Installation Instructions

ArmorPoint 4-Channel 24V dc Analog Input

Module, Series A

Catalog Number 1738-IE4CM12

Topic

Important User Information

Environment and Enclosure

Prevent Electrostatic Discharge

About the Module

Mount the I/O Base

Install the Module

Remove the Module From the Mounting Base

Wire the Module

Communicate with Your Module

Interpret the Status Indicators

Specifications

5

6

3

4

Page

2

3

7

8

8

10

12

2 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls

(Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell

Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING

Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

IMPORTANT

ATTENTION

Identifies information that is critical for successful application and understanding of the product.

Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.

SHOCK HAZARD

Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.

BURN HAZARD

Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.

Publication

1738-IN024C-EN-P - March 2010

ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 3

Environment and Enclosure

ATTENTION

This equipment is intended for use in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating.

This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.

This equipment is supplied as enclosed equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication.

Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.

In addition to this publication, see:

• Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for additional installation requirements.

• NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure

Prevent Electrostatic Discharge

ATTENTION

This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment.

• Touch a grounded object to discharge potential static.

• Wear an approved grounding wriststrap.

• Do not touch connectors or pins on component boards.

• Do not touch circuit components inside the equipment.

• Use a static-safe workstation, if available.

• Store the equipment in appropriate static-safe packaging when not in use.

Publication

1738-IN024C-EN-P - March 2010

4 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A

ATTENTION

Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements.

ATTENTION

To comply with the CE Low Voltage Directive (LVD), all connected I/O must be powered from a source compliant with the following:

Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

About the Module

The ArmorPoint I/O family consists of modular I/O modules. The sealed

IP67 housing of these modules requires no enclosure. (Note that environmental requirements other than IP67 may require an additional appropriate housing.) I/O connectors are sealed M12 style. The mounting base ships with the module. The 1738-IE4CM12 module is shown below.

1738-IE4CM12

Connector M12-A

0

1738-IE4CM12/A

Analog Current In

1

MOD

NET

Connector M12-B

LED Indicators

Connector M12-C

2

3

2

3

0

1

Connector M12-D

Publication

1738-IN024C-EN-P - March 2010

44367

ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 5

Mount the I/O Base

Mount the I/O base on a wall or panel, using the screw holes provided in the base

.

IMPORTANT

The ArmorPoint I/O module must be mounted on a grounded metal mounting plate or other conductive surface.

Mounting illustration for the ArmorPoint adapter with I/O bases

Adapter

46.25 mm

(1.8 in)

51.9 mm

(2.0 in)

20.1 mm

(0.8 in)

51.9 mm

(2.0 in)

20.1 mm

(0.8 in)

51.9 mm

(2.0 in)

102 mm

(4.02 in)

56 mm

(2.2 in)

43769

Follow the instructions to install the mounting base.

1. Lay out the required points as shown above in the drilling dimension drawing.

2. Drill the necessary holes for M4 (#8) machine or self-tapping screws.

3. Mount the base using M4 (#8) screws.

4. Ground the system using the ground lug connection.

The ground lug connection is also a mounting hole.

Publication

1738-IN024C-EN-P - March 2010

6 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A

Mounting base

Set the keyswitch position to 3, for the

1738 analog input modules

Ground lug connection

Latching mechanism

43675

Install the Module

Follow the instructions to install the analog input module.

1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number 3 aligns with the notch in the base.

2. Position the module vertically above the mounting base.

The module bridges two bases.

Publication

1738-IN024C-EN-P - March 2010

ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 7

Module bridges two bases.

0

1738-IE4CM12/A

Analog Current In

1

MOD

NET

2

3

2

3

0

1

44368

3. Push the module down until it engages the latching mechanism.

You will hear a clicking sound when the module is properly engaged.

The locking mechanism locks the module to the base.

Remove the Module From the Mounting Base

Follow the instructions to remove the module from the mounting base.

1. Put a flat blade screwdriver into the slot of the orange latching mechanism.

2. Push the screwdriver toward the I/O module to disengage the latch.

The module lifts up off the base.

3. Pull the module off of the base.

Publication

1738-IN024C-EN-P - March 2010

8 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A

Wire the Module

1738-IE4CM12

(view into connector)

Pin 1 - 24V dc

Pin 2 - Input

Pin 3 - Common

Pin 4 - Common

Pin 5 - No Connect

44315

IMPORTANT

Analog modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.

ATTENTION

Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements.

Communicate with Your Module

I/O messages are sent to (consumed) and received from (produced) the

ArmorPoint I/O modules. These messages are mapped into the processor’s memory. These ArmorPoint I/O analog input modules produce 12 bytes of input data (scanner Rx) and fault status data. They do not consume I/O data

(scanner Tx).

Publication

1738-IN024C-EN-P - March 2010

ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 9

Default Data Map for the Module

1738-IE4CM12

Message size: 12 Bytes

Produces

(Scanner Rx)

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Input Channel 0 High Byte

Input Channel 1 High Byte

Input Channel 0 Low Byte

Input Channel 1 Low Byte

Input Channel 2 High Byte

Input Channel 3 High Byte

Status Byte for Channel 1

O

R

U

R

H

H

A

L

L

A

H

A

L

A

Status Byte for Channel 3

O

R

U

R

H

H

A

L

L

A

H

A

L

A

No consumed data

C

M

C

M

C

F

C

F

Input Channel 2 Low Byte

Input Channel 3 Low Byte

Status Byte for Channel 0

O

R

U

R

H

H

A

L

L

A

H

A

L

A

Status Byte for Channel 2

O

R

U

R

H

H

A

L

L

A

H

A

L

A

C

M

C

M

C

F

C

F

Consumes

(scanner Tx)

Where:

CF = Channel Fault Status, 0 = no error, 1 = fault

CM = Calibration Mode; 0 = normal, 1 = calibration mode

LA = Low Alarm; 0 = no error, 1 = fault

HA = High Alarm; 0 = no error, 1 = fault

LLA = Low/Low Alarm; 0 = no error, 1 = fault

HHA = High/High Alarm; 0 = no error, 1 = fault

UR = Underrange; 0 = no error; 1 = fault

OR = Overrange; 0 = no error; 1 = fault

Publication

1738-IN024C-EN-P - March 2010

10 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A

Interpret the Status Indicators

1738-IE4CM12

0

1738-IE4CM12/A

Analog Current In

1

MOD

NET

Module Status Indicator

Network Status Indicator

2

3

2

3

0

1

I/O Status Indicators

44367

Status Indicators

Indicator State

Module

Status

Off

Green

Flashing green

Flashing red

Red

Flashing red/green

Description

No power applied to device.

Device operating normally.

Device needs commissioning due to missing, incomplete, or incorrect configuration.

Recoverable fault.

Unrecoverable fault - may require device replacement.

Device is in self-test.

Publication

1738-IN024C-EN-P - March 2010

ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 11

Status Indicators (Continued)

Indicator State

Network

Status

Off

Flashing green

Green

Flashing red

Red

Flashing red/green

I/O Status Off

Solid green

Flashing green

Solid red

Flashing red

Description

Device is not on line:

- Device has not completed dup_MAC-id test.

- Device not powered.Check module status indicator.

Device is on line but has no connections in the established state.

Device is on line and has connections in the established state.

One or more I/O connections in timed-out state.

Critical link failure - failed communication device.

Device detected error that prevents it from communicating on the network.

Communication faulted device - the device has detected a network access error and is in communication faulted state. Device has received and accepted an Identity Communication Faulted Request - long protocol message.

Module in CAL mode.

Normal (channel scanning inputs).

Channel being calibrated.

No power or major channel fault.

Channel at end of range (over or under).

Publication

1738-IN024C-EN-P - March 2010

12 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A

Specifications

IMPORTANT

Note that the input step response and input update rate for

1738-IE4CM12 differ from those of catalog number 1738-IE2CM12.

General

Attribute

Number of inputs

Input point density

Input current signal range

Absolute accuracy

(1)

Accuracy drift w/temp., current input

Digital filter time constant

Input common mode rejection ratio

Input conversion type

Input impedance

Input normal mode rejection ratio

Input resistance

Input resolution, bits

Value

4

4 single-ended, non-isolated

4…20 mA

0…20 mA

0.1% Full Scale @ 25°C

30 ppm/°C

0…10,000 ms (default = 0 ms)

120 dB

Sigma Delta

60

Ω

-60 dB

Notch filter

15.7 Hz @ Notch = 60 Hz (default)

13.1 Hz @ Notch = 50 Hz

26.2 Hz @ Notch = 100 Hz

31.4 Hz @ Notch = 120 Hz

52.4 Hz @ Notch = 200 Hz

62.9 Hz @ Notch = 240 Hz

78.6 Hz @ Notch = 300 Hz

104.8 Hz @ Notch = 400 Hz

125.7 Hz @ Notch = 480 Hz

60

Ω

16 bits - over 0…21 mA; 0.32

μA/cnt

Publication

1738-IN024C-EN-P - March 2010

ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 13

General (Continued)

Attribute

Input step response (per channel)

Input update rate

(per module)

Value

50 ms @ Notch = 60 Hz (default)

60 ms @ Notch = 50 Hz

30 ms @ Notch = 100 Hz

25 ms @ Notch = 120 Hz

15 ms @ Notch = 200 Hz

12.5 ms @ Notch = 240 Hz

10 ms @ Notch = 300 Hz

7.5 ms @ Notch = 400 Hz

6.25 ms @ Notch = 480 Hz

200 ms @ Notch = 60 Hz (default)

240 ms @ Notch = 50 Hz

120 ms @ Notch = 100 Hz

100 ms @ Notch = 120 Hz

60 ms @ Notch = 200 Hz

50 ms @ Notch = 240 Hz

40 ms @ Notch = 300 Hz

30 ms @ Notch = 400 Hz

25 ms @ Notch = 480 Hz

Signed integer

24V dc

Input data format

External dc power supply voltage, nom.

External dc power supply voltage range

10…28.8V dc

External dc power supply current

15 mA @ 24V dc

Overvoltage protection, input Fault protected to 28.8V dc

PointBus current

Power dissipation, max.

Thermal dissipation, max.

Calibration

Keyswitch position

75 mA @ 5V dc

0.6 W @ 28.8V dc

2.0 BTU/hr @ 28.8V dc

Factory calibrated

3

Publication

1738-IN024C-EN-P - March 2010

14 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A

General (Continued)

Attribute

Indicators

Enclosure type rating

Mounting base screw torque

Value

1 green/red module status indicator, logic side

1 green/red network status indicator, logic side

4 green/red input status indicators, logic side

Isolation voltage 50V (continuous), Reinforced Insulation Type, field-side to system

Type tested at 1250V ac for 60 s, field-side to system

No isolation between individual channels

Dimensions (HxWxD), approx. 71.6 x 33.1 x 111.6 mm (2.82 x1.30 x 4.39 in.)

Meets IP65/66/67/69K (when marked)

M4 (#8) screw

0.85 Nm (7.5 lb-in) in Aluminum

1.81 Nm (16 lb-in) in Steel

2 - on signal ports

Wiring category

(2)

Weight, approx.

290 g (10.2 oz)

(1)

(2)

Includes offset, gain, non-linearity and repeatability error terms.

Use this Conductor Category information for planning conductor routing. Refer to Industrial

Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental

Attribute Value

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…60 °C (-4…140 °F)

Temperature, nonoperating

Relative humidity

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat):

-40…85 °C (-40…185 °F)

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% non-condensing

Vibration IEC 60068-2-6 (Test Fc, Operating): 5g @ 10…500 Hz

Publication

1738-IN024C-EN-P - March 2010

ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 15

Environmental (Continued)

Attribute Value

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50g

Emissions

ESD immunity

Radiated RF immunity

CISPR 11: Group 1, Class A

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz

3V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz

EFT/B immunity

Surge transient immunity

IEC 61000-4-4:

±3 kV at 5 kHz on signal ports

IEC 61000-4-5:

±1 kV line-line (DM) on signal ports

±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz

Certifications

Certification (when product is marked)

(1)

CE

C-Tick

Value

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR11; Industrial Emissions

(1)

See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and other certification details.

Publication

1738-IN024C-EN-P - March 2010

Rockwell Automation Support

Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com

, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com

.

Installation Assistance

If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer

Support number for initial help in getting your product up and running.

United States 1.440.646.3434

Monday – Friday, 8 a.m. – 5 p.m. EST

Outside United States Please contact your local Rockwell Automation representative for any technical support issues.

New Product Satisfaction Return

Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

United States Contact your distributor. You must provide a Customer Support case number

(see phone number above to obtain one) to your distributor in order to complete the return process.

Outside United States Please contact your local Rockwell Automation representative for the return procedure.

Allen-Bradley, Rockwell Automation, TechConnect, and ArmorPoint are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1738-IN024C-EN-P - March 2010

Supersedes Publication 1738-IN024B-EN-P - February 2010 Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals