1. Change to read: 10/12 Continuous Non

1. Change to read: 10/12 Continuous Non
1.
Change to read: 10/12 Continuous Non-Overlapping Cycles.
a.
changed in doc - if I redo the pdf it will delete all my comments. see 2nd doc attached. mpm
1 In This Document| Elspec
IN THIS DOCUMENT
I.
Input Characteristics.................................................................................................................... 3
II.
BLACKBOX Web Interface Display .................................................................................................... 4
III.
Measurement Range, Resolution & Accuracy ..................................................................................... 10
IV.
Measurement Method ................................................................................................................. 12
V.
General Specifications................................................................................................................ 15
VI.
PQZIP Recording ....................................................................................................................... 17
VII. Physical ................................................................................................................................. 18
VIII. Dimensional View...................................................................................................................... 19
VIII.1
G4410 ........................................................................................................................... 19
VIII.2
G4420 & G4430 ............................................................................................................... 19
IX.
Multi IO Module ........................................................................................................................ 20
IX.1
Physical ........................................................................................................................ 22
IX.2
Dimensional View............................................................................................................. 22
IX.2.1
Expansion Option A - G4K With One Multi I/O Module .............................................................. 22
IX.2.2
Expansion Option B - G4K With Two Multi I/O Modules ............................................................ 22
2 In This Document| Elspec
I.
Input Characteristics
VOLTAGE INPUTS
G4410
G4420
G4430
Number of Inputs
AC: 4 (3 Phase &
Neutral)
AC: 4 (3 Phase &
Neutral)
AC: 4 (3 Phase &
Neutral)
Maximum Input Voltage (VRMS)
1KV
1KV
1KV
Nominal Voltage Range (VRMS)
110 to 690V
110 to 690V
110 to 690V
Maximum Peak Measurement Voltage (VPk)
8kV
8kV
8kV
Input Impedance
3MΩ
3MΩ
3MΩ
Bandwidth
6.25kHz
12.5kHz
25kHz
Nominal Frequency
42.5 to 69Hz
42.5 to 69Hz
42.5 to 69Hz
CURRENT INPUTS
G4410
G4420
G4430
Number of Inputs
AC: 4 (3 Phase &
Neutral)
AC: 4 (3 Phase &
Neutral)
AC: 4 (3 Phase &
Neutral)
Nominal Full Scale (IRMS)
5A
5A
5A
Maximum Peak Measurement (IPk)
50A
50A
50A
Range
0 to 50A
0 to 50A
0 to 50A
Burden
0.1mVA @ 5A
0.1mVA @ 5A
0.1mVA @ 5A
Bandwidth
6.25kHz
6.25kHz
6.25kHz
SAMPLING SYSTEM
G4410
G4420
G4430
Voltage
256 Samples/Cycle
512 Samples/Cycle
1024/512
Samples/Cycle
Current
256 Samples/Cycle
256 Samples/Cycle
256/512
Samples/Cycle
Type of Analog to Digital Converter
16/20 1 Bit
16/20 1 Bit
16/20 1 Bit
Resolution
Dual Range Gain of 2 x 16 Bit on 8 Channels
PLL Synchronization
1024 Samples on 10/12 Cycles According IEC61000-4-7
Maximum Sampling Rate for Each
Channel Simultaneously:
1
Effective Bit
3 Input Characteristics | Elspec
II.
BLACKBOX Web Interface Display
REAL-TIME DATA
Total Measurements
Summary
Available in Monitoring >> Summary

Frequency

Current (Current Single Phase System/ Current Averaged Over All 3
Phases in 3 Phase System)

Line to Line Voltage (Averaged Over All 3 Phases)

Line to Neutral Voltage (Averaged Over All 3 Phases)

Total System Power Factor (Over 3 Phases)

Phase Order (Voltage Phase Order From V1 Moving Clockwise)
Synchronization Status

Time Synchronization

DSP Synchronization
10/12 Cycles
According to IEC 61000-4-30. Minimum, Maximum & Average Values of:
Available in Monitoring >> Voltage & Current

RMS (Voltage & Current)

THD (Voltage & Current)

Crest Factor (Voltage & Current)

K Factor (Current)

TDD (Current)

THD Even/Odd (Voltage & Current)

Over/Under Deviation (Voltage)

Unbalance (Voltage & Current)
150/180 Cycles, 10 Minutes, 2 Hours
Aggregation
According to IEC 61000-4-30:

Frequency 10 Seconds
Available in Monitoring >> Average

RMS (Voltage)

Over/Under Deviation (Voltage)

Unbalance (Voltage & Current)
Power
Per Phase & Total:
Available in Monitoring >> Power

Active Power

Reactive power

Apparent Power

True Power Factor

Displacement Power Factor
4 BLACKBOX Web Interface Display | Elspec
REAL-TIME DATA
Temperature
Displays Average, Minimum & Maximum Values of:
Available in Monitoring >> Temperature

Internal Temperature (DSP Module)

External Temperature (Outside via PT100)

PSU Temperature (Power Supply Module)
Phasor
Shows Real Time Phasor Diagram:
Available in Monitoring >> Phasors

Voltage & Current (Depending on the Power Configuration.
Select Combinations - Phase to Phase, Phase to Line Voltage &
Current)

Normalize (Vector Part of the Largest Vector)

Amplitude (Per Phasor)

Angle (Relative to V1/V12 - Depending on the Network
Topology)
Exportable to: MetaFile, BMP, JPG, PNG, Text/Data
Waveform Display
Captures Waveforms Up To 11 Channels – By:
Graph / Table / Both

Cycle Selection (1 to 4 Cycles)
Available in Monitoring >> Waveform

Voltage & Current (Depending on Power Configuration: Select
Combinations - Phase to Phase, Phase to Line Voltage & Current)
Exportable to: MetaFile, BMP, JPG, PNG, Text/Data
Voltage Flickering
Available in Monitoring >> Voltage Flickering
Aggregation:

PSTINST to PST 2 Seconds (Instantaneous Flicker Evaluation)

PSST 10 Seconds (As per PSST Averaged over 10 Seconds)

PST 10 Minutes (According to IEC61000-4-15, Short Term Flicker
Evaluation)

SPLT – PLT 1 Hour

PLT 2 Hours (According to IEC61000-4-15, Long Term Flicker
Evaluation)

LPLT 10 Hours (PLT Averaged over 10 Hours)

LPLT 1 Day (PLT Averaged over 1 Day)

LPLT 7 Days (PLT Averaged over 7 Days)
5 BLACKBOX Web Interface Display | Elspec
REAL-TIME DATA
Pinst Waveform
Displays Voltage Instantaneous Flicker Waveforms
Graph / Table / Both
Exportable to: MetaFile, BMP, JPG, PNG,Text/Data
Available in Monitoring >> Pinst Waveforms
Minimum / Maximum Flickering
Available in Monitoring >> Min/Max Flickering
Displays Minimum / Maximum Short & Long Term Voltage Flickering
Values:

PST INST – PST 2 Seconds (Instantaneous Flicker Evaluation)

PSST 10 Seconds (As per PSST Averaged over 10 Seconds)

PST 10 Minutes (According to IEC61000-4-15, Short Term Flicker
Evaluation)

SPLT – PLT 1 Hour

PLT 2 Hours (According to IEC61000-4-15, Long Term Flicker
Evaluation)

LPLT 10 Hours (PLT Averaged over 10 Hours)

LPLT 1 Day (PLT Averaged over 1 Day)

LPLT 7 Days (PLT Averaged over 7 Days)
Voltage & Current Harmonics
According to IEC61000-4-7:
Bar Graph / Table / Both

10/12 Cycles Harmonics & Inter-Harmonics (Voltage & Current)
Available in Monitoring >> V&I Harmonics

150/180 Cycles Harmonic & Inter-Harmonics (Voltage Only)

10 Minutes Harmonics & Inter-Harmonics (Voltage Only)

2 Hours Harmonics & Inter-Harmonics (Voltage Only)

Harmonic Angles (Voltage & Current)
Harmonics Display:

Real Values

Values Relative to the Fundamental Harmonic
Exportable to: MetaFile, BMP, JPG, PNG, Text/Data
Power Harmonics
According to IEC61000-4-7:
Bar Graph / Table / Both

