Technical manual for the Vedo system 2.5.X

Technical manual for the Vedo system 2.5.X
EN
TECHNICAL
MANUAL
Technical manual for the Vedo system 2.5.X
Passion.Technology.Design.
Warnings
• Install the equipment by carefully following the instructions given by the manufacturer
and in compliance with the standards in force.
• All the equipment must only be used for the purpose it was designed for. Comelit
Group S.p.A. declines any responsibility for improper use of the apparatus, for any
alterations made by others for any reason or for the use of non-original accessories
or materials.
• Installation, mounting and assistance procedures for electrical devices must only be
performed by specialised electricians.
• For standard-compliant installation, a suitable (two-pole) device must be provided
for isolating and protecting the network power supply in the building's electrical
system (see diagram on page 8), in compliance with the standards in force (law
46/90): for example, a two-pole overload circuit breaker with rated current 6A. There
must be a gap of at least 3 [mm] between the isolating device contacts.
Maintenance
• Cut off the power supply before carrying out any maintenance work.
• It is recommended to check the correct operation of the safety system periodically
(at least once a month).
• Remove any dust accumulated in the control panel housing with a damp cloth,
without using any solvent, and check that there are no foreign bodies.
• Check the conditions of the connectors and the conductors.
• Carry out the maintenance and operation test of all the components (smoke
sensors, movement sensors, ...) as indicated in the respective technical manuals.
• Replace the protections on the terminals.
Certifications
• All the products comply with the requirements of Directive 2006/95/EC (which
replaces Directive 73/23/EEC and subsequent amendments), as certified by the
CE mark they carry.
• The device complies with the following standards:
• EN60950-1/A1:2010 relating to the safety of information technology equipment.
• EN50130-4:2011 relating to Alarm systems Part 4: Electromagnetic
compatibility
• EN50131 relating to Alarm systems - Intrusion and Hold Up alarm systems
• EN50136 elating to Alarm systems - Alarm transmission systems and
equipment
• All the system components must have safety grade 2 or higher to obtain grade 2
alarm system certification according to standard EN50131.
Product labels
• All articles have an ID label for product traceability. Two examples are shown
below:
article code
PCBVEDO68
000P1515XXXXXXXX
Via Don Arrigoni, 5
24020 Rovetta (BG) - Italy
article code
VEDOGSM
000P1515XXXXXXXX
Via Don Arrigoni, 5 - 24020 Rovetta (BG) - Italy
interpretation serial number:
protocol number
manufacturer’s
name
EAN article
identification code
serial number
manufacturer’s
name
serial number
000PWWYYXXXXXXXX
date of manufacture
week of manufacture (WW)
and year of manufacture (YY)
(in the sample label
1515= week15 of the year 15)
Control panel identification label
Grade 2 / Class II
EN 50131-1
EN 50131-3
EN 50131-6
EN 50131-10
Vin:230V~ +10% -15% 50/60Hz
EN 50136-1
Max Current 0,6A
EN 50136-2
(SP2/DP1)
TA-BBBB
VEDO34MXX
EN 60950
Table of contents
1. Introduction to the system............................................5
1.1 DESCRIPTION OF SYSTEM COMPONENTS...................................5
1.2.1 Main system specifications:.....................................................5
INPUTS / OUTPUTS / BALANCING...........................................................5
PROGRAMMING / MAINTENANCE...........................................................5
USER CODES / KEYS / REMOTE CONTROLS .......................................5
COMPATIBLE DEVICES / NUMBER OF DEVICES SUPPORTED............5
1.1.1 Communication standard.........................................................5
1.1.2 Addressing the modules...........................................................5
1.2 GENERAL...........................................................................................5
VARIOUS FUNCTIONS COMMON TO ALL CONTROL PANELS..............6
ONLY WITH GSM MODULE ART. VEDOGSM...........................................6
ONLY WITH IP MODULE ART. VEDOIP.....................................................6
ACTIVATIONS.............................................................................................6
ALERTS......................................................................................................6
ATS CATEGORIES BASED ON CONFIGURATIONS................................7
1.2.2 Power supply unit technical specifications...........................7
MAXIMUM CURRENT AVAILABLE FOR EXTERNAL DEVICES ON THE
BASIS OF THE CONTROL PANEL CONFIGURATION.............................8
1.2.3 Power supply unit technical specifications............................8
EXAMPLE OF TWO-POLE ISOLATING DEVICE.......................................8
2. Identification of parts and separation of circuits........9
2.1 POSITIONING OF COMPONENTS AND FIXTURES (FOR ART.
BOXPLASTIC)....................................................................................9
2.2 ROUTES FOR SEPARATING THE SELV CIRCUIT AND THE HIGH
VOLTAGE CIRCUIT (FOR ART. BOXPLASTIC)................................9
2.3 POSITIONING OF COMPONENTS AND FIXTURES (FOR ART.
BOXMETAL).......................................................................................10
2.4 ROUTES FOR SEPARATING THE SELV CIRCUIT AND THE HIGH
VOLTAGE CIRCUIT (FOR ART. BOXMETAL)...................................11
3. Technical and installation specifications.....................12
3.1 BOXPLASTIC.....................................................................................12
3.1.1 Technical specifications...........................................................12
3.1.2 Installation..................................................................................12
3.2 BOXMETAL........................................................................................12
3.2.1 Technical specifications...........................................................12
3.2.2 Installation..................................................................................12
3.3 CONTROL PANEL CARD ART. PCBVEDO10, ART. PCBVEDO34,
ART. PCBVEDO68, ART. PCBVEDO200...........................................13
3.3.1 Main features..............................................................................13
3.3.2 Technical specifications...........................................................14
CONFIGURATION JUMPERS....................................................................14
VARIOUS CONNECTORS..........................................................................14
MODULE CONNECTORS..........................................................................14
LED MEANINGS.........................................................................................14
TERMINAL BLOCK M11-M12.....................................................................14
TERMINAL BLOCK M2-M3-M4-M5............................................................14
TERMINAL BLOCK M6-M7-M8-M9-M10....................................................14
MOUNTING................................................................................................14
3.4 INTERNAL EXPANSIONS..................................................................15
3.4.1 Telephone dialler functions (PSTN as standard)....................15
SPECIFICATIONS ACCORDING TO STANDARD EN50136-2..................15
CONNECTION OF THE TELEPHONE LINE TO THE CONTROL PANEL.15
3.4.2 Messages and Voice Control expansion module (Art.
VEDOVOICE)..............................................................................15
AUDIO MODULE FUNCTIONS..................................................................15
Certification ID code
"XX" represents all control panels of the same type
For every type of control panel (VEDO10, VEDO34, VEDO34M, VEDO68,
VEDO68M), there are different language versions, identified by a code. To keep
things simple, in the manual the control panels are only referred to as VEDO10,
VEDO34, VEDO34M, VEDO68, VEDO68M. The full article code will appear on the
traceability label (e.g. VEDO34MEN)
for Italian XX = "" (e.g. VEDO34M)
for English XX = EN (e.g. VEDO34MEN)
for French XX = FR (e.g. VEDO34MFR)
for Dutch XX = NL (e.g. VEDO34MNL)
for Spanish XX = ES (e.g. VEDO34MES)
2
TECHNICAL SPECIFICATIONS.................................................................15
SPECIFICATIONS ACCORDING TO STANDARD EN50136-2..................15
FITTING THE MESSAGES AND VOICE CONTROL EXPANSION MODULE....15
3.4.3 GSM communication expansion module (Art. VEDOGSM)...16
GSM MODULE FUNCTIONS.....................................................................16
TECHNICAL SPECIFICATIONS.................................................................16
SPECIFICATIONS ACCORDING TO STANDARD EN50136-2..................16
MEANING OF THE LEDS ON THE IP GSM MODULE..............................16
CONFIGURATION JUMPERS....................................................................16
FITTING THE GSM MODULE....................................................................16
FITTING THE SIM CARD...........................................................................17
3.4.4 TCP/IP Ethernet expansion module (Art. VEDOIP).................18
TCP/IP MODULE FUNCTIONS..................................................................18
TECHNICAL SPECIFICATIONS.................................................................18
3.9 EXPANSIONS ON 485 BUS...............................................................28
3.9.1 Expansions plastic housing.....................................................28
MOUNTING THE PLASTIC HOUSING......................................................28
MEANING OF THE LEDS ON THE IP MODULE.......................................18
3.9.2 Expansion on bus with 8 balanceable inputs and 8 logic
outputs on bus (Art. VEDO8I8O)...............................................28
FITTING THE TCP/IP MODULE.................................................................18
MAIN FEATURES.......................................................................................28
FITTING THE RJ45 CONNECTOR............................................................18
TECHNICAL SPECIFICATIONS.................................................................28
FITTING THE RJ45 CONNECTOR............................................................18
CONFIGURATION JUMPERS....................................................................29
FITTING THE MICROSD MEMORY CARD................................................18
ADDRESSING............................................................................................29
REMOVING THE MICROSD MEMORY CARD..........................................18
SETTING THE SPEED OF THE CARD ON THE BUS...............................29
SPECIFICATIONS ACCORDING TO STANDARD EN50136-2..................18
3.5 GENERAL INFORMATION ABOUT CONNECTING DEVICES TO
THE BUS.............................................................................................19
3.5.1 Bus line termination..................................................................19
3.6 WIRING THE INPUTS........................................................................19
3.6.1 Normally closed (NC)................................................................19
3.6.2 Normally open (NO)...................................................................19
3.6.3 Single balance............................................................................19
3.6.4 Double balance..........................................................................19
3.6.5 Triple balance.............................................................................20
3.6.6 Triple balance with jamming.....................................................20
3.6.7 Double zone (double)................................................................20
3.6.8 Double zone with end of line (EOL double).............................20
3.6.9 Wiring the control panel's 24-hour input.................................20
3.6.10 Wiring the telephone dialler on the PSTN network..............20
3.7 CONTROL AND DISPLAY COMPONENTS.......................................21
3.7.1 LCD keypad (Art. VEDOLCD) and keypad with RFID key
reader (Art. VEDOLCDPROX)....................................................21
MAIN FEATURES:......................................................................................21
TECHNICAL SPECIFICATIONS.................................................................21
MEANING OF THE KEYPAD LEDS...........................................................21
LCD KEYPAD TERMINAL BLOCK DESCRIPTION....................................21
DIP SWITCHES AND BUS TERMINATION................................................21
MOUNTING THE KEYPADS.......................................................................22
3.7.2 RFID proximity reader on bus (Art. VEDOPROX)...................22
MAIN FEATURES.......................................................................................22
TECHNICAL SPECIFICATIONS.................................................................22
SETTING RFID READER SPEED..............................................................22
ADDRESSING............................................................................................23
RFID KEY READER ON BUS TERMINAL BLOCK DESCRIPTION...........23
485 LINE TERMINATION............................................................................23
MEANING OF THE LEDS ON THE RFID READER...................................23
MOUNTING THE RFID KEY READER ON BUS........................................23
3.7.3 RFID keys (Art. SK9050x/A)......................................................24
3.8 OTHER DEVICES THAT CAN BE CONNECTED TO THE 485 BUS....24
3.8.1 Vedo Touch (Art. VEDOTOUCH) / Mini Touch (Art. 20034607)
with RFID key reader.................................................................24
MAIN FEATURES:......................................................................................24
TERMINAL BLOCK M1...............................................................................29
TERMINAL BLOCK M2...............................................................................29
LED MEANINGS.........................................................................................29
MOUNTING................................................................................................29
3.9.3 Bidirectional radio expansion on bus (Art. VEDORF)............29
MAIN FEATURES.......................................................................................29
TECHNICAL SPECIFICATIONS.................................................................29
CONFIGURATION JUMPERS....................................................................29
ADDRESSING............................................................................................30
SETTING THE SPEED OF THE CARD ON THE BUS...............................30
TERMINAL BLOCK DESCRIPTION...........................................................30
LED MEANINGS.........................................................................................30
MOUNTING................................................................................................30
3.9.4 PAL/IP video module Art. VEDOCCTV.....................................30
MAIN FEATURES.......................................................................................30
TECHNICAL SPECIFICATIONS.................................................................31
CONFIGURATION JUMPERS....................................................................31
CONNECTING VEDOCCTV WITH SWITCH/HUB AND CONTROL PANEL
POWER SUPPLY........................................................................................31
CONNECTING THE VEDOCCTV MODULE WITH POE SWITCH/HUB....31
MMS
SUPPORT
–
SYSTEM
DESCRIPTION
AND
MINIMUM
REQUIREMENTS.......................................................................................31
VIDEO STREAMING SUPPORT, RECORDING FILMS AND FRAME
CAPTURES - DESCRIPTION OF THE MINIMUM FEATURES OF THE
SYSTEM.....................................................................................................31
NETWORK PARAMETERS OF PAL/IP MODULE......................................31
3.10 WIRELESS SENSORS AND ACCESSORIES.................................32
3.11 OUTPUTS SIREN CONNECTION EXAMPLES...............................32
3.11.1 Connecting a self-powered siren with 3 or 2 wires..............32
3.11.2 Connecting a non-self-powered indoor siren.......................32
3.11.3 2-wire connection of indoor siren and self-powered siren
with siren fault zone and siren sabotage zone.......................33
3.11.4 2-wire connection of self-powered siren with siren fault
zone and siren sabotage zone..................................................33
3.11.5 3-wire connection of self-powered siren with siren fault
zone and siren sabotage zone..................................................33
3.12 EXAMPLE OF CONNECTION TO OUTPUTS TC1 AND TC2.........33
485 LINE TERMINATION............................................................................25
3.13 POWER SUPPLY STATIONS...........................................................34
3.13.1 Power supply unit management card for VEDO series
control panels Art. PCBPSU.....................................................34
LED MEANINGS.........................................................................................25
MAIN FEATURES.......................................................................................34
ADDRESSING THE DEVICE ON THE BUS...............................................25
TECHNICAL SPECIFICATIONS.................................................................34
TECHNICAL SPECIFICATIONS.................................................................25
DESCRIPTION OF TERMINAL BLOCK.....................................................25
SPEED SETTING.......................................................................................25
TERMINAL BLOCK M1-M2-M3-M4-M5-M6................................................34
MOUNTING................................................................................................25
ADDRESSING............................................................................................35
3.8.2 Planux Manager with RFID key reader (Art. 20034801)..........26
SETTING THE SPEED OF THE CARD ON THE BUS...............................35
MAIN FEATURES:......................................................................................26
LED MEANINGS.........................................................................................35
TECHNICAL SPECIFICATIONS.................................................................26
POWER SUPPLY UNIT CONNECTOR......................................................35
DESCRIPTION OF TERMINAL BLOCK.....................................................26
CONFIGURATION JUMPERS....................................................................35
485 LINE TERMINATION............................................................................26
ANTI-TAMPER CONNECTION...................................................................35
ADDRESSING THE DEVICE ON THE BUS...............................................26
CONNECTING V- REFERENCE TERMINAL ............................................35
SPEED SETTING.......................................................................................26
EARTH CONNECTION...............................................................................35
MOUNTING................................................................................................26
3.14 BUS ATOR (VEDOISO)....................................................................35
3.8.3 Icona Manager ViP (Art. 20003310W).......................................27
MAIN FEATURES:......................................................................................27
TECHNICAL SPECIFICATIONS.................................................................27
DESCRIPTION OF TERMINAL BLOCK 1..................................................27
DESCRIPTION OF TERMINAL BLOCK 2..................................................27
DESCRIPTION OF TERMINAL BLOCK 3..................................................27
485 LINE TERMINATION............................................................................27
LED MEANINGS.........................................................................................27
ADDRESSING THE DEVICE ON THE BUS...............................................27
SPEED SETTING.......................................................................................27
MAIN FEATURES.......................................................................................35
TECHNICAL SPECIFICATIONS.................................................................35
BUS ISOLATOR TERMINAL BLOCK..........................................................35
ADDRESSING............................................................................................36
SETTING SPEED ON THE BUS................................................................36
CONFIGURATION JUMPERS....................................................................36
LED MEANINGS.........................................................................................36
TAMPER CONTACT CONNECTION..........................................................36
MOUNTING................................................................................................36
MOUNTING................................................................................................27
3
4. Appendix: Mounting instructions.................................37
4.1 OPENING THE HOUSING ART. BOXPLASTIC.................................37
4.2 PREPARING THE HOUSING ART. BOXPLASTIC............................37
4.3 FIXING THE HOUSING ART. BOXPLASTIC TO THE WALL............37
4.4 MOUNTING THE CONTROL PANEL CARD ART. PCBVEDO10 /
PCBVEDO34 / PCBVEDO68 / PCBVEDO200 AND PCBPSU IN A
HOUSING ART. BOXPLASTIC...........................................................38
4.6 MOUNTING THE EXPANSION ART. VEDO8I8O AND ART. VEDORF
IN A HOUSING ART. BOXPLASTIC...................................................38
4.5 MOUNTING THE POWER SUPPLY UNIT PSU15 IN A HOUSING ART.
BOXPLASTIC.....................................................................................38
4.7 OPENING THE HOUSING ART. BOXMETAL....................................39
4.8 FIXING THE HOUSING ART. BOXMETAL TO THE WALL...............39
4.9 MOUNTING THE CONTROL PANEL CARD ART. PCBVEDO10 /
PCBVEDO34 / PCBVEDO68 / PCBVEDO200 AND PCBPSU IN A
HOUSING ART. BOXMETAL..............................................................40
4.11 MOUNTING THE POWER SUPPLY UNIT PSU15 - PSU50 IN A
HOUSING ART. BOXMETAL..............................................................40
4.10 MOUNTING THE EXPANSION ART. VEDO8I8O IN A HOUSING
ART. BOXMETAL................................................................................40
TOTAL RESET............................................................................................51
PARTIAL RESET (CODE RECOVERY)......................................................51
5.3.20 Setting the control panel to Service Status .........................52
5.3.21 Exiting Service Status.............................................................52
5.4 FAST NAVIGATION OF KEYPAD MENU (INSTALLER AND USER)...52
EXAMPLE 1: "ENABLE BUZZER" ON KEYPAD 1.....................................52
EXAMPLE 1: "ENABLE BUZZER" ON KEYPAD 1 FROM DEPTH LEVEL 2
PARAMETERS PRG./VEDOTOUCH..........................................................52
5.5 CONFIGURATIONS NECESSARY TO GUARANTEE GRADE 2
CERTIFICATION ACCORDING TO EN50131-1.................................53
5.5.1 Keypads......................................................................................53
5.5.2 App..............................................................................................53
5.5.3 Input/output expansions (8I8O)................................................53
5.5.4 Power supply stations...............................................................53
5.5.5 Isolators......................................................................................54
5.5.6 Radio expansion........................................................................54
5.5.7 Radio outputs.............................................................................54
RADIO OUTPUT EVENTS.........................................................................54
RADIO OUTPUT CONFIGURATION..........................................................54
4.12 MOUNTING THE MODULE ART. VEDOCCTV IN A METAL
HOUSING ART. BOXMETAL..............................................................41
5.5.8 Radio controls............................................................................54
5.5.9 Radio zones................................................................................54
4.13 FITTING THE BATTERY ART. 30076003 / 30076004 IN METAL
CONTAINER ART. BOXMETAL..........................................................41
5.5.10 Wired zones..............................................................................54
4.14 MOUNTING THE KEYPAD ART. VEDOLCD - ART. VEDOLCDPROX
ON BOX 503.......................................................................................42
4.15 MOUNTING THE KEYPAD ON THE WALL ART. VEDOLCD - ART.
VEDOLCDPROX.................................................................................42
4.16 MOUNTING THE VEDO TOUCH (ART. VEDOTOUCH) / MINI
TOUCH (ART. 20034607) ON BOX 503.............................................43
4.17 MOUNTING PLANUX MONITOR (ART. 20034801) WITH FLUSHMOUNTED BOX ART. 6117................................................................44
4.18 MOUNTING PLANUX MONITOR (ART. 20034801) WITH WALL
SUPPORT ART. 6120.........................................................................45
4.19 WALL-MOUNTING ICONA MANAGER VIP (ART. 6620) / SU 503
SERIES BOX / ROUND BOX............................................. 46
4.20 MOUNTING ICONA MANAGER VIP ON A FLUSH MOUNTED BOX
ART. 6117............................................................................................47
4.21 PREPARING THE PLASTIC HOUSING FOR MOUNTING THE
EXPANSION ART. VEDORF / VEDO8I8O..........................................48
4.22 WALL-MOUNTING THE PLASTIC HOUSING FOR MOUNTING THE
EXPANSION ART. VEDORF / VEDO8I8O..........................................48
5. Appendix: notes on installation and programming....49
5.1 WHAT TO DO BEFORE POWERING UP THE SYSTEM..................49
5.1.1 Connect the zone inputs correctly...........................................49
5.1.2 Connect the bus modules.........................................................49
5.1.3 Close all the anti-tamper inputs...............................................49
5.1.4 Powering up...............................................................................49
5.2 DEFAULT CONFIGURATION.............................................................49
5.3 INTRODUCTION TO PROGRAMMING FROM THE KEYPAD..........49
5.3.1 Keypad description...................................................................49
5.3.2 Default codes ............................................................................49
5.3.3 Keypad navigation mode..........................................................49
5.3.4 Modifying a numerical value.....................................................49
5.3.5 Editing an alphanumeric string................................................49
5.3.6 Setting the keypad serial number............................................50
5.3.7 Total activation of the alarm system........................................50
5.3.8 Partial activation of the alarm system / execution of a
scenario......................................................................................50
5.3.9 Total deactivation of the alarm system....................................50
5.3.10 Muting an alarm with the system deactivated......................50
5.3.11 Entering programming as a User...........................................50
5.3.12 Entering programming as an Installer (installer code
authorisation).............................................................................50
5.3.13 Changing date and time..........................................................50
5.3.14 Acquiring an RFID key code from the keypad......................50
5.3.15 Acquiring a radio sensor code from the keypad..................51
4
5.3.16 Acquiring a radio control code from the keypad..................51
5.3.17 Acquiring a siren code from the keypad...............................51
5.3.18 Exiting programming mode....................................................51
5.3.19 Restoring factory settings......................................................51
RADIO SUBZONE PARAMETERS.............................................................54
SUBZONE PARAMETERS.........................................................................54
5.5.11 Areas.........................................................................................54
5.5.12 Wired outputs...........................................................................54
WIRED OUTPUT EVENTS.........................................................................55
WIRED OUTPUT CONFIGURATION.........................................................55
5.5.13 User...........................................................................................55
CODE TYPE...............................................................................................55
5.5.14 Installers...................................................................................55
CODE TYPE...............................................................................................55
5.5.15 IP Options ................................................................................55
5.5.16 GSM settings............................................................................55
5.5.17 Telephone Options...................................................................55
5.5.18 Phone Book / Email.................................................................55
5.5.19 Digital communicator contacts list........................................55
5.5.20 Generic events.........................................................................55
5.5.21 Detailed events........................................................................56
DETAILED EVENTS FLAGS......................................................................56
5.5.22 Service voice messages.........................................................57
5.5.23 Timer Types..............................................................................57
TIMER TYPE SCHEDULES.......................................................................57
5.5.24 Timer Model .............................................................................57
5.5.25 System Parameters.................................................................57
5.5.26 Events to be saved..................................................................57
5.6 CONFIGURATIONS NECESSARY TO GUARANTEE INCERT
CERTIFICATION.................................................................................59
5.6.1 Code type...................................................................................59
5.6.2 System parameters....................................................................59
5.7 OFFICIAL SYMBOL CONVENTIONS FOR ANTI-INTRUSION
SYSTEMS...........................................................................................59
5.8 SHIELDED CABLE CONDUCTOR RESISTANCE TABLE................59
5.8.1 Input and signal connections...................................................59
5.8.2 Power supply connections.......................................................60
5.9 DATA NETWORK CONNECTION CABLE.........................................60
1. Introduction to the system
Vedo is a modern, practical I&HAS (Intrusion and Hold Up alarm
system) capable of meeting the technical and performance
requirements of modern security systems to the best effect. The Vedo
system allows the creation of systems that require up to 68 individually
balanced standard zones with triple balance, which can be assigned to
a maximum of 16 areas.
The system integrates home automation functions that do not influence
the behaviour of the alarm system.
1.1 DESCRIPTION OF SYSTEM COMPONENTS
The control panel is enclosed in a compact housing, which also
accommodates the power supply unit. According to system
requirements, it is possible to equip the control panel card directly with
a module for GSM communication, a messages / voice control module
and a module for communication on IP protocol.
The connectors for powering the control panel are routed from the
power supply unit.
Inside the metal housings it is possible to accommodate 2 standard
input/output expansions. In the plastic housings it is possible to fit
2 8IO expansion modules or 1 8IO expansion module and a radio
expansion. The expansion modules are connected to the Bus.
The system comprises a master unit (the control panel) and a certain
number of slave units (the peripherals on the Bus). Regardless
of system activation status, the control panel's task is to query the
peripheral units periodically to determine correct operation and obtain
information about system status. Each peripheral component is
equipped with local intelligence, which enables it to perform a certain
number of tasks independently and, at the request of the control panel,
communicate its status and any information relating to its specific
peripheral functions.
1.1.1 Communication standard
Communication between the control panel and the expansions
takes place by means of a standard RS485 Bus. The control
panel's standard communication speed is set to 38400 baud.
1.1.2 Addressing the modules
The modules are all connected to the same Bus, and are
recognisable by their unique address. Depending on the
peripheral, this address can be configured by physical means
(e.g. DIP switches as on the input and output expansions) or by
means of a software configuration (e.g. LCD keypads).
√√ IMPORTANT: no two components of the same type and
with the same logical address must be present on the bus.
For example, there cannot be two or more keypads with
the same address. Should this happen, the system will be
unable to function correctly and will generate a bus error.
1.2 GENERAL
The control panel is supplied with a built-in digital dialler.
The control panel can be programmed directly from the keypad or,
more easily, by means of dedicated software. The audio messages
can be modified only by using the programming software from a PC.
The association of zones to areas and partial subgroups of areas
allows total, partial or selective activation of the system, according to
the authorisations assigned (at the configuration stage) to the user
who performs the operations.
Each input event can be associated with multiple outputs, thus
potentially involving all the outputs configured at the installation stage.
The flexibility of this arrangement makes it possible to adapt the control
panel to the most wide-ranging requirements.
1.2.1 Main system specifications:
TAB_caratteristiche centrale
INPUTS / OUTPUTS / BALANCING
VEDO10
VEDO34
VEDO34M
Control Panel Inputs
VEDO68
VEDO68M
VEDO200
VEDO200M
68 (64Radio)
200
200
8 + 1 24h
18
(2wire+8radio)
(max 16 radio)
34 (mixed)
34 (mixed)
Maximum Number Outputs (wired +radio)
16
36
36
50
50
100
100
Double Function
No
Yes
Yes
Yes
Yes
Yes
Yes
Maximum Number of Inputs
Control Panel Outputs
Balance Type
68 (64Radio)
3: 1Relay [email protected] + 2oc 100mA
NO, NC,
Single,
Double, Triple,
Triple with
jamming
NO, NC, Single, Double, Triple, Triple with jamming, Double zone, Double zone with end of line
PROGRAMMING / MAINTENANCE
VEDO10
VEDO34
VEDO34M
Programming/Reading of options in local/
remote mode
VEDO68
VEDO68M
VEDO200
VEDO200M
Yes
Central programming
USB/LAN
Programming from Keypad or Vedo Touch
with emulated keypad
Yes
Programmable test call
Yes
Remote maintenance
Yes with IP card
Periodic test call
Yes on digital dialler
USER CODES / KEYS / REMOTE CONTROLS
VEDO10
VEDO34
VEDO34M
VEDO68
VEDO68M
VEDO200
VEDO200M
User Code
8
32
32
50
50
200
200
Installer Code
2
5
5
5
5
5
5
Manufacturer Code
1
Remote controls
11
38
38
56
56
64
64
Keys
11
38
38
56
56
200
200
VEDO200M
COMPATIBLE DEVICES / NUMBER OF DEVICES SUPPORTED
VEDO10
VEDO34
VEDO34M
VEDO68
VEDO68M
VEDO200
Plastic housing
Yes
Yes
No
Yes
No
Yes
No
Metal housing
No
No
Yes
No
Yes
No
Yes
PSU15
PSU15
PSU15
PSU50
PSU15
PSU15
PSU50
PSU15
PSU15
PSU50
2
4
4
8
8
8
8
Power supply unit
Maximum number power supply stations
5
Number of IN/OUT expansions
0
8
8
12
12
50
RFID readers
2
8
8
8
8
16
16
2 (min 1)*
8 (min 1)*
8 (min 1)*
8 (min 1)*
8 (min 1)*
16 (min 1)*
16 (min 1)*
Keypads / Keypads with proximity reader
50
Vedo Touch with proximity reader
1
2
2
4
4
4
4
Touch Devices (Mini Touch, Planux Manager,
Icona Manager VIP with proximity reader)
1
2
2
4
4
4
4
Radio Receivers
1
2
2
3
3
8
8
Plug-in Audio Module
Yes
Voice Menu Command Interface
Yes
Plug-in GSM Module
Yes
Plug-in TCP/IP Module
Yes
PAL IP Module
2
Number of cameras managed
4
8 (for every PAL/IP module)
Integrated interface PSTN
Yes
App Phone
8
* it is recommended to install at least one keypad (Art. VEDOLCD / Art. VEDOLCDPROX)
ACTIVATIONS
Areas
VEDO10
VEDO34
VEDO34M
VEDO68
VEDO68M
VEDO200
VEDO200M
2
8
8
8
8
16
16
32
32
60
60
32
32
Area activation modes
4 (Total, partial 1, partial 2, partial 1+2)
Partial Activations
Activation Programmes (Scenarios)
2
8
8
8
16
Programmable Auto Activation/Deactivation
Auto-activation Models (Public Holidays +
Schedules)
30
Area Exclusion for Patrol function with
automatic or manual reactivation
Timer
Accepts commands from telephone with tone
dialling or by SMS
16
Yes
Yes
4
16
16
16
16
Activation/Deactivation, activation/deactivation of zones, outputs, timers, Status interrogation of individual Areas and Zones),
stop alarms.
ALERTS
VEDO10
Alert options in accordance with EN50131-1
Text-to-Speech Audio Messages (general
events)
VEDO34
20
32
Audio message
VEDO68
32
48
Built-in digital dialler
Yes
Voice Telephone Numbers, SMS and MMS
16
Digital Telephone Numbers
4
Email addresses
16
Events Log (according to standard EN50131-1)
1024 events with date and time
Additional Events Log
1024 events with date and time
VEDO200
VEDO200M
48
48
48
4096 events with date and time
4096 events with date and time
Yes
Supports the CONTACT ID protocol
Priority in processing and indicating signals
VEDO68M
1020 minutes
SMS and for Alarm Receiving Centres
Yes
1) Alarm Events, 2) Sabotage, 3) Malfunctions, 4) Exclusions, 5) Other events
In the telephone options it is possible to set the priority for sending messages by sms, email, mms, voice, digital
VARIOUS FUNCTIONS COMMON TO ALL CONTROL PANELS
• Up to 10 simultaneous connections
• Telephone access via sounder or dialler
• Telephone line status check
• Skip Answerer
• Possibility of sharing the telephone line with another
answering device
• Integrated voice calls (Text To Speech)
• Telephone voice control, with remote DTMF management
• Possibility of downloading pre-recorded Text to Speech
voice messages
• Function keys for alarm calls and rapid activations (available
on keypad, Mini Touch, Planux Manager, and App)
• Event transmission in Contact ID format
ONLY WITH GSM MODULE ART. VEDOGSM
• GSM850, EGSM900, DCS1800, PCS 1900
• GSM/GPRS channel support
• Main or reserve telephone dialler
• Indication of alarms/malfunctions/sabotage/events via SMS
• Customisable SMS messages
• Control panel status interrogation via SMS
• Checking residual credit of the prepaid SIM
• Transmission of Voice Messages via GSM
• Transmission of Contact ID via GSM
6
VEDO34M
Type A: two sirens with remote power supply + PSTN or GSM or IP dialler. The first siren connected to the control panel
relay, the second siren connected to an additional output (for example, an output on an 8IO expansion device) via a lowconsumption relay.
Type B: one self-powered siren + PSTN or GSM or IP dialler.
Type C: two active diallers of PSTN or GSM or IP.
• Event transmission in Contact ID format
• Event transmission by email with images
• Event transmission by MMS
ONLY WITH IP MODULE ART. VEDOIP
• Ethernet Interface.
• Event transmission on IP
• Programming and Monitoring of the control panel via LAN
through Safe Manager
• Programming and Monitoring of the control panel via
Internet through Safe Manager
• Control panel management vie Internet through Vedo App
• Event alert via e-mail and on Vedo App with alerts with
proprietary protocol
• Alert by e-mail for alarms/malfunctions/sabotage/events
with images
ATS CATEGORIES BASED ON CONFIGURATIONS
The Vedo control panels equipped with transmission devices (integrated or optional extras) listed in the table below are SPTs (Supervised
Premises Transceiver) which interface with the alarm system and transmit alarms via various networks.
SPT CONFIGURATION
Primary interface
PCBVEDOXX(PSTN)
PSTN
PSTN or GSM
PSTN or Email IP
PSTN o GSM or Email IP
GSM
VEDOGSM
√
√
√
√
VEDOIP
√
√
√
√
Email IP
DUAL PATH
SP2
√
SP2
DP1
SP2
DP1
SP2
DP1
SP2
√
√
√
GSM or Email IP
ATS CONFIGURATION
SINGLE PATH
SP2
SP2
DP1
1.2.2 Power supply unit technical specifications
Technical specifications complying with standard EN50131-6 (new standard which establishes the required performances of a power
supply unit in alarm systems).
VEDO10
VEDO34
VEDO34M
VEDO68
VEDO68M
VEDO200
VEDO200M
260 x 280 x 80
mm
260 x 280 x 80
mm
440 x 315 x 95
mm
260 x 280 x 80
mm
440 x 315 x 95
mm
260 x 280 x 80
mm
440 x 315 x 95
mm
Weight (without battery)
1313g
1313g
3845 (with
PSU15)
4039 (with
PSU50)
1313g
3845 (with
PSU15)
4039 (with
PSU50)
1313g
3845 (with
PSU15)
4039 (with
PSU50)
Power supply units supported
PSU15
PSU15
PSU15
PSU50
PSU15
PSU15
PSU50
PSU15
PSU15
PSU50
Art. 30076003
12V/7Ah
Art. 30076003
12V/7Ah
Art. 30076003
12V/7Ah
Art. 30076004
12V and 18Ah
Art. 30076003
12V/7Ah
Art. 30076003
12V/7Ah
Art. 30076004
12V and 18Ah
Art. 30076003
12V/7Ah
Art. 30076003
12V/7Ah
Art. 30076004
12V e 18Ah
8h
8h
8h/19h
8h/19h
8h
8h/19h
Dimensions (L x H x P)
Batteries supported
Max. battery charging current
Battery 80% charging time
0.8A
8h
Low Battery Fault Generation in
presence of EPS
12V
Low Battery Fault Generation in
absence of EPS
11.5V
Low output voltage fault on power
supply unit
12.8V
Control panel switch-off in absence
of EPS for Protection against
deep discharges (the battery is
disconnected to avoid damage)
10.5V
Maximum current for V+SIR outputs
0.75A
Intervention voltage of the
protection against voltage surges:
battery disconnection
15V
Maximum current for V+bus,V+AUX
outputs
1.5A
Output voltage operating range
(Vbus, VAUX1, VAUX2)
10 ~ 15 V
CN1 input voltage operating range
12.8 ~ 15 V
CN2 input voltage operating range
(Battery)
10.5 ~ 15 V
Control panel card consumption
(min./max.)
Control panel in standby: 50mA +
All active outputs: 40mA +
PSTA active and communicating: 35mA +
Audio: 1mA +
GSM: 10mA idle, 35mA communicating +
IP: 55mA
Average power consumption in 1 h: PCBVEDOXX 90mAh, VEDOGSM 24mAh, VEDOIP 55mAh
Maximum consumption (with
audio module, IP module active
and connected, GSM module
transmitting)
Control panel in alarm status with all expansions active: 216mA
Control panel in standby with all expansions active: 116mA
Maximum current available for
external devices
Depends on the control panel configuration (see table “Maximum current available for external devices on the basis of the control panel
configuration”, page 8)
Maximum current delivered to
outputs TC1 and TC2
100mA
Relay contacts capacity in output
exchange NO-COM-NC
Operating temperature and
Operating humidity
Safety grade
Type of power supply unit
Environmental class
3A @ 24V
-10° / + 55° with warm dry air
-10° / + 40° C with max + 93% RH (not condensed)
2 according to EN50131-1 *
not certified
TYPE A according to standard EN50131-6
II according to EN50131-1
not certified
* Respecting any indications for configuration and installation
7
MAXIMUM CURRENT AVAILABLE FOR EXTERNAL DEVICES ON THE BASIS OF THE CONTROL PANEL CONFIGURATION
POSSIBLE CONFIGURATIONS
POWER
SUPPLY UNIT
BATTERY
CONTROL PANEL
MAXIMUM CURRENT
VEDO10
VEDO34
VEDO34M
VEDO68
VEDO68M
VEDO200
VEDO200M
30076004 12V and
18Ah
PSU50
1500mA
(– mean current
absorbed by the
control panel)
√
√
√
30076004 12V and
18Ah
PSU15
700mA
(– mean current
absorbed by the
control panel)
√
√
√
30076003 12V and 7Ah
PSU15
580mA
(– mean current
absorbed by the
control panel)
30076003 12V e 7Ah
PSU50
580mA
(– mean current
absorbed by the
control panel)
√
√
√
√
√
√
√
√
√
Internal expansions: Art. VEDOVOICE, VEDOGSM, VEDOIP
The control panel is certified up to grade 2 according to
standard EN50131-1. It is possible to maintain grade 2 system
certification only if the system consists of components of grade
II or higher.
Keypads and activators: Art. VEDOLCD, VEDOLCDPROX
Expansions on 485 bus: Art. VEDO8I8O
Power supply units: Art. PSU15, PSU50
Articles certified with safety grade 2 according to standard
EN50131-1:
PIsolators: Art. VEDOISO
Housings: Art. BOXPLASTIC, BOXMETAL
Control panel cards: Art. PCBVEDO10, PCBVEDO34,
PCBVEDO68
1.2.3 Power supply unit technical specifications
Art. PSU15 / PSU50 complies with standards EN50130-4:2011, EN 60950-1:2006 + A11:2009 + A1:2010 + A12:2011 + A2:2013
Power supply unit versions
Name of manufacturer / supplier
Dimensions (L x H x P)
Weight
PSU15
PSU50
Comelit Group S.p.A.
Comelit Group S.p.A.
78 x 110 x 36 mm
98 x129 x40 mm
241 g
435 g
Input voltage
230V~ + 10% -15%
AC input frequency
AC Alternating Current
Output voltage
Rated current
Output voltage ripple
Voltage surge protection
Overload protection
Operating temperature and Operating humidity
50/60 Hz
@230V~ : 0,6A
14.0 V
@230V~ : 1,3A
± 2%
14.0 V
1.5A Max
300mV
+50%
110~180% rated output power
-10° / + 55° with warm dry air
-10° / + 40° C with max + 93% RH (not condensed)
Safety grade
2 according to EN50131-1*
II according to EN50131-1
* Respecting any indications for configuration and installation
EXAMPLE OF TWO-POLE ISOLATING DEVICE
EARTH
NEUTRAL
PHASE
Control
panel
230 V
50 Hz
FIG_sezionamento impianto
8
± 2%
5A Max
Environmental class
Wiring diagram: two-pole mains switch
(for example overload circuit breaker with
rated current 6A) able to isolate the power
supply of the device. There must be a gap
of at least 3 [mm] between the isolating
device contacts.
√
2. Identification of parts and separation of circuits
1
2.1 POSITIONING OF
COMPONENTS AND
FIXTURES (FOR
ART. BOXPLASTIC)
1. Holes for fixing the housing
2. Clips for fixing the control panel card
Art. PCBVEDO10 - PCBVEDO34
- PCBVEDO68 - PCBVEDO200 PCBPSU
3. Clip for fixing expansion Art.
VEDO8I8O
4. Housing of fixing screw for power
supply unit Art. PSU15
5. Clip for fixing battery Art. 30076003
6. Position of control panel identification
label
7. Anti-tear tamper hole
8. Cable inlet holes
9. Clip for fixing expansion Art. VEDORF
/ VEDO8I8O
A. Control panel card position Art.
PCBVEDO10 - PCBVEDO34
- PCBVEDO68 - PCBVEDO200 PCBPSU
B. Expansion position Art. VEDO8I8O
C. Power supply unit position Art. PSU15
D. Battery position Art. 30076003
E. Position of tamper
F. Expansion position Art. VEDORF /
VEDO8I8O
When fixing the product to
the wall, use the 5 wall plugs
supplied: FISCHER SX 6 S
ART.570021.
A1.Position of communication module
VEDOGSM
A2.Position of messages expansion
VEDOVOICE
A3.Position of IP module VEDOIP
For standard-compliant
installation, pay attention to the
correct route of the earthing
cables and of the SELV circuit
and high voltage cables.
3
4
A
1
C
B
8
8
9
F
E
5
D
8
7
1
1
1 2
2.2 ROUTES FOR
SEPARATING THE
SELV CIRCUIT
AND THE HIGH
VOLTAGE CIRCUIT
(FOR ART.
BOXPLASTIC)
1. VEDOIP expansion network connector
2. Expansion antenna connector Art.
VEDOGSM
3. Battery connector
4. PSU connector
5. Control panel card PSR connections
6. Fixing screw for power supply unit
PSU15
7. Internal fuse 250V~ T2A (for Art.
PSU15), Internal fuse 250V~ T2.5A
(for PSU50)
8. Cable for connecting the power supply
unit to earth Art. PSU15
9. High Voltage Cables
10.Cable for connecting the control
panel card to earth Art. PCBVEDO10
- PCBVEDO34 - PCBVEDO68 PCBVEDO200
11.Balance resistor
12.GSM Antenna
13.Tamper connectors
2
6
34
A1
10
5
6
A2
A3
7
13
8
10
9
11
12
9
1
2
3
a
2.3 POSITIONING OF
COMPONENTS AND
FIXTURES (FOR
ART. BOXMETAL)
1. GSM antenna output
2. Supports for fixing the control panel
card Art. PCBVEDO10 - PCBVEDO34
- PCBVEDO68 - PCBVEDO200 PCBPSU
3. Holes for fixing the housing
4. Cable inlet holes
5. Supports for fixing ( ) and holding
expansion Art. VEDO8I8O
6. Anti-tear Tamper hole
7. Screws for fixing ( ) and holding PAL
module Art. VEDOCCTV
8. Supports for fixing power supply unit
9. Anti-sabotage protection panel
10.Inlet holes for power supply unit
blocking clamp
11.Position of control panel identification
label
12.Housing of fixing screw for power
supply unit Art. PSU50
13.Housing of fixing screw for power
supply unit Art. PSU15
A. Control panel card position Art.
PCBVEDO10 - PCBVEDO34 PCBVEDO68 - PCBVEDO200 PCBPSU
B. Expansion position Art. VEDO8I8O
C. Expansion position Art. VEDO8I8O
D. Tamper position
E. Battery position Art. 30076003 /
Art. 30076004
F. Power supply unit position Art.
PSU15/PSU50
G.PAL/IP module position Art.
VEDOCCTV
2
4
A
5
b 3
B
6
D
C
7
G
4
7
8
F
9
In order to guarantee
certification of the system it
is necessary to fix the 7Ah
or 18Ah battery to the metal
housing with the double-sided
tape provided (See ).
E
When fixing the product to
the wall, use the 5 wall plugs
supplied: FISCHER SX 6 S
ART.570021.
10
11
Optional positions*
a. Holes for fitting supports for fixing the
expansion Art. VEDO8I8O
b. Screws for fixing ( ) and holding PAL
module Art. VEDOCCTV
* for further information, see the manual
of Art. BOXMETAL
3
10
5
13 12
3
1
2
2.4 ROUTES FOR
SEPARATING THE
SELV CIRCUIT
AND THE HIGH
VOLTAGE CIRCUIT
(FOR ART.
BOXMETAL)
3
4
5
6
A1
7
CO
A3
NO
1. GSM antenna output
2. Expansion antenna connector Art.
VEDOGSM
3. PSU connector
4. Battery connector
5. VEDOIP expansion network connector
6. Balance resistor
7. Tamper connectors
A2
8. VEDOCCTV network connector #
9. Earth
connection
according
to
standard EN60950.
10.Internal fuse 250V~ T2A (for Art.
PSU15), Internal fuse 250V~ T2.5A
(for PSU50)
11.High Voltage Cables.
A1.Position of communication module
VEDOGSM
A2.Position of messages expansion
VEDOVOICE
A3.Position of IP module VEDOIP
8
For standard-compliant
installation, pay attention
to the correct route of the
earthing cables and of the
SELV circuit and high voltage
cables.
A
C
D
B
# (!) With the VEDOCCTV
module fitted in a central
position (as in the picture) use
a mains power supply cable
with double insulation (to
prevent the coaxial cables of
the cameras coming in contact
with 230V wires)
(!) If the mains cable inlet hole
is shared with other cables of
the control panel wiring (as
in the picture), use a mains
power supply cable with
double insulation.
7
CO
NO
11 10
9
C
1
2
A
B
4
3
D
D
11
3. Technical and installation specifications
3.1 BOXPLASTIC
Art. BOXPLASTIC complies with standards EN501311, EN50131-3, EN50131-6, EN50136-1, EN50136-2, EN
60950-1:2006 + A11:2009 + A1:2010 + A12:2011 + A2:2013,
EN50130-4
3.1.1 Technical specifications
3.2 BOXMETAL
Art. BOXMETAL complies with standards EN50131-1,
EN50131-3, EN50131-6, EN50136-1, EN50136-2, EN 609501:2006 + A11:2009 + A1:2010 + A12:2011, EN50130-4)
3.2.1 Technical specifications
Features Value
Name of manufacturer / supplier Comelit Group S.p.A.
Dimensions (b x h x d) 280 x 260 x 80 mm
803g (housing + micro switch + fixing
Weight
screws)
-10° / + 55° with warm dry air
Operating temperature and Operating
-10° / + 40° C with max + 93% RH
humidity
(not condensed)
Certified safety grade 2 according to EN50131-1*
Environmental class II according to EN50131-1
* Respecting any indications for installation
3.1.2 Installation
For the instructions for mounting the housing, see page 37
A standard-compliant connection to the electric power
network must be provided.
For standard-compliant installation, prepare the cables and leads
necessary for wiring the system as indicated on page. 9.
In order to guarantee Grade 2 certification according to EN50131-1
the tamper must be mounted and configured correctly
If the control panel is already assembled, you will have
to remove the electronic cards and the power supply unit
from the housing, so as not to risk damaging them
12
Features Value
Name of manufacturer / supplier Comelit Group S.p.A.
Dimensions (b x h x d) 315 x 440 x 95 mm
Weight 3250 g (housing + fixing supports)
-10° / + 55° with warm dry air
Operating temperature and Operating
-10° / + 40° C with max + 93% RH
humidity
(not condensed)
Certified safety grade 2 according to EN50131-1*
Environmental class II according to EN50131-1
* Respecting any indications for installation
3.2.2 Installation
For the instructions for mounting the housing, see page 39
A standard-compliant connection to the electric power
network must be provided.
For standard-compliant installation, prepare the cables and leads
necessary for wiring the system as indicated on page 10-11
In order to guarantee Grade 2 certification according to EN50131-1
the tamper must be mounted and configured correctly.
3.3.1 Main features
3.3 CONTROL PANEL CARD ART. PCBVEDO10,
ART. PCBVEDO34, ART. PCBVEDO68, ART.
PCBVEDO200
• 0.75A / 13.8 V self-resettable fuse for protecting the power
supply to the siren outputs
• 1.5A / 13.8 V self-resettable fuse for protecting the power
supply to the RS485 buses
• 1.5A / 13.8 V self-resettable fuse for protecting the power
supply to the sensors
• all the inputs are filtered and protected against electrical and
electrostatic discharges
• alarm relay with potential-free exchange contact 24V= 3A
• 2 programmable logic outputs with configurable polarity,
limited to 100mA, self- resettable
• built-in digital dialler
• separate power supply unit, switching type direct from mains
• power supply protection against overloads, short-circuits
and voltage surges
• battery connection (up to 18 A/h hours –12V) protected
against reversed polarity and short-circuits
• circuit for dynamic testing of backup battery charge state
• circuit for monitoring the positive siren voltages, 485 bus
and sensor auxiliary positive
• on-board 485 bus terminal resistor, which can be activated
by means of a jumper
• USB interface for connection to a configuration system
The control panel card is available in 4 versions with different
features, see the table on page 5 for the detailed features of the
control panels VEDO10, VEDO34, VEDO68, VEDO200, VEDO34M,
VEDO68M, VEDO200M which include the respective control panel
cards (PCBVEDO10, PCBVEDO34, PCBVEDO68, PCBVEDO34,
PCBVEDO68, PCBVEDO200)
The card has a basic configuration with 8 freely programmable zones
+1 sabotage zone. It has a relay output, which by default, manages the
sirens, and 2 low-consumption programmable outputs.
The control panel card is supplied with a built-in digital dialler, which
allows the transmission of voice messages by means of an additional
audio/voice control module.
It is equipped with 8 standard wired zones and one anti-tamper zone.
It also has one relay output and 2 configurable 100 mA open-collector
outputs.
The association of zones to areas and partial subgroups of areas
allows total, partial or selective activation of the system, according to
the authorisations assigned at the configuration stage to the user who
performs the operations.
Each input event can be associated with multiple outputs, thus
potentially involving all the outputs configured at the installation stage.
The flexibility of this arrangement makes it possible to adapt the control
panel to the most wide-ranging requirements.
Control
panel
cards
PCBVEDO10,
PCBVEDO34,
PCBVEDO68, conform to standards EN50131-1 and
EN50131-3
M11
M12
Fig Scheda Centrale
L1
MOD5
L2
TEL2
CN1
TEL1
GSM COMMUNICATION
MODULE POSITION
CN2
M2
V+
BUS
MOD2
JP6
A
B
M3
JP1
CN4
V-
JP7
MESSAGES
EXPANSION
POSITION
DL1
JP2
JP3
COM
NC
JP8
NO
CARDS POSITION
FOR FUTURE USES
IP COMMUNICATION
MODULE POSITION
TC2
M5
MOD3
MOD1
V+
SIR
TC1
V-
JP5
CN3
JP4
DL5
DL4
DL3
DL2
M4
V+
AUX
I1
I2
M6
V-
I3
M7
I4
I5
I6
M8
V-
I7
I8
M9
V+
AUX
V-
24H
M10
Holes for fixing the control panel card to the metal housing Art. BOXMETAL
Fixtures for cards/expansions
13
WARNING!
With PCBVEDO200 control panel card. f more than 20
peripherals are connected to the system via BUS:
• keypads (VEDOLCD, VEDOLCDPROX),
• RFID readers (VEDOPROX),
• system managers (VEDOTOUCH, MiniTouch 20034607,
Planux Manager 20034801, Icona Manager ViP Art.
20003310W),
• radio / wired expansions (VEDORF, VEDO8I8O)
• Power supply unit management card (PCBPSU)
• Bus isolator (VEDOISO)
we recommend changing the RS485 BUS communication
speed for the control panel and all peripherals and
adjusting it from 38400 to 115.200.
3.3.2 Technical specifications
In order to guarantee compliance with Standards EN50131-1 and
EN50131-3:
• 3 control panel inputs must be programmed to manage the
following events: Detector fault, Anti-robbery device fault, Siren
fault;
LED MEANINGS
Name Function
DL1 Presence of microcontroller power supply
DL2 Errors on 485 bus
DL3 Control panel operating: 1 second ON/OFF
Control panel in standby to download parameters: 0.2 seconds ON/OFF
DL4 Internal use
DL5 Not fitted
TERMINAL BLOCK M11-M12
Name Function
L1 Conductor 1 input from telephone line. Is connected directly to
terminal TEL1
L2 Conductor 2 input from telephone line
TEL2 Conductor 2 output to telephone
TEL1 Conductor 1 output to telephone. Is connected directly to terminal
L1
TERMINAL BLOCK M2-M3-M4-M5
Name Function
Connection for a functional earth connection.
V+ bus
A RS485 data bus - A
• one control panel input must be activated in the event of a fault (DO
NOT connect the additional or self-powered sirens to this output)
B RS485 data bus - B
V-
• a Siren sabotage zone must be provided.
Dimensions (b x h x d) 140 x 127 x 28 mm
125g without earth cable
135g with earth cable
Control panel in standby: 50mA +
All active outputs: 40mA +
PSTN active and communicating:
35mA +
Audio: 1mA +
Consumption (min./max.) GSM: 10mA idle, 35mA communicating +
IP: 55mA
Average power consumption in 1 h:
PCBVEDOXX 90mAh,
VEDOGSM 24mAh
VEDOIP 55mAh
-10° / + 55° with warm dry air
Operating temperature and Operating
-10° / + 40° C with max + 93% RH (not
humidity
condensed)
Operating voltage 10V
to 15V
NO
Normally open connection for alarm relay (RY1). When the relay is
attracted, the COM and NO terminals are kept closed together.
TC1 As per TC2, but controlled by JP4
V- Power supply negative
TERMINAL BLOCK M6-M7-M8-M9-M10
Name Function
V+ AUX Power supply positive for signal sensors. Limited to 1.5A / 13.8 V
I1 Programmable input zone 1.
I2 Programmable input zone 2.
V- Inputs common / Power supply negative
I3 Programmable input zone 3.
Environmental class II according to EN50131-1
I4 Programmable input zone 4.
* Respecting any indications for configuration and installation
I5 Programmable input zone 5.
CONFIGURATION JUMPERS
I6 Programmable input zone 6.
Function
V- Inputs common / Power supply negative
JP1 If activated, enables 485 bus terminal resistor
I7 Programmable input zone 7.
JP2 Reserved
JP4 TC2 polarity: Open Collector (OC) or Positive Command on TC (TC)
Normally closed connection for alarm relay (RY1). In standby the
COM and NC terminals are kept closed together.
Programmable block logic output. Permitted load 100mA.
Polarity is determined by jumper JP5. If JP5 is set to OC (0 V), the
output acts as an open collector: in standby, it will not allow the
TC2
passage of current, and if activated, it will close to earth. If JP5 is
set to TC (13,8 V), however, in standby it will not allow the passage
of current and if activated, it will present a positive to the terminal.
Device Type TYPE B according to standard EN50131-3
JP3 Reset (closing it and then opening it restarts the programme)
NC
V+ SIR Battery charge and power supply positive. Limited to 0.75 A / 13.8 V
Certified safety grade (for PCBVEDO10,
2 according to EN50131-1*
PCBVEDO34, PCBVEDO68)
Name
Power supply negative All terminals marked V- are connected to
each other
COM Connection for alarm relay exchange control panel pin (RY1)
Features Value
Name of manufacturer / supplier Comelit Group S.p.A.
Weight
Power supply positive for 485 communication bus. Limited to 1.5A
/ 13.8 V
I8 Programmable input zone 8.
V+ AUX
Power supply positive for signal sensors. Electrically connected to
terminal 1 of the same terminal block. Shares its limitation.
V- Power supply negative
JP5 TC1 polarity: Open Collector (OC) or Positive Command on TC (TC)
24H Programmable anti-tamper input.
JP6 Restore initial configuration (see installation paragraph)
JP7 Service input
JP8 Future uses
VARIOUS CONNECTORS
Name Function
CN1 PSU connector
CN2 Battery connector
CN3 USB
CN4 Reserved
MODULE CONNECTORS
Name Function
MOD1 IP communication expansion module connection
MOD2 Messages and voice control expansion module connection
MOD3 Future uses
MOD5 GSM communication expansion module connection
14
MOUNTING
Article PCBVEDO10 / PCBVEDO34 / PCBVEDO68
PCBVEDO200 can be installed:
• plastic housing Art. BOXPLASTIC (see page 38)
/
In order to guarantee compliance with standard EN60950
the earthing must be connected as shown on page 9
• metal housing Art. BOXMETAL (see page 40)
In order to guarantee compliance with standard EN60950
the earthing must be connected as shown on page 11
3.4 INTERNAL EXPANSIONS
IMPORTANT: any operation involving the assembly or
disassembly of expansion modules must be performed
with all input power (from power supply unit or battery)
OFF, in order to avoid permanently damaging the
expansion module you intend to add or remove, as well as
the control panel card.
3.4.1 Telephone dialler functions (PSTN as standard)
•
•
•
•
•
•
•
telephone line presence check
number dialling, both pulse and DTMF
16 telephone numbers for voice calls
Contact ID compatible built-in digital dialler
4 telephone numbers for Contact ID
configurable test call
override answering machine option
3.4.2 Messages and Voice Control expansion module (Art. VEDOVOICE)
Optional, contains the part of the audio messages relating to
the digital dialler, i.e. contains the audio messages to be sent
on the standard or GSM telephone line. Equipped with a plug-in
connector for simplified fitting.
The voice control section cannot be customised. It allows an
authorised user to perform guided activation, deactivation,
modification and status checking operations on the system
from a remote location, using a standard telephone or mobile
phone.
A second section is provided for the input of custom messages,
In other words, all messages intended to provide specific
information about the system. This information includes all data
relating to alarm signalling (e.g. the data identifying the system
address: "Home of Mr John Smith, Queen Street, London").
The device is immune to the disturbances governed by
standard EN 50130-4.
The message expansion module does not initially contain any
messages and must therefore be configured (by means of the
configuration software) at the time of first installation. The same
applies in the event of replacement of or addition to an existing
system.
SPECIFICATIONS ACCORDING TO STANDARD EN50136-2
Art. VEDOVOICE complies with standards EN50131-1,
EN50136-2
Emission standards with which the device complies:
EN61000-6-3, EN50130-4, EN301489-1, EN301489-3,
EN301489-7, EN50136-2.
Features Value
Types of alarm transmission for
ATS2 according to EN50131-1
which the device is suitable
Interface type Integrated into the control panel
Operating mode saving and forwarding
event / event transmission (pass- event transmission (pass-through)
through)
Generation and/or transmission
times of alarm messages
voice messages: 10 sec.
Times for generating a reply signal CONTACT ID: times according to
(when used) standard SIA DC-05-1999.09
Times for detecting and presenting
line disconnection: 10 sec.
faults
Method for signalling faults to alarm
Alert send failure: regular or on event
system
Minimum level DTMF tones at
Level of output signals and/or input: 36mVeff - 28.8dbV 100mVpp
sensitivity of input signals Level DTMF tones at output: low
freq 9dBm / high freq 11dBm
ATS2-I0 no information protection
Safety signals level supplied ATS2-S0 protection against
substitution
Calibration instructions calibration not necessary
PSTN
Sharing of transmission connections possible in systems with adsl and
other telephones
CONNECTION OF THE TELEPHONE LINE TO THE CONTROL PANEL
L1 L2 T1 T2
CONTROL
PANEL
If this module is not fitted, the only type of audio information that
it will be possible to send by telephone is audio tones.
AUDIO MODULE FUNCTIONS
• Up to 48 standard messages
• 16 freely usable messages (recording and transfer only
from PC software)
• 6 service voice messages
• system management by means of interface with voice menu
• Facility for activation, deactivation, output status modification
and alarm reset from a remote location
TECHNICAL SPECIFICATIONS
Features Value
Name of manufacturer / supplier Comelit Group S.p.A.
Dimensions (b x h x d) 24 x 21 x 12 mm
Weight 4 g
Consumption (min./max.) 1mA
-10° / + 55° with warm dry air
Operating temperature and
-10° / + 40° C with max + 93% RH
Operating humidity
(not condensed)
Certified safety grade 2 according to EN50131-1*
Environmental class II according to EN50131-1
* Respecting any indications for configuration and installation
SPECIFICATIONS ACCORDING TO STANDARD EN50136-2
Features Value
Types of alarm transmission for
ATS2 according to EN50131-1
which the device is suitable
Interface type Control panel expansion
ATS2-I0 no protection of information
Safety signals level supplied ATS2-S0 no protection against
substitution
Voltage operating range 3.3V ± 2%
FITTING THE MESSAGES AND VOICE CONTROL EXPANSION
MODULE
MODEM
First check that all power is OFF.
ADSL
FILTER
To fit the message and voice control expansion module, simply
plug it into connector MOD2 of the control panel card (see page
13). The module connector should plug into its counterpart
without requiring any force.
No auxiliary connection is required.
TELEPHONE
LINE
15
3.4.3 GSM communication expansion module (Art.
VEDOGSM)
The GSM communication expansion module Art. VEDOGSM
allows telephone calls, SMS, MMS and e-mails to be sent on
the data network. Combined with the voice message card Art.
VEDOVOICE, it allows the remote management of the control
panel by a voice communicator.
Art. VEDOGSM complies with standards EN50131-1,
EN50136-1, EN50136-2, EN 61000-6-3 (2007) + A1 (2011)
The device is immune to the disturbances governed by
standard EN 50130-4.
Emission standards with which the device complies: EN610006-3, EN50130-4, EN301489-1, EN301489-3, EN301489-7.
GSM MODULE FUNCTIONS
•
•
•
•
•
•
•
•
•
•
•
•
GSM850, EGSM900, DCS1800, PCS 1900
GSM/GPRS channel support
Main or reserve telephone dialler
Indication of alarms/malfunctions/sabotage/events via SMS
Customisable SMS messages
Control panel status interrogation via SMS
Checking residual credit of the prepaid SIM
Transmission of Voice Messages via GSM
Transmission of Contact ID via GSM
Event transmission in Contact ID format
Event transmission by email with images
Event transmission by MMS
voice messages: 10 sec.
Generation and/or transmission e-mail: 10 sec without image / 90
times of alarm messages sec with image
MMS: 90 sec.
Times for generating a reply signal CONTACT ID: times according to
(when used) standard SIA DC-05-1999.09
No GSM/GPRS coverage: 120 sec.
Times for detecting and presenting
SIM fault: 20 sec.
faults
antenna disconnected: 45 sec.
Method for signalling faults to alarm
Alert send failure: regular or on event
system
Minimum level DTMF tones at
Level of output signals and/or input: 36mVeff - 28.8dbV 100mVpp
sensitivity of input signals Level DTMF tones at output: low
freq 9dBm / high freq 11dBm
ATS2-I0 no information protection
Safety signals level supplied ATS2-S0 protection against
substitution
Sharing of transmission connections
GSM: GSM850, EGSM900,
DCS1800, PCS 1900
Class 4 (2W) for GSM850 / EGSM900
Class 1 (1W) for DCS1800 / PCS1900
Voltage operating range 10 - 15 V
MEANING OF THE LEDS ON THE IP GSM MODULE
Name Function
DL1
Red LED: GSM communication. Flashes when a transfer via
the GSM or GPRS network is in progress, e.g. during receipt
of an SMS or during registration with the network at the time of
initialisation.
DL2
red LED steadily lit: during reset, during initial configuration
of the module and when engaged by the control panel to
communicate via GSM/GPRS.
flashing red LED: in all other conditions.
DL3 Green LED: module serial communication Lights up briefly when
the module communicates with the control panel.
DL5 DL1 DL2 DL3 DL4
DL4
Green LED: module serial communication Lights up briefly when
the module communicates with the control panel.
Red LED off: indicates that there is no signal (e.g. antenna or
SIM card missing)
Red LED on: active radio connection. Four different levels
DL5 of strength indicate the level of GSM signal received. If this
indicator is lit, the module is capable of operating.
(from control panel Fw version 2.2.1, this indication is only visible
with "service" jumper JP7 inserted).
CONFIGURATION JUMPERS
P1
Name Function
P3
P2
P1 If disconnected, the LEDs go off
P2 Reserved
1
2
3
1. Antenna connector
2. SIM housing
3. Module connector position
Holes for fixing the VEDOGSM module to the control panel card
Art. PCBVEDO10, Art. PCBVEDO34, Art. PCBVEDO68, Art.
PCBVEDO200
TECHNICAL SPECIFICATIONS
Features Value
Name of manufacturer / supplier Comelit Group S.p.A.
Dimensions (b x h x d)
Weight
Consumption (min./max.)
70 x 48 x 29 mm
(without antenna)
26g without antenna
44g with antenna
10mA in Idle
35mA in communication
Average power consumption in 1 h:
VEDOGSM 24mAh
-10° / + 55° with warm dry air
Operating temperature and
-10° / + 40° C with max + 93% RH
Operating humidity
(not condensed)
Certified safety grade 2 according to EN50131-1*
Environmental class II according to EN50131-1
* Respecting any indications for configuration and installation
SPECIFICATIONS ACCORDING TO STANDARD EN50136-2
Features Value
Types of alarm transmission for
ATS2 according to EN50131-1
which the device is suitable
Interface type Control panel expansion
Operating mode saving and
forwarding event / event transmission event transmission (pass-through)
(pass-through)
16
P3 Reserved
FITTING THE GSM MODULE
Make sure the card on which you intend to fit the module is
not connected to the power supply.
IMPORTANT: any operation involving the assembly or
disassembly of expansion modules must be performed
with all input power (from power supply unit or battery)
OFF, in order to avoid permanently damaging the
expansion module you intend to add or remove, as well as
the control panel card.
Insert the plastic spacers in the relevant holes. Then, taking care
to plug the module connector into the control panel connector
designated MOD5 correctly (see page 13), apply sufficient
pressure to engage the spacers in the GSM expansion card
and plug the connector in almost completely.
„„ Once the module has been fitted correctly, connect the antenna
that you intend to use by tightening the connector on the cable
to the gold-coloured connector on the GSM module.
Before using the module, it must be enabled with the
Safe Manager software. If the module is enabled but not
connected, a fault will be generated.
IMPORTANT: place the antenna in the special slot under
the battery (as shown in the figure).
CAUTION:
If the position of the control panel does not allow the reception
of an adequate GSM signal to ensure a good connection, it is
possible to fit an external antenna:
- moving the antenna and using an extension cable,
- using an external antenna (Art. 2G50000296).
For this purpose, there is a pre-marked section to allow
easy exit of the antenna cable.
ANTENNA POSITIONING WITH HOUSING ART. BOXMETAL
20 cm
The antenna must be correctly connected and its connector
must be fully tightened.
Antenna presence can be detected only using the antenna
supplied. In all other cases antenna presence detection
must be excluded from the GSM dialler options.
Place the antenna at least 20 cm away from the GSM
module.
Do not place the antenna on metal surfaces
1
2
OK !
FITTING THE SIM CARD
First check that all power is OFF.
IMPORTANT: place the antenna outside the
housing using the "antenna outlet" provided
Do not place the antenna on metal surfaces
NO !
ANTENNA POSITIONING WITH HOUSING ART.
BOXPLASTIC
√√ The SIM card must be enabled, and if it is a pay-as-you-go
type, it must have sufficient credit on it to be able to make
phone calls or send messages. It is not essential to unlock it,
because the control panel is capable of managing the PIN to
unlock the SIM card.
1. Gently force the top of the SIM connector towards the centre
of the control panel card (downwards if the control panel is
already mounted on the wall).
2. Once you have overcome the resistance, turn it over on its
hinges.
3. Insert the SIM card in the mobile part in such a way that you
can see the gold-coloured contacts of the SIM and that the
bevelled corner is on the left.
4. Repeat the sequence in reverse to release the SIM card
from its seat.
1
2
17
3.4.4 TCP/IP Ethernet expansion module (Art. VEDOIP)
Provides support for connecting the alarm control panel to the
network. Allows an authorised user to access the control panel
locally or remotely. Once connected to the control panel, users
can totally or partially activate and deactivate the areas within
their sphere of competence, and check the status of each input.
Equipped with a plug-in connector for simplified fitting. Needs
to be connected to a LAN with Standard Ethernet 10BASE-T
IPv4
Art. VEDOIP complies with standards EN50131-1 and
EN50131-3, EN50136-2
ATS2-I0 no protection of information
Safety signals level supplied ATS2-S0 no protection against
substitution
Voltage operating range 3.3V
MEANING OF THE LEDS ON THE IP MODULE
Meaning of the LEDs of the RJ45 network connector
Name
D2
1
D1
Function
Yellow LED ON
link OK
Green LED ON
ACT
Meaning of the LEDs on the IP module (Normal operating mode)
Name
TCP/IP MODULE FUNCTIONS
• Ethernet Interface.
• Event transmission on IP
• Programming and Monitoring of the control panel via LAN
through Safe Manager
• Programming and Monitoring of the control panel via
Internet through Safe Manager
• Control panel management vie Internet through Vedo App
• Event alert via e-mail and on Vedo App with alerts with
proprietary protocol
• Alert by e-mail for alarms/malfunctions/sabotage/events
with images
± 2%
D1
D2
Status
Function
flashing slowly
module working correctly
flashing quickly
module operating but SD memory card missing
or defective
flashing
confirms communication with the control panel
Meaning of the LEDs on the IP module (Program updating stage)
Name
D1+D2
Status
Function
D1+D2 steadily lit
Updating in progress
D1 flashing + D2
inverted flashing
MicroSD card missing
D1 steadily lit + D2
flashing
MicroSD card missing for a file necessary
for correct operation
FITTING THE TCP/IP MODULE
2
3
1.
2.
3.
4.
4
Make sure the card on which you intend to fit the
module is not connected to the power supply.
RJ45 connector yellow LED
RJ45 connector green LED
RJ45 network connector
Micro SD memory slot
Holes for fixing the VEDOIP module to the control panel card Art.
PCBVEDO10, Art. PCBVEDO34, Art. PCBVEDO68, Art. PCBVEDO200
TECHNICAL SPECIFICATIONS
Features Value
Name of manufacturer / supplier Comelit Group S.p.A.
Dimensions (b x h x d) 75 x 31 x 33 mm
Weight 18 g
55mA
Consumption (min./max.) Average power consumption in 1 h:
VEDOIP 55mAh
„„ Insert the plastic spacers in the relevant holes. Press the
spacers until they click into the TP/IP expansion card.
FITTING THE RJ45 CONNECTOR
In order to be used, once fitted on the control panel card,
the IP module must be connected to a Standard Ethernet
10BASE-T compatible hub or to a switch with the same
specifications, that allows it to be connected to a data
network. For further details on this operation see paragraph
"5.9 Data network connection cable" on page 60
„„ Plug the cable in fully, until you feel it engage,
in the only accessible connector of the IP
communication module, with the tab facing
the front panel of the control panel housing.
-10° / + 55° with warm dry air
Operating temperature and Operating
-10° / + 40° C with max + 93% RH
humidity
(not condensed)
Certified safety grade 2 according to EN50131-1*
Environmental class II according to EN50131-1
* Respecting any indications for configuration and installation
FITTING THE RJ45 CONNECTOR
„„ Press the tab (1) of the connector and remove
it from the module (2).
SPECIFICATIONS ACCORDING TO STANDARD EN50136-2
Features Value
Types of alarm transmission for
ATS2 according to EN50131-1
which the device is suitable
FITTING THE MICROSD MEMORY CARD
The IP communication module is equipped with a
compartment for a 4GB MicroSD memory card.
Interface type Control panel expansion
Operating mode saving and forwarding
event / event transmission (pass- event transmission (pass-through)
through)
Generation and/or transmission e-mail: 4 sec without image / 35 sec
times of alarm messages with image
No link: 10 sec.
No internet: 120 sec.
Times for detecting and presenting SD fault: 10 sec.
faults DDNS interrogation fault: 35 sec.
SMTP server connection fault: after
76 minutes
Method for signalling faults to alarm
Alert send failure: regular or on event
system
Calibration instructions
Calibration not necessary
Sharing of transmission connections Standard Ethernet 10BASE-T IPv4
18
„„ Fully insert the card into the connector with the goldcoloured contacts not visible.
REMOVING THE MICROSD MEMORY CARD
1. Push the card fully into the connector, then
2. release it: the card will be pushed outwards so
that you can grip it more easily.
D2
1
D1
2
To remove the SD card from the Ethernet expansion
device, the expansion device must be disabled. Do not
disconnect the control panel power supply while the
Ethernet expansion device is enabled.
3.5 GENERAL INFORMATION ABOUT CONNECTING
DEVICES TO THE BUS
As a general precaution, note that the 485 bus cable could cause
disturbances on cables carrying video or comparable signals, if the two
are laid adjacent to each other. We therefore recommend that you use
separate channels for these two types of cable and that you connect
the alarm system bus only with shielded and twisted pair cable with
known impedance of 120 Ohm.
Non-compliance with the above may cause communication errors
or poor quality communication between modules and control panel.
There is also a risk that the conductors of the cables themselves might
not be shielded correctly.
For correct sizing of cables, refer to the table"5.8 Shielded cable
conductor resistance table".
It is recommended to use a shielded cable for the
connections,with one end of the shield connected to Vand the other left free.
IMPORTANT: for correct communication between the devices
connected to the bus, it is good practice for the devices themselves to
be interconnected without branches, i.e. avoid star connections as far
as possible. If the use of branches is unavoidable, make sure that they
are as short as possible. Consequently, it is advisable to route the bus
cable correctly by adhering to the ideal connection and minimising any
deviation from it. The best way to connect the devices is to use the “in
and out” method.
3.6 WIRING THE INPUTS
The inputs routed to the control panel or to the peripherals on the bus,
including bidirectional inputs when used as inputs, are of universal
type.
This means that, depending on their physical connection and
their parameter settings on the control panel, they can assume the
configurations shown below.
IMPORTANT: input balancing resistors, if used, must be installed in
the sensor to which they are associated.
It is recommended to use a shielded cable for the
connections,with one end of the shield connected to Vand the other left free.
3.6.1 Normally closed (NC)
NC: detects the opening of a normally closed contact connected
between an input terminal and the respective negative (-V). It is
not capable of detecting a line sabotage state: in the event of
cutting, it can generate an error or alarm; in the event of a line
short-circuit, it does nothing.
NC
IN
ALARM
-V
3.6.2 Normally open (NO)
CONNECTION TO THE BUS TERMINALS
FROM THE
CONTROL PANEL
TO THE
NEXT MODULE
NO: detects the closure of a normally open contact connected
between an input terminal and the respective negative (-V). It is
not capable of detecting a line sabotage state: in the event of a
line short-circuit, it can generate an error or alarm; in the event
of cutting, it does nothing.
NO
IN
-V +V
A
ALARM
B
-V
MODULE 1
EXAMPLE OF "IN AND OUT" TYPE CONNECTION
3.6.3 Single balance
3.5.1 Bus line termination
The two end devices (the two devices furthest from each other
in an ideal layout) must balance the line with the appropriate
end-of-line resistor (120 ohm). On some devices, this resistor
is installed on-board and can be activated by means of a
jumper or DIP switch. 2 end-of-line resistors are supplied with
the control panel, for use when a device without an on-board
termination (e.g. RFID key reader) is connected to the end of
the line.
IMPORTANT: the control panel can be positioned at any point
along the line, provided that the line is correctly terminated in
a 120 Ohm balancing resistor at both ends, as shown in the
guideline diagram.
CONNECTION TO THE BUS TERMINALS: GUIDELINE DIAGRAM
Detects the opening of a normally closed contact disposed in
series with a balanced line (on 1.8K) connected between an
input terminal and the respective negative (-V). Detects a
sabotage state due to a line short-circuit. In the event of cutting,
it can generate an error or alarm.
NC
IN
1K8
ALARM
-V
3.6.4 Double balance
Detects the opening of a normally closed contact disposed in
series with a balanced line (on 1.8K) connected between an
input terminal and the respective negative (-V). Adding a
second balancing resistor (also 1.8K) makes it possible to
distinguish an alarm state from a line sabotage state, both in
the event of cutting and short-circuit.
ALARM
NC
TAMPER
-V
+V
A
BUS
B
CONTROL PANEL:
ENABLE BUS
BALANCING
BUS
-V +V TO B
MODULE 1
-V +V TO B
MODULE 2
-V +V
A
B
MODULE N-1
-V +V
A
B
MODULE N:
ENABLE BUS
BALANCING
BUS
NC
IN
-V
In order to guarantee compliance with standard EN 501311, all the alarm, anomaly and control zones must be at
least in double balance. Single balance may be enough for
sabotage.
19
3.6.5 Triple balance
Detects and distinguishes the opening of two normally closed
contacts, usually alarm and electrical fault, disposed in series
with a balanced line (on 1.8K) connected between an input
terminal and the respective negative (-V). Its ability to
distinguish derives from the adoption of a second balancing
resistor (1.8K) disposed in parallel to the first of the contacts to
be monitored and a third balancing resistor (3.3K). This
configuration makes it possible to distinguish between an
alarm/electrical fault state and a line sabotage state, both in the
event of cutting and short-circuit.
ALARM
3.6.8 Double zone with end of line (EOL double)
Detects and distinguishes the opening of two normally closed
contacts, usually relating to two different sensors, disposed in
series with a line with a balanced line (1K8) connected between
an input terminal and the respective negative (-V). Its ability to
distinguish between the two sensors derives from the adoption
of a balancing resistor (1.8K) disposed in parallel to the contact
of the first sensor to be monitored and a second balancing
resistor (3.3K) disposed in parallel to the contact of the second
sensor to be monitored. This configuration makes it possible to
distinguish between an alarm/electrical fault state and a line
sabotage state, both in the event of cutting and short-circuit.
The alarms are correctly recognised and assigned to the sensor
from which they originate. The sabotage, however, can only be
generically attributed to the wired line for the input to which it is
connected.
FAULT
NC
NC
TAMPER
NC
IN
SENSOR 1
-V
SENSOR 2
ALARM 2
ALARM 1
NC
3.6.6 Triple balance with jamming
NC
TAMPER 1
TAMPER 2
NC
Detects and distinguishes the opening of two normally closed
contacts, alarm and jamming of the motion sensor, disposed in
series with a balanced line (on 1.8K) connected between an
input terminal and the respective negative (-V). Its ability to
distinguish derives from the adoption of a second balancing
resistor (1.8K) disposed in parallel to the first of the contacts to
be monitored and a third balancing resistor (3.3K). This
configuration makes it possible to distinguish between a state
of alarm and jamming of the motion sensor and a line sabotage
state, both in the event of cutting and short-circuit.
Jamming will be treated with a dedicated fault event.
IN
1K8
NC
3K3
-V
1K8
3.6.9 Wiring the control panel's 24-hour input
The 24-hour input must be configured as single balance with a
resistance of 1.8 KΩ. Refer to the relevant paragraph for
information about correct connection of the tamper lines (see
page 10).
NC
24H
1K8
ALARM
-V
ALARM
NC
JAMMING
3.6.10 Wiring the telephone dialler on the PSTN network
NC
TAMPER
NC
To connect the telephone dialler to the telephone network
correctly, you must first locate the point at which the line enters
the house. The dialler must be connected as the first device, as
viewed from the incoming telephone line.
IN
-V
3.6.7 Double zone (double)
Detects and distinguishes the opening of two normally closed
contacts, usually relating to two different sensors, disposed in
series with a line with comparable behaviour to that of an NC
line, connected between an input terminal and the respective
negative (-V). Its ability to distinguish between the two sensors
derives from the adoption of a balancing resistor (1.8K)
disposed in parallel to the contact of the first sensor to be
monitored and a second balancing resistor (3.3K) disposed in
parallel with the contact of the second sensor to be monitored.
It is not capable of detecting a line sabotage state: in the event
of cutting it can generate an error or sabotage; in the event of a
line short-circuit it does nothing. The sabotage can only be
generically attributed to the wired line for the input to which it is
connected.
SENSOR 1
NC
TAMPER 1
TAMPER 2
NC
-V
20
ADSL
FILTER
ALARM 2
NC
1K8
MODEM
SENSOR 2
ALARM 1
IN
L1 L2 T1 T2
NC
3K3
TELEPHONE
LINE
CONTROL
PANEL
3.7 CONTROL AND DISPLAY COMPONENTS
TECHNICAL SPECIFICATIONS
3.7.1 LCD keypad (Art. VEDOLCD) and keypad with
RFID key reader (Art. VEDOLCDPROX)
Features
Dimensions (b x h) 120 x 101 x 20 mm
The LCD keypad allows an authorised user to enable and
disable the system, to check the system status and manage its
general features, and to check the event log history.
Weight
Consumption (min./max.)
Using the keypad, it is also possible quickly to modify the
system settings and the options of each individual output.
The connection terminal block is identical to that of the LCD
keypad without RFID reader.
Art. VEDOLCD / VEDOLCDPROX complies with standards
EN50131-1 and EN50131-3
MAIN FEATURES:
• Backlit 2 x 16 character LCD display.
• Initial software addressing, from built-in keypad.
• Four LEDs for immediate indication of power ON, battery
alarm, generic error and alarm in progress.
• Backlit keypad with ten number keys and eleven function
keys.
• Two universal inputs, configurable as NC, NO, single, double
and triple balance, triple balance with jamming, double zone
and double zone with termination, with possibility of direct
connection of roller shutter contacts (switch alarm).
• On-board 485 bus end-of-line resistor, which can be
activated by DIP switch.
• Anti-tamper and anti-tear tamper.
1
2
3
4
19mA with LEDs off,
61mA during alarm alert
to 15V
-10° / + 55° with warm dry air
Operating temperature and
-10° / + 40° C with max + 93% RH (not
Operating humidity
condensed)
Certified safety grade 2 according to EN50131-1*
Device Type TYPE B according to standard EN50131-3
The LCD keypad is equipped with 2 freely configurable alarm
inputs.
The RFID reader antenna is located in the bottom left-hand
corner of the housing. The RFID key must be brought close
to this area of the housing so that the reader can recognise it
correctly.
140 g + 8 g fixing screws (Vedo LCD) 150 g + 8 g
fixing screws (Vedo LCD PRO)
Operating voltage 10V
Operations are performed by means of a combination of
numerical keys and function keys, whereas feedback is both
visual (alphanumeric display and LEDs) and aural (buzzer.)
KEYPAD WITH RFID KEY READER
ART. VEDOLCDPROX
The LCD keypad with RFID reader is identical to the standard
LCD keypad in every respect, except that it is equipped with an
RFID reader module. This version enables users, according to
their authorisations, to activate the system partially or totally or
deactivate it, using an RFID key, without having to enter a code,
thereby saving time. It is compatible with Comelit RFID keys.
Value
Name of manufacturer / supplier Comelit Group S.p.A.
Environmental class II according to EN50131-1
* Respecting any indications for configuration and installation
MEANING OF THE KEYPAD LEDS
The keypad has 4 indicator LEDs:
LED
Colour
Green
Yellow
Yellow
Red
Status
Function
Off
Mains power not present
On
Mains power present
Slow flash
Mains power OK, but system not ready
for enabling or there are (non-excluded)
open zones
Off
Battery OK
On
Indicates an anomaly in the battery of
the control panel and/or of a bus power
supply unit
Off
No problem
On
Problem detected
Slow flash
Presence of isolated, excluded, restricted
zones, or of temporarily excluded
anomalies/sabotages.
Off
No alarm, sabotage or ongoing fault
On
Alarm, sabotage or fault
Slow flash
Alarm event log, sabotage or fault
LCD KEYPAD TERMINAL BLOCK DESCRIPTION
Name
Function
I1
Input 1
I2
Input 2
V-
Power supply negative input / Inputs reference
B
RS485 data bus - B
TO
RS485 data bus - A
V-
Power supply negative input
V+
Power supply positive input 13.8V
DIP SWITCHES AND BUS TERMINATION
BUZZER
DIP1
DIP2
EXCLUDED
OFF
OFF
LOW
ON
OFF
HIGH
OFF
ON
HIGH
ON
ON
TAMPER
DIP3
ACTIVE
OFF
EXCLUDED
ON
485 LINE TERMINATION
DIP4
EXCLUDED
OFF
ACTIVE
ON
5
1.
2.
3.
4.
5.
Indicator LED
Display
Function keys (programmable)
RFID reader (only for Art. VEDOLCDPROX)
Terminal block
21
MOUNTING THE KEYPADS
The base of the keypads, both with and without RFID reader,
has a series of slots in it to ensure versatility of mounting on a
wide range of supports, starting with the ordinary type 503 box.
„„ Locate the area with the tamper support, with the pre-marked
break-off panel for facilitating detachment of the tamper, and
remove the silicone key acting as a tamper. Put it in a clean
place.
Cable routing
3.7.2 RFID proximity reader on bus (Art.
VEDOPROX)
The RFID proximity reader on bus allows activation and
deactivation with RFID keys without contact. An RFID key can
be associated to each user. Each key can operate on the zones
and areas for which the associated user is enabled.
Its mechanical configuration is such that it can be used directly
on all residential series that use an adapter for Keystone
standard RJ45 network connector. It is compatible with Comelit
RFID keys.
MAIN FEATURES
• Simplified mounting with Keystone generic RJ45 adapter on
residential series frames.
• Four LEDs with partially assignable functions.
• Quick total activation option.
• Choice of several activation modes.
• Physical addressing of device by means of DIP switches.
Fixing holes*
Elastic closure clips
Position of silicone tamper
Anti-tear tamper hole
The base of the keypads, both with and without RFID reader, has a series
of slots in it to ensure versatility of mounting on a wide range of supports,
starting with the ordinary type 503 box.
Fixing on box 503
See assembly sequence on page 42.
Wall mounting
See assembly sequence on page 42.
IMPORTANT: when closing the housing, remember to refit
the tamper in its place. The black, conductive part must
be visible.
TECHNICAL SPECIFICATIONS
Features
Value
Name of manufacturer / supplier Comelit Group S.p.A.
Dimensions (b x h x d) 55 x 48 x 19 mm
Weight 28g
10mA in Idle status
Consumption (min./max.) 15mA with LEDs on
45mA during key reading
Operating voltage 10 - 15 V
Operating temperature -10° / + 40° C
Operating humidity max +85% (not condensed)
In order to guarantee Grade 2 certification according to EN50131-1
the tamper must be mounted and configured correctly
Device Type B according to EN50131-3
Environmental class Environmental class II
SETTING RFID READER SPEED
IMPORTANT: At first start-up, the RFID reader is ready to
communicate at 38400 baud rate. To modify the communication
speed, proceed as follows:
1. With the device powered up, set DIP switch 6 to ON. The
LEDs on the RFID will light up until they are all lit, and will
then all go off and start lighting up again (learning mode)
2. In this condition, set Dip Switches 1 and 2 (as indicated in
the table to configure the desired speed)
3. Once you have set the speed, set DIP switch 6 back to OFF.
The speed is now set.
4. Set DIP switches 1 to 5 according to the address to be set.
Baud
DIP 1
9600
OFF
DIP 2
OFF
38400
ON
OFF
57600
OFF
ON
115200
ON
ON
Note that the standard speed of the bus for VEDO control
panels is 38400 baud.
22
MEANING OF THE LEDS WHEN THE CYCLE IS IN PROGRESS
LED
Red
Blue
Yellow
ADDRESSING
DIP switches 1 to 5 are for addressing the reader on the bus.
On the current version, only addresses 1 to 8 are used, so DIP
switches 4 and 5 must be left on OFF.
Code
DIP1
DIP2
DIP3
DIP4
DIP5
1
OFF
OFF
OFF
OFF
OFF
2
ON
OFF
OFF
OFF
OFF
3
OFF
ON
OFF
OFF
OFF
4
ON
ON
OFF
OFF
OFF
5
OFF
OFF
ON
OFF
OFF
6
ON
OFF
ON
OFF
OFF
7
OFF
ON
ON
OFF
OFF
8
ON
ON
ON
OFF
OFF
RFID KEY READER ON BUS TERMINAL BLOCK DESCRIPTION
Name
Green
Power supply positive input
V-
Power supply negative input
A
RS485 data bus - A
B
RS485 data bus - B
485 LINE TERMINATION
If the RFID reader is connected as the final point of the bus line,
you need to connect a 120 ohm 1/4W 5% resistor in parallel to
the 485 bus line, i.e. between terminals A and B.
MEANING OF THE LEDS ON THE RFID READER
The reader has 4 indicator LEDs, the meaning of which varies
according to reader status:
• reader in standby (no cycle in progress): the LEDs show
the operating status of the areas enabled on the reader
• cycle in progress: the LEDs light up in sequence to provide
users with an indication of which scenarios are available,
allowing them to make a choice
• during key presentation
Function
Request execution of action associated with LED
Slow flash
Action associated with LED requires forcing to be
executed
On
Request execution of action associated with LED
Slow flash
Action associated with LED requires forcing to be
executed
On
Request execution of action associated with LED
Slow flash
Action associated with LED requires forcing to be
executed
On
Request execution of action associated with LED
Slow flash
Action associated with LED requires forcing to be
executed
MEANING OF LEDs DURING PRESENTATION OF THE KEY
LED
Red
Blue
Yellow
Function
V+
Status
On
Green
Status
Function
Off
Request for deactivation of all areas covered by the
reader.
On
Request for activation of the activation profile
associated with the RED LED
Fast flash
The reader is forcing the activation profile associated
with the RED LED (*)
Off
Request for deactivation of all areas covered by the
reader.
On
Request for activation of the activation profile
associated with the BLUE LED
Fast flash
The reader is forcing the activation profile associated
with the BLUE LED (*)
Off
Request for deactivation of all areas covered by the
reader.
On
Request for activation of the activation profile
associated with the YELLOW LED
Fast flash
The reader is forcing the activation profile associated
with the YELLOW LED (*)
Off
Request for deactivation of all areas covered by the
reader.
On
Request for activation of the activation profile
associated with the GREEN LED
Fast flash
The reader is forcing the activation profile associated
with the GREEN LED (*)
(*) The purpose of forcing is to overcome a 'not ready' condition
in one or more of the zones associated with the areas covered
by the reader, and/or an anomaly which can be overridden due
to the choices made at the time of control panel configuration.
MOUNTING THE RFID KEY READER ON BUS
To mount the RFID key reader, you need to use an interface
plate for standard Keystone RJ45 sockets that is compatible
with the residential series you intend to use.
Simply connect the adapter to the plate and then plug the
reader into the adapter, pressing it fully home until you hear the
two parts engage.
The cycle actions associated with the LEDs by default are:
• Red LED: Total activation
• Yellow LED: Scenario P1
• Blue LED: Scenario P2
• Green LED: Scenario P1+P2
IMPORTANT: The actions associated with the LEDs can be
changed by the installer during system programming.
MEANING OF THE LEDs WITH THE READER IN STANDBY
(no cycle in progress)
LED
Red
Blue
Yellow
Green
Status
Function
On
Scenario associated with the Red LED active
Slow flash
System not activated and alarm, sabotage or fault
event memory present
Fast flash
System activated and alarm, sabotage or fault event
memory present
On
Scenario associated with the Blue LED active
Slow flash
System activated with unknown scenario (not saved)
On
Scenario associated with the Yellow LED active
Fast flash
Fault present
On
Scenario associated with the Green LED active
Fast flash
System not ready for enabling or there are (nonexcluded) open zones
23
3.7.3 RFID keys (Art. SK9050x/A)
The keys are made using high-security, bidirectional RFID
transponders.
The technology used is such that the keys can communicate
with the reader without any need for electrical contacts and
hence with problems of contact wear. This ensures that
performance remains high over time.
Used in conjunction with the RFID key readers (on bus, on
keypad, on Vedo Touch, on Minitouch or on Planux Manager),
they make it possible to activate and deactivate the system
without any need for electrical contact. An RFID key can be
associated to each user. Each key can operate on the zones
and areas for which the associated user is enabled.
They are available in various colours and their housing is
shaped in such a way that they can easily be added to a bunch
of keys on a keyring, so that they are always to hand.
The unique ID of the digital key is defined by the crc32 of the
bytes that form the unique code of the key, and can have a
value between 1 and 2^32-1, therefore generating a maximum
number of 2^32-2 possible values.
3.8 OTHER DEVICES THAT CAN BE CONNECTED TO THE 485 BUS
3.8.1 Vedo Touch (Art. VEDOTOUCH) / Mini Touch
(Art. 20034607) with RFID key reader
Vedo Touch/Minitouch is an innovative interface equipped with
a touch screen, via which authorised users can interact with
the alarm system. The level of interaction makes it possible
to perform all operations than can be done from the keypad,
whether relating to use, configuration or control by the user.
The combined use of text, symbols and colours makes the
available functions immediately comprehensible.
As well as offering alarm system management features, Mini
Touch is capable of interacting with the Simplebus home
automation system, thereby ensuring integration between the
two systems.
Mini Touch is equipped with three bidirectional lines as
standard, which are identical to those of the input and output
expansion module and are hence fully programmable and can
be used both as I/O lines connected to the security system, or
assigned to home automation use.
The position of the RFID reader's antenna is on the right-hand
side of the Mini Touch, and is clearly identified by a symbol
screen-printed on the surface of the frame. The RFID key must
be brought close to this area of the housing so that the reader
can recognise it correctly.
The predisposed mountings are designed for fitting Vedo
Touch/Mini Touch on a standard type 503 box.
MAIN FEATURES:
• 3.5” resistive touch panel
• Optical tamper
• 485 bus interface for direct alarm interfacing
• Simplebus interface for home automation interfacing (only for
Mini Touch)
• Basic bridging from alarm to home automation (facility for data
exchange between alarm and home automation) (only for Mini
Touch)
• Alarm keypad emulation for configuration (only for Vedo Touch)
• Built-in RFID reader as standard
1
2
3
4
5
6
7
1.
2.
3.
4.
24
RFID reader
3.5” touch screen
Tamper
Ethernet connector
5. Terminal block for connection
6. Indicator LED
7. CV8
The RS485 bus of the device must be connected exclusively
to other Comelit devices (alarm bus).
The Ethernet ports can be connected to other Comelit
devices or to other 10Base2 Ethernet ports where there is
no potential overvoltage on the distribution system (wiring
contained within a single building).
TECHNICAL SPECIFICATIONS
Features
Value
Name of manufacturer / supplier Comelit Group S.p.A.
Dimensions (b x h x d) 125 x 85 x 28 mm
Weight 150g
ADDRESSING THE DEVICE ON THE BUS
Like any other device connected to the 485 bus, the Vedo
Touch/Mini Touch must respond to a single address that can
be configured from the display.
For Vedo Touch
1. Access the settings menu by pressing
.
2. Type in the installer code (default=1961) and confirm
3. Follow this path "Options/Configuration/Bus 485 address"
4. Type in the identification number of the device on the bus
and confirm (to modify the address, delete the present value
by pressing ‘C’).
80mA all off
Consumption (min./max.) 135mA TFT on
250mA led on at 100%
Operating voltage 10V
at 24V
Operating temperature -15° / +55°C
Operating humidity max +85% RH (not condensed)
B (Vedo Touch) / A (Mini Touch)
according to EN50131-3
Device Type
Environmental class II according to EN50131-1
DESCRIPTION OF TERMINAL BLOCK
V+
V-
D
B
A
I1
I2
I3
NC
3. Follow this path "Options/Configuration/Bus 485 address"
Function
Power supply positive input *
Power supply negative input, common to home automation bus
D
Data Signal for home automation Simplebus
A
RS485 data bus - A
B
RS485 data bus - B
COM
NO
and press the icon
.
2. Type in the installer code (default=1961) and confirm
V-
NC
For Mini Touch
1. Access the alarm menu with
4. Type in the identification number of the device on the bus
Name
V+
M
CO
NO
Output 1 relay normally closed contact (for Mini Touch only for home
automation use)
Output 1 common relay (for Mini Touch only for home automation use)
Output 1 relay normally open contact (for Mini Touch only for home
automation use)
I1
Programmable input/output connection (for Mini Touch only for home
automation use)
I2
Programmable input/output connection (for Mini Touch only for home
automation use)
I3
Programmable input/output connection (for Mini Touch only for home
automation use)
SPEED SETTING
For Vedo Touch
.
1. Access the settings menu by pressing
2. Type in the installer code (default=1961) and confirm
3. Follow this path "Options/Configuration/Bus 485 speed"
4. Select the desired speed (default=38400)
*The device Mini Touch Art. 20034607 must be powered by the
control panel or by Comelit Art. 20022101 or another security
power supply unit in compliance with EN 61558-2-6.
485 LINE TERMINATION
Name
CV8
Function
If activated, connects the line termination to the 485 bus line
LED MEANINGS
The device has a LED backlit system that indicates the status
of the system climate zones and the status of the anti-intrusion
system.
Colour
steady red
flashing red
yellow
blue
orange
For Mini Touch
1. Access the alarm menu with
and press the icon
.
2. Type in the installer code (default=1961) and confirm
3. Follow this path "Options/Configuration/Bus 485 speed"
4. Type in the identification number of the device on the bus
Signal
Alarm memory
Alarm in progress
Alarm system fault
Climate on in summer mode.
Climate on in winter mode.
The LED indicates one event at a time, giving priority to alarm
events. In the absence of signals a courtesy light is active (if
programmed), with a colour defined at the time of configuration.
MOUNTING
The article Vedo Touch (Art. VEDOTOUCH) / Mini Touch (Art.
20034607) can be installed on box 503 (see page 43)
25
3.8.2 Planux Manager with RFID key reader (Art.
20034801)
TECHNICAL SPECIFICATIONS
Features
Planux Manager is a built-in supervisor: as well as incorporating
all the control features available on Mini Touch, it performs
advanced, full-duplex door entry monitor functions, with
dedicated, programmable function keys. It does not have any
alarm inputs or outputs.
MAIN FEATURES:
• 3.5” resistive touch panel
• 485 bus interface for direct alarm interfacing
• Simplebus interface for home automation interfacing
• Basic bridging from alarm to home automation (facility for
data exchange between alarm and home automation)
• Built-in RFID reader as standard
• Full-duplex door entry monitor
Dimensions (b x h x d) 145 x 145 x 36 mm
Weight 370g
160mA all off
Consumption (min./max.) 220mA with tft on
250mA all on
Operating voltage 10V
Operating humidity max +85% RH (not condensed)
Device type A according to EN50131-3
Environmental class II according to EN50131-1
DESCRIPTION OF TERMINAL BLOCK
2
S
+V
3
D
B
A
S-
S+
P
CF
P
CF
L
L
Name
1.
2.
3.
4.
5.
6.
7.
+VS
4
12
11
10
Microphone
Touch screen
Key sensor
Loudspeaker
Door lock key
Privacy / Doctor key (programmable)
Self-ignition key (programmable)
9
8
7
6
8. Programmable key 2
9. Programmable key 1
10.Colour key
11.Contrast key
12.Brightness key
13.Menu key
14.Audio key
-
+
Function
Power supply for door entry monitor (for example: bracket 6214KC)
D
Data Signal for home automation Simplebus
B
RS485 data bus - B
TO
RS485 data bus - A
5
13
at 24V
Operating temperature -10° / +40° C
1
14
Value
Name of manufacturer / supplier Comelit Group S.p.A.
S-
Call repeater device connection
S+
Call repeater device connection
CFP
Floor door call input
CFP
Floor door call input
L
Video door entry bus line connection terminal
L
Video door entry bus line connection terminal
-
Power supply negative input, common to home automation bus
and alarm bus
+
Power supply positive input
485 LINE TERMINATION
Name
CV8
Function
If activated, connects the line termination to the 485 bus line
ADDRESSING THE DEVICE ON THE BUS
See Mini Touch page 25.
1
2
3
4
1.
2.
3.
4.
26
CV8 485 line termination.
Terminal block for system connection
CV5 Jumper for video closure.
CN4 CN5 Monitor bracket connectors.
SPEED SETTING
See Mini Touch page 25.
MOUNTING
The article Planux Manager (Art. 20034801) can be installed:
• with flush-mounted box Art. 6117 (see page 44)
• with wall support Art. 6120 (see page 45)
3.8.3 Icona Manager ViP (Art. 20003310W)
DESCRIPTION OF TERMINAL BLOCK 1
Icona Manager ViP is a built-in supervisor with door entry
monitor functions and the ability to display and check the status
of the SimpleHome home automation system and of the Vedo
anti-intrusion system.
MAIN FEATURES:
• LCD display 4.3’’ 16:9 capacitive touch
• RJ45 connector for connection to the Ethernet network
• RFID antenna for reading Comelit keys
• Sensor for detecting ambient temperature and humidity
0-45°C, precision +/- 0.3 °C
• Real time clock (RTC);
• Micro SD connector accessible;
• Micro SD for saving data, loading custom ringtones, saving
and exporting films from the video memory;
• Audio broadcast
1
2
13
Name
Function
MB
negative of the secondary RS485 bus
(terminal not fitted by product rev1.0)
MA
positive of the secondary RS485 bus
(terminal not fitted by product rev1.0)
B
negative of the alarm RS485 bus
A
positive of the alarm RS485 bus
V-
card earth
S-
negative pole of the additional ringtone output
S+
positive pole of the additional ringtone output
DESCRIPTION OF TERMINAL BLOCK 2
Name
Function
D
home automation bus
V-
card earth
V+
power supply positive pole
DESCRIPTION OF TERMINAL BLOCK 3
Name
Function
AL
alarm contact input
PAN
panic contact input
CFP
contact input outside door
3
485 LINE TERMINATION
12
4
11
1.
2.
3.
4.
5.
6.
7.
8.
10
9
8
7
Microphone
4.3" touch screen, 16:9
RFID key sensor
Door opening button (programmable)
Privacy / Doctor key [programmable]
Self-ignition key [programmable]
Open doors key
Video memory key
6
5
D
V–
MB
V+
MA
B
JP2
A
V–
AL
S+
CFP
PAN
S–
Function
JP1
if closed, enables the 120 Ohm termination between lines A and B
of RS485 alarm bus
JP2
if closed, enables the 120 Ohm termination between lines MA and
MB of the secondary RS485 bus
(jumper not fitted by product rev1.0)
LED MEANINGS
9. K
ey "3" [programmable]
default = off
10.Key "2" [programmable]
default = general actuator
11.Key "1" [programmable]
default = off
12.Audio key
13.Micro SD card input
JP1
Name
Name
Status
DL1
Flashing
signals Ethernet activity
Yellow
data transmission and reception activity on the
SimpleHome bus
Red
data collision on the SimpleHome bus
DL2
Function
ADDRESSING THE DEVICE ON THE BUS
See Mini Touch page 25.
SPEED SETTING
See Mini Touch page 25.
MOUNTING
The article Icona Manager ViP (Art. 20003310W) can be
installed:
• with flush-mounted box Art. 6117 (see page 47)
• with wall support Art. 6620 (see page 46)
RJ45
DL2
DL1
TECHNICAL SPECIFICATIONS
Features
Value
Name of manufacturer / supplier Comelit Group S.p.A.
Dimensions (b x h x d) 147 x 142 x 23 mm
Weight 282g
75mA medium,
Consumption (min./max.) 160mA TFT on,
200mA max.
Operating voltage 10V
at 24V
Operating temperature -5° / +45° C
Operating humidity 0-90% RH
Device Type A according to EN50131-3
Environmental class I according to EN50131-1
27
3.9 EXPANSIONS ON 485 BUS
The expansions on bus Art. VEDO8I8O and VEDORF are
supplied complete with plastic housing complying with
EN50131, so they can also be installed on the outside of the
articles BOXPLASTIC and BOXMETAL.
The housing can be fixed to the wall or mounted in flushmounted boxes on the wall. A pre-marked section on the
bottom is for routing the cables through, and another premarked section in the top right-hand corner, coinciding with a
fixing hole, provides anti-tear protection.
The expansion module is fixed to the base of the housing with
2 self-tapping screws.
The cover is secured to the base by means of three fasteners
on the top and two spring clips at the bottom. There are also
two safety screws to prevent accidental opening.
3.9.2 Expansion on bus with 8 balanceable inputs
and 8 logic outputs on bus (Art. VEDO8I8O)
A maximum of two input/output expansions can be fitted inside
the control panel, but others can be mounted in the appropriate
plastic housing.
Each input can be configured as NC, NO, single, double
balance, triple balance, triple balance with jamming, double
zone and double zone with termination.
Set to detect tampering if the housing is opened or the unit is
removed from the wall.
Tampers can be disabled.
Art. VEDO8I8O complies with standards EN50131-1 and
EN50131-3
MAIN FEATURES
• 8 alternatively configurable inputs/outputs
• Inputs can be configured as NC, NO, single, double balance,
triple balance, triple balance with jamming, double zone and
double zone with termination.
• Option of direct connection with roller shutter contacts
(switch alarm)
• Outputs can be configured as monostable, monostable with
configurable pattern, bistable or bistable with configurable
pattern
• Anti-tamper and anti-tear tamper
• On-board 485 bus terminal resistor, which can be activated
by means of a jumper
• Addressing by means of DIP switch
3.9.1 Expansions plastic housing
1
DL1
JP3
ON
Cable inlet hole
Optional fixing holes
Anti-tear tamper hole
Pre-marked optional fixing holes
Card fixing holes Art.
VEDO8I8O/ VEDORF
3
1 2 3 4 5 6 7 8
SW2
SW3
Wall mounting holes
2
JP1
JP2
JP4
MOUNTING THE PLASTIC HOUSING
See assembly sequence on page 48.
To ensure anti-tear protection, the hole associated with the premarked area with anti-tear function must always be anchored
to the wall. Failure to anchor this section will make the anti-tear
protection useless.
IMPORTANT: when refitting the expansion card in its housing, make
sure that the anti-tear tamper (the one furthest to the left as viewed
in the illustrations on page 48) is held properly closed by the tab
originating from the pre-marked anti-tear area of the housing.
In order to guarantee compliance with Standards EN50131-1 and
EN50131-3, the expansions VEDO8I8O and VEDORF, if installed
outside the control panel housing, must have their anti-sabotage
and anti-tear contacts enabled, and so the jumpers on the
expansion must be disconnected
V+
V-
A
B
V+
AUX
V-
I1
I2
V-
M1
I3
I4
I5
I6
V-
I7
I8
M2
1. Dip Switch
2. Anti-tear tamper
3. Anti-tamper tamper
Holes for fixing the VEDO818O card to the metal housing Art. BOXMETAL.
TECHNICAL SPECIFICATIONS
Features Value
Name of manufacturer / supplier Comelit Group S.p.A.
Dimensions (b x h x d) 126 x 80 x 32 mm (in the housing)
143g with housing and screws for fixing to
Weight the wall
39g card alone
Consumption (min./max.)
22mA/27mA exclusing the current supplied by
the output
Operating voltage 10 - 15 V
-10° / + 55° with warm dry air
Operating temperature and
-10° / + 40° C with max + 93% RH (not
Operating humidity
condensed)
Certified safety grade 2 according to EN50131-1*
Device Type TYPE B according to standard EN50131-3
Environmental class II according to EN50131-1
* Respecting any indications for configuration and installation
28
3.9.3 Bidirectional radio expansion on bus (Art.
VEDORF)
CONFIGURATION JUMPERS
Name Function
JP1
If activated, disables anti-removal (anti-tear) tamper
JP2
If activated, disables anti-opening tamper
JP4
If activated, enables 485 bus terminal resistor
The modules operate in bidirectional mode (reception and
transmission). This makes it possible to associate radio
controls, radio alarm sensors (contacts and/or volumetric
detectors) and supervised wireless sirens to the control panel.
ADDRESSING
DIP switches 1 to 6 (of SW1) are for addressing the module
on the bus. On the current version, only addresses 1 to 12 are
used, so DIP switches 5 and 6 must be left on OFF.
No.
DIP1
DIP2
DIP3
DIP4
DIP5
1
OFF
OFF
OFF
OFF
OFF
DIP6
OFF
2
ON
OFF
OFF
OFF
OFF
OFF
3
OFF
ON
OFF
OFF
OFF
OFF
4
ON
ON
OFF
OFF
OFF
OFF
5
OFF
OFF
ON
OFF
OFF
OFF
6
ON
OFF
ON
OFF
OFF
OFF
7
OFF
ON
ON
OFF
OFF
OFF
8
ON
ON
ON
OFF
OFF
OFF
9
OFF
OFF
OFF
ON
OFF
OFF
10
ON
OFF
OFF
ON
OFF
OFF
11
OFF
ON
OFF
ON
OFF
OFF
12
ON
ON
OFF
ON
OFF
OFF
MAIN FEATURES
• Up to 32 radio zones per module
• Up to 16 radio outputs (including max 8 sirens)
• Up to 8 radio sirens
• Possibility of bidirectional communication
• Operating frequency in 868 MHz band, FSK mode
• Sensor and siren status monitoring
• Separate management of intruder and sabotage alarms
• Radio device power supply monitoring, including sirens
• Monitoring
1
2
ON
3
D4
1 2 3 4 5 6
JP6
JP7
SETTING THE SPEED OF THE CARD ON THE BUS
BAUD
DIP7
DIP8
9600
OFF
OFF
38400
ON
OFF
57600
OFF
ON
115200
ON
ON
JP3
JP1
Note that the standard speed of the bus for VEDO control
panels is 38400 baud.
TERMINAL BLOCK M1
Power supply positive input
V-
Power supply negative input
A
RS485 data bus - A
B
RS485 data bus - B
Features Value
Dimensions (b x h x d) 126 x 80 x 32 mm (in the housing)
131g with housing and screws for fixing
Weight to the wall
29g card alone
Power supply positive output
V-
Power supply negative - output reference
I1
Input 1 / Output 1
I2
Input 2 / Output 2
V-
Power supply negative input / Inputs reference
I3
Input 3 / Output 3
I4
Input 4 / Output 4
I5
Input 5 / Output 5
I6
Input 6 / Output 6
V-
Power supply negative input / Inputs reference
I7
Input 7 / Output 7
I8
Input 8 / Output 8
Consumption (min./max.) 55mA medium, 60mA max
Operating voltage 10 - 15 V
-10° / + 55° with warm dry air
Operating temperature and
-10° / + 40° C with max + 93% RH (not
Operating humidity
condensed)
Device Type TYPE B according to standard EN50131-3
Environmental class II according to EN50131-1
CONFIGURATION JUMPERS
Name Function
LED MEANINGS
DL1
B
Name of manufacturer / supplier Comelit Group S.p.A.
Name Function
Name
A
TECHNICAL SPECIFICATIONS
TERMINAL BLOCK M2
V+ AUX
V-
1. Dip Switch
2. Anti-tear tamper
3. Anti-tamper tamper
Holes for fixing the VEDORF card to the metal housing Art. BOXMETAL.
Name Function
V+
V+
Flashing
Function
fast
(50ms ON / 50ms OFF)
expansion connected
slow
(200ms ON / 200ms OFF)
expansion not connected
JP1
If activated, enables 485 bus terminal resistor
JP3
Reserved
JP6
If activated, disables anti-removal (anti-tear) tamper
JP7
If activated, disables anti-opening tamper
MOUNTING
The article VEDO8I8O can be installed in:
• plastic housing Art. BOXPLASTIC (see page 38)
• plastic housing for expansion (see page 28, 48)
• metal housing Art. BOXMETAL (see page 40)
29
ADDRESSING
DIP switches 1 to 4 are for addressing the module on the bus.
On the current version, only addresses 1,2 and 3 are used, so
DIP switches 3 and 4 must be left set to OFF.
No.
DIP1
DIP2
DIP3
1
OFF
OFF
OFF
DIP4
OFF
2
ON
OFF
OFF
OFF
3
OFF
ON
OFF
OFF
SETTING THE SPEED OF THE CARD ON THE BUS
BAUD
DIP5
DIP6
9600
OFF
OFF
38400
ON
OFF
57600
OFF
ON
115200
ON
ON
3.9.4 PAL/IP video module Art. VEDOCCTV
The PAL/IP module allows integration of the video-surveillance
part with the alarm control panel for
• sending MMS
• sending alarm alerts (with frames taken from the cameras
on the system), on system managers (Vedo Touch, Mini
Touch, Icona Manager VIP) and App
• activating live streaming (of the cameras on the system),
by the system manager (Vedo Touch, Mini Touch, Icona
Manager VIP) or by App
• consulting the recorded films (of the cameras on the system,
4 IP cameras and one chosen analogue camera), by the
system manager (Vedo Touch, Mini Touch, Icona Manager
VIP) or by App
1
2
4
DL1
Note that the standard speed of the bus for VEDO control
panels is 38400 baud.
3
TERMINAL BLOCK DESCRIPTION
Name
Function
V+
Power supply positive input
V-
Power supply negative input
A
RS485 data bus - A
B
RS485 data bus - B
LED MEANINGS
Name
D4
Flashing
Meaning
fast
(50ms ON / 50ms OFF)
expansion connected
slow
(200ms ON / 200ms OFF)
expansion not connected
MOUNTING
The article VEDORF can be installed in:
• plastic housing Art. BOXPLASTIC (see page 38)
• plastic housing for expansion (see page 28, 48)
The expansion Art. VEDORF cannot be mounted inside the
metal housing Art. BOXMETAL
5
1.
2.
3.
4.
5.
Reserved terminals
Ethernet port
Data transmission warning light
Power supply terminals
Signal connection terminals for 4 cameras
Holes for fixing the VEDOCCTV module to the metal housing Art. BOXMETAL.
MAIN FEATURES
• Possibility of controlling 4 analogue cameras
• Option of controlling 4 IP cameras and configuring video
recording:
• Resolution=320x240
• Codec=Mjpg
• Fps=from 1 to 12 (programmable)
• Video recording duration from 5 to 10 sec
(programmable)
• Recording duration before alarm event (pre-alarm)
from 0-10 sec (programmable).
The pre-alarm time cannot be greater
than the total recording time.
If using third-party IP cameras, make sure that:
They support the default video streaming configuration,
i.e. MJPEG, 320x240 pixel with FPS from 1 to 12.
The URL providing access to video streaming for the IP
camera is known.
All IP cameras interfacing with the VEDOCCTV module
should adopt the same configuration as the lowdefinition channel (same codec, same resolution, same
frame rate...).
30
• Signalling camera and SD faults
• Extraction, archiving and sending of frames (from a
minimum of 1 to a maximum of 4) from the video of the
analogue and IP cameras.
• Archiving and reproduction in streaming (up to a maximum
of 10 seconds with possibility of anticipating the start of the
recording with respect to the moment of the alarm) of a film
from all the IP cameras and one chosen analogue camera.
• Possibility of connection to a PoE switch/hub, in order to do
without the power supply from the control panel (NB: the
power supply from the control panel allows the device to
operate in case of temporary absence of mains power).
If an analogue camera has the video recording on prealarm function enabled, the VEDOCCTV will not be able
to detect the status of the remaining analogue cameras
(enabled, faulty, not connected).
Features Value
Name of manufacturer / supplier Comelit Group S.p.A.
Dimensions (b x h x d) 83 x 66 x 37 mm
Weight 85g
75mA with camera off
95mA with camera on
at 24V
on aux
10V
POE on ethernet
Operating voltage
Operating temperature -10° / +40° C
Operating humidity max +85% RH (not condensed)
CONFIGURATION JUMPERS
Name Function
JP1
Internal use
CN2
Reserved
JP2
Resetting configuration
CONNECTING VEDOCCTV WITH SWITCH/HUB AND CONTROL
PANEL POWER SUPPLY
TO THE 12V POWER SUPPLY
OF THE CONTROL PANEL
NETWORK CABLE
NETWORK CABLE
NETWORK CABLE FOR CONNECTION
TO THE IP MODULE OF THE CONTROL PANEL
NETWORK CABLE FOR CONNECTION
IP CAMERA
LOCAL NETWORK
POE SWITCH / HUB
CONNECTION TERMINALS
SIGNAL FOR 4 CAMERAS
The power supply from switch/hub does not allow
the device to operate in case of temporary absence
of mains power.
TECHNICAL SPECIFICATIONS
Consumption (min./max.)
CONNECTING THE VEDOCCTV MODULE WITH POE SWITCH/HUB
NETWORK CABLE FOR CONNECTION
OF THE IP MODULE OF THE CONTROL PANEL
NETWORK CABLE FOR CONNECTION
IP CAMERA
LOCAL NETWORK
HUB OR SWITCH
CONNECTION TERMINALS
SIGNAL FOR 4 CAMERAS
The power supply from the control panel allows the
device to operate in case of temporary absence of
mains power.
MMS SUPPORT – SYSTEM DESCRIPTION AND MINIMUM REQUIREMENTS
IMPORTANT: In order to use the send MMS on alarm
function, the control panel must be equipped with the IP
module and the GSM module.
After configuring the system correctly, the MMS function will:
• inform the recipient, by MMS, of an alarm event relating to
a zone covered by a specific camera (one camera can be
associated to a given zone).
• include in the same message up to 4 different frames,
captured at different times by the camera associated to the
zone in alarm.
VIDEO STREAMING SUPPORT, RECORDING FILMS AND FRAME
CAPTURES - DESCRIPTION OF THE MINIMUM FEATURES OF
THE SYSTEM
IMPORTANT: In order to use the video streaming functions
from the IP cameras on alarm, the control panel must be
equipped with the IP module.
In order to use:
• the function of sending 4 frames captured by the camera
in the alarm zone to system managers (Vedo Touch, Mini
Touch, Icona Manager VIP) and App;
• the function of activating live streaming by the system
manager (Vedo Touch, Mini Touch, Icona Manager VIP) or
by App;
the control panel must be equipped with the Ethernet
expansion module.
After configuring the system and the film recording function
correctly:
• the alert function will send 4 frames (captured in successive
moments by the camera in the alarm zone) to system
managers (Vedo Touch, Mini Touch, Icona Manager VIP)
and to App.
• the live streaming function will allow the reproduction of the
desired camera to be sent by the system manager (Vedo
Touch, Mini Touch, Icona Manager VIP) and by App;
• the film viewing function will allow the reproduction of the
recording to be sent in streaming by the system manager
(Vedo Touch, Mini Touch, Icona Manager VIP) or by App;
NETWORK PARAMETERS OF PAL/IP MODULE
To be correctly configured by the control panel, the VEDOCCTV
module must be reachable at a known IP address. To ensure
that the communication works in both directions, it is necessary
for the PAL/IP to know the control panel IP address. In default
configuration, the PAL/IP module has the following parameters:
IP Address: 192,168.1,233
Submask: 255,255,255.0
Control panel IP Address: 192,168.1,230
TCP Port control panel 10012
These parameters can be modified when you configure the
system.
31
3.10 WIRELESS SENSORS AND ACCESSORIES
3.11 OUTPUTS SIREN CONNECTION EXAMPLES
For further information on the correct positioning and mounting
of wireless sensors and sirens, refer to the respective instruction
sheets enclosed with the devices in question:
• Bidirectional PET Immunity infrared sensor, via radio
(Art. RFPIRP)
• Magnetic contact sensor with radio transceiver (Art.
RFMAGW/ RFMAGB)
• 4-key radio control (Art. RFREMOTE4)
• Self-powered indoor siren (Art. RFINTSIR)
• Self-powered outdoor siren (Art. RFEXTSIR)
• Wireless smoke and heat detector (Art. RFSMOKE)
• Radio anti-panic button (Art. RFPANIC)
• Infrared volumetric radio sensor with camera (Art.
RFPIRCAM)
The control panel is equipped with a relay capable of supporting
3A at 24V , with potential-free exchange, which is assigned by
default to the control of an alarm sounder. This relay can be
used to control a self-powered siren and a standard siren. The
exchange is accessible via the terminals COM (common), NC
(exchange closed to common in standby) and NO (exchange
open in standby) of terminal block M3-M4.
A positive dedicated to charging the battery of a self-powered
unit is available on terminal V+SIR of terminal block M4. This
positive is limited by a 0.75 A resettable fuse.
In order to guarantee compliance with Standards EN501311 and EN50131-3, a siren sabotage zone must be provided
It is recommended to use a shielded cable for the
connections,with one end of the shield connected to Vand the other left free.
The 2-wire connection is recommended if using sirens that
require a current higher than 0.75 A in alarm mode
3.11.1 Connecting a self-powered siren with 3 or 2 wires
With 3-wire connection, the control panel passes only one
block positive through the relay associated to the alarm; the
siren power supply is connected separately to two terminals on
the control panel (V+SIR and V-). In an alarm state, the block
positive is removed and the siren sounds, being able to use its
backup
battery and the system battery.
3-WIRE CONNECTION
M2
2-WIRE CONNECTION
V+
COM
VSELFPOWERED SIREN
3-WIRE CONNECTION
V+
COM
V-
SELFPOWERED SIREN
M2
COM
NC
NO
V+SIR
TC2
TC1
V-
V+
COM
VSELFPOWERED SIREN
With 2-wire connection, the control panel passes a block
positive and recharges through the relay associated to the
alarm. The siren negative is connected to the control panel V-.
In an alarm state, this positive is removed and the siren sounds
under
own power.
2-WIRE its
CONNECTION
M2
COM
NC
NO
V+SIR
TC2
TC1
V-
V+
COM
VSELFPOWERED SIREN
COM
NC
NO
V+SIR
TC2
TC1
V-
3.11.2 Connecting a non-self-powered indoor siren
It is sometimes necessary to connect an additional, non-selfpowered, indoor siren as backup for the outdoor siren. Using
two-wire connection for the outdoor self-powered siren
simplifies the wiring, as shown in the circuit diagram below.
M2
V+
V+
COM
INTERNAL
SIREN
32
V-
V-
SELFPOWERED SIREN
COM
NC
NO
V+SIR
TC2
TC1
V-
3.11.3 2-wire connection of indoor siren and selfpowered siren with siren fault zone and siren
sabotage zone
SELF-POWERED
SIREN
V+
COM
TMP NC
TMP NC
VFAULT OC
R TAMPER 1K8
R FAULT 1K8
R FAULT 1K8
COM
NC
NO
V+ SIR
TC2
TC1
V-
CONTROL
PANEL
CARD
V+
VTMP NC
TMP NC
3.11.4 2-wire connection of self-powered siren with
siren fault zone and siren sabotage zone
SELF-POWERED
SIREN
R TAMPER 1K8
R FAULT1 1K8
R FAULT2 1K8
Output configured as OC. If the output is configured as an
open collector (OC), in standby the output will be fluctuating
(=no voltage) but in active status it will close terminal TC to V-.
This type of behaviour can be figured with the jumpers of the
control panel card Art. PCBVEDO10, Art. PCBVEDO34, Art.
PCBVEDO68, Art. PCBVEDO200 as follows:
IX: Siren sabotage zone in single balance
IY: Siren fault zone in double balance
V+
COM
TMP NC
TMP NC
VFAULT OC
Terminal block M5 has two generic outputs, TC1 and TC2.
These outputs can be configured as open collectors for earth or
for positive.
Output configured as TC. If the output is configured as a TC,
in standby the output will be fluctuating (=no voltage) but in
active status it will close terminal TC to positive.
IX
IY
INTERNAL
SIREN
3.12 EXAMPLE OF CONNECTION TO OUTPUTS TC1
AND TC2
COM
NC
NO
V+ SIR
TC2
TC1
V-
OUTPUT TC1
ON
OFF
CONTROL
PANEL
CARD
OUTPUT TC2
ON
OFF
IX
IY
R TAMPER1 1K8
R FAULT3 1K8
R FAULT4 1K8
The output has a high
impedance
The output has a high
impedance
JP4 ON OC
JP4 ON TC
Output connects
terminal to earth.
Output assumes value
of approximately 13V.
The output has a high
impedance
The output has a high
impedance
COM
NC
NO
V+ SIR
TC2
TC1
V-
CONTROL
PANEL
CARD
EXTERNAL RELAY ON TC2 OC MODE
(JP4 ON OC)
OC
M2
12V
3.11.5 3-wire connection of self-powered siren with
siren fault zone and siren sabotage zone
SELF-POWERED
SIREN
JP5 ON TC
Output assumes value
of approximately 13V.
For the connection of LEDs or small relays, refer to the diagram
below.
IX: Siren sabotage zone in single balance
IY: Siren fault zone in double balance
V+
COM
TMP NC
TMP NC
VFAULT OC
JP5 ON OC
Output connects
terminal to earth.
EXTERNAL LED ON TC1 TC MODE
(JP5 ON TC)
COM
NC
NO
V+SIR
TC2
TC1
V-
JP4
TC
OC
JP5
TC
IX
IY
IX: Siren sabotage zone in single balance
IY: Siren fault zone in double balance
33
3.13 POWER SUPPLY STATIONS
Low Battery Fault Generation in
11.5V
absence of EPS
3.13.1 Power supply unit management card for
VEDO series control panels Art. PCBPSU
This device can be used to expand Vedo series systems by
providing:
• A new branch to the RS485 data BUS, electrically isolated
with the corresponding power supply output.
• 2 auxiliary power supply outputs.
• 4 Open Collector indication outputs.
• One terminal for tamper contact.
Switch-off Art. PCBPSU in absence
of EPS for Protection against Deep 10.5V
Discharges
Intervention voltage of the protection
against
15V
voltage surges: battery
disconnection
Maximum current for Outputs
1.5A
V+BUS OUT,V+AUX1, V+AUX2
Output voltage operating range
10-15V
(V+BUS OUT,V+AUX1,V+AUX2)
CN1 input voltage operating range 12.8-15V
CN2 input voltage operating range
10.5-15V
(Battery)
CN2
Control panel card consumption
15/20mA
Art. PCBPSU (min./max.)
Maximum current available for
Grade 2: 550mA
external devices
CN1
Grade 2: 1.45A
Maximum current delivered to
100mA
outputs TC1 and TC2
-10° / + 55° with warm dry air
Operating temperature and Operating
-10° / + 40° C with max + 93% RH
humidity
(not condensed)
V+
VA
B
V+
VA
B
6
M2
M3
5
DL1
DL2
DL3
Type of power supply unit
For the Technical Specifications linked to the type of power supply unit,
see paragraph 1.2.4.
JP1
TERMINAL BLOCK M1-M2-M3-M4-M5-M6
Name Function
1 2 3 4 5 6 7 8
Earth Earth connection terminal
4
3
2
1
M4
M5
M6
1. CN1 PSU connector
4. Outputs Power Supply
2. CN2 Battery connector"
5. Data BUS out
3. Outputs
6. Data BUS in
Holes for fixing the PCBPSU card to the metal housing BOXMETAL.
MAIN FEATURES
• The auxiliary power supplies provided by the card are
acquired by the mains power supply units connected
to connector CN1.
• The Open Collector outputs are configured to provide
fault and anomaly indications.
• If the power supply unit is not connected to a control panel,
the indication delay times are as follows: power supply
network alarm delay=1 minute, battery alarm delay=5
minutes.
• When the device is connected to a Vedo series control
panel, it is possible to monitor the status of the auxiliary
power supplies and the power supply unit itself. In this case
network alarm delay and battery alarm delay times can be
configured (using the Safekey keypad or the Safe Manager
software).
TECHNICAL SPECIFICATIONS
bus IN
V+ 485 communication BUS power supply input positive
V- 485 communication BUS power supply input negative
A RS485 data BUS for connection to the control panel (IN) - A
B RS485 data BUS for connection to the control panel (IN) - B
bus OUT
V+ Power supply positive output. 485 communication bus. Limited to 1.5A
V- Power supply negative - output reference. 485 communication BUS
power supply
A RS485 data BUS for connection to other devices (OUT) - A
B RS485 data BUS for connection to other devices (OUT) - B
bus OUT
V+ Power supply positive output. 485 communication bus. Limited to 1.5A
V- Power supply negative - output reference. 485 communication BUS
power supply
A RS485 data BUS for connection to other devices (OUT) - A
B RS485 data BUS for connection to other devices (OUT) - B
OUTPUTS POWER SUPPLY
V+AUX1 Auxiliary 1 power supply output positive. Limited to 1.5A
V- Auxiliary 1 power supply output negative
V+AUX2 Auxiliary 2 power supply output positive. Limited to 1.5A
V- Auxiliary 2 power supply output negative
Features Value
Name of manufacturer / supplier Comelit Group S.p.A.
Dimensions (b x h x d) 140x127x23mm
Housings supported
Art.
BOXPLASTIC
Power supply units supported PSU15
Batteries supported
Art. 30076003
12V/7Ah
Art. BOXMETAL
PSU15
PSU50
Art. 30076003
12V/7Ah
Art. 30076004
12V and 18Ah
Max. battery charging current 0.8A
Battery 80% charging time 8h
Low Battery Fault Generation in
12V
presence of EPS
24H Tamper contact input
OUTPUTS
Weight 115gr
34
TYPE A according to standard
EN50131-6
Environmental class II according to EN50131-1
JP2
V+ AUX1
VV+ AUX2
V24H
01
02
03
04
M1
8h/19h
O1 Open Collector Output 1. Programmed as module Anti-Sabotage by
default. The output is active when module sabotage occurs.
O2 Open Collector Output 2. Programmed as module Low Battery
Anomaly by default. The output is active when the programmed time
has elapsed since the moment at which the battery was no longer
detected or the does not respect the values indicated in the technical
specifications.
O3 Open Collector Output O3. Programmed as module No 230V Mains
Anomaly by default. The output is active when the programmed time
has elapsed since the moment at which the network was no longer
detected.
O4 Open Collector Output O4. Programmed by default to indicate the
fault of the power supply unit or of the power supply outputs. The
output is active when there is a fault in the power supply unit or on the
power supply outputs V+bus, VAUX1 or VAUX2
ADDRESSING
The device address must be unique and can only be
programmed using dip switches.
No.
DIP1
DIP2
DIP3
1
OFF
OFF
OFF
2
ON
OFF
OFF
3
OFF
ON
OFF
4
ON
ON
OFF
5
OFF
OFF
ON
6
ON
OFF
ON
7
OFF
ON
ON
8
ON
ON
ON
DIP4
DIP5
DIP6
not
used
SETTING THE SPEED OF THE CARD ON THE BUS
Note that the standard speed of the bus for VEDO control
panels is 38400 Baud.
BAUD
DIP7
DIP8
OFF
ON
OFF
57600
OFF
ON
115200
ON
ON
Art. VEDOISO omplies with standards EN50131-1 and EN50131-3
MAIN FEATURES
This device can be used to isolate the system so that any faults
or sabotage events which occur downline do not affect the
entire system.
The device is equipped with a dual connection to the VEDO
system 485 BUS:
• the IN port (input)
• the OUT port (output)
The section of the system that you want to isolate from the rest
must be connected to the OUT port.
OUT
B
LED MEANINGS
A
M4
Art.VEDOISO V- V+
DL1 Flashing slowly: no data transfer over BUS at the speed set using
the dip switch.
Flashing quickly: data transfer over BUS in progress.
IN
B
4
3
2
1
ON
24H V- V+
A
5
S1
IN
M2
OUT
6
Name Function
DL2
OFF
Isolator module on control panel bus series Vedo. Allows
protection against faults and sabotage.
JP2
9600
38400 (default)
3.14 BUS ATOR (VEDOISO)
M3
IN
Very slow flashing: (approx. 3 seconds) no data package on the
BUS.
M1
DL1
JP1
DL2 Off: the peripheral is communicating correctly.
DL3 On: indicates that one of the Open Collector outputs is under
protection due to a short circuit.
POWER SUPPLY UNIT CONNECTOR
Name
Function
CN1 External 230 V - 50 Hz power supply unit connector
TECHNICAL SPECIFICATIONS
Features Value
Name of manufacturer / supplier Comelit Group S.p.A.
Dimensions (b x h x d) 56 x 53 x 19 mm
CN2 Battery connector
Weight (without box) 26g + 4g fixing screws
Consumption (min./max.) 40mA
CONFIGURATION JUMPERS
Name
Function
JP1 RS485 output termination*
JP2 RS485 input termination*
Operating voltage 10V
Certified safety grade 2 according to EN50131-1*
* Always remember to insert an end-of-line resistor between A and B of the 485
connection (using the relevant jumpers) to the two ends of the main bus line.
ANTI-TAMPER CONNECTION
The 24H terminal needs the Tamper contact to be connected in
single balanced configuration.
A resistance of 1.8KΩ, in series with the contact, is required.
to 15V
-10° / + 55° with warm dry air
Operating temperature and Operating
-10° / + 40° C with max + 93% RH
humidity
(not condensed)
Device Type B according to EN50131-3
Environmental class II according to EN50131-1
* Respecting any indications for configuration and installation
BUS ISOLATOR TERMINAL BLOCK
Name
Function
IN
ALARMS
SINGLE BALANCED
CONNECTING V- REFERENCE TERMINAL
The incoming RS485 bus (bus IN) is electrically isolated from
the rest of the card. As a result, the V- input terminal must only
be connected to the bus running towards the control panel.
Do not connect the V- terminal for the incoming bus to
other V- terminals present, and do not use it as a reference
for outgoing power supply voltage values. This could
damage the devices used, or cause them to malfunction.
B RS485 data bus for connection to Input B of the control panel serial
line
A RS485 data bus for connection to Input A of the control panel serial
line
24H Tamper contact input
V- Power supply negative input
V+ Power supply positive input
OUT
B RS485 data bus, detects operating anomalies around the output
branch and intervenes by isolating the faulty or sabotaged branch.
Terminal B for peripheral input connection via bus.
A RS485 data bus, detects operating anomalies around the output
branch and intervenes by isolating the faulty or sabotaged branch.
Terminal A for peripheral input connection via bus.
V- Power supply negative output
EARTH CONNECTION
For standard-compliant installation, connect the earth terminal
to the system earth, passing through the power supply earth
connection using the yellow/green cable supplied with the device
housings.
V+ Power supply positive output
In the event of V+ V- power supply shortage, the auto-reset fuse
intervenes. For the reset to take place correctly, the power supply
must be cut off for one minute.
To guarantee system certification, the power supply unit must be
positioned in boxes protected by an anti-opening switch, or in
the control panel housing. The 24h input must be connected to a
balanced line, and connected to a Vedo system input line.
35
ADDRESSING
The device address must be unique and can only be
programmed using dip switches.
No.
DIP1
DIP2
DIP3
1
OFF
OFF
OFF
DIP4
OFF
2
ON
OFF
OFF
OFF
3
OFF
ON
OFF
OFF
4
ON
ON
OFF
OFF
5
OFF
OFF
ON
OFF
6
ON
OFF
ON
OFF
7
OFF
ON
ON
OFF
8
ON
ON
ON
OFF
9
OFF
OFF
OFF
ON
10
ON
OFF
OFF
ON
11
OFF
ON
OFF
ON
12
ON
ON
OFF
ON
13
OFF
OFF
ON
ON
14
ON
OFF
ON
ON
15
OFF
ON
ON
ON
16
ON
ON
ON
ON
SETTING SPEED ON THE BUS
Note that the standard speed of the bus for VEDO control
panels is 38400 Baud.
BAUD
DIP5
DIP6
9600
OFF
OFF
38400
OFF
ON
57600
ON
OFF
115200
ON
ON
DEFAULT
CONFIGURATION JUMPERS
To access dip switch S1 and jumpers JP1 and JP2, you must
remove the plastic casing at the top.
Name
Function
JP1 If activated, enables 485 bus input terminal resistor*
JP2 If activated, enables 485 bus output terminal resistor*
LED MEANINGS
Name Function
DL1 Flashing slowly: no data transfer over bus at the speed set using
the dip switch.
Flashing quickly: data transfer over bus in progress.
DL2 Off: the peripheral is communicating correctly;
Very slow flashing: (approx. 3 seconds) no data package on the
BUS.
TAMPER CONTACT CONNECTION
The 24H terminal needs the Tamper contact to be connected in
single balanced configuration. A resistance of 1.8KΩ, in series
with the contact, is required.
ALARMS
SINGLE BALANCED
To guarantee system certification, the isolator must be positioned
in boxes protected by an anti-opening switch, or in the control
panel housing. The 24h input must be connected to a balanced line.
MOUNTING
The plastic housing allows flush mounting in residential series
boxes or on DIN rails.
1
2
36
3
4
4. Appendix: Mounting instructions
4.1 OPENING THE HOUSING ART. BOXPLASTIC
3
1
2
1
2
4.2 PREPARING THE HOUSING ART. BOXPLASTIC
If the control panel is already assembled, you will have to remove the electronic cards and the power supply unit from the
housing, so as not to risk damaging them
3
2
1
1
2
3
2
1
3
2
4.3 FIXING THE HOUSING ART. BOXPLASTIC TO THE WALL
1
2
1
37
4.4 MOUNTING THE CONTROL PANEL CARD ART.
PCBVEDO10 / PCBVEDO34 / PCBVEDO68 /
PCBVEDO200 AND PCBPSU IN A HOUSING
ART. BOXPLASTIC
4.5 MOUNTING THE POWER SUPPLY UNIT PSU15
IN A HOUSING ART. BOXPLASTIC
1
1
3
1
2
3
4.6 MOUNTING THE EXPANSION ART. VEDO8I8O
AND ART. VEDORF IN A HOUSING ART.
BOXPLASTIC
3
2
1
38
CLACK!
2
4.7 OPENING THE HOUSING ART. BOXMETAL
2
2
open
1
2
1
4.8 FIXING THE HOUSING ART. BOXMETAL TO THE WALL
2
1
5mm
1
2
2
1
3
4
39
4.9 MOUNTING THE CONTROL PANEL CARD ART.
PCBVEDO10 / PCBVEDO34 / PCBVEDO68 / PCBVEDO200
AND PCBPSU IN A HOUSING ART. BOXMETAL
4.10 MOUNTING THE EXPANSION ART. VEDO8I8O
IN A HOUSING ART. BOXMETAL
4.11 MOUNTING THE POWER SUPPLY UNIT PSU15 - PSU50 IN A HOUSING ART. BOXMETAL
CLACK!
1
2
1
2
1
2
3
4
3
40
BLOCKING (OPTIONAL)
4.12 MOUNTING THE MODULE ART. VEDOCCTV IN A METAL HOUSING ART. BOXMETAL
2
1
4.13 FITTING THE BATTERY ART. 30076003 / 30076004 IN METAL CONTAINER ART. BOXMETAL
# only with Art. 30076004
1
2
41
4.14 MOUNTING THE KEYPAD ART. VEDOLCD - ART. VEDOLCDPROX ON BOX 503
1
2
3
1
2
1
3
2
2
2
3
1
4
OPENING
4.15 MOUNTING THE KEYPAD ON THE WALL ART. VEDOLCD - ART. VEDOLCDPROX
1
2
1
2
1
3
2
2
2
3
4
42
OPENING
1
1
4
150 cm
120 cm
4.16 MOUNTING THE VEDO TOUCH (ART. VEDOTOUCH) / MINI TOUCH (ART. 20034607) ON BOX 503
2
3
OPENING
43
4.17 MOUNTING PLANUX MONITOR (ART. 20034801) WITH FLUSH-MOUNTED BOX ART. 6117
14,5 cm
2
3
1
145-150 cm
115-125 cm
14,5 cm
5
1
4
2
3
5
6
8
9
ALTO
UP
HAUT
OBEN
4
2
2
1
3
7
2
1
DISASSEMBLY
44
3
4.18 MOUNTING PLANUX MONITOR (ART. 20034801) WITH WALL SUPPORT ART. 6120
145-150 cm
14,5 cm
1
2
4
5
115-125 cm
14,5 cm
3
6
2
2
1
7
10
3
8
9
DISASSEMBLY
45
4.19 WALL-MOUNTING ICONA MANAGER VIP (ART. 6620) / SU 503 SERIES BOX / ROUND BOX
with Art.6620*
14,2 cm
2
with Art.6620*
with Art.6620*
130 cm
160 cm
14,7 cm
1
1
2
3A
Lmin = 6,5 cm
Lmax = 7 cm
1
2
2
5A
4A
1
2
2
2
1
3C
1
6
7
* Art. 6620 (optional)
2
CLACK !
1
2
1
2
8
1
DISASSEMBLY
46
1
3B
Art. 20003310W
4.20 MOUNTING ICONA MANAGER VIP ON A FLUSH MOUNTED BOX ART. 6117
160 cm
14,7 cm
1
130 cm
14,2 cm
2
3
2
3
L min = 6 cm
5
L max = 10 cm
1
2
4
4
1
5
6
CLACK !
2
1
2
1
2
2
1
7
8
Art. 20003310W
1
9
1
2
DISASSEMBLY
47
4.21 PREPARING THE PLASTIC HOUSING FOR MOUNTING THE EXPANSION ART. VEDORF / VEDO8I8O
1
VEDO8I8O
VEDORF
2
2
3
2
3
1
1
2
4.22 WALL-MOUNTING THE PLASTIC HOUSING FOR MOUNTING THE EXPANSION ART. VEDORF / VEDO8I8O
1
1
2
2
1
2
CLACK!
2
1
3
4
1
2
2
3
OPENING
48
5
5. Appendix: notes on installation and programming
5.1 WHAT TO DO BEFORE POWERING UP THE
SYSTEM
5.3.2 Default codes
The default codes are as follows:
Master Installer Code:001961
User 1 Code111111
5.1.1 Connect the zone inputs correctly
Make sure that all the inputs are connected correctly (closed to
negative directly or via suitably sized resistors, according to the
configuration of the individual inputs).
5.1.2 Connect the bus modules
Make sure that all the modules are connected to each other
correctly and to the alarm control panel.
Remember to make as straight a connection as possible (in and
out type), and that any branches must be as short as possible.
Always remember to insert an end-of-line resistor between A
and B of the 485 connection to the two ends of the main bus
line.
5.1.3 Close all the anti-tamper inputs
Close all the enclosures of the bus modules and of the control
panel or, alternatively, bypass the anti-tamper microswitches.
For standard EN50131, the anti-tamper inputs must be configured
at least in single balance.
IMPORTANT: upon first start-up, only keypad number 1 will
be considered active.
5.1.4 Powering up
It will now be possible to power up the system: power up the alarm
control panel from its power supply unit and connect the battery.
If everything is connected correctly, the green LED on the power
supply unit will light up, confirming that the PSU is working
The control panel will start operating and will confirm this by
causing LED DL3 to flash on the control panel card (1 second
on/off).
5.2 DEFAULT CONFIGURATION
The control panel is factory-set to consider only keypad number 1 to be
present. The control panel's alarm inputs, furthermore, are all enabled
and configured as double balance.
5.3 INTRODUCTION TO PROGRAMMING FROM THE
KEYPAD
5.3.3 Keypad navigation mode
It is possible to configure the system and enter or modify data
using one of the system keypads.
to move about in the menu and
Use the keys
the key
to pass to the next level or to confirm the entry of a
new data item.
Press C to return to the previous menu
THE UNAUTHENTICATED USER can use only the delete key “C”
or the numerical keys. If a key that is not usable is pressed, the
display will show the message "FUNCTION NOT AVAILABLE".
THE USER WHO IS AUTHENTICATED on the keypad and who
presses button C will be returned to the previous menu until the
area status is displayed. If the value of the area status display
time for that keypad is not unlimited, the next time button C is
pressed will return the keypad to standby position, without giving
any indication of the current area status (immediately hiding the
information on the display).
5.3.4 Modifying a numerical value
To modify a numerical value, type in the desired value, following
the format shown on the display, omitting non-numerical
characters, but filling in all the numerical characters of the
proposed format.
e.g. date DD-MM-YY must be entered as DDMMYY; 2
September 2012 will become 020912, without dashes but
with a zero at the beginning to fill the tens digit for the days.
e.g. Setpoint 1.14 is entered as 114, without the decimal
point.
5.3.5 Editing an alphanumeric string
Once you have selected the string you wish to change (for
example, the description of a zone) the first character available
for editing will start to flash. At this point characters can be
entered or replaced using the same technique as used in
mobile telephones with a pushbutton keypad. Press the
same key several times to change the suggested character in
accordance with a set sequence. The table below shows the
sequence of characters available for each key.
Press the C key when the first character is flashing to exit the
string without saving any changes.
To move around within the string, use the right and left
navigation keys.
5.3.1 Keypad description
Pressing the C key while inside the string deletes the character
to the left of the flashing character.
The new character, when necessary, will be entered to the left
of the flashing character.
1.
Press Confirm to save the changes.
The table below shows the keys and the sequence of characters
associated with each
2.
Number key
3.
4.
6.
1. Partial 1 and Partial 2 Keys
2. Navigation keys/function keys
3. Confirm key
5.
4. ON/OFF Keys
5. Programming key
6. Cancel key
Corresponding character sequence
1
2
3
4
5
6
7
8
. , :
A B
D E
G H
J K
M N
P Q
T U
0
(space) 0
9
; _ - # * ' @ / 1
C a b c 2
F d e f 3
I g h i 4
L j k l 5
O m n o 6
R S p q r s 7
V t u v 8
W X Y Z w x y z 9
When the keypad is packaged a transparent label is applied (it
can then be removed during programming).
Incorrect application of the label can cause the keys to
stick
49
5.3.6 Setting the keypad serial number
At first start-up, the keypad displays the message NOT
CONNECTED. To enable the control panel to recognise
keypad number 1 (the only keypad that can be recognised by
the control panel by default), proceed as follows:
1. Press the prog key on the keypad: the display will show the
message 1 Config. Bus followed by two vertical arrows (up
and down).
2. Press confirm .
3. Enter the serial number of the first keypad by typing the
digits 001 in sequence, and then press confirm.
4. The display now shows the message SERIAL COM. Speed:
with the proposal "38400".
5. Press confirm.
»» Keypad number one will now be taken in charge by the
control panel and can be used for activating, deactivating
and configuring the system.
5.3.7 Total activation of the alarm system
1. From the keypad, enter a valid user code (the default setting
is 111111) and then press the ON key
2. The keypad asks for confirmation: “TOTAL ACTIVATION?”
3. Press the Confirm key to confirm.
4. The keypad confirms the action with the message:
“ACTIVATED”
5.3.8 Partial activation of the alarm system /
execution of a scenario
1. From the keypad, enter a valid user code (default 111111)
followed by either the Partial 1 key or the Partial 2 key.
2. If necessary, use the up and down navigation keys to select a different
scenario from the proposed scenario, and then press Confirm.
3. The keypad confirms the action with the message:
“ACTIVATED”
5.3.9 Total deactivation of the alarm system
1. From the keypad, enter a valid user code (the default setting
is 111111) and then press the OFF key.
2. The keypad confirms the action with the message:
“DEACTIVATED”
3. Deactivation will also deactivate any alarms in progress
within a few seconds.
5.3.10 Muting an alarm with the system deactivated
1. From the keypad, enter a valid user code (default 111111).
2. Once the code has been recognised, press the Prog key
until the message “DONE” appears on the screen.
3. This will mute the alarm.
5.3.11 Entering programming as a User
1. From the keypad, enter a valid user code (default 111111)
2. Press Prog.
3. The first line of the display will show the message "System
Mgmt.” indicating that you can now modify the system
options.
5.3.12 Entering programming as an Installer
(installer code authorisation)
√√ The installer code must be authorised by the user, so
the procedure is as follows:
1. Go into programming mode as a user (see previous
paragraph).
2. Using the navigation keys (up and down), select the
“COMMANDS” menu on the second line of the display, and
press Confirm: the message “GENERATE COMMAND” will
appear on the first line of the display.
3. Using the navigation keys (up and down), select “AUTH.
INSTALLER?” on the second line, and press Confirm: the
message “DONE” will appear on the display.
4. Press C until you have exited the menus completely (i.e.
until the date and time are displayed on the keypad).
5. From the keypad, enter a valid installer code (default master
code 001961).
6. Press Prog.
7. The first and second lines of the display will show the
messages “Main Menu” and “Parameter Mgmt.” indicating
50
that you can now display or modify the system options.
8. From this position, you can use the navigation keys to
select either the “System Mgmt.” menu, which corresponds
to the user menu, or the “Parameter Prog.” menu, which is
reserved for the installer.
9. Press the Confirm key to enter the respective submenus.
5.3.13 Changing date and time
√√ To change the date and time from the keypad, you
need to go into programming mode.
As installer:
1. Go into programming mode as an installer (see relevant
paragraph).
2. Using the navigation keys, select “System Mgmt.”, then
continue as a user.
As user:
1. Go into programming mode as a user (see relevant
paragraph).
2. Using the navigation keys (up and down), select the
“Options” menu on the second line of the display, and press
Confirm.
3. Using the navigation keys (up and down), select the
“Change date/time” option on the second line, and press
Confirm.
4. The first line will show DD-MM-YY (day, month and year)
and the second line will display the date set on the control
panel.
5. Enter the date using the number keys (e.g.: 1 September
2012 becomes 010912), then confirm.
6. The first line of the display now shows HH-MM (hours and
minutes) and the second line shows the time set on the
control panel.
7. Enter the time in the format displayed (e.g. 1.15 pm becomes
1315), then confirm.
8. This done, the display will show the message PARAMETER
CHANGED.
9. Press C to go up one level in the menu, or C repeatedly until
the date and time appear on the keypad.
5.3.14 Acquiring an RFID key code from the keypad
1. From the keypad, enter a valid installer code (default master
code 001961).
2. Press Prog.
3. The first and second lines of the display will show the
messages “Main Menu” and “Parameter Prog.” respectively,
indicating that you can now modify the system options
4. Press the Confirm key to enter the respective submenus.
5. Using the navigation keys (up and down) select
“ProximityKeys” submenu. Press confirm.
6. The display will show the message “Key 1” and below it, the
parameter that you can modify, namely “Description”
7. Using the navigation keys (left and right), select the number
of the key you intend to acquire.
8. Press Confirm if you intend to change the description,
then confirm to make the change or press C to leave the
description as it is.
9. Using the navigation keys (up and down), select the
"Acquire" submenu. Still using the navigation keys, select
the type of peripheral from which you intend to acquire the
key code and its bus address, then press Confirm again.
10.The display will show the message “Acq. Key: In progress...”
11.Bring the key close to the RFID reader: the message will
change from "In progress..." to "Acquired".
12.Press Confirm: the display will show a description of the
colour of the key's plastic housing
13.Press Confirm again to associate the key to the desired
user.
14.Once you have finished making changes from the keypad,
remember to transfer them to the PC by means of the
Comelit alarm control panels configuration programme.
5.3.15 Acquiring a radio sensor code from the
keypad
1. Insert the battery in the sensor to be learned and wait until
the led stops flashing.
2. From the keypad, enter a valid installer code (default master
code 001961).
3. Press Prog.
4. The first and second lines of the display will show the
messages “Main Menu” and “Parameter Prog.” respectively,
indicating that you can now modify the system options
5. Press the Confirm key to enter the respective submenus.
6. Using the navigation keys (up and down), select “Radio
Zones” submenu. Press confirm.
7. The display will show the message “Radio Zone 1” and below
it, the parameter that you can modify, namely “Description”.
8. Using the navigation keys (left and right), select the position
in which you intend to acquire the sensor.
9. Using the navigation keys (up and down), select “Acquisition”
and press Confirm The display will show the message “Acq.
Radio Zone: In progress...”
10.Now press and release the tamper button on the sensor.
11.If acquisition is successful, the display will show the type of
sensor and the unique code number of the sensor.
12.If acquisition fails because the sensor is already saved
on the control panel, the display will show the message
“Acq. failed Dev. Duplicated” In this case, it is preferable to
acquire the parameters from a PC using the configuration
software, in order to check the programmed sensors, the
acquired codes and their parameters. This will make it
easier to correct any configuration errors.
13.Once you have finished making changes from the keypad,
remember to transfer them to the PC by means of the
Comelit alarm control panels configuration programme.
5.3.16 Acquiring a radio control code from the
keypad
1. Press buttons n° 2 and 3 simultaneously until the radio
control LEDs start flashing autonomously, then release
the buttons and wait for the LEDs to go off. Should this not
happen within about ten seconds (e.g. with a new radio
control) move onto the next point.
2. From the keypad, enter a valid installer code (default master
code 001961).
3. Press Prog.
4. The first and second lines of the display will show the
messages “Main Menu” and “Parameter Prog.” respectively,
indicating that you can now modify the system options
5. Press the Confirm key to enter the respective submenus.
6. Using the navigation keys (up and down), select the “Radio
Controls” submenu. Press Confirm
7. The display will show the message “Radio Control 1”
and below it, the parameter that you can modify, namely
“Description”.
8. Using the navigation keys (left and right) select the position
in which you intend to acquire the radio control.
9. Using the navigation keys (up and down), select “Acquisition”
and press Confirm The display will show the message “Acq.
Radio Tel.: In progress...”
10.Press buttons 3 and 4 simultaneously until the radio control
LEDs start flashing, then release the buttons.
11.If acquisition is successful, the display will show the
message “DEV. PENDANT” and the unique code number of
the radio control.
12.Using the navigation keys (up and down), select “User” and
press Confirm
13.Use the navigation keys to choose the user to whom the
radio control is to be associated and press Confirm.
14.Once you have finished making changes from the keypad,
remember to transfer them to the PC by means of the
Comelit alarm control panels configuration programme.
5.3.17 Acquiring a siren code from the keypad
1. Disconnect the siren battery, if connected, and disconnect
the audio from its connector. If the audio is already
disconnected, connect it briefly to discharge the capacitors
in the circuit and ensure subsequent clean switch-on.
2. From the keypad, enter a valid installer code (default master
code 001961).
3. Press Prog.
4. The first and second lines of the display will show the
messages “Main Menu” and “Parameter Prog.” respectively,
indicating that you can now modify the system options
5. Press the Confirm key to enter the respective submenus.
6. Using the navigation keys (up and down) select the “Radio
Outputs” submenu. Press confirm.
7. The display will show the message “Output 1” and below it,
the parameter that you can modify, namely“Description”
8. Using the navigation keys (left and right) select the position
in which you intend to acquire the radio control.
9. Using the navigation keys (up and down) select “Acquisition”.
10.Press and hold the siren's LEARN button, which is located
near the connection strip for the configuration jumpers, and
connect the battery. Hold the LEARN button down until the
siren flashing light starts flashing quickly, then release the
button.
11.Wait until the flasher starts flashing more slowly.
12.Now press Confirm on the keypad. The display will show the
message “Acq. Radio Tel.: In progress...”
13.After about fifteen seconds, the result of the acquisition will
appear on the display.
14.Once you have finished making changes from the keypad,
remember to transfer them to the PC by means of the
Comelit alarm control panels configuration programme.
5.3.18 Exiting programming mode
„„ To exit programming mode, simply press C until you have
exited the menus completely, i.e. until the date and time are
displayed on the keypad.
5.3.19 Restoring factory settings
You can reset the control panel configuration at two levels: level
one, defined as Partial, and level two, defined as Total.
TOTAL RESET
A total reset reconfigures the control panel card to its default
settings, in such a way that it can be re-used as though newly
unpacked from its packaging. Total resets can be performed
only via the configuration software, provided you know both a
user code and an installer code. It may be necessary to perform
a partial reset to recover the necessary codes.
The total reset process is described in the procedures set
down in the system configuration manual.
PARTIAL RESET (CODE RECOVERY)
A partial reset is confined to recovering the control panel codes,
thereby making it possible to restore a system from which all
the necessary codes for use and management have been lost.
A partial reset can be performed in hardware mode only.
To perform a partial reset to recover the default master installer
and user codes, proceed as follows:
1.
2.
3.
4.
Switch off all power to the control panel card
Insert a jumper on connector JP6
Power up the control panel
Wait until LED DL3 starts flashing at about 1 flash per
second
5. Remove the jumper from JP6
6. The codes are now restored to their factory settings
51
5.3.20 Setting the control panel to Service Status
This function allows the installer to work on the Vedo
System with complete peace of mind, with the siren, PSTN
part, GSM part and email all "silenced".
The control panel is working and can be programmed (via
Safe Manager) but does not generate any Alarm event.
1. From the keypad, enter a valid user code (default 111111).
2. Press Prog.
3. The first line of the display will show the message “System
Mgmt.” indicating that you can now modify the system
options.
4. Using the navigation keys (up and down), select the
“COMMANDS” menu on the second line of the display, and
press Confirm: the message “GENERATE COMMAND” will
appear on the first line of the display.
5. Using the navigation keys (up and down), select “AUTH.
INSTALLER?” on the second line, and press Confirm: the
message “DONE” will appear on the display.
6. Press C until you have exited the menus completely (i.e.
until the date and time are displayed on the keypad).
7. From the keypad, enter a valid installer code (default master
code 001961).
8. Press Prog.
9. Open the control panel cover.
10.Insert jumper JP7.
5.4 FAST NAVIGATION OF KEYPAD MENU
(INSTALLER AND USER)
At whatever menu depth level you are, it is possible to use fast
navigation by inserting the coordinates.
The coordinates are inserted in pairs of lines, or columns, for each
navigation depth level.
Each coordinate is confirmed by pressing prog.
The end of inserting the coordinates is confirmed by pressing
Any error in entering the coordinates is indicated with the message
"FUNCTION NOT AVAILABLE". The same message is also displayed
if a user does not possess the necessary authorisations for access to
the navigation level requested.
Start entering the coordinates from the current level.
EXAMPLE 1: "ENABLE BUZZER" ON KEYPAD 1
Traditional navigation with keys
LEVEL 1
(1 Main Menu
(1 Main Menu
.1) Prog. Parameters
.2) System Mgmt.
LEVEL 2
»» The control panel will remain in service while jumper
JP7 remains inserted. The keypad display will show
"SCHEDULED MAINTENANCE!" or "N" across all areas.
(.1 Prog. Parameters
(.1 Parameters Prog.
.1) Keypads
....) ......
LEVEL 3
10 ×
(.1 Keypad 1
5.3.21 Exiting Service Status
1. From the keypad, enter a valid installer code (default master
code 001961).
2. Press Prog.
3. Remove jumper JP7.
4. Close the control panel cover.
5. Press C until you completely leave the menus.
.
Fast navigation can be cancelled by pressing "C" until all the
numbers entered have been deleted.
(.1 Keypad 1
.1) Description
.16) Buzzer enabled
Fast navigation
1. Consult the table with the indices of the parameters* and
find the index of the desired function
Indices
Parameters
1.1.1.1.x.16
Buzzer on
LEVEL 3
LEVEL 2
LEVEL 1
where x= "device number" coordinate
2. Type in the index as follows, pressing prog at "." and
pressing
at the end of the sequence:
1
1
1
1
1
16
* the following pages show only the indices of the parameters
to be configured to obtain grade 2 certification according to
EN50131-1.
EXAMPLE 1: "ENABLE BUZZER" ON KEYPAD 1 FROM DEPTH
LEVEL 2 PARAMETERS PRG./VEDOTOUCH
Traditional navigation with keys
LEVEL 2
(1 Prog. Parameters
(.1 Parameters Prog.
.1) Keypads
.2) Vedotouch
LEVEL 3
(.1 Keypad 1
.1) Description
52
10 ×
(.1 Keypad 1
.16) Buzzer enabled
5.5 CONFIGURATIONS NECESSARY TO
GUARANTEE GRADE 2 CERTIFICATION
ACCORDING TO EN50131-1
Fast navigation
1. Consult the table with the indices of the parameters* and
find the index of the desired function, starting from the
current depth level
Indices
Parameters
1.1.1.1.x.16
Buzzer on
LEVEL 3
LEVEL 2
This chapter provides indications on the configuration parameters
which, if varied, could lower the safety level of the system, and the
configurations necessary to guarantee I&HAS certification.
For further details on programming and configuration,
consult the programming technical manual (downloadable
from the website pro.comelitgroup.com).
2. Type in the index as follows, pressing prog at "." and
at the end of the sequence:
pressing
1
1
1
16
* the following pages show only the indices of the parameters
to be configured to obtain grade 2 certification according to
EN50131-1.
5.5.1 Keypads
Vedo10 x: from 1 to 2 / Vedo34 x: from 1 to 8 / Vedo68 x: from 1 to 8 / Vedo200 x: from 1 to 16
Indices
Parameters
1.1.1.1.x.2
1.1.1.1.x.4
1.1.1.1.x.5
1.1.1.1.x.16
1.1.1.1.x.17
1.1.1.1.x.18
1.1.1.1.x.19
1.1.1.1.x.22
1.1.1.1.x.24
1.1.1.1.x.25
1.1.1.1.x.26
Checked areas
Tamper areas
Technical areas
Buzzer on
Entrance Buzzer
Exit Buzzer
Alarm Buzzer
Pre-alert Buzzer
System status display time
Tamper cycles
Technical cycles
Unlimited System status
display time
Unlimited tamper cycles
Unlimited technical cycles
Quick activation
Area status
Zones open
Send email
Send Digital Com
Buzzer ActDeact
Buzzer Act.Failed
1.1.1.1.x.27
1.1.1.1.x.28
1.1.1.1.x.29
1.1.1.1.x.33
1.1.1.1.x.35
1.1.1.1.x.37
1.1.1.1.x.40
1.1.1.1.x.41
1.1.1.1.x.43
1.1.1.1.x.44
Configurations necessary to guarantee
Grade 2 certification
At least one selected area
At least one selected area
At least one selected area
Active
Active
Active
Active
Active
0 (+30 seconds)
Unlimited
Unlimited
Deselected
Selected
Selected
Deselected
Selected
Selected
Selected
Selected
Selected
Selected
5.5.2 App
x: from 1 to 8
Indices
Parameters
1.1.1.5.x.2
1.1.1.5.x.3
1.1.1.5.x.4
1.1.1.5.x.9
1.1.1.5.x.10
1.1.1.5.x.12
1.1.1.5.x.23
Controllable areas
Tamper areas
Tamper cycles
Send email
Send digital communication
Unlimited tamper cycles
Unlimited start-up time
Configurations necessary to guarantee
Grade 2 certification
At least one selected area
At least one selected area
Unlimited
Selected
Selected
Selected
Deselected
5.5.3 Input/output expansions (8I8O)
Vedo10 x: not available / Vedo34 x: from 1 to 8 / Vedo68 x: from 1 to 12 / Vedo200 x: from 1 to 50
Indices
Parameters
1.1.1.7.x.2
1.1.1.7.x.3
1.1.1.7.x.4
1.1.1.7.x.5
1.1.1.7.x.8
1.1.1.7.x.9
1.1.1.7.x.11
1.1.1.7.x.12
Tamper areas
Technical areas
Tamper cycles
Technical cycles
Unlimited tamper cycles
Unlimited technical cycles
Send email
Send Digital Com
Configurations necessary to guarantee
Grade 2 certification
At least one selected area
At least one selected area
Unlimited
Unlimited
Selected
Selected
Selected
Selected
5.5.4 Power supply stations
Vedo10 x: from 1 to 1 / Vedo34 x: from 1 to 4 / Vedo68 x: from 1 to 8 / Vedo200 x: from 1 to 8
Indices
Parameters
1.1.1.8.x.2
1.1.1.8.x.3
1.1.1.8.x.4
1.1.1.8.x.5
1.1.1.8.x.7
1.1.1.8.x.8
1.1.1.8.x.10
1.1.1.8.x.11
1.1.1.8.x.13
1.1.1.8.x.14
1.1.1.8.x.15
Tamper Areas
Technical Areas
Tamper cycles
Technical cycles
Unlimited tamper cycles
Unlimited technical cycles
Send email
Send digital communications
Tamper enabled
Network alarm delay
Battery alarm delay
Configurations necessary to guarantee
Grade 2 certification
At least one selected area
At least one selected area
Unlimited
Unlimited
Selected
Selected
Selected
Selected
Selected
Max 60 seconds
Max 5 minutes
53
5.5.5 Isolators
5.5.9 Radio zones
Vedo10 x: from 1 to 4 / Vedo34 x: from 1 to 8 / Vedo68 x: from 1 to 16 / Vedo200 x: from 1 to 16
Indices
Parameters
1.1.1.9.x.2
1.1.1.9.x.3
1.1.1.9.x.4
1.1.1.9.x.5
1.1.1.9.x.7
1.1.1.9.x.8
1.1.1.9.x.10
1.1.1.9.x.11
1.1.1.9.x.13
Tamper areas
Technical areas
Tamper cycles
Technical cycles
Unlimited tamper cycles
Unlimited technical cycles
Send email
Send digital communications
Tamper enabled
Configurations necessary to guarantee
Grade 2 certification
At least one selected area
At least one selected area
Unlimited
Unlimited
Selected
Selected
Selected
Selected
Selected
5.5.6 Radio expansion
Vedo10 x: from 1 to 1 / Vedo34 x: from 1 to 2 / Vedo68 x: from 1 to 3 / Vedo200 x: from 1 to 8
Indices
Parameters
1.1.1.10.x.2
1.1.1.10.x.3
1.1.1.10.x.4
1.1.1.10.x.5
1.1.1.10.x.7
1.1.1.10.x.8
1.1.1.10.x.10
1.1.1.10.x.11
Tamper areas
Technical areas
Tamper cycles
Technical cycles
Unlimited tamper cycles
Unlimited technical cycles
Send email
Send digital communication
Configurations necessary to guarantee
Grade 2 certification
At least one selected area
At least one selected area
Unlimited
Unlimited
Selected
Selected
Selected
Selected
5.5.7 Radio outputs
Configurations necessary to guarantee
Grade 2 certification
1.1.1.11.x.7
Siren on time out (not active) **
1.1.1.11.x.8
Siren sound for on (not active) **
1.1.1.11.x.13
Cycle Outputs
**
1.1.1.11.x.14
Unlimited Cycle Outputs
**
1.1.1.11.x.15
Output type
*** Monostable
1.1.1.11.x.17
OFF Time
**
1.1.1.11.x.19
ON Time
**
1.1.1.11.x.20
System status areas
At least one selected area
1.1.1.11.x.21
Tamper and technical areas
At least one selected area
1.1.1.11.x.22
Sabotage cycles
Unlimited
1.1.1.11.x.23
Technical cycles
Unlimited
1.1.1.11.x.24
Monitoring time
Maximum 20 minutes
1.1.1.11.x.25
Unlimited sabotage cycles
Selected
1.1.1.11.x.26
Unlimited technical cycles
Selected
1.1.1.11.x.31
Disable battery check
Deselected
** The total activation time of a siren must not exceed that prescribed by local regulations.
*** These apply only to sirens
Parameters
Parameters
1.1.1.11.x.27.y.1
Event
1.1.1.11.x.27.y.2
Polarity
1.1.1.11.x.27.y.3
And/or
* These apply only to sirens
Parameters
1.1.1.11.x.28.1.1
Timer in And
Timer in Or
Events logic
Send email
Send digital communicator
Output activation only with
system activated
1.1.1.11.x.28.1.2
1.1.1.11.x.28.1.7
1.1.1.11.x.28.1.9
1.1.1.11.x.28.1.10
1.1.1.11.x.28.1.12
Configurations necessary to guarantee
Grade 2 certification
* Alarms/Sabotage+ Motion sensor
jamming fault
* Direct
* OR
Configurations necessary to guarantee
Grade 2 certification
* No timer
* No timer
* OR
Selected
Selected
Selected if connected to a siren
* These apply only to sirens
Vedo10 x: from 1 to 11 / Vedo34 x: from 1 to 64 / Vedo68 x: from 1 to 96 / Vedo200 x: from 1 to
256
Parameters
1.1.1.12.x.3
1.1.1.12.x.5
1.1.1.12.x.7
1.1.1.12.x.13
1.1.1.12.x.14
1.1.1.12.x.19
Areas
Unlimited fault cycles
Fault cycles
Send email
Send digital communications
Forced activation
54
Monitoring
Unlimited fault cycles
Fault cycles
Tamper enable
Configurations necessary to guarantee
Grade 2 certification
At least one selected area
Selected
Unlimited
Selected
Selected
Deselected
Configurations necessary to guarantee
Grade 2 certification
Maximum 20 minutes
Selected
Unlimited
Selected
RADIO SUBZONE PARAMETERS
Indices
Parameters
Configurations necessary to guarantee
Grade 2 certification
1.1.1.13.x.21.1.3
Areas
At least one selected area
1.1.1.13.x.21.1.4
Alarm cycles
Can be self-disabled (alarm
only)
Can be self-disabled with
reset (alarm only)
Unlimited alarm cycles
Send email
Send digital com
1.1.1.13.x.21.1.22
1.1.1.13.x.21.1.23
1.1.1.13.x.21.1.30
1.1.1.13.x.21.1.44
1.1.1.13.x.21.1.45
Unlimited
Deselected
Deselected
Selected
Selected
Selected
5.5.10 Wired zones
Vedo10 x: from 1 to 16 / Vedo34 x: from 1 to 95 / Vedo68 x: from 1 to 133 / Vedo200 x: from 1 to
453
Vedo10 y: from 1 to 1 / Vedo34 y: from 1 to 2 / Vedo68 y: from 1 to 2 / Vedo200 y: from 1 to 2
Configurations necessary to guarantee
Grade 2 certification
All alarm, fault and command zones
must be set to double or triple balance or
1.1.1.14.x.13
Balancing
double with EOL. The sabotage zones
must be set to single or double or triple or
triple with jamming or double with EOL.
1.1.1.14.x.14
Unlimited fault cycles
Selected
1.1.1.14.x.15
Fault cycles
Unlimited
* If triple balance is not used for all the sensors, three inputs of the control panel must be
programmed to signal the following events:
- Detector fault
- Anti-robbery device fault, if robbery zone present
- Siren fault
In order to guarantee compliance with Standards EN50131-1 and EN50131-3:
In order to guarantee compliance with Standards EN50131-1 and EN50131-3, a siren sabotage
zone must be provided.
Parameters
SUBZONE PARAMETERS
Indices
Parameters
1.1.1.14.x.15.y.3
Areas
Alarm cycles
Can be self-disabled (alarm
only)
Can be self-disabled with
reset (alarm only)
Unlimited alarm cycles
Send email
Send digital com
1.1.1.14.x.15.y.4
1.1.1.14.x.15.y.22
1.1.1.14.x.15.y.44
1.1.1.14.x.15.y.45
Configurations necessary to guarantee
Grade 2 certification
At least one selected area
Unlimited
Deselected
Deselected
Selected
Selected
Selected
5.5.11 Areas
Vedo10 x: from 1 to 2 / Vedo34 x: from 1 to 8 / Vedo68 x: from 1 to 8 / Vedo200 x: from 1 to 16
Indices
Parameters
1.1.1.16.x.4
1.1.1.16.x.5
1.1.1.16.x.8
1.1.1.16.x.10
1.1.1.16.x.15
Entry 1 time
Entry 2 time
Pre-alert time
Pre-alarm time
Report pre-alert
Configurations necessary to guarantee
Grade 2 certification
Max 45 seconds
Max 45 seconds
Other than 0
0
Selected
5.5.12 Wired outputs
Vedo10 x: from 1 to 7 / Vedo34 x: from 1 to 75 / Vedo68 x: from 1 to 115 / Vedo200 x: from 1 to
419
y: from 1 to 4
Indices
5.5.8 Radio controls
Indices
1.1.1.13.x.3
1.1.1.13.x.16
1.1.1.13.x.18
1.1.1.13.x.20
1.1.1.14.x.15.y.30
RADIO OUTPUT CONFIGURATION
Indices
Parameters
1.1.1.14.x.15.y.23
RADIO OUTPUT EVENTS
Indices
Indices
Indices
Vedo10 x: from 1 to 16 / Vedo34 x: from 1 to 32 / Vedo68 x: from 1 to 48 / Vedo200 x: from 1 to
128
y: from 1 to 4
Indices
Vedo10 x: from 1 to 16 / Vedo34 x: from 1 to 64 / Vedo68 x: from 1 to 96 / Vedo200 x: from
1 to 256
Parameters
Configurations necessary to guarantee
Grade 2 certification
* Monostable
Deselected
**
**
**
**
1.1.1.17.x.3
Output type
1.1.1.17.x.5
Unlimited cycles
1.1.1.17.x.6
ON time scale
1.1.1.17.x.7
ON Time
1.1.1.17.x.8
OFF TIME:
1.1.1.17.x.10
Cycles
* These apply only to outputs connected to sirens
** The total activation time of a siren must not exceed that prescribed by local regulations.
5.5.15 IP Options
WIRED OUTPUT EVENTS
Indices
Parameters
1.1.1.17.x.11.y.1
Event
1.1.1.17.x.11.y.2
Polarity
And/or
1.1.1.17.x.11.y.3
* These apply only to outputs connected to sirens
Configurations necessary to guarantee
Grade 2 certification
* Alarms/Sabotage+ Motion sensor
jamming fault
* Direct
* OR
WIRED OUTPUT CONFIGURATION
Indices
Parameters
1.1.1.17.x.12.1.1
Timer in And
Timer in Or
Events logic
Send email
Send digital communicator
Output activation only with
system activated
1.1.1.17.x.12.1.2
1.1.1.17.x.12.1.7
1.1.1.17.x.12.1.9
1.1.1.17.x.12.1.10
1.1.1.17.x.12.1.12
Configurations necessary to guarantee
Grade 2 certification
* No timer
* No timer
* OR
Selected
Selected
Selected if connected to a siren
* These apply only to outputs connected to sirens.
For standard EN50131 an output of the control panel must be activated in the case of a fault and must not
be connected to a siren.
5.5.13 User
Vedo10 x: from 1 to 8 / Vedo34 x: from 1 to 32 / Vedo68 x: from 1 to 50 / Vedo200 x: from 1 to 200
Indices
Parameters
1.1.1.20.x.17
1.1.1.20.x.18
Send email
Send digital communicator
Configurations necessary to guarantee
Grade 2 certification
Selected
Selected
The codes accepted must have 6 figures and range from 000000 to 999998. Code 999999 is
not an accepted code. The robbery code is the user code + 1.
Example: user code 111111, the corresponding robbery code is 111112. Code 119999,
robbery code = 120000. Code 123459, robbery code = 123460 - It is not possible to register
a user code corresponding to an existing user code + 1, since this new code corresponds to
the robbery code of the existing user.
In the system it is therefore possible to store up to a theoretical maximum of 999943 user
codes. The calculation is the result of the fact that it is not possible to create a user code that
is the same as an existing user code + (which is the robbery code). The actual maximum
number of user codes that can be fitted is shown in the table “USER CODES / KEYS /
REMOTE CONTROLS” on page 5.
The authorised user can perform an infinite number of changes of his user code and can
create and eliminate another user, whereas he is unable to modify any user code other than
his own.
CODE TYPE
Indices
Parameters
1.1.1.24.1.1
1.1.1.24.1.2
1.1.1.24.1.3
1.1.1.24.1.4
1.1.1.24.1.5
1.1.1.24.1.18
1.1.1.24.1.19
1.1.1.24.1.20
1.1.1.24.1.21
1.1.1.24.1.22
1.1.1.24.1.23
1.1.1.24.1.24
1.1.1.24.1.28
1.1.1.24.1.29
IP
Netmask
Gateway
Dns1
Dns2
SMTP server
SMTP port
SMTP Email
SMTP Username
SMTP Password
SMTP Email subj.
SMTP with ssl
SMTP enable
Internet check enable
* If the digital communicator or voice messages are not enabled
5.5.16 GSM settings
Indices
Parameters
1.1.1.25.1.24
Jamming control
Indices
Parameters
1.1.1.22.x.19
Request assistance
1.1.1.22.x.20
1.1.1.22.x.21
1.1.1.22.x.23
Change Pin
Reset control panel
Fault management
1.1.1.22.x.26
Programme from PC
1.1.1.22.x.42
1.1.1.22.x.44
Codes menu
FW Update
1.1.1.22.x.45
Reset alarms L3
Configurations necessary to guarantee
Grade 2 certification
Active for at least one type of user (x
enab. inst.) and one type of installer (x
enab. manuf.)
Active only for installers
Active at least for manufacturer
Active for all
Active at least for installer and
manufacturer
Active for all
Only for manufacturer
Selected
Deselected for Patrol
5.5.14 Installers
Vedo10 x: from 1 to 3 / Vedo34 x: from 1 to 6 / Vedo68 x: from 1 to 6 / Vedo200 x: from 1 to 6
Indices
Parameters
1.1.1.21.x.5
1.1.1.21.x.6
Send email
Send digital communicator
Configurations necessary to guarantee
Grade 2 certification
Selected
Selected
Configurations necessary to guarantee
Grade 2 certification
Selected
5.5.17 Telephone Options
Indices
Parameters
1.1.1.27.1.5
Tones recognition timeout
Telephone line parameters
(pstn)
Length of call
Voice message repetition
Attempts
Send message
Termination with confirmation
Tones control (pstn)
Telephone line control (pstn)
Alert Priority Setup
1.1.1.27.1.9
1.1.1.27.1.10
1.1.1.27.1.12
1.1.1.27.1.14
1.1.1.27.1.15
1.1.1.27.1.16
1.1.1.27.1.19
1.1.1.27.1.20
1.1.1.27.1.21
Configurations necessary to guarantee
Grade 2 certification
= 60 seconds
Selected
= 60 seconds
5
3
Press key 1
Selected
Selected
Selected
SMS and MMS follow
5.5.18 Phone Book / Email
x: from 1 to 16
Configurations necessary to guarantee
Grade 2 certification
1.1.1.28.x.1
Description
*
1.1.1.28.x.2
Telephone
*
1.1.1.28.x.4
Line active
* At least one selected
1.1.1.28.x.7
Email receipt
* At least one selected
* If the digital communicator is not active, at least one user must be present
Indices
x: from 1 to 9
Configurations necessary to guarantee
Grade 2 certification
* Completed
* Completed
* Completed
* Completed
* Completed
* Completed
* Completed
* Completed
* Completed
* Completed
* Completed
* Completed
* Selected
* Selected
Parameters
5.5.19 Digital communicator contacts list
x: from 1 to 4
Indices
Parameters
1.1.1.29.x.2
1.1.1.29.x.4
1.1.1.29.x.5
1.1.1.29.x.6
Periodic test
Protocol
Test period
Attempts
1.1.1.29.x.7
Number to call
1.1.1.29.x.8
Customer code
1.1.1.29.x.10
Periodic test start date
Configurations necessary to guarantee
Grade 2 certification
Active
Contact ID
<=25h
1
If the digital communicator is not active,
at least the telephone sounder or email
transmission must be configured correctly
Valorised
Value before date of activating the system
(must be before current date)
5.5.20 Generic events
Vedo10 x: from 1 to 20 / Vedo34 x: from 1 to 32 / Vedo68 x: from 1 to 48 / Vedo200 x: from 1 to 48
CODE TYPE
Configurations necessary to guarantee
Grade 2 certification
1.1.1.30.x.2
Event
*
1.1.1.30.x.5
Activation voice message
Active for at least one phone
1.1.1.30.x.6
Reset voice message
Active for at least one phone
1.1.1.30.x.9
Send activation email
Active for at least one email
1.1.1.30.x.19
Send address
* Selected
* If the digital communicator is not active, the following events must be signalled:
- Robbery Alarm
- Burglar Alarm
- H24 Alarm
- Sabotage
- Expansion bus
- No network
- Radio sensor battery low
- Radio siren battery low
- Auto-activation failed
- Failed activation fault
- Zone fault
- Robbery zone fault
- Motion sensor jamming fault
- Regular PSTN and email communication
- Regular GSM communication
Of course it must also be completed by sending the respective voice message.
Indices
x: from 1 to 9
Indices
Parameters
1.1.1.22.x.19
Request assistance
1.1.1.22.x.20
1.1.1.22.x.21
1.1.1.22.x.23
Change Pin
Reset control panel
Fault management
1.1.1.22.x.26
Programme from PC
1.1.1.22.x.42
1.1.1.22.x.44
Codes menu
FW Update
1.1.1.22.x.45
Reset alarms L3
Configurations necessary to guarantee
Grade 2 certification
Active for at least one type of user (x
enab. inst.) and one type of installer (x
enab. manuf.)
Active only for installers
Active at least for manufacturer
Active for all
Active at least for installer and
manufacturer
Active for all
Only for manufacturer
Selected
Deselected for Patrol
Parameters
55
5.5.21 Detailed events
x: from 1 to 8 y: from 1 to 8
Indices
Parameters
1.1.1.31.x.3
1.1.1.31.x.4
communicator telephones
Areas
Configurations necessary to guarantee
Grade 2 certification
At least one selected
At least one selected
DETAILED EVENTS FLAGS
Indices
Parameters
1.1.1.31.x.6.y.2
Zone Exclusion
1.1.1.31.x.6.y.3
Zone Isolation
1.1.1.31.x.6.y.4
1.1.1.31.x.6.y.5
1.1.1.31.x.6.y.6
1.1.1.31.x.6.y.7
1.1.1.31.x.6.y.8
Total ON
Partial 1 ON
Partial 2 ON
Effective activation
Deactivated
1.1.1.31.x.6.y.10
Burglar Alarm
1.1.1.31.x.6.y.11
24H Alarm
1.1.1.31.x.6.y.12
Fire Alarm
1.1.1.31.x.6.y.13
Panic Alarm
1.1.1.31.x.6.y.14
Robbery Alarm
1.1.1.31.x.6.y.15
Flood alarm
1.1.1.31.x.6.y.16
Gas Alarm
1.1.1.31.x.6.y.17
Medical Alarm
1.1.1.31.x.6.y.18
Zones Sabotage Tamper
1.1.1.31.x.6.y.19
Siren tamper
1.1.1.31.x.6.y.20
Radio device jamming
1.1.1.31.x.6.y.21
Tamper App
1.1.1.31.x.6.y.22
Tamper free 1
1.1.1.31.x.6.y.23
Tamper free 2
1.1.1.31.x.6.y.24
Tamper free 3
1.1.1.31.x.6.y.25
Tamper free 4
1.1.1.31.x.6.y.26
Bus I/O expansions tamper
1.1.1.31.x.6.y.27
BUS keypad tamper
1.1.1.31.x.6.y.28
RFID tamper
1.1.1.31.x.6.y.29
Safetouch tamper
1.1.1.31.x.6.y.30
1.1.1.31.x.6.y.31
1.1.1.31.x.6.y.32
Touch Tamper
BUS power supply station or
isolator tamper
BUS radio concentrator
tamper
1.1.1.31.x.6.y.33
Bus siren tamper
1.1.1.31.x.6.y.34
Alarm communication device
tamper
1.1.1.31.x.6.y.35
IP expansion tamper
1.1.1.31.x.6.y.36
IP video expansion tamper
1.1.1.31.x.6.y.37
Tamper bus free 0
1.1.1.31.x.6.y.38
Tamper bus free 1
1.1.1.31.x.6.y.39
Tamper bus free 2
1.1.1.31.x.6.y.40
Tamper bus free 3
1.1.1.31.x.6.y.41
Tamper bus free 4
1.1.1.31.x.6.y.42
Remote communications
tamper
1.1.1.31.x.6.y.43
GSM concentrator jamming
1.1.1.31.x.6.y.44
False code
1.1.1.31.x.6.y.45
Zone Fault
1.1.1.31.x.6.y.46
Siren fuse fault
56
Configurations necessary to guarantee
Grade 2 certification
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - activation: Selected
* - activation: Selected
* - activation: Selected
* - activation: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
Indices
Parameters
1.1.1.31.x.6.y.47
Radio control fault
1.1.1.31.x.6.y.48
Power supply unit fuse fault
1.1.1.31.x.6.y.49
Power supply unit battery
fault
1.1.1.31.x.6.y.50
Radio output battery fault
1.1.1.31.x.6.y.51
Bus siren battery fault
1.1.1.31.x.6.y.52
No power supply unit network
1.1.1.31.x.6.y.53
Radio zone battery fault
1.1.1.31.x.6.y.54
Radio control battery fault
1.1.1.31.x.6.y.55
Input voltage level fault
1.1.1.31.x.6.y.56
Output voltage level fault
1.1.1.31.x.6.y.57
Zones RX monitoring
1.1.1.31.x.6.y.58
Outputs RX monitoring
1.1.1.31.x.6.y.59
Output fault
1.1.1.31.x.6.y.60
Camera fault
1.1.1.31.x.6.y.61
No GSM/GPRS coverage
1.1.1.31.x.6.y.62
Telephone line fault
1.1.1.31.x.6.y.63
Failed communication fault
1.1.1.31.x.6.y.64
Robbery zone fault
1.1.1.31.x.6.y.65
Failed activation fault
1.1.1.31.x.6.y.66
IP Expansion fault on bus
1.1.1.31.x.6.y.67
Motion sensor jamming fault
1.1.1.31.x.6.y.68
Fault free 5
1.1.1.31.x.6.y.69
Fault free 6
1.1.1.31.x.6.y.70
I/O expansion Bus Fault
1.1.1.31.x.6.y.71
Keypad Bus Fault
1.1.1.31.x.6.y.72
Reader Bus Fault
1.1.1.31.x.6.y.73
Safe Touch Bus Fault
1.1.1.31.x.6.y.74
Touch Bus Fault
1.1.1.31.x.6.y.75
Isolator Power Supply Unit
Bus Fault
1.1.1.31.x.6.y.76
Radio Concentrator Bus Fault
1.1.1.31.x.6.y.77
Siren Bus Fault
1.1.1.31.x.6.y.78
Alarm Communication Device
Bus Fault
1.1.1.31.x.6.y.79
IP Expansion Bus Fault
1.1.1.31.x.6.y.80
IP Video Expansion Bus Fault
1.1.1.31.x.6.y.81
Fault free bus 0
1.1.1.31.x.6.y.82
Fault free bus 1
1.1.1.31.x.6.y.83
Fault free bus 2
1.1.1.31.x.6.y.84
Fault free bus 3
1.1.1.31.x.6.y.85
Fault free bus 4
1.1.1.31.x.6.y.86
Control Panel Battery Fault
1.1.1.31.x.6.y.87
Control Panel Power Supply
Mains Outage
1.1.1.31.x.6.y.88
Control panel pstn fault
1.1.1.31.x.6.y.89
Control panel GSM fault
1.1.1.31.x.6.y.90
Control panel IP fault
1.1.1.31.x.6.y.91
Control panel voice synthesis
fault
1.1.1.31.x.6.y.92
Control panel Intercom fault
1.1.1.31.x.6.y.93
1.1.1.31.x.6.y.94
Control panel home
automation expansion fault
Auxiliary power supply fuse
fault
Configurations necessary to guarantee
Grade 2 certification
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
* - activation: Selected
* - reset: Selected
Configurations necessary to guarantee
Grade 2 certification
* - activation: Selected
1.1.1.31.x.6.y.95
Bus power supply fuse fault
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.96
Siren power supply fuse fault
* - reset: Selected
Control panel power supply
* - activation: Selected
1.1.1.31.x.6.y.97
unit fault
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.98
Control panel bus fault
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.99
Telephone line fault
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.100 No GSM network
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.101 No GPRS network
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.102 Date lost
* - reset: Selected
1.1.1.31.x.6.y.108 L2 forced ON
* - activation: Selected
1.1.1.31.x.6.y.109 L3 forced ON
* - activation: Selected
1.1.1.31.x.6.y.116 Timed activation error
* - activation: Selected
* - activation: Selected
1.1.1.31.x.6.y.119 Technical programming
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.120 Control panel in service
* - reset: Selected
1.1.1.31.x.6.y.126 Change date and time
* - activation: Selected
* - activation: Selected
1.1.1.31.x.6.y.127 Change site data
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.140 Lock RFID
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.143 Lock Web
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.144 Lock PC
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.145 Lock SMS
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.146 Lock voice
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.147 Home autom. lock
* - reset: Selected
1.1.1.31.x.6.y.151 Activation action
* - activation: Selected
1.1.1.31.x.6.y.152 Burglar Alarm Action
* - activation: Selected
1.1.1.31.x.6.y.153 24H Alarm Action
* - activation: Selected
1.1.1.31.x.6.y.154 Fire Alarm Action
* - activation: Selected
1.1.1.31.x.6.y.155 Panic Alarm Action
* - activation: Selected
1.1.1.31.x.6.y.156 Robbery Alarm Action
* - activation: Selected
1.1.1.31.x.6.y.157 Flood Alarm Action
* - activation: Selected
1.1.1.31.x.6.y.158 Gas Alarm Action
* - activation: Selected
1.1.1.31.x.6.y.159 Medical Alarm Action
* - activation: Selected
1.1.1.31.x.6.y.177 Zone exclusion command
* - activation: Selected
1.1.1.31.x.6.y.178 Zone inclusion command
* - activation: Selected
1.1.1.31.x.6.y.179 Zone isolation command
* - activation: Selected
1.1.1.31.x.6.y.180 Zone activation command
* - activation: Selected
* - activation: Selected
1.1.1.31.x.6.y.183 Safe Touch lock
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.188 Touch lock
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.200 App locked
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.205 Touch lock
* - reset: Selected
Digital communicator manual * - activation: Selected
1.1.1.31.x.6.y.208
test
* - reset: Selected
* - activation: Selected
1.1.1.31.x.6.y.216 Zone Restriction
* - reset: Selected
Communicator parameters
1.1.1.31.x.6.y.219
* - activation: Selected
changed
* - activation: Selected
1.1.1.31.x.6.y.220 Updating firmware
* - reset: Selected
* Only for the digital communicator and email columns
Indices
Parameters
5.5.22 Service voice messages
x: from 1 to 6
Indices
Parameters
1.1.1.36.x.1
Text
Configurations necessary to guarantee
Grade 2 certification
The system address field must be
completed
5.5.23 Timer Types
Vedo10 x: from 1 to 4 / Vedo34 x: from 1 to 8 / Vedo68 x: from 1 to 8 / Vedo200 x: from 1 to 32
Vedo10 y: from 1 to 4 / Vedo34 y: from 1 to 16 / Vedo68 y: from 1 to 16 / Vedo200 y: from 1 to 32
TIMER TYPE SCHEDULES
Configurations necessary to guarantee
Grade 2 certification
1.1.1.37.x.2.y.1
Time ON1
Timer 4 completed*
1.1.1.37.x.2.y.2
Time OFF1
Timer 4 completed*
* Timer 4 completed and linked with the two regular general events
Indices
Parameters
5.5.24 Timer Model
Vedo10/Vedo34/Vedo68 x: from 1 to 30 / Vedo200 x: from 1 to 60
Indices
Parameters
1.1.1.39.x.1
1.1.1.39.x.2
1.1.1.39.x.3
1.1.1.39.x.4
1.1.1.39.x.5
1.1.1.39.x.6
1.1.1.39.x.7
1.1.1.39.x.8
1.1.1.39.x.9
1.1.1.39.x.10
Start day of week
End day of week
Start month
End month
Start date
Selection
End date
Start year
End year
Timer Type
Configurations necessary to guarantee
Grade 2 certification
Line 1 '*'
Line 1 '*'
Line 1 '*'
Line 1 '*'
Line 1 '*'
First line selected
Line 1 '*'
Line 1 '*'
Line 1 '*'
Line 1 'Timer 4'
5.5.25 System Parameters
Indices
Parameters
1.1.1.42.1.2
1.1.1.42.1.3
1.1.1.42.1.4
1.1.1.42.1.5
1.1.1.42.1.14
1.1.1.42.1.15
1.1.1.42.1.16
1.1.1.42.1.17
1.1.1.42.1.18
1.1.1.42.1.19
Customer Name
System Address
Network alarm delay
Battery alarm delay
Code errors
Reactivation time
Alarm Cycles
Fault Cycles
Unlimited Alarm Cycles
Unlimited fault cycles
Device locked for incorrect
code
Activation with monitoring
fault
Forcing level 3 faults
Forcing level 3 sabotage
Installer always active
IP card enable
1.1.1.42.1.20
1.1.1.42.1.23
1.1.1.42.1.24
1.1.1.42.1.25
1.1.1.42.1.30
1.1.1.42.1.32
1.1.1.42.1.33
Audio control enable
1.1.1.42.1.34
1.1.1.42.1.37
1.1.1.42.1.38
GSM card enable
PSTN enable (on board)
Failed activation fault enable
Enable test for fault and
zones sabotage
1.1.1.42.1.39
Configurations necessary to guarantee
Grade 2 certification
Fill in the field
Fill in the field
Max 60 seconds
Max 5 minutes
<=10
Minimum 2 minutes
Unlimited
Unlimited
Selected
Selected
Selected
Selected
Selected
Selected
Deselected
At least one active of PSTN, GSM and IP
Active if digital communicator or IP card is
not enabled
At least one active of PSTN, GSM and IP
At least one active of PSTN, GSM and IP
Selected
Deselected
5.5.26 Events to be saved
x: from 1 to 2
Indices
Parameters
1.1.1.43.x.2
1.1.1.43.x.3
1.1.1.43.x.4
1.1.1.43.x.5
1.1.1.43.x.6
1.1.1.43.x.7
1.1.1.43.x.8
1.1.1.43.x.10
1.1.1.43.x.11
1.1.1.43.x.12
1.1.1.43.x.13
1.1.1.43.x.14
1.1.1.43.x.15
1.1.1.43.x.16
1.1.1.43.x.17
1.1.1.43.x.18
1.1.1.43.x.19
1.1.1.43.x.20
1.1.1.43.x.21
1.1.1.43.x.26
1.1.1.43.x.27
1.1.1.43.x.28
1.1.1.43.x.29
1.1.1.43.x.30
Zone Exclusion
Zone Isolation
Total ON
Partial 1 ON
Partial 2 ON
Effective activation
Deactivated
Burglar Alarm
24H Alarm
Fire Alarm
Panic Alarm
Robbery Alarm
Flood alarm
Gas Alarm
Medical Alarm
Zones Sabotage Tamper
Siren tamper
Radio device jamming
Tamper App
Bus I/O expansions tamper
Bus keypad tamper
RFID tamper
Safetouch tamper
Touch Tamper
Bus power supply station or
isolator tamper
Bus radio concentrator
tamper
Bus siren tamper
Alarm communication device
tamper
IP expansion tamper
IP video expansion tamper
Remote communications
tamper
GSM concentrator jamming
False code
Zone Fault
Siren fuse fault
Radio control fault
1.1.1.43.x.31
1.1.1.43.x.32
1.1.1.43.x.33
1.1.1.43.x.34
1.1.1.43.x.35
1.1.1.43.x.36
1.1.1.43.x.42
1.1.1.43.x.43
1.1.1.43.x.44
1.1.1.43.x.45
1.1.1.43.x.46
1.1.1.43.x.47
Configurations necessary to guarantee
Grade 2 certification
Selected
Selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
57
Indices
Parameters
1.1.1.43.x.48
Power supply unit fuse fault
Power supply unit battery
fault
Radio output battery fault
Bus siren battery fault
No power supply unit network
Radio zone battery fault
Radio control battery fault
Input voltage level fault
Output voltage level fault
Zones RX monitoring
Outputs RX monitoring
Output fault
Camera fault
No GSM/GPRS coverage
Telephone line fault
Failed communication fault
Robbery zone fault
Failed activation fault
IP Expansion fault on bus
Motion sensor jamming fault
I/O expansion Bus Fault
Keypad Bus Fault
Reader Bus Fault
Safe Touch Bus Fault
Touch Bus Fault
Isolator Power Supply Unit
Bus Fault
Radio Concentrator Bus Fault
Siren Bus Fault
Alarm Communication Device
Bus Fault
IP Expansion Bus Fault
IP Video Expansion Bus Fault
Control Panel Battery Fault
Control Panel Power Supply
Mains Outage
Control panel pstn fault
Control panel GSM fault
Control panel IP fault
Control panel voice synthesis
fault
Auxiliary power supply fuse
fault
Bus power supply fuse fault
Siren power supply fuse fault
Control panel power supply
unit fault
Control panel bus fault
Telephone line fault
No GSM network
No GPRS network
Date lost
Inactivity
Zone test
User logged in
L2 forced ON
L3 forced ON
Negligence
Alarm log
Reset alarms
Stop alarms
Stop telephone calls
Timed activation error
Technical programming
Control panel in service
Reset system alarms
Stop system alarms
Stop system telephone calls
Change date and time
Change site data
Telephone call failed
Outgoing phone
communication
Digital communicator
periodic test
Lock keypad
Lock RFID
Lock Web
Lock PC
Lock SMS
Lock voice
Activation action
Burglar Alarm Action
24H Alarm Action
Fire Alarm Action
Panic Alarm Action
Robbery Alarm Action
Flood Alarm Action
1.1.1.43.x.49
1.1.1.43.x.50
1.1.1.43.x.51
1.1.1.43.x.52
1.1.1.43.x.53
1.1.1.43.x.54
1.1.1.43.x.55
1.1.1.43.x.56
1.1.1.43.x.57
1.1.1.43.x.58
1.1.1.43.x.59
1.1.1.43.x.60
1.1.1.43.x.61
1.1.1.43.x.62
1.1.1.43.x.63
1.1.1.43.x.64
1.1.1.43.x.65
1.1.1.43.x.66
1.1.1.43.x.67
1.1.1.43.x.70
1.1.1.43.x.71
1.1.1.43.x.72
1.1.1.43.x.73
1.1.1.43.x.74
1.1.1.43.x.75
1.1.1.43.x.76
1.1.1.43.x.77
1.1.1.43.x.78
1.1.1.43.x.79
1.1.1.43.x.80
1.1.1.43.x.86
1.1.1.43.x.87
1.1.1.43.x.88
1.1.1.43.x.89
1.1.1.43.x.90
1.1.1.43.x.91
1.1.1.43.x.94
1.1.1.43.x.95
1.1.1.43.x.96
1.1.1.43.x.97
1.1.1.43.x.98
1.1.1.43.x.99
1.1.1.43.x.100
1.1.1.43.x.101
1.1.1.43.x.102
1.1.1.43.x.103
1.1.1.43.x.106
1.1.1.43.x.107
1.1.1.43.x.108
1.1.1.43.x.109
1.1.1.43.x.110
1.1.1.43.x.111
1.1.1.43.x.113
1.1.1.43.x.114
1.1.1.43.x.115
1.1.1.43.x.116
1.1.1.43.x.119
1.1.1.43.x.120
1.1.1.43.x.123
1.1.1.43.x.124
1.1.1.43.x.125
1.1.1.43.x.126
1.1.1.43.x.127
1.1.1.43.x.130
1.1.1.43.x.131
1.1.1.43.x.132
1.1.1.43.x.135
1.1.1.43.x.140
1.1.1.43.x.143
1.1.1.43.x.144
1.1.1.43.x.145
1.1.1.43.x.146
1.1.1.43.x.151
1.1.1.43.x.152
1.1.1.43.x.153
1.1.1.43.x.154
1.1.1.43.x.155
1.1.1.43.x.156
1.1.1.43.x.157
58
Configurations necessary to guarantee
Grade 2 certification
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Only set selected
Selected
Only set selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Indices
Parameters
1.1.1.43.x.158
1.1.1.43.x.159
1.1.1.43.x.160
1.1.1.43.x.161
1.1.1.43.x.162
1.1.1.43.x.163
1.1.1.43.x.164
Gas Alarm Action
Medical Alarm Action
Event 1 key command
Event 2 key command
Extraordinary command
Stop alarms command
Reset alarms command
Reset telephone calls
command
Reset Control panel
command
Request support command
Authorise installer command
Confirm code command
Confirm key command
Login upgrade command
Authorise manufacturer
command
Zone exclusion command
Zone inclusion command
Zone isolation command
Zone activation command
Safe Touch lock
Touch lock
Added code command
Removed code command
Changed code command
Added key command
Removed key command
Changed key command
Database reset command
App locked
Touch lock
Digital communicator manual
test
Sending SMS
Sending email
Sending MMS
Activation lock cause
Sending telephone call
Zone Restricted
NAK digital communication
1.1.1.43.x.165
1.1.1.43.x.166
1.1.1.43.x.167
1.1.1.43.x.168
1.1.1.43.x.169
1.1.1.43.x.170
1.1.1.43.x.171
1.1.1.43.x.172
1.1.1.43.x.177
1.1.1.43.x.178
1.1.1.43.x.179
1.1.1.43.x.180
1.1.1.43.x.183
1.1.1.43.x.188
1.1.1.43.x.191
1.1.1.43.x.192
1.1.1.43.x.193
1.1.1.43.x.194
1.1.1.43.x.195
1.1.1.43.x.196
1.1.1.43.x.197
1.1.1.43.x.200
1.1.1.43.x.205
1.1.1.43.x.208
1.1.1.43.x.209
1.1.1.43.x.210
1.1.1.43.x.211
1.1.1.43.x.213
1.1.1.43.x.214
1.1.1.43.x.216
1.1.1.43.x.217
Selected
1.1.1.43.x.218
Selected
Selected
1.1.1.43.x.219
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Only set selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
1.1.1.43.x.220
1.1.1.43.x.221
Configurations necessary to guarantee
Grade 2 certification
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Selected
Selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Selected
Selected
Selected
Only set selected
Only set selected
Only set selected
Only set selected
Only set selected
Selected
Only set selected
Digital communication OK
Only set selected
Communicator parameters
changed
Updating firmware
NAK email communication
Only set selected
Selected
Only set selected
5.6 CONFIGURATIONS NECESSARY TO
GUARANTEE INCERT CERTIFICATION
5.7 OFFICIAL SYMBOL CONVENTIONS FOR ANTIINTRUSION SYSTEMS
This chapter provides indications on the configuration parameters
which, if varied, could lower the safety level of the system, and the
configurations necessary to guarantee I&HAS certification.
Magnetic contact detector
Inertial vibration detector
For further details on programming and configuration, consult
the programming technical manual, which can be downloaded
from the website pro.comelitgroup.com/
To guarantee Incert certification, ALL configurations
required for Grade 2 certification (see "5.2 Configurations
necessary to guarantee grade 2 certification according to
EN50131-1" on page 53) must be observed, except for
the settings listed in the following tables.
5.6.1 Code type
Indices
Parameters
1.1.1.22.x.45
Reset allarmi L3
5.6.2 System parameters
Indices
Parameters
1.1.1.42.1.25
Forcing level 2 sabotage
Microphone glass break detector
Microphone detector
Passive infrared detector
Configurations necessary to
guarantee INCERT certification
Selezionato
Deselezionato per produttore
Microwave detector
Control panel
Configurations necessary to
guarantee INCERT certification
Deselected
Control component with electronic key
Message dispatcher on dedicated line
Message dispatcher on switched line
Self-powered audible alarm device
Audible alarm device
Illuminating alarm device
5.8 SHIELDED CABLE CONDUCTOR RESISTANCE
TABLE
SHIELDED
ALARM CABLE
FORMATION
CONDUCTOR
DIAMETER [mm]
MINIMUM
RESISTANCE
OHM PER 1
METRE
MINIMUM
RESISTANCE
OHM PER 100
METRES
n X 0.22 mm2
0.50
0.085
8.5
n X 0.50 mm2
0.80
0.032
3.2
n X 0.75 mm2
0.90
0.026
2.6
n X 1 mm2
1
0.020
2
n X 1.5 mm2
1.28
0.013
1.3
n X 2.5 mm2
1.65
0.008
0.82
5.8.1 Input and signal connections
For the bus signals (A and B) you can use a conductor with
section of 0.22 mm².
The resistance shown in the table refers to a single conductor,
so if, for example, you want to evaluate the additional resistance
introduced by the cable for a run of 100m, you need to double
the length. You therefore need to consider 200m total length of
conductor (100m outward to the point and 100m return from
the point).
In the case of a contact connected to the control panel by a
run of 100m of cable with “n” structure for 0.22 mm², the total
resistance added by the cable becomes 17 ohm. For connection
to an alarm input, 17 ohm does not generally compromise the
performance of the system.
59
5.8.2 Power supply connections
In the above circumstances, the resistance can be overlooked
in the majority of cases. More care must be taken, however, if
the cable has to carry power: in this case, the resistance could
cause a significant drop for the purposes of correct operation of
the device you intend to power.
Supposing we have a run of 100m of cable powering a device
with consumption of 100mA. Using Ohm's Law 1, let us analyse
the voltage drops for a range of sections:
0.22 mm² : V=R*I = 17*0.1 = 1.7V
0.50 mm² : V=R*I = 6.4*0.1 = 0.64V
0.75 mm² : V=R*I = 5.2*0.1 = 0.52V
1 mm² : V=R*I = 4*0.1 = 0.4V
This is why it is important to size the power supply conductors
correctly.
V = R * I. The estimated drop in Volts is equal to the total resistance
of the circuit, expressed in Ohms, multiplied by the circulating
current I, expressed in amps.
5.9 DATA NETWORK CONNECTION CABLE
To connect the IP module from the Vedo control panel to a data
network, you need to go through a hub or a network switch. The
control panel will be connected by means of a network cable in
straight configuration. In many cases, it will be possible to buy a
standard cable of suitable length, but when this is not possible,
you will need to make the connection autonomously.
This is done using UTP CAT5 cable or higher.
The cable will be terminated at both ends with RJ45 plugs with
the aid of a specific crimp tool. Both RJ45 plugs must be wired
in the same sequence as shown in the figure.
The conductor colours shown in the figure must be rigorously
observed. Non-conformance with the colours may cause the
connection to work intermittently or not at all.
Procedure:
1. Remove about 5 cm of jacket from the cable so as to make
the 4 pairs of wire accessible
2. Separate the conductors in the pairs
3. Stretch the conductors out so as to straighten them, and
place them in the order shown in the figure
4. Adjust the length of the conductors to about 12mm
5. Insert the conductors as shown in the figure (the connector
is illustrated as seen from the side)
CERTIFIED MANAGEMENT SYSTEMS
w w w.comelitgroup.com
Via Don Arrigoni, 5 - 24020 Rovetta (BG) - Italy
60
1ª edizione 05/2017
cod. 2G40001679
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement