getting started
GETTING STARTED
2.0 GETTING STARTED
To help ensure a project starts on the right foot, in this section, NUDURA
has compiled some helpful tips to help guide your building design, contract
documentation, basic structural analysis, layout and elevation planning,
estimation techniques and formulae and finally requirements for a typical
permit submission involving NUDURA product as well as tips on preconstruction planning specific for a NUDURA building site. Following these
steps should help to avoid delays when submitting your documents for
building permit approval, and start your project on its way to a smooth and
efficient build.
The permit applicant (usually the contractor) is ultimately responsible for
communicating with, and ensuring that, the building department has the
required information to process and issue a permit for a proposed project.
FIGURE 2.01
2.1 DRAWING & CONTRACT DOCUMENT PREPARATIONS
A smooth permit submission starts with the project drawings. Whether the project is starting from scratch in planning for
use of NUDURA or you are converting a drawing set from conventional construction to NUDURA, the building official will
need to see sufficient documentation to corroborate that NUDURA is being used on the project and how it is specified
and detailed.
First, determine the size and scope of your proposed building design and prepare your drawing set (or contact a local
draftsperson or AutoCAD designer) to reflect the fact that the building is being constructed using NUDURA Integrated
Building Technology. NUDURA’s experience has shown that there is nothing that gets a Building Official more incensed
than a contractor or designer attempting to substitute a building system or component on a set of plans or building site
that has not been properly referenced or documented on the permit application documents. Here are a few guidelines on
what to include that will help the Building Official be more accepting of the submission documents:
(a) Notes on the basement floor plan, either stand alone or indicating by arrow, to the foundation wall:
• The Form Unit Core Thickness proposed for the installation
• The Horizontal Bar Diameter and required c/c spacing (per the Governing Code Data, NUDURA Structural
Data or Evaluation Report, usually 18” o/c (457 mm) or at floor levels and every other course at minimum
if permitted by code)
• The Vertical Bar Diameter and required c/c spacing (reference back to the design tables for the local
region– below grade)
• Indicate that the vertical steel will project 20” to 24” (500 mm to 600 mm) above the first pour to stub
into the main level wall cavity
• Indicate that footing dowels of minimum #4 (USA) or 10M (CAN) bar at a maximum of 24”(600 mm) o/c,
or #5 (USA) or 15M (CAN) bar at a maximum 48” (1220 mm) along the footing centre line and project into
the foundation wall above the footing a minimum of 8” (200 mm)
(b) Notes on the main and any subsequent floor plan either stand alone or indicating by arrow to the exterior
walls:
• The Form Unit Core Thickness
• The Horizontal Bar Diameter and required c/c spacing (usually 18” o/c (457 mm) or reference the tables
for the local region or Evaluation Report)
• The Vertical Bar Diameter and required c/c spacing (reference the tables for the local region or
Evaluation Report)
M A N U A L
13
I N S T A L L A T I O N
GETTING STARTED
• Indicate how the floors will be attached to the NUDURA wall (rim joist bolts, ICF Connect etc) and
attach any corroborating data from the manufacturer or applicable code for spacing of these
attachments. If a second floor is required, indicate that the vertical steel will project between 20”
and 24” (508 mm and 610 mm) above the first pour to stub into the 2nd level wall cavity
• Indicate the roof truss sill anchor bolts diameter & spacing
(c) For all floor plans (including foundation plan), indicate at each window the required specifications for the
lintels intended to be installed. These will include:
• The number, and diameter of the bottom horizontal bars in the lintel
• The stirrup end distance (SED - the distance in from the edge of the opening that the stirrups
start). Refer the Building Official to the installation manual diagram or perhaps staple a copy to the
drawings to show the lintel cross section
• The stirrup spacing back to the jamb from the SED, (see the lintel table notes in appendix E)
• The overall height of the lintel
• Indicate on the plan with a dashed line (i.e. ___________ _ ___________) the fact that the bottom
and top horizontal steel of the lintel extends 24” (610 mm) beyond the edge of the openings
• As an alternate to including the above notes at each window, a lintel schedule which the openings
can be referenced to can be created, similar to a Window Schedule Layout. This method of notation
is preferred
2.1.1 GUIDELINES FOR REINFORCING STEEL DESIGN AND
PLACEMENT
In preparing drawings, the most important difference between typical poured concrete walls and NUDURA walls
is the fact that the walls are reinforced walls. Under most building codes, NUDURA is classified as a “Flat Wall ICF
System” meaning that it enables the creation of flat monolithic structural reinforced concrete walls contained within
the form system.
HOW NUDURA STEEL PLACEMENT DIFFERS FROM CONVENTIONAL POURED WALL
REINFORCEMENT DESIGN
In considering flat wall design using NUDURA Insulated Concrete Forms, it is best to consider the wall in exactly
the same manner as all performance based building codes do – it is simply a structurally reinforced monolithic flat
concrete wall with insulation mounted to both sides of the poured wall.
1.
MINIMAL TIE WIRING. Though selected details of
steel tying may be required at custom column or beam
installations or around openings, the primary assembly
of steel occurs without the use of tie wiring. Instead,
NUDURA relies on features built into its web or cross tie
design to enable the wall to be constructed by relying
on the “Non-contact Lap Splice” method of reinforcing
for both horizontal and vertical steel placement as is
provided for under Section 12 of ACI 318 in the USA
and CAN/CSA A23.1 and A23.3 in Canada. Under most
code bodies all non-contact lap splices installed must be
lapped a minimum lap splice length of 40 times the bar
diameter. This falls under the applicable concrete codes
for monolithic concrete walls which this distance is
based on requirements for bundled bars laps in flexural
members as per ACI 318 Section 7.6.6.4 and CAN/CSA
A23.3 Section 7.4.2.3. In addition, the lapped bars must
not be positioned greater than 1/5th of the lap splice
length apart or any further apart than 6” (152 mm).
(Section 12.14.2.3 of both ACI 318 & CSA A23.3).
FIGURE 2.02
14
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
2. ORDER OF STEEL PLACEMENT. Unlike traditional forming, where the steel grid is cross wired together prior
to the final form face being installed, NUDURA wall reinforcing steel proceeds with placement of HORIZONTAL
steel being laid in, in non-contact splice fashion, course by course as the form units (or blocks) are installed
around the wall in bond stacking fashion. Corners and T form Wall connections, again, will normally feature
non-contact lap splice connections (unless specific requirements of the design parameters for a local
condition would dictate otherwise). VERTICAL steel placement then proceeds once coursing heights have
reached either the top of each floor height of wall being installed (in multi-story installations) or (in the case
of a staged single story tall height wall pour) at the designated termination drop height as dictated by the
engineer (typically between 8’ and 12’ (2.4 m and 3.6 m in height). In these instances, the steel is cut by the
installer to ensure a 40 times bar diameter non-contact lap splice with the level of floor being installed above
it.
3. NO TIE WIRING AT FOOTINGS. Again, as
adopted within most building codes, the
footing dowels are in place to resist lateral
movement at the base of the wall section
through the installation of wet set dowels
which extend from the footing into the
base of the wall to be installed over it. The
assembly order of the vertical steel requires
that they be placed AFTER the wall is
installed to full floor course height. This also
dictates that there is NO requirement for
the contractor/installer to provide tie wiring
of the vertical steel to the footing (footer)
dowels. Hence, a non-contact lap splice
between the footing (footer) dowels and the
wall steel is required at this junction.
FIGURE 2.03
HORIZONTAL STEEL PLACEMENT METHOD
FIGURE 2.04
NUDURA’s unique web design allows the contractor/installer the ability to
precisely locate reinforcing steel within the wall cavity, ensuring the rebar
stays in the optimal required location, thus maximizing the strength of the
complete concrete wall. (See Fig. 2.04) This is enabled by notches or capture
lugs that are molded into the top and bottom of each cross tie connecting
web, which allows the contractor/installer to accurately install the
horizontal reinforcement bars within the concrete core in accordance with
the Engineer’s specifications. This eliminates the requirement of tie wiring
the horizontal reinforcement bar in the correct location specified by the
Engineer (in fact, enabling placement as close as ¾” (19 mm) from the inside
face of the form). This improves overall strength performance of the wall
assembly which gives the design professional the comfort level of knowing
the reinforcing steel has been cast in exact locations as specified.
NOTE: In the diagram (Fig. 2.04), for a 6” (152 mm) core form, there are 4 pairs of horizontal steel capture lugs per
connection web, each of the lugs being positioned approximately ¾” (19 mm) apart. This design feature is typical
across the form line design for each cavity width of form available - with the wider forms providing more options for
steel placement as space permits. The 3/4” (19 mm) gap is the secret to enabling vertical steel to be installed once course
installations are completed (see Vertical Steel Placement Method under this Section).
M A N U A L
15
I N S T A L L A T I O N
GETTING STARTED
HORIZONTAL STEEL SPECIFICATION TIPS
• NUDURA forms are manufactured to a course height of
18” (457 mm). Therefore, for efficient on-site installation,
always specify horizontal reinforcing at no denser a
placement than 18” (457 mm) o/c. (Adjust vertical
reinforcing density so that this 18” (457 mm) module can
be maintained horizontally).
• If EXTRA horizontal reinforcement should be required
(i.e. for higher seismic zones), consider moving to
a higher diameter bar or – as a last resort, consider
specifying placement of bar at the top AND bottom of a
form unit.
• As per installation instruction, detailing would typically
show the horizontal reinforcing oscillating from one
lock position (of the pair of reinforcing steel cradles) to
the other between horizontal lap splices. As installation
proceeds up the wall, the installer will install the steel
in the course immediately above in exact opposite
positioning of the course below, in such a way that at
every course (every 18” (457 mm)), horizontal bar will
be capturing either one side of the vertical steel or the
other as per positioning specification by the engineer
(see Figure 2.05a).
• The placement of the horizontal steel can secure the
vertical steel in the center and either the tension or
compression side of the wall.
• To take full advantage of the accuracy of steel
placement, the engineer may detail horizontal steel
placement to position the vertical steel to occur:
(a) Towards the tension (usually towards the “inside”
of a below grade wall)
(b) Towards the outside (tension side) of a foundation
wall containing back fill higher than the prevailing
grade around it or if installed as a non-laterally
supported retaining wall
(c) To the center of an above grade wall anticipating
wind loading from multiple directions (as shown in
Fig. 2.05b)
FIGURE 2.05a
FIGURE 2.05b
16
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
VERTICAL STEEL PLACEMENT METHOD
NUDURA’s cross connecting web ties are preformed into the EPS panels at 8” (203 mm) o/c increments. To optimize
vertical steel placement, a NUDURA Trained Installer is instructed to do 3 things:
(a) Ensure that the forms are placed with ALL webs being in vertical alignment with each other.
(b) Feed vertical steel downward into the wall such that it will be WOVEN into the central 3/4” (19 mm) gap that is
formed by the oscillating placement of the horizontal steel courses (as noted above)
(c) Install vertical steel so that it occurs adjacent to a web on the side from which concrete is intended to be first
placed into the wall. This means that as the concrete pushes against the vertical steel, the pressure of the
concrete will drive the steel against the web and the web will prevent the vertical steel from moving out of
alignment during the pour (hence, no tie wiring required)
By following the vertical steel specification tips given below, the design professional will guarantee that the installer
will be able to best optimize accurate and rapid steel installation within the NUDURA wall system.
VERTICAL STEEL SPECIFICATION TIPS
Using the above installer techniques as a guide, remember that reinforcing steel proceeds MOST efficiently if specified
on vertical grids that are multiples of 8” (203 mm) on center. (i.e. 8, 16, 24, 32, 40, 48” (203, 406, 610, 813, 1016, 1219
mm) o/c).
If the design calculation requires vertical steel at increments not within the 8” (203mm) spacing of the web, NUDURA
recommends that the designer consider doubling every other reinforcement bar or to vary the bar diameter. This
achieves the same required cross sectional area of steel in order to meet the design specifications.
When dealing with a cold joint, it is recommended to wet set dowels into the concrete as deep as 40 times the
diameter of the reinforcement bar using a non contact lap splice. This will facilitate an easier in-field build than more
traditional methods which require joint level access for tie wiring. Always remember that vertical steel is placed AFTER
the wall is constructed to the designated construction height and prior to concrete placement.
2.1.2 HOW TO DESIGN WALLS AND LINTELS USING
APPENDIX D AND E
Anyone already familiar with either the prescriptive methods employed in the design tables featured in either the USA
International Residential Code (Section R404 and R611) or in NBC Codes 2005 and later under Section 9.17 and 9.20 can
skip this information. However, if needed, you can always refer to this method if instructing someone new on how to
use the Structural Design Tables contained in Appendix D and E of this manual.
Why use separate tables from Code Published Prescriptive Data? The Tables contained in Appendices D and E have
been designed to conform to exactly the same concrete standards and limits as the IRC and NBC Code Tables conform
to. However, NUDURA’s Engineers have designed these tables to ideally work with the specific geometry of the
NUDURA Form System (i.e. form unit heights of 18” (457 mm) and vertical web spacing at 8” (203 mm) on center and
core thicknesses exactly matching the available form unit thicknesses of NUDURA’s form line-up).
IMPORTANT NOTES
1. Remember that the Design Tables have been based on the design methods adopted for prescriptive design
for residential construction (single family residences, townhouse or one and two family homes) in either
Canada or in the USA ONLY, and in conformance with the allowable limits under the applicable code sections
or the applicable evaluation report for each country.
M A N U A L
17
I N S T A L L A T I O N
GETTING STARTED
2. Similar to the majority of prescriptive data available in North America, NUDURA’s Structural Tables
(Appendix D for Wall Design and E for Lintel Design) have been prepared basing design on 2 key elements:
Minimum Concrete Compressive Strength shall be: Minimum Yield Strength of Reinforcing Steel shall be: 60 kips/in2 or 400 Grade
3,000 lb/in2 or 20 MPa
3. Remember as well that the Engineers who have designed these tables have spelled out clear limitations
to their use in the notes preceding the tables, limiting such things as maximum allowable live and dead
loads, truss and floor span limits, roof slope, number of storeys above (maximum 2) and below (maximum
1) grade, even maximum allowable plan dimension, (in exact conformance with the prescriptive limits of
the applicable Code). NUDURA’s engineers have assured that the selected design options will exceed the
minimum reinforcement requirements for each country. However, please note that the designer/builder
remains fully responsible for the CORRECT usage of these tables in applying the design parameters required
to yield the final results.
BELOW GRADE WALL DESIGN = APPENDIX D
The designer needs to know 5 pieces of data:
1. The desired core thickness that the client wishes to be used in the design (always start with 6” (152 mm)).
2. The maximum height of the wall from the top surface of the footing to the underside of the floor joist
connection to the wall.
3. The height of backfill being placed against the wall. This is defined as the distance from the top of the
basement floor slab to the maximum level of the backfill outside of the basement.
4. The general type of soil
condition anticipated
for the site, whether
it will be gravel/sand,
sand loam mix, or
clay or silt mix. The
designer or builder
should consider the
worst case scenario if a
combination of these
soils is expected on site.
2
3
4
1
5. The seismic zone
classification for the
site. (Depending on
location this may or
may NOT effect the
design of below grade
walls since backfill
stresses tend to far
outweigh seismic
effects).
FIGURE 2.06
18
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
PROCEDURE
1. Knowing above information, from the Below Grade Design Tables select the correct design table from the
options available (based on desired core thickness (6, 8 or 10” (152, 203, or 254 mm)) and seismic risk (Low
or High).
2. Once the table has been selected, from the 2 left hand columns of the table, identify the required wall
height and backfill height for each wall condition.
3. Next select the appropriate set of columns corresponding to the prevailing soil type at your site.
4. Note the required reinforcement for the condition at the corresponding cell to your required backfill height
and desired core thickness of concrete. If there is NO notation, it means that you must select a higher core
thickness of concrete.
5. If after repeating the scenario for both 8” (203 mm) and 10” (254 mm) core thicknesses, no scenario is able
to be located to satisfy the requirement, a structural engineer will have to be contracted to complete the
design to suit the condition.
ABOVE GRADE WALL DESIGN = APPENDIX D
As in Below Grade Design, the designer again needs to know 5 pieces of data:
1. The desired core thickness that the client wishes to be used in the design (Unless there are tight spatial
considerations, always start with 6” (152 mm)).
2. Whether the wall being considered is one of 3 scenarios
(a) The TOP floor of a one or two storey NUDURA building
(b) The BOTTOM storey of a NUDURA Building with light framed 2nd storey and roof
(c) The BOTTOM storey of a FULL two storey NUDURA Building
The 3rd scenario will usually require denser, or more, reinforcement than the first 2 scenarios.
3. The maximum height of the wall from the top surface of the ground floor to the underside of either the
ceiling joists or roof trusses of either the 1st or 2nd floor.
4. The seismic condition
anticipated for the
site. (The higher the
classification, the more
steel will be required in
the design.) This data
can be gleaned from
the applicable Building
Code or identified
by the local Building
Official for your region.
1
3
2
FIGURE 2.07
I N S T A L L A T I O N
M A N U A L
19
5. The wind speed (or
design wind pressure)
for the site. Again,
the higher the wind
pressure, the more
severe the steel
placement or increased
the bar diameter will
be. Like the seismic
data, you can obtain
this pressure from the
Building Code or your
local Building Official.
4
GETTING STARTED
PROCEDURE
1. Knowing above information, from the Above Grade Design Tables select the correct design table from
the options available, (based on wind pressure and seismic zone thickness (Low, Medium or High to the
maximum condition noted). If your scenario is not listed, a professional engineer MUST be contracted to
complete the design.
2. Once the table has been selected, from the left side of the table, identify the required wall height for your
design from the very left hand column of the table.
3. Next, select the appropriate set of columns corresponding to the prevailing seismic zone of your site.
4. Finally, select your desired wall core thickness.
5. Note the required reinforcement for the condition at the corresponding cell to your required wall height
and desired core thickness of concrete. If there is NO notation, it means that you must select a higher core
thickness of concrete.
6. If no scenario can be located to satisfy the requirement after testing all subsequent core thicknesses, as in the
Below Grade Tables, a structural engineer will have to be contracted to complete the design to suit the site
condition.
LINTEL REINFORCEMENT DESIGN
Similar to the Wall Design Tables found in Appendix D, the Lintel Reinforcing Steel Design Tables in Appendix E
apply to residential buildings ONLY that conform to the statement of limitations applied to the Prescriptive Design
Requirements for Flat Wall Insulating Concrete Forms as noted in the IRC (USA) and under Part 9 of the NBC (CAN)
(i.e. light frame roofs and light framed floor systems).
IMPORTANT NOTES REGARDING LINTEL DESIGN
Again, the Designer is cautioned to carefully review the design limits and notes that precede the Lintel Design Tables
to assure that they fully understand what the limitations for application are. Of special importance within these notes
is the fact that the tables are designed to resist UNIFORMLY DISTRIBUTED LOADS ONLY. Point loads as may be applied
by girder trusses or beams have not been taken into consideration in the designs. In cases such as these, consideration
should be made in your design to either:
(a) Relocate the point load, if possible.
(b) Relocate the opening.
(c) If neither is possible, an engineer should be contracted to produce a stamped lintel design specific to the
condition to carry the point load.
DETERMINING UNIFORMLY DISTRIBUTED LOADS
NUDURA’s lintel tables differ somewhat from design data that may be contained in some Code Prescriptive Material in
that the user must calculate the anticipated Uniformly Distributed Load (or UDL) condition for your lintel design. The
following procedure outlines how this is accomplished.
1. First, If you are a design builder and you have already ordered or commissioned truss drawings or floor
trusses for the project, the accompanying paperwork from the truss company or joist manufacturer can be
used to automatically give you the required uniformly distributed loads at the reaction or bearing points of
the truss or floor joist/truss without having to calculate yourself. If you don’t have truss drawings or preengineered floor system drawings, you will have to calculate these loads yourself as outlined below.
20
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
2. First you need to determine the anticipated Live and Dead Loads for the building.
Dead Loads (or DL) are defined as any load that forms a permanent part of the building structure, such as
joists, trusses, sheathing, shingles, tiles , etc. (these will typically fall anywhere between 5 to 15 lbs/ft2
(24.41 kg/m2 or 0.239 kPa). If floor or roof finishes demand heavier materials (such as tiles or slate) find out
their densities/area of coverage and be sure to add these to your loads.
Live Loads (or LL) are defined as any load that will act on the structure temporarily. These include occupants
and furniture for floors, wind and, most importantly, snow loads for roofs. This data is already set by your
local Building Code. Just as you did for the seismic and wind data for your wall design, consult either the
code or your local building official for the assigned climatic and live load data for your area.
Occupant live loads will vary with occupancy type. See the list below for some examples of how these loads
can change. The chances are, if you are using NUDURA’s tables for prescriptive design, you will only need
to worry about residential live loads. However, if you are using the tables as a guide for quoting other work
(that will involve engineer design at a later date) remember that lintel design for things such as offices,
churches or theater type complexes will demand significantly more live load to be designed for, hence much
more steel required for the lintels.
Residences: 40 lbs/ft2 (195.30 kg/m2 or 1.92 kPa)
Commercial: 50 lbs/ft2 (244.12 kg/m2 or 2.39 kPa)
Assembly: 100 lbs/ft2 (488.24 kg/m2 or 4.79 kPa)
3. Next, for each lintel condition, examine the opening condition in context to where it occurs in the building
plan. (i.e. under a roof bearing or under a floor bearing condition). If the lintel condition is occurring in the
bottom storey of a two storey building, although the roof condition in the storey above will exert some load,
the majority of this load will be spread through the wall reinforcement occurring far above the lintel that’s
carrying the floor; the prominent load to be considered will be the condition immediately above the lintel
(the floor load).
4. Note on the plan where the roof or floor trusses bearing onto the lintel span to the rest of the building. If it is
a roof condition, chances are the roof truss may be spanning the full width of the plan. These are usually the
most severe conditions of reinforcement. If the lintel will be carrying roof trusses, check whether or not there
is a bearing wall in the middle of the floor plan carrying part of the roof truss. Note the dimensions of the
span from the exterior bearing wall containing the opening, and the bearing condition on the opposite end
of the truss or floor framing member.
5. If the opening is under a floor, the bearing point of the floor span will often be located in the middle of the
building depth, particularly if standard floor joists are being used. In the case of engineered wood or framed
floor systems (floor trusses), the spans will typically be longer, and perhaps will extend full depth/width of a
floor plan to an exterior wall. Again, note the total span length of the structural member.
6. Now that you have the load data, calculating the uniformly distributed load (UDL) for your lintel conditions
will be fairly easy. NUDURA’s lintel tables have been designed to assign the safety factors FOR you. As
a designer, you need not apply any additional safety factors for live or dead loads as these have been
computed INTO the results on the tables. To calculate UDL use this simple formula:
UDL = (Total DL + Total LL) x ½ the span member length
The result will give you a load expressed in lbs per linear foot (or kg per linear meter) ready for use in the next
section.
M A N U A L
21
I N S T A L L A T I O N
GETTING STARTED
THE LINTEL DESIGN PROCESS
3
2
To use the Lintel Design Tables, you will need to
know 4 pieces of data. These include:
1. The lintel’s concrete core thickness
2. The available height in the wall above
the lintel
3. The width of the opening required to
be spanned
4. The total UDL calculated from above
4
_______________________________
1. Select the appropriate Lintel based
on the easy number system listed in
the lower right corner of each Table.
The first digit stands for the lintel core
thickness- the second 2 digits after the
FIGURE 2.08
dash indicate the height or depth of the
lintel in “inches”. For example, as noted in Figure 2.08, Lintel No. L6-15 means that it will be a lintel for a 6”
(152 mm) thick wall that will be 15” (381 mm) deep when completed. A common strategy established by
many designers or builders is to try and stick with a common lintel height that can be repeated around the
building with a common stirrup height for a broad range of openings. This way, if stirrups are ordered
pre-bent from a metal fabricator, all stirrups can be ordered the same height for the entire job without
worry of which lintel they will be assembled into. For this reason, where possible, select the lintel height
that will enable this to happen easily without compromising on strength requirement. Garage door and
wide window openings may be the exception that requires a differing height of lintel.
2. On the left side of the Table, select the opening width required to be spanned. The Tables cover an
opening range from 3’-0” (900 mm) up to as much as 20’-0” (6.0 m) where lintel depths permit.
3. On the right side of the table, select the column that corresponds to or EXCEEDS your required UDL load
that you calculated in the previous section. Here the load options range from a low of 480 lbs/ft (7.0 KN/m)
to a maximum of 2,395 lb/ft (35.0 KN/m).
4. At the cell corresponding to both opening width and load record the information indicated. This will give
2 pieces of data:
(a) The number and diameter of steel bars required for forming the bottom bar portion of the lintel
(b) The stirrup end distance required (measured from the opening jamb condition back towards the
middle of the opening) at which to begin placement of the stirrups if they are required for the
lintel
If the stirrup end distance is noted as 0-inches, this means that NO shear stirrups will be required to
construct the lintel.
Notice that each Table features a thick diagonal line that runs upward generally from the lower left to
the upper right of each table, subdividing the cell data of the table into 2 separate sections. Any scenario
appearing above or left of this line will NOT require shear stirrups. Anything below and right of this line
WILL REQUIRE shear stirrups.
5. The final element is stirrup spacing. This can always be found in the NOTES section appearing at the bottom
of the applicable table you are working with, specific for any condition noted on that particular table.
6. Do not forget as well, that the notes also detail options for substitution of bars, should the contractor or
builder NOT have a larger desired bar on site for construction of the lintels.
7. The final step is to record the above sets of data into a lintel schedule for presentation with the drawings.
22
I N S T A L L A T I O N
M A N U A L
1
GETTING STARTED
2.1.3 REQUIRED WALL THICKNESS
Although the following information may not directly pertain to prescriptive design, this simple reference matrix is
produced below (Figure 2.09) to assist engineers, designers and contractors alike in selecting an appropriate core
thickness of NUDURA forms for optimum wall performance (i.e. to yield the most efficient combination of concrete and
steel for required condition).
IMPORTANT NOTE: The recommendations contained in this document are intended as a general guideline only and
should not be construed as a substitute for proper engineered design to ACI 318 (USA) or CAN/CSA A23.3 (CAN)
Standards. Rather, this document is intended as a guideline to aid in selection of an appropriate form thickness for a
suggested wall height or building type for budget, quotation or preliminary design consideration purposes ONLY.
In addition, also bear in mind that changes in the Canadian Concrete Design Standard in 2004 (CSA A23.3-04), may
dictate larger core thicknesses than are projected by this table. For example, single warehouse or gymnasium heights
of 22’ to 25’ (6.7 m to 7.6 m) previously found to be in conformance with slenderness ratios of the 1994 Code when
constructed with 8 inch (203 mm) core walls MAY be required by your engineer to be larger than shown here if the
design condition is close to the maximum heights shown in this table.
In addition, it is important to note that special local contributing factors such as high clay content in soils, high seismic
velocities, or wind pressures in excess of 21 psf (20 mph to 40 mph) or 1.0 KPa (32 km/h to 64km/h) may dictate
selection of a thicker core form if the design condition is close to the maximum heights suggested in this table. In most
cases, the suggested recommendations herein will result in optimum reinforcing patterns capable of resisting the
required loadings for each scenario. Wherever the term “Consult Engineering” is used, this suggests that one should
consult professional design advice regarding the core thickness being considered for the height noted before making a
decision to use the core thickness noted in the quotation or estimation.
FORM
THICKNESS
BASEMENT/FOUNDATION
LIMITS
SINGLE STOREY
LIMITATION
MULTI STOREY
LIMITATION
COMMON BUILDING
TYPES
4”
102 mm
Basement not permitted
Frost/Stem wall only.
subject to
engineering consultation
Safe to 10’ >10’
Consult Engineering
2 stories
10’ floor + gable end
12/12 pitch
Exterior walls of:
houses – single, semi &
townhouse, small offices
single or 2 storey
6”
152 mm
8’ – clay
9’ – gravel
10’ – Consult Engineering
Safe to 14’ – 16’
>16’ – Consult
Engineering
3 stories
4 with Eng. Design
10’-14’ ht/floor
Almost any building type –
maximum 16’ single storey
height without pilasters
8”
203 mm
9’ – clay
10’ – gravel
11’ – Consult Engineering
Safe to 16’ – 25’
>25’ – Consult
Engineering
Lower 2-4 floors
of 5-8 stories
(use 6” on upper 2-3
stories)
Warehouses, theatres,
church tall walls
lower floors of hotels,
condos, apartments
10”
254 mm
10’ – clay
11’ – gravel
12’ – Consult Engineering
Safe to 25’ – 35’
>35’ – Consult
Engineering
Lower 2-4 floors
of 9-12 stories
Under ground garages,
theatre walls, fly lofts
lower floors of hotels,
condos, apartments
12”
305 mm
11’ – clay
12’ – gravel
≥13 Consult Engineering
Safe to 35’ – 40’
>40’ – Consult
Engineering
Consult Engineering
Heavy tall industrial
applications
deep foundation walls
FIGURE 2.09
M A N U A L
23
I N S T A L L A T I O N
GETTING STARTED
2.1.4 LAYOUT PLANNING USING NUDURA FORMS
In the move from traditional wall systems to the use of NUDURA Integrated Building Technology in the construction
industry, there are important elements for the contractor/installer to consider especially with respect to plan layouts.
First and foremost is the overall wall thickness. Unlike many other
traditional walls, the exterior face of a NUDURA wall is located a full
2 5/8” (67 mm) distance from the concrete core it contains. Therefore,
if an engineer specifies the exterior limit of his structure relative to a
grid line, ensure that the architectural detail and plan always reflects
that the exterior of the building is located such that the exterior
insulation will lie outboard of the grid line, clear of this element.
The concrete core also has insulation on the interior face of the wall,
which is located 2 5/8” (67 mm) from the inside face of the concrete
core. This means that no matter what the structural drawings for the
building show, the architectural plan will reflect a wall thickness that
is 5 1/4” (133 mm) thicker than the actual concrete core.
Appendix A of this manual contains the form unit profiles for
each unit available in the NUDURA lineup. Although each form in
Appendix A is shown with a 6” (152 mm) concrete core, alternative
core thicknesses are available and details for each of these can
be obtained from NUDURA through your local distributor. The
geometry in particular of the 90º, 45º and T Form Unit profiles
dictate strongly the dimensions that will follow for "NUDURA
Friendly" layout dimensions. These dimensions are based on 3 very
important rules of on-site installation which are as follows:
1. Both corner units (45º and 90º) and T form Units are
formed so that they can be bond stacked, course on
course, with each other to create an ideal 16” (406 mm)
overlap with the interfacing standards. This practice
encourages consistency from course to course and
maintains maximum strength in the construction of the
wall for handling concrete pressures.
2. To maintain the geometry in Point 1 above, this manual
teaches installer/contractors to avoid cutting corners or T
Form Units, hence the layout tables reflect this philosophy.
Only when designers require tight corner changes will the
contractor/installer entertain cutting a corner form unit
to achieve an in-field build. The reason NUDURA tries not
to cut the corner forms is that under concrete pressure is
increased pressure in these areas. This practice also better
maintains an ideal offset of 16” (406 mm) when the corner
forms are reversed on successive course placement, as
shown in Figure 2.11.
FIGURE 2.10
FIGURE 2.11
3. The standard forms that are assembled within each course between the corners and T form units work
best if the cut length of form occurs in multiples of 8” (203 mm). This assures that the vertical interlock of
the webs will be maintained everywhere throughout the wall height. This is ideal for both the contractor/
installer and the end user in that, at every location, the webs are assured to be in-line for drywall and other
finish attachments both interior and exterior. This also allows the building owner or occupant to know where
fastening is possible for the anchorage of decorative and storage elements. It should be noted that the wall
can, if necessary, be constructed to ANY dimension required by the designer. However, optimum layouts will
result best if the 8” (203 mm) increment recommendation is followed.
24
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
CORNER TO CORNER FORM LAYOUT SCENARIOS
On the basis of the key assumptions noted above, NUDURA has created layout tables for every core thickness of form
offered, for planning scenarios, involving each of the wall profile intersections noted below. The number of tables
necessary to cover scenarios by reference table for wall lengths up to 50’ (15.24 m) is too numerous to publish in hard
copy here. However, should the contractor/installer need a copy of these tables, please contact the local distributor.
Figure 2.12 is a typical example of how to use these tables to quickly identify the closest “NUDURA Friendly”
dimension for the condition required for each wall segment of the proposed plan layout. In the instructions in each
case remember that the scenarios given at the start of the tables indicate dimensions achievable if, and when, field
condition demands that the corner form be cut.
IMPORTANT NOTES REGARDING APPLICATION OF “NUDURA FRIENDLY” DIMENSIONS
Though a designer may use this information to ensure the most optimal design for NUDURA form units possible, there
are factors to be considered in the planning and final installation of the product in-field:
Not every designated wall of a NUDURA plan layout can be designed to be optimally laid out to “NUDURA Friendly”
dimensions. This is definitely true for building layouts where there are odd numbers of outside or inside corners.
In such cases, ONE of the intersecting dimensions to the odd corner MUST be sacrificed to meet the optimal layout
condition. The non-conforming plan dimension can simply be indicated on the plan to alert the in-field contractor that
one of the walls intersecting this corner will have to be custom built with a smaller than 8”(203 mm) increment.
In the perfect world of computer aided design, dimensional layouts are always exact. Despite the intent of achieving
perfect NUDURA dimensioning, the designer and contractor should bear in mind that ICF products being formed
with EPS foam are subject to minor product dimensional tolerances that must be taken care of in the final in-field
build. While NUDURA quality control processes strive to achieve tolerances within +/- 1/8” (3.2 mm), form unit length
tolerances can vary by as much as 1/8” (3.2 mm) shorter or up to 3/8” (9.5 mm) longer on an 8’ (2.44 m) standard form
as a result of variances in, EPS bead type, EPS pre-expansion levels, bead aging time, manufacturing plant humidity
and temperature at time of molding, and rate of post-mould shrinkage. Generally the product is rarely on the high
or low end of these tolerances. NUDURA’s manufacturing facilities take great pride in ensuring that all products
produced maintain a constant dimension. However, both designer and contractor/installer must be ever mindful that
accommodation of this factor may, at some point in time, have to be made in the final installation.
T FORM UNIT SCENARIOS
There are 16 possible combinations of T Form Units in concert with all available corner conditions, meaning that across
all 5 core thicknesses of forms, the possible table combinations of available corner configurations when combining
forms of different or same core thicknesses are simply too numerous to present in pre-calculated dimension, tabular
format. In lieu of pre-calculated dimension tables, NUDURA has compiled each of these 16 scenarios into basic base
dimension reference tables that cover each possible corner configuration combination and enable the user to easily
calculate the closest “NUDURA friendly” dimension needed for the projects design.
In the pages following, NUDURA has elected to show 2 sample calculations to give an idea of how to work with the
tables to arrive at the required “NUDURA Friendly” dimension (one sample shown in imperial dimension, the other
shown in metric, covering 2 different long and short T combinations). As with the corner to corner scenarios, each of
the 16 T Form calculation scenarios can be found in the NUDURA Friendly Dimension Table document.
M A N U A L
25
I N S T A L L A T I O N
GETTING STARTED
Corner to Corner Layout Charts
Step 1: Locate Chart that coincides with your core thickness and
corner condition.
Step 2: Find dimension closest to that which you desire for the
corner condition.
Step 3: Closest dimensions to 20' (6100 mm) are 19' 10 5/8"
(6057 mm) or 20' 6 5/8" (6260 mm), so for example take 19' 10
5/8" as the overall wall length.
Step 4: Subtract initial length of two corner forms (first unshaded
cell) from Dimension A. Eg 19' 10 5/8" - 3' 2 5/8" = 16' 8"
Step 5: Calculate number of standards between. Balance is 16' 8"
or (5080 mm), so divided by 8' (2438 mm) to give, 2 standard
blocks and one 8" (200 mm) piece of standard block.
8" (200 mm) 90° to 45° Corner
Form Units
Dim. A
(Imp)
Dim. A
(Met. mm)
1' 10 5/8"
2' 6 5/8"
576
779
3' 2 5/8"
3' 10 5/8"
4' 6 5/8"
5' 2 5/8"
5' 10 5/8"
6' 6 5/8"
7' 2 5/8"
7' 10 5/8"
8' 6 5/8"
9' 2 5/8"
9' 10 5/8"
10' 6 5/8"
11' 2 5/8"
11' 10 5/8"
12' 6 5/8"
13' 2 5/8"
13' 10 5/8"
14' 6 5/8"
15' 2 5/8"
15' 10 5/8"
16' 6 5/8"
17' 2 5/8"
17' 10 5/8"
18' 6 5/8"
19' 2 5/8"
19' 10 5/8"
20' 6 5/8"
21' 2 5/8"
21' 10 5/8"
22' 6 5/8"
23' 2 5/8"
23' 10 5/8"
24' 6 5/8"
25' 2 5/8"
25' 10 5/8"
26' 6 5/8"
982
1185
1388
1591
1794
1997
2200
2403
2606
2809
3012
3215
3418
3621
3824
4027
4230
4433
4636
4839
5042
5245
5448
5651
5854
6057
6260
6463
6666
6869
7072
7275
7478
7681
7884
8087
Dim. A
(Imp)
Dim. A
(Met. mm)
27' 2 5/8"
27' 10 5/8"
28' 6 5/8"
29' 2 5/8"
29' 10 5/8"
30' 6 5/8"
31' 2 5/8"
31' 10 5/8"
32' 6 5/8"
33' 2 5/8"
33' 10 5/8"
34' 6 5/8"
35' 2 5/8"
35' 10 5/8"
36' 6 5/8"
37' 2 5/8"
37' 10 5/8"
38' 6 5/8"
39' 2 5/8"
39' 10 5/8"
40' 6 5/8"
41' 2 5/8"
41' 10 5/8"
42' 6 5/8"
43' 2 5/8"
43' 10 5/8"
44' 6 5/8"
45' 2 5/8"
45' 10 5/8"
46' 6 5/8"
47' 2 5/8"
47' 10 5/8"
48' 6 5/8"
49' 2 5/8"
49' 10 5/8"
50' 6 5/8"
8290
10293
12296
14299
16302
18305
20308
22311
24314
26317
28320
30323
32326
34329
36332
38335
40338
42341
44344
46347
48350
50353
52356
54359
56362
58365
60368
62371
64374
66377
68380
70383
72386
74389
76392
78395
26
I N S T A L L A T I O N
M A N U A L
FIGURE 2.12
GETTING STARTED
FIGURE 2.13
M A N U A L
27
I N S T A L L A T I O N
GETTING STARTED
FIGURE 2.14
28
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
RADIUS WALL SCENARIOS
Radius walls are formed simply through the use of NUDURA’s straight 8’ (2.44 m) standard form unit panel system
coupled with NUDURA’s cross linked insert webs. The contractor/installer does not need to worry about perfect
configuration of "NUDURA Friendly" dimensions for radius wall designs since coordination of in-field construction is
largely handled through the custom radius cuts that are made at the factory. NUDURA Inc. has developed a simple
Radius Wall Calculation Spread Sheet which assists the contractor/installer and designer in knowing what lengths of
form cuts will be made by the computer program at our plant to facilitate the cutting of the segments to construct a
radius wall. Should the contractor/installer require a copy of the electronic version for in-field cutting of a radius wall,
please contact the local distributor. For more information on radius walls, refer to the Technical Bulletin on this subject,
included in Appendix F.
2.1.5 WALL HEIGHT CHARTS
Stack heights for ensuring wall heights are achieved with NUDURA construction can be particularly important
especially when considering such things as:
• Footing elevations relative to grade
• Brick finishes relative to grade levels
• Floor bearing heights relative to finished grade
• Floor bearing height relative to each other
NUDURA’s form heights do not always need to be considered for elevation design layout. Contractor/installers working
regularly with the NUDURA Wall System will plan stack heights to suit the elevation layout requirements of the building
as assigned by the architect or designer, no matter what this may be. However, if the designer requires optimum
conditions for ease of construction of NUDURA on site, here is a list of tips to remember for achieving optimum design
for installation of NUDURA forms:
•
Avoid using height adjusters or use them sparingly. Using height adjusters will add to the labor cost due
to the fact that they are 32” (813 mm) in length by 3” (76 mm) high. The man-hours/ft² (man-hours/m2) will
increase significantly for this area of the wall. Therefore, if floor heights can be coordinated with the design
to avoid use of height adjusters, this will serve to make the project more cost efficient.
•
If a half form will achieve optimum stack height within the projected wall assembly from top of footing to
parapet or roof line, plan to use the half height form at either the footing or the top of the wall or roof line.
Do NOT specify half height forms at any portion of a continuous stack height as this will cause additional
form support to have to be added by the installer prior to concrete placement.
•
When installing brick ledges, it is recommended to adjust the height of the first course in order to ensure
that the brick line starts at a full course. If this is not possible then the brick elevation can be achieved by
using the NUDURA Brick Ledge Extension Form.
•
When planning complex details, always remember that if full height hinge pin web forms are being used,
the crucial structural hinge pin ties that connect the panels together start at 2” (50 mm) from the top and
bottom of the form and are each 3” (76 mm) in height. Avoid any detailing that will require the installer to
cut the form in this region. If this is unavoidable, be sure to detail it as an insert web form and the installer
will order and install accordingly, and will detail the web connections to handle the condition of bearing
accordingly.
•
Avoid using Brick Ledge Forms as floor supports for any application. Brick Ledge Forms have limited
bearing capacities and therefore should not be relied on for carrying floor loads. Additional finishing
requirements of the corbel could prove undesirable to the building owner.
M A N U A L
29
I N S T A L L A T I O N
GETTING STARTED
The following are optimal stack height charts for planning wall stack heights up to 36’ 6” (11.125 m) in height. Obviously,
higher wall heights are possible and employ the same basics of geometry as illustrated on the following pages.
IMPERIAL OR U.S. STANDARD DIMENSION WALL HEIGHT CHART
NO. OF
COURSES
STANDARD
FORM HEIGHT
OF WALL
PLUS ONE 3"
HIGH
HEIGHT
ADJUSTER
PLUS ONE 6" HIGH
HALF
PLUS ONE 9"
HIGH HALF
STANDARD
1
1' 6"
1' 9"
2'
2' 3"
2'6"
2' 9"
2
3'
3' 3"
3' 6"
3' 9"
4'
4' 3"
3
4' 6"
4' 9"
5'
5' 3"
5' 6"
5' 9"
4
6'
6' 3"
6' 6"
6' 9"
7'
7' 3"
5
7' 6"
7' 9"
8'
8' 3"
8' 6"
8' 9"
6
9'
9' 3"
9' 6"
9' 9"
10'
10' 3"
7
10' 6
10' 9"
11'
11' 3"
11' 6"
11' 9"
8
12'
12' 3"
12' 6"
12' 9
13'
13' 3"
9
13' 6"
13' 9"
14'
14' 3"
14' 6"
14' 9"
10
15'
15' 3"
15' 6"
15' 9"
16'
16' 3"
11
16' 6
16' 9"
17'
17' 3"
17' 6"
17' 9"
12
18'
18' 3"
18' 6"
18' 9"
19'
19' 3"
13
19' 6"
19' 9"
20'
20' 3"
20' 6"
20' 9"
14
21'
21' 3"
21' 6"
21' 9"
22'
22' 3"
15
22' 6"
22' 9"
23'
23' 3"
23' 6"
23' 9"
16
24'
24' 3"
24' 6"
24' 9"
25'
25' 3"
17
25' 6"
25' 9"
26'
26' 3"
26' 6"
26' 9"
18
27'
27' 3"
27' 6"
27' 9"
28'
28' 3
19
28' 6
28' 9
29'
29' 3"
29' 6"
29' 9"
20
30'
30' 3"
30' 6"
30' 9"
31'
31' 3"
21
31' 6"
31' 9"
32'
32' 3"
32' 6"
32' 9"
22
33'
33' 3"
33' 6"
33' 9"
34'
34' 3"
23
34' 6"
34' 9"
35'
35' 3"
35' 6"
35' 9"
24
36'
36' 3"
36' 6"
36' 9"
37'
37' 3"
PLUS ONE 12"
HIGH
OPTIMIZER FORM
PLUS ONE 15"
HIGH
SEGMENT
Note: The 15" segment can be achieved by cutting a Standard Form or using one Optimizer Form and one Height Adjuster
FIGURE 2.15
30
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
METRIC DIMENSION WALL HEIGHT CHART
NO. OF
COURSES
STANDARD
FORM HEIGHT
OF WALL
METERS
PLUS ONE
7.2 mm HIGH
HEIGHT
ADJUSTER
METERS
PLUS ONE
152 mm HIGH HALF
OPTIMIZER OR
CUT STANDARD
METERS
PLUS ONE
229 mm HIGH
HALF
STANDARD
METERS
PLUS ONE
305 mm HIGH
OPTIMIZER FORM
METERS
PLUS ONE
381 mm HIGH
SEGMENT
METERS
1
0.457
0.533
0.610
0.686
0.762
0.838
2
0.914
0.991
1.067
1.143
1.219
1.295
3
1.372
1.448
1.524
1.600
1.676
1.753
4
1.829
1.905
1.981
2.057
2.133
2.210
5
2.286
2.363
2.438
2.514
2.590
2.668
6
2.743
2.820
2.895
2.971
3.047
3.125
7
3.201
3.277
3.352
3.428
3.504
3.582
8
3.658
3.734
3.809
3.885
3.961
4.040
9
4.116
4.192
4.266
4.342
4.418
4.497
10
4.573
4.649
4.723
4.799
4.875
4.955
11
5.030
5.106
5.180
5.256
5.332
5.412
12
5.488
5.564
5.637
5.713
5.789
5.869
13
5.945
6.021
6.094
6.170
6.246
6.327
14
6.403
6.478
6.551
6.627
6.703
6.784
15
6.861
6.936
7.008
7.084
7.160
7.242
16
7.317
7.393
7.465
7.541
7.617
7.699
17
7.775
7.850
7.922
7.998
8.074
8.156
18
8.232
8.307
8.379
8.455
8.531
8.614
19
8.690
8.765
8.836
8.912
8.988
9.071
20
9.147
9.222
9.293
9.369
9.445
9.529
21
9.604
9.679
9.750
9.826
9.902
9.986
22
10.062
10.137
10.207
10.283
10.359
10.443
23
10.519
10.594
10.664
10.740
10.816
10.901
24
10.977
11.051
11.121
11.197
11.273
11.358
Note: The 381mm segment can be achieved by cutting a Standard Form or using one Optimizer Form and one Height Adjuster
FIGURE 2.16
M A N U A L
31
I N S T A L L A T I O N
GETTING STARTED
2.2 ESTIMATING
2.2.1 IMPERIAL (US STANDARD) FORMULAE
NUDURA material requirements for any project can easily be determined manually through the simple calculations
within this manual. In all cases the estimator must collect the following information from the plan in order to ensure
the estimate is accurate.
Please refer to Section 2.2.2 for Metric Calculation Formulae.
Total linear footage of perimeter _____________________________________________________________________
Total # of 90° corners ______________________________________________________________________________
Total # of 45° corners ______________________________________________________________________________
Total # of T connections ____________________________________________________________________________
Total linear footage of tapered top form _______________________________________________________________
Total linear footage of brick ledge form _______________________________________________________________
Total linear footage of brick ledge extension ___________________________________________________________
Height of the wall _________________________________________________________________________________
Total # of courses _________________________________________________________________________________
Total linear footage of optimizer _____________________________________________________________________
Total linear footage of height adjusters _______________________________________________________________
Total # of courses of height adjusters _________________________________________________________________
Total linear footage to be waterproofed _______________________________________________________________
Total height to be waterproofed _____________________________________________________________________
Total linear footage to be parged ____________________________________________________________________
Total height to be parged __________________________________________________________________________
Total ft² of openings (width x height) _________________________________________________________________
Total linear footage of opening width _________________________________________________________________
Total linear footage of opening height ________________________________________________________________
Wall cavity thickness _______________________________________________________________________________
The estimator will need to take the total lineal footage of the building and add 2 ft for each inside 90° corner and 1 ft
for each inside 45° corner on the footprint.
32
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
This chart enables an estimator working in imperial or US Standard dimensions to easily summarize the necessary
information regarding total opening width and height for estimating rough buck material along with the total ft² of
openings there are in the building. These totals will be used in estimating formulas further on in this section.
IMPERIAL OR US STANDARD DIMENSION OPENINGS SUMMARY CHART
OPENING #
QUANTITY
X WIDTH
X
HEIGHT
= TOTAL FT²
TOTALS
TO CALCULATE THE STANDARD FORM UNITS:
• Gross Wall Area (ft²) = Total Linear footage of wall (ft) x Total Height (ft)
• Net Wall Area (ft²) = Gross Wall Area (ft²) – Total area of openings (ft²)
• Total Standards/course = (Total Lineal footage of wall – (# 90° Corners x 4) – (# 45° Corners x 3)) ÷ 8
• Total Standards before deductions = Total Standards/course x # of courses
If brick ledge, taper top, or T forms are needed for the building they need to be subtracted off the total standards
calculated above.
• Standards (BL) = Lineal Footage of Brick Ledge ÷ 8
• Standards (TT) = Lineal Footage of Taper Top ÷ 8
• Standards (OP) = ((LFOP x # COP) ÷ 4) ÷ 3
• Standards (TF) = (# of T Forms x # of courses) ÷ 2
• Total Standards = Total Standards before deductions - Standards (BL) - Standards (TT) - Standards (OP) - Standards (TF)
TO CALCULATE THE NUMBER OF 90° CORNER FORMS:
90° form = #90 x #C
This formula multiplies the number of 90° turn by the number of courses.
TO CALCULATE THE NUMBER OF 45° CORNER FORMS:
45° form = #45 x #C
This formula multiplies the number of 45° turn by the number of courses.
M A N U A L
33
I N S T A L L A T I O N
GETTING STARTED
TO CALCULATE THE NUMBER OF T FORMS:
T form = #Ts x #C
This formula multiplies the T connection by the number of courses.
TO CALCULATE THE NUMBER OF BRICK LEDGE FORMS:
BLF4 = LFBLF ÷ 4 or BLF8 = LFBLF ÷ 8
This formula divides the linear footage of brick ledge form units by 4 or 8. Brick Ledge forms are available in 2 lengths.
8’ lengths are available from NUDURA’s Canadian plant and the 4’ length is available from the US plant.
Note: Additional brick ledge form units may be required for corners.
TO CALCULATE THE NUMBER OF BRICK LEDGE EXTENSIONS:
BLE = LFBLE x .375
# of Screws = BLE x 3
# of V Strips = BLE ÷ 3
This formula multiplies the linear footage of brick ledge extension by .375. The formulas also calculate the number of
screws needed for attaching the BLE and also the V Strips needed also.
Note: Additional brick ledge extension may be required for corners.
TO CALCULATE THE NUMBER OF OPTIMIZER FORMS:
OP = (LFOP x # COP) ÷ 4
OP Ties = OP x 6
This formula corrects the linear footage of perimeter of Optimizer required, divides by 4, multiples by 2 and multiplies
by the number of courses required.
TO CALCULATE THE NUMBER OF HEIGHT ADJUSTERS:
HA = (LFHA x 2 x #CHA) ÷ 2.67
HA Ties = (HA ÷ 2) x 4
This formula corrects the linear footage of perimeter of Height Adjuster required, divides by 2.67’, multiplies by 2 and
multiplies by the number of courses required.
TO CALCULATE THE NUMBER OF ROLLS OF WATERPROOFING:
WP = LFWP X HWP ÷ 210
A roll of waterproofing is 225 sq. ft. but the effective coverage is 210 sq. ft allowing for overlapping the edge of the
membrane.
TO CALCULATE THE NUMBER OF BAGS OF PREPCOAT PARGING MIX:
PC = LFPAR X HPAR ÷ 75
The surface area to be parged is divided by 75 which is the average coverage obtained per bag for two coat
application.
TO CALCULATE THE NUMBER FIBER MESH ROLLS:
FM = LFPAR X HPAR ÷ 475
A roll of fiber mesh is 475 sq. ft. an allowance for overlap may be required depending on the application techniques.
TO CALCULATE THE QUANTITY OF WALL ALIGNMENT SYSTEM:
WAS = LFPER + 1 per corners or tees ÷ 5.333
The formula allows for one unit every 5’ 4” plus an additional unit for every corner and tee wall connection. Should
a site have numerous openings with center of opening less than 5’ 4” apart the quantity of WAS may need to be
increased.
34
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
TO CALCULATE THE AMOUNT OF REBAR:
How to Determine the Required Reinforcing Steel to Wall Area “Ratio”
The ratios shown in Table 2.2.1.1
(below) have been calculated by
totaling the bar length specified for
each scenario then dividing this length
by the total square footage of wall area
that encompasses these bars. Using
this method, a ratio can be specified
for both vertical and horizontal mats
of steel separately (if they are different
diameters from each other) Or if both
mats are the same diameter of steel, the
ratio can be specified as a “Combined
Steel Mat”.
Width = 2 x vert. spacing (8”, 12”, 16”, 24”, 32”, or 48” o/c)
Height = 2 x horizontal spacing (18” or 36”)
FIGURE 2.17
REBAR = LFPER X HW X
Multiplier (see Table 2.2.1.1)
The linear footage of the
wall is multiplied by the
height of the wall and
multiplied by a value
obtained in Table 1.0 which
is a constant. The result
is in feet. This constant is
for a rebar grid in the wall
18” x 16” horizontally and
vertically respectively with
an allowance for horizontal
splices.
M A N U A L
35
I N S T A L L A T I O N
GETTING STARTED
TO CALCULATE THE VOLUME OF CONCRETE:
Yds³ of concrete = LFPER X HW X MULTIPLIER (Table 2.2.1.1)
The concrete multipliers shown in Table 2.2.1.2 (below) are constants, each of which represents the total volume of
concrete (in cubic yards) that is necessary to cover 1 square foot of wall area for the specified core thickness of form.
To calculate the amount of concrete required to fill the wall, simply multiply the total area of the wall (in square feet)
by the multiplier shown for the selected core thickness of form. The volume of concrete ordered should be reduced
in accordance with window and door openings. If using a concrete pump as a method of placement, an allowance
must be included within the calculated volume of concrete to account for waste. NUDURA recommends an additional
concrete volume of 1 yd3 to 2 yd3 for the pump unit.
TO CALCULATE THE NUMBER OF VERTICAL JOINT CLIPS:
VJC = (LFPER ÷ 8’ x 4 per standard x # of courses) + (# of Corners x 4 x # of courses)
The VJC formula takes the lineal footage of the perimeter of the structure and divides by the length of a standard form.
Then multiply this by 4 per standard form and then multiply again by the number of courses. The second part of this
formula then takes the number of corners and multiplies by 4 clips per corner and then multiplies by the number of
courses.
Note: Remember that what is in the brackets must be completed before adding them together for the total
number of clips.
36
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
ESTIMATING FORMULAE SUMMARY – (IMPERIAL/ US STANDARD)
STANDARD FORM UNITS:
Gross Wall Area (ft²) = Total Linear footage of wall (ft) x Total Height (ft)
Net Wall Area (ft²) = Gross Wall Area (ft²) – Total area of openings (ft²)
Total Standards/course = (Total Lineal footage of wall – (# 90° Corners x 4) – (# 45° Corners x 3)) ÷ 8
Total Standards before deductions = Total Standards/course x # of courses
Standards (BL) = Lineal Footage of Brick Ledge ÷ 8
Standards (TT) = Lineal Footage of Taper Top ÷ 8
Standards (OP) = ((LFOP x # COP) ÷ 4) ÷ 3
Standards (TF) = (# of T Forms x # of courses) ÷ 2
TOTAL STANDARDS = Total Stds before deductions - Stds (BL) – Stds (TT) - Stds (OP) - Stds (TF)
90° FORM UNIT: 90° FORM = #90 x #C
45° FORM UNIT: 45° FORM = #45 x #C
T FORM UNIT: T FORM = #Ts x #C
BRICK LEDGE FORM 4’ UNIT: BLF4 = LFBLF ÷ 4
BRICK LEDGE FORM 8’ UNIT: BLF8 = LFBLF ÷ 8
OPTIMIZER FORM UNIT: OP = (LFOP x # COP) ÷ 4
OP Ties = OP x 6
BRICK LEDGE EXTENSION: BLE = LFBLE x 0.375
# of Screws = BLE x 6
HEIGHT ADJUSTER: HA = (LFHA x 2 x #CHA) ÷ 2.67
HA Ties = (HA ÷ 2) x 4
WATERPROOFING: WP = LFWP x HWP ÷ 210
PARGING COAT: PC = LFPAR x HPAR ÷ 75
FIBER MESH: FM = LFPAR x HPAR ÷ 475
WALL ALIGNMENT SYSTEMS: WAS = (LFPER + 1 per corner or tees) ÷ 5.33
REBAR: REBAR = LFPER x HW x 1.5
CONCRETE (IMPERIAL) Yds³ = LFPER x HW x Concrete Multiplier (Table 2.2.1.2)
VERTICAL JOINT CLIPS VJC = (LFPER ÷ 8’ x 4 per standard x # of courses) + (# of Corners x 4 x # of courses)
M A N U A L
37
I N S T A L L A T I O N
GETTING STARTED
ESTIMATING RADIUS WALLS (IMPERIAL OR US STANDARD)
For determining total number of radius forms required for on site construction of a NUDURA radius wall or for
preparing an order for factory cut NUDURA radius forms, you can use the calculation formula below. This formula
assumes that any radius constructed will be an “arc length segment” of a full circle with a known angle of rotation:
The following information is required to determine total number of radius forms for any given radius wall in a floor
plan:
1. The Outside radius (measured in inches from the focus point to the outside face of the NUDURA form)
2. The Inside Radius (equals the Outside Radius in inches less the total form thickness being used)
3. The Degrees of Turn of Radius (this is total number of degrees of rotation that the radius covers of a full circle)
4. The Total Wall Height (measured in inches).
TO CALCULATE THE TOTAL NUMBER OF RADIUS FORMS REQUIRED:
No. of forms per course No. of Forms = Outside Radius (in inches) x 6.283 x (Degrees of Turn of Radius/360) _______________________________________________________ 96 No. of courses
X
Wall Height (in inches)
__________________
18
NOTES:
1. To assure adequate product for accommodating custom fitting of the wall forms into the standard elements
of the plan, the first part of the calculation (no. of forms per course) above should be ROUNDED up to a
whole number or (full form length) before multiplying by the number of courses of forms required.
2. Do NOT deduct any allowance for openings particularly if placing orders at the factory for custom radius
forms.
As an alternate, you can also obtain NUDURA’s radius wall form unit spread sheet calculator through your distributor
which enables the same calculation to be performed in Microsoft excel® along with giving the required cut segment
lengths. (The distributor can also duplicate the quantity portion of this calculator by entering data into the NUDURA
radius wall digital order form).
Further guidance on estimating for NUDURA radius walls is available through your NUDURA distributor OR can be
downloaded directly from the Construction Professional Section of NUDURA’s Website under “Technical Bulletins and
Guides”.
38
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
2.2.2 METRIC FORMULAE
NUDURA material requirements for any project can easily be determined manually through the simple calculations
within this manual. In all cases the estimator must collect the following information from the plan in order to ensure
the estimate is accurate.
Please refer to section 2.2.1 for the imperial formulas.
Total linear meters of perimeter _____________________________________________________________________
Total # of 90° corners ______________________________________________________________________________
Total # of 45° corners ______________________________________________________________________________
Total # of T connections ____________________________________________________________________________
Total linear meters of tapered top form _______________________________________________________________
Total linear meters of brick ledge form ________________________________________________________________
Total linear meters of brick ledge extension ____________________________________________________________
Height of the wall _________________________________________________________________________________
Total # of courses _________________________________________________________________________________
Total linear meters of height adjusters ________________________________________________________________
Total linear meters of optimizer ______________________________________________________________________
Total # of courses of height adjusters _________________________________________________________________
Total linear meters to be waterproofed ________________________________________________________________
Total height to be waterproofed_____________________________________________________________________ Total linear meters to be parged _____________________________________________________________________
Total height to be parged __________________________________________________________________________
Total m² of openings (width x height)_________________________________________________________________
Total linear meters of opening width _________________________________________________________________
Total linear meters of opening height _________________________________________________________________
Wall cavity thickness _______________________________________________________________________________
The estimator will need to take the total lineal footage of the building and add 0.61 m for each inside 90° corner and
0.31 m for each inside 45° corner on the footprint.
M A N U A L
39
I N S T A L L A T I O N
GETTING STARTED
This chart enables an estimator working in metric dimensions to easily summarize the necessary information regarding
total opening width and height for estimating rough buck material along with the total m² of openings there are in the
building. These totals will be used in estimating formulas further on in this section.
METRIC DIMENSION OPENINGS SUMMARY CHART
OPENING #
QUANTITY
X WIDTH
X
HEIGHT
= TOTAL m²
TOTALS
TO CALCULATE THE STANDARD FORM UNITS:
• Gross Wall Area (m²) = Total Linear footage of wall (m) x Total Height (m)
• Net Wall Area (m²) = Gross Wall Area (m²) – Total area of openings (m²)
• Total Standards/course = (Total Lineal meters of wall – (# 90° Corners x 4) – (# 45° Corners x 3)) ÷ 2.44
• Total Standards before deductions = Total Standards/course x # of courses
If brick ledge, taper top, or T forms are needed for the building they need to be subtracted off the total standards
calculated above.
• Standards (BL) = Lineal meters of Brick Ledge ÷ 2.44
• Standards (TT) = Lineal meters of Taper Top ÷ 2.44
• Standards (OP) = ((LMOP x # COP) ÷ 1.219) ÷ 3
• Standards (TF) = (# of T Forms x # of courses) ÷ 0.61
• Total Standards = Total Standards before deductions - Standards (BL) - Standards (TT) - Standards (TF)
TO CALCULATE THE NUMBER OF 90° CORNER FORMS:
90° form = #90 x #C
This formula multiplies the number of 90° corners by the number of courses.
TO CALCULATE THE NUMBER OF 45° CORNER FORMS:
45° form = #45 x #C
This formula multiplies the number of 45° angles by the number of courses.
40
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
TO CALCULATE THE NUMBER OF T FORMS:
T form = #T x #C
This formula multiplies the T connection by the number of courses.
TO CALCULATE THE NUMBER OF BRICK LEDGE FORMS:
BLF = LDBLF ÷ 2.44 or BLF8 = LDBLF ÷ 1.22
This formula divides the linear footage of brick ledge form units by 1.22 or 2.44. Brick Ledge forms are available in
2 lengths; 2.44m lengths are available from NUDURA’s Canadian plant and the 1.22m lengths are available from the US
plant. Note: Additional brick ledge form units may be required for corners.
TO CALCULATE THE NUMBER OF BRICK LEDGE EXTENSIONS:
BLE = LDBLE ÷ 0.8128
# of Screws = BLE x 6
This formula divides the linear meters of brick ledge extension by 0.8128.
Note: Additional brick ledge extension may be required for corners.
TO CALCULATE THE NUMBER OF OPTIMIZER FORMS:
OP = (LMOP x 2 x #COP) ÷ 1.219
OPTIES = (OP ÷ 2) x 6
This formula corrects the linear meters of perimeter of Optimizer required, divides by 4, multiples by 2 and multiplies
by the number of courses required.
TO CALCULATE THE NUMBER OF HEIGHT ADJUSTERS:
HA = (LDHA x #CHA x 2) ÷ 0.8128
HA Ties = (HA ÷ 2) x 4
This formula divides the length of Height Adjuster (0.8128 m), and multiplies by the number of courses required
TO CALCULATE THE NUMBER OF ROLLS OF WATERPROOFING:
WP = LMWP x HWP ÷ 19.5
A roll of waterproofing is 20.9 sq. m. but the wall coverage is 19.5 m². This allows for a 76 mm overlap at the edges of
the membrane.
TO CALCULATE THE NUMBER OF BAGS OF PREPCOAT PARGING MIX:
PC = LMPAR x HPAR ÷ 6.97
The surface area to be parged is divided by 6.97 m². This is the average coverage obtained per bag for a two coat
application. (Base & Finish Coats)
TO CALCULATE THE NUMBER OF FIBER MESH ROLLS:
FM = LMPAR x HPAR ÷ 44.1
A roll of fiber mesh is 44.1 sq. m. An allowance for overlap may be required depending on the application techniques.
TO CALCULATE THE QUANTITY OF WALL ALIGNMENT SYSTEM:
WAS = LDPER + 1 per corner and T intersections ÷ 1.63
The formula allows for one unit every 1.63 m plus an additional unit for every corner and T wall connection. Should
a site have numerous openings with center of opening less than 1.63 m apart, the quantity of WAS may need to be
increased.
M A N U A L
41
I N S T A L L A T I O N
GETTING STARTED
TO CALCULATE THE AMOUNT OF REBAR:
How to Determine the Required Reinforcing Steel to Wall Area “Ratio”
The ratios shown in Table 2.2.2.1
have been calculated by totaling
the bar length specified for
each scenario then dividing
this length by the total square
footage of wall area that
encompasses these bars.
Using this method, a ratio can
be specified for both vertical
and horizontal mats of steel
separately (if they are different
diameters from each other) Or if
both mats are the same diameter
of steel, the ratio can be specified
as a “Combined Steel Mat”.
Width = 2 x vert. spacing (203mm, 406mm, 610mm, 813mm, or 1213mm o/c)
Height = 2 x horizontal spacing (457mm or 914mm)
FIGURE 2.18
REBAR = LMPER x HW x
MULTIPLIER (Table 2.2.2.1)
The linear meter of the wall
is multiplied by both the
height of the wall and by
value obtained in Table 2.2.2.1
which is a constant. The result
is in meters. This constant
is for a rebar grid in the wall
0.457m x 0.406m horizontally
and vertically respectively
with an allowance for
horizontal splices.
42
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
TO CALCULATE THE VOLUME OF CONCRETE:
m³ of CONCRETE = LMPER x HW x Concrete Multiplier (Table 2.2.2.2)
The concrete multipliers shown in Table 2.2.2.2 (below) are constants, each of which represent the total volume of
concrete (in cubic yards) that is necessary to cover 1 square meter of wall area for the specified core thickness of form.
To calculate the amount of concrete required to fill the wall, simply multiply the total area of the wall (in square meters)
by the multiplier shown for the selected core thickness of form. The volume of concrete ordered should be reduced
in accordance with window and door openings. If using a concrete pump as a method of placement, an allowance
must be included within the calculated volume of concrete to account for waste. NUDURA recommends an additional
concrete volume of 1 m3 to 2 m3 for the pump unit.
TO CALCULATE THE NUMBER OF VERTICAL JOINT CLIPS:
VJC = (LFPER ÷ 2.44m x 4 per standard x # of courses) + (# of Corners x 4 x # of courses)
The VJC formula takes the lineal footage of the perimeter of the structure and divides by the length of a standard form.
Then multiply this by 4 per standard form and then multiply again by the number of courses. The second part of this
formula then takes the number of corners and multiplies by 4 clips per corner and then multiplies by the number of
courses.
Note: Remember that what is in the brackets must be completed before adding them together for the total
number of clips.
M A N U A L
43
I N S T A L L A T I O N
GETTING STARTED
ESTIMATING FORMULAE SUMMARY (METRIC)
STANDARD FORM UNITS:
Gross Wall Area (m²) = Total Linear footage of wall (m) x Total Height (m)
Net Wall Area (m²) = Gross Wall Area (m²) – Total area of openings (m²)
Total Standards/course = (Total Lineal meters of wall – (# 90° Corners x 4) – (# 45° Corners x 3)) ÷ 2.44
Total Standards before deductions = Total Standards/course x # of courses
Standards (BL) = Lineal meters of Brick Ledge ÷ 2.44
Standards (TT) = Lineal meters of Taper Top ÷ 2.44
Standards (OP) = ((LMOP x # COP) ÷ 1.219) ÷ 3
Standards (TF) = (# of T Forms x # of courses) ÷ 0.61
TOTAL STANDARDS = Total Standards before deductions - Standards (BL) - Standards (TT) - Standards (TF)
90° FORM UNIT: 90° FORM = #90 x #C
45° FORM UNIT: 45° FORM = #45 x #C
T FORM UNIT: T FORM = #T x #C
BRICK LEDGE FORM 1.22m UNIT: BLF = LMBLF ÷ 1.22
BRICK LEDGE FORM 2.44m UNIT: BLF = LMBLF ÷ 2.44
BRICK LEDGE EXTENSION: BLE = LMBLE x .375
# of Screws = BLE x 6
OPTIMIZER FORM UNIT: OP = (LMOP x # COP) ÷ 1.219
OP Ties = OP x 6
HEIGHT ADJUSTER: HA = LMPER x .75 x #CHA
HA Ties = (HA ÷ 2) x 4
WATERPROOFING: WP = LMWP x HWP ÷ 19.5
PARGING COAT: PC = LMPAR x HPAR ÷ 6.97
FIBER MESH: FM = LMPAR x HPAR ÷ 44.1
WALL ALIGNMENT SYSTEMS: WAS = LMPER + 1 per corner or tees ÷ 1.63
REBAR: REBAR = LMPER x HW x MULTIPLIER (Table 2.2.2.1)
CONCRETE: Concrete = LMPER x HW x Concrete Multiplier (Table 2.2.2.2)
VERTICAL JOINT CLIPS: VJC = (LFPER ÷ 2.44m x 4 x #C) + (# of Corners x 4 x #C)
44
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
ESTIMATING RADIUS WALLS (METRIC)
For determining total number of radius forms required for on site construction of a NUDURA radius wall or for
preparing an order for factory cut NUDURA radius forms, you can use the calculation formula below. This formula
assumes that any radius constructed will be an “arc length segment” of a full circle with a known angle of rotation:
The following information is required to determine total number of radius forms for any given radius wall in a floor
plan:
1. The Outside radius (measured in millimeters) from the focus point to the outside face of the NUDURA form
2. The inside radius (equals the Outside radius (in millimeters) less the total form thickness being used)
3. The Degrees of Turn of radius (this is total number of degrees of rotation that the radius covers of a full circle)
4. The Total Wall Height (measured in millimeters).
TO CALCULATE THE TOTAL NUMBER OF RADIUS FORMS REQUIRED:
No. of forms per course No. of courses
No. of Forms = Outside radius (in mm) x 6.283 x (Degrees of Turn of Radius/360) X
_______________________________________________________ 2438 Wall Height (in mm)
__________________
457
NOTES:
1. To assure adequate product for accommodating custom fitting of the wall forms into the standard elements
of the plan, the first part of the calculation (no. of forms per course) above should be ROUNDED up to a
whole number or (full form length) before multiplying by the number of courses of forms required.
2. Do NOT deduct any allowance for openings particularly if placing orders at the factory for custom radius
forms.
As an alternate, you can also obtain NUDURA’s radius wall form unit spread sheet calculator through your distributor
which enables the same calculation to be performed in Microsoft excel® along with giving the required cut segment
lengths. (The distributor can also duplicate the quantity portion of this calculator by entering data into the NUDURA
radius wall digital order form).
Further guidance on estimating for NUDURA radius walls is available through your NUDURA distributor Or can be
downloaded directly from the Construction Professional Section of NUDURA’s Website under “Technical Bulletins and
Guides”.
M A N U A L
45
I N S T A L L A T I O N
GETTING STARTED
2.2.3 FORM UNIT CONCRETE VOLUMES
46
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
M A N U A L
47
I N S T A L L A T I O N
GETTING STARTED
2.3 BUILDING PERMIT SUBMISSION REQUIREMENTS
If a Builder or Contractor is submitting for permit on a NUDURA
Building with custom stamped documentation that has been
overseen by a professional engineer, normally permit submission
to a Building Department can proceed with little delay. However,
this section of the manual is intended to provide suggestions to
the contractor who has never submitted for permit before using
NUDURA Integrated Building Technology. The suggestions provided
here, as academic as they may be, will help a permit submission to
go as smoothly as possible.
First: understand that the Building Official needs to be able
to reference an enabling piece of legislation that ensures the
engineering specifications for the building are provided for under
local jurisdiction.
FIGURE 2.19
USA
The US National Code Agency “The international Code Council” is responsible for administering the 2003, 2006
and 2009 international residential Building Codes. The local municipality, dependant upon State, may have already
adopted one of the three codes mentioned above or is well on its way to doing so. These codes contain prescriptive
structural design tables for both below grade and above grade reinforcing steel requirements, as well as typical lintel
designs tables. These tables are referenced within NUDURA’s ICC-ES evaluation report (ESR-2092). A copy of this
evaluation report can be downloaded from NUDURA’s web site and should be submitted to the building department
for permit approval.
CANADA
Since 2005, prescriptive structural design tables and scope of applicability limits are also have been provided under the
Housing and Small Buildings section of the National Building Code (Part 9) and under Part 9 of the Ontario, Quebec,
Alberta and British Columbia Building Codes.
In either case (USA or Canada) the design builder or contractor can ensure a much smoother permit submission and
direct acceptance of the Building Official if the following guidelines are applied during plan submissions.
First, since the local Building Official may not have seen NUDURA before, ensure that he or she has a copy of
2 important documents:
(a) The NUDURA Installation Manual
(b) The applicable NUDURA evaluation report or Intertek Product Certification Documentation for your region
USA - ICC-ES – ESR-2092
CAN - Intertek Certification Documentation to CAN/ULC S717.1 and its related documents
Europe - EOTA- Eta-07 0034
Other State, Provincial or Regional approvals may be required to be included with the permit submission to
demonstrate the system’s compliance with these provisions as well. if you are unsure, check with your distributor.
They can advise you on the additional documents that may be required for your specific region. These documents are
summarized in the following section, (Section 2.4).
48
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
2.4 EVALUATION REPORTS AND APPROVALS
USA EVALUATIONS AND APPROVALS
National: • Certified to: ASTM E 2634
• ICC-ES (AC-353)
Intertek: SDID No. 21903
ESR-2092 (TYPES I-V/ N/C, A&C*)
State:
• State of Florida
FL1585-R3
County/City: • Miami Metro Dade • City of New York NOA 16-0627-01
Complies with OTCR 2009-020
*Approved for use in “Attics and Crawlspaces” uncovered per report conditions
CANADA EVALUATIONS AND APPROVALS
National:
• Certified to: CAN/ULC S717.1
Intertek: SDID No. 21903
EUROPE EVALUATIONS AND APPROVALS
International: • European Union of Technical Assements (EOTA)
Assessed in Compliance with EOTA: ETAG 009
• British Board of Agrément (BBA) ETA-07/0034
France: • CSTB (Based on ETA 07/0034)
• ACERMI Issuing Summer 2017
DTA 16/09-581
MIDDLE EAST EVALUATIONS AND APPROVALS
United Arab Emirates:
• Certified to ASTM C78
• Dubai Central Laboratory: CL 16020326
ASTM C578
Certificate No. CL16020326
ESR-2092
ETA-07/0034
M A N U A L
49
I N S T A L L A T I O N
GETTING STARTED
2.5 BUILDING DEPARTMENT: TYPICAL EXPECTATIONS
Most building departments have put together a set of guidelines
of necessary documentation that needs to be included with any
submission to obtain a building permit. Without these documents,
permit delays can occur costing time and money for any project.
It is imperative that whoever is submitting for the building permit
communicate with the building department and ask them for
a list of required documentation. Remember that the building
department cannot make assumptions about the building process
as in many cases the building department can have a number of
internal departments reviewing a set of plans.
NUDURA has included here a list of potential documents that
might be required for submission to a building department to gain
a building permit for a building using the NUDURA Form System.
FIGURE 2.20
Note: This list is only a guide and is not intended to override any existing requirements a building department
might already have in place.
Completed set of working drawings
Floor Plans
• Show that NUDURA ICF is being used by some means- either on the plans directly or notes outlining
INTENTION to substitute the conventional construction method shown with NUDURA.
• List the size and spacing of the vertical and horizontal reinforcing steel and make reference from where this
was obtained.
• If beam pockets are needed, show location and reference any additional reinforcing steel necessary.
Elevations
Building Section Drawings
• Show floor to floor heights for each story
• Exterior Finishes
• Interior Finishes
• Backfill Heights
• Footing Sizes
Relevant Detail Section Drawings
• Include photocopies of any details from this manual
• Floor Connection Details
• Roof Connection Details
Don’t forget to ensure that the drawing set has been produced to include the data outlined under Section 2.1 “Drawing
and Contract Document Preparations”. This will help the Building Official to understand all of the prescriptive elements
being covered in the design and avoid any question both during plan examination and subsequent inspection on site.
And finally be sure to include copies of:
• The applicable evaluation report for the site
• Additional regional documentation as may be required
• Structural Table Data to corroborate design
• Lintel schedule, if produced separately
50
I N S T A L L A T I O N
M A N U A L
GETTING STARTED
2.6 PRE CONSTRUCTION PLANNING
To ensure that the project is successful, it’s important to start with a detailed plan of action before any work
commences. Having a plan of execution is just as important as a detailed building plan, and this will help the contractor
avoid costly delays in construction along with bringing the project in on budget. The following steps will ensure the
project gets started on the right path to completion.
STEP 1: UNDERSTAND THE PROPERTY: identify
the services that will need to be brought into the building.
Determining the necessary services and the connection points,
will allow the contractor to plan entry locations for penetrations
going through the wall section.
Obtain all the necessary permits, and become familiar with the
local by-laws and covenants for the area before construction.
Remember that soil conditions and the lot elevations will
have an effect on footing (footer) sizes and building elevation
for the area. Water tables may also dictate the elevation of a
building and it is recommended that a contractor check with
local residents for any water issues in the area – particularly any
seasonal flood issues that can assist in setting final elevation of
the building OUT of potential water problems down the road.
Matching the building elevation with property slopes will ensure
proper drainage away from the building once construction
is completed. it will also be beneficial to plan the building’s
finished elevation to meet surrounding properties and the
finished elevations. Consulting a professional for site planning
and drainage planning will ensure costly maintenance in the
future can be avoided.
FIGURE 2.21
STEP 2: SITE PREPARATION: As with any
construction site, heavy construction equipment is
necessary for completion of the project. NUDURA
Integrated Building Technology is no different
as there will be large delivery vehicles, heavy
excavation equipment, and concrete trucks and
pumps entering the property. All of these vehicles
will require additional room to maneuver around
the site to effectively perform the tasks needed
to complete the project. Depending upon soil
conditions, a solid sub base for the driveway will
ensure the above mentioned pieces of equipment
can maneuver around the site with ease. This
will also help to compact the soil, which will limit
settlement once the finished grade is determined.
Also make sure that there is room for any pieces
of equipment needing to swing booms into the
structure without interference from electrical lines,
neighboring dwellings, and any other dangerous obstructions.
FIGURE 2.22
Now that the above steps have been reviewed, the contractor has the necessary plan to move forward with
construction of the building. These items need to be documented for site plan submission to the local building
department and are an essential part of the package the home owner requires, keeping on file for future maintenance
of the property.
M A N U A L
51
I N S T A L L A T I O N
Was this manual useful for you? yes no
Thank you for your participation!