Active Power Harmonics
Available in Monitoring >> P&Q Harmonics

Reactive Power Harmonics
Exportable to: MetaFile, BMP, JPG, PNG, Text/Data
6 BLACKBOX Web Interface Display | Elspec
REAL-TIME DATA
Spectrum
Voltage & Current Spectrum Display:
Bar Graph / Table / Both

Available in Monitoring >> Spectrum
Exportable to: MetaFile, BMP, JPG, PNG, Text/Data
Harmonics Table
According to IEC61000-4-7:
Available in Monitoring >> Harmonics Table

10/12 Cycles Harmonics & Inter-Harmonics (Voltage & Current)

150/180 Cycles Harmonic & Inter-Harmonics (Voltage Only)

10 Minutes Harmonics & Inter-Harmonics (Voltage Only)

2 Hours Harmonics & Inter-Harmonics (Voltage Only)

Harmonic Angles (Voltage & Current)
Harmonics Relative to the First Harmonic up to 11 Channels
Harmonics Display:

Real Values

Values Relative to the Fundamental Harmonic
V/I, Minimum & Maximum Harmonics Table
Summarizes V/I Minimum / Maximum Harmonic Values:
Available in Monitoring >> V/I Min/Max
Harmonics

Harmonic Angles (Voltage & Current)

Harmonic Amplitude Values (Voltage & Current)
PQ Minimum & Maximum Harmonics Table
Available in Monitoring >> V/I Min/Max
Harmonics
According to IEC61000-4-7:

Active Power Harmonics

Reactive Power Harmonics
7 BLACKBOX Web Interface Display | Elspec
ENERGY DATA
Consumption & Demand Table
Summary Amount & Makeup of the Net Energy (Received & Delivered):
Available in Energy >> Consumption &
Demand

Net Consumption

Demand

Peak Demand
Energy Flow:

Active Energy (Real Energy in kWh)

Reactive Energy (Volt Amperes Reactive Energy in kVArh)

Apparent Energy (Volt Amperes Reactive Energy in kVArh & Energy
kVAh)
Detailed Information Table
Detailed Amount & Makeup of the Energy Flow:
Available in Energy >> Detailed Information

Current Period

Total Consumption

Demand

Peak Demand
Energy:

Received Energy (Active & Reactive)

Delivered Energy (Active & Reactive)

Generated Energy (Active & Reactive)

Net Energy, Received & Delivered (Active & Reactive)

Total Energy, Received & Delivered (Active, Reactive & Apparent)
Measurement Status Summary Table
Summary with Additional Statistics & Context on Energy:
Available in Energy >> Measurement Status

Started (Date & time stamp when the Energy Meter was originally
activated for the very first time)

Last Start (Date & Time Stamp from the Last Energy Meter Reset)

Up Time (Total Cumulative Operational Time of Energy Meter
Since Last Start)

Down Time (Total Cumulative Time Energy Meter was Inoperative)

Availability (Actual Operational Time of Energy Meter)

Energy (Metering) Interval

Sliding Window (Averaging System In Use):

Enable (Energy is Calculated Using Sliding Interval for Each Energy
Meter)

Disable (Energy is Calculated Using Fixed Interval for Each Energy
Meter)
8 BLACKBOX Web Interface Display | Elspec
POWER QUALITY DATA
Compliance Summary Table
Compliance Standard Status & Summary:
Available in Power Quality >> Summary

Event Status (Pass / Fail)

Compliance Summary
Built in Multi-standard compliance, with support for EN50160 &
other National Standards:
Available in Configuration >> PQ Compliance
Compliance Info Table
Supplies Detailed Compliance Info:
Available in Power Quality >> Information

Compliance Criteria

PQ Compliance
Built in Multi Standard Compliance, with support for EN50160 &
other National Standards:
Available in Configuration >> PQ Compliance
Compliance Chart
Displays Compliance Levels (Equals to % of Time OK):
Available in Power Quality >> Chart

PQ Compliance
Exportable to: MetaFile, BMP, JPG, PNG, Text/Data
Events
Displays Log of Configured PQ Events
Available in Power Quality >> Events
Configurable EN50160/Compliance Events (DIP/SWELL/VInterruptions)
(Available in Configuration >> PQ Compliance)
9 BLACKBOX Web Interface Display | Elspec
III.
Measurement Range, Resolution & Accuracy
VOLT/AMPS/HERTZ
MEASUREMENT RANGE
RESOLUTION
ACCURACY
VRMS (AC & DC)
0 to 900V
0.01V
±0.1% of Nominal Voltage1
ARMS
1 to 5A
0.1mA
±0.1% of Nominal Current
VPk
8KV
10mV
±0.1% from Reading
Voltage Crest Factor
1<
0.01
Better than 0.5%
Current Crest Factor
1<
0.01
Better than 0.5%
Hz to 50Hz Nominal
42.5 to 62Hz
10mHz
±5mHz
Hz to 60Hz Nominal
51 to 69Hz
10mHz
±5mHz
K-Factor
0<
0.01
±0.25%
DIPS, SWELLS & INTERRUPTIONS
MEASUREMENT RANGE
RESOLUTION
ACCURACY
VRMS½ (AC & DC)
0 to 900V
0.01V
±0.2% of Nominal Voltage
Duration
HHH,MM,SS,MMM
Half Cycle
One Cycle
Threshold Levels
Programmable Thresholds & Hysteresis in Percentage of Nominal Voltage
Event Detection Based Upon ½ Cycle RMS Voltages
Captures Dips, Swells, Interruptions & Rapid Voltage Changes
VOLTAGE HARMONICS
MEASUREMENT RANGE
Harmonic Order
1 to 50 Grouping: Harmonic Subgroups According to IEC61000-4-7
Inter-Harmonic Order
1 to 50 Grouping: Inter-Harmonic Subgroups According to IEC61000-4-7
THD
0 to 100%
0.01%
±0.25%
THD Even
0 to 100%
0. 01%
±0.25%
THD Odd
0 to 100%
0.01%
±0.25%
Hz (Spectrum)
0 to 3174Hz
fSys 10/12
±5%
Phase Angle
-180 to +180º
0.01º
±0.01º
1
(n=50)
For Nominal Voltage 80 to 690V
10 Measurement Range, Resolution & Accuracy | Elspec
RESOLUTION
ACCURACY
POWER & ENERGY
MEASUREMENT RANGE
RESOLUTION
ACCURACY
Active Power
±5kW x CT Ratio x PT Ratio
10mW
±0.2%
Reactive Power
±5kVAr x CT Ratio x PT Ratio
10mVAR
±2%
Apparent Power
±5kVA x CT Ratio x PT Ratio
10mVA
±0.2%
Active Energy
±5kWh x CT Ratio x PT Ratio
10mWh
±0.2%
Reactive Energy
±5kVArh x CT Ratio x PT Ratio
10mVArh
±2%
Apparent Energy
±5kVAh x CT Ratio x PT Ratio
10mVAh
±0.2%
True Power Factor
±1 (CAP\IND)
10µ
±0.2%
Displacement Power Factor
±1 (CAP\IND)
10µ
±0.2%
FLICKERING
MEASUREMENT RANGE
RESOLUTION
ACCURACY
PSST, PST 10 Minutes, SPLT, PLT 2
Hours, LPLT
0 to 20
0.01
±5%
PSTINST
0 to 20
0.01
±8%
UNBALANCE
MEASUREMENT RANGE
RESOLUTION
ACCURACY
Volts (Negative & Zero Seq.)
Ratio
0 to 100%
0.1%
0.15%
Current (Negative & Zero Seq.)
Ratio
0 to 100%
0.1%
0.5%
TRANSIENT CAPTURE
ACCURACY
Minimum Detection Duration
78.1 μs (G4410)
39 μs (G4420)
19.5 μs (G4430)
11 Measurement Range, Resolution & Accuracy | Elspec
IV.
Measurement Method
VRMS
= Number of Samples
= Specific Channel
10/12 Continuous Non-Overlapping Cycles
In Accordance with IEC61000-4-30
VRMS½ , ARMS½
Value Is Measured Over 1 Cycle, Commencing At a Fundamental Zero
Crossing, & Refreshed Each Half-Cycle. This Technique Is Independent
For Each Channel In Accordance With IEC61000-4-30
ARMS
= Number of Samples
= Specific Channel
10/12 Continuous Non-Overlapping Cycles
In Accordance with IEC61000-4-30
HRMS
= Number of Samples
= Specific Channel
10/12 Continuous Non-Overlapping Cycles
In Accordance with IEC61000-4-30
VPk, IPk
Absolute Highest Sample Value Within 10/12 Cycle Interval
V Crest Factor
Measures Ratio Between the VPK and VRMS
A Crest Factor
Measures ratio between the IPk & ARMS
Hz
Measured Every 10 Seconds in Accordance with IEC61000-4-30
THD
C = Harmonic RMS Value
n = Harmonic Order
THD Even
C = Harmonic RMS Value
n = Harmonic Order
THD Odd
C = Harmonic RMS Value
n = Harmonic Order
12 Measurement Method | Elspec
Harmonics
In Accordance With IEC61000-4-7
Inter-Harmonics
In Accordance With IEC61000-4-7
Watt
n = 2 to 50
VA
VAR
True Power Factor (PF)
QUADRAT
PF UNIT
I
+
+
+
IND
II
-
+
-
CAP
III
-
-
+
IND
IV
+
-
-
CAP
Displacement Power Factor (PF)
Same as True PF, But Only With Fundamental Components:
Unbalance
The Supply Voltage Unbalance is Evaluated Using the Method of
Symmetrical Components in Accordance with IEC61000-4-30
Zero Sequence Unbalance
Negative Sequence Unbalance
Positive Sequence
Defined as the symmetrical vector system derived by application of the
Fortescue’s transformation matrix, and that rotates in the same
direction as the power frequency voltage (or current):
U1 =
(U a +
Ub +
Uc) where
and Ua, Ub, Uc and are line to neutral voltages (fundamental
component)
In Accordance With IEC61000-3-13, ed. 1.0 (2008-02) Ref: 3.26.3
Negative Sequence
Defined as the symmetrical vector system derived by application of the
Fortescue’s transformation matrix, and that rotates in the opposite
direction to the power frequency voltage (or current):
U2 =
(U a +
Ub +
Uc) where
and Ua, Ub, Uc and are line to neutral voltages (fundamental
component)
In Accordance With IEC61000-3-13, ed. 1.0 (2008-02) Ref: 3.26.4
13 Measurement Method | Elspec
Zero Sequence
Defined as the in-phase symmetrical vector system derived by
application of the Fortescue’s transformation matrix:
U0 =
(U a +
Ub + Uc) where Ua, Ub, Uc and are line to neutral
voltages (fundamental component)
In Accordance With IEC61000-3-13, ed. 1.0 (2008-02) Ref: 3.26.5
Flicker
Five Block Digital Flickermeter as Described in IEC 61000-4-15 Edition 2.
Functional & Design Specification Includes 230V/50Hz, 230V/60Hz,
120V/50Hz, 120V/60Hz Lamp Models
Flicker PINST (Instantaneous Term
Flicker Evaluation)
Output of Block 5 of the Flickermeter in Accordance with IEC61000-4-15
Edition 2
Flicker PST (Short Term Flicker
Evaluation)
The Standard Measurement Time For
is 10 Minutes:
Where the Percentiles
, , ,
,
are the Flicker Levels
Exceeded for 0.1, 1, 3, 10 & 50% of the Time During The Observation
Period. The Suffix “s” in the Formula Indicates that the Smoothed Value
Should be Used. The Smoothed Values are Obtained Using the Following
Formulas:
P(1s) = (P(.7) + P(1) + P(1.5))/3
P(3s) = (P(2.2) + P(3) + P(4))/3
P(10s) = (P(6) + P(8) + P(10) + P(13) + P(17))/5
P(50s) = (P(30) + P(50) + P(80))/3
Flicker PLT (Long Term Flicker
Evaluation)
The Long-Term PLT is Derived From the Short-Term Values Over 12 ShortTerm Values of 10 Minutes Each Over a Period of 2 hours:
Where
(i = 1, 2, 3, ...) are the Consecutive Readings of the
