eCONNECT_PDU_METERED_DATASHEET P2, L2 Locking
PRODUCT DATA SHEET
Protecting your technology investment.
Metered eConnect® PDU
For use in data centers and
ADVANTAGES
equipment room racks and
Input Current Reading – Provides input
current reading for initial installation and
proper balanced operation.
cabinets, where deployment
of networked PDUs is not an
option. Local display provides
High Temperature Rating – Designed
to withstand ambient air temperatures up to
149°F (65°C)
easy reading of input current
to help with initial installation
and proper balanced operation.
Preinstalled Option – Eases installation
and deployment
Locking Outlets – Patented Click Secure
Locking Outlets prevent accidental power loss
KEY FEATURES
• Withstands hot aisle temperatures of highdensity data center environments with an
ambient temperature rating of 149°F (65°C)
10
Click
Secure
Technology
• Provides easy reading of input current across
phases through the use of local LED display
• Protects equipment from current spikes and
nuisance tripping with highly reliable, heat
tolerant 100%-rated magnetic hydraulic
breakers
• Prevents accidental disconnections through
optional locking outlets, which ensure straight
cords stay securely fastened to IEC outlets
• Vertical PDU installs quickly with universal,
tool-less mounting hardware or available
shipped preinstalled in CPI cabinets
• Offers a broad range of standard configurations,
combining different power inlets/plugs and
outlets for configurations that match facility
requirements
• Fits in the zero U space at the side of cabinets
and does not block access to equipment
mounting rails or exhaust airflow
SPECIFICATIONS
Description:
Use:
Power Input:
Power Output:
Power Inlet/Plugs:
Power Cord:
Power Outlet
Receptacles:
Circuit Protection:
Meter Specifications:
Grounding/Bonding:
Finish:
Single-input, vertical rack-mount PDUs
For indoor use only, in environmentally controlled areas, may not be used outdoors or in harsh
environments
Specific to PDU, alternating current, 50/60 Hz (see ordering table)
Stated as voltage range, maximum current, load and inlet/plug type
Specific to PDU, limited by circuit breakers (see ordering table)
NEMA or IEC power inlet/plug, specific to PDU (see order tables)
Standard attached cord is 10'L (3 m), not rated for plenum use
Order cord separately for models with IEC C20 inlet
NEMA 5-15/20R, IEC C13 and/or IEC C19 Outlets, specific to PDU (see order table)
Includes power cord retention tethers to secure straight power cords at all non-locking outlets
Optional Click Secure Locking IEC Outlets
UL 489 listed, single-pole or two-pole, hydraulic-magnetic breakers to resist effects of
high temperatures
Low-profile design minimizes size of breaker boxes on PDUs and prevents accidental discharge
Number and type specific to PDU (see table)
Display: 4-digit LED, displays input current for all phases; typical accuracy of +/-2%
All PDUs have a grounded power inlet/plug and an external ground connection with a
threaded M5 attachment point
Includes a grounding kit with a 12”L (300 mm), 12 AWG stranded copper wire jumper, and drop
in attachment hardware for F-Series TeraFrame® Gen 3 Cabinet, N-Series TeraFrame Gen 3
Cabinet or GF-Series GlobalFrame® Gen 2 Cabinet
Black only
Global Availability
US & Canada
+1-800-834-4969
Toronto, Ontario, Canada
+905-850-7770
chatsworth.com
[email protected]
Latin America
+52-55-5203-7525
Toll Free within Mexico
01-800-01-7592
chatsworth.com.co
Europe
+44-1628-524-834
chatsworth.com
Middle East & Africa
Dubai, UAE
+971-4-2602125
chatsworth.ae
Asia Pacific
+86 21 6880-0266
chatsworth.com.cn
PRODUCT DATA SHEET
Metered eConnect® PDU
SPECIFICATIONS
Reliable Load Balancing
Chatsworth Products' (CPI) Metered eConnect® Power Distribution Units (PDUs)
provide input current readings for accurate phase load balancing. Whether you
need to connect a few pieces of equipment or support high-density computing
with multiple blade servers in every cabinet, Metered eConnect PDUs provide
simple, reliable power distribution to equipment in your racks and cabinets.
UL, CSA C22.2 (Canada), CE (EU), FCC Part 15, Class A, EN
55022, RoHS Compliant
Temperature: 32°F – 149°F (0°C – 65°C) at Input Power Rating
(kW)
Operating Conditions:
Relative Humidity: 5% – 95%, non-condensing
Elevation: 0 – 10,000 feet (0 – 3,000 meters)
Temperature: -13°F – 149°F (-25°C – 65°C)
Storage/Non-operating
Relative Humidity: 5% – 95%, non-condensing
Conditions:
Elevation: 0 – 50,000 feet (0 – 15,000 m)
Includes two tool-less mounting shoulder washers and
installation hardware
The PDU can be installed with the inlet power cord near the
top or bottom of the cabinet
Washers can be installed spaced 64.75” (1645 mm) or 61.25”
(1556 mm) apart to match most rack/cabinet mounting
Installation Hardware: brackets
The washers can also be offset 2” (51 mm) to provide
additional space at the top or bottom of the cabinet for the
power cord in shorter cabinets
PDUs that are 75”H (1905 mm) must be placed in 45U or taller
cabinets
Not included with PDU, order separately
Rack/Cabinet
Mounting Brackets:
Included with most CPI Cabinets, check cabinet specifications
3-year standard with advanced replacement. Extended
Warranty:
Warranties up to 5 years available.
Certifications:
Choose a Metered eConnect PDU for reliable power distribution in high-density
applications that require input current reading for phase load balancing on threephase PDUs or A/B power load balancing with multiple PDUs. CPI’s Metered
eConnect PDUs feature locking IEC outlets, universal tool-less mounting and can
be confidently deployed in cabinets with CPI Vertical Exhaust Ducts or in hot aisle
containment applications with ambient air temperatures up to 149°F (65°C).
No Accidental Disconnections
Vertical eConnect PDUs with IEC outlets are available with Click Secure Locking
Outlets, which prevent accidental disconnections. This patented feature securely
fastens standard straight cords to the PDU, protecting your power from sudden
disruptions. PDUs without locking outlets are also available.
eConnect PDUs are suitable for global use. Most PDUs include an attached 10’L
(3 m) power cord with an IEC or NEMA style plug rated for 100-125 Volt, 200-240
Volt or 380-415 Volt input, and some models have an IEC C20 inlet, allowing the
power cords to be ordered separately to match specific site requirements. See
reverse for product selection, or contact CPI Technical Support for configuration
assistance.
COMPATIBLE WITH
• CPI Cabinet Systems
• CPI Rack Systems
RELATED PRODUCTS
• Input Power Cords
• Mounting Brackets
Click
Secure
Technology
Click Secure Locking Outlets!
This patented feature securely fastens straight equipment power cords to the PDU, protecting your
power from sudden disruptions. Simply insert the equipment plug into locking outlet, easily clicking
it into the locked position. To release, lightly squeeze the locking mechanism. Locking outlets
secure cords but still maintain the PDU’s space-saving, low-profile design.
Insert - Click!
Squeeze
locking
mechanism
Release
Plug
2
Chatsworth Products
PRODUCT DATA SHEET
Metered eConnect® PDU
ORDERING INFORMATION
Metered Vertical eConnect PDUs
Part Number
Outlet
Input
Amp
kW*
Output
Plug
Dimensions - in (mm)
Breakers
(Hydraulic Magnetic)
Outlets
H***
W
D
(24) C13, (6) C19
70.5 (1791)
2.2 (56)
2.2 (56)
100-240 Volt, Single-Phase Input - Worldwide
L2-1A1E3
20
1.9
C20 Inlet**
1 x 2P 20A
120 Volt, Single-Phase Input - North America Models
P2-1C0A5*****
20
1.9
L5-20P
1 x 2P 20A
(24) 5-20R
70.5 (1791)
2.2 (56)
2.2 (56)
P2-1D0A5*****
30
2.8
L5-30P
2 x 2P 20A
(24) 5-20R
70.5 (1791)
2.2 (56)
2.2 (56)
P2-1D0B5*****
30
2.8
L5-30P
2 x 2P 20A
(36) 5-20R
70.5 (1791)
2.2 (56)
2.2 (56)
70.5 (1791)
2.2 (56)
2.2 (56)
120-208 Volt, Single-Phase Input - North America Models
L2-1K0K4
30
4.9
L14-30P
2 x 2P 20A
(24) C13, (6) C19, (6) 5-20R
208 Volt, Single-Phase Input - North America Models
L2-1E0E3
20
3.3
L6-20P
1 x 2P 20A
(24) C13, (6) C19
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1F0G3
30
4.9
L6-30P
2 x 2P 20A
(30) C13, (6) C19
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1F0B1
30
4.9
L6-30P
2 x 2P 20A
(36) C13
70.5 (1791)
2.2 (56)
2.2 (56)
120/208 Volt, Three-Phase Input - North America Models
L2-1N0K4
20
5.7
L21-20P
3 x 2P 20A
(24) C13, (6) C19, (6) 5-20R
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1N0G3
20
5.7
L21-20P
3 x 2P 20A
(30) C13, (6) C19
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1N0B1
20
5.7
L21-20P
3 x 2P 20A
(36) C13
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1P0K4
30
8.6
L21-30P
3 x 2P 20A
(24) C13, (6) C19, (6) 5-20R
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1P0G3
30
8.6
L21-30P
3 x 2P 20A
(30) C13, (6) C19
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1P0B1
30
8.6
L21-30P
3 x 2P 20A
(36) C13
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1M0B1
30
8.6
L15-30P
3 x 2P 20A
(36) C13
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1M0G3
30
8.6
L15-30P
3 x 2P 20A
(30) C13, (6) C19
70.5 (1791)
2.2 (56)
2.2 (56)
208 Volt, Three-Phase Input- North America Models
L2-1T0F3
50
9.9
CS8365C
3 x 2P 20A
(24) C13, (12) C19
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1T0G3
50
9.9
CS8365C
3 x 2P 20A
(30) C13, (6) C19
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1T0B1
50
9.9
CS8365C
3 x 2P 20A
(36) C13
70.5 (1791)
2.2 (56)
2.2 (56)
L2-3U0H3
50
14.3
CS8365C
6 x 2P 20A
(36) C13, (6) C19
75.0 (1905)
2.7 (69)
2.2 (56)
L2-3U0F3
50
14.3
CS8365C
6 x 2P 20A
(24) C13, (12) C19
75.0 (1905)
2.7 (69)
2.2 (56)
L2-3V0F3
60
17.2
IEC 60A 3P+E
6 x 2P 20A
(24) C13, (12) C19
75.0 (1905)
2.7 (69)
2.2 (56)
L2-2R0H3
30
17.2
L22-30P
6 x 1P 20A
(36) C13, (6) C19
72.0 (1829)
2.35 (60)
2.2 (56)
L2-2R0F3
30
17.2
L22-30P
6 x 1P 20A
(24) C13, (12) C19
72.0 (1829)
2.35 (60)
2.2 (56)
240/415 Volt, Three-Phase Input - North America Models
Notes: Order mounting brackets separately. On single-phase PDUs, output voltage equals input voltage. On three-phase PDUs, 208 VAC nominal output through C13 and C19 outlets; 120 VAC nominal output
through NEMA 5-20R outlets.
Amperage: 20A within North America and 16A outside of North America.
* For kW column, all values are derated calculations per UL for use in North America. The Input Amp column lists the maximum rated value of the input plug/inlet and circuit breaker rating. UL/NEC
regulatory code requires current ratings on product labels to be derated to 80% of the maximum rated values (for example: 20 Amp = 16 Amp on UL product label). For the Input kW column, all values are derated
calculations per UL for use in North America.
** Order power cord separately for PDU with C20 input.
*** PDUs that are 72”H (1829 mm) must be placed in 44U or taller CPI cabinets. PDUs that are 75”H (1905 mm) must be placed in 45U or taller CPI cabinets.
**** Capacity when used at 230V with a 16A power cord. Actual capacity will vary if connected to lower voltage or to a lower amperage input plug.
*****PDUs have non-locking outlets.
1
3
Chatsworth Products
PRODUCT DATA SHEET
Metered eConnect® PDU
ORDERING INFORMATION
Metered Vertical eConnect PDUs - Outside North America
Part Number
Outlet
Input
Amp
kW*
Output
Plug
Dimensions - in (mm)
Breakers
(Hydraulic Magnetic)
Outlets
H***
W
D
220-240 Volt, Single-Phase Input
L2-1H0E3
32
7.3¥
IEC 32A 1P+N+E
2 x 2P 16A
(24) C13, (6) C19
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1H0G3
32
7.3¥
IEC 32A 1P+N+E
2 x 2P 16A
(30) C13, (6) C19
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1H0B1
32
7.3¥
IEC 32A 1P+N+E
2 x 2P 16A
(36) C13
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1W0G3
16
11≠
IEC 16A 3P+N+E
3 x 2P 16A
(30) C13, (6) C19
70.5 (1791)
2.2 (56)
2.2 (56)
L2-1W0B1
16
11≠
IEC 16A 3P+N+E
3 x 2P 16A
(36) C13
70.5 (1791)
2.2 (56)
2.2 (56)
L2-2Y0F3
32
22.1≠
EC 32A 3P+N+E
6 x 1P 16A
(24) C13, (12) C19
72.0 (1829)
2.35 (60)
2.2 (56)
L2-2Y0H3
32
22.1≠
EC 32A 3P+N+E
6 x 1P 16A
(36) C13, (6) C19
72.0 (1829)
2.35 (60)
2.2 (56)
220-240/380-415 Volt, Three-Phase Input
Notes: Order mounting brackets separately. On single-phase PDUs, output voltage equals input voltage. On three-phase PDUs, 208 VAC nominal output through C13 and C19 outlets; 120 VAC nominal output
through NEMA 5-20R outlets.
* For kW column, all values are derated calculations per UL for use in North America. The Input Amp column lists the maximum rated value of the input plug/inlet and circuit breaker rating. UL/NEC
regulatory code requires current ratings on product labels to be derated to 80% of the maximum rated values (for example: 20 Amp = 16 Amp on UL product label). For the Input kW column, all values are derated
calculations per UL for use in North America.
** Order power cord separately for PDU with C20 input.
*** PDUs that are 72”H (1829 mm) must be placed in 44U or taller CPI cabinets. PDUs that are 75”H (1905 mm) must be placed in 45U or taller CPI cabinets.
**** Capacity when used at 230V with a 16A power cord. Actual capacity will vary if connected to lower voltage or to a lower amperage input plug.
¥ Capacity when used at a nominal voltage of 230V.
≠ Capacity when used at a nominal voltage of 230V/415V 3-phase.
For detailed, model-specific dimensions and technical specification information, download the cut sheet for your selected PDU part number by
entering it into the CPI website search field at the top right corner of our website: www.chatsworth.com.
4
Chatsworth Products
PRODUCT DATA SHEET
Metered eConnect® PDU
ACCESSORIES
IEC 16A 2P+E
IEC C20 PDU Input Power Cords
Use Input power cords with eConnect PDUs that have
IEC C20 inlets.
• Select power cord to match power connection in the
facility
• IEC C19 Connector attaches to the C20 Inlet on the PDU
• Sold individually, order one power cord per PDU
eConnect PDU Accessories
POWER CORD PLUG TABLE:
Locking
(Single-Phase)
Straight
Plugs
NEMA L5-15P
110-125VAC/15A
NEMA 5-15P
110-125VAC/15A
NEMA L5-20P
110-125VAC/20A
NEMA 5-20P
110-125VAC/20A
NEMA L6-15P
200-240VAC/15A
NEMA 6-15P
200-240VAC/15A
Description
Shipping
Weight
lb (kg)
17763-001
PDU Input Power Cord, 110-125 VAC or 200-240 VAC,
IEC C19 Connector to IEC C20 Plug, 10’L (3 m)
3 (1.4)
17763-002
PDU Input Power Cord, 110-125 VAC,
IEC C19 Connector to NEMA 5-15P Plug, 8’2”L (2.4 m)
3 (1.4)
17763-003
PDU Input Power Cord, 110-125 VAC,
IEC C19 Connector to NEMA 5-20P Plug, 8’2”L (2.4 m)
3 (1.4)
17763-004
PDU Input Power Cord, 200-240 VAC,
IEC C19 Connector to NEMA 6-15P Plug, 8’2”L (2.4 m)
3 (1.4)
17763-005
PDU Input Power Cord, 200-240 VAC,
IEC C19 Connector to NEMA 6-20P Plug, 8’2”L (2.4 m)
3 (1.4)
17763-006
PDU Input Power Cord, 110-125 VAC,
IEC C19 Connector to NEMA L5-15P Plug, 10’L (3 m)
3 (1.4)
17763-007
PDU Input Power Cord, 110-125 VAC,
IEC C19 Connector to NEMA L5-20P Plug, 10’L (3 m)
3 (1.4)
17763-008
PDU Input Power Cord, 200-240 VAC,
IEC C19 Connector to NEMA L6-15P Plug, 10’L (3 m)
3 (1.4)
17763-009
PDU Input Power Cord, 200-240 VAC,
IEC C19 Connector to NEMA L6-20P Plug, 10’L (3 m)
3 (1.4)
17763-010
PDU Input Power Cord, 200-240 VAC,
IEC C19 Connector to IEC 16A 2P+E Plug, 10’L (3 m)
3 (1.4)
NEMA L6-20P
200-240VAC/20A
NEMA 6-20P
200-240VAC/20A
IEC Plugs
EC 60320 C-19/C-20
110-240VAC/20A
Part
Number
IEC 16A 1P+N+E
200-240 VAC/16A
Note: Splitter is required when attaching two probes together. 17763-xxx would be used in conjunction
with L2-1A1E3.
Additional Accessories
17762-003
39110-C01
17762-002
13780-C01
Part
Number
Description
Shipping
Weight
lb (kg)
17762-003
Cord Retention Tethers, Pack of 50
1 (0.5)
17762-002
Ground Wire Kit
1 (0.5)
17762-001
Tool-less Mounting Hardware Kit, Pack of 2
1 (0.5)
39110-C01
Mounting Bracket Kit for F-Series TeraFrame Gen 3
Cabinet or GF-Series GlobalFrame Gen 2 Cabinet System
2 (0.9)
13780-C01
Mounting Bracket Kit for F-Series TeraFrame Gen 2
Cabinet System
2 (0.9)
25140-701
Mounting Bracket Kit for GF-Series GlobalFrame Gen 1
Cabinet System
2 (0.9)
13762-701
Mounting Bracket Kit for M-Series MegaFrame Cabinet or
C-Series SlimFrame Cabinet System
2 (0.9)
35700-701
Mounting Bracket Kit for Rack Systems
2 (0.9)
Note: Each PDU includes Cord Retention Tethers, Ground Wire Kit and Tool-less Mounting Hardware.
They are listed as Service Parts. Mounting Brackets are included with CPI Cabinet Systems.
25140-701
13762-701
5
Chatsworth Products
PRODUCT DATA SHEET
Metered eConnect® PDU
ORDERING INFORMATION
PLUG/INLET TABLE:
POWER RECEPTACLE/OUTLET TABLE
Single-Phase/
Locking
Receptacles/
Outlets
NEMA L5-20P
110-125 VAC/20A
NEMA L5-30P
110-125 VAC/30A
NEMA L14-20P
120/240 VAC/20A
NEMA L14-30P
120/240 VAC/30A
NEMA L15-20P
208 VAC/20A
IEC C20
110/125 VAC/20A
NEMA 5-20R
120 VAC/20A
NEMA L6-20P
200-240 VAC/20A
NEMA L6-30P
200-240 VAC/30A
NEMA L15-30P
208 VAC/30A
NEMA L21-20P
120/208 VAC/20A
NEMA L21-30P
120/208 VAC/30A
NEMA L22-20P
380/415 VAC/20A
NEMA L22-30P
380/415 VAC/30A
IEC C20
200/240 VAC/20A
IEC 16A 1P+N+E
200/240 VAC/16A
IEC 32A 1P+N+E
200/240 VAC/32A
IEC 16A 3P+N+E
230/400 VAC/16A
IEC 32A 3P+N+E
230/400 VAC/32A
IEC C19
IEC C13
UL: 120/208VAC/15A UL: 120/208VAC/20A
CE: 208VAC/16A
CE: 208VAC/10A
Split-Phase/
Locking
Three-Phase/
Locking
50A CS8365C
208 VAC/50A*
Power Inlet
Universal/
Locking
* Note: 50A CS8365C is rated for 50A, but maximum input is 35A on three-breaker PDUs.
power
Order PDUs preinstalled to your cabinet.
Add power. Make it easy.
Simplify ordering, shipping and installation by
requesting eConnect PDUs to be installed in
CPI's GF-Series GlobalFrame or F-Series
TeraFrame Cabinets before they leave the factory.
Go to the Product Configurator to configure a
cabinet with PDUs preinstalled.
CPI now offers Extended Limited Warranties on CPI-Branded Electronic products,
available for two additional years beyond the expiration of the Original Warranty
Period (3 years).
Interested in learning more about our Power Products? Call us at 800-834-4969, or
email Technical Support at [email protected]
Contact CPI Customer Service, or visit www.chatsworth.com/warranty for more
information.
While every effort has been made to ensure the accuracy of all information, CPI does not accept liability for
any errors or omissions and reserves the right to change information and descriptions of listed services and products.
©2017 Chatsworth Products, Inc. All rights reserved. Chatsworth Products, CPI, CPI Passive Cooling, eConnect, RMR, MegaFrame,
Saf-T-Grip, SeismicFrame, SlimFrame, TeraFrame, GlobalFrame, CUBE-iT PLUS, Evolution, OnTrac, QuadraRack and Velocity are federally
registered trademarks of Chatsworth Products. Simply Efficient, Secure Array, EuroFrame, Clik-Nut and Motive are trademarks of
Chatsworth Products. All other trademarks belong to their respective companies. 05/17 MKT-60020-692