- No category
advertisement
Installation Instructions
ArmorPoint 4-Channel 24V dc Analog Input
Module, Series A
Catalog Number 1738-IE4CM12
Topic
Prevent Electrostatic Discharge
Remove the Module From the Mounting Base
Interpret the Status Indicators
Specifications
Page
12
2 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD
Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.
Publication
1738-IN024C-EN-P - March 2010
ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 3
Environment and Enclosure
ATTENTION
This equipment is intended for use in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as enclosed equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication.
Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for additional installation requirements.
• NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure
Prevent Electrostatic Discharge
ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment.
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication
1738-IN024C-EN-P - March 2010
4 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A
ATTENTION
Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements.
ATTENTION
To comply with the CE Low Voltage Directive (LVD), all connected I/O must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
About the Module
The ArmorPoint I/O family consists of modular I/O modules. The sealed
IP67 housing of these modules requires no enclosure. (Note that environmental requirements other than IP67 may require an additional appropriate housing.) I/O connectors are sealed M12 style. The mounting base ships with the module. The 1738-IE4CM12 module is shown below.
1738-IE4CM12
Connector M12-A
0
1738-IE4CM12/A
Analog Current In
1
MOD
NET
Connector M12-B
LED Indicators
Connector M12-C
2
3
2
3
0
1
Connector M12-D
Publication
1738-IN024C-EN-P - March 2010
44367
ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 5
Mount the I/O Base
Mount the I/O base on a wall or panel, using the screw holes provided in the base
.
IMPORTANT
The ArmorPoint I/O module must be mounted on a grounded metal mounting plate or other conductive surface.
Mounting illustration for the ArmorPoint adapter with I/O bases
Adapter
46.25 mm
(1.8 in)
51.9 mm
(2.0 in)
20.1 mm
(0.8 in)
51.9 mm
(2.0 in)
20.1 mm
(0.8 in)
51.9 mm
(2.0 in)
102 mm
(4.02 in)
56 mm
(2.2 in)
43769
Follow the instructions to install the mounting base.
1. Lay out the required points as shown above in the drilling dimension drawing.
2. Drill the necessary holes for M4 (#8) machine or self-tapping screws.
3. Mount the base using M4 (#8) screws.
4. Ground the system using the ground lug connection.
The ground lug connection is also a mounting hole.
Publication
1738-IN024C-EN-P - March 2010
6 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A
Mounting base
Set the keyswitch position to 3, for the
1738 analog input modules
Ground lug connection
Latching mechanism
43675
Install the Module
Follow the instructions to install the analog input module.
1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number 3 aligns with the notch in the base.
2. Position the module vertically above the mounting base.
The module bridges two bases.
Publication
1738-IN024C-EN-P - March 2010
ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 7
Module bridges two bases.
0
1738-IE4CM12/A
Analog Current In
1
MOD
NET
2
3
2
3
0
1
44368
3. Push the module down until it engages the latching mechanism.
You will hear a clicking sound when the module is properly engaged.
The locking mechanism locks the module to the base.
Remove the Module From the Mounting Base
Follow the instructions to remove the module from the mounting base.
1. Put a flat blade screwdriver into the slot of the orange latching mechanism.
2. Push the screwdriver toward the I/O module to disengage the latch.
The module lifts up off the base.
3. Pull the module off of the base.
Publication
1738-IN024C-EN-P - March 2010
8 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A
Wire the Module
1738-IE4CM12
(view into connector)
Pin 1 - 24V dc
Pin 2 - Input
Pin 3 - Common
Pin 4 - Common
Pin 5 - No Connect
44315
IMPORTANT
Analog modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.
ATTENTION
Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements.
Communicate with Your Module
I/O messages are sent to (consumed) and received from (produced) the
ArmorPoint I/O modules. These messages are mapped into the processor’s memory. These ArmorPoint I/O analog input modules produce 12 bytes of input data (scanner Rx) and fault status data. They do not consume I/O data
(scanner Tx).
Publication
1738-IN024C-EN-P - March 2010
ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 9
Default Data Map for the Module
1738-IE4CM12
Message size: 12 Bytes
Produces
(Scanner Rx)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Input Channel 0 High Byte
Input Channel 1 High Byte
Input Channel 0 Low Byte
Input Channel 1 Low Byte
Input Channel 2 High Byte
Input Channel 3 High Byte
Status Byte for Channel 1
O
R
U
R
H
H
A
L
L
A
H
A
L
A
Status Byte for Channel 3
O
R
U
R
H
H
A
L
L
A
H
A
L
A
No consumed data
C
M
C
M
C
F
C
F
Input Channel 2 Low Byte
Input Channel 3 Low Byte
Status Byte for Channel 0
O
R
U
R
H
H
A
L
L
A
H
A
L
A
Status Byte for Channel 2
O
R
U
R
H
H
A
L
L
A
H
A
L
A
C
M
C
M
C
F
C
F
Consumes
(scanner Tx)
Where:
CF = Channel Fault Status, 0 = no error, 1 = fault
CM = Calibration Mode; 0 = normal, 1 = calibration mode
LA = Low Alarm; 0 = no error, 1 = fault
HA = High Alarm; 0 = no error, 1 = fault
LLA = Low/Low Alarm; 0 = no error, 1 = fault
HHA = High/High Alarm; 0 = no error, 1 = fault
UR = Underrange; 0 = no error; 1 = fault
OR = Overrange; 0 = no error; 1 = fault
Publication
1738-IN024C-EN-P - March 2010
10 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A
Interpret the Status Indicators
1738-IE4CM12
0
1738-IE4CM12/A
Analog Current In
1
MOD
NET
Module Status Indicator
Network Status Indicator
2
3
2
3
0
1
I/O Status Indicators
44367
Status Indicators
Indicator State
Module
Status
Off
Green
Flashing green
Flashing red
Red
Flashing red/green
Description
No power applied to device.
Device operating normally.
Device needs commissioning due to missing, incomplete, or incorrect configuration.
Recoverable fault.
Unrecoverable fault - may require device replacement.
Device is in self-test.
Publication
1738-IN024C-EN-P - March 2010
ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 11
Status Indicators (Continued)
Indicator State
Network
Status
Off
Flashing green
Green
Flashing red
Red
Flashing red/green
I/O Status Off
Solid green
Flashing green
Solid red
Flashing red
Description
Device is not on line:
- Device has not completed dup_MAC-id test.
- Device not powered.Check module status indicator.
Device is on line but has no connections in the established state.
Device is on line and has connections in the established state.
One or more I/O connections in timed-out state.
Critical link failure - failed communication device.
Device detected error that prevents it from communicating on the network.
Communication faulted device - the device has detected a network access error and is in communication faulted state. Device has received and accepted an Identity Communication Faulted Request - long protocol message.
Module in CAL mode.
Normal (channel scanning inputs).
Channel being calibrated.
No power or major channel fault.
Channel at end of range (over or under).
Publication
1738-IN024C-EN-P - March 2010
12 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A
Specifications
IMPORTANT
Note that the input step response and input update rate for
1738-IE4CM12 differ from those of catalog number 1738-IE2CM12.
General
Attribute
Number of inputs
Input point density
Input current signal range
Absolute accuracy
(1)
Accuracy drift w/temp., current input
Digital filter time constant
Input common mode rejection ratio
Input conversion type
Input impedance
Input normal mode rejection ratio
Input resistance
Input resolution, bits
Value
4
4 single-ended, non-isolated
4…20 mA
0…20 mA
0.1% Full Scale @ 25°C
30 ppm/°C
0…10,000 ms (default = 0 ms)
120 dB
Sigma Delta
60
Ω
-60 dB
Notch filter
15.7 Hz @ Notch = 60 Hz (default)
13.1 Hz @ Notch = 50 Hz
26.2 Hz @ Notch = 100 Hz
31.4 Hz @ Notch = 120 Hz
52.4 Hz @ Notch = 200 Hz
62.9 Hz @ Notch = 240 Hz
78.6 Hz @ Notch = 300 Hz
104.8 Hz @ Notch = 400 Hz
125.7 Hz @ Notch = 480 Hz
60
Ω
16 bits - over 0…21 mA; 0.32
μA/cnt
Publication
1738-IN024C-EN-P - March 2010
ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 13
General (Continued)
Attribute
Input step response (per channel)
Input update rate
(per module)
Value
50 ms @ Notch = 60 Hz (default)
60 ms @ Notch = 50 Hz
30 ms @ Notch = 100 Hz
25 ms @ Notch = 120 Hz
15 ms @ Notch = 200 Hz
12.5 ms @ Notch = 240 Hz
10 ms @ Notch = 300 Hz
7.5 ms @ Notch = 400 Hz
6.25 ms @ Notch = 480 Hz
200 ms @ Notch = 60 Hz (default)
240 ms @ Notch = 50 Hz
120 ms @ Notch = 100 Hz
100 ms @ Notch = 120 Hz
60 ms @ Notch = 200 Hz
50 ms @ Notch = 240 Hz
40 ms @ Notch = 300 Hz
30 ms @ Notch = 400 Hz
25 ms @ Notch = 480 Hz
Signed integer
24V dc
Input data format
External dc power supply voltage, nom.
External dc power supply voltage range
10…28.8V dc
External dc power supply current
15 mA @ 24V dc
Overvoltage protection, input Fault protected to 28.8V dc
PointBus current
Power dissipation, max.
Thermal dissipation, max.
Calibration
Keyswitch position
75 mA @ 5V dc
0.6 W @ 28.8V dc
2.0 BTU/hr @ 28.8V dc
Factory calibrated
3
Publication
1738-IN024C-EN-P - March 2010
14 ArmorPoint 4-Channel 24V dc Analog Input Module, Series A
General (Continued)
Attribute
Indicators
Enclosure type rating
Mounting base screw torque
Value
1 green/red module status indicator, logic side
1 green/red network status indicator, logic side
4 green/red input status indicators, logic side
Isolation voltage 50V (continuous), Reinforced Insulation Type, field-side to system
Type tested at 1250V ac for 60 s, field-side to system
No isolation between individual channels
Dimensions (HxWxD), approx. 71.6 x 33.1 x 111.6 mm (2.82 x1.30 x 4.39 in.)
Meets IP65/66/67/69K (when marked)
M4 (#8) screw
0.85 Nm (7.5 lb-in) in Aluminum
1.81 Nm (16 lb-in) in Steel
2 - on signal ports
Wiring category
(2)
Weight, approx.
290 g (10.2 oz)
(1)
(2)
Includes offset, gain, non-linearity and repeatability error terms.
Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)
Temperature, nonoperating
Relative humidity
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat):
-40…85 °C (-40…185 °F)
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration IEC 60068-2-6 (Test Fc, Operating): 5g @ 10…500 Hz
Publication
1738-IN024C-EN-P - March 2010
ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 15
Environmental (Continued)
Attribute Value
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50g
Emissions
ESD immunity
Radiated RF immunity
CISPR 11: Group 1, Class A
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz
3V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz
EFT/B immunity
Surge transient immunity
IEC 61000-4-4:
±3 kV at 5 kHz on signal ports
IEC 61000-4-5:
±1 kV line-line (DM) on signal ports
±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Certifications
Certification (when product is marked)
(1)
CE
C-Tick
Value
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR11; Industrial Emissions
(1)
See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and other certification details.
Publication
1738-IN024C-EN-P - March 2010
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com
, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer
Support number for initial help in getting your product up and running.
United States 1.440.646.3434
Monday – Friday, 8 a.m. – 5 p.m. EST
Outside United States Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number
(see phone number above to obtain one) to your distributor in order to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Allen-Bradley, Rockwell Automation, TechConnect, and ArmorPoint are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1738-IN024C-EN-P - March 2010
Supersedes Publication 1738-IN024B-EN-P - February 2010 Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 Important User Information
- 3 Environment and Enclosure
- 3 Prevent Electrostatic Discharge
- 4 About the Module
- 5 Mount the I/O Base
- 6 Install the Module
- 7 Remove the Module From the Mounting Base
- 8 Wire the Module
- 8 Communicate with Your Module
- 9 Default Data Map for the Module
- 10 Interpret the Status Indicators