K-Factor
Where
14 Measurement Method | Elspec
is the Harmonic #, and
is the RMS value of the
TH
Harmonic
V.
General Specifications
STORAGE CAPACITY
G4410
G4420
G4430
Internal Memory
128MB
4GB
16GB
REAL-TIME (SELF SYNCHRONIZATION)
Real Time Clock
± 1 Second per 24 Hours
Time Synchronization
Optional GPS/SNTP/IRIGB/DCF-77 time sync module provides time
uncertainty better than 100μs. When synchronization becomes
unavailable, Time Tolerance is 1 second per day.
DEVICE SYNCHRONIZATION ACCURACY
GPS & PPS
IRIG B
1
Better than 100µs
100 to 200µs
DCF-77
±15ms
SNTP Server
50 to 100µs
COMMUNICATION
CONTROL
Web Server
Comprehensive web server for local & remote real-time
monitoring & control
FTP Server
Standard protocol for main storage memory
PORTS
G4410
G4420
G4430
Ethernet Ports
1
2
2
RS485/422
1
1
1
LAN 1
Baud Rate
10/100MBit
Communication Protocols
Modbus TCP, OPC, DNP3, TELNET & SMTP Client
Connector Type
RJ45 Female With Led Indicators
Power Over Ethernet (PoE- In)
1 (Available as Input – 13 Watt, DC: 48V)
LAN 2
Baud Rate
10/100MBit
Communication Protocols
Modbus TCP, OPC, DNP3, TELNET & SMTP Client
Connector Type
RJ45 Female With Led Indicators
Power Over Ethernet (PoE- Out)
1 (Available as Output - 13 Watt, DC: 48V)
RS485/422 CONNECTION
Baud Rate
Configurable: 1200 / 2400 / 4800 / 9600 / 14400 / 19200 / 38400
57600 / 115200
Communication Protocols
Modbus RTU, PPP & TTY
Duplex
Full
Maximum Cable Length
15.2m (50′)
1
Only if Multi I/O Module is present
15 General Specifications | Elspec
APPLICABLE STANDARDS
Measurement Standards
EN50160, IEEE1159, IEEE519, IEC61000-4-15, IEC61000-4-7,
IEC61000-4-30 Class A, IEC62053-22/23 Class 0.2
EMC Standards
EN55011 Group 1 Class A, EN60439-1 (Clauses 7.9.1, 7.9.3, 7.9.4,
7.10.3, 7.10.4), FCC Part 15 Subpart B Class A, IEC61000-3-3,
EN61000-6-2, IEC60255
Environmental Standards
IEC60068-2-1, 2, 6, 11, 27, 30, 75
Safety Standards
EN61010-1:2001 2ND Edition
POWER SUPPLY
Power Over Ethernet (PoE- In)1
According to 802.3af
Operating Range
AC: 100 to 260V @ 50/60Hz
DC: 100 to 300V
Auxiliary AC Supply
DC: 48V
Low Voltage Ride Through
Up to 25 Seconds
1
G4420 & G4430 Units Only
16 General Specifications | Elspec
VI.
PQZIP Recording
METHOD
PQZIP compression technology which enables continuous gap-less1 recording of all electrical parameters-related data
for a significant time duration without the need of event thresholds of any kind. Events, Flicker and Energy are noncompressed parameters.
WAVEFORM
G4410
G4420
G4430
Voltage Sampling per Cycle
256
512
1024/512
Current Sampling per Cycle
256
256
256/512
Recording Time
1 Day Continuous
Recording at a Fixed
Ratio Mode of 3GB/Month
3 Months Continuous
Recording at a Fixed
Ratio Mode of
1.2GB/Month
1 & Year Continuous
Recording at a Fixed
Ratio Mode of
1.2GB/Month
EVENTS
Memory
Up to 12K Event Logs
FLICKER PST
G4410
G4420
G4430
Recording Interval
10 Minutes
10 Minutes
10 Minutes
Recording Time
1 Day Continuous
Recording at a Fixed
Ratio Mode of 3GB/Month
3 Months Continuous
Recording at a Fixed
Ratio Mode of
1.2GB/Month
1 & Year Continuous
Recording at a Fixed
Ratio Mode of
1.2GB/Month
ENERGY
G4410
G4420
G4430
Energy Interval
1, 2, 5, 10, 15, 30 & 60
Minutes
1, 2, 5, 10, 15, 30 & 60
Minutes
1, 2, 5, 10, 15, 30 & 60
Minutes
Recording Time
1 Day Continuous
Recording at a Fixed
Ratio Mode of 3GB/Month
3 Months Continuous
Recording at a Fixed
Ratio Mode of
1.2GB/Month
1 & Year Continuous
Recording at a Fixed
Ratio Mode of
1.2GB/Month
1
99.9% of the Time
17 PQZIP Recording | Elspec
VII.
Physical
PHYSICAL
Dimensions
175mm x 232mm x137.5mm (6.88” x 9.13” x 5.41”)
Weight
1.7Kg (3.74Lb)
ENVIRONMENTAL
Design
Sleek black, shock proof, easy install, with Multi I/O extension
option
Drip and Dust Proof
IP20 according to IEC60529 when used in tilt stand position
Shock and Vibration
Shock 30g, Vibration: 3g Sinusoid, Random 0.03 g2/Hz according
to MIL-PRF-28800F Class 2
Operating Temperature
-20 to 70°C (-4 to 158°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Humidity
85%
Maximum Operating Altitude
2Km (1.24Mi)
Warranty
One Year
TEMPERATURE SENSORS
External Temperature Sensor (PT100)
-40 to 90°C (-40 to 210°F)
Internal PSU Temperature Sensor
Informative
Internal DSP Temperature Sensor
Informative
18 Physical | Elspec
VIII.
Dimensional View
VIII.1 G4410
VIII.2 G4420 & G4430
19 Dimensional View | Elspec
IX.
Multi IO Module
DIGITAL INPUTS
Channels
8
Sampling
800Hz @ 50Hz
960Hz @ 60Hz
Range
3 DC Options Ranging From 0 to 220V:
 3.3V, Vin < 48V
 <48 to 110V
 <110 to 220V (Requires Additional Resistor)
Pulse Type
KYZ, 0->1->0, 1->0->1
Isolation Connector
125V
DIGITAL OUTPUTS
Channels
4
Maximum Switching Voltage
AC: 35V; DC: 45V
Pulse Type
KYZ, 0->1->0, 1->0->1
ANALOG INPUTS
Channels
4
Sampling Rate
2Hz
Signal
4-20mA (Continuous DC)
Impedance
25Ω
Maximum Voltage (Common Mode)
270V
ANALOG OUTPUTS
Channels
4
Signal
4-20mA (Continuous DC)
Accuracy
0.1% (10 Bit D to A Resolution)
RELAY OUTPUT MODULE
Channels
3 x Change Over
Contact Configuration
1 CO (SPDT – Single Pole Double Throw)
Rated Voltage
AC: 250V
Maximum Switching Voltage
AC: 400V
Maximum Current
AC: 5A/250V; 10A/110V
DC: 5A/30V
Maximum Peak Current
15A
Rated Current
6A
Operating Time
4ms
Release Time
6ms
Maximum Reaction Time
10ms
Maximum Drop-out Time
4ms
Output Resistance
50MΩ
20 Multi IO Module | Elspec
RS232 CONNECTIONS
Baud Rate
Configurable: 1200 / 2400 / 4800 / 9600 / 14400 / 19200 / 38400
57600 / 115200
Duplex
Full
Supported Protocols
GPS
Connector Type
DB9 Male
Maximum Cable Length
15.2m (500’)
21 Multi IO Module | Elspec
IX.1 Physical
PHYSICAL
Dimensions
Expansion Option A – One Module
175mm x 232mm x 137.5mm (6.88” x 9.13” x 5.41”)
Expansion Option B – Two Modules
175mm x 232mm x 171mm (6.88” x 9.13” x 6.73”)
Weight
Expansion Option A – One Module
1.8Kg (3.96Lb)
Expansion Option B – Two Modules
1.9Kg (4.18Lb)
IX.2 Dimensional View
IX.2.1 Expansion Option A - G4K With One Multi I/O Module
IX.2.2 Expansion Option B - G4K With Two Multi I/O Modules
22 Multi IO Module | Elspec
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement