PSF238TFIS:PSF221TFIS.qxd
15/09/2009 11:43 Page 1
D A T A S H E E T
MZX-e
Extinguishing Control Panel
Features:
Comprehensive facilities for gaseous extinguishing systems
Monitored inputs for gas discharged, gas low, isolation valve closed/abnormal, gas trapped in manifold
Control inputs for auto/manual, gas hold, gas abort
1 minute actuator cut off option
Monitored actuator/solenoid release
Extensive disablement options
Common fire, fault, relay / monitored output facilities
1st, 2nd, 3rd stage and gas discharged relay / monitored output facilities
Reset relay facilities
Intrinsically safe barrier settings
Metron or solenoid compatible
Single or double knock operation
Pre-discharge delay adjustable from 0 to 60 seconds
Discharged indication with or without pressure switch
Inhibit silence alarms until gas discharged
Latching or non latching fault indication option
Option for rapid buzzer pulse when gas imminent
One man zone and sounder test
Approval to BS EN 12094-1:2003 additional options
Approval to BS EN 54-2 and 4
Designed to BS 7273-1:2000
Easily removable chassis
MZX-e
The MZX-e gaseous extinguishant control panel is powerful yet user-friendly and is designed and manufactured to a high standard. The panel features approval to BS EN 12094-
1:2003, BS EN 54-2 and 4 and is designed to BS 7273 part 1.
The panel has extensive configuration options but is easy to install, programme and operate. The removable chassis enables the engineer to “first fix” an empty cabinet and then fit the chassis at the commissioning stage.
This is supported by comprehensive documentation on commissioning, operating, maintenance and fault finding. In addition there is a comprehensive range of compatible accessories available to meet most customer requirements.
PSF238TFIS:PSF221TFIS.qxd
15/09/2009 11:43 Page 2
MZX-e Extinguishing Control Panel
Operation
Three fully-monitored detection zones are provided. Zones 1 and 2 normally provide first stage and second stage fire conditions to allow extinguishant discharge (coincidence detection zones). Zone
3 is an auxiliary zone for detection only purposes. Zone 4 is used as a manual release zone.
Facilities
Three fully-monitored alarm circuits are provided, each rated at
0.5A with various configuration options via the engineers DIL switch settings. Two circuits are designed to provide audible warning of any fire condition and one circuit to provide an individually distinct audible warnings of the pre-discharge, discharged and emergency hold condition.
Two fully-monitored actuator/solenoid circuits, each rated at 1A, operate simultaneously upon “extinguishant release”.
An RS485 multi-drop circuit link supports up to 7 Status
Controller/Indicators of any type mixed on the communication path. Additional terminals and configuration options allows the engineer to configure the manual release, abort and hold switches to either data comms or hard wired inputs as required.
Normally-open inputs provide for remote evacuate, silence alarms, system reset, lock-off input, low pressure and gas discharged pressure switch input.
Outputs are provided for first stage signalling, second stage signalling, system discharged, common fire and common fault .
These outputs may be configured as either Volt-Free C/O contacts or monitored 24V (50mA) outputs. A system reset Volt-Free relay is also provided.
Configuration
The use of DIL switches on the internal motherboard enables the engineer to easily configure the extensive options available and view the panel’s configuration upon any return visit.
PSF238TFIS:PSF221TFIS.qxd
15/09/2009 11:43 Page 3
MZX-e Extinguishing Control Panel
* = Open & short cct flt monitored I/P
Double knock detection zones
*Zone 1
*Zone 2
Aux detection zone
*Aux Zone
Gas discharged pressure switch
*Gas Released
Fire
Z1
Fault/
Disabled
Z1
Fire
Z2
Fault/
Disabled
Z2
Fire
Aux
Fault/
Disabled
Aux
Gas
Released
Internal
Fault
Internal
Sndr 1 flt
Sndr 2 flt
Internal
Ext Sndr Fault
Internal
Act 1 flt
Act 2 flt
General
Fire
Sounder
Test
General
Fire
Sounder
Fault/
Disabled
Extinguishing
Disabled
** = Open & short circuit monitored output
Gen Sndr 1**
Gen Sndr 2**
Ext Sndr**
Act 1**
Act 2**
Continuous online Z1, Z2, Aux Zone.
Remote Sound Alarm
Max O/P: 0.5A
Pulsed on Z1/Z2 Double K in auto on Man Rel.
Continuous on actuator activation or disch P/S I/P signal Active
Max O/P: 0.5A
Operating on pre-discharge timer
Ended or Man Rel in immediate mode
Max O/P: 1A
Gas Low
(Low pressure switch
/ low weight)
Gas isolation valve.
(Valve Stuck)
(Valve Closed)
- see valve wiring diagram
Gas trapped in manifold
Conventional
Manual Release
Zone
Conventional
E Hold Input
Conventional
Abort Input
Conventional
Auto/Manual
Switch Input
To Status
Indicator /
Controller
*Gas Low
*Isol Valve
Abnormal
*Isol Valve
Closed
*Gas Trapped
Pressure switch
*Manual
Release
*Emergency
Hold
*Emergency
Hold
*Auto/Manual
Lock Off
RS485 serial data (SLU)
+24V AUX 1A Output
0V AUX 1A Output
*RCI
Remote Controls Input:
4K7 = Sound Alarms
1K8 = Silence Alarms
560R = Reset Panel
Gas
Low
Internal
Fault Open & Short cct flt monitored I/P.
680 Ohm = Ext Low
Isolation
Valve
Abnormal
Isolation
Valve
Closed
Internal
Fault
Open & Short cct flt monitored I/P.
