L16RE-2V data shEEt
L16RE-2V data sheet
for Renewable Energy and Backup Power Applications
PREMIUM LINE
Model:
L16RE-2V with Bayonet Cap
Dimensions:
inches (mm)
Battery:
Flooded/wet lead-acid battery
Color:
Maroon (case/cover)
Material:Polypropylene
Product Specification
ENERGY
(kWh)
CAPACITY A Amp-Hours (AH)
BCI
GROUP
SIZE
TYPE
903
L16RE-2V*
2-Hr
Rate
5-Hr
Rate
10-Hr
Rate
20-Hr
Rate
722
909
1021
1110
48-Hr
Rate
72-Hr
Rate
100-Hr
Rate
100-Hr
Rate
VOLTAGE
TERMINAL
Type
DIMENSIONS B Inches (mm)
Length
Width
Height C
11-5/8 (295)
7 (178)
17-11/16 (450)
WEIGHT lbs.
(kg)
Premium Line - DEEP-CYCLE FLOODED BATTERIES
1182
1210
1235
2.47
2 VOLT
Charging Instructions
5
119 (54)
TERMINAL CONFIGURATIONS
Charger Voltage Settings (at 77°F/25°C)
5
LT
Voltage per cell
Absorption charge
2.35-2.45
Float charge
2.20
Equalize charge
2.58
Do not install or charge batteries in a sealed or non-ventilated compartment. Constant under or
overcharging will damage the battery and shorten its life as with any battery.
L-Terminal
Terminal Height Inches (mm)
1-3/4 (43)
Torque Values LB-IN (Nm)
100 – 120 (11 – 14)
Through-hole Diameter (mm)
3/8 (10)
* Polyon™ Case
operational data
Operating Temperature
Self Discharge
Specific Gravity
-4°F to 113°F (-20°C to +45°C). At temperatures
below 32°F (0°C) maintain a state of charge
greater than 60%.
Up to 4% per week
The specific gravity
at 100% state-ofcharge is 1.280
Premium Line batteries manufactured prior to March 2012 have 1.260 SG value.
Charging temperature compensation
To the Voltage Reading -- Subtract 0.005 volt per cell (VPC) for every 1°C above 25°C or add 0.005 volt per cell for every 1°C below 25°C.
Expected life vS. Temperature
Chemical reactions internal to the battery are driven by voltage and temperature. The higher the battery temperature, the faster chemical reactions will
occur. While higher temperatures can provide improved discharge performance the increased rate of chemical reactions will result in a corresponding loss of
battery life. As a rule of thumb, for every 10°C increase in temperature the reaction rate doubles. Thus, a month of operation at 35°C is equivalent in battery
life to two months at 25°C. Heat is an enemy of all lead acid batteries, FLA, AGM and gel alike and even small increases in temperature will have a major
influence on battery life.
The amount of amp-hours (AH) a battery can deliver when discharged at a constant rate at 80°F (27°C) for Premium Line and maintain a voltage above 1.75 V/cell. Capacities are based on
peak performance.
Dimensions are based on nominal size. Dimensions may vary depending on type of handle or terminal. Batteries to be mounted with .5 inches (12.7 mm) spacing minimum.
Dimensions taken from bottom of the battery to the highest point on the battery. Heights may vary depending on type of terminal.
Trojan’s battery testing procedures adhere to both BCI and IEC test standards.
Made in the USA
Page 1 of 2
L16RE-2V_TRJNRE_ DS_1012
A.
B.
C.
L16RE-2V data sheet
for Renewable Energy and Backup Power Applications
PREMIUM LINE
Battery dimensions (shown with LT)
16-11/16
(424)
17-11/16
(450)
Height
15-7/8
(402)
11-5/8
(295)
7
(178)
Width
Length
Typical cycle life in a stationary application
140
60
4000
120
50
3500
100
3000
80
2500
60
2000
40
4500
Number of Cycles
Percent capacity vs. temperature
40
30
20
10
1500
0
20
1000
-10
0
500
-20
-20
0
20%
30%
40%
50%
60%
70%
Depth-of-Discharge
80%
90%
100%
-30
-40
0%
20%
40%
60%
80%
100%
-40
120%
call 800.423.6569 or + 1.562.236.3000 or visit www.trojanbatteryRE.com
12380 Clark Street, Santa Fe Springs, CA 90670 • USA or email [email protected]
© 2012 Trojan Battery Company. All rights reserved. Trojan Battery Company is not liable for damages that may result from any information provided in or omitted from this
publication, under any circumstances. Trojan Battery Company reserves the right to make adjustments to this publication at any time, without notices or obligation.
Page 2 of 2
L16RE-2V_TRJNRE_ DS_1012
Trojan batteries are available worldwide.
We offer outstanding technical support, provided by full-time application engineers.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement