ACT ACTpro 1520 is a single-door IP controller that can be expanded to control up to 32 doors with ACTpro door stations. It has a built-in web server, supports DHCP/static IP addresses, voltage monitoring, break glass monitoring, and has status LEDs for easy monitoring. It also allows for entry and exit readers, reader short circuit protection, anti-passback, interlocking, and a USB connection for ACTWin software.
Advertisement
Advertisement
ACTpro 1520 Single Door IP Controller
with 12 V DC 2A power supply.
PSU Operating & Installation Instructions
18-00084
ACTpro 1520 PSU Operating and Installation Manual
This manual refers to the ACTpro 1520 controller. The ACTpro 1520 includes an ACTpro 1500 with an integrated 12 V DC 2A power supply. Access Control Technology Ltd. reserve the right to change the contents of this manual and the system it applies to without prior notice.
While every effort has been taken by ACT to ensure the accuracy of the information contained within this document, ACT assumes no responsibility for any errors or omissions. No liability is assumed for damages resulting from the use of information contained within this document.
Access Control Technology
Unit C1, South City Business Centre,
Tallaght, Dublin 24, Ireland.
Tel: +353-1-4662570 - UK
LoCall: 0845 300 5204
Fax: +353-1-4662570
Web: www.accesscontrol.ie
E-mail: [email protected]
Copyright
2012 Access Control Technology Ltd.
ACTpro 1520 PSU Operating and Installation Manual
Introduction
The ACTpro 1520 is a single door IP controller, the ACTpro 1520 includes an ACTpro
1500 controller with an integrated 12 V DC 2A power supply. It expanded to 32 doors with
ACTpro 120 or ACTpro 100e door stations.
The power supply is capable of delivering the full rated 2A current to the load and has an additional 0.5A for charging the battery.
ACTpro 1520 Features and Specification:
Features:
Controls up to 32 doors
Built-in web server (only for use with single ACTpro 1500)
DHCP / Static IP addresses
Voltage monitoring
Break glass monitoring
NetBIOS name
Status LED‟s
Space for cable management
Entry & exit readers
Reader short circuit protection
Anti-passback
Interlocking
USB connection for ACTWin software
TCP/IP connection for ACTWin software or Web Browser
Main relay for door control / AUX relay for alarm monitoring
Supports all ACTpro readers (RFID 125KHz, MIFARE Classic, DESFire EV1)
Capabilities
Number of doors
Number of Users
User Groups
Time Zones
Door Groups
Log Events
1 (expandable to maximum of 32)
15,000 (2 credentials per user)
250
250
250
5000
Browser Compatibility
Technical Details:
Relay contact rating
Indoor use only
Microsoft Internet Explorer 8 or 9, Firefox Version 8.0
Main relay 5A / 50 Vac, AUX relay 1A / 50 Vac
ACTpro 1520 PSU Operating and Installation Manual
Electrical Specification:
Input Voltage 220-240 V AC
Frequency
Input Fuse
Output Voltage
Max Load
Electronic Output fuse
Battery Current
Battery Protections
47-53 Hz
625mA 250V anti-surge fuse
13.65V (+/- 2%)
2A
Yes
≈ 0.5A for a battery discharged to ≈ 10V
Deep discharge/Over charge/Reverse polarity
Physical Specification:
Operating Tempature -10 to +50 degrees C
Dimensions (H/W/D)
Weight
255mm/233mm/86mm
2.450Kg
PSU Output Voltage:
12V DC The power supply provides two 12V outputs. One pre-wired to power the ACTpro 1500 controller.
The full load current of 2A is shared between the two outputs.
However the total current from both outputs must not exceed 2A.
Monitoring:
Mains present The PSU MAINS PRESENT output is pre-wired to the MAINS
PRESENT input of the ACTpro controller.
Output Voltage The PSU output voltage level is reported to the ACT PC software and via the web browser.
Tamper
Note:
The enclosure lid is tamper monitored.
All faults including MAINS Present and Tamper are reported on the
ACT Software and via the web browser on the ACTpro 1520 and
1500 controller
ACTpro 1520 PSU Operating and Installation Manual
LED indicators:
Green - AC OK Indicates that the AC Mains is within specification.
Amber
– Powered By Battery Indicates that the battery is supplying the output voltage.
Red - Fuse Fault Indicates electronic output shutdown fuse is active and that no power is being supplied to the load.
The maximum current that the PSU can guarantee is 2A.
Beyond this the fuse will trip and the LED will stay on until the load is fully disconnected.
Once the load has been disconnected, remove devices to reduce the current demand below 2A.
It is important for the installer to calculate the power budget adequately. Please refer to the section titled
„Power Budget‟ for more information.
Installation Instructions:
The ACTpro 1520 is for indoor installation only and must be installed as permanently connected equipment.
This equipment must be earthed and an RCD/Earth Fault device must be fitted.
An external disconnect device must be fitted. Before installation ensure that the mains supply to the ACTpro 1520 is disconnected.
Mains power should be connected to the ACTpro 1520 by a licensed electrician in accordance with local/national codes.
Mounting.
Mount the ACTpro 1520 directly on to the wall with the supplied screws.
The keyed mounting hole should be screwed first to the wall to aid the mounting. The unit should be installed in a ventilated area that allows for accessibility after installation.
ACTpro 1520 PSU Operating and Installation Manual
Mains Power up.
Attach the correctly rated mains cable and fasten using the cable ties.
Use an approved external mains disconnect device.
Apply mains power, check the “AC OK” LED is on and measure the voltage at the output.
Battery insertion.
Disconnect the mains.
Ensure the battery has enough charge to supply the load.
Connect the red battery lead to the + battery terminal and the black lead to the – terminal.
Apply the mains power and check the “AC OK” Green LED is illuminated.
Remove the mains power and check that the “Powered By Battery” Amber led illuminated.
If the Amber led is illuminated the battery is now supplying the output.
Reapply the mains power, the “AC OK” Led will illuminate and the “Power By Battery” led will extinguish.
Power Budget.
The ACTpro 1520 can supply up to 2A to power the access control system. The ACTpro
1500 requires 250mA leaving a balance of 1750mA to power the remainder of the system.
A complete access control system will require readers and a lock mechanism all of which will require power.
The following table should be used for calculating the power budget.
ACTpro 4000 Controller
ACTpro 1500 Controller
ACTpro 100e Door Station
ACTpro-X reader (1030/1040/1040/1050/1060)
ACTPro mifare reader (1030/1040/1040/1050)
Typical Mag Lock (consult your supplier)
400mA
250mA
120mA
50mA
50mA
800mA
ACTpro 1520 PSU Operating and Installation Manual
Ordering Information:
Product description ACT Product Code
Controller
ACTpro 1500
ACTpro 1520
ACTpro 100e
ACTpro 120
Readers
ACT RFID
ACTpro 1030e
ACTpro 1040e
ACTpro 1050e
ACTpro 1060e
ACTpro-X 1030PM
ACTpro 1030e VR
ACTpro MIFARE
ACTpro MIFARE 1030e
ACTpro MIFARE 1040e
ACTpro MIFARE 1050e
ACTpro MIFARE 1060e
ACTpro-X MIFARE 1030PM
ACTpro 1030e VR
ACTpro DESFire EV1
ACTpro DESFire EV1 1030e
ACTpro DESFire EV1 1040e
ACTpro DESFire EV1 1050e
ACTpro DESFire EV1 1060e
ACTpro-X DESFire EV1 1030PM
ACTpro 1030e VR
Cards and Fobs
ACT RFID ISO-B
ACT RFID FOB-B
ACTpro MIFARE Card
ACTpro MIFARE Fob
ACTpro DESFire EV1 Card
ACTpro DESFire EV1 Fob
Software
ACTWin pro
Communications
ACT USB Mini 5m
Single door IP controller expandable to 32 doors with ACTpro door stations
ACTpro 1500 contoller with integrated 12 V DC 2amp power supply
Single door station
ACTpro 100e door stations with integrated 12 V DC 2amp power supply
ACT RFID slimline, proximity reader, IP67
ACT RFID Surface / Flush, proximity reader, IP67 rated
ACT RFID Surface/ Flush, PIN & proximity reader, IP67
ACT PIN only reader
Panel mount multi-format proximity reader, IP67
Vandal Resistant cover for the ACTpro 1030e
ACT RFID slimline, proximity reader, IP67
ACT RFID Surface / Flush, proximity reader, IP67 rated
ACT RFID Surface/ Flush, PIN & proximity reader, IP67
ACT PIN only reader
Panel mount multi-format proximity reader, IP67
Vandal Resistant cover for the ACTpro 1030e
ACT RFID slimline, proximity reader, IP67
ACT RFID Surface / Flush, proximity reader, IP67 rated
ACT RFID Surface/ Flush, PIN & proximity reader, IP67
ACT PIN only reader
Panel mount multi-format proximity reader, IP67
Vandal Resistant cover for the ACTpro 1030e
ACT RFID Batch Cards
ACT RFID Batch Fobs
ACT MIFARE 1K Cards
ACT MIFARE 1K Fobs
ACT DESFire EV1 Cards
ACT DESFire EV1 Fobs
PC application software
5M mini USB cable
ACTpro 1520 PSU Operating and Installation Manual
ACT Contact Details:
Tel: +353-1-4662570
UK LoCall: 0845 300 5204
Fax: +353-1-4662570
Web: www.accesscontrol.ie
E-mail: [email protected]
E-mail: [email protected]
Certifications:
The ACTpro 1520 complies with the following European directives 2004/108/EC and EN60950-1
Advertisement