680 Ohm = V/Closed
2K2 = V/Abnormal
Gas
Trapped in
Manifold
Internal
Fault
S/D
O/P
1 flt
Internal
S/D
O/P
2 flt
S/D
O/P
3 flt
Each Plant Shutdown O/P has:
1 O/P link configurable as fault monitored/powered when active (as per fire routing O/P) or 1 V/F C/O relay contact rated 1 Amp @ 24 VDC
1st stage Plant
Shutdown** Active on any fire Z1 or Z2 in auto, Man Rel or Gas
Released P/S signal
2nd stage Plant
Shutdown**
Active on coincidence fire on
Z1 or Z2 in auto, Man Rel or
Gas Released P/S signal
Panel
Manual
Release
Internal
Fault
Panel
MR
Man
Rel
Active
Man
Rel
Fault/
Disabled
Internal
Fault
Panel
MR
E Hold
Active
Internal
Fault
E Abort
Active
Internal
Fault
Auto &
Manual
Manual
Only
Internal
Fault
Gas Release (SLU)
Gas Manual (SLU)
Gas Auto (SLU)
Timer Hold (SLU)
Release Aborted (SLU)
Release Disabled (SLU)
Release Count Down (SLU)
Internal
SLU
Fault
Aux DC Supply Max O/P
1A Fused
Remote
Sound
Alarms
Active
RCI
Fault
Extinguishing
Reset
Inhibit
Active
Illuminates steady while Extinguishing
Reset is Inhibited
S/D Outputs
Disabled
3rd stage Plant
Shutdown**
Active on Actuators operated
(if no Discharged Pressure
Switch) or Gas Released P/S signal
Link configurable O/Ps:
Link ON:
Open/short cct fault monitored, powered at
24V DC when active
Link OFF:
1 x Volt-Free Changeover relay contact
(Rated 1A @ 24VDC)
Internal
Gas Rel Sig
(Routing) Fault
Fire Sig
(Routing)
Active
Fault/
Disabled
Fire Sig
(Routing)**
Operating on any fire
Z1,Z2 Aux Zone
Fault Sig
(Routing)
Fault /Disabled
Gas Rel
Signal
(Routing)
Active Disabled
Fire Sig
(Routing)**
Gas Released
(Routing)**
Operating (de-energising) on any fault including
Valve Abnormal but not
Valve Closed
Operating on Gas P/S active I/P or Actuator operated when in “No
Discharge P/S” mode
RP - E/Hold Active or Panel in Auto
RP - E/Hold Active or Panel in Manual
DIL Switch
Selectable
RP - Actuators (Extinguishing) Disabled
Open collector O/Ps each rated 50mA
RP - Isol Valve Closed
RP - Isol Valve Abnormal
RP - Fire Z1
RP - Fire Z2
RP - Fire Aux Zone
RP - Manual Release Operated
Max O/P 0.25A (Fused)
1 x VF C/O relay contact
(Rated 1 Amp @ 24VDC)
+24V Aux 250mA Output
Aux Reset
Operating for 10 seconds after operation of Fire Reset switch
PSF238TFIS:PSF221TFIS.qxd
15/09/2009 11:43 Page 4
Status Indicators
Fully Specified Status / Control Indicator (SLU 3)
Release Aborted (Yellow)
Release Held (Yellow)
Discharged (Red)
Automatic & Manual (Green)
Manual Only (Yellow)
Release Disabled (Yellow)
SLU Fault (Yellow)
Press to Abort Release (White)
Press & hold to Hold
Release (White)
Manual Release (Yellow)
Test Lamps
Automatic & Manual
Manual Only
Secinds until Discharge
RS485 data and 28/0V
DC to next SLU
Auto/manual selection I/P from door lock
(Alternative)
Open/short circuit fault monitored
10K = Auto
250 Ohm to 1K = Manual
O/C or S/C = Manual + Fault
1K Ohm
Switches in Auto position
(4x max)
10K Ohm EOL
Basic Status / Control Indicator (SLU 2)
Discharged (Red)
Automatic & Manual (Green)
Manual Only (Yellow)
Release Disabled (Yellow)
SLU Fault (Yellow)
Manual Release (Yellow)
RS485 data and 28/0V
DC to next SLU
Test Lamps
Automatic & Manual
Manual Only
Auto/manual selection I/P from door lock
(Alternative)
Open/short circuit fault monitored
10K = Auto
250 Ohm to 1K = Manual
O/C or S/C = Manual + Fault
Status Lamp Unit (SLU 1)
Discharged (Red)
Automatic & Manual (Green)
Manual Only (Yellow)
Test Lamps
Release Aborted (Yellow)
Release Held (Yellow)
Release Disabled (Yellow)
SLU Fault (Yellow)
1K Ohm
Switches in Auto position
(4x max)
RS485 data and 28/0V
DC to next SLU
10K Ohm EOL
Weatherproof Basic Status / Control Indicator (SLU 4)
Discharged (Red)
Automatic & Manual (Green)
Manual Only (Yellow)
Release Aborted (Yellow)
Release Held (Yellow)
Release Disabled (Yellow)
SLU Fault (Yellow)
RS485 data and 28/0V
DC to next SLU
Automatic & Manual
Manual Only
Test Lamps
Auto/manual selection I/P from door lock (Alternative)
Open/short circuit fault monitored
10K = Auto
250 Ohm to 1K = Manual
O/C or S/C = Manual + Fault
1K Ohm
Switches in Auto position
(4x max)
10K Ohm EOL
For further information on how we can help you please visit our website at www.tycofis.com or e-mail us on [email protected]. The right is reserved to modify or withdraw any product or service without notice. PSF238TFIS Issue 2 Sept 2009 © 2009