Liebert® GXT4™ UPS 208 V, 5000 VA – 10,000 VA, 6000RTL630

Liebert® GXT4™ UPS 208 V, 5000 VA – 10,000 VA, 6000RTL630
Liebert® GXT4™ UPS 208 V, 5000 VA – 10,000 VA, 6000RTL630
User Manual
Table of Content
Important Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Glossary of Symbols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.0 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Available Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Appearance and Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.1 Appearance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.2 Rear Panel Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4 Removable Power Distribution Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5 Internal Battery Packs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.6 Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.6.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters . . . . . . . . . . . . . . . . .
1.6.2 Rectifier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6.3 Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6.4 Battery Charger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6.5 DC-to-DC Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6.6 Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6.7 Internal Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6.8 Maintenance Bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
13
13
13
13
13
13
13
1.7 Operating Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.7.1 Mains Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7.2 Manual Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7.3 Battery Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7.4 Battery Recharge Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7.5 Frequency Converter Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7.6 Active ECO Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
14
14
14
15
15
2.0 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.1 Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.2 What’s Included. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.3 Preparation for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.3.1 Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
i
Liebert® GXT4™ User Manual
2.4 Install the Main Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.4.1 Tower UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.4.2 Rack Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.5 External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.6 Connect Input/Output Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.6.1 Install the Power Distribution Box on 5000VA and 6000VA Models . . . . . . . . . . . . . . . . .
2.6.2 Remove the Power Distribution Box from 5000VA and 6000VA Models . . . . . . . . . . . . .
2.6.3 Remove the Power Distribution Cover from 8000VA and 10,000VA Models . . . . . . . . . .
2.6.4 Install the Power Distribution Box on 8000VA and 10,000VA Models . . . . . . . . . . . . . . .
2.6.5 Distribution Box Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.6.5.1 Terminal Block Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21
22
23
24
24
25
2.7 IT Power System Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.0 Operation and Display Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.1 LED Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.2 Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.3 LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.4 Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.4.1 Startup Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.2 Default Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.3 Main Menu Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.4 Prompt List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.5 Warning List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.6 Fault List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
33
33
42
42
43
4.0 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.1 Startup Checklist for the Liebert GXT4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.2 Starting the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.3 Manual Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.4 Manual Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.5 Shut Down the GXT4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.6 Disconnecting Input Power from the GXT4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.7 Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Liebert® GXT4™ User Manual
ii
5.0 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.1 Liebert IntelliSlot Communication Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.1.1 Liebert MultiLink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.2 USB Port Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.2.1 Configuration Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.3 Terminal Block Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.3.1 Any Mode Shutdown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.2 Battery Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.3 On Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.4 Low Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50
50
51
51
5.4 Remote Emergency Power Off—GXT4-6000RTL630. . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.0 Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.1 Replacing the Internal Battery Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.1.1 Battery Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.2 Battery Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.3 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.4 Checking UPS Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.5 Checking UPS Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.6 Replacing the Power Module on 8000 and 10,000VA models . . . . . . . . . . . . . . . . . . . . . 57
7.0 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.1 UPS Symptoms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.1.1 Indicator and LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.1.2 Audible Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
7.2 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
8.0 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
8.1 Auto-Learning Battery Run Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
8.2 Product Warranty Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
8.3 Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
iii
Liebert® GXT4™ User Manual
List of Figures
Figure 1-1: Liebert GXT4 5000VA and 6000VA, front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 1-2: Rear panel—5000VA and 6000VA with input power hard-wired box . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 1-3: Rear panel—GXT4-6000RTL630 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 1-4: Rear panel—8000VA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 1-5: Power distribution models for 5000 VA and 6000 VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 1-6: Power distribution models for 8000 VA and 10,000 VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 1-7: Power distribution models for 8000 VA and 10,000 VA models (continued) . . . . . . . . . . . . . . . . . . . . 11
Figure 1-8: Internal battery pack with connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 2-1: Support bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 2-2: Remove the front plastic bezel cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 2-3: Rotate the operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 2-4: External battery cabinets connected to GXT4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 2-5: Power distribution box removal from 5000VA and 6000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 2-6: Power distribution box removal from 8000VA and 10,000VA models . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 2-7: Distribution box electrical connections diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 2-8: Terminal block connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 3: Remove cover from IT Power System Connectors compartment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 3-1: Operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 3-2: Menu structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 3-3: Startup screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 3-4: Startup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 3-5: Starting and Start Successful screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 3-6: Default screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 3-7: Main Menu screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 3-8: Status screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 3-9: CONFIGURATION screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 3-10: UPS screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 3-11: Battery screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 3-12: ECO Mode screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 3-13: LCD screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 3-14: Language screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 3-15: Color screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 3-16: Factory Default screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 3-17: Control screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 3-18: Turn UPS On or Off screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 3-19: Alarm Control screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 3-20: Batt Test screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 3-21: Log screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 3-22: Clear Log screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 3-23: About screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 3-24: Network screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Liebert® GXT4™ User Manual
iv
Figure 5-1: Terminal-block communication pin layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 5-2: REPO switch connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 6-1: Removing the front bezel cover and battery door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 6-2: Disconnecting the battery plug and battery receptacle (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 6-3: Pull out the battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Figure 6-4: Removing power module from Liebert GXT4 8000 and 10,000VA models . . . . . . . . . . . . . . . . . . . . . 57
v
Liebert® GXT4™ User Manual
List of Tables
Table 1-1: UPS models, power ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 2-1: Branch circuit breaker ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 2-2: Electrical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 3-1: LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 3-2: Control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 3-3: System prompts and meanings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 3-4: Warning list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 3-5: Fault list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Table 5-1: Output voltage option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Table 6-1: Replacement internal battery pack model number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 7-1: Description of the displayed fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Table 7-2: Audible alarm description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Table 7-3: Troubleshooting table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Table 8-1: UPS specifications—5000, 6000, 8000 and 10,000 models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Table 8-2: UPS specifications—Liebert GXT4-6000RTL630 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Table 8-3: Internal battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Table 8-4: External battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Table 8-5: Power distribution specifications: GXT4-5000RT208, GXT4-6000RT208 and GXT4-6000RTL630 *. . 66
Table 8-6: Power distribution box specifications for GXT4-8000RT208 and GXT4-10000RT208 . . . . . . . . . . . . . 67
Table 8-7: Power distribution box specifications for GXT4-8000RT208 and GXT4-10000RT208 . . . . . . . . . . . . . 67
Table 8-8: Battery run time, minutes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Liebert® GXT4™ User Manual
vi
Important Safety Instructions
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety and operating instructions before
operating the uninterruptible power system (UPS). Adhere to all warnings on the unit and in this manual.
Follow all operating and user instructions. This equipment can be operated by individuals without previous
training.
This product is designed for commercial/industrial use only. It is not intended for use with life support and
other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label.
The UPS is designed for data processing equipment. The UPS is not for use in a computer room as
defined in the standard, Protection of Electronic Computer/Data Processing Equipment ANSI/NFPA 75. If
uncertain, consult your dealer or local Emerson Network Power® representative.
This UPS is designed for use on a properly grounded (earthed), 100/200, 110/220, 115/230,
120/208,120/240 or 127/220VAC, 50 or 60Hz supply. The factory default setting is 120/208VAC, 60Hz.
Installation instructions and warning notices are in this manual.
The Liebert GXT4 208VAC 5000 - 10000 is designed for use with a four-wire input (L1, L2, N, G).
The Liebert GXT4-6000RTL630 is designed be used with a three-wire, two-phase utility source (L1, L2, G).
! WARNING
The battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed when replacing the battery pack:
•
•
•
•
•
Wear rubber gloves and boots
Remove rings, watches and other metal objects.
Use tools with insulated handles.
Do not lay tools or other metal objects on the batteries.
If the battery kit is damaged in any way or shows signs of leakage, contact your local Emerson
representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Handle, transport and recycle batteries in accordance with local regulations.
! WARNING
Although the Liebert GXT4 has been designed and manufactured to ensure personal safety,
improper use can result in electrical shock or fire. To ensure safety, observe the following
precautions:
•
•
•
•
Turn Off and unplug the Liebert GXT4 before cleaning it.
Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
Never block or insert any objects into the ventilation holes or other openings of the UPS.
Do not place the Liebert GXT4 power cord where it might be damaged.
ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT4 complies with the limits for a Class A digital
device, pursuant to Part 15 of FCC rules.
Operation is subject to the following conditions:
• This device may not cause harmful interference.
• This device must accept any interference received, including interference that may cause undesired
operation. Operating this device in a residential area is likely to cause harmful interference that users
must correct at their own expense.
The Liebert GXT4 series complies with the requirements of EMC Directive 2004/108/EC and the published
technical standards. Continued compliance requires installation in accordance with these instructions and
use of accessories approved by Emerson.
1
Liebert® GXT4™ User Manual
Important Safety Instructions
NOTICE
This is a product for restricted sales distribution to informed partners. Installation restrictions or
additional measures may be needed to prevent radio interference.
Operate the UPS in an indoor environment only in an ambient temperature range of 0-40°C (32-104°F).
Install it in a clean environment, free from moisture, flammable liquids, gases and corrosive substances.
The Liebert GXT4-5000RT208, Liebert GXT4-6000RT208 and the Liebert GXT4-6000RTL630 contain no
user-serviceable parts except the internal battery pack. The Liebert GXT4-10000RT208 and the Liebert
GXT4-8000RT208 contain no user-serviceable parts except the internal battery pack and the Power
Module. The UPS On/Off push buttons do not electrically isolate internal parts. Under no circumstances
attempt to gain access internally due to the risk of electric shock or burn.
Do not continue to use the UPS if the front panel indications are not in accordance with these operating
instructions or the UPS performance alters in use. Refer all faults to your dealer.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the
required precautions. Keep unauthorized personnel away from the batteries. Keep unauthorized personnel
away from the batteries. Proper disposal of batteries is required. Refer to your local laws and regulations
for disposal requirements.
Never block or insert any object into the ventilation holes or other openings.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS, for
example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using half-wave
rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn Off and isolate the UPS before cleaning it. Use only a soft cloth, never liquid or aerosol cleaners.
Information for the Protection of the Environment
UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic cards,
electronic components). The components removed must be taken to specialized collection and disposal
centers.
Liebert® GXT4™ User Manual
2
Glossary of Symbols
Glossary of Symbols
Risk of electrical shock
!
Indicates caution followed by important instructions
AC input
AC output
i
-
Requests the user to consult the manual
+
Indicates the unit contains a valve-regulated lead acid battery
PbH2SO4
R
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
WEEE
3
Liebert® GXT4™ User Manual
Glossary of Symbols
Page intentionally left blank.
Liebert® GXT4™ User Manual
4
Product Description
1.0 Product Description
The Liebert GXT4 is a compact, online uninterruptible power system (UPS) that continuously conditions
and regulates its output voltage. The UPS is designed to supply microcomputers and other sensitive
electronic equipment with clean sine wave input power.
Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject
to voltage sags, spikes and complete failure that may interrupt computer operations, cause data loss and
damage equipment.
The Liebert GXT4 protects equipment from these disturbances. The Liebert GXT4 continuously charges its
batteries from the mains, enabling it to supply power to connected loads, even when the mains fail.
This section describes the UPS, its features, models, appearance and components, operating principles
and operating mode.
1.1 Features
The UPS includes these features:
• Intelligent battery management to extend battery life
• LCD for user-friendly operation and local monitoring and configuration of operational parameters
• Flexible network management with Liebert MultiLink® software
• Fan fault self-inspection and automated diagnostic function
• Intelligent fan operation, automatically changing rotation speed depending on system requirements, to
decrease power consumption and noise
• Input circuit breaker to ease recovery from overloads
• CE mark and safety approval from CE
• Communication options: USB port, Liebert IntelliSlot® port and terminal block communication
• Dry contacts for remote monitoring
• Input power factor greater than 0.99
• Output voltage selection function
1.2 Available Models
Available models of the UPS are listed in Table 1-1:
Table 1-1
UPS models, power ratings
Model Number
Nominal Power Rating
GXT4-5000RT208
5000VA / 4000W
GXT4-6000RT208
6000VA / 4800W
GXT4-6000RTL630
6000VA / 4200W
GXT4-8000RT208
8000VA / 7200W
GXT4-10000RT208
10000VA / 9000W
5
Liebert® GXT4™ User Manual
Product Description
1.3 Appearance and Components
1.3.1
Appearance
The Liebert GXT4 rack/tower models in various power ratings have the same general appearance,
controls and features (see Figure 1-1). The various rack/tower models differ largely in the type of
receptacles each has.
Figure 1-1 Liebert GXT4 5000VA and 6000VA, front view
Upper Bezel
Operation and Display Panel
Upper Bezel
Operation and
Display Panel
Lower Bezel and Battery Access Door
1.3.2
Lower Bezel and Battery Access Door
Rear Panel Features
The rear panel of the Liebert GXT4 has these features:
• Liebert IntelliSlot® Port
• USB port
• Input Circuit Breaker
• Maintenance Bypass Circuit Breaker (not present on all optional POD’s)
• REPO connection
• Input Receptacle
• General Output Receptacles (on optional PODs)
• External Battery Connector
• Cooling Fan
• Terminal Block Communication
• Output Circuit Breakers (on optional PODs)
Liebert® GXT4™ User Manual
6
Product Description
Figure 1-2 Rear panel—5000VA and 6000VA with input power hard-wired box
Knockouts for
Hard-Wired
Power Input
and Output
Liebert IntelliSlot
Unity-DP Card
USB Port
REPO
Terminal Block
Communication
External Battery
Connector
Input Breaker
NOTE
Hard-wired and hard-wired/receptacle boxes that include a manual bypass switch permit AC
power to continue to flow from the utility input to the load while the box is removed from the UPS.
For details, refer to 2.6 - Connect Input/Output Power.
Figure 1-3 Rear panel—GXT4-6000RTL630
REPO Connection
Block
USB Port
Terminal Block
Communication
Output Breaker for
L6-20R #2 and #3
Output Breaker
for L6-30R #4
External
Battery
Connector
Liebert IntelliSlot
Unity-DP Card
Input Breaker
for L6-30P #1
IT Power
System
Access
Cover
Maintenance
Bypass Breaker
Output Breaker
for L6-30R #5
5
1
2
4
3
7
Liebert® GXT4™ User Manual
Product Description
Figure 1-4 Rear panel—8000VA
Terminal Block
Communication
Liebert IntelliSlot
Unity-DP Card
REPO Connection Block
Maintenance
Bypass Switch
USB Port
Output Breaker
Switch
Input
Breaker
Switch
Cover for Power
Distribution Box
Connections
Knockouts
for Hard-Wired
Power Input
External Battery
Connectors
Liebert® GXT4™ User Manual
8
Product Description
1.4 Removable Power Distribution Box
The UPS is shipped with a power-distribution pack installed. This box contains the UPS input circuit
breaker.
Figure 1-5 Power distribution models for 5000 VA and 6000 VA models
PD2-001 shown as example;
similar features on other distribution
boxes arranged differently
Maintenance
Bypass Breaker
Output Power
Breakers for
Pigtails
L14-30 Input
Power Connector
Push Button Output
Power Breakers for
L5-20 Receptacles
PD2-001
Receptacles: four 5-20; one
L14-30; one L6-30R
L14-30 Output
Power
Connectors
PD2-005
Receptacles: four L5-20R; two L6-30R
PD2-002
Receptacles: two 5-20R; two L6-20R
PD2-003
receptacles: four 5-20R; two L6-30R
PD2-006
Receptacles: four L6-20R; two L6-20R
PD2-004
Receptacles: four L5-20R; two L5-30R
PD2-007
Receptacles: two L6-30R; two L6-20R
9
Liebert® GXT4™ User Manual
Product Description
Figure 1-6 Power distribution models for 8000 VA and 10,000 VA models
PD2-101 shown as example;
similar features on other
distribution boxes arranged differently
Output Circuit Breaker
Switch for L6-30R Pigtail #1
5-20R Output
Receptacles
L6-30ROutput
Receptacles
Push Button
Circuit Breakers
for 5-20R
5-20R Output
Receptacles
Receptacles
PD2-101
Receptacles: two L6-30R; eight 5-20R
2
1
Output Circuit Breaker
Switch for L6-30R Pigtail #2
PD2-105
Receptacles:
four 5-20R
two L5-30R
two L5-20R
PD2-102
Receptacles:
four L6-20R
four 5-20R
PD2-103
Receptacles:
four L6-30R
four 5-20R
PD2-106
Receptacles:
four L6-20R
four L5-20R
PD2-104
Receptacles:
four 5-20R
two L6-30R
two L6-20R
Liebert® GXT4™ User Manual
10
Product Description
Figure 1-7 Power distribution models for 8000 VA and 10,000 VA models (continued)
PD2-107
Receptacles: four L5-20R;
four 5-15R
PD2-201
Receptacles:
two IEC320-C19
eight IEC320-C13
PD2-108
Receptacles:
two L6-30R;
two L6-20R
PD2-202
Receptacles:
(12) IEC320-C13
PD2-109
Receptacles:
two L14-30R
PD2-204
Receptacles:
two IEC309-32A
four IEC320-C13
PD2-200
Receptacles:
four IEC320-C19
four IEC320-C13
11
Liebert® GXT4™ User Manual
Product Description
1.5 Internal Battery Packs
The UPS has two internal battery packs behind a battery access door on the front of the unit. Each internal
battery pack is fitted with a connector to link to the UPS.
NOTE
GXT4 10,000-VA battery pack shown in Figure 1-8. 5000-VA and 6000-VA
battery packs have the same features.
Figure 1-8 Internal battery pack with connector
Battery Handle
Battery Connector
Front of Battery Pack
1.6 Major Components
The UPS is composed of mains input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery charger,
DC-to-DC converter, battery, dynamic bypass and UPS output.
Maintenance Bypass
(5/6 kVA in POD)
(8/10 kVA in frame)
Internal
Bypass
L1
TVSS
EMI/RFI
Input
Filter
L2
N
General Outlet
(POD
Dependent )
L1
Rectifier/PFC
DC-DC
Converter
Inverter
EMI/RFI
Output
Filter
L2
N
G
G
Battery
Charger
General Outlet
(POD
Dependent )
General Outlet
(POD
Dependent )
General Outlet
(POD
Dependent )
Battery
1.6.1
General Outlet
(POD
Dependent )
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters
These UPS components provide surge protection and filter both electromagnetic interference (EMI) and
radio frequency interference (RFI). They minimize any surges or interference present in the mains line and
keep the sensitive equipment protected.
Liebert® GXT4™ User Manual
12
Product Description
1.6.2
Rectifier/Power Factor Correction (PFC) Circuit
In normal operation, the rectifier/power factor correction (PFC) circuit converts mains AC power to
regulated DC power for use by the inverter while ensuring that the waveshape of the input current used by
the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
• The mains power is used as efficiently as possible by the UPS.
• The amount of distortion reflected on the mains is reduced.
This results in cleaner power being available to other devices in the building not being protected by the
Liebert GXT4.
1.6.3
Inverter
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and inverts it
into precise, regulated sinewave AC power. Upon a mains power failure, the inverter receives its required
energy from the battery through the DC-to-DC converter. In both modes of operation, the UPS inverter is
on-line and continuously generating clean, precise, regulated AC output power.
1.6.4
Battery Charger
The battery charger utilizes energy from the mains power and precisely regulates it to continuously float
charge the batteries. The batteries are being charged whenever the Liebert GXT4 is connected to mains
power.
1.6.5
DC-to-DC Converter
The DC-to-DC converter utilizes energy from the battery system and raises the DC voltage to the optimum
operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency
and voltage, thus increasing reliability.
1.6.6
Battery
The Liebert GXT4 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life,
operate the UPS in an ambient temperature of 15°C to 25°C (59°F to 77°F). Optional external battery
cabinets are available to extend battery run times. For run times, see Table 8-8.
1.6.7
Internal Bypass
The Liebert GXT4 provides an alternate path for mains power to the connected load in the unlikely event of
a UPS malfunction. Should the UPS have an overload, overtemperature or any other UPS failure
condition, the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by
an audible alarm and illuminated amber Bypass LED (other LEDs may be illuminated to indicate the
diagnosed problem). To manually transfer the connected load from the inverter to bypass, press the
Standby/Manual Bypass button once and hold it for about 2 seconds
1.6.8
Maintenance Bypass
The Liebert GXT4 provides a manual maintenance bypass in a removable section of the rear of the UPS.
This allows replacement of the UPS in the event of a UPS malfunction while keeping the connected
equipment powered with utility power.
NOTE
The bypass power path does NOT protect the connected equipment from disturbances in
the mains supply.
13
Liebert® GXT4™ User Manual
Product Description
1.7 Operating Mode
The UPS operation modes include the following: Mains (AC) Mode, Bypass Mode, Battery Mode, Battery
Recharge Mode, Active ECO Mode and Frequency Converter Mode.
Refer to 3.0 - Operation and Display Panel for details about the operating mode indicators and control
buttons.
1.7.1
Mains Mode
During Mains Mode, the mains provides input power to the Liebert GXT4. The filters, PFC circuit and
inverter process this power to provide high-quality sine wave power to connected loads. The UPS
maintains the batteries in a fully charged state.
1.7.2
Manual Bypass Mode
Manual Bypass Mode occurs when the unit is manually placed in internal bypass by navigating the LCD
menu to select 3 Control > 1 Turn On & Off > Turn UPS Bypass. Bypass operation is indicated by an
audible alarm and illuminated amber bypass indicator. (If other indicators are illuminated, refer to 7.0 Troubleshooting). During Bypass Mode, mains power bypasses the inverter and provides energy to the
connected load.
NOTICE
Risk of loss of power to the connected load. Can cause equipment damage.
Turning Off the UPS in Bypass Mode will result in loss of output power to the connected load.
1.7.3
Battery Mode
The Liebert GXT4 enters Battery Mode when mains power fails or is outside acceptable limits. The battery
system supplies power through the DC-to-DC converter to the inverter to generate clean AC power for the
connected loads.
When the Liebert GXT4 enters Battery Mode, the UPS sounds a half-second beep at 10-second intervals.
When approximately 2 minutes of run time remains, the beeps sound every 5 seconds to warn that the
battery is getting low (this Low Battery Warning is user-configurable).
In Battery Mode, the battery indicator will illuminate and the LCD will show the prompt utility power not
available.
Press either the Up or Down button once, then press the Enter button to clear the prompt and silence the
audible alarm. Once the alarm prompt has been acknowledged, the screen showing the estimated battery
run time and battery capacity will be visible. Refer to 7.0 - Troubleshooting.
For approximate battery run times, refer to Table 8-4.
NOTICE
Risk of loss of power to the connected load. Can cause equipment damage.
Turning Off the Liebert GXT4 when it is in Battery Mode will result in loss of output power to the
connected load.
If the UPS is turned Off manually, it must be manually restarted after mains power returns.
If the UPS is turned Off by a communication signal or because the batteries are depleted, it will
operate as set in the configuration program for Auto-Restart (Refer to 5.2.1 - Configuration
Program).
1.7.4
Battery Recharge Mode
Once mains power is applied to the Liebert GXT4, the Battery Charger begins charging the batteries.
Liebert® GXT4™ User Manual
14
Product Description
1.7.5
Frequency Converter Mode
All models of the Liebert GXT4 are capable of frequency conversion. Frequency Conversion Mode can be
selected using the configuration program. Allowable frequency operating modes include:
• Auto Sensing - 50Hz or 60Hz – Bypass Enabled
• Auto Sensing - 50Hz or 60Hz – Bypass Disabled
• Frequency Converter - 50Hz – Bypass Disabled
• Frequency Converter - 60Hz – Bypass Disabled
NOTE
The default for all models of the Liebert GXT4 is “Auto Sensing - 50Hz or 60Hz – Bypass
Enabled.”
! WARNING
Risk of electric shock. Can cause injury or death.
Never touch the AC input receptacle while the UPS is operating. Voltage may still be present even
when the AC input indicator is Off.
1.7.6
Active ECO Mode
All Liebert GXT4 models can operate in Active ECO Mode. In this mode, the connected equipment is
powered through the bypass path to increase efficiency, reducing the electrical costs.
Active ECO mode keeps the rectifier and inverter operating, allowing the inverter to remain synchronized
to bypass. This synchronization allows the transfer of the connected equipment to UPS inverter power
almost seamlessly if bypass power falls outside the user-set limits. Once bypass power returns within the
acceptable parameters, the UPS will return to Active ECO Mode operation.
The default setting is Active ECO Mode Off.
15
Liebert® GXT4™ User Manual
Product Description
Page intentionally left blank.
Liebert® GXT4™ User Manual
16
Installation
2.0 Installation
Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to
do so in 4.2 - Starting the UPS.
2.1 Unpacking and Inspection
Unpack the UPS and conduct the following checks:
• Inspect the UPS for shipping damage. Report any shipping damage to the carrier and your local dealer
or Emerson® representative immediately.
• Check the accessories against the delivery list. If there is any discrepancy, contact your local dealer or
your Emerson representative immediately
! CAUTION
The UPS is heavy (see 8.0 - Specifications). Take proper precautions when lifting or
moving it.
2.2 What’s Included
The Liebert GXT4 is shipped with the following items:
• Terminal Block Communication terminals
• Compact Disk with
• Liebert MultiLink®
• Configuration program
• User manual (electronic version)
• Liebert IntelliSlot® Web card (IS-WEBCARD), factory-installed
• USB cable, one; 1.2 m (3.9 ft.)
• Rack mounting hardware including screws, handles, and rack slide kit
• Power Distribution Box, installed on Liebert GXT4
• Support base set, one
• Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
NOTE
The GXT4 External Battery Cabinet shipping package includes one battery cabinet, two spacers
for tower configuration, one DC power cable and rack mounting hardware, including screws,
handles and mounting rail kit.
17
Liebert® GXT4™ User Manual
Installation
2.3 Preparation for Installation
2.3.1
Installation Environment
Install the Liebert GXT4 indoors in a controlled environment, where it cannot be accidentally turned Off.
Place it where air flows unrestricted around the unit. The installation location must be free of water,
flammable liquids, gases, corrosives and conductive contaminants. Maintain an ambient temperature
range of 0 to 32 - 104°F (0 – 40°C).
NOTE
UPS operation in sustained temperatures outside the range of 59° – 77°F (15 – 25°C)
reduces battery life.
Installation Clearances
Maintain a clearance of at least 100 mm (4 inches) in the front and rear of the Liebert GXT4. Do not
obstruct the air inlets on the front panel or rear panel of the UPS—blocking the air inlets reduces ventilation
and heat dissipation, shortening the service life of the Liebert GXT4.
2.4 Install the Main Cabinet
The Liebert GXT4 may be installed in either a tower configuration or in a rack, depending on available
space and use considerations. Determine the type of installation and follow the appropriate instructions in
either 2.4.1 - Tower UPS Installation or 2.4.2 - Rack Installation.
2.4.1
Tower UPS Installation
To install the Liebert GXT4 as a tower:
1. Take the support bases out of the accessories bag (see Figure 2-1).
Figure 2-1 Support bases
Connectors
Spacers
Support Bases
2. If optional Liebert external battery cabinets will be connected to the Liebert GXT4, take out the spacers
shipped with the battery cabinet.
3. Connect the spacers and the support bases as shown in Figure 2-1. Each Liebert GXT4 needs two
assembled support bases, one in the front and one in the rear.
Liebert® GXT4™ User Manual
18
Installation
4. Adjust the direction of the operation and display panel and logo on the Liebert GXT4.
a. Remove the front plastic bezel cover as shown in Figure 2-2.
Figure 2-2 Remove the front plastic bezel cover
Front plastic
bezel cover
b. Pull the operation and display panel gently, rotate it 90 degrees clockwise and snap it back into
position, as shown in Figure 2-3.
Figure 2-3 Rotate the operation and display panel
Operation and
display panel
rotated clockwise
90 degrees
c.
Pull the logo on the front plastic bezel cover gently, rotate it 90 degrees clockwise and snap it back
into position. The rotated front plastic bezel cover is shown in Figure 2-3.
d. Replace the front plastic bezel cover on the Liebert GXT4. At this point, the UPS operation and
display panel and logo have been rotated 90 degrees clockwise, which provides upright viewing
for users.
5. Place the Liebert GXT4 and any battery cabinets on the support bases. Each Liebert GXT4 needs two
support assemblies.
2.4.2
Rack Installation
The Liebert GXT4 UPS and external battery cabinets (EBC), when installed in a rack enclosure, must be
supported by a shelf or rack-mount rails. The Liebert GXT4 UPS and EBC units ship with all required
hardware to allow rack-mount installation. Because different rack-mount options install differently, refer to
the installation instructions provided with the rack mount kit being used.
! CAUTION
The GXT4 is heavy; see 8.0 - Specifications. The UPS must be installed as near the bottom of a
rack as possible. If placed too high, it can make the rack top-heavy and prone to tipping over.
19
Liebert® GXT4™ User Manual
Installation
2.5 External Battery Cabinet Installation
! WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within.
Ensure that the Liebert GXT4 is shut down and power has been disconnected before beginning
any work on or in the unit.
! CAUTION
The external battery cabinet(s) are heavy (see Table 8-3). Take proper precautions when lifting
them.
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run
time. External battery cabinets are designed to be placed on one side of the UPS in a tower configuration
or stacked beneath the UPS in a rack configuration.
Figure 2-4 External battery cabinets connected to GXT4
GXT4
Cable connects battery
cabinet
Battery Cabinet
Second connector permits adding
more battery cabinets to 6000VA
Liebert GXT4
1. Inspect the external battery cabinet for freight damage. Report damage to the carrier and your local
dealer or Emerson representative.
2. Optional rack-mount hardware is shipped with the external battery cabinet and may be installed at this
time if desired.
• Securing hardware and slide rails are sold separately. Please contact your local dealer or Emerson
representative for these additional options and any assistance needed. Fasten the slides into
position with the screws per the instructions included with the slide rails.
3. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of support
base extensions ships with each external battery cabinet.
4. Verify the External Battery Cabinet breaker is in the Off position.
5. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, then to
the rear of the UPS.
6. Turn the External Battery Cabinet breaker to the On position.
Liebert® GXT4™ User Manual
20
Installation
7. Verify the circuit breaker on the External Battery Cabinet is in the On position.
8. Use the included configuration program or the LCD to program the UPS with the number of external
battery cabinets connected. Instructions for the configuration program are in 5.2.1 - Configuration
Program.
The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer
to Table 8-4.
NOTE
When removing an external battery cabinet, the circuit breaker on the rear of the cabinet must be
turned off before disconnecting the cable.
NOTE
If the UPS is to be shipped or stored for an extended time, the connector should be disconnected.
This will minimize any standby current drain on the batteries and help attain their design life.
2.6 Connect Input/Output Power
The GXT4-5000RT208, Liebert GXT4-6000RT208 and Liebert GXT4-6000RTL630 are shipped with a
power distribution box attached. The Liebert GXT4-8000RT208 and Liebert GXT4-10000RT208 are
shipped with a cover plate over the power distribution connector.
Follow the instructions below for removal and installation.
NOTE
Do not operate the UPS with the power distribution box removed. To shut off all power to this box
and to the load, utility input power must be disconnected.
2.6.1
Install the Power Distribution Box on 5000VA and 6000VA Models
1. Align the connectors and press the power distribution box onto the UPS.
2. Hold the box firmly against the UPS and tighten the captive screws except the one over the
maintenance bypass breaker.
3. Turn the output and input breakers On.
4. Start the UPS according to startup instructions.
5. Verify that the UPS lamp is illuminated.
6. Turn the maintenance bypass breaker Off.
7. Insert the maintenance bypass interlock bracket behind the captive screw and tighten the screw.
NOTE
The maintenance bypass breaker interlock bracket must be installed behind the captive screw,
and the screw must be tightened for the UPS to operate in inverter mode.
21
Liebert® GXT4™ User Manual
Installation
2.6.2
Remove the Power Distribution Box
from 5000VA and 6000VA Models
1. Manually transfer the connected equipment to the internal bypass.
a. From the main menu select CONTROL, then press Enter.
b. Select TURN ON & OFF and press Enter.
c.
Select TURN UPS BYPASS and press Enter. The UPS will transfer the connected loads to the
internal bypass. (For help, refer to 4.4 - Manual Bypass.)
d. Loosen the captive screw over the maintenance bypass breaker (see Figure 2-5 for the breaker’s
location).
e. Turn the maintenance bypass breaker On.
NOTICE
The load is unprotected from disturbances in the power supply while the UPS is on bypass.
2. Turn the output and input breakers Off.
3. Loosen other captive screws until the power distribution box releases.
4. Remove the power distribution box from the UPS and set it aside.
5. Loosen the screws over the plastic cover for the connector on the rear of the panel.
6. Slide the plastic cover over the connector and tighten the screws.
Figure 2-5 Power distribution box removal from 5000VA and 6000VA models
Extract these four
captive screws
Pigtails
removed for
clarity
Maintenance Bypass Breaker
Liebert® GXT4™ User Manual
22
Installation
2.6.3
Remove the Power Distribution Cover
from 8000VA and 10,000VA Models
! WARNING
Risk of electric shock. Can cause injury or death.
The UPS must be shut down or the load must be transferred to an external maintenance bypass
before a power distribution box may be added, changed or removed.
If the UPS will be shut down, the connected load must be shut down (refer to 4.5 - Shut Down the
GXT4).
If the UPS will be transferred to maintenance bypass, it must be transferred to an external
maintenance bypass. A maintenance bypass in the UPS frame must not be used.
Verify that the Liebert GXT4 is shut down and that all local and remote electric input power has
been disconnected before beginning any work on or in the UPS.
1. Shut down the Liebert GXT4 (for help, refer to 4.5 - Shut Down the GXT4).
a. From the Main Menu select CONTROL, press Enter, then select TURN ON & OFF.
b. Press the enter key.
c.
Select TURN UPS OFF, then press Enter.
Power to the connected loads is now Off.
2. Turn the output and input breakers Off.
3. Support the power distribution box and remove the two screws at the top of the box.
4. Remove the cover or power distribution box from the UPS and set it aside.
5. If removing a power distribution box, carefully pull apart the power distribution box connector and the
UPS connector.
Figure 2-6 Power distribution box removal from 8000VA and 10,000VA models
Extract screws at these places
Pigtails
removed for
clarity
Tabs slip into slots on UPS
23
Liebert® GXT4™ User Manual
Installation
2.6.4
Install the Power Distribution Box
on 8000VA and 10,000VA Models
! WARNING
Risk of electric shock. Can cause injury or death.
The UPS must be shut down or the load must be transferred to an external maintenance bypass
before a power distribution box may be added, changed or removed.
If the UPS will be shut down, the connected load must be shut down (refer to 4.5 - Shut Down the
GXT4).
If the UPS will be transferred to maintenance bypass, it must be transferred to an external
maintenance bypass. A maintenance bypass in the UPS frame must not be used.
Verify that the Liebert GXT4 is shut down and that all local and remote electric input power has
been disconnected before beginning any work on or in the UPS.
1. With the cover or distribution box removed, press the UPS and distribution box connectors together.
Ensure that the connectors are fully seated.
2. Align the screw holes and press the power distribution box onto the UPS, making sure that the tabs at
the bottom of the box fit into the slots on the UPS.
3. Attach the box to the UPS by installing screws into the two holes at the top of the box.
4. Tighten the screws.
5. Turn the output and input breakers On.
6. Start the UPS according to startup instructions.
2.6.5
Distribution Box Electrical Connections
Electrical connections are made through a removable power distribution box that attaches to the rear of the
UPS.
• PD2-HDWR-MBS, PD2-001, PD2-002, PD2-003, PD2-004, PD2-005, PD2-006 and PD2-007 models
fit the 5000 and 6000VA models of the Liebert GXT4
• PD2-L630 fits the GXT4-6000RTL630
• PD2-101, PD2-102, PD2-103, PD2-104, PD2-105, PD2-106, PD2-107, PD2-108, PD2-109, PD2-200,
PD2-201, PD2-202, PD2-204models fit the 8000 and 10,000VA models of the Liebert GXT4
The installer must provide an upstream branch circuit breaker. The input circuit breaker on the distribution
box and the output circuit breaker on the rear of the power distribution box disconnect all power between
the main cabinet and the distribution box.
Models equipped with a manual bypass breaker pass bypass power directly to the bypass breaker from the
input terminal block. The input circuit breaker on the distribution box does not disconnect power from the
manual bypass breaker.
Table 2-1
Branch circuit breaker ratings
Unit Rating
5000VA
6000VA
8000VA
10,000VA
Liebert® GXT4™ User Manual
Maximum Breaker Rating
D Type 30A Long Delay
D Type 60A Long Delay
24
Installation
Figure 2-7 Distribution box electrical connections diagram
UPS
Input
CB
UPS
Output
CB
Input
CB
Maintenance
Bypass Breaker
Maintenance
Bypass Breaker
Output
Distribution
POD
Input
Output
Indicator Indicator
Utility
Input
Output
Indicator Indicator
Utility
Input
External
Branch CB
Output
Terminal
Block
Optional
Output
Distribution
Plate
Input
External
Branch CB
Distribution Box Electrical Connections
for 5000 and 6000VA Models
2.6.5.1
Output
CB
Distribution Box Electrical Connections
for 8000 and 10,000VA Models
Terminal Block Connections
Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share
the same conduit. Emerson recommends using strain relief when installing the wire.
Table 2-2
Electrical specifications
Recommended
(Maximum) External
Overcurrent Protection
Recommended Wire
(Including ground wire)
(75°C copper wire)
Maximum Wire
Accepted by
Terminal Block
GXT4-5000RT208
GXT4-6000RT208
GXT4-6000RTL630
30A
10AWG (4mm2)
8AWG (6mm2)
GXT4-8000RT208
GXT4-10000RT208
60A
6AWG (10mm2)
4AWG (16mm2)
UPS Model
25
Terminal
Tightening
Torque
20 in-lb
(2.26 Nm)
Liebert® GXT4™ User Manual
Installation
Figure 2-8 Terminal block connections
Liebert GXT4-5000 and 6000RT208
L2
N
L1
L2
OUTPUT
N
L1
INPUT
Liebert GXT4-8000 and 10,000RT208
L2
N
L1
L2
OUTPUT
N
L1
INPUT
NOTE
1. Emerson recommends installing a UL489-approved breaker upstream of unit.
2. The installer must provide circuit breaker protection according to local codes. The mains
disconnect should be within sight of the UPS or have appropriate an appropriate lock-out.
Maintain service space around the UPS or use flexible conduit.
3. The installer must provide output distribution panels, circuit breaker protection or emergency
disconnects according to local codes. Output circuits must not share a common conduit with
any other wiring.
4. Liebert GXT4 models with a cord-connected input plug that is to be used as the power
disconnecting device must be installed near a wall socket or outlet that is easily accessible per
the National Electric Code / NFPA 70 requirements. Models that qualify are:
• Liebert GXT4-6000RTL630 with standard POD
GXT4-5000RT208 and GXT4-6000RT208 fitted with the optional POD’s PD2-001,
PD2-002, PD2-003, PD2-004, PD2-005, PD2-006 and PD2-007.
Liebert® GXT4™ User Manual
26
Installation
2.7 IT Power System Configuration
1. Remove screws on the IT Power System Access Cover as shown in Figure 3.
2. Disconnect the connectors as shown in figure.
3. Install IT Power System Access Cover and screws.
Figure 3
Remove cover from IT Power System Connectors compartment
IT Power System
Connectors
Remove Screws
27
Liebert® GXT4™ User Manual
Installation
Page intentionally left blank.
Liebert® GXT4™ User Manual
28
Operation and Display Panel
3.0 Operation and Display Panel
This chapter describes the Liebert GXT4 controls, particularly the operation and display panel on the front
of the Liebert GXT4. The panel has four control buttons, seven LED indicators and a liquid crystal display
(LCD), as shown in Figure 3-1.
Figure 3-1 Operation and display panel
Battery Indicator
Inverter Indicator
Fault
Indicator
Bypass
Indicator
LCD
Panel
ECO Mode
Indicator
ESC
Button
Enter
Button
UP Button
DOWN Button
3.1 LED Indicators
The seven LED indicators on the front of the operation and display panel are:
• Inverter
• Battery
• Bypass
• ECO Mode
• Fault
Figure 3-1 shows the indicators’ locations; their descriptions and functions are shown in Table 3-1.
Table 3-1
LED Indicators
LED indicators
LED Color
Description
Inverter
Green
On when the inverter is supplying power
Bypass
Amber
On when the load is supplied by the mains through
automatic/manual bypass
Battery
Amber
On when the load is supplied by the battery
Fault
ECO Mode
Red
Green
On when an error has occurred within the UPS
On when the UPS is in ECO Mode
29
Liebert® GXT4™ User Manual
Operation and Display Panel
3.2 Control Buttons
The four control buttons on the front of the operation and display panel are:
• ESC
• Up
• Down
• Enter
Figure 3-1 shows the buttons’ locations; their descriptions and functions are shown in Table 3-2.
Table 3-2
Control buttons
Control Buttons
Description
ESC Button
Pressing this button returns to the previous menu or aborts any change in the input data field
before confirming.
Up Button
Pressing this button can move the cursor up or increase the value displayed in the input data
field. When a menu is displayed on several screens, pressing the button can scroll up.
Down Button
Pressing this button can move the cursor down or decrease the value displayed in the input data
field. When a menu is displayed on several screens, pressing the button can scroll down.
Enter Button
Pressing this button can enter the next level menu or confirm the parameter setting value.
3.3 LCD
The LCD panel shows the UPS status and enables changes to the UPS settings by assisting in navigating
through the Liebert GXT4’s menu (see 3.4 - Menu Structure).
Liebert® GXT4™ User Manual
30
Operation and Display Panel
3.4 Menu Structure
The menu structure of the LCD is shown in Figure 3-2.
Figure 3-2 Menu structure
Audible Alarm
Output
Startup on Bypass
Load
Status
Input
Battery
Enable Auto Restart
Time Since Startup
Frequency Selection
Start
Windows
System
Status
UPS
Enable Guaranteed
Shutdown
Output Level Selection
Configuration
Battery Cabinets
Turn UPS
On/Off
Turn UPS On
Turn UPS Off
BATT
Low Battery Time Warning
Batt Test Interval
Main
Menu
Control
Alarm
Control
1. Audible Alarm On
2. Audible Alarm Off
Batt Test
1. Start
2. Cancel
3. Batt Test Result
Batt Replace Time
Enable /Disable
Voltage
Tolerance
ECO Mode
View Log
Frequency
Tolerance
Log
Requalification
Time
Clear Log
About
Factory
Default
PN/SN/Firmware Version
Language
Address: MAC
LCD
Color
Address: IPV4
Network
1 English
2 French
Address: IPV6STATIC
Address: IPV6AUTO
Address: IPV6LINK
31
Liebert® GXT4™ User Manual
Operation and Display Panel
3.4.1
Startup Screen
When the Liebert GXT4 is starting up, it initiates a self-test and displays the screen shown in Figure 3-3 for
about 10 seconds.
Figure 3-3 Startup screen
EMERSON
Network Power
After about 10 seconds, the LCD shows one of the On screens in Figure 3-4; the screen shown depends
on whether input power is available.
Figure 3-4 Startup screens
O/P: 0V
HZ 0.0A
I/P : 120 V 60HZ 0.0A
BATT: 100 % 320 MINS
LOAD: 0%
AC NOT AVAILABLE
START ON BATTERY?
YES NO
O/P: 0V 0HZ 0.0A
I/P : 120V 60HZ 0.0A
BATT: 100% 320MINS
LOAD: 0%
1
2
TURN ON UPS
YES NO
No.
Description
1
Input power is available.
2
Input power is not available.
To turn On the UPS, press either the Up or Down button to select YES and press the Enter button. The
UPS will start up, the LCD will display UPS STARTING and then START SUCCESSFUL after the UPS is
turned On, as shown in Figure 3-5.
Figure 3-5 Starting and Start Successful screens
UPS STARTING
START SUCCESSFUL
O/P: 0V 0HZ 0.0A
I/P : 120V 60HZ 0.0A
BATT: 100% 320MINS
LOAD: 0%
O/P: 120V 60HZ 4.6A
I/P : 120V 60HZ 5.0A
BATT: 100% 15MINS
LOAD: 40%
Liebert® GXT4™ User Manual
32
Operation and Display Panel
3.4.2
Default Screen
Press any button in the START SUCCESSFUL screen to enter the default interface, shown in Figure 3-6.
NOTE
Values shown in the default screen will vary depending on installation
and configuration.
In the default screen, the LCD shows the UPS model, output parameters, input parameters, battery
capacity with run time estimate and load percentage. The UPS operation mode (online /inverter, ECO,
Battery or Bypass) will be indicated by the LED indicators.
If no control button (ESC, Up, Down, Enter) is pressed for 2 minutes, the LCD will enter the screen saver
mode (backlight turns off). It will remain off until a control button is pressed.
Figure 3-6 Default screen
GXT4-UPS
3KVA
O/P: 120V 60HZ 11.7A
I /P: 120V 60HZ 13.1A
BATT: 100 % 3MINS
LOAD: 100%
3.4.3
Main Menu Screen
Press the Enter button in the default screen to enter the MAIN MENU screen, as shown in Figure 3-7.
To select a submenu, press the Up or Down button to move the cursor to the required item, then press the
Enter button to enter its submenu or set its parameter.
Figure 3-7 Main Menu screen
1
2
3
4
5
6
STATUS
CONFIGURATION
CONTROL
LOG
ABOUT
NETWORK
33
Liebert® GXT4™ User Manual
Operation and Display Panel
STATUS Screen
In the MAIN MENU screen, select STATUS to enter the Status Screen, displaying OUTPUT, LOAD, INPUT,
BATTERY and TIME SINCE STARTUP, as shown in Figure 3-8.
Figure 3-8 Status screens
OUTPUT
LOAD
VOLTAGE
:
120V
FREQUENCY :
60HZ
CURRENT
:
17.6A
POWER
: 2112 KWH
CAP :
WATT :
VA
:
INPUT
VOLT
FREQ
CURR
POWER
90%
1620W
1800VA
:
:
:
:
120V
60 HZ
18.6A
97KWH
BATTERY
TIME SINCE STARTUP
CAPACITY :
RUNTIME :
VOLTAGE :
90%
100 MINS
80V
05D
15H
30M
CONFIGURATION Screen
Select MAIN MENU > CONFIGURATION to enter the Configuration menu. This menu has seven
submenus, as shown in Figure 3-9.
In the CONFIGURATION screen, press the Up or Down button to move the cursor to the required item,
then press the Enter button to enter a submenu or set its parameters.
Figure 3-9 CONFIGURATION screen
1.
2.
3.
4.
5.
6.
7.
Liebert® GXT4™ User Manual
UPS
BATTERY
ECO MODE
OUTLET 1
OUTLET2
LCD
FACTORY DEFAULT
34
Operation and Display Panel
UPS Screen
Select MAIN MENU > CONFIGURATION > UPS to enter the UPS screen. This menu has six screens, as
shown in Figure 3-10.
Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm
the settings.
Figure 3-10 UPS screens
AUDIBLE ALARM
STARTUP ON BYPASS
GUARANTEE SHUTDOWN
OFF
NO
NO
ENABLE AUTO RESTART
FREQUENCY SELECTION
VOLTAGE SELECTION
YES
AUTO - BYPASS ENABLE
230
Battery Screen
Select MAIN MENU > CONFIGURATION > BATTERY to enter the BATTERY screen. This menu has four
screens, as shown in Figure 3-11.
Press the Up or Down button to increase or decrease the value of the settings, and press the Enter button
to confirm it.
Figure 3-11 Battery screen
EXT BATT CABINET
0
LOW BATTERY TIME
CABINETS
2
BATT TEST INTERVAL
8
MINS
BATT REPLACE TIME
WEEKS
2014 Y
35
1M
1D
Liebert® GXT4™ User Manual
Operation and Display Panel
ECO Mode Screens
Select MAIN MENU > CONFIGURATION > ECO MODE to enter the ECO MODE screens, as shown in
Figure 3-12.
Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm
the settings.
Figure 3-12 ECO Mode screen
ECO MODE
VOLTAGE TOLERANCE
ON
10%
FREQUENCY TOLERANCE
REQUALIFICATION TIME
3 Hz
5 MINS
No.
Description
1
Outlet control is on.
2
Outlet control is off.
LCD screen
Select Main Menu -> 2 CONFIGURATION -> 6 LCD to enter the LCD screen. This menu has two
submenus, LANGUAGE and COLOR, as shown in Figure 3-13.
Figure 3-13 LCD screen
1 LANGUAGE
2 COLOR
Liebert® GXT4™ User Manual
36
Operation and Display Panel
Select 1 LANGUAGE and press the Enter button to enter the LANGUAGE screen,
as shown in Figure 3-14.
The Liebert GXT4 is capable of supporting multiple languages. For the list of supported languages and
instructions on how to upload them, refer to the Configuration Program user manual on the included CD.
Figure 3-14 Language screen
1 English
2
Select ‘2 COLOR’ and press the Enter button to enter the COLOR screen, as shown in Figure 3-15.
Figure 3-15 Color screen
EMERSON
EMERSON
EMERSON
EMERSON
FACTORY DEFAULT screen
Select MAIN MENU -> 2 CONFIGURATION -> 7 FACTORY DEFAULT to enter the FACTORY DEFAULT
screen, as shown in Figure 3-16.
Figure 3-16 Factory Default screen
RESET ALL SETTINGS
TO FACTORY DEFAULT
SETTINGS?
YES NO
37
Liebert® GXT4™ User Manual
Operation and Display Panel
Control Screen
Select MAIN MENU -> 3 CONTROL to enter the CONTROL screen. This screen has three submenus,
TURN ON & OFF, ALARM CONTROL and BATT TEST, as shown in Figure 3-17.
In the CONTROL screen, press the Up or Down button to move the cursor to the required item, and press
the Enter button to enter its submenu.
Figure 3-17 Control screen
1 TURN ON & OFF
2 ALARM CONTROL
3 BATT TEST
TURN ON & OFF screen
Select MAIN MENU -> 3 CONTROL -> 1 TURN ON & OFF to enter the TURN ON & OFF screen. This
screen shows one of two displays, TURN ON UPS and TURN OFF UPS, depending on the state of the
UPS, as shown in Figure 3-18.
Figure 3-18 Turn UPS On or Off screen
TURN OFF UPS
TURN ON UPS BYPASS
TURN ON UPS
1
Liebert® GXT4™ User Manual
2
No.
Description
1
UPS is off.
2
UPS is on.
38
Operation and Display Panel
ALARM CONTROL screen
Select MAIN MENU -> 3 CONTROL -> 2 ALARM CONTROL to enter the ALARM CONTROL screen, as
shown in Figure 3-19. This section allows active audible alarms to be silenced. To completely turn off the
audible alarm, refer to CONFIGURATION > UPS as shown in Figure 3-10.
Figure 3-19 Alarm Control screen
1 AUDIBLE ALARM ON
2 AUDIBLE ALARM OFF
BATT TEST screen
Select MAIN MENU -> 3 CONTROL -> 3 BATT TEST to enter the BATT TEST screen, as shown in
Figure 3-20.
Figure 3-20 Batt Test screen
1 START
2 CANCEL
3 BATT TEST RESULT
Log Screen
Select MAIN MENU -> 4 LOG to enter the LOG screen. This screen has two submenus, VIEW LOG and
CLEAR LOG, as shown in Figure 3-21.
Figure 3-21 Log screens
254 /255
1 VIEW LOG
2 CLEAR LOG
255 OD 1H 17m AGO
UPS switch to Online
mode
39
Liebert® GXT4™ User Manual
Operation and Display Panel
CLEAR LOG Screen
Select MAIN MENU > LOG > CLEAR LOG to enter the CLEAR LOG screen, as shown in Figure 3-22.
Press the Up or Down button to move the cursor to the required item. Press the Enter button to confirm the
settings.
Figure 3-22 Clear Log screen
DO YOU WANT TO
CLEAR EVENT LOGS?
YES
NO
ABOUT Screen
Select MAIN MENU> ABOUT to enter the ABOUT screen, as shown in Figure 3-23. The ABOUT screen
displays UPS model, serial number, software version and hardware version.
Figure 3-23 About screen
PN: GXT4-2000 RT230
SN:1XXX60XXX1AFCXX
FW VER: U100D100
HW VER: H100
Liebert® GXT4™ User Manual
40
Operation and Display Panel
Network
Select MAIN MENU>NETWORK to enter the NETWORK screen.
The NETWORK screen displays the MAC address and the IPv4 IP address. If the Liebert GXT4 is fitted
with an optional Liebert IntelliSlot® Web card (Liebert IS-WEBCARD), the screen will display IPv6 IP
address settings (IPv6 requires configuration), as shown in Figure 3-24.
Figure 3-24 Network screens
ADDRESS MAC
ADDRESS IPV4
ADDRESS IPV6 STATIC
00-02-11-4X-AX
10.163.226 .231 /24
::
ADDRESS IPV6 LINK
ADDRESS IPV6 AUTO
Fe80::202:99ff:fe0f:4ba
2%1
::
41
Liebert® GXT4™ User Manual
Operation and Display Panel
3.4.4
Prompt List
A prompt screen is displayed during the operation of the system to alert you to certain conditions and/or to
require your confirmation of a command or other operation. See Table 3-3 for the prompts and meanings.
Table 3-3
System prompts and meanings
Prompt
Meanings
Mains Power Restored
The mains power returns and the UPS transfers back to mains (AC)
mode.
UPS Return From A Low Battery Condition
The UPS transfers back to mains (AC) mode from battery low mode.
UPS Return From Battery Mode
The UPS transfers back to mains (AC) mode from battery mode.
UPS Self Test Successful
The UPS self-test is successfully performed.
UPS Shutdown Command Received
The UPS shut down was initiated through communication.
UPS Turn Off
The UPS shuts down and has no output power.
UPS Turn On
The UPS starts up successfully and supplies protected power to the
load.
UPS Shutdown Process Had Been
Cancelled
The shutdown command sent through Liebert MultiLink or SNMP card
to the UPS is canceled,
ECO Mode Enabled
The UPS is configured to ECO mode operation,
ECO Mode Disabled
The UPS is configured to Online mode, supplying protected power to
the load through the inverter.
UPS Internal Temperature Return To
Normal
The internal temperature of the UPS recovers to normal range.
UPS Load Return From Overload
The loads are reduced, and the UPS recovers to normal state from
overload.
Load On Inverter
The inverter is on and supplies protected power to the load.
Load On ECO Bypass
The UPS is on ECO mode; the mains is supplying power to the load
directly to reduce energy usage.
Bypass Power Restored
The bypass power recovered and the UPS can now transfer to bypass.
3.4.5
Warning List
All UPS warning messages are described in Table 3-4.
Table 3-4
Warning list
Warning
Description
Mains Power Not Available
The mains power is not available, or it cannot satisfy the input
requirements for the UPS to operate from mains power
UPS Batteries Low And Exhausted Soon
The battery capacity is low and will be exhausted soon
UPS Has Switched To Battery Mode
The mains power is abnormal or the PFC side is faulty, the UPS
transfers back to Battery mode
Load On Bypass
The UPS transfers to Bypass mode, at this point, the input mains power
supplies power to the load directly, and the load is not protected
Input Power Wiring Error
L-N line reverse or PE not connected.
Bypass Power Not Available
The bypass power is not available, or it cannot satisfy the requirements
for the UPS transfers to bypass
UPS Maintenance Bypass Output
The UPS transfers to maintenance bypass.
AC input not qualified, cannot start UPS
The utility power is not qualified, the inverter cannot be powered up
Output disabled
REPO terminal connect error
Liebert® GXT4™ User Manual
42
Operation and Display Panel
3.4.6
Fault List
All UPS fault messages are described in Table 3-5.
Table 3-5
Fault list
Fault
Description
UPS Self-Test Failed
The battery is bad or weak or not connected.
UPS Overload
The UPS is overloaded.
Inverter Out Of Order
The inverter has failed.
Battery Weak/Bad
The battery is bad or weak.
Output Short Circuit
The output connection is short-circuited.
DC Bus Overvoltage
The DC bus is faulty.
UPS Overtemperature
Overtemperature occurs to the UPS and the UPS will transfer to Bypass mode.
Charger Out Of Order
The charger has failed.
Fan Out Of Order
At least one fan is failed.
DC Bus Discharge Fail
DC-DC failure occurs.
Rectifier Out Of Order
Rectifier failure occurs.
If a fault occurs, the UPS automatically switches to Bypass Mode. The original operating mode will be
maintained only in the case of a battery disconnection fault. The fault message alternates with UPS Mode
once a second, the red fault indicator on the operation and display panel lights up and the alarm sounds
continuously.
If a fault occurs:
1. Enter the ALARM CONTROL screen (see Figure 3-19), and select AUDIBLE ALARM ON or AUDIBLE
ALARM OFF to switch the alarm On or Off.
2. Enter the EVENT LOG screen (see Figure 3-21), and select VIEW LOG to view the entire Event log.
NOTE
There will be a short delay before the EVENT LOG screen displays the historical fault log to allow
the log to load.
43
Liebert® GXT4™ User Manual
Operation and Display Panel
Page intentionally left blank.
Liebert® GXT4™ User Manual
44
Operation
4.0 Operation
This section describes checks to be made before starting the UPS, how to start the UPS, manual battery
test, manual bypass, shutting down the UPS and disconnecting mains power from the UPS.
NOTE
The Liebert GXT4’s battery has been fully charged before delivery, but some charge will be lost
during storage and shipping. To ensure that the battery has adequate reserve power to protect the
connected load, charge the battery for 5 hours before putting the UPS into service.
4.1 Startup Checklist for the Liebert GXT4
Before starting the UPS, perform these checks:
___ 1. Check that the input plugs and loads are connected properly and reliably.
___ 2. Check that the battery cable is connected properly.
___ 3. Check that the communication cables are connected properly.
4.2 Starting the UPS
1. Plug the UPS into the appropriate AC outlet.
2. Close the input breaker on the rear of the unit.
3. The UPS will begin the startup sequence once AC power is present.
NOTE
The UPS will sound an audible alarm, this is normal.
4. On the LCD, press either the Up or Down button once, then press the Enter button to turn On the UPS.
The UPS will sound the audible alarm again as the output receptacles are now being powered by the
internal bypass, then will sound one more time as the inverter powers the connected equipment.
5. Check the LCD and LED indicators to ensure that the UPS is operating normally.
6. Check the load percentage on the default screen to ensure that the connected equipment is not
exceeding the UPS’s rated capacity.
The UPS is now providing conditioned and protected power to the connected equipment.
4.3 Manual Battery Test
To initiate a manual battery test, select MAIN MENU > CONTROL>BATT TEST>START.
• If the battery test results show FAILED, allow the UPS to recharge the batteries for 24 hours.
• Retest the batteries after 24 hours of charging.
• After the batteries have been retested, if the battery test still shows FAILED, contact your local
Emerson® representative or Emerson Network Power Channel Support.
45
Liebert® GXT4™ User Manual
Operation
4.4 Manual Bypass
To manually transfer the connected equipment to the internal bypass:
1. From the main menu select Control then press enter.
2. Select TURN ON & OFF and press Enter.
3. Select TURN UPS BYPASS and press Enter. The UPS will transfer the connected loads to the internal
bypass.
If the internal bypass is not available because of input power problems, pressing this button once will be
ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If
other indicators are illuminated, refer to 7.0 - Troubleshooting.)
4.5 Shut Down the GXT4
To shut down the UPS from the LCD:
1. From the Main Menu select CONTROL, press Enter, then select TURN ON & OFF.
2. Press the Enter key.
3. Select TURN UPS OFF, then press Enter. Press either the Up or Down button to move the cursor to
confirm the turn off command and press Enter. The UPS will sound an audible alarm; this is normal.
4. Power to the connected equipment is now Off.
The UPS display will still be illuminated because the batteries are still being charged. The UPS may now
be disconnected from AC power, and the UPS will completely shut down in approximately 15 seconds.
4.6 Disconnecting Input Power from the GXT4
1. After the UPS has been shut down as detailed in 4.5 - Shut Down the GXT4, disconnect the input
cable from the wall socket.
2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates
that the power-off is complete.
3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery
cabinet.
After powering Off the UPS, the UPS ceases output and the load is powered Off.
4.7 Maintenance Bypass
Maintenance Bypass Mode is used when maintenance or replacement is required. To place the unit in
Maintenance Bypass:
1. Place the UPS on internal bypass. This may be done by either of the following methods:
a. Refer to 4.4 - Manual Bypass.
b. Slide the bracket away from the manual bypass breaker on the rear of the UPS. This requires
loosening the captive screw and sliding the bracket up and away from the Manual Bypass breaker.
2. Move the Manual Bypass breaker on the rear of the UPS to the bypass position. This requires
loosening the captive screw and sliding the bracket up and away from the Manual Bypass breaker.
Liebert® GXT4™ User Manual
46
Communication
5.0 Communication
This section describes the communication ports on the rear of the UPS:
• Liebert IntelliSlot® port
• USB port (standard B-type)
• Terminal Block Communication
! CAUTION
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be
segregated and run separate from all other power cables.
5.1 Liebert IntelliSlot Communication Cards
The Liebert IntelliSlot port accepts four optional cards:
• Liebert IntelliSlot Web Card (IS-WEBCARD)
• Liebert IntelliSlot Relay Card (IS-RELAY)
• Liebert IntelliSlot MultiPort Card (IS-MULTIPORT)
• Liebert IntelliSlot Unity Card (IS-UNITY-DP)
The Liebert IntelliSlot Web Card provides SNMP monitoring and control of the UPS across the network.
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and
delivers support for Liebert MultiLink® shutdown software.
The Liebert IntelliSlot MultiPort Card provides four sets of contacts for support of up to four computers that
have Liebert MultiLink installed.
The Liebert IntelliSlot Unity Card provides SNMP and/or RS-485 monitoring of the UPS across the network
and/or building management system. The Liebert IntelliSlot UNITY card also enables monitoring external
temperature, humidity and contact closure inputs using external sensors.
Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the UPS or any
additional ancillary product for the Liebert GXT4. These instructions are available at:
multilink.liebert.com
5.1.1
Liebert MultiLink
Liebert MultiLink monitors the UPS continuously and can shut down the computer or server in the event of
an extended power failure. Liebert MultiLink can also be configured to shut down the UPS.
Liebert MultiLink can communicate with the UPS via the USB port, RS232 port, contact closures via
terminal block or over the network via SNMP using the Liebert IS-WEBCARD. An optional Liebert MultiLink
license kit permits shutting down multiple computers that are protected by the UPS.
For more information about the Liebert IntelliSlot SNMP Card, Liebert IntelliSlot Web Card and Liebert
MultiLink License Kits, visit the Liebert Web site (www.liebert.com) or contact your local Emerson®
representative.
47
Liebert® GXT4™ User Manual
Communication
5.2 USB Port Communication
The standard B-type USB port is used to connect the UPS and network server or other computer system
using Liebert MultiLink®.
A standard B-type USB port is provided to allow connection to a computer or network server. The USB port
can be used to communicate with the Liebert GXT4 configuration program (see section 5.2.1 Configuration Program for details) or Liebert MultiLink (refer to 5.1.1 - Liebert MultiLink for description)
that is provided on the CD that is included with the UPS.
5.2.1
Configuration Program
The configuration program is on the Liebert GXT4 CD and can be used instead of making configuration
setting changes from the LCD panel. The configuration program communicates to a computer running a
Microsoft® Windows® operating system via the included USB cable.
For most users, the factory default settings are adequate. This section give a brief overview of the features
and parameters that are available for modification, as well as the factory default settings. Should any
changes be necessary, refer to the Configuration Program User Manual that is located on the included CD
for further details.
The configuration program allows these features of the Liebert GXT4 to be changed:
• Change and set the display language
• Enable/Disable Auto-Restart (default is Enable)
• Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz, bypass disabled
(default is Auto-Select with bypass enabled)
• Set the Low Battery Warning alarm time from 2 to 30 minutes (default is 2 minutes)
• Enable/Disable the Auto-Battery test (default is Enable)
• Enable/Disable Auto-Restart after removing Remote shutdown (default is Disable)
• Set the wiring mode of Remote shutdown (default is normally open)
• Set the Auto-Enable output after remote shutdown (default is Disable)
• Set the Auto-Battery test to 8, 12, 16, 20, or 26 weeks (default is 8 weeks)
• Select the number of external battery cabinets connected to the UPS to adjust the remaining run time
calculated by Emerson® software products (default is zero)
• Select one of multiple output voltages to match various voltages (see Table 5-1).
Table 5-1
Output voltage option
UPS Model
FactoryDefault Setting
Output Voltage Option
GXT4-6000RTL630
208 VAC
200V, 208V, 220V, 230V, 240V
GXT4-5000RT208
GXT4-6000RT208
GXT4-8000RT208
GXT4-10000RT208
208/120 VAC
200/100V, 208/120V, 220/110V,
230/115V, 240/120V, 220/127V
NOTICE
The output voltage settings cannot be changed while the UPS is On and powering connected
loads.
Liebert® GXT4™ User Manual
48
Communication
NOTE
Programming the output voltage of the Liebert GXT4-5000RT208, GXT4-6000RT208, GXT48000RT208, and GXT4-10000RT208 models to 220/110VAC automatically derates both the VA
and Watt ratings to 90% of the units ratings and programming the output voltage to 200/100VAC
automatically derates both the VA and Watt ratings to 80% of the units ratings (refer to 9.0 Specifications for the VA and Watt ratings)
NOTE
• This program is compatible with UPS models beginning with ‘GXT4,’ as in ‘GXT4-3000RT230.’
It is not compatible with earlier versions of the Liebert GXT UPS.
• A computer running Microsoft® Windows 2000®, Windows XP®, Windows Vista®, Windows 7 or
Windows 8 is required to set up and run the configuration program.
5.3 Terminal Block Communication
The Terminal Block includes eight pins, as shown in Figure 5-1.
Figure 5-1 Terminal-block communication pin layout
No.
Description
1
Low battery warning
2
On-battery warning
3
Any mode shutdown
4
Battery mode shutdown
49
Liebert® GXT4™ User Manual
Communication
5.3.1
Any Mode Shutdown
The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter
and static switch so that there is no power to the loads.
Any Mode Shutdown can be operated locally or remotely:
• Local Any Mode Shutdown can be performed by shorting the pins in terminal 3 for the UPS-models
ending in RT208, and pins1 and 2 for the GXT4-6000RTL630 model.
• Remote Any Mode Shutdown can be performed using a switch mounted at a remote location and
connected to the pins in terminal 3 for the UPS-models ending in RT208, and pins1 and 2 for the
GXT4-6000RTL630 model.
NOTE
Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown,
depending on the settings in the configuration program.
A current-limited source for this optocoupler (+12 VDC, 50 mA) will be available from the UPS.
The connection to the UPS for remote connection will be via terminal block connector.
Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations.
! WARNING
When the Auto-Enable output option is selected and the UPS output is disabled using Any Mode
Shutdown, the Liebert GXT4’s output can turn On automatically and without warning if the
connection is changed.
5.3.2
Battery Mode Shutdown
Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and static
switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS
will still be active.
Battery Mode Shutdown can be performed locally or remotely:
• Local Battery Mode shutdown can be performed by shorting the pins in terminal 4 for the UPS-models
ending in RT208, and pins3 and 4 for the GXT4-6000RTL630 model.
• Remote Battery Mode Shutdown can be performed using a switch mounted in a remote location and
connected to the pins in terminal 4 for the UPS-models ending in RT208, and pins 3 and 4 for the
GXT4-6000RTL630 model.
NOTE
Remote Power Off will be performed by NO contact.
A current-limited source (+12 VDC, 50 mA) will be available from UPS.
The connection to the Liebert GXT4 for remote connection will be via terminal block connector.
Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and
laws.
This signal must last for 1.5 seconds or longer.
A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown
timer. This timer cannot be stopped once triggered. If the mains power returns during this
countdown, the Liebert GXT4 will still shut down and must remain shut down for 10 seconds.
Whether the UPS turns back On when the power is restored depends on the auto-restart setting.
Liebert® GXT4™ User Manual
50
Communication
5.3.3
On Battery
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the
battery this dry contact will be closed.
5.3.4
Low Battery
Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the
battery and has reached the Low Battery Warning time selected in the configuration program, this dry
contact will be closed.
NOTE
The rated values for the dry contacts for the On Battery and Low Battery signals are:
• Rated Voltage: 30 V (AC or DC)
• Rated Current: 300 mA
5.4 Remote Emergency Power Off—GXT4-6000RTL630
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input
feeder breaker to remove all sources of power to the UPS and connected equipment to comply with
national and local wiring codes and regulations.
Figure 5-2 REPO switch connection diagram
UPS ships with REPO jumper
installed allowing the UPS
to operate
1
Opening the REPO connection will disable the UPS.
Manual restart using the front panel is required after
the REPO connection is closed again.
2
1
2
Normally closed switch system
(fail-safe)
! CAUTION
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should be
shielded and run separately from power cables.
51
Liebert® GXT4™ User Manual
Communication
Remote Emergency Power Off—GXT4-5000RT208,
GXT4-6000RT208, GXT4-8000RT208, GXT4-10000RT208
+24 V supplied
by GXT4 UPS
How UPS ships, with jumper removed
and in the accessory bag.
1
2
3
4
2
3
4
2
3
4
2
3
4
+24 V supplied
by GXT4 UPS
How UPS must be wired to operate with no repo connection.
Jumper in accessory bag must be installed.
1
+24 V supplied
by GXT4 UPS
How UPS must be wired to operate
with connection to a normally-closed (NC) repo connection.
Jumper in accessory bag must be removed as this wired
to a remote switch.
1
+24 V supplied
by GXT4 UPS
How UPS must be wired to operate
with connection to a normally-open (NO) repo connection.
Jumper in accessory bag must be installed.
Liebert® GXT4™ User Manual
1
52
Maintenance
6.0 Maintenance
This section describes replacing the internal battery pack, precautions, checking the Liebert GXT4’s status
and checking UPS functions.
! WARNING
The battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed before replacing the battery pack:
•
•
•
•
Remove rings, watches and other metal objects.
Use tools with insulated handles.
Do not lay tools or other metal objects on the batteries.
If the battery kit is damaged in any way or shows signs of leakage, contact your local Emerson
representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Handle, transport and recycle batteries in accordance with local regulations.
6.1 Replacing the Internal Battery Pack
The Liebert GXT4 is designed to allow the user to replace the internal battery pack safely. Refer to
Table 6-1 for internal battery pack part numbers for Liebert GXT4 UPS:
Table 6-1
Replacement internal battery pack model number
Replacement Internal Battery
Pack Model Number
Quantity
Required
GXT4-5000RT208
GXT4-6000RT208
GXT4-144VBATKIT
1
GXT4-6000RTL630
GXT4-240VBATKIT
2
GXT4-8000RT208
GXT4-10000RT208
GXT4-240VRTBKIT
2
53
Liebert® GXT4™ User Manual
UPS Model Number
Maintenance
6.1.1
Battery Replacement Procedures
Read all safety cautions before proceeding. A trained user can replace the internal battery pack when the
UPS is always in a restricted access location (such as a rack or server closet). Contact your local dealer or
Emerson representative to obtain the pricing of the appropriate replacement battery pack.
! CAUTION
Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to
the instructions.
1. Remove the front plastic bezel cover from the UPS.
2. Loosen and remove the 6 screws on the battery door, as shown in Figure 6-1.
3. Lay the battery door and screws aside for reassembly.
Figure 6-1 Removing the front bezel cover and battery door
Battery Door
Screws, 6
Front Bezel
4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown in
Figure 6-2.
Figure 6-2 Disconnecting the battery plug and battery receptacle (front view)
Battery
Connector
Battery
Receptacle
Battery
Connector
Battery
Receptacle
Liebert® GXT4™ User Manual
54
Maintenance
5. Grasp the battery handle, and pull the internal battery pack out of the UPS, as shown in Figure 6-3.
Repeat this step if both battery packs will be replaced. Each model has two battery packs.
Figure 6-3 Pull out the battery
5000 & 6000 VA models
6000RTL630, 8000VA /
10,000VA model
Internal
Battery
Pack
Internal
Battery
Pack
(one of 2)
Battery
Handle
Battery
Handle
Pull Out with Battery Handle
Each model has two
battery packs.
Pull Out with Battery Handle
6. Unpack the new internal battery pack. Take care not to destroy the packing.
Compare the new and old internal battery pack to make sure they are the same type and model. If so,
proceed with Step 7; if they are different, stop and contact your local Emerson representative, or
Emerson Channel Support.
7. Line up and slide in the new internal battery pack.
8. Reconnect the battery plug and battery receptacle
9. Push the battery wire and internal battery pack back into the UPS.
10. Reattach the front battery door with the six screws.
11. Reattach the front plastic bezel cover to the UPS.
NOTE
The internal battery pack is hot-swappable. However, caution should be exercised because during
this procedure the load is unprotected from disturbances and power outages. Do not replace the
battery while the UPS is operating in Battery Mode. This will result in a loss of output power and
will drop the connected load.
6.2 Battery Charging
The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their design
life. The Liebert GXT4 charges the batteries continuously when it is connected to the utility input power.
If the Liebert GXT4 will be stored for a long time, Emerson recommends connecting the UPS to input
power for at least 24 hours every four to six months to ensure full recharge of the batteries.
55
Liebert® GXT4™ User Manual
Maintenance
6.3 Precautions
Although the Liebert GXT4 has been designed and manufactured to ensure personal safety, improper use
can result in electrical shock or fire. To ensure safety, observe the following precautions:
• Turn Off and unplug the Liebert GXT4 before cleaning it.
• Wear rubber gloves and boots.
• Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
• Never block or insert any objects into the ventilation holes or other openings of the Liebert GXT4.
• Do not place the Liebert GXT4 power cord where it might be damaged.
6.4 Checking UPS Status
Emerson recommends checking the UPS operation status every six months.
• Check if the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm?
• Check if the UPS is operating in Bypass mode: Normally, the UPS operates in Normal Mode; if it is
operating in Bypass Mode, stop and contact your local Emerson representative or Emerson Channel
Support.
• Check if the battery is discharging: When the utility input is normal, the battery should not discharge. If
the UPS is operating in Battery Mode, stop and contact your local Emerson representative or Emerson
Channel Support.
6.5 Checking UPS Functions
NOTE
UPS function check procedures may interrupt power supply to the connected load.
Emerson recommends checking the UPS functions once every six months.
Back up the load data before conducting the UPS functions check. Procedures are as follows:
1. Press the Standby/Manual Bypass button to check whether the alarm and indicators are normal.
2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators are On
and the UPS is operating normally.
3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode.
The UPS should initiate battery self-test. Check to determine whether the battery is operating normally.
If not, stop and contact your local Emerson representative or Emerson Channel Support.
Liebert® GXT4™ User Manual
56
Maintenance
6.6 Replacing the Power Module on 8000 and 10,000VA models
! CAUTION
The UPS must be switched to manual bypass before personnel begin to replace the power
module.
NOTICE
During the procedure, the connected load will not be protected from power disturbances, such as
spikes, sags and failure.
To remove the UPS power module without shutting off power to the connected load:
1. Place the UPS on internal bypass. This may be done by any of the three following methods:
a. Refer to 4.4 - Manual Bypass.
b. Slide the bracket away from the manual bypass switch on the rear of the UPS; this requires
loosening the captive screw and sliding the bracket away from the manual bypass switch.
c.
Remove the front grille covering the power module.
2. Move the manual bypass breaker on the rear of the UPS to the bypass position; this requires loosening
the captive screw and sliding the bracket away from the manual bypass switch (see Figure 1-6).
3. Open the input circuit breaker on the rear of the UPS (see Figure 1-6).
4. Open the output circuit breaker on the rear of the UPS (see Figure 1-6).
5. Remove the top two front plastic bezels by pulling them forward.
6. Remove the power module cover grille and the battery cover grille with the screws securing them to
the frame.
7. Disconnect the slotted battery connectors from the internal battery packs.
8. If additional external batteries are used, disconnect the two external battery connectors.
9. Slide power module restraint lever up out of the locked position.
10. Slide the power module out the front, supporting its weight as it is withdrawn.
Figure 6-4 Removing power module from Liebert GXT4 8000 and 10,000VA models
Power module
pulled part of
the way out of
an 8000 or
10,000VA unit
11. Insert the replacement UPS power module.
12. Slide the power module restraint lever back into the locked position.
13. Reconnect the slotted internal battery connectors.
57
Liebert® GXT4™ User Manual
Maintenance
14. Reconnect the external battery cables, if used.
15. Reattach both front cover grilles.
16. Reattach the front plastic bezels.
17. Close the input circuit breaker on the rear of the UPS (see Figure 1-6).
18. Close the output circuit breaker on the rear of the UPS (see Figure 1-6).
19. Move the bypass breaker on the rear of the UPS back to the INVERTER position (see Figure 1-6).
20. Slide the bracket back next to the manual bypass breaker and tighten its thumbscrew.
21. Press the On button on the front panel one time to return the UPS to Normal Mode operation (see
Figure 3-1).
NOTE
The power module restraint lever must be fully engaged for the UPS to operate in
Normal Mode.
Liebert® GXT4™ User Manual
58
Troubleshooting
7.0 Troubleshooting
This section indicates various UPS symptoms a user may encounter and provides a troubleshooting guide
in the event the UPS develops a problem. Use the following information to determine whether external
factors caused the problem and how to remedy the situation.
7.1 UPS Symptoms
The following symptoms indicate the Liebert GXT4 is malfunctioning:
• The relative indicators illuminate, indicating the UPS has detected a problem.
• An alarm buzzer sounds, alerting the user that the UPS requires attention.
7.1.1
Indicator and LCD
In addition to the fault indicator being illuminated, the LCD will display the fault. The displayed fault on the
LCD is described in Table 7-1
Table 7-1
Displayed Fault
Description of the displayed fault
Cause
Corrective Steps
UPS self test failed
The battery is bad or weak.
Contact customer service.
UPS shutdown
command received
The UPS shuts down through communication. Contact customer service.
UPS overload
The UPS is overloaded.
Reduce the load and contact customer
service.
Inverter Out of Order
The inverter is faulty.
Contact customer service.
Battery Weak/Bad
The battery is bad or weak.
Replace the battery.
Output Short Circuit
The output connection is short-circuited.
Shut down the equipment and contact
customer service.
DC Bus Overvoltage
The DC bus is faulty.
Contact customer service.
UPS Overtemperature
Over-temperature occurs to the UPS and the
UPS will transfer to Bypass mode.
Reduce the load and contact customer
service.
Charger Out of Order
The charger is faulty.
Contact customer service.
Fan Out of Order
At least one fan is faulty.
Contact customer service.
DC Bus Discharge Fail A DC-DC failure occurs.
Contact customer service.
NOTE
If the UPS encounters a fault and no correction attempt is performed within 2 minutes, the LCD
backlight will flash (on 1 second and off 1 second) as an alert.
Press any button to exit the alert mode. If no correction attempt is performed on the UPS, the LCD
backlight will flash again until the UPS fault is corrected.
59
Liebert® GXT4™ User Manual
Troubleshooting
7.1.2
Audible Alarm
An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS operating
status. The audible alarm will sound as described in Table 7-2.
Table 7-2
Audible alarm description
Condition
Alarm
Battery discharge
Half-second beep every 10 seconds
Low battery
Two half-second beeps every 5 seconds
UPS fault, load on bypass
1-second beep every 4 seconds
UPS fault, no power to load
Continuous
Overload
Half-second beep every half second
Battery replacement
2-second beep every 2 minutes
Battery loss
Continuous
Wiring problem (loss of proper grounding for UPS)
Continuous
Bypass reminder
1-second beep every 60 seconds
7.2 Troubleshooting
In the event of an issue with the UPS, refer to Table 7-3 to determine the cause and solution. If the fault
persists, contact Emerson® Channel Support.
Table 7-3
Problem
UPS fails to start
Cause
Solution
UPS is short-circuited or
overloaded
Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in
output receptacles. Ensure loads are not defective or shorted internally.
Batteries are not charged
enough or not connected
Check to ensure the internal battery is connected. If it is not, make the
connection and try to start the unit. If the battery is connected, leave the
UPS connected to input power for 24 hours to recharge batteries, then try
to start the unit.
UPS is not plugged in
UPS is operating from battery mode. Ensure UPS is securely plugged
into the wall receptacle.
Battery indicator UPS input protection fuse has
is illuminated
blown/opened
UPS has
reduced battery
backup time
Troubleshooting table
UPS is operating from battery mode. Save data and close applications.
Replace UPS input fuse, then restart UPS.
Mains power is out of tolerance
UPS is operating from battery mode. Save data and close applications.
Ensure mains supply voltage is within acceptable limits for UPS.
Batteries are not fully charged
Keep UPS plugged in continuously at least 24 hours to recharge
batteries.
UPS is overloaded
Check load level indicator and reduce the load on the UPS.
Batteries may not be able to
hold a full charge due to age
Replace batteries. Contact your local dealer, Emerson representative or
Emerson Channel Support for replacement battery kit.
Battery indicator Battery source is not available;
is flashing.
continuous horn.
Check battery connections, completely power down and restart UPS.
NOTE: If the battery circuit opens while the UPS is running, it will be
detected when the next battery test is performed.
Because the voltage or
Bypass indicator
frequency is outside acceptable
is flashing.
limits, the bypass is disabled.
The AC input powers the PFC input and serves as the bypass source. If
the AC is present but the voltage or frequency exceeds the acceptable
range for safe operation with a load, the bypass will be disabled and this
indicator will flash, indicating that the bypass is unavailable.
Liebert® GXT4™ User Manual
60
Troubleshooting
When reporting a UPS issue to Emerson, include the UPS model and serial number. These are located in
several places for your ease of location:
• on the top panel (rack mount orientation)
• the left side (tower orientation)
• the rear panel
• on the front of the unit behind the front plastic bezel
• on the LCD select Main Menu > About.
61
Liebert® GXT4™ User Manual
Troubleshooting
Page intentionally left blank.
Liebert® GXT4™ User Manual
62
Specifications
8.0 Specifications
Table 8-1
UPS specifications—5000, 6000, 8000 and 10,000 models
Model Number
Model Rating
Dimensions, Rack Mount, W x D x H
Unit, in. (mm)
Shipping, in. (mm)
GXT45000RT208
4000W/5000VA
GXT46000RT208
4800W/6000VA
GXT48000RT208
7200W/8000VA
GXT410000RT208
9000W/10000VA
16.9 x 26.1 x 6.8 (430 x 662 x 173)
16.9 x 26.5 x 10.3 (430 x 672 x 261)
35 x 27 x 26 (889 x 686 x 661)
35 x 27 x 32 (889 x 686 x 813)
131.8 (59.8)
212.7 (96.7)
202.8 (92)
297.6 (135)
Weight lb (kg)
Unit, lb (kg)
Shipping, lb (kg)
Input AC Parameters
Nominal Operating Frequency
Factory Default VAC
L1-L2 Factory Default Input Phase Angle
Allowable Input Phase Angle
Factory Default L1-N, L2-N VAC
User Configurable L1-N, L2-N VAC
50 or 60Hz (Factory Default is 60Hz)
120/208VAC at 120 degrees
120 degrees
120 degrees
120, 180, 240 degrees, auto-sensing on application of alternating current
(Restrictions for L-N voltages other than 120VAC)
120 VAC nominal
100/110/115/120VAC (can be modified with configuration program)
Input Frequency w/o Battery Operation
Input Power Connection
120/208VAC at 120 degrees
40 - 70 Hz
Hard-Wired Terminal Block 3W + G (L-L-N-G)
150VAC
L1-N, L2-N Maximum Allowable VAC
Output AC Parameters
Factory Default VAC
120/208VAC @ 120 degrees
L1-L2 Factory Default Output Phase Angle
Allowable Output Phase Angle
120 degrees
120, 180, 240 degrees, auto-sensing on initial application of input AC
Factory Default L1-N, L2-N VAC
120VAC nominal
User Configurable L1-N, L2-N VAC
L1-N, L2-N, Operating Load Range
105% to 130%
131% to 150%
151% to 200%
>200% (impact load)
Bypass Protection Limits
Disable Bypass Operation
Re-Enable Bypass Operation
Disable Bypass Operation
100/110/115/120/127VAC, ±2%
1 Minute
10 seconds
1 second
At least 5 cycles
If input voltage exceeds ±15% of the nominal voltage
If input voltage returns to within ±10% of nominal output voltage
When the input frequency prevents synchronous operation
Environmental
32 to 104 (0 to 40)
Operating Temp, °F (°C)
5 to 122 (-15 to 50)
Storage Temp, °F (°C)
0% to 95%, non-condensing
Relative Humidity
Operating Elevation
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating
Audible Noise less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides
Agency
Safety
RFI/EMI
UL 1778, c-UL Listed
FCC Class A
Surge Immunity
IEEE/ANSI C62.41 Category A & B
Transportation
ISTA Procedure 1E
63
Liebert® GXT4™ User Manual
Specifications
Table 8-2
UPS specifications—Liebert GXT4-6000RTL630
Model Number
GXT4-6000RTL630
Model Rating
4200W/6000VA
Dimensions, Rack Mount, W X D X H, in. (mm)
Unit
16.9 x 22.6 x 8.5 (430 x 574 x 217)
Shipping
35 x 27 x 29 (889 x 686 x 737)
Weight, lb (kg)
Unit
132.2 (60)
Shipping
216.5 (98)
Input AC Parameters
Nominal Operating Frequency
50 or 60Hz (Factory Default, 60)
Factory Default VAC
208VAC
208/220/230/240VAC
(may be modified with configuration program)
176 – 280VAC
User Configurable VAC
Operating Voltage Range Without Battery Operation
Maximum Allowable VAC
280VAC
Input Frequency Without Battery Operation
40 - 70Hz
Input Power Connection
L6-30P Plug (on PD-L630 power distribution box)
Factory Default VAC
Frequency
208
(2) L6-20R and (2) L6-30R on 12" (300mm) cords
(on PD-L630 power distribution box)
50Hz or 60Hz, Nominal
Waveform
Sinewave
Duration Inverter Will Support Rated Load
105% to 130%
1 Minute
Output AC Parameters
Output Connections
131% to 150%
10 seconds
151% to 200%
1 second
>200% (impact load)
At least 5 cycles
Bypass Protection Limits
Disable Bypass Operation
Re-Enable Bypass Operation
Disable Bypass Operation
If input voltage exceeds ±15% of the nominal voltage
If input voltage returns to within ±10% of nominal output voltage
When the input frequency prevents synchronous operation
Environmental
Operating Temp, °F (°C)
32 to 104 (0 to 40); No Derating
Storage Temp, °F (°C)
5 to 122 (-15 to 50)
Humidity
Operating Elevation
Audible Noise
0% to 95% Relative Humidity, non-condensing
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating
Less than 55dBA at 3.2ft. (1m) rear;
Less than 50dBA at 3.2ft. (1m) front and sides
Agency
Safety
Liebert® GXT4™ User Manual
UL 1778, c-UL Listed
EMI/EMC
FCC Class A
ESD
EN61000-4-2
Radiated Susceptibility
EN61000-4-3
Electrical Fast Transient
EN61000-4-4
Surge Immunity
EN61000-4-5
Transportation
ISTA Procedure 1E
64
Specifications
Table 8-3
Internal battery cabinet specifications
GXT4-144VBATKIT
GXT4-240VBATKIT
GXT4-288VBATKIT
GXT4-5000RT208
GXT4-6000RT208
GXT4-6000RTL630
GXT4-8000RT208
GXT4-10000RT208
8.1 x 19.3 x 2.8
(206 x 490 x 70)
7.2 x 15.4 x 4.4
(184 x 390 x 113)
8.1 x 19.7 x 5.3
(207 x 500 x 135)
10.3 x 23.7 x 12.2
(262 x 602 x 310)
10.3 x 18.4 x 7
(262 x 467 x 178)
9.5 x 23.9 x 12.2
(242 x 607 x 310)
Unit
75.8 (34.4)
45.4 (20.6)
71.1 (32.3)
Shipping
81.1 (36.8)
50.7 (23)
76.4 (34.7)
Model Number
Used with UPS Model
Dimensions, Rack Mount, W x D x H, in (mm)
Unit
Shipping
Weight lb (kg)
Type
Valve-regulated, non-spillable, flame retardant, lead acid
Quantity x V x Rating
Battery Mfr / Part #
2 x 6 x 12V x 9.0 AH
2 x 10 x 12V x 5.0AH
2 x 12 x 12V x 9.0 AH
CSB UPS12460F2
CSB/HR1221W
CSB UPS12460F2
Backup Time
See Table 8-8
Recharge Time
5 hours to 90% capacity after full discharge into 100% load
Environmental
32 to 104 (0 to 40)
Operating Temp, °F (°C)
Storage Temp, °F (°C)
5 to 122 (-15 to 50)
0% to 95%, non-condensing
Relative Humidity
Operating Elevation
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating
Agency
Safety
UL 1778, c-UL Listed
FCC Class A
RFI/EMI
Transportation
ISTA Procedure 1A
65
Liebert® GXT4™ User Manual
Specifications
Table 8-4
Model Number
External battery cabinet specifications
GXT4-144VBATT
GXT4-240VBATT
GXT4-288VBATT
GXT4-5000 &
GXT4-6000RT208
GXT4-6000RTL630
GXT4-8000 &
GXT4-10000RT208
Unit (with bezel)
16.9 x 26.1 x 3.3
(430 x 662 x 85)
16.9 x 22.6 x 6.8
(430 x 574 x 173)
16.9 x 26.5 x 6.8
(430 x 672 x 173)
Shipping
25.8 x 34.3 x 12.3
(655 x 872 x 312)
20.9 x 29.3 x 18.7
(530 x 745 x 475
24.5 x 33.1 x 18.7
(622 x 842 x 475)
99.9 (45.3)
143.3 (65)
167.6 (76.2)
121 (55)
176.4 (80)
198 (90)
Used w/UPS Model
Dimensions, W x D x H, in. (mm)
Weight, lb (kg)
Unit
Shipping
Battery Parameters
Type
Qty x V
Valve-regulated, non-spillable, lead acid
2 x 6 x 12V x 9.0 AH
Battery Mfr., Part #
2 x 10 x 12V x 9.0AH
2 x 12 x 12V x 9.0 AH
CSB UPS12460F2; CSBHR1234WF2
Backup Time
See Table 8-8
Environmental
Operating Temp, °F (°C)
32 to 104 (0 to 40)
Storage Temp, °F (°C)
5 to 122 (-15 to 50)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating
Agency
Safety
UL 1778, c-UL Listed
RFI/EMI
FCC Class A
Transportation
Table 8-5
ISTA Procedure 1A
Power distribution specifications: GXT4-5000RT208, GXT4-6000RT208 and GXT4-6000RTL630 *
Power Distribution Box Model #
PD Model #
PD2-HDWR-MBS
PD2-001
PD2-002
PD2-003
PD2-004
PD2-005
PD2-006
PD2-007
PD2-L630 *
Dimensions, W x D x H, in (mm)
Unit
4.7x13.2x4.1
(119x335x105)
10.2x18.4x8.7
(260x467
x222)
5.2x15.5x3.5 (132x393x88)
Shipping
9.5x20.7x9.1 (242x527x230)
Weight, lb (kg)
Unit
Shipping
6 (2.7)
8.8 (4)
8.6 (3.9)
9.5 (4.3)
8.8 (4)
8.2 (3.7)
11 (5)
10.8 (4.9) 10.8 (4.9) 12.1 (5.5) 12.8 (5.8) 11.7 (5.3) 11.7 (5.3)
8.6 (3.9)
9.9 (4.5)
10.6 (4.8)
9.5 (4.3)
11 (5)
Electrical Specifications
Amp Rating
Input Power Hard-Wired Terminal
Connections Block 3W + G (L-L-N-G)
30A 2-pole input breaker for UPS input power
(1) L14-30P on a 10.5 ft. (3.2m) cord
(4) 5-20R
(2) L5-20R
(2) 5-20R (4) 5-20R (4) L5-20R (4) L5-20R
(4) L6-20R
(1) L14-30R
(2) L6-20R
(2) L6-20R (2) L6-30R (2) L5-30R (2) L6-30R
(1) L6-30R
PD2-L630 is only compatible with the GXT4-6000RTL630 UPS model
Output
Power Hard-Wired Terminal
Connection Block 3W + G (L-L-N-G)
*
Liebert® GXT4™ User Manual
66
(1) L6-30P
(2) L6-30R
(2) L6-20R
Specifications
Table 8-6
Power distribution box specifications for GXT4-8000RT208 and GXT4-10000RT208
Power Distribution Box Model #
POD Model #
PD2-101
PD2-102
PD2-103
PD2-104
PD2-105
PD2-106
Dimensions, W x D x H, in. (mm)
Unit
7.4 x 5.7 (188 x 145)
Shipping
11.9 x 20.6 x 8.7 (302 x 522 x 220)
Weight, lb (kg)
Unit
4.4 (2)
6.6 (3)
6.6 (3)
6.6 (3)
4.4 (2)
6.6 (3)
Shipping
6.6 (3)
8.8 (4)
8.8 (4)
8.8 (4)
6.6 (3)
8.8 (4)
(4) 5-15/20R
(2) L5-30R
(2) L5-20R
(4) L6-20R
(4) L5-20R
Electrical Specifications
Amp Rating
2-pole 60A Input Breaker
Input Power
Connection
Custom Connector 3W + G(L-L-N-G) to UPS
Output Power
Connections
Table 8-7
(2) L6-30R
(8) 5-15/20R
(4) L6-20R
(4) 5-15/20R
(4) 5-15/20R
(4) L6-30R
(4) 5-15/20R
(2) L6-30R
(2) L6-20R
Power distribution box specifications for GXT4-8000RT208 and GXT4-10000RT208
Power Distribution Box Model #
POD Model #
PD2-107
PD2-108
PD2-109
PD2-200
PD2-201
PD2-202
PD2-204
Dimensions, W x D x H, in. (mm)
Unit
7.4 x 5.7 (188 x 145)
Shipping
11.9 x 20.6 x 8.7 (302 x 522 x 220)
Weight, lb (kg)
Unit
6.6 (3)
4.4 (2)
6.6 (3)
Shipping
8.8 (4)
6.6 (3)
15 (6.8)
Electrical Specifications
Amp Rating
2-pole 60A Input Breaker
Input Power
Connection
Custom Connector 3W + G(L-L-N-G) to UPS
Output Power
Connections
(4) L5-20R
(4) 5-15/20R
(2) L620R
(2) L630R
(2) L14-30R
(4) IEC320-C19 (2) IEC320-C19
(2) IEC309-32A
(12) IEC320-C13
(4) IEC320-C13 (8) IEC320-C13
(4) IEC320-C13
67
Liebert® GXT4™ User Manual
Specifications
Table 8-8
Number of External
Battery Cabinets
Internal Battery
Internal Battery
+ 1 External
Battery Cabinet
Internal Battery
+ 2 External
Battery Cabinets
Internal Battery
+ 3 External
Battery Cabinets
Battery run time, minutes
208/120 VAC RT Models
208 VAC RT Model
Load Percent
of Capacity
5 kVA
6 kVA
8 kVA
10 kVA
6 kVA (L630)
10%
134
112
121
98
92
20%
65
52
63
48
39
30%
39
31
42
32
34
40%
27
21
29
22
26
50%
20
15
22
16
18
60%
16
12
18
13
16
70%
12
9
14
10
12
80%
10
8
11
7
10
90%
8
6
9
7
9
100%
7
5
8
5
8
10%
281
235
256
206
265
20%
144
119
142
113
124
30%
92
77
100
79
99
40%
67
53
72
55
67
50%
50
40
55
42
52
60%
40
32
44
34
44
70%
33
26
36
27
34
80%
27
21
29
21
27
90%
23
18
25
20
24
100%
20
15
22
16
21
10%
441
367
400
322
462
20%
222
186
217
175
223
30%
146
120
156
124
177
40%
108
88
114
90
126
50%
84
68
90
72
98
60%
68
53
77
57
85
70%
55
43
59
45
66
80%
46
38
49
37
52
90%
40
32
43
35
48
100%
36
27
39
29
43
10%
603
505
550
444
671
20%
304
252
298
236
323
30%
198
166
210
170
254
40%
147
122
156
126
182
50%
117
95
126
100
145
60%
95
78
106
82
126
70%
81
63
86
68
100
80%
68
53
72
53
83
90%
57
45
61
50
74
100%
50
40
55
42
65
Run times in this table are approximate. They are based on new, fully charged standard battery modules at a temperature of 77°F (25°C) with
100% resistive UPS loading. Run times listed above can vary by ±5% due to manufacturing variances of the individual batteries.
Liebert® GXT4™ User Manual
68
Specifications
Table 8-8
Number of External
Battery Cabinets
Internal Battery
+ 4 External
Battery Cabinets
Internal Battery
+ 5 External
Battery Cabinets
Internal Battery
+ 6 External
Battery Cabinets
Battery run time, minutes (continued)
208/120 VAC RT Models
208 VAC RT Model
Load Percent
of Capacity
5 kVA
6 kVA
8 kVA
10 kVA
6 kVA (L630)
10%
766
638
696
566
883
20%
389
322
381
302
429
30%
252
208
269
214
336
40%
188
156
198
161
237
50%
149
122
161
129
190
60%
122
100
136
107
166
70%
104
84
111
87
135
80%
88
72
92
72
111
90%
78
60
83
67
100
100%
68
53
75
56
90
10%
939
783
854
685
1108
20%
476
393
467
370
538
30%
307
255
329
262
420
40%
227
190
239
195
296
50%
181
149
195
156
235
60%
149
122
166
130
207
70%
127
104
136
109
168
80%
110
88
114
88
139
90%
95
78
102
84
126
100%
84
67
91
73
115
10%
1116
931
1015
814
1329
20%
564
468
553
440
643
30%
364
301
389
310
506
40%
268
223
285
229
356
50%
212
177
228
184
283
60%
177
145
194
153
247
70%
149
122
160
129
201
80%
130
106
136
106
167
90%
114
91
119
100
152
100%
101
82
110
86
139
Run times in this table are approximate. They are based on new, fully charged standard battery modules at a temperature of 77°F (25°C) with
100% resistive UPS loading. Run times listed above can vary by ±5% due to manufacturing variances of the individual batteries.
Using the configuration program or the LCD panel, the user may specify the number of external battery
cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 8-8 shows the estimated run times at different loads.
69
Liebert® GXT4™ User Manual
Specifications
8.1 Auto-Learning Battery Run Times
As batteries age, the estimated run times may become less accurate. The Liebert GXT4 is programmed to
“learn” from a full battery discharge and modify the estimated run time for the measured battery capacity.
This can improve accuracy and compensate for aging batteries or batteries that operate at different
ambient temperatures.
The UPS will update the anticipated run time calculation only under certain conditions.
• The UPS must have a steady load that is greater than 20%.
• The UPS must be at 100% charge at the start of a battery discharge.
• The battery discharge must continue uninterrupted until the batteries reach their end-of-discharge
voltage.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in Table 8-8
will be restored. This will override any value that is Auto-Learned.
8.2 Product Warranty Registration
Registration is not required to activate the product warranty on a Liebert UPS. Registration is required to
qualify for the Product Protection Promise. To register, visit the Emerson Network Power® Web site to fill
out the online form at:
www.emersonnetworkpower.com/en-US/Forms/Pages/LiebertProductWarrantyRegistration.aspx
• To contact warranty support by e-mail: [email protected]
8.3 Technical Support
Technical support contacts are listed on the back cover of this document. To contact Emerson Channel
Product Support:
Phone
• NORTH AMERICA: 1-800-222-5877
• OUTSIDE NORTH AMERICA: 00-800-1155-4499
E-mail
• TECHNICAL SUPPORT: [email protected]
Liebert® GXT4™ User Manual
70
Technical Support / Service
Web Site
www.liebert.com
Monitoring
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Thermal Management Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims
all liability for damages resulting from use of this information or for any errors or omissions.
© 2016 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to changewithout notice.
® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-23194_REV2_6-16
590-1365-501A
Emerson Network Power
www.emersonnetworkpower.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement