PIM-530 Series Protectowire Linear Heat Detector Interface Module

PIM-530 Series Protectowire Linear Heat Detector Interface Module
PIM-530 Series Protectowire Linear Heat Detector
Interface Module
F eatures
• Provides a single zone interface for Protectowire Digital
Linear Heat Detectors
• Capable of Class A (Style D) or Class B (Style B)
monitoring of up to 6560 Feet (2000 Meters) of
Protectowire Linear Heat Detector
• Integrated Protectowire Alarm Point Location Meter with
“on-screen” field calibration
• 64 Event History Log (FIFO)
• 4x20 LED backlit LCD display
• Individual Power, Alarm and Fault indicators
• Plug-in terminals for easier field wiring connections
• 4-20mA outputs for Status and Alarm Point Location
• Optional intrinsically safe detection circuit available for
use in hazardous locations
General
The PIM-530 is a detection control module that acts as an interface between a main fire alarm control panel detection circuit or
addressable node and Protectowire Digital Linear Heat Detector.
The module provides one (1) supervised detection circuit that
may be field wired for either Class A (Style D) or Class B (Style B)
service. The alarm initiating circuit is capable of operating up to
6560 feet (2000 meters) of Standard PHSC or PLR Digital Type
Protectowire Linear Heat Detectors. The PIM-530 initiating circuit is also compatible with other types of non-resistive normally
open contact alarm initiating devices.
Description
The PIM-530 operates using conventional initiating device circuit
technology and contains an integrated on-board Protectowire
Alarm Point Location Meter. The module also includes a time and
date clock, 64 event history log, Form C contacts for host panel
interface and dual 4-20mA status outputs.
APPROVED
The module is designed for easy installation and can be optionally
provided in a NEMA-4X* rated enclosure for mounting outside of
the host fire alarm control panel or remotely near the hazard to be
protected.
In order to ensure proper operation, each PIM-530 module requires regulated resettable 24 VDC external power which is normally provided by the host fire alarm panel. Each module
contains a green “Power-On” LED indicator, one (1) red “Alarm”
LED indicator, and one (1) yellow “Trouble” LED indicator. One
(1) set of Form C alarm contacts and one (1) set of Form C trouble contacts to connect the unit to the host fire alarm panel. The
module also provides two 4-20mA outputs one which allows
monitoring of the module status and the other for monitoring
alarm point location information.
The standard PIM-530 module contains a built in Protectowire
Alarm Point Location Meter. This meter will automatically display
the distance from the beginning of the detector run to the heat ac-
An ISO 9001:2008 Registered Company
tuated (shorted) portion of the detector. The Alarm Point Location
Meter can be programmed to display distance in either standard
units (Feet) or metric units (Meters). The meter display provides a
simple “on screen” calibration procedure allowing the measurement
to be field calibrated to the installed detector length and ambient
temperature for optimal accuracy.
Specifications
Electrical
• Power input - Regulated 12 to 24 VDC (+10% / -15%) @
1 Watt
• Power Limited, onboard surge and EMI protection devices
Inputs
• One initiating device circuit capable of monitoring up to
6,560 feet (2,000 m) of PHSC or PLR Digital Type
Protectowire Linear Heat Detector.
Option I
• Intrinsically Safe Initiating device circuit, up to 6,560 feet
(2,000 m) or less as permitted by the hazardous location
calculation and application.
Environmental
• Ambient temperature Range:
Standard version -20° to 120°F (-4° to 49°C)
LT version -40° to 120°F (-40° to 49°C)
• Humidity: Max. 95% non-condensing
Indicators
• 4x20 Character LED backlit LCD display
• One green “Power” indicator
• One red “Alarm” indicator
• One yellow “Fault” indicator
Relay Outputs (Rated 1 amp @ 24VDC Resistive)
• One (1) set of Form C (SPDT) Fault Contacts
• One (1) set of Form C (SPDT) Alarm Contacts
4-20mA Outputs
• One(1) 4-20mA Output for module status
• One (1) 4-20mA Output for Alarm Point Location Readings
Optional Enclosure Specifications
• 10.5" H x 8.5" W x 4.5" D (27cm x 21.5cm x 11.4cm)
• Add 1.6" (4cm) to overall height for external mounting feet
• Clear full view door
• NEMA 4X Rated (Rating UL listed only)*
(Closest IEC equivalent - IP66)
Option I increases enclosure size. Consult Factory.
Option I - Intrinsically Safe Detection Circuit
• Option I provides an intrinsically safe Class B detection circuit for
use in those areas classified as hazardous. This feature utilizes one
shunt diode barrier per zone and is FM Approved for Class I, II
and III, Division 1, Groups A, B, C, D, E, F and G; Class I,
Zone 0, AEx ia IIC T6 Ga -29°C ≤ Ta ≤+49°C.
4-20mA Output Information
Description - The PIM-530 provides two 4-20mA outputs that allow
for monitoring of the module status and active alarm point location
reading. These outputs are intended for annunciation purposes only.
Module monitoring is intended to be accomplished using the onboard dry contacts connected to a listed or approved fire detection
control panel initiating device circuit.
For Class “A” wiring configurations the status output will also indicate
which detector input is currently being measured by the alarm point
location meter. The measurement is alternated between inputs approximately every 3 seconds with the status output indicating which input
is currently being read.
Consult Manual for detailed output levels for each status loop.
Note: All specifications subject to change without notice.
Ordering Information
Model No.
Description
PIM-530
Interface Module for Protectowire Types PHSC/PLR with LCD display and navigation buttons.
PIM-530E
Interface Module for Protectowire Types PHSC/PLR with LCD display and navigation buttons mounted in a
NEMA-4X (IP66) Enclosure.
PIM-530E-I
Interface Module with ISB for Protectowire Types PHSC/PLR with LCD display and navigation buttons mounted in a
NEMA-4X (IP66) Enclosure.
PIM-530LT
Interface Module for Protectowire Types PHSC/PLR without LCD display and navigation buttons for use in low temperature environments. This model requires the use of a separately ordered hand-held programmer. Consult Factory for details.
PIM-530LTE
Interface Module for Protectowire Types PHSC/PLR without LCD display and navigation buttons, mounted in a NEMA4X (IP66) Enclosure. For use in low temperature environments. This model requires the use of a separately ordered handheld programmer. Consult Factory for details.
PIM-530LTE-I
Interface Module with ISB for Protectowire Types PHSC/PLR without LCD display and navigation buttons, mounted in a
NEMA- 4X (IP66) Enclosure. For use in low temperature environments. This model requires the use of a separately ordered
hand-held programmer. Consult Factory for details.
CTMP-1
Hand-held programmer for PIM-530LT Models. Required for commissioning system, setting alarm temperature and
accessing history log.
The Protectowire Company, Inc.
© 2016 The Protectowire Co., Inc.
n
60 Washington Street, Pembroke, MA 02359 U.S.A. n p:781-826-3878
web: www.protectowire.com n email: [email protected]
SPECIAL HAZARD FIRE DETECTION SYSTEMS
n
f:781-826-2045
DS 9260-1016 (1C)