9590-1001 ACM INSTALL GUIDE WEBSITE

9590-1001 ACM INSTALL GUIDE WEBSITE
ACTRON CONNECT MODULE
INSTALLATION & COMMISSIONING GUIDE
ActronConnect Module
ACM-1
Please Read This Guide
Congratulations on your purchase of an
ActronConnect Module. This unit has been
designed and manufactured with the highest
quality standard in mind.
Please read this guide thoroughly and keep it
in a safe place for future reference.
Copyright © 2015 Actron Engineering Pty. Ltd. All rights reserved.
This manual is a controlled document which contains confidential and proprietary information.
Distribution, modification, copying and/or reproduction are prohibited without written consent from ActronAir.
TABLE OF CONTENTS
ITEMS TO CONSIDER
Introduction .................................................................... 3
Kit Contents List ............................................................ 3
Items to Consider .......................................................... 3
Safety Instructions ......................................................... 3
Codes, Regulations & Standards .................................. 3
Specifications ................................................................ 4
Installation Instructions
Power Supply Installation Procedures ........................... 5
ActronConnect Module Installation Procedures ............ 8
Requirements for ACM Optimum Signal Performance... 9
Commissioning Instructions
ActronConnect Commissioning ..................................... 12
Wiring Diagram .............................................................. 20
• Carefully unpack the ActronConnect Module from its
packaging and ensure that all parts are included.
• Fully check the contents of your ActronConnect
Module kit against the content list upon receiving
your shipment. Inspect the module, components and
accessories for any sign of shipping damage. If there
is any damage to the contents, contact ActronAir
Customer Care Department immediately on:
1300 135 995.
• Make certain that the ActronConnect module is
compatible with the ActronAir air conditioning system
you plan to install it on. (See FAQs about the product).
• Take time to thoroughly read the installation &
commissioning instructions before proceeding with the
installation.
INTRODUCTION
SAFETY INSTRUCTIONS
CONGRATULATIONS on your purchase of an
ActronConnect Module! This has been designed and
engineered to give you total control of your ActronAir
ducted air conditioner, whether you are at home or
away. By using either the ActronConnect App on your
Apple iOS devise or through supported web browsers
from any smart phone, tablet or PC / Mac, you can now
monitor and control your air conditioner from wherever
you have internet connectivity.
The procedures outlined in this guide are provided
to correctly & safely install the ActronConnect
Module (ACM) to an appropriate ActronAir ducted air
conditioning system. Failure to follow these procedures
may result in personal injury, damage to the air
conditioner, damage to the ActronConnect module or
incorrect operation of the air conditioning system. Such
failure could render your warranty null and void.
KIT CONTENTS LIST
1 Pc - ActronConnect Wi-Fi Module
(ActronAir Part No. ACM-1)
1 Pc - ActronConnect Antenna
1 Pc - Power Supply pre-wired with
Power & Data cables - Sold as Spare Part Kit
(ActronAir Part No. 2020-200K)
1 Pc - Adhesive Back Wiring Diagram label
(ActronAir Document No. WD0904)
1 Pc - Installation & Commissioning Guide
(ActronAir Document No. 9590-1000)
1 Pc - Quick Start Guide
1 Pc - Double Sided Tape (50 x 30 x 2mm)
2 Pcs - M3 x 4mm Pan Head Screws
2 Pcs - #6 x 30mm Pan Head Needle Point Screws
1 Pc - Shipping Carton
2
Safety instructions and warnings provided on this
installation manual are in-exhaustive and given as
a guide only. Prevailing WH&S regulations must
be observed and will take precedence to the safety
instructions contained in this manual. Safe work
practices and environment must be of paramount
importance in the performance of all service
procedures.
• Ensure that all safety work procedures & Instructions
are adhered to at all times in order to prevent personal
injury or damage to the equipment.
• Only licensed service persons are allowed to perform
the procedures described in this manual.
• The indoor (evaporator) unit electrical panel has
230VAC electrical components inside. PLEASE
ISOLATE THE INCOMING POWER SUPPLY BEFORE
COMMENCING WORK. Supply can be isolated at the
Main Isolator located near the Air Conditioner (if fitted)
or at the Main Supply Circuit Breaker in the Distribution
Board supplying the Air Conditioner. Correct Lock Out
& Tag Out procedures should be followed to ensure
Power Supply is not re-energized accidently.
• The ActronConnect Module is IP20 Rated - NOT
FOR OUTDOOR USE. Install your ACM away from
excessive dust, heat and moisture.
• The ActronConnect Module is not a toy, keep away
from children and ensure that they are not allowed to
play or tamper with the device.
• The air conditioning electrical panel & the Actron
Connect module / kit contain static sensitive electronic
components. Careful handling & correct anti-static
procedures must be followed to prevent damage of the
equipment. Failure to protect the electronic components
from static electricity may cause unrepairable damage,
which is NOT COVERED for replacement under
Warranty.
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
• The instructions herein refer to work involving a Computer CPU
Chip & Electronic CPU Board, please ensure all Instructions are
followed accurately so as to prevent damage to these fragile & delicate
components.
CODES, REGULATIONS & STANDARDS
The installer and/or contractor assumes responsibility to ensure that
ActronConnect Module installation and commissioning comply with the
relevant council, state / federal codes, regulations and building code
standards. All electrical wiring must be in accordance with current
electrical authority regulations and all wiring connections to be as
per electrical diagram provided with the unit.
SPECIFICATIONS
ActronConnect Module Part No. ACM-1
Wi-Fi Protocol
802.11b/g/n
Operating System Requirement
IOS 6.1.3 or later version
Security Protocol
Web-128, WPA-PSK, WPA2-PSK
Hardware Voltage
9VDC - 15 VDC
Max. Operating Temperature
60oC
IP Rating
IP20
Max Cable Length from ACM to
Power Supply Kit
10 metres
Access Point Distance *
15 metres
Wi-Fi Range
70m line of sight
* The maximum distance that can be established between ACM and mobile device
(i.e. iphone, ipad, laptop) if the mobile device is acting as an access point.
Power Supply Part No. 2020-200K
Output Ratings
12VDC 1.3A 15.6W
Input Ratings
85~264VAC 120~370VDC
- Frequency Range
47~63Hz
- Inrush Current
Cold Start 65A / 230VAC
- Efficiency (Typical)
81%
- AC Current (Typical)
0.35A / 115VAC
0.25A / 230VAC
Working Temperature
-20~+70oC
Working Humidity
20-90% RH
non-condensing
Overload Protection
Above 105% Rated Power
O/L Protection Type
Hiccup mode, auto recovery after
fault condition is removed
Over Voltage Protection
13.8-16.2V
O/V Protection Type
Shut-Off o/p voltage, clamping by
zener diode
3
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
INSTALLATION INSTRUCTIONS
1.0 ActronConnect Power Supply & Module Installation Procedures:
1.1 Power Supply Installation Procedures:
Step 1.1.1. Isolate electrical power to the air conditioner at isolator or main switchboard.
Step 1.1.2. Remove lid from indoor unit electrical panel.
Lid- Electrical
Panel
Indoor Unit
Step 1.1.3. Mount the ActronConnect power supply kit, using either of the two options below, to the base of
the electrical panel as shown below:
Option 1 (Using the 2x4mm M3 screws):
“PLUG C” (RJ45 Data) & Cable
to ActronConnect Module
Power Supply Kit
(Pre-wired Supplied)
Ensure that the earth ring terminal is pointing towards
the right side (looking at the electrical panel)
Ensure the power supply ventilation
holes are NOT covered by the excess
cables or other foreign matter.
2x4mm M3
Mounting Screws
NOTE: Use mounting screws when holes
are existing in Electrical Panel base.
Option 2 (Using the Double Sided Tape):
“PLUG C” (RJ45 Data) & Cable
to ActronConnect Module
Power Supply Kit
(Pre-wired Supplied)
Ensure that the earth ring terminal is pointing towards
the right side (looking at the electrical panel)
Ensure the power supply ventilation
holes are NOT covered by the excess
cables or other foreign matter.
Double Sided
Tape
4
NOTES: Use double sided tape where there are no holes in the Electrical Panel base.
Make sure that the base of the electrical panel and the power supply are
clean and free of dirt or dust in order to provide a strong tape adhesion.
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
Step 1.1.4. Refer to the wiring diagram for the cable connections on pages 29 - 33.
Step 1.1.5A.
(Classic, ESP Plus & ESP Platinum Plus Models)
“PLUG A”
2 Pin Power
Connector
Step 1.1.5B.
(ESP Ultima & ESP Platinum Ultima Only)
P1
2 Pin Socket
Auxiliary Power
Socket
Ultima Power
Connector
“PLUG A” 2 Pin Power
Connector
P1
2 Pin Socket
Connect “PLUG A” (2 Pin Power Connector) for the
230VAC of the power supply into the corresponding
2 Pin Socket labelled “P1 (240VAC)” on the Indoor
PCB AMIB. (This plug only goes in one way, ensure
it is in correct orientation before pushing it all the
way in).
Unplug Ultima 2 Pin Power Connector from “P1”
and connect “PLUG A” as in Step 5A above.
Then, plug the Ultima power connector into the
auxiliary power socket.
Step 1.1.6. Connect “EARTH RING LUG” to the earthing bolt of the indoor unit electrical panel. Unscrew
the nut, remove the washer & slide the EARTH RING LUG over the bolt making sure all of the existing
earthing lugs remain connected. Replace earthing washer & nut and tighten the nut securely.
Earthing Bolt
& Washer
Existing
Earth Wires
ACM
Earth Wire
Step 1.1.7. Connect “PLUG B” (4 Pin JST) for the data of ActronAir Connect Module into the
corresponding 4 Pin Socket labelled “J4 DATA” on the Indoor PCB AMIB. (This plug only goes in one
way, ensure it is in correct orientation before pushing it all the way in).
ACM
“PLUG B”
(4 Pin JST)
Indoor
PCB AMIB
J4 DATA
(4 Pin Socket)
DATA
DATA
5
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
Step 1.1.8. Take the “PLUG C” (RJ45 Data) for the ActronConnect Module & run it out from the indoor
electrical panel via the large cable gland on the right side of the electrical panel. Feed the data cable all
of the way out so that only a minimum cable length remains inside the panel. Using cable ties, secure the
cable to the electrical panel and into the zone cables exiting from the same cable gland.
Run the ACM data
cable out from the
electrical panel
Large
Cable Gland
NOTE: For optimum performance & module communication integrity, keep the ActronConnect
Module data cable as far as possible from the 230VAC mains.
Step 1.1.9. Take the wiring diagram with adhesive back, peel off adhesive protection strip & stick the wiring
diagram unto the front the electrical panel lid.
Wiring Diagram
Electrical Panel
Indoor Unit
Lid- Electrical
Panel
Step 1.1.10. Check all connections and screw lid back onto indoor electrical panel.
6
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
1.2 ActronConnect Module Installation Procedures:
IMPORTANT NOTE: ActronConnect Module CANNOT be installed on the sheet metal
part of the indoor unit (particularly at the top) as the performance & integrity of the
wireless signal will be greatly reduced.
Step 1.2.1. Install the ActronConnect Module to a suitable secure location, like a roof joist or similar using
the supplied screws. Keep the module at least 0.5m away from the roof line and 1m from the indoor
unit, large metal objects or other sources of interference (e.g. antennas, exhaust fans, duct work, etc.).
Also ensure it is kept away from potential sources of dust, heat & moisture (i.e. light fixtures, heaters,
bathroom exhaust fan outlets, etc.)
Install the ActronConnect Module 0.5m
away (or greater) from the roof line.
Do Not Install the ActronConnect
Module on top of the indoor unit
ActronConnect Module
Roof
0.5
Manhole
m>
A
Indoor Unit
Return
Air Grille
w.i.r
1m>
See notes 3 & 4 for
ActronConnect Module
location requirements.
Install the ActronConnect Module 1m
away (or greater) from the Indoor unit .
ACTRONCONNECT MODULE INSTALLATION DIAGRAM
ActronConnect
Module
Roof Joist
Securely run cables along the roof
joist and at least 300mm away from
any other installed cable (i.e. power,
lights, PC data, TV antenna, etc.)
Secure the ActronConnect
Module to the roof joist using
the supplied screws.
DETAIL - “A”
NOTES:
1. Maximum Allowable Cable Length between the indoor unit and the ActronConnect module is 10m. This can be
achieved with the use of a 2-Way Joiner PN: 2045-121 (Sold Separately) and a 7m ACM extension cable PN: 4070-027
(Sold Separately). The Actron Power Supply kit comes pre-wired with 3m cable. Do not run ACM cable in parallel with the
240V power supply cable and keep 300mm minimum distance from other cables (mains, data, antenna, etc).
2. DO NOT USE Actron CAT5E zone cables to extend ACM cables.
3. Locate the ActronConnect Module as close as possible to the ceiling and the manhole for ease of access, ensuring that
LED is facing towards the manhole and that the roof insulation does not come into contact with the module.
4. Do not install ActronConnect Module in roof cavities where temperature can exceed 60oC. In the event where you require
to install the Actron Connect Module below the ceiling line (Eg. Storage cabinet), please ensure you use an appropriate
plastic enclosure (supplied by others) that complies with all relevant safety codes, regulations and standards.
7
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
Requirements for ActronConnect Module Optimum Signal Performance:
The ACM optimum signal performance depends on the mounting orientation of the unit and the positioning of the
antenna in relation to the Wi-Fi router.
Mounting Orientation
As much as possible, install the module in a direct line of sight with the router and keep the antennas parallel.
BEST
ACCEPTABLE
POOR
WORST
Location / Positioning
Do not locate the module where the signal will be blocked by any large metal, concrete structure or objects
with high water content. People, animals and plants are composed mostly of water. Make sure that these do
not interfere with the module signal. Maintain at least 0.5m distance between the ACM & router antennas.
Avoid getting the antenna in direct contact with any metal or near power supply.
NO BLOCKING OBJECTS ALLOWED
Typical Home Installation Examples:
Single Level Dwelling
As much as possible, install the ACM
with the antenna parallel and in direct
line of sight with the router antenna
Two Level or Multi-Level Dwelling
As much as possible, install the
ACM with the antenna parallel
and in direct line of sight with
the router antenna.
8
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
Step 1.2.2. Do not place the ActronConnect module where it can be easily damaged by accidentally
stepping on it or where it can be covered by ceiling insulation.
Step 1.2.3. Refer to the module mounting diagram - Requirements for ACM Optimum Signal Performance,
for the best mounting direction of the module based on your particular installation requirement.
Step 1.2.4. Refer to the wiring diagram for the cable connections on pages 29 - 33.
Step 1.2.5. Take the ActronConnect module 3m Grey Data Cable running from the indoor electrical panel
& run it to the installed module, ensuring it is in a position where it cannot be easily damaged and it is at
least 300mm away from any other installed cables (i.e. power, lights, PC data, TV antenna, etc.). If it is
impossible to avoid running the ACM data cable close to the other cables, run it across the other cables
at 90 degree (do not run in parallel).
3m ACM
Data Cable from the
Indoor Unit
ActronConnect
Module
Run the ACM data
cable from the Indoor
Unit to the ACM
Step 1.2.6. Secure the 3m Grey Data Cable to the timber roof joist or similar with the cable ties or other
suitable cable fixing fasteners. Do not loop any excess cable in a tight loop. Leave it loose.
NOT RECOMMENDED
Do NOT loop excess cable
9
RECOMMENDED
RUN data cable as straight
and short as possible
Strong possibility of communication problems.
No electro-magnetic interference.
The “loops” can cause an electro-magnetic
interference, upsetting data communication.
Keep communication cable at least 300mm
from high voltage cables.
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
Step 1.2.7. Connect “PLUG C” (RJ45 Data Plug) into ACM “Socket C” (labelled communication to indoor
board). This plug only goes in one way, ensure it is in correct orientation before pushing it all the way to
“lock” it in. Ensure there is an adequate slack on the cable so that no undue strain is placed on the RJ45
plug. Then screw Antenna into ACM socket and align as per instructions on Appendix A - Requirements
for ACM Optimum Signal Performance.
Antenna
ACM
Data Socket
Label - ACM
Data Socket
Antenna
“PLUG C”
(RJ45 Data Plug)
ACM
Antenna Socket
ACM
Data Socket
ACM
Data Socket
Step 1.2.8. Check all connections & cables to ensure correct connections and cables are secured properly.
Step 1.2.9. Power-up the air conditioner by turning-On the main isolator or at the Main Supply Circuit
Breaker in the Distribution Board. Ensure that the air conditioner powers up and operates correctly.
Step 1.2.10. Perform ActronConnect Module commissioning.
10
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
COMMISSIONING INSTRUCTIONS
2.0 ActronConnect Commissioning
Ensure that your home Wi-Fi network is switched-on and there is power to your air conditioner
before setting up your ActronConnect system,
Step 2.1 Download the ActronConnect app from the Apple app store.
2
1
Step 2.2 Open the ActronConnect app and press “no account? create one” to create your ActronAir
account.
1
2
11
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
Step 2.3 The Terms & Conditions page will appear, ensure that you read the Terms & Conditions and if you
accept, press “Accept” to proceed with commissioning.
NOTE:
• Visit www.actronair.com.au/privacy for
the updated Privacy Policy.
SCROLL DOWN
to read the
Terms & Conditions
and Accept
Step 2.4 Fill-in the details in the required fields of the registration page (i.e. your email address, password
& post code). You may also enter your details on the optional fields to help troubleshooting in the event
you need to contact our Technical Support team in the future. Then press “submit” to register your details.
1
2
NOTES: 1. You can chose any password, which is not necessarily the one you use for
your email access.
2. It is also advisable to create a different password for your ActronConnect
account, for your extra security.
3. Non-alphanumeric characters, i.e. %, #, $, space or & may be used for
stronger password security.
12
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
Step 2.5 Set up your air conditioning type & number of zones. Then press “next” to proceed.
1
2
3
5
6
4
13
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
Step 2.6 When the Welcome page appear, exit the ActronConnect app and go to your iOS device (iphone,
ipad, ipod etc...) “Setting” menu, click on “Wi-Fi”.
Step 2.7 Under devices, select the “ActronConnect” Wi-Fi network. Press “Join Anyway” to proceed.
2
1
NOTE: You may need to Turn-On your Wi-Fi, if it is Turned-Off.
14
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
IMPORTANT INFORMATION:
Wait for the Wi-Fi signal ( ) to appear before proceeding to the next step (it can take up to 1 minute).
If it hasn’t appeared, continue with the set up process.
Wi-Fi signal
wait for
approximate
1 minute
Step 2.8 After establishing your air conditioner’s Wi-Fi network (after connecting to ActronConnect),
re-open the ActronConnect app and press “next”.
1
2
15
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
Step 2.9 Set up your air conditioner network connection to your router by selecting your SSID (your
Wi-Fi network name) and typing your Passphrase (your Wi-Fi network password).
Illustrations below show how to select your SSID and how to enter and verify your Passphrase:
1
2
Scroll Up/Down to select your
Wi-Fi network name.
(Example “Your Network Name”)
3
5
7
4/6
8
NOTES: 1. SSID - Service Set Identifier, the name of the wireless network. All of the wireless
devices on a wireless local area network (WLAN) must employ the same SSID in order
to communicate with each other.
2. Passphrase - Password for your Wi-Fi network.
16
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
Step 2.10 Wait for the system to finish encrypting your air conditioner for access.
Once your air conditioner Wi-Fi access is
established, the screen below will be displayed
Do not
press “home”
Step 2.11 Close the ActronConnect app, then go to “Settings” and connect to your router.
1
2
NOTES: 1. You are now connected to ActronConnect network.
2. You must be within 15 meters between the installed ActronConnect Module
and the configuration device (iphone, ipod, PC...), to ensure optimum
communication signals.
17
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
Step 2.12 Re-open the ActronConnect app and press the “home” button.
After you established the air conditioner and iOS network
connectivity, the ActronConnect home page (as shown above)
will appear and you are now set to remotely operate and
control your air conditioner by using your iOS device.
18
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
WIRING DIAGRAM
R
Base
Model No:
Description:
Drawn:
This drawing remains the intellectual property of Actron Engineering Pty Ltd.
Reproduction, modification and/or distribution are prohibited without written consent.
Approved:
Variation Code:
SRG/V/M
Variation:
ACTRON CONNECT
M-SERIES INDOOR BOARD WITH ACTRON CONNECT
ACM MODULE & AUX POWER SUPPLY
Date:
MJH
MJH
Date:
14-07-2013
Drawing No:
Revision
Size:
B
A5
WD0904
20-07-2013
IMPORTANT:
IMPORTANT :
DONOT
NOTMOUNT
MOUNT
ACM
DIRECTLY
DO
ACM
DIRECTLY
ON INDOOR
ON INDOOR UNIT
UNIT.
- FOR OPTIMUM PERFORMANCE OF Wi-Fi
- FOR OPTIMUM PERFORMANCE OF
SIGNAL MOUNT 1 METRE AWAY (OR GREATER)
WIFI SIGNAL MOUNT MINUMUM OF
AND NOT ABOVE THE INDOOR UNIT.
1 METRE AWAY & NOT ABOVE
- MOUNT
MINIMUM 0.5 METRE BELOW ROOF
EVAPORATOR
LINE.
- MOUNT MINIMUM 1 METRE BELOW ROOF
ACTRON
CONNECT
MODULE
(ACM)
ACM POWER SUPPLY
(240VAC - 12VDC 1.3A)
ANTENNA
ADJ
RST MODE
ETH AC
PWR
BLUE
COIL IN
SENSOR
EC CONTROL
BROWN
EXV
BROWN
BRN / WHITE (GREEN)
GREEN / YELLOW
BLUE
BROWN
N
-V +V
P1
DC OUT
E2
AC IN
3G LPW WIFI ETH
A
SCRN
COM
PWR
KEY
COM
DATA
EARTH
NEUT
ACT
COIL OUT
SENSOR
B
MINOR NOTE REVISIONS
N/A
Rev.
Description
PCR
A
ORIGINAL
19
MJH 31-10-13
By
Date
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
A
FERRITE
E
N
A
EMC-1
Description
BLUE
FIELD WIRING BY
INSTALLER
ACT
BROWN
NEUT
NEUT
ACT
RLY
ZONE 2
DATA
ZONE 1
ZONE 3
ZONE 4
EXV
INDOOR
COIL OUT
SENSOR
INDOOR
COIL IN
SENSOR
RJ45 SOCKETS FOR ACTRON AIR
CAT5E ZONE CABLES
SCRN
ORIGINAL
By
PCR
Date
MJH 05-11-13
N/A
POWER
COM
KEY
SENSOR
OPTIONAL
SENSOR 1
SCREEN
WIRES
BROWN
N
EXV
-V +V
DC OUT
(DEPENDANT ON
MODEL VARIANTS)
IF FITTED
ADJ
OPTIONAL
SENSOR 2
DO NOT
CONNECT
SCREEN
AT WALL
CONTROL
SENSOR WIRING
R
ETH AC
ANTENNA
Description:
Variation Code:
ACM
AMIB
EMC
EXV
F
IF
IFRC
TX
WC
Variation:
LEGEND
Date:
Date:
02-07-2013
05-11-2013
WD0903
Drawing No:
B
Revision
SRG/V EVAPORATOR WITH EC FAN MOTOR
& OPTIONAL ACM WIFI MODULE & POWER SUPPLY
PWR
MH
MJH
WIFI
MODULE
Base
Model No:
RST MODE
ROOF
- MOUNT MINIMUM
0.5 METRE
BELOW
ROOF LINE.
- MOUNT MINIMUM
1 METRE
BELOW
POWER
COM
KEY
UNIT.
- FOR OPTIMUM PERFORMANCE OF Wi-Fi SIGNAL
- FOR OPTIMUM
OF AND
MOUNT 1 METRE
AWAYPERFORMANCE
(OR GREATER)
WIFI SIGNAL MOUNT 1 METRE AWAY
NOT ABOVE
THE
INDOOR
UNIT.
& NOT
ABOVE
EVAPORATOR
DO NOT
IMPORTANT:
MOUNT
ACM
DIRECTLY
ON INDOOR
DO NOT
MOUNT
WIFI MODULE
DIRECTLY ON EVAPORATOR UNIT
IMPORTANT :
SENSOR
SEE JUMPER PIN POSITION
TABLES ON UNIT WIRING DIAGRAM
FOR CORRECT POSITION
A
AC IN
GREEN / YELLOW
This drawing remains the intellectual property of Actron Engineering Drawn:
Pty Ltd. Reproduction, modification and/or distribution are prohibited
Approved:
without written consent.
FIELD WIRING BY INSTALLER CABLE MUST BE 2 CORE SHIELDED CABLE WITH SHIELD WIRE
CONNECTED TO THE SCREEN / COMMON TERMINAL
(EITHER 2C 14/0.20 SHIELDED OR 2C TWISTED PAIR 7/0.30 SHIELDED CABLE ACCEPTABLE)
TO OUTDOOR UNIT
LAYOUT CHANGES, ADDED SRV DETAILS
INTERNAL AUTO RESET
OVERLOAD PROTECTION
ECM
CONTROL
MODULE
F1
2A
COM
TX
20VA
BLUE
FIELD WIRING FOR M-SERIES
CONTROLS ONLY
KEY
ACM POWER SUPPLY
(240VAC - 12VDC 1.3A)
3G LPW WIFI ETH
Rev.
B
IF-1
EC
INDOOR FAN (IF)
1
A
N
EC CONTROL
EARTH
E2
PWR
P1
COM
BRN / WHITE (GREEN)
20
BROWN
AMZ-24V
Size:
A4
WIRING DIAGRAM
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
Description
FERRITE
ECM
CONTROL
MODULE
FIELD WIRING BY
INSTALLER
AMIB
DATA LOG
EXV
ZONE
MOTOR
INDOOR
COIL OUT
SENSOR
INDOOR
COIL IN
SENSOR
SCRN
KEY
AM-ZS
COM
ZONE
SENSOR 1
ACT
ORIGINAL
PCR
By
Date
SCREEN
WIRES
POWER
COM
KEY
SENSOR
A
N
AC IN
EXV
-V +V
DC OUT
DO NOT
CONNECT
SCREEN
AT WALL
CONTROL
ADJ
UNIT.
POWER
COM
KEY
SENSOR
RST MODE
ROOF
R
PWR
Variation Code:
ACM
AMIB
EMC
EXV
F
IF
IFRC
TX
WC
Variation:
LEGEND
MH
MJH
Date:
Date:
05-11-2013
05-11-2013
WD0907
Drawing No:
B
Revision
A4
Size:
EVAPORATOR WITH EC FAN MOTOR, 8Z-VAV ULTIMA
MODULE & OPTIONAL ACM WIFI MODULE & POWER SUPPLY
Description: SRM
Base
Model No:
ETH AC
ANTENNA
WIFI
MODULE
- MOUNT MINIMUM
METRE
BELOW
ROOF LINE.
- MOUNT0.5
MINIMUM
1 METRE
BELOW
- FOR OPTIMUM PERFORMANCE OF Wi-Fi SIGNAL
- FOR OPTIMUM
PERFORMANCE
OF AND
MOUNT 1 METRE
AWAY (OR
GREATER)
WIFI SIGNAL MOUNT 1 METRE AWAY
NOT ABOVE& THE
INDOOR
UNIT.
NOT ABOVE
EVAPORATOR
DO NOT
IMPORTANT:
MOUNT
ACM
DIRECTLY
ON INDOOR
DO NOT
MOUNT
WIFI MODULE
DIRECTLY ON EVAPORATOR UNIT
This drawing remains the intellectual property of Actron Engineering Drawn:
Pty Ltd. Reproduction, modification and/or distribution are prohibited
Approved:
without written consent.
FIELD WIRING BY INSTALLER CABLE MUST BE 2 CORE SHIELDED CABLE WITH SHIELD WIRE
CONNECTED TO THE SCREEN / COMMON TERMINAL
(EITHER 2C 14/0.20 SHIELDED OR 2C TWISTED PAIR 7/0.30 SHIELDED CABLE ACCEPTABLE)
E
N
A
EMC-1
240V
MAINS
ZONE ZONE ZONE ZONE
4
3
2
1
NEUT
ULTIMA MODULE
(8Z-VAV)
DATA
ZONE ZONE ZONE ZONE
8
7
6
5
BLUE
BLUE
BROWN
BROWN
TO ZONE 2 - 8
BLUE
ZONE
CONTROL 1
AM-ZC
BROWN
IMPORTANT :
3G LPW WIFI ETH
A
Rev.
INTERNAL AUTO RESET
OVERLOAD PROTECTION
INDOOR FAN (IF)
IF-1
EC
A
N
1
TO OUTDOOR UNIT
EC CONTROL
EARTH
E2
PWR
P1
COM
ACM POWER SUPPLY
(240VAC - 12VDC 1.3A)
GREEN / YELLOW
ULTIMA 8Z-VAV MODULE CONNECTIONS & ACCESSORIES
(SRM MODELS ONLY)
BROWN
21
BRN / WHITE (GREEN)
8Z-VAV
WIRING DIAGRAM
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
240V
MAINS
AMIB
DATA LOG
ULTIMA MODULE
(8Z-VAV)
ACT
Description
ORIGINAL
PCR
By
Date
FIELD WIRING BY INSTALLER CABLE MUST BE 2 CORE 7/0.30 SHIELDED TWISTED PAIR DATA CABLE
WITH SCREEN WIRE CONNECTED TO THE SCREEN TERMINAL ON INDOOR UNIT
& SCREEN FOIL CLAMPED TO P-CLIP ON OUTDOOR UNIT
FIELD WIRING BY
INSTALLER
DATA
KEY
N
AC IN
-V +V
DC OUT
POWER
COM
KEY
SENSOR
DO NOT
CONNECT
SCREEN
AND SENSOR
AT WALL
CONTROL
POWER
COM
KEY
SENSOR
DATA CABLE SCREEN WIRE KEEP AS SHORT AS POSSIBLE
SEE JUMPER PIN POSITION
TABLES FOR CORRECT SETTING
ADJ
R
Description:
Base
Model No:
PWR
ACM
AMIB
EMC
EXV
F
IF
IFRC
TX
WC
8Z-VAV
A/C Model
N/A
N/A
E
Variation:
LEGEND
Date:
Date:
05-11-2013
05-11-2013
WD2004
Drawing No:
A
Revision
ERM EVAPORATOR WITH EC FAN MOTOR
& OPTIONAL ACM WIFI MODULE & POWER SUPPLY
Variation Code:
ERM4-19AS
D
ERM3-17AS
ERM2-14AS
C
B
A
Jumper Pin
Position
PCB Model: AMIB-PVVM
PCB JUMPER PIN
POSITION TABLES
ETH AC
ANTENNA
WIFI
MODULE
MH
MJH
RST MODE
ROOF
- MOUNT MINIMUM
0.5 METRE BELOW ROOF LINE.
- MOUNT MINIMUM 1 METRE BELOW
& NOT ABOVE EVAPORATOR
DO NOT MOUNT WIFI MODULE
- FOR OPTIMUM PERFORMANCE
OF Wi-Fi SIGNAL
DIRECTLY ON EVAPORATOR UNIT
MOUNT 1 METRE AWAY (OR GREATER) AND
- FOR OPTIMUM PERFORMANCE OF
NOT ABOVE THEWIFI
INDOOR
UNIT.
SIGNAL MOUNT
1 METRE AWAY
IMPORTANT:
DO NOT MOUNT ACM DIRECTLY ON INDOOR UNIT.
This drawing remains the intellectual property of Actron Engineering Drawn:
Pty Ltd. Reproduction, modification and/or distribution are prohibited
Approved:
without written consent.
SCREEN
WIRES
INDOOR
COIL IN
SENSOR
A
MAINTAIN TWISTED PAIR
UNTIL TERMINAL ON AMIB
ZONE
CONTROL 1
ZONE
MOTOR
ACM POWER SUPPLY
(240VAC - 12VDC 1.3A)
BROWN
IMPORTANT :
3G LPW WIFI ETH
A
Rev.
CB-1
10 A
E
N
A
FERRITE
(IF FITTED)
IF-1
1 EC
ACT
ZONE ZONE ZONE ZONE
4
3
2
1
COM
ZONE ZONE ZONE ZONE
8
7
6
5
BLUE
BLUE
ECM
CONTROL
MODULE
NEUT
TO ZONE 2 - 8
NEUT
ZONE
SENSOR 1
GREEN / YELLOW
RJ45 SOCKETS FOR ACTRON AIR
CAT5E SPEC CABLES ONLY
SCRN
INTERNAL AUTO RESET
OVERLOAD PROTECTION
BROWN
BROWN
B (-)
(+) A
BLUE
INDOOR FAN (IF)
A
N
EMC-1
LINE 1
OUTDOOR
DATA
FERRITE
NEUT
EC CONTROL
EARTH
E2
PWR
P1
COM
BROWN
22
BRN / WHITE (GREEN)
FIELD WIRING
Size:
A4
WIRING DIAGRAM
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
BROWN
BLUE
Description
ORIGINAL
PCR
By
ACT
ZONE 1
NEUT
Date
RLY
ZONE 2
OPTIONAL
SENSOR 2
FIELD WIRING BY INSTALLER CABLE MUST BE 2 CORE 7/0.30 SHIELDED TWISTED PAIR DATA CABLE
WITH SCREEN WIRE CONNECTED TO THE SCREEN TERMINAL ON INDOOR UNIT
& SCREEN FOIL CLAMPED TO P-CLIP ON OUTDOOR UNIT
FIELD WIRING BY
INSTALLER
ACT
ZONE 4
INDOOR
COIL IN
SENSOR
BROWN
N
AC IN
-V +V
DC OUT
POWER
COM
KEY
SENSOR
DO NOT
CONNECT
SCREEN
AND SENSOR
AT WALL
CONTROL
POWER
COM
KEY
SENSOR
DATA CABLE SCREEN WIRE KEEP AS SHORT AS POSSIBLE
SCREEN
WIRES
ADJ
SEE JUMPER PIN POSITION
TABLES FOR CORRECT SETTING
MAINTAIN TWISTED PAIR
UNTIL TERMINAL ON AMIB
A
GREEN / YELLOW
SCRN
R
Description:
Base
Model No:
ETH AC
ANTENNA
WIFI
MODULE
PWR
A/C Model
ERV4-19AS
N/A
N/A
D
E
ACM
AMIB
EMC
EXV
F
IF
IFRC
TX
WC
LEGEND
MH
MJH
Date:
Date:
05-11-2013
05-11-2013
WD2005
Drawing No:
A
Revision
ERV EVAPORATOR WITH EC FAN MOTOR
& OPTIONAL ACM WIFI MODULE & POWER SUPPLY
Variation:
AMZ-24V
Variation Code:
ERV3-17AS
C
ERV2-14AS
B
A
Jumper Pin
Position
PCB Model: AMIB-P1VV
PCB JUMPER PIN
POSITION TABLES
RST MODE
ROOF
- MOUNT MINIMUM
0.5 METRE BELOW ROOF LINE.
- MOUNT MINIMUM 1 METRE BELOW
& NOT ABOVE EVAPORATOR
NOT MOUNT WIFI MODULE
- FOR OPTIMUMDO
PERFORMANCE
OF Wi-Fi SIGNAL
DIRECTLY ON EVAPORATOR UNIT
MOUNT 1 METRE AWAY (OR GREATER) AND
- FOR OPTIMUM PERFORMANCE OF
NOT ABOVE THE
UNIT.
WIFI INDOOR
SIGNAL MOUNT
1 METRE AWAY
IMPORTANT:
DO NOT MOUNT ACM DIRECTLY ON INDOOR UNIT.
This drawing remains the intellectual property of Actron Engineering Drawn:
Pty Ltd. Reproduction, modification and/or distribution are prohibited
Approved:
without written consent.
OPTIONAL
SENSOR 1
ZONE 3
RJ45 SOCKETS FOR ACTRON AIR
CAT5E ZONE CABLES
DATA
ACM POWER SUPPLY
(240VAC - 12VDC 1.3A)
3G LPW WIFI ETH
A
Rev.
CB-1
10 A
E
N
A
FERRITE
(IF FITTED)
TX
20VA
F1
2A
NEUT
IF-1
1 EC
COM
ECM
CONTROL
MODULE
NEUT
FIELD WIRING FOR M-SERIES
CONTROLS ONLY
KEY
INTERNAL AUTO RESET
OVERLOAD PROTECTION
ACT
B (-)
(+) A
BLUE
INDOOR FAN (IF)
A
N
EMC-1
LINE 1
OUTDOOR
DATA
FERRITE
NEUT
EC CONTROL
EARTH
E2
PWR
P1
COM
BROWN
23
BRN / WHITE (GREEN)
IMPORTANT :
Size:
A4
WIRING DIAGRAM
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
1800 119 229
www.actronair.com.au
Refrigerant Trading Authorisation
No.: AU06394
Actron Engineering Pty Ltd
ABN 34 002 767 240
HEAD OFFICE SYDNEY AUSTRALIA
Copyright © 2015 Actron Engineering Pty. Ltd.
Printed in Australia
Part No. 9590-1001
Rev. No. 3.0 150901C
Was this manual useful for you? yes no