Industrial Ethernet - Challenges and Drawbacks Comparison

Industrial Ethernet - Challenges and Drawbacks Comparison
Industrial Ethernet - Challenges and
Drawbacks
Comparison
of
MODBUS TCP/IP
and
EtherNet/IP
Bachelor Thesis
Fall semester 2010/2011
Markus Klein
0726101
[email protected]
Supervisor
Ao. Univ. Prof. Dr. Wolfgang Kastner
Statement
Hereby I declare that this work has been written autonomously, that all
used sources and utilities are denoted accordingly and that these points
of the work - including tables, maps and figures - which where taken from
other creations or the Internet have been marked as borrowing by quoting
the original sources. This document at hand will not be submitted to any
other course.
Hiermit erkläre ich, dass ich diese Arbeit selbständig verfasst habe, dass
ich die verwendeten Quellen und Hilfsmittel vollständig angegeben habe
und dass ich die Stellen der Arbeit – einschließlich Tabellen, Karten und
Abbildungen –, die anderen Werken oder dem Internet im Wortlaut oder
dem Sinn nach entnommen sind, auf jeden Fall unter Angabe der Quelle
als Entlehnung kenntlich gemacht habe.
i
Contents
Statement
i
Contents
ii
List of Tables
iii
List of Figures
iii
Abstract
iv
1 Introduction
1.1 Industrial Communication
1.1.1 Fieldbuses . . . . .
1.1.2 Standardization . .
1.2 Ethernet in Automation . .
.
.
.
.
1
1
2
3
3
.
.
.
.
.
6
6
7
7
9
10
.
.
.
.
.
.
12
12
13
14
14
15
16
4 Conclusion
4.1 Availability . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
17
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
2 EtherNet/IP
2.1 Description . . . . . . . . . . . . .
2.2 History . . . . . . . . . . . . . . .
2.3 Protocol Specification . . . . . . .
2.3.1 Data model and addressing
2.3.2 Services . . . . . . . . . . .
3 MODBUS
3.1 Description . . . . . . . . . . . . .
3.2 History . . . . . . . . . . . . . . .
3.3 Protocol Specification . . . . . . .
3.3.1 Data model and addressing
3.3.2 Services . . . . . . . . . . .
3.4 Communication over TCP/IP . . .
ii
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
4.2
4.3
4.4
4.5
Data management and addressing
Performance . . . . . . . . . . . .
Security . . . . . . . . . . . . . . .
Real-Time . . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 18
. 19
. 19
. 20
Bibliography
22
List of Tables
2.1 EtherNet/IP message types. [12, p. 11] . . . . . . . . . . . . . .
11
3.1
15
MODBUS data model - table types . . . . . . . . . . . . . . . .
List of Figures
1.1
Automation pyramid [13, p. 536] . . . . . . . . . . . . . . . . .
2.1
2.2
2.3
2.4
EtherNet/IP Protocol Stack [12, p. 6] . . . . .
Services provided by CIP . . . . . . . . . . . .
CIP multi-protocol support [12, p. 6] . . . . .
CIP connection and Connection ID. [10, p. 13]
.
.
.
.
6
8
8
10
3.1 MODBUS communication stack [6, p. 2] . . . . . . . . . . . .
3.2 EtherNet/IP Originator with embedded MODBUS integration
[11, p. 2] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 CIP Originator to Modbus/TCP Target Devices [11, p. 3] . . . .
3.4 MODBUS Application Data Unit [6, p. 4] . . . . . . . . . . . .
12
iii
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
1
13
13
14
Abstract
This paper provides a general overview of industrial communication on
fieldbus level using state-of-the-art Ethernet-based protocols.
After having a look at the history of fieldbuses and the legal standards,
this paper builds the bridge to modern Ethernet-based fieldbus protocols,
which are designed to match today’s requirements in industrial automation.
Special focus is on the protocols EtherNet/IP, based on the sophisticated Common Industrial Protocol, and MODBUS TCP/IP, the Ethernetbased version of the former de-facto industry standard MODBUS.
Finally, this report compares the two protocols, putting specific attention on some important aspects and challenges of these protocols.
iv
1
Introduction
1.1 Industrial Communication
Machines, possibly consisting of several dedicated devices, have to talk to
a controller or with each other. The underlying communication protocol
builds the backbone of any automation system.
Figure 1.1: Automation pyramid [13, p. 536]
The automation pyramid in Figure 1.1 depicts the levels of automation
within a factory. Each of these levels has its own requirements of communication, called industrial communication.
Industrial communication is used since the early 1980s. Until now,
the technologies were undergoing massive changes as new demanding requirements sought for new ideas.
Today’s protocols and devices break with the traditional view of the
automation pyramid (Figure 1.1). As embedded CPUs are getting faster
and smaller, sensors and actuators are getting more intelligent. These
intelligent devices are subsumed under the term “Smart Instruments”.
Smart Instruments may include the necessary hardware to be directly in1
CHAPTER 1. INTRODUCTION
2
tegrated into the control level of the automation pyramid, mixing up the
classic definition of the levels. Thus, it is suggested to distinguish between
the functional architecture and the operational architecture. [14, p. 84]
Some advantages of this integration process are:
• Faster access to devices.
• Direct access to devices’ data for immediate evaluation in MES or
SCADA systems.
• Cost saving for hardware like cabling on the field level.
1.1.1
Fieldbuses
A fieldbus is a communication system that interconnects field level devices and builds the bridge to control level PLCs. The very first system,
used in an experiment, was built in France, 1981 [14, p. 82]. Following
this experiment a working group was established, creating the FIP (now
WorldFIP) fieldbus. Other groups in different countries also developed
new bus systems, leading to a variety of protocols during the 1980s.
Facing this wide range of fieldbuses leads to the question “What is a
fieldbus?”. J.P. Thomesse states two objectives, how a fieldbus may be
seen by a designer: [14, p. 81]
• A fieldbus is only a network for simplifying the wiring between devices.
• A fieldbus is the spinal column of a distributed real-time system.
Thomesse furthermore describes the main requirements important
for all fieldbuses from the end-user’s point of view: [14, p. 83]
• Safety, availability and dependability
• Better maintainability
• Better modularity, and capacity for evolution
CHAPTER 1. INTRODUCTION
3
• Openness, interoperability, interchangeability and long life-times
• Better performance and lower costs
1.1.2
Standardization
In parallel to the development of over 50 fieldbuses, various committees of standardization organisations were working on fieldbus standards,
paving the way for better interoperability between fieldbuses.
In Europe, FIP and PROFIBUS were popular fieldbuses. Both came
from different countries and both tried to bring their approach into an
international standard. This was one reason for the so called “Fieldbus
War”, preventing a worldwide standard.
Finally, after more than ten years passing by, the war was put to an
end. IEC 61158 (1999), the long awaited international standard for fieldbuses, was released. The standard is not based on an agreement of the
competing companies, but simply structures all of the present approaches
and combines them to a single document structure. The additional set of
standards in IEC 61784 define profiles, telling how to combine the modules of IEC 61158 for the specific fieldbuses.
1.2
Ethernet in Automation
Ethernet has been used on the management level and enterprise level
for a long time, connecting any kind of device using Internet technology.
Bringing this technology one level down to the control level is the next
step of the integration process. Considering the levels of the automation
pyramid this means, that the fieldbus directly connects to a company’s
LAN/intranet removing a complete (operational) level from the pyramid.
This once again helps to reduce costs and increases flexibility in today’s production processes.
Increasing needs for transportation of bigger data quantities and low
cost circuits for Ethernet are reasons for manufacturers to create protocols on basis of Ethernet, IP and TCP/UDP. [1, p. 1102]
CHAPTER 1. INTRODUCTION
4
In [2, p. 1118], Max Felser defines two requirements for using Ethernet
on fieldbus level:
• Support migration of the office Ethernet to real-time Ethernet
• Use of standard components: bridges, Ethernet controllers and protocol stacks as far as possible
Tackling the problem of non-determinism of the Ethernet protocol
on one hand and the need for guaranteed real-time transmissions on the
other hand led to the development of diverse modifications of the standard Ethernet and TCP/IP protocols.
In [1, p. 1114], Decotignie lists the following proposals for “Industrial
Ethernet” supporting real-time communications: PROFINET, Ethernet
Powerlink, JetSync, EtherNet/IP, SERCOS III, Modbus-TCP, EtherCAT,
PowerDNA, Real-Time Publish-Subscribe and SynqNet. Some of today’s
big players are MODBUS TCP, PROFINET IO, EtherNet/IP, Ethernet Powerlink and EtherCAT.
[2, p. 1121] shows the possible structures used to realize real-time Ethernet. The following list briefly describes the different approaches:
• Top of TCP/IP: Places the real-time components on top of the standard TCP/IP protocol stack (e.g. EtherNet/IP).
• Top of Ethernet: Modifies or replaces the TCP/IP stack with the
real-time protocol, but doesn’t touch the Ethernet layer (e.g. PROFINET
CBA).
• Modified Ethernet: Provides a dedicated real-time protocol, that includes a modified Ethernet layer (e.g. EtherCAT).
No question, Ethernet will pave its way in industrial automation. As
a single versatile protocol Ethernet will be the best solution for the majority of cases. Unfortunately, current evolution shows a similar development of industrial Ethernet standards as it has been the case with fieldbus
standards. In 2005, IEC 61784 already contained ten real-time Ethernet
CHAPTER 1. INTRODUCTION
5
profiles. In the latest revision of the standard, this has been expanded
with two additional profiles, namely: RAPIEnet (CFP17) and SafetyNET
p (CFP18). [3]
Max Felser ends his paper [2] with the question: “Is it up to the end
user and the market to decide which one of the proposed solutions fulfils
the requirement of the automation applications and will end up in real
applications?” In 2011, the answer to this questions seems to be “Yes”, but
to say it with the words of J.P. Thomesse: “The world is still not stable.”
[14, p. 91]
2 EtherNet/IP
The full name of EtherNet/IP is Ethernet Industrial Protocol derived
from the underlying CIP (Common Industrial Protocol). EtherNet/IP
is often confused with a combination of Ethernet and Internet Protocol,
well known from the TCP/IP model, used in a wide range of network applications. What is even more confusing is the fact, that EtherNet/IP as
an application layer protocol (refer to OSI model [4]) actually operates
over Ethernet (physical layer) and the Internet Protocol stack (network
and transport layer).
2.1
Description
EtherNet/IP follows the Open Systems Interconnection (OSI) model with
its seven layers [4]. As depicted in Figure 2.1 and like all other CIP protocols, this protocol implements CIP at the top three layers (session, presentation and application). The remaining four layers are adapted to the specific EtherNet/IP technology using an unmodified TCP/UDP/IP stack.
Figure 2.1: EtherNet/IP Protocol Stack [12, p. 6]
6
CHAPTER 2. ETHERNET/IP
7
2.2 History
The EtherNet/IP protocol was initially developed by Allen-Bradley (Rockwell Automation, USA) in the late 1990s.
Since 2001, EtherNet/IP is maintained by the Open DeviceNet Vendors Association (short ODVA1 ), which is an international organization
supporting technologies based on CIP.
Currently, ODVA has over 500 registered vendors, including leading
automation companies, and is responsible for ensuring multi-vendor interoperability.
2.3
Protocol Specification
The EtherNet/IP application layer protocol is based on the Common Industrial Protocol (CIP) standard, which provides compatibility to DeviceNet,
CompoNet and ControlNet. [9, p. 2]
CIP, formerly known as Control and Information Protocol, is a collection of messages and services with the focus on manufacturing automation applications providing a unified communication architecture. Due
to the generic definition of messages and services, CIP is truly mediaindependent (refer to Figures 2.2 and 2.3).
CIP uses an object model approach containing data addressing methods and message exchange rules.
This approach is strictly object-oriented at the upper layers of the protocol. An object is a collection of attributes, services, connections and behaviours. For standard purpose tasks like analog/digital I/O, file transfers or position feedback, CIP provides an object library. The communication model is based on the producer-consumer model, enabling a flexible
and efficient usage of limited network resources.
Device interoperability is assured by device profiles defining groups
of available objects together with configuration options and I/O data formats.
1
http://www.odva.org/
CHAPTER 2. ETHERNET/IP
Figure 2.2: Services provided by CIP
Figure 2.3: CIP multi-protocol support [12, p. 6]
8
CHAPTER 2. ETHERNET/IP
2.3.1
9
Data model and addressing
As described, CIP uses an object oriented approach for defining a device’s
capabilities. Therefore, CIP specifies three types of objects a device may
contain: [12, p. 8]
• Required Objects: These objects are mandatory to any CIP device
and include the Identity Object, the Message Router Object and networkspecific objects.
• Application Objects: Depending on the device type and its function,
these objects define, how data is encapsulated by a device.
• Vendor-specific Objects: Objects describing vendor-specific services,
which are not listed in a device profile.
The Identity Object (class ID 0x01) is a read-only object (except for
one attribute) that defines basic information about a device. Mandatory
attributes of this class are: Vendor ID, Device Type, Product Code, Revision, Status, Serial Number and Product Name.
The Message Router Object of a node takes care of distributing explicit message requests to the appropriate application objects. [10]
As multiple instances of an object can co-exist in one device, this set of
instances is referred as Class. This may be confusing when compared to
object oriented approaches in software engineering (SE), as an object in
the SE world is commonly known to be an instance of a class. So to build
the bridge:
• A class in SE world is an object in CIP world.
• A class in CIP world is a set of objects instantiated from the same
class in SE world.
Furthermore, CIP also specifies the methods used to access the data.
Assembly Objects allow vendors to define a message (I/O or configuration) containing a variety of data from different other objects. E.g. an
CHAPTER 2. ETHERNET/IP
10
Assembly Object can be a collection of several attributes of diverse application objects.
An interesting aspect of EtherNet/IP (CIP) is the very fine grained addressing schema for objects. [12, p. 9]
An object address (called CIP Segment) is well structured and is assembled by the the following parts:
• Device network address: Can be a node address or a medium access
control identifier.
• Class ID: This holds the ID of the class this instance belongs to.
• Instance ID: The instance itself.
• Attribute ID: The attribute that is of interest.
• Service code: Describes the action/service required by this request.
Each part of a CIP Segment can have various formats: 1 byte, 2 byte
or 4 byte. [10, p. 25]
2.3.2
Services
“CIP is a connection-based protocol. A CIP connection provides a path
between multiple application objects. When a connection is established,
the transmissions associated with that connection are assigned a Connection ID.” [10, p. 13]
Figure 2.4: CIP connection and Connection ID. [10, p. 13]
To establish such a connection, the Unconnected Message Manager
(UCMM) function is used, which processes unconnected explicit requests
CHAPTER 2. ETHERNET/IP
11
and responses. The UCMM Forward_Open service request message contains all required information to initiate a connection between the originator and the target device.
Depending on the typical form of communication, EtherNet/IP defines two types of messages. Table 2.1 provides an overview which types
are available and which protocols (on lower OSI layers) are used. [12, p.
11]
CIP Message Type
Explicit
Implicit
CIP CommunicaConnected or Unconnected
tion Relationship
Connected1
Transport
col
TCP/IP
UDP/IP
Communication
Type
Request/reply transactions
I/O data transfers
Typical Use
Non time-critical information data
Real-time I/O data
1
Proto-
“With Implicit Messaging you establish an association (a ’CIP connection’) between two
devices and produce the Implicit Messages according to a predetermined trigger mechanism,...” [12, p. 11]
Table 2.1: EtherNet/IP message types. [12, p. 11]
Implicit messaging has the big advantage, that it can make use of
the producer/consumer principle. This means that it is only necessary to
send I/O data once and all interested receivers can read the data, helping
to massively reduce load on the bus in cases where many devices send lots
of data on high rates. Additionally, there is no request/response pattern
for implicit messages once the connection has been established, reducing bus load even more. The sending of implicit messages can either be
triggered cyclically or at change of state or due to an application specific
reason.
3
3.1
MODBUS
Description
MODBUS is a powerful application layer [4] messaging protocol. It is
solely based on the client/server principle and can be operated over several buses and networks.
Figure 3.1: MODBUS communication stack [6, p. 2]
Figure 3.1 shows the main three buses that may be utilized by MODBUS. Communication between these buses in heterogeneous networks is
easily possible, since the simple structure of the protocol allows building
of inexpensive gateways.
Modbus-IDA focuses on driving the evolution towards the MODBUS
TCP/IP protocol.
Although MODBUS is only a tiny protocol compared to other Ethernet based protocols, there is no doubt that it will not lose its position in
industry. Integration of MODBUS devices will even be more comfortable,
since big players, like EtherNet/IP in 2007, introduced additional specifications for mapping MODBUS based devices directly into their architecture. (Compare also “CIP network specification” - Volume seven, [11]
and “CIP-Modbus Integration” [15])
CIP-to-Modbus integration supports all kinds of messaging and performs necessary translations to make MODBUS device data consistent
12
CHAPTER 3. MODBUS
13
with the CIP communications model. Figures 3.2 and 3.3 show how the
integration is achieved.
Figure 3.2: EtherNet/IP Originator with embedded MODBUS integration
[11, p. 2]
Figure 3.3: CIP Originator to Modbus/TCP Target Devices [11, p. 3]
3.2
History
MODBUS was originally developed by Modicon, today Schneider Electric, and is the de-facto standard for serial communication in automation
industry since 1979. In April 2004, Schneider Automation transferred
its copyright to Modbus-IDA, a non-profit organisation founded in 2002.
Today, Modbus-IDA provides the infrastructure to distribute all kinds of
CHAPTER 3. MODBUS
14
information about MODBUS. This also includes directories of suppliers
and integrators as well a device database.
3.3
Protocol Specification
The basis of the MODBUS protocol is the General MODBUS frame, also
called PDU (Protocol Data Unit), which only consists of two parts. It is
completely independent of any underlying communication layer. These
parts are:
• Function: A field of one byte containing the ID of the requested
service.
• Data: A field of variable size containing the required payload for
the requested service.
The so called ADU (Application Data Unit) is the real frame containing the PDU and additional fields used by the underlying communication
protocol. Figure 3.4 explains the nesting of ADU and PDU.
Figure 3.4: MODBUS Application Data Unit [6, p. 4]
As depicted, the ADU is terminated by the field “Error check”. Depending on the underlying communication protocol this field may be optional, if the functionality is already included in the particular protocol.
For instance, TCP/IP already includes error checking and CRC, so this
field is omitted.
3.3.1
Data model and addressing
The MODBUS standard defines four table types each of them containing
entries with ascending index. Each table entry is a mapping from its index
CHAPTER 3. MODBUS
15
to a device’s physical application memory address. Table 3.1 describes the
four types and what data may be lodged behind an entry.
Table type
Object type
Access
Discrete Input
Coils
Input Registers
Holding Registers
Single Bit
Read
Single Bit
Read/Write
16-bit Word Read
16-bit Word Read/Write
Table 3.1: MODBUS data model - table types
A table entry is addressed using its index, which has a width of 16 bits,
so a maximum size of 65536 entries per table type is possible.
A completely different approach has also been tried by specifying “Object Messaging Specification for the MODBUS/TCP Protocol” [5].
3.3.2
Services
Transactions
Since MODBUS only supports the request/response pattern, sending
of data can only be initiated by the client. The server (device) never sends
anything without receiving an adequate request beforehand. Hence MODBUS only allows polling of attached devices.
One transaction involves the following steps:
1. A PDU is sent from one client to a server containing the requested
service specified by the function code.
2. The server processes the request.
3. The received PDU (possibly filled with data) is returned to the client.
4. The client processes the response.
In case an exception arises on the server, step 3 is modified. The most
significant bit in the function code of the PDU is set to logic one and exception data is optionally appended.
CHAPTER 3. MODBUS
16
Function codes
Function codes specify the available services a device offers. The majority of codes are standardized, but a couple of codes are open to be implemented with vendor/user specific functionality.
Functions are available for different types of service: data access, diagnostics and others. Functions for data access are furthermore grouped
into functions for Bit-access (Discrete Inputs and Coils), Word-access (Input Registers and Holding Registers) and file record access.
It is not required for a device to implement all functions codes. In case
a client requests a function that is not implemented, an exception has to
be returned. Refer to [6, p. 48] for a detailed description of exception
responses.
3.4
Communication over TCP/IP
In cases where TCP/IP is the underlying communication protocol of choice,
the “Additional address” field of the ADU in Figure 3.4 is replaced by
the MBAP Header (MODBUS Application Protocol Header). The “Error check” field is omitted in favour of the error checking mechanisms
of TCP/IP and Ethernet.
The MBAP Header structure is described in Chapter 3.1.3 in [7, p. 5].
For transactions over TCP/IP, port 502 has been reserved for MODBUS servers (devices). Any request ADU of a client will be addressed to
the respective server on port 502. Message switching and routing are not
in the scope of MODBUS, but of TCP/IP and therefore any device on the
market can be used for these purposes.
The field “Unit Identifier” in the MBAP Header is of special interest
when gateways are used to integrate devices e.g. connected via a serial
line into the TCP/IP world. This field is used by the gateway to determine
the destination of the request within the subordinated bus.
4
Conclusion
Modern automation requires high integration of management and controlling tasks into the production process. Cost efficiency, interoperability and interchangeability are more important than ever. To achieve such
a high integration a common communication protocol, covering everything from the sensor to the SCADA system, is needed. Since Ethernet
and TCP/IP have been a standard in corporate networks for years now, it
seems reasonable to concentrate the development of fieldbuses on them.
Using Ethernet based solutions has big advantages for companies, such
as:
• Lots of protocol specific know-how is already present in the company.
• Necessary equipment for TCP/IP networks is present as well, so it
is not necessary to install additional cabling for the fieldbuses.
• Integration of high level management functions is possible, without
the introduction of new interfaces, leading to cost reduction.
In the following sections the described Ethernet protocols EtherNet/IP
and MODBUS TCP/IP are compared on aspects important for future automation challenges.
Although it is possible to integrate MODBUS into EtherNet/IP networks, it may be useful for companies to evaluate, which protocol better
fits their needs as there may be certain issues, preventing a successful integration of older MODBUS devices into EtherNet/IP. [15]
4.1
Availability
This aspect mainly affects the costs of an automation system.
17
CHAPTER 4. CONCLUSION
18
Whereas MODBUS is freely available to everyone, EtherNet/IP requires to be subscribed to ODVA1 in order to obtain the specifications of
the protocols.
The MODBUS specification can be downloaded from the Modbus-IDA
Website2 and is free of charge. In contrast, the EtherNet/IP specifications
are sold on CDs and can cost up to several thousand dollars. For vendors
it is highly recommended becoming a member of ODVA and gaining an
official Vendor ID.
4.2
Data management and addressing
Both protocols can address the same number of devices. The effective
amount only depends on the configured IP subnet.
The amount of addressable data (objects) differs quite a lot. As MODBUS reserves 16-bit for addressing, a maximum of 65536 items per table
type can be addressed. EtherNet/IP is able to address a far greater range
of objects (and attributes), depending on the chosen CIP Segment format.
Assuming the biggest format with 4 bytes, a total amount of 232 instances per class ID and 232 attributes per instance can be addressed. Each
attribute can be one of the CIP data types, which follow the requirements
of IEC 61131-3.
Last but not least MODBUS completely misses a standard how clients
can gather meta-information of data objects. Examples of missing information are: valid range of a value, physical unit, scale, etc.
Due to the detailed specification of CIP, EtherNet/IP offers a far better basis for building interoperable and interchangeable devices, as the
device profiles and electronic data sheets explicitly explain the provided
data objects (including parameters and attributes) and services.
1
http://odva.org/Home/MEMBERS/tabid/108/lng/en-US/language/
en-US/Default.aspx
2
http://modbus.org/specs.php
CHAPTER 4. CONCLUSION
4.3
19
Performance
The maximum data rate the protocols offer, is primary depending on the
underlying Ethernet protocol. Having nets with up to 10Gbit/s, services
with high data rate requirements are possible. However, with embedded
processors we are facing the problem, that a device might not be able to
process data with such high rates.
Moreover, taking a closer look at the protocols reveals other problems.
Typically industrial communication data size is not bigger than a couple
of bytes, but the minimum frame size of 1Gbit/s Ethernet is 512bytes, resulting in a data efficiency of approximately 5% or less. Also application
protocol efficiency is a factor. MODBUS has a quite good protocol efficiency of about 60%. But MODBUS only offers a request/response communication pattern, whereas EtherNet/IP additionally supports a producer/consumer pattern utilizing UDP. However, UDP has a much better
protocol efficiency than TCP, because of the missing acknowledgement
transactions.
4.4
Security
This topic is probably the most sensitive and problematic in today’s information technology world. Being aware that security threats have been
present for years, there have been rather little efforts to tackle this subject in automation. But things will change, at least since this omnipresent
virus called Stuxnet has been around. [8]
Looking at these massive efforts taken to finally modify a PLC, it is
clear that things will get even worse, when target devices are on the same
net as the normal PCs, which will reduce the necessary steps to reach the
final bus system to which the target is connected.
For instance, MODBUS itself only provides protection against malformed ADUs by checking the proper format of the frame upon receipt.
All other potential security threats are related to the underlying communication technology and have to be addressed in these layers. For TCP/IP,
CHAPTER 4. CONCLUSION
20
a properly configured firewall would help to protect the network from external attackers.
Having this in mind, it seems quite horrible, that neither MODBUS
nor EtherNet/IP have any security mechanism. So if a fieldbus LAN is
directly accessible by normal PC stations or even the Internet, one’s really
on high risk.
Both protocols lack of functions like access tables, defining which device on the net has the right to send a specific request or command. Since
the traffic is not encrypted, all devices connected to the bus are able to
listen to all transmissions and - even worse - are able to manipulate data.
To sum up, companies have to find a trade-off between high integration of fieldbuses to their company net and the risk of security issues.
4.5
Real-Time
Protocols for safety critical applications require one thing: real-time data
transfers with deterministic response times.
Facing this requirement Ethernet-based applications seem to be a dead
end. Due to the CSMA/CD principle used to control media access, Ethernet has an inherent non-determinism, which makes it not reliable enough
to be used for safety critical applications, no matter how fast Ethernet will
ever be.
Especially for MODBUS the available speed and response times are
limited by Ethernet. It is not possible to reach the required response times
for real-time applications like motion control without modifying the underlying technologies.
MODBUS itself has no capabilities of serving real-time services. RealTime Publisher Subscriber (RTPS) protocol is a real-time extension for
MODBUS. It uses the UDP protocol to create multicast messages used for
the producer/consumer pattern. “Contrary to the standard MODBUS
protocol, the RTPS protcol is not used very much in practical industrial
applications today, and therefore it is not known exactly what sort of
performance this protocol really has to offer. ... required performance
CHAPTER 4. CONCLUSION
21
of the “process application class” [M.K.: less than 10ms response time],
..., may be reached with this system.” [2, p. 1122]
CIP also offers an add-on for real-time data transmission, called “CIP
Sync”. This extension removes the hard requirements from the Ethernet layers and establishes a common timebase throughout all device. The
provided clock synchronisation algorithm achieves deviations of less than
200ns, which is sufficient even for the most demanding motion control applications. All messages sent are time-stamped causing a small amount
of jitter to be negligible.
Bibliography
[1]
Jean Dominique Decotignie. Ethernet-based real-time and industrial communications. Proc. IEEE, 93(6):1102–1117, June 2005.
[2] Max Felser. Real-Time Ethernet - Industry Prospective. Proc. IEEE,
93(6):1118–1129, June 2005.
[3] International Electrotechnical Commission.
2010.
IEC 61784-2, July
[4] International Organization for Standardization. ISO/IEC 7498-1,
1994.
[5] Modbus-IDA.
MODBUS/TCP
Object Messaging Specification
Protocol V1.1, November 2004.
for
the
URL
http://modbus.org/docs/Object_Messaging_Protocol_
ExtensionsVers1.1.doc.
[6] Modbus-IDA. MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b, December 2006. URL http://modbus.org/docs/
Modbus_Application_Protocol_V1_1b.pdf.
[7] Modbus-IDA.
MODBUS MESSAGING ON TCP/IP IMPLEMENTATION GUIDE V1.0b, October 2006.
URL http:
//modbus.org/docs/Modbus_Messaging_Implementation_
Guide_V1_0b.pdf.
[8] Eric Chien Nicolas Falliere, Liam O Murchu. Symantec security
response w32.stuxnet dossier. Technical report, Symantec, February 2011. URL http://www.symantec.com/content/en/us/
enterprise/media/security_response/whitepapers/w32_
stuxnet_dossier.pdf.
[9] ODVA, Inc.
Common Industrial Protocol (CIP) (PUB122),
2006.
URL http://www.odva.org/Portals/0/Library/
Publications_Numbered/PUB00122R0_CIP_Brochure_
ENGLISH.pdf.
22
BIBLIOGRAPHY
23
[10] ODVA, Inc.
The Common Industrial Protocol
and the Family of CIP Networks (PUB122), 2006.
(CIP)
URL
http://www.odva.org/Portals/0/Library/Publications_
Numbered/PUB00123R0_Common%20Industrial_Protocol_
and_Family_of_CIP_Netw.pdf.
[11] ODVA, Inc. Common Industrial Protocol (CIP) - Modbus Integration, April 2008. URL http://www.odva.org/Portals/0/
Library/Publications_Numbered/PUB00193R0_CIP-Modbus_
Integration_Overview.pdf.
[12] ODVA, Inc. EtherNet/IP Quick Start for Vendors Handbook:
A Guide for EtherNet/IP Developers (PUB213R0), 2008. URL
http://www.odva.org/Portals/0/Library/Publications_
Numbered/PUB00213R0_EtherNetIP_Developers_Guide.pdf.
[13] Martin Polke. Prozeßleittechnik. Oldenbourg Verlag, 1994.
[14] Jean Pierre Thomesse. Fieldbuses and interoperability. Cntr. Eng.
Pract., 7(1):81–94, 1999.
[15] Todd A. Snide.
Cip-modbus integration.
port, ODVA, Inc.,Modbus-IDA, April 2008.
Technical reURL http:
//modbus.org/docs/CIP%20Modbus%20Integration%
20Hanover%20Fair_0408.pdf.