Vertiv GXT4-6000RT230E Installer/User Manual


Add to my manuals
66 Pages

advertisement

Vertiv GXT4-6000RT230E Installer/User Manual | Manualzz

Liebert® GXT4™ UPS

230 V, 5000 VA – 10,000 VA

Installer/User Guide

Technical Support Site

If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. For additional assistance, visit https://www.VertivCo.com/en-us/support/

TABLE OF CONTENTS

1 Important Safety Precautions

2 Product Description

2.1 Features

2.2 Available Models

2.3 Front Panel and Controls

2.4 Rear Panel Features

2.5 Removable Power Distribution Box

2.6 Internal Battery Packs

2.7 Major Components

2.7.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters

2.7.2 Rectifier/Power Factor Correction (PFC) Circuit

2.7.3 Inverter

2.7.4 Battery Charger

2.7.5 DC-to-DC Converter

2.7.6 Battery

2.7.7 Internal Bypass

2.7.8 Maintenance Bypass

2.8 Operating Modes

2.8.1 Mains Mode

2.8.2 Manual Bypass Mode

2.8.3 Battery Mode

2.8.4 Battery Recharge Mode

2.8.5 Frequency Converter Mode

2.8.6 Active ECO Mode

3 Installation

3.1 What’s Included

3.2 Unpacking and Inspection

3.3 Preparation for Installation

3.3.1 Installation Environment

3.3.2 Installation Clearances

3.4 Installing the UPS

3.4.1 Tower Installation

3.4.2 Rack Installation

3.5 Installing External Battery Cabinets

3.5.1 Installing the Optional Liebert IntelliSlot® Card and Communication Cables

3.6 Connecting Input/Output Power

3.6.1 Installing the Power Distribution Box

3.6.2 Electrical Connections for the Power-distribution Box

3.6.3 Removing the Power Distribution Box

3.7 Configuring an IT Power System

Vertiv | Liebert GXT4 Installer/User Guide |

21

22

22

19

21

21

21

21

18

18

19

17

17

17

17

18

25

25

27

28

22

23

23

25

25

16

17

17

15

16

16

16

16

12

12

14

7

11

11

11

3

4 Operation and Display Panel

4.1 LED Indicators

4.2 Control Buttons

4.3 LCD

4.4 Menu Structure

4.4.1 Startup Screen

4.4.2 Default Screen

4.4.3 Main Menu Screen

4.5 Prompt List

4.6 Warning List

4.7 Fault List

5 Operation

5.1 Startup Checklist for the GXT4

5.2 Starting the UPS

5.3 Performing a Manual Battery Test

5.4 Performing Manual Bypass

5.5 Shutting Down the GXT4

5.6 Disconnecting Input Power from the GXT4

5.7 Placing UPS in Maintenance Bypass

6 Communication

6.1 Liebert IntelliSlot Communication Cards

6.1.1 Liebert MultiLink

6.2 USB Port Communication

6.2.1 Configuration Program

6.3 Terminal Block Communication

6.3.1 Any Mode Shutdown

6.3.2 Battery Mode Shutdown

6.3.3 On Battery

6.3.4 Low Battery

6.4 Remote Emergency Power Off

7 Maintenance

7.1 Replacing the Internal Battery Pack

7.1.1 Battery Replacement Procedures

7.2 Battery Charging

7.3 Precautions

7.4 Checking UPS Status

7.5 Checking UPS Functions

8 Troubleshooting

8.1 UPS Symptoms

8.1.1 Indicator and LCD

8.1.2 Audible Alarm

8.2 Troubleshooting UPS Issues

Vertiv | Liebert GXT4 Installer/User Guide |

46

46

46

49

49

45

45

46

43

43

43

43

44

42

42

42

52

52

53

53

53

50

51

52

54

54

41

41

41

41

42

37

38

38

32

33

34

34

34

31

31

32

4

9 Specifications

9.1 Auto-Learning Battery Run Times

Appendices

Appendix A: Technical Support

57

62

63

63

Vertiv | Liebert GXT4 Installer/User Guide |

5

Vertiv | Liebert GXT4 Installer/User Guide |

6

1 IMPORTANT SAFETY PRECAUTIONS

SAVE THESE INSTRUCTIONS

This manual contains important safety instructions that must be followed during the installation and maintenance of the UPS and batteries. Read this manual thoroughly before attempting to install or operate this UPS.

UPS Safety Notes

This UPS contains no user-serviceable parts except the internal battery pack. The Off/Bypass push button does not electrically isolate internal parts. Under no circumstances attempt to gain internal access other than to replace the batteries due to risk of electric shock or burn. Do not continue to use the

UPS if the front panel indications are not in accordance with these operating instructions or if the UPS performance alters in use. Refer all faults to your local dealer, Vertiv™ representative or Vertiv™ Channel

Support.

This UPS has an internal battery, and the output receptacles of the UPS may carry live voltage even if the

UPS is not connected to utility input power.

Before moving or rewiring this UPS, disconnect utility input power and the battery and make sure that the

UPS is completely shut down. Otherwise, the output terminal may carry live voltage, presenting an electric shock hazard.

To ensure human safety and normal UPS operation, the UPS must be properly grounded before use.

When the UPS is connected to an IT power distribution system, a short-circuit protection device must be installed on the neutral line.

Install and use the Liebert GXT4 in the following environments:

• Temperature: 32°F - 104°F (0°C - 40°C), relative humidity: 0% to 95% non-condensing

• Out of direct sunlight

• Away from heat sources

• Stable surface, not subject to vibrations or shocks

• Away from dust and other particulates

• Away from corrosive substances, salts and flammable gases

Keep the air inlet and outlet of this UPS unobstructed. Poor ventilation will increase the internal temperature of the UPS and can adversely affect the UPS and its batteries.

Keep liquid and foreign objects away from the UPS.

In case of fire, use a dry chemical fire extinguisher to put out the fire. Using a fluid fire extinguisher may cause electric shock.

This product is designed for commercial/industrial use only. This UPS is not intended for use with life support and other designated critical devices. Maximum load must not exceed that shown on the UPS rating label. This UPS is designed for data processing equipment. If uncertain, consult your local dealer or

Vertiv™ representative.

Vertiv | Liebert GXT4 Installer/User Guide |

7

Battery Safety

WARNING! Risk of electric shock and explosion. Can cause equipment damage, injury and death. Do not dispose of the battery in a fire. The battery may explode. Do not open or damage the battery. Released electrolyte is toxic and is harmful to skin and eyes. If electrolyte comes into contact with the skin, wash the affected area immediately with plenty of clean water and get medical attention.

WARNING! Risk of electric shock. Can cause equipment damage, injury and death. A battery can present a risk of electrical shock and high short-circuit current.

The following precautions should be observed when working on batteries:

• Remove watches, rings and other metal objects.

• Use tools with insulated handles.

• Wear rubber gloves and boots.

• Do not lay tools or metal parts on top of batteries.

• Disconnect charging source prior to connecting or disconnecting battery terminals.

• If the battery kit is damaged in any way or shows signs of leakage, contact your local Vertiv™ representative immediately.

• Handle, transport and recycle batteries in accordance with local regulations.

• Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if grounds are removed during installation and maintenance (applicable to a UPS and a remote battery supply not having a grounded supply circuit).

ELECTROMAGNETIC COMPATIBILITY The Liebert GXT4 series complies with the limits for a CLASS A

DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules. Operation is subject to the following conditions:

• This device may not cause harmful interference.

• This device must accept any interference received, including interference that may cause undesired operation.

Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense.

The Liebert GXT4 series complies with the requirements of EMC Directive 2004/108/EC and the published technical standards. Continued compliance requires installation in accordance with these instructions and use of accessories approved by Vertiv™.

Vertiv | Liebert GXT4 Installer/User Guide |

8

Information for the Protection of the Environment

UPS Servicing: UPS makes use of components dangerous for the environment (electronic cards, electronic components). The components removed must be taken to specialized collection and disposal centers.

NOTICE TO EUROPEAN UNION CUSTOMERS: DISPOSAL OF OLD APPLIANCES—This product has been supplied from an environmentally aware manufacturer that complies with the Waste Electrical and

Electronic Equipment (WEEE) Directive 2002/96/CE.

The “crossed-out wheelie bin” symbol at right is placed on this product to encourage you to recycle wherever possible. Please be environmentally responsible and recycle this product through your recycling facility at its end of life. Do not dispose of this product as unsorted municipal waste. Follow local municipal waste ordinances for proper disposal provisions to reduce the environmental impact of waste electrical and electronic equipment (WEEE).

For information regarding the scrapping of this equipment, please browse

h ttp s://www.vertivco.com /en -em ea/

(“Products session” or “Contact us” session) or call our worldwide technical support.

• Toll Free: 00 80011554499

• Toll Number Based in Italy: +39 0298250222

Table 1.1 Glossary of Symbols

SYMBOL DESCRIPTION

Risk of electrical shock

Indicates caution followed by important instructions

AC input

AC output

Requests the user to consult the manual

Indicates the unit contains a valve-regulated lead acid battery

SYMBOL DESCRIPTION

Recycle

DC voltage

Equipment grounding conductor

Bonded to ground

AC voltage

Vertiv | Liebert GXT4 Installer/User Guide |

9

This page intentionally left blank.

Vertiv | Liebert GXT4 Installer/User Guide |

10

2 PRODUCT DESCRIPTION

The Liebert GXT4 is a compact, online uninterruptible power system (UPS) that continuously conditions and regulates its output voltage. The Liebert GXT4 is designed to supply microcomputers and other sensitive equipment with clean sine-wave input power.

Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject to voltage sags, spikes and complete failure that may interrupt computer operations, cause data loss, and damage equipment.

The Liebert GXT4 protects equipment from these disturbances. The Liebert GXT4 continuously charges its batteries from the mains, enabling it to supply power to connected loads, even when the mains fail.

2.1 Features

• Intelligent battery management to extend the battery life

• LCD for user-friendly operation and local monitoring and configuration of operational parameters

• Flexible network management with Liebert MultiLink™ software

• Fan fault self-inspection and automated diagnostic function

• Intelligent fan operation, automatically changing rotation speed depending on system requirements, to decrease power consumption and noise

• Input circuit breaker to ease recovery from overloads

• CE mark and safety approval from CE

• Communication options: USB port, Liebert IntelliSlot® port and terminal-block communication

• Dry contacts for remote monitoring

• Input power factor greater than 0.99

• Output voltage selection function

2.2 Available Models

Available models of the UPS are listed in the following table.

Table 2.1 UPS models, power ratings

MODEL NUMBER NOMINAL POWER RATING

GXT4-5000RT230

GXT4-5000RT230E

GXT4-6000RT230

GXT4-6000RT230E

GXT4-10000RT230

GXT4-10000RT230E

5000VA / 4000W

6000VA / 4800W

10000VA / 9000W

Vertiv | Liebert GXT4 Installer/User Guide |

11

2.3 Front Panel and Controls

The Liebert GXT4 rack/tower models in various power ratings have the same general appearance, controls and features as shown in the following figure. The various rack/towermodels differ largely in the type of receptacles each has.

Figure 2.1 Front view

NO.

DESCRIPTION

1

2

3

Upper bezel

Operation and display panel

Lower bezel and battery-access door

2.4 Rear Panel Features

The rear panel of the Liebert GXT4 has these features:

• Liebert IntelliSlot® Port

• USB port

• Input Circuit Breaker

• Maintenance Bypass Circuit Breaker

• REPO connection

• Input Receptacle

• General Output Receptacles

• External Battery Connector

• Cooling Fan

• Terminal Block Communication

• Output Circuit Breakers )

Vertiv | Liebert GXT4 Installer/User Guide |

12

Figure 2.2 Rear panel—5000VA and 6000VA

6

7

4

5

1

2

3

NO.

DESCRIPTION NO.

Liebert IntelliSlot Unity-DP card 8

Terminal-block communication 9

REPO 10

USB port 11

C19 output-power receptacles 12

External battery connector 13

IT Power System access cover 14

DESCRIPTION

Input circuit breaker

Output circuit breakers

Knockouts for hard-wired power input and output

Output circuit breaker

Maintenance bypass breaker

C13 output receptacles

Output circuit breakers

NOTE: Hard-wired and hard-wired/receptacle boxes that include a manual bypass switch permit AC power to continue to flow from the utility input to the load while the box is removed from the UPS. For details, refer to

Connecting Input/Output Power on page 25.

Vertiv | Liebert GXT4 Installer/User Guide |

13

Figure 2.3 Rear panel—10,000VA

NO.

DESCRIPTION NO.

DESCRIPTION

6

7

4

5

1

2

3

DB9 ports (parallel communication)

USB port

C19 output receptacles

External battery connector

Liebert IntelliSlot Unity-DP card

11

12

IT Power System Access Cover 13

Knockouts for hard-wired power input and output 14

8

9

10

Output circuit breakers

C13 output receptacles

Input circuit breaker

Output circuit breaker

Maintenance bypass breaker

REPO

Terminal-block communication

2.5 Removable Power Distribution Box

The UPS ships with a power-distribution pack installed. This box contains the UPS input circuit breaker.

Figure 2.4 Power distribution box for 5000 VA and 6000 VA models

Vertiv | Liebert GXT4 Installer/User Guide |

1

2

NO.

DESCRIPTION

Outer-surface view

Quick-connect

14

Figure 2.5 Power distribution box for 10,000 VA models

NO.

DESCRIPTION

1

2

3

Front view, PD2-CE10HDWRMBS

Inner-surface view

Quick-connects

2.6 Internal Battery Packs

The UPS has two internal battery packs behind a battery-access door on the front of the unit. Each internal battery pack is fitted with a connector to link to the UPS.

GXT4 10,000-VA battery pack shown is shown in the figure. 5000-VA and 6000-VA battery packs have the same features.

Figure 2.6 Internal battery pack with connector

Vertiv | Liebert GXT4 Installer/User Guide |

1

2

NO.

DESCRIPTION

Battery handle

Battery connector

15

2.7 Major Components

The UPS is composed of mains input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery charger, DCto-DC converter, battery, dynamic bypass and UPS output.

Figure 2.7 Operating principle diagram

2.7.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters

The UPS has surge protection and filters that protect the connected load from power surges, electromagnetic interference (EMI) and radio frequency interference (RFI). These features can minimize any surges or interference present in the mains power. The filters also prevent surges or interference generated by the UPS from adversely affecting devices connected on the same branch as the UPS.

2.7.2 Rectifier/Power Factor Correction (PFC) Circuit

In normal operation, the rectifier/PFC circuit converts mains power to regulated DC power for use by the inverter while ensuring that the wave shape of the input current used by the UPS is near ideal. Extracting this sine-wave input current achieves two objectives:

• Efficient power use by the UPS

• Reduced reflected harmonics

This results in cleaner power available to other devices in the building that are not protected by the

GXT4.

2.7.3 Inverter

In normal operation, the inverter utilizes the DC output of the PFC circuit to produce precise, regulated sine-wave AC power. When mains power fails, the inverter receives DC power from the DC-to-DC

Converter. In either operation mode, the UPS inverter is online, continuously generating clean, precise, regulated AC output power.

2.7.4 Battery Charger

The battery charger utilizes energy from the mains power and precisely regulates it to continuously float charge the batteries. The batteries are being charged whenever the GXT4 is plugged in, even when the

UPS is not turned On.

Vertiv | Liebert GXT4 Installer/User Guide |

16

2.7.5 DC-to-DC Converter

The DC-to-DC converter raises the DC voltage from the battery to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.

2.7.6 Battery

The GXT4 uses valve-regulated, non-spillable, lead acid batteries. To maintain battery design life, Operate the GXT4 in an ambient temperature of 15°C to 25°C (59°F to 77°F).

Optional external battery cabinets are available to extend battery run times.

2.7.7 Internal Bypass

The GXT4 provides an alternate path for mains power to the connected load in the unlikely event of a

UPS malfunction. Should the UPS have an overload, over-temperature or any other UPS failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by an audible alarm and illuminated amber Bypass LED (other LEDs may be illuminated to indicate the diagnosed problem).

To manually transfer the connected load from the inverter to bypass, press the Standby/Manual Bypass button once and hold it for about 2 seconds

2.7.8 Maintenance Bypass

The GXT4 provides a manual maintenance bypass in a removable section of the rear of the UPS. This allows replacement of the UPS in the event of a UPS malfunction while keeping the connected equipment powered with utility power.

NOTE: The bypass power path does not protect the connected equipment from disturbances in the mains supply.

2.8 Operating Modes

The UPS operation modes include the following: Mains (AC) Mode, Bypass Mode, Battery Mode, Battery

Recharge Mode, Active ECO Mode and Frequency Converter Mode.

Refer to

Operation and Display Panel on page 31 for details about the operating mode indicators and

control buttons.

2.8.1 Mains Mode

During Mains Mode, the mains provides input power to the GXT4. The filters, PFC circuit and inverter process this power to provide high-quality sine wave power to connected loads. The UPS maintains the batteries in a fully-charged state.

Vertiv | Liebert GXT4 Installer/User Guide |

17

2.8.2 Manual Bypass Mode

Manual Bypass Mode occurs when the unit is manually placed in internal bypass by navigating the LCD menu to select 3 Control > 1 Turn O n & O ff > Turn UPS Bypass. Bypass operation is indicated by an audible alarm and illuminated amber bypass indicator. (If other indicators are illuminated, refer to

Troubleshooting on page 53). During Bypass Mode, mains power bypasses the inverter and provides

energy to the connected load.

NOTICE

Risk of loss of power to the connected load. Can cause equipment damage.

Turning Off the UPS in Bypass Mode will result in loss of output power to the connected load.

2.8.3 Battery Mode

The GXT4 enters Battery Mode when mains power fails or is outside acceptable limits. The battery system supplies power through the DC-to-DC converter to the inverter to generate clean AC power for the connected loads.

When the GXT4 enters Battery Mode, the UPS sounds a half-second beep at 10-second intervals. When approximately 2 minutes of run time remains, the beeps sound every 5 seconds to warn that the battery is getting low (this Low Battery Warning is user-configurable).

In Battery Mode, the battery indicator will illuminate and the LCD will show the prompt utility power not

availab le.

Press either the Up or Down button once, then press the Enter button to clear the prompt and silence the audible alarm. Once the alarm prompt has been acknowledged, the screen showing the estimated battery run time and battery capacity will be visible. Refer to

Troubleshooting on page 53.

For approximate battery run times, refer to .

NOTICE

Risk of loss of power to the connected load. Can cause equipment damage.

Turning Off the GXT4 when it is in Battery Mode will result in loss of output power to the connected load.

If the UPS is turned Off manually, it must be manually restarted after mains power returns.

If the UPS is turned Off by a communication signal or because the batteries are depleted, it will operate as set in the configuration program for Auto-Restart (Refer to

Configuration Program on page 44).

2.8.4 Battery Recharge Mode

Once mains power is applied to the GXT4, the Battery Charger begins charging the batteries.

Vertiv | Liebert GXT4 Installer/User Guide |

18

2.8.5 Frequency Converter Mode

All models of the GXT4 are capable of frequency conversion. Frequency Conversion Mode can be selected using the configuration program. Allowable frequency operating modes include:

• Auto Sensing - 50Hz or 60Hz – Bypass Enabled

• Auto Sensing - 50Hz or 60Hz – Bypass Disabled

• Frequency Converter - 50Hz – Bypass Disabled

• Frequency Converter - 60Hz – Bypass Disabled

NOTE: The default for all models of the Liebert GXT4 is “Auto Sensing - 50Hz or 60Hz – Bypass

Enabled.”

WARNING! Risk of electric shock. Can cause injury or death. Never touch the AC input receptacle while the UPS is operating. Voltage may still be present even when the AC input indicator is Off.

2.8.6 Active ECO Mode

All Liebert GXT4 models can operate in Active ECO Mode. In this mode, the connected equipment is powered through the bypass path to increase efficiency, reducing the electrical costs.

Active ECO mode keeps the rectifier and inverter operating, allowing the inverter to remain synchronized to bypass. This synchronization allows the transfer of the connected equipment to UPS inverter power almost seamlessly if bypass power falls outside the user-set limits. Once bypass power returns within the acceptable parameters, the UPS will return to Active ECO Mode operation.

The default setting is Active ECO Mode Off.

Vertiv | Liebert GXT4 Installer/User Guide |

19

This page intentionally left blank.

Vertiv | Liebert GXT4 Installer/User Guide |

20

3 INSTALLATION

Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in

Starting the UPS on page 41.

3.1 What’s Included

• Terminal Block Communication Terminals

• Compact Disk with:

• Liebert MultiLink® Shutdown Software

• Configuration Program

• User Manual (electronic version)

• Liebert IntelliSlot Unity card (IS-UNITY-DP), factory installed (not included with units with model number ending with an “E”)

• USB Cable—one, 2 m (6-1/2 ft) long

• Rack mounting hardware, including screws, mounting rail kit (mounting rail kit not included with “E” models)

• Power-distribution box, installed on GXT4.

• Two plastic, tower-stand support-base sets (four pieces)

• Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)

NOTE: The GXT4 External Battery Cabinet shipping package includes one battery cabinet, two spacers for tower configuration and one DC-power cable and rack-mounting hardware, including screws, handles and mounting rail kit (not included with “E” models).

3.2 Unpacking and Inspection

Unpack the UPS and conduct the following checks:

• Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and your local dealer or your Vertiv™ representative immediately.

• Check the accessories included in packaging list. If there is any discrepancy, contact your local dealer or your Vertiv™ representative immediately.

CAUTION: The UPS is heavy (see Specifications). Take proper precautions when lifting or moving it.

3.3 Preparation for Installation

3.3.1 Installation Environment

• Install the UPS indoors in a controlled environment, where it cannot be accidentally turned Off.

The installation environment should meet the specifications listed in

Specifications on page 57.

• Place it in an area of unrestricted air-flow around the unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants. Avoid direct sunlight.

NOTE: Operating the UPS in temperatures above 77°F (25°C) reduces battery life.

Vertiv | Liebert GXT4 Installer/User Guide |

21

3.3.2 Installation Clearances

Maintain at least 4 in. (100 mm) clearance in the front and rear of the GXT4. Do not obstruct the air inlets on the front panel and rear panel of the UPS. Blocking the air inlets reduces ventilation and heat dissipation, shortening the service life of the Liebert GXT4.

3.4 Installing the UPS

The Liebert GXT4 may be installed as a tower or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instructions. See

Tower

Installation on page 22 or

Rack Installation on page 23.

NOTE: When installing the UPS or making input and output connections, comply with all relevant safety codes and standards

3.4.1 Tower Installation

To install the GXT4 as a tower:

1. Take the support bases out of the accessories box.

Figure 3.1 Support bases

NO.

DESCRIPTION

1 Support bases

2 Spacers with connectors

2. If optional, Liebert external battery cabinets will be connected, take out the spacers shipped with the battery cabinet.

3. Connect the spacers and the support bases as shown in Figure 3.1 above. Each GXT4 requires

2 support bases, one in the front and one in the rear.

4. Adjust the direction of the operation and display panel and logo on the GXT4.

a. Remove the front plastic bezel cover as shown the following figure.

b. Pull the operation and display panel gently, rotate it 90 degrees clockwise and snap it back into position, as shown.

c. Pull the logo on the front plastic bezel cover gently, rotate it 90 degrees clockwise and snap it back into position.

d. Replace the front plastic bezel cover.

The operation and display panel and logo have been rotated 90 degrees clockwise, for upright viewing.

Vertiv | Liebert GXT4 Installer/User Guide |

22

Figure 3.2 Remove the front plastic bezel cover and rotate display

NO.

DESCRIPTION

1 Remove bezel cover.

2 Rotate display 90 degrees.

5. Place the GXT4 and any battery cabinets on the 2 support bases.

3.4.2 Rack Installation

When installed in a rack enclosure, the GXT4 UPS and external battery cabinets (EBC) must be supported by a shelf or rack-mount rails. The GXT4 and EBC units ship with all required hardware for rack-mount installation (not included with model numbers that end in “E”). Because different rack-mount options install differently, refer to the installation instructions provided with the rack mount kit being used.

CAUTION: The GXT4 is heavy. The UPS must be installed as near the bottom of a rack as possible. If placed too high, it can make the rack top-heavy and prone to tipping over. For unit weights, see

Specifications on page 57.

3.5 Installing External Battery Cabinets

WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power supplies before working within. Ensure that the Liebert GXT4 is shut down and power has been disconnected before beginning any work on or in the unit.

CAUTION: The external battery cabinet(s) are heavy (see Table 9.3 on page 59). Take proper

precautions when lifting them.

Optional, Liebert external battery cabinets (EBC) may be connected to the UPS to provide additional battery run time. External battery cabinets are placed on one side of the UPS in a tower configuration or stacked beneath the UPS in a rack configuration.

Vertiv | Liebert GXT4 Installer/User Guide |

23

Figure 3.3 External battery cabinets connected to GXT4

1

2

3

NO.

DESCRIPTION

GXT4

External battery cabinet (EBC)

Cable connects EBC to GXT4.

To install the external battery cabinet(s):

1. Inspect the EBC for freight damage. Report damage to the carrier and your local dealer or

Vertiv™ representative.

2. Optional rack-mount hardware is shipped with the external battery cabinet and may be installed at this time.

• Securing hardware and slide rails are sold separately. Please contact your local dealer or

Vertiv™ representative for these additional options and any assistance needed. Fasten the slides into position with the screws per the instructions included with the slide rails.

3. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of support-base extensions ships with each EBC.

4. Verify the that the EBC breaker is in the "Off" position.

5. Connect the supplied EBC cable to the rear of the cabinet, then to the rear of the UPS.

6. Turn the EBC breaker to the "On" position.

7. Verify the circuit breaker on the EBC is in the "On" position.

8. Use the included configuration program or the LCD display to program the UPS with the number of external battery cabinets connected. Instructions for the configuration program are in

Configuration Program on page 44.

The UPS is now equipped with additional back-up battery run time. For approximate battery run times,

refer to Table 9.4 on page 59.

Vertiv | Liebert GXT4 Installer/User Guide |

24

NOTE: When removing an EBC, the circuit breaker on the rear of the cabinet must be turned off before disconnecting the cable.

NOTE: If the UPS will be shipped or stored for an extended time, the connector should be disconnected. This will minimize any stand-by current drain on the batteries and help attain their design life.

3.5.1 Installing the Optional Liebert IntelliSlot® Card and Communication Cables

1. On the GXT4, remove the protective cover of the Liebert IntelliSlot port and set it aside.

2. Insert the IntelliSlot card into the IntelliSlot port and secure it with screws.

3. To connect any cable associated with and IntelliSlot card, refer to the quick-installation guide provided with the card.

To configure and use the Liebert IntelliSlot communication card, refer to the card’s user manual. Find manuals online at http://www.VertivCo.com/en-us/support/.

3.6 Connecting Input/Output Power

The GXT4 ships with a power distribution box attached.

Refer to the following instructions for removal and installation.

NOTE: Do not operate the UPS with the power distribution box removed. To shut off all power to this box and to the load, utility input power must be disconnected.

3.6.1 Installing the Power Distribution Box

1. Align the connectors and press the power-distribution box onto the UPS.

2. Hold the box firmly against the UPS and tighten the captive screws except the one over the maintenance bypass breaker.

3. Turn the output and input breakers "On."

4. Start the UPS according to start-up instructions.

5. Verify that the UPS lamp is illuminated.

6. Turn the maintenance bypass breaker "Off."

7. Insert the maintenance-bypass-interlock bracket behind the captive screw and tighten the screw.

NOTE: The maintenance bypass breaker interlock bracket must be installed behind the captive screw, and the screw must be tightened for the UPS to operate in inverter mode.

3.6.2 Electrical Connections for the Power-distribution Box

Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS.

• PD2-CE6HDWRMBS fits the 5000 and 6000VA models of the Liebert GXT4

• PD2-CE10HDWRMBS fits the 10,000VA model of the Liebert GXT4

The installer must provide an upstream branch circuit breaker. The input circuit breaker on the distribution box and the output circuit breaker on the rear of the power distribution box disconnect all power between the main cabinet and the distribution box.

Vertiv | Liebert GXT4 Installer/User Guide |

25

Models equipped with a manual bypass breaker pass bypass power directly to the bypass breaker from the input terminal block. The input circuit breaker on the distribution box does not disconnect power from the manual bypass breaker.

Table 3.1  Branch circuit breaker ratings

UNIT RATING MAXIMUM BREAKER RATING

5000VA

6000VA

10,000VA

D Type 32A

D Type 32A

D Type 63A

Figure 3.4 Distribution box electrical connections diagram

Terminal Block Connections

Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share the same conduit. We recommend using strain relief when installing the wire.

Table 3.2  Terminal-block Electrical specifications

UPS MODEL

RECOMMENDED

(MAXIMUM)

EXTERNAL

OVERCURRENT

PROTECTION

RECOMMENDED

WIRE

(INCLUDING

GROUND WIRE)

(75°C COPPER

WIRE)

MAXIMUM

WIRE

ACCEPTED

BY

TERMINAL

BLOCK

TERMINAL

TIGHTENING

TORQUE

GXT4-5000RT230

GXT4-6000RT230

32A 4mm

2

(10AWG) 6mm

2

(8AWG)

GXT4-10000RT230 63A 10mm

2

(6AWG)

16mm

2

(4AWG)

2.26 Nm

(20 in-lb)

Vertiv | Liebert GXT4 Installer/User Guide |

26

Figure 3.5 Terminal block connections

1. We recommend installing a breaker upstream of unit.

2. The installer must provide circuit breaker protection according to local codes. The mains disconnect should be within sight of the UPS or have appropriate an appropriate lock-out.

Maintain service space around the UPS or use flexible conduit.

3. The installer must provide output distribution panels, circuit breaker protection or emergency disconnects according to local codes. Output circuits must not share a common conduit with any other wiring.

3.6.3 Removing the Power Distribution Box

1. Manually transfer the connected equipment to the internal bypass.

a. From the main menu select CONTROL, then press Enter.

b. Select TUR N O N & O FF and press Enter.

c. Select TUR N O N UPS BYPASS and press Enter.

The UPS transfers the connected loads to the internal bypass. (For help, refer to

Performing Manual Bypass on page 42.)

d. Loosen the captive screw over the maintenance bypass breaker (see the following figure for the breaker’s location).

e. Turn the maintenance bypass breaker On.

NOTICE

The load is unprotected from disturbances in the power supply while the UPS is on bypass.

2. Turn the output and input breakers Off.

3. Loosen other captive screws until the power distribution box releases.

4. Remove the power distribution box from the UPS and set it aside.

5. On the rear of the panel, loosen the screws of the protective cover for the connectors, slide it over the connectors, and tighten the screws.

Vertiv | Liebert GXT4 Installer/User Guide |

27

Figure 3.6 Power distribution box removal

NO.

DESCRIPTION

1

2

Captive screws to loosen.

Maintenance bypass breaker

3.7 Configuring an IT Power System

1. Remove screws on the IT Power System Access Cover as shown in the figure.

2. Disconnect the connectors as shown in the figure.

3. Install the IT Power System Access Cover and screws.

Figure 3.7 Remove cover from IT Power System Connectors compartment

Vertiv | Liebert GXT4 Installer/User Guide |

28

1

2

NO.

DESCRIPTION

Remove screws.

IT power system connectors

Vertiv | Liebert GXT4 Installer/User Guide |

29

This page intentionally left blank.

Vertiv | Liebert GXT4 Installer/User Guide |

30

4 OPERATION AND DISPLAY PANEL

The operation and display panel on the front of the GXT4 has control buttons, LED indicators and a liquid-crystal display (LCD).

Figure 4.1 Operation and display panel

NO.

DESCRIPTION NO.

DESCRIPTION

3

4

5

1

2

Fault indicator

Inverter indicator

Battery indicator

Bypass indicator

ECO mode indicator

6

7

8

9

10

Enter button

Down button

Up button

Escape button

LCD panel

4.1 LED Indicators

The LED indicators on the front of the operation and display panel are:

• Inverter

• Battery

• Bypass

• ECO Mode

• Fault

Figure 4.1 above shows the indicators’ locations. Their descriptions and functions are as follows.

Vertiv | Liebert GXT4 Installer/User Guide |

31

Table 4.1 LED indicators

INDICATOR COLOR DESCRIPTION

Inverter

Bypass

Battery

Fault

ECO Mode

Green

Amber

Amber

Red

Green

On when the inverter is supplying power

On when the load is supplied by the mains through automatic/manual bypass

On when the load is supplied by the battery

On when an error has occurred within the UPS

On when the UPS is in ECO Mode

4.2 Control Buttons

The control buttons are described in the following table.

Table 4.2 Control buttons

BUTTON DESCRIPTION

ESC

Up

Down

Pressing this button returns to the previous menu or aborts any change in the input data field before confirming.

Pressing this button can move the cursor up or increase the value displayed in the input data field. When a menu is displayed on several screens, pressing the button can scroll up.

Pressing this button can move the cursor down or decrease the value displayed in the input data field. When a menu is displayed on several screens, pressing the button can scroll down.

Pressing this button can enter the next level menu or confirm the parameter setting value.

Enter

4.3 LCD

The LCD panel shows the UPS status and enables changes to the UPS settings by assisting in navigating through the GXT4 menu (see

Menu Structure on page 33).

Vertiv | Liebert GXT4 Installer/User Guide |

32

4.4 Menu Structure

The menu structure of the the LDC display is shown in the following figure.

Figure 4.2 Menu structure

Vertiv | Liebert GXT4 Installer/User Guide |

33

4.4.1 Startup Screen

When the GXT4 is starting up, it initiates a self-test and displays the start-up screen about 10 seconds.

After about 10 seconds, the LCD shows one of the "On" screens. The screen shown depends on whether or not input power is available.

• When input power is available: TURN ON UPS.

• When input power is not available: AC NOT AVAILABLE START ON BATTERY?

To turn On the UPS, press the Up or Down button to select YES and press the Enter button. The UPS will start up, the LCD will display UPS STAR TIN G and then STAR T SUCCESSFUL after the UPS is turned On..

4.4.2 Default Screen

Press any button in the START SUCCESSFUL screen to enter the default interface.

NOTE: Values shown in the default screen will vary depending on installation and configuration.

In the default screen, the LCD shows the UPS model, output parameters, input parameters, battery capacity with run time estimate and load percentage. The UPS operation mode (online/inverter, ECO,

Battery or Bypass) will be indicated by the LED indicators.

If no control button (ESC, Up, Down, Enter) is pressed for 2 minutes, the LCD will enter the screen-saver mode (back light turns off). It will remain off until a control button is pressed.

4.4.3 Main Menu Screen

Press the Enter button in the default screen to enter the MAIN MENU screen.

To select a submenu, press the Up or Down button to move the cursor to the required item, then press the

Enter button to enter its submenu or set its parameter.

Menu options

STATUS Screen

In the MAIN MENU screen, select STATUS to enter the Status Screen, displaying OUTPUT, LOAD,

INPUT, BATTERY and TIME SINCE STARTUP.

CONFIGURATION Screen

Select MAIN MEN U > CO N FIGUR ATIO N to enter the Configuration menu

In the CONFIGURATION screen, press the Up or Down button to move the cursor to the required item, then press the Enter button to enter a submenu or set its parameters.

UPS Screen

Select MAIN MEN U > CO N FIGUR ATIO N > UPS to enter the UPS screen. This menu has six screens.

Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings.

Vertiv | Liebert GXT4 Installer/User Guide |

34

Battery Screen

Select MAIN MEN U > CO N FIGUR ATIO N > BATTER Y to enter the BATTERY screen. This menu has four screens.

Press the Up or Down button to increase or decrease the value of the settings, and press the Enter button to confirm it.

ECO Mode Screen

Select MAIN MEN U > CO N FIGUR ATIO N > ECO MO DE to enter the ECO MODE screens.

Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings.

Outlet1 Output Control Screen

Select MAIN MEN U > 2 CO N FIGUR ATIO N > 4 O UTLET1 to enter the OUTLET1 screen. This menu has two sub menus

Select 1 O UTLET CO N TR O L and press the Enter button to enter the OUTLET CONTROL screen.

Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings.

Outlet1 Outlet Setting screen

Select MAIN MEN U > 2 CO N FIGUR ATIO N > 4 O UTLET1 to enter the OUTLET1 screen. This menu has two sub menus

Select 2 O utlet Setting and press the Enter button to enter the OUTLET SETTING screen.

Outlet2 Screen

The Outlet2 screens are the same as the Outlet1 screens. The same settings are available as on the

Outlet1 screen. If the Outlet2 group will have the same settings as the Outlet1 group, GXT4 offers a programming shortcut. When configuring the Outlet2 group, select YES and press the Enter button to apply the Outlet1 settings to the Outlet2 screen.

Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings.

LCD screen

Select Main Menu > 2 CO N FIGUR ATIO N > 6 LCD to enter the LCD screen. This menu has two sub menus, LANGUAGE and COLOR.

Select 1 LAN GUAGE and press the Enter button to enter the LANGUAGE screen.

Vertiv | Liebert GXT4 Installer/User Guide |

35

Lanquage screen

GXT4 supports multiple languages. For the list of supported languages and instructions on how to upload them, refer to the Configuration Program user manual on the included CD.

Color screen

Select 2 CO LO R and press the Enter button to enter the COLOR screen.

FACTORY DEFAULT screen

Select MAIN MEN U > 2 CO N FIGUR ATIO N > 7 FACTO R Y DEFAULT to enter the FACTORY DEFAULT screen.

Control Screen

Select MAIN MEN U > 3 CO N TR O L to enter the CONTROL screen. This screen has three sub menus,

TURN ON & OFF, ALARM CONTROL and BATT TEST.

In the CONTROL screen, press the Up or Down button to move the cursor to the required item, and press the Enter button to enter its sub menu.

TURN ON & OFF screen

Select MAIN MEN U -> 3 CO N TR O L -> 1 TUR N O N & O FF to enter the TURN ON & OFF screen. This screen shows one of two displays, TURN ON UPS and TURN OFF UPS, depending on the state of the

UPS.

ALARM CONTROL screen

Select MAIN MEN U -> 3 CO N TR O L -> 2 ALAR M CO N TR O L to enter the ALARM CONTROL screen.

This section allows active audible alarms to be silenced.

To completely turn off the audible alarm, select CO N FIGUR ATIO N > UPS.

BATT TEST screen

Select MAIN MEN U -> 3 CO N TR O L -> 3 BATT TEST to enter the BATT TEST screen.

Log Screen

Select MAIN MEN U -> 4 LO G to enter the LOG screen. This screen has two submenus, VIEW LOG and CLEAR LOG.

CLEAR LOG Screen

Select MAIN MEN U > LO G > CLEAR LO G to enter the CLEAR LOG screen.

Press the Up or Down button to move the cursor to the required item. Press the Enter button to confirm the settings.

Vertiv | Liebert GXT4 Installer/User Guide |

36

ABOUT Screen

Select MAIN MEN U> ABO UT to enter the ABOUT screen. The ABOUT screen displays UPS model, serial number, software version and hardware version.

Network

Select MAIN MEN U > N ETW O R K to enter the NETWORK screen.

The NETWORK screen displays the MAC address and the IPv4 IP address. If the GXT4 is fitted with an optional Liebert IntelliSlot Web card (Liebert IS-WEBCARD), the screen will display IPv6 IP address settings (IPv6 requires configuration).

4.5 Prompt List

A prompt screen is displayed during the operation of the system to alert you to certain conditions and/or to require your confirmation of a command or other operation. See the following table for the prompts and meanings.

Table 4.3 System prompts and meanings

PROMPT MEANINGS

Mains Power Restored

UPS Return From A Low Battery Condition

UPS Return From Battery Mode

The mains power returns and the UPS transfers back to mains (AC) mode.

The UPS transfers back to mains (AC) mode from battery low mode.

The UPS transfers back to mains (AC) mode from battery mode.

UPS Self Test Successful

UPS Shutdown Command Received

UPS Turn Off

UPS Turn On

The UPS self-test is successfully performed.

The UPS shut down was initiated through communication.

The UPS shuts down and has no output power.

The UPS starts up successfully and supplies protected power to the load.

UPS Shutdown Process Had Been Cancelled The shutdown command sent through Liebert MultiLink or SNMP card to the UPS is canceled,

ECO Mode Enabled

ECO Mode Disabled

The UPS is configured to ECO mode operation,

The UPS is configured to Online mode, supplying protected power to the load through the inverter.

UPS Internal Temperature Return To Normal The internal temperature of the UPS recovers to normal range.

UPS Load Return From Overload

Load On Inverter

Load On ECO Bypass

Bypass Power Restored

The loads are reduced, and the UPS recovers to normal state from overload.

The inverter is on and supplies protected power to the load.

The UPS is on ECO mode; the mains is supplying power to the load directly to reduce energy usage.

The bypass power recovered and the UPS can now transfer to bypass.

Vertiv | Liebert GXT4 Installer/User Guide |

37

4.6 Warning List

All UPS warning messages are described the following table.

Table 4.4 Warning list

WARNING DESCRIPTION

Mains Power Not Available

The mains power is not available, or it cannot satisfy the input requirements for the UPS to operate from mains power

UPS Batteries Low And

Exhausted Soon

UPS Has Switched To Battery

Mode

Load On Bypass

The UPS transfers to Bypass mode, at this point, the input mains power supplies power to the load directly, and the load is not protected

L-N line reverse or PE not connected.

Input Power Wiring Error

Bypass Power Not Available The bypass power is not available, or it cannot satisfy the requirements for the UPS transfers to bypass

UPS Maintenance Bypass Output The UPS transfers to maintenance bypass.

AC input not qualified, cannot start UPS

Output disabled

The battery capacity is low and will be exhausted soon

The mains power is abnormal or the PFC side is faulty, the UPS transfers back to Battery mode

The utility power is not qualified, the inverter cannot be powered up

REPO terminal connect error

4.7 Fault List

All UPS fault messages are described the following table.

Table 4.5 Fault list

FAULT DESCRIPTION

UPS Self-Test Failed

UPS Overload

Inverter Out Of Order

Battery Weak/Bad

Output Short Circuit

DC Bus Overvoltage

The battery is bad or weak or not connected.

The UPS is overloaded.

The inverter has failed.

The battery is bad or weak.

The output connection is short-circuited.

The DC bus is faulty.

UPS Overtemperature Overtemperature occurs to the UPS and the UPS will transfer to Bypass mode.

Charger Out Of Order The charger has failed.

Fan Out Of Order At least one fan is failed.

DC Bus Discharge Fail DC-DC failure occurs.

Rectifier Out Of Order Rectifier failure occurs.

Vertiv | Liebert GXT4 Installer/User Guide |

38

If a fault occurs, the UPS automatically switches to Bypass Mode. The original operating mode will be maintained only in the case of a battery disconnection fault. The fault message alternates with UPS Mode once a second, the red fault indicator on the operation and display panel lights up and the alarm sounds continuously.

If a fault occurs:

1. Enter the ALARM CONTROL screen, and select AUDIBLE ALAR M O N or AUDIBLE ALAR M O FF to switch the alarm On or Off.

2. Enter the EVENT LOG screen, and select VIEW LO G to view the entire event log.

NOTE: There will be a short delay before the EVENT LOG screen displays the historical fault log to allow the log to load.

Vertiv | Liebert GXT4 Installer/User Guide |

39

This page intentionally left blank.

Vertiv | Liebert GXT4 Installer/User Guide |

40

5 OPERATION

This section describes checks to be made before starting the UPS, how to start the UPS, manual battery test, manual bypass, shutting down the UPS and disconnecting mains power from the UPS.

NOTE: The GXT4's battery has been fully-charged before delivery, but some charge will be lost during storage and shipping. To ensure that the battery has adequate reserve power to protect the connected load, charge the battery for 5 hours before putting the UPS into service.

5.1 Startup Checklist for the GXT4

Before starting the UPS, perform these checks:

1. Check that the unit was wired by a qualified electrician and loads are connected properly and reliably.

2. Check that the battery cable is connected properly.

3. Check that the communication cables are connected properly.

5.2 Starting the UPS

1. Verify that the unit is wired by a qualified electrician and the circuit breaker in the feeder panel is closed.

2. Close the input breaker on the rear of the unit.

3. The UPS will begin the startup sequence once AC power is present.

NOTE: The UPS will sound an audible alarm, this is normal.

4. On the LCD, press either the Up or Down button once, then press the Enter button to turn On the UPS.

T h e UPS will sou n d th e au d ib le alarm ag ain as th e ou tp u t recep tacles are n ow b ein g p owered b y th e in tern al b yp ass, th en will sou n d on e m ore tim e as th e in verter p owers th e con n ected eq u ip m en t.

5. Check the LCD and LED indicators to ensure that the UPS is operating normally.

6. Check the load percentage on the default screen to ensure that the connected equipment is not exceeding the UPS’s rated capacity.

The UPS is now providing conditioned and protected power to the connected equipment.

5.3 Performing a Manual Battery Test

To initiate a manual battery test, select MAIN MEN U > CO N TR O L> BATT TEST > STAR T.

• If the battery test results show FAILED, allow the UPS to recharge the batteries for 24 hours.

• Retest the batteries after 24 hours of charging.

• After the batteries have been retested, if the battery test still shows FAILED, contact your local

Vertiv™ representative or Technical Support.

Vertiv | Liebert GXT4 Installer/User Guide |

41

5.4 Performing Manual Bypass

To manually transfer the connected equipment to the internal bypass:

1. From the main menu select Control then press enter.

2. Select TUR N O N & O FF and press Enter.

3. Select TUR N UPS BYPASS and press Enter. The UPS will transfer the connected loads to the internal bypass.

If the internal bypass is not available because of input power problems, pressing this button once will be ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If other indicators are illuminated, refer to

Troubleshooting on page 53.)

5.5 Shutting Down the GXT4

To shut down the UPS from the LCD:

1. From the Main Menu select CO N TR O L, press Enter, then select TUR N O N & O FF.

2. Press the Enter key.

3. Select TUR N UPS O FF, then press Enter. Press either the Up or Down button to move the cursor to confirm the turn off command and press Enter.

T h e UPS will sou n d an au d ib le alarm . T h is is n orm al.

4. Power to the connected equipment is now Off.

The UPS display will still be illuminated because the batteries are still being charged. The UPS may now be disconnected from AC power, and the UPS will completely shut down in approximately 15 seconds.

5.6 Disconnecting Input Power from the GXT4

1. After the UPS has been shut down as detailed in

Shutting Down the GXT4 on page 42,

disconnect the input cable from the wall socket.

2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped.

This indicates that the power-off is complete.

3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet.

After powering Off the UPS, the UPS ceases output and the load is powered Off.

5.7 Placing UPS in Maintenance Bypass

Maintenance Bypass Mode is used when maintenance or replacement is required. To place the unit in

Maintenance Bypass:

1. Place the UPS on internal bypass. This may be done by either of the following methods: a. Refer to

Performing Manual Bypass on page 42.

b. Slide the bracket away from the manual bypass breaker on the rear of the UPS. This requires loosening the captive screw and sliding the bracket up and away from the

Manual Bypass breaker.

2. Move the Manual Bypass breaker on the rear of the UPS to the bypass position. This requires loosening the captive screw and sliding the bracket up and away from the Manual Bypass breaker.

Vertiv | Liebert GXT4 Installer/User Guide |

42

6 COMMUNICATION

This section describes the communication ports on the rear of the UPS:

• Liebert IntelliSlot® port

• USB port (standard B-type)

• Terminal Block Communication

CAUTION: To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be segregated and run separate from all other power cables.

6.1 Liebert IntelliSlot Communication Cards

The Liebert IntelliSlot port accepts four optional cards:

• Liebert IntelliSlot Web Card (IS-WEBCARD)

• Liebert IntelliSlot Relay Card (IS-RELAY)

• Liebert IntelliSlot MultiPort Card (IS-MULTIPORT)

• Liebert IntelliSlot Unity Card (IS-UNITY-DP)

The Liebert IntelliSlot Web Card provides SNMP monitoring and control of the UPS across the network.

The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and delivers support for Liebert MultiLink

® shutdown software.

The Liebert IntelliSlot MultiPort Card provides four sets of contacts for support of up to four computers that have Liebert MultiLink installed.

The Liebert IntelliSlot Unity Card provides SNMP and/or RS-485 monitoring of the UPS across the network and/or building management system. The Liebert IntelliSlot UNITY card also enables monitoring external temperature, humidity and contact closure inputs using external sensors.

Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink

®

, the UPS or any additional ancillary product for the Liebert GXT4. The instructions are available at http://www.VertivCo.com/en-us/support/.

6.1.1 Liebert MultiLink

Liebert MultiLink monitors the UPS continuously and can shut down the computer or server in the event of an extended power failure. LiebertMultiLink can also be configured to shut down the UPS.

LiebertMultiLink can communicate with the UPS via the USB port, RS232 port, contact closures via terminal block or over the network via SNMP using the Liebert IS-UNITY-DP card. An optional Liebert

MultiLink license kit permits shutting down multiple computers that are protected by the UPS.

For more information about the Liebert IntelliSlot SNMP Card, Liebert IntelliSlot Web Card and Liebert

MultiLink License Kits, visit www.VertivCo.com or contact your Vertiv™ representative.

6.2 USB Port Communication

The standard B-type USB port is used to connect the UPS and network server or other computer system using Liebert MultiLink.

Vertiv | Liebert GXT4 Installer/User Guide |

43

A standard B-type USB port is provided to allow connection to a computer or network server. The USB port can be used to communicate with the GXT4 configuration program (see section

Configuration

Program on page 44 for details) or Liebert MultiLink (see

Liebert MultiLink on page 43 for description)

that is provided on the CD that is included with the UPS.

6.2.1 Configuration Program

The configuration program is on the Liebert GXT4 CD and can be used instead of making configuration setting changes from the LCD panel. The configuration program communicates to a computer running a

Microsoft® Windows® operating system via the included USB cable.

For most users, the factory-default settings are adequate. This section give a brief overview of the features and parameters that are available for modification, as well as the factory-default settings. Should any changes be necessary, refer to the Configuration Program User Manual that is located on the included CD for further details.

The configuration program allows these features of the GXT4 to be changed:

• Change and set the display language

• Enable/Disable Auto-Restart (default is Enable)

• Select frequency converter operation with a fixed output frequency of 50 Hz or 60 Hz, bypass disabled (default is Auto-Select with bypass enabled)

• Set the Low Battery Warning alarm time from 2 to 30 minutes (default is 2 minutes)

• Enable/Disable the Auto-Battery test (default is Enable)

• Enable/Disable Auto-Restart after removing Remote shutdown (default is Disable)

• Set the wiring mode of Remote shutdown (default is normally open)

• Set the Auto-Enable output after remote shutdown (default is Disable)

• Set the Auto-Battery test to 8, 12, 16, 20, or 26 weeks (default is 8 weeks)

• Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculated by Vertiv™ software products (default is zero)

• Select one of multiple output voltages to match various voltages.

Table 6.1 Output voltage option

UPS MODEL FACTORY DEFAULT SETTING OUTPUT VOLTAGE OPTION

All models 230 VAC 220V, 230V, 240V

NOTICE

The output voltage settings cannot be changed while the UPS is On and powering connected loads.

NOTE: This program is compatible with UPS models beginning with ‘GXT4,’ as in ‘GXT4-3000RT230.’ It is not compatible with earlier versions of the Liebert GXT UPS.

A computer running Microsoft® Windows 2000®, Windows XP®, Windows Vista®, Windows 7 or

Windows 8 is required to set up and run the configuration program.

Vertiv | Liebert GXT4 Installer/User Guide |

44

6.3 Terminal Block Communication

The Terminal Block includes eight pins, as shown the figure

Figure 6.1 Terminal-block communication pin layout

NO.

DESCRIPTION

1

2

3

4

Low battery warning

On-battery warning

Any mode shutdown

Battery mode shutdown

6.3.1 Any Mode Shutdown

The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter and static switch so that there is no power to the loads.

Any Mode Shutdown can be operated locally or remotely:

• Local Any Mode Shutdown can be performed by shorting the pins in terminal 3.

• Remote Any Mode Shutdown can be performed using a switch mounted at a remote location and connected to the pins in terminal 3.

NOTE: Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown, depending on the settings in the configuration program.

A current-limited source for this optocoupler (+12 VDC, 50 mA) will be available from the UPS.

The connection to the UPS for remote connection will be via terminal block connector.

Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations.

WARNING! When the Auto-Enable output option is selected and the UPS output is disabled using Any Mode Shutdown, the GXT4 output can turn On automatically and without warning if the connection is changed.

Vertiv | Liebert GXT4 Installer/User Guide |

45

6.3.2 Battery Mode Shutdown

Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active.

Battery Mode Shutdown can be performed locally or remotely:

• Local Battery Mode shutdown can be performed by shorting the pins in terminal 4.

• Remote Battery Mode Shutdown can be performed using a switch mounted in a remote location and connected to the pins in terminal 4.

NOTE: Remote Power Off will be performed by NO contact.

A current-limited source (+12 VDC, 50 mA) will be available from UPS.

The connection to the GXT4 for remote connection will be via terminal block connector.

Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.

This signal must last for 1.5 seconds or longer.

A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown timer. This timer cannot be stopped once triggered. If the mains power returns during this countdown, the GXT4 will still shut down and must remain shut down for 10 seconds. Whether the UPS turns back

On when the power is restored depends on the auto-restart setting.

6.3.3 On Battery

On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this dry contact will be closed.

6.3.4 Low Battery

Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery and has reached the Low Battery Warning time selected in the configuration program, this dry contact will be closed.

The rated values for the dry contacts for the On Battery and Low Battery signals are:

• Rated Voltage: 30 V (AC or DC)

• Rated Current: 300 mA

6.4 Remote Emergency Power Off

The UPS is equipped with a Remote Emergency Power Off (REPO) connector.

The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations.

Vertiv | Liebert GXT4 Installer/User Guide |

46

Figure 6.2 REPO switch connection diagram

1

2

NO.

DESCRIPTION

UPS ships with REPO jumper installed, allowing the UPS to operate.

Normally-closed switch system (fail-safe)

Opening the REPO connection disables the UPS.

Manual restart using the front panel is required after the REPO connection is closed again.

CAUTION: To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should be shielded and run separately from power cables.

Vertiv | Liebert GXT4 Installer/User Guide |

47

This page intentionally left blank.

Vertiv | Liebert GXT4 Installer/User Guide |

48

7 MAINTENANCE

This section describes replacing the internal battery pack, precautions, checking the UPS status and checking UPS functions.

WARNING! Risk of electric shock. Can cause equipment damage, injury and death. A battery can present a risk of electrical shock and high short-circuit current.

The following precautions should be observed when working on batteries:

• Remove watches, rings and other metal objects.

• Use tools with insulated handles.

• Wear rubber gloves and boots.

• Do not lay tools or metal parts on top of batteries.

• Disconnect charging source prior to connecting or disconnecting battery terminals.

• If the battery kit is damaged in any way or shows signs of leakage, contact your Vertiv™ representative immediately.

• Handle, transport and recycle batteries in accordance with local regulations.

• Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if grounds are removed during installation and maintenance (applicable to a UPS and a remote battery supply not having a grounded supply circuit).

7.1 Replacing the Internal Battery Pack

The GXT4 allows you to replace the internal battery pack safely. Refer to Table 7.1 below for internal

battery pack part numbers for GXT4:

Table 7.1 Replacement internal battery pack model number

UPS MODEL NUMBER

REPLACEMENT INTERNAL

BATTERY PACK MODEL NUMBER

QUANTITY REQUIRED

GXT4-5000RT230

GXT4-5000RT230E

GXT4-6000RT230

GXT4-6000RT230E

GXT4-10000RT230

GXT4-10000RT230E

GXT4-240VBATKIT

GXT4-240VBATKIT

GXT4-240RTBKIT

2

2

2

Vertiv | Liebert GXT4 Installer/User Guide |

49

7.1.1 Battery Replacement Procedures

Read all safety cautions before proceeding. A trained user can replace the internal battery pack when the

UPS is always in a restricted access location (such as a rack or server closet). Contact your local dealer or

Vertiv™ representative to obtain the pricing of the appropriate replacement battery pack.

CAUTION: Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to the instructions.

1. Remove the front plastic bezel cover from the UPS.

2. Loosen and remove the screws on the battery door, as shown in Figure 7.1 below.

3. Lay the battery door and screws aside for reassembly.

4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as

shown in Figure 7.1 below.

Figure 7.1 Removing the front bezel cover and battery door

1

2

3

NO.

DESCRIPTION

Screws, 6

Battery door

Front bezel

4

5

NO.

DESCRIPTION

Battery connector

Battery receptacle

Vertiv | Liebert GXT4 Installer/User Guide |

50

5. Grasp the battery handle, and pull the internal battery pack out of the UPS, as shown in the following figure.

Repeat this step if both battery packs will be replaced. Each model has two battery packs.

Figure 7.2 Pull out the battery

NO.

DESCRIPTION

1

2

Internal battery pack (one of two)

Battery handles

3 Pull out battery pack with handle.

6. Unpack the new internal battery pack. Take care not to destroy the packing.

Compare the new and old internal battery pack to make sure they are the same type and

model. If so, proceed with 7. If they are different, stop and contact your Vertiv™ representative,

or Technical Support.

7. Line up and slide in the new internal battery pack.

8. Reconnect the battery plug and battery receptacle.

9. Push the battery wire and internal battery pack back into the UPS.

10. Reattach the front battery door with the 6 screws.

11. Reattach the front plastic bezel cover to the UPS.

NOTE: The internal battery pack is hot-swappable. However, caution should be exercised because during this procedure the load is unprotected from disturbances and power outages. Do not replace the battery while the UPS is operating in Battery Mode. This will result in a loss of output power and will drop the connected load.

7.2 Battery Charging

The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their design life. The GXT4 charges the batteries continuously when it is connected to the utility input power.

If the GXT4 will be stored for a long time, We recommend connecting the UPS to input power for at least

24 hours every 4 to 6 months to ensure full recharge of the batteries.

Vertiv | Liebert GXT4 Installer/User Guide |

51

7.3 Precautions

Although the Liebert GXT4 is designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions:

• Turn Off and unplug the GXT4 before cleaning it.

• Wear rubber gloves and boots.

• Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.

• Never block or insert any objects into the ventilation holes or other openings of the GXT4.

• Do not place the GXT4 power cord where it might be damaged.

7.4 Checking UPS Status

We recommend checking the UPS operation status every six months.

• Check if the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm?

• Check if the UPS is operating in Bypass mode: Normally, the UPS operates in Normal Mode. If it is operating in Bypass Mode, stop and contact your local Vertiv™ representative or Technical

Support.

• Check if the battery is discharging: When the utility input is normal, the battery should not discharge. If the UPS is operating in Battery Mode, stop and contact your Vertiv™ representative or Technical Support.

7.5 Checking UPS Functions

NOTE: UPS function check procedures may interrupt power supply to the connected load.

We recommend checking the UPS functions once every 6 months.

Back-up the load data before conducting the UPS functions check. Procedures are as follows:

1. Press the Standby/Manual Bypass button to check whether the alarm and indicators are normal.

2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators are On and the UPS is operating normally.

3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode.

The UPS should initiate battery self-test. Check to determine whether the battery is operating normally. If not, stop and contact your Vertiv™ representative or Technical Support.

Vertiv | Liebert GXT4 Installer/User Guide |

52

8 TROUBLESHOOTING

This section indicates various UPS symptoms you may encounter and provides a troubleshooting guide in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation.

8.1 UPS Symptoms

The following symptoms indicate the GXT4 is malfunctioning:

• The relative indicators illuminate, indicating the UPS has detected a problem.

• An alarm buzzer sounds, alerting the user that the UPS requires attention.

8.1.1 Indicator and LCD

In addition to the fault indicator being illuminated, the LCD will display the fault. The displayed fault on the LCD is described in the following table

Table 8.1 Description of displayed faults

DISPLAYED FAULT CAUSE CORRECTIVE STEPS

Contact technical support.

UPS self test failed

UPS shutdown command received

UPS overload

Inverter Out of Order

Battery Weak/Bad

Output Short Circuit

The battery is bad or weak.

The UPS shuts down through communication.

The UPS is overloaded.

The inverter is faulty.

The battery is bad or weak.

The output connection is short-circuited.

Contact customer service.

Reduce the load and contact technical support.

Contact technical support.

Replace the battery.

Shut down the equipment and contact technical support.

Contact technical support.

DC Bus Overvoltage

UPS Overtemperature

Charger Out of Order

Fan Out of Order

DC Bus Discharge Fail

The DC bus is faulty.

Over-temperature occurs to the UPS and the UPS will transfer to

Bypass mode.

The charger is faulty.

At least one fan is faulty.

A DC-DC failure occurs.

Reduce the load and contact technical support.

Contact technical support.

Contact technical support.

Contact technical support.

NOTE: If the UPS encounters a fault and no correction attempt is performed within 2 minutes, the LCD backlight will flash (on 1 second and off 1 second) as an alert.

Press any button to exit the alert mode. If no correction attempt is performed on the UPS, the LCD back light will flash again until the UPS fault is corrected.

Vertiv | Liebert GXT4 Installer/User Guide |

53

8.1.2 Audible Alarm

An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS operating status. The audible alarm will sound as described in the following table.

Table 8.2 Audible alarm description

CONDITION ALARM

Battery discharge

Low battery

UPS fault, load on bypass

UPS fault, no power to load

Overload

Half-second beep every 10 seconds

Two half-second beeps every 5 seconds

1-second beep every 4 seconds

Continuous

Half-second beep every half second

Battery replacement

Battery loss

2-second beep every 2 minutes

Continuous

Wiring problem (loss of proper grounding for UPS) Continuous

Bypass reminder 1-second beep every 60 seconds

8.2 Troubleshooting UPS Issues

In the event of an issue with the UPS, refer to the following table to determine the cause and solution. If the fault persists, contact Vertiv™ Technical Support. See

Technical Support on page 63

Table 8.3 Troubleshooting table

PROBLEM CAUSE SOLUTION

UPS is short-circuited or overloaded

UPS fails to start

Batteries are not charged enough or not connected

Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally.

Check to ensure the internal battery is connected. If it is not, make the connection and try to start the unit. If the battery is connected, leave the UPS connected to input power for 24 hours to recharge batteries, then try to start the unit.

Battery indicator is illuminated

UPS has reduced battery backup time

Battery indicator is flashing.

Bypass indicator is flashing.

UPS is not plugged in

UPS input protection fuse has blown/opened

UPS is operating from battery mode. Ensure UPS is securely plugged into the wall receptacle.

UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then restart UPS.

Mains power is out of tolerance

UPS is operating from battery mode. Save data and close applications. Ensure mains supply voltage is within acceptable limits for UPS.

Batteries are not fully charged Keep UPS plugged in continuously at least 24 hours to recharge batteries.

UPS is overloaded Check load level indicator and reduce the load on the UPS.

Batteries may not be able to hold a full charge due to age

Replace batteries. Contact your local dealer, Vertiv™ representative or Technical Support for replacement battery kit.

Battery source is not available; continuous horn.

Check battery connections, completely power down and restart UPS.

NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed.

Because the voltage or frequency is outside acceptable limits, the bypass is disabled.

The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this indicator will flash, indicating that the bypass is unavailable.

Vertiv | Liebert GXT4 Installer/User Guide |

54

When reporting a UPS issue to Vertiv™, include the UPS model and serial number. These are located in several places for your ease of location:

• on the top panel (rack mount orientation)

• the left side (tower orientation)

• the rear panel

• on the front of the unit behind the front plastic bezel

• on the LCD select Main Menu > About.

Vertiv | Liebert GXT4 Installer/User Guide |

55

This page intentionally left blank.

Vertiv | Liebert GXT4 Installer/User Guide |

56

9 SPECIFICATIONS

Table 9.1 Specifications

MODEL NUMBER

GXT4-5000RT230

GXT4-5000RT230E

5000VA/4000W RATING

Dimensions, mm (in)

Unit, W x D x H

Shipping, W x D x H

GXT4-6000RT230

GXT4-6000RT230E

6000VA/4800W

430 x 574 x 217

(16.9 x 22.4 x 8.5)

516 x 745 x 530

(20.3 x 29.3 x 20.9)

Weight, kg (lb)

Unit

Shipping

Input AC Parameters

Operating Frequency, Nom

Factory Default VAC

User-Configurable VAC

Operating Voltage Range Without Battery

Operation

Maximum Allowable VAC

Input Frequency Without Battery Operation

60 (132.2)

75 (165.4); “E” model 71 (156.5)

GXT4-10000RT230

GXT4-10000RT230E

10,000VA/9000W

430 x 581 x 261

(16.9 x 22.9 x 10.3)

530 x 745 x 563

(20.9 x 29.3 x 22.2)

70 (154.3)

96 (211.6); “E” model 92 (202.8)

50 or 60Hz (Factory Default is 50)

230VAC

220/230/240VAC

(May be modified using included configuration program)

176 - 280VAC

280VAC

40 - 70Hz

PD2-CE6HDWRMBS Standard

(See 1.4 - Removable Power Distribution Box)

PD2-CE10HDWRMBS Standard

(See 1.4 - Removable Power Distribution Box)

Input Power Connection

Output AC Parameters

AC-AC Efficiency

Factory Default VAC

Output Connections

92% AC-AC

230VAC

PD2-CE6HDWRMBS Standard

(See 1.4 - Removable Power Distribution Box)

50Hz or 60Hz, Nominal

PD2-CE10HDWRMBS Standard

(See 1.4 - Removable Power Distribution Box)

Sinewave

>200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10 seconds; 105 - 130% 1 minute

Frequency

Waveform

Main Mode Overload

Internal Battery Charger

Charger Current, Amperes

Battery Parameters

Type

Quantity x V

Battery Mfr. / Part #

Backup Time

1.3

2.6

Valve-regulated, non-spillable, lead acid

20 x 12V

5AH battery, CSB HR1221W or YUASA NPH5-12

9AH battery, CSB UPS12460F2 or CSB

HR1234WF2

See Table 9.4 on page 59

Vertiv | Liebert GXT4 Installer/User Guide |

57

Table 9.1 Specifications (continued)

MODEL NUMBER

RATING

Recharge Time (Internal Batteries)

Bypass Protection Limits

Disable Bypass Operation

Re-Enable Bypass Operation

Disable Bypass operation

Environmental

Operating Temperature, °C (°F)

Storage Temperature, °C (°F)

Relative Humidity

Operating Elevation

Audible Noise

Agency

Safety

EMI/EMC/C-Tick EMC

ESD

Radiated Susceptibility

Electrical Fast Transient

Surge Immunity

Transportation

GXT4-5000RT230

GXT4-5000RT230E

GXT4-6000RT230

GXT4-6000RT230E

GXT4-10000RT230

GXT4-10000RT230E

5000VA/4000W 6000VA/4800W 10,000VA/9000W

5 hr. to 90% capacity after full discharge into 100% load

If input voltage exceeds ±15% of the nominal voltage

If input voltage returns to within ±10% of nominal output voltage

When the input frequency prevents synchronous operation

0 to 40 (32 to 104) (no derating)

-15 to 50 (5 to 122)

0-95% non-condensing

Up to 1000m (3281 ft) at 25°C (77°F) without derating

<55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides

IEC62040-1:2008 version, GS mark

IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)

IEC/EN EN61000-4-2, Level 4, Criteria A

IEC/EN EN61000-4-3, Level 3, Criteria A

IEC/EN EN61000-4-4, Level 4, Criteria A

IEC/EN EN61000-4-5, Level 3, Criteria A

ISTA Procedure 1E

Table 9.2 Power-distribution specifications

MODEL NUMBER: PD2-CE6HDWRMBS PD2-CE10HDWRMBS

Amp Rating

Input Power Connection

Output Power Connection

Includes:

32 Amps 63 Amps

Single-phase (L-N-G) hard-wired, 6-10mm2 (8-10AWG)

Single-phase (L-N-G) hard-wired, 6-10mm2 (8-10AWG)

Two IEC320 C19 16A/250V Sockets

Six C13 10A/250V Sockets

Manual Bypass Switch with Indicator Lamps

Four IEC320 C19 16A/250V Sockets,

Four C13 10A/250V Sockets

Manual Bypass Switch with Indicator Lamps

Input Branch Circuit

Breaker, Supplied by User

32A 63A

Vertiv | Liebert GXT4 Installer/User Guide |

58

Table 9.3 External battery cabinet specifications

MODEL NUMBER GXT4-240VBATT

USED WITH UPS MODEL

Dimensions, W x D x H, mm (in.)

Unit (with bezel)

Shipping

Weight, kg (lb)

Unit

Shipping

Battery Parameters

Type

Quantity x V

Battery Manufacturer, Part #

Backup Time

Environmental

Operating Temp, °C (°F)

Storage Temp, °C (°F)

Relative Humidity

Operating Elevation

Agency

Safety

Transportation

GXT4-5000RT230; GXT4-6000RT230; GXT4-10000RT230

430 x 581 x 173 (16.9 x 22.9 x 6.8)

530 x 745 x 475 (20.9 x 29.3 x 18.7)

65 (143.3)

80 (176.4); “E” models 76 (167.6)

Valve-regulated, non-spillable, lead acid

1 x 20 x 12V

9AH; CSB UPS12460F2 or CSB HR1234WF2

See Table 9.4 below

0 to 40 (32 to 104)

-15 to 50 (5 to 122)

0-95% non-condensing

Up to 1000m (3280.83 ft.) at 25°C (77°F)

IEC62040-1:2008 version

ISTA Procedure 1E

Table 9.4 Battery run times, minutes

NUMBER OF

BATTERIES/CABINETS

LOAD PERCENT OF

CAPACITY

Internal Battery

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

5KVA

24

18

14

95

42

36

29

12

11

9

230VAC RT MODELS

6KVA

17

13

11

86

38

31

23

9

7

7

10KVA

13

10

7

99

44

25

17

6

4

4

Vertiv | Liebert GXT4 Installer/User Guide |

59

Table 9.4 Battery run times, minutes (continued)

NUMBER OF

BATTERIES/CABINETS

LOAD PERCENT OF

CAPACITY

Internal Battery

+ 1 External

Battery Cabinet

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

5KVA

80

64

49

273

143

107

38

33

29

24

Internal Battery

+ 2 External

Battery Cabinets

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

146

119

94

476

254

191

72

63

56

47

Internal Battery

+ 3 External

Battery Cabinets

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

211

173

137

111

97

689

374

274

88

74

230VAC RT MODELS

6KVA

61

45

36

249

116

86

29

24

21

18

113

89

69

431

207

158

56

47

42

37

165

130

105

88

73

627

299

226

64

58

10KVA

44

34

26

209

105

63

21

17

14

12

76

56

44

327

164

103

37

29

24

22

105

82

65

53

43

450

221

141

37

33

Vertiv | Liebert GXT4 Installer/User Guide |

60

Table 9.4 Battery run times, minutes (continued)

NUMBER OF

BATTERIES/CABINETS

LOAD PERCENT OF

CAPACITY

Internal Battery

+ 4 External

Battery Cabinets

Internal Battery

+ 5 External

Battery Cabinets

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

1143

626

455

345

281

224

184

163

148

125

5KVA

277

225

182

910

499

363

148

130

118

100

230VAC RT MODELS

6KVA

216

173

141

824

397

297

118

99

90

82

1033

498

371

268

213

176

148

125

114

103

Internal Battery

+ 6 External

Battery Cabinets

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

1367

750

547

416

338

270

217

196

178

152

1248

601

448

322

256

210

177

151

138

124

Run times in this table are approximate. They are based on new, fully charged standard battery modules at a temperature of 25°C (77°F) with 100% resistive UPS loading. Run times listed above can vary by ±5% due to manufacturing variances of the batteries.

192

151

125

106

87

826

409

257

75

68

10KVA

134

106

85

574

282

179

71

57

48

43

164

129

106

695

345

217

87

74

60

55

Vertiv | Liebert GXT4 Installer/User Guide |

61

9.1 Auto-Learning Battery Run Times

As batteries age, the estimated run times may become less accurate. The Liebert GXT4 is programmed to

“learn” from a full battery discharge and modify the estimated run time for the measured battery capacity.

This can improve accuracy and compensate for aging batteries or batteries that operate at different ambient temperatures.

The UPS will update the anticipated run time calculation only under certain conditions.

• The UPS must have a steady load that is greater than 20%.

• The UPS must be at 100% charge at the start of a battery discharge.

• The battery discharge must continue uninterrupted until the batteries reach their end-ofdischarge voltage.

If all conditions are not met, the run time calculation will not be modified.

If the configuration program is used to change the number of battery cabinets, then the values in the battery above table will be restored. This will override any value that is auto-learned.

Vertiv | Liebert GXT4 Installer/User Guide |

62

APPENDICES

Appendix A: Technical Support

Our Technical Support staff is ready to assist you with any installation or operating issues you may encounter with your Liebert product. Please call or e-mail us:

Technical support: e: [email protected]

p: 1-800-222-5877 menu option 1

Monitoring support: e: [email protected]

p: 1-800-222-5877 menu option 2

Warranty support: e: [email protected]

p: 1-800-222-5877 menu option 3

Vertiv | Liebert GXT4 Installer/User Guide |

63

This page intentionally left blank.

Vertiv | Liebert GXT4 Installer/User Guide |

64

VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA

© 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.

SLI-23197_REV3_5-17/590-1367-501B