6500(S)

REFLECTED BEAM SMOKE DETECTOR

INSTALLATION AND MAINTENANCE INSTRUCTIONS

I 56- 3797- 003

GENERAL

The model 6500 is an addressable long range projected beam smoke detector designed to provide open area protection. It consists of a combined transmitter/receiver unit and a reflector. Smoke entering the area between the two components causes a reduction in the signal returned to the receiver.

When the obscuration reaches the alarm threshold, selected at the transmitter/ receiver unit, the detector generates an alarm signal. Complete blockage of the beam causes a fault signal. Slow changes in obscuration due to a build up of dirt or dust on the lens of the detector are compensated for by a microcontroller that continuously monitors the signal strength and periodically updates the alarm and fault thresholds. When the self-compensation circuit reaches its limit, the detector generates a fault signal, indicating the need for service. After local testing is complete, the yellow LED will blink a pattern to indicate the level of drift compensation employed during the test (see Blinks

Output by Yellow LED table at back of manual).

The model 6500S includes an integral servo controlled calibrated test filter, which allows automatic remote alarm testing.

SPECIFICATIONS

General

Range:

Sensitivity:

Maximum angular misalignment

Environmental

5 to 70m

70 to 100m using optional accessory 6500-LRK/BEAMLRK

Level 1 = 25% (1.25dB)

Level 2 = 30% (1.55dB)

Level 3 = 40% (2.22dB)

Level 4 = 50% (3.01dB)

Level 5 = 30% to 50% Adjusting

(Acclimate Level 1)

Level 6 = 40% to 50% Adjusting

(Acclimate Level 2)

Detector ± 0.5°

Reflector ± 10°

Temperature:

Humidity:

-30°C to 55°C

10% to 95% Relative Humidity

(Non-condensing)

Mechanical

Dimensions (Without Faceplate):

Dimensions (With Faceplate):

Wiring:

Adjustment Angle:

229mm x 178mm x 84mm

253mm x 193mm x 84mm

0.3 mm² to 3.2 mm²

±10° Horizontal and Vertical

Electrical

Voltage:

Avg. Standby Current:

Advanced Protocol Mode:

Max. Alarm Current (LED on):

Max. Fault Current (LED on):

Max. Alignment Current:

External Supply (for 6500S auto -alarm test only)

Remote Output (alarm):

15 to 32 VDC (15-28.5V when using isolators)

2mA @ 24VDC; 1 comm. every

5sec, LED flashing.

Read 16 sec. LED blink 8 sec

8.5mA

2.5mA

20mA

Voltage:

Current:

15 to 32 VDC

0.5A Max.

Voltage:

Current:

15 to 32VDC

6mA to 15mA.

Limited by 2.2KΩ resistor

PARTS LIST

Description Quantity

Transmitter/Receiver Unit 1

Paintable Trim Ring

Reflector (REFL6500)

1

1

Plug-in Terminal Blocks

Isolator Shunts

Orange Alignment Assistance Label

Instruction Manual

3

2

1

1

APPROVED ACCESSORIES

6500-LRK/BEAMLRK

Long Range Kit comprising three additional 20cm x 20cm reflectors, which may be mounted in a square with the supplied reflector, permitting the detector to be used for ranges from 70m to 100m.

6500-MMK/BEAMMMK

Multi-Mounting Kit allowing the 6500 to be mounted to ceilings, or to walls where the detector and reflector cannot be mounted within 10° of one another. One kit mounts either the transmitter/receiver unit or reflector. If the transmitter/receiver is mounted on the MMK, then the 6500-SMK/BEAMSMK must be used. Note that only a single 20cm x 20cm reflector can be mounted using the MMK: The 6500-LRK/BEAMLRK is not compatible with the MMK.

6500-SMK/BEAMSMK

Surface Mounting Kit for the transmitter receiver (also used in combination with the 6500-MMK/BEAMMMK) to give an additional 43mm depth to assist surface mounting and to permit side entry cabling.

RTS151KEY

Remote test and annunciator accessory that enables the detector to be tested remotely, providing test and reset functions, it has a Red LED to indicate alarm conditions (Note: Back-box, if required, needs to be ordered separately - part number WM2348).

DETECTOR MOUNTING

Location

The 6500 must be located in accordance with local standards and guidelines, for example BS5839 part 1. For general information, refer to the application guide for projected beam smoke detectors available on request from your supplier.

Mounting Position

Beam detectors require a very stable mounting surface for proper operation. A surface that moves, shifts, vibrates, or warps over time may cause false alarm or fault conditions. Initial selection of a proper mounting surface will eliminate nuisance alarms and fault signals. Mount the detector on a stable mounting surface such as brick, concrete, a sturdy load-bearing wall, support column, structural beam, or other surface that is not expected to experience vibration or movement over time. DO NOT MOUNT the beam detector on corrugated metal walls, sheet metal walls, external building sheathing, external siding, suspended ceilings, steel web trusses, rafters, non-structural beam, joists, or other such surfaces. The reflector has a much greater tolerance to movement than the transmitter/receiver, hence in cases where only one stable mounting surface as defined above can be used, the transmitter/receiver unit should be mounted to the stable surface. See specifications for maximum permissible angular misalignment; movement outside these limits may cause nuisance alarms and faults.

Mounting Considerations

• There must be a permanent clear line of vision between the detector and the reflector.

• Reflective objects should be a minimum of 380mm from the line of sight between the detector and reflector to avoid compromise of the protected area by reflected light.

• Direct sunlight or strong lights into the transmitter/receiver unit should be avoided. There should be a minimum of 10° between the paths of the light source and the detector beam.

• Operation of the detector through panes of glass should be avoided if possible. If it is necessary to pass though glass, the angle between the beam and glass should be set a minimum of 10° off perpendicular, and operation through multiple panes should be avoided.

MOUNTING

The transmitter/receiver unit may be mounted directly to the wall, with rear cable entry. The detector base has four primary mounting holes, one in each corner of the base. All four holes must be used to provide secure mounting. In order to mount the detector to the wall, the outer cover must be removed after unscrewing it’s four retaining screws.

DB200-00-02 1 I56-3797-003

Please refer to the relevant kit instructions if the transmitter/receiver is to be mounted onto the 6500-SMK/BEAMSMK or 6500-MMK/BEAMMMK allowing more flexibility for cable entry.

WALL

MOUNTING

SCREW X 4 COVER

SCREW

X 4

Figure 1: Transmitter/Receiver Wall Mounting

The reflector is mounted directly to the wall using all four of it’s mounting holes, one in each corner. The reflector must be mounted such that the plane of the reflector is perpendicular to the optical line of sight to the transmitter/receiver unit. The maximum tolerance for non-perpendicular mounting locations is

10°. If this tolerance is not possible, then the 6500-MMK/BEAMMMK should be used, see 6500-MMK/BEAMMMK instructions for mounting details.

1 2 3 4 1 2 3 4 1 2 3 4

WALL

10°

10°

REFLECTOR

* CAN BE USED FOR TERMINATING CABLE SCREENS

Figure 3: Detector Terminal Connections

ACCEPTABLE MOUNTING

LOCATIONS FOR REFLECTOR

Figure 2a: Reflector Mounting Guidelines

10° MAXIMUM

RTS151/KEY

4

5

6

3

2

1

T2-1

T2-2

T2-3

T2-4

6500(S)

REMOTE ALARM

OUTPUT

AUX (-)

TEST INPUT

RESET INPUT

OPTICAL LINE OF SIGHT

Figure 2b: Reflector Mounting Guidelines

REFLECTOR

WIRING

Note: All wiring must be installed in accordance with local requirements.

Warning: Before working on the system, notify the proper authorities that the system is undergoing maintenance and will be temporarily out of service.

Wiring connections are made to pluggable terminal blocks, which can accept wire sizes from 0.3 mm² to 3.2 mm². For best results screened cable should be used. Refer to the control panel instructions for cable type limitations.

DB200-00-02 2

SEE RTS151KEY INSTALLATION INSTRUCTIONS

FOR ELECTRICAL RATINGS OF RTS151KEY

Figure 4: RTS151KEY Wiring

Signal Name Terminal Normal State

Reset Input to

Test Input to

T2-4

T2-3

Aux- T2-2

Remote Alarm Out T2-1

Remote Fault Out T3-3

Active Comment

State

High impedance 0V

High impedance 0V

0V -

High impedance +24V

High impedance +24V

Momentarily connect

Aux- to operate

Momentarily connect

Aux- to operate

Internally connected to

Power -ve

Via 2.2k ohms current limit resistor

Via 2.2k ohms current limit resistor

Table 0: Use of Input – Output Signals .

WARNING

All INPUT and OUTPUT signal terminals are active LOW (0V)

Do not connect any other voltage to these terminals or serious damage to the product may result.

I56-3797-003

ALIGNMENT

SENSITIVITY

TEST

RESET

ISOLATOR SHUNTS

(SHOWN DISABLED)

Figure 6: Switch

Locations

ALIGNMENT

P O S I T I O N

INDICATOR

ALIGNMENT

MIRROR

ALIGNMENT GUN

SIGHT

REMOTE

POWER

SOURCE

(6500S ONLY)

LOOP (+)

LOOP (-)

LOOP (-)

LOOP (+)

DIGITAL SIGNAL

STRENGTH

READOUT

Figure 5: Wiring Diagram

ADDRESS SELECTION

Set the sensor address (see Figure 6) by using a flat blade screwdriver to turn the two rotary switches to the left of the main optical assembly, selecting the desired number between 01 and 159 (Note: The number of addresses available will be dependent on panel capability, check the panel documentation for information on this). A breakaway stop on the Tens rotary switch needs to be removed for panels capable of handling more than 99 addresses.

SHORT CIRCUIT ISOLATION

The detector includes on-board short circuit isolation. In cases where it is not desired the isolator can be bypassed using the two shunts on the circuit board.

See Figure 6 for jumper locations. The detector is supplied with the jumpers fitted and the isolators bypassed.

ALIGNMENT PROCEDURE

Warning: When power is initially applied to the detector, before the alignment procedure has been completed, it may enter fault or alarm. To prevent unwanted alarms, disable the zone prior to applying power.

The alignment of the 6500 is divided into four steps: Coarse alignment, fine adjustment, final gain adjustment, and final verification. It is necessary for all four steps to be executed properly to ensure proper alignment of the product.

Pre-Alignment Checklist

• Ensure that both the detector and reflector are mounted securely to stable surfaces.

• Ensure that all wiring is correct, and that terminal blocks are fully seated into their receptacles on the detector.

• Complete any wiring dressing to minimize movement to the detector once the alignment procedure is completed.

• Ensure that the appropriate reflectors are used for the installed distance.

• Ensure that the line of sight between the detector and reflector is clear and that reflective objects are a minimum of 380mm from the line of sight.

• Ensure that both the detector and reflector are mounted within their operational parameters for off axis angles.

O P T I C S

LOCK-DOWN

SCREWS X 2

HORIZONTAL

ADJUSTMENT

Figure 7: Alignment

Adjustment Locations

VERTICAL ADJUSTMENT

• Disable the zone or system to prevent unwanted alarms before applying power.

• Ensure power to the detector is “ON”.

• Normally, due to the current drain during alignment, only one unit on a loop should be in alignment mode at any time

Step 1. Coarse Alignment

See figures 6 and 7.

1. Ensure that both of the optics lock-down screws are loosened so that the optics will move freely.

2. Looking through the alignment mirror at both the alignment gun sight and reflector simultaneously, locate the position of the reflector in the optical sight. Note that initially this step will require some practice. An orange sticky label is supplied, which may be temporarily mounted next to the reflector to aid initial location if the distance between the reflector and the detector is large.

3. Once the reflector has been located, begin to adjust both the horizontal and vertical alignment knobs so that the reflector becomes centred in the alignment mirror. Caution: If the optics are incorrectly aligned in this step, it will not be possible to proceed with the next step.

Note that the coarse alignment procedure will not give accurate alignment. It is sufficient only as a starting point for the next step. On completion of the fine adjustment procedure, the alignment gun sight may not appear to be centred on the reflector.

DB200-00-02 3 I56-3797-003

SCREW

LOCATIONS

REFLECTOR

Figure 8: Coarse Alignment Procedure

EYE

SCREW

LOCATIONS

RESET SWITCH

Figure 9: Housing Screw Locations

Step 2. Fine Adjustment

See figures 6 to 8.

1. Ensure that no objects are in the line of sight between the detector and the reflector.

2. Depress the Alignment switch once. Both the digital display and the yellow

LED should turn on indicating that alignment mode has been entered. The display should begin reading “- -” signifying an electronic gain adjustment.

After a few moments the display will indicate a numeric value near 20.

Note: If the display reads “Lo” then the detector is not receiving enough light from the reflector. Go back and repeat the course alignment step and verify that the proper number of reflectors is used for the installed distance.

The display will continue to read “Lo” until the detector receives enough light from the reflector to continue with the fine adjustment step.

Note: In alignment mode (indicated by the yellow LED and the numeric display) the sensitivity select and test switches are disabled.

3. Once the display shows a number, begin adjusting the horizontal and vertical alignment knobs one at a time to increase signal level on the display. Continue adjusting each axis one at a time going back and forth between them until a peak value is indicated. If a value of 90 is achieved, the detector will reduce it’s electronic gain. This will be indicated by a “- -” reading on the display. When this happens halt any further adjustment until the display again reads a numeric value. This process may occur more than once during the fine adjustment step.

4. Once satisfied that it is not possible to achieve a higher reading on the display depress the alignment switch to complete the fine adjustment step. The digital display readout will turn “OFF” and the yellow LED will remain “ON”.

5. Ensure that both of the optics lock-down screws are re-tightened.

Note: It may not be possible to achieve a figure close to 90 on the display during the last adjustment iteration. Each time the figure 90 is reached the gain is reduced, making it more difficult to achieve high values. Any number is acceptable, provided it is the highest figure that can be achieved after the final gain adjustment.

At this time it is sensible to set the sensitivity of the detector using the sensitivity switch and digital display. See SENSITIVITY SELECTION for further details.

Step 3. Final Gain Adjustment

See figure 9.

In this step, the detector electronically adjusts its internal gain one final time.

It is necessary to complete this step with the outer housing installed since the housing will change the amount of light received from the reflector.

1. Install the outer housing of the detector. The housing is installed by tightening the four captive screws, one in each corner of the housing.

Note: The housing contains a gasket seal that protects the detector circuitry from corrosion and moisture. To ensure that this gasket performs correctly, it is necessary to tighten all four of the screws holding the outer housing in place evenly.

2. Remove the protective film from the front surface of the outer housing.

Note that the outer housing may require cleaning if any residue remains.

Use only a soft, damp cloth: Do not use any solvents.

3. To initiate the final electronic gain adjustment, the reset switch must be depressed using a small screwdriver or similar tool. Once depressed the yellow LED will begin to blink. On completion, the yellow LED will stop blinking and the green LED will begin blinking (dependant on panel operation), indicating that the gain adjustment was successful.

Note: Use caution not to block the line of sight between the detector and reflector in this step.

4. Install the outer aesthetic ring by snapping it onto the outer housing.

Note: If the outer aesthetic ring has been painted ensure that the paint is completely dry before proceeding with this step.

Step 4. Final Verification

This step is required to ensure the detector has been set up correctly and will detect smoke at the proper sensitivity level.

1. With the detector functioning (dependant on the operation of the control panel, this may be indicated by the green LED blinking), completely block the reflector with a non-reflective opaque material. After about 30 seconds, the detector should enter either the fault or alarm condition. If the detector does not enter the fault or alarm condition, there is a problem with the installation.

2. Complete a sensitivity test of the detector as described in SENSITIVITY

TESTING below.

SENSITIVITY SELECTION

The sensitivity of the detector can be set only when the housing is removed and the detector is not in the fine adjustment step of the alignment mode. To enter the selection mode, press the sensitivity button once (see figure 6). The digital display will illuminate and read the current sensitivity setting in percent obscuration. Press the sensitivity button again to rotate to the next setting.

Once the required setting is achieved (See table 1), the detector will exit the sensitivity selection mode if no further switch presses occur.

In addition to the four standard sensitivity selections the detector has two

Acclimate settings. When either of these settings is chosen the detector will automatically adjust its sensitivity using advanced software algorithms to select the optimum sensitivity for the environment. The sensitivity will be continuously adjusted within the ranges specified in the Chart 1.

Percentage obscuration can be converted to percent per metre assuming uniform smoke density for the entire length of the beam. Chart 1 converts obscuration to percent per metre for all acceptable sensitivity settings.

Sensitivity Setting % Obscuration

Level 1

Level 2

Level 3

Level 4

Acclimate Level 1

Acclimate Level 2

25

30

40

50

30 to 50

40 to 50

Table 1: Sensitivity Settings

Display Reading

25

30

40

50

A1

A2

DB200-00-02 4 I56-3797-003

7

6

4

3

2

1

GRAPH 1: SENSITIVITY (%M vs DISTANCE)

(Assuming Uniform Smoke Distribution)

Level 1

Level 2

Level 3

Level 4

0

0 10 20 30 40 50 60

Distance (Metres)

70 80 90 100

SENSITIVITY TESTING

NOTES:

1. Before testing, notify the proper authorities that the smoke detector system is undergoing maintenance, and therefore the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.

Detectors must be tested after installation and following periodic maintenance.

The sensitivity of the 6500 may be tested as follows:

Calibrated Test Filter Method

The sensitivity of the detector can be tested using an opaque material (such as this manual ) to cover the reflector by an amount indicated by the graduated scale on the reflector, see Figure 10.

1. Verify the sensitivity setting of the detector in % obscuration. See the

Sensitivity Selection section of this manual for sensitivity determination if sensitivity is unknown.

2. Place the blocking material over the reflector, lining it up with the graduated marks that are 10 less than the detector setting in % obscuration. The detector should not alarm or fault. Keep the material in place for a minimum of 1 minute.

3. Place the blocking material over the reflector lining it up with the graduated marks that are 10 more than the detector setting in % obscuration. The detector should enter alarm within 1 minute.

4. The detector can be reset with the reset switch on the detector unit or remote reset.

LINE UP EDGE OF BLOCKING MATERIAL

WITH APPROPRIATE OBSCURATION LEVEL

MOVE BLOCKING MATERIAL TO

DESIRED AMOUNT OF OBSCURATION

Test Failure Checks

If the detector fails either the sensitivity or functional test, several steps should be taken to determine if the detector is faulty or simply needs to be re-adjusted, before returning the unit. These steps include:

1. Verify all wiring connections and appropriate power is applied to the detector.

2. Verify that the optical line of sight is free from obstructions or any other light sources including reflective objects such as gloss painted surfaces.

It is imperative that at least 90% of the received light is from the reflector alone, otherwise sensitivity cannot be assured.

3. Apply the maintenance procedure in this manual. Repeat the test procedure. If the detector still fails the test procedure proceed with step 4.

4. Repeat the alignment procedure in this manual. If the alignment procedure is successful repeat the test procedure. If the detector still fails the test it should be returned for repair.

6500 BEAM DETECTOR: SET-UP PROCEDURE SUMMARY

Beam Alignment ensure power is on

Course Alignment

Carry out using target eyepiece

Adjust using horizontal and vertical thumb screws

Fine Adjustment

Initiate using Alignment Switch

Continue adjustment using horizontal and vertical thumb screws

When the adjustment is complete press the Alignment Switch

Sensitivity Setting

Select using Sensitivity Switch

Final Gain Adjustment – ensure front cover is fitted

Initiate using the Reset Switch

Completed when the green LED blinks

Final Verification

Use obscuration filters or reflector test card to initiate Fire and Fault signals

MAINTENANCE

Note: Before cleaning the detector, notify the proper authorities that the smoke detector system is undergoing maintenance, and therefore the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.

1. Carefully clean the outer housing lens face. A damp soft cloth with a mild soap may be used. Avoid products with solvents or ammonia.

2. Carefully clean the reflector. A damp soft cloth with a mild soap may be used. Avoid products with solvents or ammonia.

Functional Testing

For periodic maintenance functional testing, the detector can either be tested using the Calibrated Test Filter method, by using the local test switch on the transmitter/receiver unit or remotely using the Remote Test Station.

The Remote Test Station, RTS151KEY, can be used with the 6500 beam smoke detector. The wiring diagram to connect the 6500/S to the key is displayed on page 2 of this manual.

The 6500S is equipped with an integral sensitivity test feature that consists of a calibrated test filter attached to a servomotor inside the detector optics.

When a test is initiated using the remote test station or local test switch the test filter is moved in the pathway of the light beam. If the correct level of signal reduction is received the detector will enter alarm. If the proper level of signal reduction was not achieved, indicating that the sensitivity of the detector is out of tolerance, the detector will enter the fault condition.

Note: This test should satisfy most local periodic maintenance and testing requirements.

If the detector fails this test refer to the Test Failure Checks described above

PAINTING

The outer aesthetic ring may be painted using enamel or acrylic paints either by brush or spray.

Note: Never paint the flat lens surface of the outer housing.

Figure 10. Reflector Test Card Procedure

DB200-00-02 5 I56-3797-003

Blinks Output by Yellow LED once the Device has Passed a

Local Test

Percent the detector has drifted

Number of blinks output

<10%

<20%

<30%

None

1

2

3 <40%

<50%

<60%

<70%

<80%

<90%

<100%

6

7

4

5

8

9

DB200-00-02

Pittway Tecnologica S.r.l., Via Caboto 19/3, 34147 TRIESTE, Italy

6

0832

6500(S)

DoP Ref:

0832-CPD-0326 12

EN54-12, EN54-17: 2005

Optical Beam Smoke Detector

Intended for use in fire detection and fire alarm systems in and around buildings

System Sensor Europe

Pittway Tecnologica Srl, Via

Caboto 19/3, 34147 TRIESTE,

Italy

I56-3797-003

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Frequently Answers and Questions

What range of voltage does the detector's electrical system operate on?
The electrical system operates on a voltage range of 15 to 32 VDC.
What is the maximum current draw of the detector in alarm condition?
In alarm condition, the maximum current draw is 8.5 mA.
What is the maximum permissible angular misalignment for the detector and reflector?
The maximum permissible angular misalignment is ±0.5° for the detector and ±10° for the reflector.
What type of batteries does the detector use?
The provided information does not specify the type of batteries used by the System Sensor 6500S.
What is the purpose of the orange alignment assistance label?
The orange alignment assistance label helps align the detector and reflector during installation.
Does the detector have a self-test feature?
The 6500S model includes an integral servo-controlled, calibrated test filter, which allows automatic remote alarm testing.
What is the maximum number of reflectors that can be used with the multi-mounting kit?
Only a single 20 cm x 20 cm reflector can be mounted using the multi-mounting kit.