Paragon Focus RS Slide Control fireplace Owner's Manual
Below you will find brief information for fireplace Focus RS Slide Control. This is a room sealed live fuel effect gas fire that does not require a conventional chimney and can be installed against an outside wall. The appliance is fitted with a flame supervision device that constantly monitors the flame and will cause the gas to be switched off if the flames are extinguished. The appliance includes a slide control for adjusting the flame height and a glass panel that acts as a dress guard. It can be operated on either its low or high setting and has a safety device to prevent overheating.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
PARAGON FIRES
PARAGON FOCUS RS
Slide Control
ROOM SEALED INSET LIVE FUEL EFFECT GAS FIRE
OWNER'S
MANUAL
Please read these instructions carefully before you start using the appliance
Keep this booklet handy for future reference
This appliance is for use in GREAT BRITAIN or
IRELAND only
TELFORD
SHROPSHIRE
ENGLAND
PARAGON FOCUS RS SC Instructions
CONTENTS
User‟s Instructions
SECTION ONE Important Information
Consumer Protection
Health and Safety Notice
SECTION TWO Introduction
SECTION THREE Operation
Lighting the Fire
Turning Off the Fire
SECTION FOUR Cleaning and Coal Laying
Cleaning Decorative Trim
Cleaning: Black Painted Surfaces
Cleaning: Glass Panel
Cleaning and Replacing Coals
SECTION FIVE Replacement Parts
Installation Instructions
PAGE
SECTION SIX Appliance Data
SECTION SEVEN Regulations and Warnings
12
13
14
SECTION EIGHT Siting the Appliance
General Requirements
SECTION NINE Preparing the Appliance for Installation
14
15
16
SECTION TEN Install the appliance
Installing the Appliance into a Cavity Wall 16
Installing the Appliance into a Deep Rebated Surround or Dummy Breast 17
6
6
6
5
5
5
3
3
3
3
5
6
7
11
12
Installing the Appliance into a Timber Framed Dwelling
Connecting the Gas Supply
Checking Gas Soundness
SECTION ELEVEN Assemble the Appliance
SECTION TWELVE Check Operation of Fire
Check Burner Pressure and General Operation
SECTION THIRTEEN Instruct and Advise Customer
Maintenance Instructions
SECTION FOURTEEN Maintenance Instructions
General
Replacement of Gas Control
Replacement of Injector
Replacement of the Micro Switch
Replacement of the Thermocouple
Replacement of Pilot Injector
Replacement of Spark Electrode
Replacement of Spark Generator
21
21
22
22
22
22
22
19
20
20
20
21
23
23
23
23
23
2 5307LT(4:09/10)
PARAGON FOCUS RS SC
Users Instructions
SECTION ONE Important Information
Consumer Protection Information
As manufacturers and suppliers of heating products, we take every care, as far as is reasonably practicable, that these products are so designed and constructed as to meet the general safety requirement when properly used and installed. To this end, our products are thoroughly tested and examined before despatch.
IMPORTANT NOTICE: Any alteration that is not approved by the appliance manufacturer could invalidate the approval of the appliance, operation of the warranty and could affect your statutory rights.
Health and Safety Notice
Important
This appliance could contain some of the materials, indicated below, that could be interpreted as being injurious to health and safety. It is the users / installers responsibility to ensure that the necessary personal protective clothing is worn when handling these materials, see below for information.
Artificial Fuels, Mineral Wool, Insulation Material, Refractory/Ceramic Fibres, Glass Yarn - may
be harmful if inhaled, may be irritating to skin, eyes, nose and throat.
When handling
avoid inhaling and contact with skin or eyes. Use disposable gloves, facemasks
and eye protection. After handling wash hands and other exposed parts. If a vacuum is used for cleaning the coals or cleaning after servicing / installation it is recommended that it be of the type fitted with a HEPA filter.
Disposal of refractory/ceramic materials
. To keep dust to a minimum these materials
should be securely wrapped in polythene and be clearly labelled ‘RCF waste’. These materials are not classified as ‘hazardous waste’ and should be disposed of at a site licensed for the disposal of industrial waste.
The PARAGON FOCUS RS SC is an inset room sealed decorative fuel-effect gas appliance.
The PARAGON FOCUS RS SC is available in Natural Gas (G20 @ 20 mbar Only). The marking
(G20 for natural gas) on the packaging and the data badge specify the gas for which the appliance has been factory set. Note: These appliances should only be used on the
appropriate gas specified. They are not suitable for conversion from one gas to the other.
Failure to install appliance correctly could lead to prosecution.
In GB (Great Britain), the appliance must be installed and serviced by a competent person i.e.
CORGI-registered, in accordance with the GAS SAFETY (INSTALLATION AND USE)
REGULATIONS, The Building Regulations (or The Building Regulations (Scotland) or The
Building Regulations (Northern Ireland)) and The Current I.E.E. Wiring Regulations, if appropriate.
In IE (Ireland), the appliance must be installed and serviced by a competent person and installed in accordance with the current edition of I.S.813 Domestic Gas Installation, the current Building
Regulations and the current ETCI rules for electrical installation, if appropriate.
The PARAGON FOCUS RS does not require a chimney, but must be installed against an outside wall.
It is important that the flue terminal is regularly checked and kept clear at all times.
If the terminal is accessible to people (i.e. less than 2m above a walkway, balcony etc.) the terminal guard must be fitted to prevent access to the flue outlet, which becomes hot when the fire is in use.
All combustible material must be removed from behind the fire and fire trim.
3 5307LT(4:09/10)
PARAGON FOCUS RS SC Users Instructions
SECTION ONE Important Information Cont.
As the PARAGON FOCUS RS SC is a room sealed appliance (i.e. air for the combustion process is taken from outside the room) no purpose built ventilation is requires.
The PARAGON FOCUS RS SC is designed and tested to meet the requirements of the European
Standard EN 613.
Although the PARAGON FOCUS RS SC is fitted with a glass front which acts as a dress guard it is strongly recommended that a fireguard should be used for the protection of children, the elderly or infirm. Fireguards should conform to B. S. 6539 (1984) (Fireguards for use with solid fuel appliance).
The slot located at the top of the PARAGON FOCUS RS SC are the hot air outlets and as such must not be obstructed in any way (particularly by clothes or other combustibles). In addition the base of the appliance should not be obstructed by such items as this may adversely affect the performance of the appliance.
Care should be taken to prevent any damage being caused to surrounding soft furnishings or decoration. Many wall coverings may become discoloured if placed too close to the appliance, it is strongly recommended that any proposed wall covering intended for use immediately above the appliance should be tested in the hottest position (immediately above) first. Run the fire on high over a few days
The first time you light your new appliance a smell may occur due to its new condition. This is quite normal and will soon disappear after a few hours use at maximum setting (open a window until the smell disappears).
The appliance MUST NOT be used if the glass panel is not correctly fitted or if this panel is cracked or broken.
Any debris should be cleaned from the appliance. A vacuum cleaner can be used but only after all the loose coals have been removed.
Prior to removing or cleaning the fuel bed components refer to the ‘Health and Safety
Notice’ located on page 3 of this booklet.
The appliance should be serviced annually by a competent person i.e. a CORGI registered
engineer in accordance with these instructions.
The glass or any part of the appliance MUST NOT be cleaned or wiped whilst the appliance is
HOT, to do so could be dangerous and may damage the paintwork of the appliance.
The cast fire front or Fascia casing MUST BE positioned in front of the fire whilst it is burning.
A where a fire front (fret) is used with this appliance it must conform to the following:
It must be made from non-combustible material.
Its general construction should enable it to stand firmly across the full width of the burner.
The design of the fire front (fret) must have a removable ashtray cover (lower section).
The ash tray cover must have cut outs and or holes which provide ventilation to the underside of the burner.
The effective area of ventilation through the ash tray cover must be greater than 1365mm
2
(2.12 sq. ins.)
Effective Ventilation
1365mm
2
MINIMUM
REMOVABLE COVER
4 5307LT(4:09/10)
PARAGON FOCUS RS SC Users Instructions
SECTION TWO Introduction
The PARAGON FOCUS RS SC is an inset room sealed live fuel-effect gas appliance designed for use in locations that do not have a conventional chimney. The appliance must be installed against an outside wall because the air to support combustion is taken from the outside and the products of combustion are expelled to the outside.
The appliance incorporates a safety device in the form of a FLAME SUPERVISION DEVICE, which constantly monitors the flame and will cause the gas to be switched off if the flames are extinguished for any reason. THIS DEVICE MUST NOT BE OVERRIDDEN. If this situation occurs on a regular basis have the appliance checked by a qualified engineer. The problem may be due to a blocked or restricted flue.
Before removing the fret, trim, glass or fuel bed for cleaning the fire should be turned off, and left to cool down.
NOTE: In use some discoloration of the components will take place in the combustion box, this is normal, but can be kept to a minimum if the coals are placed correctly (i.e. after cleaning). See
Section 4.
As with all heating appliances certain areas (Working Surfaces) become very hot when the appliance is in use. Only the ashpan knob and the gas control knob should be touched when the fire is being used.
SECTION THREE Operation
Do not use this appliance without the glass panel fitted, or if this panel is cracked or broken.
WARNING: If the burner or pilot is extinguished for any reason, do not attempt to re-light the pilot for at least three minutes.
The full lighting procedure is as follows: - a. Push slide control lever down, as far as possible a clicking noise will be heard and the pilot will light, HOLD DOWN FIRMLY FOR ABOUT 20 SECONDS. b. c.
Allow the lever to spring up the pilot light should remain alight and the main burner should light on its low setting.
Should the pilot fail to light, pull the lever fully up to turn off the appliance, wait 3 d. minutes and repeat the procedure (a &b). If the pilot does not light and no clicking noise is heard replace the battery and try again.
After lighting the pilot flame and the main burner on its low setting the control lever may be lifted until slight resistance is felt, this will put the burner on its high setting. e. f. g. h. extent.
To completely extinguish the fire, pull the lever up past the resistance to its fullest
The fire may be operated on either its low or high setting.
It is recommended that the appliance is operated on its high setting for a short period before adjusting to the low setting.
If the ignition does not operate fit a new 9V battery (PP3/MN1602) to the ignition unit, located behind the fret adjacent to the gas inlet pipe, and repeat ignition procedure prior to reporting a fault.
5 5307LT(4:09/10)
PARAGON FOCUS RS SC
Users Instructions
SECTION FOUR Cleaning & Fuel Bed Laying
Warning: -Before you clean any part of the appliance ensure that the appliance is switched off and cool.
CLEANING: DECORATIVE TRIM
The Decorative finish of the trim is coated with a high temperature lacquer, it should be wiped with a soft, clean, dry, cloth only.
The trim should be removed for cleaning. The fret should be removed before removing the trim, which is held in place by four magnets.
CLEANING: BLACK PAINTED SURFACES
These surfaces should be dusted regularly and any marks removed with a soft cloth.
Abrasive or chemical cleaner should never be used.
CLEANING: GLASS PANEL
From time to time it may be necessary to clean the glass panel.
We recommend you use a Ceramic Hob Cleaner (brands such as HOB BRITE and VITRO CLEN
have been found to be acceptable) these are available from most leading Supermarkets.
Remove the glass panel as follows:
Remove ash pan cover and fret.
Remove decorative trim (held in place with four magnets).
Slacken but do not remove the 4 nuts securing the bottom glass clamp.
Remove the 3 screws located down each side. Note: when they are replaced ensure the glass is
central and these brackets pushed up to the side of the glass before tightening the finger nuts.
While supporting the glass panel, remove the 4 nuts securing the top glass clamp, remove the top clamp and slide the glass out gently.
Lay the glass panel down on a flat working surface on top of an old opened newspaper with the side to be cleaned uppermost take care not to erase the dot printing
Follow the Instructions on the Hob Cleaner Bottle.
On stubborn stains (where the appliance has been used for a long period without glass panel being cleaned), use a new Brillo Pad well wetted with the Hob cleaner applied directly to it.
Ensure all the residues of the cleaner are removed with a damp cloth and the glass panel is completely dry before fitting to the appliance.
6 5307LT(4:09/10)
PARAGON FOCUS RS SC
Users Instructions
SECTION FOUR Cleaning & Fuel Bed Laying Continued
Note: - If the fuel bed has not been placed correctly, causing the gas flame to contact the glass this may result in glass staining that cannot be removed by cleaning.
Re-assemble in reverse order ensuring the seal is compressed evenly at the top and bottom
Re-fit the top outlet grill before re-fitting the trim and fret and before re-lighting.
CLEANING AND REPLACING Fuel Bed Parts
Important: - Refer to
the ‘Health & Safety Notice located on page 3 of this booklet before cleaning or replacing any refractory material.
Use only the Fuel Bed part provided NO OTHER FUEL BED PARTS SHOULD BE
ADDED to the appliance
If any Fuel Bed Parts are broken then they must be replaced before the appliance is used.
Note:- There are three possible fuel bed arrangements
COAL, PEBBLE or DRIFTWOOD
Please check the label on the appliance carton to ensure you have the correct fuel bed
The fuel bed parts are delicate and should be handled with great care.
The loose part should be removed for cleaning. They can be brushed very gently with a soft brush to remove dust or any deposits.
A vacuum cleaner may only be used after all the loose coals have been removed.
COAL BED LAYOUT
The Coal set as shown consists of:
Rear Matrix
Front Matrix
Twelve Individual Coals
Five “A” Shaped
Seven “B” Shaped
The Rear Matrix is located so that it fits behind the burned (ensure it is not placed over the burner)
The Front Matrix is located as shown in front of the burner
.
7 5307LT(4:09/10)
PARAGON FOCUS RS SC
Users Instructions
SECTION FOUR Cleaning & Fuel Bed Laying Continued
Position two “A” coals and two “B” coals as shown in the picture.
Position two “A” coals and three “B” coals as shown in the picture.
Finally position one “A” coal and two “B” coals as shown in the picture
That completes the coal bed assembly
Go to section eleven to complete the appliance assembly
Ensure the glass panel and other associated parts are fitted before lighting the appliance
8 5307LT(4:09/10)
PARAGON FOCUS RS SC
Users Instructions
SECTION FOUR Cleaning & Fuel Bed Laying Continued
The Pebble set as shown consists of:
Rear Matrix
Front Matrix
Twelve Individual Pebbles
Marked on their underside
“2B” 4off
“3B” 1off
“4B” 2off
“2G” 2off
“4G” 3off
The Rear Matrix is located so that it fits behind the burned (ensure it is not placed over the burner
The Front Matrix is located as shown in front of the burner
Position the five pebbles shown with the marking placed below or to the rear of the pebble.
Position the four pebbles shown with the marking placed below or to the rear of the pebble
9 5307LT(4:09/10)
PARAGON FOCUS RS SC
User Instructions
SECTION FOUR Cleaning & Fuel Bed Laying Continued
Finally position the three pebbles shown with the marking placed below or to the rear of the pebble
That completes the pebbles bed assembly
Go to section eleven to complete the appliance assembly
Ensure the glass panel and other associated parts are fitted before lighting the appliance
The Driftwood set as shown consists of:
Rear Matrix
Front Matrix
Nine Individual Driftwood parts
Marked on their underside
“D1” 1off “D15” 1off
“D2” 1off
“D12” 2off
“D13” 1off
“D16” 1off
“D24” 2off
The Rear Matrix is located so that it fits behind the burned (ensure it is not placed over the burner)
The Front Matrix is located as shown in front of the burner.
Position the four driftwood shapes shown with the marking placed below or to the rear of the shape.
10 5307LT(4:09/10)
PARAGON FOCUS RS SC
User Instructions
SECTION FOUR Cleaning & Fuel Bed Laying Continued
Position the three driftwood shapes shown with the marking placed below or to the rear of the shape.
Finally position the last two driftwood shapes shown with the marking placed below or to the rear of the shape.
That completes the pebbles bed assembly
Go to section eleven to complete the appliance assembly
Ensure the glass panel and other associated parts are fitted before lighting the appliance
SECTION FIVE Replacement Parts
The only user removable parts are: -
Cast fret
Top Outlet Grill
Glass panel, fixing clamps and fret apron
Decorative Trim
Refractory fuel bed components
11 5307LT(4:09/10)
PARAGON FOCUS RS SC
Installation Instructions
SECTION SIX Appliance Data
Wall Cut-out dimensions:
Overall dimensions:
Forward Projection: 90mm, (From fireplace opening
Including typical fret.)
Weight: 38.5kg (Boxed excluding fret)
37kg (Unboxed excluding fret)
Flue Length and duct length:
Height
Width
Height
Width
553mm
405mm
601mm
501mm
100mm (minimum) to l metre (maximum)
Standard length supplied with fire-400mm (200mm after cutting).
Additional 400mm & 1m tubes supplied as optional extras. (No bends should be fitted in the flue pipe)
Pressure Test Point Location:
Gas Connection:
Gas inlet elbow
8.0mm O/D, tube.
Data Badge Location: On base of appliance, behind decorative fret.
Note: When flue length exceeds 200mm you may experience outing from cold. In this case it may be necessary to remove the restrictor plate. Please ensure that the flue pipe has been adequately sealed before undertaking removal of this plate.
MODEL Natural Gas(G20) Version
Category of appliance
NO
X
Class
Efficiency Class
Gas Category
C
II
3
1
I
2H
Gas Type
Gas Pressure +/- 1.0mbar
Gas Input (Max)
(Min)
G20 Natural Gas
20 mbar
5.2 kW Gross (0.49m
3
/hr)
2.4 kW Gross
Injectors size 360
NOTE: The efficiency of this appliance has been measured as specified in BS EN613-2001 and the result is 76.2.% natural gas The gross calorific value of the fuel has been used for this efficiency calculation. GasTec have certified the test data from which it has been calculated. The efficiency value may be used in the UK Government‟s Standard Assessment Procedure (SAP) for energy rating of dwellings.
12 5307LT(4:09/10)
PARAGON FOCUS RS SC Installation Instructions
SECTION SEVEN Regulations and Warnings
THIS APPLIANCE MUST ONLY BE INSTALLED IN GREAT BRITAIN OR IRELAND.
THE APPLIANCE IS AVAILABLE IN NATURAL GAS only.
CONFIRM THAT THE APPLIANCE IS SUITABLE PRIOR TO INSTALLATION (G20 FOR
NATURAL GAS) (REFER TO DATA BADGE ON BASE OF APPLIANCE). NOTE: THE
APPLIANCE SHOULD ONLY BE USED ON THE APPROPRIATE GAS SPECIFIED. IT IS NOT
SUITABLE FOR CONVERSION FROM ONE GAS TO THE OTHER.
THIS APPLIANCE MUST BE INSTALLED ON A SUITABLE OUTSIDE WALL.
NO SPECIAL VENTILATION BRICKS OR VENTS ARE REQUIRED INTO THE ROOM
CONTAINING THE APPLIANCE.
IT IS THE LAW THAT ALL GAS APPLIANCES MUST BE INSTALLED BY A COMPETENT
PERSON; I.E. A CORGI REGISTERED INSTALLER, IN ACCORDANCE WITH THE CURRENT
GAS SAFETY (INSTALLATION AND USE) REGULATIONS 1994 (AS AMENDED), ALL
RELEVANT PARTS OF THE LOCAL AND NATIONAL BUILDING REGULATIONS AND ALL
RELEVANT RECOMMENDATIONS OF THE CURRENT BRITISH STANDARDS. FAILURE TO
DO SO COULD LEAD TO PROSECUTION.
THE FOLLOWING ARE THE RELEVANT CODES OF PRACTICE AND BRITISH STANDARDS: -
B.S. 5871 PART 2 B.S. 5440 PART 1
B.S. 6891 B.S. 1945
Note:- This appliance must be installed to current versions of the above standards and include any relevant amendments.
THE BUILDING REGULATIONS ISSUED BY THE DEPARTMENT OF THE ENVIRONMENT.
THE BUILDING STANDARDS (SCOTLAND) (CONSOLIDATED) REGULATIONS ISSUED BY THE
SCOTTISH DEVELOPMENT OFFICE.
PRIOR TO THE INSTALLATION ENSURE THAT THE LOCAL DISTRIBUTION CONDITIONS
(INDENTIFICATION OF TYPE OF GAS AND PRESSURE) AND ADJUSTMENT OF THE
APPLIANCE ARE COMPATIBLE. (G20 @ 20mbar Natural Gas Version)
WARNINGS
As this appliance has components, which get very hot as with all such fires, it is recommended that a fireguard should be used for the protection of children, the elderly, or the infirm. Fireguards should conform to B.S.6539 (1984) (Fireguards for use with solid fuel appliances).
During initial use, an odour may be evident. This will soon disappear if the fire is run on its maximum setting for a few hours.
Care must be taken to prevent any damage being caused to surrounding soft furnishing or decoration, e.g. wall coverings may become discoloured if placed too close to the appliance.
IMPORTANT NOTES
This appliance is a fuel effect gas fire designed for use in locations that do not have a conventional chimney.
13 5307LT(4:09/10)
PARAGON FOCUS RS SC Installation Instructions
SECTION EIGHT Siting the Appliance
(When installing in a timber framed dwelling reference must be made to the specific installation requirements stated in Section 10 Installing the Appliance in Timber Framed Dwelling).
THERE ARE TWO TYPES OF INSTALLATION (into conventional masonry walls): -
The appliance body can be recessed back into the brickwork cavity so that the appliance is flush fitting with the wall or fireplace back panel, see Installation Instructions,
OR
With a dummy chimneybreast constructed forward into the room to take up the 180mm depth of the firebox. This depth can be reduced if a deep rebated surround is also used the rebate depth can be deducted from the dummy breast depth
Any surround used must meet the specification stated later in this section. Prior to installing the appliance all combustible materials must be removed from the rear faces as described in Section 10.
GENERAL REQUIREMENTS
The flue and air duct length must be between 100mm to
1metre. The fire is supplied with a standard pipe length of
400mm (to be cut in half to make a flue and air duct length of 200mm) The flue and air duct must not accommodate any bends.
Other lengths of flue and air duct are available
The flue outlet must terminate on a suitable outside wall.
The minimum flue terminal clearances, which must be
F
G
H
I
J
B
C
D
E maintained, are as shown below.
A Directly below an openable window or other opening. E.g. air brick
Below gutters, soil pipes or drain pipes
Below eaves
Below balconies or car port roofs
From vertical drain pipes and soil pipes
From internal and external corners
Above ground, roof or balcony level
From a surface facing the terminal
From a terminal facing the terminal
From an opening in a car port into a dwelling e.g. door, window, etc
300mm
300mm
300mm
600mm
75mm
300mm
370mm
600mm
1200mm
1200mm
K
L
Vertically from a terminal on the same wall
Horizontally from a terminal on the same wall
Note: These dimensions are taken from the centre of the circular flue outlet.
1500mm
300mm
14 5307LT(4:09/10)
PARAGON FOCUS RS SC Installation Instructions
SECTION EIGHT Siting the Appliance Continued
The back panel of the surround must have a cut-out within the maximum and minimum dimensions as shown.
Ensure that gas supply is suitably sited.
A non-combustible hearth must be provided beneath the appliance if the appliance is fitted at low level (less than
150mm from floor). The hearth must have a minimum thickness of 12mm and the perimeter 50mm above floor level. The hearth must extend the full width of the appliance and must project forward a minimum of 100mm in front of the appliance.
Alternatively the appliance may be fitted without a hearth (Hole in the Wall type installations), 50mm min. from the floor to the base of appliance
The minimum clearance from the hearth (base of appliance) to the underside of a combustible shelf should be determined using the shelf chart.
Minimum width between vertical sides of
1025 combustible surround should not be less than 800 mm provided fire is central to the
1000 surround and sides do not project more than
150 mm. When vertical side forward projection is increased by 12.5 mm add 50
950
900 mm to inside width of surround.
Check with the supplier or manufacturer that the surround meets 150
0
C minimum rating
(attention should especially be given to man made materials such as resin).
When installing in a timber framed dwelling reference must be made to the specific
850
800
750
0 25 50 75 100 125 150 175 200 225
"B" SHELF WIDTH installation requirements stated in Section
10 Installing The Appliance In Timber
Framed Dwelling.
all dimensions in mm's
EXAMPLE: 925 SHELF HEIGHT=165 MAX. SHELF WIDTH
SECTION NINE Preparing the Appliance for Installation
Carefully unpack the appliance from the carton and check the contents.
Lift off the decorative trim, which is held by four magnets and put to one side.
Lift away the fascia grill unit, which hooks over the lip of the combustion chamber.
Lay the appliance on its back ensuring suitable protection is provided for the carpet / floor.
Remove the two cross head nuts securing the fret apron and remove the apron
Remove the crosshead nuts from the top and bottom glass panel clamps and lift away carefully the both clamps.
With extreme care lift away the glass panel and put to one side in a safe place note the printing and ensure it is placed so that it is fitted correctly.
Remove the refractory components from the inside of the appliance.
The appliance is now ready for installation.
15 5307LT(4:09/10)
PARAGON FOCUS RS SC Installation Instructions
SECTION TEN To Install the Appliance
INSTALLING THE APPLIANCE INTO CAVITY WALL (
When installing in a timber framed dwelling reference must be made to the specific installation requirements stated later in this Section
„Installing The Appliance In Timber
Framed Dwelling‟).
Ensure it is a suitable outside wall constructed of non-combustible materials and that the flue position
CENTRE LINE OF
INSTALLATION
5 5 5 m m
202 mm 202 mm
MARK POSITION
OF LINTEL
MARKING OUT WALL FOR
CAVITY RECESSED
INSTALLATIONS meets the requirements previously
105 mm
POSITION
OF PILOT
HOLE
480 mm
POSITION
OF PILOT
HOLE described in Section 8.
Mark a horizontal line on the wall at the intended hearth surface or
HEARTH SURFACE LINE
OR BASE LINE FOR
HOLE IN WALL (50mm min. from floor) appliance base height (50mm min for Hole in Wall installation (the
FLOOR SURFACE skirting board must be cut away from behind the fire).
Mark a vertical line on the wall at the intended centre of the appliance up from the horizontal line for a height of 555mm.
Mark two more vertical lines 202mm either side of the centre line for a height of 555mm.
Mark a horizontal line at a height of 555mm above the hearth line, joining the two outside lines together.
Mark the position for a lintel above the top horizontal line.
Mark two short horizontal lines so they cross the centre line, one at 105mm and the second at
480mm above hearth level line. These are the centre points for the air duct and flue holes.
Using a long masonry drill, make two pilot holes completely through the wall, ensure the holes are drilled accurately at the centres and square to the wall both horizontally and vertically at the two cross points previously marked.
Cut out the brickwork of the inner skin of the cavity wall for the lintel, and position and fix the lintel with mortar.
Cut out the brickwork under the lintel, between the two outside vertical lines into the cavity.
Ensure the cut-out width is square, try the appliance into the opening.
Using 125mm (5”) core drill, cut two holes following the pilot holes, drill from the outside through to the cavity.
Remove any cavity insulation from the cut-out opening and for a further 100mm
LINTEL SET
IN POSITION into the cavity gap each side and above.
Pack “Rockwool” around the sides and top of the opening into the cavity for a depth of 100mm.
Lay the hearth if required so that it is positioned correctly to the horizontal line.
Position and fix the back panel and surround if required.
Offer the appliance into the opening and
125mm CORE
DRILLED HOLES
OUTER SKIN
OF W ALL
CUT OUT IN W ALL FOR
CAVITY RECESSED
INSTALLATIONS
CAVITY PACKED 100mm
DEEP W ITH ROCKW OOL
ALL FOUR SIDES
HEARTH SURFACE LINE
FLOOR SURFACE mark through the gas pipe entry hole (see connecting the gas supply later in this manual).
Pass a tape measure through the core-drilled holes and record the distance from the back of the spigots to the surface of the outside wall.
16 5307LT(4:09/10)
PARAGON FOCUS RS SC Installation Instructions
SECTION TEN To Install the Appliance Continued
Increase both the recorded distances by 15mm each, and cut two lengths from the 100mm diameter pipe.
Remove the appliance from the opening, and position the gas supply (see connecting the gas supply later in this manual), taking account of the relative gas regulations appertaining to a gas pipe in a cavity. Note the gas feed must be fitted with an isolation valve.
Position and seal the pipes to their respective spigots on the rear of the appliance (use flue seal or fire cement to ensure airtight seal, it must not obstruct the flue).
Peal the backing off the length of foam seal and affix to the rear outer edge of the appliance flange.
Push the appliance back into the opening and fill any space behind the appliance with
“Rockwool”.
Complete the gas connection (see connecting the gas supply later in this manual).
Drill the four fixing holes through the hole in the flange of the appliance and fix back using plug and screws.
Fit the outer wall terminal plate, with the “Rockwool” gasket sandwiched between it and the wall, with the double spigot at the top so that it seals to both the flue pipe and the air duct, (use flue seal or fire cement to ensure air tight seal).
Drill through the four holes in the outer wall terminal plate and fix back to the wall using plugs and screws.
Position the outer terminal cover and fix to wall terminal plate with the four screws provided.
If the flue outlet is fitted below 2m from the floor or a balcony then the flue guard must be fitted.
INSTALLING THE APPLIANCE INTO DEEP REBATED FIRE SURROUND OR
DUMMY CHIMNEY BREST. Additional duct pipe/s will be required. (
When installing in a timber framed dwelling reference must be made to the specific installation requirements stated later in this
Section „Installing The Appliance In Timber Framed Dwelling‟).
Ensure it is a suitable outside wall constructed of non-combustible materials and that the flue position meets the requirements previously
MARKING OUT WALL FOR
INSTALLATIONS INTO described.
Mark a horizontal line on the wall at the intended hearth surface or appliance base height (150mm min. for Hole in Wall installation) the skirting board must be cut away from behind the fire.
Mark a vertical line on the wall at the intended centre of the
CENTRE LINE OF
INSTALLATION
105 mm
POSITION
OF PILOT
HOLE
DEEP REBATED SURROUND
480 mm
POSITION
OF PILOT
HOLE
HEARTH SURFACE LINE
OR BASE LINE FOR
HOLE IN WALL (50mm min.from floor)
FLOOR SURFACE appliance up from the horizontal line for a height of 555mm.
Mark two short horizontal lines so they cross the centre line, one at 105mm and the second at
480mm above hearth level line. These are the centre points for the air duct and flue holes.
Using a long masonry drill, make two pilot holes completely through the wall, ensure the holes are drilled accurately at the centres and square to the wall both horizontally and vertically at the two cross points previously marked.
17 5307LT(4:09/10)
PARAGON FOCUS RS SC Installation Instructions
SECTION TEN To Install the Appliance Continued
Using 125mm (5”) core drill, cut two holes following the pilot holes, drill from the outside of the dwelling through to the cavity, and from the inside through to the cavity
Remove any combustible material that may be present if the rear of the appliance is contacting the wall i.e. ensure no battens etc., behind dry lining
Lay the hearth or a non-combustible base (for Hole in Wall) so that it is positioned correctly to the horizontal line.
Temporally position and fix the back panel and deep surround, or construct a dummy chimney breast as required, avoiding combustible materials coming in close proximity to the appliance or the flue, leaving access to pack around the appliance with “Rockwool”.
Offer the appliance into the opening and mark through the gas pipe entry hole (see connecting the gas supply later in this manual).
Pass a tape measure through the core-drilled holes and record the distance from the back of the spigots to the surface of the outside wall.
Increase both the recorded distances by 15mm each, and cut the lengths from the 100mmdiameter pipe - you will probably require an extra pipe.
Remove the appliance from the opening, and position the gas supply (see connecting the gas supply later in this manual), taking account of the relative gas regulations appertaining to a gas pipe in a cavity.
Permanently fix the deep rebated surround in position, and pack the void behind the fascia panel of the deep rebated surround with “Rockwool”. Pack 150mm thickness of “Rockwool” over the appliance top and side if it is fitted into a dummy chimneybreast, and fill any space between the appliance and the outside wall.
Position and seal the pipes two their respective spigots on the rear of the appliance (use flue seal or fire cement to ensure airtight seal, it must not obstruct the flue).
Peal the backing off the length of foam seal and affix to the rear outer edge of the appliance flange.
Push the appliance back into the opening and fill any space behind the appliance with
“Rockwool”.
Complete the gas connection (see connecting the gas supply later in this manual).
Drill the four fixing holes through the hole in the flange of the appliance and fix back using plus and screws.
Fit the outer wall terminal plate, with the “Rockwool” gasket sandwiched between it and the wall, with the double spigot at the top so that it seals to both the flue pipe and the air duct, (use flue seal or fire cement to ensure air tight seal, it must not obstruct the flue).
Drill through the four holes in the outer wall terminal plate and fix back to the wall using plugs and screws.
Position the outer terminal cover and fix to wall terminal plate with the four screws provided.
If the flue outlet is fitted below 2m from the floor or a balcony then the flue guard must be fitted.
18 5307LT(4:09/10)
PARAGON FOCUS RS SC
Installation Instructions
SECTION TEN To Install the Appliance Continued
TIMBER FRAMED DWELLING
This method allows for installation in timber frame buildings. Where removal of any part of the inner timber leaf of the wall is involved the structural integrity of the wall must be maintained and the advice of your local Building Control Department should be sought. If the property is under N.H.B.C. cover, it is advised that their advice should also be sought. Reference should be made to the British Gas Publication DM2 "Guide For Gas Installations In Timber Frame
Housing" or CORGI “Gas installations in Timber Frame Buildings” ISBN1-902632-30-3
Special attention must be paid to the location of the studwork frames of the inner leaf and the appliance positioned accordingly. Electrical cables and pipework that run within the inner timber leaf must also be located and taken into account when positioning the appliance.
The following methods of installation may be adapted for use in timber frame buildings providing extra care is taken to protect combustible materials from contact with hot surfaces.
Method 1 (For installation into a extended fire surround or false chimney breast)
An insulation material (20mm “Superlux” or equivalent) must protect all combustible surfaces
(including plasterboard) situated within the opening. A minimum clearance of 50mm must be allowed between the appliance case (rear, top and sides) and the material used to line the opening. The base of the opening must be non-combustible.
Wrap the appliance body (top, rear and sides) an d both flue tubes with “Rockwool” (50mm minimum thickness).
Where the duct pipes pass through the inner timber leaf concentric holes 200mm diameter should be cut around each duct pipe, allowing a minimum 50mm air gap all round each duct pipe. A noncombustible sleeve 200mm diameter must be fitted to these clearance holes.
To ensure that any condensation formed on the duct pipes does not drip on to the inner wall a length of galvanised wire must wrapped around each flue pipe and secured in position by twisting the ends together. Ensure that the twisted ends are located at the bottom of the pipes and the wire is centrally located within the cavity.
The vapour barrier on the back of the inner timber leaf should be carefully cut and fixed to prevent ingress of damp into the plasterboard layer.
Method 2 (For installation into the inner timber leaf of the wall
Find a suitable position between the wall panel frames and carefully open up a hole (minimum dimension 505mm wide x 605mm x 230mm depth) this will ensure 50mm minimum clearance around the appliance body Note: the 230mm could be reduced to 200mm if no combustible material is left between the back of the fire box and the outer skin on brickwork. Careful attention must be made to securing the damp proof membrane back into position. (Note: To achieve the minimum depth requirement it may be necessary to deepen the cavity by building up the wall surface with an appropriate none combustible material.)
Line the exposed cavity (top, rear and sides) with an insulation material (20mm “Superlux” or equivalent) to form a boxed chamber. The base of the opening must be non-combustible.
Wrap the appliance body (top, rear and sides) and both flue tubes with “Rockwool” (50mm minimum thickness).
Where the duct pipes pass through the inner timber leaf, concentric holes 200mm diameter should be cut around each flue pipe, allowing a minimum 50mm air gap all round each flue pipe.
A non-combustible sleeve 200mm diameter must be fitted to these clearance holes.
To ensure that any condensation formed on the duct pipes does not drip on to the inner wall a length of galvanised wire must wrapped around each flue pipe and secured in position by twisting the ends together. Ensure that the twisted ends are located at the bottom of the pipes and the wire is centrally located within the cavity.
19 5307LT(4:09/10)
PARAGON FOCUS RS SC Installation Instructions
SECTION TEN To Install the Appliance Continued
TIMBER FRAMED DWELLING CONTINUED
The vapour barrier on the back of the inner timber leaf should be carefully cut and fixed to prevent ingress of damp into the plasterboard layer.
NOTE:
Neither the appliance nor the “Rockwool” insulating pad may overhang the cavity space.
Routing of the gas supply must be carried out inline with the recommendations specified in the British
Gas Publication DM2 „Guide for gas installation in Timber Frame Housing.
CONNECTING THE GAS SUPPLY
TURN OFF ANY GAS APPLIANCES THAT ARE FED BY THE METER AND ISOLATE THE GAS
SUPPLY BY TURNING OFF AT THE METER.
Connections may be made from the front of the appliance from either the left or the right in 8mmdia. pipe or a concealed connection from the rear of the appliance a hole with a grommet is provided at the rear.
An isolating cock is fitted in the supply feed to the fire to facilitate servicing. It may be rotated for right gas connection.
When a concealed gas fitting from the rear is required it is necessary to route the pipe to the left side of the unit, taking into account the requirements of BS 6891 1988 dealing with enclosed pipes.
When installing the firebox into a cavity wall, any part of the installation pipe work installed in the void open to the cavity wall must be enclosed in a gas tight sleeve. It must be sealed at the point at which the sleeved installation pipe enters the fire (The Gas Safety (Installation and Use)
Regulations Certificate of exemption number 1 of 1996). Where the pipe enters the fire the outer sleeve must be sealed to the grommet and the pipe must be sealed to its outer sleeve using suitable mastic.
CHECKING GAS SOUNDNESS
Complete gas connection to the fire and check for gas soundness in accordance with current codes of practice.
SECTION ELEVEN Assemble the Appliance
Position the refractory fuel bed components as described in section four of this manual, it is important that the fuel bed is positioned exactly as described to ensure the correct operation of the appliance. Badly positioned fuel bed components may result in the gas flame being driven forward onto the glass and permanently marking it.
Position the lower glass clamp over the lower four studs. Start the crosshead nuts on these four studs two turns on each.
Taking great care, locate the glass panel into the space behind the lower glass clamp, ensuring it is positioned centrally with the printed surface to the inside and the wide area of print at the lower edge, push it back into position and fit the top clamp with four crosshead nuts.
Tighten the crosshead nuts up evenly ensuring that the glass compresses the seal on all four sides.
Position the fret apron and secure with two cross head nuts
Position the grill fascia so that it hooks centrally over the top flange of the combustion box and covers both glass side clamps.
Position four magnets in two up each side of the appliance flange, and offer the decorative trim up squarely and centrally.
20 5307LT(4:09/10)
PARAGON FOCUS RS SC Installation Instructions
SECTION TWELVE Check Operation of Fire
CONNECTING CONTROL LEVER
Remove the two m4 screws from the slide bar.
Slide control lever within handle guide bracket and refit the two m4 screws.
CONNECTING THE BATTERY
Connect boot lead to battery, which is located bottom centre of the appliance above the valve.
Slide the battery below the valve as shown.
CHECK BURNER PRESSURE AND GENERAL OPERATION
Turn on the gas supply to the appliance and check for soundness in accordance with current codes of practice.
Turn off the gas supply at the external Isolation valve.
Remove the pressure test point screw from the inlet elbow and connect the pressure gauge.
Turn on the gas to the appliance at the Isolation valve.
Push down on the lever to ignition position and allow the air in the pipe to be purged.
Keep the lever down and check that the electrode is sparking at the gap between the thermocouple tip and the electrode; continue until pilot ignition is established.
When established the control lever may be lifted until a resistance is felt, this will put the burner on its high setting.
Check that the inlet pressure 20mbar +/- 1 mbar for natural gas .
Turn off gas supply, at the isolation valve. Disconnect the pressure gauge and replace the pressure test point screw.
Turn on the supply to the appliance and check the pressure test point for soundness with detection fluid.
PARAGON FOCUS RS SC Installation Instructions
21 5307LT(4:09/10)
SECTION THIRTEEN Instruct and Advise the Customer
Demonstrate the lighting and extinguishing procedure to the consumer/user and the removal and refitting of the decorative trim for cleaning.
Explain that for the first few hours of the fire operating there will be an initial odour. This is due to the curing of the paint, the appliance should be operated on its high setting, and it is recommended that a window is left open until that odour has completely disappeared.
Instruct on the glass removal and refitting.
Instruct on the fuel bed cleaning and advise that a vacuum cleaner can be used but only after all the loose fuel bed shapes have been removed.
Refer to ‘Health & Safety Notice (See Section
One) at the front of this booklet before proceeding.
Advise that the appliance should be serviced annually by a competent person i.e. a CORGI
registered engineer in accordance with these instructions.
Although the appliance is fitted with a glass front which acts as a dress guard it is strongly recommended that a fireguard should be used for the protection of children, the elderly or infirm.
Fireguards should conform to B. S. 6539 (1984) (Fireguards for use with solid fuel appliance).
Hand these instructions to the user.
22 5307LT(4:09/10)
PARAGON FOCUS RS SC Maintenance Instructions
SECTION FOURTEEN Maintenance Instructions
General
Servicing should be carried out annually by a competent person such as a CORGI-registered person in accordance with the relevant regulations, to ensure the safe and correct operation of the appliance.
Warning: - Before commencing any service or replacement of parts, turn off the gas supply to the fire.
After servicing check for gas soundness.
When ordering spare parts please quote appliance name and serial number these can be found on the data badge, which is located on the appliance remove the decorative fire front for access.
If soot has accumulated check to establish cause, rectify and clean flue accordingly.
Important: -
Refer to ‘Health & Safety Notice (See Page 3) at the front of this booklet before removing the fuel bed components.
Examine the coals for signs of cracking and replace if necessary.(IMPORTANT) see coal layout procedure in section four of this manual before attempting to replace coals, which should only be replaced as a complete set with no extra coals added.
Check pilot aeration holes for linting, use a vacuum cleaner to remove any lint taking care not to damage the pilot head.
Replacement of Gas Control
1. Remove the fret or fascia and turn off the gas supply ay the isolation cock.
2. Disconnect the injector pipe from the left hand side of the gas control.
3. Disconnect the pilot pipe from the underside of the pilot burner.
4. Pull off the connection to the spark electrode
5. Undo the supply connection to the pressure test elbow and Injector.
6. Remove the 2 connections to the micro switch.
7. Remove fixing pin holding generator shield and lift off.
8. Remove fixing stud holding generator and remove.
9. Remove thermocouple from the rear of the gas control.
10. Remove the two screws holding the gas valve to bracket.
11. Remove gas control.
12. Change or service the valve and replace in reverse order.
13. Turn on the gas supply, check for soundness and re- commission.
Replacement of Injector
1. Remove the fret or fascia and turn off the gas supply ay the isolation cock.
2. Remove the glass and fuel bed components as described earlier in this manual.
3. Undo and remove the 2 screw holding the burner in place
4. Carefully remove the burner lifting from the right hand end of the burner.
5. Loosen and remove the injector back nut.
6. Undo the compression connection to the injector and lift it away
Clean or replace injector and replace in reverse order, ensuring that the connection to the injector fixing is sound air test if in doubt.
7. Turn on the gas supply, check for soundness and re- commission.
23 5307LT(4:09/10)
PARAGON FOCUS RS SC Maintenance Instructions
SECTION FOURTEEN Maintenance Instructions Continued
Replacement of the Micro Switch
1. Remove the two fixing screws holding the micro switch and pull forward.
2. Pull off the cable connections from the switch.
3. Remove the two screws holding the switch in place and lift away the switch, replace in reverse order.
Replacement of the Thermocouple
1. Repeat operations 1-14 for removal of gas control.
2. Pull off the cable connections from the switch.
3. Replace in reverse order.
4. Turn on the gas supply, check for soundness and re- commission.
Replacement of the Pilot Injector
1. Undo the pilot tube nut at the pilot bracket.
2. Pull the pipe gently back taking care not to damage.
3. Remove the pilot injector from inside the pilot bracket.
4. Clean or replace in reverse order, turn on the gas supply, check for soundness and re- commission.
Replacement of the Spark Electrode
1. Remove the cable from the electrode connection.
2. Undo the electrode nut at the pilot bracket.
3. Remove the electrode carefully.
4. Clean or replace in reverse order, and re- commission.
Replacement of the Spark Generator
1. Remove the fret or fascia .
2. Remove fixing pin holding generator shield and lift off.
3. Pull off the connection to the spark electrode.
4. Remove the 2 connections to the micro switch.
5. Remove fixing stud holding generator and remove.
When ordering parts quote 'PARAGON FOCUS RS' and the serial number of the fire, which can be found on the data badge which is located on the appliance remove decorative trim for access.
Paragon Fires
Telford
Shropshire
TF3 3AR
Telephone 0845 5195991
Web Site www.paragonfires.co.uk
24 5307LT(4:09/10)
Paragon Fires
PARAGON FOCUS RS SC
THIS IS YOUR EXTENDED FIVE YEAR PARTS
WARRANTY
PLEASE READ IT CAREFULLY AND ENSURE YOUR INSTALLER HAS FILLED IN
THE FIRST PORTION, KEEP IT IN A SAFE PLACE SO THAT IT IS AVAILABLE
WHEN YOUR
CORGI
ENGINEER CARRIES OUT THE ANNUAL SERVICE.
THIS IN NO WAY REDUCES YOUR STATUTORY RIGHTS
THE WARRANTY COMMENCES FROM THE DATE OF PURCHASE YOU MUST
RETAIN YOUR RECEIPT OR INVOICE AS PROOF OF PURCHASE.
THIS EXTENDED WARRANTY SPECIFICALLY EXCLUDES SOFT REFRACTORY
COMPONENTS, THE BULB AND ANY BATTERIES.
Terms and Conditions
1. The appliance must be installed by a CORGI registered person.
2. The appliance must be used in accordance with the users instructions.
3. The appliance must be serviced annually by a CORGI registered person.
4. The service log must be correctly filled out and the record of annual services must be up to date and supported by receipts in each case.
5. This warranty is not transferable and relates to the original installation only.
6. The Registration Form must be correctly filled out and returned.
7. The appliance has not been subjected to misuse or accident or been modified or repaired by any person other than the authorised employee or authorised representative of Charlton and Jenrick Ltd.
8. The registration form must be returned within 3 months of purchase.
PARAGON HELPDESK NUMBER 0845 5195991
25 5307LT(4:09/10)
WARRANTY COVER
Important
For future reference we suggest you record the following details here, and keep the receipt as proof of purchase. This information may be asked for when you contact the helpdesk.
Model: PARAGON FOCUS RS SC
Serial No.
This information can be found on the label attached to the packaging and on the data badge, which is located on the base of the appliance.
Retailer Name: ___________________________________________
Address:
________________________________
___________________________________________
___________________________________________
Date of Purchase:
Service Log
The following information must be complete and supported by receipts as part of the conditions of the extended three year parts warranty and the appliance must be registered by completing and returning the registration document (last page of this booklet) to Paragon
Fires.
Date of First annual service:
Engineer Name
Corgi Registration No.
Date of Second annual service:
Engineer Name
Corgi Registration No.
We may introduce modifications to products from time to time, and consequently the details given in this booklet are subject to alteration without notice.
Paragon Fires
Telford
Shropshire
TF3 3AR
Telephone 0845 5195991
Web Site
www.paragonfires.co.uk
26 5307LT(4:09/10)
PLEASE REGISTER YOUR 12 MONTH WARRANTY WITH US TODAY
Simply detach this sheet from this booklet, complete and return it in a stamped addressed envelope to:
PARAGON FIRES
Charlton and Jenrick Ltd
UNIT D
STAFFORD PARK 2
TELFORD
SHROPSHIRE
TF3 3AR
YOUR DETAILS
Name
________________________________
Address
________________________________
Post Code TELEPHONE No.
PRODUCT DETAILS
Model: PARAGON FOCUS RS SC
Serial No.
Date of Purchase
This information can be found on the label attached to the packaging and on the data badge, which is located on the base of the appliance.
WHERE DID YOU PURCHASE THIS PRODUCT
Name ________________________________
Address
________________________________
Post Code TELEPHONE No.
27 5307LT(4:09/10)
Paragon Focus RS SC Coal
Product
ID Label
A-0128
Serial No
Prefix
KK
Data Badge
Burner Tray / Box Assembly
Air Test Completed
Microswitch Check
Warning Label (Fire Guard)
Front Matrix (4605)
Rear Matrix 4604
Coal Set (4606)
Installation Seal / Slide Control Handle and screws/ 7mm Spanner (4253)
Restrictor Elbow (2613)
Magnets (4 x 3048) / 9v Battery (1904)
Glass Panel
Canopy (4540)
Flue Assembly
Terminal Guard
Wall Gasket
Flue Pipe
Fret Plate
Doughnut Seal (2)
Owners Book
Serial Number
Inspector
Paragon Focus RS SC Pebble
Product
ID Label
A-0129
Serial No
Prefix
KK
Data Badge
Burner Tray / Box Assembly
Air Test Completed
Microswitch Check
Warning Label (Fire Guard)
Front Matrix (4607)
Rear Matrix 4604
Pebble Set (4611)
Installation Seal / Slide Control Handle and screws/ 7mm Spanner (4253)
Restrictor Elbow (2613)
Magnets (4 x 3048) / 9v Battery (1904)
Glass Panel
Canopy (4540)
Flue Assembly
Terminal Guard
Wall Gasket
Flue Pipe
Fret Plate
Doughnut Seal (2)
Owners Book
Serial Number
Inspector
28
Paragon Focus RS SC Driftwood
Product
ID Label
A-0130
Serial No
Prefix
KK
Data Badge
Burner Tray / Box Assembly
Air Test Completed
Microswitch Check
Warning Label (Fire Guard)
Front Matrix
Rear Matrix 4604
Driftwood Set
Installation Seal / Slide Control Handle and screws/ 7mm Spanner (4253)
Restrictor Elbow (2613)
Magnets (4 x 3048) / 9v Battery (1904)
Glass Panel
Canopy (4540)
Flue Assembly
Terminal Guard
Wall Gasket
Flue Pipe
Fret Plate
Doughnut Seal (2)
Owners Book
Serial Number
Inspector
5307LT(4:09/10)