NetworX Series
TM
NX-6-EUR Control Panel
Installation manual
g
imagination at work
NX-6-EUR Installation manual
Page 2
02/07/06
CONTENTS
CONTENTS .................................................................................................................................................................................... 3
GENERAL INFORMATION............................................................................................................................................................ 5
ORDERING INFORMATION ......................................................................................................................................................... 5
FEATURE DEFINITIONS ............................................................................................................................................................... 6
PROGRAMMING THE NX-6 KEYPADS ......................................................................................................................................14
PROGRAMMING THE LED KEYPADS .............................................................................................................................................................................. 14
PROGRAMMING THE NX-148 LCD KEYPADS ............................................................................................................................................................. 18
KEYPAD FUNCTIONS FOR THE NX-148 LCD KEYPAD ............................................................................................................................................... 21
PROGRAMMING THE NX-6 CONTROL PANEL........................................................................................................................26
PROGRAMMING THE NX-6 CONTROL PANEL VIA THE LED KEYPAD ......................................................................................................................... 26
ENTERING THE PROGRAM MODE................................................................................................................................................................. 26
SELECTING THE MODULE TO PROGRAM.................................................................................................................................................... 26
PROGRAMMING A LOCATION.......................................................................................................................................................................... 26
EXITING A LOCATION .......................................................................................................................................................................................... 26
EXITING THE PROGRAM MODE....................................................................................................................................................................... 27
PROGRAMMING DATA........................................................................................................................................................................................ 27
LOADING FACTORY DEFAULTS ....................................................................................................................................................................... 28
ENROLLING MODULES AND KEYPADS........................................................................................................................................................ 28
PROGRAMMING THE NX-6 CONTROL PANEL VIA LCD KEYPAD ................................................................................................................................ 30
ENTERING THE PROGRAM MODE................................................................................................................................................................. 30
SELECTING THE MODULE TO PROGRAM.................................................................................................................................................... 30
PROGRAMMING A LOCATION.......................................................................................................................................................................... 30
EXITING THE PROGRAM MODE....................................................................................................................................................................... 32
LOADING FACTORY DEFAULTS ....................................................................................................................................................................... 32
ENROLLING MODULES AND KEYPADS........................................................................................................................................................ 32
IMPORTANT REMARKS..............................................................................................................................................................33
TAMPER MEMORIZATION ................................................................................................................................................................................................. 33
DISABLING TAMPER ALARMS IN PROGRAM MODE ........................................................................................................................................................ 33
COUNTRY CODE ............................................................................................................................................................................................................... 33
KEYPAD TAMPER LOCKOUT ............................................................................................................................................................................................. 33
CLC/TS 50131-3 COMPLIANCY................................................................................................................................................................................. 34
CONTROL PANEL PROGRAMMING LOCATIONS....................................................................................................................35
TELEPHONE NUMBER 1................................................................................................................................................................................................... 35
FORMAT SELECTIONS ...................................................................................................................................................................................................... 36
REPORTING EVENTS TO PHONE NUMBER 1................................................................................................................................................................... 37
TELEPHONE NUMBER 2................................................................................................................................................................................................... 38
REPORTING EVENTS TO PHONE NUMBER 2................................................................................................................................................................... 39
TELEPHONE NUMBER 3................................................................................................................................................................................................... 40
REPORTING EVENTS TO PHONE NUMBER 3................................................................................................................................................................... 41
SPECIAL FORMATS ........................................................................................................................................................................................................... 43
DOWNLOAD PARAMETERS .............................................................................................................................................................................................. 44
FEATURE AND REPORT SELECTIONS (FOR PARTITION 1) .............................................................................................................................................. 45
ENTRY/EXIT TIMERS ......................................................................................................................................................................................................... 46
ZONE CONFIGURATIONS AND PARTITION SELECTION .................................................................................................................................................. 47
GENERAL OPTIONS .......................................................................................................................................................................................................... 51
PROGRAMMING THE OUTPUTS ....................................................................................................................................................................................... 55
NX-6-EUR Installation manual
Page 3
02/07/06
SETUP FOR AUTO-TEST, AUTO-ARM AND OPENING/CLOSING TIMES ......................................................................................................................... 58
COMMUNICATOR CODES FOR SLOW SPEED FORMATS ONLY ...................................................................................................................................... 60
PROGRAMMING PARTITION PARAMETERS ..................................................................................................................................................................... 68
PROGRAMMING ZONE CONFIGURATION GROUPS ........................................................................................................................................................ 69
NX-6 PROGRAMMING WORKSHEETS .....................................................................................................................................80
BOARD INSTALLATION .............................................................................................................................................................91
NX-6 WIRING DIAGRAM............................................................................................................................................................92
TERMINAL DESCRIPTION..........................................................................................................................................................93
TECHNICAL SPECIFICATIONS...................................................................................................................................................94
TECHNICAL SPECIFICATIONS NX-6 ............................................................................................................................................................................... 94
TECHNICAL SPECIFICATIONS NX-108, NX-116, NX-124...................................................................................................................................... 94
TECHNICAL SPECIFICATIONS NX-1308, NX-1316, NX-1324.............................................................................................................................. 95
TECHNICAL SPECIFICATIONS NX-148.......................................................................................................................................................................... 95
APPENDIX 1: REPORTING FIXED CODES IN CONTACT-ID AND SIA.................................................................................96
APPENDIX 2: REPORTING ZONE CODES IN SIA OR CONTACT ID .......................................................................................97
APPENDIX 3: EXPANDER NUMBERS FOR REPORTING EXPANDER TROUBLE ...................................................................99
KEYPADS ........................................................................................................................................................................................................................... 99
REMOTE POWER SUPPLY NX-320E ............................................................................................................................................................................. 99
WIRELESS RECEIVER NX-448E..................................................................................................................................................................................... 99
OUTPUT MODULE NX-507E OR NX-508E................................................................................................................................................................ 99
CE DECLARATION ....................................................................................................................................................................100
NX-6-EUR Installation manual
Page 4
02/07/06
GENERAL INFORMATION
The NX-6-EUR (from now on called NX-6) NetworX from Caddx represents a new approach to
the design of security systems. The NX-6 is probably the most flexible, durable, and userfriendly control panel ever seen in our industry. Its features include sophisticated software
enabling as many as 40 users to interface with 6 zones, wireless expandable up to 16 zones, 2
partitions, with access, audio verification, and input/output modules, all reported with SIA and
Contact ID formats which are extremely fast and very comprehensive. Thanks to the NetworX
design, a fully loaded system can be housed in one single metal enclosure, establishing for the
first time, a logical solution and design response to modular systems. Up to 3 modules can be
added to expand the capabilities of the NX-6.
ORDERING INFORMATION
For detailed ordering information and part numbers, please refer to the EMEA Distribution
price list of the Caddx product range.
NX-6-EUR Installation manual
Page 5
02/07/06
FEATURE DEFINITIONS
Abort
If this option is enabled, the NX-6 will wait the programmed number of seconds (0-255) in
location 40 prior to sending an alarm. During this delay time, the “Cancel” LED will flash. To
abort the report, type in a code and press the [Cancel] key. The LED will go out. If the report is
not aborted within the allotted time, the LED will go out when the report is sent. The dialler
delay is programmed at location 40, segment 8. Each zone can be defined as a “dialler delay
zone” by defining the relevant option in segment 3 of the appropriate zone configuration
group (see locations 110-169).
AC fail / low battery report/warning
The NX-6 can be programmed to report an AC failure and/or low battery conditions to the
central station. Low battery will be detected as the battery gets discharged down to 10,5Vdc
and lower. It can also be programmed to sound the keypad immediately when the condition is
detected. The AC failure report/warning can be delayed (see locations 37, 39 and 40).
AC power / low battery sounder alert
If this option is enabled, the NX-6 will beep the keypad sounder upon arming or disarming, if
the AC power is not present or if a low battery has been detected (see location 23, segment 2).
Arm / disarm codes
The NX-6 may have 40 four-digit or six-digit codes to arm/disarm the control panel. All the
codes must have the same number of digits. The factory default for user 1 is [1]-[2]-[3]-[4]
when using a 4-digit code, or [1]-[2]-[3]-[4]-[5]-[6] for a 6-digit code. This code can then be
used to enter the new arm/disarm codes (see location 41).
Automatic arming
If programmed, the NX-6 will Auto Arm at a specified time. At this time, the keypad will start
beeping before the panel arms and this for the amount of time set as warning time (warning
timer). The arming process will be stopped during the warning time if a code is entered on the
keypad or when movement has been detected. The NX-6 will attempt to arm again after the
amount of time set as retry time (retry timer) until the next “opening” time (loc. 52), or until the
system is armed. The panel will not try to re-arm if the retry feature has been disabled. If a
zone is faulted before the warning timer starts and stays faulted when the panel tries to autoarm, the zone will automatically be bypassed. The auto arming of a partition can be
programmed so that it is silent. If closing reports are sent, the user code will be 97 (see
locations 23 segment 2, location 40 segment 12 and 13 and location 52-55).
Automatic bypass / instant arming
When this option is enabled, the control panel can automatically bypass interior follower
zones if no exit is detected during the exit delay time. Entry delay zones can also be made
instant (see location 23, segments 1 and 2).
Auto cancel
If enabled, the Cancel and/or Abort features will be automatic (pressing the [Cancel] button is
not required). The Cancel and Abort features, in locations 23 & 40 respectively, must be
enabled to permit this Auto feature to work. For proper operation of these features, “Dialer
Delay” must be enabled in the zone configuration group (see locations 110-169).
NX-6-EUR Installation manual
Page 6
02/07/06
Auto-test
This feature will cause the panel to call the central station, in order to report a communicator
test at a specified interval (see location 51). Also, the auto-test report may be enabled ONLY
when the control panel is armed see location 37 segment 4).
Auxiliary outputs
The NX-6 has four programmable outputs which can be used to activate LED’s, sirens, flashes,
etc. (see the terminal description and locations 47-50).
Auxiliary power overcurrent
The NX-6 will light up the “Service” LED on the keypad whenever too much current is being
drawn from any device powered by the system. This condition can be reported to the central
station (see location 37 segment 3).
A+B alarm reporting (Sweden)
When this feature is enabled, a first trigger from a zone will send a BG report
(unverified alarm or B-alarm) for that zone. The B-alarm message will be written in the log. In
addition, a fix 30 minutes timer will start. If a zone is triggered for a 2nd time within the 30
minutes time frame, this zone will send a BA report (burglary alarm or verified alarm) to the
monitoring station. If there is no 2nd zone that was triggered within 30 minutes, the timer will
be cleared. A+B alarm reporting only works with intrusion zone types using the SIA formats.
When this feature is enabled, the standard cross-zoning feature will be in-active (see location
37 segment 3).
Box tamper
The NX-6 has an input for a normally closed tamper switch (see wiring diagram). The box
tamper can be programmed to report, and/or sound the siren and/or the keypad. These
terminals can be enabled or disabled by programming (see locations 37 segment 2 and 3, and
location 39).
Built In siren driver
The NX-6 has a built-in 112 dB siren driver. If desired, this built-in driver can easily be
converted to a 1 amp voltage output by programming (see location 37 segment 2).
Bypass toggle
This feature will enable the end user to toggle (turn on or off) the bypass of an interior zone
while the system is armed. This is done by pressing the [Bypass] key (see location 23 segment
2).
Call back
When this feature is enabled, the control panel will use the call back phone number to call the
download computer before it begins a download (see locations 21 and 22).
Cancel
If this feature is enabled, the NX-6 will send a “Cancel” report when the system is disarmed
and the [Cancel] button is pressed within 5 minutes of an alarm. Once the [Cancel] key has
been pressed, the “Cancel” LED will light up until the central station acknowledges the “Cancel”
report (see location 23 segment 3).
Chime
This feature can be turned on and off using the “chime” key. When the system is in the
disarmed state, a trip on selected zones will generate either a DING-DONG or a single tone
through the keypad sounder (depending on the keypad programming). This lowest level of
security can be enabled by zone; this is done by programming the appropriate zone
configuration for it, or by customizing its zone configuration (see locations 111-169).
NX-6-EUR Installation manual
Page 7
02/07/06
Code required options
The NX-6 can be programmed to require a code in order to bypass zones and/or to initiate a
download using the [*]-[9]-[8] or [*]-[9]-[9] function (see locations 23 segment 2 and 41).
Communication formats
The NX-6 can report in multiple formats. You are recommended to use Contact ID or SIA
formats if possible. If you wish to report to a private phone (using the voice module) or to a
central station in a 4+2 format, you must program each code that is to be reported (see
locations 56-83 and 111-169).
Configuration groups
The NX-6 has 30 configuration groups that determine how each zone will function and report.
The default configuration groups are listed on pages 44-46. All configuration groups are fully
programmable via downloading and via the keypad (see locations 111-169).
Country code
The NX-6 has the ability to set different “country codes”. Each country code has specific
default settings. Before start programming the NX-6, it is important to select the country code
that is required. Once the country code has been selected, it will remain set, even after an
installer reset. When changing the country code during programming, all existing
programming will be cleared to the defaults for that country (see location 213).
Cross zoning
This feature requires two or more trips within a specified time on one or more zones that are
programmed as “cross zones” before it will report an alarm. During the time between trips, the
NX-6 can be programmed to sound the keypad and/or the siren. The NX-6 can also be
programmed to report an alarm after two or more trips on the same zone. The first trip on a
cross-zone is also logged (see locations 37 segment 1, 39, 40 and 110-169).
Daylight savings time
The NX-6 has the possibility to switch automatically from summer to wintertime and vice
versa. This option will move the clock backward on the last Sunday of October (3 a.m.
becomes 2 a.m.) and will move the clock forward on the last Sunday of March (2 a.m. becomes
3 a.m.) (see location 37, segment 5, option 8).
Dual / split / multiple reports
The NX-6 can send communication reports to three different phone numbers for dual, split or
multiple reports: these can be selected by event or by partition (see locations 4, 10, and 16).
Duress code
If a duress code is programmed, the NX-6 will send a duress signal whenever the panel is
armed or disarmed with this code. If open/close reports are sent, the user code will be 254
(see location 44).
Dynamic battery test
The NX-6 can be programmed to perform a dynamic battery test for a selected duration when
the panel is armed or disarmed for the first time each day. The NX-6 can also be programmed
to perform a ‘missing battery’ test every 12 seconds (see locations 37 segments 2 and 3 and
location 40).
NX-6-EUR Installation manual
Page 8
02/07/06
End of line resistor defeat
The NX-6 can be programmed to make zones 1-6 for normally closed operation only,
eliminating the need of the end of line resistors on these zones. When a zone is programmed
for normally closed operation, a short on that zone will not change the loop condition, and an
open on that zone will produce a faulted condition. This feature will be ignored by any priority
zone (see locations 110-169).
Entry-guard
This unique low level arming mode has been developed to reduce the most common source of
false alarms. When armed in the “Stay Instant” mode, opening any zone designated as an
“Entry Guard Zone” will initiate the keypad sounder and start the entry delay before
generating an alarm. All the other zones will function as normal. This arming mode will
encourage system owners to use their systems more frequently when the premises are
occupied (see locations 111-169).
Exit error / Exit error Delay 1
If the option Exit error is enabled on location 23 segment 3, the NX-6 will send an “Exit Error
Report” when an entry/exit zone is faulted, at the instant the exit delay expires. If also the
option “Exit Error Delay 1” is enabled on location 37 segment 7, the NX-6 will send an “Exit
Error Report” when only an entry/exit delay 1 zone is faulted, at the instant the exit delay
expires. An entry/exit delay 2 zone that is faulted at the end of the exit delay will not have
siren activation and will not log an exit error. The “Exit Error Report” will be sent together with
the user number that was used to arm the system, provided that the panel is not disarmed
before the entry delay expires. The alarm report will also be sent. If both features “Exit Error
Report” and “Exit Error Delay 1” are not enabled the siren will sound if any entry/exit zone is
faulted, as soon as the exit delay expires. If the option “Exit Error Delay 1” is enabled, the siren
will sound if only an entry/exit 1 zone is faulted (see location 23 segment 3 and location 37
segment 7).
Expander trouble
The NX-6 will report expander trouble to the central station if this option is enabled. This
condition will light up the “Service” LED on the keypad, even if it is not reported.
NOTE: The keypads are considered to be expanders. The number of expansion devices that
are reported can be found in appendix 3 (see location 37 segment 3).
Early to Open/ Late to Close
If an opening occurs before the opening and closing times, the NX-6 will send an “Early Open”
report. If it fails to close on or before the designated closing time, the NX-6 will send a “Late to
Close”report. (see location 23 segment 4)
Fail to communicate
The NX-6 will light up the “Service” LED if a report fails to reach the central station. If this
option is enabled, a fail to communicate code will be reported when the next report is
successfully communicated. A fail to communicate is always logged as “data lost” (see
location 37 segment 4).
Final set door
If this feature is enabled, it will only be applicable for secondary entry/exit zones (f.e.
configuration group 9 or 19). If the final set door option is enabled, the exit time will
immediately expire as soon as the secondary entry/exit zone (type 9 or 19) becomes ready
again. This feature can only be used in combination with magnetic contracts (see location 23,
segment 2, option 8).
NX-6-EUR Installation manual
Page 9
02/07/06
Fire alarm verification
When this feature is enabled, the NX-6 will verify a fire alarm by requiring more than one trip
on a smoke detector (the same or another one) within a specified time (120-255 seconds)
before it generates an alarm (see location 40 segment 9).
First opening/last closing report for multiple partitions
If this feature is enabled, the NX-6 will only transmit a closing report after ALL partitions have
been armed. An opening report will be sent as soon as one partition has been disarmed (see
location 37).
Force arming
If this option is enabled, the NX-6 can be “Force Armed” when zones have been violated. In this
condition, the “Ready” LED will flash if a “Force Armable” zone is not secure. At the end of the
exit delay, these zones will become bypassed, unless the option “No auto-bypass for force
armable zones” is set (location 23, segment 5 option 1). If these zones become secured at any
time during the arming cycle, they will be unbypassed and will become active in the system. If
“Bypass Report” is enabled, the force arming zones can be programmed to report bypass
when they are force armed (default), or not to report bypass even if “Bypass Report” is enabled
(see locations 37 segment 5, and 111-169 segment 2).
Guard codes (Sweden)
User codes 16 and 17 can be considered as so called “guard codes”. In this case, user codes
16 and 17 cannot be programmed or changed anymore via a master code. They can only be
changed via downloading. Guard code 16 will be able to arm/disarm at any time. Guard code
17 will only be able to arm/disarm during an alarm condition. Only when an alarm condition
occurs, guard code 17 will be able to disarm the system. After having evaluated the alarm
condition, guard code 17 can arm the system again but will not be able to disarm anymore
(see location 41, segment 1, option 7).
Group bypass
A designated group of zones can be programmed to bypass by pressing [Bypass]-[0]-[0][Bypass] prior to arming (see locations 111-169 segment 2).
Immediate restore by zone
The NX-6 can be programmed to send alarm and restore reports as soon as they occur, or to
wait until the siren time has expired or the system has been disarmed. (see location 37
segment 2).
Internal event log
Up to 512 events can be stored in memory together with the date and time of the event. These
events can be viewed later on via the LCD keypad, or by downloading. All reportable events
are reported to the log.
Keypad activated panics
The NX-6 has three keypad activated panics that will send reports to the central station,
auxiliary 1 (Fire), auxiliary 2 (Medical) and keypad panic. Auxiliary 1 will activate the steady
(Fire) siren, auxiliary 2 will sound the keypad, and the keypad panic can be programmed to be
silent or audible (see location 23 segment 1).
Keypad shutdown mode
This feature will extinguish all the LED’s on the keypad, except the “Power” LED, after 60
seconds have elapsed without a keypress. Pressing a valid user code (not an installer code) will
light up all the LED’s (see location 41, segment 1, option 5). This option requires bilingual LCD
keypads. This option is an alternative for LED-extinguish.
Keypad sounder control
The NX-6 can be programmed to sound the keypad sounder for certain events (see location
39).
NX-6-EUR Installation manual
Page 10
02/07/06
Keypad tamper
If this option is enabled, the NX-6 will disable the keypad for 60 seconds, and will
communicate a tamper signal to the central station whenever 30 keypresses are entered
without producing a valid code (see location 23 segment 1).
Keyswitch arm/disarm
Any zone on the NX-6 can be programmed as a momentary or maintained keyswitch zone. If a
zone has been programmed as a momentary keyswitch, momentary shorts on this zone will
arm/disarm the control. A zone can be also being programmed as a maintained keyswitch.
The control panel will be armed as long as such a zone is shorted. A keyswitch zone can arm
in AWAY or STAY mode (see location 23, segment 4, option 8). If opening/closing reports are
sent, the user code will be 99 (see “default zone configurations”)
LED extinguish
This feature will extinguish all the LED’s on the keypad, except the “Power” LED, after 60
seconds have elapsed without a keypress. Pressing any numeric key will light up all the LED’s
(see location 23 segment 2).
Local programming lockout
This feature will disable programming of all locations, or for specified locations, from the
keypad (see location 21).
Log full report
A report can be sent to the central station when the event log is full (see location 37 segment
4).
Log protection
This feature will prevent a single, non-zone reportable event to fill up the event memory. The
event will only be logged for a maximum of 3 times between closings or code entry. (see
location 37 segment 6).
Lost clock service light
The NX-6 can be programmed to light up the “Service” LED on a LED keypad or give a “Service”
message on a LCD keypad when the internal clock time is invalid due to power loss. On LCD
keypads, if programmed to show the system time, a “Set Clock, *97” message will always be
displayed (see location 37 segment 5).
Manual test
The NX-6 can be programmed to perform a bell and/or communicator test; to do this, enter
[*]-[4]-[4] while the system is in the disarmed state. Each time that [*]-[4]-[4] is entered, a
dynamic battery test will also be performed (see location 37 segment 2).
Night Mode
Applies to NX-1208E / NX-1248E keypads. In this mode, the control panel will bypass all zones
that have the Entry Guard feature enabled. (See location 23 and 111-169)
On board zone disable
The 6 zones on the NX-6 panel can be disabled, in order to obtain a completely wireless alarm
system. A mix of hardwired and wireless zones is also possible (see location 37 segment 5).
Partitions
The NX-6 can be partitioned into a maximum of 2 separate systems with distinct reporting
codes, user codes, and operating features for each system (see locations 26- 36 and locations
171-205).
NX-6-EUR Installation manual
Page 11
02/07/06
Program code
The factory default for the “Go To Program” code is [9]-[7]-[1]-[3] when using a 4-digit code; or,
if the 6-digit option is used, the default is [9]-[7]-[1]-[3]-[0]-[0]. The program code can also be
used as an arm/disarm code. If it is used as an arm/disarm code, and if open/close reports are
sent, the user code will be 255 (see location 43).
Quick arm feature
The NX-6 has a single-button “Quick Arm” feature which can be used to arm the system by
pressing the [Exit] key or the [Stay] key on the keypad. If closing reports are sent, the user code
will be 98 (see location 23 segment 1).
Recent closing
If this option is enabled, the NX-6 will send a “Recent Closing Report” to the central station if
an alarm occurs within 5 minutes after the panel is armed. The user number that was used to
arm the system will also be sent (see location 23 segment 3).
Re-exit
The NX-6 can restart the exit delay for a quick exit without the need to disarm the system; this
is done by pressing the [Exit] key while the system is still armed (= after exit delay has expired).
The re-exit is also logged (see location 23 segment 1).
Shutdown
This mode will cause the keypads to extinguish all LED’s, except the “Power” LED, and to refuse
keypresses (see location 21).
Siren blast for arming
The NX-6 can be programmed to give a one-second siren blast when the panel is armed, at
the end of the exit delay, or when the central station receiver acknowledges the closing report.
It can also give one blast for remote (keyswitch) arming, and two blasts for remote disarming
(see location 37 segment 1).
Siren supervision
The NX-6 has a “Siren Supervision” circuit that will constantly monitor the siren on the NX-6; it
can also be programmed to report if the wires are cut (see location 37 segment 3).
Silent exit option
The exit delay can be silenced by pressing [*]-[Exit] before arming the control panel, or when
using the re-exit feature. The exit delay can also be silenced permanently in all partitions (see
location 37 segment 5).
Start/end programming and end downloading
A report can be sent when local programming is started and ended. A report can also be sent
when a download session ends (see location 37 segment 4).
Swinger shutdown
This feature allows one or more zones to be bypassed automatically after a specified number
of alarms (from 0 to 255). If immediate restore is enabled in location 37, the alarms (and
restores, if this option is enabled) will be sent as they occur. If immediate restore is not
enabled, a second or subsequent alarm will not be sent until the siren times out (see location
37 segment 2 and location 38).
Telephone line monitor
The NX-6 has a telephone line monitor which monitors the voltage and current of the
telephone line, in order to detect a faulty phone line. This condition can also be reported to the
central station. If the report is enabled, only the telephone line restore will be reported. A
telephone line cut is always logged (see locations 37 segment 3, location 39 and location 40
segment 5).
NX-6-EUR Installation manual
Page 12
02/07/06
Two call answering machine defeat
If this option is enabled, two telephone calls must be made to the premises in order to defeat
an answering machine. On the first call, let the phone ring one or two times. The control panel
will detect these rings and start a 45-second timer; during this time, the control panel will
answer the next call on the first ring. This is not recommended for commercial applications
(see location 21).
User authorization to enter program mode
Entering program mode via the installer code is only possible within 60 seconds following a
user code entry (see location 41,segment1, option 6).
Walktest mode
Walktest mode is used to test your system without activating the siren and/or communicator.
The walktest mode is activated by pressing [*]-[chime] followed by the master code.
Walktest mode is not possible if any partition is armed or if the communicator is active.
Wireless sensor absent/low battery
The NX-6 will send a report to the central station when a wireless sensor has detected a low
battery, or has not reported to the receiver. The “Service” LED will light up when either of these
conditions exists (see location 37 segment 4).
Zone activity monitor
This feature will send a report to the central station when a particular zone does not change
conditions within the specified number of hours/days programmed (see location 37, location
40 and locations 110-169).
Zone bypassed sounder alert
With this feature enabled, if a zone is bypassed, the NX-6 will beep the keypad sounder when
the zone is armed (see location 23 segment 2).
Zone Doubling
This feature allows you to use the six zones on the panel as twelve normally closed zones.
When this feature is used, European double E.O.L. configuration cannot be used. THIS FEATURE
DOES NOT INCREASE THE TOTAL NUMBER OF AVAILABLE ZONES BEYOND 16. Zones 7-12
should not be programmed as a fire zone type when Zone Doubling is used. If one of the
twelve zones must be a fire zone, it must be one of Zones 1 to 6. The corresponding upper
zone will become unavailable. For example: if Zone 6 is a fire zone, then Zone 12 will not be
available. (See location 37, segment 5).
NX-6-EUR Installation manual
Page 13
02/07/06
PROGRAMMING THE NX-6 KEYPADS
Programming the LED keypads
This section describes how to program the address and partition for each keypad, and it also
explains the options that are available. The address of the keypad is important because the
panel uses it to supervise the keypads.
The factory default for the master code is [1]-[2]-[3]-[4] when using a 4-digit code, or [1]-[2][3]-[4]-[5]-[6] for a 6-digit code. The factory default for the “Go To Program” code is [9]-[7]-[1][3] for a 4-digit code, or [9]-[7]-[1]-[3]-[0]-[0] for a 6-digit code.
[*]-[9]-[3]
SET KEYPAD OPTIONS
1.
Enter [*]-[9]-[3] [program code]- the “Service” LED will flash.
2.
LED’s 1-8 can now be toggled on/off to enable/disable the following functions:
3.
After enabling/disabling the desired functions press [*]
LED
Keypad feature enabled
1
2
3
Box tamper on
Enable silent keypad option (no entry/exit delay sounder, no chime)
Enable Ding Dong sound for chime - If this is off, the chime will be a single tone
(see location 40).
Enable keypress silence option
(Silences the pulsing keypad sounder for 5 seconds when a key is pressed).
Enable armed status suppression
(Will not allow the keypad to display faulted or bypassed zones when the system is
armed).
Enable panic, fire, medical beep tone
(Will sound a short beep to verify that the keypress has been accepted).
Suppresses the “Service” LED
(Will not allow the “Service” LED to light up for any reason. If there is a system
malfunction (trouble), pressing [*]-[2] will still display the service menu.)
Enable multi-partition viewing
(Enables temporary viewing of all partitions, by pressing [*]-[1]-[partition number]).
4
5
6
7
8
NX-6-EUR Installation manual
Page 14
02/07/06
[*]-[9]-[4]
[*]-[9]-[5]
[*]-[9]-[6]
[*]-[9]-[7]
SET KEYPAD NUMBER AND PARTITION
1.
Enter [*]-[9]-[4]-[program code]- the “Service” LED and the “Instant” LED will flash.
2.
Enter the keypad number (1-8).
3.
Press [*]- the “Instant” LED will illuminate steadily, and the “Service” LED will carry on
flashing.
4.
Enter the partition number for the keypad. The keypad will automatically exit this mode
now).
SET ELAPSED INCREMENTS (HOURS/DAYS) SINCE LAST AUTOTEST
1.
Enter [*]-[9]-[5]-[program code]- the “Service” LED will flash.
2.
Enter [100's digit] -[10's digit]-[1's digit]-[#].
SET SYSTEM DATE
1.
Enter [*]-[9]-[6]- the “Service” LED will flash.
2.
Enter [master code]-[day of week (1=Sun)]-[month 10's digit]-[month 1's digit]-[day 10's
digit].
3.
[day 1's digit]-[year 10's digit]-[year 1's digit].
SET SYSTEM CLOCK
1.
Enter [*]-[9]-[7]- the “Service” LED will flash.
2.
Enter [master code]-[hour 10's digit]-[hour 1's digit]-[minutes 10's digit]-[minutes 1's
digit].
Note: the clock is a 24-hour clock.
[*]-[9]-[8]
INITIATE CALLBACK
Pressing [*]-[9]-[8] while the system is disarmed will cause the control panel to perform a
callback for a download.
NOTE: A VALID USER CODE MAY BE REQUIRED AFTER [*]-[9]-[8], IF ENABLED IN LOCATION
41.
[*]-[9]-[9]
ANSWER DOWNLOAD
Pressing [*]-[9]-[9] while the system is disarmed will cause the control panel to seize the phone
line for a download.
NOTE: A VALID USER CODE MAY BE REQUIRED AFTER [*]-[9]-[9], IF ENABLED IN LOCATION
41.
NX-6-EUR Installation manual
Page 15
02/07/06
[*]-[5]
[*]-[6]
CHANGING USER CODES
1.
Enter [*]-[5]-[master code]- the “Ready” LED will flash.
2.
Enter the 2 digit user number (always 2 digits, such as “03” for user 3)- the “Ready” LED
will illuminate steadily.
3.
Enter the new user code designated for the person in question - the “Ready” LED will
flash, indicating that the code has been accepted. If the code is rejected, the sounder will
beep 3 times.
4.
If another user code needs to be programmed, return to step 2.
5.
Press [#] while the “Ready” LED is flashing in order to exit the user code programming
mode.
6.
Pressing four times (for 4-digit code) can erase a user code or six times (for 6-digit code)
the “Cancel” key.
ASSIGNING AUTHORITY LEVEL
1.
Enter [*]-[6]-[master code]- the “Ready” LED will flash.
2.
Enter [2 digit user number] (always 2 digits, such as 03 for user 3)- the “Ready” LED will
illuminate steadily and the “Instant” LED will flash. Refer to the chart below for the
description of each LED. Turn on the LED for the features that you want.
LED
ATTRIBUTES IF LED 8 IS OFF
LED
1
2
3
4
Reserved
Arm only
Arm only after closing window
Master arm/disarm (can program
other codes)
Arm/disarm code
Allowed to bypass zones (see location
23)
Code will send open / close reports
If this LED is on, LED’s 1-7 will use the
chart too the right
1
2
3
4
Activate output 1
Activate output 2
Activate output 3
Activate output 4
5
6
Arm/disarm code
Allowed to bypass zones (see location
23)
Code will send open / close reports
If this LED is off, LED’s 1-7 will use the
chart on the left
5
6
7
8
1.
7
8
ATTRIBUTES IF LED 8 IS ON
Enter [*]: The “Instant” LED will illuminate steadily.
This moves you to the ‘partition enable’. (This tells the system which partition this user
can arm/disarm.) LED’s 1-8 will light up for each partition that the user is authorised to
arm/disarm. To change any of these numbers, press 1-8 to permit or deny access to the
user. (Example: If LED 2 is lit, then the user has been assigned access to that partition. By
pressing the [2] key, the LED will go out, indicating the user has been denied access to
that partition.)
2.
Enter [*]:
This brings you back to step 2 above. At this point, you may enter another user number to
which you can assign attributes. You may continue this procedure until you have
assigned authority levels to all user numbers; otherwise, you may press the [#] key to exit
the assigning authority level program.
NX-6-EUR Installation manual
Page 16
02/07/06
NOTE:
ANY MASTER ARM/DISARM CODE CAN ADD OR CHANGE A USER CODE IF THE MASTER CODE
HAS ACCESS TO THE SAME PARTITIONS AS THE CODE BEING ADDED/CHANGED.
CONSEQUENTLY, WHEN PROGRAMMING THE USER CODES FOR A PARTITIONED SYSTEM,
LEAVE AT LEAST ONE CODE WITH ACCESS TO ALL PARTITIONS. UNLESS YOU DO THIS, YOU
WILL NOT BE ABLE TO ADD NEW USERS. (THE CODE CAN BE THE “GO TO PROGRAM CODE”,
IF ENABLED IN LOCATION 43). IF YOU WANT TO LET THE END USER ADD NEW CODES, YOU
MUST REMOVE THE PARTITION AUTHORITY FROM ALL BLANK CODES.
[*]-[CHIME]
ACTIVATING WALKTEST:
1.
Enter [*]-[CHIME].
2.
Enter [Master code].
3.
Activate all sensors to test. Each activation of a sensor is confirmed with a “ding dong”
sound with a corresponding flashing zone-indicator.
4.
Enter [Master code]. Herewith the walktest-mode is left.
Remark: Walktest mode is not possible if any partition is armed or if the communicator is
active.
Additional keypad functions are described in the appropriate user manual
NX-6-EUR Installation manual
Page 17
02/07/06
Programming the NX-148 LCD keypads
This section describes how to program the address and partition for each keypad, and it also
explains the options that are available. The address of the keypad is important because the
panel uses it to supervise the keypads.
The factory default for the Master code is [1]-[2]-[3]-[4] when using a 4-digit code, or [1]-[2][3]-[4]-[5]-[6] for a 6-digit code. The factory default for the “Go To Program” code is [9]-[7]-[1][3] when using a 4-digit code, or [9]-[7]-[1]-[3]-[0]-[0] for a 6-digit code.
[*]-[9]-[1]
[*]-[9]-[2]
ADJUSTING THE VIEW / BRIGHTNESS OF THE LCD
1.
2.
Enter [*]-[9]-[1]
Enter [master code]
3.
To advance to the brightness
option, press [*]
The LCD screen will prompt for a “master” code.
The LCD will now prompt you to increase or reduce
the viewing angle. By using the scroll keys to the right
of the LCD, you can increase or reduce the textviewing angle.
The LCD will prompt you to brighten or dim the LCD
lighting. Use the scroll keys again to set the desired
brightness. When completed, exit by pressing [*].
PROGRAMMING CUSTOM MESSAGES IN THE KEYPAD
1.
2.
3.
4.
NX-6-EUR Installation manual
Enter [*]-[9]-[2]
The LCD screen will prompt for the “Go To Program”
code.
Enter [program code]
The LCD will now prompt you to enter the message
number followed by [#]. Zones 1 through 16 custom
messages are message numbers 1-16 respectively.
Message 193 - Custom message top line.
Message 194 - Custom message bottom line.
Message 195 – Shutdown message top line.
Message 196 – Shutdown message bottom line.
Enter message number to edit, The LCD will display the zone number on the top line.
followed by [#]
The zone description will be displayed on the bottom
line. Use the instructions on page 29-30 to edit
character data.
When finished, exit by pressing [EXIT] while the LCD screen is prompting for a zone
message #. Any changes will automatically be copied to all other LCD keypads in the
system. NOTE: If you want a LCD keypad to have a different custom message, you must
enable custom message lock under the [*]-[9]-[3] function.
Page 18
02/07/06
[*]-[9]-[3]
SET KEYPAD OPTIONS
1.
2.
Enter [*]-[9]-[3]
Enter [program code]
OPT
KEYPAD FEATURES
1
CASE TAMPER ON?
Tamper switch of keypad housing active
SILENT KEYPAD?
Enable silent keypad option. If this is on, silent keypad is enabled for entry/exit
delay and chime.
DING-DONG CHIME?
Enable ding-dong sound for chime. If this is off, the chime will be a single tone.
5 SEC. SILENCE?
Enable keypress silence option. Silences the pulsing keypad sounder for 5
seconds when a key is pressed.
ARMED ZONE INFO?
Enable armed status suppression. If this is on, the keypad will not display faulted
or bypassed zones when the system is armed.
BEEP ON PANICS?
Enable panic, fire, medical beep tone. Will sound a short beep to verify that the
keypress has been accepted.
DISABLE SERVICE?
Suppresses the “Service” Message. This will not allow the “Service” message to be
displayed for any reason. If there is a system malfunction (trouble), pressing [*][2] will still display the “Service” menu.
MASTER KEYPAD?
Enable multi-partition mode.
CUSTOM MESSAGE?
Enable custom message display.
CLOCK?
Enable clock display.
CUSTOM MSG. LOCK?
Enable custom message lock. Prevents the custom message from being
overwritten during keypad copy.
SELECT AN OPTION
1234 - - - -
2
3
4
5
6
7
8
9
10
11
12
NX-6-EUR Installation manual
The LCD screen will prompt for a code.
The LCD will now prompt you through the options
listed in the following chart. The current state of the
option will be shown in the lower right corner of the
display. Press [*] to exit the current state without any
changes. Otherwise, follow the directions on the
bottom line to select the desired option. When
finished, press [*] to move to the next option.
Page 19
02/07/06
Remark :
Option 1 :
Option 2 :
Option 3 :
Option 4 :
Option 5 :
Option 6 :
Option 7 :
Option 8 :
[*]-[9]-[4]
In the menu “Select an option” 8 additional options can be selected. The
options 5 until 8 are not used for the moment and may therefore not be
selected. The options 1 and 4 are described below:
On the LCD screen “press * for help”. By this the status of the system and
the message “press * for help” are alternately displayed on the LCD screen.
This is only to inform the user of the user’s menu.
Light continuously on. By this the lights of the LCD display and the keys will
continue to light up, independently of the programming of the control panel.
(Adr 23, Segm. 2, option 1 = turn off the lights after one minute of inactivity).
ON if PIN should be hidden when programming user codes.
ON suppresses beeps when an RF transmission is lost.
Reserved (Do not program).
Disable ARM and BYPASS led for Norway/Sweden (NX-148E v3.47)
Any zone Alarm has priority over the Pre-Alarm message “Type code to
disarm” on the LCD screen (NX-148E v3.49)
Reserved (Do not program).
SET KEYPAD NUMBER AND PARTITION
1.
2.
Enter [*]-[9]-[4]
Enter [program code]
3.
Enter the keypad number
followed by [*]
4.
Enter the partition number for
the keypad
NX-6-EUR Installation manual
Page 20
The LCD screen will prompt for a code.
The LCD will now prompt you for the keypad number
followed by [*]. The current keypad number will be
displayed in the lower right hand corner.
The LCD will now prompt you for the partition number.
The current partition will be displayed in the lower
right hand corner.
The keypad will automatically exit this mode now.
02/07/06
Keypad functions for the NX-148 LCD keypad
The LCD keypads have a bilingual user’s interface. As a result, you can simply select a user’s
function on the menu. You can consult the menu by entering the [*] key.
The user of the system can easily switch from one user’s interface to another and the other
way around.
To select a user’s function, following steps have to be performed.
Step 1
Enter the [*] key until the function you want, appears on the LCD display /
screen.
Ex.
Select an option
90 = Log Review
Step 2
To select the option, you must press the appropriate option number next to
the option (ex. Consulting Log Review = option 90)
To exit the user’s menu, press the [#] key.
If you already know the option (ex. Log Review = 90) you can immediately select the wanted
option by pressing the [*]-[9]-[0] keys. By doing this you don’t have to browse through the
user’s menu.
In the following table you will find all functions that can be executed by the user.
USER’S MENU
NX-6-EUR Installation manual
Option
Description English (1)
Description English (2)
▲▼
0
1
2
3
41
42
43
44
45
46
49
5
6
7
90
91
97
CHIME
EXIT
Zone Review
Set Tone
Master Mode
Service Check
Alarm Memory
Telephone # 1
Telephone # 2
Telephone # 3
Test
Display test
Light Control
English (2)
User PIN
User Authority
Detector Reset
Log Review
View Settings
Set Date/Time
Walktest
Silent Exit
Zone Review
Set Tone
Master Mode
Service Check
Alarm Memory
Telephone # 1
Telephone # 2
Telephone # 3
Test
Display test
Light Control
English (1)
User PIN
User Authority
Detector Reset
Log Review
View Settings
Set Date/Time
Walktest
Silent Exit
Page 21
02/07/06
[*]-[9]-[0]
READING THE EVENT LOG
The NX-6 has a 512-event log which can be retrieved using a master code. This log contains a
listing of the last 512 events along with the date, time, and partition where each event
occurred.
1.
2.
3.
4.
5.
Press [*]-[9]-[0]
The LCD screen will prompt you for a code.
Enter [master code]
The LCD screen will now show the most recent event.
To view the events from the latest to the oldest, press the ‘down’ scroll key.
To view the events from the oldest to the latest, press the ‘up’ scroll key.
The display contains the following information.
Event
Date (month/Day)
Open
9/25
17:57
75
P3*
User or zone ID
Indicates partition and *
indicates an event not reported
Time shown in
24 hour format
This screen shows an opening of partition 3 on September 25th at 5:27 p.m. by user 75. The
[*] shows that this event is not programmed for reporting to the central monitoring station.
[*]-[9]-[5]
SET INCREMENTS (HOURS/DAYS) ELAPSED SINCE LAST AUTOTEST
1.
2.
3.
[*]-[9]-[7]
Enter [*]-[9]-[5]
The LCD screen will prompt for a code.
Enter [program code]
The LCD will now display the elapsed time screen.
Enter [100's digit] -[10's digit]-[1's digit]-[#]
SET SYSTEM TIME AND DATE
1.
2.
3.
4.
5.
Enter [*]-[9]-[7]
Enter [master code]
The LCD screen will prompt for a code.
The date and time will be displayed, with the current
hour flashing.
Use the ‘up’ and ‘down’ scroll keys to select the proper hour.
Enter the [*] key to move to the minutes.
Repeat until you have set the entire date.
[*]-[9]-[8]
Pressing [*]-[9]-[8] while the system is disarmed will cause the control panel to perform a
callback for a download. NOTE: A VALID USER CODE MAY BE REQUIRED AFTER [*]-[9]-[8], IF
ENABLED IN LOCATION 41 OF THE NX-6 CONTROL PANEL.
[*]-[9]-[9]
Pressing [*]-[9]-[9] while the system is disarmed will cause the control panel to seize the phone
line for a download. NOTE: A VALID USER CODE MAY BE REQUIRED AFTER [*]-[9]-[9], IF
ENABLED IN LOCATION 41 OF THE NX-6 CONTROL PANEL.
NX-6-EUR Installation manual
Page 22
02/07/06
[*]-[ ]
VIEW ZONE STATUS
1.
2.
3.
[*]-[3]
The LCD screen will display the zone status.
The LCD screen will display the list of ALL zones, in
sequential order by zone number.
VIEW ALARM MEMORY
1.
Enter [*]-[3]
2.
Use the ‘up’ and ‘down’ scroll
keys to browse through the
alarm memory.
Press [#] to exit this function.
3.
[*]-[4]-[5]
Enter [*]-[▲]
Use the ‘up’ and ‘down’ scroll
keys to browse through the
descriptions.
Press [#] to exit this function.
The LCD screen will display the zone description for
the zones.
The LCD screen will display the list, in sequential order
by zone number.
DISPLAY TEST
The keyboard also provides a test function by the means of which the LCD display and all
LED’s are tested.
Step 1
Step 2
[*]-[4]-[9]
Press [*] [4] [5]. The display and the LED’s will blink.
Press the [*] key to leave the display test.
MODIFYING LANGUAGE
The possibility exists to modify the language on the LCD display from one language to another
and the other way around.
Step 1
Step 2
[*]-[5]
Press [*] [4] [9]. The LCD display switches to the other language.
To switch back to the other language, only step 1 has to be repeated.
CHANGING USER CODES:
Note: For partitioned systems, someone changing the code of another person must have
access to all partitions, or to more partitions than the user being changed.
1.
2.
3.
4.
5.
6.
7.
NX-6-EUR Installation manual
Enter [*]-[5]
The LCD screen will prompt for a code.
Enter [master code]
The LCD screen will prompt for a user number.
Enter the 2 digit user number
The LCD screen will prompt for a new code.
(always 2 digits, i.e. “03” for
user 3)
Enter the new user code designated for the person in question. If the code is rejected,
the sounder will beep three (3) times.
If another user code needs to be programmed, return to step 3.
To exit code programming, press [#] while the LCD screen is prompting for a new user
number.
REMARK: Pressing four times (for 4-digit code) can erase a user code or six times (for
6-digit code) the “Cancel” key.
Page 23
02/07/06
[*]-[6]
ASSIGNING AUTHORITY LEVEL
Note: You must be authorized to access the partition that you wish to add to, or remove from,
another person’s authority.
1.
2.
3.
Enter [*]-[6]
Enter [master code]
Enter the 2 digit user number
(always 2 digits, i.e. “03” for
user 3)
PROMPTS
Outputs used?
Open / close report?
Bypass enable?
Arm / disarm?
4
The LCD screen will prompt for a code.
The LCD screen will prompt for a user number.
The LCD screen will prompt for a new code. The LCD
will now prompt you for the first in the following list of
attributes.
If prompt 1 (“Outputs used?”)
is answered NO, the LCD will
display the four messages
below
If prompt 1 (“Outputs used?”)
is answered YES, the LCD will
display the four messages
below
Master code?
Sched. arm only?
Arm only?
Reserved
Output 4 enable?
Output 3 enable?
Output 2 enable?
Output 1 enable?
Enter a partition number.
The LCD screen will prompt you for the next user
code.
Note: The default allows access to all partitions. The first keypress will remove access to
the partition. To re-establish access, press the partition number again. When
completed, press [*].
5.
6.
NOTE:
If another user code needs to be programmed, return to step 3.
To exit this feature, press [#].
WHEN PROGRAMMING THE USER CODES FOR A PARTITIONED SYSTEM, LEAVE AT LEAST ONE
CODE WITH ACCESS TO ALL PARTITIONS. UNLESS YOU DO THIS, YOU WILL NOT BE ABLE TO
ADD NEW USERS. (THE CODE CAN BE THE “GO TO PROGRAM CODE”, IF ENABLED IN
LOCATION 43 OF THE NX-6 CONTROL PANEL). IF YOU WANT TO LET THE END USER ADD
NEW CODES, YOU MUST REMOVE THE PARTITION AUTHORITY FROM ALL BLANK CODES.
NX-6-EUR Installation manual
Page 24
02/07/06
[*]-[CHIME]
ACTIVATING WALKTEST
1.
2.
3.
Enter [*]-[CHIME]
Enter [mastercode]
Activate all sensors to test
4.
Enter [mastercode]
Remark:
1.
2.
NX-6-EUR Installation manual
The LCD screen will prompt you for a “master code”.
The LCD screen will display the “walktest mode”
Each activation of a sensor is confirmed with a “ding
dong” sound. The zone texts of the sensors who have
reacted, are displayed one by one on the screen.
The walktest mode is left.
All activations and restore conditions occurred during the walk test, can
be verified by consulting the memory file (see function [*]-[9]-[0])
A walk test mode is not possible if any partition is armed or if the
communicator is active.
Page 25
02/07/06
PROGRAMMING THE NX-6 CONTROL PANEL
Programming the NX-6 control panel via the LED keypad
ENTERING THE PROGRAM MODE
To enter the program mode, press [*]-[8]. When you do this, the five function LED’s (Stay,
Chime, Exit, Bypass, and Cancel) will begin to flash. Next, enter the “Go To Program Code”
(FACTORY DEFAULT IS [9]-[7]-[1]-[3]). If the “Go To Program Code” is valid, the “Service” LED will
flash and the five function LED’s will illuminate steadily. You are now in the program mode,
ready to select the module to be programmed.
Note: it is impossible to enter program mode if any partition - or the system - is armed.
SELECTING THE MODULE TO PROGRAM
Since all the modules connected to the NX-6 are programmed through the keypad, the
module you are programming should be the first entry. To program the NX-6 control panel,
enter [0]-[#]. The [0] is the module number of the control panel and the [#] is the entry key.
Other module entry numbers can be found in the corresponding manuals.
PROGRAMMING A LOCATION
Once you have entered the number of the module to be programmed, the “Armed” LED will
light up, to show that it is waiting for a programming location to be entered. Any location can
be accessed by directly entering the desired programming location, followed by the
crosshatch (pound) [#] key. If the location you enter is valid, the “Armed” LED will go out, the
“Ready” LED will light up, and the binary data for the first segment of this location will be
shown by the zone LED’s. While entering new data, the “Ready” LED will begin flashing to
indicate that a data change is in process. The flashing will continue until the new data are
stored, by pressing the [*] key. When you press the [*] key, the keypad will advance to the next
segment and will display its data. Repeat this procedure until the last segment is reached.
Press the [#] key to exit from this location, and the “Armed” LED will light up again - this means
that it is waiting for a new programming location to be entered. If you want the next location
in the sequence, press the [POLICE] key. If you want the previous location, press the [FIRE] key.
If you want the same location, press the [MEDIC] key. To review the data in a location, repeat
the above procedure, pressing the [*] key without any numeric data entry. Each time you
press the [*] key, the programming data of the next segment will be displayed for review.
Note: Before programming the panel, the correct country code must be set in loc. 213
EXITING A LOCATION
After the last segment of a location has been programmed, press the [*] key to exit that
location; this turns the “Ready” LED off and the “Armed” LED on. As before, you are now ready
to enter another programming location. If you try to program an invalid entry for a particular
segment, the keypad sounder will emit a triple error beep (beep, beep, beep), and it will remain
in that segment awaiting a valid entry.
NX-6-EUR Installation manual
Page 26
02/07/06
EXITING THE PROGRAM MODE
When all the desired changes in programming have been made, it is time to exit the program
mode. Press the [Exit] key to exit this programming level, and go to the “Select a Module To
Program” level. If no additional modules are to be programmed, press the [Exit] key again to
exit the program mode. If there is a module to be programmed, you can select it by entering
its address, followed by the [#] key (see “Selecting the Module To Program” above). The
procedure for programming these devices is the same as for the control panel, except that the
locations will be for the module selected.
Note: the timeout for the program mode is 15 minutes.
PROGRAMMING DATA
There are only two possible types of programming data. One type of data is numerical: data of
this type can assume values from 0 -15 or 0 -255, depending on the location's segment. The
other type is feature selection data: this data is used to turn features on or off. Use the
following procedures when working with these two data types:
Numerical data: entering a number from 0-255 on the numeric keys of the system keypad
programs numerical data. To view the data in a location, a binary process is used. With this
process, the LED’s for zones 1 through 8 are utilized, and the numeric equivalents of their
illuminated LED’s are added together to determine the data in a programming location. The
numeric equivalents of these LED’s are as follows:
Zone 1 LED = 1
Zone 2 LED = 2
Zone 3 LED = 4
Zone 4 LED = 8
Zone 5 LED = 16
Zone 6 LED = 32
Zone 7 LED = 64
Zone 8 LED = 128
Example: If the numerical data to be programmed in a location is “66”, press [6]-[6] on the
keypad. The LED’s for zone 2 and zone 7 will light up, showing that 66 is in this location (2 + 64
= 66). See the example p. 26.
Once the data has been programmed, press the [*] key to enter the data, and advance to the
next segment of that location. After the last segment of a location has been programmed,
press the [*] key to exit from that location - this turns the “Ready” LED off and the “Armed” LED
on. As before, you are now ready to enter another programming location. If you try to
program a number that is too large for a particular segment, the keypad sounder will emit a
triple beep to indicate an error, and will remain in that segment awaiting a valid entry. Remark:
On the LCD keypad, the number in the location will be displayed. For locations with a
maximum of 15, the hexadecimal equivalent will be displayed in parenthesis. Example: 11 (B)
or 14 (E).
Feature selection data: feature selection data will display the current condition (on or off) of
eight features associated with the selected programming location and segment. If you press a
button on the keypad (1 to 8) that corresponds to the “feature number” within a segment, this
will toggle the feature (on/off). By pressing any numeric key between [1] and [8] to select a
feature, you will make the corresponding LED light up (feature ON). Press the number again,
and the LED will go out (feature OFF). You will see that numerous features can be selected
from within one segment. For instance, if you want all eight features of a segment, pressing
[1]-[2]-[3]-[4]-[5]-[6]-[7]-[8] will turn on LED's 1 to 8 as you press the keys, indicating that those
features are enabled. After you have selected the setting of the features for this segment,
press the [*] key. This will enter the data and advance automatically to the next segment of
the location. When you are in the last segment of a location and you press the [*] key to enter
the data, you will exit from that location as well. This will turn off the “Ready” LED, and will turn
on the “Armed” LED. As before, you are now ready to enter another programming location.
NX-6-EUR Installation manual
Page 27
02/07/06
LOADING FACTORY DEFAULTS
To load the factory defaults, enter the program mode using the procedure on page 24, then
type [9]-[1]-[0]-[#]. The keypad will beep 3 times to indicate that loading is in progress. The
loading takes about 6 seconds.
ENROLLING MODULES AND KEYPADS
For supervision purposes, the presence of all keypads, zone expanders, wireless receivers, and
any other modules connected to the data terminal can automatically be found and stored in
the NX-6’s memory. This allows the control panel to supervise these modules. To enroll the
modules, enter the program mode for the NX-6 control panel as described above. If necessary,
go on to program the rest of the control panel and the devices. When you exit from program
mode, the control panel will automatically enroll the devices. The enrolling process takes
about 12 seconds, during which time the “Service” LED will light up. If a module has been
enrolled but it is not detected by the control, the “Service” LED will light up.
PROGRAMMING EXAMPLE (Numerical data)
Zone 1 LED = 1
Zone 4 LED = 8
Data = 9
Zone 2 LED = 2
Zone 7 LED = 64
Data = 66
To change data
in a segment,
enter the data
followed by [*]
Enters the previous
programming “location”
NX-6-EUR Installation manual
Pressing [#] will exit
a location without
changing the data
in the current
segment
Returns to the “location”
just programmed
Page 28
Advances to the next
programming “location”
02/07/06
PROGRAMMING EXAMPLE (Feature selection data)
Location 23, segment 1
1 = Quick arm
2 = Re-exit
3 = Auto bypass
4 = Silent keypad panic
5 = Audible keypad panic
6 = Keypad auxiliary 1
7 = Keypad auxiliary 2
8 = Multi-keypad tamper
Press the key on the numeric keypad that corresponds to the feature you wish to
enable/disable. When a LED is “ON”, a feature is enabled, when “OFF” the feature is disabled.
For example, with the 1, 5 & 7 LED’s “ON”, quick arm, audible keypad panic and keypad
auxiliary 2 are enabled.
NX-6-EUR Installation manual
Page 29
02/07/06
Programming the NX-6 control panel via LCD keypad
ENTERING THE PROGRAM MODE
To enter the program mode, press [*]-[8]. The LCD screen will now prompt you for the
programming code. Next, enter the “Go To Program Code” (FACTORY DEFAULT IS 9713). If the
“Go To Program Code” is valid, the LCD screen will prompt you for the device address you wish
to program. You are now in the program mode, ready to select the module to be programmed.
Note: it is impossible to enter program mode if any partition - or the system - is armed.
SELECTING THE MODULE TO PROGRAM
Since all the modules connected to the NX-6 are programmed through the keypad, the
module you are programming should be the first entry. To program the NX-6 Control Panel,
enter [0]-[#]. The [0] is the module number of the control panel and the [#] is the entry key.
Other module entry numbers can be found in the corresponding manuals.
PROGRAMMING A LOCATION
Note: Before programming the panel, the correct country code must be set in loc. 213
Once you have entered the number of the module to be programmed, the LCD screen will
prompt you for a location number. Any location can be accessed by directly entering the
desired programming location, followed by the crosshatch (pound) [#] key. If the location you
enter is valid, the top line of the LCD screen will display the location number on the left and the
segment number on the right. The bottom line of the display will show the current data. This
data will be displayed and entered according to the type of data used (numerical, binary, or
character data). Follow the instructions below for each type of data.
NUMERICAL DATA: The top line of the display will show the current location number on the left
and the segment number on the right. The data will be displayed on the bottom line. The hex
equivalent will be shown in parenthesis. To change the data in the current location, enter the
number followed by [*]. The data will be entered and the segment will be incremented by 1.
The data for this segment will now be displayed. Continue this process until the last segment is
programmed. When you reach the last segment, the keypad will prompt you for the next
location. If you wish to exit this location before the last segment is reached, press the [#] key.
This keypress will not save the changes made to current segment, but it will exit the location.
To proceed to the next location, press the [Police] key. To return to the previous location, press
the [Fire] key. To re-enter the last location, press the [Medic] key.
BINARY DATA: The top line of the display will show the current location number on the left and
the segment number on the right. The data will be displayed on the bottom line with the
numbers 1-8 in the first 8 characters. If the number appears, this binary switch is on. If
minuses sign (-) appears where the number should be, this switch is off. Toggle the numbers
on or off, using the corresponding number digit (1 to toggle 1, 8 to toggle 8). When the
numbers are in the desired state, press the [*] key. The data will be entered and the segment
will be incremented by 1. The data for this segment will now be displayed. Continue this
process until the last segment is programmed. When you reach the last segment, the keypad
will prompt you for the next location. If you wish to exit this location before the last segment is
reached, press the [#] key. This keypress will not save the changes made to current segment,
but will exit the location. To proceed to the next location, press the [Police] key. To return to the
previous location, press the [Fire] key. To re-enter the last location, press the [Medic] key.
NX-6-EUR Installation manual
Page 30
02/07/06
CHARACTER DATA: Character data is used to enter LCD text when programming (see [*]-[9][2] feature for custom messages). Custom zone descriptions and messages are stored using
character or ASCII data types. This information is programmed using the bottom line of the
display as a text editor. Once a character location has been entered, the current data will be
displayed on the bottom line. As always, the top line will display the current location and
segment number. The five (5) function keys, as well as the ‘up’ and ‘down’ arrows to the right
of the display, are now used to edit the message before saving it back to the location storage.
An underscore (_) in the display indicates the current cursor location. To move the cursor to
the right, press the [*] key. To move the cursor to the left, press the [Cancel] key. To change
the character at the current cursor location, press the Up or Down Arrow until the desired
character is displayed. To accept this character, press the [*] key. The character will remain,
and the cursor will advance one space to the right.
You can also immediately select a character from the underlying table. By doing this you can
quickly form a word without having to scroll down all characters in the list
Follow the procedure below to select a character:
Step 1
Enter the double figured number of the wanted character of the table
below.
Confirm the character by pressing the [*] key.
Repeat steps 1 and 2 until the complete word is formed.
Confirm the word by pressing the [#] key.
Step 2
Step 3
Step 4
Key
[Stay]
[Chime]
[Exit]
[Bypass]
[Cancel]
[*]
[#]
NX-148 LIBRARY
ALARM
AREA
AUDIO
BACK
BATHROOM
BEAM
BEDROOM
BUTTON
CEILING
CLOSET
DELAY
DEN
DETECTOR
DINING
DOOR
DOWN
NX-6-EUR Installation manual
Function
Inserting spaces
Deleting characters
Access the library
Make a character or entire word flashing
Backspace
Confirm the word or character being displayed
Finished editing the line
DURESS
EAST
EMERGENCY
EXIT
EXTERIOR
FIRE
FRONT
GAME
GARAGE
GLASSBREAK
GUEST
HALL
HEAT
HOLDUP
HOUSE
INFRARED
Page 31
INSTANT
INTERIOR
JUNK
KITCHEN
LIBRARY
LIGHT
LIVING
MASTER
MICROWAVE
MOTION
NORTH
NURSERY
OFFICE
PANIC
PANTRY
PHONE
PIR
PORCH
ROOM
RUMPUS
SAFE
SENSOR
SHOCK
SHOP
SIDE
SKYLIGHT
SLIDING
SMALL
SMOKE
SOUND
SOUTH
STAIRS
STORAGE
STUDY
TAMPER
TELEVISION
TROUBLE
TV
UP
UTILITY
VAULT
WAREHOUSE
WEST
WINDOW
WING
WIRELESS
YARD
ZONE
02/07/06
ALPHANUMERIC CHARACTER TABEL
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
T
U
V
W
X
Y
Z
0
1
2
3
4
5
6
7
8
9
a
à
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
ä
ä
b
c
ç
d
e
é
è
ê
f
g
h
i
î
j
k
l
m
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
n
o
ô
ö
p
q
r
s
t
u
û
ü
v
w
x
y
z
!
”
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
#
$
&
'
(
)
*
+
,
.
/
:
;
<
=
>
.
°
EXITING THE PROGRAM MODE
When you have made all the desired changes in programming, it is time to exit the program
mode. Press the [Exit] key to exit this programming level, and go to the “Select a Module To
Program” level. If no additional modules are to be programmed, press the [Exit] key again to
exit the program mode. If there is a module to be programmed, you can select it by entering
its address, followed by the [#] key (see “Selecting the Module To Program” above). The
procedure for programming these devices is the same as for the control panel, except that the
locations will be for the module selected.
Note: the timeout for the program mode is 15 minutes.
LOADING FACTORY DEFAULTS
To load the factory defaults, enter the program mode using the above procedure, then type
[9]-[1]-[0]-[#]. The keypad will beep 3 times to show that loading is in progress. The loading
takes about 6 seconds.
ENROLLING MODULES AND KEYPADS
For supervision purposes, the presence of all keypads, zone expanders, wireless receivers, and
any other modules connected to the data terminal can automatically be found and stored in
the NX-6’s memory. This allows the control panel to supervise these modules. Note: All
modules should be connected and set to unique addresses before modules are enrolled. To
enroll the modules, enter the program mode of the NX-6 control panel as described above. If
necessary, go on to program the rest of the control panel and devices. When you exit from
program mode, the control panel will automatically enroll the devices. The enrolling process
takes about 12 seconds, during this time the “Service Screen” will be displayed. If a module
has been enrolled but it is not detected by the control, the “Service Screen” will be displayed.
NX-6-EUR Installation manual
Page 32
02/07/06
IMPORTANT REMARKS
Tamper memorization
If location 37 segment 6 option 8 is set, tamper alarm indications (zone tampers and box
tampers) can be erased by entering a valid user code.
If location 37 segment 6 option 8 is not set, tamper alarm indications (zone tampers and box
tampers) can only be erased by entering the program mode. In this case, tamper alarm
indications can only be reset by the installer.
Disabling tamper alarms in program mode
Tamper alarms (originating from zones and boxes) will be disabled during program mode. This
allows the installer to service the system without generating unwanted tamper alarms. Note
that the timeout for the program mode is 15 minutes.
Country code
The NX-6 has the ability to set different “country codes”. Each country code has specific
default settings. Before start programming the NX-6, it is important to select the country code
that is required. Once the country code has been selected, it will remain set, even after an
installer reset. When changing the country code during programming, all existing
programming will be cleared to the defaults for that country (see location 213).
Keypad tamper lockout
When this option is enabled (see location 23, segment 1), the NX-6 will disable the keypad for
60 seconds, and will communicate a tamper signal to the central station if 30 key presses are
entered without producing a valid code.
NX-6-EUR Installation manual
Page 33
02/07/06
CLC/TS 50131-3 Compliancy
In order to be compliant with the technical specification CLC/TS 50131-3 (Alarm systems – Control and
indicating equipment), the following guidelines must be taken into account :
•
Zone configuration types reporting a Hold-up alarm (event code 0) should :
- not be bypassable
- not have swinger shutdown enabled
•
All zone configuration types should be set for
- double-end-of-line configuration - 2EOL (as of loc 111 segment 3 option 2)
- fast loop response (as of loc 111 segment 3 option 1)
- swinger shutdown(*) enabled (as of loc 111 segment 3 option 6)
•
Entry/exit zone configuration types and Follower zone configuration types should be set for Force Arming
(as of loc 111 segment 2 option) in order to fulfil paragraph 12.6.6 of the technical specifications
•
The use of instant zones (zone configuration type 6) is not allowed in order to fulfil paragraph 8.2.4.3 of the
technical specifications
•
The entry time should not be more than 45 seconds (location 24)
•
The following options need to be enabled :
- keypad sounder for battery trouble (location 39 option 4)
- keypad sounder for expander trouble (location 39 option 8)
- first alarm logic (location 37 segment 6 option 4)
- log protection mode (location 37 segment 6 option 5)
- 6 digit user codes (location 41 option 1)
- keypad shutdown mode (location 41 option 5)
•
A warning device(**) should be protected by a tamper loop
•
Programmable outputs that are used for warning devices must operate for a minimum of 90 seconds and
a maximum of 15 minutes unless other requirements are demanded by local or national regulations.
(*)swinger shutdown counter (loc 38) should be set with a maximum value of 3.
(**)The BELL output should not be used to connect an internal warning device
Remarks :
All reportable events that are set will be processed. In the event of multiple events being
present simultaneously, all these events will be processed and notified.
The NX-6 provides one or more outputs to fulfill the requirements described in Table 9 of
the CLC/TS 50131-3. All options of Table 13 of the CLC/TS 50131-3 can be fulfilled.
The level of tamper protection fulfils the requirements for installations inside the
supervised premises
Indicators that share common means of annunciation will not apply any priorisation.
Maximum load taken from the AUX OUT should not exceed the values as stated in the
table below (EN-50131-6:1997 and EN50131-1:1997 table 16)
battery
NX-4
NX-6
NX-8
Max current consumpt.
77mA
96mA
105mA
Max current AUX OUT
7.2Ah
480mA
460mA
450mA
Max current AUX OUT
18Ah
570mA
560mA
550mA
NX-6-EUR Installation manual
Page 34
02/07/06
CONTROL PANEL PROGRAMMING LOCATIONS
For most routine installations, the “Quick Start” option will allow for enabling a majority of the
options available with the NX-6, when communicating in Contact ID or SIA formats and without
partitioning. The “Quick Start” locations can be identified by the symbol.
Telephone number 1
LOCATION 0 - PHONE N° 1 (20 segments, numerical data)
The first telephone number is programmed in location 0. A “14” indicates the end of the phone
number. Delays of four seconds can be programmed at any point in the phone number by
programming a “13” in the appropriate segment. The system will always wait for a dial tone,
unless the first digit of the phone number is a “13”; in this case, it will only delay. Tone (DTMF)
dialling is default. If you want pulse tone dialling, program a “15” in the segment where pulse
dialling should begin. If the entire number should be pulse dialling, program a “15” in the first
segment. Program an “11” for a “*”, and a “12” for a “#”.
Note: a zero is programmed as a “0”.
LOCATION 1 - ACCOUNT CODE FOR PHONE N° 1 (6 segments, numerical data)
Location 1 is used to program the account code that is sent when phone N°1 is dialled. A zero
in the account code is programmed as a “0”. A “10” indicates the end of the account code, so
program a “10” in the segment immediately after the last digit of the account code. If the
account code is 6 digits long, program all 6 segments.
LOCATION 2 - COMMUNICATOR FORMAT FOR PHONE N° 1 (1 segment, numerical data)
Location 2 contains the communicator format used to transmit to the receiver that is
connected to phone N°1. Consult the instructions for your central station receiver to
determine which format is compatible. Select a format from the list on the following page. If
you require a format other than those listed, review the override options described in location
18 in order to create the appropriate format. In order to create a special format, a “15” must
be programmed in location 2 in addition to the entries in location 18. If this location contains a
“0”, the built-in communicator will be disabled, and the NX-6 will function as a ‘local only’
control.
LOCATION 3 - DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE N° 1 (2 segm., numerical data)
Segment 1- Dial attempts: Location 3, segment 1 is used to enter the number of dial attempts
(1 to 15) which the communicator will make to phone N°1 before it ends the notification
process. Factory default is “8” and the communicator will make 8 attempts to the first number.
There will be a waiting time of 12 seconds between the first two dial attempts, and a
waiting time of 60 seconds between each subsequent dial attempt.
NX-6-EUR Installation manual
Page 35
02/07/06
Segment 2- Phone N° 1 backup control: Programming a “0” in segment 2 of this location will
cause the NX-6 to make the designated number of attempts to phone N°2 before setting the
“Fail To Communicate” condition and stop reporting. Programming a “1” in this segment will
cause the NX-6 to stop trying to communicate after the designated number of attempts have
been made to phone N°1. If a “2” is programmed in this segment, it will cause the NX-6 to
make the dial attempts in increments of two. The first two attempts will be made to phone
N°1, the next two attempts to phone N°2, then repeating until the total number of attempts
designated in Segment 1 is completed.
Format selections
DATA
0
1
2
3
4
5
6
7
Local
Ademco Contact ID
Ademco 4/2 Express
Reserved
Reserved
Siren Tone Format
Reserved
SIA (level 1, supporting
level 2 area modifier and
level 3 listen-in block)
8
9
Reserved
Radionics extended fast
with parity
10
11
12
Reserved
Ademco/ Silent Knight
Slow
Silent Knight 4+2 fast
13
Sescoa/Franklin Fast
14
SIA (level 1, supporting
level 3 listen-in block)
Custom format
Vocal format
XSIA (level 1, supporting
level 3 listen-in block)
XSIA (level 1, supporting
level 2 area modifier and
level 3 listen-in block)
15
16
17
18
Remark (*):
FORMAT
DESCRIPTION
Communicator is disabled
DTMF format (see appendix 1-2)
DTMF format
Siren sound, for domestic dialling*
FSK format (see appendix 1-2).
Extended event code 1800hz transmit 2300hz
handshake single round w/parity 40 PPS extended
hex capability
1900hz transmit 1400hz handshake 10 PPS double
round parity
Two-digit event code 1900hz transmit 1400hz
handshake 20 PPS double round parity
1800hz transmit 2300hz handshake 20 PPS hex
double round
FSK format (see appendix 1-2)
(See location 18)
Voice messages via NX-535, for domestic dialling*
FSK format (see appendix 1-2)
FSK format (see appendix 1-2).
The siren tone format (format 5) can be kissed off by pressing the “*” key on the telephone set
(persistent tone of 250 msec. is required).
If you want to trigger a “kiss-off” signal via a GSM, you have to take into account that this
function is network provider dependent.
Entering a valid user code on a keypad will stop the dialler when using the siren or vocal format.
NX-6-EUR Installation manual
Page 36
02/07/06
Reporting events to phone number 1
Phone N°1 has two programming locations that are used to select the events which are
reported to this phone number.
Location 4 is used to select which events are reported to phone N°1. Location 5 is used to
select which partitions are reported to phone N°1. If you do not want dual or split reporting,
use location 4 to select all events to phone N°1, and leave location 5 at the factory default of
“0”. If you want dual or split reporting, and the split is based on the event type (such as alarm,
open/close, etc.), you should use location 4 to select only those events that should be reported
to phone N°1, and you should leave location 5 at the factory default of “0”. If you want dual or
split reporting, and the split is based on partition, you should program location 4 as a “0” and
use location 5 to select those partitions that are to be reported to phone N°1. If no events are
to be reported to phone N°1, both locations should be programmed as “0”.
LOCATION 4 - EVENTS REPORTED TO PHONE N° 1 (2 segments, feature selection data)
Segment 1
Segment 2
NX-6-EUR Installation manual
1=
2=
3=
4=
5=
6=
7=
8=
Alarms
Opening and closings
Zone bypass and bypass restores
Zone trouble and trouble restores
Power fail (AC failure), low battery, power restore (AC restore) , and low
battery bestore
Bell cut, bell cut restore, telephone line restore
Test reports
Start and end programming, download complete and log full
1=
2=
3=
4=
5=
6=
7=
8=
Zone and box tamper
Auxiliary power over-current, and restore
Wireless sensor missing and restore
Wireless sensor low battery and restore
Expander trouble and restore (keypads are considered as expanders)
Fail to communicate
Alarm restore
Tamper restore
Page 37
02/07/06
LOCATION 5 - PARTITIONS REPORTED TO PHONE N° 1 (1 segment, feature selection data)
Location 5 is used when the events to be reported to a phone number are based on the
partition, regardless of the event. If you use this location, you should program location 4 as “0”.
Segment 1
1=
2=
3-8
Partition 1
Partition 2
Reserved
Telephone number 2
LOCATION 6 - PROGRAMMING PHONE N° 2 (20 segments, numerical data)
Phone N°2 is programmed in location 6. A “14” indicates the end of the phone number. Delays
of four seconds can be programmed at any point in the phone number by programming a
“13” in the appropriate segment. The system will always wait for a dial tone unless the first
digit of the phone number is a “13”; in this case, it will only delay. Tone (DTMF) dialling is
default. If you want pulse tone dialling, program a “15” in the segment where pulse dialling
should begin. If the entire number should be pulse dialling, program a “15” in the first segment.
Program an “11” for a “*”, and a “12” for a “#”.
Note: a zero is programmed as a “0”.
LOCATION 7 - ACCOUNT CODE FOR PHONE N° 2 (6 segments of numerical data)
Use location 7 to program the account code that is sent when phone N°2 is dialled. A zero in
the account code is programmed as a “0”. A “10” indicates the end of the account code, so
program a “10” in the segment immediately after the last digit of the account code. If the
account code is 6 digits long, program all 6 segments. If this location is left unprogrammed,
account code 1 will be used when the second phone number is dialled.
LOCATION 8 - COMMUNICATOR FORMAT FOR PHONE N° 2 (1 segment, numerical data)
Location 8 contains the communicator format used to transmit to the receiver that is
connected to phone N°2. Consult the instruction manual for your central station receiver in
order to determine which format is compatible, and select from the 15 formats listed on page
33. If you require a format other than those listed, review the override options described in
Location 18 to create the appropriate format. In order to create a special format, a “15” must
be programmed in location 8, in addition to the entries in location 18. If this location contains
a “0”, format 1 will be used when phone N°2 is dialled.
NX-6-EUR Installation manual
Page 38
02/07/06
LOCATION 9 - DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE N° 2 (2 segments, numerical data)
Segment 1, dial attempts: segment 1 of location 9 is used to enter the number of dial
attempts (1 to 15 attempts) that the communicator will make to phone N°2 before it ends the
notification process. Factory default is “0”, and the communicator will make the same number
of attempts as those programmed in location 3.
There will be a waiting time of 12 seconds between the first two dial attempts, and a
waiting time of 60 seconds between each subsequent dial attempt (regardless of the
number dialled).
Segment 2, phone N° 2 backup control: Programming a “0” in segment 2 of this location will
cause the NX-6 to make the designated number of attempts to phone N°1 before setting the
“fail to communicate” condition and stop reporting. Programming a “1” in this segment will
cause the NX-6 to stop trying to communicate after the designated number of attempts have
been made to phone N°2. If a “2” is programmed in this segment, it will cause the NX-6 to
make the dial attempts in increments of two. The first two attempts will be made to phone
N°2, the next two attempts to phone N°1, then repeating until the total number of attempts
designated in segment 1 is completed.
Reporting events to phone number 2
Phone N°2 can be used to back up phone N°1, or as a second receiver to multi-report or splitreport events. Phone N°2 has two programming locations that are used to select the events
that are reported to this phone number. Location 10 is used to select the events which are
reported to phone N°2, and location 11 is used to select which partitions are reported to
phone N°2. If you do not want dual or split reporting, location 10 and location 11 should be left
at the factory default of “0”. If you want multi-reporting or split reporting, and the split is based
on the event type (such as alarm, open close etc.), location 10 should be used to select only
those events that should be reported to phone N°2, and location 11 should be left at the
factory default of “0”. If you want dual or split reporting, and the split is based on partition,
then location 10 should be programmed as “0”, and location 11 should be used to select those
partitions that are to be reported to phone N°2. If no events are to be reported to phone N°2,
both locations should be at “0”.
LOCATION 10 - EVENTS REPORTED TO PHONE N° 2 (2 segments of feature selection data)
Segment 1
1=
2=
3=
4=
5=
6=
7=
8=
NX-6-EUR Installation manual
Alarms
Opening and closings
Zone bypass and bypass restores
Zone trouble and trouble restores
Power fail (AC failure), low battery, power restore (AC restore) , and low
battery restore
Bell cut, bell cut restore, telephone line restore
Test reports
Start and end programming, download complete and log full
Page 39
02/07/06
Segment 2
1=
2=
3=
4=
5=
6=
7=
8=
Zone and box tamper
Auxiliary power overcurrent, and restore
Wireless sensor missing and restore
Wireless sensor low battery and restore
Expander trouble and restore (keypads are considered as expanders)
Fail to communicate
Alarm restore
Tamper restore
LOCATION 11 - PARTITIONS REPORTED TO PHONE N° 2 (1 segment, feature selection data)
Location 11 is used when events to be reported to a phone number are based on the partition,
regardless of the event. If this location is used, location 10 should be “0”.
Segment 1
1=
2=
3-8
Partition 1
Partition 2
Reserved
Telephone number 3
LOCATION 12 - PROGRAMMING PHONE N° 3 (20 segments, numerical data)
Phone N°3 is programmed in location 12. A “14” indicates the end of the phone number.
Delays of four seconds can be programmed at any point in the phone number by
programming a “13” in the appropriate segment. The system will always wait for a dial tone
unless the first digit of the phone number is a “13”; in this case, it will only delay. Tone (DTMF)
dialling is default. If you want pulse tone dialling, program a “15” in the segment where pulse
dialling should begin. If the entire number should be pulse dialling, program a “15” in the first
segment. Program an “11” for a “*”, and a “12” for a “#”.
Note: a zero is programmed as a “0”.
LOCATION 13 - ACCOUNT CODE FOR PHONE N° 3 (6 segments, numerical data)
Use location 13 to program the account code that is sent when phone N°3 is dialled. A zero in
the account code is programmed as a “0”. A “10” indicates the end of the account code, so
program a “10” in the segment immediately after the last digit of the account code. If the
account code is 6 digits long, program all 6 segments. If location 6 is left un-programmed,
account code 1 will be used when phone N°3 is dialled.
LOCATION 14 - COMMUNICATOR FORMAT FOR PHONE N° 3 (1 segment, numerical data)
Location 14 contains the communicator format used to transmit to the receiver that is
connected to phone N°3. Consult the instruction manual for your central station receiver in
order to determine which format is compatible, and select from the 15 formats listed on page
33. If you require a format other than those listed, review the override options described in
location 18 to create the appropriate format. In order to create a special format, a “15” must
be programmed in location 14, in addition to the entries in location 18. If this location contains
a “0”, format 1 will be used when phone N°3 is dialled.
NX-6-EUR Installation manual
Page 40
02/07/06
LOCATION 15 - DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE N° 3 (2 segments, numerical data)
Segment 1, Dial Attempts: Segment 1 of location 15 is used to enter the number of dial
attempts (1 to 15) that the communicator will make to phone N°3 before it ends the
notification process. Factory default is “0”, and the communicator will make the same number
of attempts as those programmed in location 3.
There will be a waiting time of 12 seconds between the first two dial attempts, and a
waiting time of 60 seconds between each subsequent dial attempt (regardless of the
number dialled).
Segment 2, Phone # 3 Backup Control: Programming a “0” in segment 2 of this location will
cause the NX-6 to make the designated number of attempts to phone N°2 before setting the
“Fail To Communicate” condition and stop reporting. Programming a “1” in this segment will
cause the NX-6 to stop trying to communicate after the designated number of attempts have
been made to phone N°3. If a “2” is programmed in this segment, it will cause the NX-6 to
make the dial attempts in increments of two. The first two attempts will be made to phone
N°3, the next two attempts to phone N°2, then repeating until the total number of attempts
designated in segment 1 is completed.
Reporting events to phone number 3
Phone N°3 can be used as a third receiver to multi-report or split report events. Phone N°3 has
two programming locations that are used to select the events that are reported to this phone
number. Location 16 is used to select which events are reported to phone N°3, and location 17
is used to select which partitions are reported to phone N°3. If you do not want dual or split
reporting, location 16 and location 17 should be left at the factory default of “0”. If you want
multi-reporting or split reporting, and the split is based on the event type (such as alarm,
open/close, etc.), then location 16 should be used to select only those events that should be
reported to phone N°3, and location 17 should be left at the factory default of “0”. If you want
dual or split reporting, and the split is based on partition, then location 16 should be
programmed to “0” and location 17 should be used to select those partitions that are to be
reported to phone N°3. If no events are to be reported to phone N°3, both locations should be
at “0”.
NX-6-EUR Installation manual
Page 41
02/07/06
LOCATION 16 - EVENTS REPORTED TO PHONE N° 3 (2 segments, feature selection data)
Segment 1
Segment 2
1=
2=
3=
4=
5=
6=
7=
8=
Alarms
Opening and closings
Zone bypass and bypass restores
Zone trouble and trouble restores
Power fail (AC failure), low battery, power restore (AC restore), and low
battery restore
Bell cut, bell cut restore, telephone line restore
Test reports
Start and end programming, download complete and log full
1=
2=
3=
4=
5=
6=
7=
8=
Zone and box tamper
Auxiliary power overcurrent, and restore
Wireless sensor missing and restore
Wireless sensor low battery and restore
Expander trouble and restore (keypads are considered as expanders)
Fail to communicate
Alarm restore
Tamper restore
LOCATION 17 - PARTITIONS REPORTED TO PHONE N°3 (1 segment, feature selection data)
Location 17 is used when the events to be reported to a phone number are based on the
partition, regardless of the event. If this location is used, location 16 should be “0”.
Segment 1
NX-6-EUR Installation manual
1=
2=
3-8
Partition 1
Partition 2
Reserved
Page 42
02/07/06
Special formats
LOCATION 18 - CUSTOM COMMUNICATOR FORMAT (see locations 2, 8, and 14)
Segment 1
1=
2=
3=
4=
5=
6=
7=
8=
On for 1800hz transmit; Off for 1900hz
On for 2300hz handshake; Off for 1400hz
On for checksum parity; Off for double round parity
On for 2 digit event code; Off for 1 digit event code
On for extended reporting; Off for non-extended reporting
Reserved
On for 20 PPS; Off for 10 or 40 PPS
On for 10 PPS; Off for 20 or 40 PPS
Segment 2
1=
2=
3=
4=
5=
6=
7=
8=
On for pager format (no handshake required).
On for 1400/2300 handshake
Reserved
Reserved
On for Contact ID
On for SIA
On for 3 digit event code
On for DTMF
Segment 3
Reserved
Segment 4
Inter-digit time for pulse format:
The inter-digit time is the value programmed on this location, divided by the
pulse-rate (PPS) of the programmed format. This is programmed in a binary
way: in order to program the value “10”, options 2 and 4 must be selected,
for value “5”, options 1 and 3 must be selected.
Ex: when the value 10 is programmed on segment 4 and a pulse format of
20 PPS is used, the inter-digit time is 10/20 = 0.5 sec.
NX-6-EUR Installation manual
Page 43
02/07/06
Download parameters
LOCATION 19 - DOWNLOAD ACCESS CODE (8 segments, numerical data)
Location 19 contains the eight-digit access code that the NX-6 must receive from the
downloading software before the panel will allow downloading. The factory default code is
84800000.
LOCATION 20 - NUMBER OF RINGS TO ANSWER (1 segment, numerical data)
Location 20 contains the number of rings to answer for a download. Enter a number from “0”
(disabled) to “15”. Factory default is “8”, so the NX-6 will answer after 8 rings.
LOCATION 21 - DOWNLOAD CONTROL (1 segment, feature selection data)
Location 21 contains the feature selections to control download sessions. The following
features can be enabled or disabled using this location (see the feature definitions on pages 511).
Segment 1
1=
2=
3=
4=
5=
6=
7=
8=
On: enables two call answering machine defeat
Reserved
On: requires call-back before download session
Shutdown (can only be viewed from the keypad; must be changed by
downloading)
On: locks all local programming. (can only be viewed from the keypad;
must be changed by downloading)
On: locks programming of all locations associated with the
communicator (can only be viewed from the keypad; must be
changed by downloading)
On: locks out download section. (If “On”, locations 19-22 cannot be
viewed from the keypad; can only be viewed from the keypad when
“Off”.)
On: enables call-back at auto test interval
LOCATION 22 - DOWNLOAD CALL BACK NUMBER (20 segments, numerical data)
If a telephone number is programmed into this location, and “Require Call-back” is enabled in
location 21, the control panel will hang up for approximately 36 seconds (ensuring that the
calling party has disconnected), and then call back. The system will always wait for a dial tone
unless the first digit of the phone number is a “13”; in this case, it will only delay. Tone (DTMF)
dialling is default. If you want pulse tone dialling, program a “15” in the segment where pulse
dialling should begin. If the entire number should be pulse dialling, program a “15” in the first
segment. Four-second delays can be obtained anywhere in the sequence by programming a
“13” in the appropriate delay location.
Note: a zero is programmed as a “0”.
WARNING: YOU SHOULD ALWAYS CHECK THAT THE CALLBACK PHONE NUMBER IS
ACCURATE BEFORE DISCONNECTING.
NX-6-EUR Installation manual
Page 44
02/07/06
Feature and report selections (for partition 1)
LOCATION 23 - PARTITION 1, FEATURE AND REPORT SELECTIONS (5 segments, feature
selection data)
Location 23 is used to enable certain features that the user can access or see from the keypad
of the system. In addition, certain communicator reports are enabled in location 23. Each of
these features can be enabled by partition. For additional partition information, see locations
88-109.
If the feature selection location for any partition is left blank, that partition will use this location
for the feature selection.
This location contains 5 segments of 8 features each (see the feature definitions).
Segment 1
1=
2=
3=
4=
5=
6=
7=
8=
On: enables the quick arm feature (for exit and stay mode)
On: enables the re-exit feature
On: enables the automatic bypass feature (of interior zones)
On: enables the silent keypad panic feature (overrides the audible
panic selection)
On: enables the audible keypad panic feature
On: enables the keypad Aux 1 feature (FIRE)
On: enables the keypad Aux 2 feature (MEDICAL)
On: enables the keypad multiple code attempt tamper feature
(keypad lockout)
Segment 2
1=
2=
3=
4=
5=
6=
7=
8=
On: enables the LED extinguish feature
On: enables the require code for bypassing feature
On: enables the zone bypassed sounder alert feature
On: enables the AC power/low battery sounder alert feature
On: enables bypass toggle
On: enables silent auto arm
On: enables the automatic instant feature (of entry/exit zones)
On: enables final set door
Segment 3
1=
2=
3=
4=
5=
6=
7=
8=
On: enables opening and closing reports
On: enables zone bypass reporting
On: enables zone restore reporting
On: enables zone trouble reporting
On: enables zone tamper reporting
On: enables the cancel reporting
On: enables the recent closing report
On: enables the exit error report
Segment 4
1=
2=
3=
On: enables late to close / early to open reporting
On: enables auto arm in STAY mode
On: enables instant NIGHT mode (applies to NX-1208E / NX-1248E: no
toggle)
On: tamper when sensor lost if armed
On : enables instant STAY mode (toggle)
On: arming allowed with tamper memory / communication failure/
expander trouble
On : arming allowed with battery trouble
On: keyswitch zone arms in STAY mode
4=
5=
6=
7=
8=
NX-6-EUR Installation manual
Page 45
02/07/06
Segment 5
1=
2=
3=
4=
5=
6=
7=
8=
On: Disables auto-bypassing of force armable zones at the end of the
exit delay
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Entry/Exit timers
LOCATION 24 - ENTRY / EXIT TIMERS (6 segments, numerical data)
Location 24 is used to program the entry/exit times. There are 2 separate entry/exit times.
Segment 1
Entry time 1
Segment 2
Exit time 1
Segment 3
Entry time 2
Segment 4
Exit time 2
Segment 5
Segment 6
Reserved
Reserved
NX-6-EUR Installation manual
Page 46
This is the entry time that will be used when a delay 1
zone type initiates an entry delay.
Valid entries are 10-255 seconds.
This is the exit time that will be used for all zones
designated as delay 1.
Valid entries are 10-255 seconds.
This is the entry time that will be used when a delay 2
zone type initiates an entry delay.
Valid entries are 10-255 seconds.
This is the exit time that will be used for all zones
designated as delay 2.
Valid entries are 10-255 seconds.
02/07/06
Zone configurations and partition selection
DEFAULT ZONE CONFIGURATIONS
Zones can be programmed to be one of thirty different zone configurations (zone types). The
default zone configurations are listed below. Programming locations 110-169 can customise
all zone configurations.
DATA
R conf.
DESCRIPTION OF DEFAULT CONFIGURATION
1
1
2
2
3
2
4
2
5
2
6
2
7
2
8
1
9
2
10
1
11
2
DAY ZONE
Instant when system is armed; trouble zone when system is disarmed. A day zone will only
work if programmed for single end-of-line resistor.
24 HOUR AUDIBLE
Creates an instant yelping siren alarm regardless of the arming state of the control panel.
This zone type is not abortable. This zone can be bypassed.
ENTRY/EXIT DELAY 1
A trip will start entry delay 1. Absence of a trip during the exit delay will enable the Automatic
Bypass or Instant mode, if so programmed.
FOLLOWER (WITH AUTO- BYPASS DISABLED)
This zone will be instant when the system is armed and no entry or exit delays are being
timed. It is delayed during entry and exit delay times. This zone will not bypass automatically,
even if enabled in segment 1 of location 23.
INTERIOR FOLLOWER (WITH AUTO- BYPASS ENABLED)
This zone will be instant when the system is armed and no entry or exit delay is being timed.
It is delayed during entry and exit delay times. This zone will bypass automatically, if enabled
in segment 1 of location 23.
INSTANT
This zone creates an instant alarm whenever it is tripped and the armed LED is on.
24 HOUR SILENT
Creates an instant silent alarm regardless of the arming state of the control panel. It will not
display on the keypad. This zone is not abortable, but can be bypassed.
FIRE
This zone will light up the fire LED and sound the steady siren each time the zone is shorted.
It will also rapidly flash the fire LED, indicating trouble if the zone is open. This zone cannot be
bypassed.
ENTRY/EXIT DELAY 2
A trip will start entry delay 2. Absence of a trip during the exit delay will enable the automatic
bypass or instant mode, if so programmed.
24 HOUR AUDIBLE SUPERVISED
Creates an instant audible alarm, regardless of the arming state of the control panel. It will
display on the keypad (e.g. flashing zone LED’s, and changed READY LED). This zone is not
abortable and cannot be bypassed.
MOMENTARY KEYSWITCH ZONE
This zone type will arm and disarm the partition or partitions of the control panel where it is
resident, every time the zone is shorted. Keyswitch arming will report as user 99. This zone
type can only belong to 1 partition.
NX-6-EUR Installation manual
Page 47
02/07/06
12
2
13
2
14
2
15
2
16
2
17
2
18
2
19
2
20
2
21
2
22
2
23
2
INTERIOR FOLLOWER WITH “CROSS ZONE” ENABLED
This zone will be instant when the system is armed and no entry or exit delay is being timed.
It is delayed during entry and exit delay times. If a “Cross Zone” is not being timed, it will start
a “Cross Zone” timer. If a “Cross Zone” is being timed, it will create an instant alarm. This zone
will bypass automatically, when enabled in segment 1 of location 23.
INSTANT ENTRY GUARD
This zone creates an instant alarm whenever it is tripped and the stay/instant LED is off. It will
start an entry delay time 2 if it is tripped, provided that the system is armed and the
stay/instant LED is on.
ENTRY/EXIT DELAY 1 WITH GROUP BYPASS ENABLED
A trip will start entry delay 1. This zone will bypass when the “Group Bypass” command is
entered at the keypad. Absence of a trip during exit delay will enable the automatic bypass
or instant mode, if so programmed.
INTERIOR FOLLOWER WITH GROUP BYPASS ENABLED
This zone will be instant when the system is armed and no entry or exit delays are being
timed. It is delayed during entry/exit delay times. This zone will bypass when the “Group
Bypass” command is entered at the keypad. This zone will bypass automatically, if enabled in
segment 1 of location 23.
INSTANT WITH GROUP BYPASS ENABLED
This zone creates an instant alarm whenever it is tripped and the armed LED is on. This zone
will bypass when the “Group Bypass” command is entered at the keypad
MAINTAINED KEYSWITCH
This zone type will arm the partition or partitions of the control panel where it is resident, as
long as the zone is shorted. This zone type will disarm the partition or partitions of the control
where it is resident, as long as the zone is open. Keyswitch arming will report as user 99.
ENTRY/EXIT DELAY 1 FORCE ARMABLE
A trip will start entry delay 1. Absence of a trip during exit delay will enable the automatic
bypass or instant mode, if so programmed. This zone is force armable (see feature definitions
pages 5-11).
ENTRY/EXIT DELAY 2 FORCE ARMABLE
A trip will start entry delay 2. Absence of a trip during exit delay will enable the automatic
bypass or instant mode, if so programmed. This zone is force armable (see feature
definitions, pages 5-11).
ENTRY/EXIT DELAY 1 WITH CHIME ENABLED
A trip will start entry delay 1. Absence of a trip during exit delay will enable the automatic
bypass or instant mode, if so programmed. When the control panel is disarmed and the
chime mode has been set, this zone will act as a chime zone.
TECHNICAL ALARM, SUPERVISED, AUDIBLE
Any trip on a technical zone creates an audible alarm, regardless of the arming state of the
control panel. This zone can be bypassed.
TECHNICAL ALARM, SUPERVISED, SILENCE
Any trip on a silent technical zone creates a silent alarm, regardless of the arming state of
the control panel. Only the transmitter will be activated. This zone can be bypassed.
INTERIOR INSTANT ZONE
This zone creates an instant alarm whenever it is tripped during the arming state of the
control panel. This zone will bypass automatically, if enabled in segment 1 of location 23, or
when this system is armed in the “Stay” mode.
NX-6-EUR Installation manual
Page 48
02/07/06
24
2
25
2
26
2
27
2
28
2
29
30
2
INSTANT ZONE WITH CHIME ENABLED
A trip will create an alarm when the system is armed. When the control panel is disarmed
and the chime mode has been set, this zone will act as a chime zone.
FOLLOWER ZONE WITH CHIME ACTIVATED
This zone will be instant when the system is armed and no entry or exit delays are being
timed. It is delayed during entry and exit delay times. This zone will not bypass automatically,
even if enabled in segment 1 of location 23. When the control panel is disarmed and the
chime mode has been set, this zone will act as a chime zone.
24 HOUR, AUDIBLE, SUPERVISED, LOCAL
Creates an instant audible alarm, regardless of the arming state of the control panel. It will
display on the keypad (e.g. flashing zone LED’s, and changed READY LED). This zonetype will
NOT be reported.
INSTANT ZONE FORCE ARMABLE
This zone creates an instant alarm whenever the system is armed. This zone is force armable
(see feature definitions, pages 5-11).
INSTANT ZONE ACTIVITY MONITOR ENABLED
This zone creates an instant alarm whenever the system is armed. It will send a report if the
zone activity time is reached without a change of state (see location 40, segment 11 and
locations 110-169).
INSTANT ZONE WITH END OF LINE RESISTOR DEFEAT
This zone creates an instant alarm whenever the system is armed. When the loop is closed,
the zone is ready. Opening of the loop means a faulted zone (see locations 110-169).
24 HOUR, MEDICAL, AUDIBLE, SUPERVISED
Creates an instant audible alarm, regardless of the arming state of the control panel. It will
display on the keypad (e.g. flashing zone LED’s, and changed READY LED). A medical report
will be sent to the CMS.
Note: all zone configurations are programmed for double end of line resistor
configuration, except for DAY ZONE, FIRE, 24H AUDIBLE SUPERVISED and END OF LINE
RESISTOR DEFEAT.
NX-6-EUR Installation manual
Page 49
02/07/06
LOCATION 25 - ZONES 1-8 CONFIGURATION GROUP (8 segments, numerical data)
Location 25 contains the configuration group (zone type) for zones 1-8. Segment 1 is for zone
1, and segment 8 is for zone 8. You will find the default configurations in the table above.
LOCATION 26 - PARTITION SELECT, ZONES 1-8 (8 segments, feature selection data)
Location 26 is used to select the partition(s) in which zones 1 - 8 reside. A zone may reside in
any combination of the 2 partitions. If a burglary zone resides in more than 1 partition, that
zone will only be active when all the partitions in which it is resident in are armed. A zone that
resides in more than 1 partition will be reported to its lowest partition number. Location 26 has
8 segments. Segment 1 corresponds to zone 1, and segment 8 corresponds to zone 8.
Segment 1-8
1=
2=
3-8
Partition 1
Partition 2
Reserved
LOCATION 27 - ZONES 9-16 CONFIGURATION GROUP (8 segments, numerical data)
Location 27 contains the configuration group (zone type) for zones 9 -16. Segment 1 is for
zone 9, and segment 8 is for zone 16. You will find the default configurations in the table
above.
LOCATION 28 - PARTITION SELECT, ZONES 9-16 (8 segments, feature selection data)
Location 28 is used to select the partition(s) in which zones 9-16 reside. A zone may reside in
any combination of the 2 partitions. If a burglary zone resides in more than 1 partition, that
zone will only be active when all the partitions are armed. A zone that resides in more than 1
partition will be reported to its lowest partition. Location 28 has 8 segments. Segment 1
corresponds to zone 9 and Segment 8 corresponds to zone 16.
Segment 1-8
1=
2=
3-8
Partition 1
Partition 2
Reserved
LOCATION 29-36 - RESERVED
NX-6-EUR Installation manual
Page 50
02/07/06
General options
LOCATION 37 - SIREN AND SYSTEM SUPERVISION (7 segments, feature selection data)
Location 37 is used to enable various system feature and reporting options.
Segment 1
1=
2=
3=
4=
5=
6=
7=
8=
On: if siren sounds for “Telephone Line Cut” when armed
On: if siren sounds for “Telephone Line Cut” when disarmed
On: if siren blast at arming (pulse)
On: if siren blast at exit expiration (pulse)
On: if siren blast at closing kiss-off (pulse)
On: if siren sounds during a “Cross Zone” verification time
On: if siren sounds for a zone or box tamper
On: if siren blasts 1 time for keyswitch or wireless arming; 2 times for
disarming
Segment 2
1=
8=
On: if siren driver should be a voltage output. Off: if on-board siren
driver is enabled
On: if sirens sound for expander trouble
On: for zones to restore immediately. Off: for zones to restore only
when the siren is off or disarmed
On: if dynamic battery test is performed at arming. Off: if dynamic
battery test is performed at disarming (See location 40)
On: if battery missing test is performed every 12 seconds
On: if manual bell test is performed during [*]-[4]-[4] test function
On: if manual communicator test is performed during [*]-[4]-[4] test
function
On: if Box Tamper terminals on the control panel are enabled
Segment 3
1=
2=
3=
4=
5=
6=
7=
8=
On: if box tamper report is enabled
On: if AC fail reporting is enabled
On: if low battery reporting is enabled
On: if Aux. power overcurrent report is enabled
On: if siren supervision report is enabled
On: if restore telephone line cut report is enabled
On: A+B Alarm. Off: cross-zoning
On: if expander trouble reporting is enabled
Segment 4
1=
2=
3=
4=
5=
6=
7=
8=
On: if fail to communicate report is enabled
On: if log full report is enabled
On: if autotest report is enabled
On: if start/end programming report is enabled
On: if end download report is enabled
On: if sensor low battery report is enabled
On: if sensor missing report is enabled
On: if autotest report is enabled ONLY when the system is armed
2=
3=
4=
5=
6=
7=
NX-6-EUR Installation manual
Page 51
02/07/06
Segment 5
1=
2=
3=
4=
5=
6=
7=
8=
On: enable lost clock service light
On: enables Zone Doubling (requires NX-200 Zone Doubling Kit).
On: disables on-board zones
On: will allow two trips on same cross-zone to activate an alarm
On: will not allow zones that are force armed to report bypass
On: enables silent exit option
On: activate “first disarm reporting” - “last arm reporting” for
partitions
On: switch “summer/wintertime” and vice versa
Segment 6
1=
2=
3=
4=
5=
6=
7=
8=
On: enable 2 wire smoke sensors (AUX4 - COM)
On: Use internal crystal for clock
On: zone activity monitor in hours (not in days)
On: enables first alarm logic
On: enables log protection
On : disables Clean Me report
On : siren output is steady in case of fire alarm
On: valid user code will reset tamper memory
Segment 7
1=
2=
3-8
On: dial via GSM when phone line trouble (*)
On: Exit Error limited to Entry/Exit delay 1
Reserved
(*)Note: This feature is only used when the NX-7002 is enrolled by the panel
and if the NX-7002 is used as backup (GSM voice channel) for the PSTN dialler
of the panel. Also telephone line monitoring needs to be enabled in location
40. Do not use this feature as the only backup feature of the PSTN dialler but
use this in addition with the standard backup options as described in the NX7002 manual.
LOCATION 38 - SWINGER SHUTDOWN COUNT
Location 38 contains the number of trips on a zone before that zone will be automatically
bypassed. From 0 to 255. Refer to the feature definitions.
LOCATION 39 - KEYPAD SOUNDER CONTROL (1 segment, feature selection data)
Segment 1
1=
2=
3=
4=
5=
6=
7=
8=
NX-6-EUR Installation manual
On: if keypad sounds for “Telephone Line Cut” when the system is
armed
On: if keypad sounds for “Telephone Line Cut” when disarmed
On: if keypad sounds for an AC power failure
On: if keypad sounds when a low battery is detected
On: if keypad sounds during cross zone trip time
On: if keypad sounds for zone and box tampers
On: if keypad sounds for Emergency keys
On: if keypad sounds for Expander trouble
Page 52
02/07/06
LOCATION 40 - SYSTEM TIMERS (14 segments, numerical data)
Location 40 contains the duration of various system timing functions. Example: If you want the
duration of the dynamic battery test to be 30 minutes, you should program [3]- [0]-[*] in
segment 1 of this location. The [3]-[0] is the number of minutes; the [*] stores the data, and
moves to the next segment of this location.
Segment 1
Segment 2
Segment 3
Segment 4
Segment 5
Segment 6
Segment 7
Segment 8
Segment 9
Segment 10
Segment 11
Segment 12
Segment 13
Segment 14
Dynamic battery test duration in minutes, 0-255 minutes (“0” = no test)
AC fail report delay in minutes, 0-255 minutes
Power up delay in seconds, 0-60 seconds (“0” = no power up delay)
Siren time in minutes, 1-255 minutes
Telephone line cut delay in seconds, 0-255 seconds (“0” = no telephone line
monitoring enabled)
Cross zone time in minutes, 0-255 (“0” = no cross zoning)
Chime time in 50 msec. (1/ 20th second) increments from 0-12 seconds (“0”
= follows zone 255 latched)
Dial delay in seconds, 0-255 seconds (0 no abort delay)
Fire alarm verification time in seconds, 120-255 seconds (“0” = no fire
alarm verification). Values less than 120 sec. are considered as 120 sec.
Listen-in time in seconds, 0-255 (“ 0” = no listen-in time)
Zone activity monitor feature timed in hours/days, 0-255 (“0” = disabled)
Auto arming warning timer, 1-255 minutes
Auto arming retry timer, 1-255 minutes
Programming Timeout, 1-255 minutes (“0” = 15 minutes)
LOCATION 41 - CODE REQUIREMENTS (1 segment, feature data)
Segment 1
1=
2=
3=
4=
5=
6=
7=
8=
On: enables the 6-digit code option. If 6-digit option is enabled, all
arm/disarm codes and the “Go To Program Code” are 6 digits. If this
option is enabled, the default user 1 code is [1]-[2]-[3]-[4]-[5]-[6].
NOTE: IF YOU ENABLE THIS OPTION, VERIFY THAT THE “GO TO
PROGRAM CODE” IS A SIX-DIGIT CODE BEFORE YOU EXIT FROM
PROGRAMMING
On: requires code entry for [*]-[9]-[8] (perform callback download) and
[*]-[9]-[9] (answer incoming call for download) functions
On: enables Auto Cancel / Abort
Reserved
On: keypad shutdown mode
On: user authorisation to enter program mode
On: codes 16 and 17 are guard codes
Reserved
LOCATION 42 - GO TO PROGRAM CODE (6 segments, numerical data)
Location 42 contains the “Go To Program Code”. This location contains a code with either 4 or
6 digits. If the 6-digit code option is enabled in Location 41, THIS CODE MUST CONTAIN SIX (6)
DIGITS. If this option is not enabled in location 41, the last 2 segments (digits) will be ignored.
With the NX-6 disarmed, the “Go To Program Code” can be used to enter the Program Mode.
NX-6-EUR Installation manual
Page 53
02/07/06
LOCATION 43 - GO TO PROGRAM CODE PARTITION AND AUTHORIZATION (2 segments, feature selection data)
The “Go To Program Code” can be used as a standard arm/disarm code. When using the code
to arm or disarm, the user ID is 255. (It is not possible to change this code in the run mode).
Segment 1
Segment 2
1=
2=
3=
4=
5=
6=
7=
8=
Reserved
On: enables “Go To Program Code” as an arm only code
On: enables “Go To Program Code” as an arm only, after closing
On: enables “Go To Program Code” as a master arm/disarm code (can
change user codes)
On: enables “Go To Program Code” as an arm/disarm code
On: enables “Go To Program Code” to bypass zones
On: enables “Go To Program Code” opening and closing reports
Reserved
1=
2=
3-8
On: enables the “Go To Program Code” for partition 1
On: enables the “Go To Program Code” for partition 2
Reserved
LOCATION 44 - DURESS CODE (6 segments, numerical data)
Location 43 contains the “Duress” code. This Location contains either 4 or 6 digits. If the 6-digit
code option is enabled in location 41, THIS CODE MUST CONTAIN SIX (6) DIGITS. If the 6-digit
option is not enabled in location 41, the last 2 digits will be ignored. If the duress code is
programmed, it will work for all partitions.
NX-6-EUR Installation manual
Page 54
02/07/06
Programming the outputs
LOCATION 45 - AUXILIARY OUTPUT 1-4 PARTITION SELECTION (4 segments, feature selection data)
Location 45 is used to select the partition(s) in which the events must occur before the
output(s) will activate. Location 45 has 4 segments. Segment 1 corresponds to output 1, and
segment 2 corresponds to output 2, segments 3 and 4 correspond to outputs 3 and 4.
Segment 1
(Auxiliary 1)
1= Partition #1
2= Partition #2
3-8 Reserved
Segment 2
(Auxiliary 2)
1= Partition #1
2= Partition #2
3-8 Reserved
Segment 3
(Auxiliary)
1= Partition #1
2= Partition #2
3-8 Reserved
Segment 4
(Auxiliary)
1= Partition #1
2= Partition #2
3-8 Reserved
LOCATION 46 - AUXILIARY OUTPUT 1-4 SPECIAL TIMING (4 segments, feature selection data)
Location 46 contains special timing feature activation for the 4 auxiliary outputs (relays).
Segment 1 corresponds to output 1, segment 2 corresponds to output 2. Segments 3 and 4
correspond to outputs 3-4.
Segment 1-4
1=
2=
3=
4=
5=
6=
7=
8=
NX-6-EUR Installation manual
On: if output should be timed in minutes; Off: if timed in seconds
On: if output should latch; Off: if output should be timed
On: if output should stop timing when the code is entered; Off: if
the output should continue to time when the code is entered
On: if output should only activate between the closing and
opening time in locations 52 and 53
On: if output should only activate between the opening and
closing time in locations 52 and 53
On: if output should be inverted (0 volts going to 12 volts when
activated)
Reserved
Reserved
Page 55
02/07/06
LOCATION 47 - AUXILIARY OUTPUT 1, EVENT AND TIME (2 segments, numerical data)
Segment 1
Segment 2
Use the chart below to select the event that will activate auxiliary output 1
(relay 1)
Program the timing from 0-255 (minutes or seconds, depending on the
data programmed in segment 1, location 46). Programming a “0” makes
the output follow the event
LOCATION 48 - AUXILIARY OUTPUT 2, EVENT AND TIME (2 segments, numerical data)
Segment 1
Segment 2
Use the chart below to select the event that will activate auxiliary output 2
(relay 2)
Program the timing from 0-255 (minutes or seconds, depending on the
data programmed in segment 2, location 46). Programming a “0” makes
the output follow the event
LOCATION 49- AUXILIARY OUTPUT 3, EVENT AND TIME (2 segments, numerical data)
Segment 1
Segment 2
Use the chart below to select the event that will activate auxiliary output 3
Program the timing from 0-255 (minutes or seconds, depending on the
data programmed in segment 3, location 46). Programming a “0” makes
the output follow the event
LOCATION 50- AUXILIARY OUTPUT 4, EVENT AND TIME (2 segments, numerical data)
Segment 1
Segment 2
NX-6-EUR Installation manual
Use the chart below to select the event that will activate auxiliary output 4
Program the timing from 0-255 (minutes or seconds, depending on the
data programmed in segment 4, location 46). Programming a “0” makes
the output follow the event
Page 56
02/07/06
AUXILIARY OUTPUT EVENT SELECTION
DATA
EVENT
DATA
EVENT
0
1
2
3
4
5
6
7
8
9
10
Burglary alarm
Fire alarm
24 hour alarm
Trouble alarm
Tamper alarm
Yelping siren
Steady siren
Any siren
Any bypass
AC fail
Low battery
30
31
32
33
34
35
36
37
38
39
40
11
12
13
14
15
Duress
Aux 1 keypad (fire alarm)
Aux 2 keypad (medical alarm)
Panic keypad
Keypad tamper
41
42
43
44
45
16
17
18
Autotest
Alarm memory (solid)
Entry
48♦
Open period
Closed period
Listen-in
Line seizure
Reserved
Fail to communicate
Telephone line fault
Program mode
Download in process
Smoke power
Short circuit (overcurrent on 12
Vdc)
Box tamper
Siren tamper
Any open
Any short
Any fault (open/short on non-fire
zone)
Any alarm
Beeping keypad
Code entry (see note below)
19
Exit
49♣
Key FOB function 1
20
Entry or exit
Key FOB function 2
21
22
23
24
Armed state
Disarmed state
Ready
Not ready
50♣
51
52
53
54
25
26
27
28
29
Fire
Fire trouble
Chime
Expander trouble
Dynamic battery test time
46
47
55
56
57
58
Always ON
Autoarm warning time
Any siren when in away mode
Progress of entry/exit (follows
keypad buzzer)
Auxiliary communication failure
Radio test
Any siren when armed in any mode
Alarm memory (pulsating)
Note :
♦
♣
NX-6-EUR Installation manual
When event 48 is programmed, it is possible to program a user code authorisation to
select the output(s), which a particular code will activate. When LED 8 is on for an
authorisation, then LED’s -24 will correspond to the code that activates outputs 1 - 2
respectively. (See “Programming the LED Keypads”)
Events 49 and 50 require one or more of the following to operate: wireless receivers or
cardreaders.
If set to follow condition, these events will be 1 second.
Page 57
02/07/06
Setup for auto-test, auto-arm and opening/closing times
LOCATION 51 - AUTOTEST CONTROL (4 segments, numerical data)
Segment 1
Segment 2
Segment 3
Segment 4
Program a “1” if the interval is to be in hours; program a “0” for days. Add
a “2” to suppress the daily test or a “3” to suppress the hourly test if any
report has been sent
Program the autotest interval from 1-255 hours/days
Program the autotest report hour in 24 hour format (if the interval is in
hours, this segment Is ignored)
Program the autotest report time, number of minutes after the hour
LOCATION 52 - OPENING TIME/AUTOMATIC DISARMING TIME (2 segments, numerical data)
Location 52 contains the time (in 24 hour format) when the NX-6 will enable the disarm
capability for codes designated as ‘arm only after closing’. This time is only valid on those days
programmed in location 54. This is also the time when the panel will automatic disarm.
Note: Opening time must be earlier than closing time so that autoarm, Aux. outputs, or code
authorisation can function properly.
Segment 1
Segment 2
Program the hour of the opening time
Program the minutes after the hour of the opening time
LOCATION 53 - CLOSING TIME/AUTOMATIC ARMING TIME (2 segments, numerical data)
Location 53 contains the time (in 24 hour format) when the NX-6 will disable the disarm
capability for codes designated as ‘arm only after closing’. This is also the time when the
automatic arming sequence will begin (if this option is enabled in location 55).
Note: Opening time must be earlier than closing time so that auto arm, Aux. outputs, or code
authorisation can function properly.
Segment 1
Segment 2
NX-6-EUR Installation manual
Program the hour of the closing / auto arm time
Program the minutes after the hour of the closing / auto arm time
Page 58
02/07/06
LOCATION 54 - DAYS OF THE WEEK “ARM ONLY AFTER CLOSE WINDOW” CODES FUNCTION IN PARTITIONS 1
AND 2 (2 Segments, feature selection data)
Location 54 selects the days of the week on which each partition is open. On these days, “arm
only after close window” codes will be able to arm and disarm during “open window”. On days
not selected here, “arm only after close window” codes will not disarm (see locations 52 and
53 for the opening and closing times for the open days).
Segment 1-2
1=
2=
3=
4=
5=
6=
7=
8=
“Arm only after close window” will arm/disarm on Sunday
“Arm only after close window” will arm/disarm on Monday
“Arm only after close window” will arm/disarm on Tuesday
“Arm only after close window” will arm/disarm on Wednesday
“Arm only after close window” will arm/disarm on Thursday
“Arm only after close window” will arm/disarm on Friday
“Arm only after close window” will arm/disarm on Saturday
Reserved
LOCATION 55 - DAYS OF THE WEEK FOR AUTO ARMING IN PARTITIONS 1 AND 2 (2 Segments, feature selection
data)
Location 55 selects the days on which each partition will auto-arm. Segment 1 is for partition
1, and segment 2 is for partition 2. If a zone is faulted before the warning timer and stays
faulted during the warning timer, the zone will automatically be bypassed. If the zone restores,
it will be unbypassed and active in the system.
Segment 1-2
NX-6-EUR Installation manual
1=
2=
3=
4=
5=
6=
7=
8=
Auto arming on Sunday
Auto arming on Monday
Auto arming on Tuesday
Auto arming on Wednesday
Auto arming on Thursday
Auto arming on Friday
Auto arming on Saturday
Disable retry timer
Page 59
02/07/06
Communicator codes for slow speed formats only
LOCATIONS 56-83 ARE ONLY USED WHEN REPORTING EVENTS TO A PAGER, OR WHEN USING A
SLOW FORMAT SUCH AS 4+2. WHEN USING CONTACT ID OR SIA, THERE IS NO NEED TO
PROGRAM THESE LOCATIONS.
LOCATION 56 - RESTORE COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (2 segments, numerical data)
Location 56 contains the event code for any zone “Alarm” and “Restore” for a 4+2 and 3+1
format. For a 4+2 format, the digit programmed in this location will be sent as the tens digit of
the alarm event code. As ones digit, the zone number (1-F) will be reported (e.g. zone 16 = 1,
zone 10 = A).
This location contains 8 segments. Any segment left as “0” will follow the segment 1 selection.
Segments 1-2 contain the alarm code for zone 1 to 16.
Segments 5-6 contain the restore code for zone 1 to 16.
Segment 1
Segment 2
Segment 3
Segment 4
Segment 5
Segment 6
Segment 7
Segment 8
Zones 1-15, “Alarm Code”
Zone 16, “Alarm Code”
Reserved
Reserved
Zones 1-15, “Restore Code”
Zone 16, “Restore Code”
Reserved
Reserved
LOCATION 57 - BYPASS COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (8 segments, numerical data)
Location 57 contains the event code for a zone “Bypass” with a 4+2 and 3+1 format. For a 4+2
format, the digit programmed in this location will be sent as the tens digit. As ones digit, the
zone number (1-F) will be reported (e.g. zone 16 = 1, zone 10 = A).
This location contains 8 segments. Any segment left as “0” will follow the segment 1 selection.
Segments 1-2 contain the bypass code per bank of 15 zones. Segments 3-8 are reserved.
When unbypassing a zone, the restore code of location 56 will be used.
Segment 1
Segment 2
Segment 3-8
NX-6-EUR Installation manual
Zones 1-15, “Bypass Code”
Zone 16 “Bypass Code”
Reserved
Page 60
02/07/06
LOCATION 58 - TAMPER COMMUNICATOR CODE, SLOW SPEED FORMATS (8 segments, numerical data)
Location 58 contains the event code for a zone “Tamper” with a 4+2 and 3+1 format. For a 4+2
format, the digit programmed in this location will be sent as the tens digit. As ones digit, the
zone number (1-F) will be reported (e.g. zone 16 = 1, zone 10 = A).
Any segment left as “0” will follow the segment 1 selection.
Segments 1-2 contain the tamper code per bank of 15 zones.
Segments 3-8 are reserved.
To report a restore, the restore code of location 56 will be used.
Segment 1
Segment 2
Segment 3-8
Zones 1-15, “Tamper Code”
Zone 16 “Tamper Code”
Reserved
LOCATION 59 - TROUBLE COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (8 segments, numerical data)
Location 59 contains the event code for a zone “Trouble” with a 4+2 and 3+1 format. For the
4+2 format, the digit programmed in this location will be sent as the tens digit. As ones digit,
the zone number (1-F) will be reported (e.g. zone 16 = 1, zone 10 = A).
Any segment left as “0” will follow segment 1 selection.
Segments 1-2 contain the trouble code per bank of 15 zones.
Segments 3-8 are reserved.
To report a restore, the restore code of location 56 will be used.
Segment 1
Segment 2
Zones 1-15, “Trouble Code”
Zone 16 “Trouble Code”
Segment 3-8
Reserved
NX-6-EUR Installation manual
Page 61
02/07/06
LOCATION 60 - SENSOR LOW BATTERY COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (8 segments,
numerical data)
Location 60 contains the event code for a zone “Sensor Low Battery” for a 4+2 and 3+1
format. For a 4+2 format, the digit programmed in this location will be sent as the tens digit. As
ones digit, the zone number (1-F) will be reported (e.g. zone 16 = 1, zone 10 = A).
Any segment left as “0” will follow the segment 1 selection.
Segments 1-2 contain the sensor low battery code per bank of 15 zones.
Segments 3-8 are reserved.
To report a restore, the restore code of location 56 will be used.
Segment 1
Segment 2
Segment 3-8
Zones 1-15, “Sensor Low battery Code”
Zone 16 “Sensor Low Battery Code”
Reserved
LOCATION 61 - SENSOR MISSING COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (8 segments, numerical
data)
Location 61 contains the event code for a zone “Sensor-missing” for a 4+2 and 3+1 format. For
a 4+2 format, the digit programmed in this location will be sent as the tens digit. As ones digit,
the zone number (1-F) will be reported (e.g. zone 16 = 1, zone 10 = A).
Any segment left as “0” will follow the segment 1 selection.
Segments 1-2 contain the sensor missing code per bank of 15 zones.
Segments 3-8 are reserved.
To report a restore, the restore code of location 56 will be used.
Segment 1
Segment 2
Segment 3-8
Zones 1-15, “Sensor Missing Code”
Zone 16 “Sensor Missing Code”
Reserved
LOCATION 62 - DURESS COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (2 segments, numerical data)
Location 62 contains the tens and ones digits that will be sent for a 4+2 and 3+1 format if the
Duress code is enabled in location 44. Segment 1 contains the tens digit, and segment 2
contains the ones digit.
For a 3+1 format, only the segment 1 digit (tens) will be sent.
NX-6-EUR Installation manual
Page 62
02/07/06
LOCATION 63 - KEYPAD AUXILIARY 1 COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (2 segments,
numerical data)
Location 63 contains the tens and ones digits that will be sent for a 4+2 and 3+1 format if the
keypad “Auxiliary 1” (FIRE) is enabled in the partition feature selection. Segment 1 contains the
tens digit; segment 2 contains the ones digit. For a 3+1 format, only the segment 1 digit (tens)
will be sent.
LOCATION 64 - KEYPAD AUXILIARY 2 COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (2 segments,
numerical data)
Location 64 contains the tens and ones digits that will be sent for a 4+2 and 3+1 format if the
keypad “Auxiliary 2” (MEDICAL) is enabled in the partition feature selection. Segment 1
contains the tens digit; segment 2 contains the ones digit. For a 3+1 format, only the segment
1 digit (tens) will be sent.
LOCATION 65 - KEYPAD PANIC COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (2 segments, numerical
data)
Location 65 contains the tens and ones digits that will be sent for a 4+2 and 3+1 format if the
keypad “Panic” is enabled in the partition feature selection. Segment 1 contains the tens digit,
and segment 2 contains the ones digit. For a 3+1 format, only the segment 1 digit (tens) will be
sent.
LOCATION 66 - KEYPAD MULTIPLE CODE ENTRY TAMPER COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
(2 segments, numerical data)
Location 66 contains the tens and ones digits that will be sent for a 4+2 and 3+1 format if the
keypad “Multiple Code Entry” (Tamper) is enabled in the partition feature selection. Segment 1
contains the tens digit, and segment 2 contains the ones digit. For a 3+1 format, only the
segment 1 digit (tens) will be sent.
LOCATION 67 - BOX TAMPER / BOX TAMPER RESTORE COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (4
segments, numerical data)
Location 67 contains the tens and ones digits that will be sent for a 4+2 and 3+1 format if the
“Box Tamper” feature is enabled in location 37. Segment 1 contains the tens digit of the “Box
Tamper”. Segment 2 contains the ones digit of the “Box Tamper”. Segment 3 contains the tens
digit of the “Box Tamper Restore”. Segment 4 contains the ones digit of the “Box Tamper
Restore”. For a 3+1 format, only the segment 1 resp. segment 3 digit (tens) will be sent.
NX-6-EUR Installation manual
Page 63
02/07/06
LOCATION 68 - AC FAIL / AC FAIL RESTORE COMMUNICATOR CODES, SLOW SPEED FORMATS ONLY (4 segments,
numerical data)
Location 68 contains the tens and ones digits for a 4+2 and 3+1 format that will be sent if “AC
Fail Reporting” is enabled. Segment 1 contains the tens digit of the “AC Fail Reporting”.
Segment 2 contains the ones digit of the “AC Fail Reporting”. Segment 3 contains the tens digit
of the “AC Fail Restore”. Segment 4 contains the ones digit of the “AC Fail Restore”. For a 3+1
format, only the segment 1 resp. segment 3 digit (tens) will be sent.
LOCATION 69 - LOW BATTERY / LOW BATTERY RESTORE COMMUNICATOR CODES, SLOW SPEED FORMATS ONLY
(4 segments, numerical data)
Location 69 contains the tens and ones digits for a 4+2 and 3+1 format that will be sent if
“Low Battery Reporting” is enabled. Segment 1 contains the tens digit of the “Low Battery
Reporting”. Segment 2 contains the ones digit of the “Low Battery Reporting”. Segment 3
contains the tens digit of the “Low Battery Restore”. Segment 4 contains the ones digit of the
“Low Battery Restore”. For a 3+1 format, only the segment 1 digit resp. segment 3 digit (tens)
will be sent.
LOCATION 70 - AUX POWER OVERCURRENT/ AUX POWER OVERCURRENT RESTORE COMMUNICATOR CODES,
SLOW SPEED FORMATS ONLY (4 segments, numerical data)
Location 70 contains the tens and ones digits for a 4+2 and 3+1 format that will be sent if “Aux
Power Overcurrent Reporting” is enabled. Segment 1 contains the tens digit of the “Aux Power
Overcurrent Reporting”. Segment 2 contains the ones digit of the “Aux Power Overcurrent
Reporting”. Segment 3 contains the tens digit of the “Aux Power Overcurrent Restore”.
Segment 4 contains the ones digit of the “Aux Power Overcurrent Restore”. For a 3+1 format,
only the segment 1 resp. segment 3 digit (tens) will be sent.
LOCATION 71 - BELL TAMPER AND BELL TAMPER RESTORE COMMUNICATOR CODES, SLOW SPEED FORMATS
ONLY (4 segments, numerical data)
Location 71 contains the tens and ones digits for a 4+2 and 3+1 format that will be sent if
siren supervision reporting is enabled. Segment 1 contains the tens digit of the “Bell Tamper
Reporting”. Segment 2 contains the ones digit of the “Bell Tamper Reporting”. Segment 3
contains the tens digit of the “Bell Tamper Restore”. Segment 4 contains the ones digit of the
“Bell Tamper Restore”. For a 3+1 format, only the segment 1 resp. segment 3 digit (tens) will be
sent.
LOCATION 72 - TELEPHONE LINE CUT RESTORE COMMUNICATOR CODES, SLOW SPEED FORMATS ONLY (4
segments, numerical data)
Location 72 contains the tens and ones digits for a 4+2 and 3+1 format that will be sent if
“Telephone Line Cut Restore Reporting” is enabled. Segment 1 and segment 2 are reserved.
Segment 3 contains the tens digit of the “Telephone Line Cut Restore”. Segment 4 contains the
ones digit of the “Telephone Line Cut Restore”.
For a 3+1 format, only the segment 3 digit (tens) will be sent.
NX-6-EUR Installation manual
Page 64
02/07/06
LOCATION 73 - Reserved
LOCATION 74 - EXPANDER TROUBLE AND EXPANDER TROUBLE RESTORE COMMUNICATOR CODES, SLOW
SPEED FORMATS ONLY (4 segments, numerical data)
Location 74 contains the tens and ones digits for a 4+2 and 3+1 format that will be sent if
“Expander Trouble Reporting” is enabled. Segment 1 contains the tens digit of the “Expander
Trouble Reporting”. Segment 2 contains the ones digit of the “Expander Trouble Reporting”.
Segment 3 contains the tens digit of the “Expander Trouble Restore”. Segment 4 contains the
ones digit of the “Expander Trouble Restore”. For a 3+1 format, only the segment 1 digit resp.
segment 3 digit (tens) will be sent.
LOCATION 75 - FAIL TO COMMUNICATE COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (2 segments,
numerical data)
Location 75 contains the tens and ones digits for a 4+2 and 3+1 format that will be sent if the
“Fail To Communicate Reporting” is enabled. Segment 1 contains the tens digit, and segment 2
contains the ones digit. For a 3+1 format, only the segment 1 digit (tens) will be sent.
LOCATION 76 - LOG FULL COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (2 segments, numerical data)
Location 76 contains the tens and ones digits for a 4+2 and 3+1 format if the “Log Full
Reporting” is enabled. Segment 1 contains the tens digit, and segment 2 contains the ones
digit.
For a 3+1 format, only the segment 1 digit (tens) will be sent.
LOCATION 77 - OPENING COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (8 segments, numerical data)
Location 77 contains the tens digit for a 4+2 and 3+1 format if “Opening Reporting” is enabled.
For a 4+2 format, the digit programmed in this section will be sent as the tens digit of the
alarm event code. As ones digit, the user number (1-F) will be reported (e.g. code 16 = 1, code
40 = A). This location contains 8 segments. Any segment left as “0” will follow the segment 1
selection. Segments 1-3 contain the opening code per bank of 15 codes. Segments 4-8 are
reserved.
If you need to report openings and closings with a unique code per user, Contact ID or SIA
format must be used.
Segment 1
Segment 2
Segment 3
Segment 4-8
NX-6-EUR Installation manual
Codes 1-15, “Opening Code”
Codes 16-30, “Opening Code”
Codes 31-40, “Opening Code”
Reserved
Page 65
02/07/06
LOCATION 78 - CLOSING COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (8 segments, numerical data)
Location 78 contains the tens digit for a 4+2 and 3+1 format if “Closing Reporting” is enabled.
For a 4+2 format, the digit programmed in this section will be sent as the tens digit of the
alarm event code. As ones digit, the user number (1-F) will be reported (e.g. code 16 = 1, code
40 = A). This location contains 8 segments. Any segment left as “0” will follow the segment 1
selection. Segments 1-3 contain the closing code per bank of 15 codes. Segments 4-8 are
reserved.
If you need to report openings and closings with a unique code per user, Contact ID or SIA
format must be used.
Segment 1
Segment 2
Segment 3
Segment 4-8
Codes 1-15, “Closing Code”
Codes 16-30, “Closing Code”
Codes 31-40, “Closing Code”
Reserved
LOCATION 79 - AUTOTEST COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (2 segments, numerical data)
Location 79 contains the tens and ones digits for a 4+2 and 3+1 format that will be sent if
“Autotest” or “Manual Test” is enabled. Segment 1 contains the tens digit, and segment 2
contains the ones digit.
For a 3+1 format, only the segment 1 digit (tens) will be sent.
LOCATION 80 - RECENT CLOSING AND EXIT ERROR COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (2
segments, numerical data)
Location 80 contains the tens digit for a 4+2 and 3+1 format that will be sent if “Recent
Closing” and/or “Exit Error Reporting” are enabled. Segment 1 contains the tens digit for the
“Recent Closing Reporting”. Segment 2 contains the digit for the “Exit Error Reporting”. As ones
digit, the user number (1-F) of the user who closed, will be sent. If you need to report Recent
Closings and Exit Errors with a unique code per user, Contact ID or SIA format must be used.
LOCATION 81 - START PROGRAM AND END PROGRAM COMMUNICATOR CODES, SLOW SPEED FORMATS ONLY (4
segments, numerical data)
Location 81 contains the tens and ones digits for a 4+2 and 3+1 format that will be sent if
“Start / End Programming Reporting” is enabled. Segment 1 contains the tens digit of the
“Start Program Reporting”. Segment 2 contains the ones digit of the “Start Program Reporting”.
Segment 3 contains the tens digit of the “End Program Reporting”. Segment 4 contains the
ones digit of the “End Program Reporting”.
For a 3+1 format, only the segment 1 digit resp. segment 3 digit (tens) will be sent.
NX-6-EUR Installation manual
Page 66
02/07/06
LOCATION 82 - END DOWNLOAD COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (4 segments,
numerical data)
Location 82 contains the tens and ones digits for a 4+2 and 3+1 format that will be sent if “End
Downloading Reporting” is enabled. Segment 1 and 2 are reserved. Segment 3 contains the
tens digit of the “End Download Reporting”. Segment 4 contains the ones digit of the “End
Download Reporting”. Note: A start download report will be sent to the internal event log.
For a 3+1 format, only the segment 1 digit (tens) will be sent.
LOCATION 83 - CANCEL COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (1 segments, numerical data)
Location 83 contains the tens digit for a 4+2 and 3+1format that will be sent if “Cancel
Reporting” is enabled. Segment 1 contains the tens digit for the “Cancel Communicator
Reporting”. As ones digit, the user number (1-F) of the user who cancelled, will be sent. If you
need to report Cancels with a unique code per user, Contact ID or SIA format must be used.
LOCATIONS 84-87 - RESERVED
NX-6-EUR Installation manual
Page 67
02/07/06
Programming partition parameters
LOCATIONS 88-109 ARE FOR PROGRAMMING DIFFERENT ACCOUNT CODES AND/OR
FEATURES FOR EACH PARTITION. IF A LOCATION IS LEFT UNPROGRAMMED, THE FEATURE
FOR PARTITION 1 AND THE ACCOUNT CODE FOR THE PHONE NUMBER WILL BE USED
LOCATION 88 - ACCOUNT CODE FOR PARTITION 1 (6 segments, numerical data)
Location 88 contains the account code that is sent when partition 1 is reported. If location 88
is left unprogrammed (all “10”s), then the account code corresponding to the phone number
that is dialled will be used. If the account code is less than six digits, program a “10” in the
segment immediately after the last digit of the account code. If the account code is 6 digits
long, program all 6 segments.
LOCATION 89 - ACCOUNT CODE FOR PARTITION 2 (6 segments, numerical data)
Location 89 contains the account code that is sent when partition 2 is reported. If location 89
is left unprogrammed (all “10”s), then the account code corresponding to the phone number
that is dialled will be used. If the account code is less than six digits, program a “10” in the
segment immediately after the last digit of the account code. If the account code is 6 digits
long, program all 6 segments.
LOCATION 90 - PARTITION 2 FEATURE AND REPORTING SELECTIONS (5 segments, feature selection data)
Location 90 is used to enable certain features that the user can access or see from the keypad
of the system. In addition, certain communicator reports are enabled in this location. Each of
these features can be enabled by partition. This location contains 5 segments, with eight
possible features per segment. Refer to location 23 for the feature selections. If all the
segments are blank (nothing enabled), the features for partition 1 will be used.
LOCATION 91 - PARTITION 2 ENTRY EXIT TIMERS (6 segments, numerical data)
Location 91 is used to enter the entry and exit times, in seconds. There are 2 separate entry
and exit times. Valid entries are 10-255 seconds. If all the segments are “0”, the entry and exit
times for partition 1 will be used.
Segment 1
Entry time 1
Segment 2
Exit time 1
Segment 3
Entry time 2
Segment 4
Exit time 2
Segment 5
Segment 6
Reserved
Reserved
Entry time that will be used when a delay 1 zone type
initiates an entry delay
Exit time that will be used for all zones designated as
delay 1
Entry time that will be used when a delay 2 zone type
initiates an entry delay
Exit time that will be used for all zones designated as
delay 2
LOCATION 92-109 - RESERVED
NX-6-EUR Installation manual
Page 68
02/07/06
Programming zone configuration groups
LOCATIONS 110-169 ARE USED TO CHANGE THE ZONE CONFIGURATIONS AS LISTED IN THE
TABLE ON PAGES 44-46. THESE LOCATIONS ARE CONSIDERED AS ADVANCED
PROGRAMMING, AND THEY SHOULD ONLY BE CHANGED IF YOU HAVE A THOROUGH
UNDERSTANDING OF THE OPERATION OF EACH BIT.
LOCATION 110 - CONFIGURATION GROUP 1 ALARM EVENT CODE (1 segment, numerical data)
Location 110 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 111 - CONFIGURATION GROUP 1 CHARACTERISTIC SELECT (5 segments, feature selection data)
Segment 1
1=
2=
3=
4=
5=
6=
7=
8=
Fire (turn on if this is a fire zone)
24 hour (turn on for non-fire 24 hour zones)
Keyswitch zone (normally open switch)
Follower (turn on for burglary zones that are Instant during non-entry
times)
Delay 1 zone (follows timer 1 Entry and Exit times)
Delay 2 zone (follows timer 2 Entry and Exit times)
Interior (turn on if this zone should Automatically Bypass or Bypass
for Stay Arming)
Local only (turn on if this zone should not be reported)
Remark: for a maintained keyswitch (ON/OFF), program both
“keyswitch” and “local”
Segment 2
1=
2=
3=
4=
5=
6=
7=
8=
On: if configuration group will beep the keypad for alarm
On: if configuration group will sound the yelping siren for alarm
On: if configuration group will sound the steady siren for alarm
On: if configuration group will chime
On: if configuration group can be bypassed
On: if configuration group is included in the group shunt
On: if configuration group is force armable
On: if configuration group is entry guard
Segment 3
1=
2=
On: enables Fast Loop Response. (50mS) - Off= 500mS
On: enables Double End Of Line Tamper zone. (Mainly used for
tamper on wireless zones)
On: enables Trouble Reporting zone. (Day zone and Fire zones)
On: if configuration group is a Cross Zone
On: enables Dialler Delay zone. (See location 40)
On: if configuration group will use swinger shutdown. (See location
38)
On: enables Restore reporting
On: enables Listen-In. (See location 40)
3=
4=
5=
6=
7=
8=
NX-6-EUR Installation manual
Page 69
02/07/06
Segment 4
1=
2=
4=
5=
6=
7=
8=
On: enables zone activity monitor
On: enables end of line resistor defeat on non-fire/non-keyswitch
zones
On : enables zone to act as request to exit input / disables for alarm
activation
On : enables zone to act as access entry point (Door Shunt)(*)
Reserved
Reserved
Reserved
Reserved
1-8
Reserved
3=
Segment 5
(*)Note :
…
Refer to NX-17xxE door control installer manual. Do not enable this segment unless
configured with Door Control.
LOCATION 112 - CONFIGURATION GROUP 2 ALARM EVENT CODE (1 segment, numerical data)
Location 112 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 113 - CONFIGURATION GROUP 2 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 114 - CONFIGURATION GROUP 3 ALARM EVENT CODE (1 segment, numerical data)
Location 114 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 115 - CONFIGURATION GROUP 3 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 116 - CONFIGURATION GROUP 4 ALARM EVENT CODE (1 segment, numerical data)
Location 116 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm. This location is not used for slow speed formats (like 4+2 and 3+1). This location
may also contain the alarm report code for the Robofon format (value 00-99).
NX-6-EUR Installation manual
Page 70
02/07/06
LOCATION 117 - CONFIGURATION GROUP 4 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 118 - CONFIGURATION GROUP 5 ALARM EVENT CODE (1 segment, numerical data)
Location 118 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 119 - CONFIGURATION GROUP 5 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 120 - CONFIGURATION GROUP 6 ALARM EVENT CODE (1 segment, numerical data)
Location 120 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 121 - CONFIGURATION GROUP 6 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 122 - CONFIGURATION GROUP 7 ALARM EVENT CODE (1 segment, numerical data)
Location 122 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 123 - CONFIGURATION GROUP 7 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
NX-6-EUR Installation manual
Page 71
02/07/06
LOCATION 124 - CONFIGURATION GROUP 8 ALARM EVENT CODE (1 segment, numerical data)
Location 124 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 125 - CONFIGURATION GROUP 8 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 126 - CONFIGURATION GROUP 9 ALARM EVENT CODE (1 segment, numerical data)
Location 126 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 127 - CONFIGURATION GROUP 9 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 128 - CONFIGURATION GROUP 10 ALARM EVENT CODE (1 segment, numerical data)
Location 128 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 129 - CONFIGURATION GROUP 10 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 130 - CONFIGURATION GROUP 11 ALARM EVENT CODE (1 segment, numerical data)
Location 130 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
NX-6-EUR Installation manual
Page 72
02/07/06
LOCATION 131 - CONFIGURATION GROUP 11 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 132 - CONFIGURATION GROUP 12 ALARM EVENT CODE (1 segment, numerical data)
Location 132 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 133 - CONFIGURATION GROUP 12 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 134 - CONFIGURATION GROUP 13 ALARM EVENT CODE (1 segment, numerical data)
Location 134 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 135 - CONFIGURATION GROUP 13 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 136 - CONFIGURATION GROUP 14 ALARM EVENT CODE (1 segment, numerical data)
Location 136 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 137 - CONFIGURATION GROUP 14 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
NX-6-EUR Installation manual
Page 73
02/07/06
LOCATION 138 - CONFIGURATION GROUP 15 ALARM EVENT CODE (1 segment, numerical data)
Location 138 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 139 - CONFIGURATION GROUP 15 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 140 - CONFIGURATION GROUP 16 ALARM EVENT CODE (1 segment, numerical data)
Location 140 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 141 - CONFIGURATION GROUP 16 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 142 - CONFIGURATION GROUP 17 ALARM EVENT CODE (1 segment, numerical data)
Location 142 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 143 - CONFIGURATION GROUP 17 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 144 - CONFIGURATION GROUP 18 ALARM EVENT CODE (1 segment, numerical data)
Location 144 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
NX-6-EUR Installation manual
Page 74
02/07/06
LOCATION 145 - CONFIGURATION GROUP 18 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 146 - CONFIGURATION GROUP 19 ALARM EVENT CODE (1 segment, numerical data)
Location 146 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 147 - CONFIGURATION GROUP 19 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 148 - CONFIGURATION GROUP 20 ALARM EVENT CODE (1 segment, numerical data)
Location 148 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 149 - CONFIGURATION GROUP 20 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 150 - CONFIGURATION GROUP 21 ALARM EVENT CODE (1 segment, numerical data)
Location 150 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 151 - CONFIGURATION GROUP 21 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
NX-6-EUR Installation manual
Page 75
02/07/06
LOCATION 152 - CONFIGURATION GROUP 22 ALARM EVENT CODE (1 segment, numerical data)
Location 152 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 153 - CONFIGURATION GROUP 22 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 154 - CONFIGURATION GROUP 23 ALARM EVENT CODE (1 segment, numerical data)
Location 154 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 155 - CONFIGURATION GROUP 23 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 156 - CONFIGURATION GROUP 24 ALARM EVENT CODE (1 segment, numerical data)
Location 156 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 157 - CONFIGURATION GROUP 24 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 158 - CONFIGURATION GROUP 25 ALARM EVENT CODE (1 segment, numerical data)
Location 158 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 159 - CONFIGURATION GROUP 25 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
NX-6-EUR Installation manual
Page 76
02/07/06
LOCATION 160 - CONFIGURATION GROUP 26 ALARM EVENT CODE (1 segment, numerical data)
Location 160 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 161 - CONFIGURATION GROUP 26 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 162 - CONFIGURATION GROUP 27 ALARM EVENT CODE (1 segment, numerical data)
Location 162 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 163 - CONFIGURATION GROUP 27 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 164 - CONFIGURATION GROUP 28 ALARM EVENT CODE (1 segment, numerical data)
Location 164 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 165 - CONFIGURATION GROUP 28 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
NX-6-EUR Installation manual
Page 77
02/07/06
LOCATION 166 - CONFIGURATION GROUP 29 ALARM EVENT CODE (1 segment, numerical data)
Location 166 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 167 - CONFIGURATION GROUP 29 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATION 168 - CONFIGURATION GROUP 30 ALARM EVENT CODE (1 segment, numerical data)
Location 168 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 169 - CONFIGURATION GROUP 30 CHARACTERISTIC SELECT (5 segments, feature selection data)
Use the “Configuration Group Characteristic Selections” described in Location 111.
LOCATIONS 170-205 - RESERVED
LOCATION 206 – AUTO DISARM DAY SELECTOR (2 segments, feature selection data)
Location 206 selects which days each partition will auto disarm. Segment 1 is for partition 1
and segment 8 is for partition 8.
Segment 1-2
NX-6-EUR Installation manual
1=
2=
3=
4=
5=
6=
7=
8=
Auto disarming on Sunday
Auto disarming on Monday
Auto disarming on Tuesday
Auto disarming on Wednesday
Auto disarming on Thursday
Auto disarming on Friday
Auto disarming on Saturday
Reserved
Page 78
02/07/06
LOCATIONS 207-211 - RESERVED
LOCATION 212 – PROGRAMMING THE LCD KEYPAD ADDRESS (1 segment, numerical data)
When using the XSIA dialler format, the system requires at least 1 LCD keypad. The panel will
get the zone descriptions from the first language from that LCD keypad which has the address
defined in location 212. If your system has an LCD keypad it is recommended that it will be
placed in location 1 keypad 1. This will allow location 212 to be left at the factory default. If the
LCD keypad is selected as something other than partition 1 / keypad 1, program the
appropriate address in location 212. Select the address from the location chart.
Keypad
1
2
3
4
5
6
7
8
Part 1
192
200
208
216
224
232
240
248
Part 2
193
201
209
217
225
233
241
249
LOCATION 213 – PROGRAMMING THE COUNTRY CODE (1 segment, numerical data)
The NX-6 has the ability to set different “country codes”. Each country code has specific
default settings. Before start programming the NX-6, it is important to select the country code
that is required (see table below). Once the country code has been selected, it will remain set,
even after an installer reset. When changing the country code during programming, all
existing programming will be cleared to the defaults for that country.
Code
0
1
2
3
4
5
6
7
8
9
10
50
NX-6-EUR Installation manual
Country
No country (default)
Holland
Belgium / Poland
Sweden
Italy
Spain
Greece
South Africa
Israel
Reserved
Turkey
US
Page 79
02/07/06
NX-6 PROGRAMMING WORKSHEETS
(Factory defaults for NX-6-EUR (BEL/POL) are in bold italic text)
LOC
PG
0
33
PHONE 1
1
33
PHONE 1, ACCOUNT CODE
2
33
PHONE 1, REPORTING FORMAT
0
3
33
PHONE 1, DIAL ATTEMPTS
BACKUP CONTROL
8
0
4
35
5
DESCRIPTION
DEFAULT
14-14-14-14-14-14-14-14-14-14-1414-14-14-14-14-14-14-14-14
10 – 10 – 10 – 10 – 10 – 10
PHONE 1, SELECTING EVENTS TO REPORT TO PHONE 1
Segment 1 (Circle Numbers To Program)
Segment 2 (Circle Numbers To Program)
1
Alarms
1
Tampers (zones and box)
2
Open/Close
2
Short Circuit
3
Bypass
3
Sensor Lost
4
Zone Trouble
4
Sensor Low Battery
5
Power Trouble (AC Failure or Low Batt.)
5
Expander Trouble (incl. keypad)
6
Siren & Telephone Fault
6
Failure To Communicate
7
Test Reports
7
Alarm Restore
8
Program, Download, & Log Full
8
Tamper Restore
36
PHONE 1, SELECTING WHICH PARTITIONS REPORT TO PHONE 1
Segment 1 (Circle Numbers To Program)
1
Partition 1
2
Partition 2
14-14-14-14-14-14-14-14-14-14-1414-14-14-14-14-14-14-14-14
6
36
PHONE 2
7
36
PHONE 2, ACCOUNT CODE
8
36
PHONE 2, REPORTING FORMAT
0
9
37
PHONE 2, DIAL ATTEMPTS
BACKUP CONTROL
8
0
10
37
11
PROGRAMMING DATA
10 – 10 – 10 – 10 – 10 – 10
PHONE 2, SELECTING EVENTS TO REPORT TO PHONE 2
Segment 1 (Circle Numbers To Program)
Segment 2 (Circle Numbers To Program)
1
Alarms
1
Tampers (zones and box)
2
Open/Close
2
Short Circuit
3
Bypass
3
Sensor Lost
4
Zone Trouble
4
Sensor Low Battery
5
Power Trouble (AC Failure or Low Batt.)
5
Expander Trouble (incl. keypad)
6
Siren & Telephone Fault
6
Failure To Communicate
7
Test Reports
7
Alarm Restore
8
Program, Download, & Log Full
8
Tamper Restore
38
PHONE 2, SELECTING WHICH PARTITIONS REPORT TO PHONE 2
Segment 1 (Circle Numbers To Program)
1
Partition 1
2
Partition 2
NX-6-EUR Installation manual
Page 80
02/07/06
14-14-14-14-14-14-14-14-14-14-1414-14-14-14-14-14-14-14-14
12
38
PHONE 3
13
38
PHONE 3, ACCOUNT CODE
14
38
PHONE 3, REPORTING FORMAT
0
15
39
PHONE 3, DIAL ATTEMPTS
BACKUP CONTROL
8
0
16
40
17
18
10 – 10 – 10 – 10 – 10 – 10
PHONE 3, SELECTING EVENTS TO REPORT TO PHONE 3
Segment 1 (Circle Numbers To Program)
Segment 2 (Circle Numbers To Program)
1
Alarms
1
Tampers (zones and box)
2
Open/Close
2
Short Circuit
3
Bypass
3
Sensor Lost
4
Zone Trouble
4
Sensor Low Battery
5
Power Trouble (AC Failure or Low Batt.)
5
Expander Trouble (incl. keypad)
6
Siren & Telephone Fault
6
Failure To Communicate
7
Test Reports
7
Alarm Restore
8
Program, Download, & Log Full
8
Tamper Restore
40
PHONE 3, SELECTING WHICH PARTITIONS REPORT TO PHONE 3
Segment 1 (Circle Numbers To Program)
1
Partition 1
2
Partition 2
41
FORMAT OVERRIDE
Segment 2 (Circle Numbers To Program)
Segment 1 (Circle Numbers To Program)
1
On = 1800hz transmit; Off = 1900hz
1
2
On = 2300hz handshake; Off = 1400hz
2
On = pager format (no handshake required)
On = 1400/2300 handshake
3
On =chksum parity; Off = double round par.
3
Reserved
4
On = 2 digit event code; Off = 1 digit code
4
Reserved
5
On = extended reporting; Off =non-extended
5
On = Contact ID
6
Reserved
6
On = SIA
7
On = 20 PPS; Off = 10 or 40 PPS
7
On = 3 digit event code
8
On = 10 PPS; Off = 20 or 40 PPS
Segment 3 RESERVED
8
On = DTMF
Segment 4 INTER-DIGIT TIME
19
42
DOWNLOAD ACCESS CODE
20
42
RINGS TO ANSWER DOWNLOAD
21
42
42
8-4-8-0-0-0-0-0
8
DOWNLOAD CONTROL
Segment 1 (Circle Numbers To Program)
1
22
0-0-0-0
Enables two-call answering machine defeat
2
Reserved
3
Requires callback before downloading
4
Shutdown control panel
5
Lock out local programming
6
Lock out communicator programming
7
Lock out download section
8
Enables callback at autotest interval
14-14-14-14-14-14-14-14-14-14-1414-14-14-14-14-14-14-14-14
CALLBACK PHONE NUMBER
NX-6-EUR Installation manual
Page 81
02/07/06
23
43
PARTITION 1, FEATURE SELECTION
Segment 1
Segment 2
1
Quick Arm
1
LED extinguish enable
2
Re-Exit
2
3
Auto Bypass (interior)
4
Silent Panic
3
4
5
Audible Panic
5
Segment 3
Require user code for bypassing zones
1
2
Open/Close
Bypass
Bypass sounder alert
AC power/ low battery sounder alert
3
Restore
4
Trouble
Enables bypass toggle
5
Tamper
6
Auxiliary 1
6
Enables silent auto arm
6
Cancel
7
8
Auxiliary 2
Multi Keypress Tamper
7
Enables automatic instant (entry/exit)
7
Recent Closing
8
Final set door
8
Exit Error
Segment 5
Segment 4
24
44
1
Late to close/early to open
1
2
Auto arm in stay mode
2
Disables auto bypassing of force armable zones
Reserved
3
Enables instant night
3
Reserved
4
Tamper when sensor lost if armed
4
Reserved
5
6
Enables instant stay toggle
Arming with tamper mem./ comm. failure
5
Reserved
6
Reserved
7
Arming with battery trouble
7
Reserved
8
Keyswitch zone arms in stay mode
8
Reserved
ENTRY/EXIT TIMERS
Segment 1 (Entry Time 1)
30
Segment 2 (Exit Time 1)
60
Segment 3 (Entry Time 2)
30
Segment 4 (Exit Time 2)
60
Reserved
0
Reserved
0
3-5-6-6-6-6-6-6
25
48
ZONES 1-8, CONFIGURATION GROUPS
26
48
ZONES 1-8, PARTITION SELECTION (Segment 1=Zone 1 thru Segment 8=Zone 8)
Segments
Partition 1
1
1
2
1
3
1
4
1
5
1
Partition 2
2
2
2
2
2
6
1
2
6-6-6-6-6-6-6-6
27
48
ZONES 9-16, CONFIGURATION GROUPS
28
48
ZONES 9-16, PARTITION SELECTION (Segment 1=Zone 9 thru Segment 8=Zone 16)
29-36
48
7
1
8
1
2
2
Segments
Partition 1
1
1
2
1
3
1
4
1
5
1
6
1
7
1
8
1
Partition 2
2
2
2
2
2
2
2
2
Reserved
NX-6-EUR Installation manual
Page 82
02/07/06
37
49
SIREN AND SYSTEM SUPERVISION
Segment 1 (Circle Numbers To Program)
1
Siren sounds for telephone line cut while armed
2
Siren sounds for telephone line cut while disarmed
3
Siren blast at arming (pulse)
4
Siren blast at exit delay expiration (pulse)
5
Siren blast at closing kissoff (pulse)
6
7
Siren sounds during a cross zone verification time
Siren sounds for a tamper
8
Siren blast once for keyswitch arming, twice for disarming
Segment 2 (Circle Numbers To Program)
1
Convert siren driver to voltage out
2
Siren sounds for expander trouble
3
Zones to always restore
4
5
Dynamic battery test performed upon arming
Battery missing test performed every 12 seconds
6
Manual bell test performed during [*]-[4]-[4] test function
7
8
Manual communicator test performed during [*]-[4]-[4] test function
Box tamper enabled
1
Box Tamper report enabled
2
AC Fail report enabled
Segment 3 (Circle Numbers To Program)
3
Low Battery report enabled
4
Auxiliary power overcurrent report enabled
5
Siren supervision report enabled
6
Restore Telephone Line Cut report enabled
7
8
A+B alarm
Expander trouble report enabled
1
Failure To Communicate report enabled
2
Log Full report enabled
3
4
Autotest report enabled
Start and End Programming report enabled
Segment 4 (Circle Numbers To Program)
5
End Download report enabled
6
Sensor Low Battery report enabled
7
Sensor Missing report enabled
8
Autotest report enabled ONLY when system is armed
Segment 5 (Circle Numbers To Program)
1
Lost Clock service LED enable
2
Enable zone doubling
3
Disable on-board zones
4
Enable two trips on the same cross-zone to activate the alarm
5
6
Disable bypass reports for force armed zones
Silent exit
7
Activate “first disarm reporting” - “last arm reporting” for partitions
8
Automatic switch summer/wintertime and vice versa
Segment 6 (Circle Numbers To Program)
1
Enable 2 wire smoke sensors
2
Use internal crystal for clock
3
Enable zone activity in hours (not in days)
4
Enable first alarm logic
5
Enable log protection
6
7
Disable Clean Me report
Siren output is steady in case of fire alarm
8
User code will reset tamper memory
NX-6-EUR Installation manual
Page 83
02/07/06
37
Segment 7 (Circle Numbers To Program)
49
1
2
1-8
dial via GSM when phone line trouble (only when NX-7002 is used)
Exit Error limited to Entry/Exit delay 1
Reserved
38
50
SWINGER COUNTDOWN COUNT
39
50
KEYPAD SOUNDER CONTROL
0
Segment 1 (Circle Numbers To Program)
40
41
51
51
1
Keypad sounds for Telephone Line Cut when in the Armed state
2
Keypad sounds for Telephone Line Cut when in the Disarmed state
3
Keypad sounds upon AC Power Failure
4
Keypad sounds upon Low Battery Detection
5
6
Keypad sounds during Cross Zone Trip Time
Keypad sounds for Tamper Alarm
7
Keypad sounds for Emergency keys
8
Keypad sounds for Expander Trouble
SYSTEM TIMERS
Segment 1
Dynamic Battery Test duration (0-255 minutes)
Segment 2
AC Failure report delay (0-255 minutes)
0
60
Segment 3
Power Up Delay (0-60 seconds)
Segment 4
Siren Time (1-255 minutes)
0
3
Segment 5
Telephone Line Cut delay (0-255 seconds)
0
Segment 6
Cross Zone Time (0-255 minutes)
5
Segment 7
Chime Time in 50 mS increments (0-255)
5
Segment 8
Dialer delay (0-255 seconds)
0
Segment 9
Fire Alarm Verification Time (120-255 seconds)
0
Segment 10
Listen-In Time (0-255 seconds)
0
Segment 11
Zone monitor timer hours/days (0-255)
0
Segment 12
Auto arming warning timer (1-255 minutes)
1
Segment 13
Auto arming retry timer (1-255 minutes)
45
Segment 14
Programming timeout (1-255 minutes) (“0”=15 minutes)
0
USER CODE REQUIREMENTS
Segment 1 (Circle Numbers To Program)
1
2
Enables six digit code option. All arm/disarm/Go to program codes require six digits
Requires valid user code entry so that [*]-[9]-[8] and [*]-[9]-[9] functions can work
3
Enables Auto Cancel / Abort
4
Reserved
5
On: keypad shutdown mode
6
On: user authorization to enter program mode
7
On: codes 16 and 17 are guard codes
8
Reserved
NX-6-EUR Installation manual
Page 84
02/07/06
9-7-1-3-0-0
42
51
GO TO PROGRAM CODE
43
52
GO TO PROGRAM CODE PARTITION AND AUTHORIZATION
Segment 1 (Circle Numbers To Program)
1
Reserved
2
Enables “Go To Program Code” as an arm only code
3
Enables “Go To Program Code” as an arm only code after closing
4
Enables “Go To Program Code” as a master arm/disarm code (can change user codes)
5
Enables “Go To Program Code” as an arm/disarm code
6
Enables “Go To Program Code” to bypass zones
7
Enables “Go To Program Code” opening and closing reports
8
Reserved
1
Enables “Go To Program Code” for partition #1.
2
Enables “Go To Program Code” for partition #2.
Segment 2 (Circle Numbers To Program)
15-15-15-15-15-15
44
52
DURESS CODE
45
53
AUXILIARY OUTPUTS 1-4 PARTITION SELECTION
46
47
53
54
Segments
Partition 1
1
1
2
1
3
1
4
1
Partition 2
2
2
2
2
AUXILIARY OUTPUTS 1-4 SPECIAL TIMING
Segments
1
2
3
Auxiliary output timed in minutes
1
1
1
Auxiliary output to latch
Auxiliary output to stop timing when user code is entered
2
3
1
2
2
3
2
3
Auxiliary output to activate only between closing and opening time
4
4
4
4
Auxiliary output to activate only between opening and closing time
5
5
5
Invert auxiliary output (0 volts going to 12 volts when activated)
6
5
6
6
6
Reserved
7
7
7
7
Reserved
8
8
8
8
AUXILIARY OUTPUT 1, EVENT & TIME (open collector 1)
Segment 1
Program the event number for output 1
Segment 2
48
54
AUXILIARY OUTPUT 2, EVENT & TIME (open collector 2)
Segment 1
Program the event number for output 2
Segment 2
49
54
54
56
Program the timing for output 3
AUXILIARY OUTPUT 4, EVENT & TIME (open collector 4)
Segment 1
Program the event number for output 4
Segment 2
51
Program the timing for output 1
AUXILIARY OUTPUT 3, EVENT & TIME (open collector 3)
Segment 1
Program the event number for output 3
Segment 2
50
Program the timing for output 1
Program the timing for output 4
AUTOTEST CONTROL
Segment 1
Program a “1” if the interval is hours, or a “0” for days.
Add a “2” to suppress the daily test or a “3” to suppress
the hourly test
Segment 2
Program the autotest interval from 1-255 days or hours
3
7=Each siren activation
0 sec.=follow event
7=Each siren activation
0 sec.=follow event
2=24 hour alarm
10=10 sec.
39= smoke power
0=follow event
0
1
Segment 3
Program the autotest report in 24 hour time format
2
Segment 4
Program the autotest report time, minutes after the
hour
0
NX-6-EUR Installation manual
Page 85
4
02/07/06
52
53
54
55
56
56
57
57
OPENING TIME / AUTO DISARM TIME
Segment 1
Program the hour of the opening time
8
Segment 2
Program the minutes after the hour of the opening time
0
CLOSING TIME / AUTO ARMING TIME
Segment 1
Program the hour of the closing time / auto arming time
20
Segment 2
0
Program the minutes after hour of closing / auto arming time
DAYS OF THE WEEK WHEN “ARM ONLY AFTER CLOSE” WILL ARM/DISARM IN PARTITIONS 1-2
Segments
Sunday
1
1
2
1
Monday
2
2
Tuesday
3
3
Wednesday
4
4
Thursday
5
5
Friday
6
6
Saturday
7
7
Reserved
8
8
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
DAYS OF THE WEEK WHEN “AUTO ARMING” WILL OCCUR IN PARTITIONS 1-2
Segments
1
2
Sunday
1
1
Monday
2
2
Tuesday
3
3
Wednesday
4
4
Thursday
5
5
Friday
6
6
Saturday
7
7
Reserved
8
8
NX-6-EUR Installation manual
Reserved
Page 86
Reserved
Reserved
02/07/06
56
58
ALARM AND RESTORE COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
Segment 1
Zone 1-15 Alarm code
Segment 2
0
Reserved
0
Segment 5
Zone 1-15 Restore code
0
Segment 6
Zone 16 Restore code
0
Reserved
0
Segment 3-4
Segment 7-8
57
58
BYPASS COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
Segment 1
Zone 1-15 Bypass code
Segment 2
Segment 3-8
58
59
Segment 3-8
59
Segment 3-8
60
60
Segment 3-8
60
0
0
Reserved
0
Segment 3-8
0
Zone 16 Trouble Code
0
Reserved
0
0
Zone 16 Sensor Low Battery Code
0
Reserved
0
SENSOR MISSING COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
Segment 1
Zone 1-15 Sensor Missing Code
Segment 2
0
Zone 16 Tamper Code
SENSOR LOW BATTERY COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
Segment 1
Zone 1-15 Sensor Low Battery Code
Segment 2
61
0
Reserved
TROUBLE COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
Segment 1
Zone 1-15 Trouble Code
Segment 2
0
Zone 16 Bypass code
TAMPER COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
Segment 1
Zone 1-15 Tamper Code
Segment 2
59
0
Zone 16 Alarm code
0
Zone 16 Sensor Missing Code
0
Reserved
0
COMMUNICATOR CODES FOR SLOW SPEED FORMATS ONLY
62
60
DURESS
0-0
63
61
AUXILIARY 1 (fire)
0-0
64
61
AUXILIARY 2 (medical alarm)
0-0
65
61
KEYPAD PANIC
0-0
66
61
KEYPAD MULTIPLE CODE ENTRY TAMPER
67
61
BOX TAMPER / BOX TAMPER RESTORE
0-0-0-0
68
62
AC FAIL / AC RESTORE
0-0-0-0
69
62
LOW BATTERY / LOW BATTERY RESTORE
0-0-0-0
70
62
POWER SHORT / POWER SHORT RESTORE
0-0-0-0
71
62
BELL TAMPER / BELL TAMPER RESTORE
0-0-0-0
72
62
TELEPHONE LINE CUT RESTORE
0-0-0-0
73
63
Reserved
74
63
EXPANDER TROUBLE / EXPANDER TROUBLE RESTORE
75
63
FAILURE TO COMMUNICATE
0-0
76
63
LOG FULL COMMUNICATOR CODE
0-0
77
63
OPENING CODE COMMUNICATOR CODE
Segment 1
Opening Code for Codes 1-15
64
0-0
0-0-0-0
0
Segment 2
Opening Code for Codes 16-30
0
Segment 3
Opening Code for Codes 31-40
0
Reserved
0
CLOSING COMMUNICATOR CODE
Segment 1
Closing Code for Codes 1-15
0
Segment 4-8
78
0-0
Segment 2
Closing Code for Codes 16-30
0
Segment 3
Closing Code for Codes 31-40
0
Segment 4-8
0
Reserved
79
64
AUTOTEST COMMUNICATOR CODE
0-0
80
64
RECENT CLOSING AND EXIT ERROR
0-0
NX-6-EUR Installation manual
Page 87
02/07/06
81
64
START PROGRAMMING / END PROGRAMMING
0-0-0-0
82
65
RESERVED / END DOWNLOAD
0-0-0-0
83
65
CANCEL COMMUNICATOR CODE
84-87
65
RESERVED
88
66
PARTITION 1, ACCOUNT CODE
10-10-10-10-10-10
89
66
PARTITION 2, ACCOUNT CODE
10-10-10-10-10-10
90
66
PARTITION 2, FEATURE SELECTION
Segment 1
91
92-109
66
66
0
0-0-0-0-0-0-00
Segment 2
Segment 3
1
Quick Arm
1
LED extinguish enable
1
Open/Close
2
Re-Exit
2
Require user code for bypassing zones
2
Bypass
3
Auto Bypass (interior)
3
Bypass sounder alert
3
Restore
4
Silent Panic
4
AC power/ low battery sounder alert
4
Trouble
5
Audible Panic
5
Enables bypass toggle
5
Tamper
6
Auxiliary 1
6
Enables silent auto arm
6
Cancel
7
Auxiliary 2
7
Enables automatic instant (entry/exit)
7
Recent Closing
8
Multi Keypress Tamper
Segment 4
8
Final set door
1
Late to close/early to open
1
2
Auto arm in stay mode
2
Reserved
3
Enables instant night
3
Reserved
4
Tamper when sensor lost if armed
4
Reserved
5
Enables instant stay toggle
5
Reserved
8
Exit Error
Segment 5
Disables auto bypassing of force armable zones
6
Arming with tamper mem./ comm. failure
6
Reserved
7
Arming with battery trouble
7
Reserved
8
Keyswitch zone arms in stay mode
8
Reserved
ENTRY/EXIT TIMERS
Segment 1 (Entry Time 1)
0
Segment 2 (Exit Time 1)
0
Segment 3 (Entry Time 2)
0
Segment 4 (Exit Time 2)
0
Reserved
0
Reserved
0
Reserved
NX-6-EUR Installation manual
Page 88
02/07/06
4
110
67
CONFIGURATION GROUP 1 ALARM CODE
111
67
CONFIGURATION GROUP 1 CHARACTERISTIC SELECT
Segment 1 (Circle Numbers To Program)
1
Fire (enable for fire zone)
5
Delay 1 zone (enable to follow Timer 1 Entry/Exit times)
2
24 Hour (enable for non-fire 24 hour zone)
6
Delay 2 zone (enable to follow Timer 1 Entry / Exit times)
3
Keyswitch zone
7
Interior (Enable for auto bypass or stay arming)
4
Follower (enable for burglary zones that are
8
Local Only (enable if zone is not to be reported)
instant during non-entry times)
Segment 2 (Circle Numbers To Program)
1
Keypad audible on alarm
5
Bypassable
2
Yelping siren on alarm
6
Group Shunt
3
Steady siren on alarm
7
Force armable
4
Chime
8
Entry Guard
Segment 3 (Circle Numbers To Program)
Fast Loop Response
5
6
Swinger zone
3
Double End of Line Tamper zone
Trouble zone (Fire and Day zone)
7
Restore reporting
4
Cross Zone
8
Listen-In
1
2
Dialer Delay zone
Segment 4 (Circle Numbers To Program)
1
Zone activity monitor
5
2
End of line resistor defeat
6
Reserved
3
Zone acts as request to exit input
7
Reserved
4
Zone acts as acces control zone
1-8
Reserved
8
Reserved
Segment 5 (Circle Numbers To Program)
Reserved
THE DEFAULTS LISTED IN THE ODD-NUMBERED LOCATIONS BELOW REPRESENT THE FIVE SEGMENTS OF EACH OF
THOSE LOCATIONS. USE THE FIVE SEGMENT CHARTS FROM LOCATION 111 TO UNDERSTAND THESE DEFAULTS.
112
68
CONFIGURATION GROUP 2 ALARM EVENT CODE
113
68
CONFIGURATION GROUP 2 CHARACTERISTIC SELECT
114
68
CONFIGURATION GROUP 3 ALARM EVENT CODE
115
68
CONFIGURATION GROUP 3 CHARACTERISTIC SELECT
116
68
CONFIGURATION GROUP 4 ALARM EVENT CODE
117
69
CONFIGURATION GROUP 4 CHARACTERISTIC SELECT
118
69
CONFIGURATION GROUP 5 ALARM EVENT CODE
119
69
CONFIGURATION GROUP 5 CHARACTERISTIC SELECT
120
69
CONFIGURATION GROUP 6 ALARM EVENT CODE
121
69
CONFIGURATION GROUP 6 CHARACTERISTIC SELECT
122
69
CONFIGURATION GROUP 7 ALARM EVENT CODE
123
69
CONFIGURATION GROUP 7 CHARACTERISTIC SELECT
124
70
CONFIGURATION GROUP 8 ALARM EVENT CODE
125
70
CONFIGURATION GROUP 8 CHARACTERISTIC SELECT
126
70
CONFIGURATION GROUP 9 ALARM EVENT CODE
127
70
CONFIGURATION GROUP 9 CHARACTERISTIC SELECT
128
70
CONFIGURATION GROUP 10 ALARM EVENT CODE
129
70
CONFIGURATION GROUP 10 CHARACTERISTIC SELECT
130
70
CONFIGURATION GROUP 11 ALARM EVENT CODE
131
71
CONFIGURATION GROUP 11 CHARACTERISTIC SELECT
132
71
CONFIGURATION GROUP 12 ALARM EVENT CODE
133
71
CONFIGURATION GROUP 12 CHARACTERISTIC SELECT
134
71
CONFIGURATION GROUP 13 ALARM EVENT CODE
135
71
CONFIGURATION GROUP 13 CHARACTERISTIC SELECT
136
71
CONFIGURATION GROUP 14 ALARM EVENT CODE
137
71
CONFIGURATION GROUP 14 CHARACTERISTIC SELECT
NX-6-EUR Installation manual
Page 89
2
2-125-278
7
5-125-25678
5
45-125-25678
5
457-125-25678
4
0-125-25678
0
2-5-278
1
1-13-378
7
6-125-25678
13
24-12-78
3
3-0-2
5
457-125-245678
4
0-1258-25678
7
5-1256-25678
02/07/06
138
72
CONFIGURATION GROUP 15 ALARM EVENT CODE
139
72
CONFIGURATION GROUP 15 CHARACTERISTIC SELECT
140
72
CONFIGURATION GROUP 16 ALARM EVENT CODE
141
72
CONFIGURATION GROUP 16 CHARACTERISTIC SELECT
142
72
CONFIGURATION GROUP 17 ALARM EVENT CODE
143
72
CONFIGURATION GROUP 17 CHARACTERISTIC SELECT
144
72
CONFIGURATION GROUP 18 ALARM EVENT CODE
145
73
CONFIGURATION GROUP 18 CHARACTERISTIC SELECT
146
73
CONFIGURATION GROUP 19 ALARM EVENT CODE
147
73
CONFIGURATION GROUP 19 CHARACTERISTIC SELECT
148
73
CONFIGURATION GROUP 20 ALARM EVENT CODE
149
73
CONFIGURATION GROUP 20 CHARACTERISTIC SELECT
150
73
CONFIGURATION GROUP 21 ALARM EVENT CODE
151
73
CONFIGURATION GROUP 21 CHARACTERISTIC SELECT
152
74
CONFIGURATION GROUP 22 ALARM EVENT CODE
153
74
CONFIGURATION GROUP 22 CHARACTERISTIC SELECT
154
74
CONFIGURATION GROUP 23 ALARM EVENT CODE
155
74
CONFIGURATION GROUP 23 CHARACTERISTIC SELECT
156
74
CONFIGURATION GROUP 24 ALARM EVENT CODE
157
74
CONFIGURATION GROUP 24 CHARACTERISTIC SELECT
158
74
CONFIGURATION GROUP 25 ALARM EVENT CODE
159
75
CONFIGURATION GROUP 25 CHARACTERISTIC SELECT
160
75
CONFIGURATION GROUP 26 ALARM EVENT CODE
161
75
CONFIGURATION GROUP 26 CHARACTERISTIC SELECT
162
75
CONFIGURATION GROUP 27 ALARM EVENT CODE
163
75
CONFIGURATION GROUP 27 CHARACTERISTIC SELECT
164
75
CONFIGURATION GROUP 28 ALARM EVENT CODE
165
75
CONFIGURATION GROUP 28 CHARACTERISTIC SELECT
166
76
CONFIGURATION GROUP 29 ALARM EVENT CODE
167
76
CONFIGURATION GROUP 29 CHARACTERISTIC SELECT
5
457-1256-25678
4
0-1256-25678
3
38-0-2
7
5-1257-25678
7
6-1257-25678
7
5-1245-25678
20
24-125-278
20
24-5-278
5
7-125-25678
4
0-1245-25678
5
45-1245-25678
3
248-125-2
4
0-1257-25678
4
0-125-25678-1
4
0-125-5678-2
11
168
76
CONFIGURATION GROUP 30 ALARM EVENT CODE
169
76
CONFIGURATION GROUP 30 CHARACTERISTIC SELECT
170205
76
RESERVED
206
76
DAYS OF THE WEEK WHEN “AUTO DISARMING” WILL OCCUR IN PARTITIONS 1-2
207211
77
24-125-278
0-0-0-0-0-0-0-0
Segments
1
2
Sunday
1
1
Monday
2
2
Tuesday
3
3
Wednesday
4
4
Thursday
5
5
Friday
6
6
Saturday
7
7
Reserved
8
8
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
RESERVED
212
77
LCD KEYPAD ADDRESS FOR XSIA ZONE DESCRIPTIONS
213
77
COUNTRY CODE
NX-6-EUR Installation manual
192
0
Page 90
02/07/06
BOARD INSTALLATION
Inside the can, several 2-holed insertion points have been constructed. This allows for either
vertical or horizontal placement of the modules. Notice that each insertion point has two sizes
of holes -a larger hole and a smaller hole.
Diagram 1: The black plastic PCB guides are grooved on one edge where the PC
board will be seated. The end with the half-moon protrusion fits into the larger
hole. The smaller hole is for the screw.
Diagram 2: Place the first black plastic PCB guide in the top insertion point,
grooved edge downward. The half-moon protrusion will be in the large hole. It
does not require force. Insert one of the provided screw into the smaller hole
(from inside the can) to secure it in place. A screwdriver should reach through
the notch that runs the length of the guide to tighten the screw. The second PBC
guide should be positioned opposite the first (grooved edge up) and placed in
the lower insertion point, using the same procedures described above. Once
mounted, screw it in securely.
Diagram 3: The PC Board should slide freely in the grooves of both guides.
Note: For installation, service or maintenance a set of screwdrivers is required
(not included).
Note: A cam lock is provided to close the door of the cabinet. Use the key (2
keys included) to close the cabinet.
NX-6-EUR Installation manual
Page 91
02/07/06
THIS LED IS LIT DURING
COMMUNICATION.
Aux. Outs 1 - 3 Current
limited to 250 microamps
when output is positive &
250 mA when output is
negative.
Aux. Out 4 (as Smoke +)
Current limited to 250 mA
when output is positive and
250 microamps when
output is negative.
Aux 4 defaults to SMOKE +
& can be used as Zone 7
for 2-wire smoke loop. Connect
Between Aux 4 & COM.
Program LOC 37, SEG 6, OPT 1.
IF BOX TAMPER IS ENABLED IN LOC 37,
CONNECT A NORMALLY CLOSED
SWITCH TO THESE PINS.
CHECK REQUIRED BATTERY
STANDBY TIME WITH LOCAL
REGULATIONS. CONTROL
PANEL DRAWS 60mA IN
STANDBY.
RED
Transmission of burglary/fire alarms
direclty to a police/fire brigade
emergency number is NOT permitted.
Alarms should be transmitted to an
authorized central station.
AUX +
COM
POS
COM
DATA
BELL +
BELL -
AC
AC
EARTH
COM
COM
COM
(SMOKE +)
AUX 4
ZONES
THESE LEDs ARE FOR
PROPER CIRCUIT
OPERATION ONLY
6
5
4
3
2
3
2
BLACK
PROGRAM
1
Page 92
BOX TAMPER
1
KEYPAD
ALL ZONE INPUTS ARE SUPERVISED.
NX-6-EUR Installation manual
AUXOUT
WARNING – TO PREVENT RISK
OF ELECTRIC SHOCK- ALWAYS
DISCONNECT THE TELEPHONE
LINE PRIOR TO SERVICING.
DUBLIN, IRELAND
UNDER FULL-LOAD, THE CONTROL PANEL
NO LONGER PROCESSES SENSOR TRIPS
AT 9.25 VOLTS.
THE TOTAL STANDBY CURRENT DRAWN FROM
TERMINALS AUX+AND KEYPAD POS WHEN
ADDED TOGETHER, MUST NOT EXCEED 1AMP
WITH A 35VA TRANSFORMER.
KEYPAD POS AND AUX + TERMINALS
ARE LIMITED TO 1 AMP.
(Supervised)
(Supervised)
DO NOT
CONNECT
230VAC TO
TERMINAL
STRIP.
50Hz
PRIMARY
FUSE
500mA.
+10%/-15%
230V AC
TO ADDITIONAL
KEYPADS AND
EXPANSION
DEVICES.
FOR VOLTAGE OUTPUT
PROGRAM LOCATION 37,
SEGMENT 2, FEATURE 1.
BUILT IN SIREN DRIVER
FOR 15 OR 30 WATT
SPEAKERS 4,8 OR 16
OHM LOAD.
MAKE SURE TO PROGRAM LOC 37, SEG 6, OPTION 1
FOR 2-WIRE SMOKE LOOP.
KEYPAD PART #
NX-108E NX-116E NX-124E
NX-1208E NX-1248E NX-148E
NX-1308E NX-1316E
NX-1324E NX-1348E-ICON
NX-1508E NX-1516E
CE APPROVED TRANSFORMER.
16,5Vac / 35VA
MAX TOTAL WIRE RUN IS 800m.
MAX NUMBER OF DEVICES IS 8
KEYPADS + 3 OTHER DEVICES.
LIGHTNING PROTECTION
THE CONTROL PANEL
MUST BE EARTH GROUNDED
FOR LIGHTNING PROTECTION
TO WORK EFFECTIVELY.
ANY COM
TERMINAL
NORMALLY OPEN
CONTACT WITH
E.O.L. RESISTOR.
3.3K
E.O.L.
1 NORMALLY OPEN
CONTACT AND
1 NORMALLY CLOSED
CONTACT WITH E.O.L.
RESISTOR.
3.3K
E.O.L.
NORMALLY CLOSED 2 NORMALLY
CONTACT WITH E.O.L. OPEN CONTACT
RESISTOR.
AND 2 NORMALLY
CLOSED CONTACT
WITH E.O.L.
ANY ZONE ANY COM
TERMINAL TERMINAL RESISTOR.
3.3K
E.O.L.
ANY COM ANY ZONE ANY COM
TERMINAL TERMINAL TERMINAL
3.3K
E.O.L.
ANY ZONE
TERMINAL
DOUBLED ZONE
CONFIGURATION
USED AS A FIRE
ZONE.
3.74K
E.O.L.
TAMPER
CONTACT
ANY COM
TERMINAL
EUROPEAN
1E.O.L./ 2E.O.L.
680 ohm
GOLD
BRN
GRAY
BLUE
2 WIRE SMOKE E.O.L.
BRN
BRN
GRAY
WHT
BLUE
6.98K
ZONE DOUBLING
ZONES 7 - 12
3.74K
BRN
BRN
YEL
VIOLET
ORG
ZONE DOUBLING
ZONES 1- 6
E.O.L
RESISTORS
EUROPEAN DOUBLE
E.O.L. CONFIGURATION
3.3K
E.O.L.
3.3K
E.O.L.
ANY ZONE
TERMINAL
ANY ZONE ANY COM ANY ZONE ANY COM
TERMINAL TERMINAL TERMINAL TERMINAL
The 3.74K resistor
is for zones 1 - 6.
The 6.98K resistor
is for zones 7 - 12.
IF A DOUBLED ZONE
IS USED AS A FIRE ZONE,
THE HIGH ZONE (7 - 12)
IS NOT USABLE.
DOUBLED ZONE
CONFIGURATION.
3.74K
E.O.L. (1 - 6)
6.98K
E.O.L. (7 - 12)
ANY ZONE
TERMINAL
NX-6 WIRING DIAGRAM
AUDIO TAP
1
02/07/06
TERMINAL DESCRIPTION
TERMINAL
DESCRIPTION
R1
R
T
T1
EARTH
AC
BELL + & BELL -
House Telephone Ring.
Telephone Ring.
Telephone Tip.
House Telephone Tip.
Earth Ground.
AC input. Connect to a 16.5V 35VA CE approved transformer.
If used as a siren output (default), the speaker rating should be 15 watt at 8 or 16 ohm, or
30/40 watt at 4, 8, or 16 ohms. If voltage output is selected in location 37, this output
becomes voltage output, 12VDC, 1 Amp maximum load.
NOTE: A 3.3KW resistor may be required across the bell terminals when a 12 VDC siren
is used. If no resistor is used, you may experience voltage leakage into the siren, which
will cause these devices to output a small signal.
Connect to the data terminal on the keypads and the expanders. Maximum wire run is
800 m with 2 mm² wire. The minimum wire sizes at 75, 150, 300 and 600 m are 0.12, 0.33,
0.83 and 1.3 mm² respectively. These numbers are for one keypad at the end of the wire
and a voltage drop of max. 2 Volts. When connecting more than one keypad to the end of
the wire, a higher gauge wire will be required. The maximum number of devices are max.
8 keypads and max 3 expanders..
Connect to the Common terminal on the keypads and the expanders.
Connect to the positive terminal on the keypads and the expanders. This terminal and
AUX PWR + are limited to 1 Amp total current when added together.
KP DATA
KP COM
KP POS
COM
AUX PWR+
Connect the negative wire of powered devices such as motion and smoke detectors.
Connect the positive wire of all powered devices except smoke detectors and keypads.
This terminal and KP POS are limited to 1 Amp total current when added together.
ZONE 6
Connect to one side of zone 6 loop. Connect the other side to the com. terminal. Open or
short causes alarm.
COM
ZONE 5
Common (-) terminal for zones 5 & 6. (See the wiring diagram for examples)
Connect to one side of zone 5 loop. Connect the other side to COM terminal. Open or short
causes alarm.
ZONE 4 - ZONE 1
AUX OUT 4
SMOKE +
(ZONE 7)
AUX OUT 3 - AUX
OUT 1
Connect as described for zones 5 & 6. (See the wiring diagram for examples)
Smoke detector power 12VDC. Current limited to 250 mA when output is positive and
250 microamps when output is negative. This output defaults to Smoke Power, but can be
re-configured. Zone 7 may be used for a 2-wire smoke detector using a 680 Ω E.O.L.
resistor, program location 37, segm.6 option 1.
Connect negative lead of low current device [relay, LED (install 1K resistor in series with
LED), etc.]. Connect positive lead of device to AUX PWR +. Current limited to 250
microamps maximum when output is positive and 250 mA when output is negative.
NX-6-EUR Installation manual
Page 93
02/07/06
TECHNICAL SPECIFICATIONS
Technical specifications NX-6
Operating power
- Nominal
- Minimum/maximum
Current consumption
Battery
16.5 Vac, 50/60Hz, 35VA
14.05 Vac - 18.15 Vac
Min 95 mA, Max 96 mA
max. 12V/18 Ah
use rechargeable lead-acid battery only
72 hours
EN50131-6 Grade 2 Type A
10.50 Vdc/1.5 A
13.85 Vdc/1.7 A
5%
0 - 50° C
Maximum recharge time
Auxiliary Power
- Minimal
- Nominal/Maximum
- Maximum ripple
Operating temperature
Loop resistance
- Standard loop
- 2-wire fire loop
Built-in siren driver
Loop response
Dimensions (PCB board only)
Weight (PCB board only)
Classifications
300 Ohms maximum
30 Ohms maximum
112 dB, 2 tones (steady or yelp)
selectable: 50 ms or 500 ms
280 x 90 mm
250 g
Security Grade 2
Environmental Class 2
Applied standards
EMC
Environmental
Control and Indicating equipment
EN50130-4
EN50130-5
CLC/TS 50131-3
Technical specifications NX-108, NX-116, NX-124
Operating power
- Nominal
- Minimum/maximum
Operating temperature
Dimensions
Current consumption
- Minimum (quiescent, no lighting)
- Nominal (quiescent, lighting ON)
Current consumption in alarm
- 1 zone in alarm, sounder/lighting ON
- Maximum (all LED’s ON, sounder ON)
Weight
NX-6-EUR Installation manual
Page 94
12 Vdc
9 Vdc - 14 Vdc
0 - 50° C
163 x 102 x 26 mm
NX-108
NX-116
10 mA
10 mA
29 mA
29 mA
42 mA
90 mA
228 g
42 mA
110 mA
230 g
NX-124
10 mA
29 mA
42 mA
130 mA
232 g
02/07/06
Technical specifications NX-1308, NX-1316, NX-1324
Operating power
- Nominal
- Minimum/maximum
Operating temperature
Dimensions
Current consumption
- Minimum (quiescent, no lighting)
- Nominal (quiescent, lighting ON)
Current consumption in alarm
- 1 zone in alarm, sounder/lighting ON
- Maximum (all LED’s ON, sounder ON)
Weight
12 Vdc
9 Vdc - 14 Vdc
0 - 50° C
158 x 135x 30 mm
NX-1308
NX-1316
23 mA
23 mA
29 mA
29 mA
55 mA
90 mA
264 g
47 mA
110 mA
264 g
NX-1324
23 mA
29 mA
55 mA
130 mA
270 g
Technical specifications NX-148
Operating power
- Nominal
- Minimum/maximum
Operating temperature
Dimensions
Current consumption
- Minimum (quiescent, no lighting)
- Nominal (quiescent, minimum lighting)
- Nominal (quiescient, maximum lighting)
Current consumption in alarm
- 1 zone in alarm, sounder/lighting ON
- Maximum (all LED’s ON, sounder ON)
Weight
NX-6-EUR Installation manual
Page 95
12 Vdc
9 Vdc - 14 Vdc
0 - 50° C
158 x 135 x 30 mm
20 mA
25 mA
48 mA
65 mA
110 mA
290 g
02/07/06
APPENDIX 1: REPORTING FIXED CODES IN CONTACT-ID AND
SIA
The table below lists the event codes sent for the following reports (if enabled) when using CONTACT ID or SIA formats.
CONTACT ID
SIA
MANUAL TEST
REPORT
601
RX
AUTOTEST
602
RP
OPEN (User Number)
401
OP
CLOSE (User Number)
401
CL
CANCEL (User Number)
406
OC
DOWNLOAD COMPLETE
412
RS
START PROGRAM
627
LB
END PROGRAM
628
LX
RECENT CLOSE (User Number)
401
CR
EXIT ERROR (User Number)
457
EE
EVENT LOG FULL
605
JL
FAIL TO COMMUNICATE
354
RT
EXPANDER TROUBLE (device number)
333
ET
EXPANDER RESTORE (device number)
333
ER
TELEPHONE FAULT
351
LT
TELEPHONE RESTORE
351
LR
SIREN TAMPER
321
YA
SIREN RESTORE
321
YH
AUX POWER OVERCURRENT (device number)
312
YP
AUX POWER RESTORE (device number)
312
YQ
LOW BATTERY (device number)
309
YT
LOW BATTERY RESTORE (device number)
309
YR
AC FAIL (device number)
301
AT
AC RESTORE (device number)
301
AR
BOX TAMPER (device number)
137
TA
BOX TAMPER RESTORE (device number)
137
TR
KEYPAD TAMPER
137
TA
KEYPAD PANIC (audible)
120
PA
KEYPAD PANIC (silent)
121
HA
DURESS
121
HA
KEYPAD AUXILIARY 1
110
FA
KEYPAD AUXILIARY 2
100
MA
RF SENSOR LOST (zone number)
381
*T
RF SENSOR RESTORE (zone number)
381
*R
SENSOR LOW BATTERY (zone number)
384
XT
SENSOR BATTERY RESTORE (zone number)
384
XR
ZONE TROUBLE (zone number)
380
*T
ZONE TROUBLE RESTORE (zone number)
380
*R
ZONE TAMPER (zone number)
137
TA
ZONE TAMPER RESTORE (zone number)
137
TR
ZONE BYPASS (zone number)
570
*B
BYPASS RESTORE (zone number)
570
*U
EARLY OPEN / LATE CLOSE
451
OK
FAIL TO CLOSE
454
CI
ZONE ACTIVITY FAULT
391
NA
ZONE ACTIVITY RESTORE
391
NS
FREEZE ALARM
159
ZA
HEAT ALARM RESTORE
158
KH
MANUAL FIRE ALARM (pull station)
115
FA
THE NUMBER IN PARENTHESES FOLLOWING THE EVENT IS THE NUMBER THAT WILL BE REPORTED AS THE ZONE NUMBER. IF THERE ARE NO
PARENTHESES, THE ZONE WILL BE “0”. SEE APPENDIX 3 FOR THE DEVICE NUMBERS.
* The character transmitted in this slot will be the first character from the event code of the zone that is bypassed or in trouble (see locations
110 - 169).
NX-6-EUR Installation manual
Page 96
02/07/06
APPENDIX 2: REPORTING ZONE CODES IN SIA OR CONTACT
ID
The NX-6 has the ability to report SIA level 1 transmissions to either or both phone numbers. Each report in SIA
consists of an Event Code and a Zone or User ID. The Zone ID will be the zone number that is in alarm. The event
code will come from the chart below, and it will be programmed in the configuration group event code.
Programmed Event Code
SIA Code
Description
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
HA
FA
PA
BA
BA
BA
UA
BA
BA
UA
HA
MA
PA
TA
RP
GA
KA
WA
QA
SA
ZA
KH
FA
Holdup Alarm
Fire Alarm
Panic alarm
Burglary Alarm
Burglary Alarm
Burglary Alarm
Untyped Alarm
Burglary Alarm
Burglary Alarm
Untyped Alarm
Holdup Alarm
Medical Alarm
Panic alarm
Tamper Alarm
Periodic Test
Gas Alarm
Heat Alarm
Water Alarm
Emergency Alarm
Sprinkler Alarm
Freeze Alarm
Heat Alarm Restore
Manual Fire Alarm
NX-6-EUR Installation manual
Page 97
02/07/06
The NX-6 can report Ademco Contact ID transmissions. Each report in Contact ID consists of an Event Code and a
Zone ID. The zone ID is the zone that generated the alarm. The event code will come from the chart below, and it
will be programmed in the configuration group event code.
Programmed Event Code
CONTACT-ID
Description
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
122
110
120
130
131
132
133
134
135
150
121
100
123
137
602
151
158
154
140
140
159
158
115
Silent Panic
Fire Alarm
Panic alarm
Burglary Alarm
Perimeter Alarm
Interior Alarm
24 Hour Burglary
Entry Alarm
Day/Night Alarm
Non Burglary 24 Hour
Duress Alarm
Medical Alarm
Audible Panic Alarm
Tamper Alarm
Periodic Test
Gas Detected
High Temp
Water Leakage
General Alarm
General Alarm
Low Temp
Heat Alarm Restore
Manual Fire Alarm
NX-6-EUR Installation manual
Page 98
02/07/06
APPENDIX 3: EXPANDER NUMBERS FOR REPORTING
EXPANDER TROUBLE
The tables below list the device numbers that will be reported for each expander/keypad where a trouble condition
is present. For trouble conditions relating to the control panel, the device number is “0”.
Keypads
KEYPAD
PART 1
PART 2
1
2
3
4
5
6
7
8
192
200
208
216
224
232
240
248
193
201
209
217
225
233
241
249
Remote power supply NX-320E
Power supply
DIP 1
DIP 2
DIP 3
Expander number reported
1
2
3
4
5
6
7
8
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
84
85
86
87
88
89
90
91
Wireless receiver NX-448E
Wireless receiver
DIP 1
DIP 2
DIP 3
Expander number reported
1
2
3
4
5
6
7
8
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
35
36
37
38
39
32
33
34
Output module NX-507E or NX-508E
Output module
DIP 1
DIP 2
DIP 3
Expander number reported
1
2
3
4
5
6
7
8
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
24
25
26
27
28
29
30
31
NX-6-EUR Installation manual
Page 99
02/07/06
CE DECLARATION
NX-6-EUR Installation manual
Page 100
02/07/06
NX-6-EUR Installation manual
Page 101
02/07/06
NX-6-EUR Installation manual
Page 102
02/07/06
NX-6-EUR Installation manual
Page 103
02/07/06
NX-6-EUR Installation manual
Page 104
02/07/06
NX-6-EUR Installation manual
Page 105
02/07/06
NX-6-EUR Installation manual
Page 106
02/07/06
NX-6-EUR Installation manual
Page 107
02/07/06
www.gesecurity.net
EMEA Distribution is a division of GE Security EMEA bvba
COPYRIGHT ©2006
© GE Security EMEA bvba. All rights reserved. GE Security EMEA bvba grants the right to reprint this manual for
internal use only. GE Security EMEA bvba reserves the right to change information without notice.