Electro Controls
Thermostats - 2017
WattsIndustries.co.uk
THErMOSTATS - MECHAnICAL
CAPILLArY THErMOSTATS 1 STAGE
EC.. EC..D / EC..DM EC..W
These products are used to monitor the temperature of air or liquids. Applications include heating and air conditioning systems. The liquid filled sensing element enables a rapid response to temperature changes.
EC..D / EC..DM
EC..W
Adjustment under the cover
Terminals 0.5-2.5mm² rising clamps
Copper capillary & bulb
Volt free contacts
Max. ambient -40/+70°C
Thermostats may be calibrated by slowly turning the centre nut on the adjusting spindle.
Enclosure Flammability UL94-VO
Type
EC-1ML
EC-2
EC-3
EC-4
EC-5
EC-6
EC-7
EC-8
EC-3D
EC-6D
EC-6DM
EC-7DM
Stages
1
1
1
1
1
1
1
1
1
1
1
1
Range
°C
-10/+12
-20/+40
-20/+40
-20/+40
-20/+40
0/100
0/200
0/200
-15/+45
0/70
30/65
60/95
Diff
°C
Hand reset open low
0.5
1.5
3.5
5
2
5
Hand reset open high
1.5
2
Hand reset open high
Hand reset open high
EC..
230VAC
SPDT
15(8)A
15(3)A
15(6)A
15(6)A
15(6)A
15(4)A
15(6)A
15(6)A
15(8)A
15(8)A
15(8)A
15(8)A
Capillary
Length
1.8m
2m
2m
2m
2m
2m
2m
2m
Bulb mm
10 x 100**
8 x 140
8 x 140
8 x 100
8 x 100
8 x 100
8 x 70
8 x 70 rigid stem includes duct holder rigid stem includes duct holder rigid stem includes duct holder rigid stem includes duct holder
Max. Bulb
Temp °C
200
60
70
180
180
120
240
240
70
90
90
115
EC-3W
EC-4W
EC-6W
EC-7W
EC-8W
1
1
1
1
1
-20/+40
-20/+40
0/100
0/200
0/200
1.5
3.5
2
5
Hand reset open high
15(6)A
15(6)A
15(4)A
15(6)A
15(6)A
2m
2m
2m
2m
2m
8 x 140
8 x 100
8 x 100
8 x 70
8 x 70
70
180
120
240
240
*Also available with IP65 weatherproof enclosure. **Size/shape differs from other EC.. thermostats - does not fit standard pockets.
DIMENSIONS
65
EC.. / EC..W
70
65
EC..D / EC..DM
305 70
20
100
87
57
100
49
20
FOR SMALL DUCTS
BEND AT REQUIRED LENGTH
28.5
Drilling Data
38
ACCESSORIES:
20
EE-1A Duct bulb holder
155
305
73
62
40
1
2
"
BSP
EE-1B Brass Bulbwell
EE-STE Stainless Steel Bulbwell
8.3 ID
IP65
IP65
IP65
IP65
IP65
WIRING:
EC-1ML EC.. / EC..W
EC..D / EC..DM
Enclosure
IP40
IP43
IP43
IP43
IP43
IP43
IP43
IP43
IP43*
IP43*
IP43*
IP43*
W
2
1
R
4
B
+T
OPEN LOW 1-2 opens on temp fall.
Temp must rise to allow resetting.
40
-20
20
10
1 2 3
+T
1-2 close on temp fall. 1-3 close on temp rise.
3 2
-15
3 2
+T
40
1
25
1
OPEN HIGH 1-2 opens on temp rise.
Temp must fall to allow resetting.
24
T: +44 (0) 1480 407074
\
F: +44 (0) 1480 407076
THErMOSTATS - MECHAnICAL
CAPILLArY THErMOSTATS 2-3-4 STAGES
These products can be used to monitor the temperature of air or liquids. Applications include switching multiple heating and air conditioning systems.
The liquid filled sensing element enables a rapid response to temperature changes.
EMC-2..
Type Stages
EMC-22A
EMC-23A
2
2
EMC-22AW 2
EMC-23AW 2
EMC-341
EMC-342
DIMENSIONS
3/4
3/4
Range
°C
- 20/+40
0/100
- 20/+40
0/100
- 20/+40
0/100
Diff Per
Stage °C
1.5
2.5
1.5
2.5
1
2
EMC-22A.. / 23A..
Diff. Between
Stages °C
1/10 adj.
2/20 adj.
1/10 adj.
2/20 adj.
1
2.5
SECTION
01
EMC..
230VAC
SPDT
2x15(3)A
2x15(3)A
2x15(3)A
2x15(3)A
4x15(3)A
4x15(3)A
EMC-34..
Capillary
Length
2m
2m
2m
2m
3m
3m
EMC-2..W
Bulb mm
8 x 140
8 x 100
8 x 140
8 x 100
8 x 140
8 x 100
Adjustment under the cover
Terminals 0.5-2.5mm² rising clamp
Copper capillary & bulb
Volt free contacts
Max ambient -40/70°C
Thermostats may be calibrated by slowly turning the centre nut on the adjusting spindle.
Enclosure Flammability UL94-VO
Max. Bulb
Temp °C
60
120
60
120
60
120
Enclosure
IP43
IP43
IP65
IP65
IP65
IP65
EMC-34..
125
107
50 25
65
70
125
57
100
107
87
20
ACCESSORIES:
EE-1A Duct bulb holder
305
40
WIRING:
EMC-22..
-20
40
A
25
+
_
15
73
62
4 x 6.5
155
20
1
2
"
BSP
EE-1B Brass Bulbwell
EE-STE Stainless Steel Bulbwell
EMC-34..
40
-20
15
25
1 2 3 4
8.3 ID
1
3 2 1
2
1 2 3
+T +T
Diff between stages adjust via screw A
Contact 1-3 close on temp rise.
Contact 1-2 close on temp fall.
1 2 3
4
1 2 3 1 2 3
1 2 3 1 2 3
+T +T
+T +T
Htg only = wire 1st stg htg to last stg on stat & follow downwards in sequence
Clg only = wire 1st stg clg to 1st stg on stat & follow upwards in sequence
Htg & Clg = wire heating on lower stages & cooling on higher stages [email protected]
\
wattsindustries.co.uk
25
THErMOSTATS - MECHAnICAL
FrEEZE PrOTECTIOn THErMOSTATS
EFP..
These products are used to prevent the freezing of liquids inside pipes or heating/cooling coils.
Tamperproof adjustment
Copper capillary tin plated
Volt free contacts
Max. ambient -30/+70 C
Enclosure Flammability UL94-V0
EFP..
EFP.. W
Type
EFP-1
EFP-2
EFP-3
EFP-4
EFP-1W
EFP-2W
EFP-3W
EFP-4W
DIMENSIONS
Range °C Diff °C
-15/+15 2
-15/+15 hand reset open low
-15/+15 2
-15/+15 hand reset open low
-15/+15 2
-15/+15 hand reset open low
-15/+15 2
-15/+15 hand reset open low
EFP..
85
70
64
1
40
75
10
30
7,5
37
4,5
230VAC
SPDT
Capillary
Length
24(10)A 6m
24(10)A 6m
24(10)A 3m
24(10)A 3m
Max. Bulb
Temp °C
Enclosure
200 IP43
200 IP43
200 IP43
200 IP43
24(10)A 6m
24(10)A 6m
24(10)A 3m
24(10)A 3m
200 IP65
200 IP65
200 IP65
200 IP65
125
EFP..W
125
107
107
50 25
20 conduit
4 x 6.5
20
ACCESSORIES:
EE-1C Capillary Clips (per pack of 6)
100mm max
WIRING:
1
2
4
+T
Open low = Contact 1 - 4 opens on temperature fall.. Temperature must rise to allow resetting
INSTALLATION:
Fit the sensor to the front of the coil (downstream/air offside) or wrap around the pipe to guard against freezing at any point. No more than 10cm of the capillary should be outside the controlled space. The thermostat will switch when 30cm or more of any part of the capillary senses the set-point temperature. If the capillary is damaged, the unit will cut-out to the safety side.
THE TEMPERATURE AROUND THE HOUSING SHOULD BE MAINTAINED HIGHER THAN THE SENSOR.
26
T: +44 (0) 1480 407074
\
F: +44 (0) 1480 407076
THErMOSTATS - MECHAnICAL
IMMErSIOn THErMOSTATS SInGLE/DUAL FUnCTIOn
EBS.. EBD..
SECTION
01
These products are used to monitor liquid temperatures in pipes, boilers, tanks etc. The liquid filled sensing enables a rapid response to temperature changes.
The EBS is a single function thermostat and the
EBD dual function has two separate thermostats inside the enclosure.
EBD..
Hand reset models have a push button on the front cover.
Volt free contacts
Max. ambient 80°C (EBS-1 55°C)
All supplied complete with removable brass pocket ½" BSP.
Concealed adjustment
Enclosure Flammability = UL94-V0
EBS..
Type
EBS-1
EBS-2
EBS-3
EBS-4
EBS-7
EBS-8
EBS-9
EBS-20/L280
EBS-30/L280
EBS-70/L280
EBS-80/L280
EBD-1
EBD-2
EBD-8
EBD-9
EBD-32/L260
EBD-38/L260
DIMENSIONS
ACCESSORIES:
Range °C
Control Limit
0/35
0/80
35/95
50/130
-
-
-
Control
Diff. °C
-
-
-
0.5
2
4
- 6
30/65 Hand reset open high
60/95 Hand reset open high
95/130 Hand reset open high
Limit
-
-
-
-
-
-
-
230VAC SPDT
Control Limit
10(3)A
10(3)A
15(5)A
15(5)A
15(5)A
15(5)A
15(5)A
-
-
-
-
-
-
-
0/70
35/95
-
-
- 2
- 4
30/65 Hand reset open high
60/95 Hand reset open high
0/80
35/95
35/95
0/80
35/95
60/95
50/130 95/130
35/95
35/95
35/95
60/95
2
4
4
4
4
4
-
-
-
-
10(3)A
15(5)A
15(5)A
15(5)A
-
-
-
-
2
4
10(3)A 10(3)A
15(5)A 15(5)A
Hand reset open high 15(5)A 15(5)A
Hand reset 15(5)A 15(5)A
4 15(5)A 15(5)A
Hand reset open high 15(5)A 15(5)A
EBS..
57
1
2
"
BSP
7.3 ID
53
85
57
1
2
"
BSP
280
280
280
280
100
100
100
100
260
260
Bulbwell
Length
120
100
100
100
100
100
100
EBD..
14.3 ID
78
90
115
90
115
100
115
115
115
115
115
Max. Bulb
Temp. °C
55
100
115
150
90
115
150
85
M20
100 / 120 / 280
20
M20
100 / 260
20
Enclosure
IP43
IP43
IP43
IP43
IP43
IP43
IP43
IP43
IP43
IP43
IP43
IP43
IP43
IP43
IP43
IP43
IP43
EE-9B
Spare brass pocket 100mm for EBS-2..9 ( NOT for EBS-1)
EE-ST9
Stainless steel pocket 100mm for EBS-2..9 ( NOT for EBS-1)
100
1
2
"
BSP
7.3 ID
WIRING:
EBS..
3
1
2
+T
3 2
-15
40
1
25
EBD..
3
1 removable link
2 3
+T
2
+T
1
3 2
-15
3 2
-15
40
1
25 40
1
25
1-2 close on temp fall. 1-3 close on temp rise. OPEN HIGH Contact 1-2 opens on temp rise. Temp must fall to allow resetting [email protected]
\
wattsindustries.co.uk
27
THErMOSTATS - MECHAnICAL
STrAP-On THErMOSTATS
These products can be used to monitor the temperature of liquids in pipes and cylinders.
BRC.. ESS..
ESS..
Volt free contacts
ESS.. Adjustment under the cover
Terminals 0.5-2.5mm
Enclosure Flammability: BRC=UL94-HB
ESS=UL94-V0
Type
BRC
ESS-1
ESS-2
ESS-32
ESS-3
ESS-42
ESS-4
DIMENSIONS
Range °C
20/90
-25/+45
0/70
35/95
50/130
30/65
60/95
46
38
96
Diff °C
5
2
2
4
6
Hand reset open high
Hand reset open high
BRC..
57
BRC..
65
86
19
ACCESSORIES:
FIXING STRAP FOR BRC
230VAC
SPDT
15(3)A
10(3)A
10(3)A
15(5)A
15(5)A
15(5)A
15(5)A
107
ESS..
Max. Bulb
Temp °C
120
70
90
115
130
90
115
70
Enclosure
IP30
IP43
IP43
IP43
IP43
IP43
IP43
FIXING STRAP FOR ESS
EE-ESS
20
FIXING STRAP ADJUSTABLE UP TO 150MM DIA. IS INCLUDED.
LONGER FIXING STRAPS ARE AVAILABLE ON REQUEST.
WIRING:
BRC.. ESS..
2 1 3
+T
3 2
-15
40
1
25
3
1
2
+T
Contacts 1-3 close on temperature rise.
Contacts 1-2 close on temperature fall.
Contacts 1-3 close on temperature rise.
Contacts 1-2 close on temperature fall.
Open high = Contact 1-2 opens on temperature rise. Temp must fall to allow resetting.
INSTALLATION:
Fix the thermostat securely to the pipe. The ambient temperature around the sensor can affect the switching point.
28
T: +44 (0) 1480 407074
\
F: +44 (0) 1480 407076
THErMOSTATS - MECHAnICAL
OUTSIDE FrOST THErMOSTATS
SECTION
01
EOF..
EOF thermostats are used to monitor temperature outside buildings and switch heating/cooling or other units in the event of high/low temperatures. The EOF-01 is a single function unit and the EOF-21 is a dual function unit which has 2 separate thermostats inside one enclosure.
Adjustment under the cover on all models
Enclosure Flammability = UL94-V2
EOF-01 is single function
EOF-21 is dual function
(2 thermostats inside one enclosure)
Type
EOF-01
EOF-21
Range °C
-20/+30
-20/+30 & -20/+30
EOF-01
EOF-21
Diff °C 230VAC
SPDT
Sensing
Element
Max. Ambient
°C
Enclosure
1 10(3)A Bimetal 60 IP65
1 2x10(3)A Bimetal 60 IP65
DIMENSIONS
125
107
EOF-01
50 25
EOF-21
175
157 50 25
125
107
125
107
4 x 6.5
20
4 x 6.5
20
WIRING:
EOF-01 EOF-21
N
L
Htg
L
Clg
L
4 2 3 1
N L
Htg
L
Clg
L
4 2 3 1
N L
Htg
L
Clg
L
4 2 3 1
+T
+T
+T
On temperature rise 2-1 close
On temperature fall 2-3 close
On temperature rise 2-1 close
On temperature fall 2-3 close
INSTALLATION:
Outside Thermostats & Sensors which are used for frost protection should be mounted on the North side of the building.
If this is not possible, shield the sensor from direct sunlight.
\
wattsindustries.co.uk
29
THErMOSTATS - MECHAnICAL
SPACE THErMOSTATS
ECS..
Type ECS thermostats monitor temperatures inside factories, greenhouses and areas subject to high humidity or regular washdown processes.
The liquid filled sensing elements are fixed to the side of the weatherproof enclosures.
Type
ECS-3
ECS-4
ECS-6
DIMENSIONS
Range °C
-20/+40
-20/+40
0/80
Diff °C
1.5
3.5
2.5
107
230VAC
SPDT
15(6)A Volt free
15(6)A Volt free
15(4)A Volt free
ECS..
Sensing
Element
Bellows
Bellows
Bellows
75
57
ECS..
50 25
125
Adjustment under the cover
Terminals 0.5-2.5mm rising clamps
Enclosure Flammability = UL94-V2
Max.Ambient
°C
60
60
80
Enclosure
IP65
IP65
IP65
4 x 6.5
20
WIRING:
ECS..
3 2 1
+T
40
-20
10
20
Contact 1-2 close on temp fall. Contact 1-3 close on temp rise.
30
T: +44 (0) 1480 407074
\
F: +44 (0) 1480 407076
THErMOSTATS - MECHAnICAL rOOM THErMOSTATS 1 STAGE
These products can be used to monitor the temperature inside buildings and switch heating, cooling or other units. These units are tamperproof.
Type
TA-2
Stages
1
RTBSB-001.045
RTBSB-001.010
RTBSB-001.048
1
1
1
Range
°C
5/30
-20/+30
5/30
10/60
RTBSB-001.910*
* Concealed adjustment.
1
DIMENSIONS
80
TA-2
5/30
42
74
RTBSB..
SECTION
23
01
EOF..
TA-2
0.5
0.5
0.5
PTR01-0..
Diff °C approx
1
PTR01-910
230VAC
Element
SPDT 10(2.5)A Volt Free Contacts
SPDT 10(3)A
SPDT 10(3)A
SPDT 10(3)A
-
-
-
0.5 SPDT 10(3)A -
TA-2
Main adjustment via knob.
Backplate for 1 gang BS box is included.
RTBSB-001.010/045/048
Knob adjustment only.
Range and limit stops provided.
Order backplate separately.
Enclosure Flammability = UL94-V0
RTBSB-001.910
Adjustment under the cover.
Function
Htg or Clg
Sensing
Bellows
Enclosure
IP20
Htg or Clg
Htg or Clg
Htg or Clg
Bimetal
Bimetal
Bimetal
IP30
IP30
IP30
Htg or Clg Bimetal IP30
80 74 70
60
ACCESSORIES:
EG-1000
EG-2000
EG-3000
Stat Guard Internal Dims 133 H x 155 W x 70 D
Stat Guard Internal Dims 102 H x 123 W x 60 D
Stat Guard Internal Dims 123 H x 196 W x 70 D
High impact polycarbonate, virtually unbreakable. Supplied with lock & key
EE-BP2
Backplate for RTBSB.. will fit square or round outlet boxes.
WIRING:
INSTALLATION:
TA-2
1 3 4
+T
To remove the TA-2 front cover and access the terminals, release the top clip using a small, flat screwdriver.
Install at a height of approx. 1.5m
Keep away from radiators, direct sunlight & other heat sources.
EG..
RTBSB-001.010/045/048/910
N
L
HTG
L
CLG
L
4
2 3 1
C
+T
EE-8P2
\
wattsindustries.co.uk
31
THErMOSTATS - MECHAnICAL rOOM THErMOSTATS 2-3-4 STAGES
These products can be used to monitor the temperature inside buildings. Up to 4 stages are available to control multiple heating/cooling or other units in various combinations.
Type
MTR10-005
METR75-820
MTR52-018
EMR-22A
EMR-34
Stages
2
2
2
2
3/4
Range
°C
5/30
5/30
5/30
0/50
0/50
MTR..
140
Diff Per
Stage °C
1
1
1
1
1
MTR52..
MTR10.. / METR75..
MTR..
Knob adjustment with range and limit stops.
Enclosure Flammability = UL94-V0
EMR..
Adjustment under the cover.
For various combinations of htg/clg.
Volt free contacts
Terminals 0.5-2.5mm² rising clamps
EMR..
Diff. Between
Stages °C
Switch Rating
230VAC
2
0.5/5 adj.
2
2 x 10(3)A
2 x 8(3)A
On-Off switch
2 x 10(3)A
On-Off switch & 3 speed fan switch
Function
1 Htg + 1 Clg
2 Htg
1 Htg + 1 Clg
Sensing
Element
Bimetal
NTC
Bimetal
Enclosure
IP30
IP30
IP30
1/10 adj.
1
2 x SPDT 15(3)A Volt free
4 x SPDT 15(3)A Volt free
Htg/Clg
Htg/Clg
Bellows
Bellows
IP30
IP30
27.5
188 70
164
110
60
79
ACCESSORIES:
EG-1000
EG-2000
EG-3000
Stat Guard Internal Dims 133 H x 155 W x 70 D
Stat Guard Internal Dims 102 H x 123 W x 60 D
Stat Guard Internal Dims 123 H x 196 W x 70 D
(Guards are not suitable for EMR.. )
High impact polycarbonate, virtually unbreakable. Supplied with lock & key
WIRING:
CLG
L
1
L
HTG
L N
2 3 4
+T
Heat 1 Heat 2
L
1 2 3
L
METR75-820
Load Supply
L in L out N
4 8 9 10 5 6
ON/OFF switch
7
Clg
L
1
L
Htg
L
2
3
N
4
R
+T
MTR52-018
N
7
N
8
L
9
I II III
14 15 16
On-Off
I
II
III
-20
40
A
+
_
25
15
Diff between stages adjust via screw A
3
1
2
STAGES
1 1 2
2
3
+ T
+ T
EMR-34
1 2
1
3 1 2
2
STAGES
3 1
3
2 3 1
4
2 3
+ T + T + T + T
Htg only = wire 1st stg htg to last stg on stat & follow downwards in sequence
Clg only = wire 1st stg clg to 1st stg on stat & follow upwards in sequence
Htg & Clg = wire heating on lower stages & cooling on higher stages
32
T: +44 (0) 1480 407074
\
F: +44 (0) 1480 407076
THErMOSTATS - MECHAnICAL
THErMOSTAT GUArDS
A range of transparent, high impact, polycarbonate thermostat guards for use with a variety of thermostats/sensors etc.
The guards screw fix to the wall over the existing thermostat.
Type
EG-1000
EG-2000
EG-3000
EG-KEY
DIMENSIONS
Application Examples
MTR10..
TA-2, PTR01.. ER.. EH.. EHR..
Various (Not suitable for EMR..)
D
EG-1000
W
H
EG-2000
D
W
H
SECTION
D
EG-3000
W
H
01
EG-2000
Supplied with lock and key
Ideal for use in public areas, sports halls etc.
Flammability = UL94-V0
Self locking snap-lock cover, use key to unlock.
EG-3000
Virtually unbreakable
Virtually unbreakable
Virtually unbreakable
EG-1000
Description
Unobstructed airflow
Unobstructed airflow
Unobstructed airflow
Tamperproof
Tamperproof
Tamperproof
EXTERNAL
H 192
W 212
D 70
INTERNAL
H 133
W 155
D 70
EXTERNAL
H 152
W 170
D 60
INTERNAL
H 102
W 123
D 60
EXTERNAL
H 181
W 251
D 70
INTERNAL
H 123
W 196
D 70
INSTALLATION:
AIRFLOW [email protected]
\
wattsindustries.co.uk
33
THErMOSTATS - ELECTrOnIC
SEnSOrS / ADJUSTErS / DISPLAYS FOr ETE.. THErMOSTATS / E13.. COnTrOLLErS
E10..
E10-B
NTC sensors, adjusters
& displays for use with
ETE.. Electroic
Thermostats /
Thermometers & E13..
Temperature Controllers.
Enclosure Flammability:
E10-D, I, S, X = UL94-V0
E10-H, R, V = L94-HB
E10-T = UL94-V2
Type Function
E10-G..
Description
E10-S
E10-V
E10-C
E10-R
E10-K
E10-P..
E10-D
E10-X
E10-I
Dimensions
E10-T
E10-H
Protection
E10-B Bead sensor
E10-C Cable Sensor
E10-D Duct sensor
E10-DA Duct Averaging
E10-H Black bulb sensor
E10-I Immersion sensor
E10-K Fan coil sensor
E10-R Room sensor
With 2 way terminal strip
With 2mm cable
Probe length 160mm
Probe length160mm (use 2 x E10-DA for averaging)
For radiant tube heaters
ORDER POCKET SEPARATELY Probe length 120mm
With duct flange & 2m cable
Can be mounted on square or round outlet box
E10-RA Room sensor
E10-S Strap-On sensor
As E10-R (use 2 x E10-RA for averaging)
Includes fixing strap for up to 6" dia. Pipe. 2m cable
E10-V Room sensor + Knob With knob adj ±4°C above & below main set point knob setting
E10 -X Outside sensor Weather proof
E10-P50 Setpoint adjuster
E10-P95 Setpoint adjuster
E10-P4 Setpoint adjuster
-10/+50°C Front panel moubting
25/95°C
±4°C
Front panel mounting
Front panel mounting.
For minor adjustment of main set point knob setting
E10-T Digital display
OPTIONAL E10-T.. ONLY
Selectable -10/+50°C or 25/95°C
230 VAC supply. Front panel mounting 48H x 96W x 104D Panel cut-out
Only for use with ETE.. Thermostats or E13.. Temperature Controllers
L24 = 24VAC supply
ACCESSORIES:
WIRING:
EE-STK ½" BSP x 120mm Stainless Steel pocket for E10-I
Special Face Plates are available in Brass, White, Satin and others on request
(see page G2)
E10.. SENSORS
E10-P..
–
Sensor 7.1 mm dia x 40
Approx 80 dia x 55
Approx 80 dia x 55
85H x 85W x 30D + bulb 16mm
Approx 80 dia x 55
Duct tube 80mm long
85H x 85W x 30D
85H x 85W x 30D
Approx 80 dia x 55
85H x 85W x 30d + knob
Approx 80 dia x 55
48H x 48W
48H x 48W
48H x 48W
44H x 91W
DRILLING DETAIL FOR E10-P..
IP00
IP65
IP65
IP65
IP30
IP65
IP65
IP30
IP30
IP65
IP30
IP65
IP00
E10-RA
E10-V using in-built sensor E10-V using remote sensor
INSTALLATION:
Terminals 0.5 -2.5mm²
Max length 100mm.
Sensor cable size 7/0.2mm
Screened cable is recommended.
Keep away from power cables/units which may cause interference.
The screen should be earthed at the controller end only.
34
T: +44 (0) 1480 407074
\
F: +44 (0) 1480 407076
THErMOSTATS - ELECTrOnIC
ELECTrOnIC THErMOSTAT - 1 STAGE DIGITAL
ETE-1D
SECTION
02
This product monitors the temperature of air or liquid in a heating system and controls heating or cooling units in response to temperature changes
230VAC
SPDT
LCD display.
Digital set up of control mode, set point, night set back and differential.
Volt free relay contacts.
Ambient -10 to +50 deg C.
Temperature resolution 0.5 deg C.
°C/°F display (ETE-1D mode only).
Night setback is standard via optional time switch.
Compatible with the functions and accessories of the ETE-150 and ETE-195 range.
Power
Consumed
Protection
10(3)A 0.5W max IP00
Type
ETE-1D
Range
Deg C
-10/+95
Differential
Deg C
0.5/10
Night set
Range C
0-40
Supply
+- 10%
230VAC
Add L24 for optional 24VAC supply. A 120VAC version is available on request.
ACCESSORIES
See table for the valid accessories
Accessory type
Temperature sensors
Set point adjuster
Digital Set point adjuster
Digital room sensor
Analogue Display
Accessory part number
E10-B/C/D/DA/G./H/I/K/R/RA/S/V/X
E10-P4,E10-P50 and E10-P95
E10-S110
E10-RD
E10-T
Digital display E10-TD
Enclosure EE-M1T
DIN rail holder EE-DR1
DIMENSIONS/TERMINATIONS:
24mm
65�mm
Electro�Controls
ETE-1D
Single�Stage Thermostat www.electrocontrols.co.uk
°C/°F
SET
LED1
P0
P4
N1
PB
PA
PR
0V/
D0
D1
S2
S1
Selected Product mode
ETE-1D ETE-150 ETE-195
✓ ✓ ✓
✓ ✓
✓
✓
✓ ✓
✓
✓ ✓ ✓
✓ ✓ ✓
Connections
L and N
NO,C,NC
S1 and S2
0 and N1
PA and PB
P4 and P0
P0 and PR
D1 and D0
230VAC or 24VAC supply
Volt free relay connections
Sensor
Night setback
E10-S110 Remote set point adjuster
E10-P4
E10-P50 or E10-P95
E10-T
L N
230VAC
NC NO C
VOLT FREE�230VAC�10(3)A
EXAMPLE:
RELAY ON
DIFFERENTIAL
OFF ON
TIMING DIAGRAM:
EXAMPLE:
RELAY ON
DIFFERENTIAL
OFF ON
TEMP( °C )
30 29 28 27 26 25 24 2 3 22 21
20
21
(SP)
22 23 2 4 25 26 27 28 29 30
This diagram shows some examples of the relay state with rising and falling temperatures for the cooling and heating modes.
EXAMPLE:
DIFFERENTIAL
RELAY O N O F F ON
TEMP( °C )
30 29 28 27 26
25
24 2 3 22 21
20
(SP)
21 22 23 2 4
25
26 27 28 29 30
TEMP( °C )
10 11 12 13 14 15 16 1 7 18 19
20
19
(SP)
18 17 1 6 15 14 13 12 11 10
SET UP
:
INSTALLATION:
Turn on the power. Momentarily the display will show all the screen characters then the Product mode
O N O F F ON
EtE1D (ETE-1D), EtE50 (ETE-150) or
EtE95 (ETE-195) and will settle to show HTG/CLG, TEMP and the actual temperature. This is the main menu or Temperature screen.
To select HTG/CLG and one of the Product modes ETE-1D, ETE-150 or ETE-195 press the set button for 3 sec. HTG/CLG and the last selected Product mode will flash.
18 10 11 12 13 14 15 16 1 7
20
19
(SP)
1 6
Use ↓ button to select either ETE1D, ETE50 or ETE95.
Use ↑ button to select either HTG or CLG
Press SET briefly to exit.
19 18 17 15 14 13 12 11 10
Briefly press SET repeatedly to select the required parameters of SETPOINT, NIGHT SET and DIFFERENTIAL. The numerical values of these parameters will be blinking and the ↑↓ buttons can be used to set the numerical value required.
Whilst setting any parameter if the buttons are left for 10 sec the screen will return to the Temperature screen.
In the Temperature screen use of the ↑↓ buttons will toggle between °C and °F if required.
DIAGNOSTIC MESSAGES
SEN0P Sensor open circuit.
SENs
Sensor short circuit
Lo/
Set temperature below or above product range
ErrPA
E10-S110 short circuit (ETE-1D only). Once this problem has been addressed press SET to revert to normal operation.
Observe the local regulations regarding electrical installations. Size the power supply cables according to the load.
The minimum sensor cable size is 7/0.2mm with a max length of 100m. Screened cable is recommended and the screen should be earthed at the controller end only.
Keep supply and sensor cables away from other power cables and devices which may cause interference.
\
wattsindustries.co.uk
35
THErMOSTATS - ELECTrOnIC
ELECTrOnIC THErMOSTAT - 2-4-6-8 STAGE DIGITAL
ETE-..D
ETE-4D
ETE-2D
These products monitor the temperature of air or liquid in a heating system and control heating or cooling units in response to temperature changes.
ETE-8D
Type Stages Range (°C) Differential per Stage (°C)
Difference b/w Stages (°C)
Night Set
Range (°C)
ETE-2D
ETE-4D
2
4
-10/+95
-10/+95
0.5/5 adj
0.5/3 adj
1/15 adj
1/6 adj
0-40
0-40
ETE-6D
ETE-8D
6
8
-10/+95
-10/+95
0.5/3 adj
0.5/3 adj
1/3 adj
1/3 adj
0-40
0-40
Add L24 for optional 24VAC/DC supply. A 120VAC version is available on request
ACCESSORIES
See table below for the valid accessories
Accessory type
Temperature sensors
Set point adjuster
Digital Set point adjuster
Digital room sensor
Analogue Display
Digital display
Accessory part number
E10-B/C/D/DA/G./H/I/K/R/RA/S/V/X
E10-P4,E10-P50 and E10-P95
E10-S110
E10-RD
E10-T
E10-TD
EE-M2T Enclosure for ETE-2D
EE-M3T Enclosure for ETE-4D
EE-M5T Enclosure for ETE-6D and 8D
LCD display.
Digital set up of control mode, Set Point,
Night Setback, Time Delay,
Differential per Stage and
Difference between Stages.
Volt free relay contacts.
Ambient -10 to +50 deg C.
Temperature resolution 0.5 deg C.
°C or °F selection (ETE-2D, 4D, 6D or 8D only).
Time delay 1-200 seconds all models.
Night Setback is standard via optional time switch.
Compatible with the functions and accessories of the ETE-(2/4/6/8)50 and ETE-(2/4/6/8)95.
Supply
+- 10%
230VAC
230VAC
230VAC
230VAC
230VAC
SPDT
10(3)A
10(3)A
10(3)A
10(3)A
Power
Consumed
2VA max
3VA max
5VA max
5VA max
Selected Product mode
ETE-2D,4D,6D or 8D
✓
ETE-250,450,650 or 850
✓
ETE-295,495, 695 or 895
✓
✓
✓
✓
✓
✓
✓
✓
EE-DR6 Din rail holder for ETE-2D
EE-DR7 Din rail holder for ETE-4D
EE-DR5 Din rail holder for ETE-6D and 8D
DIMENSIONS/TERMINATIONS:
ETE-2D
93mm 93mm 140mm
ETE-4D
24mm 24mm 140mm 35mm 35mm
93mm °C/°F
SET
°C/°F
SET
24mm
STAGE1
STAGE1
°C/°F
STAGE2
PB
PA
SET
Electro�Controls
ETE-2D
2�Stage Thermostat www.electrocontrols.co.uk
50/60Hz
230VAC
L
L
ETE-2D
2�Stage Thermostat www.electrocontrols.co.uk
L N
ETE-2D
2�Stage Thermostat www.electrocontrols.co.uk
N
N
C1 N
NC1 NO1
230VAC
C1
C1
N
NC2
NO1
NO2
C2
C2
C1 NC2
VOLT FREE�230VAC�10(3)A
NO2 C2
PB
PA
PR
0V/
P0
D1
P4
S2
N1
S1
0V/
D0
P0
PB
P4
PA
N1
PR
STAGE2
0V/
D0
D1
S2
S1
Lower for HT G
CL G
S1
C2 C1 NC2
Wire�Stages:
Lower for HT
Higher for CL
G
G
NO2
Wire�Stages:
Lower
C2 for HT
Higher for
G
CL G
PR
P0
P4
N1
To�select�NEUTRAL ZONE�or
ETE-4D/50/95, press�and�hold SET for
To�select�NEUTRAL ZONE�or
ETE-4D/50/95, press�and�hold SET to�select�NEUTRAL ZONE to�select�NEUTRAL ZONE and to�select ETE-4D/50/95.
and ETE-4D/50/95.
Press
SET
to�exit.
140mm
Wire�Stages:
Lower for HT
Higher for CL
G
G
Wire�Stages:
Lower for HT
Higher for CL
G
G
To�select�NEUTRAL ZONE�or
ETE-4D/50/95, press�and�hold SET for and
3sec.
to�select to�select�NEUTRAL ZONE
ETE-4D/50/95.
Press
SET
to�exit.
Wire�Stages:
Lower for HT G
Higher for CL G
Electro�Controls
ETE-�4D
4�Stage Thermostat www.electrocontrols.co.uk
SET
SET
SET
°C/°F
PB
50/60Hz
230VAC
STAGE1
STAGE1
50/60Hz
230VAC
STAGE2
L N
ETE-�4D
4�Stage Thermostat
L
L
50/60Hz
230VAC
N
N
NC1
NC1
NO1 L
NO1 L
NO1
C1 N
C1 N
C1 NC2 NO2
C2 C1
STAGE3
C3 C2
STAGE4
PR
D1
P4
S2
N1
S1
0V/
D0
P0
PB
P4
PA
N1
PR
0V/
P0
STAGE4
D1
S2
C4 C3
S1
NC4 NO4 C4
C2 C1
C2 NC3 NO3
C3 C2
C3 NC4 NO4
C4 C3
C4
NC4 NO4 C4
Electro�Controls
ETE-�4D
4�Stage Thermostat www.electrocontrols.co.uk
50/60Hz
230VAC
L N NC1 NO1 C1 NC2
VOLT FREE�230VAC�10(3)A
To�select�NEUTRAL ZONE�or To�select�NEUTRAL ZONE�or
ETE-68D/50/95, press�and�hold SET for 3sec.
and
Use to�select�NEUTRAL ZONE to�select ETE-68D/50/95.
for and
3sec.
Press to�select to�select�NEUTRAL ZONE
ETE-68D/50/95.
Press
SET
to�exit.
Wire�Stages:
Lower for HT G
Higher for CL G
Wire�Stages:
Lower for HT
Higher for CL
G
G
To�select�NEUTRAL ZONE�or
ETE-68D/50/95, press�and�hold SET for 3sec.
Use to�select�NEUTRAL ZONE and to�select ETE-68D/50/95.
Press
SET
to�exit.
Wire�Stages:
Lower for HT
Higher for CL
G
G
NO2 C2
STAGE1
STAGE1
Electro�Controls
ETE- 6 8 D
6/8�Stage Thermostat www.electrocontrols.co.uk
50/60Hz
230VAC
Electro�Controls
ETE- 6 8 D
6/8�Stage Thermostat www.electrocontrols.co.uk
L N
ETE- 6 8 D
6/8�Stage Thermostat www.electrocontrols.co.uk
50/60Hz
L
L
N
N NC1 NO1
50/60Hz
230VAC L N NC1 NO1
C1 N
STAGE2
C2 C1
STAGE3
ETE-8D
C1 N
C1 NC2 NO2
C2 C1
C2 NC3 NO3 C3 NC4 NO4
C4 C3
C4 NC5 NO5
C5 C4
C5 NC6 NO6
C6 C5
C6 NC7 NO7
C7 C6
C7 NC8 NO8
C8 C7
C8
NC8 NO8 C8
C1 NC2 NO2 C2 NC3 NO3 C3
STAGE4
C4 C3
C4
STAGE5
C5 C4
L
STAGE6
N NC1 NO1 C1 NC2 NO2 C2
C6 C5
STAGE7
C7 C6
°C/°F
NC6 NO6 C6 NC7 NO7 C7 NC8 NO8 C8
NC3 NO3 C3 NC4 NO4 C4
°C/°F
SET SET
STAGE8
°C/°F
SET
PB
PA
PR
P0
PB
S2
N1
S1
0V/
D0
P4
PA
N1
PR
0V/
P0
D1
P4
STAGE8
D1
S2
C8 C7
S1
NC8 NO8 C8
P0
P4
N1
PB
PA
PR
0V/
D0
D1
S2
S1
35mm
239mm 35mm
PB
PA
PR
P0
P4
N1
0V/
D0
D1
S2
S1
Connections
L+ and N-
NC,NO,C
S1 and S2
0V and N1
PA and PB
35mm
P4 and P0
P0 and PR
D1 and D0
230VAC or 24VAC/DC supply
Volt free relay connections
Sensor
Night setback
E10-S110 Remote set point adjuster
E10-P4
E10-P50 or E10-P95
E10-T
36
T: +44 (0) 1480 407074
\
F: +44 (0) 1480 407076
THErMOSTATS - ELECTrOnIC
SECTION
02
MOUNTING DIMENSIONS:
Type
ETE-2D
ETE-4D
ETE-6D and 8D
2 holes on diagonal at 117.15mm centres
2 holes on diagonal at 134.5mm centres
3 holes, X dim 215mm centres, Y dim 100mm centres
TIMING DIAGRAM:
The diagram below shows an example on the ETE-4D relay states with rising and falling temperatures for the situation with the Neutral Zone set at 2 stages of heating and 2 stages of cooling.
TIMING�DIAGRAM:
EXAMPLE: ETE-4D
NEUTRAL ZONE
=�ON
HTG
<
1 2 3 4 5 6 7 8
x x x x
>
CLG
DIFFERENTIAL PER�STAGE (DPS)
=�3°C
DIFFERENCE�B/W�STAGES (DBS)
=�2°C;
=�OFF
SETPOINT=�20°C
DPS1 DBS1-2
STAGE1
STAGE2
STAGE3
STAGE4
STAGE1�ON
DPS2 DBS2-3
TEMP( °C )
10 11 12 13 14 15 16 17
TEMPERATURE�FALLING
18 19
20
21
(SP)
22 23 24 25 26 27 28 29
TEMPERATURE�FALLING
30
SET UP
:
STAGE1
STAGE2
STAGE3
STAGE4
TEMP( °C )
DBS2-3 DPS3
DBS3-4 DPS4
10 11 12 13 14 15 16 17
TEMPERATURE�RISING
18 19
20
21
(SP)
22 23 24 25 26 27 28 29
TEMPERATURE�RISING
30
Turn on the power. Momentarily the display will show all the screen characters then the Product mode
EtE4D (if the product is ETE-4D),
EtE50 or ete95 and will settle to show the NEUTRAL ZONE, TEMPERATURE and the actual temperature. This is the main menu or Temperature screen.
To select the NEUTRAL ZONE (the number of HTG/CLG stages) and one of the Product modes ETE4D, ETE50 or ETE95, press the
SET button for 3 sec. The NEUTRAL ZONE cursor (
▌ ) and the last selected Product e.g. if the product is ETE-4D, ete4d mode will blink.
Use ▲ button to select the NEUTRAL ZONE required.
Use ▼ button to select either ETE4D, ETE50 or ETE95.
Press
SET briefly to exit.
Briefly press
SET repeatedly to select the required parameters of SET POINT, NIGHT SETBACK, TIME DELAY, DIFFERENTIAL PER STAGE and DIFFERENCE
B/W STAGES. The numerical values of these parameters will be blinking and the ▲▼ buttons can be used to set the numerical value required.
Whilst setting any parameter if the buttons are left for 10 sec the screen will return to the Temperature screen.
In the Temperature screen use of the
▲▼ buttons will toggle between °C and °F if required.
SEN0P
SENs
Lo
/
ErrPA
Sensor open circuit.
Sensor short circuit
Set temperature below or above product range
E10-S110 short circuit (ETE-2/4/6/8D only). Once this problem has been addressed press
SET to revert to normal operation.
Observe the local regulations regarding electrical installations.
Size the power supply cables according to the load.
The minimum sensor cable size is 7/0.2mm with a max length of 100m. screened cable is recommended and the screen should be earthed at the controller end only.
Keep supply and sensor cables away from other power cables and devices which may cause interference.
\
wattsindustries.co.uk
37
THErMOSTATS - ELECTrOnIC
ELECTrOnIC THErMOSTAT/THErMOMETEr WITH DISPLAY
ETE-D4/D6
Both products are Front Panel mounted with a digital display which indicates the sensed temperature.
The ETE-D4 is suitable for controlling valves, motors, fans etc and heating or cooling devices.
Type ETE-D6 is a STAND ALONE
THERMOMETER.
ETE-D4
ETE-D6
Volt free contacts
Accuracy approx 1% of range
ORDER DISPLAY UNIT + SENSOR ONLY
For use with E10.. SENSORS ONLY -
SEE SEPARATE DATA SHEET
NOT for use with E10.. REMOTE
ADJUSTERS & DISPLAY units or ETE.. THERMOSTATS
Enclosure Flammability = UL94-V2
Type Description Stages Display Range ° C Diff °C Supply 230VAC Power
Consumption
Digital -10/+50 or 25/95 0.5/10 adj 230VAC 10(3)A 3.3VA ETE-D4 Thermostat 1
ETE-D6 Thermometer –
OPTIONAL L24 = 24VAC supply
Digital -10/+50 or 25/95 – 230VAC – 3.3VA
DIMENSIONS
ETE-D4/D6
96
104
91
° C
48 PANEL CUT OUT
Mounting
Front Panel
Front Panel
Enclosure
IP00
IP00
44
WIRING:
95
Fixing brackets & screws are provided.
ETE-D6
SENSOR
S1 S2
F
0
E
4
C
Rotary switch: To select the temperature range:
Position E -10/+50 C Position F 25/95 C
8
L N
WIRING:
ETE-D4
SENSOR
S1 S2
4
F
0
E
C
8
L
+
_
N NC NO
+ T
Rotary switch : To select the temperature range
Position E -10/+50 C Position F 25/95 C
D4
C
On increase to the setpoint C-NO makes
On decrease (diff) C-NC makes
ADJUSTMENT:
INSTALLATION:
ETE-D4
Press either button on the front panel and the current Setpoint is displayed. Adjust to the required value by pressing the buttons (left = decrease, right = increase) The Diff is then displayed which can also be adjusted in the same way, if required.
After the adjustments have been made, the sensed temperature will be displayed automatically.
ETE-D4/D6
Terminals 0.5-2.5mm Sensor / control signal cable size 7/0 . 2 m m Max length 100m
Screened cable is recommended. The screen should be earthed at controller end only.
Keep sensor/control signal wires away from power cables/units which may cause interference.
38
T: +44 (0) 1480 407074
\
F: +44 (0) 1480 407076
ELECTRO CATALOGUE-UK-W-UK UK-W-UK-05-2017-Rev0
Watts Industries UK Ltd
Colmworth Business Park, Eaton Socon, St. Neots, PE19 8YX, UK
T: +44 (0) 1480 407074 • F: +44 (0) 1480 407076 [email protected] • wattsindustries.co.uk
© 2017 Watts
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project