9
67.9
117.1
15.3
123.7 110.6 95.6
80.5
65.5
115.8
15.3
64.8
47.8
159.8
15.5
91.8
74.7
57.7
144.5
15.5
118.7 101.7 84.6
67.6
129.2
15.6
130.4 124.6 107.6 90.5
73.4
121.2
15.4
128.4 122.0 104.9 87.9
70.8
119.9
15.5
71.3
52.2
165.3
15.6
100.8 81.7
62.6
149.5
15.7
130.2 111.2 92.1
73.0
133.7
15.7
135.3 136.2 117.2 98.1
79.0
125.4
15.5
133.2 133.3 114.3 95.2
76.1
124.1
15.6
110.5 89.3
68.1
154.5
15.8
142.7 121.5 100.3 79.0
138.1
15.8
140.1 140.6 119.4 98.1
76.9
129.6
15.6
138.0 138.0 116.8 95.6
74.4
128.2
15.7
120.2 96.9
73.5
159.4
15.9
155.2 131.8 108.4 85.0
142.5
15.9
145.0 145.0 121.6 98.2
74.8
133.7
15.7
142.7 142.7 119.4 96.0
72.6
132.3
15.8
90
56.6
82.9
106.6
112.9
69.8
93.6
117.4
117.1
115.8
82.9
104.2
128.1
121.2
119.9
96.0
114.8
133.7
125.4
124.1
126.5
138.1
129.6
128.2
138.2
142.5
133.7
132.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
48.7
35.8
70.0
57.1
44.2
91.3
78.4
65.5
52.6
112.9 96.0
83.1
70.2
54.9
40.0
78.7
63.8
48.9
102.5 87.6
72.7
57.9
117.1 107.3 92.5
77.6
115.8 102.3 87.4
72.5
61.1
44.2
87.4
70.5
53.7
113.7 96.9
80.0
63.2
121.2 118.6 101.8 85.0
119.9 113.1 96.3
79.4
67.2
48.5
96.1
77.3
58.5
124.9 106.1 87.3
68.5
125.4 125.4 111.1 92.4
124.1 123.9 105.1 86.3
105.6 84.6
63.6
137.1 116.1 95.2
74.2
129.6 129.6 110.9 89.9
128.2 128.1 107.1 86.1
115.1 91.9
68.8
142.5 126.2 103.0 79.9
133.7 133.7 110.6 87.4
132.3 132.3 109.1 86.0
65
57.3
62.7
57.7
68.1
62.6
73.6
67.5
68.9
65.2
64.3
62.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
66
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKTA3 thru T12 Cooling and Reheat Capacities
ZKTA3 (3.0 Ton) Cooling
Air on
Evaporator Coil
CFM
750
900
1050
1200
1350
1500
750
900
1050
1200
1350
1500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
48.2
43.9
39.6
35.5
50.4
45.9
41.4
37.1
33.3
52.7
47.9
43.2
38.7
34.7
54.9
50.0
45.1
40.4
36.2
50.0
45.0
40.4
36.2
49.9
45.0
40.3
36.2
0.2
0.8
1.3
1.1
0.5
1.1
1.6
1.4
1.3
0.8
1.3
1.9
1.7
1.6
1.0
1.6
2.2
2.0
1.8
1.4
2.0
1.8
1.6
1.2
1.8
1.6
1.5
20.1
24.6
29.0
35.5
22.1
27.8
33.4
37.1
33.3
24.1
31.0
37.8
38.7
34.7
26.1
34.2
42.2
40.4
36.2
36.8
43.6
40.4
36.2
39.3
45.0
40.3
36.2
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
38.8
35.6
32.5
27.3
40.5
37.2
33.9
28.5
26.2
42.2
38.7
35.3
29.7
27.2
43.9
40.3
36.7
30.8
28.3
40.1
36.5
30.7
28.2
40.0
36.4
30.6
28.1
3.1
2.8
2.6
2.7
3.0
2.7
2.5
2.7
2.4
2.8
2.6
2.4
2.6
2.3
2.7
2.5
2.3
2.5
2.2
2.5
2.3
2.5
2.2
2.5
2.3
2.5
2.2
13.9
19.9
25.9
27.3
17.2
23.4
29.5
28.5
26.2
20.6
26.8
33.1
29.7
27.2
23.9
30.3
36.7
30.8
28.3
32.4
36.5
30.7
28.2
34.4
36.4
30.6
28.1
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
16.2
13.0
43.5
1.6
21.3
18.1
14.9
39.8
1.8
26.5
23.3
20.1
16.8
36.0
2.0
32.6
28.4
25.1
21.9
18.7
31.4
1.9
18.2
14.3
45.5
1.7
23.9
20.0
16.1
41.6
1.9
29.5
25.6
21.7
17.8
37.6
2.1
35.2
31.3
27.4
23.5
19.6
32.8
2.0
33.4
30.5
26.6
22.7
18.8
29.7
1.9
20.3
15.7
47.4
1.8
26.4
21.8
17.2
43.3
2.0
32.5
27.9
23.4
18.8
39.2
2.1
37.8
34.2
29.6
25.0
20.5
34.2
2.1
34.8
33.3
28.8
24.2
19.6
31.0
1.9
22.3
17.0
49.4
1.9
28.9
23.6
18.4
45.1
2.1
35.5
30.3
25.0
19.8
40.9
2.2
40.4
37.1
31.8
26.6
21.3
35.6
2.2
36.2
36.2
30.9
25.7
20.4
32.3
2.0
31.0
25.2
19.5
45.0
2.0
38.2
32.3
26.6
20.8
40.8
2.1
40.4
38.7
33.0
27.2
21.5
35.5
2.1
36.2
36.2
30.4
24.7
18.9
32.2
1.9
33.1
26.8
20.6
45.0
1.9
40.9
34.4
28.2
21.9
40.7
2.1
40.3
40.3
34.1
27.8
21.6
35.5
2.0
36.2
36.2
29.9
23.7
17.4
32.1
1.9
95°F
11.6
8.5
36.4
2.7
16.9
13.8
10.8
32.8
2.7
22.2
19.1
16.1
13.0
29.2
2.6
26.6
21.0
18.0
14.9
11.9
25.0
2.6
13.5
9.8
37.5
2.7
19.7
16.0
12.3
33.8
2.7
25.8
22.1
18.4
14.7
30.1
2.6
28.0
24.3
20.6
16.9
13.2
25.8
2.6
26.0
22.3
18.6
14.9
11.2
24.9
2.4
15.5
11.2
38.6
2.7
22.5
18.1
13.8
34.8
2.7
29.4
25.1
20.7
16.4
31.0
2.6
29.4
27.6
23.2
18.9
14.5
26.5
2.6
27.2
25.3
21.0
16.6
12.3
25.6
2.5
17.5
12.5
39.7
2.7
25.3
20.3
15.3
35.8
2.7
33.1
28.1
23.1
18.1
31.9
2.6
30.8
30.8
25.8
20.8
15.8
27.3
2.6
28.3
28.3
23.3
18.3
13.3
26.4
2.5
26.7
21.1
15.5
35.8
2.6
34.7
29.2
23.6
17.9
31.9
2.6
30.7
30.7
25.1
19.5
13.8
27.3
2.5
28.2
28.2
22.6
17.0
11.3
26.4
2.4
28.2
21.9
15.6
35.8
2.6
36.4
30.3
24.1
17.8
31.9
2.5
30.6
30.6
24.3
18.1
11.8
27.3
2.5
28.1
28.1
21.8
15.6
9.3
26.4
2.4
90
17.0
22.2
27.5
31.4
19.7
25.6
31.5
32.8
29.7
22.3
28.9
35.4
34.2
31.0
25.0
32.2
39.4
35.6
32.3
34.6
40.1
35.5
32.2
36.9
40.7
35.5
32.1
12.7
19.0
25.3
25.0
16.5
22.0
27.5
25.8
24.9
20.4
25.0
29.7
26.5
25.6
24.2
28.0
31.9
27.3
26.4
30.4
31.9
27.3
26.4
32.7
31.9
27.3
26.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
13.9
10.7
19.1
16.0
12.8
24.3
21.2
18.1
14.9
29.6
24.7
21.6
18.4
15.9
12.1
21.8
18.0
14.2
27.7
23.9
20.1
16.3
31.6
27.8
24.0
20.2
29.7
26.4
22.6
18.8
17.9
13.4
24.4
20.0
15.5
31.0
26.5
22.1
17.6
33.6
30.9
26.4
21.9
31.0
29.3
24.9
20.4
19.9
14.8
27.1
22.0
16.8
34.3
29.2
24.0
18.9
35.6
34.0
28.8
23.7
32.3
32.3
27.1
22.0
28.9
23.2
17.5
36.5
30.8
25.1
19.4
35.5
34.7
29.0
23.3
32.2
32.2
26.5
20.8
30.6
24.4
18.1
38.6
32.4
26.1
19.9
35.5
35.5
29.2
23.0
32.1
32.1
25.9
19.6
105°F
11.2
8.3
16.1
13.1
10.2
20.9
17.9
15.0
12.1
24.7
19.5
16.5
13.6
13.0
9.4
18.4
14.9
11.3
23.9
20.3
16.8
13.2
25.5
22.1
18.5
14.9
24.9
21.4
17.8
14.2
14.7
10.5
20.8
16.6
12.4
26.9
22.7
18.5
14.3
26.4
24.7
20.5
16.3
25.6
23.9
19.6
15.4
16.4
11.6
23.2
18.4
13.5
30.0
25.1
20.3
15.4
27.3
27.3
22.5
17.6
26.4
26.4
21.5
16.7
24.9
19.5
14.0
30.9
26.7
21.2
15.7
27.3
27.3
21.9
16.4
26.4
26.4
20.9
15.5
26.7
20.6
14.5
31.9
28.2
22.1
16.0
27.3
27.3
21.2
15.2
26.4
26.4
20.3
14.2
65
15.3
16.4
15.0
17.5
15.9
18.6
16.9
17.6
15.1
16.7
13.4
10.7
11.4
10.6
12.1
11.2
12.8
11.8
10.9
10.0
9.1
8.2
67
5123247-TTG-A-0515
ZKTA3 (3.0 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
750
900
1050
1200
1350
1500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
34.0
30.0
26.0
22.8
34.5
30.4
26.4
23.1
23.7
35.0
30.9
26.8
23.4
24.0
35.4
31.3
27.2
23.8
24.4
31.5
27.3
23.9
24.5
31.6
27.4
24.0
24.6
2.4
2.5
2.6
2.4
2.5
2.6
2.7
2.5
2.5
2.6
2.7
2.8
2.6
2.6
2.7
2.8
2.9
2.7
2.7
2.7
2.9
2.6
2.6
2.7
2.8
2.5
2.5
11.6
18.1
24.6
22.8
15.9
20.7
25.5
23.1
23.7
20.1
23.2
26.3
23.4
24.0
24.4
25.8
27.2
23.8
24.4
28.4
27.3
23.9
24.5
31.1
27.4
24.0
24.6
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
10.9
8.1
31.5
2.1
15.3
12.4
9.6
27.2
2.3
19.6
16.8
13.9
11.1
22.8
2.6
22.8
18.0
15.1
12.3
9.5
20.5
2.2
12.4
9.0
31.4
2.3
17.2
13.8
10.3
27.1
2.5
22.0
18.6
15.1
11.7
22.7
2.8
23.1
19.9
16.5
13.0
9.6
20.4
2.4
23.7
20.4
17.0
13.5
10.1
22.5
2.5
13.9
9.8
31.3
2.5
19.2
15.1
11.0
26.9
2.8
24.4
20.4
16.3
12.2
22.6
3.0
23.4
21.8
17.8
13.7
9.6
20.3
2.6
24.0
22.4
18.3
14.3
10.2
22.5
2.7
15.4
10.7
31.2
2.7
21.1
16.4
11.8
26.8
3.0
26.9
22.2
17.5
12.8
22.4
3.3
23.8
23.8
19.1
14.4
9.7
20.2
2.8
24.4
24.4
19.7
15.0
10.3
22.4
2.9
23.1
17.9
12.6
27.1
2.9
27.1
24.1
18.8
13.6
22.7
3.1
23.9
23.9
18.6
13.3
8.1
20.5
2.7
24.5
24.5
19.2
14.0
8.7
22.7
2.8
25.2
19.3
13.4
27.4
2.7
27.4
26.0
20.2
14.3
23.0
3.0
24.0
24.0
18.1
12.3
6.4
20.7
2.6
24.6
24.6
18.8
12.9
7.0
22.9
2.7
90
11.5
17.2
22.8
20.5
15.9
19.3
22.7
20.4
22.5
20.3
21.4
22.6
20.3
22.5
24.7
23.6
22.4
20.2
22.4
26.5
22.7
20.5
22.7
27.4
23.0
20.7
22.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
9.9
7.9
14.5
11.7
9.0
18.3
15.6
12.9
10.1
20.5
16.5
13.7
11.0
11.8
8.5
16.0
12.7
9.3
20.1
16.8
13.5
10.2
20.4
17.7
14.4
11.1
22.5
19.5
16.2
12.8
13.7
9.2
17.5
13.6
9.7
21.9
18.0
14.1
10.2
20.3
19.0
15.0
11.1
22.5
21.0
17.0
13.1
15.6
9.8
19.0
14.5
10.0
22.4
19.2
14.7
10.2
20.2
20.2
15.7
11.2
22.4
22.4
17.9
13.4
21.4
16.3
11.2
22.7
21.6
16.5
11.4
20.5
20.5
15.4
10.3
22.7
22.7
17.6
12.5
23.7
18.0
12.3
23.0
23.0
18.2
12.6
20.7
20.7
15.0
9.3
22.9
22.9
17.2
11.5
65
8.3
7.7
9.5
7.2
9.2
6.7
8.9
5.2
7.4
3.7
5.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
68
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKTA3 (3.0 Ton) Reheat
Air on
Evaporator Coil
CFM
Total
Capacity1
(MBh)
Total
Input
(kW)2
62.5
64
65.3
62.5
64
65.3
62.5
64
65.3
14.1
15.3
17.0
14.9
15.6
16.1
21.7
22.3
22.5
1.3
1.3
1.4
1.3
1.3
1.3
1.9
1.9
1.8
62.5
64
65.3
62.5
64
65.3
62.5
64
62
18.5
19.7
20.9
19.2
20.3
22.2
19.8
21.1
22.3
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
62.5
64
65.3
62.5
64
65.3
62.5
64
65.3
16.3
17.6
18.8
16.6
18.0
18.9
15.8
17.3
18.5
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
62.5
64
65.3
62.5
64
65.3
62.5
64
62
12.0
12.5
13.4
11.8
12.9
13.9
11.7
12.6
13.6
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
WB
(°F)
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
(- indicates heating)
Capacity1
Return Dry Bulb (°F)
(MBh)
75
40 °F
1050
1200
1350
50 °F
8.9
8.1
7.1
9.7
8.7
7.8
11.1
9.3
8.0
19.7
21.3
22.5
20.3
21.2
23.1
21.6
23.1
24.7
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
8.1
6.6
5.4
9.0
7.6
6.3
9.8
8.4
7.2
17.0
18.4
19.6
17.0
18.5
19.9
16.1
17.3
18.8
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
7.2
5.5
4.0
7.4
6.1
5.0
7.8
6.7
5.2
15.0
16.2
16.6
14.9
16.1
17.2
14.4
15.6
16.7
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
4.5
3.1
1.9
5.0
3.7
2.3
5.6
4.0
2.7
7.5
8.5
9.3
8.8
8.0
8.2
6.0
6.7
7.7
2.3
2.3
2.4
2.3
2.3
2.4
2.3
2.3
2.3
60 °F
1050
1200
1350
1200
1350
1200
1350
6.8
5.5
4.4
7.9
6.6
5.5
8.4
6.8
5.7
80 °F
85 °F
1050
8.9
7.5
6.2
9.8
8.3
7.1
10.9
9.7
8.2
70 °F
75 °F
1050
Sensible Capacity (MBh)
(- indicates heating)
Return Dry Bulb (°F)
75
Total
Input
(kW)2
5.9
4.5
3.6
6.7
5.5
3.9
7.1
5.8
4.4
95 °F
1.7
0.5
-0.9
-0.6
0.6
-0.9
1.9
0.6
-0.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
69
5123247-TTG-A-0515
ZKTA4 (4.0 Ton) Cooling
Air on
Evaporator Coil
CFM
1000
1200
1400
1600
1800
2000
1000
1200
1400
1600
1800
2000
70
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
70.8
62.1
53.5
48.3
73.1
64.2
55.3
50.0
48.7
75.5
66.3
57.1
51.6
50.2
77.9
68.4
58.9
53.2
51.8
70.3
60.5
54.7
53.2
72.1
62.1
56.1
54.7
1.6
2.0
2.4
2.0
1.8
2.2
2.6
2.2
2.2
2.1
2.4
2.8
2.4
2.4
2.3
2.6
3.0
2.6
2.6
2.4
2.8
2.4
2.4
2.2
2.6
2.2
2.2
27.3
34.1
40.8
48.3
30.4
37.7
45.1
50.0
48.7
33.4
41.4
49.4
51.6
50.2
36.5
45.1
53.7
53.2
51.8
48.1
57.9
54.7
53.2
51.0
62.1
56.1
54.7
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
52.2
47.9
43.6
37.9
54.4
49.9
45.4
39.5
39.6
56.6
51.9
47.3
41.1
41.2
58.8
54.0
49.1
42.7
42.8
54.1
49.2
42.7
42.8
54.2
49.3
42.8
42.9
4.4
3.9
3.4
3.9
4.2
3.7
3.2
3.6
3.6
4.0
3.5
3.0
3.4
3.4
3.7
3.3
2.9
3.2
3.2
3.5
3.1
3.4
3.4
3.7
3.3
3.7
3.7
24.8
30.5
36.3
37.9
27.7
33.9
40.1
39.5
39.6
30.5
37.3
44.0
41.1
41.2
33.4
40.7
47.9
42.7
42.8
44.1
48.6
42.7
42.8
47.5
49.3
42.8
42.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
22.8
18.2
61.5
3.0
29.5
24.9
20.3
55.0
3.0
36.2
31.6
27.0
22.4
48.5
2.9
46.8
37.7
33.1
28.5
23.9
43.1
2.9
25.1
19.9
63.8
3.0
32.5
27.3
22.0
57.1
3.0
39.9
34.6
29.4
24.2
50.3
2.9
48.9
41.3
36.1
30.9
25.6
44.7
2.9
48.7
44.1
38.9
33.7
28.4
44.1
2.9
27.5
21.6
66.1
3.0
35.5
29.6
23.8
59.1
3.0
43.5
37.6
31.8
25.9
52.2
2.9
51.1
44.9
39.0
33.1
27.3
46.3
2.9
50.2
48.0
42.1
36.2
30.3
45.7
2.9
29.9
23.4
68.4
3.0
38.6
32.0
25.5
61.2
3.0
47.2
40.7
34.1
27.6
54.0
2.9
53.2
48.5
42.0
35.4
28.9
47.9
2.9
51.8
51.8
45.3
38.7
32.2
47.3
2.9
40.9
33.7
26.6
62.2
3.0
50.0
42.8
35.7
28.5
54.8
2.9
54.7
52.3
45.1
38.0
30.8
48.7
2.9
53.2
53.2
46.1
38.9
31.7
48.0
2.9
43.2
35.4
27.7
63.1
3.0
52.8
45.0
37.2
29.4
55.7
2.9
56.1
56.1
48.3
40.5
32.7
49.5
2.9
54.7
54.7
46.9
39.1
31.3
48.8
2.9
95°F
20.5
16.1
51.3
4.2
26.2
21.9
17.6
45.4
3.9
31.9
27.6
23.3
19.0
39.6
3.6
37.9
33.9
29.5
25.2
20.9
34.1
3.8
22.6
17.5
52.8
4.1
28.8
23.8
18.7
46.8
3.8
35.1
30.0
25.0
19.9
40.8
3.5
39.5
36.8
31.7
26.7
21.6
35.1
3.7
39.6
36.9
31.8
26.8
21.7
35.7
3.7
24.7
18.9
54.3
4.0
31.5
25.7
19.9
48.2
3.7
38.2
32.4
26.6
20.8
42.0
3.4
41.1
39.7
33.9
28.1
22.3
36.2
3.6
41.2
39.8
34.0
28.2
22.4
36.8
3.6
26.9
20.3
55.8
3.9
34.1
27.6
21.0
49.5
3.6
41.3
34.8
28.3
21.7
43.2
3.4
42.7
42.7
36.1
29.6
23.1
37.2
3.5
42.8
42.8
36.2
29.7
23.1
37.9
3.5
36.9
29.7
22.5
49.9
3.7
44.7
37.5
30.3
23.1
43.5
3.5
42.7
42.7
35.5
28.4
21.2
37.5
3.6
42.8
42.8
35.6
28.4
21.3
38.1
3.6
39.7
31.8
24.0
50.3
3.9
48.0
40.2
32.3
24.5
43.8
3.6
42.8
42.8
35.0
27.1
19.3
37.8
3.7
42.9
42.9
35.1
27.2
19.4
38.4
3.7
90
26.1
32.3
38.5
43.1
29.0
35.8
42.6
44.7
44.1
32.0
39.3
46.7
46.3
45.7
34.9
42.9
50.8
47.9
47.3
46.1
53.3
48.7
48.0
49.3
55.7
49.5
48.8
21.3
28.4
35.5
34.1
25.3
31.6
37.8
35.1
35.7
29.4
34.8
40.2
36.2
36.8
33.5
38.0
42.6
37.2
37.9
41.5
43.2
37.5
38.1
44.9
43.8
37.8
38.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
21.6
17.2
27.8
23.4
18.9
34.1
29.6
25.2
20.7
42.3
35.8
31.3
26.9
23.9
18.7
30.7
25.5
20.4
37.5
32.3
27.2
22.0
44.2
39.1
33.9
28.8
44.1
40.5
35.4
30.2
26.1
20.3
33.5
27.7
21.8
40.9
35.0
29.2
23.3
46.1
42.3
36.5
30.6
45.7
43.9
38.1
32.2
28.4
21.9
36.3
29.8
23.3
44.3
37.7
31.2
24.7
47.9
45.6
39.1
32.5
47.3
47.3
40.7
34.2
38.9
31.7
24.5
47.3
40.2
33.0
25.8
48.7
47.5
40.3
33.2
48.0
48.0
40.9
33.7
41.5
33.6
25.8
50.4
42.6
34.8
27.0
49.5
49.5
41.6
33.8
48.8
48.8
41.0
33.1
105°F
18.4
14.1
24.1
19.9
15.6
29.8
25.6
21.3
17.1
34.1
29.2
25.0
20.7
20.4
15.4
26.6
21.7
16.7
32.9
27.9
22.9
18.0
35.1
31.9
26.9
22.0
35.7
32.4
27.5
22.5
22.4
16.7
29.1
23.5
17.8
35.9
30.2
24.6
18.9
36.2
34.6
28.9
23.2
36.8
35.1
29.5
23.8
24.4
18.0
31.7
25.3
18.9
39.0
32.6
26.2
19.8
37.2
37.2
30.8
24.5
37.9
37.9
31.5
25.1
34.4
27.3
20.3
41.1
35.2
28.1
21.1
37.5
37.5
30.4
23.4
38.1
38.1
31.1
24.0
37.1
29.4
21.6
43.2
37.9
30.1
22.4
37.8
37.8
30.0
22.3
38.4
38.4
30.7
22.9
65
22.4
23.6
25.1
24.8
26.4
26.0
27.7
26.0
26.5
26.0
25.3
16.5
17.0
17.6
17.5
18.1
18.1
18.7
16.3
16.9
14.5
15.2
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKTA4 (4.0 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
1000
1200
1400
1600
1800
2000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
50.4
43.0
35.6
30.3
51.2
43.7
36.1
30.8
31.9
52.0
44.4
36.7
31.3
32.4
52.9
45.1
37.3
31.8
32.9
45.7
37.8
32.2
33.5
46.4
38.4
32.7
34.0
4.0
3.9
3.8
3.7
4.0
3.9
3.8
3.7
3.8
4.0
3.9
3.8
3.7
3.8
4.0
3.9
3.8
3.8
3.8
3.9
3.9
3.8
3.8
4.0
3.9
3.8
3.8
17.7
26.2
34.6
30.3
23.0
29.3
35.5
30.8
31.9
28.3
32.3
36.4
31.3
32.4
33.6
35.4
37.3
31.8
32.9
38.8
37.8
32.2
33.5
42.2
38.4
32.7
34.0
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
16.3
12.1
49.5
3.7
22.0
17.8
13.6
40.5
3.9
27.7
23.5
19.3
15.2
31.5
4.0
30.3
24.6
20.5
16.3
12.1
26.5
3.6
18.1
13.3
49.6
3.9
24.4
19.5
14.7
40.6
4.0
30.7
25.8
20.9
16.1
31.5
4.1
30.8
27.0
22.1
17.3
12.4
26.5
3.8
31.9
28.0
23.2
18.3
13.4
28.1
3.8
20.0
14.5
49.7
4.0
26.8
21.3
15.7
40.6
4.1
33.6
28.1
22.5
17.0
31.4
4.2
31.3
29.4
23.8
18.3
12.8
26.4
3.9
32.4
30.5
24.9
19.4
13.8
28.1
3.9
21.9
15.6
49.9
4.2
29.2
23.0
16.8
40.6
4.3
36.6
30.3
24.1
17.9
31.3
4.3
31.8
31.8
25.5
19.3
13.1
26.3
4.0
32.9
32.9
26.7
20.5
14.3
28.0
4.1
31.9
24.9
18.0
41.6
4.2
37.5
32.9
26.0
19.0
32.2
4.3
32.2
32.2
25.3
18.4
11.4
27.0
3.9
33.5
33.5
26.5
19.6
12.6
28.8
4.0
34.6
26.9
19.3
42.6
4.1
38.4
35.5
27.9
20.2
33.0
4.2
32.7
32.7
25.1
17.4
9.8
27.7
3.8
34.0
34.0
26.3
18.6
11.0
29.5
3.9
90
16.5
24.0
31.5
26.5
22.4
26.9
31.5
26.5
28.1
28.4
29.9
31.4
26.4
28.1
34.3
32.8
31.3
26.3
28.0
36.2
32.2
27.0
28.8
39.5
33.0
27.7
29.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
12.8
10.1
19.9
15.8
11.7
25.6
21.5
17.4
13.3
26.5
20.0
15.9
11.8
15.9
11.2
22.2
17.4
12.7
28.4
23.7
18.9
14.2
26.5
22.1
17.4
12.6
28.1
23.6
18.8
14.1
19.0
12.2
24.5
19.0
13.6
31.3
25.9
20.5
15.1
26.4
24.2
18.8
13.4
28.1
25.8
20.4
15.0
22.2
13.3
26.8
20.7
14.6
31.3
28.1
22.0
15.9
26.3
26.3
20.2
14.2
28.0
28.0
22.0
15.9
29.4
22.6
15.7
32.2
30.6
23.8
17.0
27.0
27.0
20.2
13.4
28.8
28.8
21.9
15.1
32.0
24.4
16.9
33.0
33.0
25.6
18.1
27.7
27.7
20.1
12.6
29.5
29.5
21.9
14.4
65
7.7
7.8
9.3
8.0
9.6
8.1
9.8
6.6
8.3
5.0
6.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
71
5123247-TTG-A-0515
ZKTA4 (4.0 Ton) Reheat
Air on
Evaporator Coil
CFM
Total
Capacity1
(MBh)
Total
Input
(kW)2
62.5
64
65.3
62.5
64
65.3
62.5
64
65.3
24.5
25.7
26.6
24.0
25.8
27.1
24.3
26.2
27.1
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
62.5
64
65.3
62.5
64
65.3
62.5
64
62
21.8
25.3
26.9
22.7
25.4
26.9
20.1
22.3
23.7
2.6
2.7
2.7
2.7
2.7
2.7
2.6
2.6
2.6
62.5
64
65.3
62.5
64
65.3
62.5
64
65.3
19.0
21.5
22.2
19.3
21.3
22.6
16.9
18.2
19.9
2.7
2.8
2.8
2.8
2.8
2.8
2.7
2.7
2.8
62.5
64
65.3
62.5
64
65.3
62.5
64
62
17.7
19.0
20.4
16.2
18.2
19.6
13.3
14.8
15.8
2.9
2.9
2.9
2.9
3.0
3.0
2.9
2.9
2.9
WB
(°F)
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
(- indicates heating)
Capacity1
Return Dry Bulb (°F)
(MBh)
75
40 °F
1200
1600
2000
50 °F
9.1
7.4
6.1
12.4
10.0
8.3
12.9
11.1
9.2
22.9
26.9
27.1
24.5
26.7
28.5
22.7
24.7
26.5
2.6
2.7
2.6
2.6
2.6
2.6
2.6
2.6
2.6
7.1
6.3
4.8
9.9
8.8
7.5
10.2
8.6
6.9
19.8
23.0
23.5
20.6
22.4
24.4
18.2
20.5
21.4
2.7
2.8
2.7
2.7
2.8
2.8
2.7
2.7
2.7
5.5
5.1
2.8
8.1
6.3
4.7
7.9
6.3
4.8
17.6
20.9
21.5
17.9
19.9
21.1
15.1
16.7
18.3
2.8
2.9
2.9
2.9
2.9
2.9
2.8
2.8
2.8
5.0
3.4
2.1
6.4
5.0
3.1
6.6
4.7
3.1
12.8
13.8
14.0
9.7
10.8
12.2
6.2
7.2
8.0
3.1
3.2
3.1
3.1
3.2
3.2
3.0
3.0
3.0
60 °F
1200
1600
2000
1600
2000
1600
2000
6.2
0.0
2.9
8.8
6.8
5.9
8.9
7.7
5.3
80 °F
85 °F
1200
8.0
7.2
5.5
11.2
9.2
7.7
11.6
10.0
8.5
70 °F
75 °F
1200
Sensible Capacity (MBh)
(- indicates heating)
Return Dry Bulb (°F)
75
Total
Input
(kW)2
4.7
3.7
2.3
7.5
5.7
4.1
7.1
5.6
4.0
95 °F
3.5
-0.2
-1.5
2.4
1.0
-0.7
1.4
-0.1
-1.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
72
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKTA5 (5.0 Ton) Cooling
Air on
Evaporator Coil
CFM
1250
1500
1750
2000
2250
2500
1250
1500
1750
2000
2250
2500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
81.7
72.8
64.0
57.0
85.0
75.8
66.6
59.3
58.1
88.3
78.7
69.2
61.6
60.4
91.6
81.7
71.8
63.9
62.6
82.5
72.5
64.5
63.3
83.4
73.2
65.2
63.9
5.9
5.0
4.0
3.6
5.4
4.5
3.6
3.2
4.1
4.9
4.1
3.2
2.8
3.7
4.4
3.6
2.8
2.5
3.2
3.9
3.0
2.6
3.5
4.2
3.3
2.8
3.7
33.6
41.9
50.2
57.0
37.9
47.1
56.4
59.3
58.1
42.1
52.3
62.5
61.6
60.4
46.3
57.5
68.6
63.9
62.6
60.8
70.9
64.5
63.3
64.2
73.2
65.2
63.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
70.7
62.8
54.8
48.1
73.1
64.9
56.7
49.7
49.7
75.5
67.0
58.5
51.3
51.3
77.9
69.1
60.4
52.9
52.9
69.3
60.5
53.0
53.1
69.4
60.7
53.2
53.2
3.7
3.7
3.7
4.0
3.8
3.7
3.7
4.0
4.0
3.8
3.7
3.7
4.0
4.0
3.8
3.8
3.7
4.0
4.1
3.9
3.9
4.3
4.3
4.1
4.1
4.5
4.5
30.8
38.2
45.5
48.1
34.5
42.5
50.5
49.7
49.7
38.2
46.8
55.4
51.3
51.3
41.8
51.1
60.4
52.9
52.9
55.0
60.5
53.0
53.1
58.9
60.7
53.2
53.2
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
27.7
21.9
76.2
4.8
36.1
30.2
24.3
67.8
4.3
44.4
38.5
32.6
26.7
59.4
3.8
57.0
45.7
39.9
33.9
28.1
52.5
3.8
31.1
24.3
79.0
4.6
40.4
33.6
26.8
70.3
4.1
49.6
42.9
36.1
29.3
61.6
3.7
59.3
50.9
44.1
37.4
30.6
54.5
3.6
58.1
52.1
45.3
38.6
31.8
53.9
4.1
34.4
26.8
81.9
4.3
44.6
37.0
29.4
72.9
3.9
54.8
47.2
39.5
31.9
63.9
3.5
61.6
56.0
48.4
40.7
33.1
56.4
3.4
60.4
57.3
49.7
42.1
34.4
55.8
3.9
37.8
29.3
84.7
4.1
48.9
40.4
31.9
75.4
3.7
60.1
51.5
43.0
34.5
66.1
3.3
63.9
61.2
52.7
44.1
35.6
58.4
3.2
62.6
62.6
54.1
45.6
37.0
57.8
3.6
51.6
42.4
33.2
75.9
3.9
63.3
54.1
44.9
35.8
66.5
3.5
64.5
63.2
54.0
44.8
35.6
58.8
3.5
63.3
63.3
54.1
44.9
35.7
58.2
3.9
54.3
44.5
34.6
76.4
4.1
66.6
56.7
46.9
37.1
66.9
3.7
65.2
65.2
55.3
45.5
35.6
59.2
3.7
63.9
63.9
54.0
44.2
34.4
58.5
4.1
95°F
25.3
19.7
65.8
4.9
32.6
27.0
21.5
57.8
4.6
39.9
34.3
28.8
23.2
49.8
4.3
48.1
41.4
35.8
30.3
24.7
43.0
4.6
28.0
21.6
67.2
4.8
36.0
29.5
23.1
59.0
4.5
44.0
37.5
31.1
24.6
50.8
4.3
49.7
45.2
38.8
32.3
25.8
43.9
4.6
49.7
45.3
38.8
32.3
25.9
44.9
4.6
30.8
23.4
68.6
4.7
39.4
32.1
24.7
60.3
4.5
48.1
40.7
33.3
26.0
51.9
4.2
51.3
49.1
41.7
34.3
27.0
44.9
4.5
51.3
49.1
41.7
34.4
27.0
45.9
4.5
33.5
25.2
70.0
4.7
42.8
34.6
26.3
61.5
4.4
52.2
43.9
35.6
27.3
53.0
4.1
52.9
52.9
44.6
36.4
28.1
45.8
4.4
52.9
52.9
44.7
36.4
28.1
46.8
4.4
46.0
37.0
27.9
61.6
4.6
56.0
46.9
37.9
28.9
53.1
4.3
53.0
53.0
44.0
35.0
25.9
45.9
4.6
53.1
53.1
44.0
35.0
26.0
46.9
4.7
49.1
39.4
29.6
61.6
4.8
59.8
50.0
40.2
30.4
53.1
4.5
53.2
53.2
43.4
33.6
23.8
45.9
4.8
53.2
53.2
43.4
33.6
23.8
46.9
4.9
90
32.2
40.1
47.9
52.5
36.2
44.8
53.4
54.5
53.9
40.1
49.5
59.0
56.4
55.8
44.0
54.3
64.5
58.4
57.8
57.9
65.7
58.8
58.2
61.6
66.9
59.2
58.5
25.3
35.2
45.1
43.0
31.0
39.4
47.7
43.9
44.9
36.8
43.6
50.4
44.9
45.9
42.5
47.8
53.0
45.8
46.8
51.5
53.1
45.9
46.9
55.3
53.1
45.9
46.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
26.5
20.8
34.3
28.6
22.9
42.1
36.4
30.7
25.0
52.5
43.6
37.8
32.1
29.6
23.0
38.2
31.6
25.0
46.8
40.2
33.6
27.0
54.5
48.1
41.4
34.8
53.9
48.7
42.1
35.4
32.6
25.1
42.0
34.5
27.0
51.5
43.9
36.4
28.9
56.4
52.5
45.0
37.5
55.8
53.2
45.7
38.2
35.6
27.2
45.9
37.5
29.1
56.1
47.7
39.3
30.9
58.4
57.0
48.6
40.2
57.8
57.8
49.4
41.0
48.8
39.7
30.6
59.6
50.5
41.4
32.3
58.8
58.1
49.0
39.9
58.2
58.2
49.1
39.9
51.7
41.9
32.1
63.2
53.4
43.5
33.7
59.2
59.2
49.3
39.5
58.5
58.5
48.7
38.9
105°F
21.7
16.5
29.7
24.3
18.9
37.8
32.1
26.6
21.2
43.0
35.7
30.3
24.8
24.5
18.1
33.0
26.6
20.2
41.5
35.1
28.7
22.3
43.9
39.1
32.7
26.3
44.9
39.9
33.5
27.1
27.3
19.7
36.2
28.9
21.6
45.2
38.1
30.8
23.5
44.9
42.5
35.1
27.8
45.9
43.4
36.0
28.7
30.0
21.2
39.5
31.2
22.9
48.9
41.2
32.9
24.6
45.8
45.8
37.5
29.2
46.8
46.8
38.5
30.3
42.5
33.4
24.3
50.8
44.1
35.0
26.0
45.9
45.9
36.8
27.7
46.9
46.9
37.8
28.7
45.5
35.6
25.8
52.7
47.0
37.2
27.3
45.9
45.9
36.1
26.2
46.9
46.9
37.1
27.2
65
26.4
28.2
28.8
30.0
30.7
31.8
32.6
30.8
30.8
29.7
29.1
19.4
19.9
20.8
20.4
21.4
21.0
22.0
18.7
19.7
16.4
17.4
73
5123247-TTG-A-0515
ZKTA5 (5.0 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
1250
1500
1750
2000
2250
2500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
60.8
52.8
44.7
37.9
61.3
53.2
45.0
38.2
40.1
61.7
53.5
45.3
38.5
40.4
62.2
53.9
45.7
38.8
40.7
53.9
45.6
38.7
40.7
53.8
45.6
38.7
40.6
6.1
5.6
5.0
5.3
5.9
5.4
4.8
5.1
5.2
5.7
5.2
4.7
4.9
5.0
5.5
5.0
4.5
4.8
4.8
5.2
4.7
5.0
5.1
5.5
4.9
5.2
5.3
19.8
32.2
44.7
37.9
27.6
36.3
45.0
38.2
40.1
35.4
40.4
45.3
38.5
40.4
43.2
44.4
45.7
38.8
40.7
48.1
45.6
38.7
40.7
51.7
45.6
38.7
40.6
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
18.1
13.3
55.9
7.3
26.9
21.6
16.2
47.8
6.5
35.7
29.8
24.5
19.1
39.6
5.7
37.9
30.0
24.7
19.4
14.0
32.9
5.9
20.9
14.6
55.4
7.0
30.0
23.6
17.3
47.3
6.2
39.0
32.7
26.4
20.0
39.2
5.4
38.2
32.9
26.6
20.3
14.0
32.5
5.7
40.1
34.6
28.3
22.0
15.6
35.4
5.8
23.8
15.9
54.8
6.7
33.1
25.7
18.4
46.8
5.9
42.3
35.6
28.3
20.9
38.8
5.2
38.5
35.8
28.5
21.2
13.9
32.1
5.4
40.4
37.7
30.3
23.0
15.7
35.0
5.5
26.6
17.2
54.3
6.4
36.1
27.8
19.5
46.3
5.7
45.7
38.5
30.1
21.8
38.3
4.9
38.8
38.8
30.4
22.1
13.8
31.7
5.1
40.7
40.7
32.4
24.1
15.8
34.6
5.2
38.9
29.8
20.7
46.2
5.9
45.6
41.2
32.1
23.0
38.2
5.1
38.7
38.7
29.6
20.5
11.4
31.6
5.4
40.7
40.7
31.6
22.5
13.4
34.5
5.5
41.8
31.9
22.0
46.0
6.1
45.6
44.0
34.1
24.2
38.1
5.3
38.7
38.7
28.8
18.9
9.0
31.5
5.6
40.6
40.6
30.7
20.8
10.9
34.4
5.7
90
18.9
29.2
39.6
32.9
27.2
33.2
39.2
32.5
35.4
35.6
37.2
38.8
32.1
35.0
43.9
41.1
38.3
31.7
34.6
44.6
38.2
31.6
34.5
46.0
38.1
31.5
34.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
12.5
10.1
24.0
18.8
13.6
34.3
27.5
22.3
17.1
32.9
24.3
19.1
13.9
17.4
11.1
27.0
20.7
14.4
36.5
30.3
24.0
17.8
32.5
26.8
20.5
14.3
35.4
29.3
23.0
16.8
22.3
12.2
29.9
22.6
15.3
38.8
33.0
25.7
18.4
32.1
29.2
21.9
14.7
35.0
31.9
24.7
17.4
27.2
13.2
32.8
24.5
16.1
38.3
35.7
27.4
19.1
31.7
31.7
23.4
15.0
34.6
34.6
26.3
18.0
35.4
26.3
17.1
38.2
38.2
29.3
20.1
31.6
31.6
22.4
13.3
34.5
34.5
25.3
16.2
38.1
28.1
18.2
38.1
38.1
31.1
21.2
31.5
31.5
21.5
11.5
34.4
34.4
24.4
14.5
65
8.7
8.0
10.5
7.4
10.1
6.7
9.6
4.1
7.1
1.6
4.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
74
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKTA5 (5.0 Ton) Reheat
Air on
Evaporator Coil
CFM
Total
Capacity1
(MBh)
Total
Input
(kW)2
62.5
64
65.3
62.5
64
65.3
62.5
64
65.3
26.8
28.9
30.0
29.2
30.8
31.4
29.8
31.2
31.4
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
62.5
64
65.3
62.5
64
65.3
62.5
64
62
26.7
28.9
31.6
27.9
31.0
32.9
26.8
29.5
31.7
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
62.5
64
65.3
62.5
64
65.3
62.5
64
65.3
22.8
25.5
27.8
23.2
25.7
27.8
21.6
23.8
26.1
3.5
3.5
3.5
3.5
3.5
3.5
3.4
3.5
3.5
62.5
64
65.3
62.5
64
65.3
62.5
64
62
17.4
19.7
21.6
17.3
19.4
20.9
16.0
18.0
19.4
3.5
3.6
3.6
3.6
3.6
3.6
3.5
3.6
3.6
WB
(°F)
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
(- indicates heating)
Capacity1
Return Dry Bulb (°F)
(MBh)
75
40 °F
1750
2000
2250
50 °F
8.4
6.4
4.8
11.0
8.6
5.8
10.5
7.6
6.0
29.3
32.4
34.7
30.3
32.3
35.3
29.6
32.1
34.5
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
9.2
6.9
5.4
10.9
8.4
6.7
9.5
6.9
4.5
24.5
27.0
28.7
25.0
27.3
29.6
23.6
26.1
28.2
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
7.1
5.1
3.3
8.0
5.9
4.3
6.8
4.5
1.9
21.3
23.9
25.8
21.3
23.7
25.7
19.5
22.0
24.1
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.9
2.0
-0.3
5.0
2.5
0.5
3.5
0.4
-1.7
8.3
9.8
11.2
7.1
8.8
10.3
5.0
6.1
8.3
3.8
3.8
3.9
3.8
3.8
3.9
3.8
3.8
3.9
60 °F
1750
2000
2250
2000
2250
2000
2250
8.0
6.4
4.3
9.0
6.9
4.9
7.3
4.7
2.7
80 °F
85 °F
1750
10.7
9.2
7.3
11.9
9.9
8.4
11.1
8.5
6.2
70 °F
75 °F
1750
Sensible Capacity (MBh)
(- indicates heating)
Return Dry Bulb (°F)
75
Total
Input
(kW)2
6.3
4.6
2.7
7.3
5.3
3.6
5.6
3.1
1.0
95 °F
-1.8
-3.9
-5.3
-0.9
-3.0
-5.2
-3.3
-6.2
-8.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
75
5123247-TTG-A-0515
ZKT06 (6.5 Ton) Cooling
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
76
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
99.9
91.5
83.0
72.4
106.5
97.5
88.5
77.2
78.2
113.1
103.5
93.9
81.9
83.1
119.7
109.5
99.4
86.7
87.9
109.6
99.5
86.8
88.0
109.7
99.6
86.9
88.0
5.1
5.0
5.0
4.9
5.1
5.1
5.1
5.0
5.0
5.2
5.2
5.1
5.1
5.1
5.3
5.2
5.2
5.1
5.2
5.2
5.1
5.1
5.1
5.1
5.1
5.0
5.0
39.3
50.3
61.3
72.4
45.5
57.8
70.1
77.2
78.2
51.6
65.2
78.8
81.9
83.1
57.8
72.7
87.6
86.7
87.9
74.8
91.9
86.8
88.0
76.9
96.1
86.9
88.0
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
81.2
75.9
70.7
64.9
87.0
81.4
75.8
69.7
63.0
92.9
87.0
81.0
74.4
67.3
98.8
92.5
86.1
79.1
71.5
90.8
84.5
77.6
70.2
89.1
83.0
76.2
68.9
6.5
6.5
6.4
6.4
6.6
6.5
6.5
6.4
6.5
6.7
6.6
6.6
6.5
6.5
6.7
6.7
6.6
6.6
6.6
6.6
6.6
6.5
6.6
6.6
6.5
6.5
6.5
34.6
45.6
56.7
64.9
40.1
52.5
64.9
69.7
63.0
45.5
59.3
73.2
74.4
67.3
51.0
66.2
81.4
79.1
71.5
68.3
82.2
77.6
70.2
70.4
83.0
76.2
68.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
33.2
27.1
90.5
5.8
44.2
38.1
32.1
83.7
5.7
55.2
49.2
43.1
37.0
76.9
5.7
70.1
60.9
54.9
48.8
42.7
68.7
5.7
37.9
30.3
96.8
5.9
50.2
42.6
35.1
89.5
5.8
62.5
54.9
47.4
39.8
82.2
5.8
75.6
68.1
60.5
52.9
45.4
73.4
5.7
78.2
72.6
65.0
57.5
49.9
70.6
5.7
42.6
33.5
103.0
5.9
56.2
47.1
38.0
95.2
5.9
69.8
60.7
51.6
42.6
87.5
5.8
81.2
75.2
66.2
57.1
48.0
78.1
5.8
83.1
80.3
71.2
62.1
53.1
75.2
5.8
47.3
36.7
109.3
6.0
62.2
51.6
41.0
101.0
6.0
77.0
66.5
55.9
45.3
92.8
5.9
86.7
82.4
71.8
61.3
50.7
82.9
5.9
87.9
87.9
77.4
66.8
56.2
79.7
5.9
64.0
53.1
42.2
100.2
5.9
79.3
68.4
57.5
46.7
92.0
5.9
86.8
84.6
73.8
62.9
52.0
82.2
5.8
88.0
88.0
77.1
66.2
55.3
79.1
5.8
65.7
54.6
43.4
99.4
5.8
81.5
70.3
59.1
48.0
91.3
5.8
86.9
86.9
75.7
64.5
53.4
81.5
5.8
88.0
88.0
76.8
65.6
54.4
78.5
5.8
95°F
28.4
22.3
76.9
7.3
39.5
33.3
27.2
70.8
7.3
50.5
44.4
38.2
32.1
64.7
7.2
63.3
54.3
48.1
42.0
35.8
59.4
7.2
32.5
25.0
81.8
7.4
45.0
37.5
30.0
75.3
7.4
57.4
49.9
42.4
34.9
68.8
7.3
68.6
61.0
53.5
46.0
38.5
63.2
7.3
63.0
58.6
51.1
43.5
36.0
61.6
7.3
36.7
27.8
86.7
7.5
50.5
41.6
32.8
79.8
7.5
64.3
55.4
46.6
37.7
73.0
7.4
73.8
67.8
59.0
50.1
41.2
67.0
7.3
67.3
65.1
56.2
47.3
38.5
65.2
7.4
40.8
30.6
91.6
7.6
56.0
45.8
35.6
84.3
7.6
71.2
61.0
50.8
40.5
77.1
7.5
79.1
74.6
64.4
54.2
43.9
70.8
7.4
71.5
71.5
61.3
51.1
40.9
68.9
7.4
57.6
47.0
36.3
83.1
7.5
73.2
62.6
51.9
41.3
75.9
7.4
77.6
75.4
64.7
54.1
43.4
69.7
7.4
70.2
70.2
59.6
48.9
38.3
67.9
7.4
59.3
48.2
37.1
81.8
7.4
75.3
64.2
53.1
42.0
74.8
7.4
76.2
76.2
65.1
54.0
42.9
68.6
7.3
68.9
68.9
57.8
46.8
35.7
66.9
7.3
90
36.9
48.0
59.0
68.7
42.8
55.1
67.5
73.4
70.6
48.6
62.3
76.0
78.1
75.2
54.4
69.5
84.5
82.9
79.7
71.6
87.0
82.2
79.1
73.7
89.5
81.5
78.5
31.0
43.2
55.3
59.4
37.4
49.6
61.8
63.2
61.6
43.8
56.0
68.3
67.0
65.2
50.2
62.5
74.7
70.8
68.9
64.7
74.8
69.7
67.9
66.9
74.8
68.6
66.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
30.8
24.7
41.8
35.7
29.6
52.9
46.8
40.7
34.5
66.7
57.6
51.5
45.4
35.2
27.7
47.6
40.0
32.5
60.0
52.4
44.9
37.3
72.1
64.6
57.0
49.5
70.6
65.6
58.0
50.5
39.6
30.7
53.3
44.4
35.4
67.0
58.1
49.1
40.1
77.5
71.5
62.6
53.6
75.2
72.7
63.7
54.7
44.0
33.6
59.1
48.7
38.3
74.1
63.7
53.3
42.9
82.9
78.5
68.1
57.7
79.7
79.7
69.3
59.0
60.8
50.0
39.3
76.3
65.5
54.7
44.0
82.2
80.0
69.3
58.5
79.1
79.1
68.3
57.6
62.5
51.4
40.3
78.4
67.3
56.1
45.0
81.5
81.5
70.4
59.3
78.5
78.5
67.3
56.2
105°F
26.2
20.1
37.1
31.0
24.8
47.9
41.8
35.7
29.6
58.5
49.9
43.8
37.7
30.0
22.6
42.2
34.8
27.4
54.4
47.0
39.6
32.1
62.6
56.1
48.7
41.3
61.4
55.5
48.1
40.6
33.8
25.1
47.3
38.6
29.9
60.9
52.2
43.5
34.7
66.7
62.3
53.6
44.9
65.1
61.6
52.9
44.2
37.6
27.6
52.5
42.5
32.5
67.3
57.3
47.3
37.3
70.8
68.5
58.5
48.5
68.9
67.7
57.7
47.7
54.2
43.8
33.3
69.1
59.1
48.7
38.2
69.7
68.6
58.1
47.7
67.9
67.3
56.8
46.4
56.0
45.1
34.2
70.9
60.9
50.0
39.1
68.6
68.6
57.7
46.8
66.9
66.9
56.0
45.1
65
39.3
41.9
43.0
44.6
45.8
47.3
48.6
47.7
46.8
48.1
45.1
31.6
33.9
33.2
36.2
35.5
38.5
37.7
37.2
35.9
35.9
34.2
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT06 (6.5 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
72.6
65.6
58.6
53.8
76.5
69.1
61.8
56.7
60.1
80.4
72.7
64.9
59.6
63.2
84.3
76.2
68.1
62.5
66.3
75.4
67.3
61.8
65.5
74.5
66.6
61.1
64.8
8.1
8.1
8.1
8.0
8.2
8.2
8.2
8.1
8.1
8.4
8.3
8.3
8.2
8.2
8.5
8.4
8.4
8.3
8.3
8.3
8.3
8.2
8.2
8.3
8.2
8.1
8.1
27.5
40.7
54.0
53.8
34.8
46.7
58.7
56.7
60.1
42.1
52.7
63.4
59.6
63.2
49.4
58.8
68.1
62.5
66.3
61.1
67.3
61.8
65.5
63.4
66.6
61.1
64.8
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
24.0
18.0
68.3
9.0
34.7
28.6
22.5
60.4
8.9
45.3
39.2
33.1
27.1
52.6
8.9
53.8
45.6
39.5
33.4
27.4
48.2
8.8
27.5
20.2
71.2
9.1
39.4
32.1
24.8
63.0
9.0
51.4
44.0
36.7
29.4
54.7
9.0
56.7
51.2
43.9
36.6
29.3
50.2
8.9
59.7
52.4
45.1
37.7
30.4
58.7
8.9
31.0
22.4
74.1
9.2
44.2
35.6
27.1
65.5
9.2
57.4
48.9
40.3
31.8
56.9
9.1
59.6
56.8
48.3
39.7
31.2
52.2
9.0
63.0
58.1
49.6
41.0
32.5
61.2
9.0
34.4
24.6
77.1
9.3
49.0
39.2
29.4
68.1
9.3
63.5
53.7
43.9
34.1
59.1
9.2
62.5
62.5
52.7
42.9
33.1
54.2
9.1
66.3
63.9
54.1
44.3
34.5
63.6
9.1
50.8
40.6
30.3
67.6
9.2
65.0
55.7
45.4
35.1
58.7
9.2
61.8
61.8
51.5
41.3
31.0
53.8
9.0
65.5
64.3
54.1
43.8
33.6
63.2
9.0
52.7
42.0
31.3
67.2
9.1
66.6
57.6
46.9
36.2
58.4
9.1
61.1
61.1
50.4
39.7
28.9
53.5
8.9
64.8
64.8
54.1
43.4
32.7
62.7
9.0
90
24.0
38.3
52.6
48.2
33.0
43.9
54.7
50.2
58.7
42.0
49.4
56.9
52.2
61.2
51.0
55.0
59.1
54.2
63.6
57.5
58.7
53.8
63.2
59.9
58.4
53.5
62.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
21.5
15.8
32.2
26.2
20.2
42.6
36.6
30.6
24.6
48.2
41.2
35.2
29.2
25.0
17.8
36.6
29.4
22.2
48.3
41.1
33.9
26.7
50.2
46.3
39.1
31.9
58.0
49.3
42.1
34.8
28.4
19.7
41.0
32.6
24.2
54.0
45.6
37.2
28.8
52.2
51.4
43.0
34.6
60.8
54.7
46.3
37.9
31.8
21.6
45.4
35.9
26.3
59.1
50.1
40.5
30.9
54.2
54.2
46.8
37.2
63.6
60.0
50.5
40.9
47.4
37.4
27.3
58.7
52.2
42.1
32.1
53.8
53.8
44.9
34.9
63.2
61.4
51.3
41.3
49.4
38.9
28.3
58.4
54.3
43.7
33.2
53.5
53.5
43.0
32.5
62.7
62.7
52.2
41.7
65
23.1
24.7
27.6
26.2
29.5
27.7
31.3
24.8
31.2
22.0
31.2
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
77
5123247-TTG-A-0515
ZKT06 (6.5 Ton) Reheat
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
78
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
31.6
32.2
28.5
36.1
36.7
32.6
34.2
40.5
41.2
36.7
38.3
45.0
45.7
40.8
42.5
42.5
43.2
38.5
40.2
40.0
40.6
36.2
37.9
4.5
4.6
4.4
4.3
4.5
4.3
4.4
4.2
4.3
4.2
4.2
4.1
4.2
4.0
4.1
4.0
4.1
4.0
4.0
3.9
4.0
3.9
4.0
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
38.2
38.2
35.5
38.4
38.4
35.7
34.7
38.6
38.6
35.9
34.9
38.8
38.9
36.1
35.1
39.0
39.1
36.3
35.3
39.2
39.3
36.5
35.5
5.7
5.1
5.3
5.5
4.9
5.1
5.1
5.2
4.7
4.9
4.8
5.0
4.4
4.6
4.6
5.2
4.6
4.8
4.8
5.3
4.8
5.0
5.0
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
35°F
1.6
1.5
1.5
34.9
5.1
1.5
1.5
1.4
1.4
35.2
4.9
1.6
1.6
1.5
1.5
1.4
32.0
4.9
2.2
1.6
0.9
37.2
4.9
6.6
5.9
5.3
4.6
37.6
4.7
10.8
10.1
9.4
8.8
8.1
34.2
4.7
17.1
16.4
15.8
15.1
14.5
34.5
4.7
2.9
1.7
0.4
39.6
4.7
11.6
10.4
9.1
7.8
39.9
4.5
19.9
18.6
17.4
16.1
14.8
36.3
4.5
29.8
29.5
28.2
26.9
25.7
36.6
4.5
3.6
1.7
-0.1
41.9
4.5
16.7
14.8
12.9
11.1
42.3
4.3
29.0
27.1
25.3
23.4
21.6
38.4
4.3
42.5
42.5
40.6
38.7
36.9
38.8
4.4
4.6
2.8
1.0
40.8
4.6
17.5
15.7
13.9
12.1
41.1
4.4
31.6
29.1
27.3
25.5
23.7
37.4
4.4
40.2
40.2
38.3
36.5
34.7
37.7
4.4
5.7
3.9
2.1
39.6
4.6
18.4
16.6
14.8
13.0
40.0
4.4
34.2
31.1
29.3
27.5
25.8
36.3
4.4
37.9
37.9
36.1
34.3
32.5
36.7
4.5
55°F
36.3
5.7
3.4
2.9
2.4
1.9
36.2
5.3
8.8
8.3
7.8
7.3
6.7
33.1
5.2
36.8
5.6
5.8
5.2
4.5
3.9
36.7
5.2
15.3
14.7
14.0
13.3
12.7
33.5
5.0
19.4
18.7
18.1
17.4
16.8
32.9
5.0
37.3
5.4
8.3
7.5
6.6
5.8
37.2
5.0
21.9
21.0
20.2
19.4
18.6
34.0
4.9
27.2
26.9
26.1
25.3
24.5
33.4
4.9
37.8
5.3
10.7
9.7
8.8
7.8
37.7
4.9
28.4
27.4
26.5
25.5
24.6
34.4
4.8
35.1
35.1
34.1
33.2
32.2
33.8
4.8
38.0
5.4
12.9
11.7
10.6
9.5
38.0
5.0
32.4
32.0
30.8
29.7
28.6
34.6
4.9
35.3
35.3
34.2
33.0
31.9
34.1
4.9
38.2
5.5
15.0
13.7
12.5
11.2
38.2
5.0
36.5
36.5
35.2
33.9
32.6
34.8
4.9
35.5
35.5
34.2
32.9
31.6
34.3
4.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
45°F
2.5
2.2
1.9
1.7
5.2
4.9
4.6
4.4
6.2
5.6
4.9
4.2
13.0
12.4
11.7
11.1
18.2
17.6
16.9
16.3
9.9
8.9
7.9
6.8
20.9
19.8
18.8
17.8
28.5
28.2
27.2
26.1
13.7
12.3
10.8
9.4
28.7
27.3
25.9
24.5
38.8
38.8
37.4
36.0
15.2
13.7
12.2
10.8
32.0
30.5
29.1
27.6
37.7
37.7
36.2
34.8
16.7
15.2
13.6
12.1
35.3
33.8
32.3
30.7
36.7
36.7
35.1
33.6
65°F
2.4
2.1
1.8
1.5
6.5
6.2
5.9
5.6
4.9
4.3
3.8
3.2
13.9
13.3
12.7
12.2
17.0
16.5
15.9
15.3
7.4
6.6
5.8
5.0
21.2
20.4
19.6
18.8
25.4
25.2
24.3
23.5
9.9
8.9
7.8
6.8
28.5
27.5
26.4
25.3
33.8
33.8
32.8
31.7
12.2
10.9
9.7
8.4
31.7
31.2
29.9
28.7
34.1
34.1
32.8
31.6
14.4
13.0
11.6
10.1
34.8
34.8
33.4
32.0
34.3
34.3
32.8
31.4
65
4.1
10.4
15.6
16.7
25.1
23.1
34.5
26.1
33.3
29.2
32.0
5.3
11.6
14.8
18.0
22.7
24.3
30.7
27.4
30.3
30.5
29.9
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT06 (6.5 Ton) Reheat (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
34.3
34.2
30.6
35.1
35.0
31.3
31.2
35.9
35.8
32.0
31.9
36.7
36.6
32.7
32.6
37.0
36.9
33.0
32.8
37.2
37.1
33.2
33.1
5.7
5.4
5.0
5.7
5.4
5.0
5.0
5.7
5.4
5.0
5.0
5.7
5.4
5.0
5.0
5.6
5.4
4.9
4.9
5.6
5.3
4.9
4.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
32.4
5.6
1.3
1.2
1.1
1.0
32.2
5.6
4.3
4.2
4.1
4.0
3.9
28.2
4.8
33.5
5.8
4.0
3.5
3.0
2.6
33.3
5.7
12.4
12.0
11.5
11.0
10.6
29.1
4.9
14.6
14.2
13.7
13.3
12.8
29.4
4.9
34.5
5.9
6.6
5.8
5.0
4.2
34.4
5.8
20.5
19.7
18.9
18.1
17.3
30.1
5.1
23.6
23.4
22.6
21.8
21.0
30.4
5.0
35.6
6.0
9.2
8.1
6.9
5.7
35.5
5.9
28.7
27.5
26.3
25.2
24.0
31.0
5.2
32.6
32.6
31.4
30.3
29.1
31.3
5.2
35.9
5.8
11.5
10.2
8.8
7.4
35.8
5.8
30.9
30.4
29.0
27.6
26.2
31.3
5.0
32.8
32.8
31.5
30.1
28.7
31.6
5.0
36.2
5.7
13.9
12.3
10.7
9.1
36.1
5.6
33.2
33.2
31.6
30.0
28.4
31.6
4.9
33.1
33.1
31.5
29.9
28.3
31.9
4.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
0.3
0.4
0.5
0.6
2.1
2.2
2.2
2.3
3.0
2.7
2.3
1.9
11.0
10.6
10.3
9.9
12.2
11.9
11.5
11.2
5.7
4.9
4.1
3.3
19.9
19.1
18.3
17.4
21.8
21.6
20.8
20.0
8.5
7.2
6.0
4.7
28.8
27.5
26.3
25.0
31.3
31.3
30.1
28.8
10.9
9.4
7.9
6.4
30.2
29.6
28.0
26.5
31.6
31.6
30.1
28.6
13.3
11.5
9.8
8.0
31.6
31.6
29.8
28.1
31.9
31.9
30.1
28.4
65
2.4
9.5
10.8
16.6
19.2
23.8
27.6
25.0
27.1
26.3
26.6
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
79
5123247-TTG-A-0515
ZKT07 (7.5 Ton) Cooling
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
80
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
95.3
88.9
82.4
72.3
104.3
97.2
90.1
79.1
76.9
113.3
105.5
97.8
85.9
83.6
122.2
113.8
105.4
92.7
90.2
116.9
108.2
95.1
92.7
119.9
111.0
97.6
95.1
5.1
5.0
4.9
4.9
5.1
5.0
5.0
4.9
4.9
5.2
5.1
5.0
5.0
5.0
5.2
5.1
5.1
5.0
5.0
5.2
5.1
5.1
5.1
5.2
5.1
5.1
5.1
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
101.5
93.1
84.7
76.8
104.3
95.7
87.0
78.9
78.3
107.1
98.2
89.3
81.0
80.4
109.9
100.7
91.6
83.1
82.4
101.5
92.3
83.7
83.1
102.3
93.0
84.3
83.7
6.6
6.6
6.5
6.5
6.6
6.6
6.5
6.5
6.5
6.6
6.6
6.5
6.5
6.5
6.6
6.6
6.5
6.5
6.5
6.6
6.5
6.5
6.5
6.6
6.6
6.5
6.5
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
90
85
80
75
70
65
75°F
41.7
33.4
25.0
98.4
5.8
49.7
41.3
33.0
24.6
91.0
5.8
57.7
49.3
41.0
32.6
24.2
83.6
5.7
72.3
63.4
49.7
41.3
32.9
24.6
74.5
5.7
50.1
40.6
31.2
104.3
5.9
60.3
50.9
41.4
32.0
96.4
5.8
70.6
61.1
51.7
42.2
32.8
88.5
5.8
79.1
73.2
62.8
53.3
43.9
34.4
79.0
5.7
76.9
74.8
63.8
54.3
44.9
35.4
77.6
5.7
58.4
47.9
37.4
110.2
5.9
70.9
60.4
49.9
39.4
101.9
5.8
83.4
72.9
62.4
51.9
41.3
93.5
5.8
85.9
82.9
75.8
65.3
54.8
44.3
83.4
5.7
83.6
82.5
77.0
66.5
55.9
45.4
82.0
5.7
66.8
55.2
43.6
116.0
5.9
81.6
69.9
58.3
46.7
107.3
5.9
96.3
84.7
73.1
61.5
49.9
98.5
5.8
92.7
92.7
88.9
77.3
65.7
54.1
87.9
5.8
90.2
90.2
90.2
78.6
67.0
55.4
86.3
5.8
86.8
74.3
61.8
49.4
109.2
5.9
103.7 89.9
77.5
65.0
52.5
100.3
5.8
95.1
95.1
93.3
80.8
68.4
55.9
89.4
5.8
92.7
92.7
92.7
80.2
67.7
55.3
87.9
5.8
92.0
78.7
65.3
52.0
111.1
5.9
111.0 95.2
81.9
68.5
55.2
102.0
5.8
97.6
97.6
97.6
84.3
71.0
57.7
91.0
5.8
95.1
95.1
95.1
81.8
68.4
55.1
89.4
5.8
95°F
43.2
35.6
27.9
94.5
7.5
55.7
48.0
40.3
32.7
86.4
7.5
68.2
60.5
52.8
45.1
37.4
78.3
7.5
76.8
76.8
65.4
57.7
50.0
42.3
71.2
7.4
47.9
39.1
30.3
96.9
7.5
61.5
52.7
43.9
35.0
88.5
7.5
75.0
66.2
57.4
48.6
39.8
80.2
7.4
78.9
78.9
71.0
62.2
53.4
44.6
73.0
7.4
78.3
78.3
71.1
62.2
53.4
44.6
73.0
7.4
52.6
42.6
32.7
99.2
7.5
67.2
57.3
47.4
37.4
90.6
7.5
81.9
72.0
62.0
52.1
42.1
82.1
7.4
81.0
81.0
76.7
66.8
56.9
46.9
74.7
7.4
80.4
80.4
76.7
66.8
56.9
46.9
74.8
7.4
57.3
46.2
35.1
101.5
7.5
73.0
61.9
50.9
39.8
92.7
7.5
88.7
77.7
66.6
55.6
44.5
84.0
7.4
83.1
83.1
82.4
71.4
60.3
49.2
76.5
7.4
82.4
82.4
82.4
71.4
60.3
49.3
76.5
7.4
78.2
66.2
54.2
42.2
93.0
7.4
90.9
82.9
70.9
58.9
46.9
84.3
7.4
83.7
83.7
83.4
71.4
59.4
47.4
76.7
7.4
83.1
83.1
83.1
71.1
59.1
47.1
76.7
7.4
83.3
70.4
57.5
44.5
93.3
7.4
93.0
88.2
75.2
62.3
49.4
84.5
7.4
84.3
84.3
84.3
71.4
58.5
45.5
76.9
7.4
83.7
83.7
83.7
70.7
57.8
44.9
76.9
7.4
90
42.5
52.7
63.0
74.5
49.0
60.9
72.8
79.0
77.6
55.5
69.1
82.7
83.4
82.0
62.0
77.3
92.5
87.9
86.3
82.5
97.3
89.4
87.9
87.7
102.0
91.0
89.4
39.4
52.8
66.2
71.2
45.1
58.4
71.7
73.0
73.0
50.7
63.9
77.1
74.7
74.8
56.4
69.5
82.6
76.5
76.5
74.7
83.5
76.7
76.7
79.9
84.5
76.9
76.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
34.5
26.4
44.7
36.7
28.6
54.9
46.9
38.9
30.8
70.1
57.5
49.5
41.5
39.9
30.7
51.8
42.6
33.5
63.7
54.5
45.4
36.3
76.0
66.9
57.8
48.6
76.5
67.4
58.3
49.1
45.3
35.0
58.9
48.6
38.4
72.4
62.2
52.0
41.7
82.0
76.3
66.1
55.8
81.4
76.9
66.6
56.4
50.7
39.4
65.9
54.6
43.3
81.2
69.9
58.5
47.2
87.9
85.7
74.3
63.0
86.3
86.3
75.0
63.7
70.2
58.0
45.8
86.4
74.2
62.0
49.7
89.4
88.3
76.1
63.9
87.9
87.9
75.6
63.4
74.5
61.4
48.3
91.7
78.5
65.4
52.3
91.0
91.0
77.9
64.7
89.4
89.4
76.3
63.1
105°F
33.0
25.5
45.3
37.7
30.2
57.5
50.0
42.5
34.9
71.2
60.6
53.1
45.5
36.4
27.7
49.7
41.0
32.3
63.0
54.3
45.6
36.9
73.0
65.8
57.1
48.4
73.0
66.1
57.4
48.7
39.7
29.8
54.1
44.2
34.3
68.4
58.6
48.7
38.8
74.7
70.9
61.1
51.2
74.8
71.3
61.4
51.6
43.0
32.0
58.5
47.4
36.4
73.9
62.8
51.8
40.8
76.5
76.1
65.1
54.1
76.5
76.5
65.5
54.4
62.7
50.8
38.8
78.0
67.3
55.3
43.4
76.7
76.5
64.6
52.6
76.7
76.7
64.8
52.8
67.0
54.1
41.2
82.1
71.7
58.8
46.0
76.9
76.9
64.0
51.1
76.9
76.9
64.0
51.1
65
33.4
39.5
40.0
45.6
46.2
51.7
52.3
51.6
51.2
51.6
50.0
38.0
39.7
40.0
41.4
41.7
43.0
43.4
40.6
40.8
38.2
38.3
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT07 (7.5 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
87.6
79.7
71.9
65.7
89.4
81.4
73.4
67.1
67.8
91.2
83.1
74.9
68.5
69.2
93.1
84.7
76.4
69.8
70.6
84.5
76.2
69.6
70.4
84.3
76.0
69.5
70.2
8.4
8.4
8.4
8.3
8.3
8.3
8.4
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.2
35.5
49.9
64.3
65.7
42.2
55.2
68.3
67.1
67.8
48.9
60.6
72.3
68.5
69.2
55.5
66.0
76.4
69.8
70.6
71.2
76.2
69.6
70.4
76.5
76.0
69.5
70.2
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
30.5
23.1
80.6
9.2
42.5
35.1
27.8
73.0
9.2
54.6
47.2
39.8
32.4
65.5
9.3
65.7
55.8
48.4
41.1
33.7
60.2
9.3
33.6
25.0
82.0
9.2
46.7
38.1
29.5
74.3
9.2
59.7
51.1
42.6
34.0
66.6
9.3
67.1
60.5
51.9
43.3
34.7
61.2
9.2
67.8
61.1
52.5
43.9
35.4
62.5
9.2
36.8
27.0
83.3
9.2
50.8
41.0
31.2
75.5
9.2
64.9
55.1
45.3
35.5
67.7
9.2
68.5
65.2
55.4
45.6
35.8
62.2
9.2
69.2
65.8
56.0
46.3
36.5
63.6
9.2
39.9
28.9
84.7
9.2
55.0
44.0
33.0
76.7
9.2
70.0
59.1
48.1
37.1
68.8
9.2
69.8
69.8
58.8
47.9
36.9
63.2
9.2
70.6
70.6
59.6
48.6
37.6
64.6
9.2
59.3
47.4
35.5
76.0
9.2
73.0
63.6
51.7
39.8
68.1
9.2
69.6
69.6
57.7
45.8
33.9
62.6
9.2
70.4
70.4
58.4
46.5
34.6
64.0
9.1
63.7
50.8
38.0
75.3
9.1
76.0
68.2
55.4
42.5
67.5
9.2
69.5
69.5
56.6
43.8
30.9
62.0
9.2
70.2
70.2
57.3
44.5
31.6
63.4
9.1
90
30.9
47.0
62.3
60.2
39.3
52.1
64.9
61.2
62.5
47.7
57.3
67.6
62.2
63.6
56.1
62.4
68.8
63.2
64.6
67.8
68.1
62.6
64.0
73.1
67.5
62.0
63.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
27.9
20.7
39.8
32.5
25.3
51.6
44.4
37.2
29.9
60.2
51.0
43.8
36.6
30.9
22.4
43.7
35.2
26.7
56.5
48.0
39.5
31.1
61.2
55.2
46.7
38.3
62.5
56.1
47.7
39.2
33.8
24.1
47.6
37.9
28.2
61.3
51.6
41.9
32.2
62.2
59.4
49.7
40.0
63.6
60.4
50.7
40.9
36.7
25.8
51.5
40.5
29.6
66.2
55.3
44.3
33.4
63.2
63.2
52.6
41.6
64.6
64.6
53.6
42.7
55.9
44.0
32.1
68.1
60.0
48.1
36.2
62.6
62.6
50.9
39.0
64.0
64.0
52.1
40.3
60.3
47.5
34.7
67.5
64.7
51.9
39.1
62.0
62.0
49.2
36.4
63.4
63.4
50.6
37.8
65
29.4
29.8
30.7
30.2
31.2
30.7
31.7
27.1
28.4
23.6
25.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
81
5123247-TTG-A-0515
ZKT07 (7.5 Ton) Reheat
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
82
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
57.4
54.9
52.4
48.7
62.8
60.0
57.2
53.0
49.6
68.1
65.0
61.9
57.4
53.7
73.4
70.0
66.6
61.8
57.8
71.8
68.3
63.3
59.3
73.5
69.9
64.9
60.7
4.6
4.4
4.3
4.1
4.5
4.4
4.2
4.0
4.0
4.5
4.3
4.2
4.0
3.9
4.5
4.3
4.2
4.0
3.9
4.3
4.2
4.0
3.9
4.3
4.2
4.0
3.9
7.7
14.9
21.7
11.2
22.2
32.6
37.1
14.8
29.5
43.6
47.5
18.4
36.8
54.5
57.8
18.9
37.5
58.3
59.3
19.4
38.2
62.1
60.7
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
59.9
54.2
48.5
44.6
62.6
56.6
50.7
46.6
46.2
65.2
59.0
52.8
48.5
48.1
67.8
61.4
54.9
50.5
50.1
63.0
56.4
51.8
51.4
64.6
57.9
53.2
52.7
5.1
4.9
4.7
4.5
5.1
4.9
4.7
4.5
4.4
5.1
4.9
4.6
4.4
4.4
5.1
4.8
4.6
4.4
4.3
4.8
4.6
4.4
4.3
4.8
4.6
4.4
4.3
3.9
12.6
22.2
5.4
17.0
29.9
35.3
6.8
21.4
37.7
42.7
8.2
25.8
45.4
50.1
9.6
29.8
49.3
51.4
11.0
33.9
53.2
52.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
35°F
58.7
4.9
6.3
4.9
3.5
54.6
4.7
13.5
12.1
10.7
9.3
50.5
4.5
20.3
18.9
17.5
16.1
14.7
46.6
4.3
62.7
4.8
9.1
7.0
4.9
58.3
4.6
20.1
18.0
15.9
13.8
53.9
4.4
30.5
28.4
26.3
24.2
22.1
49.8
4.2
35.0
32.9
30.8
28.7
26.6
47.9
4.2
66.6
4.8
12.0
9.2
6.4
62.0
4.6
26.7
23.9
21.1
18.3
57.3
4.4
40.8
38.0
35.2
32.4
29.6
53.0
4.2
46.4
44.0
41.2
38.4
35.6
50.9
4.1
70.6
4.8
14.9
11.4
7.9
65.7
4.6
33.3
29.8
26.3
22.8
60.8
4.4
51.0
47.5
44.0
40.5
37.0
56.1
4.2
57.8
55.1
51.6
48.1
44.6
54.0
4.1
15.5
12.1
8.6
67.4
4.6
34.0
30.6
27.2
23.8
62.3
4.4
53.2
48.3
44.9
41.4
38.0
57.6
4.2
59.3
57.9
54.5
51.1
47.6
55.3
4.1
16.1
12.7
9.4
69.1
4.6
34.8
31.4
28.1
24.7
63.9
4.4
55.3
49.1
45.7
42.4
39.0
59.0
4.2
60.7
60.7
57.4
54.0
50.6
56.7
4.1
55°F
57.9
5.4
2.7
1.6
51.6
5.2
11.4
10.2
9.0
7.9
45.3
5.0
21.0
19.9
18.7
17.5
16.4
42.1
4.8
59.7
5.4
3.7
2.1
53.2
5.2
15.4
13.7
12.1
10.5
46.6
4.9
28.3
26.7
25.1
23.5
21.8
43.4
4.7
33.7
32.1
30.4
28.8
27.2
42.7
4.7
61.4
5.4
4.7
2.7
54.7
5.1
19.3
17.3
15.2
13.1
48.0
4.9
35.6
33.6
31.5
29.4
27.3
44.7
4.7
41.9
40.3
38.2
36.1
34.1
43.9
4.6
63.1
5.3
5.7
3.2
56.2
5.1
23.3
20.8
18.3
15.7
49.4
4.9
42.9
40.4
37.9
35.4
32.8
45.9
4.7
50.1
48.5
46.0
43.4
40.9
45.2
4.6
6.6
3.7
57.9
5.1
26.9
23.9
21.0
18.0
50.8
4.9
48.0
46.5
43.6
40.6
37.6
47.3
4.7
51.4
50.6
47.6
44.7
41.7
46.5
4.6
7.6
4.2
59.6
5.1
30.5
27.1
23.7
20.3
52.3
4.9
53.2
52.7
49.3
45.9
42.5
48.7
4.7
52.7
52.7
49.3
45.9
42.5
47.9
4.6
90
5.8
13.7
21.9
8.3
19.6
31.3
36.2
10.8
25.4
40.6
45.1
13.3
31.3
50.0
54.0
14.3
33.7
53.8
55.3
15.2
36.0
57.6
56.7
1.5
11.0
22.4
2.2
14.3
28.8
33.5
2.9
17.6
35.2
39.3
3.6
20.9
41.7
45.2
4.1
25.7
45.2
46.5
4.6
30.5
48.7
47.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
45°F
4.5
3.2
1.9
12.4
11.1
9.9
8.6
20.7
19.4
18.1
16.8
6.4
4.6
2.7
17.7
15.9
14.0
12.1
29.4
27.6
25.7
23.8
34.3
32.5
30.6
28.8
8.4
5.9
3.5
23.0
20.6
18.1
15.7
38.2
35.8
33.3
30.9
44.1
42.1
39.7
37.3
10.3
7.3
4.3
28.3
25.3
22.3
19.3
47.0
44.0
40.9
37.9
54.0
51.8
48.8
45.8
11.1
7.9
4.7
30.5
27.3
24.1
20.9
50.6
47.4
44.2
41.0
55.3
54.3
51.1
47.9
11.8
8.4
5.1
32.6
29.3
25.9
22.5
54.3
50.9
47.5
44.1
56.7
56.7
53.3
50.0
65°F
10.0
9.0
7.9
6.9
21.4
20.4
19.3
18.3
12.9
11.6
10.2
8.9
27.5
26.1
24.7
23.4
32.2
30.8
29.4
28.1
1.2
15.9
14.2
12.5
10.8
33.5
31.8
30.1
28.4
38.7
37.6
35.9
34.2
1.5
18.9
16.8
14.7
12.7
39.6
37.6
35.5
33.5
45.2
44.4
42.3
40.3
1.5
23.2
20.6
18.0
15.5
44.1
43.0
40.4
37.9
46.5
46.1
43.6
41.0
1.5
27.5
24.4
21.3
18.2
48.7
48.4
45.3
42.2
47.9
47.9
44.8
41.7
65
15.5
22.0
26.9
28.5
34.8
34.9
42.8
37.8
44.7
40.7
46.6
17.3
22.0
26.7
26.7
32.5
31.4
38.2
35.3
38.4
39.2
38.6
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT07 (7.5 Ton) Reheat (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
56.0
49.0
42.0
39.6
56.8
49.7
42.6
40.2
39.2
57.6
50.4
43.2
40.8
39.7
58.4
51.1
43.8
41.4
40.3
52.8
45.3
42.8
41.6
54.5
46.8
44.1
43.0
5.7
5.5
5.2
5.0
5.7
5.5
5.2
5.0
4.9
5.7
5.4
5.2
5.0
4.9
5.6
5.4
5.2
5.0
4.9
5.4
5.2
5.0
4.9
5.4
5.1
4.9
4.9
9.4
22.6
11.6
27.7
31.7
13.8
32.8
36.0
16.0
37.9
40.3
21.6
41.0
41.6
27.2
44.1
43.0
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
54.0
6.0
46.3
5.8
8.6
7.7
6.8
6.0
38.7
5.5
21.7
20.9
20.0
19.1
18.3
37.2
5.3
53.9
6.0
46.2
5.7
10.5
9.4
8.3
7.2
38.6
5.5
26.6
25.5
24.4
23.3
22.2
37.0
5.3
30.6
29.5
28.4
27.3
26.2
35.6
5.2
53.8
5.9
46.1
5.7
12.5
11.1
9.8
8.4
38.4
5.5
31.5
30.1
28.8
27.4
26.1
36.9
5.3
35.5
34.9
33.6
32.2
30.9
35.5
5.2
53.6
5.9
45.9
5.7
14.4
12.8
11.2
9.7
38.2
5.4
36.3
34.7
33.2
31.6
30.0
36.8
5.3
40.3
40.3
38.7
37.1
35.5
35.4
5.2
47.7
5.7
19.4
17.3
15.1
12.9
39.7
5.4
40.2
39.4
37.3
35.1
32.9
38.2
5.2
41.6
41.6
39.5
37.3
35.1
36.7
5.2
49.5
5.6
24.4
21.7
18.9
16.2
41.2
5.4
44.1
44.1
41.4
38.6
35.9
39.6
5.2
43.0
43.0
40.2
37.5
34.7
38.1
5.1
90
7.8
22.7
8.9
26.5
30.0
10.0
30.4
32.7
11.1
34.2
35.4
17.5
36.9
36.7
23.9
39.6
38.1
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
7.1
6.4
5.8
5.1
22.0
21.3
20.7
20.0
8.1
7.3
6.4
5.6
25.7
24.9
24.0
23.2
29.1
28.3
27.4
26.6
9.0
8.1
7.1
6.1
29.4
28.4
27.4
26.4
32.2
32.2
31.2
30.3
10.0
8.9
7.7
6.6
33.0
31.9
30.8
29.7
35.4
35.4
35.0
33.9
15.7
13.9
12.2
10.4
36.3
35.9
34.1
32.4
36.7
36.7
35.4
33.6
21.4
19.0
16.6
14.1
39.6
39.6
37.5
35.0
38.1
38.1
35.7
33.3
65
19.3
22.4
25.8
25.5
29.3
28.5
32.8
30.6
31.8
32.6
30.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
83
5123247-TTG-A-0515
ZKT08 (8.5 Ton) Cooling
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
84
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
121.9
118.1
114.3
105.8
126.3
122.4
118.4
109.7
107.0
130.7
126.6
122.6
113.5
110.8
135.1
130.9
126.7
117.3
114.5
130.9
126.8
117.4
114.5
131.0
126.8
117.4
114.6
6.4
6.4
6.3
6.2
6.5
6.4
6.4
6.2
6.3
6.5
6.4
6.4
6.3
6.3
6.5
6.5
6.4
6.3
6.4
6.5
6.4
6.3
6.4
6.5
6.5
6.3
6.4
54.3
71.1
87.8
105.8
59.7
79.1
98.4
109.7
107.0
65.1
87.0
108.9
113.5
110.8
70.6
95.0
119.5
117.3
114.5
99.4
123.1
117.4
114.5
103.7
126.8
117.4
114.6
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
115.5
107.5
99.5
91.9
119.5
111.3
103.0
95.2
92.1
123.6
115.1
106.5
98.5
95.2
127.7
118.9
110.1
101.7
98.4
119.8
110.9
102.5
99.2
120.8
111.8
103.3
99.9
8.3
8.1
8.0
7.9
8.3
8.2
8.0
7.9
7.9
8.3
8.2
8.0
7.9
8.0
8.4
8.2
8.1
8.0
8.0
8.3
8.1
8.0
8.0
8.3
8.1
8.0
8.1
50.3
66.9
83.4
91.9
57.6
75.0
92.3
95.2
92.1
64.9
83.1
101.2
98.5
95.2
72.3
91.2
110.1
101.7
98.4
97.1
110.9
102.5
99.2
103.1
111.8
103.3
99.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
43.2
32.9
118.7
7.4
60.8
50.5
40.2
112.8
7.3
78.4
68.1
57.8
47.5
106.9
7.2
98.7
83.7
73.4
63.1
52.8
98.9
7.0
47.9
36.1
122.9
7.4
67.3
55.5
43.7
116.8
7.3
86.6
74.8
63.0
51.2
110.7
7.2
104.9 92.0
80.2
68.4
56.6
102.4
7.1
107.0 97.1
85.3
73.5
61.7
99.6
7.1
52.7
39.4
127.2
7.4
73.7
60.5
47.2
120.9
7.3
94.8
81.5
68.2
54.9
114.6
7.2
111.1 100.2 86.9
73.6
60.3
106.0
7.1
110.8 105.8 92.5
79.2
65.9
103.0
7.2
57.4
42.6
131.4
7.4
80.2
65.4
50.6
124.9
7.3
103.0 88.2
73.4
58.6
118.4
7.2
117.3 108.5 93.7
78.9
64.1
109.5
7.1
114.5 114.5 99.7
84.9
70.1
106.5
7.2
84.1
68.8
53.5
125.4
7.4
108.1 92.8
77.5
62.2
118.8
7.3
117.4 112.9 97.6
82.3
67.0
109.9
7.1
114.5 114.5 99.2
83.9
68.6
106.9
7.2
87.9
72.1
56.3
125.9
7.4
113.1 97.3
81.5
65.7
119.3
7.3
117.4 117.4 101.6 85.8
70.0
110.4
7.2
114.6 114.6 98.8
83.0
67.2
107.3
7.2
95°F
41.1
31.1
108.8
9.3
56.8
46.8
36.8
100.5
9.1
72.5
62.5
52.5
42.4
92.1
9.0
91.9
76.8
66.8
56.7
46.7
85.2
8.9
46.0
34.3
112.4
9.3
63.3
51.6
39.9
103.8
9.2
80.6
68.9
57.2
45.6
95.1
9.0
95.2
84.7
73.0
61.3
49.7
88.0
8.9
92.1
82.9
71.2
59.6
47.9
85.8
9.0
50.8
37.5
115.9
9.4
69.7
56.4
43.1
107.0
9.2
88.7
75.3
62.0
48.7
98.1
9.0
98.5
92.6
79.3
65.9
52.6
90.8
8.9
95.2
90.7
77.3
64.0
50.7
88.5
9.0
55.6
40.7
119.5
9.4
76.2
61.2
46.3
110.3
9.2
96.7
81.8
66.8
51.8
101.2
9.1
101.7 100.5 85.5
70.6
55.6
93.6
8.9
98.4
98.4
83.4
68.5
53.5
91.2
9.0
81.0
64.9
48.8
111.2
9.3
102.8 86.7
70.6
54.5
102.0
9.1
102.5 101.9 85.8
69.7
53.6
94.3
9.0
99.2
99.2
83.1
67.0
50.9
92.0
9.1
85.9
68.6
51.4
112.1
9.3
108.9 91.7
74.4
57.2
102.8
9.1
103.3 103.3 86.1
68.9
51.6
95.1
9.0
99.9
99.9
82.7
65.5
48.3
92.7
9.1
90
52.3
69.0
85.6
98.9
58.7
77.0
95.3
102.4
99.6
65.0
85.0
105.1
106.0
103.0
71.4
93.1
114.8
109.5
106.5
98.3
117.0
109.9
106.9
103.4
119.3
110.4
107.3
44.7
63.5
82.4
85.2
54.4
71.5
88.6
88.0
85.8
64.2
79.5
94.9
90.8
88.5
74.0
87.6
101.2
93.6
91.2
93.4
102.0
94.3
92.0
99.2
102.8
95.1
92.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
42.1
32.0
58.8
48.6
38.5
75.4
65.3
55.1
45.0
95.3
80.2
70.1
59.9
46.9
35.2
65.3
53.5
41.8
83.6
71.9
60.1
48.4
100.1 88.3
76.6
64.9
99.6
90.0
78.3
66.5
51.7
38.4
71.7
58.4
45.1
91.7
78.4
65.1
51.8
104.8 96.4
83.1
69.8
103.0 98.2
84.9
71.6
56.5
41.7
78.2
63.3
48.4
99.9
85.0
70.1
55.2
109.5 104.5 89.6
74.7
106.5 106.5 91.6
76.7
82.6
66.9
51.2
105.4 89.7
74.0
58.4
109.9 107.4 91.7
76.0
106.9 106.9 91.2
75.5
86.9
70.4
53.9
111.0 94.5
78.0
61.5
110.4 110.4 93.8
77.3
107.3 107.3 90.7
74.2
105°F
38.2
28.2
53.6
43.7
33.8
69.0
59.1
49.2
39.3
85.2
70.3
60.4
50.5
42.9
31.3
60.0
48.4
36.8
77.1
65.5
53.9
42.3
88.0
77.9
66.3
54.7
85.8
76.4
64.9
53.3
47.5
34.3
66.3
53.1
39.8
85.1
71.8
58.6
45.4
90.8
85.4
72.2
58.9
88.5
83.8
70.6
57.4
52.2
37.3
72.7
57.8
42.9
93.1
78.2
63.3
48.4
93.6
93.0
78.1
63.2
91.2
91.2
76.4
61.5
77.4
61.3
45.3
97.2
83.0
67.0
51.0
94.3
94.0
78.0
61.9
92.0
92.0
75.9
59.9
82.1
64.9
47.7
101.3 87.8
70.7
53.5
95.1
95.1
77.9
60.7
92.7
92.7
75.5
58.4
65
49.8
53.1
54.8
56.5
58.3
59.8
61.8
60.3
59.8
60.8
57.7
40.6
43.1
41.7
45.7
44.1
48.3
46.6
45.9
43.9
43.5
41.2
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT08 (8.5 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
102.2
93.5
84.8
78.5
105.2
96.2
87.3
80.8
79.6
108.2
99.0
89.8
83.1
81.8
111.2
101.7
92.3
85.4
84.1
102.6
93.0
86.1
84.8
103.4
93.8
86.8
85.5
10.3
10.1
10.0
9.9
10.4
10.2
10.0
9.9
10.0
10.4
10.2
10.0
9.9
10.0
10.4
10.2
10.0
9.9
10.0
10.3
10.1
10.0
10.1
10.3
10.1
10.0
10.1
39.0
60.2
81.3
78.5
51.2
68.1
85.0
80.8
79.6
63.4
76.0
88.6
83.1
81.8
75.7
84.0
92.3
85.4
84.1
89.7
93.0
86.1
84.8
95.4
93.8
86.8
85.5
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
35.2
25.4
95.6
11.4
50.4
40.6
30.8
86.5
11.1
65.5
55.8
46.0
36.2
77.4
10.9
78.5
63.8
54.0
44.2
34.4
71.8
10.8
39.7
28.3
98.0
11.4
56.6
45.2
33.7
88.7
11.2
73.5
62.0
50.6
39.1
79.4
11.0
80.8
71.0
59.6
48.1
36.6
73.6
10.9
79.6
69.9
58.5
47.0
35.5
73.3
11.0
44.3
31.1
100.5
11.4
62.9
49.7
36.6
90.9
11.2
81.5
68.3
55.2
42.1
81.4
11.0
83.1
78.2
65.1
51.9
38.8
75.4
10.9
81.8
77.0
63.9
50.7
37.6
75.1
11.0
48.8
34.0
102.9
11.4
69.1
54.3
39.5
93.1
11.2
89.5
74.6
59.8
45.0
83.3
11.0
85.4
85.4
70.6
55.8
41.0
77.3
10.9
84.1
84.1
69.3
54.5
39.6
77.0
11.0
73.7
57.7
41.8
93.9
11.3
91.6
79.3
63.3
47.4
84.0
11.1
86.1
86.1
70.1
54.2
38.2
77.9
11.0
84.8
84.8
68.8
52.8
36.9
77.6
11.1
78.3
61.1
44.0
94.7
11.4
93.8
84.0
66.9
49.7
84.7
11.1
86.8
86.8
69.7
52.6
35.4
78.6
11.1
85.5
85.5
68.3
51.2
34.1
78.2
11.2
90
36.2
56.8
77.4
71.8
49.9
64.7
79.4
73.6
73.3
63.7
72.5
81.4
75.4
75.1
77.4
80.4
83.3
77.3
77.0
86.0
84.0
77.9
77.6
91.6
84.7
78.6
78.2
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
31.0
22.6
47.1
37.5
27.8
62.1
52.4
42.7
33.1
71.8
57.3
47.7
38.0
36.6
25.3
53.3
41.9
30.6
70.0
58.6
47.3
35.9
73.6
64.2
52.8
41.5
73.3
63.4
52.1
40.7
42.3
28.0
59.5
46.4
33.4
77.9
64.8
51.8
38.7
75.4
71.0
58.0
44.9
75.1
70.2
57.1
44.1
47.9
30.7
65.6
50.9
36.1
83.3
71.1
56.3
41.6
77.3
77.3
63.1
48.4
77.0
77.0
62.2
47.5
70.1
54.1
38.2
84.0
75.6
59.7
43.8
77.9
77.9
62.3
46.4
77.6
77.6
61.7
45.8
74.5
57.4
40.3
84.7
80.2
63.1
46.0
78.6
78.6
61.5
44.4
78.2
78.2
61.2
44.1
65
28.3
30.1
29.3
31.9
31.0
33.6
32.7
30.5
29.8
27.3
27.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
85
5123247-TTG-A-0515
ZKT08 (8.5 Ton) Reheat
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
86
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72.0
74.0
61.6
73.3
75.3
62.6
58.2
74.5
76.7
63.6
59.2
75.7
78.1
64.7
60.2
73.9
76.5
63.0
58.8
72.0
75.0
61.4
57.4
5.0
4.9
5.1
4.9
4.8
5.0
4.7
4.8
4.7
5.0
4.7
4.7
4.6
4.9
4.6
4.7
4.6
4.9
4.6
4.7
4.6
4.9
4.6
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
53.3
49.0
46.3
56.3
51.8
49.0
43.2
59.4
54.6
51.6
45.5
62.4
57.4
54.3
47.9
66.2
60.9
57.6
50.8
70.1
64.5
60.9
53.7
6.1
5.8
5.4
6.0
5.7
5.4
5.3
6.0
5.7
5.4
5.3
6.0
5.7
5.3
5.2
5.9
5.6
5.3
5.2
5.9
5.6
5.3
5.2
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
35°F
8.5
7.1
5.7
62.7
5.5
11.6
10.2
8.8
7.3
61.5
5.3
21.8
20.4
18.9
17.5
16.1
53.9
5.3
13.4
11.3
9.2
64.8
5.5
17.9
15.8
13.7
11.6
63.6
5.3
33.6
31.5
29.4
27.3
25.2
55.8
5.2
37.4
35.3
33.2
31.2
29.1
50.7
5.0
18.2
15.5
12.7
66.9
5.4
24.1
21.4
18.7
15.9
65.7
5.2
45.3
42.6
39.9
37.1
34.4
57.6
5.2
48.8
47.8
45.0
42.3
39.6
52.4
5.0
23.0
19.6
16.2
69.1
5.3
30.4
27.0
23.6
20.2
67.8
5.1
57.1
53.7
50.4
47.0
43.6
59.5
5.1
60.2
60.2
56.8
53.5
50.1
54.0
4.9
25.8
22.4
18.9
70.1
5.3
33.7
30.2
26.8
23.3
68.7
5.1
62.0
60.1
56.7
53.2
49.8
60.3
5.1
58.8
58.8
55.4
51.9
48.4
54.8
4.9
28.7
25.1
21.6
71.0
5.3
37.0
33.5
29.9
26.4
69.7
5.1
61.4
61.4
61.4
59.5
55.9
61.2
5.1
57.4
57.4
53.9
50.4
46.8
55.6
4.9
55°F
48.0
6.2
7.3
6.5
5.7
4.9
42.2
6.1
14.6
13.9
13.1
12.3
11.5
39.1
5.8
53.6
6.1
11.9
10.5
9.1
7.7
47.0
6.1
23.8
22.4
21.0
19.6
18.1
43.5
5.7
28.6
27.1
25.7
24.3
22.9
36.3
5.7
59.2
6.1
16.6
14.5
12.5
10.4
51.7
6.0
33.0
31.0
28.9
26.8
24.8
47.8
5.7
38.2
37.5
35.4
33.4
31.3
39.8
5.6
64.8
6.1
21.3
18.5
15.8
13.1
56.5
6.0
42.2
39.5
36.8
34.1
31.4
52.2
5.7
47.9
47.9
45.2
42.4
39.7
43.3
5.6
67.4
6.0
24.7
21.4
18.1
14.9
58.8
6.0
48.8
45.6
42.3
39.0
35.8
54.4
5.6
50.8
50.8
47.5
44.3
41.0
45.2
5.6
70.0
6.0
28.1
24.2
20.4
16.6
61.1
5.9
55.5
51.6
47.8
44.0
40.2
56.5
5.6
53.7
53.7
49.9
46.1
42.3
47.1
5.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
45°F
3.5
2.4
1.3
9.5
8.4
7.2
6.1
18.2
17.1
16.0
14.9
5.6
3.8
2.1
14.9
13.2
11.4
9.7
28.7
26.9
25.2
23.4
33.0
31.2
29.5
27.7
7.6
5.2
2.8
20.4
18.0
15.6
13.2
39.2
36.8
34.4
32.0
43.5
42.6
40.2
37.8
9.7
6.6
3.6
25.8
22.8
19.7
16.7
49.7
46.6
43.6
40.5
54.0
54.0
51.0
47.9
10.9
7.5
4.2
29.2
25.8
22.5
19.1
55.4
52.9
49.5
46.1
54.8
54.8
51.4
48.1
12.1
8.4
4.7
32.5
28.9
25.2
21.5
61.2
59.1
55.4
51.7
55.6
55.6
51.9
48.2
65°F
4.4
4.0
3.5
3.1
9.5
9.1
8.6
8.2
9.1
8.0
6.9
5.8
20.2
19.1
18.0
16.9
22.6
21.5
20.4
19.3
13.7
12.0
10.2
8.5
30.9
29.1
27.4
25.7
33.0
32.4
30.7
28.9
18.3
15.9
13.6
11.2
41.6
39.2
36.8
34.4
43.3
43.3
41.0
38.6
22.2
19.2
16.3
13.3
47.7
45.5
42.6
39.6
45.2
45.2
42.2
39.3
26.0
22.5
19.0
15.4
53.8
51.9
48.3
44.8
47.1
47.1
43.5
40.0
65
13.8
21.7
26.0
29.6
35.4
37.5
44.9
42.8
44.7
48.0
44.5
7.7
15.8
18.2
23.9
27.2
32.0
36.2
36.6
36.3
41.2
36.4
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT08 (8.5 Ton) Reheat (Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
42.8
35.4
31.9
50.9
42.1
38.0
29.4
59.1
48.9
44.0
34.1
67.2
55.6
50.1
38.8
68.6
56.7
51.1
39.6
69.9
57.8
52.1
40.4
6.3
6.5
6.2
6.2
6.4
6.1
6.1
6.2
6.4
6.1
6.0
6.2
6.3
6.0
6.0
6.1
6.3
6.0
5.9
6.1
6.3
5.9
5.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
37.6
6.4
1.6
1.5
1.4
1.2
28.6
6.8
4.4
4.3
4.2
4.1
4.0
24.7
6.5
48.3
6.4
6.2
5.4
4.7
3.9
37.3
6.8
16.6
15.8
15.0
14.3
13.5
32.5
6.5
16.6
15.8
15.0
14.3
13.5
22.5
6.4
58.9
6.3
10.8
9.4
8.0
6.6
46.0
6.7
28.7
27.3
25.9
24.5
23.1
40.2
6.4
27.7
27.3
25.9
24.5
23.1
28.4
6.4
69.6
6.3
15.4
13.3
11.3
9.2
54.7
6.7
40.9
38.8
36.8
34.7
32.6
48.0
6.4
38.8
38.8
36.8
34.7
32.6
34.3
6.3
69.7
6.2
19.7
17.0
14.4
11.7
54.6
6.6
46.5
45.5
42.8
40.1
37.5
47.9
6.3
39.6
39.6
36.9
34.3
31.6
34.0
6.3
69.8
6.2
24.0
20.8
17.5
14.2
54.5
6.6
52.1
52.1
48.8
45.6
42.3
47.7
6.3
40.4
40.4
37.1
33.9
30.6
33.7
6.2
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
3.3
2.9
2.5
2.0
13.0
12.5
12.1
11.6
10.6
10.1
9.7
9.3
7.9
6.8
5.7
4.6
26.6
25.5
24.4
23.3
22.4
22.2
21.1
20.0
12.5
10.7
9.0
7.3
40.2
38.5
36.7
35.0
34.3
34.3
32.6
30.8
17.2
14.9
12.5
10.2
45.3
45.4
43.1
40.7
34.0
34.0
31.6
29.3
22.0
19.0
16.0
13.1
47.7
47.7
47.7
46.4
33.7
33.7
30.7
27.8
65
11.2
8.8
22.2
19.0
33.3
29.1
38.3
26.9
43.4
24.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
87
5123247-TTG-A-0515
ZKT10 (10 Ton) Cooling
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
88
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
137.8
131.8
125.8
113.9
143.9
137.6
131.3
118.9
114.8
150.0
143.4
136.9
123.9
119.6
156.1
149.3
142.5
129.0
124.5
151.7
144.8
131.1
126.6
154.2
147.2
133.3
128.6
7.3
7.1
7.0
6.9
7.4
7.2
7.0
6.9
6.9
7.4
7.2
7.1
7.0
7.0
7.4
7.3
7.1
7.0
7.0
7.3
7.1
7.0
7.0
7.3
7.2
7.1
7.1
67.5
85.5
103.5
113.9
73.5
93.3
113.1
118.9
114.8
79.5
101.1
122.7
123.9
119.6
85.5
108.9
132.2
129.0
124.5
116.7
139.7
131.1
126.6
124.5
147.2
133.3
128.6
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
127.3
119.8
112.4
103.2
132.4
124.6
116.9
107.3
106.5
137.4
129.4
121.3
111.4
110.6
142.5
134.1
125.8
115.5
114.7
136.0
127.5
117.1
116.2
137.8
129.2
118.6
117.8
9.2
9.1
9.0
9.0
9.2
9.1
9.0
9.0
8.9
9.2
9.2
9.1
9.0
9.0
9.3
9.2
9.1
9.0
9.0
9.2
9.1
9.0
9.0
9.2
9.1
9.0
9.0
57.6
75.9
94.3
103.2
65.2
85.0
104.8
107.3
106.5
72.9
94.1
115.3
111.4
110.6
80.5
103.1
125.8
115.5
114.7
110.2
127.5
117.1
116.2
117.3
129.2
118.6
117.8
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
55.5
43.9
132.5
8.2
73.9
62.3
50.6
125.8
8.1
92.3
80.6
69.0
57.4
119.1
8.0
112.8 97.5
85.8
74.2
62.6
108.5
7.9
60.4
47.3
138.1
8.3
80.2
67.1
54.0
131.1
8.2
100.0 86.9
73.8
60.7
124.1
8.0
118.2 105.1 92.0
78.9
65.8
113.1
8.0
114.8 108.3 95.2
82.2
69.1
110.6
7.9
65.3
50.8
143.7
8.3
86.5
72.0
57.4
136.4
8.2
107.7 93.2
78.6
64.0
129.1
8.1
123.6 112.7 98.1
83.5
69.0
117.7
8.0
119.6 116.2 101.6 87.0
72.5
115.1
8.0
70.2
54.2
149.3
8.4
92.8
76.8
60.8
141.7
8.2
115.4 99.4
83.4
67.4
134.1
8.1
129.0 120.2 104.2 88.2
72.2
122.2
8.0
124.5 124.0 108.0 91.9
75.9
119.6
8.0
99.1
81.6
64.0
143.8
8.2
123.1 105.6 88.0
70.5
136.2
8.1
131.1 126.7 109.2 91.6
74.1
124.1
8.0
126.6 126.3 108.8 91.2
73.7
121.4
8.0
105.4 86.4
67.3
146.0
8.3
130.9 111.8 92.7
73.6
138.2
8.1
133.3 133.3 114.2 95.1
76.0
125.9
8.1
128.6 128.6 109.6 90.5
71.4
123.2
8.0
95°F
47.1
36.2
117.5
10.5
65.0
54.1
43.3
110.8
10.4
83.0
72.1
61.2
50.3
104.0
10.3
101.2 84.7
73.8
62.9
52.0
96.1
10.2
52.5
39.8
122.4
10.5
72.3
59.6
46.9
115.4
10.4
92.1
79.4
66.7
54.0
108.3
10.3
106.0 93.3
80.6
67.9
55.2
100.1
10.2
106.5 96.1
83.4
70.7
58.0
99.2
10.2
58.0
43.5
127.3
10.5
79.6
65.1
50.6
120.0
10.4
101.2 86.7
72.2
57.7
112.6
10.3
110.7 101.8 87.3
72.8
58.3
104.0
10.2
110.6 104.9 90.4
75.9
61.4
103.2
10.2
63.5
47.2
132.1
10.5
86.8
70.5
54.3
124.6
10.4
110.2 93.9
77.6
61.3
117.0
10.3
115.5 110.4 94.1
77.8
61.5
108.0
10.2
114.7 113.7 97.4
81.1
64.8
107.1
10.2
92.4
74.7
56.9
126.1
10.4
117.2 99.4
81.7
63.9
118.4
10.3
117.1 114.5 96.7
79.0
61.2
109.4
10.2
116.2 115.8 98.0
80.2
62.5
108.4
10.2
98.0
78.8
59.5
127.6
10.4
124.2 104.9 85.7
66.4
119.8
10.3
118.6 118.6 99.4
80.2
60.9
110.7
10.2
117.8 117.8 98.6
79.3
60.1
109.8
10.2
90
62.6
80.7
98.9
108.5
69.4
89.1
108.9
113.1
110.6
76.2
97.6
119.0
117.7
115.1
83.0
106.0
129.0
122.2
119.6
113.4
133.6
124.1
121.4
120.9
138.2
125.9
123.2
52.8
72.3
91.8
96.1
61.8
81.0
100.2
100.1
99.2
70.7
89.6
108.6
104.0
103.2
79.6
98.3
117.0
108.0
107.1
105.2
118.4
109.4
108.4
112.0
119.8
110.7
109.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
51.3
40.0
69.5
58.2
46.9
87.6
76.4
65.1
53.9
107.0 91.1
79.8
68.6
56.5
43.6
76.3
63.4
50.5
96.0
83.1
70.2
57.4
112.1 99.2
86.3
73.4
110.6 102.2 89.3
76.4
61.7
47.1
83.0
68.5
54.0
104.4 89.9
75.4
60.9
117.1 107.2 92.7
78.2
115.1 110.5 96.0
81.5
66.8
50.7
89.8
73.7
57.5
112.8 96.7
80.5
64.4
122.2 115.3 99.2
83.0
119.6 118.9 102.7 86.5
95.8
78.1
60.5
120.2 102.5 84.9
67.2
124.1 120.6 103.0 85.3
121.4 121.0 103.4 85.7
101.7 82.6
63.4
127.5 108.3 89.2
70.0
125.9 125.9 106.8 87.6
123.2 123.2 104.1 84.9
105°F
44.2
33.5
61.6
50.9
40.3
79.1
68.4
57.7
47.0
95.1
80.3
69.6
58.9
49.3
36.9
68.5
56.1
43.7
87.8
75.3
62.9
50.5
99.4
88.5
76.0
63.6
99.2
89.5
77.0
64.6
54.5
40.3
75.5
61.3
47.2
96.5
82.3
68.1
54.0
103.7 96.6
82.5
68.3
103.2 97.7
83.6
69.4
59.6
43.7
82.4
66.5
50.6
105.2 89.3
73.4
57.5
108.0 104.8 88.9
73.0
107.1 106.0 90.1
74.2
87.8
70.5
53.1
111.2 94.6
77.2
59.9
109.4 107.8 90.4
73.1
108.4 107.9 90.5
73.2
93.2
74.4
55.6
117.3 99.9
81.1
62.2
110.7 110.7 91.9
73.1
109.8 109.8 91.0
72.1
65
57.3
60.5
63.5
63.7
67.0
66.8
70.4
67.6
68.1
68.5
65.7
48.2
51.2
52.2
54.2
55.3
57.1
58.3
55.7
55.8
54.3
53.3
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT10 (10 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
107.7
101.7
95.6
89.0
112.4
106.1
99.8
92.8
91.9
117.1
110.6
104.0
96.7
95.7
121.8
115.0
108.2
100.6
99.6
116.2
109.3
101.7
100.6
117.5
110.5
102.7
101.7
11.9
11.7
11.6
11.4
11.8
11.7
11.5
11.3
11.4
11.8
11.7
11.5
11.3
11.4
11.8
11.6
11.5
11.3
11.4
11.6
11.5
11.3
11.4
11.7
11.5
11.3
11.4
48.1
68.7
89.3
89.0
58.3
76.9
95.6
92.8
91.9
68.5
85.2
101.9
96.7
95.7
78.7
93.4
108.2
100.6
99.6
100.1
109.3
101.7
100.6
106.8
110.5
102.7
101.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
41.3
30.8
98.0
13.2
58.2
47.7
37.3
92.6
13.0
75.1
64.6
54.2
43.7
87.3
12.8
89.0
75.9
65.4
54.9
44.4
81.8
12.6
46.1
34.0
102.5
13.1
64.8
52.6
40.5
96.9
13.0
83.4
71.3
59.1
47.0
91.3
12.8
92.8
83.7
71.5
59.4
47.2
85.6
12.5
91.9
82.8
70.7
58.5
46.4
84.6
12.7
51.0
37.2
107.0
13.1
71.4
57.5
43.7
101.2
12.9
91.8
77.9
64.1
50.3
95.3
12.7
96.7
91.5
77.6
63.8
50.0
89.4
12.5
95.7
90.5
76.7
62.9
49.1
88.3
12.6
55.8
40.3
111.5
13.0
77.9
62.5
47.0
105.4
12.8
100.1 84.6
69.1
53.6
99.3
12.7
100.6 99.3
83.8
68.3
52.8
93.1
12.4
99.6
98.3
82.8
67.3
51.8
92.0
12.6
83.2
66.2
49.3
106.4
12.9
105.3 89.7
72.8
55.8
100.2
12.7
101.7 101.0 84.1
67.1
50.2
94.0
12.4
100.6 100.0 83.1
66.1
49.2
92.9
12.6
88.4
70.0
51.6
107.3
12.9
110.5 94.8
76.4
58.1
101.1
12.7
102.7 102.7 84.4
66.0
47.6
94.8
12.5
101.7 101.7 83.3
65.0
46.6
93.7
12.7
90
43.3
65.1
86.8
81.8
54.8
72.9
91.0
85.6
84.6
66.3
80.8
95.2
89.4
88.3
77.8
88.6
99.3
93.1
92.0
95.1
100.2
94.0
92.9
101.5
101.1
94.8
93.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
38.4
28.1
54.8
44.5
34.3
71.2
60.9
50.6
40.4
81.8
71.4
61.2
50.9
42.9
31.1
61.0
49.2
37.3
79.1
67.2
55.4
43.5
85.6
78.9
67.0
55.1
84.6
76.2
64.3
52.4
47.5
34.0
67.3
53.8
40.3
87.1
73.6
60.1
46.6
89.4
86.3
72.8
59.3
88.3
83.4
69.9
56.4
52.0
36.9
73.5
58.4
43.3
95.0
79.9
64.8
49.7
93.1
93.1
78.6
63.5
92.0
90.5
75.4
60.3
78.5
62.0
45.5
99.3
84.8
68.3
51.8
94.0
94.0
77.7
61.2
92.9
92.1
75.6
59.1
83.6
65.6
47.7
101.1 89.8
71.8
53.9
94.8
94.8
76.8
58.9
93.7
93.7
75.7
57.8
65
40.6
43.2
40.5
45.8
42.9
48.4
45.3
44.7
42.5
40.9
39.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
89
5123247-TTG-A-0515
ZKT10 (10 Ton) Reheat
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
90
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
81.3
75.9
70.6
72.8
82.4
76.7
71.0
73.6
65.6
83.5
77.5
71.5
74.3
66.1
84.7
78.3
71.9
75.1
66.6
79.5
73.3
76.3
67.8
80.8
74.7
77.5
69.0
6.2
6.1
6.0
5.8
6.2
6.0
5.9
5.7
5.7
6.1
6.0
5.9
5.7
5.6
6.1
6.0
5.9
5.7
5.6
6.0
5.9
5.7
5.6
6.0
5.9
5.7
5.6
12.0
26.3
42.2
15.1
31.5
50.1
56.8
18.1
36.6
58.0
61.7
21.2
41.8
66.0
66.6
22.5
44.3
71.7
67.8
23.8
46.7
77.5
69.0
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
52.1
55.3
58.4
52.2
56.5
59.8
63.2
56.5
55.7
60.8
64.4
68.0
60.8
60.0
65.1
69.0
72.8
65.2
64.2
66.7
70.4
63.0
62.1
64.4
68.0
60.9
60.0
7.4
6.9
6.5
6.2
7.4
6.9
6.5
6.2
6.1
7.3
6.9
6.5
6.2
6.1
7.3
6.9
6.5
6.2
6.1
7.0
6.6
6.3
6.2
7.0
6.6
6.3
6.2
1.2
16.2
28.2
2.0
22.5
39.0
46.2
2.9
28.9
49.8
55.2
3.7
35.3
60.6
64.2
4.1
37.8
60.7
62.1
4.5
40.4
60.9
60.0
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
35°F
66.7
6.8
9.6
7.1
4.7
65.6
6.5
23.9
21.5
19.1
16.6
64.5
6.2
39.7
37.3
34.9
32.5
30.0
62.5
6.0
69.4
6.8
12.1
9.2
6.2
68.3
6.5
28.6
25.6
22.7
19.7
67.1
6.2
47.2
44.2
41.3
38.3
35.4
65.0
6.0
53.9
50.9
48.0
45.0
42.1
60.6
5.9
72.1
6.7
14.7
11.2
7.8
70.9
6.5
33.2
29.7
26.3
22.8
69.7
6.2
54.6
51.1
47.7
44.2
40.8
67.6
6.0
60.2
58.7
55.3
51.8
48.4
63.0
5.9
74.9
6.7
17.2
13.3
9.3
73.6
6.4
37.8
33.9
29.9
25.9
72.4
6.2
62.0
58.0
54.1
50.1
46.1
70.1
5.9
66.6
66.6
62.6
58.6
54.7
65.4
5.9
18.3
14.1
9.9
73.1
6.5
40.1
35.9
31.7
27.5
71.9
6.2
67.7
61.5
57.3
53.1
49.0
69.7
6.0
67.8
67.8
63.6
59.4
55.2
64.9
5.9
19.4
15.0
10.6
72.6
6.5
42.3
38.0
33.6
29.2
71.4
6.2
73.5
65.0
60.6
56.2
51.8
69.2
6.0
69.0
69.0
64.6
60.2
55.8
64.5
5.9
55°F
46.4
7.7
49.0
7.3
14.7
13.2
11.7
10.2
51.6
6.9
26.7
25.2
23.7
22.3
20.8
46.1
6.5
51.3
7.7
54.1
7.3
20.3
18.1
15.8
13.6
57.0
6.8
36.8
34.5
32.3
30.1
27.8
50.8
6.5
44.0
41.7
39.5
37.3
35.0
50.2
6.5
56.1
7.7
59.2
7.3
25.9
22.9
20.0
17.0
62.3
6.8
46.8
43.9
40.9
37.9
34.9
55.6
6.5
54.1
53.0
50.0
47.0
44.0
54.9
6.5
60.9
7.7
64.3
7.2
31.5
27.8
24.1
20.4
67.6
6.8
56.9
53.2
49.4
45.7
42.0
60.4
6.5
64.2
64.2
60.5
56.8
53.0
59.6
6.5
63.3
7.3
33.8
29.7
25.7
21.6
66.7
6.9
58.9
56.8
52.8
48.7
44.7
59.5
6.6
62.1
62.1
58.0
54.0
49.9
58.8
6.5
62.4
7.3
36.0
31.7
27.3
22.9
65.7
6.9
60.9
60.5
56.2
51.8
47.4
58.6
6.6
60.0
60.0
55.6
51.2
46.8
57.9
6.5
90
6.6
21.3
35.2
8.5
27.0
44.6
51.5
10.5
32.8
53.9
58.4
12.5
38.5
63.3
65.4
13.3
41.1
66.2
64.9
14.1
43.6
69.2
64.5
13.0
23.7
19.4
34.9
40.6
25.7
46.2
50.1
32.0
57.5
59.6
36.0
58.0
58.8
40.0
58.6
57.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
45°F
4.6
2.7
19.3
17.3
15.4
13.4
33.2
31.3
29.3
27.4
6.0
3.4
24.4
21.8
19.3
16.7
42.0
39.4
36.8
34.2
48.9
46.3
43.7
41.1
7.3
4.1
29.6
26.3
23.1
19.9
50.7
47.5
44.3
41.1
57.1
55.9
52.6
49.4
8.6
4.8
34.7
30.8
27.0
23.1
59.4
55.6
51.7
47.9
65.4
65.4
61.5
57.7
9.2
5.1
36.9
32.8
28.7
24.6
63.3
59.2
55.1
50.9
64.9
64.9
60.8
56.7
9.8
5.4
39.2
34.8
30.4
26.0
67.2
62.8
58.4
54.0
64.5
64.5
60.1
55.7
65°F
11.8
10.6
9.4
8.2
22.5
21.3
20.0
18.8
17.4
15.4
13.5
11.5
33.0
31.0
29.0
27.1
38.6
36.6
34.7
32.7
23.0
20.2
17.5
14.8
43.5
40.7
38.0
35.3
49.1
48.1
45.4
42.6
28.5
25.1
21.6
18.1
54.0
50.5
47.0
43.5
59.6
59.6
56.1
52.6
32.0
28.0
24.0
20.0
56.3
54.5
50.5
46.5
58.8
58.7
54.7
50.7
35.5
31.0
26.5
22.0
58.6
58.5
53.9
49.4
57.9
57.9
53.4
48.9
65
25.4
31.6
38.6
37.8
46.2
44.1
53.8
46.8
52.6
49.6
51.3
17.6
25.1
30.7
32.5
39.9
40.0
49.1
42.5
46.7
44.9
44.4
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT10 (10 Ton) Reheat (Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
40.8
42.8
44.9
39.9
46.1
48.4
50.7
45.2
44.8
51.4
54.0
56.6
50.4
49.9
56.7
59.6
62.4
55.6
55.1
60.0
62.9
56.0
55.5
60.5
63.4
56.4
55.9
8.0
7.6
7.2
6.9
8.0
7.6
7.2
6.8
6.8
8.0
7.6
7.1
6.8
6.8
8.0
7.6
7.1
6.8
6.8
7.6
7.2
6.9
6.8
7.7
7.2
6.9
6.9
9.9
19.1
16.2
30.9
34.9
22.5
42.6
45.0
28.8
54.3
55.1
34.2
55.4
55.5
39.7
56.4
55.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
35.1
8.4
36.6
8.0
9.0
8.1
7.1
6.2
38.1
7.5
18.2
17.3
16.3
15.4
14.5
33.8
7.2
40.9
8.4
42.7
7.9
14.5
12.8
11.1
9.4
44.5
7.5
29.2
27.5
25.7
24.0
22.3
39.5
7.2
33.2
31.5
29.8
28.1
26.4
39.3
7.1
46.7
8.3
48.8
7.9
20.0
17.5
15.1
12.6
50.9
7.5
40.1
37.6
35.1
32.7
30.2
45.1
7.1
44.2
43.2
40.7
38.3
35.8
44.9
7.1
52.5
8.3
54.9
7.9
25.6
22.3
19.0
15.8
57.3
7.4
51.1
47.8
44.6
41.3
38.0
50.8
7.1
55.1
54.9
51.7
48.4
45.1
50.5
7.1
56.7
7.9
30.3
26.3
22.4
18.4
59.2
7.5
53.7
52.1
48.1
44.2
40.2
52.5
7.2
55.5
55.4
51.4
47.5
43.5
52.2
7.1
58.5
8.0
35.0
30.4
25.7
21.0
61.0
7.5
56.4
56.4
51.7
47.1
42.4
54.2
7.2
55.9
55.9
51.2
46.6
41.9
53.9
7.2
90
6.8
14.6
13.0
26.8
29.3
19.3
39.0
39.9
25.6
50.8
50.5
32.4
52.5
52.2
39.3
54.2
53.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
6.1
5.5
4.8
4.2
13.9
13.3
12.6
12.0
11.6
10.2
8.7
7.3
25.3
23.9
22.5
21.0
27.9
26.4
25.0
23.6
17.1
14.8
12.6
10.4
36.8
34.5
32.3
30.0
39.2
38.4
36.1
33.9
22.6
19.5
16.5
13.4
48.2
45.1
42.1
39.1
50.5
50.3
47.2
44.2
28.5
24.6
20.7
16.8
51.2
49.7
45.8
41.9
52.2
52.1
48.2
44.2
34.5
29.7
24.9
20.1
54.2
54.2
49.5
44.7
53.9
53.9
49.1
44.3
65
11.3
19.6
22.1
27.8
31.6
36.0
41.2
38.0
40.3
39.9
39.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
91
5123247-TTG-A-0515
ZKT12 (12.5 Ton) Cooling
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
92
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
190.5
180.7
171.0
158.6
199.8
189.6
179.4
166.3
154.4
209.1
198.4
187.7
174.1
161.6
218.4
207.3
196.1
181.8
168.8
211.2
199.9
185.3
172.0
215.2
203.6
188.8
175.3
9.0
9.2
9.3
9.1
9.2
9.3
9.4
9.2
9.2
9.3
9.4
9.6
9.4
9.3
9.4
9.6
9.7
9.5
9.5
9.6
9.7
9.5
9.5
9.5
9.7
9.5
9.4
87.6
111.5
135.4
158.6
94.7
119.8
145.0
166.3
154.4
101.9
128.2
154.5
174.1
161.6
109.0
136.6
164.1
181.8
168.8
148.0
179.4
185.3
172.0
159.4
194.6
188.8
175.3
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
180.0
165.1
150.2
137.5
188.2
172.7
157.1
143.8
139.4
196.5
180.3
164.0
150.1
145.5
204.8
187.8
170.9
156.4
151.6
193.2
175.8
160.9
156.0
198.6
180.7
165.4
160.3
11.9
11.8
11.7
11.5
12.0
11.9
11.7
11.6
11.6
12.0
11.9
11.8
11.6
11.7
12.1
12.0
11.9
11.7
11.7
12.0
11.9
11.7
11.7
12.0
11.9
11.7
11.8
75.6
99.3
123.0
137.5
83.2
109.0
134.8
143.8
139.4
90.7
118.6
146.6
150.1
145.5
98.3
128.3
158.4
156.4
151.6
138.6
169.6
160.9
156.0
148.9
180.7
165.4
160.3
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
73.4
59.1
185.2
10.5
97.2
83.0
68.8
172.9
10.5
121.1 106.9 92.7
78.4
160.6
10.5
158.6 158.6 150.5 136.2 122.0
148.0
10.3
78.6
62.4
194.0
10.6
103.7 87.5
71.3
181.1
10.6
128.8 112.6 96.4
80.3
168.3
10.6
166.3 166.3 157.9 141.8 125.6
155.1
10.4
154.4 148.9 132.7 116.6 100.4
146.9
10.4
83.8
65.7
202.8
10.7
110.1 92.0
73.9
189.3
10.7
136.4 118.3 100.2 82.1
175.9
10.7
174.1 174.1 165.4 147.3 129.2
162.1
10.5
161.6 156.6 138.5 120.4 102.3
153.5
10.5
89.0
68.9
211.6
10.8
116.5 96.5
76.5
197.5
10.8
144.1 124.1 104.0 84.0
183.5
10.8
181.8 181.8 172.9 152.9 132.8
169.1
10.6
168.8 164.4 144.3 124.3 104.2
160.2
10.6
126.6 105.3 83.9
202.2
10.8
156.7 135.4 114.0 92.7
187.8
10.8
185.3 185.3 169.5 148.2 126.8
173.1
10.6
172.0 169.8 148.5 127.1 105.8
164.0
10.6
136.7 114.0 91.4
206.9
10.8
169.4 146.7 124.0 101.4
192.2
10.8
188.8 188.8 166.2 143.5 120.9
177.1
10.6
175.3 175.3 152.6 130.0 107.3
167.8
10.6
95°F
61.3
46.9
168.2
13.3
85.0
70.6
56.3
153.8
13.2
108.6 94.3
80.0
65.6
139.5
13.0
133.0 114.6 100.2 85.9
71.5
127.9
12.9
67.2
51.2
175.5
13.3
93.0
77.0
60.9
160.6
13.2
118.8 102.8 86.7
70.7
145.6
13.1
140.8 124.8 108.8 92.8
76.8
133.5
12.9
139.4 125.8 109.8 93.8
77.7
130.3
13.0
73.0
55.4
182.9
13.4
101.0 83.3
65.6
167.3
13.3
128.9 111.2 93.5
75.8
151.8
13.1
148.6 135.1 117.4 99.7
82.0
139.2
13.0
145.5 136.1 118.4 100.7 83.1
135.7
13.0
78.9
59.6
190.3
13.4
109.0 89.6
70.2
174.1
13.3
139.0 119.6 100.3 80.9
157.9
13.2
156.4 145.3 126.0 106.6 87.2
144.8
13.0
151.6 146.4 127.1 107.7 88.4
141.2
13.1
117.4 96.2
75.1
178.5
13.3
149.7 128.5 107.3 86.1
161.8
13.2
160.9 155.4 134.2 113.0 91.8
148.4
13.0
156.0 153.4 132.2 111.0 89.8
144.7
13.1
125.9 102.9 79.9
182.8
13.3
160.4 137.4 114.4 91.4
165.8
13.2
165.4 165.4 142.4 119.4 96.4
152.0
13.0
160.3 160.3 137.3 114.3 91.3
148.3
13.1
90
81.6
105.4
129.2
148.0
89.0
114.4
139.9
155.1
146.9
96.3
123.4
150.6
162.1
153.5
103.6
132.4
161.2
169.1
160.2
143.3
174.5
173.1
164.0
154.1
187.7
177.1
167.8
71.8
95.1
118.4
127.9
79.5
104.5
129.4
133.5
130.3
87.3
113.9
140.5
139.2
135.7
95.1
123.3
151.6
144.8
141.2
133.3
158.7
148.4
144.7
143.3
165.8
152.0
148.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
67.3
53.0
91.1
76.8
62.5
114.9 100.6 86.3
72.0
148.0 139.6 125.3 111.1
72.9
56.8
98.3
82.2
66.1
123.8 107.7 91.6
75.5
155.1 149.5 133.4 117.3
146.9 137.3 121.2 105.2
78.4
60.5
105.5 87.6
69.7
132.7 114.8 96.9
79.0
162.1 159.3 141.4 123.5
153.5 146.4 128.5 110.6
83.9
64.2
112.7 93.0
73.3
141.5 121.8 102.1 82.4
169.1 169.1 149.4 129.7
160.2 155.4 135.7 116.0
122.0 100.8 79.5
153.2 131.9 110.7 89.4
173.1 173.1 151.9 130.6
164.0 161.6 140.3 119.1
131.3 108.5 85.6
164.9 142.0 119.2 96.4
177.1 177.1 154.3 131.5
167.8 167.8 145.0 122.1
105°F
58.0
43.9
81.0
66.9
52.8
103.9 89.8
75.7
61.6
125.7 110.1 96.0
81.9
63.7
47.8
88.6
72.8
56.9
113.6 97.7
81.9
66.0
132.1 119.8 104.0 88.1
130.3 117.1 101.2 85.4
69.3
51.7
96.3
78.7
61.0
123.3 105.6 88.0
70.4
138.4 129.5 111.9 94.3
135.7 126.6 109.0 91.3
75.0
55.6
104.0 84.6
65.2
132.9 113.6 94.2
74.8
144.8 139.2 119.8 100.4
141.2 136.1 116.7 97.3
112.3 91.2
70.2
143.5 122.5 101.5 80.4
148.4 145.6 124.6 103.5
144.7 142.2 121.1 100.1
120.6 97.9
75.2
154.1 131.4 108.7 86.1
152.0 152.0 129.3 106.6
148.3 148.3 125.6 102.9
65
96.8
101.2
89.1
105.6
92.7
110.0
96.3
109.3
97.8
108.6
99.3
67.8
72.2
69.5
76.6
73.7
81.1
77.9
82.5
79.1
84.0
80.2
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT12 (12.5 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
156.3
142.6
128.8
118.4
162.8
148.5
134.1
123.3
121.1
169.3
154.4
139.5
128.2
126.0
175.8
160.3
144.9
133.1
130.8
163.7
147.9
135.9
133.5
167.0
150.9
138.6
136.2
14.6
14.5
14.4
14.2
14.7
14.6
14.4
14.3
14.3
14.7
14.6
14.5
14.3
14.4
14.8
14.7
14.5
14.4
14.4
14.7
14.5
14.4
14.4
14.7
14.5
14.4
14.4
67.9
90.8
113.7
118.4
75.9
100.0
124.1
123.3
121.1
83.9
109.2
134.5
128.2
126.0
91.9
118.4
144.9
133.1
130.8
128.0
147.9
135.9
133.5
137.7
150.9
138.6
136.2
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
54.8
40.9
144.5
16.0
77.0
63.1
49.3
131.3
15.9
99.1
85.3
71.5
57.6
118.1
15.7
118.4 105.7 91.8
78.0
64.1
108.8
15.6
60.2
44.5
150.2
16.0
84.3
68.6
52.9
136.4
15.9
108.4 92.7
77.0
61.3
122.7
15.8
123.3 114.8 99.1
83.4
67.7
113.0
15.6
121.1 108.4 92.7
77.0
61.3
112.0
15.7
65.6
48.0
155.8
16.1
91.6
74.1
56.5
141.5
16.0
117.6 100.1 82.5
65.0
127.2
15.8
128.2 124.0 106.4 88.8
71.3
117.3
15.7
126.0 117.1 99.5
81.9
64.4
116.2
15.7
71.0
51.6
161.4
16.2
98.9
79.5
60.1
146.6
16.0
126.9 107.5 88.1
68.6
131.8
15.9
133.1 133.1 113.7 94.3
74.9
121.5
15.7
130.8 125.7 106.3 86.9
67.5
120.4
15.8
107.1 86.2
65.3
148.9
16.0
137.4 116.5 95.6
74.7
133.9
15.9
135.9 135.9 115.0 94.1
73.2
123.4
15.7
133.5 131.0 110.1 89.2
68.3
122.3
15.8
115.3 92.9
70.5
151.2
16.0
147.9 125.5 103.1 80.7
135.9
15.8
138.6 138.6 116.3 93.9
71.5
125.3
15.7
136.2 136.2 113.9 91.5
69.1
124.2
15.7
90
60.9
86.6
110.3
108.8
72.3
95.5
118.8
113.0
112.0
83.6
104.5
127.2
117.3
116.2
95.0
113.4
131.8
121.5
120.4
122.7
133.9
123.4
122.3
132.0
135.9
125.3
124.2
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
51.5
37.9
73.0
59.4
45.8
94.4
80.8
67.2
53.6
108.8 102.4 87.6
74.0
56.7
41.2
80.0
64.4
48.9
103.2 87.7
72.1
56.6
113.0 109.8 94.3
78.7
112.0 99.7
84.2
68.6
61.9
44.4
87.0
69.5
52.0
112.0 94.5
77.0
59.5
117.3 117.3 100.9 83.4
116.2 107.5 90.0
72.6
67.0
47.6
93.9
74.5
55.1
120.8 101.4 82.0
62.5
121.5 121.5 107.6 88.1
120.4 115.4 95.9
76.5
102.0 81.2
60.4
131.3 110.5 89.7
69.0
123.4 123.4 105.4 84.6
122.3 119.8 99.0
78.3
110.0 87.9
65.8
135.9 119.6 97.5
75.4
125.3 125.3 103.2 81.1
124.2 124.2 102.1 80.0
65
60.4
63.2
53.1
65.9
55.1
68.7
57.0
63.9
57.5
59.0
58.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
93
5123247-TTG-A-0515
ZKT12 (12.5 Ton) Reheat
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
94
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
87.0
84.6
82.9
89.0
86.5
84.8
82.2
90.9
88.4
86.6
84.0
92.8
90.3
88.5
85.9
94.1
91.5
89.7
87.1
95.4
92.8
91.0
88.3
7.7
7.3
7.3
7.4
7.1
7.1
7.7
7.2
6.9
6.8
7.4
6.9
6.6
6.6
7.1
7.5
7.1
7.1
7.7
8.0
7.7
7.6
8.3
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
84.8
81.9
78.7
88.8
85.8
82.5
76.1
92.8
89.7
86.2
79.5
96.8
93.6
89.9
83.0
99.3
96.0
92.2
85.1
101.8
98.4
94.6
87.2
8.9
8.7
8.2
8.6
8.3
7.8
8.7
8.2
8.0
7.5
8.3
7.8
7.6
7.1
8.0
8.2
8.0
7.5
8.4
8.6
8.4
7.9
8.8
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
35°F
6.6
4.8
3.1
85.9
8.3
14.4
12.7
11.0
9.2
83.3
8.0
20.3
18.6
16.9
15.2
13.5
80.8
7.7
11.5
9.2
6.9
88.9
8.0
26.3
24.0
21.7
19.5
86.2
7.7
36.7
34.4
32.1
29.8
27.5
83.6
7.4
43.1
40.9
38.6
36.3
34.0
79.1
8.2
16.4
13.5
10.7
91.8
7.7
38.3
35.4
32.5
29.7
89.1
7.4
53.1
50.2
47.4
44.5
41.6
86.4
7.2
63.2
60.0
57.1
54.2
51.4
81.8
7.9
21.3
17.9
14.4
94.8
7.4
50.2
46.8
43.3
39.9
91.9
7.1
69.5
66.0
62.6
59.1
55.7
89.2
6.9
83.2
79.1
75.6
72.2
68.7
84.4
7.6
15.2
12.5
9.9
96.7
7.8
35.5
32.8
30.2
27.5
93.8
7.6
48.0
45.4
42.7
40.1
37.4
91.0
7.3
58.0
55.0
52.4
49.7
47.1
86.1
8.0
9.1
7.2
5.4
98.6
8.3
20.7
18.9
17.0
15.2
95.6
8.0
26.6
24.7
22.9
21.0
19.2
92.8
7.8
32.9
31.0
29.2
27.3
25.5
87.8
8.5
55°F
4.6
2.9
1.2
84.2
9.3
9.3
7.6
5.9
4.2
79.1
8.9
15.1
13.4
11.7
10.0
8.3
74.6
8.4
9.9
7.4
5.0
87.3
9.2
21.9
19.4
16.9
14.5
82.0
8.8
36.5
34.1
31.6
29.1
26.7
77.4
8.3
38.4
36.0
33.5
31.0
28.6
72.6
9.0
15.2
11.9
8.7
90.4
9.1
34.4
31.2
27.9
24.7
85.0
8.7
58.0
54.7
51.5
48.3
45.0
80.2
8.2
60.7
57.8
54.6
51.3
48.1
75.2
8.9
20.5
16.5
12.4
93.5
9.0
47.0
42.9
38.9
34.9
87.9
8.6
79.4
75.4
71.4
67.4
63.4
83.0
8.1
83.0
79.6
75.6
71.6
67.6
77.8
8.8
17.4
13.6
9.8
97.7
9.2
39.3
35.5
31.8
28.0
91.8
8.8
66.2
62.4
58.7
54.9
51.1
86.6
8.3
69.3
65.9
62.1
58.4
54.6
81.2
9.0
14.3
10.8
7.3
101.9
9.5
31.7
28.1
24.6
21.1
95.7
9.1
53.0
49.4
45.9
42.4
38.8
90.3
8.6
55.7
52.2
48.7
45.1
41.6
84.7
9.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
45°F
5.6
3.9
2.2
11.8
10.1
8.4
6.7
17.7
16.0
14.3
12.6
10.7
8.3
5.9
24.1
21.7
19.3
17.0
36.6
34.2
31.9
29.5
40.8
38.4
36.0
33.7
15.8
12.7
9.7
36.3
33.3
30.2
27.2
55.5
52.5
49.4
46.4
61.9
58.9
55.8
52.8
20.9
17.2
13.4
48.6
44.9
41.1
37.4
74.5
70.7
67.0
63.3
83.1
79.4
75.6
71.9
16.3
13.1
9.9
37.4
34.2
31.0
27.8
57.1
53.9
50.7
47.5
63.7
60.5
57.3
54.1
11.7
9.0
6.3
26.2
23.5
20.8
18.1
39.8
37.1
34.4
31.7
44.3
41.6
38.9
36.2
65°F
10.4
8.9
7.3
5.8
24.9
23.4
21.8
20.3
18.2
16.0
13.9
11.8
40.0
37.9
35.8
33.7
44.1
42.0
39.9
37.8
25.9
23.2
20.5
17.8
55.1
52.4
49.8
47.1
60.3
57.7
55.1
52.4
1.1
33.6
30.4
27.1
23.8
70.3
67.0
63.7
60.4
76.4
73.5
70.2
66.9
31.7
28.3
25.0
21.6
69.4
66.0
62.6
59.3
72.7
70.3
66.9
63.6
29.8
26.3
22.8
19.4
68.5
65.0
61.6
58.1
68.9
67.1
63.7
60.2
65
10.9
27.1
31.3
43.3
49.7
59.5
68.2
44.3
50.8
29.0
33.5
18.7
31.5
35.6
44.4
49.7
57.2
63.7
55.9
60.2
54.6
56.8
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT12 (12.5 Ton) Reheat (Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
83.6
76.2
70.5
85.8
78.2
72.3
69.0
88.0
80.2
74.2
70.8
90.1
82.2
76.0
72.6
96.1
87.6
81.0
77.3
102.0
93.0
86.0
82.1
9.7
9.2
8.7
9.9
9.3
8.8
9.3
10.0
9.4
8.9
9.5
10.1
9.5
9.0
9.6
10.3
9.6
9.1
9.7
10.4
9.8
9.2
9.8
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
83.0
10.2
11.5
10.1
8.7
7.3
73.4
9.4
34.8
33.4
32.0
30.6
29.2
66.4
8.9
84.3
10.5
14.5
12.7
10.9
9.1
74.4
9.7
43.6
41.8
40.0
38.2
36.4
67.3
9.3
49.8
48.1
46.3
44.5
42.7
65.5
9.7
85.5
10.9
17.4
15.2
13.1
10.9
75.5
10.1
52.3
50.2
48.0
45.8
43.7
68.2
9.6
59.9
57.7
55.5
53.4
51.2
66.4
10.0
86.8
11.3
20.3
17.8
15.2
12.7
76.5
10.5
61.1
58.5
56.0
53.5
50.9
69.1
10.0
69.9
67.3
64.8
62.3
59.7
67.4
10.4
94.4
11.3
24.1
21.1
18.1
15.2
83.4
10.5
72.5
69.6
66.6
63.7
60.7
75.4
9.9
76.0
74.7
71.8
68.8
65.8
73.4
10.4
102.0
11.3
27.8
24.5
21.1
17.7
90.3
10.4
84.0
80.6
77.2
73.8
70.5
81.7
9.9
82.1
82.1
78.7
75.3
71.9
79.5
10.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
12.6
11.4
10.1
8.8
44.7
43.4
42.1
40.9
10.8
9.3
7.9
6.4
47.1
45.6
44.2
42.7
55.5
54.1
52.7
51.2
8.9
7.2
5.6
4.0
49.5
47.9
46.2
44.6
59.4
57.6
56.0
54.4
7.0
5.2
3.4
1.6
51.9
50.1
48.3
46.5
63.3
61.2
59.4
57.6
16.4
13.9
11.3
8.8
75.4
73.1
70.6
68.0
73.4
73.4
73.4
73.4
25.9
22.6
19.3
16.0
81.7
81.7
81.7
81.7
79.5
79.5
79.5
79.5
65
39.6
41.3
49.8
43.0
52.8
44.7
55.8
65.5
71.5
81.7
79.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
95
5123247-TTG-A-0515
Drive Selection
1.
Determine side or bottom supply duct Application.
2.
Determine desired airflow.
3.
Calculate or measure the amount of external static pressure.
• Add or deduct any additional static resistance from “Additional Static Resistance Table”.
4.
Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance
table. (Linear interpolation may be necessary.)
5.
Noting the RPM and BHP from step 4, locate the appropriate motor and, or drive on the RPM selection table.
6.
Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.
7.
Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
8.
Determine turns open to obtain the desired operation point.
Example
1.
2600 CFM
2.
1.6 iwg
3.
Using the supply air blower performance table below, the following data point was located: 1268 RPM & 1.95 BHP.
4.
Using the RPM selection table below, Size X and Model Y is found.
5.
1.95 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.
6.
1268 RPM is within the range of the 2 HP drives.
7.
Using the 2 HP motor and drive, .5 turns open will achieve 1268 RPM.
Airflow Performance
Example Supply Air Blower Performance
Air Flow
(CFM)
2200
2400
2600
2800
Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
804
835
869
906
0.50
0.66
0.84
1.03
1.5 HP & Field Supplied Drive
866
0.71
925
0.90
982
897
0.87
956
1.06 1013
931
1.05
990
1.24 1047
968
1.25 1027 1.43 1084
1.06
1.22
1.40
1.60
1038
1069
1103
1139
Standard 1.5 HP & Drive
1.21 1092 1.35 1147
1.37 1124 1.51 1178
1.55 1158 1.69 1212
1.75 1194 1.89 1249
1.48
1.64
1.82
2.02
1203
1234
1268
1304
Alternate 2 HP & Drive
1.61 1259 1.73 1317
1.77 1290 1.90 1348
1.95 1324 2.07 1382
2.14 1361 2.27
-
1.87
2.03
2.21
-
Example RPM Selection
Size
(Tons)
Model
X
Y
Airflow
Option
Std.
H. Static
HP
1.5
2
Max
BHP
1.73
2.30
Motor
Sheave
1VM50
1VM50
Blower
Sheave
AK74
AK64
6 Turns
Open
N/A
N/A
5 Turns
Open
897
1039
4 Turns
Open
945
1094
3
6
0.00
0.00
0.01
0.01
0.01
0.00
0.00
0.01
0.01
0.01
3 Turns
Open
991
1150
2 Turns
Open
1035
1207
1 Turn
Open
1079
1256
Fully
Closed
1126
1308
Example Additional Static Resistance
Size
(Tons)
X
96
Model
Y
CFM Cooling Only
900
1000
1100
1200
1300
0.05
0.05
0.04
0.04
0.03
Economizer
4” Pleated Filter
-0.05
-0.03
-0.02
0.00
0.01
0.01
0.02
0.03
0.04
0.05
Electric Heat kW
9
15
0.00
0.00
0.01
0.01
0.01
0.01
0.02
0.02
0.02
0.03
20
24
0.01
0.02
0.02
0.02
0.03
0.01
0.02
0.02
0.02
0.03
Johnson Controls Unitary Products
5123247-TTG-A-0515
Altitude and Temperature Correction for CFM, Static
Pressure and Power.
use the indoor blower tables for high altitude applications,
certain corrections are necessary.
The information below should be used to assist in application of
product when being applied at altitudes at or exceeding 1000
feet above sea level.
A centrifugal fan is a "constant volume" device. This means
that, if the rpm remains constant, the CFM delivered is the
same regardless of the density of the air. However, since the air
at high altitude is less dense, less static pressure will be
generated and less power will be required than a similar
application at sea level. Air density correction factors are shown
in Table 14 and Figure 27.
The air flow rates listed in the standard blower performance
tables are based on standard air at sea level. As the altitude or
temperature increases, the density of air decreases. In order to
Altitude/Temperature Correction Factors
Air
Temp.
40
50
60
70
80
90
100
0
1.060
1.039
1.019
1.000
0.982
0.964
0.946
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817
Altitude (Ft.)
5000
0.882
0.864
0.848
0.832
0.817
0.802
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
1.100
1.050
Correction Factor
1.000
Sea Level
0.950
1000 ft
0.900
2000 ft
0.850
3000 ft
0.800
5000 ft
0.750
6000 ft
7000 ft
4000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650
0.600
40
50
60
70
80
90
100
Air Temperature (ºF)
The examples below will assist in determining the airflow
performance of the product at altitude.
blower tables to select the blower speed and the BHP
requirement.
Example 1: What are the corrected CFM, static pressure, and
BHP at an elevation of 5,000 ft. if the blower performance data
is 6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution: As in the example above, no temperature
information is given so 70°F is assumed.
Solution: At an elevation of 5,000 ft. the indoor blower will still
deliver 6,000 CFM if the rpm is unchanged. However, Table 13
must be used to determine the static pressure and BHP. Since
no temperature data is given, we will assume an air temperature
of 70°F. Table 15 shows the correction factor to be 0.832.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Corrected BHP = 4.0 x 0.832 = 3.328
Example 2: A system, located at 5,000 feet of elevation, is to
deliver 6,000 CFM at a static pressure of 1.5". Use the unit
Johnson Controls Unitary Products
The 1.5" static pressure given is at an elevation of 5,000 ft. The
first step is to convert this static pressure to equivalent sea level
conditions.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
BHP at 5,000 ft. = 3.2 x .832 = 2.66
97
5123247-TTG-A-0515
Indoor Blower Specifications
Motor
Airflow
Size
Model
Option
(Tons)
TA3
(3)
TA4
(4)
TA5
(5)
T06
(6.5)
T07
(7.5)
T08
(8.5)
T10
(10)
T12
(12.5)
TA3
(3)
TA4
(4)
TA5
(5)
T06
(6.5)
T07
(7.5)
T08
(8.5)
T10
(10)
T12
(12.5)
TA3
(3)
TA4
(4)
TA5
(5)
T06
(6.5)
T07
(7.5)
T08
(8.5)
T10
(10)
T12
(12.5)
ZU
ZU
ZU
ZU
ZU
ZU
ZU
ZU
ZW
ZW
ZW
ZW
ZW
ZW
ZW
ZW
ZK
ZK
ZK
ZK
ZK
ZK
ZK
ZK
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
HP
RPM
Eff.
SF
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
1-1/2
2
1-1/2
3
2
3
2
3
3
5
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
1-1/2
2
1-1/2
3
2
3
2
3
3
5
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
1-1/2
2
1-1/2
3
2
3
2
3
3
5
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.87
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.87
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.87
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
Motor Sheave
Datum Dia.
Bore (in.)
Frame
(in.)
56
2.0 - 3.0
7/8
56
3.0 - 4.0
7/8
56
2.0 - 3.0
7/8
56
3.0 - 4.0
7/8
56
2.6 - 3.6
7/8
56
4.2 - 5.2
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
184T
4.3 - 5.3
1-1/8
56
2.0 - 3.0
7/8
56
3.0 - 4.0
7/8
56
2.0 - 3.0
7/8
56
3.0 - 4.0
7/8
56
2.6 - 3.6
7/8
56
4.2 - 5.2
7/8
56
2.6 - 3.6
7/8
56
3.6 - 4.6
7/8
56
2.6 - 3.6
7/8
56
3.6 - 4.6
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
184T
4.3 - 5.3
1-1/8
56
1.2 - 2.9
7/8
56
3.0 - 4.0
7/8
56
1.2 - 2.9
7/8
56
3.0 - 4.0
7/8
56
1.2 - 2.9
7/8
56
3.0 - 4.0
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
56
3.4 - 4.4
7/8
184T
4.3 - 5.3
1-1/8
Model
1VM34
1VL44
1VM34
1VL44
1VL40
1VP56
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
1VM34
1VL44
1VM34
1VL44
1VL40
1VP56
1VL40
1VM50
1VL40
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
1VP34
1VL44
1VP34
1VL44
1VP34
1VL44
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
Datum Dia.
Bore (in.)
(in.)
6.5
1
6.5
1
5.2
1
5.2
1
5.7
1
7.0
1
7.0
1
6.0
1
7.0
1
5.7
1
9.0
1
7.0
1
8.0
1
7.0
1
7.0
1
6.7
1
6.5
1
6.5
1
5.2
1
5.2
1
5.7
1
7.0
1
7.0
1
7.0
1
6.5
1
6.5
1
8.5
1
7.0
1
8.0
1
7.0
1
7.0
1
6.7
1
5.7
1
5.5
1
5.7
1
5.5
1
5.7
1
5.5
1
7.0
1
6.0
1
7.0
1
5.7
1
8.5
1
7.0
1
8.0
1
7.0
1
7.0
1
6.7
1
Model
AK69
AK69
AK56
AK56
AK61
AK74
AK74
AK64
AK74
AK61
AK94
AK74
AK84
AK74
AK74
BK77
AK69
AK69
AK56
AK56
AK61
AK74
AK74
AK74
AK69
AK69
AK89
AK74
AK84
AK74
AK74
BK77
AK61
AK59
AK61
AK59
AK61
AK59
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A47
A47
A47
A47
A47
A51
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
A47
A47
A47
A47
A47
A51
A53
A54
A52
A54
A56
A54
A56
A54
A54
BX55
A47
A47
A47
A47
A47
A47
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Power Exhaust Specifications
Model
Voltage
2PE04703225
2PE04703246
2PE04703258
208/230-1-60
460-1-60
575-1-60
HP
3/4
3/4
3/4
Motor
RPM1
1075
1075
1050
QTY
1
1
1
LRA
7.8
3.4
2.9
Motor
FLA
5
2.2
1.5
MCA
6.3
2.8
1.9
Fuse Size
10
5
4
CFM @
0.1 ESP
3800
3800
3800
1. Motors are multi-tapped and factory wired for high speed.
98
Johnson Controls Unitary Products
5123247-TTG-A-0515
RPM Selection
Size
(Tons)
TA3
(3)
Model
ZU
TA4
(4)
ZU
TA5
(5)
ZU
T06
(6.5)
ZU
T07
(7.5)
ZU
T08
(8.5)
ZU
T10
(10)
ZU
T12
(12.5)
ZU
TA3
(3)
ZW
TA4
(4)
ZW
TA5
(5)
ZW
T06
(6.5)
ZW
T07
(7.5)
ZW
T08
(8.5)
ZW
T10
(10)
ZW
T12
(12.5)
ZW
TA3
(3.0)
ZK
TA4
(4.0)
ZK
TA5
(5.0)
ZK
T06
(6.5)
ZK
T07
(7.5)
ZK
T08
(8.5)
ZK
T10
(10)
ZK
T12
(12.5)
ZK
Airflow
Option
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
1.5
1.5
1.5
1.5
1.5
2
1.5
2
1.5
3
2
3
2
3
3
5
1.5
1.5
1.5
1.5
1.5
2
1.5
2
1.5
3
2
3
2
3
3
5
1.5
Max
BHP
1.5
1.5
1.5
1.5
1.5
2
1.73
2.30
1.73
3.45
2.30
3.45
2.30
3.45
3.45
5.75
1.5
1.5
1.5
1.5
1.5
2
1.73
2.30
1.73
3.45
2.30
3.45
2.30
3.45
3.45
5.75
1.5
H. Static
1.5
1.5
1VL44
AK59
N/A
Std.
1.5
1.5
1VP34
AK61
N/A
H. Static
1.5
1.5
1VL44
AK59
N/A
Std.
1.5
1.5
1VP34
AK61
N/A
HP
Motor
Sheave
1VM34
1VL44
1VM34
1VL44
1VL40
1VP56
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
1VM34
1VL44
1VM34
1VL44
1VL40
1VP56
1VL40
1VM50
1VL40
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
1VP34
Blower
Sheave
AK69
AK69
AK56
AK56
AK61
AK74
AK74
AK64
AK74
AK61
AK94
AK74
AK84
AK74
AK74
BK77
AK69
AK69
AK56
AK56
AK61
AK74
AK74
AK74
AK69
AK69
AK89
AK74
AK84
AK74
AK74
BK77
AK61
6 Turns
Open
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1052
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1052
N/A
5 Turns
Open
531
796
663
995
787
1035
887
1039
887
1088
690
887
776
887
887
1095
531
796
663
995
787
1035
641
887
690
955
731
887
776
887
887
1095
575
4 Turns
Open
584
849
730
1062
847
1084
936
1094
936
1147
728
936
819
936
936
1136
584
849
730
1062
847
1084
690
936
743
1008
771
936
819
936
936
1136
636
3 Turns
Open
637
902
796
1128
908
1134
986
1150
986
1205
767
986
863
986
986
1175
637
902
796
1128
908
1134
739
986
796
1062
812
986
863
986
986
1175
696
2 Turns
Open
690
955
863
1194
968
1183
1035
1207
1035
1265
805
1035
906
1035
1035
1216
690
955
863
1194
968
1183
789
1035
849
1115
852
1035
906
1035
1035
1216
757
1 Turn
Open
743
1008
929
1261
1029
1232
1084
1256
1084
1312
843
1084
949
1084
1084
1272
743
1008
929
1261
1029
1232
838
1084
902
1168
893
1084
949
1084
1084
1272
817
Fully
Closed
796
1062
995
1327
1089
1281
1134
1308
1134
1365
882
1134
992
1134
1134
N/A
796
1062
995
1327
1089
1281
887
1134
955
1221
934
1134
992
1134
1134
N/A
878
878
941
1004
1066
1129
1192
575
636
696
757
817
878
878
941
1004
1066
1129
1192
575
636
696
757
817
878
H. Static
2
2
1VL44
AK59
N/A
878
941
1004
1066
1129
1192
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
Std.
H. Static
1.5
2
1.5
3
2
3
2
3
3
5
1.73
2.30
1.73
3.45
2.30
3.45
2.30
3.45
3.45
5.75
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1052
897
1039
897
1088
735
880
785
880
880
1095
945
1094
945
1147
775
928
821
928
928
1136
991
1150
991
1205
815
972
858
972
972
1175
1035
1207
1035
1265
851
1016
901
1016
1016
1216
1079
1256
1079
1312
889
1067
940
1067
1067
1272
1126
1308
1126
1365
930
1110
980
1110
1110
N/A
Johnson Controls Unitary Products
99
5123247-TTG-A-0515
Additional Static Resistance - ZUTA3 thru TA5
Size
(Tons)
Model
TA3 (3)
TA4 (4)
ZU
TA5 (5)
ZU
CFM Cooling Only1 Economizer2 3 4” Pleated Filter2
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
0.05
0.05
0.04
0.04
0.03
0.03
0.03
0.02
0.02
0.01
0.01
0.00
-0.01
-0.01
-0.01
-0.02
-0.02
-0.02
-0.03
-0.03
-0.04
-0.04
-0.05
-0.05
-0.03
-0.02
0.00
0.01
0.03
0.04
0.06
0.07
0.08
0.10
0.11
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23
0.01
0.02
0.03
0.04
0.05
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.07
0.08
0.08
0.09
0.10
0.10
0.11
0.12
0.12
0.13
0.14
3
6
0.00
0.00
0.01
0.01
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.06
0.07
0.08
0.00
0.00
0.01
0.01
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.06
0.07
0.08
Electric Heat kW2
9
15
0.00
0.00
0.01
0.01
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.06
0.07
0.08
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.07
0.04
0.04
0.05
0.05
0.06
0.07
0.07
0.08
0.09
0.10
0.11
20
24
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.07
0.04
0.04
0.05
0.05
0.06
0.07
0.07
0.08
0.09
0.10
0.11
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.07
0.04
0.04
0.05
0.05
0.06
0.07
0.07
0.08
0.09
0.10
0.11
1. Add these values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Additional Static Resistance - ZW/ZKTA3 thru TA5
Size
(Tons)
Model
TA3 (3)
ZW/ZK
TA4 (4)
TA5 (5)
ZW/ZK
CFM Cooling Only1 Economizer2 3 4” Pleated Filter2
900
1000
1100
1200
1300
1400
1500
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
0.05
0.05
0.04
0.04
0.03
0.03
0.03
-0.01
-0.01
-0.01
-0.01
-0.01
-0.01
-0.02
-0.02
-0.02
-0.03
-0.03
-0.04
-0.04
-0.05
-0.05
-0.03
-0.02
0.00
0.01
0.03
0.04
0.10
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23
0.01
0.02
0.03
0.04
0.05
0.07
0.08
0.05
0.06
0.06
0.07
0.08
0.08
0.09
0.10
0.10
0.11
0.12
0.12
0.13
0.14
3
6
0.00
0.00
0.01
0.01
0.01
0.02
0.02
0.01
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.06
0.07
0.08
0.00
0.00
0.01
0.01
0.01
0.02
0.02
0.01
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.06
0.07
0.08
Electric Heat kW2
9
15
0.00
0.00
0.01
0.01
0.01
0.02
0.02
0.01
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.06
0.07
0.08
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.07
0.07
0.08
0.09
0.10
0.11
20
24
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.07
0.07
0.08
0.09
0.10
0.11
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.07
0.07
0.08
0.09
0.10
0.11
1. Add these values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
100
Johnson Controls Unitary Products
5123247-TTG-A-0515
Additional Static Resistance - ZU/ZKT06 thru T12
Size
(Tons)
T06 (6.5)
T07 (7.5)
T08 (8.5)
T10 (10)
T12 (12.5)
Model
CFM
Cooling Only1
Economizer2 3
4” Filter2
ZU/ZK
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
0.00
-0.01
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
-0.09
-0.09
-0.10
-0.11
0.07
0.09
0.11
0.13
0.16
0.18
0.20
0.22
0.24
0.27
0.29
0.31
0.30
0.35
1900
0.06
2100
0.07
2300
0.08
2500
0.09
2700
0.11
2900
0.12
3100
0.14
3300
0.16
3500
0.18
3700
0.20
3900
0.23
4100
0.25
4300
0.28
4500
0.30
4700
0.33
4900
0.36
5100
0.39
5300
0.42
5500
0.45
5700
0.48
5900
0.52
6100
0.56
6300
0.60
0.02
0.02
0.04
0.11
0.18
0.25
0.31
0.37
0.43
0.49
0.54
0.58
0.65
0.69
0.74
0.78
0.82
0.86
0.89
0.93
0.96
0.98
1.01
ZU/ZK
Electric Heat kW2
24
36
09
18
0.10
0.11
0.12
0.14
0.15
0.16
0.18
0.19
0.20
0.21
0.23
0.24
0.25
0.26
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
54
0.12
0.05
0.06
0.07
0.08
0.10
0.13
0.06
0.07
0.08
0.09
0.11
0.14
0.07
0.08
0.09
0.10
0.13
0.16
0.08
0.09
0.10
0.11
0.14
0.17
0.09
0.10
0.12
0.13
0.16
0.19
0.10
0.11
0.13
0.14
0.18
0.20
0.12
0.13
0.15
0.16
0.20
0.22
0.13
0.14
0.17
0.18
0.22
0.25
0.15
0.16
0.19
0.20
0.24
0.27
0.17
0.18
0.21
0.22
0.26
0.29
0.19
0.20
0.23
0.24
0.28
0.32
0.21
0.22
0.25
0.26
0.31
0.35
0.23
0.24
0.28
0.29
0.34
0.38
0.25
0.26
0.30
0.31
0.37
0.41
0.28
0.29
0.33
0.34
0.40
0.44
0.30
0.31
0.35
0.37
0.43
0.47
0.33
0.34
0.38
0.40
0.46
0.51
0.35
0.37
0.41
0.43
0.49
0.56
0.38
0.40
0.44
0.46
0.53
0.58
0.41
0.43
0.47
0.49
0.56
0.62
0.44
0.46
0.50
0.53
0.59
0.67
0.47
0.49
0.53
0.56
0.62
0.71
0.50
0.53
0.56
0.59
0.65
1. Add these values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Johnson Controls Unitary Products
101
5123247-TTG-A-0515
Additional Static Resistance - ZWT06 thru T12
Size
(Tons)
T06 (6.5)
T07 (7.5)
T08 (8.5)
T10 (10)
T12 (12.5)
Model
CFM
Cooling Only1
Economizer2,3
4” Filter2
ZW
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
0.06
0.07
0.08
0.09
0.11
0.12
0.14
0.16
0.18
0.20
0.23
0.25
0.28
0.30
0.33
0.36
0.39
0.42
0.45
0.48
0.52
0.56
0.60
0.02
0.02
0.04
0.11
0.18
0.25
0.31
0.37
0.43
0.49
0.54
0.58
0.65
0.69
0.74
0.78
0.82
0.86
0.89
0.93
0.96
0.98
1.01
0.12
0.13
0.14
0.16
0.17
0.19
0.20
0.22
0.26
0.27
0.29
0.32
0.35
0.38
0.41
0.44
0.47
0.51
0.55
0.58
0.62
0.67
0.71
Electric Heat kW2
24
36
9
18
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.53
0.56
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
54
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.62
0.65
1. Add these values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is
less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
102
Johnson Controls Unitary Products
5123247-TTG-A-0515
Gas Heat Minimum Supply Air
Size
(Tons)
Model
TA3
(3)
ZU/ZW/ZK
TA4
(4)
ZU/ZW/ZK
TA5
(5)
ZU/ZW/ZK
T06
(6.5)
T07
(7.5)
T08
(8.5)
T10
(10)
T12
(12.5)
ZU/ZW/ZK
ZU/ZW/ZK
ZU/ZW/ZK
ZU/ZW/ZK
ZU/ZW/ZK
Supply Air (CFM)
Heating
Min
Max
890
2220
915
2370
1130
1800
890
2220
915
2370
1290
2250
915
2370
1380
2570
1580
2630
1950
3250
1950
3250
2250
3750
2250
3750
2550
4250
2550
4250
3000
5000
3000
5000
3750
6250
3750
6250
Heat Size
(A,B)06 / (N,S)06
(A,B)08 / (N,S)08
(A,B)11 / (N,S)11
(A,B)06 / (N,S)06
(A,B)08 / (N,S)08
(A,B)11 / (N,S)11
(A,B)08 / (N,S)08
(A,B)11 / (N,S)11
(A,B)16 / (N,S)16
(N,S)12
(N,S)18
(N,S)12
(N,S)18
(N,S)12
(N,S)18
(N,S)18
(N,S)24
(N,S)18
(N,S)24
Electric Heat Minimum Supply Air
3 thru 5 Tons
Size
(Tons)
Model
TA3
(3)
ZU/ZW/ZK
TA4
(4)
ZU/ZW/ZK
TA5
(5)
ZU/ZW/ZK
Voltage
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
Minimum Supply Air (CFM)
Heater kW
9
15
1020
1020
960
960
960
960
1420
1420
1400
1400
1400
1400
1600
1600
1600
1600
1600
1600
3
960
980
-
6
960
960
1280
1400
1600
1600
-
9
1950
1950
1950
2250
2250
2250
2550
2550
2550
-
Minimum Supply Air (CFM)
Heater kW
18
24
36
1950
1950
1950
1950
1950
1950
1950
1950
1950
2250
2250
2250
2250
2250
2250
2250
2250
2250
2550
2550
2550
2550
2550
2550
2550
2550
2550
3000
3000
3000
3000
3000
3000
3000
3000
3000
3750
3750
3750
3750
3750
3750
3750
3750
3750
20
1420
1400
1400
1600
1600
1600
24
1600
1600
1600
6-1/2 thru 12-1/5 Tons
Size
(Tons)
Model
T06
(6.5)
ZU/ZW/ZK
T07
(7.5)
ZU/ZW/ZK
T08
(8.5)
ZU/ZW/ZK
T10
(10)
ZU/ZW/ZK
T12
(12.5)
ZU/ZW/ZK
Johnson Controls Unitary Products
Voltage
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
54
3500
3000
3500
4000
3750
3750
103
5123247-TTG-A-0515
Airflow Performance
ZUTA3 thru T12 Side Duct Application
ZUTA3 (3.0 Ton) Side Duct
Air Flow
(CFM)
900
1000
1100
1200
1300
1400
1500
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
560
582
601
620
638
655
673
0.29
0.29
0.30
0.32
0.35
0.39
0.43
Standard 1.5 HP & Drive
628
0.35
695
0.42
650
0.34
716
0.42
670
0.35
736
0.43
688
0.37
754
0.45
706
0.40
772
0.48
724
0.44
790
0.51
741
0.48
807
0.56
760
781
801
819
837
855
872
0.51
0.51
0.52
0.54
0.57
0.60
0.65
823
845
864
883
901
918
936
0.61
0.61
0.62
0.64
0.67
0.70
0.75
Hi Static 1.5 HP & Drive
886
0.72
949
0.82
908
0.71
970
0.82
927
0.72
990
0.83
946
0.74 1008 0.85
964
0.77 1026 0.88
981
0.81 1044 0.91
999
0.85 1061 0.96
1011
1032
1052
1070
1088
1106
1124
0.92 1073 1.01 1136
0.92 1095 1.01 1158
0.93 1114 1.02 1177
0.95 1133 1.04 1196
0.98 1151 1.06 1214
1.01 1168 1.10 1231
1.06 1186 1.15 1249
1.5 HP & Field Supplied Drive
1.09
1.08
1.09
1.11
1.14
1.18
1.22
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZUTA4 (4.0 Ton) Side Duct
Air Flow
(CFM)
1200
1300
1400
1500
1600
1700
1800
1900
2000
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS4
620
0.32
638
0.35
655
0.39
673
0.43
691
0.48
709
0.54
728
0.60
747
0.67
766
0.75
688
706
724
741
759
777
796
815
834
0.37
0.40
0.44
0.48
0.54
0.59
0.66
0.73
0.80
754
772
790
807
825
843
862
881
901
Standard 1.5 HP & Drive
0.45
819
0.54
883
0.48
837
0.57
901
0.51
855
0.60
918
0.56
872
0.65
936
0.61
890
0.70
954
0.67
908
0.76
972
0.73
927
0.82
991
0.80
946
0.89 1010
0.87
966
0.96 1029
0.64
0.67
0.70
0.75
0.80
0.86
0.92
0.99
1.06
946
964
981
999
1017
1035
1053
1073
1092
0.74
0.77
0.81
0.85
0.90
0.96
1.03
1.09
1.17
1008
1026
1044
1061
1079
1097
1116
1135
1155
0.85
0.88
0.91
0.96
1.01
1.07
1.13
1.20
1.27
Hi Static 1.5 HP & Drive
1070 0.95 1133 1.04
1088 0.98 1151 1.06
1106 1.01 1168 1.10
1124 1.06 1186 1.15
1141 1.11 1204 1.20
1160 1.17 1222 1.26
1178 1.23 1241 1.32
1197 1.30 1260 1.39
1217 1.37 1279 1.46
1196
1214
1231
1249
1267
1285
1303
1323
-
1.11
1.14
1.18
1.22
1.27
1.33
1.39
1.46
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZUTA5 (5.0 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field Supplied Drive
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
1.
2.
3.
4.
104
659
675
691
707
724
741
759
778
797
817
838
0.35
0.38
0.42
0.47
0.53
0.59
0.65
0.73
0.81
0.90
1.00
719
735
751
767
784
801
819
838
857
877
898
0.46
0.50
0.54
0.58
0.64
0.70
0.77
0.84
0.92
1.01
1.11
780
796
812
829
846
863
881
900
919
939
960
Hi Static 2 HP & Drive
Standard 1.5 HP & Drive
0.57
0.60
0.64
0.69
0.75
0.81
0.87
0.95
1.03
1.12
1.22
843
859
875
891
908
925
943
962
981
1002
1022
0.67
0.71
0.75
0.79
0.85
0.91
0.98
1.05
1.13
1.22
1.32
905
920
936
953
970
987
1005
1024
1043
1063
1084
0.77
0.81
0.85
0.90
0.95
1.01
1.08
1.15
1.23
1.32
1.42
964
980
996
1012
1029
1047
1065
1083
1103
1123
1144
0.87
0.91
0.95
0.99
1.05
1.11
1.18
1.25
1.33
1.42
1.52
1020
1036
1052
1069
1085
1103
1121
1139
1159
1179
1200
0.97
1.01
1.05
1.09
1.15
1.21
1.28
1.35
1.43
1.52
1.62
1071
1087
1103
1120
1137
1154
1172
1191
1210
1230
1251
1.07
1.11
1.15
1.20
1.25
1.31
1.38
1.45
1.53
1.62
1.72
1116
1132
1148
1165
1182
1199
1217
1236
1255
1275
1296
1.17 1154
1.21 1170
1.25 1186
1.30 1202
1.35 1219
1.41 1236
1.48 1254
1.56 1273
1.64 1292
1.73 1312
1.82 1333
FS4
1.28
1.32
1.36
1.41
1.46
1.52
1.59
1.66
1.74
1.83
1.93
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUT06 (6.5 Ton) Side Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
751
776
804
835
869
906
945
987
1030
Field Supplied Drive
0.22
813
0.43
872
0.35
838
0.56
897
0.50
866
0.71
925
0.66
897
0.87
956
0.84
931
1.05
990
1.03
968
1.25 1027
1.25 1007 1.46 1066
1.48 1048 1.69 1107
1.73 1092 1.94 1151
0.62
0.75
0.90
1.06
1.24
1.43
1.65
1.88
2.12
929
954
982
1013
1047
1084
1123
1165
1208
0.78
0.92
1.06
1.22
1.40
1.60
1.81
2.04
2.29
Standard 1.5 HP & Drive
985
0.93 1040 1.07
1010 1.07 1064 1.20
1038 1.21 1092 1.35
1069 1.37 1124 1.51
1103 1.55 1158 1.69
1139 1.75 1194 1.89
1179 1.96 1234 2.10
1220 2.19
-
1095
1119
1147
1178
1212
1249
1288
-
1.20
1.33
1.48
1.64
1.82
2.02
2.23
-
1150
1175
1203
1234
1268
1304
-
Hi Static 2 HP & Drive
1.33 1206 1.46 1265
1.46 1231 1.59 1289
1.61 1259 1.73 1317
1.77 1290 1.90 1348
1.95 1324 2.07 1382
2.14 1361 2.27
2 HP & Field Supplied Drive
1.59
1.72
1.87
2.03
2.21
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZUT07 (7.5 Ton) Side Duct
Air Flow
(CFM)
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
776
0.35
838
0.56
804
0.50
866
0.71
835
0.66
897
0.87
869
0.84
931
1.05
906
1.03
968
1.25
945
1.25 1007 1.46
987
1.48 1048 1.69
1030 1.73 1092 1.94
1076 1.99 1138 2.20
1124 2.27 1185 2.48
897
925
956
990
1027
1066
1107
1151
1197
1245
0.75
0.90
1.06
1.24
1.43
1.65
1.88
2.12
2.39
2.67
954
982
1013
1047
1084
1123
1165
1208
1254
1302
Standard 1.5 HP & Drive
0.92 1010 1.07 1064
1.06 1038 1.21 1092
1.22 1069 1.37 1124
1.40 1103 1.55 1158
1.60 1139 1.75 1194
1.81 1179 1.96 1234
2.04 1220 2.19 1275
2.29 1264 2.44 1319
2.56 1310 2.71 1364
2.84 1357 2.99 1412
1.20
1.35
1.51
1.69
1.89
2.10
2.33
2.58
2.84
3.12
1119
1147
1178
1212
1249
1288
1330
1374
1419
1467
Hi Static 3 HP & Drive
1.33 1175 1.46 1231 1.59 1289
1.48 1203 1.61 1259 1.73 1317
1.64 1234 1.77 1290 1.90 1348
1.82 1268 1.95 1324 2.07 1382
2.02 1304 2.14 1361 2.27 1419
2.23 1344 2.36 1400 2.48 1458
2.46 1385 2.59 1442 2.71 1500
2.71 1429 2.84 1485 2.96 1544
2.97 1475 3.10 1531 3.23 1589
3.25 1522 3.38
3 HP & Field Supplied Drive
1.72
1.87
2.03
2.21
2.40
2.62
2.85
3.10
3.36
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZUT08 (8.5 Ton) Side Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
628
0.56
678
0.76
648
0.67
698
0.87
666
0.80
717
1.00
684
0.95
735
1.15
702
1.11
753
1.31
721
1.28
772
1.48
742
1.47
793
1.67
765
1.67
815
1.86
789
1.87
840
2.07
730
750
768
786
804
824
844
867
891
Standard 2 HP & Drive
0.93
781
1.09
833
1.04
801
1.20
853
1.17
820
1.33
871
1.32
838
1.48
889
1.48
856
1.64
907
1.65
875
1.81
927
1.84
896
2.00
947
2.04
918
2.19
970
2.24
943
2.40
995
1.25
1.36
1.49
1.63
1.79
1.97
2.15
2.35
2.56
883
903
922
940
958
977
998
1020
1045
1.41
1.52
1.65
1.80
1.96
2.13
2.32
2.51
2.72
933
953
971
989
1007
1027
1047
1070
1094
Hi Static 3 HP & Drive
1.59
980
1.80 1025 2.05 1068
1.70 1000 1.91 1046 2.16 1088
1.83 1019 2.04 1064 2.29 1106
1.98 1037 2.19 1082 2.44 1124
2.14 1055 2.35 1100 2.60 1142
2.31 1074 2.52 1119 2.77
2.50 1095 2.71 1140 2.96
2.70 1117 2.91
2.90
3 HP & Field Supplied Drive
2.35
2.46
2.59
2.74
2.90
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Johnson Controls Unitary Products
105
5123247-TTG-A-0515
ZUT10 (10 Ton) Side Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
675
0.53
726
0.74
686
0.63
738
0.84
699
0.75
750
0.96
713
0.88
764
1.09
728
1.02
779
1.23
745
1.18
796
1.39
763
1.36
815
1.57
783
1.55
835
1.76
805
1.77
856
1.98
828
2.00
879
2.21
852
2.25
904
2.46
879
2.52
930
2.73
906
2.81
958
3.02
776
787
800
814
829
846
864
884
906
929
953
980
1007
0.94
1.04
1.16
1.28
1.43
1.59
1.76
1.96
2.17
2.41
2.66
2.93
3.22
824
835
847
861
877
893
912
932
953
976
1001
1027
1055
Standard 2 HP & Drive
1.12
870
1.30
914
1.23
881
1.41
925
1.34
893
1.52
938
1.47
907
1.65
952
1.61
923
1.79
967
1.77
939
1.95
984
1.95
958
2.13 1002
2.15
978
2.33 1022
2.36
999
2.54 1044
2.59 1022 2.77 1067
2.85 1047 3.03 1092
3.12 1073 3.30
3.41
-
1.48
1.58
1.70
1.83
1.97
2.13
2.31
2.50
2.72
2.95
3.20
-
957
969
981
995
1010
1027
1046
1066
1087
1110
1135
-
Hi Static 3 HP & Drive
1.65 1000 1.82 1041 1.99 1082
1.76 1011 1.93 1052 2.10 1093
1.87 1024 2.04 1065 2.21 1106
2.00 1037 2.17 1079 2.34 1119
2.14 1053 2.31 1094 2.48 1135
2.30 1069 2.47 1111 2.64 1152
2.48 1088 2.65 1129 2.82 1170
2.67 1108 2.84 1149 3.02 1190
2.89 1129 3.06 1171 3.23 1211
3.12 1152 3.29
3.37
3 HP & Field Supplied Drive
2.17
2.27
2.39
2.52
2.66
2.82
3.00
3.19
3.41
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZUT12 (12.5 Ton) Side Duct
Air Flow
(CFM)
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
6000
6200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
713
728
745
763
783
805
828
852
879
906
936
966
999
1032
1067
1103
0.88
1.02
1.18
1.36
1.55
1.77
2.00
2.25
2.52
2.81
3.12
3.45
3.80
4.16
4.54
4.94
Field Supplied Drive
764
1.09
814
1.28
779
1.23
829
1.43
796
1.39
846
1.59
815
1.57
864
1.76
835
1.76
884
1.96
856
1.98
906
2.17
879
2.21
929
2.41
904
2.46
953
2.66
930
2.73
980
2.93
958
3.02 1007 3.22
987
3.33 1037 3.53
1018 3.66 1067 3.86
1050 4.01 1100 4.20
1084 4.37 1133 4.57
1119 4.75 1168 4.95
1155 5.15 1204 5.34
Hi Static 5 HP & Drive
861
877
893
912
932
953
976
1001
1027
1055
1084
1115
1147
1181
1216
1252
1.47
1.61
1.77
1.95
2.15
2.36
2.59
2.85
3.12
3.41
3.72
4.05
4.39
4.75
5.13
5.53
907
923
939
958
978
999
1022
1047
1073
1101
1130
1161
1193
1227
1262
1298
1.65
1.79
1.95
2.13
2.33
2.54
2.77
3.03
3.30
3.59
3.90
4.23
4.57
4.93
5.31
5.71
952
967
984
1002
1022
1044
1067
1092
1118
1146
1175
1206
1238
1271
1306
-
1.83
1.97
2.13
2.31
2.50
2.72
2.95
3.20
3.47
3.76
4.07
4.40
4.75
5.11
5.49
-
Standard 3 HP & Drive
995
2.00 1037 2.17
1010 2.14 1053 2.31
1027 2.30 1069 2.47
1046 2.48 1088 2.65
1066 2.67 1108 2.84
1087 2.89 1129 3.06
1110 3.12 1152 3.29
1135 3.37 1177 3.54
1161 3.65 1203 3.82
1189 3.94 1231 4.11
1218 4.24 1260 4.42
1249 4.57 1291 4.74
1281 4.92 1323 5.09
1315 5.28 1357 5.45
1350 5.66
5 HP & Field Supplied Drive
1079
1094
1111
1129
1149
1171
1194
1219
1245
1273
1302
1333
1365
1398
-
2.34
2.48
2.64
2.82
3.02
3.23
3.46
3.72
3.99
4.28
4.59
4.91
5.26
5.62
-
1119
1135
1152
1170
1190
1211
1235
1259
1285
1313
1343
1373
1405
-
2.52
2.66
2.82
3.00
3.19
3.41
3.64
3.89
4.16
4.45
4.76
5.09
5.44
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
106
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUTA3 thru T12 Bottom Duct Application
ZUTA3 (3.0 Ton) Bottom Duct
Air Flow
(CFM)
900
1000
1100
1200
1300
1400
1500
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
605
621
637
651
666
681
697
Standard 1.5 HP & Drive
0.23
671
0.33
738
0.25
688
0.34
754
0.27
703
0.36
769
0.30
717
0.39
784
0.33
732
0.43
799
0.37
747
0.47
814
0.42
763
0.51
830
0.42
0.44
0.46
0.49
0.52
0.56
0.61
804
820
835
850
865
880
896
0.52
0.53
0.56
0.58
0.62
0.66
0.71
869
885
900
915
930
945
961
Hi Static 1.5 HP & Drive
0.62
933
0.71
995
0.63
949
0.72 1011
0.65
964
0.74 1026
0.68
979
0.77 1041
0.71
994
0.81 1056
0.75 1009 0.85 1071
0.80 1025 0.90 1087
0.80
0.82
0.84
0.87
0.90
0.94
0.99
1054 0.89 1111 0.98
1071 0.91 1127 1.00
1086 0.93 1142 1.02
1100 0.96 1157 1.05
1115 0.99 1172 1.08
1130 1.03 1187 1.12
1146 1.08 1203 1.17
1.5 HP & Field Supplied Drive
1164
1180
1195
1210
1225
1240
1256
1.07
1.09
1.11
1.13
1.17
1.21
1.26
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZUTA4 (4.0 Ton) Bottom Duct
Air Flow
(CFM)
1200
1300
1400
1500
1600
1700
1800
1900
2000
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS4
651
0.30
666
0.33
681
0.37
697
0.42
714
0.47
732
0.53
751
0.60
771
0.68
793
0.75
717
732
747
763
780
798
817
837
859
0.39
0.43
0.47
0.51
0.57
0.63
0.70
0.77
0.85
784
799
814
830
846
864
883
904
925
Standard 1.5 HP & Drive
0.49
850
0.58
915
0.52
865
0.62
930
0.56
880
0.66
945
0.61
896
0.71
961
0.66
913
0.76
978
0.73
930
0.82
996
0.79
950
0.89 1015
0.87
970
0.96 1035
0.95
991
1.04 1056
0.68
0.71
0.75
0.80
0.86
0.92
0.98
1.06
1.14
979
994
1009
1025
1042
1059
1079
1099
1120
0.77
0.81
0.85
0.90
0.95
1.01
1.08
1.15
1.23
1041
1056
1071
1087
1103
1121
1140
1161
1182
0.87
0.90
0.94
0.99
1.04
1.10
1.17
1.25
1.32
Hi Static 1.5 HP & Drive
1100 0.96 1157 1.05
1115 0.99 1172 1.08
1130 1.03 1187 1.12
1146 1.08 1203 1.17
1163 1.14 1220 1.22
1181 1.20 1237 1.29
1200 1.26 1257 1.35
1220 1.34 1277 1.43
1242 1.42 1298 1.51
1210
1225
1240
1256
1273
1291
1310
-
1.13
1.17
1.21
1.26
1.31
1.37
1.44
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZUTA5 (5.0 Ton) Bottom Duct
Air Flow
(CFM)
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field Supplied Drive
673
0.47
736
0.54
797
693
0.49
756
0.57
817
713
0.53
777
0.60
837
734
0.57
797
0.65
858
755
0.62
819
0.70
879
776
0.69
840
0.76
900
798
0.76
861
0.84
921
819
0.84
882
0.92
943
840
0.93
903
1.01
964
861
1.03
925
1.11
985
882
1.14
946
1.22 1006
0.63
0.65
0.69
0.73
0.79
0.85
0.92
1.00
1.10
1.20
1.30
855
874
895
916
937
958
979
1001
1022
1043
1064
Standard 1.5 HP & Drive
0.72
910
0.82
964
0.75
930
0.85
984
0.78
951
0.88 1004
0.83
971
0.92 1025
0.88
992
0.98 1046
0.94 1014 1.04 1067
1.02 1035 1.11 1089
1.10 1056 1.20 1110
1.19 1077 1.29 1131
1.29 1099 1.39 1152
1.40 1120 1.50 1173
0.92
0.95
0.98
1.03
1.08
1.14
1.22
1.30
1.39
1.49
1.60
1016
1036
1057
1077
1098
1120
1141
1162
1183
1204
1226
1.03
1.06
1.09
1.14
1.19
1.25
1.32
1.41
1.50
1.60
1.71
1067
1087
1107
1128
1149
1171
1192
1213
1234
1255
1276
Hi Static 2 HP & Drive
1.14 1117 1.25 1166
1.17 1137 1.28 1186
1.20 1157 1.31 1207
1.25 1178 1.36 1228
1.30 1199 1.41 1249
1.36 1221 1.47 1270
1.44 1242 1.55 1291
1.52 1263 1.63 1312
1.61 1284 1.72 1334
1.71 1305 1.82 1355
1.82 1326 1.93 1376
3 HP & Field Supplied Drive
1.36
1.39
1.42
1.47
1.52
1.59
1.66
1.74
1.83
1.93
2.04
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Johnson Controls Unitary Products
107
5123247-TTG-A-0515
ZUT06 (6.5 Ton) Bottom Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
775
0.31
850
0.53
803
0.45
878
0.67
838
0.60
913
0.82
878
0.78
953
1.00
923
0.98
997
1.20
971
1.20 1046 1.42
1023 1.44 1097 1.66
1077 1.71 1151 1.93
1133 1.99 1208 2.21
924
952
986
1027
1071
1119
1171
1225
-
Standard 1.5 HP & Drive
0.72
998
0.89 1072
0.86 1026 1.03 1100
1.01 1060 1.19 1134
1.19 1100 1.36 1174
1.39 1145 1.56 1219
1.61 1193 1.78 1267
1.85 1245 2.03 1319
2.12 1299 2.29
-
1.05
1.19
1.34
1.52
1.72
1.94
2.18
-
1147
1175
1210
1250
1294
1343
-
Hi Static 2 HP & Drive
1.20 1224 1.35 1303 1.51
1.34 1252 1.49 1331 1.65
1.49 1286 1.65 1365 1.81
1.67 1327 1.82 1405 1.98
1.87 1371 2.02 1450 2.18
2.09 1419 2.24
2 HP & Field Supplied Drive
1384
1412
1447
1487
-
1.69
1.83
1.98
2.16
-
1469
1497
1532
-
1.89
2.03
2.18
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZUT07 (7.5 Ton) Bottom Duct
Air Flow
(CFM)
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
803
0.45
878
0.67
838
0.60
913
0.82
878
0.78
953
1.00
923
0.98
997
1.20
971
1.20 1046 1.42
1023 1.44 1097 1.66
1077 1.71 1151 1.93
1133 1.99 1208 2.21
1192 2.30 1267 2.52
1253 2.63 1327 2.85
952
986
1027
1071
1119
1171
1225
1282
1341
1401
Standard 1.5 HP & Drive
0.86 1026 1.03 1100
1.01 1060 1.19 1134
1.19 1100 1.36 1174
1.39 1145 1.56 1219
1.61 1193 1.78 1267
1.85 1245 2.03 1319
2.12 1299 2.29 1373
2.41 1356 2.58 1430
2.71 1414 2.88 1489
3.04 1475 3.21 1549
1.19
1.34
1.52
1.72
1.94
2.18
2.45
2.73
3.04
3.37
Hi Static 3 HP & Drive
1175 1.34 1252 1.49 1331
1210 1.49 1286 1.65 1365
1250 1.67 1327 1.82 1405
1294 1.87 1371 2.02 1450
1343 2.09 1419 2.24 1498
1394 2.33 1471 2.49 1550
1448 2.60 1525 2.75 1604
1505 2.88 1582 3.04 1661
1564 3.19 1641 3.34
3 HP & Field Supplied Drive
1.65
1.81
1.98
2.18
2.40
2.65
2.91
3.20
-
1412
1447
1487
1532
1580
1632
1686
1742
-
1.83
1.98
2.16
2.36
2.58
2.82
3.09
3.37
-
1497
1532
1572
1617
1665
1717
1771
-
2.03
2.18
2.36
2.56
2.78
3.02
3.29
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZUT08 (8.5 Ton) Bottom Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
1.
2.
3.
4.
108
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS4
674
0.71
689
0.86
707
1.01
728
1.17
751
1.34
776
1.53
804
1.74
835
1.97
867
2.21
731
746
764
785
808
833
861
892
924
Standard 2 HP & Drive
0.88
786
1.05
838
1.02
801
1.20
854
1.17
819
1.35
872
1.33
840
1.51
892
1.51
863
1.68
915
1.70
888
1.87
941
1.90
916
2.08
969
2.13
947
2.31
999
2.37
979
2.55 1032
1.24
1.38
1.53
1.69
1.87
2.06
2.26
2.49
2.73
887
903
921
941
964
990
1018
1048
1081
1.42
1.56
1.71
1.87
2.05
2.24
2.44
2.67
2.91
933
948
966
987
1010
1035
1063
1094
1127
1.59
1.73
1.88
2.04
2.22
2.41
2.61
2.84
3.08
Hi Static 3 HP & Drive
974
1.74 1010 1.87 1040 1.97
989
1.88 1025 2.01 1056 2.11
1007 2.03 1043 2.16 1074 2.26
1028 2.20 1064 2.33 1094 2.42
1051 2.37 1087 2.50 1117 2.60
1076 2.56 1112 2.69 1142 2.79
1104 2.77 1140 2.90 1170 2.99
1135 2.99
3 HP & Field Supplied Drive
1064
1080
1098
1118
1141
1167
-
2.03
2.17
2.32
2.48
2.66
2.85
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUT10 (10 Ton) Bottom Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied
Drive
722
0.83
744
0.97
769
1.13
797
1.32
828
1.52
861
1.75
897
2.00
935
2.27
976
2.57
1019 2.88
1065 3.22
Standard 2 HP & Drive
776
798
823
851
882
915
951
989
1030
1073
1119
0.97
1.12
1.28
1.46
1.67
1.90
2.15
2.42
2.72
3.03
3.36
828
850
875
903
934
967
1002
1041
1082
1125
-
1.11
1.26
1.42
1.60
1.81
2.04
2.29
2.56
2.86
3.17
-
878
900
925
953
983
1017
1052
1091
1132
1175
-
1.25
1.39
1.55
1.74
1.94
2.17
2.42
2.69
2.99
3.30
-
926
949
974
1001
1032
1065
1101
1139
1180
1223
-
Hi Static 3 HP & Drive
1.37
973
1.50 1018
1.52
995
1.64 1041
1.68 1020 1.80 1066
1.86 1048 1.99 1093
2.07 1078 2.19 1124
2.30 1112 2.42 1157
2.55 1147 2.67 1193
2.82 1186 2.95 1231
3.12 1227 3.24 1272
3.43
3 HP & Field Supplied Drive
1.62
1.76
1.92
2.11
2.32
2.54
2.80
3.07
3.36
-
1063
1085
1110
1138
1168
1201
1237
1275
-
1.74
1.88
2.05
2.23
2.44
2.67
2.92
3.19
-
1106
1128
1153
1181
1212
1245
1280
1319
-
1.86
2.00
2.17
2.35
2.56
2.79
3.04
3.31
-
1149
1171
1196
1224
1254
1287
1323
1362
-
1.99
2.13
2.29
2.48
2.68
2.91
3.16
3.43
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZUT12 (12.5 Ton) Bottom Duct
Air Flow
(CFM)
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
797
1.32
851
1.46
828
1.52
882
1.67
861
1.75
915
1.90
897
2.00
951
2.15
935
2.27
989
2.42
976
2.57 1030 2.72
1019 2.88 1073 3.03
1065 3.22 1119 3.36
1113 3.57 1167 3.72
1163 3.94 1217 4.09
1216 4.34 1270 4.48
1270 4.75 1324 4.89
1327 5.17 1381 5.32
1385 5.62
-
903
934
967
1002
1041
1082
1125
1171
1219
1269
1321
1376
1433
-
1.60
1.81
2.04
2.29
2.56
2.86
3.17
3.50
3.86
4.23
4.62
5.03
5.46
-
953
983
1017
1052
1091
1132
1175
1221
1269
1319
1371
1426
1483
-
Standard 3 HP & Drive
1.74 1001 1.86 1048 1.99
1.94 1032 2.07 1078 2.19
2.17 1065 2.30 1112 2.42
2.42 1101 2.55 1147 2.67
2.69 1139 2.82 1186 2.95
2.99 1180 3.12 1227 3.24
3.30 1223 3.43 1270 3.55
3.64 1269 3.76 1316 3.89
3.99 1317 4.12 1364 4.24
4.36 1367 4.49 1414 4.62
4.76 1420 4.88 1466 5.01
5.17 1474 5.29 1521 5.42
5.59 1531 5.72
5 HP & Field Supplied Drive
1093
1124
1157
1193
1231
1272
1315
1361
1409
1459
1512
1566
-
2.11
2.32
2.54
2.80
3.07
3.36
3.67
4.01
4.36
4.74
5.13
5.54
-
1138
1168
1201
1237
1275
1316
1360
1405
1453
1504
1556
1611
-
Hi Static 5 HP & Drive
2.23 1181 2.35 1224
2.44 1212 2.56 1254
2.67 1245 2.79 1287
2.92 1280 3.04 1323
3.19 1319 3.31 1362
3.48 1360 3.60 1402
3.80 1403 3.92 1446
4.13 1449 4.25 1491
4.48 1497 4.61 1540
4.86 1547 4.98 1590
5.25 1600 5.37 1642
5.66
-
2.48
2.68
2.91
3.16
3.43
3.73
4.04
4.38
4.73
5.10
5.50
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Johnson Controls Unitary Products
109
5123247-TTG-A-0515
ZWTA3 thru T12 Side Duct Application
ZWTA3 (3.0 Ton) Side Duct
Air Flow
(CFM)
900
1000
1100
1200
1300
1400
1500
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
560
582
601
620
638
655
673
0.29
0.29
0.30
0.32
0.35
0.39
0.43
Standard 1.5 HP & Drive
628
0.35
695
0.42
650
0.34
716
0.42
670
0.35
736
0.43
688
0.37
754
0.45
706
0.40
772
0.48
724
0.44
790
0.51
741
0.48
807
0.56
760
781
801
819
837
855
872
0.51
0.51
0.52
0.54
0.57
0.60
0.65
823
845
864
883
901
918
936
0.61
0.61
0.62
0.64
0.67
0.70
0.75
Hi Static 1.5 HP & Drive
886
0.72
949
0.82
908
0.71
970
0.82
927
0.72
990
0.83
946
0.74 1008 0.85
964
0.77 1026 0.88
981
0.81 1044 0.91
999
0.85 1061 0.96
1011
1032
1052
1070
1088
1106
1124
0.92 1073 1.01 1136
0.92 1095 1.01 1158
0.93 1114 1.02 1177
0.95 1133 1.04 1196
0.98 1151 1.06 1214
1.01 1168 1.10 1231
1.06 1186 1.15 1249
1.5 HP & Field Supplied Drive
1.09
1.08
1.09
1.11
1.14
1.18
1.22
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZWTA4 (4.0 Ton) Side Duct
Air Flow
(CFM)
1200
1300
1400
1500
1600
1700
1800
1900
2000
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS4
608
0.25
623
0.28
637
0.31
650
0.35
664
0.39
678
0.44
693
0.50
708
0.56
725
0.62
677
692
706
720
734
748
763
778
794
0.34
0.37
0.40
0.44
0.49
0.54
0.59
0.65
0.72
744
758
772
786
800
814
829
844
860
0.44
0.47
0.50
0.54
0.58
0.63
0.69
0.75
0.82
Standard 1.5 HP & Drive
807
0.54
868
0.64
822
0.57
883
0.67
836
0.60
897
0.70
849
0.64
911
0.74
863
0.68
924
0.78
877
0.73
938
0.83
892
0.79
953
0.89
907
0.85
968
0.95
924
0.92
985
1.02
927
942
956
970
984
998
1013
1028
1044
0.74
0.77
0.80
0.84
0.88
0.93
0.99
1.05
1.12
986
1001
1015
1028
1042
1056
1071
1086
1102
0.84
0.86
0.90
0.93
0.98
1.03
1.08
1.15
1.21
1043
1058
1072
1086
1100
1114
1129
1144
1160
Hi Static 1.5 HP & Drive
0.93 1101 1.02 1160
0.96 1116 1.04 1175
0.99 1130 1.08 1189
1.03 1144 1.12 1202
1.07 1158 1.16 1216
1.12 1172 1.21 1230
1.18 1186 1.26 1245
1.24 1202 1.33 1260
1.30 1218 1.39 1277
1.10
1.13
1.16
1.20
1.24
1.29
1.35
1.41
1.47
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive
ZWTA5 (5.0 Ton) Side Duct
Air Flow
(CFM)
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
1.
2.
3.
4.
110
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
659
675
691
707
724
741
759
778
797
817
838
1.5 HP & Field Suplied Drive
0.35
719
0.46
780
0.38
735
0.50
796
0.42
751
0.54
812
0.47
767
0.58
829
0.53
784
0.64
846
0.59
801
0.70
863
0.65
819
0.77
881
0.73
838
0.84
900
0.81
857
0.92
919
0.90
877
1.01
939
1.00
898
1.11
960
0.57
0.60
0.64
0.69
0.75
0.81
0.87
0.95
1.03
1.12
1.22
843
859
875
891
908
925
943
962
981
1002
1022
0.67
0.71
0.75
0.79
0.85
0.91
0.98
1.05
1.13
1.22
1.32
905
920
936
953
970
987
1005
1024
1043
1063
1084
Standard 1.5 HP & Drive
0.77
964
0.87 1020
0.81
980
0.91 1036
0.85
996
0.95 1052
0.90 1012 0.99 1069
0.95 1029 1.05 1085
1.01 1047 1.11 1103
1.08 1065 1.18 1121
1.15 1083 1.25 1139
1.23 1103 1.33 1159
1.32 1123 1.42 1179
1.42 1144 1.52 1200
0.97
1.01
1.05
1.09
1.15
1.21
1.28
1.35
1.43
1.52
1.62
1071
1087
1103
1120
1137
1154
1172
1191
1210
1230
1251
1.07
1.11
1.15
1.20
1.25
1.31
1.38
1.45
1.53
1.62
1.72
Hi Static 2 HP & Drive
1116 1.17 1154 1.28
1132 1.21 1170 1.32
1148 1.25 1186 1.36
1165 1.30 1202 1.41
1182 1.35 1219 1.46
1199 1.41 1236 1.52
1217 1.48 1254 1.59
1236 1.56 1273 1.66
1255 1.64 1292 1.74
1275 1.73 1312 1.83
1296 1.82 1333 1.93
FS4
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWT06 (6.5 Ton) Side Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
514
529
544
559
574
590
607
624
641
FS4
0.15
586
0.23
601
0.33
616
0.43
631
0.54
646
0.67
662
0.80
679
0.95
695
1.10
713
0.33
0.41
0.51
0.61
0.72
0.85
0.98
1.13
1.28
657
672
687
702
717
733
750
766
784
0.52
0.60
0.69
0.80
0.91
1.03
1.17
1.31
1.47
727
741
756
771
787
802
819
836
853
Standard 1.5 HP & Drive
0.71
794
0.89
857
0.79
808
0.97
872
0.88
823
1.07
886
0.98
838
1.17
902
1.10
853
1.28
917
1.22
869
1.41
933
1.36
886
1.54
949
1.50
903
1.69
966
1.66
920
1.84
984
1.07
1.15
1.24
1.35
1.46
1.59
1.72
1.86
2.02
917
931
946
961
977
993
1009
1026
1043
1.23
1.31
1.41
1.51
1.62
1.75
1.88
2.03
2.18
972
986
1001
1016
1032
1047
1064
1081
1098
Hi Static 2 HP & Drive
1.38 1021 1.50 1064
1.46 1036 1.58 1079
1.55 1051 1.67 1094
1.65 1066 1.78 1109
1.77 1081 1.89 1124
1.89 1097 2.02 1140
2.03 1113 2.15 1157
2.17 1130 2.29
2.33
FS4
1.59
1.67
1.77
1.87
1.98
2.11
2.24
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZWT07 (7.5 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS4
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
1.
2.
3.
4.
619
631
642
652
663
675
688
703
718
0.07
0.16
0.27
0.39
0.53
0.68
0.84
1.03
1.23
656
670
682
692
703
714
726
739
753
769
0.24
0.32
0.41
0.52
0.64
0.77
0.92
1.09
1.28
1.47
711
724
736
747
757
768
780
793
807
823
0.48
0.57
0.66
0.76
0.88
1.02
1.17
1.34
1.52
1.72
768
781
793
804
814
825
837
850
864
880
Standard 1.5 HP & Drive
0.73
826
0.96
886
0.81
840
1.04
899
0.90
852
1.14
911
1.01
862
1.24
922
1.13
873
1.36
932
1.26
884
1.50
943
1.41
896
1.65
955
1.58
909
1.82
968
1.76
923
2.00
983
1.96
939
2.20
998
1.19
1.27
1.36
1.47
1.59
1.73
1.88
2.04
2.23
2.43
945
959
970
981
992
1003
1014
1027
1042
1058
1.41
1.49
1.58
1.69
1.81
1.94
2.09
2.26
2.44
2.64
1003
1016
1028
1039
1049
1060
1072
1085
1100
1115
Hi Static 3 HP & Drive
1.61 1058 1.79 1110
1.69 1072 1.87 1124
1.78 1084 1.97 1136
1.89 1094 2.07 1146
2.01 1105 2.19 1157
2.14 1116 2.33 1168
2.29 1128 2.48 1180
2.46 1141 2.65 1193
2.64 1155 2.83
2.84 1171 3.03
-
1.95
2.04
2.13
2.24
2.36
2.49
2.64
2.81
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZWT08 (8.5 Ton) Side Duct
Air Flow
(CFM)
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
654
0.32
706
0.53
664
0.43
716
0.64
675
0.53
726
0.74
686
0.63
738
0.84
699
0.75
750
0.96
713
0.88
764
1.09
728
1.02
779
1.23
745
1.18
796
1.39
763
1.36
815
1.57
783
1.55
835
1.76
805
1.77
856
1.98
755
765
776
787
800
814
829
846
864
884
906
0.73
0.83
0.94
1.04
1.16
1.28
1.43
1.59
1.76
1.96
2.17
Standard 2 HP & Drive
803
0.92
849
1.10
813
1.02
859
1.20
824
1.12
870
1.30
835
1.23
881
1.41
847
1.34
893
1.52
861
1.47
907
1.65
877
1.61
923
1.79
893
1.77
939
1.95
912
1.95
958
2.13
932
2.15
978
2.33
953
2.36
999
2.54
893
904
914
925
938
952
967
984
1002
1022
1044
1.27
1.38
1.48
1.58
1.70
1.83
1.97
2.13
2.31
2.50
2.72
937
947
957
969
981
995
1010
1027
1046
1066
1087
1.44
1.55
1.65
1.76
1.87
2.00
2.14
2.30
2.48
2.67
2.89
Hi Static 3 HP & Drive
979
1.62 1020 1.79 1061 1.96
989
1.72 1030 1.89 1071 2.07
1000 1.82 1041 1.99 1082 2.17
1011 1.93 1052 2.10 1093 2.27
1024 2.04 1065 2.21 1106 2.39
1037 2.17 1079 2.34 1119 2.52
1053 2.31 1094 2.48 1135 2.66
1069 2.47 1111 2.64 1152 2.82
1088 2.65 1129 2.82 1170 3.00
1108 2.84 1149 3.02 1190 3.19
1129 3.06 1171 3.23 1211 3.41
3 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Johnson Controls Unitary Products
111
5123247-TTG-A-0515
ZWT10 (10 Ton) Side Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
675
0.53
726
0.74
686
0.63
738
0.84
699
0.75
750
0.96
713
0.88
764
1.09
728
1.02
779
1.23
745
1.18
796
1.39
763
1.36
815
1.57
783
1.55
835
1.76
805
1.77
856
1.98
828
2.00
879
2.21
852
2.25
904
2.46
879
2.52
930
2.73
906
2.81
958
3.02
776
787
800
814
829
846
864
884
906
929
953
980
1007
0.94
1.04
1.16
1.28
1.43
1.59
1.76
1.96
2.17
2.41
2.66
2.93
3.22
824
835
847
861
877
893
912
932
953
976
1001
1027
1055
Standard 2 HP & Drive
1.12
870
1.30
914
1.23
881
1.41
925
1.34
893
1.52
938
1.47
907
1.65
952
1.61
923
1.79
967
1.77
939
1.95
984
1.95
958
2.13 1002
2.15
978
2.33 1022
2.36
999
2.54 1044
2.59 1022 2.77 1067
2.85 1047 3.03 1092
3.12 1073 3.30
3.41
-
1.48
1.58
1.70
1.83
1.97
2.13
2.31
2.50
2.72
2.95
3.20
-
957
969
981
995
1010
1027
1046
1066
1087
1110
1135
-
Hi Static 3 HP & Drive
1.65 1000 1.82 1041 1.99 1082
1.76 1011 1.93 1052 2.10 1093
1.87 1024 2.04 1065 2.21 1106
2.00 1037 2.17 1079 2.34 1119
2.14 1053 2.31 1094 2.48 1135
2.30 1069 2.47 1111 2.64 1152
2.48 1088 2.65 1129 2.82 1170
2.67 1108 2.84 1149 3.02 1190
2.89 1129 3.06 1171 3.23 1211
3.12 1152 3.29
3.37
3 HP & Field Supplied Drive
2.17
2.27
2.39
2.52
2.66
2.82
3.00
3.19
3.41
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZWT12 (12.5 Ton) Side Duct
Air Flow
(CFM)
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
6000
6200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
713
728
745
763
783
805
828
852
879
906
936
966
999
1032
1067
1103
0.88
1.02
1.18
1.36
1.55
1.77
2.00
2.25
2.52
2.81
3.12
3.45
3.80
4.16
4.54
4.94
Field Supplied Drive
764
1.09
814
1.28
779
1.23
829
1.43
796
1.39
846
1.59
815
1.57
864
1.76
835
1.76
884
1.96
856
1.98
906
2.17
879
2.21
929
2.41
904
2.46
953
2.66
930
2.73
980
2.93
958
3.02 1007 3.22
987
3.33 1037 3.53
1018 3.66 1067 3.86
1050 4.01 1100 4.20
1084 4.37 1133 4.57
1119 4.75 1168 4.95
1155 5.15 1204 5.34
Hi Static 5 HP & Drive
861
877
893
912
932
953
976
1001
1027
1055
1084
1115
1147
1181
1216
1252
1.47
1.61
1.77
1.95
2.15
2.36
2.59
2.85
3.12
3.41
3.72
4.05
4.39
4.75
5.13
5.53
907
923
939
958
978
999
1022
1047
1073
1101
1130
1161
1193
1227
1262
1298
1.65
1.79
1.95
2.13
2.33
2.54
2.77
3.03
3.30
3.59
3.90
4.23
4.57
4.93
5.31
5.71
952
967
984
1002
1022
1044
1067
1092
1118
1146
1175
1206
1238
1271
1306
-
1.83
1.97
2.13
2.31
2.50
2.72
2.95
3.20
3.47
3.76
4.07
4.40
4.75
5.11
5.49
-
Standard 3 HP & Drive
995
2.00 1037 2.17
1010 2.14 1053 2.31
1027 2.30 1069 2.47
1046 2.48 1088 2.65
1066 2.67 1108 2.84
1087 2.89 1129 3.06
1110 3.12 1152 3.29
1135 3.37 1177 3.54
1161 3.65 1203 3.82
1189 3.94 1231 4.11
1218 4.24 1260 4.42
1249 4.57 1291 4.74
1281 4.92 1323 5.09
1315 5.28 1357 5.45
1350 5.66
5 HP & Field Supplied Drive
1079
1094
1111
1129
1149
1171
1194
1219
1245
1273
1302
1333
1365
1398
-
2.34
2.48
2.64
2.82
3.02
3.23
3.46
3.72
3.99
4.28
4.59
4.91
5.26
5.62
-
1119
1135
1152
1170
1190
1211
1235
1259
1285
1313
1343
1373
1405
-
2.52
2.66
2.82
3.00
3.19
3.41
3.64
3.89
4.16
4.45
4.76
5.09
5.44
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
112
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWTA3 thru T12 Bottom Duct Application
ZWTA3 (3.0 Ton) Bottom Duct
Air Flow
(CFM)
900
1000
1100
1200
1300
1400
1500
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
605
621
637
651
666
681
697
Standard 1.5 HP & Drive
0.23
671
0.33
738
0.25
688
0.34
754
0.27
703
0.36
769
0.30
717
0.39
784
0.33
732
0.43
799
0.37
747
0.47
814
0.42
763
0.51
830
0.42
0.44
0.46
0.49
0.52
0.56
0.61
804
820
835
850
865
880
896
0.52
0.53
0.56
0.58
0.62
0.66
0.71
869
885
900
915
930
945
961
Hi Static 1.5 HP & Drive
0.62
933
0.71
995
0.63
949
0.72 1011
0.65
964
0.74 1026
0.68
979
0.77 1041
0.71
994
0.81 1056
0.75 1009 0.85 1071
0.80 1025 0.90 1087
0.80
0.82
0.84
0.87
0.90
0.94
0.99
1054 0.89 1111 0.98
1071 0.91 1127 1.00
1086 0.93 1142 1.02
1100 0.96 1157 1.05
1115 0.99 1172 1.08
1130 1.03 1187 1.12
1146 1.08 1203 1.17
1.5 HP & Field Supplied Drive
1164
1180
1195
1210
1225
1240
1256
1.07
1.09
1.11
1.13
1.17
1.21
1.26
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZWTA4 (4.0 Ton) Bottom Duct
Air Flow
(CFM)
1200
1300
1400
1500
1600
1700
1800
1900
2000
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS4
635
0.25
648
0.28
661
0.32
675
0.37
690
0.42
706
0.48
723
0.55
741
0.62
760
0.69
704
717
730
744
759
775
792
810
829
0.34
0.38
0.42
0.46
0.51
0.57
0.64
0.71
0.79
770
782
796
810
825
841
857
875
894
Standard 1.5 HP & Drive
0.44
832
0.54
893
0.47
845
0.58
906
0.51
858
0.62
919
0.56
872
0.66
933
0.61
887
0.72
948
0.67
903
0.77
964
0.74
920
0.84
981
0.81
938
0.91
999
0.88
957
0.99 1018
0.65
0.68
0.72
0.77
0.82
0.88
0.94
1.01
1.09
953
966
979
993
1008
1024
1041
1059
1078
0.75
0.78
0.82
0.87
0.92
0.98
1.04
1.11
1.19
1013
1025
1039
1053
1068
1084
1101
1118
1137
0.85
0.88
0.92
0.96
1.02
1.08
1.14
1.21
1.29
Hi Static 1.5 HP & Drive
1073 0.94 1134 1.02
1085 0.97 1147 1.05
1099 1.01 1160 1.09
1113 1.05 1174 1.14
1128 1.11 1189 1.19
1144 1.17 1205 1.25
1161 1.23 1222 1.31
1178 1.30 1240 1.38
1197 1.38 1258 1.46
1197
1210
1223
1237
1252
1268
1285
1303
1322
1.08
1.12
1.16
1.20
1.26
1.31
1.38
1.45
1.53
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZWTA5 (5.0 Ton) Bottom Duct
Air Flow
(CFM)
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field Supplied Drive
673
0.47
736
0.54
797
693
0.49
756
0.57
817
713
0.53
777
0.60
837
734
0.57
797
0.65
858
755
0.62
819
0.70
879
776
0.69
840
0.76
900
798
0.76
861
0.84
921
819
0.84
882
0.92
943
840
0.93
903
1.01
964
861
1.03
925
1.11
985
882
1.14
946
1.22 1006
0.63
0.65
0.69
0.73
0.79
0.85
0.92
1.00
1.10
1.20
1.30
855
874
895
916
937
958
979
1001
1022
1043
1064
0.72
0.75
0.78
0.83
0.88
0.94
1.02
1.10
1.19
1.29
1.40
Standard 1.5 HP & Drive
910
0.82
964
0.92
930
0.85
984
0.95
951
0.88 1004 0.98
971
0.92 1025 1.03
992
0.98 1046 1.08
1014 1.04 1067 1.14
1035 1.11 1089 1.22
1056 1.20 1110 1.30
1077 1.29 1131 1.39
1099 1.39 1152 1.49
1120 1.50 1173 1.60
1016
1036
1057
1077
1098
1120
1141
1162
1183
1204
1226
1.03
1.06
1.09
1.14
1.19
1.25
1.32
1.41
1.50
1.60
1.71
1067
1087
1107
1128
1149
1171
1192
1213
1234
1255
1276
1.14
1.17
1.20
1.25
1.30
1.36
1.44
1.52
1.61
1.71
1.82
Hi Static 2 HP & Drive
1117 1.25 1166 1.36
1137 1.28 1186 1.39
1157 1.31 1207 1.42
1178 1.36 1228 1.47
1199 1.41 1249 1.52
1221 1.47 1270 1.59
1242 1.55 1291 1.66
1263 1.63 1312 1.74
1284 1.72 1334 1.83
1305 1.82 1355 1.93
1326 1.93 1376 2.04
2 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Johnson Controls Unitary Products
113
5123247-TTG-A-0515
ZWT06 (6.5 Ton) Bottom Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS4
603
0.13
627
0.26
650
0.40
673
0.55
696
0.71
720
0.87
745
1.05
771
1.24
797
1.44
656
680
703
726
749
773
798
824
850
0.36
0.49
0.63
0.78
0.94
1.10
1.28
1.47
1.67
Standard 1.5 HP & Drive
718
0.58
784
0.79
742
0.71
808
0.92
765
0.85
831
1.06
788
1.00
854
1.21
811
1.16
878
1.37
835
1.32
902
1.53
860
1.50
926
1.71
886
1.69
952
1.90
912
1.89
979
2.10
851
875
898
921
944
968
993
1019
1045
0.98
1.12
1.25
1.40
1.56
1.73
1.91
2.09
2.29
914
937
961
984
1007
1031
1056
1081
1108
1.16
1.29
1.43
1.58
1.73
1.90
2.08
2.27
2.47
968
992
1015
1038
1061
1085
1110
1136
1162
Hi Static 2 HP & Drive
1.31 1010 1.43 1035 1.53
1.44 1034 1.57 1059 1.66
1.58 1057 1.71 1082 1.80
1.73 1080 1.85 1105 1.95
1.89 1103 2.01 1128 2.10
2.05 1127 2.18 1152 2.27
2.23 1152 2.36 1177 2.45
2.42 1178 2.54 1203 2.64
2.62 1204 2.74 1229 2.84
3 HP & Field Supplied Drive
1039
1063
1086
1109
1133
1157
1181
1207
1234
1.59
1.72
1.86
2.01
2.16
2.33
2.51
2.70
2.90
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZWT07 (7.5 Ton) Bottom Duct
Air Flow
(CFM)
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS4
644
0.11
666
0.26
689
0.42
712
0.60
736
0.80
761
1.00
787
1.22
813
1.46
841
1.70
869
1.96
698
720
743
766
790
815
840
867
894
923
0.38
0.53
0.69
0.87
1.06
1.27
1.49
1.73
1.97
2.22
755
777
800
823
847
872
898
924
952
980
Standard 1.5 HP & Drive
0.62
814
0.85
874
0.77
836
1.00
896
0.93
859
1.16
919
1.11
882
1.34
942
1.31
906
1.53
967
1.52
931
1.74
991
1.74
957
1.96 1017
1.97
984
2.19 1044
2.21 1011 2.44 1071
2.47 1039 2.69 1099
1.06
1.21
1.37
1.55
1.74
1.95
2.17
2.40
2.65
2.90
933
956
978
1002
1026
1051
1076
1103
1130
1158
1.26
1.41
1.57
1.75
1.94
2.15
2.37
2.61
2.85
3.10
990
1012
1035
1058
1082
1107
1133
1160
1187
1215
1.46
1.61
1.77
1.95
2.14
2.35
2.57
2.80
3.05
3.30
Hi Static 3 HP & Drive
1043 1.66 1090 1.87 1131
1065 1.81 1113 2.02 1153
1088 1.97 1135 2.18 1176
1111 2.15 1159 2.36 1199
1135 2.34 1183 2.55 1223
1160 2.55 1208 2.76 1248
1186 2.77 1233 2.98 1274
1212 3.01 1260 3.21
3 HP & Field Supplied Drive
2.09
2.24
2.40
2.58
2.78
2.98
3.20
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZWT08 (8.5 Ton) Bottom Duct
Air Flow
(CFM)
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
1.
2.
3.
4.
114
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS4
685
0.59
702
0.70
722
0.83
744
0.97
769
1.13
797
1.32
828
1.52
861
1.75
897
2.00
935
2.27
976
2.57
739
756
776
798
823
851
882
915
951
989
1030
0.74
0.85
0.97
1.12
1.28
1.46
1.67
1.90
2.15
2.42
2.72
Standard 2 HP & Drive
791
0.88
841
1.01
808
0.99
858
1.12
828
1.11
878
1.25
850
1.26
900
1.39
875
1.42
925
1.55
903
1.60
953
1.74
934
1.81
983
1.94
967
2.04 1017 2.17
1002 2.29 1052 2.42
1041 2.56 1091 2.69
1082 2.86 1132 2.99
889
906
926
949
974
1001
1032
1065
1101
1139
1180
1.14
1.25
1.37
1.52
1.68
1.86
2.07
2.30
2.55
2.82
3.12
936
953
973
995
1020
1048
1078
1112
1147
1186
1227
Hi Static 3 HP & Drive
1.27
981
1.39 1025 1.51 1069
1.37
999
1.49 1043 1.62 1086
1.50 1018 1.62 1063 1.74 1106
1.64 1041 1.76 1085 1.88 1128
1.80 1066 1.92 1110 2.05 1153
1.99 1093 2.11 1138 2.23 1181
2.19 1124 2.32 1168 2.44 1212
2.42 1157 2.54 1201 2.67 1245
2.67 1193 2.80 1237 2.92 1280
2.95 1231 3.07 1275 3.19 1319
3.24 1272 3.36
3 HP & Field Supplied Drive
1.63
1.74
1.86
2.00
2.17
2.35
2.56
2.79
3.04
3.31
-
1111
1129
1149
1171
1196
1224
1254
1287
1323
1362
-
1.75
1.86
1.99
2.13
2.29
2.48
2.68
2.91
3.16
3.43
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWT10 (10 Ton) Bottom Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied
Drive
722
0.83
744
0.97
769
1.13
797
1.32
828
1.52
861
1.75
897
2.00
935
2.27
976
2.57
1019 2.88
1065 3.22
Standard 2 HP & Drive
776
798
823
851
882
915
951
989
1030
1073
1119
0.97
1.12
1.28
1.46
1.67
1.90
2.15
2.42
2.72
3.03
3.36
828
850
875
903
934
967
1002
1041
1082
1125
-
1.11
1.26
1.42
1.60
1.81
2.04
2.29
2.56
2.86
3.17
-
878
900
925
953
983
1017
1052
1091
1132
1175
-
1.25
1.39
1.55
1.74
1.94
2.17
2.42
2.69
2.99
3.30
-
926
949
974
1001
1032
1065
1101
1139
1180
1223
-
Hi Static 3 HP & Drive
1.37
973
1.50 1018
1.52
995
1.64 1041
1.68 1020 1.80 1066
1.86 1048 1.99 1093
2.07 1078 2.19 1124
2.30 1112 2.42 1157
2.55 1147 2.67 1193
2.82 1186 2.95 1231
3.12 1227 3.24 1272
3.43
3 HP & Field Supplied Drive
1.62
1.76
1.92
2.11
2.32
2.54
2.80
3.07
3.36
-
1063
1085
1110
1138
1168
1201
1237
1275
-
1.74
1.88
2.05
2.23
2.44
2.67
2.92
3.19
-
1106
1128
1153
1181
1212
1245
1280
1319
-
1.86
2.00
2.17
2.35
2.56
2.79
3.04
3.31
-
1149
1171
1196
1224
1254
1287
1323
1362
-
1.99
2.13
2.29
2.48
2.68
2.91
3.16
3.43
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZWT12 (12.5 Ton) Bottom Duct
Air Flow
(CFM)
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
797
1.32
851
1.46
828
1.52
882
1.67
861
1.75
915
1.90
897
2.00
951
2.15
935
2.27
989
2.42
976
2.57 1030 2.72
1019 2.88 1073 3.03
1065 3.22 1119 3.36
1113 3.57 1167 3.72
1163 3.94 1217 4.09
1216 4.34 1270 4.48
1270 4.75 1324 4.89
1327 5.17 1381 5.32
1385 5.62
-
903
934
967
1002
1041
1082
1125
1171
1219
1269
1321
1376
1433
-
1.60
1.81
2.04
2.29
2.56
2.86
3.17
3.50
3.86
4.23
4.62
5.03
5.46
-
953
983
1017
1052
1091
1132
1175
1221
1269
1319
1371
1426
1483
-
Standard 3 HP & Drive
1.74 1001 1.86 1048 1.99
1.94 1032 2.07 1078 2.19
2.17 1065 2.30 1112 2.42
2.42 1101 2.55 1147 2.67
2.69 1139 2.82 1186 2.95
2.99 1180 3.12 1227 3.24
3.30 1223 3.43 1270 3.55
3.64 1269 3.76 1316 3.89
3.99 1317 4.12 1364 4.24
4.36 1367 4.49 1414 4.62
4.76 1420 4.88 1466 5.01
5.17 1474 5.29 1521 5.42
5.59 1531 5.72
5 HP & Field Supplied Drive
1093
1124
1157
1193
1231
1272
1315
1361
1409
1459
1512
1566
-
2.11
2.32
2.54
2.80
3.07
3.36
3.67
4.01
4.36
4.74
5.13
5.54
-
1138
1168
1201
1237
1275
1316
1360
1405
1453
1504
1556
1611
-
Hi Static 5 HP & Drive
2.23 1181 2.35 1224
2.44 1212 2.56 1254
2.67 1245 2.79 1287
2.92 1280 3.04 1323
3.19 1319 3.31 1362
3.48 1360 3.60 1402
3.80 1403 3.92 1446
4.13 1449 4.25 1491
4.48 1497 4.61 1540
4.86 1547 4.98 1590
5.25 1600 5.37 1642
5.66
-
2.48
2.68
2.91
3.16
3.43
3.73
4.04
4.38
4.73
5.10
5.50
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Johnson Controls Unitary Products
115
5123247-TTG-A-0515
ZKTA3 thru T12 Side Duct Application
ZKTA3 (3.0 Ton) Side Duct
1
Available External Static Pressure - IWG
Air
Flow
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS4
Standard 1.5 HP & Drive
Hi Static 1.5 HP & Drive
900
480
0.4
582
0.4
673
0.5
756
0.5
830
0.6
898
0.7
960
0.8
1018
0.9
1072
1.0
1124
1.1
1000
489
0.4
591
0.4
682
0.5
764
0.6
839
0.6
907
0.7
969
0.8
1026
0.9
1080
1.0
1132
1.1
1100
500
0.4
602
0.4
693
0.5
776
0.6
850
0.6
918
0.7
980
0.8
1038
0.9
1092
1.0
1144
1.1
1200
513
0.4
614
0.5
706
0.5
788
0.6
863
0.7
931
0.8
993
0.8
1050
0.9
1104
1.0
1156
1.1
1300
525
0.4
627
0.5
719
0.6
801
0.6
876
0.7
943
0.8
1005
0.9
1063
1.0
1117
1.1
1169
1.2
1400
537
0.5
639
0.5
731
0.6
813
0.7
888
0.7
955
0.8
1017
0.9
1075
1.0
1129
1.1
1181
1.2
1500
549
0.5
650
0.6
742
0.6
824
0.7
899
0.8
966
0.9
1028
0.9
1086
1.0
1140
1.1
1192
1.2
1.
2.
3.
4.
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZKTA4 (4.0 Ton) Side Duct
1
Available External Static Pressure - IWG
Air
Flow
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
(CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field
Supplied Drive
Standard 1.5 HP & Drive
Hi Static 1.5 HP & Drive
1200
513
0.4
614
0.5
706
0.5
788
0.6
863
0.7
931
0.8
993
0.8
1050
0.9
1104
1.0
1156
1.1
1300
525
0.4
627
0.5
719
0.6
801
0.6
876
0.7
943
0.8
1005
0.9
1063
1.0
1117
1.1
1169
1.2
1400
537
0.5
639
0.5
731
0.6
813
0.7
888
0.7
955
0.8
1017
0.9
1075
1.0
1129
1.1
1181
1.2
1500
549
0.5
650
0.6
742
0.6
824
0.7
899
0.8
966
0.9
1028
0.9
1086
1.0
1140
1.1
1192
1.2
1600
558
0.6
660
0.6
752
0.7
834
0.8
909
0.8
976
0.9
1038
1.0
1096
1.1
1150
1.2
1202
1.3
1700
566
0.6
668
0.7
760
0.7
842
0.8
917
0.9
984
1.0
1046
1.1
1104
1.1
1158
1.2
1210
1.4
1800
573
0.7
675
0.7
766
0.8
849
0.9
923
1.0
991
1.0
1053
1.1
1110
1.2
1164
1.3
1216
1.4
1900
577
0.8
679
0.8
771
0.9
853
1.0
928
1.0
995
1.1
1057
1.2
1115
1.3
1169
1.4
1221
1.5
2000
580
0.8
682
0.9
773
1.0
856
1.0
930
1.1
998
1.2
1060
1.3
1117
1.4
1172
1.5
1224
1.6
FS4
1.
2.
3.
4.
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZKTA5 (5.0 Ton) Side Duct
Air
Flow
(CFM)
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard 1.5 HP & Drive
Hi Static 2 HP & Drive
1500
616
0.5
685
0.6
766
0.7
833
0.8
905
0.9
975
1.0
1035
1.0
1101
1.1
1163
1.2
1229
1600
638
0.6
707
0.7
781
0.7
848
0.8
920
0.9
990
1.0
1050
1.1
1104
1.1
1166
1.2
1232
1.3
1.3
1700
655
0.6
724
0.7
796
0.8
863
0.9
935
1.0
1005
1.1
1064
1.1
1109
1.2
1172
1.3
1238
1.4
1800
670
0.7
739
0.8
810
0.8
877
0.9
949
1.0
1018
1.1
1078
1.2
1117
1.2
1179
1.3
1245
1.5
1900
686
0.7
755
0.8
823
0.9
890
1.0
962
1.1
1032
1.2
1091
1.2
1125
1.3
1187
1.4
1253
1.5
2000
702
0.8
772
0.9
836
1.0
903
1.1
975
1.2
1045
1.3
1078
1.3
1135
1.4
1197
1.5
1263
1.6
2100
722
0.9
791
1.0
849
1.0
916
1.1
988
1.2
1058
1.3
1089
1.4
1147
1.5
1209
1.6
1275
1.7
2200
745
0.9
814
1.0
861
1.1
928
1.2
1000
1.3
1050
1.4
1102
1.5
1159
1.6
1221
1.7
1287
1.8
2300
772
1.0
841
1.1
874
1.2
941
1.3
1013
1.4
1064
1.5
1115
1.6
1173
1.7
1235
1.8
-
-
2400
804
1.1
832
1.2
886
1.3
953
1.4
1033
1.4
1078
1.6
1130
1.7
1188
1.8
-
-
-
-
2500
841
1.2
844
1.3
898
1.4
965
1.5
1049
1.5
1094
1.7
-
-
-
-
2 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
116
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT06 thru T12 Side Duct Application
ZKT06 (6.5 Ton) Side Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
778
803
833
866
902
941
983
1028
1074
1.5 HP & Field Supplied Drive
0.37
838
0.56
895
0.50
864
0.69
921
0.64
893
0.83
951
0.80
926
0.99
984
0.97
962
1.16 1020
1.16 1002 1.35 1059
1.37 1043 1.56 1101
1.60 1088 1.79 1145
1.84 1134 2.03 1192
0.73
0.85
1.00
1.15
1.33
1.52
1.73
1.95
2.20
951
977
1006
1039
1076
1115
1157
1201
-
0.88
1.00
1.14
1.30
1.47
1.67
1.88
2.10
-
Standard 1.5 HP & Drive
1005 1.01 1059 1.13
1031 1.14 1085 1.26
1061 1.28 1114 1.40
1094 1.43 1147 1.56
1130 1.61 1183 1.73
1169 1.80 1222 1.92
1211 2.01 1264 2.13
1255 2.24
-
1112
1138
1168
1201
1237
1276
1318
-
Hi Static 2 HP & Drive
1.25 1166 1.36 1221 1.47 1278
1.37 1192 1.49 1247 1.60 1304
1.51 1221 1.63 1276 1.74 1333
1.67 1254 1.78 1309 1.90 1366
1.85 1291 1.96 1346 2.07 1402
2.04 1330 2.15 1385 2.26
2.25
2 HP & Field Supplied Drive
1.59
1.72
1.86
2.02
2.19
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZKT07 (7.5 Ton) Side Duct
Air Flow
(CFM)
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field Supplied Drive
803
0.50
864
0.69
833
0.64
893
0.83
866
0.80
926
0.99
902
0.97
962
1.16
941
1.16 1002 1.35
983
1.37 1043 1.56
1028 1.60 1088 1.79
1074 1.84 1134 2.03
1123 2.10 1183 2.29
1174 2.38 1234 2.57
921
951
984
1020
1059
1101
1145
1192
1241
1292
0.85
1.00
1.15
1.33
1.52
1.73
1.95
2.20
2.46
2.74
Standard 1.5 HP & Drive
977
1.00 1031 1.14
1006 1.14 1061 1.28
1039 1.30 1094 1.43
1076 1.47 1130 1.61
1115 1.67 1169 1.80
1157 1.88 1211 2.01
1201 2.10 1255 2.24
1248 2.35 1302 2.48
1297 2.61 1351 2.74
1348 2.88 1402 3.02
1085
1114
1147
1183
1222
1264
1309
1355
1404
1455
1.26
1.40
1.56
1.73
1.92
2.13
2.36
2.60
2.86
3.14
Hi Static 3 HP & Drive
1138 1.37 1192 1.49 1247 1.60
1168 1.51 1221 1.63 1276 1.74
1201 1.67 1254 1.78 1309 1.90
1237 1.85 1291 1.96 1346 2.07
1276 2.04 1330 2.15 1385 2.26
1318 2.25 1372 2.36 1427 2.47
1362 2.47 1416 2.59 1471 2.70
1409 2.72 1463 2.83 1518 2.94
1458 2.98 1512 3.09 1567 3.21
1509 3.26 1562 3.37
3 HP & Field Supplied Drive
1304
1333
1366
1402
1442
1483
1528
1574
1623
-
1.72
1.86
2.02
2.19
2.38
2.59
2.82
3.06
3.32
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZKT08 (8.5 Ton) Side Duct
Air Flow
(CFM)
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field
Supplied Drive
684
0.48
695
0.58
706
0.67
719
0.78
732
0.89
747
1.02
764
1.16
783
1.33
803
1.51
825
1.71
849
1.92
Standard 2 HP & Drive
735
745
756
769
782
797
814
833
853
875
899
0.67
0.76
0.86
0.96
1.08
1.21
1.35
1.51
1.69
1.89
2.11
783
793
805
817
831
846
862
881
901
923
947
0.84
0.94
1.04
1.14
1.25
1.38
1.53
1.69
1.87
2.07
2.29
829
840
851
863
877
892
909
927
948
970
993
1.01
1.11
1.20
1.31
1.42
1.55
1.69
1.86
2.04
2.23
2.45
874
885
896
908
922
937
954
972
992
1014
1038
Hi Static 3 HP & Drive
1.17
1.27
1.36
1.47
1.58
1.71
1.85
2.02
2.20
2.39
2.61
918
928
939
952
965
980
997
1016
1036
1058
1082
1.32
1.42
1.52
1.62
1.74
1.86
2.01
2.17
2.35
2.55
2.77
960
970
981
994
1007
1023
1039
1058
1078
1100
1124
1.48
1.57
1.67
1.78
1.89
2.02
2.16
2.32
2.50
2.70
2.92
1001 1.63 1041 1.78
1011 1.73 1052 1.88
1023 1.82 1063 1.98
1035 1.93 1075 2.08
1049 2.04 1089 2.19
1064 2.17 1104 2.32
1080 2.31 1121 2.47
1099 2.48 1139 2.63
1119 2.66 1159 2.81
1141 2.86 1181 3.01
1165 3.07 1205 3.23
3 HP & Field Supplied Drive
1081
1091
1103
1115
1128
1144
1160
1179
1199
1221
1245
1.94
2.04
2.13
2.24
2.35
2.48
2.62
2.79
2.97
3.16
3.38
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Johnson Controls Unitary Products
117
5123247-TTG-A-0515
ZKT10 (10 Ton) Side Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive
706
0.67
756
0.86
719
0.78
769
0.96
732
0.89
782
1.08
747
1.02
797
1.21
764
1.16
814
1.35
783
1.33
833
1.51
803
1.51
853
1.69
825
1.71
875
1.89
849
1.92
899
2.11
874
2.16
924
2.35
901
2.42
952
2.61
930
2.70
981
2.88
961
2.99 1011 3.18
805
817
831
846
862
881
901
923
947
972
1000
1029
1059
1.04
1.14
1.25
1.38
1.53
1.69
1.87
2.07
2.29
2.52
2.78
3.06
3.35
Standard 2 HP & Drive
851
1.20
896
1.36
863
1.31
908
1.47
877
1.42
922
1.58
892
1.55
937
1.71
909
1.69
954
1.85
927
1.86
972
2.02
948
2.04
992
2.20
970
2.23 1014 2.39
993
2.45 1038 2.61
1019 2.69 1064 2.85
1046 2.95 1091 3.11
1075 3.23 1120 3.39
-
939
952
965
980
997
1016
1036
1058
1082
1107
1134
-
1.52
1.62
1.74
1.86
2.01
2.17
2.35
2.55
2.77
3.01
3.26
-
Hi Static 3 HP & Drive
981
1.67 1023 1.82 1063 1.98
994
1.78 1035 1.93 1075 2.08
1007 1.89 1049 2.04 1089 2.19
1023 2.02 1064 2.17 1104 2.32
1039 2.16 1080 2.31 1121 2.47
1058 2.32 1099 2.48 1139 2.63
1078 2.50 1119 2.66 1159 2.81
1100 2.70 1141 2.86 1181 3.01
1124 2.92 1165 3.07 1205 3.23
1149 3.16 1190 3.31
1177 3.42
3 HP & Field Supplied Drive
1103
1115
1128
1144
1160
1179
1199
1221
1245
-
2.13
2.24
2.35
2.48
2.62
2.79
2.97
3.16
3.38
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZKT12 (12.5 Ton) Side Duct
Air Flow
(CFM)
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
6000
6200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP & Field Supplied Drive
747
1.02
797
1.21
846
764
1.16
814
1.35
862
783
1.33
833
1.51
881
803
1.51
853
1.69
901
825
1.71
875
1.89
923
849
1.92
899
2.11
947
874
2.16
924
2.35
972
901
2.42
952
2.61 1000
930
2.70
981
2.88 1029
961
2.99 1011 3.18 1059
993
3.31 1043 3.49 1092
1027 3.64 1077 3.83 1126
1063 3.99 1113 4.18 1161
1100 4.36 1150 4.55 1198
1138 4.75 1188 4.93 1237
1178 5.15 1228 5.34 1277
Hi Static 5 HP & Drive
1.38
1.53
1.69
1.87
2.07
2.29
2.52
2.78
3.06
3.35
3.67
4.00
4.35
4.72
5.11
5.51
892
909
927
948
970
993
1019
1046
1075
1106
1138
1172
1207
1244
1283
1323
1.55
1.69
1.86
2.04
2.23
2.45
2.69
2.95
3.23
3.52
3.84
4.17
4.52
4.89
5.28
5.68
937
954
972
992
1014
1038
1064
1091
1120
1151
1183
1217
1252
1289
1328
-
1.71
1.85
2.02
2.20
2.39
2.61
2.85
3.11
3.39
3.68
4.00
4.33
4.68
5.05
5.44
-
Standard 3 HP & Drive
980
1.86 1023 2.02
997
2.01 1039 2.16
1016 2.17 1058 2.32
1036 2.35 1078 2.50
1058 2.55 1100 2.70
1082 2.77 1124 2.92
1107 3.01 1149 3.16
1134 3.26 1177 3.42
1163 3.54 1206 3.69
1194 3.84 1236 3.99
1226 4.15 1269 4.30
1260 4.48 1302 4.64
1296 4.84 1338 4.99
1333 5.20 1375 5.36
1371 5.59 1413 5.74
5 HP & Field Supplied Drive
1064
1080
1099
1119
1141
1165
1190
1218
1247
1277
1310
1344
1379
1416
-
2.17
2.31
2.48
2.66
2.86
3.07
3.31
3.57
3.85
4.14
4.46
4.79
5.14
5.51
-
1104
1121
1139
1159
1181
1205
1231
1258
1287
1318
1350
1384
1419
1456
-
2.32
2.47
2.63
2.81
3.01
3.23
3.47
3.72
4.00
4.29
4.61
4.94
5.29
5.66
-
1144
1160
1179
1199
1221
1245
1270
1298
1327
1357
1390
1424
1459
-
2.48
2.62
2.79
2.97
3.16
3.38
3.62
3.88
4.16
4.45
4.77
5.10
5.45
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
118
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKTA3 thru T12 Bottom Duct Application
ZKTA3 (3.0 Ton) Bottom Duct
1
Available External Static Pressure - IWG
Air
Flow
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS4
Standard 1.5 HP & Drive
Hi Static 1.5 HP & Drive
900
544
0.4
632
0.5
708
0.5
774
0.6
834
0.7
889
0.8
941
0.9
993
1.0
1047
1.1
1104
1.2
1000
549
0.4
637
0.5
713
0.5
779
0.6
839
0.7
894
0.8
946
0.9
998
1.0
1052
1.1
1109
1.2
1100
562
0.4
649
0.5
725
0.6
792
0.6
852
0.7
906
0.8
959
0.9
1010
1.0
1064
1.1
1121
1.2
1200
579
0.5
666
0.5
742
0.6
809
0.6
868
0.7
923
0.8
975
0.9
1027
1.0
1081
1.1
1138
1.2
1300
598
0.5
685
0.5
761
0.6
828
0.7
887
0.8
942
0.8
994
0.9
1046
1.0
1100
1.2
1157
1.3
1400
617
0.5
705
0.6
781
0.6
847
0.7
907
0.8
962
0.9
1014
1.0
1066
1.1
1119
1.2
1177
1.3
1500
637
0.6
724
0.6
800
0.7
867
0.8
927
0.8
981
0.9
1034
1.0
1085
1.1
1139
1.2
1196
1.4
FS4
1.
2.
3.
4.
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZKTA4 (4.0 Ton) Bottom Duct
1
Available External Static Pressure - IWG
Air
Flow
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard 1.5 HP & Drive
Hi Static 1.5 HP & Drive
1200
579
0.5
666
0.5
742
0.6
809
0.6
868
0.7
923
0.8
975
0.9
1027
1.0
1081
1.1
1138
1300
598
0.5
685
0.5
761
0.6
828
0.7
887
0.8
942
0.8
994
0.9
1046
1.0
1100
1.2
1157
1.2
1.3
1400
617
0.5
705
0.6
781
0.6
847
0.7
907
0.8
962
0.9
1014
1.0
1066
1.1
1119
1.2
1177
1.3
1500
637
0.6
724
0.6
800
0.7
867
0.8
927
0.8
981
0.9
1034
1.0
1085
1.1
1139
1.2
1196
1.4
1600
655
0.6
743
0.7
819
0.7
885
0.8
945
0.9
1000
1.0
1052
1.1
1104
1.2
1158
1.3
1215
1.4
1700
672
0.7
760
0.7
836
0.8
902
0.9
962
1.0
1017
1.0
1069
1.1
1121
1.2
1175
1.3
1232
1.5
1800
687
0.7
775
0.8
851
0.9
918
0.9
977
1.0
1032
1.1
1084
1.2
1136
1.3
1190
1.4
1247
1.5
1900
700
0.8
788
0.9
864
0.9
930
1.0
990
1.1
1045
1.2
1097
1.3
1149
1.4
1202
1.5
1260
1.6
2000
711
0.9
798
0.9
874
1.0
941
1.1
1000
1.2
1055
1.2
1107
1.3
1159
1.4
1213
1.6
1270
1.7
FS4
1.
2.
3.
4.
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZKTA5 (5.0 Ton) Bottom Duct
1
Available External Static Pressure - IWG
Air
Flow
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard 1.5 HP & Drive
Hi Static 2 HP & Drive
1500
613
0.5
684
0.6
759
0.7
831
0.7
928
0.8
984
0.9
1042
1.0
1093
1.1
1149
1.2
1201
1.3
1600
629
0.6
700
0.6
775
0.7
847
0.8
929
0.8
985
0.9
1043
1.0
1098
1.1
1154
1.2
1206
1.3
1700
646
0.6
717
0.7
793
0.8
864
0.8
934
0.9
990
1.0
1048
1.1
1106
1.2
1161
1.3
1214
1.4
1800
666
0.7
737
0.7
812
0.8
884
0.9
943
1.0
999
1.1
1057
1.2
1116
1.3
1172
1.4
1224
1.5
1900
687
0.7
758
0.8
833
0.9
905
0.9
954
1.0
1010
1.1
1068
1.2
1128
1.3
1184
1.4
1236
1.5
2000
710
0.8
781
0.9
856
0.9
927
1.0
968
1.1
1024
1.2
1082
1.3
1142
1.4
1198
1.5
1250
1.6
2100
733
0.8
804
0.9
879
1.0
951
1.1
983
1.2
1039
1.3
1097
1.4
1157
1.5
1213
1.6
1265
1.7
2200
758
0.9
828
1.0
904
1.1
947
1.2
1000
1.3
1056
1.4
1116
1.5
1174
1.6
1229
1.7
1281
1.8
2300
783
1.0
854
1.1
929
1.1
964
1.3
1018
1.4
1075
1.5
1133
1.6
1191
1.7
1246
1.8
-
-
2400
809
1.1
879
1.2
932
1.3
983
1.4
1037
1.5
1094
1.6
1152
1.7
1209
1.8
-
-
-
-
2500
835
1.1
906
1.2
951
1.4
1001
1.5
1055
1.6
1112
1.7
1170
1.8
2 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Johnson Controls Unitary Products
119
5123247-TTG-A-0515
ZKT06 thru T12 Bottom Duct Application
ZKT06 (6.5 Ton) Bottom Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field Supplied Drive
801
0.45
874
0.65
831
0.59
903
0.78
867
0.74
940
0.93
910
0.91
983
1.10
957
1.10 1030 1.30
1009 1.32 1082 1.51
1064 1.56 1137 1.75
1122 1.82 1194 2.02
1182 2.10 1254 2.30
946
975
1012
1055
1102
1154
1208
1266
-
Standard 1.5 HP & Drive
0.82 1018 0.97 1090
0.95 1047 1.10 1119
1.10 1084 1.25 1156
1.27 1126 1.43 1199
1.47 1174 1.62 1246
1.69 1225 1.84 1298
1.92 1280 2.08 1353
2.19
-
1.11
1.24
1.39
1.57
1.76
1.98
2.22
-
Hi Static 2 HP & Drive
1163 1.25 1238 1.38
1193 1.38 1267 1.51
1229 1.53 1304 1.66
1272 1.70 1347 1.84
1320 1.89 1394 2.03
1371 2.11 1446 2.25
2 HP & Field Supplied Drive
1315
1344
1381
1424
1471
-
1.52
1.66
1.81
1.98
2.17
-
1395
1424
1461
1503
-
1.68
1.81
1.96
2.14
-
1477
1507
1543
-
1.86
1.99
2.14
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZKT07 (7.5 Ton) Bottom Duct
Air Flow
(CFM)
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field
Supplied Drive
831
0.59
867
0.74
910
0.91
957
1.10
1009 1.32
1064 1.56
1122 1.82
1182 2.10
1244 2.41
1308 2.73
Standard 1.5 HP & Drive
903
940
983
1030
1082
1137
1194
1254
1317
1381
0.78
0.93
1.10
1.30
1.51
1.75
2.02
2.30
2.60
2.93
975
1012
1055
1102
1154
1208
1266
1326
1389
1453
0.95
1.10
1.27
1.47
1.69
1.92
2.19
2.47
2.77
3.10
1047
1084
1126
1174
1225
1280
1338
1398
1461
1525
1.10
1.25
1.43
1.62
1.84
2.08
2.34
2.62
2.93
3.25
Hi Static 3 HP & Drive
1119
1156
1199
1246
1298
1353
1410
1471
1533
1597
1.24 1193 1.38 1267
1.39 1229 1.53 1304
1.57 1272 1.70 1347
1.76 1320 1.89 1394
1.98 1371 2.11 1446
2.22 1426 2.35 1501
2.48 1484 2.61 1559
2.76 1544 2.90 1619
3.07 1606 3.20 1681
3.39
3 HP & Field Supplied Drive
1.51
1.66
1.84
2.03
2.25
2.49
2.75
3.03
3.33
-
1344
1381
1424
1471
1523
1578
1636
1696
-
1.66
1.81
1.98
2.17
2.39
2.63
2.89
3.17
-
1424
1461
1503
1551
1602
1657
1715
1775
-
1.81
1.96
2.14
2.33
2.55
2.79
3.05
3.33
-
1507
1543
1586
1634
1685
1740
1798
-
1.99
2.14
2.31
2.51
2.73
2.96
3.23
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZKT08 (8.5 Ton) Bottom Duct
Air Flow
(CFM)
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field
Supplied Drive
715
0.72
768
734
0.83
786
755
0.95
808
779
1.09
832
806
1.25
859
837
1.44
889
870
1.65
922
906
1.88
959
945
2.13
998
987
2.40 1040
1032 2.70 1084
Standard 2 HP & Drive
0.85
0.96
1.08
1.22
1.38
1.57
1.78
2.01
2.26
2.53
2.83
818
837
858
882
910
940
973
1009
1048
1090
1135
0.98
1.08
1.20
1.35
1.51
1.69
1.90
2.13
2.38
2.66
2.95
867
886
907
931
958
989
1022
1058
1097
1139
1184
1.09
1.20
1.32
1.46
1.63
1.81
2.02
2.25
2.50
2.78
3.07
Hi Static 3 HP & Drive
914
933
954
978
1005
1036
1069
1105
1144
1186
1231
1.21
1.31
1.44
1.58
1.74
1.93
2.13
2.36
2.61
2.89
3.18
960
1.32 1004 1.43
978
1.42 1022 1.53
1000 1.55 1044 1.65
1024 1.69 1068 1.80
1051 1.85 1095 1.96
1081 2.04 1125 2.14
1114 2.24 1158 2.35
1150 2.47 1195 2.58
1190 2.72 1234 2.83
1231 3.00 1276 3.11
1276 3.29 1320 3.40
3 HP & Field Supplied Drive
1047
1066
1087
1111
1138
1168
1202
1238
1277
1319
-
1.53
1.64
1.76
1.90
2.07
2.25
2.46
2.69
2.94
3.21
-
1089
1108
1129
1153
1181
1211
1244
1280
1319
1361
-
1.64
1.75
1.87
2.01
2.17
2.36
2.57
2.80
3.05
3.32
-
1131
1150
1171
1195
1222
1252
1286
1322
1361
1403
-
1.75
1.86
1.98
2.12
2.28
2.47
2.68
2.91
3.16
3.43
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
120
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT10 (10 Ton) Bottom Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field
Supplied Drive
755
0.95
808
779
1.09
832
806
1.25
859
837
1.44
889
870
1.65
922
906
1.88
959
945
2.13
998
987
2.40 1040
1032 2.70 1084
1079 3.01 1132
1129 3.35
-
Standard 2 HP & Drive
1.08
1.22
1.38
1.57
1.78
2.01
2.26
2.53
2.83
3.15
-
858
882
910
940
973
1009
1048
1090
1135
1182
-
1.20
1.35
1.51
1.69
1.90
2.13
2.38
2.66
2.95
3.27
-
907
931
958
989
1022
1058
1097
1139
1184
1231
-
1.32
1.46
1.63
1.81
2.02
2.25
2.50
2.78
3.07
3.39
-
Hi Static 3 HP & Drive
954
1.44 1000 1.55
978
1.58 1024 1.69
1005 1.74 1051 1.85
1036 1.93 1081 2.04
1069 2.13 1114 2.24
1105 2.36 1150 2.47
1144 2.61 1190 2.72
1186 2.89 1231 3.00
1231 3.18 1276 3.29
3 HP & Field Supplied Drive
1044
1068
1095
1125
1158
1195
1234
1276
1320
-
1.65
1.80
1.96
2.14
2.35
2.58
2.83
3.11
3.40
-
1087
1111
1138
1168
1202
1238
1277
1319
-
1.76
1.90
2.07
2.25
2.46
2.69
2.94
3.21
-
1129
1153
1181
1211
1244
1280
1319
1361
-
1.87
2.01
2.17
2.36
2.57
2.80
3.05
3.32
-
1171
1195
1222
1252
1286
1322
1361
1403
-
1.98
2.12
2.28
2.47
2.68
2.91
3.16
3.43
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZKT12 (12.5 Ton) Bottom Duct
Air Flow
(CFM)
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP & Field
Supplied Drive
837
1.44
870
1.65
906
1.88
945
2.13
987
2.40
1032 2.70
1079 3.01
1129 3.35
1182 3.71
1237 4.08
1294 4.48
1354 4.89
1416 5.33
-
Standard 3 HP & Drive
889
922
959
998
1040
1084
1132
1182
1235
1290
1347
1407
1469
-
1.57
1.78
2.01
2.26
2.53
2.83
3.15
3.48
3.84
4.22
4.61
5.03
5.46
-
940
973
1009
1048
1090
1135
1182
1232
1285
1340
1398
1457
1519
-
1.69
1.90
2.13
2.38
2.66
2.95
3.27
3.61
3.96
4.34
4.74
5.15
5.58
-
989
1022
1058
1097
1139
1184
1231
1281
1334
1389
1446
1506
1568
-
1.81
2.02
2.25
2.50
2.78
3.07
3.39
3.72
4.08
4.46
4.85
5.27
5.70
-
1036 1.93 1081 2.04
1069 2.13 1114 2.24
1105 2.36 1150 2.47
1144 2.61 1190 2.72
1186 2.89 1231 3.00
1231 3.18 1276 3.29
1278 3.50 1324 3.61
1328 3.84 1374 3.95
1381 4.20 1426 4.31
1436 4.57 1481 4.68
1493 4.97 1539 5.08
1553 5.38 1599 5.49
5 HP & Field Supplied Drive
Hi Static 5 HP & Drive
1125
1158
1195
1234
1276
1320
1368
1418
1471
1526
1583
1643
-
2.14
2.35
2.58
2.83
3.11
3.40
3.72
4.06
4.41
4.79
5.19
5.60
-
1168
1202
1238
1277
1319
1364
1411
1461
1514
1569
1626
1686
-
2.25
2.46
2.69
2.94
3.21
3.51
3.83
4.16
4.52
4.90
5.29
5.71
-
1211
1244
1280
1319
1361
1406
1453
1503
1556
1611
1669
-
2.36
2.57
2.80
3.05
3.32
3.62
3.93
4.27
4.63
5.01
5.40
-
1252
1286
1322
1361
1403
1447
1495
1545
1598
1653
1710
-
2.47
2.68
2.91
3.16
3.43
3.73
4.05
4.38
4.74
5.12
5.51
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Johnson Controls Unitary Products
121
5123247-TTG-A-0515
Sound Performance
Indoor Sound Power Levels (3 thru 5 Ton)
Indoor Sound Power Levels (Horizontal Ducted Inlet, Standard Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA3 / 3 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Horizontal (Side Return) Ducted Inlet
612 - 3 Turns Open Equivalent
709 - 1 Turn Open Equivalent
0.5
0.4
Airflow (CFM)
850
1300
Blower Motor BHP
0.37
External Static Pressure (IWG)
0.40
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
73
77
73
77
125
61
70
66
71
250
56
63
60
64
500
51
56
55
57
1000
44
48
51
52
2000
41
44
48
49
4000
44
47
47
48
8000
42
44
43
44
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA4 / 4 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Horizontal (Side Return) Ducted Inlet
612 - 3 Turns Open Equivalent
709 - 1 Turn Open Equivalent
External Static Pressure (IWG)
0.5
0.4
Airflow (CFM)
850
1300
Blower Motor BHP
0.37
Octave Center Freq. Hz
ID Blower Only (dB)
0.40
Cooling
Operation1
(dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
73
77
73
77
125
61
70
66
71
250
56
63
60
64
500
51
56
55
57
1000
44
48
51
52
2000
41
44
48
49
4000
44
47
47
48
8000
42
44
43
44
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
122
Johnson Controls Unitary Products
5123247-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA5 / 5 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Horizontal (Side Return) Ducted Inlet
Indoor Blower Speed (RPM)
814 - 3 Turns Open Equivalent
918 - 1 Turn Open Equivalent
0.6
0.8
Airflow (CFM)
1700
1950
Blower Motor BHP
0.42
External Static Pressure (IWG)
0.88
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
77
81
85
82
125
71
80
68
81
250
63
67
64
68
500
58
60
60
61
1000
56
57
58
59
2000
52
53
55
55
4000
51
51
54
54
8000
47
47
48
48
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Indoor Sound Power Levels (Horizontal Ducted Discharge, Standard Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA3 / 3 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Horizontal (Side Supply) Ducted Discharge
Indoor Blower Speed (RPM)
610 - 3 Turns Open Equivalent
710 - 1 Turn Open Equivalent
External Static Pressure (IWG)
0.5
0.6
Airflow (CFM)
850
950
Blower Motor BHP
0.37
Octave Center Freq. Hz
ID Blower Only (dB)
0.42
Cooling
Operation1
(dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
77
78
79
79
125
74
75
75
76
250
66
68
70
70
500
61
61
65
64
1000
60
62
65
66
2000
52
52
58
58
4000
52
52
59
60
8000
44
44
50
50
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Johnson Controls Unitary Products
123
5123247-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA4 / 4 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Horizontal (Side Supply) Ducted Discharge
610 - 3 Turns Open Equivalent
710 - 1 Turn Open Equivalent
0.5
0.6
External Static Pressure (IWG)
Airflow (CFM)
850
950
Blower Motor BHP
0.37
0.42
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
77
78
79
79
125
74
75
75
76
250
66
68
70
70
500
61
61
65
64
1000
60
62
65
66
2000
52
52
58
58
4000
52
52
59
60
8000
44
44
50
50
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA5 / 5 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Horizontal (Side Supply) Ducted Discharge
810 - 3 Turns Open Equivalent
External Static Pressure (IWG)
918 - 1 Turn Open Equivalent
0.4
0.8
Airflow (CFM)
2050
1950
Blower Motor BHP
0.73
0.88
1
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
85
83
83
83
125
78
79
76
79
250
69
70
69
70
500
68
68
68
68
1000
64
64
65
65
2000
63
63
64
64
4000
64
64
64
64
8000
59
59
59
60
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
124
Johnson Controls Unitary Products
5123247-TTG-A-0515
Indoor Sound Power Levels (Vertical Ducted Inlet, Standard Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA3 / 3 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Return) Ducted Inlet
Indoor Blower Speed (RPM)
609 - 3 Turns Open Equivalent
708 - 1 Turn Open Equivalent
0.4
0.4
Airflow (CFM)
850
1150
Blower Motor BHP
0.32
External Static Pressure (IWG)
0.38
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
76
76
74
76
125
63
70
66
70
250
55
62
59
62
500
54
55
58
59
1000
48
48
53
53
2000
44
44
48
48
4000
41
44
45
46
8000
42
43
43
44
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA4 / 4 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Return) Ducted Inlet
Indoor Blower Speed (RPM)
609 - 3 Turns Open Equivalent
708 - 1 Turn Open Equivalent
External Static Pressure (IWG)
0.4
0.4
Airflow (CFM)
850
1150
Blower Motor BHP
0.32
Octave Center Freq. Hz
ID Blower Only (dB)
0.38
Cooling
Operation1
(dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
76
76
74
76
125
63
70
66
70
250
55
62
59
62
500
54
55
58
59
1000
48
48
53
53
2000
44
44
48
48
4000
41
44
45
46
8000
42
43
43
44
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Johnson Controls Unitary Products
125
5123247-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA5 / 5 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Vertical (Bottom Return) Ducted Inlet
812 - 3 Turns Open Equivalent
915- 1 Turn Open Equivalent
0.6
0.8
Airflow (CFM)
1575
1800
Blower Motor BHP
0.64
External Static Pressure (IWG)
Octave Center Freq. Hz
ID Blower Only (dB)
0.83
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
75
78
80
80
125
66
80
69
81
250
59
66
62
65
500
60
60
63
63
1000
57
57
60
60
2000
52
53
55
55
4000
49
50
53
53
8000
44
45
47
47
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Indoor Sound Power Levels (Vertical Ducted Discharge, Standard Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA3 / 3 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Vertical (Bottom Supply) Ducted Discharge
609 - 3 Turns Open Equivalent
712 - 1 Turn Open Equivalent
External Static Pressure (IWG)
0.4
0.6
Airflow (CFM)
850
950
Blower Motor BHP
0.32
0.42
1
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
76
77
81
81
125
68
68
72
72
250
55
65
57
57
500
56
57
57
57
1000
51
57
52
56
2000
49
49
50
50
4000
48
48
49
51
8000
46
46
47
48
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
126
Johnson Controls Unitary Products
5123247-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA4 / 4 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Supply) Ducted Discharge
Indoor Blower Speed (RPM)
609 - 3 Turns Open Equivalent
712 - 1 Turn Open Equivalent
0.4
0.6
External Static Pressure (IWG)
Airflow (CFM)
850
950
Blower Motor BHP
0.32
0.42
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
76
77
81
81
125
68
68
72
72
250
55
65
57
57
500
56
57
57
57
1000
51
57
52
56
2000
49
49
50
50
4000
48
48
49
51
8000
46
46
47
48
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA5 / 5 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Supply) Ducted Discharge
Indoor Blower Speed (RPM)
809 - 3 Turns Open Equivalent
External Static Pressure (IWG)
914 - 1 Turn Open Equivalent
0.5
0.8
Airflow (CFM)
1700
1800
Blower Motor BHP
0.64
0.83
1
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
81
81
79
79
125
75
75
75
76
250
65
65
63
63
500
67
67
67
67
1000
63
63
63
63
2000
61
62
61
61
4000
62
62
61
61
8000
57
57
56
56
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Johnson Controls Unitary Products
127
5123247-TTG-A-0515
Indoor Sound Power Levels (Horizontal Ducted Inlet, High Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA3 / 3 Ton / High Static Belt Drive
TEST CONFIGURATION
Horizontal (Side Return) Ducted Inlet
876 - 4 Turns Open Equivalent
1,064 - 1/2 Turn Open Equivalent
1,190 - 2.5 Turns Open Equivalent1
1.0
1.6
2.0 1
Nominal Airflow (CFM)
1,200
1,100
1,000
Blower Motor BHP
0.64
0.93
Indoor Blower Speed (RPM)
External Static Pressure (IWG)
1.08
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
63
75
80
81
81
81
83
125
69
71
71
73
73
75
250
62
68
66
71
68
70
500
54
56
57
59
59
60
1000
52
56
56
58
58
60
2000
47
49
52
52
54
56
4000
43
45
48
49
51
53
8000
43
45
45
46
47
48
1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.
2. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA4 / 4 Ton / High Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Horizontal (Side Return) Ducted Inlet
965 - 5.5 Turns Open Equivalent
1,088 - 4 Turns Open Equivalent
1.0
1.6
2.0
Nominal Airflow (CFM)
1,600
1,400
1,200
Blower Motor BHP
0.86
1.03
1.13
External Static Pressure (IWG)
1,186 - 2.5 Turns Open Equivalent
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
74
80
77
80
81
81
125
69
74
72
75
75
76
250
68
68
68
69
70
71
500
62
62
60
61
61
63
1000
60
61
58
58
59
60
2000
57
57
53
54
55
56
4000
56
56
49
50
51
52
8000
54
54
45
47
47
48
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
128
Johnson Controls Unitary Products
5123247-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA5 / 5 Ton / High Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Horizontal (Side Return) Ducted Inlet
1,012- 5.5 Turns Open Equivalent
1,134 - 3 Turns Open Equivalent
1,174 - 2 Turns Open Equivalent
1.0
1.6
2.0
Nominal Airflow (CFM)
2,000
1,800
1,600
Blower Motor BHP
1.04
1.25
External Static Pressure (IWG)
1.39
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
76
78
78
79
79
81
125
70
73
73
76
74
77
250
68
70
68
69
69
70
500
61
62
61
62
60
62
1000
61
62
61
62
58
60
2000
57
58
57
58
54
56
4000
56
56
55
56
52
53
8000
50
50
50
50
47
48
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Indoor Sound Power Levels (Horizontal Ducted Discharge, High Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA3 / 3 Ton / High Static Belt Drive
Horizontal (Side Supply) Ducted Discharge
TEST CONFIGURATION
896 - 3.5 Turns Open Equivalent
1,072 - Fully Closed Equivalent
1,170 - 2.5 Turns Open Equivalent1
1.0
1.6
2.0 1
Nominal Airflow (CFM)
1,200
1,100
1,000
Blower Motor BHP
0.64
0.93
1.08
Indoor Blower Speed (RPM)
External Static Pressure (IWG)
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
63
77
81
83
84
83
84
125
74
76
76
77
80
80
250
67
68
70
70
72
73
500
65
66
67
67
67
68
1000
61
62
67
67
66
69
2000
58
60
63
63
63
64
4000
57
59
62
62
62
63
8000
51
53
56
57
56
58
1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.
2. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Johnson Controls Unitary Products
129
5123247-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA4 / 4 Ton / High Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Horizontal (Side Supply) Ducted Discharge
922 - 6 Turns Open Equivalent
1,069 - 4 Turns Open Equivalent
1,165 - 2.5 Turns Open Equivalent
1.0
1.6
2.0
Nominal Airflow (CFM)
1,600
1,400
1,200
Blower Motor BHP
0.86
1.03
External Static Pressure (IWG)
1.13
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
80
82
82
83
84
84
125
76
77
76
77
78
79
250
71
72
72
72
74
74
500
69
69
69
69
70
70
1000
65
65
69
69
70
70
2000
64
64
64
64
65
65
4000
63
63
63
63
64
64
8000
58
58
58
58
59
59
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA5 / 5 Ton / High Static Belt Drive
Horizontal (Side Supply) Ducted Discharge
TEST CONFIGURATION
Indoor Blower Speed (RPM)
1,009- 5.5 Turns Open Equivalent
1,131 - 3 Turns Open Equivalent
1.0
1.6
2.0
2,000
1,800
1,600
External Static Pressure (IWG)
Nominal Airflow (CFM)
Blower Motor BHP
Octave Center Freq. Hz
1.04
ID Blower
Only (dB)
1,184 - 2 Turns Open Equivalent
1.25
Cooling
Operation1 (dB)
ID Blower
Only (dB)
1.39
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
84
85
82
83
82
83
125
78
79
79
79
78
79
250
75
75
74
75
73
73
500
71
71
70
71
69
69
1000
69
69
71
71
71
72
2000
66
67
67
67
66
66
4000
66
66
66
67
66
66
8000
61
62
61
62
60
60
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
130
Johnson Controls Unitary Products
5123247-TTG-A-0515
Indoor Sound Power Levels (Vertical Ducted Inlet, High Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA3 / 3 Ton / High Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Return) Ducted Inlet
927 - 3 Turns Open Equivalent
1,085 - 1/2 Turn Open Equivalent
1,190 - 2.5 Turns Open Equivalent1
1.0
1.6
2.01
Nominal Airflow (CFM)
1,200
1,100
1,000
Blower Motor BHP
0.68
0.93
1.09
Indoor Blower Speed (RPM)
External Static Pressure (IWG)
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
63
77
79
82
83
79
81
125
68
69
70
71
72
73
250
60
67
62
69
64
67
500
58
58
63
63
62
63
1000
54
55
60
60
60
60
2000
48
49
56
56
55
55
4000
43
44
48
49
51
51
8000
44
44
45
46
47
47
1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.
2. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA4 / 4 Ton / High Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Vertical (Bottom Return) Ducted Inlet
968 - 5.5 Turns Open Equivalent
1,120 - 3.5 Turns Open Equivalent
1,218 - 2.0 Turns Open Equivalent
1.0
1.6
2.0
Nominal Airflow (CFM)
1,600
1,400
1,200
Blower Motor BHP
0.86
1.03
1.13
External Static Pressure (IWG)
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
77
79
78
78
81
81
125
69
73
71
73
73
74
250
63
63
63
64
66
66
500
63
64
62
63
64
64
1000
59
59
59
59
61
61
2000
54
54
53
54
56
56
4000
49
49
48
48
50
51
8000
45
46
45
46
47
47
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Johnson Controls Unitary Products
131
5123247-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA5 / 5 Ton / High Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Vertical (Bottom Return) Ducted Inlet
1,039 - 5 Turns Open Equivalent
1,143 - 3 Turns Open Equivalent
1,201 - 2 Turns Open Equivalent
1.0
1.6
2.0
Nominal Airflow (CFM)
2,000
1,800
1,600
Blower Motor BHP
1.11
1.25
External Static Pressure (IWG)
1.39
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
79
80
77
77
81
81
125
74
75
71
73
73
74
250
63
65
63
64
63
65
500
62
63
64
64
62
62
1000
61
61
61
61
59
59
2000
55
56
55
56
54
55
4000
52
52
50
51
50
50
8000
47
47
46
46
46
46
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Indoor Sound Power Levels (Vertical Ducted Discharge, High Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA3 / 3 Ton / High Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Vertical (Bottom Supply) Ducted Discharge
920 - 3.0 Turns Open Equivalent
1,074 - Fully Closed Equivalent
1,189 - 2.0 Turns Open Equivalent1
1.0
1.6
2.01
1,200
1,100
1,000
External Static Pressure (IWG)
Nominal Airflow (CFM)
Blower Motor BHP
0.68
0.93
1.09
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
63
81
82
81
81
82
82
125
78
78
78
78
81
81
250
69
70
70
71
74
74
500
67
68
68
69
71
71
1000
62
63
67
68
70
71
2000
60
61
62
63
65
66
4000
61
61
63
63
66
66
8000
54
55
57
57
60
61
1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.
2. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
132
Johnson Controls Unitary Products
5123247-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA4 / 4 Ton / High Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Vertical (Bottom Supply) Ducted Discharge
962 - 5.5 Turns Open Equivalent
1,092 - 3.5 Turns Open Equivalent
1,190 - 2.0 Turns Open Equivalent
1.0
1.6
2.0
Nominal Airflow (CFM)
1,600
1,400
1,200
Blower Motor BHP
0.86
1.03
External Static Pressure (IWG)
1.13
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
83
84
82
82
83
83
125
80
81
79
80
80
81
250
75
75
74
75
75
75
500
71
72
70
71
71
72
1000
66
67
70
71
72
72
2000
63
64
64
64
65
65
4000
64
64
64
64
65
66
8000
58
59
59
59
60
60
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZU/ZW/ZKTA5 / 5 Ton / High Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Vertical (Bottom Supply) Ducted Discharge
1,033 - 5.5 Turns Open Equivalent
1,135 - 3 turns Open Equivalent
1.0
1.6
2.0
2,000
1,135
1,175
External Static Pressure (IWG)
Nominal Airflow (CFM)
Blower Motor BHP
1.11
1,175 - 2.5 Turns Open Equivalent
1.25
1.39
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
83
83
83
83
85
86
125
84
84
82
82
79
81
250
79
80
77
78
66
66
500
73
73
70
71
65
66
1000
69
70
69
70
61
65
2000
67
67
65
66
60
61
4000
67
68
66
67
61
62
8000
62
63
60
61
54
54
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Johnson Controls Unitary Products
133
5123247-TTG-A-0515
Indoor Sound Power Levels (6.5 thru 12.5 Ton)
Size
(Tons)
T06
(6.5)
T07
(7.5)
T08
(8.5)
T10
(10)
T12
(12.5)
Model
CFM
ESP
(IWG)
Blower
RPM
BHP
Sound Rating1
dB (A)
63
Sound Power, dB (10-12) Watts
Octave Band Centerline Frequency (Hz)
125
250
500
1000
2000
4000
8000
ZU/ZW/ZK
2600
0.6
812
1.14
74
71
73
73
71
69
65
65
60
ZU/ZW/ZK
3000
0.6
854
1.47
77
74
76
76
74
72
68
68
63
ZU/ZW/ZK
3400
0.6
872
1.65
80
77
79
79
77
75
71
71
66
ZU/ZW/ZK
4000
0.6
959
2.29
83
80
82
82
80
78
74
74
69
ZU/ZW/ZK
5000
0.6
1132
3.74
87
84
86
86
84
82
78
78
73
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings.
134
Johnson Controls Unitary Products
5123247-TTG-A-0515
Outdoor Sound Power Levels
ZH/ZJ/ZR0TA3 thru T12
Size
(Tons)
TA3
(3)
TA4
(4)
TA5
(5)
T06
(6.5)
T07
(7.5)
T08
(8.5)
T10
(10)
T12
(12.5)
TA3
(3)
TA4
(4)
TA5
(5)
T06
(6.5)
T07
(7.5)
T08
(8.5)
T10
(10)
T12
(12.5)
TA3
(3)
TA4
(4)
TA5
(5)
T06
(6.5)
T07
(7.5)
T08
(8.5)
T10
(10)
T12
(12.5)
Model
Sound Rating1
dB (A)
63
125
ZU
81
82.5
86.5
78.0
75.5
76.5
ZU
78
82.0
86.0
78.5
75.5
ZU
84
81.0
91.0
82.5
ZU
87
89.0
88.5
ZU
92
93.0
ZU
92
ZU
Octave Band Centerline Frequency (Hz)
250
500
1000
2000
4000
8000
68.5
63.0
56.5
73.0
68.0
63.0
56.0
80.5
79.0
73.5
69.5
64.5
84.5
84.5
82.0
76.5
72.0
66.5
92.0
90.5
88.0
86.5
83.0
77.5
73.5
97.0
94.0
93.5
90.5
87.0
81.5
76.0
69.0
91
99.5
91.5
91.5
89.0
86.0
80.5
76.5
71.0
ZU
86
89.5
91.0
85.5
84.0
81.0
76.5
71.0
62.5
ZW
77
82.0
83.5
80.0
73.0
70.0
65.5
60.5
55.5
ZW
80
80.0
87.0
77.0
75.5
75.0
70.5
65.5
62.0
ZW
84
86.5
87.0
86.0
79.0
76.5
71.5
68.0
64.0
ZW
85
87.5
85.0
84.0
82.0
80.0
75.5
71.5
67.0
ZW
90
90.0
93.0
90.5
86.0
83.5
81.5
78.0
75.0
ZW
92
97.0
94.0
93.5
90.5
87.0
81.5
76.0
69.0
ZW
91
99.5
91.5
91.5
89.0
86.0
80.5
76.5
71.0
ZW
85
89.0
88.0
83.5
83.5
78.5
74.0
69.5
64.5
ZK
77
82.0
83.5
80.0
73.0
70.0
65.5
60.5
55.5
ZK
81
87.5
88.5
83.0
77.5
73.5
70.5
67.0
62.0
ZK
84
86.5
87.0
86.0
79.0
76.5
71.5
68.0
64.0
ZK
83
~
88.0
82.5
81.5
78.0
73.0
69.0
62.0
ZK
83
~
89.5
83.5
82.0
78.0
72.5
68.0
60.5
ZK
83
~
89.0
84.5
81.5
78.0
72.5
68.5
70.5
ZK
83
~
89.5
83.5
81.0
78.0
72.0
68.5
70.5
ZK
84
~
90.0
84.5
81.5
77.5
72.0
68.5
61.5
1. Rated in accordance with AHRI 270 standard.
Johnson Controls Unitary Products
135
5123247-TTG-A-0515
Electrical Data
ZUTA3 thru TA5 Standard Indoor Blower - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
9.1
68.0
14.2
2.1
5.2
5.5
0.0
230
9.1
68.0
14.2
2.1
5.2
5.5
0.0
460
4.5
34.0
7.0
1.3
2.6
2.2
0.0
575
3.8
28.0
6.0
0.7
2.0
1.8
0.0
208
11.6
88.0
17.5
2.1
5.2
5.5
0.0
230
11.6
88.0
17.5
2.1
5.2
5.5
0.0
460
5.6
44.0
8.0
1.3
2.6
2.2
0.0
575
4.5
36.0
7.0
0.7
2.0
1.8
0.0
208
14.1
88.0
22.0
2.1
5.2
5.5
0.0
230
14.1
88.0
22.0
2.1
5.2
5.5
0.0
460
7.7
55.0
12.0
1.3
2.6
2.2
0.0
575
5.1
36.0
7.5
0.7
2.0
1.8
0.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA1
(Amps)
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
18.7
18.7
22.1
30.1
45.7
18.7
18.7
24.5
33.6
51.6
9.5
9.5
12.3
16.8
25.8
7.4
13.3
20.5
21.8
22.1
30.1
45.7
58.5
21.8
24.5
33.6
51.6
66.6
10.9
12.3
16.8
25.8
33.3
8.3
13.3
20.5
26.6
27.0
27.0
30.1
45.7
58.5
69.0
27.0
27.0
33.6
51.6
66.6
78.7
14.7
14.7
16.8
25.8
33.3
39.3
9.7
13.3
20.5
26.6
31.4
MCA1
w/Pwr
Exh
(Amps)
24.2
24.2
29.0
37.0
52.6
24.2
24.2
31.4
40.4
58.5
11.7
11.7
15.0
19.5
28.6
9.2
15.6
22.8
27.3
29.0
37.0
52.6
65.4
27.3
31.4
40.4
58.5
73.5
13.1
15.0
19.5
28.6
36.1
10.1
15.6
22.8
28.8
32.5
32.5
37.0
52.6
65.4
75.8
32.5
32.5
40.4
58.5
73.5
85.5
16.9
16.9
19.5
28.6
36.1
42.1
11.5
15.6
22.8
28.8
33.6
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
25
30
25
30
25
30
35
40
50
60
25
30
25
30
25
35
35
45
60
60
15
15
15
15
15
15
20
20
30
30
15
15
15
20
25
25
30
35
30
35
35
40
50
60
60
70
30
35
30
35
35
45
60
60
70
80
15
15
15
15
20
20
30
30
35
40
15
15
15
20
25
25
30
30
35
45
35
45
40
45
50
60
60
70
70
80
35
45
35
45
40
45
60
60
70
80
80
90
20
20
20
20
20
20
30
30
35
40
40
45
15
15
15
20
25
25
30
30
35
35
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
136
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUT06 thru T12 Standard Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
9.6
68.0
14.5
2.1
5.2
5.5
0.0
230
9.6
68.0
14.5
2.1
5.2
5.5
0.0
460
4.9
34.0
7.7
1.3
2.6
2.2
0.0
575
3.8
28.0
6.0
0.7
2.0
1.8
0.0
208
11.9
88.0
18.5
3.0
5.2
5.5
0.0
230
11.9
88.0
18.5
3.0
5.2
5.5
0.0
460
5.2
44.0
8.1
1.6
2.6
2.2
0.0
575
4.8
36.0
7.5
1.4
2.0
1.8
0.0
208
12.2
88.0
19.0
3.0
6.8
5.5
0.0
230
12.2
88.0
19.0
3.0
6.8
5.5
0.0
460
5.8
44.0
9.0
1.6
3.4
2.2
0.0
575
4.4
36.0
5.5
1.4
2.4
1.8
0.0
T06
(6.5)
T07
(7.5)
T08
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
Stages
Amps
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
31.0
31.0
53.3
69.0
95.0
31.0
33.6
60.6
78.7
108.7
16.1
16.8
30.3
39.3
54.4
11.9
13.3
24.2
31.4
43.4
38.0
38.0
53.3
69.0
95.0
38.0
38.0
60.6
78.7
108.7
17.5
17.5
30.3
39.3
54.4
15.5
15.5
24.2
31.4
43.4
40.3
40.3
55.3
71.0
97.0
40.3
40.3
62.6
80.7
110.7
19.7
19.7
31.3
40.3
55.4
15.0
15.0
24.7
31.9
43.9
36.5
37.0
60.2
75.8
101.9
36.5
40.4
67.5
85.5
115.6
18.3
19.5
33.1
42.1
57.1
13.7
15.6
26.4
33.6
45.6
43.5
43.5
60.2
75.8
101.9
43.5
43.5
67.5
85.5
115.6
19.7
19.7
33.1
42.1
57.1
17.3
17.3
26.4
33.6
45.6
45.8
45.8
62.2
77.8
103.9
45.8
45.8
69.5
87.5
117.6
21.9
21.9
34.1
43.1
58.1
16.8
16.8
26.9
34.1
46.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
40
45
40
45
60
70
70
80
100
110
40
45
40
45
70
70
80
90
110
125
20
20
20
20
35
35
40
45
60
60
15
15
15
20
25
30
35
35
45
50
45
50
45
50
60
70
70
80
100
110
45
50
45
50
70
70
80
90
110
125
20
20
20
20
35
35
40
45
60
60
20
20
20
20
25
30
35
35
45
50
50
50
50
50
60
70
80
80
100
110
50
50
50
50
70
70
90
90
125
125
25
25
25
25
35
35
45
45
60
60
15
20
15
20
25
30
35
35
45
50
137
5123247-TTG-A-0515
ZUT06 thru T12 Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
3.0
6.8
5.5
0.0
230
16.0 110.0 24.9
3.0
6.8
5.5
0.0
460
7.8
52.0
12.1
1.6
3.4
2.2
0.0
575
5.7
38.9
8.9
1.4
2.4
1.8
0.0
208
23.1 160.0 36.0
2.1
9.6
5.5
0.0
230
23.1 160.0 36.0
2.1
9.6
5.5
0.0
460
12.2
87.0
19.0
1.3
4.7
2.2
0.0
575
8.7
62.0
13.5
0.7
3.6
1.8
0.0
T10
(10)
T12
(12.5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
48.9
55.3
71.0
97.0
149.4
48.9
62.6
80.7
110.7
138.4
24.2
31.3
40.3
55.4
69.2
17.9
24.7
31.9
43.9
55.0
70.0
70.0
74.5
100.5
152.9
70.0
70.0
84.2
114.2
141.9
37.2
37.2
42.0
57.0
70.8
25.8
26.2
33.4
45.4
56.5
54.4
62.2
77.8
103.9
156.2
54.4
69.5
87.5
117.6
145.3
26.4
34.1
43.1
58.1
72.0
19.7
26.9
34.1
46.1
57.2
75.5
75.5
81.3
107.4
159.7
75.5
75.5
91.0
121.1
148.8
39.4
39.4
44.7
59.7
73.6
27.6
28.4
35.6
47.6
58.7
1
Model
kW
Stages
Amps
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
60
70
60
70
80
80
100
110
150
175
60
70
70
70
90
90
125
125
150
175
30
30
35
35
45
45
60
60
80
80
20
25
25
30
35
35
45
50
60
60
90
90
90
90
90
90
110
110
175
175
90
90
90
90
90
100
125
125
175
175
45
50
45
50
45
50
60
60
80
80
30
35
30
35
35
40
50
50
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
138
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUTA3 thru TA5 Hi Static Indoor Blower - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
9.1
68.0
14.2
2.1
5.2
5.5
0.0
230
9.1
68.0
14.2
2.1
5.2
5.5
0.0
460
4.5
34.0
7.0
1.3
2.6
2.2
0.0
575
3.8
28.0
6.0
0.7
2.0
1.8
0.0
208
11.6
88.0
17.5
2.1
5.2
5.5
0.0
230
11.6
88.0
17.5
2.1
5.2
5.5
0.0
460
5.6
44.0
8.0
1.3
2.6
2.2
0.0
575
4.5
36.0
7.0
0.7
2.0
1.8
0.0
208
14.1
88.0
22.0
2.1
6.8
5.5
0.0
230
14.1
88.0
22.0
2.1
6.8
5.5
0.0
460
7.7
55.0
12.0
1.3
3.4
2.2
0.0
575
5.1
36.0
7.5
0.7
2.4
1.8
0.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
18.7
18.7
22.1
30.1
45.7
18.7
18.7
24.5
33.6
51.6
9.5
9.5
12.3
16.8
25.8
7.4
13.3
20.5
21.8
22.1
30.1
45.7
58.5
21.8
24.5
33.6
51.6
66.6
10.9
12.3
16.8
25.8
33.3
8.3
13.3
20.5
26.6
28.6
28.6
32.1
47.7
60.5
71.0
28.6
28.6
35.6
53.6
68.6
80.7
15.5
15.5
17.8
26.8
34.3
40.3
10.1
13.8
21.0
27.1
31.9
24.2
24.2
29.0
37.0
52.6
24.2
24.2
31.4
40.4
58.5
11.7
11.7
15.0
19.5
28.6
9.2
15.6
22.8
27.3
29.0
37.0
52.6
65.4
27.3
31.4
40.4
58.5
73.5
13.1
15.0
19.5
28.6
36.1
10.1
15.6
22.8
28.8
34.1
34.1
39.0
54.6
67.4
77.8
34.1
34.1
42.4
60.5
75.5
87.5
17.7
17.7
20.5
29.6
37.1
43.1
11.9
16.1
23.3
29.3
34.1
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
25
30
25
30
25
30
35
40
50
60
25
30
25
30
25
35
35
45
60
60
15
15
15
15
15
15
20
20
30
30
15
15
15
20
25
25
30
35
30
35
35
40
50
60
60
70
30
35
30
35
35
45
60
60
70
80
15
15
15
15
20
20
30
30
35
40
15
15
15
20
25
25
30
30
40
45
40
45
40
45
50
60
70
70
80
80
40
45
40
45
40
45
60
70
70
80
90
90
20
25
20
25
20
25
30
30
35
40
45
45
15
15
15
20
25
25
30
30
35
35
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
139
5123247-TTG-A-0515
ZUT06 thru T12 Hi Static Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
9.6
68.0
14.5
2.1
6.8
5.5
0.0
230
9.6
68.0
14.5
2.1
6.8
5.5
0.0
460
4.9
34.0
7.7
1.3
3.4
2.2
0.0
575
3.8
28.0
6.0
0.7
2.4
1.8
0.0
208
11.9
88.0
18.5
3.0
9.6
5.5
0.0
230
11.9
88.0
18.5
3.0
9.6
5.5
0.0
460
5.2
44.0
8.1
1.6
4.7
2.2
0.0
575
4.8
36.0
7.5
1.4
3.6
1.8
0.0
208
12.2
88.0
19.0
3.0
9.6
5.5
0.0
230
12.2
88.0
19.0
3.0
9.6
5.5
0.0
460
5.8
44.0
9.0
1.6
4.7
2.2
0.0
575
4.4
36.0
5.5
1.4
3.6
1.8
0.0
T06
(6.5)
T07
(7.5)
T08
(8.5)
140
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
32.6
32.6
55.3
71.0
97.0
32.6
35.6
62.6
80.7
110.7
16.9
17.8
31.3
40.3
55.4
12.3
13.8
24.7
31.9
43.9
42.4
42.4
58.8
74.5
100.5
42.4
42.4
66.1
84.2
114.2
19.6
19.6
32.9
42.0
57.0
17.1
17.1
26.2
33.4
45.4
43.1
43.1
58.8
74.5
100.5
43.1
43.1
66.1
84.2
114.2
21.0
21.0
32.9
42.0
57.0
16.2
16.2
26.2
33.4
45.4
38.1
39.0
62.2
77.8
103.9
38.1
42.4
69.5
87.5
117.6
19.1
20.5
34.1
43.1
58.1
14.1
16.1
26.9
34.1
46.1
47.9
47.9
65.7
81.3
107.4
47.9
47.9
73.0
91.0
121.1
21.8
22.2
35.7
44.7
59.7
18.9
18.9
28.4
35.6
47.6
48.6
48.6
65.7
81.3
107.4
48.6
48.6
73.0
91.0
121.1
23.2
23.2
35.7
44.7
59.7
18.0
18.0
28.4
35.6
47.6
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
40
45
40
45
60
70
80
80
100
110
40
45
40
45
70
70
90
90
125
125
20
20
20
25
35
35
45
45
60
60
15
15
15
20
25
30
35
35
45
50
50
50
50
50
60
70
80
90
110
110
50
50
50
50
70
80
90
100
125
125
20
25
20
25
35
40
45
45
60
60
20
20
20
20
30
30
35
40
50
50
50
60
50
60
60
70
80
90
110
110
50
60
50
60
70
80
90
100
125
125
25
25
25
25
35
40
45
45
60
60
20
20
20
20
30
30
35
40
50
50
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUT06 thru T12 Hi Static Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
3.0
9.6
5.5
0.0
230
16.0 110.0 24.9
3.0
9.6
5.5
0.0
460
7.8
52.0
12.1
1.6
4.7
2.2
0.0
575
5.7
38.9
8.9
1.4
3.6
1.8
0.0
208
23.1 160.0 36.0
2.1
14.0
5.5
0.0
230
23.1 160.0 36.0
2.1
14.0
5.5
0.0
460
12.2
87.0
19.0
1.3
6.6
2.2
0.0
575
8.7
62.0
13.5
0.7
5.2
1.8
0.0
T10
(10)
T12
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
51.7
58.8
74.5
100.5
152.9
51.7
66.1
84.2
114.2
141.9
25.5
32.9
42.0
57.0
70.8
19.1
26.2
33.4
45.4
56.5
74.4
74.4
80.0
106.0
158.4
74.4
74.4
89.7
119.7
147.4
39.1
39.1
44.3
59.4
73.2
27.4
28.2
35.4
47.4
58.5
57.2
65.7
81.3
107.4
159.7
57.2
73.0
91.0
121.1
148.8
27.7
35.7
44.7
59.7
73.6
20.9
28.4
35.6
47.6
58.7
79.9
79.9
86.8
112.9
165.2
79.9
79.9
96.5
126.6
154.3
41.3
41.3
47.1
62.1
76.0
29.2
30.4
37.6
49.6
60.7
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
60
70
80
90
110
110
175
175
60
70
70
80
90
100
125
125
175
175
30
35
35
40
45
45
60
60
80
80
20
25
30
30
35
40
50
50
70
70
90
100
90
100
90
100
110
125
175
175
90
100
90
100
90
100
125
150
175
175
50
50
50
50
50
50
60
70
80
90
35
35
35
35
40
40
50
50
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
141
5123247-TTG-A-0515
ZUTA3 thru TA5 Standard Indoor Blower - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
9.1
68.0
14.2
2.1
5.2
5.5
10.0
230
9.1
68.0
14.2
2.1
5.2
5.5
10.0
460
4.5
34.0
7.0
1.3
2.6
2.2
5.0
575
3.8
28.0
6.0
0.7
2.0
1.8
4.0
208
11.6
88.0
17.5
2.1
5.2
5.5
10.0
230
11.6
88.0
17.5
2.1
5.2
5.5
10.0
460
5.6
44.0
8.0
1.3
2.6
2.2
5.0
575
4.5
36.0
7.0
0.7
2.0
1.8
4.0
208
14.1
88.0
22.0
2.1
5.2
5.5
10.0
230
14.1
88.0
22.0
2.1
5.2
5.5
10.0
460
7.7
55.0
12.0
1.3
2.6
2.2
5.0
575
5.1
36.0
7.5
0.7
2.0
1.8
4.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
28.9
28.9
34.6
42.6
58.2
28.9
28.9
37.0
46.1
64.1
14.6
14.6
18.5
23.0
32.1
11.5
18.3
25.5
31.8
34.6
42.6
58.2
71.0
31.8
37.0
46.1
64.1
79.1
15.9
18.5
23.0
32.1
39.6
12.3
18.3
25.5
31.6
37.0
37.0
42.6
58.2
71.0
81.5
37.0
37.0
46.1
64.1
79.1
91.2
19.7
19.7
23.0
32.1
39.6
45.6
13.7
18.3
25.5
31.6
36.4
34.4
34.4
41.5
49.5
65.1
34.4
34.9
43.9
52.9
71.0
16.8
16.8
21.3
25.8
34.8
13.3
20.6
27.8
37.3
41.5
49.5
65.1
77.9
37.3
43.9
52.9
71.0
86.0
18.1
21.3
25.8
34.8
42.3
14.1
20.6
27.8
33.8
42.5
42.5
49.5
65.1
77.9
88.3
42.5
43.9
52.9
71.0
86.0
98.0
21.9
21.9
25.8
34.8
42.3
48.3
15.5
20.6
27.8
33.8
38.6
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
35
40
35
40
40
45
45
50
60
70
35
40
35
40
40
45
50
60
70
80
15
20
15
20
20
25
25
30
35
35
15
15
20
25
30
30
40
45
40
45
45
50
60
70
80
80
40
45
40
45
50
60
70
80
80
90
20
20
20
25
25
30
35
35
40
45
15
15
20
25
30
30
35
35
50
50
50
50
50
50
60
70
80
80
90
90
50
50
50
50
50
60
70
80
80
90
100
100
25
25
25
25
25
30
35
35
40
45
50
50
15
20
20
25
30
30
35
35
40
40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
142
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUT06 thru T12 Standard Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
9.6
68.0
14.5
2.1
5.2
5.5
10.0
230
9.6
68.0
14.5
2.1
5.2
5.5
10.0
460
4.9
34.0
7.7
1.3
2.6
2.2
5.0
575
3.8
28.0
6.0
0.7
2.0
1.8
4.0
208
11.9
88.0
18.5
3.0
5.2
5.5
10.0
230
11.9
88.0
18.5
3.0
5.2
5.5
10.0
460
5.2
44.0
8.1
1.6
2.6
2.2
5.0
575
4.8
36.0
7.5
1.4
2.0
1.8
4.0
208
12.2
88.0
19.0
3.0
6.8
5.5
10.0
230
12.2
88.0
19.0
3.0
6.8
5.5
10.0
460
5.8
44.0
9.0
1.6
3.4
2.2
5.0
575
4.4
36.0
5.5
1.4
2.4
1.8
4.0
T06
(6.5)
T07
(7.5)
T08
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
41.1
42.6
65.8
81.5
107.5
41.1
46.1
73.1
91.2
121.2
21.2
23.0
36.6
45.6
60.6
15.9
18.3
29.2
36.4
48.4
48.0
48.0
65.8
81.5
107.5
48.0
48.0
73.1
91.2
121.2
22.5
23.0
36.6
45.6
60.6
19.5
19.5
29.2
36.4
48.4
50.3
50.3
67.8
83.5
109.5
50.3
50.3
75.1
93.2
123.2
24.7
24.7
37.6
46.6
61.6
19.0
19.0
29.7
36.9
48.9
46.6
49.5
72.7
88.3
114.4
46.6
52.9
80.0
98.0
128.1
23.4
25.8
39.3
48.3
63.4
17.7
20.6
31.4
38.6
50.6
53.5
53.5
72.7
88.3
114.4
53.5
53.5
80.0
98.0
128.1
24.7
25.8
39.3
48.3
63.4
21.3
21.3
31.4
38.6
50.6
55.8
55.8
74.7
90.3
116.4
55.8
55.8
82.0
100.0
130.1
26.9
26.9
40.3
49.3
64.4
20.8
21.1
31.9
39.1
51.1
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
50
50
50
70
80
90
90
110
125
50
50
50
60
80
80
100
100
125
150
25
25
25
30
40
40
50
50
70
70
20
20
20
25
30
35
40
40
50
60
50
60
50
60
70
80
90
90
110
125
50
60
50
60
80
80
100
100
125
150
25
25
25
30
40
40
50
50
70
70
20
25
20
25
30
35
40
40
50
60
60
60
60
60
70
80
90
100
110
125
60
60
60
60
80
90
100
100
125
150
30
30
30
30
40
45
50
50
70
70
20
25
20
25
30
35
40
40
50
60
143
5123247-TTG-A-0515
ZUT06 thru T12 Standard Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
3.0
6.8
5.5
10.0
230
16.0 110.0 24.9
3.0
6.8
5.5
10.0
460
7.8
52.0
12.1
1.6
3.4
2.2
5.0
575
5.7
38.9
8.9
1.4
2.4
1.8
4.0
208
23.1 160.0 36.0
2.1
9.6
5.5
10.0
230
23.1 160.0 36.0
2.1
9.6
5.5
10.0
460
12.2
87.0
19.0
1.3
4.7
2.2
5.0
575
8.7
62.0
13.5
0.7
3.6
1.8
4.0
T10
(10)
T12
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
58.9
67.8
83.5
109.5
161.9
58.9
75.1
93.2
123.2
150.9
29.2
37.6
46.6
61.6
75.5
21.9
29.7
36.9
48.9
60.0
80.0
80.0
87.0
113.0
165.4
80.0
80.0
96.7
126.7
154.4
42.2
42.2
48.2
63.2
77.1
29.8
31.2
38.4
50.4
61.5
64.4
74.7
90.3
116.4
168.7
64.4
82.0
100.0
130.1
157.8
31.4
40.3
49.3
64.4
78.2
23.7
31.9
39.1
51.1
62.2
85.5
85.5
93.8
119.9
172.2
85.5
85.5
103.5
133.6
161.3
44.4
44.4
51.0
66.0
79.8
31.6
33.4
40.6
52.6
63.7
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
70
80
90
100
110
125
175
175
70
80
80
90
100
100
125
150
175
175
35
35
40
45
50
50
70
70
80
90
25
25
30
35
40
40
50
60
70
70
100
100
100
100
100
100
125
125
175
175
100
100
100
100
100
110
150
150
175
175
50
50
50
50
50
60
70
70
90
90
35
40
35
40
40
45
60
60
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
144
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUTA3 thru TA5 Hi Static Indoor Blower - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
9.1
68.0
14.2
2.1
5.2
5.5
10.0
230
9.1
68.0
14.2
2.1
5.2
5.5
10.0
460
4.5
34.0
7.0
1.3
2.6
2.2
5.0
575
3.8
28.0
6.0
0.7
2.0
1.8
4.0
208
11.6
88.0
17.5
2.1
5.2
5.5
10.0
230
11.6
88.0
17.5
2.1
5.2
5.5
10.0
460
5.6
44.0
8.0
1.3
2.6
2.2
5.0
575
4.5
36.0
7.0
0.7
2.0
1.8
4.0
208
14.1
88.0
22.0
2.1
6.8
5.5
10.0
230
14.1
88.0
22.0
2.1
6.8
5.5
10.0
460
7.7
55.0
12.0
1.3
3.4
2.2
5.0
575
5.1
36.0
7.5
0.7
2.4
1.8
4.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
28.9
28.9
34.6
42.6
58.2
28.9
28.9
37.0
46.1
64.1
14.6
14.6
18.5
23.0
32.1
11.5
18.3
25.5
31.8
34.6
42.6
58.2
71.0
31.8
37.0
46.1
64.1
79.1
15.9
18.5
23.0
32.1
39.6
12.3
18.3
25.5
31.6
38.6
38.6
44.6
60.2
73.0
83.5
38.6
39.0
48.1
66.1
81.1
93.2
20.5
20.5
24.0
33.1
40.6
46.6
14.1
18.8
26.0
32.1
36.9
34.4
34.4
41.5
49.5
65.1
34.4
34.9
43.9
52.9
71.0
16.8
16.8
21.3
25.8
34.8
13.3
20.6
27.8
37.3
41.5
49.5
65.1
77.9
37.3
43.9
52.9
71.0
86.0
18.1
21.3
25.8
34.8
42.3
14.1
20.6
27.8
33.8
44.1
44.1
51.5
67.1
79.9
90.3
44.1
45.9
54.9
73.0
88.0
100.0
22.7
22.7
26.8
35.8
43.3
49.3
15.9
21.1
28.3
34.3
39.1
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
35
40
35
40
40
45
45
50
60
70
35
40
35
40
40
45
50
60
70
80
15
20
15
20
20
25
25
30
35
35
15
15
20
25
30
30
40
45
40
45
45
50
60
70
80
80
40
45
40
45
50
60
70
80
80
90
20
20
20
25
25
30
35
35
40
45
15
15
20
25
30
30
35
35
50
50
50
50
50
60
70
70
80
80
90
100
50
50
50
50
50
60
70
80
90
90
100
100
25
30
25
30
25
30
35
40
45
45
50
50
15
20
20
25
30
30
35
35
40
40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
145
5123247-TTG-A-0515
ZUT06 thru T12 Hi Static Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
9.6
68.0
14.5
2.1
6.8
5.5
10.0
230
9.6
68.0
14.5
2.1
6.8
5.5
10.0
460
4.9
34.0
7.7
1.3
3.4
2.2
5.0
575
3.8
28.0
6.0
0.7
2.4
1.8
4.0
208
11.9
88.0
18.5
3.0
9.6
5.5
10.0
230
11.9
88.0
18.5
3.0
9.6
5.5
10.0
460
5.2
44.0
8.1
1.6
4.7
2.2
5.0
575
4.8
36.0
7.5
1.4
3.6
1.8
4.0
208
12.2
88.0
19.0
3.0
9.6
5.5
10.0
230
12.2
88.0
19.0
3.0
9.6
5.5
10.0
460
5.8
44.0
9.0
1.6
4.7
2.2
5.0
575
4.4
36.0
5.5
1.4
3.6
1.8
4.0
T06
(6.5)
T07
(7.5)
T08
(8.5)
146
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
42.7
44.6
67.8
83.5
109.5
42.7
48.1
75.1
93.2
123.2
22.0
24.0
37.6
46.6
61.6
16.3
18.8
29.7
36.9
48.9
52.4
52.4
71.3
87.0
113.0
52.4
52.4
78.6
96.7
126.7
24.6
25.7
39.2
48.2
63.2
21.1
21.1
31.2
38.4
50.4
53.1
53.1
71.3
87.0
113.0
53.1
53.1
78.6
96.7
126.7
26.0
26.0
39.2
48.2
63.2
20.2
20.3
31.2
38.4
50.4
48.2
51.5
74.7
90.3
116.4
48.2
54.9
82.0
100.0
130.1
24.2
26.8
40.3
49.3
64.4
18.1
21.1
31.9
39.1
51.1
57.9
57.9
78.2
93.8
119.9
57.9
58.4
85.5
103.5
133.6
26.8
28.4
41.9
51.0
66.0
22.9
22.9
33.4
40.6
52.6
58.6
58.6
78.2
93.8
119.9
58.6
58.6
85.5
103.5
133.6
28.2
28.4
41.9
51.0
66.0
22.0
22.6
33.4
40.6
52.6
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
50
50
60
70
80
90
100
110
125
50
50
50
60
80
90
100
100
125
150
25
25
25
30
40
45
50
50
70
70
20
20
20
25
30
35
40
40
50
60
60
60
60
60
80
80
90
100
125
125
60
60
60
60
80
90
100
110
150
150
25
30
30
30
40
45
50
60
70
70
25
25
25
25
35
35
40
45
60
60
60
70
60
70
80
80
90
100
125
125
60
70
60
70
80
90
100
110
150
150
30
30
30
30
40
45
50
60
70
70
25
25
25
25
35
35
40
45
60
60
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZUT06 thru T12 Hi Static Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
3.0
9.6
5.5
10.0
230
16.0 110.0 24.9
3.0
9.6
5.5
10.0
460
7.8
52.0
12.1
1.6
4.7
2.2
5.0
575
5.7
38.9
8.9
1.4
3.6
1.8
4.0
208
23.1 160.0 36.0
2.1
14.0
5.5
10.0
230
23.1 160.0 36.0
2.1
14.0
5.5
10.0
460
12.2
87.0
19.0
1.3
6.6
2.2
5.0
575
8.7
62.0
13.5
0.7
5.2
1.8
4.0
T10
(10)
T12
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
61.7
71.3
87.0
113.0
165.4
61.7
78.6
96.7
126.7
154.4
30.5
39.2
48.2
63.2
77.1
23.1
31.2
38.4
50.4
61.5
84.4
84.4
92.5
118.5
170.9
84.4
84.4
102.2
132.2
159.9
44.1
44.1
50.6
65.6
79.5
31.4
33.2
40.4
52.4
63.5
67.2
78.2
93.8
119.9
172.2
67.2
85.5
103.5
133.6
161.3
32.7
41.9
51.0
66.0
79.8
24.9
33.4
40.6
52.6
63.7
89.9
89.9
99.3
125.4
177.7
89.9
91.0
109.0
139.1
166.8
46.3
46.3
53.3
68.4
82.2
33.2
35.4
42.6
54.6
65.7
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
80
80
90
100
125
125
175
175
70
80
80
90
100
110
150
150
175
175
35
40
40
45
50
60
70
70
90
90
25
30
35
35
40
45
60
60
70
70
100
110
100
110
100
110
125
150
175
200
100
110
100
110
110
110
150
150
175
175
50
50
50
50
60
60
70
70
90
90
40
40
40
40
45
45
60
60
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
147
5123247-TTG-A-0515
ZWTA3 thru TA5 Standard Indoor Blower - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
8.7
68.0
13.5
2.1
5.2
5.5
0.0
230
8.7
68.0
13.5
2.1
5.2
5.5
0.0
460
4.6
34.0
7.1
1.3
2.6
2.2
0.0
575
3.5
28.0
5.5
0.7
2.0
1.8
0.0
208
11.2
88.0
17.5
2.1
5.2
5.5
0.0
230
11.2
88.0
17.5
2.1
5.2
5.5
0.0
460
5.6
44.0
8.0
1.3
2.6
2.2
0.0
575
4.5
36.0
7.0
0.7
2.0
1.8
0.0
208
14.1
88.0
22.0
2.1
5.2
5.5
0.0
230
14.1
88.0
22.0
2.1
5.2
5.5
0.0
460
7.7
55.0
12.0
1.3
2.6
2.2
0.0
575
5.1
36.0
7.5
0.7
2.0
1.8
0.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
18.2
18.2
22.1
30.1
45.7
18.2
18.2
24.5
33.6
51.6
9.6
9.6
12.3
16.8
25.8
7.0
13.3
20.5
21.3
22.1
30.1
45.7
58.5
21.3
24.5
33.6
51.6
66.6
10.9
12.3
16.8
25.8
33.3
8.3
13.3
20.5
26.6
27.0
27.0
30.1
45.7
58.5
69.0
27.0
27.0
33.6
51.6
66.6
78.7
14.7
14.7
16.8
25.8
33.3
39.3
9.7
13.3
20.5
26.6
31.4
23.7
23.7
29.0
37.0
52.6
23.7
23.7
31.4
40.4
58.5
11.8
11.8
15.0
19.5
28.6
8.8
15.6
22.8
26.8
29.0
37.0
52.6
65.4
26.8
31.4
40.4
58.5
73.5
13.1
15.0
19.5
28.6
36.1
10.1
15.6
22.8
28.8
32.5
32.5
37.0
52.6
65.4
75.8
32.5
32.5
40.4
58.5
73.5
85.5
16.9
16.9
19.5
28.6
36.1
42.1
11.5
15.6
22.8
28.8
33.6
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
25
30
25
30
25
30
35
40
50
60
25
30
25
30
25
35
35
45
60
60
15
15
15
15
15
15
20
20
30
30
15
15
15
20
25
25
30
35
30
35
35
40
50
60
60
70
30
35
30
35
35
45
60
60
70
80
15
15
15
15
20
20
30
30
35
40
15
15
15
20
25
25
30
30
35
45
35
45
40
45
50
60
60
70
70
80
35
45
35
45
40
45
60
60
70
80
80
90
20
20
20
20
20
20
30
30
35
40
40
45
15
15
15
20
25
25
30
30
35
35
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
148
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWT06 thru T12 Standard Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
9.3
68.0
14.5
2.1
5.2
5.5
0.0
230
9.3
68.0
14.5
2.1
5.2
5.5
0.0
460
4.9
34.0
7.6
1.3
2.6
2.2
0.0
575
3.8
28.0
6.0
0.7
2.0
1.8
0.0
208
11.9
88.0
18.5
3.0
5.2
5.5
0.0
230
11.9
88.0
18.5
3.0
5.2
5.5
0.0
460
5.2
44.0
8.1
1.6
2.6
2.2
0.0
575
4.8
36.0
7.5
1.4
2.0
1.8
0.0
208
12.2
88.0
19.0
3.0
6.8
5.5
0.0
230
12.2
88.0
19.0
3.0
6.8
5.5
0.0
460
5.8
44.0
9.0
1.6
3.4
2.2
0.0
575
4.4
36.0
5.5
1.4
2.4
1.8
0.0
T06
(6.5)
T07
(7.5)
T08
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
30.3
30.3
53.3
69.0
95.0
30.3
33.6
60.6
78.7
108.7
16.1
16.8
30.3
39.3
54.4
11.9
13.3
24.2
31.4
43.4
38.0
38.0
53.3
69.0
95.0
38.0
38.0
60.6
78.7
108.7
17.5
17.5
30.3
39.3
54.4
15.5
15.5
24.2
31.4
43.4
40.3
40.3
55.3
71.0
97.0
40.3
40.3
62.6
80.7
110.7
19.7
19.7
31.3
40.3
55.4
15.0
15.0
24.7
31.9
43.9
35.8
37.0
60.2
75.8
101.9
35.8
40.4
67.5
85.5
115.6
18.3
19.5
33.1
42.1
57.1
13.7
15.6
26.4
33.6
45.6
43.5
43.5
60.2
75.8
101.9
43.5
43.5
67.5
85.5
115.6
19.7
19.7
33.1
42.1
57.1
17.3
17.3
26.4
33.6
45.6
45.8
45.8
62.2
77.8
103.9
45.8
45.8
69.5
87.5
117.6
21.9
21.9
34.1
43.1
58.1
16.8
16.8
26.9
34.1
46.1
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
35
45
35
45
60
70
70
80
100
110
35
45
35
45
70
70
80
90
110
125
20
20
20
20
35
35
40
45
60
60
15
15
15
20
25
30
35
35
45
50
45
50
45
50
60
70
70
80
100
110
45
50
45
50
70
70
80
90
110
125
20
20
20
20
35
35
40
45
60
60
20
20
20
20
25
30
35
35
45
50
50
50
50
50
60
70
80
80
100
110
50
50
50
50
70
70
90
90
125
125
25
25
25
25
35
35
45
45
60
60
15
20
15
20
25
30
35
35
45
50
149
5123247-TTG-A-0515
ZWT06 thru T12 Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
3.0
6.8
5.5
0.0
230
16.0 110.0 24.9
3.0
6.8
5.5
0.0
460
7.8
52.0
12.1
1.6
3.4
2.2
0.0
575
5.7
38.9
8.9
1.4
2.4
1.8
0.0
208
23.1 160.0 36.0
2.1
9.6
5.5
0.0
230
23.1 160.0 36.0
2.1
9.6
5.5
0.0
460
12.2
87.0
19.0
1.3
4.7
2.2
0.0
575
8.7
62.0
13.5
0.7
3.6
1.8
0.0
T10
(10)
T12
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
48.9
55.3
71.0
97.0
149.4
48.9
62.6
80.7
110.7
138.4
24.2
31.3
40.3
55.4
69.2
17.9
24.7
31.9
43.9
55.0
70.0
70.0
74.5
100.5
152.9
70.0
70.0
84.2
114.2
141.9
37.2
37.2
42.0
57.0
70.8
25.8
26.2
33.4
45.4
56.5
54.4
62.2
77.8
103.9
156.2
54.4
69.5
87.5
117.6
145.3
26.4
34.1
43.1
58.1
72.0
19.7
26.9
34.1
46.1
57.2
75.5
75.5
81.3
107.4
159.7
75.5
75.5
91.0
121.1
148.8
39.4
39.4
44.7
59.7
73.6
27.6
28.4
35.6
47.6
58.7
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
60
70
80
80
100
110
150
175
60
70
70
70
90
90
125
125
150
175
30
30
35
35
45
45
60
60
80
80
20
25
25
30
35
35
45
50
60
60
90
90
90
90
90
90
110
110
175
175
90
90
90
90
90
100
125
125
175
175
45
50
45
50
45
50
60
60
80
80
30
35
30
35
35
40
50
50
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
150
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWTA3 thru TA5 Hi Static Indoor Blower - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
8.7
68.0
13.5
2.1
5.2
5.5
0.0
230
8.7
68.0
13.5
2.1
5.2
5.5
0.0
460
4.6
34.0
7.1
1.3
2.6
2.2
0.0
575
3.5
28.0
5.5
0.7
2.0
1.8
0.0
208
11.2
88.0
17.5
2.1
5.2
5.5
0.0
230
11.2
88.0
17.5
2.1
5.2
5.5
0.0
460
5.6
44.0
8.0
1.3
2.6
2.2
0.0
575
4.5
36.0
7.0
0.7
2.0
1.8
0.0
208
14.1
88.0
22.0
2.1
6.8
5.5
0.0
230
14.1
88.0
22.0
2.1
6.8
5.5
0.0
460
7.7
55.0
12.0
1.3
3.4
2.2
0.0
575
5.1
36.0
7.5
0.7
2.4
1.8
0.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
18.2
18.2
22.1
30.1
45.7
18.2
18.2
24.5
33.6
51.6
9.6
9.6
12.3
16.8
25.8
7.0
13.3
20.5
21.3
22.1
30.1
45.7
58.5
21.3
24.5
33.6
51.6
66.6
10.9
12.3
16.8
25.8
33.3
8.3
13.3
20.5
26.6
28.6
28.6
32.1
47.7
60.5
71.0
28.6
28.6
35.6
53.6
68.6
80.7
15.5
15.5
17.8
26.8
34.3
40.3
10.1
13.8
21.0
27.1
31.9
23.7
23.7
29.0
37.0
52.6
23.7
23.7
31.4
40.4
58.5
11.8
11.8
15.0
19.5
28.6
8.8
15.6
22.8
26.8
29.0
37.0
52.6
65.4
26.8
31.4
40.4
58.5
73.5
13.1
15.0
19.5
28.6
36.1
10.1
15.6
22.8
28.8
34.1
34.1
39.0
54.6
67.4
77.8
34.1
34.1
42.4
60.5
75.5
87.5
17.7
17.7
20.5
29.6
37.1
43.1
11.9
16.1
23.3
29.3
34.1
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
25
30
25
30
25
30
35
40
50
60
25
30
25
30
25
35
35
45
60
60
15
15
15
15
15
15
20
20
30
30
15
15
15
20
25
25
30
35
30
35
35
40
50
60
60
70
30
35
30
35
35
45
60
60
70
80
15
15
15
15
20
20
30
30
35
40
15
15
15
20
25
25
30
30
40
45
40
45
40
45
50
60
70
70
80
80
40
45
40
45
40
45
60
70
70
80
90
90
20
25
20
25
20
25
30
30
35
40
45
45
15
15
15
20
25
25
30
30
35
35
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
151
5123247-TTG-A-0515
ZWT06 thru T12 Hi Static Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
9.3
68.0
14.5
2.1
6.8
5.5
0.0
230
9.3
68.0
14.5
2.1
6.8
5.5
0.0
460
4.9
34.0
7.6
1.3
3.4
2.2
0.0
575
3.8
28.0
6.0
0.7
2.4
1.8
0.0
208
11.9
88.0
18.5
3.0
9.6
5.5
0.0
230
11.9
88.0
18.5
3.0
9.6
5.5
0.0
460
5.2
44.0
8.1
1.6
4.7
2.2
0.0
575
4.8
36.0
7.5
1.4
3.6
1.8
0.0
208
12.2
88.0
19.0
3.0
9.6
5.5
0.0
230
12.2
88.0
19.0
3.0
9.6
5.5
0.0
460
5.8
44.0
9.0
1.6
4.7
2.2
0.0
575
4.4
36.0
5.5
1.4
3.6
1.8
0.0
T06
(6.5)
T07
(7.5)
T08
(8.5)
152
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
31.9
32.1
55.3
71.0
97.0
31.9
35.6
62.6
80.7
110.7
16.9
17.8
31.3
40.3
55.4
12.3
13.8
24.7
31.9
43.9
42.4
42.4
58.8
74.5
100.5
42.4
42.4
66.1
84.2
114.2
19.6
19.6
32.9
42.0
57.0
17.1
17.1
26.2
33.4
45.4
43.1
43.1
58.8
74.5
100.5
43.1
43.1
66.1
84.2
114.2
21.0
21.0
32.9
42.0
57.0
16.2
16.2
26.2
33.4
45.4
37.4
39.0
62.2
77.8
103.9
37.4
42.4
69.5
87.5
117.6
19.1
20.5
34.1
43.1
58.1
14.1
16.1
26.9
34.1
46.1
47.9
47.9
65.7
81.3
107.4
47.9
47.9
73.0
91.0
121.1
21.8
22.2
35.7
44.7
59.7
18.9
18.9
28.4
35.6
47.6
48.6
48.6
65.7
81.3
107.4
48.6
48.6
73.0
91.0
121.1
23.2
23.2
35.7
44.7
59.7
18.0
18.0
28.4
35.6
47.6
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
40
45
40
45
60
70
80
80
100
110
40
45
40
45
70
70
90
90
125
125
20
20
20
25
35
35
45
45
60
60
15
15
15
20
25
30
35
35
45
50
50
50
50
50
60
70
80
90
110
110
50
50
50
50
70
80
90
100
125
125
20
25
20
25
35
40
45
45
60
60
20
20
20
20
30
30
35
40
50
50
50
60
50
60
60
70
80
90
110
110
50
60
50
60
70
80
90
100
125
125
25
25
25
25
35
40
45
45
60
60
20
20
20
20
30
30
35
40
50
50
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWT06 thru T12 Hi Static Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
3.0
9.6
5.5
0.0
230
16.0 110.0 24.9
3.0
9.6
5.5
0.0
460
7.8
52.0
12.1
1.6
4.7
2.2
0.0
575
5.7
38.9
8.9
1.4
3.6
1.8
0.0
208
23.1 160.0 36.0
2.1
14.0
5.5
0.0
230
23.1 160.0 36.0
2.1
14.0
5.5
0.0
460
12.2
87.0
19.0
1.3
6.6
2.2
0.0
575
8.7
62.0
13.5
0.7
5.2
1.8
0.0
T10
(10)
T12
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
51.7
58.8
74.5
100.5
152.9
51.7
66.1
84.2
114.2
141.9
25.5
32.9
42.0
57.0
70.8
19.1
26.2
33.4
45.4
56.5
74.4
74.4
80.0
106.0
158.4
74.4
74.4
89.7
119.7
147.4
39.1
39.1
44.3
59.4
73.2
27.4
28.2
35.4
47.4
58.5
57.2
65.7
81.3
107.4
159.7
57.2
73.0
91.0
121.1
148.8
27.7
35.7
44.7
59.7
73.6
20.9
28.4
35.6
47.6
58.7
79.9
79.9
86.8
112.9
165.2
79.9
79.9
96.5
126.6
154.3
41.3
41.3
47.1
62.1
76.0
29.2
30.4
37.6
49.6
60.7
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
60
70
80
90
110
110
175
175
60
70
70
80
90
100
125
125
175
175
30
35
35
40
45
45
60
60
80
80
20
25
30
30
35
40
50
50
70
70
90
100
90
100
90
100
110
125
175
175
90
100
90
100
90
100
125
150
175
175
50
50
50
50
50
50
60
70
80
90
35
35
35
35
40
40
50
50
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
153
5123247-TTG-A-0515
ZWTA3 thru TA5 Standard Indoor Blower - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
8.7
68.0
13.5
2.1
5.2
5.5
10.0
230
8.7
68.0
13.5
2.1
5.2
5.5
10.0
460
4.6
34.0
7.1
1.3
2.6
2.2
5.0
575
3.5
28.0
5.5
0.7
2.0
1.8
4.0
208
11.2
88.0
17.5
2.1
5.2
5.5
10.0
230
11.2
88.0
17.5
2.1
5.2
5.5
10.0
460
5.6
44.0
8.0
1.3
2.6
2.2
5.0
575
4.5
36.0
7.0
0.7
2.0
1.8
4.0
208
14.1
88.0
22.0
2.1
5.2
5.5
10.0
230
14.1
88.0
22.0
2.1
5.2
5.5
10.0
460
7.7
55.0
12.0
1.3
2.6
2.2
5.0
575
5.1
36.0
7.5
0.7
2.0
1.8
4.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
28.5
28.5
34.6
42.6
58.2
28.5
28.5
37.0
46.1
64.1
14.7
14.7
18.5
23.0
32.1
11.2
18.3
25.5
31.3
34.6
42.6
58.2
71.0
31.3
37.0
46.1
64.1
79.1
15.9
18.5
23.0
32.1
39.6
12.3
18.3
25.5
31.6
37.0
37.0
42.6
58.2
71.0
81.5
37.0
37.0
46.1
64.1
79.1
91.2
19.7
19.7
23.0
32.1
39.6
45.6
13.7
18.3
25.5
31.6
36.4
34.0
34.0
41.5
49.5
65.1
34.0
34.9
43.9
52.9
71.0
16.9
16.9
21.3
25.8
34.8
13.0
20.6
27.8
36.8
41.5
49.5
65.1
77.9
36.8
43.9
52.9
71.0
86.0
18.1
21.3
25.8
34.8
42.3
14.1
20.6
27.8
33.8
42.5
42.5
49.5
65.1
77.9
88.3
42.5
43.9
52.9
71.0
86.0
98.0
21.9
21.9
25.8
34.8
42.3
48.3
15.5
20.6
27.8
33.8
38.6
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
35
40
35
40
40
45
45
50
60
70
35
40
35
40
40
45
50
60
70
80
15
20
15
20
20
25
25
30
35
35
15
15
20
25
30
30
40
45
40
45
45
50
60
70
80
80
40
45
40
45
50
60
70
80
80
90
20
20
20
25
25
30
35
35
40
45
15
15
20
25
30
30
35
35
50
50
50
50
50
50
60
70
80
80
90
90
50
50
50
50
50
60
70
80
80
90
100
100
25
25
25
25
25
30
35
35
40
45
50
50
15
20
20
25
30
30
35
35
40
40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
154
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWT06 thru T12 Standard Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
9.3
68.0
14.5
2.1
5.2
5.5
10.0
230
9.3
68.0
14.5
2.1
5.2
5.5
10.0
460
4.9
34.0
7.6
1.3
2.6
2.2
5.0
575
3.8
28.0
6.0
0.7
2.0
1.8
4.0
208
11.9
88.0
18.5
3.0
5.2
5.5
10.0
230
11.9
88.0
18.5
3.0
5.2
5.5
10.0
460
5.2
44.0
8.1
1.6
2.6
2.2
5.0
575
4.8
36.0
7.5
1.4
2.0
1.8
4.0
208
12.2
88.0
19.0
3.0
6.8
5.5
10.0
230
12.2
88.0
19.0
3.0
6.8
5.5
10.0
460
5.8
44.0
9.0
1.6
3.4
2.2
5.0
575
4.4
36.0
5.5
1.4
2.4
1.8
4.0
T06
(6.5)
T07
(7.5)
T08
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
40.5
42.6
65.8
81.5
107.5
40.5
46.1
73.1
91.2
121.2
21.2
23.0
36.6
45.6
60.6
15.9
18.3
29.2
36.4
48.4
48.0
48.0
65.8
81.5
107.5
48.0
48.0
73.1
91.2
121.2
22.5
23.0
36.6
45.6
60.6
19.5
19.5
29.2
36.4
48.4
50.3
50.3
67.8
83.5
109.5
50.3
50.3
75.1
93.2
123.2
24.7
24.7
37.6
46.6
61.6
19.0
19.0
29.7
36.9
48.9
46.0
49.5
72.7
88.3
114.4
46.0
52.9
80.0
98.0
128.1
23.4
25.8
39.3
48.3
63.4
17.7
20.6
31.4
38.6
50.6
53.5
53.5
72.7
88.3
114.4
53.5
53.5
80.0
98.0
128.1
24.7
25.8
39.3
48.3
63.4
21.3
21.3
31.4
38.6
50.6
55.8
55.8
74.7
90.3
116.4
55.8
55.8
82.0
100.0
130.1
26.9
26.9
40.3
49.3
64.4
20.8
21.1
31.9
39.1
51.1
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
50
50
50
70
80
90
90
110
125
50
50
50
60
80
80
100
100
125
150
25
25
25
30
40
40
50
50
70
70
20
20
20
25
30
35
40
40
50
60
50
60
50
60
70
80
90
90
110
125
50
60
50
60
80
80
100
100
125
150
25
25
25
30
40
40
50
50
70
70
20
25
20
25
30
35
40
40
50
60
60
60
60
60
70
80
90
100
110
125
60
60
60
60
80
90
100
100
125
150
30
30
30
30
40
45
50
50
70
70
20
25
20
25
30
35
40
40
50
60
155
5123247-TTG-A-0515
ZWT06 thru T12 Standard Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
3.0
6.8
5.5
10.0
230
16.0 110.0 24.9
3.0
6.8
5.5
10.0
460
7.8
52.0
12.1
1.6
3.4
2.2
5.0
575
5.7
38.9
8.9
1.4
2.4
1.8
4.0
208
23.1 160.0 36.0
2.1
9.6
5.5
10.0
230
23.1 160.0 36.0
2.1
9.6
5.5
10.0
460
12.2
87.0
19.0
1.3
4.7
2.2
5.0
575
8.7
62.0
13.5
0.7
3.6
1.8
4.0
T10
(10)
T12
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
58.9
67.8
83.5
109.5
161.9
58.9
75.1
93.2
123.2
150.9
29.2
37.6
46.6
61.6
75.5
21.9
29.7
36.9
48.9
60.0
80.0
80.0
87.0
113.0
165.4
80.0
80.0
96.7
126.7
154.4
42.2
42.2
48.2
63.2
77.1
29.8
31.2
38.4
50.4
61.5
64.4
74.7
90.3
116.4
168.7
64.4
82.0
100.0
130.1
157.8
31.4
40.3
49.3
64.4
78.2
23.7
31.9
39.1
51.1
62.2
85.5
85.5
93.8
119.9
172.2
85.5
85.5
103.5
133.6
161.3
44.4
44.4
51.0
66.0
79.8
31.6
33.4
40.6
52.6
63.7
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
70
80
90
100
110
125
175
175
70
80
80
90
100
100
125
150
175
175
35
35
40
45
50
50
70
70
80
90
25
25
30
35
40
40
50
60
70
70
100
100
100
100
100
100
125
125
175
175
100
100
100
100
100
110
150
150
175
175
50
50
50
50
50
60
70
70
90
90
35
40
35
40
40
45
60
60
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
156
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWTA3 thru TA5 Hi Static Blower - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
8.7
68.0
13.5
2.1
5.2
5.5
10.0
230
8.7
68.0
13.5
2.1
5.2
5.5
10.0
460
4.6
34.0
7.1
1.3
2.6
2.2
5.0
575
3.5
28.0
5.5
0.7
2.0
1.8
4.0
208
11.2
88.0
17.5
2.1
5.2
5.5
10.0
230
11.2
88.0
17.5
2.1
5.2
5.5
10.0
460
5.6
44.0
8.0
1.3
2.6
2.2
5.0
575
4.5
36.0
7.0
0.7
2.0
1.8
4.0
208
14.1
88.0
22.0
2.1
6.8
5.5
10.0
230
14.1
88.0
22.0
2.1
6.8
5.5
10.0
460
7.7
55.0
12.0
1.3
3.4
2.2
5.0
575
5.1
36.0
7.5
0.7
2.4
1.8
4.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
28.5
28.5
34.6
42.6
58.2
28.5
28.5
37.0
46.1
64.1
14.7
14.7
18.5
23.0
32.1
11.2
18.3
25.5
31.3
34.6
42.6
58.2
71.0
31.3
37.0
46.1
64.1
79.1
15.9
18.5
23.0
32.1
39.6
12.3
18.3
25.5
31.6
38.6
38.6
44.6
60.2
73.0
83.5
38.6
39.0
48.1
66.1
81.1
93.2
20.5
20.5
24.0
33.1
40.6
46.6
14.1
18.8
26.0
32.1
36.9
34.0
34.0
41.5
49.5
65.1
34.0
34.9
43.9
52.9
71.0
16.9
16.9
21.3
25.8
34.8
13.0
20.6
27.8
36.8
41.5
49.5
65.1
77.9
36.8
43.9
52.9
71.0
86.0
18.1
21.3
25.8
34.8
42.3
14.1
20.6
27.8
33.8
44.1
44.1
51.5
67.1
79.9
90.3
44.1
45.9
54.9
73.0
88.0
100.0
22.7
22.7
26.8
35.8
43.3
49.3
15.9
21.1
28.3
34.3
39.1
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
35
40
35
40
40
45
45
50
60
70
35
40
35
40
40
45
50
60
70
80
15
20
15
20
20
25
25
30
35
35
15
15
20
25
30
30
40
45
40
45
45
50
60
70
80
80
40
45
40
45
50
60
70
80
80
90
20
20
20
25
25
30
35
35
40
45
15
15
20
25
30
30
35
35
50
50
50
50
50
60
70
70
80
80
90
100
50
50
50
50
50
60
70
80
90
90
100
100
25
30
25
30
25
30
35
40
45
45
50
50
15
20
20
25
30
30
35
35
40
40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
157
5123247-TTG-A-0515
ZWT06 thru T12 Hi Static Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
9.3
68.0
14.5
2.1
6.8
5.5
10.0
230
9.3
68.0
14.5
2.1
6.8
5.5
10.0
460
4.9
34.0
7.6
1.3
3.4
2.2
5.0
575
3.8
28.0
6.0
0.7
2.4
1.8
4.0
208
11.9
88.0
18.5
3.0
9.6
5.5
10.0
230
11.9
88.0
18.5
3.0
9.6
5.5
10.0
460
5.2
44.0
8.1
1.6
4.7
2.2
5.0
575
4.8
36.0
7.5
1.4
3.6
1.8
4.0
208
12.2
88.0
19.0
3.0
9.6
5.5
10.0
230
12.2
88.0
19.0
3.0
9.6
5.5
10.0
460
5.8
44.0
9.0
1.6
4.7
2.2
5.0
575
4.4
36.0
5.5
1.4
3.6
1.8
4.0
T06
(6.5)
T07
(7.5)
T08
(8.5)
158
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
42.1
44.6
67.8
83.5
109.5
42.1
48.1
75.1
93.2
123.2
22.0
24.0
37.6
46.6
61.6
16.3
18.8
29.7
36.9
48.9
52.4
52.4
71.3
87.0
113.0
52.4
52.4
78.6
96.7
126.7
24.6
25.7
39.2
48.2
63.2
21.1
21.1
31.2
38.4
50.4
53.1
53.1
71.3
87.0
113.0
53.1
53.1
78.6
96.7
126.7
26.0
26.0
39.2
48.2
63.2
20.2
20.3
31.2
38.4
50.4
47.6
51.5
74.7
90.3
116.4
47.6
54.9
82.0
100.0
130.1
24.2
26.8
40.3
49.3
64.4
18.1
21.1
31.9
39.1
51.1
57.9
57.9
78.2
93.8
119.9
57.9
58.4
85.5
103.5
133.6
26.8
28.4
41.9
51.0
66.0
22.9
22.9
33.4
40.6
52.6
58.6
58.6
78.2
93.8
119.9
58.6
58.6
85.5
103.5
133.6
28.2
28.4
41.9
51.0
66.0
22.0
22.6
33.4
40.6
52.6
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
50
50
60
70
80
90
100
110
125
50
50
50
60
80
90
100
100
125
150
25
25
25
30
40
45
50
50
70
70
20
20
20
25
30
35
40
40
50
60
60
60
60
60
80
80
90
100
125
125
60
60
60
60
80
90
100
110
150
150
25
30
30
30
40
45
50
60
70
70
25
25
25
25
35
35
40
45
60
60
60
70
60
70
80
80
90
100
125
125
60
70
60
70
80
90
100
110
150
150
30
30
30
30
40
45
50
60
70
70
25
25
25
25
35
35
40
45
60
60
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZWT06 thru T12 Hi Static Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
3.0
9.6
5.5
10.0
230
16.0 110.0 24.9
3.0
9.6
5.5
10.0
460
7.8
52.0
12.1
1.6
4.7
2.2
5.0
575
5.7
38.9
8.9
1.4
3.6
1.8
4.0
208
23.1 160.0 36.0
2.1
14.0
5.5
10.0
230
23.1 160.0 36.0
2.1
14.0
5.5
10.0
460
12.2
87.0
19.0
1.3
6.6
2.2
5.0
575
8.7
62.0
13.5
0.7
5.2
1.8
4.0
T10
(10)
T12
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
61.7
71.3
87.0
113.0
165.4
61.7
78.6
96.7
126.7
154.4
30.5
39.2
48.2
63.2
77.1
23.1
31.2
38.4
50.4
61.5
84.4
84.4
92.5
118.5
170.9
84.4
84.4
102.2
132.2
159.9
44.1
44.1
50.6
65.6
79.5
31.4
33.2
40.4
52.4
63.5
67.2
78.2
93.8
119.9
172.2
67.2
85.5
103.5
133.6
161.3
32.7
41.9
51.0
66.0
79.8
24.9
33.4
40.6
52.6
63.7
89.9
89.9
99.3
125.4
177.7
89.9
91.0
109.0
139.1
166.8
46.3
46.3
53.3
68.4
82.2
33.2
35.4
42.6
54.6
65.7
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
80
80
90
100
125
125
175
175
70
80
80
90
100
110
150
150
175
175
35
40
40
45
50
60
70
70
90
90
25
30
35
35
40
45
60
60
70
70
100
110
100
110
100
110
125
150
175
200
100
110
100
110
110
110
150
150
175
175
50
50
50
50
60
60
70
70
90
90
40
40
40
40
45
45
60
60
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
159
5123247-TTG-A-0515
ZKTA3 thru TA5 Standard Indoor Blower - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
8.7
68.0
13.5
2.1
5.2
5.5
0.0
230
8.7
68.0
13.5
2.1
5.2
5.5
0.0
460
4.6
34.0
7.1
1.3
2.6
2.2
0.0
575
3.5
28.0
5.5
0.7
2.0
1.8
0.0
208
11.9
88.0
18.5
2.1
5.2
5.5
0.0
230
11.9
88.0
18.5
2.1
5.2
5.5
0.0
460
5.2
44.0
8.1
1.3
2.6
2.2
0.0
575
4.8
36.0
7.5
0.7
2.0
1.8
0.0
208
14.1
88.0
22.0
2.1
5.2
5.5
0.0
230
14.1
88.0
22.0
2.1
5.2
5.5
0.0
460
7.7
55.0
12.0
1.3
2.6
2.2
0.0
575
5.1
36.0
7.5
0.7
2.0
1.8
0.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
18.2
18.2
22.1
30.1
45.7
18.2
18.2
24.5
33.6
51.6
9.6
9.6
12.3
16.8
25.8
7.0
13.3
20.5
24.3
24.3
30.1
45.7
58.5
24.3
24.5
33.6
51.6
66.6
11.6
12.3
16.8
25.8
33.3
9.3
13.3
20.5
26.6
27.0
27.0
30.1
45.7
58.5
69.0
27.0
27.0
33.6
51.6
66.6
78.7
14.7
14.7
16.8
25.8
33.3
39.3
9.7
13.3
20.5
26.6
31.4
23.7
23.7
29.0
37.0
52.6
23.7
23.7
31.4
40.4
58.5
11.8
11.8
15.0
19.5
28.6
8.8
15.6
22.8
29.8
29.8
37.0
52.6
65.4
29.8
31.4
40.4
58.5
73.5
13.8
15.0
19.5
28.6
36.1
11.1
15.6
22.8
28.8
32.5
32.5
37.0
52.6
65.4
75.8
32.5
32.5
40.4
58.5
73.5
85.5
16.9
16.9
19.5
28.6
36.1
42.1
11.5
15.6
22.8
28.8
33.6
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
25
30
25
30
25
30
35
40
50
60
25
30
25
30
25
35
35
45
60
60
15
15
15
15
15
15
20
20
30
30
15
15
15
20
25
25
35
40
35
40
35
40
50
60
60
70
35
40
35
40
35
45
60
60
70
80
15
15
15
15
20
20
30
30
35
40
15
15
15
20
25
25
30
30
35
45
35
45
40
45
50
60
60
70
70
80
35
45
35
45
40
45
60
60
70
80
80
90
20
20
20
20
20
20
30
30
35
40
40
45
15
15
15
20
25
25
30
30
35
35
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
160
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT06 thru T12 Standard Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
13.5
88.0
21.1
2.1
5.2
5.5
0.0
230
13.5
88.0
21.1
2.1
5.2
5.5
0.0
460
6.0
44.0
9.3
1.3
2.6
2.2
0.0
575
4.9
34.0
7.7
0.7
2.0
1.8
0.0
208
13.1
83.1
20.5
2.1
5.2
5.5
0.0
230
13.1
83.1
20.5
2.1
5.2
5.5
0.0
460
6.1
41.0
9.5
1.3
2.6
2.2
0.0
575
4.4
33.0
6.8
0.7
2.0
1.8
0.0
208
14.5
98.0
22.6
2.1
6.8
5.5
0.0
230
14.5
98.0
22.6
2.1
6.8
5.5
0.0
460
6.3
55.0
9.9
1.3
3.4
2.2
0.0
575
6.0
41.0
9.4
0.7
2.4
1.8
0.0
T06
(6.5)
T07
(7.5)
T08
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
Stages
Amps
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
39.8
39.8
53.3
69.0
95.0
39.8
39.8
60.6
78.7
108.7
18.6
18.6
30.3
39.3
54.4
14.3
14.3
24.2
31.4
43.4
38.9
38.9
53.3
69.0
95.0
38.9
38.9
60.6
78.7
108.7
18.8
18.8
30.3
39.3
54.4
13.2
13.3
24.2
31.4
43.4
43.6
43.6
55.3
71.0
97.0
43.6
43.6
62.6
80.7
110.7
20.1
20.1
31.3
40.3
55.4
17.2
17.2
24.7
31.9
43.9
45.3
45.3
60.2
75.8
101.9
45.3
45.3
67.5
85.5
115.6
20.8
20.8
33.1
42.1
57.1
16.1
16.1
26.4
33.6
45.6
44.4
44.4
60.2
75.8
101.9
44.4
44.4
67.5
85.5
115.6
21.0
21.0
33.1
42.1
57.1
15.0
15.6
26.4
33.6
45.6
49.1
49.1
62.2
77.8
103.9
49.1
49.1
69.5
87.5
117.6
22.3
22.3
34.1
43.1
58.1
19.0
19.0
26.9
34.1
46.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
50
50
50
50
60
70
70
80
100
110
50
50
50
50
70
70
80
90
110
125
20
25
20
25
35
35
40
45
60
60
15
20
15
20
25
30
35
35
45
50
50
50
50
50
60
70
70
80
100
110
50
50
50
50
70
70
80
90
110
125
20
25
20
25
35
35
40
45
60
60
15
15
15
20
25
30
35
35
45
50
50
60
50
60
60
70
80
80
100
110
50
60
50
60
70
70
90
90
125
125
25
25
25
25
35
35
45
45
60
60
20
25
20
25
25
30
35
35
45
50
161
5123247-TTG-A-0515
ZKT06 thru T12 Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
3.0
6.8
5.5
0.0
230
16.0 110.0 24.9
3.0
6.8
5.5
0.0
460
7.8
52.0
12.1
1.6
3.4
2.2
0.0
575
5.7
38.9
8.9
1.4
2.4
1.8
0.0
208
22.4 149.0 35.0
2.1
9.6
5.5
0.0
230
22.4 149.0 35.0
2.1
9.6
5.5
0.0
460
10.6
75.0
16.5
1.3
4.7
2.2
0.0
575
7.7
54.0
12.0
0.7
3.6
1.8
0.0
T10
(10)
T12
(12.5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
48.9
55.3
71.0
97.0
149.4
48.9
62.6
80.7
110.7
138.4
24.2
31.3
40.3
55.4
69.2
17.9
24.7
31.9
43.9
55.0
68.4
68.4
74.5
100.5
152.9
68.4
68.4
84.2
114.2
141.9
33.6
33.6
42.0
57.0
70.8
23.6
26.2
33.4
45.4
56.5
54.4
62.2
77.8
103.9
156.2
54.4
69.5
87.5
117.6
145.3
26.4
34.1
43.1
58.1
72.0
19.7
26.9
34.1
46.1
57.2
73.9
73.9
81.3
107.4
159.7
73.9
73.9
91.0
121.1
148.8
35.8
35.8
44.7
59.7
73.6
25.4
28.4
35.6
47.6
58.7
1
Model
kW
Stages
Amps
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
60
70
60
70
80
80
100
110
150
175
60
70
70
70
90
90
125
125
150
175
30
30
35
35
45
45
60
60
80
80
20
25
25
30
35
35
45
50
60
60
90
90
90
90
90
90
110
110
175
175
90
90
90
90
90
100
125
125
175
175
40
45
40
45
45
45
60
60
80
80
30
30
30
30
35
40
50
50
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
162
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKTA3 thru TA5 Hi Static Indoor Blower - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
8.7
68.0
13.5
2.1
5.2
5.5
0.0
230
8.7
68.0
13.5
2.1
5.2
5.5
0.0
460
4.6
34.0
7.1
1.3
2.6
2.2
0.0
575
3.5
28.0
5.5
0.7
2.0
1.8
0.0
208
11.9
88.0
18.5
2.1
5.2
5.5
0.0
230
11.9
88.0
18.5
2.1
5.2
5.5
0.0
460
5.2
44.0
8.1
1.3
2.6
2.2
0.0
575
4.8
36.0
7.5
0.7
2.0
1.8
0.0
208
14.1
88.0
22.0
2.1
6.8
5.5
0.0
230
14.1
88.0
22.0
2.1
6.8
5.5
0.0
460
7.7
55.0
12.0
1.3
3.4
2.2
0.0
575
5.1
36.0
7.5
0.7
2.4
1.8
0.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
18.2
18.2
22.1
30.1
45.7
18.2
18.2
24.5
33.6
51.6
9.6
9.6
12.3
16.8
25.8
7.0
13.3
20.5
24.3
24.3
30.1
45.7
58.5
24.3
24.5
33.6
51.6
66.6
11.6
12.3
16.8
25.8
33.3
9.3
13.3
20.5
26.6
28.6
28.6
32.1
47.7
60.5
71.0
28.6
28.6
35.6
53.6
68.6
80.7
15.5
15.5
17.8
26.8
34.3
40.3
10.1
13.8
21.0
27.1
31.9
23.7
23.7
29.0
37.0
52.6
23.7
23.7
31.4
40.4
58.5
11.8
11.8
15.0
19.5
28.6
8.8
15.6
22.8
29.8
29.8
37.0
52.6
65.4
29.8
31.4
40.4
58.5
73.5
13.8
15.0
19.5
28.6
36.1
11.1
15.6
22.8
28.8
34.1
34.1
39.0
54.6
67.4
77.8
34.1
34.1
42.4
60.5
75.5
87.5
17.7
17.7
20.5
29.6
37.1
43.1
11.9
16.1
23.3
29.3
34.1
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
25
30
25
30
25
30
35
40
50
60
25
30
25
30
25
35
35
45
60
60
15
15
15
15
15
15
20
20
30
30
15
15
15
20
25
25
35
40
35
40
35
40
50
60
60
70
35
40
35
40
35
45
60
60
70
80
15
15
15
15
20
20
30
30
35
40
15
15
15
20
25
25
30
30
40
45
40
45
40
45
50
60
70
70
80
80
40
45
40
45
40
45
60
70
70
80
90
90
20
25
20
25
20
25
30
30
35
40
45
45
15
15
15
20
25
25
30
30
35
35
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
163
5123247-TTG-A-0515
ZKT06 thru T12 Hi Static Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
13.5
88.0
21.1
2.1
6.8
5.5
0.0
230
13.5
88.0
21.1
2.1
6.8
5.5
0.0
460
6.0
44.0
9.3
1.3
3.4
2.2
0.0
575
4.9
34.0
7.7
0.7
2.4
1.8
0.0
208
13.1
83.1
20.5
2.1
9.6
5.5
0.0
230
13.1
83.1
20.5
2.1
9.6
5.5
0.0
460
6.1
41.0
9.5
1.3
4.7
2.2
0.0
575
4.4
33.0
6.8
0.7
3.6
1.8
0.0
208
14.5
98.0
22.6
2.1
9.6
5.5
0.0
230
14.5
98.0
22.6
2.1
9.6
5.5
0.0
460
6.3
55.0
9.9
1.3
4.7
2.2
0.0
575
6.0
41.0
9.4
0.7
3.6
1.8
0.0
T06
(6.5)
T07
(7.5)
T08
(8.5)
164
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
41.4
41.4
55.3
71.0
97.0
41.4
41.4
62.6
80.7
110.7
19.4
19.4
31.3
40.3
55.4
14.7
14.7
24.7
31.9
43.9
43.3
43.3
58.8
74.5
100.5
43.3
43.3
66.1
84.2
114.2
20.9
20.9
32.9
42.0
57.0
14.8
15.3
26.2
33.4
45.4
46.4
46.4
58.8
74.5
100.5
46.4
46.4
66.1
84.2
114.2
21.4
21.4
32.9
42.0
57.0
18.4
18.4
26.2
33.4
45.4
46.9
46.9
62.2
77.8
103.9
46.9
46.9
69.5
87.5
117.6
21.6
21.6
34.1
43.1
58.1
16.5
16.5
26.9
34.1
46.1
48.8
48.8
65.7
81.3
107.4
48.8
48.8
73.0
91.0
121.1
23.1
23.1
35.7
44.7
59.7
16.6
17.6
28.4
35.6
47.6
51.9
51.9
65.7
81.3
107.4
51.9
51.9
73.0
91.0
121.1
23.6
23.6
35.7
44.7
59.7
20.2
20.2
28.4
35.6
47.6
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
60
50
60
60
70
80
80
100
110
50
60
50
60
70
70
90
90
125
125
25
25
25
25
35
35
45
45
60
60
15
20
15
20
25
30
35
35
45
50
50
60
50
60
60
70
80
90
110
110
50
60
50
60
70
80
90
100
125
125
25
25
25
25
35
40
45
45
60
60
15
20
20
20
30
30
35
40
50
50
60
60
60
60
60
70
80
90
110
110
60
60
60
60
70
80
90
100
125
125
25
25
25
25
35
40
45
45
60
60
20
25
20
25
30
30
35
40
50
50
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT06 thru T12 Hi Static Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
3.0
9.6
5.5
0.0
230
16.0 110.0 24.9
3.0
9.6
5.5
0.0
460
7.8
52.0
12.1
1.6
4.7
2.2
0.0
575
5.7
38.9
8.9
1.4
3.6
1.8
0.0
208
22.4 149.0 35.0
2.1
14.0
5.5
0.0
230
22.4 149.0 35.0
2.1
14.0
5.5
0.0
460
10.6
75.0
16.5
1.3
6.6
2.2
0.0
575
7.7
54.0
12.0
0.7
5.2
1.8
0.0
T10
(10)
T12
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
51.7
58.8
74.5
100.5
152.9
51.7
66.1
84.2
114.2
141.9
25.5
32.9
42.0
57.0
70.8
19.1
26.2
33.4
45.4
56.5
72.8
72.8
80.0
106.0
158.4
72.8
72.8
89.7
119.7
147.4
35.5
35.5
44.3
59.4
73.2
25.2
28.2
35.4
47.4
58.5
57.2
65.7
81.3
107.4
159.7
57.2
73.0
91.0
121.1
148.8
27.7
35.7
44.7
59.7
73.6
20.9
28.4
35.6
47.6
58.7
78.3
78.3
86.8
112.9
165.2
78.3
78.5
96.5
126.6
154.3
37.7
38.1
47.1
62.1
76.0
27.0
30.4
37.6
49.6
60.7
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
60
70
80
90
110
110
175
175
60
70
70
80
90
100
125
125
175
175
30
35
35
40
45
45
60
60
80
80
20
25
30
30
35
40
50
50
70
70
90
100
90
100
90
100
110
125
175
175
90
100
90
100
90
100
125
150
175
175
45
45
45
45
45
50
60
70
80
90
30
30
30
35
40
40
50
50
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
165
5123247-TTG-A-0515
ZKTA3 thru TA5 Standard Indoor Blower - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
8.7
68.0
13.5
2.1
5.2
5.5
10.0
230
8.7
68.0
13.5
2.1
5.2
5.5
10.0
460
4.6
34.0
7.1
1.3
2.6
2.2
5.0
575
3.5
28.0
5.5
0.7
2.0
1.8
4.0
208
11.9
88.0
18.5
2.1
5.2
5.5
10.0
230
11.9
88.0
18.5
2.1
5.2
5.5
10.0
460
5.2
44.0
8.1
1.3
2.6
2.2
5.0
575
4.8
36.0
7.5
0.7
2.0
1.8
4.0
208
14.1
88.0
22.0
2.1
5.2
5.5
10.0
230
14.1
88.0
22.0
2.1
5.2
5.5
10.0
460
7.7
55.0
12.0
1.3
2.6
2.2
5.0
575
5.1
36.0
7.5
0.7
2.0
1.8
4.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
28.5
28.5
34.6
42.6
58.2
28.5
28.5
37.0
46.1
64.1
14.7
14.7
18.5
23.0
32.1
11.2
18.3
25.5
34.3
34.6
42.6
58.2
71.0
34.3
37.0
46.1
64.1
79.1
16.6
18.5
23.0
32.1
39.6
13.3
18.3
25.5
31.6
37.0
37.0
42.6
58.2
71.0
81.5
37.0
37.0
46.1
64.1
79.1
91.2
19.7
19.7
23.0
32.1
39.6
45.6
13.7
18.3
25.5
31.6
36.4
34.0
34.0
41.5
49.5
65.1
34.0
34.9
43.9
52.9
71.0
16.9
16.9
21.3
25.8
34.8
13.0
20.6
27.8
39.8
41.5
49.5
65.1
77.9
39.8
43.9
52.9
71.0
86.0
18.8
21.3
25.8
34.8
42.3
15.1
20.6
27.8
33.8
42.5
42.5
49.5
65.1
77.9
88.3
42.5
43.9
52.9
71.0
86.0
98.0
21.9
21.9
25.8
34.8
42.3
48.3
15.5
20.6
27.8
33.8
38.6
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
35
40
35
40
40
45
45
50
60
70
35
40
35
40
40
45
50
60
70
80
15
20
15
20
20
25
25
30
35
35
15
15
20
25
30
30
45
50
45
50
45
50
60
70
80
80
45
50
45
50
50
60
70
80
80
90
20
20
20
25
25
30
35
35
40
45
15
20
20
25
30
30
35
35
50
50
50
50
50
50
60
70
80
80
90
90
50
50
50
50
50
60
70
80
80
90
100
100
25
25
25
25
25
30
35
35
40
45
50
50
15
20
20
25
30
30
35
35
40
40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
166
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT06 thru T12 Standard Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
13.5
88.0
21.1
2.1
5.2
5.5
10.0
230
13.5
88.0
21.1
2.1
5.2
5.5
10.0
460
6.0
44.0
9.3
1.3
2.6
2.2
5.0
575
4.9
34.0
7.7
0.7
2.0
1.8
4.0
208
13.1
83.1
20.5
2.1
5.2
5.5
10.0
230
13.1
83.1
20.5
2.1
5.2
5.5
10.0
460
6.1
41.0
9.5
1.3
2.6
2.2
5.0
575
4.4
33.0
6.8
0.7
2.0
1.8
4.0
208
14.5
98.0
22.6
2.1
6.8
5.5
10.0
230
14.5
98.0
22.6
2.1
6.8
5.5
10.0
460
6.3
55.0
9.9
1.3
3.4
2.2
5.0
575
6.0
41.0
9.4
0.7
2.4
1.8
4.0
T06
(6.5)
T07
(7.5)
T08
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
49.8
49.8
65.8
81.5
107.5
49.8
49.8
73.1
91.2
121.2
23.6
23.6
36.6
45.6
60.6
18.3
18.3
29.2
36.4
48.4
48.9
48.9
65.8
81.5
107.5
48.9
48.9
73.1
91.2
121.2
23.8
23.8
36.6
45.6
60.6
17.2
18.3
29.2
36.4
48.4
53.6
53.6
67.8
83.5
109.5
53.6
53.6
75.1
93.2
123.2
25.1
25.1
37.6
46.6
61.6
21.2
21.2
29.7
36.9
48.9
55.3
55.3
72.7
88.3
114.4
55.3
55.3
80.0
98.0
128.1
25.8
25.8
39.3
48.3
63.4
20.1
20.6
31.4
38.6
50.6
54.4
54.4
72.7
88.3
114.4
54.4
54.4
80.0
98.0
128.1
26.0
26.0
39.3
48.3
63.4
19.0
20.6
31.4
38.6
50.6
59.1
59.1
74.7
90.3
116.4
59.1
59.1
82.0
100.0
130.1
27.3
27.3
40.3
49.3
64.4
23.0
23.0
31.9
39.1
51.1
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
60
60
60
70
80
90
90
110
125
60
60
60
60
80
80
100
100
125
150
25
30
25
30
40
40
50
50
70
70
20
25
20
25
30
35
40
40
50
60
60
60
60
60
70
80
90
90
110
125
60
60
60
60
80
80
100
100
125
150
25
30
25
30
40
40
50
50
70
70
20
20
20
25
30
35
40
40
50
60
60
70
60
70
70
80
90
100
110
125
60
70
60
70
80
90
100
100
125
150
30
30
30
30
40
45
50
50
70
70
25
25
25
25
30
35
40
40
50
60
167
5123247-TTG-A-0515
ZKT06 thru T12 Standard Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
3.0
6.8
5.5
10.0
230
16.0 110.0 24.9
3.0
6.8
5.5
10.0
460
7.8
52.0
12.1
1.6
3.4
2.2
5.0
575
5.7
38.9
8.9
1.4
2.4
1.8
4.0
208
22.4 149.0 35.0
2.1
9.6
5.5
10.0
230
22.4 149.0 35.0
2.1
9.6
5.5
10.0
460
10.6
75.0
16.5
1.3
4.7
2.2
5.0
575
7.7
54.0
12.0
0.7
3.6
1.8
4.0
T10
(10)
T12
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
58.9
67.8
83.5
109.5
161.9
58.9
75.1
93.2
123.2
150.9
29.2
37.6
46.6
61.6
75.5
21.9
29.7
36.9
48.9
60.0
78.4
78.4
87.0
113.0
165.4
78.4
78.6
96.7
126.7
154.4
38.6
39.2
48.2
63.2
77.1
27.6
31.2
38.4
50.4
61.5
64.4
74.7
90.3
116.4
168.7
64.4
82.0
100.0
130.1
157.8
31.4
40.3
49.3
64.4
78.2
23.7
31.9
39.1
51.1
62.2
83.9
83.9
93.8
119.9
172.2
83.9
85.5
103.5
133.6
161.3
40.8
41.9
51.0
66.0
79.8
29.4
33.4
40.6
52.6
63.7
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
70
80
90
100
110
125
175
175
70
80
80
90
100
100
125
150
175
175
35
35
40
45
50
50
70
70
80
90
25
25
30
35
40
40
50
60
70
70
100
100
100
100
100
100
125
125
175
175
100
100
100
100
100
110
150
150
175
175
45
50
45
50
50
60
70
70
90
90
35
35
35
35
40
45
60
60
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
168
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKTA3 thru TA5 Hi Static Indoor Blower - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
8.7
68.0
13.5
2.1
5.2
5.5
10.0
230
8.7
68.0
13.5
2.1
5.2
5.5
10.0
460
4.6
34.0
7.1
1.3
2.6
2.2
5.0
575
3.5
28.0
5.5
0.7
2.0
1.8
4.0
208
11.9
88.0
18.5
2.1
5.2
5.5
10.0
230
11.9
88.0
18.5
2.1
5.2
5.5
10.0
460
5.2
44.0
8.1
1.3
2.6
2.2
5.0
575
4.8
36.0
7.5
0.7
2.0
1.8
4.0
208
14.1
88.0
22.0
2.1
6.8
5.5
10.0
230
14.1
88.0
22.0
2.1
6.8
5.5
10.0
460
7.7
55.0
12.0
1.3
3.4
2.2
5.0
575
5.1
36.0
7.5
0.7
2.4
1.8
4.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
28.5
28.5
34.6
42.6
58.2
28.5
28.5
37.0
46.1
64.1
14.7
14.7
18.5
23.0
32.1
11.2
18.3
25.5
34.3
34.6
42.6
58.2
71.0
34.3
37.0
46.1
64.1
79.1
16.6
18.5
23.0
32.1
39.6
13.3
18.3
25.5
31.6
38.6
38.6
44.6
60.2
73.0
83.5
38.6
39.0
48.1
66.1
81.1
93.2
20.5
20.5
24.0
33.1
40.6
46.6
14.1
18.8
26.0
32.1
36.9
34.0
34.0
41.5
49.5
65.1
34.0
34.9
43.9
52.9
71.0
16.9
16.9
21.3
25.8
34.8
13.0
20.6
27.8
39.8
41.5
49.5
65.1
77.9
39.8
43.9
52.9
71.0
86.0
18.8
21.3
25.8
34.8
42.3
15.1
20.6
27.8
33.8
44.1
44.1
51.5
67.1
79.9
90.3
44.1
45.9
54.9
73.0
88.0
100.0
22.7
22.7
26.8
35.8
43.3
49.3
15.9
21.1
28.3
34.3
39.1
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
35
40
35
40
40
45
45
50
60
70
35
40
35
40
40
45
50
60
70
80
15
20
15
20
20
25
25
30
35
35
15
15
20
25
30
30
45
50
45
50
45
50
60
70
80
80
45
50
45
50
50
60
70
80
80
90
20
20
20
25
25
30
35
35
40
45
15
20
20
25
30
30
35
35
50
50
50
50
50
60
70
70
80
80
90
100
50
50
50
50
50
60
70
80
90
90
100
100
25
30
25
30
25
30
35
40
45
45
50
50
15
20
20
25
30
30
35
35
40
40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
169
5123247-TTG-A-0515
ZKT06 thru T12 Hi Static Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
13.5
88.0
21.1
2.1
6.8
5.5
10.0
230
13.5
88.0
21.1
2.1
6.8
5.5
10.0
460
6.0
44.0
9.3
1.3
3.4
2.2
5.0
575
4.9
34.0
7.7
0.7
2.4
1.8
4.0
208
13.1
83.1
20.5
2.1
9.6
5.5
10.0
230
13.1
83.1
20.5
2.1
9.6
5.5
10.0
460
6.1
41.0
9.5
1.3
4.7
2.2
5.0
575
4.4
33.0
6.8
0.7
3.6
1.8
4.0
208
14.5
98.0
22.6
2.1
9.6
5.5
10.0
230
14.5
98.0
22.6
2.1
9.6
5.5
10.0
460
6.3
55.0
9.9
1.3
4.7
2.2
5.0
575
6.0
41.0
9.4
0.7
3.6
1.8
4.0
T06
(6.5)
T07
(7.5)
T08
(8.5)
170
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
51.4
51.4
67.8
83.5
109.5
51.4
51.4
75.1
93.2
123.2
24.4
24.4
37.6
46.6
61.6
18.7
18.8
29.7
36.9
48.9
53.3
53.3
71.3
87.0
113.0
53.3
53.3
78.6
96.7
126.7
25.9
25.9
39.2
48.2
63.2
18.8
20.3
31.2
38.4
50.4
56.4
56.4
71.3
87.0
113.0
56.4
56.4
78.6
96.7
126.7
26.4
26.4
39.2
48.2
63.2
22.4
22.4
31.2
38.4
50.4
56.9
56.9
74.7
90.3
116.4
56.9
56.9
82.0
100.0
130.1
26.6
26.8
40.3
49.3
64.4
20.5
21.1
31.9
39.1
51.1
58.8
58.8
78.2
93.8
119.9
58.8
58.8
85.5
103.5
133.6
28.1
28.4
41.9
51.0
66.0
20.6
22.6
33.4
40.6
52.6
61.9
61.9
78.2
93.8
119.9
61.9
61.9
85.5
103.5
133.6
28.6
28.6
41.9
51.0
66.0
24.2
24.2
33.4
40.6
52.6
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
60
70
70
80
90
100
110
125
60
70
60
70
80
90
100
100
125
150
30
30
30
30
40
45
50
50
70
70
20
25
20
25
30
35
40
40
50
60
60
70
60
70
80
80
90
100
125
125
60
70
60
70
80
90
100
110
150
150
30
30
30
30
40
45
50
60
70
70
20
25
25
25
35
35
40
45
60
60
70
70
70
70
80
80
90
100
125
125
70
70
70
70
80
90
100
110
150
150
30
30
30
30
40
45
50
60
70
70
25
30
25
30
35
35
40
45
60
60
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZKT06 thru T12 Hi Static Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Compressors
(each)
Volt
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
3.0
9.6
5.5
10.0
230
16.0 110.0 24.9
3.0
9.6
5.5
10.0
460
7.8
52.0
12.1
1.6
4.7
2.2
5.0
575
5.7
38.9
8.9
1.4
3.6
1.8
4.0
208
22.4 149.0 35.0
2.1
14.0
5.5
10.0
230
22.4 149.0 35.0
2.1
14.0
5.5
10.0
460
10.6
75.0
16.5
1.3
6.6
2.2
5.0
575
7.7
54.0
12.0
0.7
5.2
1.8
4.0
T10
(10)
T12
(12.5)
Electric Heat Option
MCA1
(Amps)
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
61.7
71.3
87.0
113.0
165.4
61.7
78.6
96.7
126.7
154.4
30.5
39.2
48.2
63.2
77.1
23.1
31.2
38.4
50.4
61.5
82.8
82.8
92.5
118.5
170.9
82.8
84.1
102.2
132.2
159.9
40.5
41.6
50.6
65.6
79.5
29.2
33.2
40.4
52.4
63.5
MCA1
w/Pwr
Exh
(Amps)
67.2
78.2
93.8
119.9
172.2
67.2
85.5
103.5
133.6
161.3
32.7
41.9
51.0
66.0
79.8
24.9
33.4
40.6
52.6
63.7
88.3
88.3
99.3
125.4
177.7
88.3
91.0
109.0
139.1
166.8
42.7
44.3
53.3
68.4
82.2
31.0
35.4
42.6
54.6
65.7
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
80
80
90
100
125
125
175
175
70
80
80
90
100
110
150
150
175
175
35
40
40
45
50
60
70
70
90
90
25
30
35
35
40
45
60
60
70
70
100
110
100
110
100
110
125
150
175
200
100
110
100
110
110
110
150
150
175
175
50
50
50
50
60
60
70
70
90
90
35
35
35
40
45
45
60
60
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Electric Heat Multipliers
Voltage
Nominal
240
480
600
Applied
208
230
460
575
kW Capacity Multipliers1
0.75
0.92
0.92
0.92
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Johnson Controls Unitary Products
171
5123247-TTG-A-0515
Typical Wiring Diagrams
ZU/ZW/ZKTA3 thru T12 Typical Wiring Diagrams
Typical ZU/ZW/ZKTA3 thru TA5 Cooling Unit with Gas Heat 208/230 Volt Wiring Diagram
172
Johnson Controls Unitary Products
5123247-TTG-A-0515
Typical ZU/ZW/ZKTA3 thru TA5 Cooling Unit with Gas Heat 208/230 Volt Unit (Options)
Johnson Controls Unitary Products
173
5123247-TTG-A-0515
Typical ZU/ZW/ZKTA3 thru TA5 Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram
174
Johnson Controls Unitary Products
5123247-TTG-A-0515
Typical ZU/ZW/ZKTA3 thru TA5 Cooling Unit with Gas Heat 460/575 Volt Unit (Options)
Johnson Controls Unitary Products
175
5123247-TTG-A-0515
Typical ZU/ZW/ZKTA3 thru TA5 Cooling Unit with/without Electric Heat Wiring Diagram
176
Johnson Controls Unitary Products
5123247-TTG-A-0515
Typical ZU/ZW/ZKTA3 thru TA5 Cooling Unit with/without Electric Heat Unit (Options)
Johnson Controls Unitary Products
177
5123247-TTG-A-0515
Typical ZU/ZW/ZKT06 thru T10 Cooling Unit with Gas Heat 208/230 Volt Wiring Diagram
178
Johnson Controls Unitary Products
5123247-TTG-A-0515
Typical ZU/ZW/ZKT06 thru T10 Cooling Unit with Gas Heat 208/230 Volt Unit (Options)
Johnson Controls Unitary Products
179
5123247-TTG-A-0515
Typical ZU/ZW/ZKT06 thru T10 Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram
180
Johnson Controls Unitary Products
5123247-TTG-A-0515
Typical ZU/ZW/ZKT06 thru T10 Cooling Unit with Gas Heat 460/575 Volt Unit (Options)
Johnson Controls Unitary Products
181
5123247-TTG-A-0515
Typical ZU/ZW/ZKT06 thru T10 Cooling Unit with/without Electric Heat Wiring Diagram
182
Johnson Controls Unitary Products
5123247-TTG-A-0515
Typical ZU/ZW/ZKT06 thru T10 Cooling Unit with/without Electric Heat Unit (Options)
Johnson Controls Unitary Products
183
5123247-TTG-A-0515
Typical ZU/ZW/ZKT12 Cooling Unit with Gas Heat 208/230 Volt Wiring Diagram
184
Johnson Controls Unitary Products
5123247-TTG-A-0515
Typical ZU/ZW/ZKT12 Cooling Unit with Gas Heat 208/230 Volt Unit (Options)
Johnson Controls Unitary Products
185
5123247-TTG-A-0515
Typical ZU/ZW/ZKT12 Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram
186
Johnson Controls Unitary Products
5123247-TTG-A-0515
Typical ZU/ZW/ZKT12 Cooling Unit with Gas Heat 460/575 Volt Unit (Options)
Johnson Controls Unitary Products
187
5123247-TTG-A-0515
Typical ZU/ZW/ZKT12 Cooling Unit with/without Electric Heat Wiring Diagram
188
Johnson Controls Unitary Products
5123247-TTG-A-0515
Typical ZU/ZW/ZKT12 Cooling Unit with/without Electric Heat Unit (Options)
Johnson Controls Unitary Products
189
5123247-TTG-A-0515
BAS Controls Typical Wiring Diagrams
Typical SURVEYOR BAS Control Wiring Diagram
190
Johnson Controls Unitary Products
5123247-TTG-A-0515
Typical CPC BAS Control Wiring Diagram
Johnson Controls Unitary Products
191
5123247-TTG-A-0515
Typical HONEYWELL BAS Control Wiring Diagram
192
Johnson Controls Unitary Products
5123247-TTG-A-0515
Typical HONEYWELL BAS Control Wiring Diagram
Johnson Controls Unitary Products
193
5123247-TTG-A-0515
Weights and Dimensions
ZU/ZWTA3 thru T12 Unit Weights
Unit 4 Point Load Weight
Unit 6 Point Load Weight
FRONT
FRONT
LEFT
LEFT
B
C
B
A
A
E
F
D
Y
X
FRONT
LEFT
Weight (lbs.)
Center of Gravity
Size
Model
(Tons)
Shipping Operating
X
Y
TA3
(3)
TA4
(4)
TA5
(5)
T06
(6.5)
T07
(7.5)
T08
(8.5)
T10
(10)
T12
(12.5)
TA3
(3)
TA4
(4)
TA5
(5)
T06
(6.5)
T07
(7.5)
T08
(8.5)
T10
(10)
T12
(12.5)
194
D
C
4 Point Load Location (lbs.)
A
B
C
D
A
6 Point Load Location (lbs.)
B
C
D
E
F
ZU
728
723
40
26
175
143
182
223
121
105
92
117
134
154
ZU
768
763
40
26
185
151
192
235
128
111
97
124
141
162
ZU
869
864
40
26
210
171
217
266
145
126
110
140
160
184
ZU
915
910
38
24
212
158
230
309
149
121
100
147
177
217
ZU
915
910
38
24
212
158
230
309
149
121
100
147
177
217
ZU
1052
1047
38
24
244
182
265
356
171
139
116
169
203
249
ZU
1095
1090
38
24
254
189
276
371
178
145
120
176
211
260
ZU
1285
1280
48
24
240
281
410
350
156
173
192
280
252
227
ZW
745
740
40
26
180
147
186
228
124
108
95
120
137
157
ZW
780
775
40
24
174
142
207
253
120
104
91
133
152
175
ZW
775
770
40
24
172
141
205
251
119
103
91
132
151
174
ZW
1035
1030
39
25
245
191
260
333
170
144
122
167
195
232
ZW
1055
1050
39
25
250
195
265
340
174
146
125
170
199
236
ZW
1065
1060
38
24
247
184
268
360
173
141
117
171
206
253
ZW
1075
1070
39
24
245
191
278
357
170
143
122
178
209
248
ZW
1285
1280
48
24
240
281
410
350
156
173
192
280
252
227
Johnson Controls Unitary Products
5123247-TTG-A-0515
Weights and Dimensions
ZKTA3 thru T12 Unit Weights
Unit 4 Point Load Weight
Unit 6 Point Load Weight
FRONT
FRONT
LEFT
LEFT
B
C
B
A
A
D
C
E
F
D
Y
X
FRONT
LEFT
Weight (lbs.)
Center of Gravity
Size
Model
(Tons)
Shipping Operating
X
Y
4 Point Load Location (lbs.)
A
B
C
D
A
6 Point Load Location (lbs.)
B
C
D
E
F
TA3
(3)
ZK
872
867
40.3
25.5
205
170
223
269
141
124
110
144
163
185
TA4
(4)
ZK
885
880
40.9
25.1
202
172
232
273
139
124
112
151
168
187
TA5
(5)
ZK
872
867
41
25
198
169
230
269
136
122
110
150
166
184
ZK
962
957
38
23
214
159
249
335
150
122
101
159
191
234
ZK
970
965
38
23
216
161
251
337
151
123
102
160
193
236
ZK
1205
1200
38
25.5
297
221
291
390
208
170
141
185
223
274
ZK
1205
1200
38
25.5
297
221
291
390
208
170
141
185
223
274
ZK
1470
1465
51
25.5
270
363
477
355
172
207
254
334
272
226
T06
(6.5)
T07
(7.5)
T08
(8.5)
T10
(10)
T12
(12.5)
Johnson Controls Unitary Products
195
5123247-TTG-A-0515
ZU/ZW/ZKTA3 thru T12 Unit Accessory Weights
Unit Accessory
Economizer
Power Exhaust
Electric Heat1
Gas Heat2
Variable Frequency Drive3
Weight (lbs.)
Shipping
Operating
90
85
40
35
49
49
110
110
30
30
1. Weight given is for the maximum heater size available
(54KW).
2. Weight given is for the maximum number of tube heat
exchangers available (8 tube).
3. Weight includes mounting hardware, controls and manual
bypass option (6-1/2 to 12-1/2 ton only).
ZU/ZW/ZKTA3 thru T12 Unit Dimensions
ZU/ZWTA3 thru TA4 and ZKTA3
29.75
15.51
29.52
59.00
Ø 25.31
B
See detail A for gas inlet
A
C
D
E
11 3/8
F
See detail B for drain location
LEFT
4 3/16
FRONT
59
21 3/16
27 5/16
89
196
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZU/ZWTA5, ZKTA4 thru TA5 and ZU/ZW/ZKT06 thru T10
29.69
15.25
15.38
59.00
15.38
2X Ø 24.38
B
SEE DETAIL A FOR GAS INLET
A
C
D
E
11.38
F
59.00
4.19
LEFT
27.31
SEE DETAIL B
FOR DRAIN LOCATION
21.19
89.00
FRONT
Johnson Controls Unitary Products
197
5123247-TTG-A-0515
ZU/ZW/ZKT12
28.86
29.66
44.09
15.23
14.85
29.03
29.03
14.85
Ø 24.58 TYP. 4 PL.
15.23
B
See detail A for gas inlet
A
C
D
E
11 3/8
F
See detail B for drain location
LEFT
4 3/16
59
21 3/16
FRONT
27 5/16
89
ZH/ZJ/ZR037-150 Unit Physical Dimensions
Unit Model Number
ZUTA3, TA4, TA5, T06, T07
ZUT08, T10
ZUT12
ZWTA3, TA4, TA5
ZWT06, T07, T08, T10
ZWT12
ZKTA3, TA4, TA5
ZKT06, T07
ZKT08, T10
ZKT12
198
A
42
50 3/4
50 3/4
42
50 3/4
50 3/4
42
42
50 3/4
50 3/4
B
89
89
119 1/2
89
89
119 1/2
89
89
89
119 1/2
Dimension (in.)
C
22 1/8
18
30 3/16
24
30 3/16
24
22 1/8
18
30 3/16
24
30 3/16
24
22 1/8
18
22 1/8
18
30 3/16
24
30 3/16
24
D
3/16
3/16
3/16
3/16
3/16
3/16
3/16
3/16
3/16
3/16
15
17
17
15
17
17
15
15
17
17
E
3/16
3/16
3/16
3/16
3/16
3/16
3/16
3/16
3/16
3/16
6
6
6
6
6
6
6
6
6
6
F
3/16
3/16
3/16
3/16
3/16
3/16
3/16
3/16
3/16
3/16
Johnson Controls Unitary Products
5123247-TTG-A-0515
Detail A
3.184
3.184
Gas Pipe Inlet
Gas Pipe Inlet
Ø 2.000
Ø 2.000
Gas Exhaust Vent
Gas Exhaust Vent
Ø 3.126
Ø 3.126
17.541
14.594
7.715
7.705
4.737
4.727
42” CABINET
50 3/4” CABINET
Detail B
ZH/ZJ/ZR037-150 Unit Clearances
Direction
Top1
Front
Rear
5-3/8
Distance (in.)
72
36
36
Direction
Right
Left
Bottom2
Distance (in.)
12
36
0
1. Units must be installed outdoors. Over hanging structure or
shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustible floors made from wood
or class A, B or C roof covering materials.
3/4” FPT
Johnson Controls Unitary Products
199
5123247-TTG-A-0515
ZU/ZW/ZKTA3 thru T12 Unit Bottom Duct Openings
TOP VIEW
89
32 11/16
6 13/16
6 13/16
SUPPLY
AIR
RETURN
AIR
27 1/2
LEFT
18
24
RIGHT
21
20 1/8 19 1/8
17 1/8
12 5/16
Bottom condensate drain
14 1/2
25 9/16
Bottom gas
supply entry
16 3/8
18 1/16
FRONT
Bottom power, control
and convenience outlet
wiring entry
3X Ø 0.875
Ø 2.469
200
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZU/ZW/ZKTA3 thru T12 Unit Electrical Entry
Disconnect Swith Cover
Power Entry Ø 2-1/2
Control Entry Ø 7/8
Power Entry Ø 2-1/2
Convenience Outlet Cover
Convenience Outlet
Power Entry Ø 7/8
FRONT
ZU/ZW/ZKTA3 thru 10 Unit Side Duct Openings
Dot Plugs
18-1/4
Return
Air
A
Supply Air
D
B
2-31/32
5-5/32
C
31-11/16
Johnson Controls Unitary Products
201
5123247-TTG-A-0515
ZU/ZW/ZKT12 Unit Side Duct Openings
Dot Plugs
18-1/4
A
D
B
5-5/32
2-7/8
C
31-5/8
ZU/ZW/ZKTA3 thru T12 Side Duct Dimensions
Unit Model Number
ZUTA3, TA4, TA5, T06, T07
ZUT08, T10
ZUT12
ZWTA3, TA4, TA5
ZWT06, T07, T08, T10
ZWT12
ZKTA3, TA4, TA5
ZKT06, T07
ZKT08, T10
ZKT12
202
A
27 3/4
28 1/4
28 1/4
27 3/4
28 1/4
28 1/4
27 3/4
27 3/4
28 1/4
28 1/4
12
18
18
12
18
18
12
12
18
18
Dimension (in.)
B
C
1/16
27 1/2
1/16
28 1/4
1/16
28 1/4
1/16
27 1/2
1/16
28 1/4
1/16
28 1/4
1/16
27 1/2
1/16
27 1/2
1/16
28 1/4
1/16
28 1/4
D
16
18 1/4
18 1/4
16
18 1/4
18 1/4
16
16
18 1/4
18 1/4
Johnson Controls Unitary Products
5123247-TTG-A-0515
ZU/ZW/ZKTA3 thru T12 Unit Left Duct Opening
30-3/8
4-5/16
ZU/ZW/ZKTA3 thru T12 Unit Accessory Dimensions
ZU/ZW/ZKTA3 thru T12 Roof Curb
RIGHT
80-5/8
INSULATED DECK UNDER
CONDENSER SECTION
20
SUPPLY
20
6
RETURN
2 TYP.
30
INSULATED DECK UNDER
COMPRESSOR SECTION
50-1/2
8 or 14
Johnson Controls Unitary Products
FRONT
203
5123247-TTG-A-0515
ZU/ZW/ZKTA3 thru T12 Transition Roof Curb
2 TYP
50-1/2
30-1/2
23 4
80-5/8
26
RETURN
SUPPLY
10
76-5/8
94
FRONT
204
59-1/4
64-1/4
RIGHT
Johnson Controls Unitary Products
5123247-TTG-A-0515
Economizer Options
Economizer Usage
Application
Cabinet Height
Description
Model
Side Return
All
Horizontal economizer without barometric relief
2EE047069241
Downflow, End Return
Horizontal or ERV
42"
Economizer, 42” tall cabinet
2EE047074242
50"
Economizer, 50” tall cabinet
2EE047076242
1. Barometric relief must be ordered separately and installed in duct work.
2. Includes fresh air hood, exhaust hood and barometric relief.
Economizer Downflow W/Power Exhaust
Fresh Air Hood
Low Leak Economizer
Power Exhaust
Barometric
Relief Damper
Johnson Controls Unitary Products
Barometric Relief
Hood
205
Economizer End Return W/Power Exhaust
Fresh Air Hood
Field Installed
Duct Work
Low Leak
Economizer
Power Exhaust
Barometric Relief Damper
Barometric Relief Hood
Field Installed Horizontal Economizer W/Power Exhaust
Return Air Damper
Field Installed
Duct Work
Fresh Air Damper
Power Exhaust
Barometric
Relief Damper
Barometric
Relief Hood
Subject to change without notice. Printed in U.S.A.
Copyright © 2015 by Johnson Controls, Inc. All rights reserved.
York International Corporation
5005 York Drive
Norman, OK 73069
Fresh Air Hood
5123247-TTG-A-0515
Supersedes: Nothing
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement